This is a fire damper inspection summary report for Building 1 at the VA Manhattan facility (423 23rd Street, New York, NY 10010), conducted between August 29, 2022 and September 30, 2022 under Job #JC21-C-4387. The inspection covered 326 total dampers across 19 floors, with results categorized as: 125 passed (38%), 109 failed (33%), 62 inaccessible (19%), 30 decommissioned (9%), and zero no-longer-in-rated-barrier. The inspections were performed in accordance with NFPA 80, 105 (2010 editions), NFPA 90A (2012 edition), 101 (2012 edition), and Joint Commission standards LS.02.01.10EP-13 and EC.02.03.05EP-18.
The report provides detailed deficiency findings for all failed and inaccessible dampers, with specific location information, damper specifications, and required remedial actions. Common deficiencies among failed dampers include: requirement for duct access doors, broken or missing fusible links, motors requiring replacement or power restoration, damper springs that are broken or twisted, dampers that do not fall properly, actuator and linkage adjustments needed, and improper damper positioning outside fire walls. Inaccessible dampers are primarily blocked by obstructions or require AHU shutdowns for inspection. The report includes photographs and detailed condition summaries for each failed damper, enabling prioritization of repair work. Accompanying documentation references contracts 36C24222C0089 and Purchase Order 630C20166 associated with Rascap LLC (dba Acceptance Engineering) for fire damper inspection, repair, and testing services.
View the file
Other files
Show all 14
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
DAMPER SNAPSHOT REPORT
Manhattan VA Bldg 1
Damper Inspection 8.29.22 through 9.30.22
Client Name: VA Manhattan
Client Address:423 23rd Street, New York, NY 10010
Job #: JC21-C-4387
Inspection Summary
Building 1 Floor Fire Smoke Fire/
Smoke CRD Unk Pass Fail Inaccessible NLR Decomm Total
G 9 0 2 0 4 7 5 1 0 2 15
1 18 3 2 0 0 8 12 3 0 0 23
2 14 10 0 0 0 6 13 5 0 0 24
3 4 0 0 0 0 2 1 1 0 0 4
4 14 0 0 0 3 4 5 6 0 2 17
5 24 4 3 0 0 16 8 5 0 2 31
6 13 0 2 0 1 9 1 5 0 1 16
7 6 0 0 0 2 3 3 2 0 0 8
8 16 1 2 0 0 6 9 4 0 0 19
9 11 0 0 0 0 4 4 3 0 0 11
10 13 1 4 0 0 8 5 5 0 0 18
11 12 0 2 0 0 9 2 3 0 0 14
12 8 0 3 0 0 5 3 3 0 0 11
13 13 0 3 0 0 7 3 6 0 0 16
14 8 0 0 0 0 5 1 2 0 0 8
15 11 0 0 0 4 4 6 4 0 1 15
16 9 0 2 0 1 7 3 1 0 1 12
17 7 0 1 0 2 4 5 1 0 0 10
18 16 3 2 0 8 6 6 2 0 15 29
19 20 3 1 0 1 5 14 0 0 6 25
SubTotal 246 25 29 0 26 125 109 62 0 30 326
GrandTotal 246 25 29 0 26 125 109 62 0 30 326
CRD - Ceiling Radiation Damper Unk - Unknown NLR - No Longer in Rated Barrier Decomm - Decommissioned
Result Summary
Pass 38%
Fail 33%
Inaccessible 19%
NLR 0%
Decommissioned 9%
DAMPER CONDITION SUMMARY REPORT
Damper Inspection 8.29.22 through 9.30.22
Client Name: VA Manhattan
Client Address:423 23rd Street, New York, NY 10010
Job # JC21-C-4387
Total # of Dampers:326 # Failed:109 BRAND SERVICES inspected the below listed fire/smoke damper(s). The inspection(s) performed are intended to determine the compliance of the fire/smoke damper(s). These inspections were performed in accordance with NFPA 80, 105 (2010 editions), NFPA 90A (2012 edition), 101 (2012 edition) and Joint Commission standards LS.02.01.10EP-13 and EC.02.03.05EP-18. The inspections are not intended to constitute a warranty as to the continued operation of the damper, but to verify the operability and compliance at the time of inspection, as dated above.
