This is a Damper Snapshot Report and detailed inspection report documenting fire damper, smoke damper, and fire/smoke damper conditions at VA Manhattan Building 6 (423 23rd Street, New York, NY 10010) conducted between September 27, 2022 and December 15, 2022. The inspection was performed by Rascap LLC dba Acceptance Engineering under Contract 36C24222C0089 and Purchase Order 630C20166. A total of 270 dampers were inspected across multiple floors (Basement, Floors 1-7) with results showing 191 passed (71%), 52 failed (19%), 23 with no longer exists status (9%), and 4 inaccessible (1%). Inspections were conducted in accordance with NFPA 80, 105 (2010 editions), NFPA 90A (2012 edition), 101 (2012 edition), and Joint Commission standards LS.02.01.10EP-13 and EC.02.03.05EP-18.
The failed dampers require various corrective actions including replacement of dampers with broken/twisted springs, installation of duct access doors to enable proper inspection and testing, repair of dampers that do not fall or are wedged/blocked open, and installation of new links where missing or damaged. Specific deficiencies include dampers manufactured by Arlan, Ruskin, Lloyd, and others with issues such as broken springs, improper installation, missing actuator air supply, and inaccessibility due to obstructions. Floor 1 had the highest concentration of failures with 14 failed dampers, primarily requiring horizontal fire damper replacements ranging from 35.5x5.5 inches to 36x6 inches with associated ductwork fabrication. Floor 5 (mechanical areas) contained 24 failed dampers requiring access doors and/or replacements. The detailed deficiency report provides specific marker labels, damper IDs, locations, and required corrective actions for each failed unit.
View the file
Other files
Show all 14
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
DAMPER SNAPSHOT REPORT
Manhattan VA Bldg 6 Damper Inspection 9.27.22 through 12.15.22
Client Name: VA Manhattan Client Address:423 23rd Street, New York, NY 10010
Inspection Summary
Building 6 Floor Fire Smoke Fire/ Smoke CRD Unk Pass Fail NLE Inaccess NLR Decomm Total
G 7 0 1 0 0 6 1 0 1 0 0 8
1 22 0 0 0 3 10 14 1 0 0 0 25
2 12 0 0 0 3 9 2 3 1 0 0 15
4 4 0 0 0 0 2 2 0 0 0 0 4
5 166 2 0 0 18 143 26 17 0 0 0 186
6 9 0 0 0 2 8 1 2 0 0 0 11
7 19 0 2 0 0 13 6 0 2 0 0 21
SubTotal 239 2 3 0 26 191 52 23 4 0 0 270
GrandTotal 239 2 3 0 26 191 52 23 4 0 0 270
CRD - Ceiling Radiation Damper Unk - Unknown NLE - No Longer Exists Inaccess - Inaccessible NLR - No Longer in Rated Barrier Decomm - Decommissioned
Project: Fire Damper Inspection, Repair and Testing at the VANYHHCS Manhattan VAMC Rascap LLC dba Acceptance Engineering Contract: 36C24222C0089 and Purchase Order: 630C20166
Result Summary
Pass 71%
Fail 19%
NLE 9%
Inaccessible 1%
NLR 0%
Decommissioned 0%
Project: Fire Damper Inspection, Repair and Testing at the VANYHHCS Manhattan VAMC Rascap LLC dba Acceptance Engineering
DAMPER CONDITION SUMMARY REPORT
Damper Inspection 9.27.22 through 12.15.22
Client Name: VA Manhattan Client Address:423 23rd Street, New York, NY 10010
Total # of Dampers:270 # Failed:52 BRAND SERVICES inspected the below listed fire/smoke damper(s). The inspection(s) performed are intended to determine the compliance of the fire/smoke damper(s). These inspections were performed in accordance with NFPA 80, 105 (2010 editions), NFPA 90A (2012 edition), 101 (2012 edition) and Joint Commission standards LS.02.01.10EP-13 and EC.02.03.05EP-18. The inspections are not intended to constitute a warranty as to the continued operation of the damper, but to verify the operability and compliance at the time of inspection, as dated above.
Marker Label Result Damper ID Floor Location
Repair Data Begins Below
Date
Building 6
Fire Damper
211 Pass FD-1-01 1 Right across double doors near room 1632-B 12/06/2022
255 Pass FD-1-02 1 In hallway across from double doors by room
1632-B 12/06/2022
256 Fail FD-1-03 1 In hallway next to room 1632-B 12/06/2022
257 Pass FD-1-04 1 Inside storage room 1632-B 12/06/2022
212 Pass FD-1-05 1 Inside srorage room 1632-b 12/06/2022
217 Fail FD-1-07 1 Inside room 1609 above doorway 12/06/2022
258 Fail FD-1-07 1 Inside hallway outside bathroom 1610 12/06/2022
261 Fail FD-1-08 1 Inside waiting room by room 1501G 12/07/2022
224 Pass FD-1-08 1 Inside room 1609 12/06/2022
262 Fail FD-1-09 1 Inside waiting area by room 1501G 12/07/2022
Project: Fire Damper Inspection, Repair and Testing at the VANYHHCS Manhattan VAMC Rascap LLC dba Acceptance Engineering
263 Fail FD-1-10 1 Inside office room 1501G 12/07/2022
264 Fail FD-1-11 1 Inside room 1501G 12/07/2022
265 Fail FD-1-12 1 Inside office room 1501I by waiting area behind other offices 12/07/2022
266 Fail FD-1-13 1 Inside office room 1501I behind other offices by waiting area 12/07/2022
267 Fail FD-1-14 1 Inside office room 1501I by waiting area behind other offices 12/07/2022
268 Fail FD-1-15 1 Inside office area by waiting room behind rooms 1501 12/07/2022
269 Fail FD-1-16 1 Inside office room 1501H behind offices by waiting area 12/07/2022
270 Fail FD-1-17 1 Inside office room 1501H behind offices by waiting area 12/07/2022
272 Pass FD-1-19 1 Inside work room/silver door by emergency room/ patient room 12/14/2022
273 Pass FD-1-20 1 Inside work room/silver door next to emergency room/ patient room 12/14/2022
274 Pass FD-1-21 1 Inside office room across from double doors next to bathroom 1520 12/14/2022
275 Pass FD-1-22 1 Inside office room across from double doors next to bathroom 1520 12/14/2022
201 Pass FD-2-01 2 Just after double doors in corridor across from food court 11/22/2022
200 Pass FD-2-02 2 Just after double doors in corridor across from food court 11/22/2022
199 Pass FD-2-03 2 In corridor just after double doors across from food court 11/22/2022
198 Pass FD-2-04 2 Next to man's bathroom 11/22/2022
207 Pass FD-2-05 2 Inside men bathroom 2623 11/22/2022
Project: Fire Damper Inspection, Repair and Testing at the VANYHHCS Manhattan VAMC Rascap LLC dba Acceptance Engineering
254 Fail FD-2-06 2 Inside men's bathroom 2623 11/22/2022
208 Pass FD-2-07 2 Inside room 2621 11/22/2022
Inaccessible
FD-2-08 2 Inside eye exam room p 11/22/2022
206 Pass FD-2-09 2 In hallway next to door way to room 2677 11/22/2022
No Longer Exists
FD-2-09 2 Inside staff bathroom 2675 11/22/2022
210 Pass FD-2-10 2 Inside room 2515 11/23/2022
209 Pass FD-2-11 2 Inside room 2515 11/23/2022
