Building 6 Damper Inspection Summary Report.pdf

PDF 7 MB Posted

Attached to
Z1DA--NRM-CONST 630-26-202 Inspect and Repair Fire Dampers
Solicitation number
36C24226B0034
Issued by

About this file

This is a Damper Snapshot Report and detailed inspection report documenting fire damper, smoke damper, and fire/smoke damper conditions at VA Manhattan Building 6 (423 23rd Street, New York, NY 10010) conducted between September 27, 2022 and December 15, 2022. The inspection was performed by Rascap LLC dba Acceptance Engineering under Contract 36C24222C0089 and Purchase Order 630C20166. A total of 270 dampers were inspected across multiple floors (Basement, Floors 1-7) with results showing 191 passed (71%), 52 failed (19%), 23 with no longer exists status (9%), and 4 inaccessible (1%). Inspections were conducted in accordance with NFPA 80, 105 (2010 editions), NFPA 90A (2012 edition), 101 (2012 edition), and Joint Commission standards LS.02.01.10EP-13 and EC.02.03.05EP-18.

The failed dampers require various corrective actions including replacement of dampers with broken/twisted springs, installation of duct access doors to enable proper inspection and testing, repair of dampers that do not fall or are wedged/blocked open, and installation of new links where missing or damaged. Specific deficiencies include dampers manufactured by Arlan, Ruskin, Lloyd, and others with issues such as broken springs, improper installation, missing actuator air supply, and inaccessibility due to obstructions. Floor 1 had the highest concentration of failures with 14 failed dampers, primarily requiring horizontal fire damper replacements ranging from 35.5x5.5 inches to 36x6 inches with associated ductwork fabrication. Floor 5 (mechanical areas) contained 24 failed dampers requiring access doors and/or replacements. The detailed deficiency report provides specific marker labels, damper IDs, locations, and required corrective actions for each failed unit.

View the file

Other files

Show all 14

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

DAMPER SNAPSHOT REPORT

Manhattan VA Bldg 6 Damper Inspection 9.27.22 through 12.15.22

Client Name: VA Manhattan Client Address:423 23rd Street, New York, NY 10010

Inspection Summary

Building 6 Floor Fire Smoke Fire/ Smoke CRD Unk Pass Fail NLE Inaccess NLR Decomm Total

G 7 0 1 0 0 6 1 0 1 0 0 8

1 22 0 0 0 3 10 14 1 0 0 0 25

2 12 0 0 0 3 9 2 3 1 0 0 15

4 4 0 0 0 0 2 2 0 0 0 0 4

5 166 2 0 0 18 143 26 17 0 0 0 186

6 9 0 0 0 2 8 1 2 0 0 0 11

7 19 0 2 0 0 13 6 0 2 0 0 21

SubTotal 239 2 3 0 26 191 52 23 4 0 0 270

GrandTotal 239 2 3 0 26 191 52 23 4 0 0 270

CRD - Ceiling Radiation Damper Unk - Unknown NLE - No Longer Exists Inaccess - Inaccessible NLR - No Longer in Rated Barrier Decomm - Decommissioned

Project: Fire Damper Inspection, Repair and Testing at the VANYHHCS Manhattan VAMC Rascap LLC dba Acceptance Engineering Contract: 36C24222C0089 and Purchase Order: 630C20166

Result Summary

Pass 71%

Fail 19%

NLE 9%

Inaccessible 1%

NLR 0%

Decommissioned 0%

Project: Fire Damper Inspection, Repair and Testing at the VANYHHCS Manhattan VAMC Rascap LLC dba Acceptance Engineering

DAMPER CONDITION SUMMARY REPORT

Damper Inspection 9.27.22 through 12.15.22

Client Name: VA Manhattan Client Address:423 23rd Street, New York, NY 10010

Total # of Dampers:270 # Failed:52 BRAND SERVICES inspected the below listed fire/smoke damper(s). The inspection(s) performed are intended to determine the compliance of the fire/smoke damper(s). These inspections were performed in accordance with NFPA 80, 105 (2010 editions), NFPA 90A (2012 edition), 101 (2012 edition) and Joint Commission standards LS.02.01.10EP-13 and EC.02.03.05EP-18. The inspections are not intended to constitute a warranty as to the continued operation of the damper, but to verify the operability and compliance at the time of inspection, as dated above.

Marker Label Result Damper ID Floor Location

Repair Data Begins Below

Date

Building 6

Fire Damper

211 Pass FD-1-01 1 Right across double doors near room 1632-B 12/06/2022

255 Pass FD-1-02 1 In hallway across from double doors by room

1632-B 12/06/2022

256 Fail FD-1-03 1 In hallway next to room 1632-B 12/06/2022

257 Pass FD-1-04 1 Inside storage room 1632-B 12/06/2022

212 Pass FD-1-05 1 Inside srorage room 1632-b 12/06/2022

217 Fail FD-1-07 1 Inside room 1609 above doorway 12/06/2022

258 Fail FD-1-07 1 Inside hallway outside bathroom 1610 12/06/2022

261 Fail FD-1-08 1 Inside waiting room by room 1501G 12/07/2022

224 Pass FD-1-08 1 Inside room 1609 12/06/2022

262 Fail FD-1-09 1 Inside waiting area by room 1501G 12/07/2022

Project: Fire Damper Inspection, Repair and Testing at the VANYHHCS Manhattan VAMC Rascap LLC dba Acceptance Engineering

263 Fail FD-1-10 1 Inside office room 1501G 12/07/2022

264 Fail FD-1-11 1 Inside room 1501G 12/07/2022

265 Fail FD-1-12 1 Inside office room 1501I by waiting area behind other offices 12/07/2022

266 Fail FD-1-13 1 Inside office room 1501I behind other offices by waiting area 12/07/2022

267 Fail FD-1-14 1 Inside office room 1501I by waiting area behind other offices 12/07/2022

268 Fail FD-1-15 1 Inside office area by waiting room behind rooms 1501 12/07/2022

269 Fail FD-1-16 1 Inside office room 1501H behind offices by waiting area 12/07/2022

270 Fail FD-1-17 1 Inside office room 1501H behind offices by waiting area 12/07/2022

272 Pass FD-1-19 1 Inside work room/silver door by emergency room/ patient room 12/14/2022

273 Pass FD-1-20 1 Inside work room/silver door next to emergency room/ patient room 12/14/2022

274 Pass FD-1-21 1 Inside office room across from double doors next to bathroom 1520 12/14/2022

275 Pass FD-1-22 1 Inside office room across from double doors next to bathroom 1520 12/14/2022

201 Pass FD-2-01 2 Just after double doors in corridor across from food court 11/22/2022

200 Pass FD-2-02 2 Just after double doors in corridor across from food court 11/22/2022

199 Pass FD-2-03 2 In corridor just after double doors across from food court 11/22/2022

198 Pass FD-2-04 2 Next to man's bathroom 11/22/2022

207 Pass FD-2-05 2 Inside men bathroom 2623 11/22/2022

Project: Fire Damper Inspection, Repair and Testing at the VANYHHCS Manhattan VAMC Rascap LLC dba Acceptance Engineering

254 Fail FD-2-06 2 Inside men's bathroom 2623 11/22/2022

208 Pass FD-2-07 2 Inside room 2621 11/22/2022

Inaccessible

FD-2-08 2 Inside eye exam room p 11/22/2022

206 Pass FD-2-09 2 In hallway next to door way to room 2677 11/22/2022

No Longer Exists

FD-2-09 2 Inside staff bathroom 2675 11/22/2022

210 Pass FD-2-10 2 Inside room 2515 11/23/2022

209 Pass FD-2-11 2 Inside room 2515 11/23/2022

193 Fail FD-4-01 4 Inside OR area above smoke door 11/21/2022

194 Pass FD-4-02 4 Shaft across from dung bell shaft inside sentize room 11/21/2022

215 Pass FD-4-03 4 Inside room 4594P 11/21/2022

216 Fail FD-4-04 4 In Corridor across from room 4562 11/22/2022

22 Pass FD-5-01 5 Transfer next to stairwell 10/04/2022

21 Pass FD-5-02 5 Across elevator machine room 09/27/2022

20 Pass FD-5-03 5 Next to elevator machine room 09/27/2022

19 Pass FD-5-04 5 Inside mechanical room 09/27/2022

17 Pass FD-5-05 5 Inside mechanical room 09/27/2022

23 Fail FD-5-06 5 Inside mechanical room 09/27/2022

39 Pass FD-5-07 5 Inside mechanical area 09/27/2022

Project: Fire Damper Inspection, Repair and Testing at the VANYHHCS Manhattan VAMC Rascap LLC dba Acceptance Engineering