Marker Label
Result Damper ID Floor Location
Repair Data Begins Below
Date
Building 1
Fire Damper
226 Pass FD-G-01 G Inside hot water heater room 175-S 09/22/2022
227 Pass FD-G-02 G Inside boiler room 175-S 09/22/2022
228 Pass FD-G-03 G Inside boiler room 175-S 09/22/2022
241 Pass FD-G-08 G Inside mechanical space 09/22/2022
235 Pass FD-G-09 G Inside sprinkler pump room G128W 09/22/2022
236 Fail FD-G-10 G Inside sprinkler pump room G128W 09/22/2022
237 Pass FD-G-11 G Inside sprinkler pump room G128W 09/22/2022
238 Fail FD-G-12 G Inside sprinkler pump room G128W 09/22/2022
239 Pass FD-G-13 G Outside of sprinkler pump room G128W 09/22/2022
274 Fail FD-1-01 1 Inside mechanical room G1002 09/20/2022
275 Fail FD-1-02 1 Inside mechanical room G1002 09/20/2022
276 Fail FD-1-03 1 Inside mechanical room G1002 09/20/2022
277 Fail FD-1-04 1 Inside mechanical room G1002 09/20/2022
Inaccessible
FD-1-07 1 Above standpipe closet next to South stairwell 09/22/2022
203 Fail FD-1-08 1 Inside room 1070s 09/27/2022
Inaccessible
FD-1-09 1 Above standpipe closet by stairwell 09/22/2022
335 Fail FD-1-13 1 Inside mechanical space on roof through south stairwell 09/30/2022
337 Pass FD-1-15 1 Inside mechanical space on roof through south stairwell 09/30/2022
338 Pass FD-1-16 1 Inside mechanical space on roof through south stairwell 09/30/2022
339 Pass FD-1-17 1 Inside mechanical space on roof through south stairwell 09/30/2022
340 Pass FD-1-18 1 Inside mechanical space on roof through south stairwell 09/30/2022
205 Pass FD-1-19 1 Inside room 1028W Inside day care 09/28/2022
328 Pass FD-1-20 1 Inside daycare center in library room 09/29/2022
329 Pass FD-1-21 1 Inside daycare center in library room 09/29/2022
330 Fail FD-1-22 1 Inside daycare center in hallway 09/29/2022
331 Pass FD-1-23 1 Inside daycare center in kitchen area 09/29/2022
332 Fail FD-1-24 1 Inside bathroom Inside kitchen Inside daycare center 09/29/2022
269 Pass FD-2-01 2 In corridor on shaft next to service elevators across from federal credit union 09/20/2022
292 Pass FD-2-02 2 Shaft 09/20/2022
Inaccessible
FD-2-03 2 Inside corridor on side of service elevator 09/20/2022
271 Pass FD-2-04 2 Above standpipe door 2164-N 09/21/2022
272 Fail FD-2-05 2 Inside room 2165N 09/21/2022
304 Pass FD-2-09 2 Inside mechanical space on roof through room
2166N or 2165N 09/21/2022
303 Pass FD-2-10 2 Inside mechanical space on roof through room
2166N or 2165N 09/21/2022
318 Fail FD-2-14 2 Inside mechanical room on roof through room
2166N 09/28/2022
Inaccessible
FD-2-16 2
Inside mechanical room on roof through room 2166N
09/28/2022
323 Fail FD-2-21 2 Inside mechanical space on roof through room
2166N 09/28/2022
324 Fail FD-2-22 2 Inside mechanical space on roof through room
2166N 09/28/2022
325 Fail FD-2-23 2 Inside mechanical space on roof through room
2166N 09/28/2022
326 Fail FD-2-24 2 Inside mechanical space on roof through room
2166N 09/28/2022
273 Fail FD-2-08 2 Inside room 09/21/2022
199 Pass FD-3-01 3 Elevator wall shaft across from room 3038-W 09/20/2022
Inaccessible
FD-3-02 3
Above standpipe closet across from room 3032-W
09/20/2022