193 Fail FD-4-01 4 Inside OR area above smoke door 11/21/2022
194 Pass FD-4-02 4 Shaft across from dung bell shaft inside sentize room 11/21/2022
215 Pass FD-4-03 4 Inside room 4594P 11/21/2022
216 Fail FD-4-04 4 In Corridor across from room 4562 11/22/2022
22 Pass FD-5-01 5 Transfer next to stairwell 10/04/2022
21 Pass FD-5-02 5 Across elevator machine room 09/27/2022
20 Pass FD-5-03 5 Next to elevator machine room 09/27/2022
19 Pass FD-5-04 5 Inside mechanical room 09/27/2022
17 Pass FD-5-05 5 Inside mechanical room 09/27/2022
23 Fail FD-5-06 5 Inside mechanical room 09/27/2022
39 Pass FD-5-07 5 Inside mechanical area 09/27/2022
Project: Fire Damper Inspection, Repair and Testing at the VANYHHCS Manhattan VAMC Rascap LLC dba Acceptance Engineering
41 Pass FD-5-08 5 Inside mechanical room 09/27/2022
49 Pass FD-5-09 5 Inside mechanical room 09/27/2022
44 Pass FD-5-10 5 Inside mechanical area 09/27/2022
50 Pass FD-5-11 5 Inside mechanical area 09/27/2022
48 Pass FD-5-12 5 Inside mechanical area 09/27/2022
43 Pass FD-5-13 5 Inside mechanical room 10/04/2022
46 Pass FD-5-14 5 Inside mechanical area 10/04/2022
45 Pass FD-5-15 5 Inside mechanical room 10/04/2022
47 Pass FD-5-16 5 Inside mechanical area 10/04/2022
38 Pass FD-5-17 5 Inside mechanical room 10/04/2022
42 Pass FD-5-18 5 Inside mechanical area 10/04/2022
40 Pass FD-5-19 5 Inside mechanical room 10/04/2022
27 Pass FD-5-20 5 In side of mechanical room 10/04/2022
26 Pass FD-5-21 5 In mechanical room 10/04/2022
37 Pass FD-5-22 5 Inside mechanical area 10/04/2022
36 Pass FD-5-23 5 Inside mechanical room 10/04/2022
34 Pass FD-5-24 5 Inside mechanical room 10/04/2022
28 Pass FD-5-25 5 In side mechanical room 10/04/2022
29 Pass FD-5-26 5 In side mechanical room 10/04/2022
Project: Fire Damper Inspection, Repair and Testing at the VANYHHCS Manhattan VAMC Rascap LLC dba Acceptance Engineering
33 Pass FD-5-27 5 Inside mechanical room 10/04/2022
31 Pass FD-5-28 5 Inside mechanical room 10/04/2022
16 Pass FD-5-29 5 Inside mechanical room 10/04/2022
15 Pass FD-5-30 5 Inside mechanical room 11/15/2022
24 Pass FD-5-31 5 Inside mechanical room 10/04/2022
35 Fail FD-5-32 5 Inside mechanical area 10/04/2022
14 Fail FD-5-33 5 Inside mechanical room 10/04/2022
11 Fail FD-5-34 5 Inside mechanical room 10/04/2022
10 Pass FD-5-35 5 Inside mechanical room 10/04/2022
13 Fail FD-5-37 5 Inside mechanical room 10/04/2022
9 Pass FD-5-38 5 Inside mechanical room 10/05/2022
8 Pass FD-5-39 5 Inside mechanical room behind stairs 10/05/2022
7 Pass FD-5-40 5 Inside mechanical space 10/05/2022
32 Pass FD-5-41 5 Inside mechanical area 10/04/2022
30 Fail FD-5-42 5 Inside mechanical area 10/04/2022
51 Pass FD-5-44 5 Inside mechanical space 10/05/2022
52 Fail FD-5-45 5 Inside mechanical room 10/05/2022
190 Pass FD-5-46 5 Inside mechanical space 10/05/2022
62 Pass FD-5-47 5 Inside mechanical area 10/05/2022
Project: Fire Damper Inspection, Repair and Testing at the VANYHHCS Manhattan VAMC Rascap LLC dba Acceptance Engineering
64 Pass FD-5-48 5 Inside mechanical area 10/05/2022
68 Fail FD-5-49 5 Inside mechanical area 10/05/2022
69 Pass FD-5-50 5 Inside mechanical area 10/05/2022
72 Pass FD-5-51 5 Inside mechanical area 10/05/2022
184 Fail FD-5-52 5 Inside electrical room inside mechanical space 10/05/2022
185 Pass FD-5-53 5 Inside electrical room inside mechanical room 10/05/2022
73 Pass FD-5-54 5 Inside mechanical area 10/05/2022
77 Pass FD-5-55 5 Inside mechanical area 10/05/2022
79 Pass FD-5-56 5 Inside mechanical area 10/05/2022
81 Pass FD-5-57 5 Inside mechanical area 10/05/2022
192 Pass FD-5-58 5 Inside mechanical space 10/05/2022
191 Pass FD-5-59 5 Inside mechanical space 10/05/2022
85 Pass FD-5-60 5 Inside mechanical area 10/05/2022
89 Fail FD-5-61 5 Inside mechanical area 10/07/2022
91 Fail FD-5-62 5 Inside mechanical area 11/17/2022
93 Pass FD-5-63 5 Inside mechanical area 10/07/2022
97 Pass FD-5-64 5 Inside mechanical area 10/07/2022
150 Pass FD-5-65 5 Inside mechanical space 10/07/2022
151 Pass FD-5-66 5 Inside mechanical space 10/07/2022
Project: Fire Damper Inspection, Repair and Testing at the VANYHHCS Manhattan VAMC Rascap LLC dba Acceptance Engineering
No Longer Exists
FD-5-67 5 Inside mechanical area 11/14/2022
152 Pass FD-5-67 5 Inside mechanical space 10/07/2022
153 Pass FD-5-68 5 Inside mechanical space 10/07/2022
154 Pass FD-5-69 5 Inside mechanical space 10/07/2022
155 Pass FD-5-70 5 Inside mechanical space 10/07/2022
156 Pass FD-5-71 5 Inside mechanical space 10/07/2022
158 Pass FD-5-72 5 Inside mechanical space 10/07/2022
163 Pass FD-5-73 5 Inside mechanical space 10/07/2022
164 Pass FD-5-74 5 Inside mechanical space 10/07/2022
165 Pass FD-5-75 5 Inside mechanical space 10/07/2022
166 Pass FD-5-76 5 Inside mechanical space 10/07/2022
167 Pass FD-5-77 5 Inside mechanical space 10/07/2022
168 Pass FD-5-78 5 Inside mechanical space 10/07/2022
169 Pass FD-5-79 5 Inside mechanical space 10/07/2022
170 Pass FD-5-80 5 Inside mechanical space 10/07/2022
172 Pass FD-5-81 5 Inside mechanical space 10/07/2022
175 Pass FD-5-82 5 Inside mechanical space 10/07/2022
173 Fail FD-5-83 5 Inside mechanical space 11/14/2022
174 Pass FD-5-84 5 Inside mechanical space 11/14/2022
Project: Fire Damper Inspection, Repair and Testing at the VANYHHCS Manhattan VAMC Rascap LLC dba Acceptance Engineering
176 Pass FD-5-85 5 Inside mechanical room 11/14/2022
177 Pass FD-5-86 5 Inside mechanical room 11/14/2022
178 Pass FD-5-87 5 Inside mechanical room 11/14/2022
179 Pass FD-5-88 5 Inside mechanical room 11/14/2022
56 Pass FD-5-89 5 Inside mechanical area 11/14/2022
59 Pass FD-5-90 5 Inside mechanical area 11/14/2022
57 Pass FD-5-91 5 Inside mechanical area 11/14/2022
251 Pass FD-5-93 5 Inside mechanical space 11/14/2022
159 Pass FD-5-94 5 Inside mechanical space 11/14/2022
160 Pass FD-5-95 5 Inside mechanical space 11/14/2022
162 Pass FD-5-96 5 Inside mechanical space 11/14/2022
161 Pass FD-5-97 5 Inside mechanical space 11/14/2022
187 Pass FD-5-98 5 Inside mechanical room 11/14/2022
188 Pass FD-5-99 5 Inside mechanical space 11/14/2022
189 Pass FD-5-100 5 Inside mechanical space 11/14/2022
183 Pass FD-5-101 5 Inside mechanical room 11/14/2022
182 Pass FD-5-102 5 Inside mechanical room 11/14/2022
180 Fail FD-5-103 5 Inside mechanical room 11/14/2022
181 Fail FD-5-104 5 Inside mechanical room 11/15/2022
Project: Fire Damper Inspection, Repair and Testing at the VANYHHCS Manhattan VAMC Rascap LLC dba Acceptance Engineering
