This document appears to be a Request for Proposal (RFP) for the repair of exterior granite at the Baltimore VA Medical Center. The solicitation number is 36C24524R0037 for Project #512-23-901. The agency issuing this RFP is the Department of Veterans Affairs Veterans Health Administration, Veterans Integrated Service Network 5. The required work includes the repair of exterior granite on the medical center building. No specific award date is provided, but the response due date is stated. The RFP does not contain a detailed Performance Work Statement or Statement of Objectives, but rather appears to be a solicitation for the required construction services. Pricing terms, set asides, and other pertinent details are not included in the provided information.
View the file
Other files
Show all 20
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Department of Veterans Affairs Baltimore Hospital
Asbestos Containing Material Data Table
Campus Site Area Designation Building Number Floor Room Number Category (AHERA
Class) Material Type Location Quantity Unit of Measure Condition Comments Asbestos Content Access Hazard
Ranking Response
Action Drawing Number Photo Number
Baltimore 01 Hospital 8th Room 8A - 101 Emergency Generator Room Miscellaneous Drywall All walls 2,800 SF Good No asbestos detected High N/a H-8-1
Baltimore 01 Hospital 8th Room 8A - 101 Emergency Generator Room Miscellaneous Joint Compound All walls 2,800 SF Good No asbestos detected High N/a H-8-1
Baltimore 01 Hospital 8th Room 8A - 101 Emergency Generator Room Surfacing Plaster Bulkhead Ceiling (center) 130 SF Good No asbestos detected Low N/a H-8-1
Baltimore 01 Hospital 8th Room 8A - 101 Emergency Generator Room Miscellaneous White pipe seam sealant At generator 210 LF Good 1' diameter No asbestos detected Low N/a H-8-1
Baltimore 01 Hospital 8th Room 8A - 101 Emergency Generator Room Miscellaneous Generator gray base caulk Platform of each generator 300 SF Good No asbestos detected Low N/a H-8-1
Baltimore 01 Hospital 8th Room 8A - 101 Emergency Generator Room Surfacing Spray-on fireproofing South wall at roof top doors 20 SF Good On beams near door No asbestos detected Low N/a H-8-1
Baltimore 01 Hospital 8th Room 8A - 101 Emergency Generator Room Miscellaneous Fire door North/South walls 5 @(4'x7') Doors Good Assumed ACM Low 1 O&M H-8-1
Baltimore 02 Hospital 8th Room 8A - 102 Switch Gear Room Miscellaneous Drywall North, south and east walls 1,050 SF Good No asbestos detected High N/a H-8-1 Baltimore 02 Hospital 8th Room 8A - 102 Switch Gear Room Miscellaneous Joint Compound North, south and east walls 1,050 SF Good No asbestos detected High N/a H-8-1 Baltimore 02 Hospital 8th Room 8A - 102 Switch Gear Room Surfacing Spray-on fireproofing All ceiling & south wall 680 SF Good 32'x21' diameter No asbestos detected Low N/a H-8-1
Baltimore 02 Hospital 8th Room 8A - 102 Switch Gear Room Miscellaneous Fire door South wall 2 @(4'x7') Doors Good Generator control panels throughout
Assumed ACM Low 1 O&M H-8-1
Baltimore 03 Hospital 8th SD-100 Mechanical Room Miscellaneous Drywall North, south and west walls and ceiling 6,900 SF Good
DWJC on columns and duct throughout No asbestos detected High N/a H-8-1
Baltimore 03 Hospital 8th SD-100 Mechanical Room Miscellaneous Joint Compound North, south and west walls and ceiling 6,900 SF Good
DWJC on columns and duct throughout No asbestos detected High N/a H-8-1
Baltimore 03 Hospital 8th SD-100 Mechanical Room Surfacing Spray-on fireproofing Ceiling, I-beams & south wall 5,200 SF Good No asbestos detected Low N/a H-8-1 Baltimore 03 Hospital 8th SD-100 Mechanical Room Miscellaneous Fire stop North and south walls 25 SF Good No asbestos detected Low N/a H-8-1
Baltimore 03 Hospital 8th SD-100 Mechanical Room Miscellaneous Gray duct seam sealant Southeast side of mechanical room 50 LF Good 6x6 No asbestos detected Low N/a H-8-1
Baltimore 03 Hospital 8th SD-100 Mechanical Room Miscellaneous Dark Gray duct seam sealant Duct work at Fan 131 15 LF Good 2x2 No asbestos detected Low N/a H-8-1 Baltimore 03 Hospital 8th SD-100 Mechanical Room Miscellaneous Brown duct seam sealant On blower duct 32 LF Good 2x2 No asbestos detected Low N/a H-8-1
Baltimore 03 Hospital 8th SD-100 Mechanical Room Miscellaneous Gray duct seam caulk Southeast side of mechanical room 17 LF Good 2x2 No asbestos detected Low N/a H-8-1
Baltimore 03 Hospital 8th SD-100 Mechanical Room Miscellaneous Gray duct seam clay North side of mechanical room 216 SF Good 6x3; 2 ducts for quantification No asbestos detected Low N/a H-8-1
Baltimore 03 Hospital 8th SD-100 Mechanical Room TSI White duct powder insulation North side of mechanical room 216 SF Good 6x3; 2 ducts for quantification No asbestos detected High N/a H-8-1
Baltimore 03 Hospital 8th SD-100 Mechanical Room Miscellaneous LUC Concrete Center of mechanical room 900 SF Good 4x3 No asbestos detected Low N/a H-8-1 Baltimore 03 Hospital 8th SD-100 Mechanical Room Miscellaneous Fire door South wall 2 Doors Good Assumed ACM Low 1 O&M H-8-1 Baltimore 04 Hospital 8th SD-101 Power Plant Substation Miscellaneous Drywall North, south and west walls 1,760 SF Good No asbestos detected High N/a H-8-1 Baltimore 04 Hospital 8th SD-101 Power Plant Substation Miscellaneous Joint Compound North, south and west walls 1,760 SF Good No asbestos detected High N/a H-8-1 Baltimore 04 Hospital 8th SD-101 Power Plant Substation Surfacing Spray-on fireproofing Ceiling, I-beams & north wall 4,200 SF Good No asbestos detected Low N/a H-8-1 Baltimore 04 Hospital 8th SD-101 Power Plant Substation Miscellaneous Red fire stop South & west wall 5 SF Good No asbestos detected Low N/a H-8-1 Baltimore 04 Hospital 8th SD-101 Power Plant Substation Miscellaneous White fire stop North wall 6 SF Good No asbestos detected Low N/a H-8-1
Baltimore 04 Hospital 8th SD-101 Power Plant Substation Miscellaneous Fire door North and south walls 6 @(4'x7') Doors Good Generator control panels throughout
Assumed ACM Low 1 O&M H-8-1
Baltimore 05 Hospital 8th Room 8A - 100 Elevator Lobby Miscellaneous Drywall North, south and east walls 800 SF Good No asbestos detected High N/a H-8-1 Baltimore 05 Hospital 8th Room 8A - 100 Elevator Lobby Miscellaneous Joint Compound North, south and east walls 800 SF Good No asbestos detected High N/a H-8-1 Baltimore 05 Hospital 8th Room 8A - 100 Elevator Lobby Surfacing Spray-on fireproofing Ceiling throughout 450 SF Good No asbestos detected Low N/a H-8-1 Baltimore 05 Hospital 8th Room 8A - 100 Elevator Lobby Miscellaneous Fire stop All walls 100 LF Good No asbestos detected Low N/a H-8-1 Baltimore 05 Hospital 8th Room 8A - 100 Elevator Lobby Miscellaneous Fire door South wall 1 @(4'x7') Doors Good Assumed ACM Low 1 O&M H-8-1
