36C24419B0008-0001002.pdf

PDF 7 MB Posted

Attached to
Upgrade Public Toilets First Floor Federal contract opportunity
Solicitation number
36C24419B0008
Issued by
Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 4

About this file

36C24419B0008 0001 Atch 4 Auto-Faucet installation instructions.pdf

View the file

Other files for this federal contract opportunity

Other files attached to Upgrade Public Toilets First Floor, newest first.
File Type Posted
36C24419B0008-0001003.pdf PDF
36C24419B0008-0001005.pdf PDF
36C24419B0008-0001000.docx DOCX document
36C24419B0008-0001001.pdf PDF
36C24419B0008-0001004.pdf PDF
S02_Atch_3_UPTFF_-_Constructiion_Duration_-_Calendar_Days.pdf PDF
S02_Atch_1__Bid_Documents_Specification_02.pdf PDF
36C24419B0008.docx DOCX document
S02_Atch_2__Bid_Documents_Drawing_Set.pdf PDF
36C24419B0008_1.docx DOCX document

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

10 - TEST FAUCET OPERATION

1. Place hands under faucet. Solenoid valve should "click," LED in sensor window should blink once and water should flow from the spout.

2. When hands are removed, the water flow should stop.

CARE AND CLEANING OF CHROME AND SPECIAL FINISHES

DO NOT USE abrasive or chemical cleaners (including chlorine bleach) to clean Faucets that may dull the luster and attack the chrome or special decorative finishes. Use ONLY mild soap and water, then wipe dry with clean cloth or towel.

While cleaning the bathroom tile, protect the Faucet from any splattering of cleaner. Acids and cleaning fluids will discolor or remove chrome plating.

TROUBLESHOOTING GUIDE

1. Faucet delivers water in an uncontrolled manner.

A. Contact Sloan Valve Company Installation Engineering Department (see below).

2. Faucet does not deliver any water when Sensor is activated.

INDICATOR: Solenoid valve produces an audible "CLICK."

A. Water supply stop(s) closed. Open water supply stop(s).

B. Water strainer in control module is clogged. Close supply stops and remove water inlet line at control module. Remove, clean and reinstall strainer and water inlet line. Replace strainer if required.

INDICATOR: Solenoid valve DOES NOT produce an audible

"CLICK."

A. Batteries low (battery powered models). Replace batteries.

B. Power failure (adapter powered models). Check power supply.

3. Faucet delivers only a slow flow or dribble when Sensor is activated.

A. Water supply stop(s) are partially closed. Completely open water supply stop(s).

B. Water strainer in control module is clogged. Close supply stops and remove water inlet line at control module. Remove, clean and reinstall strainer and water inlet line. Replace strainer if required.

C. Aerator is clogged. Remove, clean, and reinstall aerator.

Replace aerator if required.

D. Valve may be obstructed. Contact Sloan Valve Company Installation Engineering Department (see below).

I

4. Faucet does not stop delivering water or continues to drip after user is no longer detected.

A. Valve is not sealing. Contact Sloan Valve Company Installation

Engineering Department (see below).

5. The water temperature is too hot or too cold on a Faucet connected to hot and cold supply lines.

A. Supply Stops are not adjusted properly. Adjust Supply Stops.

When assistance is required, please contact Sloan Valve Company Installation Engineering Department at:

1-888-SLOAN-14: (1-888-756-2614)