86 Pass FD-5-105 5 Inside mechanical room 11/15/2022
96 Pass FD-5-106 5 Inside mechanical room 11/15/2022
94 Pass FD-5-106 5 Inside mechanical room 11/15/2022
92 Pass FD-5-108 5 Inside mechanical space 11/15/2022
95 Pass FD-5-109 5 Inside mechanical space 11/15/2022
130 Pass FD-5-110 5 Inside mechanical room 11/15/2022
131 Pass FD-5-111 5 Inside mechanical space 11/15/2022
129 Pass FD-5-112 5 Inside mechanical space 11/15/2022
126 Pass FD-5-113 5 Inside mechanical room 11/15/2022
128 Pass FD-5-114 5 Inside mechanical room 11/15/2022
127 Pass FD-5-115 5 Inside mechanical space 11/15/2022
125 Fail FD-5-116 5 Inside mechanical room 11/15/2022
124 Pass FD-5-117 5 Inside mechanical space 11/15/2022
123 Fail FD-5-118 5 Inside mechanical room 11/15/2022
122 Pass FD-5-119 5 Inside mechanical space 11/15/2022
121 Pass FD-5-120 5 Inside mechanical room 11/15/2022
119 Pass FD-5-121 5 Inside mechanical room 11/15/2022
120 Pass FD-5-122 5 Inside mechanical space 11/15/2022
118 Pass FD-5-123 5 Inside mechanical room 11/15/2022
Project: Fire Damper Inspection, Repair and Testing at the VANYHHCS Manhattan VAMC Rascap LLC dba Acceptance Engineering
117 Pass FD-5-124 5 Inside mechanical space 11/15/2022
116 Pass FD-5-125 5 Inside mechanical space 11/15/2022
115 Pass FD-5-126 5 Inside mechanical space 11/15/2022
114 Pass FD-5-127 5 Inside mechanical space 11/15/2022
113 Pass FD-5-128 5 Inside mechanical space 11/15/2022
112 Pass FD-5-129 5 Inside mechanical space 11/15/2022
105 Pass FD-5-130 5 Inside mechanical space 11/15/2022
111 Pass FD-5-131 5 Inside mechanical space 11/15/2022
110 Pass FD-5-132 5 Inside mechanical space 11/15/2022
109 Pass FD-5-133 5 Inside mechanical space 11/15/2022
108 Pass FD-5-134 5 Inside mechanical space 11/15/2022
107 Fail FD-5-135 5 Inside mechanical space 11/15/2022
106 Pass FD-5-136 5 Inside mechanical space 11/15/2022
103 Pass FD-5-137 5 Inside mechanical space 11/15/2022
104 Pass FD-5-138 5 Inside mechanical space 11/15/2022
88 Pass FD-5-139 5 Inside mechanical space 11/15/2022
87 Pass FD-5-140 5 Inside mechanical space 11/16/2022
90 Fail FD-5-141 5 Inside mechanical space going through ceiling 11/16/2022
58 Pass FD-5-142 5 Inside mechanical room 11/17/2022
Project: Fire Damper Inspection, Repair and Testing at the VANYHHCS Manhattan VAMC Rascap LLC dba Acceptance Engineering
252 Pass FD-5-143 5 Mechanical space 11/16/2022
60 Pass FD-5-144 5 Inside mechanical room 11/17/2022
76 Pass FD-5-145 5 Inside mechanical space 11/16/2022
78 Pass FD-5-146 5 Inside mechanical space l 11/16/2022
136 Pass FD-5-147 5 Inside mechanical room 11/16/2022
135 Fail FD-5-148 5 Inside mechanical room 11/17/2022
134 Pass FD-5-149 5 Inside mechanical room 11/16/2022
133 Pass FD-5-150 5 Inside mechanical room 11/16/2022
138 Pass FD-5-153 5 Inside mechanical room 11/16/2022
142 Pass FD-5-154 5 Inside mechanical space 11/16/2022
143 Pass FD-5-155 5 Inside mechanical room 11/16/2022
67 Pass FD-5-156 5 Inside mechanical room 11/16/2022
66 Pass FD-5-157 5 Inside mechanical room 11/16/2022
63 Pass FD-5-158 5 Inside mechanical room 11/16/2022
140 Fail FD-5-159 5 Inside mechanical room 11/22/2022
139 Pass FD-5-160 5 Inside mechanical room 11/16/2022
141 Pass FD-5-161 5 Inside mechanical room 11/16/2022
82 Pass FD-5-162 5 Inside mechanical room 11/16/2022
80 Fail FD-5-163 5 Inside mechanical room 11/22/2022
Project: Fire Damper Inspection, Repair and Testing at the VANYHHCS Manhattan VAMC Rascap LLC dba Acceptance Engineering
75 Pass FD-5-164 5 Inside mechanical room 11/16/2022
74 Pass FD-5-165 5 Inside mechanical room 11/16/2022
253 Fail FD-5-166 5 Inside mechanical space 11/17/2022
83 Pass FD-5-167 5 Inside mechanical space going into ceiling 11/17/2022
84 Pass FD-5-168 5 Inside mechanical room going through ceiling 11/17/2022
55 Fail FD-5-169 5 Inside mechanical area 11/17/2022
12 Fail FF-5-36 5 Inside mechanical room 10/04/2022
195 Pass FD-6-02 6 Inside staff lounge room 6620 11/17/2022
222 Pass FD-6-03 6 Inside room 6522A 11/17/2022
221 Fail FD-6-04 6 Inside clean storage room 6616 11/17/2022
4 Pass FD-6-05 6 Inside clean storage access panel in MRI zone
11/17/2022
6 Pass FD-6-06 6 Inside clean storage access panel in MRI zone
11/17/2022
3 Pass FD-6-06 6 Inside clean storage access panel inside MRI zone 2 11/17/2022
5 Pass FD-6-07 6 Inside clean storage in MRI zone 2 11/17/2022
218 Pass FD-6-08 6 Inside linen chute room 6632 11/21/2022
No Longer Exists
FD-6-2 6 MRI zone 1 hallway across from 6553C01 11/17/2022
229 Fail FD-7-01 7 Inside mechanical space 10/03/2022
228 Fail FD-7-01 7 Inside mechanical space 10/03/2022
Project: Fire Damper Inspection, Repair and Testing at the VANYHHCS Manhattan VAMC Rascap LLC dba Acceptance Engineering
230 Pass FD-7-03 7 Inside mechanical space 10/03/2022
231 Pass FD-7-04 7 Inside mechanical space 10/03/2022
234 Pass FD-7-07 7 Inside mechanical space 10/03/2022
235 Pass FD-7-08 7 Inside mechanical space 10/03/2022
236 Pass FD-7-09 7 Inside mechanical space 10/03/2022
237 Fail FD-7-10 7 Inside mechanical space 10/03/2022
241 Pass FD-7-11 7 Inside mechanical space 10/04/2022
240 Pass FD-7-12 7 Inside mechanical space 10/04/2022
242 Fail FD-7-13 7 Inside mechanical space 10/04/2022
243 Pass FD-7-14 7 Inside mechanical space 10/04/2022
244 Pass FD-7-15 7 Inside mechanical space 10/04/2022
245 Pass FD-7-16 7 Inside mechanical space 10/04/2022
246 Fail FD-7-17 7 Isnide mechanical space 10/04/2022
247 Pass FD-7-18 7 Inside mechanical space 10/04/2022
248 Fail FD-7-19 7 Inside mechanical space 10/04/2022
249 Pass FD-7-20 7 Inide mechanical space 10/04/2022
250 Pass FD-7-21 7 Inside mechanical space 10/04/2022
259 Pass FD-G-01 G Inside hallway on the other side of steam pipe room 12/07/2022
Project: Fire Damper Inspection, Repair and Testing at the VANYHHCS Manhattan VAMC Rascap LLC dba Acceptance Engineering
260 Pass FD-G-02 G Inside hallway on the other side of steam pipe room 12/07/2022
276 Pass FD-G-03 G Above double doors by public elevators 12/14/2022
278 Pass FD-G-05 G Inside washer dryer room G003 12/14/2022
279 Pass FD-G-06 G Inside construction area believe to be made into operation area 12/15/2022
280 Pass FD-G-07 G Inside construction area believe to be a operation area 12/15/2022
Inaccessible
FD-G-10 G Inside linen room G503 12/15/2022
Smoke Damper
53 Fail FD-5-43 5 Inside mechanical area 10/05/2022
54 Fail SD-5-92 5 Inside mechanical area 11/14/2022