Baltimore 06 Hospital 8th Room 8D - 102 Elevator Machine Room Miscellaneous Drywall South, west and east walls 810 SF Good No asbestos detected High N/a H-8-1
Baltimore 06 Hospital 8th Room 8D - 102 Elevator Machine Room Miscellaneous Joint Compound South, west and east walls 810 SF Good No asbestos detected High N/a H-8-1
Baltimore 06 Hospital 8th Room 8D - 102 Elevator Machine Room Surfacing Spray-on fireproofing North wall 30 SF Good No asbestos detected Low N/a H-8-1
Baltimore 06 Hospital 8th Room 8D - 102 Elevator Machine Room Miscellaneous Fire door East wall 1 @(3'x7') Doors Good Assumed ACM Low 1 O&M H-8-1
Baltimore 07 Hospital 8th Radiation Storage _ NO ACCESS _ _ _ _ _ _ _ _ _ H-8-1
Baltimore 08 Hospital 9th Room 9A - 100 Elevator Machine Room Miscellaneous Drywall Corner columns (all corners) 250 SF Good No asbestos detected High N/a
Baltimore 08 Hospital 9th Room 9A - 100 Elevator Machine Room Miscellaneous Joint Compound Corner columns (all corners) 250 SF Good No asbestos detected High N/a
ACM Data Table - 1
Asbestos Containing Material Data Table
Campus Site Area Designation Building Number Floor Room Number Category (AHERA
Class) Material Type Location Quantity Unit of Measure Condition Comments Asbestos Content Access Hazard
Ranking Response
Action Drawing Number Photo Number
Baltimore 08 Hospital 9th Room 9A - 100 Elevator Machine Room Miscellaneous Brown duct seam sealant All throughout area 30 LF Good 2x2; on metal No asbestos detected Low N/a
Baltimore 08 Hospital 9th Room 9A - 100 Elevator Machine Room Miscellaneous White pipe seam sealant All throughout area 50 LF Good No asbestos detected Low N/a
Baltimore 08 Hospital 9th Room 9A - 100 Elevator Machine Room Miscellaneous Fire door South wall 1 @(3'x7') Doors Good Assumed ACM Low 1 O&M
Baltimore 09 Hospital 7th Room 7D - 100 Miscellaneous Drywall All walls 13,000 SF Good No asbestos detected High N/a H-7-1 Baltimore 09 Hospital 7th Room 7D - 100 Miscellaneous Joint Compound All walls 13,000 SF Good No asbestos detected High N/a H-7-1 Baltimore 09 Hospital 7th Room 7D - 100 Surfacing Spray-on fireproofing Throughout ceiling & all walls 16,000 SF Good No asbestos detected Low N/a H-7-1 Baltimore 09 Hospital 7th Room 7D - 100 Miscellaneous White pipe seam sealant Throughout area 7,500 SF Good No asbestos detected Low N/a H-7-1
Baltimore 09 Hospital 7th Room 7D - 100 Miscellaneous Fiberglass tank with white pipe seam sealant Southeast area, under mezzanine 1 Tank Good 5' diameter; 8' long No asbestos detected High N/a H-7-1
Baltimore 09 Hospital 7th Room 7D - 100 Miscellaneous Brown duct seam sealant Throughout area 350 LF Good 2x2; on metal No asbestos detected Low N/a H-7-1 Baltimore 09 Hospital 7th Room 7D - 100 Miscellaneous Gray duct seam sealant North side duct 100 LF Good 3X3; on metal No asbestos detected Low N/a H-7-1 Baltimore 10 Hospital 7th Room 7D - 100A Mezzanine _ No suspect ACM _ _ _ _ _ NO SUSPECT ACM _ _ N/a H-7-1 Baltimore 11 Hospital 7th Room 7D - 100E Miscellaneous Drywall All wall and throughout 4,400 SF Good No asbestos detected High N/a H-7-1 Baltimore 11 Hospital 7th Room 7D - 100E Miscellaneous Joint Compound All wall and throughout 4,400 SF Good No asbestos detected High N/a H-7-1
Baltimore 11 Hospital 7th Room 7D - 100E Surfacing Spray-on fireproofing Ceiling deck throughout 1,900 SF Good I-beams and deck No asbestos detected Low N/a H-7-1
Baltimore 11 Hospital 7th Room 7D - 100E Miscellaneous White pipe seam sealant Ceiling, north and south walls 150 LF Good Blow back No asbestos detected Low N/a H-7-1 Baltimore 11 Hospital 7th Room 7D - 100E Miscellaneous Fire door West & east walls 2 @4'x7' Doors Good Assumed ACM Low 1 O&M H-7-1 Baltimore 11 Hospital 7th Room 7D - 100E Miscellaneous Brown duct seam sealant West side of room 110 LF Good 2x1; on metal No asbestos detected Low N/a H-7-1
Baltimore 11 Hospital 7th Room 7D - 100E Miscellaneous Elevator cab/door insulation (assumed) South wall 1 Elevator Good No asbestos detected Low N/a H-7-1
Baltimore 11 Hospital 7th Room 7D - 100E Miscellaneous Fire door East/west walls 2 @(4'x7') Doors Good Assumed ACM Low 1 O&M H-7-1 Baltimore 12 Hospital 7th Room 7D - 100B Control Office Miscellaneous Drywall All walls 240 SF Good No asbestos detected High N/a H-7-1 Baltimore 12 Hospital 7th Room 7D - 100B Control Office Miscellaneous Joint Compound All walls 240 SF Good No asbestos detected High N/a H-7-1 Baltimore 12 Hospital 7th Room 7D - 100B Control Office Miscellaneous 2'x4' Fissured pinhole ceiling tile Drop ceiling throughout 240 SF Good No asbestos detected Medium N/a H-7-1 Baltimore 12 Hospital 7th Room 7D - 100B Control Office Miscellaneous Fire door South wall 1 @3'x7' Doors Good Assumed ACM Low 1 O&M H-7-1
Baltimore 12 Hospital 7th Room 7D - 100B Control Office Miscellaneous 12"x12" Tan with white streaks floor tile Throughout floor under carpet 240 SF Good No carpet mastic No asbestos detected Low N/a H-7-1
Baltimore 12 Hospital 7th Room 7D - 100B Control Office Miscellaneous Brown floor tile mastic Throughout floor under carpet 240 SF Good No asbestos detected Low N/a H-7-1 Baltimore 12 Hospital 7th Room 7D - 100B Control Office Miscellaneous Brown baseboard mastic All walls 64 LF Good No asbestos detected Low N/a H-7-1
Baltimore 13 Hospital 7th 7D-100D Bathroom Miscellaneous Drywall All walls and ceiling on northeast side 190 SF Good No asbestos detected High N/a H-7-1
Baltimore 13 Hospital 7th 7D-100D Bathroom Miscellaneous Drywall All walls and ceiling on northeast side 190 SF Good No asbestos detected High N/a H-7-1
Baltimore 13 Hospital 7th 7D-100D Bathroom Miscellaneous 2'x2' Drywall ceiling Throughout ceiling 60 SF Good No asbestos detected Medium N/a H-7-1
Baltimore 13 Hospital 7th 7D-100D Bathroom Miscellaneous Ceramic tile floor and wall grout Floor throughout & lower half of walls 280 SF Good No asbestos detected High N/a H-7-1