201 Pass FD-3-03 3 Inside office room 3019W 09/20/2022
278 Fail FD-3-04 3 Above standpipe doorway 09/27/2022
187 Fail FD-4-01 4 Elevator wall shaft across from closet left of room 4046-S 09/19/2022
188 Pass FD-4-02 4 Freight elevator wall shaft outside restroom
4054-C 09/19/2022
218 Fail FD-4-03 4 Outside above door way to mechanical room
4142N 09/20/2022
Inaccessible
FD-4-04 4 Inside mechanical space 09/20/2022
220 Pass FD-4-05 4 Inside mechanical space room 4142N 09/20/2022
Inaccessible
FD-4-06 4 Outside room 4142N 09/20/2022
222 Fail FD-4-07 4 Outside room 4142N 09/20/2022
224 Pass FD-4-09 4 Inside North stairwell 09/20/2022
225 Pass FD-4-10 4 Inside room next to fire stand door 09/20/2022
Inaccessible
FD-4-12 4 Double doors outside Center stairwell 09/21/2022
Inaccessible
FD-4-14 4 Double doors outside Center stairwell 09/21/2022
191 Fail FD-4-15 4 Bathroom inside room 4063-S 09/21/2022
Decommissioned
FD-4-325 4 Above standpipe closet next to South stairwell 09/19/2022
FD-4-327 4 Above standpipe closet next to West stairwell 09/19/2022
166 Pass FD-5-01 5 Elevator wall shaft across from closets left of room 5046-W 09/19/2022
168 Fail FD-5-02 5 Freight elevator wall shaft outside restroom
5054-C 09/19/2022
169 Pass FD-5-03 5 Double doors outside room 5064-S 09/19/2022
170 Pass FD-5-04 5 Double doors outside room 5064-S 09/19/2022
175 Pass FD-5-05 5 Inside room 5079S 09/19/2022
Inaccessible
FD-5-06 5 Above standpipe closet next to North stairwell 09/19/2022
174 Pass FD-5-07 5 Inside room 5117-N 09/19/2022
177 Pass FD-5-08 5 Inside isolation room 10 bathroom 09/19/2022
Decommissioned
FD-5-09 5 Inside supple room 5030-W 09/19/2022
184 Fail FD-5-10 5 Inside west stairwell 09/19/2022
183 Pass FD-5-11 5 Inside exam room 5014-W 09/19/2022
Decommissioned
FD-5-12 5 Inside exam room 5014-W 09/19/2022
178 Pass FD-5-13 5 Inside mechanical space room 5068S 09/20/2022
179 Pass FD-5-14 5 Mechanical room 5068-S 09/20/2022
180 Fail FD-5-15 5 Inside mechanical room 5068S 09/20/2022
181 Fail FD-5-16 5 Inside mechanical room 5068-S 09/20/2022
Inaccessible
FD-5-19 5
Inside mechanical room 5068S going through ceiling in the middle of the room towards the back
09/20/2022
251 Pass FD-5-20 5 Inside mechanical room 09/20/2022
253 Fail FD-5-21 5 Inside mechanical room 09/20/2022
252 Pass FD-5-22 5 Inside mechanical room 09/20/2022
293 Pass FD-5-23 5 Inside mechanical room 09/20/2022
250 Pass FD-5-25 5 Inside mechanical room 09/20/2022
249 Pass FD-5-26 5 Inside mechanical room 09/20/2022
Inaccessible
FD-5-30 5 Inside mechanical room 09/20/2022
155 Pass FD-6-01 6 Elevator wall shaft across from closets in elevator lobby 09/15/2022
248 Pass FD-6-02 6 Inside corridor near double doors across from room 6110C mens locker room 09/15/2022
167 Pass FD-6-03 6 Above restroom door near blood bank room
6054S 09/15/2022
Decommissioned
FD-6-04 6 Above fire equipment closet 6073S 09/15/2022
157 Pass FD-6-05 6 Inside lab area 6074-S 09/20/2022
164 Pass FD-6-08 6 Inside north stiarwell 09/19/2022
165 Pass FD-6-09 6 Inside stairwell 4 09/19/2022
163 Pass FD-6-10 6 Inside stairwell 4 09/19/2022
