Questions and Answers 36C24423Q1217 Attachment B.docx

DOCX document 849 KB Posted

Attached to
J041--Heating and Cooling | HVAC Repair on non-BAS | Board Room Roof Top Unit Replacement |
Solicitation number
36C24423Q1217
Issued by

About this file

This document contains questions and answers regarding a federal solicitation for replacement of a roof top unit at a Department of Veterans Affairs facility. Key details include that there will be no site visit, the current unit is a 7.5-ton downflow unit that is not connected to the building automation system, and contact information for the on-site representative is provided in Attachment C. No specification sheet is available for the existing equipment. Bidders are advised to obtain the model and serial number to confirm specifications. The solicitation number is 36C24423Q1217 for an HVAC repair and replacement opportunity through the Veterans Health Administration Veterans Integrated Service Network 4.

View the file

Other files

File Type Posted
36C24423Q1217 0001_1.docx DOCX document
Site Visit Information Attachment C.pdf PDF
36C24423Q1217 0001 Attachment A.pdf PDF
36C24423Q1217_1.docx DOCX document
WD 2015-4233 Philadelphia PA REV 27 6-30-23.pdf PDF
RFQ.docx DOCX document

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Contractor Questions and Answers

· Is there a scheduled site visit? Can we coordinate a site visit to assess conditions? See Attachment C.

· Is there an existing Building Automation System? Does the RTU need to be integrated to a BAS? The current unit is not connected to our BAS. Unit does not require BAS integration

· Contact info for on-site representative? See Attachment C.

· Is the unit in a downflow or horizontal configuration? (ductwork coming out of the side or the bottom on the unit?) The current unit is a downflow.

· Is there electric heat installed, or is this being used as a cooling only unit? This unit is cooling only. (No Electric heat).

· We would like to find out the size of the existing RTU. I Believe this is a 7.5 Ton unit ( Model and serial number will confirm for any bidders)

· We hope we could have a specification sheet for the existing equipment to ensure that our multiple offers are all matching or exceed the necessary specs. No spec sheet is available on site. Confirmation can be made by utilizing model and serial#.