41 Pass FD-5-08 5 Inside mechanical room 09/27/2022

49 Pass FD-5-09 5 Inside mechanical room 09/27/2022

44 Pass FD-5-10 5 Inside mechanical area 09/27/2022

50 Pass FD-5-11 5 Inside mechanical area 09/27/2022

48 Pass FD-5-12 5 Inside mechanical area 09/27/2022

43 Pass FD-5-13 5 Inside mechanical room 10/04/2022

46 Pass FD-5-14 5 Inside mechanical area 10/04/2022

45 Pass FD-5-15 5 Inside mechanical room 10/04/2022

47 Pass FD-5-16 5 Inside mechanical area 10/04/2022

38 Pass FD-5-17 5 Inside mechanical room 10/04/2022

42 Pass FD-5-18 5 Inside mechanical area 10/04/2022

40 Pass FD-5-19 5 Inside mechanical room 10/04/2022

27 Pass FD-5-20 5 In side of mechanical room 10/04/2022

26 Pass FD-5-21 5 In mechanical room 10/04/2022

37 Pass FD-5-22 5 Inside mechanical area 10/04/2022

36 Pass FD-5-23 5 Inside mechanical room 10/04/2022

34 Pass FD-5-24 5 Inside mechanical room 10/04/2022

28 Pass FD-5-25 5 In side mechanical room 10/04/2022

29 Pass FD-5-26 5 In side mechanical room 10/04/2022

Project: Fire Damper Inspection, Repair and Testing at the VANYHHCS Manhattan VAMC Rascap LLC dba Acceptance Engineering

33 Pass FD-5-27 5 Inside mechanical room 10/04/2022

31 Pass FD-5-28 5 Inside mechanical room 10/04/2022

16 Pass FD-5-29 5 Inside mechanical room 10/04/2022

15 Pass FD-5-30 5 Inside mechanical room 11/15/2022

24 Pass FD-5-31 5 Inside mechanical room 10/04/2022

35 Fail FD-5-32 5 Inside mechanical area 10/04/2022

14 Fail FD-5-33 5 Inside mechanical room 10/04/2022

11 Fail FD-5-34 5 Inside mechanical room 10/04/2022

10 Pass FD-5-35 5 Inside mechanical room 10/04/2022

13 Fail FD-5-37 5 Inside mechanical room 10/04/2022

9 Pass FD-5-38 5 Inside mechanical room 10/05/2022

8 Pass FD-5-39 5 Inside mechanical room behind stairs 10/05/2022

7 Pass FD-5-40 5 Inside mechanical space 10/05/2022

32 Pass FD-5-41 5 Inside mechanical area 10/04/2022

30 Fail FD-5-42 5 Inside mechanical area 10/04/2022

51 Pass FD-5-44 5 Inside mechanical space 10/05/2022

52 Fail FD-5-45 5 Inside mechanical room 10/05/2022

190 Pass FD-5-46 5 Inside mechanical space 10/05/2022

62 Pass FD-5-47 5 Inside mechanical area 10/05/2022

Project: Fire Damper Inspection, Repair and Testing at the VANYHHCS Manhattan VAMC Rascap LLC dba Acceptance Engineering

64 Pass FD-5-48 5 Inside mechanical area 10/05/2022

68 Fail FD-5-49 5 Inside mechanical area 10/05/2022

69 Pass FD-5-50 5 Inside mechanical area 10/05/2022

72 Pass FD-5-51 5 Inside mechanical area 10/05/2022

184 Fail FD-5-52 5 Inside electrical room inside mechanical space 10/05/2022

185 Pass FD-5-53 5 Inside electrical room inside mechanical room 10/05/2022

73 Pass FD-5-54 5 Inside mechanical area 10/05/2022

77 Pass FD-5-55 5 Inside mechanical area 10/05/2022

79 Pass FD-5-56 5 Inside mechanical area 10/05/2022

81 Pass FD-5-57 5 Inside mechanical area 10/05/2022

192 Pass FD-5-58 5 Inside mechanical space 10/05/2022

191 Pass FD-5-59 5 Inside mechanical space 10/05/2022

85 Pass FD-5-60 5 Inside mechanical area 10/05/2022

89 Fail FD-5-61 5 Inside mechanical area 10/07/2022

91 Fail FD-5-62 5 Inside mechanical area 11/17/2022

93 Pass FD-5-63 5 Inside mechanical area 10/07/2022

97 Pass FD-5-64 5 Inside mechanical area 10/07/2022

150 Pass FD-5-65 5 Inside mechanical space 10/07/2022

151 Pass FD-5-66 5 Inside mechanical space 10/07/2022

Project: Fire Damper Inspection, Repair and Testing at the VANYHHCS Manhattan VAMC Rascap LLC dba Acceptance Engineering

No Longer Exists

FD-5-67 5 Inside mechanical area 11/14/2022

152 Pass FD-5-67 5 Inside mechanical space 10/07/2022

153 Pass FD-5-68 5 Inside mechanical space 10/07/2022

154 Pass FD-5-69 5 Inside mechanical space 10/07/2022

155 Pass FD-5-70 5 Inside mechanical space 10/07/2022

156 Pass FD-5-71 5 Inside mechanical space 10/07/2022

158 Pass FD-5-72 5 Inside mechanical space 10/07/2022

163 Pass FD-5-73 5 Inside mechanical space 10/07/2022

164 Pass FD-5-74 5 Inside mechanical space 10/07/2022

165 Pass FD-5-75 5 Inside mechanical space 10/07/2022

166 Pass FD-5-76 5 Inside mechanical space 10/07/2022

167 Pass FD-5-77 5 Inside mechanical space 10/07/2022

168 Pass FD-5-78 5 Inside mechanical space 10/07/2022

169 Pass FD-5-79 5 Inside mechanical space 10/07/2022

170 Pass FD-5-80 5 Inside mechanical space 10/07/2022

172 Pass FD-5-81 5 Inside mechanical space 10/07/2022

175 Pass FD-5-82 5 Inside mechanical space 10/07/2022

173 Fail FD-5-83 5 Inside mechanical space 11/14/2022

174 Pass FD-5-84 5 Inside mechanical space 11/14/2022

Project: Fire Damper Inspection, Repair and Testing at the VANYHHCS Manhattan VAMC Rascap LLC dba Acceptance Engineering

176 Pass FD-5-85 5 Inside mechanical room 11/14/2022

177 Pass FD-5-86 5 Inside mechanical room 11/14/2022

178 Pass FD-5-87 5 Inside mechanical room 11/14/2022

179 Pass FD-5-88 5 Inside mechanical room 11/14/2022

56 Pass FD-5-89 5 Inside mechanical area 11/14/2022

59 Pass FD-5-90 5 Inside mechanical area 11/14/2022

57 Pass FD-5-91 5 Inside mechanical area 11/14/2022

251 Pass FD-5-93 5 Inside mechanical space 11/14/2022

159 Pass FD-5-94 5 Inside mechanical space 11/14/2022

160 Pass FD-5-95 5 Inside mechanical space 11/14/2022

162 Pass FD-5-96 5 Inside mechanical space 11/14/2022

161 Pass FD-5-97 5 Inside mechanical space 11/14/2022

187 Pass FD-5-98 5 Inside mechanical room 11/14/2022

188 Pass FD-5-99 5 Inside mechanical space 11/14/2022

189 Pass FD-5-100 5 Inside mechanical space 11/14/2022

183 Pass FD-5-101 5 Inside mechanical room 11/14/2022

182 Pass FD-5-102 5 Inside mechanical room 11/14/2022

180 Fail FD-5-103 5 Inside mechanical room 11/14/2022

181 Fail FD-5-104 5 Inside mechanical room 11/15/2022

Project: Fire Damper Inspection, Repair and Testing at the VANYHHCS Manhattan VAMC Rascap LLC dba Acceptance Engineering