Baltimore 14 Hospital 7th 7D-102, 103, 104, 105, 106 Miscellaneous Drywall All walls in open space & offices 3,400 SF Good No asbestos detected High N/a H-7-1 Baltimore 14 Hospital 7th 7D-102, 103, 104, 105, 106 Miscellaneous 2'x4' Fissured pinhole ceiling tile Ceiling throughout 1,428 SF Good No asbestos detected Medium N/a H-7-1 Baltimore 14 Hospital 7th 7D-102, 103, 104, 105, 106 Miscellaneous Tan baseboard mastic All walls 370 LF Good No asbestos detected Low N/a H-7-1 Baltimore 14 Hospital 7D-102, 103, 104, 105, 106 Miscellaneous Tan Wood Patterned Sheeting Throughout Floors 1,428 SF Good No asbestos detected low N/a H-7-1 Baltimore 14 Hospital 7th 7D-102, 103, 104, 105, 106 Miscellaneous Fire door North and south walls 2 @4'x7' Doors Good Assumed ACM Low 1 O&M H-7-1
Baltimore 14 Hospital 7th 7D-102, 103, 104, 105, 106 Miscellaneous Yellow carpet mastic Floor throughout 1428 SF Good No tile under on concrete No asbestos detected Low N/a H-7-1
Baltimore 15 Hospital 7th 7D-100 West Mech Rm. _ NO ACCESS _ _ _ _ _ _ _ _ _ H-7-1 Baltimore 16 Hospital 7th 7D-100G Miscellaneous Drywall All walls and ceiling 900 SF Good No asbestos detected High N/a H-7-1 Baltimore 16 Hospital 7th 7D-100G Miscellaneous Joint Compound All walls and ceiling 900 SF Good No asbestos detected High N/a H-7-1 Baltimore 16 Hospital 7th 7D-100G Miscellaneous Fire door North wall 1 @4'x7' Doors Good Assumed ACM Low 1 O&M H-7-1 Baltimore 17 Hospital 7th 7D-107 Storage Miscellaneous Drywall All walls and ceiling 1140 SF Good No asbestos detected High N/a H-7-1 Baltimore 17 Hospital 7th 7D-107 Storage Miscellaneous Joint Compound All walls and ceiling 1140 SF Good No asbestos detected High N/a H-7-1 Baltimore 17 Hospital 7th 7D-107 Storage Miscellaneous Fire door North/South walls 2 @(4'x7') Doors Good Assumed ACM Low 1 O&M H-7-1 Baltimore 18 Hospital 7th 7A-100A Miscellaneous Drywall All walls 450 SF Good No asbestos detected High N/a H-7-1 Baltimore 18 Hospital 7th 7A-100A Miscellaneous Joint Compound All walls 450 SF Good No asbestos detected High N/a H-7-1 Baltimore 19 Hospital 7th C-72 Eastern Elevator Hallway Miscellaneous Drywall All walls 4500 SF Good No asbestos detected High N/a H-7-1 Baltimore 19 Hospital 7th C-72 Eastern Elevator Hallway Miscellaneous Joint Compound All walls 4500 SF Good No asbestos detected High N/a H-7-1 Baltimore 19 Hospital 7th C-72 Eastern Elevator Hallway Miscellaneous White pipe seam sealant Throughout 550 LF Good No asbestos detected Low N/a H-7-1
Baltimore 19 Hospital 7th C-72 Eastern Elevator Hallway Surfacing Spray-on fireproofing East wall & ceiling 1,000 SF Good Beams and overflow on Ceiling deck
No asbestos detected Low N/a H-7-1
Baltimore 19 Hospital 7th C-72 Eastern Elevator Hallway Miscellaneous Brown duct seam sealant Throughout hallway at ceiling 35 LF Good On 1x2 metal duct No asbestos detected Low N/a H-7-1
Baltimore 19 Hospital 7th C-72 Eastern Elevator Hallway Miscellaneous White duct seam sealant on canvas wrap duct West & south side 30 LF Good On 3x4 duct No asbestos detected Low N/a H-7-1
Baltimore 19 Hospital 7th C-72 Eastern Elevator Hallway Miscellaneous Fire door North and south side 4 @4'x7' Doors Good Assumed ACM Low 1 O&M H-7-1 Baltimore 19 Hospital 7th C-72 Eastern Elevator Hallway Miscellaneous Red fire stop All walls 10 SF Good No asbestos detected Low N/a H-7-1
ACM Data Table - 2
Asbestos Containing Material Data Table
Campus Site Area Designation Building Number Floor Room Number Category (AHERA
Class) Material Type Location Quantity Unit of Measure Condition Comments Asbestos Content Access Hazard
Ranking Response
Action Drawing Number Photo Number
Baltimore 19 Hospital 7th C-72 Eastern Elevator Hallway Miscellaneous White fire stop All walls 10 SF Good No asbestos detected Low N/a H-7-1 Baltimore 20 Hospital 7th 7A-101 Mechanical Equipment Room Miscellaneous Drywall All walls 7000 SF Good No asbestos detected High N/a H-7-1 Baltimore 20 Hospital 7th 7A-101 Mechanical Equipment Room Miscellaneous Joint Compound All walls 7000 SF Good No asbestos detected High N/a H-7-1 Baltimore 20 Hospital 7th 7A-101 Mechanical Equipment Room Surfacing Spray-on fireproofing Ceiling and walls throughout 8500 SF Good No asbestos detected Low N/a H-7-1 Baltimore 20 Hospital 7th 7A-101 Mechanical Equipment Room Miscellaneous White pipe seam sealant Throughout 4000 LF Good No asbestos detected Low N/a H-7-1 Baltimore 20 Hospital 7th 7A-101 Mechanical Equipment Room Miscellaneous Brown metal duct seam sealant Ceiling throughout 160 LF Good No asbestos detected Low N/a H-7-1
Baltimore 20 Hospital 7th 7A-101 Mechanical Equipment Room Miscellaneous White duct seam sealant on canvas wrap duct Throughout 300 LF Good 4x4 duct No asbestos detected Low N/a H-7-1
Baltimore 20 Hospital 7th 7A-101 Mechanical Equipment Room Miscellaneous Red fire stop All walls 30 SF Good No asbestos detected Low N/a H-7-1 Baltimore 20 Hospital 7th 7A-101 Mechanical Equipment Room Miscellaneous White fire stop All walls 30 SF Good No asbestos detected Low N/a H-7-1
Baltimore 20 Hospital 7th 7A-101 Mechanical Equipment Room Miscellaneous Tan duct pin mastic South side 40 LF Good On 2x6 metal duct No asbestos detected Low N/a H-7-1
Baltimore 20 Hospital 7th 7A-101 Mechanical Equipment Room Miscellaneous Fire door North wall 4 @(4'x7') Doors Good Assumed ACM Low 1 O&M H-7-1
Baltimore 21 Hospital 7th 7A-105 Elevator Mechanical Room Miscellaneous Drywall All walls and ceiling 710 SF Good No asbestos detected High N/a H-7-1 Baltimore 21 Hospital 7th 7A-105 Elevator Mechanical Room Miscellaneous Joint Compound All walls and ceiling 710 SF Good No asbestos detected High N/a H-7-1 Baltimore 21 Hospital 7th 7A-105 Elevator Mechanical Room Miscellaneous Fire door South wall 1 @4'x7' Doors Good Assumed ACM Low 1 O&M H-7-1 Baltimore 22 Hospital 7th C7-1 Corridor Miscellaneous Drywall All walls 2500 SF Good No asbestos detected High N/a H-7-1 Baltimore 22 Hospital 7th C7-1 Corridor Miscellaneous Joint Compound All walls 2500 SF Good No asbestos detected High N/a H-7-1 Baltimore 22 Hospital 7th C7-1 Corridor Miscellaneous Tan baseboard mastic All walls 120 LF Good No asbestos detected Low N/a H-7-1 Baltimore 22 Hospital 7th C7-1 Corridor Surfacing Spray-on fireproofing Ceiling deck and west wall 1500 SF Good No asbestos detected Low N/a H-7-1 Baltimore 22 Hospital 7th C7-1 Corridor Miscellaneous White pipe seam sealant Throughout 250 LF Good No asbestos detected Low N/a H-7-1 Baltimore 22 Hospital 7th C7-1 