Fire+Smoke Damper
Inaccessible
FSD-7-05 7 Inside mechanical space 10/03/2022
Inaccessible
FSD-7-06 7 Inside mechanical space 10/03/2022
277 Fail FSD-G-04 G Next to double doors by room G591 soiled receiving room 12/14/2022
Unknown Damper
No Longer Exists
FD-1-1 1 Above beneficiary travel help center 11/23/2022
214 Fail FD-1-18 1 Inside office room 1521 12/07/2022
271 Pass FD-1-18 1 Inside soiled utility room/storage room next to service elevator 12/07/2022
197 Fail FD-2-09 2 Inside women bathroom 11/23/2022
Project: Fire Damper Inspection, Repair and Testing at the VANYHHCS Manhattan VAMC Rascap LLC dba Acceptance Engineering
Exists
FD-2-5 2 Inside staff bathroom 2675 11/22/2022
No Longer Exists
FD-2-7 2 Inside bathroom 2675 11/22/2022
No Longer Exists
FD-5-1 5 Bridge connecting building 1 and building 6 11/23/2022
No Longer Exists
FD-5-3 5 Bridge connecting building 1 and building 6 11/23/2022
No Longer Exists
FD-5-4 5
Connecting bridge between building 1 and building 6 11/23/2022
No Longer Exists
FD-5-5 5 Bridge connecting building 6 and building 1 11/23/2022
No Longer Exists
FD-5-6 5 Bridge connecting building 6 and building 1 11/23/2022
No Longer Exists
FD-5-49 5 Inside mechanical space 11/14/2022
No Longer Exists
FD-5-56 5 Inside mechanical space 11/14/2022
No Longer Exists
FD-5-73 5 Inside mechanical room 11/14/2022
No Longer Exists
FD-5-80 5 Inside mechanical space 11/16/2022
No Longer Exists
FD-5-104 5 Inside mechanical room 11/16/2022
No Longer Exists
FD-5-116 5 Inside mechanical space 11/16/2022
No Longer Exists
FD-5-117 5 Inside mechanical room 11/16/2022
No Longer Exists
FD-5-119 5 Inside mechanical space 11/15/2022
No Longer Exists
FD-5-121 5 Inside mechanical room 11/16/2022
No Longer Exists
FD-5-122 5 Inside mechanical room 11/16/2022
Project: Fire Damper Inspection, Repair and Testing at the VANYHHCS Manhattan VAMC Rascap LLC dba Acceptance Engineering
Exists
FD-5-124 5 Inside mechanical space 11/16/2022
137 Pass FD-5-151 5 Inside mechanical room 11/16/2022
132 Pass FD-5-152 5 Inside mechanical room 11/16/2022
196 Pass FD-6-01 6 Staff lounge 6620 11/17/2022
No Longer Exists
FD-G-3 6 Inside file room 6522B 11/17/2022
Project: Fire Damper Inspection, Repair and Testing at the VANYHHCS Manhattan VAMC Rascap LLC dba Acceptance Engineering
FAIL/INACCESSIBLE DAMPER DETAIL REPORT
Damper Inspection 9.27.22 through 12.15.22
Client Name: VA Manhattan Client Address: 423 23rd Street, New York, NY 10010
Legend
- Pass
- Pass (Repair)
- Fail
- Decommissioned
- No Longer in Rated Barrier(NLR)
- Inaccessible
- No Longer Exists
Project: Fire Damper Inspection, Repair and Testing at the VANYHHCS Manhattan VAMC Rascap LLC dba Acceptance Engineering
Building 6, 1st Floor(1)
Project: Fire Damper Inspection, Repair and Testing at the VANYHHCS Manhattan VAMC Rascap LLC dba Acceptance Engineering
Damper Details Marker Label:214
Area #: Building 6, 1st Floor(1) Tech: Jason Noyes
Result: Fail Damper ID: FD-1-18
Building: Building 6 Floor: 1
Location: Inside office room 1521 Category: Unknown
AHUdown: No Orientation: Vertical
Link: Unknown Design: Unknown
Damper Manufacturer: Unknown Deficiencies: • Requires duct access door
Comments for the Customer: Requires 14x14 none hinge sticky Duct access door
Date: 12/07/2022
Attachment #487558 Attachment #487559 Attachment #487560 Attachment #487561
Attachment #487562
Attachment #487563
Attachment #0000 a
Attachment #0000 b
Attachment #0000 c
Attachment #0000 c
Project: Fire Damper Inspection, Repair and Testing at the VANYHHCS Manhattan VAMC Rascap LLC dba Acceptance Engineering
Marker Label:270
Area #: Building 6, 1st Floor(1) Tech: Jason Noyes
Result: Fail Damper ID: FD-1-17
Building: Building 6 Floor: 1
Location: Inside office room 1501H behind offices by waiting area
Category: Fire Damper
AHUdown: No Orientation: Horizontal
Motor: N/A Link: Yes
Design: Curtain Damper Manufacturer: Arlan
Deficiencies:
• Damper does not fall
• Damper springs broken/twisted
• Damper wedged/blocked open
• New damper required
Comments for the Customer:
Needs new 35 1/2x5 1/2 horizontal Fire Damper and Requires duct work fabrication to remove damper and install from underneath
Date: 12/07/2022
Attachment #487341
Attachment #487342
Attachment #487343 Attachment #487344
Attachment #0000 c
Project: Fire Damper Inspection, Repair and Testing at the VANYHHCS Manhattan VAMC Rascap LLC dba Acceptance Engineering
Marker Label:269
Area #: Building 6, 1st Floor(1) Tech: Jason Noyes
Result: Fail Damper ID: FD-1-16
Building: Building 6 Floor: 1
Location: Inside office room 1501H behind offices by waiting area
Category: Fire Damper
AHUdown: No Orientation: Horizontal
Link: Yes Design: Curtain
Damper Manufacturer: Arlan Deficiencies:
• Damper does not fall
• Damper springs broken/twisted
• Damper wedged/blocked open
• New damper required
Comments for the Customer:
Needs new 35 1/2x5 1/2 horizontal Fire Damper and Requires duct work fabrication to remove damper and install from underneath
Date: 12/07/2022
Attachment #487335
Attachment #487336 Attachment #487337 Attachment #487338
Attachment #0000 c
Project: Fire Damper Inspection, Repair and Testing at the VANYHHCS Manhattan VAMC Rascap LLC dba Acceptance Engineering
Marker Label:268
Area #: Building 6, 1st Floor(1) Tech: Jason Noyes
Result: Fail Damper ID: FD-1-15
Building: Building 6 Floor: 1
Location: Inside office area by waiting room behind rooms
Category: Fire Damper
AHUdown: No Orientation: Horizontal
Link: Yes Design: Curtain
Damper Manufacturer: Arlan Deficiencies:
• Damper does not fall
• Damper springs broken/twisted
• Damper wedged/blocked open
• New damper required
Comments for the Customer:
Needs new 35 1/2x5 1/2 horizontal Fire Damper and Requires duct work fabrication to remove damper and install from underneath
Date: 12/07/2022
Attachment #487329
Attachment #487330
Attachment #487331
Attachment #487332 Attachment #487333
Project: Fire Damper Inspection, Repair and Testing at the VANYHHCS Manhattan VAMC Rascap LLC dba Acceptance Engineering
Marker Label:267
Area #: Building 6, 1st Floor(1) Tech: Jason Noyes
Result: Fail Damper ID: FD-1-14
Building: Building 6 Floor: 1
Location: Inside office room 1501I by waiting area behind other offices
Category: Fire Damper
AHUdown: No Orientation: Horizontal
Link: Yes Design: Curtain
Damper Manufacturer: Arlan Deficiencies:
• Damper does not fall
• Damper springs broken/twisted