86 Pass FD-5-105 5 Inside mechanical room 11/15/2022

96 Pass FD-5-106 5 Inside mechanical room 11/15/2022

94 Pass FD-5-106 5 Inside mechanical room 11/15/2022

92 Pass FD-5-108 5 Inside mechanical space 11/15/2022

95 Pass FD-5-109 5 Inside mechanical space 11/15/2022

130 Pass FD-5-110 5 Inside mechanical room 11/15/2022

131 Pass FD-5-111 5 Inside mechanical space 11/15/2022

129 Pass FD-5-112 5 Inside mechanical space 11/15/2022

126 Pass FD-5-113 5 Inside mechanical room 11/15/2022

128 Pass FD-5-114 5 Inside mechanical room 11/15/2022

127 Pass FD-5-115 5 Inside mechanical space 11/15/2022

125 Fail FD-5-116 5 Inside mechanical room 11/15/2022

124 Pass FD-5-117 5 Inside mechanical space 11/15/2022

123 Fail FD-5-118 5 Inside mechanical room 11/15/2022

122 Pass FD-5-119 5 Inside mechanical space 11/15/2022

121 Pass FD-5-120 5 Inside mechanical room 11/15/2022

119 Pass FD-5-121 5 Inside mechanical room 11/15/2022

120 Pass FD-5-122 5 Inside mechanical space 11/15/2022

118 Pass FD-5-123 5 Inside mechanical room 11/15/2022

Project: Fire Damper Inspection, Repair and Testing at the VANYHHCS Manhattan VAMC Rascap LLC dba Acceptance Engineering

117 Pass FD-5-124 5 Inside mechanical space 11/15/2022

116 Pass FD-5-125 5 Inside mechanical space 11/15/2022

115 Pass FD-5-126 5 Inside mechanical space 11/15/2022

114 Pass FD-5-127 5 Inside mechanical space 11/15/2022

113 Pass FD-5-128 5 Inside mechanical space 11/15/2022

112 Pass FD-5-129 5 Inside mechanical space 11/15/2022

105 Pass FD-5-130 5 Inside mechanical space 11/15/2022

111 Pass FD-5-131 5 Inside mechanical space 11/15/2022

110 Pass FD-5-132 5 Inside mechanical space 11/15/2022

109 Pass FD-5-133 5 Inside mechanical space 11/15/2022

108 Pass FD-5-134 5 Inside mechanical space 11/15/2022

107 Fail FD-5-135 5 Inside mechanical space 11/15/2022

106 Pass FD-5-136 5 Inside mechanical space 11/15/2022

103 Pass FD-5-137 5 Inside mechanical space 11/15/2022

104 Pass FD-5-138 5 Inside mechanical space 11/15/2022

88 Pass FD-5-139 5 Inside mechanical space 11/15/2022

87 Pass FD-5-140 5 Inside mechanical space 11/16/2022

90 Fail FD-5-141 5 Inside mechanical space going through ceiling 11/16/2022

58 Pass FD-5-142 5 Inside mechanical room 11/17/2022

Project: Fire Damper Inspection, Repair and Testing at the VANYHHCS Manhattan VAMC Rascap LLC dba Acceptance Engineering

252 Pass FD-5-143 5 Mechanical space 11/16/2022

60 Pass FD-5-144 5 Inside mechanical room 11/17/2022

76 Pass FD-5-145 5 Inside mechanical space 11/16/2022

78 Pass FD-5-146 5 Inside mechanical space l 11/16/2022

136 Pass FD-5-147 5 Inside mechanical room 11/16/2022

135 Fail FD-5-148 5 Inside mechanical room 11/17/2022

134 Pass FD-5-149 5 Inside mechanical room 11/16/2022

133 Pass FD-5-150 5 Inside mechanical room 11/16/2022

138 Pass FD-5-153 5 Inside mechanical room 11/16/2022

142 Pass FD-5-154 5 Inside mechanical space 11/16/2022

143 Pass FD-5-155 5 Inside mechanical room 11/16/2022

67 Pass FD-5-156 5 Inside mechanical room 11/16/2022

66 Pass FD-5-157 5 Inside mechanical room 11/16/2022

63 Pass FD-5-158 5 Inside mechanical room 11/16/2022

140 Fail FD-5-159 5 Inside mechanical room 11/22/2022

139 Pass FD-5-160 5 Inside mechanical room 11/16/2022

141 Pass FD-5-161 5 Inside mechanical room 11/16/2022

82 Pass FD-5-162 5 Inside mechanical room 11/16/2022

80 Fail FD-5-163 5 Inside mechanical room 11/22/2022

Project: Fire Damper Inspection, Repair and Testing at the VANYHHCS Manhattan VAMC Rascap LLC dba Acceptance Engineering

75 Pass FD-5-164 5 Inside mechanical room 11/16/2022

74 Pass FD-5-165 5 Inside mechanical room 11/16/2022

253 Fail FD-5-166 5 Inside mechanical space 11/17/2022

83 Pass FD-5-167 5 Inside mechanical space going into ceiling 11/17/2022

84 Pass FD-5-168 5 Inside mechanical room going through ceiling 11/17/2022

55 Fail FD-5-169 5 Inside mechanical area 11/17/2022

12 Fail FF-5-36 5 Inside mechanical room 10/04/2022

195 Pass FD-6-02 6 Inside staff lounge room 6620 11/17/2022

222 Pass FD-6-03 6 Inside room 6522A 11/17/2022

221 Fail FD-6-04 6 Inside clean storage room 6616 11/17/2022

4 Pass FD-6-05 6 Inside clean storage access panel in MRI zone

11/17/2022

6 Pass FD-6-06 6 Inside clean storage access panel in MRI zone

11/17/2022

3 Pass FD-6-06 6 Inside clean storage access panel inside MRI zone 2 11/17/2022

5 Pass FD-6-07 6 Inside clean storage in MRI zone 2 11/17/2022

218 Pass FD-6-08 6 Inside linen chute room 6632 11/21/2022

No Longer Exists

FD-6-2 6 MRI zone 1 hallway across from 6553C01 11/17/2022

229 Fail FD-7-01 7 Inside mechanical space 10/03/2022

228 Fail FD-7-01 7 Inside mechanical space 10/03/2022

Project: Fire Damper Inspection, Repair and Testing at the VANYHHCS Manhattan VAMC Rascap LLC dba Acceptance Engineering

230 Pass FD-7-03 7 Inside mechanical space 10/03/2022

231 Pass FD-7-04 7 Inside mechanical space 10/03/2022

234 Pass FD-7-07 7 Inside mechanical space 10/03/2022

235 Pass FD-7-08 7 Inside mechanical space 10/03/2022

236 Pass FD-7-09 7 Inside mechanical space 10/03/2022

237 Fail FD-7-10 7 Inside mechanical space 10/03/2022

241 Pass FD-7-11 7 Inside mechanical space 10/04/2022

240 Pass FD-7-12 7 Inside mechanical space 10/04/2022

242 Fail FD-7-13 7 Inside mechanical space 10/04/2022

243 Pass FD-7-14 7 Inside mechanical space 10/04/2022

244 Pass FD-7-15 7 Inside mechanical space 10/04/2022

245 Pass FD-7-16 7 Inside mechanical space 10/04/2022

246 Fail FD-7-17 7 Isnide mechanical space 10/04/2022

247 Pass FD-7-18 7 Inside mechanical space 10/04/2022

248 Fail FD-7-19 7 Inside mechanical space 10/04/2022

249 Pass FD-7-20 7 Inide mechanical space 10/04/2022

250 Pass FD-7-21 7 Inside mechanical space 10/04/2022

259 Pass FD-G-01 G Inside hallway on the other side of steam pipe room 12/07/2022

Project: Fire Damper Inspection, Repair and Testing at the VANYHHCS Manhattan VAMC Rascap LLC dba Acceptance Engineering

