Inspection Report Summaries.pdf
PDF 177 KB Posted
- Attached to
- J063--Fire Alarm Service and Upgrade
- Solicitation number
- 36C24226Q0336
About this file
These are fire alarm inspection reports for four Veterans Affairs medical facilities documenting compliance with fire safety standards as of December 2024 through December 2025.
Brooklyn VA (December 2024): Semi-annual inspection of 1,026 devices across all alarm system categories resulted in zero deficiencies. All tested equipment—345 smoke detectors, 137 manual pull stations, 101 heat detectors, 42 duct detectors, 122 water flow switches, 110 valve tamper switches, 44 HVAC shutdown devices, 33 speakers, 1 strobe, 76 miscellaneous devices, and 41 phones/warden stations—passed functionality and sensitivity testing. All alarm panels, supervisory functions, auxiliary functions (elevator recall, HVAC shutdown, stair pressurization), and fire pump/generator monitoring passed. Central station communication was verified. Testing met Joint Commission and NFPA 72/25 standards.
Manhattan VA (October 2025): Full campus annual inspection of 1,395 devices recorded zero deficiencies across all buildings. Initiating devices tested included 543 smoke detectors, 182 manual pull stations, 105 heat detectors, 111 duct detectors, 97 water flow switches, 36 valve tamper switches, 4 air pressure switches, and 2 pressure switches—all passed. Notification appliances included 226 speakers and 2 strobes (all functional); 12 miscellaneous fire alarm devices and 6 fire phones/warden stations passed. Auxiliary systems—62 HVAC shutdown devices and 5 elevator recall devices—functioned without failures. All smoke detector sensitivity tests were within required ranges. System achieved full compliance with NFPA 72, NFPA 25, and Joint Commission EC.02.03.05 standards.
St. Albans (Queens) VA (December 2025): Annual inspection tested 637 devices with zero device-level failures: 299 smoke detectors, 142 manual pull stations, 47 heat detectors, 3 miscellaneous initiating devices, 84 strobes/horns, 31 HVAC shutdown devices, and 31 elevator recall devices all passed functionality and sensitivity testing. However, a critical system-wide deficiency exists: all fire alarm panels across the hospital fail to communicate with one another, resulting in independent building-level operation and no signals transmitted to the central monitoring station. This communication failure represents a facility-wide life-safety impairment requiring immediate remediation to restore NFPA and Joint Commission compliance despite perfect individual device performance.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 36C24226Q0336 0002.docx | DOCX document | |
| 36C24226Q0336 0001.docx | DOCX document | |
| Site Visit Info - Fire Alarm.pdf | ||
| Brooklyn Equip. Inventory List.pdf | ||
| Manhattan Equip. Inventory List.pdf | ||
| 36C24226Q0336.docx | DOCX document | |
| Battery_Price_Schedule.pdf | ||
| NYH Battery Inventory.pdf | ||
| St Albans Equip. Inventory.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Brooklyn VA Semi-Annual Fire Alarm Inspection Report (December 2024)
Overall Condition
• All tested systems and devices passed inspection.
• No deficiencies were reported across all categories.
• The fire alarm system, including panels, initiating devices, notification appliances, and supervisory functions, is in excellent operational condition.
Systems Tested
• Alarm Panels: All panels inspected and tested; power supply, lamps, displays, fuses, and surge protection were in good condition.
• Alarm Functions: Bells, horns, strobes, and evacuation signals actuated properly.
• Supervisory Functions: AC/secondary power loss, open/short circuits, ground faults, panel-to-panel integrity, and annunciators all passed.
• Auxiliary Functions: Elevator recall, HVAC shutdown, stair pressurization, and water/temperature monitoring all passed.
• Fire Pump & Generator Supervisory: All monitored conditions (power, running status, phase reversal, auto position, trouble signals) passed.
• Central Station Communication: Verified for alarm, trouble, and supervisory signals.
Device Counts & Status
• Smoke Detectors: 345 tested – all passed.
• Manual Pull Stations: 137 tested – all passed.
• Heat Detectors: 101 tested – all passed.
• Duct Detectors: 42 tested – all passed.
• Water Flow Switches: 122 tested – all passed.
• Valve Tamper Switches: 110 tested – all passed.
• HVAC Shutdown Devices: 44 tested – all passed.
• Speakers: 33 tested – all passed.
• Strobes: 1 tested – passed.
• Miscellaneous Devices: 76 tested – all passed.
• Phones/Warden Stations: 41 tested – all passed.
Total Devices Tested: 1,026 Deficiencies: 0 (No repairs, replacements, or failures reported)
Compliance
• Testing met Joint Commission and NFPA 72/25 standards for frequency and functionality.
• Smoke detector sensitivity tests were performed and all were within acceptable ranges.
Manhattan VA – Full Campus Annual Fire Alarm Inspection (October 17, 2025)
Overall Condition Excellent operational condition overall.