• Damper wedged/blocked open
• New damper required
Comments for the Customer:
Needs new 35 1/2x5 1/2 horizontal Fire Damper and Requires duct work fabrication to remove damper and install from underneath pop pop
Date: 12/07/2022
Attachment #487264 Attachment #487265
Attachment #487266 Attachment #487267
Attachment #0000 c
Project: Fire Damper Inspection, Repair and Testing at the VANYHHCS Manhattan VAMC Rascap LLC dba Acceptance Engineering
Marker Label:266
Area #: Building 6, 1st Floor(1) Tech: Jason Noyes
Result: Fail Damper ID: FD-1-13
Building: Building 6 Floor: 1
Location: Inside office room 1501I behind other offices by waiting area
Category: Fire Damper
AHUdown: No Orientation: Horizontal
Link: Yes Design: Curtain
Damper Manufacturer: Arlan Deficiencies:
• Damper does not fall
• Damper springs broken/twisted
• Damper wedged/blocked open
• New damper required
Comments for the Customer:
Needs new 35 1/2x5 1/2 horizontal Fire Damper and Requires duct work fabrication to remove damper and install from underneath
Date: 12/07/2022
Attachment #487256 Attachment #487257 Attachment #487258 Attachment #487259
Attachment #0000 c
Project: Fire Damper Inspection, Repair and Testing at the VANYHHCS Manhattan VAMC Rascap LLC dba Acceptance Engineering
Marker Label:265
Area #: Building 6, 1st Floor(1) Tech: Jason Noyes
Result: Fail Damper ID: FD-1-12
Building: Building 6 Floor: 1
Location: Inside office room 1501I by waiting area behind other offices
Category: Fire Damper
AHUdown: Yes Orientation: Horizontal
Link: Yes Design: Curtain
Damper Manufacturer: Arlan Deficiencies:
• Damper does not fall
• Damper springs broken/twisted
• Damper wedged/blocked open
• New damper required
Comments for the Customer:
Needs new 36x6 horizontal Fire Damper and Requires duct work fabrication to remove damper and install from underneath
Date: 12/07/2022
Attachment #487252
Attachment #0000 a
Attachment #0000 b
Attachment #0000 c
Attachment #0000 c
Project: Fire Damper Inspection, Repair and Testing at the VANYHHCS Manhattan VAMC Rascap LLC dba Acceptance Engineering
Marker Label:264
Area #: Building 6, 1st Floor(1) Tech: Jason Noyes
Result: Fail Damper ID: FD-1-11
Building: Building 6 Floor: 1
Location: Inside room 1501G Category: Fire Damper
AHUdown: No Orientation: Horizontal
Motor: NO ID LABELS Link: Yes
Design: Curtain Damper Manufacturer: No ID Labels
Deficiencies:
• Damper does not fall
• Damper wedged/blocked open
• New damper required
Comments for the Customer:
Needs new 36x6 horizontal Fire Damper and Requires duct work fabrication to remove damper and install from underneath
Date: 12/07/2022
Attachment #487240 Attachment #487241
Attachment #487242
Attachment #487243
Attachment #0000 c
Project: Fire Damper Inspection, Repair and Testing at the VANYHHCS Manhattan VAMC Rascap LLC dba Acceptance Engineering
Marker Label:263
Area #: Building 6, 1st Floor(1) Tech: Jason Noyes
Result: Fail Damper ID: FD-1-10
Building: Building 6 Floor: 1
Location: Inside office room 1501G Category: Fire Damper
AHUdown: No Orientation: Horizontal
Link: Yes Design: Curtain
Damper Manufacturer: Arlan Deficiencies:
• Damper does not fall
• Damper springs broken/twisted
• Damper wedged/blocked open
• New damper required
Comments for the Customer:
Needs new 36x6 horizontal Fire Damper and Requires duct work fabrication to remove damper and install from underneath
Date: 12/07/2022
Attachment #487230 Attachment #487231 Attachment #487232 Attachment #487233
Attachment #0000 c
Project: Fire Damper Inspection, Repair and Testing at the VANYHHCS Manhattan VAMC Rascap LLC dba Acceptance Engineering
Marker Label:262
Area #: Building 6, 1st Floor(1) Tech: Jason Noyes
Result: Fail Damper ID: FD-1-09
Building: Building 6 Floor: 1
Location: Inside waiting area by room 1501G Category: Fire Damper
AHUdown: No Orientation: Horizontal
Link: Yes Design: Curtain
Damper Manufacturer: Arlan Deficiencies:
• Damper does not fall
• Damper wedged/blocked open
• New damper required
Comments for the Customer:
Needs new 36x6 horizontal Fire Damper and Requires duct work fabrication to remove damper and install from underneath
Date: 12/07/2022
Attachment #487179
Attachment #487180
Attachment #487181 Attachment #487182 Attachment #487183
Attachment #487184
Attachment #0000 a
Attachment #0000 b
Attachment #0000 c
Attachment #0000 c
Project: Fire Damper Inspection, Repair and Testing at the VANYHHCS Manhattan VAMC Rascap LLC dba Acceptance Engineering
Marker Label:261
Area #: Building 6, 1st Floor(1) Tech: Jason Noyes
Result: Fail Damper ID: FD-1-08
Building: Building 6 Floor: 1
Location: Inside waiting room by room 1501G Category: Fire Damper
AHUdown: No Orientation: Horizontal
Link: Yes Design: Curtain
Damper Manufacturer: Arlan Deficiencies:
• Damper does not fall
• Damper springs broken/twisted
• New damper required
Comments for the Customer:
Needs new 36x6 horizontal Fire Damper and Requires duct work fabrication to remove damper and install from underneath
Date: 12/07/2022
Attachment #487163 Attachment #487164 Attachment #487166 Attachment #487168 Attachment #487169
Project: Fire Damper Inspection, Repair and Testing at the VANYHHCS Manhattan VAMC Rascap LLC dba Acceptance Engineering
Marker Label:217
Area #: Building 6, 1st Floor(1) Tech: Jason Noyes
Result: Fail Damper ID: FD-1-07
Building: Building 6 Floor: 1
Location: Inside room 1609 above doorway
Category: Fire Damper
AHUdown: No Orientation: Horizontal
Link: Yes Design: Curtain
Damper Manufacturer: Arlan Access Door Size: 14"x14"
Deficiencies: • Requires duct access door
Comments for the Customer:
Requires 16x16 duct access door to be able to reach safely
Date: 12/06/2022
Attachment #486681 Attachment #486682
Attachment #486683
Attachment #486684
Attachment #0000 c
Project: Fire Damper Inspection, Repair and Testing at the VANYHHCS Manhattan VAMC Rascap LLC dba Acceptance Engineering
Marker Label:258
Area #: Building 6, 1st Floor(1) Tech: Jason Noyes
Result: Fail Damper ID: FD-1-07
Building: Building 6 Floor: 1
Location: Inside hallway outside bathroom 1610 Category: Fire Damper
AHUdown: No Orientation: Horizontal
Link: Unknown Design: Unknown
Damper Manufacturer: Unknown Deficiencies: • Requires duct access door
Comments for the Customer: Requires 14x14 or access patch to access damper
Date: 12/06/2022
Attachment #486537 Attachment #486538 Attachment #486539
Attachment #0000 a
Attachment #0000 c