Corridor Miscellaneous Red fire stop North and south walls 30 SF Good No asbestos detected Low N/a H-7-1 Baltimore 22 Hospital 7th C7-1 Corridor Miscellaneous Fire door North and south walls 4 @(4'x7') Doors Good Assumed ACM Low 1 O&M H-7-1 Baltimore 23 Hospital 7th 7D-100H Miscellaneous Drywall All walls 600 SF Good No asbestos detected High N/a H-7-1 Baltimore 23 Hospital 7th 7D-100H Miscellaneous Joint Compound All walls 600 SF Good No asbestos detected High N/a H-7-1 Baltimore 24 Hospital 7th Storage behind elevator Miscellaneous Drywall All walls and ceiling 600 SF Good No asbestos detected High N/a H-7-1 Baltimore 24 Hospital 7th Storage behind elevator Miscellaneous Joint Compound All walls and ceiling 600 SF Good No asbestos detected High N/a H-7-1 Baltimore 24 Hospital 7th Storage behind elevator Miscellaneous Fire door East wall 1 @(4'x7') Doors Good Assumed ACM Low 1 O&M H-7-1 Baltimore 25 Hospital 7th 7A-102 Miscellaneous Drywall All walls & ceiling 300 SF Good No asbestos detected High N/a H-7-1 Baltimore 25 Hospital 7th 7A-102 Miscellaneous Joint Compound All walls & ceiling 300 SF Good No asbestos detected High N/a H-7-1 Baltimore 25 Hospital 7th 7A-102 Miscellaneous Brown duct seam sealant Throughout 30 LF Good No asbestos detected Low N/a H-7-1 Baltimore 25 Hospital 7th 7A-102 Miscellaneous Fire door East wall 1 @(3'x7') Doors Good Assumed ACM Low 1 O&M H-7-1 Baltimore 26 Hospital 7th 7A-103 Miscellaneous Drywall All walls 3300 SF Good No asbestos detected High N/a H-7-1 Baltimore 26 Hospital 7th 7A-103 Miscellaneous Joint Compound All walls 3300 SF Good No asbestos detected High N/a H-7-1 Baltimore 26 Hospital 7th 7A-103 Surfacing Spray-on fireproofing All walls & ceiling 1200 SF Good No asbestos detected Low N/a H-7-1 Baltimore 26 Hospital 7th 7A-103 Miscellaneous Red fire stop All walls 30 SF Good No asbestos detected Low N/a H-7-1 Baltimore 26 Hospital 7th 7A-103 Miscellaneous White fire stop All walls 30 SF Good No asbestos detected Low N/a H-7-1 Baltimore 26 Hospital 7th 7A-103 Miscellaneous White pipe seam sealant West wall 200 LF Good No asbestos detected Low N/a H-7-1
Baltimore 26 Hospital 7th 7A-103 Miscellaneous Gray duct seam sealant East wall of lower area 10 LF Good 2x2 duct lower room; on metal No asbestos detected Low N/a H-7-1
Baltimore 26 Hospital 7th 7A-103 Miscellaneous Brown duct seam sealant West wall on upper area 16 LF Good 1x1 duct No asbestos detected Low N/a H-7-1 Baltimore 26 Hospital 7th 7A-103 Miscellaneous Tan baseboard mastic Upper area, west/east/south wall 80 LF Good No asbestos detected Low N/a H-7-1 Baltimore 26 Hospital 7th 7A-103 Miscellaneous Fire door West wall 2 @4'x7' Doors Good Assumed ACM Low 1 O&M H-7-1
Baltimore 27 Hospital 7th C7-5 & C7-7 Corridors Miscellaneous Drywall Ceiling, south, west and east walls 2000 SF Good No asbestos detected High N/a H-7-1
Baltimore 27 Hospital 7th C7-5 & C7-7 Corridors Miscellaneous Joint Compound Ceiling, south, west and east walls 2000 SF Good No asbestos detected High N/a H-7-1
Baltimore 27 Hospital 7th C7-5 & C7-7 Corridors Miscellaneous White pipe seam sealant Throughout north wall 800 SF Good No asbestos detected Low N/a H-7-1 Baltimore 27 Hospital 7th C7-5 & C7-7 Corridors Miscellaneous Red fire stop All walls 35 SF Good No asbestos detected Low N/a H-7-1 Baltimore 27 Hospital 7th C7-5 & C7-7 Corridors Surfacing Spray-on fireproofing North and south walls 20 SF Good No asbestos detected Low N/a H-7-1 Baltimore 27 Hospital 7th C7-5 & C7-7 Corridors Miscellaneous White fire stop All walls 25 SF Good No asbestos detected Low N/a H-7-1 Baltimore 27 Hospital 7th C7-5 & C7-7 Corridors Miscellaneous Fire door East and south walls 2 @4'x7' Doors Good Assumed ACM Low 1 O&M H-7-1 Baltimore 28 Hospital 7th C7-6 Corridor Miscellaneous Drywall Ceiling and north wall 2450 SF Good No asbestos detected High N/a H-7-1 Baltimore 28 Hospital 7th C7-6 Corridor Miscellaneous Joint Compound Ceiling and north wall 2450 SF Good No asbestos detected High N/a H-7-1 Baltimore 28 Hospital 7th C7-6 Corridor Miscellaneous White pipe seam sealant Throughout south wall and ceiling 1250 SF Good No asbestos detected Low N/a H-7-1 Baltimore 28 Hospital 7th C7-6 Corridor Surfacing Spray-on fireproofing Along south wall on beams 350 SF Good No asbestos detected Low N/a H-7-1 Baltimore 28 Hospital 7th C7-6 Corridor Miscellaneous Red fire stop All walls 40 SF Good No asbestos detected Low N/a H-7-1 Baltimore 28 Hospital 7th C7-6 Corridor Miscellaneous White fire stop All walls 25 SF Good No asbestos detected Low N/a H-7-1 Baltimore 28 Hospital 7th C7-6 Corridor Miscellaneous Fire door East wall 1 @4'x7' Doors Good Assumed ACM Low 1 O&M H-7-1 Baltimore 29 Hospital 7th C7-4/5 Corridor Miscellaneous Drywall Ceiling and south walls 2000 SF Good No asbestos detected High N/a H-7-1 Baltimore 29 Hospital 7th C7-4/5 Corridor Miscellaneous Joint Compound Ceiling and south walls 2000 SF Good No asbestos detected High N/a H-7-1 Baltimore 29 Hospital 7th C7-4/5 Corridor Miscellaneous White pipe seam sealant Along north wall 600 LF Good No asbestos detected Low N/a H-7-1 Baltimore 29 Hospital 7th C7-4/5 Corridor Miscellaneous Red fire stop All walls 40 SF Good No asbestos detected Low N/a H-7-1 Baltimore 29 Hospital 7th C7-4/5 Corridor Surfacing Spray-on fireproofing North wall beams 210 SF Good No asbestos detected Low N/a H-7-1 Baltimore 29 Hospital 7th C7-4/5 Corridor Miscellaneous Fire door West and south wall 2 @4'x7' Doors Good Assumed ACM Low 1 O&M H-7-1 Baltimore 30 Hospital 7th C7-3 Corridor Miscellaneous Drywall Ceiling and all walls 2300 SF Good No asbestos detected High N/a H-7-1 Baltimore 30 Hospital 7th C7-3 Corridor Miscellaneous Joint Compound Ceiling and all walls 2300 SF Good No asbestos detected High N/a H-7-1
ACM Data Table - 3
Asbestos Containing Material Data Table
Campus Site Area Designation Building Number Floor Room Number Category (AHERA
Class) Material Type Location Quantity Unit of Measure Condition Comments Asbestos Content Access Hazard
Ranking Response
Action Drawing Number Photo Number