260 Pass FD-G-02 G Inside hallway on the other side of steam pipe room 12/07/2022

276 Pass FD-G-03 G Above double doors by public elevators 12/14/2022

278 Pass FD-G-05 G Inside washer dryer room G003 12/14/2022

279 Pass FD-G-06 G Inside construction area believe to be made into operation area 12/15/2022

280 Pass FD-G-07 G Inside construction area believe to be a operation area 12/15/2022

Inaccessible

FD-G-10 G Inside linen room G503 12/15/2022

Smoke Damper

53 Fail FD-5-43 5 Inside mechanical area 10/05/2022

54 Fail SD-5-92 5 Inside mechanical area 11/14/2022

Fire+Smoke Damper

Inaccessible

FSD-7-05 7 Inside mechanical space 10/03/2022

Inaccessible

FSD-7-06 7 Inside mechanical space 10/03/2022

277 Fail FSD-G-04 G Next to double doors by room G591 soiled receiving room 12/14/2022

Unknown Damper

No Longer Exists

FD-1-1 1 Above beneficiary travel help center 11/23/2022

214 Fail FD-1-18 1 Inside office room 1521 12/07/2022

271 Pass FD-1-18 1 Inside soiled utility room/storage room next to service elevator 12/07/2022

197 Fail FD-2-09 2 Inside women bathroom 11/23/2022

Project: Fire Damper Inspection, Repair and Testing at the VANYHHCS Manhattan VAMC Rascap LLC dba Acceptance Engineering

Exists

FD-2-5 2 Inside staff bathroom 2675 11/22/2022

No Longer Exists

FD-2-7 2 Inside bathroom 2675 11/22/2022

No Longer Exists

FD-5-1 5 Bridge connecting building 1 and building 6 11/23/2022

No Longer Exists

FD-5-3 5 Bridge connecting building 1 and building 6 11/23/2022

No Longer Exists

FD-5-4 5

Connecting bridge between building 1 and building 6 11/23/2022

No Longer Exists

FD-5-5 5 Bridge connecting building 6 and building 1 11/23/2022

No Longer Exists

FD-5-6 5 Bridge connecting building 6 and building 1 11/23/2022

No Longer Exists

FD-5-49 5 Inside mechanical space 11/14/2022

No Longer Exists

FD-5-56 5 Inside mechanical space 11/14/2022

No Longer Exists

FD-5-73 5 Inside mechanical room 11/14/2022

No Longer Exists

FD-5-80 5 Inside mechanical space 11/16/2022

No Longer Exists

FD-5-104 5 Inside mechanical room 11/16/2022

No Longer Exists

FD-5-116 5 Inside mechanical space 11/16/2022

No Longer Exists

FD-5-117 5 Inside mechanical room 11/16/2022

No Longer Exists

FD-5-119 5 Inside mechanical space 11/15/2022

No Longer Exists

FD-5-121 5 Inside mechanical room 11/16/2022

No Longer Exists

FD-5-122 5 Inside mechanical room 11/16/2022

Project: Fire Damper Inspection, Repair and Testing at the VANYHHCS Manhattan VAMC Rascap LLC dba Acceptance Engineering

Exists

FD-5-124 5 Inside mechanical space 11/16/2022

137 Pass FD-5-151 5 Inside mechanical room 11/16/2022

132 Pass FD-5-152 5 Inside mechanical room 11/16/2022

196 Pass FD-6-01 6 Staff lounge 6620 11/17/2022

No Longer Exists

FD-G-3 6 Inside file room 6522B 11/17/2022

Project: Fire Damper Inspection, Repair and Testing at the VANYHHCS Manhattan VAMC Rascap LLC dba Acceptance Engineering

FAIL/INACCESSIBLE DAMPER DETAIL REPORT

Damper Inspection 9.27.22 through 12.15.22

Client Name: VA Manhattan Client Address: 423 23rd Street, New York, NY 10010

Legend

- Pass

- Pass (Repair)

- Fail

- Decommissioned

- No Longer in Rated Barrier(NLR)

- Inaccessible

- No Longer Exists

Project: Fire Damper Inspection, Repair and Testing at the VANYHHCS Manhattan VAMC Rascap LLC dba Acceptance Engineering

Building 6, 1st Floor(1)

Project: Fire Damper Inspection, Repair and Testing at the VANYHHCS Manhattan VAMC Rascap LLC dba Acceptance Engineering

Damper Details Marker Label:214

Area #: Building 6, 1st Floor(1) Tech: Jason Noyes

Result: Fail Damper ID: FD-1-18

Building: Building 6 Floor: 1

Location: Inside office room 1521 Category: Unknown

AHUdown: No Orientation: Vertical

Link: Unknown Design: Unknown

Damper Manufacturer: Unknown Deficiencies: • Requires duct access door

Comments for the Customer: Requires 14x14 none hinge sticky Duct access door

Date: 12/07/2022

Attachment #487558 Attachment #487559 Attachment #487560 Attachment #487561

Attachment #487562

Attachment #487563

Attachment #0000 a

Attachment #0000 b

Attachment #0000 c

Attachment #0000 c

Project: Fire Damper Inspection, Repair and Testing at the VANYHHCS Manhattan VAMC Rascap LLC dba Acceptance Engineering

Marker Label:270

Area #: Building 6, 1st Floor(1) Tech: Jason Noyes

Result: Fail Damper ID: FD-1-17

Building: Building 6 Floor: 1

Location: Inside office room 1501H behind offices by waiting area

Category: Fire Damper

AHUdown: No Orientation: Horizontal

Motor: N/A Link: Yes

Design: Curtain Damper Manufacturer: Arlan

Deficiencies:

• Damper does not fall

• Damper springs broken/twisted

• Damper wedged/blocked open

• New damper required

Comments for the Customer:

Needs new 35 1/2x5 1/2 horizontal Fire Damper and Requires duct work fabrication to remove damper and install from underneath

Date: 12/07/2022

Attachment #487341

Attachment #487342

Attachment #487343 Attachment #487344

Attachment #0000 c

Project: Fire Damper Inspection, Repair and Testing at the VANYHHCS Manhattan VAMC Rascap LLC dba Acceptance Engineering

Marker Label:269

Area #: Building 6, 1st Floor(1) Tech: Jason Noyes

Result: Fail Damper ID: FD-1-16

Building: Building 6 Floor: 1

Location: Inside office room 1501H behind offices by waiting area

Category: Fire Damper

AHUdown: No Orientation: Horizontal

Link: Yes Design: Curtain

Damper Manufacturer: Arlan Deficiencies:

• Damper does not fall

• Damper springs broken/twisted

• Damper wedged/blocked open

• New damper required

Comments for the Customer:

Needs new 35 1/2x5 1/2 horizontal Fire Damper and Requires duct work fabrication to remove damper and install from underneath

Date: 12/07/2022

Attachment #487335

Attachment #487336 Attachment #487337 Attachment #487338

Attachment #0000 c

Project: Fire Damper Inspection, Repair and Testing at the VANYHHCS Manhattan VAMC Rascap LLC dba Acceptance Engineering

Marker Label:268

Area #: Building 6, 1st Floor(1) Tech: Jason Noyes

Result: Fail Damper ID: FD-1-15

Building: Building 6 Floor: 1

Location: Inside office area by waiting room behind rooms

Category: Fire Damper

AHUdown: No Orientation: Horizontal

Link: Yes Design: Curtain

Damper Manufacturer: Arlan Deficiencies:

• Damper does not fall

• Damper springs broken/twisted

• Damper wedged/blocked open

• New damper required

Comments for the Customer:

Needs new 35 1/2x5 1/2 horizontal Fire Damper and Requires duct work fabrication to remove damper and install from underneath

Date: 12/07/2022

Attachment #487329

Attachment #487330

Attachment #487331

Attachment #487332 Attachment #487333

Project: Fire Damper Inspection, Repair and Testing at the VANYHHCS Manhattan VAMC Rascap LLC dba Acceptance Engineering