Project: Fire Damper Inspection, Repair and Testing at the VANYHHCS Manhattan VAMC Rascap LLC dba Acceptance Engineering
Marker Label:256
Area #: Building 6, 1st Floor(1) Tech: Jason Noyes
Result: Fail Damper ID: FD-1-03
Building: Building 6 Floor: 1
Location: In hallway next to room 1632-B Category: Fire Damper
AHUdown: No Orientation: Vertical
Link: Unknown Design: Unknown
Damper Manufacturer: Unknown Deficiencies: • Requires duct access door
Comments for the Customer:
Requires a 14x14 sticky none hinge duct access door and it's in a Tight area
Date: 12/06/2022
Attachment #486279 Attachment #486280 Attachment #486281
Attachment #0000 a
Attachment #0000 c
Project: Fire Damper Inspection, Repair and Testing at the VANYHHCS Manhattan VAMC Rascap LLC dba Acceptance Engineering
Building 6, 2nd Floor(2)
Rascap LLC dba Acceptance Engineering
Marker Label:197
Area #: Building 6, 2nd Floor(2) Tech: Jason Noyes
Result: Fail Damper ID: FD-2-09
Building: Building 6 Floor: 2
Location: Inside women bathroom Category: Unknown
AHUdown: No Orientation: Vertical
Link: Unknown Design: Unknown
Damper Manufacturer: Unknown Access Door Size: 12"x12"
Deficiencies: • Requires duct access door
Comments for the Customer:
Requires a 14x14 sticky none hinge Very hard spot to get to
Date: 11/23/2022
Attachment #480434 Attachment #480435 Attachment #480436
Attachment #480437
Attachment #480438
Attachment #480439
Attachment #0000 a
Attachment #0000 b
Attachment #0000 c
Attachment #0000 c
Project: Fire Damper Inspection, Repair and Testing at the VANYHHCS Manhattan VAMC Rascap LLC dba Acceptance Engineering
Marker Label:202
Area #: Building 6, 2nd Floor(2) Tech: Jason Noyes
Result: Inaccessible Damper ID: FD-2-08
Building: Building 6 Floor: 2
Location: Inside eye exam room p Category: Fire Damper
AHUdown: Yes Orientation: Vertical
Link: Yes Design: Curtain
Damper Manufacturer: Arlan Comments for the Customer: Requires AHU shut down
Date: 11/22/2022
Attachment #479823
Attachment #479824
Attachment #0000 a
Attachment #0000 b
Attachment #0000 c
Project: Fire Damper Inspection, Repair and Testing at the VANYHHCS Manhattan VAMC Rascap LLC dba Acceptance Engineering
Marker Label:254
Area #: Building 6, 2nd Floor(2) Tech: Jason Noyes
Result: Fail Damper ID: FD-2-06
Building: Building 6 Floor: 2
Location: Inside men's bathroom 2623 Category: Fire Damper
AHUdown: No Orientation: Vertical
Link: Yes Design: Curtain
Damper Manufacturer: Arlan Deficiencies: • Requires duct access door
Comments for the Customer:
Requires a 12x12 duct access door and is Very high up and tight spot
Date: 11/22/2022
Attachment #479656 Attachment #479657 Attachment #479658
Attachment #0000 a
Attachment #0000 c
Project: Fire Damper Inspection, Repair and Testing at the VANYHHCS Manhattan VAMC Rascap LLC dba Acceptance Engineering
Building 6, 4th Floor(4)
Rascap LLC dba Acceptance Engineering
Marker Label:216
Area #: Building 6, 4th Floor(4) Tech: Jason Noyes
Result: Fail Damper ID: FD-4-04
Building: Building 6 Floor: 4
Location: In Corridor across from room
Category: Fire Damper
AHUdown: No Orientation: Vertical
Link: Unknown Design: Unknown
Damper Manufacturer: Unknown Damper Size (i.e. 24"x12"): 22x14
Access Door Size if not listed: Tight space Deficiencies: • Requires duct access door
Comments for the Customer: Requires access door Date: 11/22/2022
Attachment #478775 Attachment #478776
Attachment #479489 Attachment #479490 Attachment #479491
Project: Fire Damper Inspection, Repair and Testing at the VANYHHCS Manhattan VAMC Rascap LLC dba Acceptance Engineering
Marker Label:193
Area #: Building 6, 4th Floor(4) Tech: Jason Noyes
Result: Fail Damper ID: FD-4-01
Building: Building 6 Floor: 4
Location: Inside OR area above smoke door
Category: Fire Damper
AHUdown: No Orientation: Vertical
Link: Unknown Design: Unknown
Damper Manufacturer: Unknown Damper Size (i.e. 24"x12"): 6x14
Deficiencies: • Requires duct access door Comments for the Customer:
Requires a 12 x12 duct access door
Date: 11/21/2022
Attachment #478707 Attachment #478708
Attachment #478709
Attachment #0000 a
Attachment #0000 c
Project: Fire Damper Inspection, Repair and Testing at the VANYHHCS Manhattan VAMC Rascap LLC dba Acceptance Engineering
Building 6, 5th Floor(5)
Rascap LLC dba Acceptance Engineering
Marker Label:80
Area #: Building 6, 5th Floor(5) Tech: Jason Noyes
Result: Fail Damper ID: FD-5-163
Building: Building 6 Floor: 5
Location: Inside mechanical room Category: Fire Damper
AHUdown: No Orientation: Horizontal
Link: Yes Design: Curtain
Damper Manufacturer: Arlan Damper Size (i.e.
24"x12"): 10x8
Deficiencies:
• Damper springs broken/twisted
• New damper required
Comments for the Customer:
Damper spring is twisted,requires new 10x10 horizontal damper
Date: 11/22/2022
Attachment #479576 Attachment #479577
Attachment #479578 Attachment #479579 Attachment #479580
Project: Fire Damper Inspection, Repair and Testing at the VANYHHCS Manhattan VAMC Rascap LLC dba Acceptance Engineering
Marker Label:89
Area #: Building 6, 5th Floor(5) Tech: Jason Noyes
Result: Fail Damper ID: FD-5-61
Building: Building 6 Floor: 5
Location: Inside mechanical area Category: Fire Damper
AHUdown: No Orientation: Horizontal
Link: Yes Design: Curtain
Damper Manufacturer: Arlan Damper Size (i.e. 24"x12"): 12x10
Access Door Size: 12"x12" Deficiencies: • No link present
• Requires new link
Date: 10/07/2022
Attachment #454279 Attachment #454280 Attachment #454281 Attachment #454282 Attachment #454283
Project: Fire Damper Inspection, Repair and Testing at the VANYHHCS Manhattan VAMC Rascap LLC dba Acceptance Engineering
Marker Label:35
Area #: Building 6, 5th Floor(5) Tech: Jason Noyes
Result: Fail Damper ID: FD-5-32
Building: Building 6 Floor: 5
Location: Inside mechanical area Category: Fire Damper
AHUdown: No Orientation: Horizontal
Link: Yes Design: Curtain
Damper Manufacturer: Arlan Damper Size (i.e. 24"x12"): 28x22
Deficiencies: • Requires duct access door Date: 10/04/2022
Attachment #451230 Attachment #451231 Attachment #451232 Attachment #451233
Attachment #0000 c
Project: Fire Damper Inspection, Repair and Testing at the VANYHHCS Manhattan VAMC Rascap LLC dba Acceptance Engineering
Marker Label:11
Area #: Building 6, 5th Floor(5) Tech: Jason Noyes
Result: Fail Damper ID: FD-5-34
Building: Building 6 Floor: 5
Location: Inside mechanical room Category: Fire Damper
AHUdown: No Orientation: Horizontal
Link: Yes Design: Curtain