Baltimore 30 Hospital 7th C7-3 Corridor Surfacing Spray-on fireproofing South wall beams 300 SF Good No asbestos detected Low N/a H-7-1 Baltimore 30 Hospital 7th C7-3 Corridor Miscellaneous White pipe seam sealant South wall 750 SF Good No asbestos detected Low N/a H-7-1 Baltimore 30 Hospital 7th C7-3 Corridor Miscellaneous Red fire stop All walls 40 LF Good No asbestos detected Low N/a H-7-1 Baltimore 30 Hospital 7th C7-3 Corridor Miscellaneous White fire stop All walls 20 LF Good No asbestos detected Low N/a H-7-1 Baltimore 30 Hospital 7th C7-3 Corridor Miscellaneous Fire door West wall 1 @4'x7' Doors Good Assumed ACM Low 1 O&M H-7-1 Baltimore 31 Hospital 7th 7A-104 Service Bay Miscellaneous Drywall North, east and south walls 2,400 SF Good No asbestos detected High N/a H-7-1 Baltimore 30 Hospital 7th C7-3 Corridor Miscellaneous Joint Compound Ceiling and all walls 2300 SF Good No asbestos detected High N/a H-7-1 Baltimore 31 Hospital 7th 7A-104 Service Bay Surfacing Spray-on fireproofing Ceiling, west and east walls 4,400 SF Good No asbestos detected Low N/a H-7-1 Baltimore 31 Hospital 7th 7A-104 Service Bay Miscellaneous White pipe seam sealant Throughout 800 LF Good No asbestos detected Low N/a H-7-1
Baltimore 31 Hospital 7th 7A-104 Service Bay Miscellaneous Brown duct seam sealant East wall 60 LF Good On metal 3x2 duct No asbestos detected Low N/a H-7-1
Baltimore 31 Hospital 7th 7A-104 Service Bay Miscellaneous Gray duct seam sealant East wall 5 LF Good On metal 1x2 duct No asbestos detected Low N/a H-7-1
Baltimore 31 Hospital 7th 7A-104 Service Bay Miscellaneous Red duct seam sealant East wall 5 LF Good On metal 1x2 duct No asbestos detected Low N/a H-7-1
Baltimore 31 Hospital 7th 7A-104 Service Bay Miscellaneous Fire door South/west walls 2 @4'x7' Doors Good Assumed ACM Low 1 O&M H-7-1 Baltimore 32 Hospital 7th 7D-101 Service Bay Miscellaneous Drywall North, east and south walls 2,300 SF Good No asbestos detected High N/a H-7-1 Baltimore 32 Hospital 7th 7D-101 Service Bay Miscellaneous Joint Compound North, east and south walls 2,300 SF Good No asbestos detected High N/a H-7-1 Baltimore 32 Hospital 7th 7D-101 Service Bay Surfacing Spray-on fireproofing Ceiling and all walls 4,500 SF Good No asbestos detected Low N/a H-7-1 Baltimore 32 Hospital 7th 7D-101 Service Bay Miscellaneous White pipe seam sealant 1200 LF Good No asbestos detected Low N/a H-7-1
Baltimore 32 Hospital 7th 7D-101 Service Bay Miscellaneous Brown duct seam sealant Throughout 80 LF Good on metal 4x4 duct/1x2 No asbestos detected Low N/a H-7-1
Baltimore 32 Hospital 7th 7D-101 Service Bay Miscellaneous Gray duct seam sealant Throughout 90 LF Good On metal 1x1 duct No asbestos detected Low N/a H-7-1
Baltimore 32 Hospital 7th 7D-101 Service Bay Miscellaneous Fire door South wall 1 @4'x7' Doors Good Assumed ACM Low 1 O&M H-7-1 Baltimore 32 Hospital 7th 7D-101 Service Bay Miscellaneous Red fire stop All walls 25 LF Good No asbestos detected Low N/a H-7-1 Baltimore 32 Hospital 7th 7D-101 Service Bay Miscellaneous White fire stop All walls 15 LF Good No asbestos detected Low N/a H-7-1 Baltimore 33 Hospital 7th 7C-100 Service Bay Miscellaneous Drywall North, west and south walls 2500 SF Good No asbestos detected High N/a H-7-1 Baltimore 33 Hospital 7th 7C-100 Service Bay Miscellaneous Joint Compound North, west and south walls 2500 SF Good No asbestos detected High N/a H-7-1 Baltimore 33 Hospital 7th 7C-100 Service Bay Surfacing Spray-on fireproofing All walls and ceiling 3500 SF Good No asbestos detected Low N/a H-7-1 Baltimore 33 Hospital 7th 7C-100 Service Bay Miscellaneous White pipe seam sealant Throughout 1500 LF Good No asbestos detected Low N/a H-7-1
Baltimore 33 Hospital 7th 7C-100 Service Bay Miscellaneous Brown duct seam sealant On west side throughout 50 LF Good on metal 3x3 duct No asbestos detected Low N/a H-7-1
Baltimore 33 Hospital 7th 7C-100 Service Bay Miscellaneous Gray duct seam sealant On duct throughout 65 LF Good On 1' diameter metal duct No asbestos detected Low N/a H-7-1
Baltimore 33 Hospital 7th 7C-100 Service Bay Miscellaneous Gray duct seam caulk Duct in center 20 LF Good On 1' diameter metal duct No asbestos detected Low N/a H-7-1
Baltimore 33 Hospital 7th 7C-100 Service Bay Miscellaneous White cloth vibration dampener East side at blowers 3 @1'x1' Dampener Good No asbestos detected High N/a H-7-1 Baltimore 33 Hospital 7th 7C-100 Service Bay Miscellaneous Red fire stop All walls 30 SF Good No asbestos detected Low N/a H-7-1 Baltimore 33 Hospital 7th 7C-100 Service Bay Miscellaneous White fire stop All walls 20 SF Good No asbestos detected Low N/a H-7-1 Baltimore 33 Hospital 7th 7C-100 Service Bay Miscellaneous Fire door North/South walls 2 @(4'x7') Doors Good Assumed ACM Low 1 O&M H-7-1 Baltimore 34 Hospital 7th 7B-100 Service Bay Miscellaneous Drywall North, south and west walls 2100 SF Good No asbestos detected High N/a H-7-1 Baltimore 34 Hospital 7th 7B-100 Service Bay Miscellaneous Joint Compound North, south and west walls 2100 SF Good No asbestos detected High N/a H-7-1 Baltimore 34 Hospital 7th 7B-100 Service Bay Surfacing Spray-on fireproofing Ceiling and walls 3200 SF Good No asbestos detected Low N/a H-7-1 Baltimore 34 Hospital 7th 7B-100 Service Bay Miscellaneous White pipe seam sealant Throughout 1200 LF Good No asbestos detected Low N/a H-7-1
Baltimore 34 Hospital 7th 7B-100 Service Bay Miscellaneous Brown duct seam sealant West side 50 LF Good on 3x4 metal duct; 1' diameter No asbestos detected Low N/a H-7-1
Baltimore 34 Hospital 7th 7B-100 Service Bay Miscellaneous Gray duct seam sealant West side 30 LF Good On metal duct No asbestos detected Low N/a H-7-1 Baltimore 34 Hospital 7th 7B-100 Service Bay Miscellaneous Red fire stop All walls 25 SF Good No asbestos detected Low N/a H-7-1 Baltimore 34 Hospital 7th 7B-100 Service Bay Miscellaneous White fire stop All walls 15 SF Good No asbestos detected Low N/a H-7-1 Baltimore 34 Hospital 7th 7B-100 Service Bay Miscellaneous Fire door East/south walls 4 @(4'x7') Doors Good Assumed ACM Low 1 O&M H-7-1 Baltimore 35 Hospital 6th 6A-133 Service Bay Miscellaneous Drywall All walls 2,400 SF Good No asbestos detected High N/a H-6-3 Baltimore 35 Hospital 6th 6A-133 Service Bay Miscellaneous Joint Compound All walls 2,400 SF Good No asbestos detected High N/a H-6-3
Baltimore 35 Hospital 6th 6A-133 Service Bay Miscellaneous Tan duct pin mastic All walls 200 LF Good Associated with Drywall No asbestos detected Low N/a H-6-3
Baltimore 35 Hospital 6th 6A-133 Service Bay Surfacing Spray-on fireproofing Beams throughout ceiling deck 650 SF Good No asbestos detected Low N/a H-6-3 Baltimore 35 Hospital 6th 6A-133 Service Bay Miscellaneous White pipe seam sealant Throughout 800 LF Good No asbestos detected Low N/a H-6-3