Marker Label:267

Area #: Building 6, 1st Floor(1) Tech: Jason Noyes

Result: Fail Damper ID: FD-1-14

Building: Building 6 Floor: 1

Location: Inside office room 1501I by waiting area behind other offices

Category: Fire Damper

AHUdown: No Orientation: Horizontal

Link: Yes Design: Curtain

Damper Manufacturer: Arlan Deficiencies:

• Damper does not fall

• Damper springs broken/twisted

• Damper wedged/blocked open

• New damper required

Comments for the Customer:

Needs new 35 1/2x5 1/2 horizontal Fire Damper and Requires duct work fabrication to remove damper and install from underneath pop pop

Date: 12/07/2022

Attachment #487264 Attachment #487265

Attachment #487266 Attachment #487267

Attachment #0000 c

Project: Fire Damper Inspection, Repair and Testing at the VANYHHCS Manhattan VAMC Rascap LLC dba Acceptance Engineering

Marker Label:266

Area #: Building 6, 1st Floor(1) Tech: Jason Noyes

Result: Fail Damper ID: FD-1-13

Building: Building 6 Floor: 1

Location: Inside office room 1501I behind other offices by waiting area

Category: Fire Damper

AHUdown: No Orientation: Horizontal

Link: Yes Design: Curtain

Damper Manufacturer: Arlan Deficiencies:

• Damper does not fall

• Damper springs broken/twisted

• Damper wedged/blocked open

• New damper required

Comments for the Customer:

Needs new 35 1/2x5 1/2 horizontal Fire Damper and Requires duct work fabrication to remove damper and install from underneath

Date: 12/07/2022

Attachment #487256 Attachment #487257 Attachment #487258 Attachment #487259

Attachment #0000 c

Project: Fire Damper Inspection, Repair and Testing at the VANYHHCS Manhattan VAMC Rascap LLC dba Acceptance Engineering

Marker Label:265

Area #: Building 6, 1st Floor(1) Tech: Jason Noyes

Result: Fail Damper ID: FD-1-12

Building: Building 6 Floor: 1

Location: Inside office room 1501I by waiting area behind other offices

Category: Fire Damper

AHUdown: Yes Orientation: Horizontal

Link: Yes Design: Curtain

Damper Manufacturer: Arlan Deficiencies:

• Damper does not fall

• Damper springs broken/twisted

• Damper wedged/blocked open

• New damper required

Comments for the Customer:

Needs new 36x6 horizontal Fire Damper and Requires duct work fabrication to remove damper and install from underneath

Date: 12/07/2022

Attachment #487252

Attachment #0000 a

Attachment #0000 b

Attachment #0000 c

Attachment #0000 c

Project: Fire Damper Inspection, Repair and Testing at the VANYHHCS Manhattan VAMC Rascap LLC dba Acceptance Engineering

Marker Label:264

Area #: Building 6, 1st Floor(1) Tech: Jason Noyes

Result: Fail Damper ID: FD-1-11

Building: Building 6 Floor: 1

Location: Inside room 1501G Category: Fire Damper

AHUdown: No Orientation: Horizontal

Motor: NO ID LABELS Link: Yes

Design: Curtain Damper Manufacturer: No ID Labels

Deficiencies:

• Damper does not fall

• Damper wedged/blocked open

• New damper required

Comments for the Customer:

Needs new 36x6 horizontal Fire Damper and Requires duct work fabrication to remove damper and install from underneath

Date: 12/07/2022

Attachment #487240 Attachment #487241

Attachment #487242

Attachment #487243

Attachment #0000 c

Project: Fire Damper Inspection, Repair and Testing at the VANYHHCS Manhattan VAMC Rascap LLC dba Acceptance Engineering

Marker Label:263

Area #: Building 6, 1st Floor(1) Tech: Jason Noyes

Result: Fail Damper ID: FD-1-10

Building: Building 6 Floor: 1

Location: Inside office room 1501G Category: Fire Damper

AHUdown: No Orientation: Horizontal

Link: Yes Design: Curtain

Damper Manufacturer: Arlan Deficiencies:

• Damper does not fall

• Damper springs broken/twisted

• Damper wedged/blocked open

• New damper required

Comments for the Customer:

Needs new 36x6 horizontal Fire Damper and Requires duct work fabrication to remove damper and install from underneath

Date: 12/07/2022

Attachment #487230 Attachment #487231 Attachment #487232 Attachment #487233

Attachment #0000 c

Project: Fire Damper Inspection, Repair and Testing at the VANYHHCS Manhattan VAMC Rascap LLC dba Acceptance Engineering

Marker Label:262

Area #: Building 6, 1st Floor(1) Tech: Jason Noyes

Result: Fail Damper ID: FD-1-09

Building: Building 6 Floor: 1

Location: Inside waiting area by room 1501G Category: Fire Damper

AHUdown: No Orientation: Horizontal

Link: Yes Design: Curtain

Damper Manufacturer: Arlan Deficiencies:

• Damper does not fall

• Damper wedged/blocked open

• New damper required

Comments for the Customer:

Needs new 36x6 horizontal Fire Damper and Requires duct work fabrication to remove damper and install from underneath

Date: 12/07/2022

Attachment #487179

Attachment #487180

Attachment #487181 Attachment #487182 Attachment #487183

Attachment #487184

Attachment #0000 a

Attachment #0000 b

Attachment #0000 c

Attachment #0000 c

Project: Fire Damper Inspection, Repair and Testing at the VANYHHCS Manhattan VAMC Rascap LLC dba Acceptance Engineering

Marker Label:261

Area #: Building 6, 1st Floor(1) Tech: Jason Noyes

Result: Fail Damper ID: FD-1-08

Building: Building 6 Floor: 1

Location: Inside waiting room by room 1501G Category: Fire Damper

AHUdown: No Orientation: Horizontal

Link: Yes Design: Curtain

Damper Manufacturer: Arlan Deficiencies:

• Damper does not fall

• Damper springs broken/twisted

• New damper required

Comments for the Customer:

Needs new 36x6 horizontal Fire Damper and Requires duct work fabrication to remove damper and install from underneath

Date: 12/07/2022

Attachment #487163 Attachment #487164 Attachment #487166 Attachment #487168 Attachment #487169

Project: Fire Damper Inspection, Repair and Testing at the VANYHHCS Manhattan VAMC Rascap LLC dba Acceptance Engineering

Marker Label:217

Area #: Building 6, 1st Floor(1) Tech: Jason Noyes

Result: Fail Damper ID: FD-1-07

Building: Building 6 Floor: 1

Location: Inside room 1609 above doorway

Category: Fire Damper

AHUdown: No Orientation: Horizontal

Link: Yes Design: Curtain

Damper Manufacturer: Arlan Access Door Size: 14"x14"

Deficiencies: • Requires duct access door

Comments for the Customer:

Requires 16x16 duct access door to be able to reach safely

Date: 12/06/2022

Attachment #486681 Attachment #486682

Attachment #486683

Attachment #486684

Attachment #0000 c

Project: Fire Damper Inspection, Repair and Testing at the VANYHHCS Manhattan VAMC Rascap LLC dba Acceptance Engineering

Marker Label:258

Area #: Building 6, 1st Floor(1) Tech: Jason Noyes

Result: Fail Damper ID: FD-1-07

Building: Building 6 Floor: 1

Location: Inside hallway outside bathroom 1610 Category: Fire Damper

AHUdown: No Orientation: Horizontal

Link: Unknown Design: Unknown

Damper Manufacturer: Unknown Deficiencies: • Requires duct access door

Comments for the Customer: Requires 14x14 or access patch to access damper

Date: 12/06/2022

Attachment #486537 Attachment #486538 Attachment #486539

Attachment #0000 a

Attachment #0000 c

Project: Fire Damper Inspection, Repair and Testing at the VANYHHCS Manhattan VAMC Rascap LLC dba Acceptance Engineering

Marker Label:256

Area #: Building 6, 1st Floor(1) Tech: Jason Noyes

Result: Fail Damper ID: FD-1-03

Building: Building 6 Floor: 1

Location: In hallway next to room 1632-B Category: Fire Damper

AHUdown: No Orientation: Vertical

Link: Unknown Design: Unknown

Damper Manufacturer: Unknown Deficiencies: • Requires duct access door

Comments for the Customer:

Requires a 14x14 sticky none hinge duct access door and it's in a Tight area

Date: 12/06/2022

Attachment #486279 Attachment #486280 Attachment #486281

Attachment #0000 a

Attachment #0000 c

Project: Fire Damper Inspection, Repair and Testing at the VANYHHCS Manhattan VAMC Rascap LLC dba Acceptance Engineering

Building 6, 2nd Floor(2)

Rascap LLC dba Acceptance Engineering

Marker Label:197

Area #: Building 6, 2nd Floor(2) Tech: Jason Noyes

Result: Fail Damper ID: FD-2-09

Building: Building 6 Floor: 2

Location: Inside women bathroom Category: Unknown

AHUdown: No Orientation: Vertical

Link: Unknown Design: Unknown

Damper Manufacturer: Unknown Access Door Size: 12"x12"

Deficiencies: • Requires duct access door

Comments for the Customer:

Requires a 14x14 sticky none hinge Very hard spot to get to

Date: 11/23/2022

Attachment #480434 Attachment #480435 Attachment #480436

Attachment #480437

Attachment #480438

Attachment #480439

Attachment #0000 a

Attachment #0000 b

Attachment #0000 c

Attachment #0000 c

Project: Fire Damper Inspection, Repair and Testing at the VANYHHCS Manhattan VAMC Rascap LLC dba Acceptance Engineering

Marker Label:202

Area #: Building 6, 2nd Floor(2) Tech: Jason Noyes

Result: Inaccessible Damper ID: FD-2-08

Building: Building 6 Floor: 2

Location: Inside eye exam room p Category: Fire Damper

AHUdown: Yes Orientation: Vertical

Link: Yes Design: Curtain

Damper Manufacturer: Arlan Comments for the Customer: Requires AHU shut down

Date: 11/22/2022

Attachment #479823

Attachment #479824

Attachment #0000 a

Attachment #0000 b

Attachment #0000 c

Project: Fire Damper Inspection, Repair and Testing at the VANYHHCS Manhattan VAMC Rascap LLC dba Acceptance Engineering

Marker Label:254

Area #: Building 6, 2nd Floor(2) Tech: Jason Noyes

Result: Fail Damper ID: FD-2-06

Building: Building 6 Floor: 2

Location: Inside men's bathroom 2623 Category: Fire Damper

AHUdown: No Orientation: Vertical

Link: Yes Design: Curtain

Damper Manufacturer: Arlan Deficiencies: • Requires duct access door

Comments for the Customer:

Requires a 12x12 duct access door and is Very high up and tight spot

Date: 11/22/2022

Attachment #479656 Attachment #479657 Attachment #479658

Attachment #0000 a

Attachment #0000 c

Project: Fire Damper Inspection, Repair and Testing at the VANYHHCS Manhattan VAMC Rascap LLC dba Acceptance Engineering

Building 6, 4th Floor(4)

Rascap LLC dba Acceptance Engineering

Marker Label:216

Area #: Building 6, 4th Floor(4) Tech: Jason Noyes

Result: Fail Damper ID: FD-4-04

Building: Building 6 Floor: 4

Location: In Corridor across from room

Category: Fire Damper

AHUdown: No Orientation: Vertical

Link: Unknown Design: Unknown

Damper Manufacturer: Unknown Damper Size (i.e. 24"x12"): 22x14

Access Door Size if not listed: Tight space Deficiencies: • Requires duct access door

Comments for the Customer: Requires access door Date: 11/22/2022

Attachment #478775 Attachment #478776

Attachment #479489 Attachment #479490 Attachment #479491

Project: Fire Damper Inspection, Repair and Testing at the VANYHHCS Manhattan VAMC Rascap LLC dba Acceptance Engineering

Marker Label:193

Area #: Building 6, 4th Floor(4) Tech: Jason Noyes

Result: Fail Damper ID: FD-4-01

Building: Building 6 Floor: 4

Location: Inside OR area above smoke door

Category: Fire Damper

AHUdown: No Orientation: Vertical

Link: Unknown Design: Unknown

Damper Manufacturer: Unknown Damper Size (i.e. 24"x12"): 6x14

Deficiencies: • Requires duct access door Comments for the Customer:

Requires a 12 x12 duct access door

Date: 11/21/2022

Attachment #478707 Attachment #478708

Attachment #478709

Attachment #0000 a

Attachment #0000 c

Project: Fire Damper Inspection, Repair and Testing at the VANYHHCS Manhattan VAMC Rascap LLC dba Acceptance Engineering

Building 6, 5th Floor(5)

Rascap LLC dba Acceptance Engineering

Marker Label:80

Area #: Building 6, 5th Floor(5) Tech: Jason Noyes

Result: Fail Damper ID: FD-5-163

Building: Building 6 Floor: 5

Location: Inside mechanical room Category: Fire Damper

AHUdown: No Orientation: Horizontal

Link: Yes Design: Curtain

Damper Manufacturer: Arlan Damper Size (i.e.

24"x12"): 10x8

Deficiencies:

• Damper springs broken/twisted

• New damper required

Comments for the Customer:

Damper spring is twisted,requires new 10x10 horizontal damper

Date: 11/22/2022

Attachment #479576 Attachment #479577

Attachment #479578 Attachment #479579 Attachment #479580

Project: Fire Damper Inspection, Repair and Testing at the VANYHHCS Manhattan VAMC Rascap LLC dba Acceptance Engineering

Marker Label:89

Area #: Building 6, 5th Floor(5) Tech: Jason Noyes

Result: Fail Damper ID: FD-5-61

Building: Building 6 Floor: 5

Location: Inside mechanical area Category: Fire Damper

AHUdown: No Orientation: Horizontal

Link: Yes Design: Curtain

Damper Manufacturer: Arlan Damper Size (i.e. 24"x12"): 12x10

Access Door Size: 12"x12" Deficiencies: • No link present

• Requires new link

Date: 10/07/2022

Attachment #454279 Attachment #454280 Attachment #454281 Attachment #454282 Attachment #454283

Project: Fire Damper Inspection, Repair and Testing at the VANYHHCS Manhattan VAMC Rascap LLC dba Acceptance Engineering

Marker Label:35

Area #: Building 6, 5th Floor(5) Tech: Jason Noyes

Result: Fail Damper ID: FD-5-32

Building: Building 6 Floor: 5

Location: Inside mechanical area Category: Fire Damper

AHUdown: No Orientation: Horizontal

Link: Yes Design: Curtain

Damper Manufacturer: Arlan Damper Size (i.e. 24"x12"): 28x22

Deficiencies: • Requires duct access door Date: 10/04/2022

Attachment #451230 Attachment #451231 Attachment #451232 Attachment #451233

Attachment #0000 c

Project: Fire Damper Inspection, Repair and Testing at the VANYHHCS Manhattan VAMC Rascap LLC dba Acceptance Engineering

Marker Label:11

Area #: Building 6, 5th Floor(5) Tech: Jason Noyes

Result: Fail Damper ID: FD-5-34

Building: Building 6 Floor: 5

Location: Inside mechanical room Category: Fire Damper

AHUdown: No Orientation: Horizontal

Link: Yes Design: Curtain

Damper Manufacturer: Arlan Damper Size (i.e. 24"x12"): 31x32

Deficiencies: • Damper springs broken/twisted

• New damper required

Date: 10/04/2022

Attachment #451312 Attachment #451314

Attachment #451315 Attachment #451316

Attachment #0000 c

Project: Fire Damper Inspection, Repair and Testing at the VANYHHCS Manhattan VAMC Rascap LLC dba Acceptance Engineering

Marker Label:12

Area #: Building 6, 5th Floor(5) Tech: Jason Noyes

Result: Fail Damper ID: FF-5-36

Building: Building 6 Floor: 5

Location: Inside mechanical room Category: Fire Damper

AHUdown: No Orientation: Vertical

Motor: N/A Link: Unknown

Design: Unknown Damper Manufacturer: Unknown

Damper Size (i.e. 24"x12"): 31x32 Deficiencies: • Requires duct access door

Date: 10/04/2022

Attachment #451351 Attachment #451352

Attachment #451353

Attachment #0000 a

Attachment #0000 c

Project: Fire Damper Inspection, Repair and Testing at the VANYHHCS Manhattan VAMC Rascap LLC dba Acceptance Engineering