Damper Manufacturer: Arlan Damper Size (i.e. 24"x12"): 31x32
Deficiencies: • Damper springs broken/twisted
• New damper required
Date: 10/04/2022
Attachment #451312 Attachment #451314
Attachment #451315 Attachment #451316
Attachment #0000 c
Project: Fire Damper Inspection, Repair and Testing at the VANYHHCS Manhattan VAMC Rascap LLC dba Acceptance Engineering
Marker Label:12
Area #: Building 6, 5th Floor(5) Tech: Jason Noyes
Result: Fail Damper ID: FF-5-36
Building: Building 6 Floor: 5
Location: Inside mechanical room Category: Fire Damper
AHUdown: No Orientation: Vertical
Motor: N/A Link: Unknown
Design: Unknown Damper Manufacturer: Unknown
Damper Size (i.e. 24"x12"): 31x32 Deficiencies: • Requires duct access door
Date: 10/04/2022
Attachment #451351 Attachment #451352
Attachment #451353
Attachment #0000 a
Attachment #0000 c
Project: Fire Damper Inspection, Repair and Testing at the VANYHHCS Manhattan VAMC Rascap LLC dba Acceptance Engineering
Marker Label:13
Area #: Building 6, 5th Floor(5) Tech: Jason Noyes
Result: Fail Damper ID: FD-5-37
Building: Building 6 Floor: 5
Location: Inside mechanical room Category: Fire Damper
AHUdown: No Orientation: Vertical
Motor: N/A Link: Unknown
Design: Unknown Damper Manufacturer: Unknown
Damper Size (i.e. 24"x12"): 36x32 Deficiencies: • Requires duct access door
Date: 10/04/2022
Attachment #451358 Attachment #451359 Attachment #451361
Attachment #0000 a
Attachment #0000 c
Project: Fire Damper Inspection, Repair and Testing at the VANYHHCS Manhattan VAMC Rascap LLC dba Acceptance Engineering
Marker Label:30
Area #: Building 6, 5th Floor(5) Tech: Jason Noyes
Result: Fail Damper ID: FD-5-42
Building: Building 6 Floor: 5
Location: Inside mechanical area Category: Fire Damper
AHUdown: No Orientation: Horizontal
Link: Yes Design: Curtain
Damper Manufacturer: Arlan Damper Size (i.e. 24"x12"): 32x19
Deficiencies: • Requires duct access door Date: 10/04/2022
Attachment #451471 Attachment #451472
Attachment #451473
Attachment #0000 a
Attachment #0000 c
Project: Fire Damper Inspection, Repair and Testing at the VANYHHCS Manhattan VAMC Rascap LLC dba Acceptance Engineering
Marker Label:14
Area #: Building 6, 5th Floor(5) Tech: Jason Noyes
Result: Fail Damper ID: FD-5-33
Building: Building 6 Floor: 5
Location: Inside mechanical room Category: Fire Damper
AHUdown: No Orientation: Horizontal
Link: Yes Design: Curtain
Damper Manufacturer: Arlan Damper Size (i.e. 24"x12"): 14x6
Deficiencies:
• Damper does not fall
• New damper required
• Damper improperly installed
Date: 10/04/2022
Attachment #451497 Attachment #451499
Attachment #451501
Attachment #451502 Attachment #451503
Attachment #451504
Attachment #0000 a
Attachment #0000 b
Attachment #0000 c
Attachment #0000 c
Project: Fire Damper Inspection, Repair and Testing at the VANYHHCS Manhattan VAMC Rascap LLC dba Acceptance Engineering
Marker Label:53
Area #: Building 6, 5th Floor(5) Tech: Jason Noyes
Result: Fail Damper ID: FD-5-43
Building: Building 6 Floor: 5
Location: Inside mechanical area Category: Smoke Damper
AHUdown: No Orientation: Vertical
Motor: N/A Link: Unknown
Design: Unknown Damper Manufacturer: Unknown
Deficiencies: • Requires duct access door Date: 10/05/2022
Attachment #451919 Attachment #451920 Attachment #451921 Attachment #451922
Attachment #0000 c
Project: Fire Damper Inspection, Repair and Testing at the VANYHHCS Manhattan VAMC Rascap LLC dba Acceptance Engineering
Marker Label:52
Area #: Building 6, 5th Floor(5) Tech: Jason Noyes
Result: Fail Damper ID: FD-5-45
Building: Building 6 Floor: 5
Location: Inside mechanical room Category: Fire Damper
AHUdown: No Orientation: Horizontal
Motor: N/A Link: Yes
Design: Curtain Damper Manufacturer: Arlan
Damper Size (i.e. 24"x12"): 16x12 Access Door Size: 10"x10"
Deficiencies: • Requires duct access door Date: 10/05/2022
Attachment #451970 Attachment #451971 Attachment #451972 Attachment #451973 Attachment #451974
Project: Fire Damper Inspection, Repair and Testing at the VANYHHCS Manhattan VAMC Rascap LLC dba Acceptance Engineering
Marker Label:68
Area #: Building 6, 5th Floor(5) Tech: Jason Noyes
Result: Fail Damper ID: FD-5-49
Building: Building 6 Floor: 5
Location: Inside mechanical area Category: Fire Damper
AHUdown: Yes Orientation: Horizontal
Link: Unknown Design: Unknown
Damper Manufacturer: Unknown Damper Size (i.e. 24"x12"): 18x16
Access Door Size: 12"x12" Deficiencies: • Requires duct access door
Date: 10/05/2022
Attachment #452426 Attachment #452428 Attachment #452430 Attachment #452432 Attachment #452433
Project: Fire Damper Inspection, Repair and Testing at the VANYHHCS Manhattan VAMC Rascap LLC dba Acceptance Engineering
Marker Label:184
Area #: Building 6, 5th Floor(5) Tech: Jason Noyes
Result: Fail Damper ID: FD-5-52
Building: Building 6 Floor: 5
Location: Inside electrical room inside mechanical space
Category: Fire Damper
AHUdown: No Orientation: Vertical
Design: Unknown Damper Manufacturer: Unknown
Deficiencies: • No damper present
• New damper required
Date: 10/05/2022
Attachment #452455 Attachment #452456 Attachment #452457 Attachment #452458 Attachment #452459
Attachment #452460
Attachment #0000 a
Attachment #0000 b
Attachment #0000 c
Attachment #0000 c
Project: Fire Damper Inspection, Repair and Testing at the VANYHHCS Manhattan VAMC Rascap LLC dba Acceptance Engineering
Marker Label:173
Area #: Building 6, 5th Floor(5) Tech: Jason Noyes
Result: Fail Damper ID: FD-5-83
Building: Building 6 Floor: 5
Location: Inside mechanical space
Category: Fire Damper
AHUdown: No Orientation: Horizontal
Link: Yes Design: Curtain
Damper Manufacturer: Arlan
Damper Size (i.e.
24"x12"): 10x14
Deficiencies:
• Damper does not fall
• Damper springs broken/twisted
• New damper required
Comments for the Customer:
Horizontal Dynamic damper will not close springs are rusted requires new one and I can't get a correct measurement because it's in the ground
Date: 11/14/2022
Attachment #475156 Attachment #475157
Attachment #475158
Attachment #475159
Attachment #0000 c
Project: Fire Damper Inspection, Repair and Testing at the VANYHHCS Manhattan VAMC Rascap LLC dba Acceptance Engineering
Marker Label:140
Area #: Building 6, 5th Floor(5) Tech: Jason Noyes
Result: Fail Damper ID: FD-5-159
Building: Building 6 Floor: 5
Location: Inside mechanical room Category: Fire Damper
AHUdown: No Orientation: Horizontal
Link: Yes Design: Curtain
Damper Manufacturer: Arlan Damper Size (i.e.
