This document is an Amendment to a Solicitation (Standard Form 30) issued by the Department of Veterans Affairs, Samuel S. Stratton VA Medical Center in Albany, New York. The amendment modifies Invitation for Bid No. 36C24227B0003 for Project 561-26-103, which concerns the upgrade of electrical and plumbing in Building 18B. The amendment was issued on November 23, 2026, with an effective date of the same date. The primary purpose of this amendment is to publish a Request for Information (RFI) answers list for interested contractors. The document confirms that all other terms and conditions of the original solicitation remain unchanged, and offerors must acknowledge receipt of this amendment prior to the specified hour and date, or risk rejection of their offers.

The amendment includes four RFI questions and answers addressing electrical installation specifications: (1) MC cable is permitted within individual rooms above ceilings, within walls, and from junction boxes to devices where code permits, while conduit is required for wiring routed above suspended ceilings in hallways; (2) compression-type fittings shall be used where conduit fittings are required; (3) conductors smaller than No. 8 AWG are not required to be solid conductors; and (4) exposed raceways installed within rooms must be surface-mounted Wiremold rather than EMT. The contracting activity is the Network Contracting Activity at the Samuel S. Stratton VA Medical Center.

View the file

Other files

Show all 16

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

5. PROJECT NUMBER (if applicable)

CODE 7. ADMINISTERED BY

2. AMENDMENT/MODIFICATION NUMBER

CODE

6. ISSUED BY

8. NAME AND ADDRESS OF CONTRACTOR

4. REQUISITION/PURCHASE REQ. NUMBER 3. EFFECTIVE DATE

9A. AMENDMENT OF SOLICITATION NUMBER

9B. DATED

PAGE OF PAGES

10A. MODIFICATION OF CONTRACT/ORDER NUMBER

10B. DATED

BPA NO. 1. CONTRACT ID CODE

FACILITY CODE CODE

Offers must acknowledge receipt of this amendment prior to the hour and date specified in the solicitation or as amended, by one of the following methods:

The above numbered solicitation is amended as set forth in Item 14. The hour and date specified for receipt of Offers

E. IMPORTANT:

is extended,

(a) By completing Items 8 and 15, and returning __________ copies of the amendment; (b) By acknowledging receipt of this amendment on each copy of the offer submitted; or (c) By separate letter or electronic communication which includes a reference to the solicitation and amendment numbers. FAILURE OF YOUR ACKNOWLEDGMENT TO BE RECEIVED AT THE PLACE DESIGNATED FOR THE RECEIPT OF OFFERS PRIOR TO THE HOUR AND DATE SPECIFIED MAY is not extended.

12. ACCOUNTING AND APPROPRIATION DATA

(REV. 11/2016)

is required to sign this document and return ___________ copies to the issuing office. is not, A. THIS CHANGE ORDER IS ISSUED PURSUANT TO: (Specify authority) THE CHANGES SET FORTH IN ITEM 14 ARE MADE IN THE CONTRACT ORDER NO. IN ITEM 10A.

15C. DATE SIGNED

B. THE ABOVE NUMBERED CONTRACT/ORDER IS MODIFIED TO REFLECT THE ADMINISTRATIVE CHANGES SET FORTH IN ITEM 14, PURSUANT TO THE AUTHORITY OF FAR 43.103(b).

RESULT IN REJECTION OF YOUR OFFER. If by virtue of this amendment you desire to change an offer already submitted, such change may be made by letter or electronic communication, provided each letter or electronic communication makes reference to the solicitation and this amendment, and is received prior to the opening hour and date specified.

C. THIS SUPPLEMENTAL AGREEMENT IS ENTERED INTO PURSUANT TO AUTHORITY OF:

D. OTHER

Contractor

16C. DATE SIGNED

14. DESCRIPTION OF AMENDMENT/MODIFICATION

16B. UNITED STATES OF AMERICA

Except as provided herein, all terms and conditions of the document referenced in Item 9A or 10A, as heretofore changed, remains unchanged and in full force and effect.

15A. NAME AND TITLE OF SIGNER 16A. NAME AND TITLE OF CONTRACTING OFFICER

15B. CONTRACTOR/OFFEROR

STANDARD FORM 30 PREVIOUS EDITION NOT USABLE

Prescribed by GSA - FAR (48 CFR) 53.243

(Type or print) (Type or print)

(Organized by UCF section headings, including solicitation/contract subject matter where feasible.)

(Number, street, county, State and ZIP Code)

(If other than Item 6)

(Specify type of modification and authority)

(such as changes in paying office, appropriation date, etc.)

(If required)

(SEE ITEM 11)

(SEE ITEM 13)

(X)

CHECK

ONE

13. THIS ITEM APPLIES ONLY TO MODIFICATIONS OF CONTRACTS/ORDERS,

IT MODIFIES THE CONTRACT/ORDER NO. AS DESCRIBED IN ITEM 14.

11. THIS ITEM ONLY APPLIES TO AMENDMENTS OF SOLICITATIONS

AMENDMENT OF SOLICITATION/MODIFICATION OF CONTRACT

(Signature of person authorized to sign) (Signature of Contracting Officer)

0006 11-23-2026

561-26-103

36C242

Department of Veterans Affairs Samuel S . Stratton VA Medical Center 113 Holland Avenue (2-90NCA) Albany NY 12208-3410

36C242

Department of Veterans Affairs Samuel S . Stratton VA Medical Center Network Contracting Activity 113 Holland Avenue (2-90NCA) Albany NY 12208-3410

To all Offerors/Bidders

36C24227B0003

X

X X

N/A x 1

Amendment to Invitaton For Bid No. 36C24227B0003, Project 561-26-103 Upgrade Electrical and Plumbing in building 18B

The purpose of this amendment is to

- Publish an RFI answers list for interested contractors

All other terms and conditions of the original solicitation remains unchanged.

Dayna Dickson-Miller

RFI Questions and Answers

Upgrade electrical and plumbing in Building 18B | 36C24227B0003

1) Is the VA allowing MC Cable on this job or is all wiring to be in conduit? Except for short whips at fixtures.

Conduit shall be provided for wiring routed above the suspended ceiling in the hallway and back to the electrical closet. Within individual rooms, MC cable may be utilized above ceilings, within walls, and from junction boxes to devices, where permitted by applicable codes.

2) If wiring needs to be in conduit are the fittings required to be compression style?

Yes. Where conduit fittings are required, compression-type fittings shall be used.

3) All wires under size 8 need to be solid conductors?

No. Conductors smaller than No. 8 AWG are not required to be solid conductors.

4) Conduits exposed in the rooms, can it be emt or does it need to be wiremold?

Exposed raceways installed within rooms shall be surface-mounted Wiremold.

File details come from the government source that posted it. Updated .