All 1,395 devices inspected passed, with zero deficiencies recorded across every building and device category.
High-Level Summary
• Total Devices Tested: 1,395
• Total Failures: 0
• Total Repaired/Serviced Items: 0
• Total Unable to Inspect: 0
System-Level Findings All major fire alarm system functions passed testing, including:
• Alarm bells, horns, strobes, and evacuation signaling
• Supervisory functions (AC loss, secondary power loss, open/short circuits, ground faults)
• Panel-to-panel communication
• Remote annunciators
• Elevator recall (primary and alternate floors)
• Stair pressurization
• HVAC shutdowns
• Fire pump supervisory monitoring
• Generator supervisory monitoring
Central Station test: Alarm, trouble, and supervisory signals were transmitted and verified successfully.
Device Category Summary Initiating Devices Device Type Tested Failures Result Smoke Detectors 543 0 All passed
Heat Detectors 105 0 All passed
Manual Pull Stations 182 0 All passed
Duct Detectors 111 0 All passed
Water Flow Switches 97 0 All passed
Valve Tamper Switches 36 0 All passed
Device Type Tested Failures Result Air Hi/Low Pressure Switches 4 0 All passed
Pressure Switches 2 0 All passed
Notification Appliances Device Type Tested Failures Result Speakers 226 0 All functional
Strobes 2 0 All functional
Miscellaneous Devices
• 12 miscellaneous fire alarm devices: All passed
• 6 fire phones/warden stations: All passed
Auxiliary Devices & Life Safety Systems HVAC Shutdown
• 62 devices tested, 0 failures
Elevator Recall
• 5 devices tested, 0 failures
Fire Pump & Generator Monitoring All supervisory points functioned correctly (power, running status, phase reversal, auto position).
Smoke Detector Sensitivity Testing All detectors tested were within required sensitivity ranges, and all passed the alarm-response test.
No units required cleaning or recalibration.
Key Takeaways
• Outstanding system performance: Zero deficiencies in a campus-wide inspection of nearly 1,400 devices.
• Full compliance with NFPA 72, NFPA 25, and Joint Commission EC.02.03.05 standards.
• All life-safety functions verified, including HVAC shutdowns, elevator recall, fire pump supervision, and generator supervisory circuits.
• Central station communication fully functional.
St. Albans (Queens) VA – Annual Fire Alarm Inspection (December 2025)
Overall Condition Strong device-level performance overall.
One major system-level deficiency impacting reliability:
• All fire alarm panels across the hospital are not communicating with one another, resulting in independent operation by building and no signals being transmitted to the central station.
Device Testing Summary Alarm-Initiating Devices
• Smoke Detectors: 299 tested, 0 failed.
• Manual Pull Stations: 142 tested, 0 failed.
• Heat Detectors: 47 tested, 0 failed.
• Miscellaneous initiating devices: 3 tested, 0 failed.
Notification Appliances
• Strobes: 84 tested, 0 failed.
• Horns: All tested units passed (exact count included within 84-item notification summary).
Auxiliary Systems HVAC Shutdown
• 31 devices tested – 0 failures.
Elevator Recall
• 31 devices tested – 0 failures.
System Power & Batteries
• Primary power, standby batteries, chargers, and system integrity checks all passed.
• All detectors listed in maintenance log were cleaned and passed sensitivity checks.
Total Devices Tested Across all categories:
637 devices tested — 0 device failures.
Summary Strengths:
• All field devices—smoke, heat, pull stations, strobes, horns—passed functional testing.
• HVAC shutdown, elevator recall, and special system interfaces are fully operational.
• All detectors cleaned and sensitivity-tested successfully.
Critical Deficiency:
• System-wide communication failure between fire alarm panels.
• No signals are reaching the central monitoring station.
• This represents a facility-wide life-safety impairment despite perfect device testing.
Conclusion The St. Albans VA fire alarm hardware (detectors, alarms, initiating devices) is fully operational and performing normally, with zero device-level deficiencies.
However, the system has a major network / communication failure affecting panel interconnection and monitoring, which must be addressed immediately to restore full NFPA and Joint Commission compliance.
| Brooklyn Inspection Report_December 2024 |
| Brooklyn VA Semi-Annual Fire Alarm Inspection Report (December 2024) |
| Overall Condition |
| Systems Tested |
| Device Counts & Status |
| Compliance |
| Manhattan Inspection Report_October 2025 |
| St Albans Inspection Report_December 2025 |
| St. Albans (Queens) VA – Annual Fire Alarm Inspection (December 2025) |
| Overall Condition |
| Device Testing Summary |
| Alarm-Initiating Devices |
| Notification Appliances |
| Auxiliary Systems |
| HVAC Shutdown |
| Elevator Recall |
System Power & Batteries
| Total Devices Tested |
| Summary |
| Conclusion |
File details come from the government source that posted it. Updated .