24"x12"): 18x6
Deficiencies:
• Damper does not fall
• Damper springs broken/twisted
Comments for the Customer:
Damper will not close, require 12×6 horizontal damper
Date: 11/22/2022
Attachment #479570 Attachment #479571 Attachment #479572
Attachment #479573 Attachment #479574
Attachment #479575
Attachment #0000 a
Attachment #0000 b
Attachment #0000 c
Attachment #0000 c
Project: Fire Damper Inspection, Repair and Testing at the VANYHHCS Manhattan VAMC Rascap LLC dba Acceptance Engineering
Marker Label:54
Area #: Building 6, 5th Floor(5) Tech: Jason Noyes
Result: Fail Damper ID: SD-5-92
Building: Building 6 Floor: 5
Location: Inside mechanical area Category: Smoke Damper
AHUdown: No Orientation: Vertical
Motor: Air Actuated Link: No
Design: Blade Damper Manufacturer: No ID Labels
Access Door Size: 14"x14" Deficiencies: • Requires duct access door
• No air to actuator
Comments for the Customer: There is no air to actuator Date: 11/14/2022
Attachment #475268 Attachment #475269 Attachment #475270 Attachment #475271 Attachment #475272
Project: Fire Damper Inspection, Repair and Testing at the VANYHHCS Manhattan VAMC Rascap LLC dba Acceptance Engineering
Marker Label:180
Area #: Building 6, 5th Floor(5) Tech: Jason Noyes
Result: Fail Damper ID: FD-5-103
Building: Building 6 Floor: 5
Location: Inside mechanical room Category: Fire Damper
AHUdown: No Orientation: Horizontal
Link: Yes Design: Curtain
Damper Manufacturer: Arlan Deficiencies: • Requires duct access door
Comments for the Customer: Requires access door 16x16 Date: 11/14/2022
Attachment #475559 Attachment #475560
Attachment #475561
Attachment #475562
Attachment #475563
Attachment #475564
Attachment #0000 a
Attachment #0000 b
Attachment #0000 c
Attachment #0000 c
Project: Fire Damper Inspection, Repair and Testing at the VANYHHCS Manhattan VAMC Rascap LLC dba Acceptance Engineering
Marker Label:181
Area #: Building 6, 5th Floor(5) Tech: Jason Noyes
Result: Fail Damper ID: FD-5-104
Building: Building 6 Floor: 5
Location: Inside mechanical room Category: Fire Damper
AHUdown: No Orientation: Horizontal
Link: Yes Design: Curtain
Damper Manufacturer: Arlan Damper Size (i.e. 24"x12"): 12x12
Deficiencies: • Requires duct access door
Comments for the Customer:
Requires duct access door 12x12 sticky none hinge
Date: 11/15/2022
Attachment #475791 Attachment #475792
Attachment #475793 Attachment #475794 Attachment #475795
Project: Fire Damper Inspection, Repair and Testing at the VANYHHCS Manhattan VAMC Rascap LLC dba Acceptance Engineering
Marker Label:123
Area #: Building 6, 5th Floor(5) Tech: Jason Noyes
Result: Fail Damper ID: FD-5-118
Building: Building 6 Floor: 5
Location: Inside mechanical room Category: Fire Damper
AHUdown: Yes Orientation: Horizontal
Link: Yes Design: Curtain
Damper Manufacturer: Arlan Damper Size (i.e.
24"x12"): 18x7
Deficiencies:
• Damper springs broken/twisted
• New damper required
Comments for the Customer:
Damper spring are twister and rusted won't close needs a new horizontal fire damper
Date: 11/15/2022
Attachment #475908
Attachment #475909
Attachment #475910 Attachment #475911
Attachment #475912
Attachment #475913 Attachment #0000 a
Attachment #0000 b
Attachment #0000 c
Attachment #0000 c
Project: Fire Damper Inspection, Repair and Testing at the VANYHHCS Manhattan VAMC Rascap LLC dba Acceptance Engineering
Marker Label:125
Area #: Building 6, 5th Floor(5) Tech: Jason Noyes
Result: Fail Damper ID: FD-5-116
Building: Building 6 Floor: 5
Location: Inside mechanical room Category: Fire Damper
AHUdown: Yes Orientation: Horizontal
Link: Yes Design: Curtain
Damper Manufacturer: Arlan Damper Size (i.e.
24"x12"): 18x7
Deficiencies:
• Damper springs broken/twisted
• New damper required
Comments for the Customer:
Damper spring are twister and rusted won't close needs a new horizontal fire damper
Date: 11/15/2022
Attachment #475917
Attachment #475920
Attachment #475921
Attachment #475922
Attachment #475923
Attachment #475924
Attachment #0000 a
Attachment #0000 b
Attachment #0000 c
Attachment #0000 c
Project: Fire Damper Inspection, Repair and Testing at the VANYHHCS Manhattan VAMC Rascap LLC dba Acceptance Engineering
Marker Label:107
Area #: Building 6, 5th Floor(5)
Tech: Jason Noyes
Result: Fail Damper ID: FD-5-135
Building: Building 6 Floor: 5
Location: Inside mechanical space
Category: Fire Damper
AHUdown: No Orientation: Horizontal
Link: Yes Design: Curtain
Damper Manufacturer: Arlan Damper Size (i.e.
24"x12"): 12x6
Deficiencies:
• Damper does not fall
• New damper required
Comments for the Customer:
Completely in floor cant measure wont close and no link and requires new horizontal fire damper
Date: 11/15/2022
Attachment #476225 Attachment #476226 Attachment #476227 Attachment #476228
Attachment #0000 c
Project: Fire Damper Inspection, Repair and Testing at the VANYHHCS Manhattan VAMC Rascap LLC dba Acceptance Engineering
Marker Label:90
Area #: Building 6, 5th Floor(5) Tech: Jason Noyes
Result: Fail Damper ID: FD-5-141
Building: Building 6 Floor: 5
Location: Inside mechanical space going through ceiling
Category: Fire Damper
AHUdown: No Orientation: Horizontal
Link: N/A Design: Curtain
Damper Manufacturer: Arlan Damper Size (i.e.
24"x12"): 28x28
Deficiencies: • No damper present
• New damper required
Comments for the Customer:
No damper present in shaft. Needs 28x28 horizontal curtain damper
Date: 11/16/2022
Attachment #476862 Attachment #476863 Attachment #476864 Attachment #476866
Attachment #0000 c
Project: Fire Damper Inspection, Repair and Testing at the VANYHHCS Manhattan VAMC Rascap LLC dba Acceptance Engineering
Marker Label:253
Area #: Building 6, 5th Floor(5) Tech: Jason Noyes
Result: Fail Damper ID: FD-5-166
Building: Building 6 Floor: 5
Location: Inside mechanical space Category: Fire Damper
AHUdown: No Orientation: Horizontal
Link: Unknown Design: Unknown
Damper Manufacturer: Unknown Deficiencies:
• No damper present
• New damper required
Comments for the Customer:
Requires A horizontal fire damper 28x28 may need to break concrete to make the Duct square again
Date: 11/17/2022
Attachment #477697 Attachment #477698 Attachment #477699 Attachment #477700
Attachment #0000 c
Project: Fire Damper Inspection, Repair and Testing at the VANYHHCS Manhattan VAMC Rascap LLC dba Acceptance Engineering
Marker Label:135
Area #: Building 6, 5th Floor(5) Tech: Jason Noyes
Result: Fail Damper ID: FD-5-148
Building: Building 6 Floor: 5
Location: Inside mechanical room Category: Fire Damper
AHUdown: No Orientation: Horizontal
Link: Yes Design: Curtain
Damper Manufacturer: Arlan Damper Size (i.e. 24"x12"): 12"×3.5"
Deficiencies: • Screw in travel path Date: 11/17/2022
Attachment #477720 Attachment #477721
Attachment #477723
Attachment #0000 a
Attachment #0000 c
Project: Fire Damper Inspection, Repair and Testing at the VANYHHCS Manhattan VAMC Rascap LLC dba Acceptance Engineering
Marker Label:91
Area #: Building 6, 5th Floor(5) Tech: Jason Noyes
Result: Fail Damper ID: FD-5-62
Building: Building 6 Floor: 5
Location: Inside mechanical area Category: Fire Damper
AHUdown: No Orientation: Horizontal
Link: Yes Design: Curtain
Damper Manufacturer: Arlan Damper Size (i.e. 24"x12"): 12x4
Access Door Size: 12"x12" Deficiencies:
• Damper does not fall
• Damper springs broken/twisted
Comments for the Customer:
Damper in floors out of brand scope
Date: 11/17/2022
Attachment #477728 Attachment #477729 Attachment #477730 Attachment #477731
Attachment #477732
Attachment #477733 Attachment #477734
Attachment #0000 a
Attachment #0000 b
Attachment #0000 c
Project: Fire Damper Inspection, Repair and Testing at the VANYHHCS Manhattan VAMC Rascap LLC dba Acceptance Engineering
Marker Label:55
Area #: Building 6, 5th Floor(5) Tech: Jason Noyes
Result: Fail Damper ID: FD-5-169
Building: Building 6 Floor: 5
Location: Inside mechanical area Category: Fire Damper
AHUdown: No Orientation: Horizontal
Link: Unknown Design: Unknown
Damper Manufacturer: Unknown Damper Size (i.e.
24"x12"): 12x12
Access Door Size: 12"x12" Deficiencies:
• No damper present
• New damper required
Comments…