Marker Label:13

Area #: Building 6, 5th Floor(5) Tech: Jason Noyes

Result: Fail Damper ID: FD-5-37

Building: Building 6 Floor: 5

Location: Inside mechanical room Category: Fire Damper

AHUdown: No Orientation: Vertical

Motor: N/A Link: Unknown

Design: Unknown Damper Manufacturer: Unknown

Damper Size (i.e. 24"x12"): 36x32 Deficiencies: • Requires duct access door

Date: 10/04/2022

Attachment #451358 Attachment #451359 Attachment #451361

Attachment #0000 a

Attachment #0000 c

Project: Fire Damper Inspection, Repair and Testing at the VANYHHCS Manhattan VAMC Rascap LLC dba Acceptance Engineering

Marker Label:30

Area #: Building 6, 5th Floor(5) Tech: Jason Noyes

Result: Fail Damper ID: FD-5-42

Building: Building 6 Floor: 5

Location: Inside mechanical area Category: Fire Damper

AHUdown: No Orientation: Horizontal

Link: Yes Design: Curtain

Damper Manufacturer: Arlan Damper Size (i.e. 24"x12"): 32x19

Deficiencies: • Requires duct access door Date: 10/04/2022

Attachment #451471 Attachment #451472

Attachment #451473

Attachment #0000 a

Attachment #0000 c

Project: Fire Damper Inspection, Repair and Testing at the VANYHHCS Manhattan VAMC Rascap LLC dba Acceptance Engineering

Marker Label:14

Area #: Building 6, 5th Floor(5) Tech: Jason Noyes

Result: Fail Damper ID: FD-5-33

Building: Building 6 Floor: 5

Location: Inside mechanical room Category: Fire Damper

AHUdown: No Orientation: Horizontal

Link: Yes Design: Curtain

Damper Manufacturer: Arlan Damper Size (i.e. 24"x12"): 14x6

Deficiencies:

• Damper does not fall

• New damper required

• Damper improperly installed

Date: 10/04/2022

Attachment #451497 Attachment #451499

Attachment #451501

Attachment #451502 Attachment #451503

Attachment #451504

Attachment #0000 a

Attachment #0000 b

Attachment #0000 c

Attachment #0000 c

Project: Fire Damper Inspection, Repair and Testing at the VANYHHCS Manhattan VAMC Rascap LLC dba Acceptance Engineering

Marker Label:53

Area #: Building 6, 5th Floor(5) Tech: Jason Noyes

Result: Fail Damper ID: FD-5-43

Building: Building 6 Floor: 5

Location: Inside mechanical area Category: Smoke Damper

AHUdown: No Orientation: Vertical

Motor: N/A Link: Unknown

Design: Unknown Damper Manufacturer: Unknown

Deficiencies: • Requires duct access door Date: 10/05/2022

Attachment #451919 Attachment #451920 Attachment #451921 Attachment #451922

Attachment #0000 c

Project: Fire Damper Inspection, Repair and Testing at the VANYHHCS Manhattan VAMC Rascap LLC dba Acceptance Engineering

Marker Label:52

Area #: Building 6, 5th Floor(5) Tech: Jason Noyes

Result: Fail Damper ID: FD-5-45

Building: Building 6 Floor: 5

Location: Inside mechanical room Category: Fire Damper

AHUdown: No Orientation: Horizontal

Motor: N/A Link: Yes

Design: Curtain Damper Manufacturer: Arlan

Damper Size (i.e. 24"x12"): 16x12 Access Door Size: 10"x10"

Deficiencies: • Requires duct access door Date: 10/05/2022

Attachment #451970 Attachment #451971 Attachment #451972 Attachment #451973 Attachment #451974

Project: Fire Damper Inspection, Repair and Testing at the VANYHHCS Manhattan VAMC Rascap LLC dba Acceptance Engineering

Marker Label:68

Area #: Building 6, 5th Floor(5) Tech: Jason Noyes

Result: Fail Damper ID: FD-5-49

Building: Building 6 Floor: 5

Location: Inside mechanical area Category: Fire Damper

AHUdown: Yes Orientation: Horizontal

Link: Unknown Design: Unknown

Damper Manufacturer: Unknown Damper Size (i.e. 24"x12"): 18x16

Access Door Size: 12"x12" Deficiencies: • Requires duct access door

Date: 10/05/2022

Attachment #452426 Attachment #452428 Attachment #452430 Attachment #452432 Attachment #452433

Project: Fire Damper Inspection, Repair and Testing at the VANYHHCS Manhattan VAMC Rascap LLC dba Acceptance Engineering

Marker Label:184

Area #: Building 6, 5th Floor(5) Tech: Jason Noyes

Result: Fail Damper ID: FD-5-52

Building: Building 6 Floor: 5

Location: Inside electrical room inside mechanical space

Category: Fire Damper

AHUdown: No Orientation: Vertical

Design: Unknown Damper Manufacturer: Unknown

Deficiencies: • No damper present

• New damper required

Date: 10/05/2022

Attachment #452455 Attachment #452456 Attachment #452457 Attachment #452458 Attachment #452459

Attachment #452460

Attachment #0000 a

Attachment #0000 b

Attachment #0000 c

Attachment #0000 c

Project: Fire Damper Inspection, Repair and Testing at the VANYHHCS Manhattan VAMC Rascap LLC dba Acceptance Engineering

Marker Label:173

Area #: Building 6, 5th Floor(5) Tech: Jason Noyes

Result: Fail Damper ID: FD-5-83

Building: Building 6 Floor: 5

Location: Inside mechanical space

Category: Fire Damper

AHUdown: No Orientation: Horizontal

Link: Yes Design: Curtain

Damper Manufacturer: Arlan

Damper Size (i.e.

24"x12"): 10x14

Deficiencies:

• Damper does not fall

• Damper springs broken/twisted

• New damper required

Comments for the Customer:

Horizontal Dynamic damper will not close springs are rusted requires new one and I can't get a correct measurement because it's in the ground

Date: 11/14/2022

Attachment #475156 Attachment #475157

Attachment #475158

Attachment #475159

Attachment #0000 c

Project: Fire Damper Inspection, Repair and Testing at the VANYHHCS Manhattan VAMC Rascap LLC dba Acceptance Engineering

Marker Label:140

Area #: Building 6, 5th Floor(5) Tech: Jason Noyes

Result: Fail Damper ID: FD-5-159

Building: Building 6 Floor: 5

Location: Inside mechanical room Category: Fire Damper

AHUdown: No Orientation: Horizontal

Link: Yes Design: Curtain

Damper Manufacturer: Arlan Damper Size (i.e.

24"x12"): 18x6

Deficiencies:

• Damper does not fall

• Damper springs broken/twisted

Comments for the Customer:

Damper will not close, require 12×6 horizontal damper

Date: 11/22/2022

Attachment #479570 Attachment #479571 Attachment #479572

Attachment #479573 Attachment #479574

Attachment #479575

Attachment #0000 a

Attachment #0000 b

Attachment #0000 c

Attachment #0000 c

Project: Fire Damper Inspection, Repair and Testing at the VANYHHCS Manhattan VAMC Rascap LLC dba Acceptance Engineering

Marker Label:54

Area #: Building 6, 5th Floor(5) Tech: Jason Noyes

Result: Fail Damper ID: SD-5-92

Building: Building 6 Floor: 5

Location: Inside mechanical area Category: Smoke Damper

AHUdown: No Orientation: Vertical

Motor: Air Actuated Link: No

Design: Blade Damper Manufacturer: No ID Labels

Access Door Size: 14"x14" Deficiencies: • Requires duct access door

• No air to actuator

Comments for the Customer: There is no air to actuator Date: 11/14/2022

Attachment #475268 Attachment #475269 Attachment #475270 Attachment #475271 Attachment #475272

Project: Fire Damper Inspection, Repair and Testing at the VANYHHCS Manhattan VAMC Rascap LLC dba Acceptance Engineering