Baltimore 35 Hospital 6th 6A-133 Service Bay Miscellaneous Brown duct seam sealant Throughout north and east side 65 LF Good On metal 1x1, 4x2, 2x2 duct No asbestos detected Low N/a H-6-3
Baltimore 35 Hospital 6th 6A-133 Service Bay Miscellaneous Gray duct seam sealant East wall 25 LF Good On metal 2x2 duct No asbestos detected Low N/a H-6-3
Baltimore 35 Hospital 6th 6A-133 Service Bay Miscellaneous Red duct seam sealant Bottom of 2x2 duct and east wall 5 LF Good No asbestos detected Low N/a H-6-3 Baltimore 35 Hospital 6th 6A-133 Service Bay Miscellaneous Red fire stop West and north wall 10 SF Good No asbestos detected Low N/a H-6-3 Baltimore 35 Hospital 6th 6A-133 Service Bay Miscellaneous Tan baseboard mastic All walls 160 LF Good No asbestos detected Low N/a H-6-3 Baltimore 35 Hospital 6th 6A-133 Service Bay Miscellaneous Fire door West wall 2 @4'x7' Doors Good Assumed ACM Low 1 O&M H-6-3 Baltimore 36 Hospital 6th 6A-133C Electrical Closet Miscellaneous Drywall All walls 550 SF Good No asbestos detected High N/a H-6-3 Baltimore 36 Hospital 6th 6A-133C Electrical Closet Miscellaneous Joint Compound All walls 550 SF Good No asbestos detected High N/a H-6-3 Baltimore 36 Hospital 6th 6A-133C Electrical Closet Surfacing Spray-on fireproofing Beams on ceiling 60 SF Good No asbestos detected Low N/a H-6-3
ACM Data Table - 4
Asbestos Containing Material Data Table
Campus Site Area Designation Building Number Floor Room Number Category (AHERA
Class) Material Type Location Quantity Unit of Measure Condition Comments Asbestos Content Access Hazard
Ranking Response
Action Drawing Number Photo Number
Baltimore 36 Hospital 6th 6A-133C Electrical Closet Miscellaneous Red fire stop All walls 10 SF Good No asbestos detected Low N/a H-6-3 Baltimore 36 Hospital 6th 6A-133C Electrical Closet Miscellaneous Fire door East wall 1 @4'x7' Doors Good Assumed ACM Low 1 O&M H-6-3 Baltimore 36 Hospital 6th 6A-133C Electrical Closet Miscellaneous Tan duct pin mastic At ceiling along south wall 16 LF Good No asbestos detected Low N/a H-6-3 Baltimore 37 Hospital 6th 6B-129 Service Bay Miscellaneous Drywall All walls 2,400 SF Good No asbestos detected High N/a H-6-4 Baltimore 37 Hospital 6th 6B-129 Service Bay Miscellaneous Joint Compound All walls 2,400 SF Good No asbestos detected High N/a H-6-4
Baltimore 37 Hospital 6th 6B-129 Service Bay Miscellaneous Tan duct pin mastic All walls 200 LF Good Associated with Drywall No asbestos detected Low N/a H-6-4
Baltimore 37 Hospital 6th 6B-129 Service Bay Surfacing Spray-on fireproofing Beams throughout ceiling deck 650 SF Good No asbestos detected Low N/a H-6-4 Baltimore 37 Hospital 6th 6B-129 Service Bay Miscellaneous White pipe seam sealant Throughout 800 LF Good No asbestos detected Low N/a H-6-4
Baltimore 37 Hospital 6th 6B-129 Service Bay Miscellaneous Brown duct seam sealant Throughout north and east side 120 LF Good On metal 1x1, 4x2, 2x2 duct No asbestos detected Low N/a H-6-3
Baltimore 37 Hospital 6th 6B-129 Service Bay Miscellaneous Gray duct seam sealant west wall 25 LF Good On metal 2x2 duct No asbestos detected Low N/a H-6-4
Baltimore 37 Hospital 6th 6B-129 Service Bay Miscellaneous Red duct seam sealant Bottom of 2x2 duct and west wall 5 LF Good No asbestos detected Low N/a H-6-4 Baltimore 37 Hospital 6th 6B-129 Service Bay Miscellaneous Red fire stop West and north wall 10 SF Good No asbestos detected Low N/a H-6-4 Baltimore 37 Hospital 6th 6B-129 Service Bay Miscellaneous Tan baseboard mastic All walls 160 LF Good No asbestos detected Low N/a H-6-4 Baltimore 37 Hospital 6th 6B-129 Service Bay Miscellaneous Fire door East wall 2 @4'x7' Doors Good Assumed ACM Low 1 O&M H-6-4 Baltimore 38 Hospital 6th 6B-129C Miscellaneous Drywall All walls 550 SF Good No asbestos detected High N/a H-6-3 Baltimore 38 Hospital 6th 6B-129C Miscellaneous Joint Compound All walls 550 SF Good No asbestos detected High N/a H-6-4 Baltimore 38 Hospital 6th 6B-129C Surfacing Spray-on fireproofing Beams on ceiling 60 SF Good No asbestos detected Low N/a H-6-4 Baltimore 38 Hospital 6th 6B-129C Miscellaneous Red fire stop All walls 10 SF Good No asbestos detected Low N/a H-6-4 Baltimore 38 Hospital 6th 6B-129C Miscellaneous Fire door West wall 1 @4'x7' Doors Good Assumed ACM Low 1 O&M H-6-4 Baltimore 38 Hospital 6th 6B-129C Miscellaneous Tan duct pin mastic At ceiling along south wall 16 LF Good No asbestos detected Low N/a H-6-4 Baltimore 39 Hospital 6th 6C-100 Service Bay Miscellaneous Drywall All walls 3500 SF Good No asbestos detected High N/a H-6-1 Baltimore 39 Hospital 6th 6C-100 Service Bay Miscellaneous Joint Compound All walls 3500 SF Good No asbestos detected High N/a H-6-1
Baltimore 39 Hospital 6th 6C-100 Service Bay Surfacing Spray-on fireproofing All beams on ceiling and north and south walls 1100 SF Good No asbestos detected Low N/a H-6-1
Baltimore 39 Hospital 6th 6C-100 Service Bay Miscellaneous White pipe seam sealant Throughout 1400 LF Good No asbestos detected Low N/a H-6-4 Baltimore 39 Hospital 6th 6C-100 Service Bay Miscellaneous Brown duct seam sealant Throughout 70 LF Good On metal ducts No asbestos detected Low N/a H-6-1 Baltimore 39 Hospital 6th 6C-100 Service Bay Miscellaneous Red fire stop Throughout all walls 50 SF Good No asbestos detected Low N/a H-6-1 Baltimore 39 Hospital 6th 6C-100 Service Bay Miscellaneous White fire stop All walls 20 SF Good No asbestos detected Low N/a H-6-1 Baltimore 39 Hospital 6th 6C-100 Service Bay Miscellaneous Fire door North and south walls 4 @4'x7' Doors Good Assumed ACM Low 1 O&M H-6-4
Baltimore 39 Hospital 6th 6C-100 Service Bay Miscellaneous Gray duct seam sealant West side/center duct 30 LF Good On 4x3 metal duct No asbestos detected Low N/a H-6-1
Baltimore 39 Hospital 6th 6C-100 Service Bay TSI White pipe breaching At pipes in south and north sides 12 SF Good No asbestos detected High N/a H-6-1 Baltimore 39 Hospital 6th 6C-100 Service Bay Miscellaneous Tan baseboard mastic All walls 220 LF Good No asbestos detected Low N/a H-6-1
Baltimore 39 Hospital 6th 6C-100 Service Bay Miscellaneous Tan duct pin mastic South aside on uncovered duct 5 LF Good On 3x3 metal duct No asbestos detected Low N/a H-6-4
Baltimore 39 Hospital 6th 6C-100 Service Bay Miscellaneous Duct pin mastic (assumed) Throughout canvas 225 LF Good Mastic on various sizes 3x3 & 2x2