Marker Label:180

Area #: Building 6, 5th Floor(5) Tech: Jason Noyes

Result: Fail Damper ID: FD-5-103

Building: Building 6 Floor: 5

Location: Inside mechanical room Category: Fire Damper

AHUdown: No Orientation: Horizontal

Link: Yes Design: Curtain

Damper Manufacturer: Arlan Deficiencies: • Requires duct access door

Comments for the Customer: Requires access door 16x16 Date: 11/14/2022

Attachment #475559 Attachment #475560

Attachment #475561

Attachment #475562

Attachment #475563

Attachment #475564

Attachment #0000 a

Attachment #0000 b

Attachment #0000 c

Attachment #0000 c

Project: Fire Damper Inspection, Repair and Testing at the VANYHHCS Manhattan VAMC Rascap LLC dba Acceptance Engineering

Marker Label:181

Area #: Building 6, 5th Floor(5) Tech: Jason Noyes

Result: Fail Damper ID: FD-5-104

Building: Building 6 Floor: 5

Location: Inside mechanical room Category: Fire Damper

AHUdown: No Orientation: Horizontal

Link: Yes Design: Curtain

Damper Manufacturer: Arlan Damper Size (i.e. 24"x12"): 12x12

Deficiencies: • Requires duct access door

Comments for the Customer:

Requires duct access door 12x12 sticky none hinge

Date: 11/15/2022

Attachment #475791 Attachment #475792

Attachment #475793 Attachment #475794 Attachment #475795

Project: Fire Damper Inspection, Repair and Testing at the VANYHHCS Manhattan VAMC Rascap LLC dba Acceptance Engineering

Marker Label:123

Area #: Building 6, 5th Floor(5) Tech: Jason Noyes

Result: Fail Damper ID: FD-5-118

Building: Building 6 Floor: 5

Location: Inside mechanical room Category: Fire Damper

AHUdown: Yes Orientation: Horizontal

Link: Yes Design: Curtain

Damper Manufacturer: Arlan Damper Size (i.e.

24"x12"): 18x7

Deficiencies:

• Damper springs broken/twisted

• New damper required

Comments for the Customer:

Damper spring are twister and rusted won't close needs a new horizontal fire damper

Date: 11/15/2022

Attachment #475908

Attachment #475909

Attachment #475910 Attachment #475911

Attachment #475912

Attachment #475913 Attachment #0000 a

Attachment #0000 b

Attachment #0000 c

Attachment #0000 c

Project: Fire Damper Inspection, Repair and Testing at the VANYHHCS Manhattan VAMC Rascap LLC dba Acceptance Engineering

Marker Label:125

Area #: Building 6, 5th Floor(5) Tech: Jason Noyes

Result: Fail Damper ID: FD-5-116

Building: Building 6 Floor: 5

Location: Inside mechanical room Category: Fire Damper

AHUdown: Yes Orientation: Horizontal

Link: Yes Design: Curtain

Damper Manufacturer: Arlan Damper Size (i.e.

24"x12"): 18x7

Deficiencies:

• Damper springs broken/twisted

• New damper required

Comments for the Customer:

Damper spring are twister and rusted won't close needs a new horizontal fire damper

Date: 11/15/2022

Attachment #475917

Attachment #475920

Attachment #475921

Attachment #475922

Attachment #475923

Attachment #475924

Attachment #0000 a

Attachment #0000 b

Attachment #0000 c

Attachment #0000 c

Project: Fire Damper Inspection, Repair and Testing at the VANYHHCS Manhattan VAMC Rascap LLC dba Acceptance Engineering

Marker Label:107

Area #: Building 6, 5th Floor(5)

Tech: Jason Noyes

Result: Fail Damper ID: FD-5-135

Building: Building 6 Floor: 5

Location: Inside mechanical space

Category: Fire Damper

AHUdown: No Orientation: Horizontal

Link: Yes Design: Curtain

Damper Manufacturer: Arlan Damper Size (i.e.

24"x12"): 12x6

Deficiencies:

• Damper does not fall

• New damper required

Comments for the Customer:

Completely in floor cant measure wont close and no link and requires new horizontal fire damper

Date: 11/15/2022

Attachment #476225 Attachment #476226 Attachment #476227 Attachment #476228

Attachment #0000 c

Project: Fire Damper Inspection, Repair and Testing at the VANYHHCS Manhattan VAMC Rascap LLC dba Acceptance Engineering

Marker Label:90

Area #: Building 6, 5th Floor(5) Tech: Jason Noyes

Result: Fail Damper ID: FD-5-141

Building: Building 6 Floor: 5

Location: Inside mechanical space going through ceiling

Category: Fire Damper

AHUdown: No Orientation: Horizontal

Link: N/A Design: Curtain

Damper Manufacturer: Arlan Damper Size (i.e.

24"x12"): 28x28

Deficiencies: • No damper present

• New damper required

Comments for the Customer:

No damper present in shaft. Needs 28x28 horizontal curtain damper

Date: 11/16/2022

Attachment #476862 Attachment #476863 Attachment #476864 Attachment #476866

Attachment #0000 c

Project: Fire Damper Inspection, Repair and Testing at the VANYHHCS Manhattan VAMC Rascap LLC dba Acceptance Engineering

Marker Label:253

Area #: Building 6, 5th Floor(5) Tech: Jason Noyes

Result: Fail Damper ID: FD-5-166

Building: Building 6 Floor: 5

Location: Inside mechanical space Category: Fire Damper

AHUdown: No Orientation: Horizontal

Link: Unknown Design: Unknown

Damper Manufacturer: Unknown Deficiencies:

• No damper present

• New damper required

Comments for the Customer:

Requires A horizontal fire damper 28x28 may need to break concrete to make the Duct square again

Date: 11/17/2022

Attachment #477697 Attachment #477698 Attachment #477699 Attachment #477700

Attachment #0000 c

Project: Fire Damper Inspection, Repair and Testing at the VANYHHCS Manhattan VAMC Rascap LLC dba Acceptance Engineering

Marker Label:135

Area #: Building 6, 5th Floor(5) Tech: Jason Noyes

Result: Fail Damper ID: FD-5-148

Building: Building 6 Floor: 5

Location: Inside mechanical room Category: Fire Damper

AHUdown: No Orientation: Horizontal

Link: Yes Design: Curtain

Damper Manufacturer: Arlan Damper Size (i.e. 24"x12"): 12"×3.5"

Deficiencies: • Screw in travel path Date: 11/17/2022

Attachment #477720 Attachment #477721

Attachment #477723

Attachment #0000 a

Attachment #0000 c

Project: Fire Damper Inspection, Repair and Testing at the VANYHHCS Manhattan VAMC Rascap LLC dba Acceptance Engineering

Marker Label:91

Area #: Building 6, 5th Floor(5) Tech: Jason Noyes

Result: Fail Damper ID: FD-5-62

Building: Building 6 Floor: 5

Location: Inside mechanical area Category: Fire Damper

AHUdown: No Orientation: Horizontal

Link: Yes Design: Curtain

Damper Manufacturer: Arlan Damper Size (i.e. 24"x12"): 12x4

Access Door Size: 12"x12" Deficiencies:

• Damper does not fall

• Damper springs broken/twisted

Comments for the Customer:

Damper in floors out of brand scope

Date: 11/17/2022

Attachment #477728 Attachment #477729 Attachment #477730 Attachment #477731

Attachment #477732

Attachment #477733 Attachment #477734

Attachment #0000 a

Attachment #0000 b

Attachment #0000 c

Project: Fire Damper Inspection, Repair and Testing at the VANYHHCS Manhattan VAMC Rascap LLC dba Acceptance Engineering

Marker Label:55

Area #: Building 6, 5th Floor(5) Tech: Jason Noyes

Result: Fail Damper ID: FD-5-169

Building: Building 6 Floor: 5

Location: Inside mechanical area Category: Fire Damper

AHUdown: No Orientation: Horizontal

Link: Unknown Design: Unknown

Damper Manufacturer: Unknown Damper Size (i.e.

24"x12"): 12x12

Access Door Size: 12"x12" Deficiencies:

• No damper present

• New damper required

Comments…