No asbestos detected Low N/a H-6-1
Baltimore 40 Hospital 6th 6C-100C Miscellaneous Drywall All walls 520 SF Good No asbestos detected High N/a H-6-1 Baltimore 40 Hospital 6th 6C-100C Miscellaneous Joint Compound All walls 520 SF Good No asbestos detected High N/a H-6-1 Baltimore 40 Hospital 6th 6C-100C Surfacing Spray-on fireproofing Ceiling beams 50 SF Good No asbestos detected Low N/a H-6-4 Baltimore 40 Hospital 6th 6C-100C Miscellaneous Tan duct pin mastic (assumed) East wall at ceiling 17 LF Good 1x1 canvas duct No asbestos detected Low N/a H-6-1 Baltimore 40 Hospital 6th 6C-100C Miscellaneous Red fire stop All walls 10 SF Good No asbestos detected Low N/a H-6-1 Baltimore 40 Hospital 6th 6C-100C Miscellaneous Fire door North wall 1 @4'x7' Doors Good Assumed ACM Low 1 O&M H-6-1 Baltimore 41 Hospital 6th 6D-158 Service Bay Miscellaneous Drywall All walls 3500 SF Good No asbestos detected High N/a H-6-2 Baltimore 41 Hospital 6th 6D-158 Service Bay Miscellaneous Joint Compound All walls 3500 SF Good No asbestos detected High N/a H-6-2
Baltimore 41 Hospital 6th 6D-158 Service Bay Surfacing Spray-on fireproofing All beams on ceiling and north and south walls 1100 SF Good No asbestos detected Low N/a H-6-2
Baltimore 41 Hospital 6th 6D-158 Service Bay Miscellaneous White pipe seam sealant Throughout 1400 LF Good No asbestos detected Low N/a H-6-2
Baltimore 41 Hospital 6th 6D-158 Service Bay Miscellaneous Brown duct seam sealant Throughout 110 LF Good On metal ducts 1x1; 3x3; 4x2 No asbestos detected Low N/a H-6-2
Baltimore 41 Hospital 6th 6D-158 Service Bay Miscellaneous Red fire stop Throughout all walls 50 SF Good No asbestos detected Low N/a H-6-2 Baltimore 41 Hospital 6th 6D-158 Service Bay Miscellaneous White fire stop All walls 20 SF Good No asbestos detected Low N/a H-6-2 Baltimore 41 Hospital 6th 6D-158 Service Bay Miscellaneous Fire door North and south walls 4 @4'x7' Doors Good Assumed ACM Low 1 O&M H-6-2
Baltimore 41 Hospital 6th 6D-158 Service Bay Miscellaneous Gray duct seam sealant East side/center duct 30 LF Good On 4x3 metal duct No asbestos detected Low N/a H-6-2
Baltimore 41 Hospital 6th 6D-158 Service Bay TSI White pipe breaching At pipes in south and north sides 12 SF Good No asbestos detected High N/a H-6-2 Baltimore 41 Hospital 6th 6D-158 Service Bay Miscellaneous Tan baseboard mastic All walls 220 LF Good No asbestos detected Low N/a H-6-2
Baltimore 41 Hospital 6th 6D-158 Service Bay Miscellaneous Tan duct pin mastic South aside on uncovered duct 5 LF Good On 3x3 metal duct No asbestos detected Low N/a H-6-2
Baltimore 41 Hospital 6th 6D-158 Service Bay Miscellaneous Duct pin mastic (assumed) Throughout canvas 225 LF Good Mastic on various sizes 3x3 & 2x2
No asbestos detected Low N/a H-6-2
ACM Data Table - 5
Asbestos Containing Material Data Table
Campus Site Area Designation Building Number Floor Room Number Category (AHERA
Class) Material Type Location Quantity Unit of Measure Condition Comments Asbestos Content Access Hazard
Ranking Response
Action Drawing Number Photo Number
Baltimore 41 Hospital 6th 6D-158 Service Bay Miscellaneous Dark Gray duct seam sealant Southern side of room 65 LF Good Assumed under canvas wrapped newer white duct No asbestos detected Low N/a H-6-2
Baltimore 42 Hospital 6th 6D-158A Electrical Closet Miscellaneous Drywall All walls 520 SF Good No asbestos detected High N/a H-6-2 Baltimore 42 Hospital 6th 6D-158A Electrical Closet Miscellaneous Joint Compound All walls 520 SF Good No asbestos detected High N/a H-6-2 Baltimore 42 Hospital 6th 6D-158A Electrical Closet Surfacing Spray-on fireproofing Ceiling beams 50 SF Good No asbestos detected Low N/a H-6-2 Baltimore 42 Hospital 6th 6D-158A Electrical Closet Miscellaneous Tan duct pin mastic (assumed) West wall at ceiling 17 LF Good 1x1 canvas duct No asbestos detected Low N/a H-6-2 Baltimore 42 Hospital 6th 6D-158A Electrical Closet Miscellaneous Red fire stop All walls 10 SF Good No asbestos detected Low N/a H-6-2 Baltimore 42 Hospital 6th 6D-158A Electrical Closet Miscellaneous Fire door North wall 1 @4'x7' Doors Good Assumed ACM Low 1 O&M H-6-2 Baltimore 43 Hospital 5th 5A-127 Service Bay Miscellaneous Drywall All walls 2,400 SF Good No asbestos detected High N/a H-5-3 Baltimore 43 Hospital 5th 5A-127 Service Bay Miscellaneous Joint Compound All walls 2,400 SF Good No asbestos detected High N/a H-5-3
Baltimore 43 Hospital 5th 5A-127 Service Bay Miscellaneous Tan duct pin mastic All walls 200 LF Good Associated with Drywall No asbestos detected Low N/a H-5-3
Baltimore 43 Hospital 5th 5A-127 Service Bay Surfacing Spray-on fireproofing Beams throughout ceiling deck 650 SF Good No asbestos detected Low N/a H-5-3 Baltimore 43 Hospital 5th 5A-127 Service Bay Miscellaneous White pipe seam sealant Throughout 800 LF Good No asbestos detected Low N/a H-5-3
Baltimore 43 Hospital 5th 5A-127 Service Bay Miscellaneous Brown duct seam sealant Throughout north and east side 65 LF Good On metal 1x1, 4x2, 2x2 duct No asbestos detected Low N/a H-5-3
Baltimore 43 Hospital 5th 5A-127 Service Bay Miscellaneous Gray duct seam sealant East wall 25 LF Good On metal 2x2 duct No asbestos detected Low N/a H-5-3
Baltimore 43 Hospital 5th 5A-127 Service Bay Miscellaneous Red duct seam sealant Bottom of 2x2 duct and east wall 5 LF Good No asbestos detected Low N/a H-5-3 Baltimore 43 Hospital 5th 5A-127 Service Bay Miscellaneous Red fire stop West and north wall 10 SF Good No asbestos detected Low N/a H-5-3 Baltimore 43 Hospital 5th 5A-127 Service Bay Miscellaneous Tan baseboard mastic All walls 160 LF Good No asbestos detected Low N/a H-5-3 Baltimore 43 Hospital 5th 5A-127 Service Bay Miscellaneous Fire door East wall 2 @4'x7' Doors Good Assumed ACM Low 1 O&M H-5-3 Baltimore 44 Hospital 5th 5A-127C Electrical Closet Miscellaneous Drywall All walls 550 SF Good No asbestos detected High N/a H-5-3 Baltimore 44 Hospital 5th 5A-127C Electrical Closet Miscellaneous Joint Compound All walls 550 SF Good No asbestos detected High N/a H-5-3 Baltimore 44 Hospital 5th 5A-127C Electrical Closet Surfacing Spray-on fireproofing Beams on ceiling 60 SF Good No asbestos detected Low N/a H-5-3 Baltimore 44 Hospital 5th 5A-127C Electrical Closet Miscellaneous Red fire stop All walls 10 SF Good No asbestos detected Low N/a H-5-3 Baltimore 44 Hospital 5th 5A-127C Electrical Closet Miscellaneous Fire door East wall 1 @4'x7' Doors Good Assumed ACM Low 1 O&M H-5-3 Baltimore 44 Hospital 5th 5A-127C Electrical Closet Miscellaneous Tan duct pin mastic At ceiling along south wall 16 LF Good No asbestos detected Low N/a H-5-3 Baltimore 45 Hospital 5th 5B-136 Service Bay Miscellaneous Drywall All walls 2,400 SF Good No asbestos detected High N/a H-5-4 Baltimore 45 Hospital 5th 5B-136 Service Bay Miscellaneous Joint Compound All walls 2,400 SF Good No asbestos detected High N/a H-5-4
Baltimore 45 Hospital 5th 5B-136 Service Bay Miscellaneous Tan duct pin mastic All walls 200 LF Good Associated with Drywall No asbestos detected Low N/a H-5-4
Baltimore 45 Hospital 5th 5B-136 Service Bay Surfacing Spray-on fireproofing Beams throughout ceiling deck 650 SF Good No asbestos detected Low N/a H-5-4 Baltimore 45 Hospital 5th 5B-136 Service Bay Miscellaneous White pipe seam sealant Throughout 800 LF Good No asbestos detected Low N/a H-5-4
Baltimore 45 Hospital 5th 5B-136 Service Bay Miscellaneous Brown duct seam sealant Throughout north and east side 120 LF Good On metal 1x1, 4x2, 2x2 duct No asbestos detected Low N/a H-5-4
Baltimore 45 Hospital 5th 5B-136 Service Bay Miscellaneous Gray duct seam sealant west wall 25 LF Good On metal 2x2 duct No asbestos detected Low N/a H-5-4
Baltimore 45 Hospital 5th 5B-136 Service Bay Miscellaneous Red duct seam sealant Bottom of 2x2 duct and west wall 5 LF Good No asbestos detected Low N/a H-5-4 Baltimore 45 Hospital 5th 5B-136 Service Bay Miscellaneous Red fire stop West and north wall 10 SF Good No asbestos detected Low N/a H-5-4 Baltimore 45 Hospital 5th 5B-136 Service Bay Miscellaneous Tan baseboard mastic All walls 160 LF Good No asbestos detected Low N/a H-5-4 Baltimore 45 Hospital 5th 5B-136 Service Bay Miscellaneous Fire door East wall 2 @4'x7' Doors Good Assumed ACM Low 1 O&M H-5-4 Baltimore 46 Hospital 5th 5B-136C Electrical Closet Miscellaneous Drywall All walls 550 SF Good No asbestos detected High N/a H-5-4 Baltimore 46 Hospital 5th 5B-136C Electrical Closet Miscellaneous Joint Compound All walls 550 SF Good No asbestos detected High N/a H-5-4 Baltimore 46 Hospital 5th 5B-136C Electrical Closet Surfacing Spray-on fireproofing Beams on ceiling 60 SF Good No asbestos detected Low N/a H-5-4 Baltimore 46 Hospital 5th 5B-136C Electrical Closet Miscellaneous Red fire stop All walls 10 SF Good No asbestos detected Low N/a H-5-4 Baltimore 46 Hospital 5th 5B-136C Electrical Closet Miscellaneous Fire door West wall 1 @4'x7' Doors Good Assumed ACM Low 1 O&M H-5-4 Baltimore 46 Hospital 5th 5B-136C Electrical Closet Miscellaneous Tan duct pin mastic At ceiling along south wall 16 LF Good No asbestos detected Low N/a H-5-4 Baltimore 47 Hospital 5th 5C-114 Service Bay Miscellaneous Drywall All walls 3500 SF Good No asbestos detected High N/a H-5-1 Baltimore 47 Hospital 5th 5C-114 Service Bay Miscellaneous Joint Compound All walls 3500 SF Good No asbestos detected High N/a H-5-1
Baltimore 47 Hospital 5th 5C-114 Service Bay Surfacing Spray-on fireproofing All beams on ceiling and north and south walls 1100 SF Good No asbestos detected Low N/a H-5-1
Baltimore 47 Hospital 5th 5C-114 Service Bay Miscellaneous White pipe seam sealant Throughout 1400 LF Good No asbestos detected Low N/a H-5-1 Baltimore 47 Hospital 5th 5C-114 Service Bay Miscellaneous Brown duct seam sealant Throughout 110 LF Good On metal ducts No asbestos detected Low N/a H-5-1 Baltimore 47 Hospital 5th 5C-114 Service Bay Miscellaneous Red fire stop Throughout all walls 50 SF Good No asbestos detected Low N/a H-5-1 Baltimore 47 Hospital 5th 5C-114 Service Bay Miscellaneous White fire stop All walls 20 SF Good No asbestos detected Low N/a H-5-1 Baltimore 47 Hospital 5th 5C-114 Service Bay Miscellaneous Fire door North and south walls 4 @4'x7' Doors Good Assumed ACM Low 1 O&M H-5-1
Baltimore 47 Hospital 5th 5C-114 Service Bay Miscellaneous Gray duct seam sealant West side/center duct 30 LF Good On 4x3 metal duct No asbestos detected Low N/a H-5-1
Baltimore 47 Hospital 5th 5C-114 Service Bay TSI White pipe breaching At pipes in south and north sides 12 SF Good No asbestos detected High N/a H-5-1 Baltimore 47 Hospital 5th 5C-114 Service Bay Miscellaneous Tan baseboard mastic All walls 220 LF Good No asbestos detected Low N/a H-5-1
Baltimore 47 Hospital 5th 5C-114 Service Bay Miscellaneous Tan duct pin mastic South aside on uncovered duct 5 LF Good On 3x3 metal duct No asbestos detected Low N/a H-5-1
Baltimore 47 Hospital 5th 5C-114 Service Bay Miscellaneous Duct pin mastic (assumed) Throughout canvas 225 LF Good Mastic on various sizes 3x3 & 2x2
No asbestos detected Low N/a H-5-1
Baltimore 48 Hospital 5th 5C-114C Electrical Closet Miscellaneous Drywall All walls 520 SF Good No asbestos detected High N/a H-5-1
ACM Data Table - 6
Asbestos Containing Material Data Table
Campus Site Area Designation Building Number Floor Room Number Category (AHERA
Class) Material Type Location Quantity Unit of Measure Condition Comments Asbestos Content Access Hazard
Ranking Response
Action Drawing Number Photo Number
Baltimore 48 Hospital 5th 5C-114C Electrical Closet Miscellaneous Joint Compound All walls 520 SF Good No asbestos detected High N/a H-5-1 Baltimore 48 Hospital 5th 5C-114C Electrical Closet Surfacing Spray-on fireproofing Ceiling beams 50 SF Good No asbestos detected Low N/a H-5-1 Baltimore 48 Hospital 5th 5C-114C Electrical Closet Miscellaneous Tan duct pin mastic (assumed) East wall at ceiling 17 LF Good 1x1 canvas duct No asbestos detected Low N/a H-5-1 Baltimore 48 Hospital 5th 5C-114C Electrical Closet Miscellaneous Red fire stop All walls 10 SF Good No asbestos detected Low N/a H-5-1 Baltimore 48 Hospital 5th 5C-114C Electrical Closet Miscellaneous Fire door North wall 1 @4'x7' Doors Good Assumed ACM Low 1 O&M H-5-1 Baltimore 49 Hospital 5th 5D-130 Service Bay Miscellaneous Drywall All walls 3500 SF Good No asbestos detected High N/a H-5-2 Baltimore 49 Hospital 5th 5D-130 Service Bay Miscellaneous Joint Compound All walls 3500 SF Good No asbestos detected High N/a H-5-2
Baltimore 49 Hospital 5th 5D-130 Service Bay Surfacing Spray-on fireproofing All ceiling beams and north and south walls 1100 SF Good No asbestos detected Low N/a H-5-2
Baltimore 49 Hospital 5th 5D-130 Service Bay Miscellaneous White pipe seam sealant Throughout 1400 SF…