161 Inaccessible FD-6-11 6 Above standpipe closet door 6149a-N 09/19/2022
Inaccessible
FD-6-12 6 Hallway next to 6149a-N 09/19/2022
158 Pass FD-6-13 6 Histology Lounge 09/21/2022
192 Pass FD-6-15 6 Inside West stairwell 09/19/2022
193 Fail FD-6-16 6 Inside mechanical room just past Fire equipment closet 09/19/2022
149 Pass FD-7-01 7 Shaft next to elevators across from closets left of room 7036-C 09/15/2022
150 Fail FD-7-02 7 Shaft on side In Corridor in front of room
7040C 09/15/2022
Inaccessible
FD-7-03 7 Above fire equipment closet 7060S 09/15/2022
153 Pass FD-7-05 7 Above standpipe closet 7092-N 09/27/2022
154 Pass FD-7-06 7 In room 7094-N 09/15/2022
Inaccessible
FD-7-07 7
Above standpipe closet across from room
7028-BW
09/15/2022
131 Fail FD-8-01 8 Shaft by elevator lobby across closets left of
8048c 09/14/2022
132 Pass FD-8-02 8 Shaft on the side of service elevators across from room 8059S 09/14/2022
Inaccessible
FD-8-05 8 Above fire equipment room 8073S 09/14/2022
148 Fail FD-8-06 8 Inside room 8075-S access panel 09/14/2022
215 Pass FD-8-07 8 Inside room 8127N 09/14/2022
143 Fail FD-8-08 8 Inside north stairwell 09/14/2022
142 Fail FD-8-09 8 Inside north stairwell 09/14/2022
133 Fail FD-8-10 8 Above door to stand pipe closet 8130-N 09/26/2022
134 Pass FD-8-11 8 Inside patient room 8131-N 09/14/2022
216 Pass FD-8-12 8 Inside room 8131N 09/14/2022
Inaccessible
FD-8-13 8 Above smoke barrier doors by 8004W 09/14/2022
138 Pass FD-8-14 8 Above smoke barrier doors by 8004W 09/14/2022
244 Fail FD-8-15 8 Inside clean linen room 8020W 09/14/2022
139 Fail FD-8-16 8 Inside West stairwell 09/14/2022
Inaccessible
FD-8-17 8 Above standpipe closet 8021W by stairwell 09/14/2022
144 Pass FD-8-18 8 Inside room 8022-W 09/14/2022
123 Pass FD-09-02 9 Freight elevator shaft outside of room 9062-C 09/14/2022
130 Fail FD-9-01 9 Shaft on the side of people elevators across from waiting room 09/13/2022
Inaccessible
FD-9-03 9 Above standpipe closet by stairwell 09/13/2022
125 Fail FD-9-04 9 Inside restroom 9090-S 09/13/2022
Inaccessible
FD-9-05 9
Above standpipe closet across from exam room 9052W
09/14/2022
127 Pass FD-9-06 9 Inside staff restroom 9029W 09/14/2022
126 Pass FD-9-07 9 Above standpipe closet across from exam rm
9179N 09/26/2022
129 Pass FD-9-08 9 Inside lounge room 9161N 09/14/2022
Inaccessible
FD-9-10 9 Inside storage room 9130C 09/14/2022
288 Fail FD-9-11 9 Inside storage room 9130C across from services elevator 09/14/2022
289 Fail FD-9-12 9 Inside storage room 9130C across from service elevator 09/14/2022
108 Pass FD-10-01 10 Shaft on the side of people elevators across from room 10048C 09/13/2022
107 Pass FD-10-02 10 Shaft across 10057S 09/13/2022
Inaccessible
FD-10-03 10 Mechanical room 10111C 09/13/2022
114 Pass FD-10-04 10 Mechanical room 10111C across from service elevators 09/13/2022
Inaccessible
FD-10-07 10
Above fire equipment door next to south stairwell
09/13/2022
112 Fail FD-10-08 10 Inside patient room 10073-S 09/13/2022
214 Pass FD-10-09 10 Inside clean linen 10137-N 09/13/2022
116 Fail FD-10-10 10 Inside North stairwell access panel 09/13/2022
115 Pass FD-10-11 10 Above fire equipment room 10134-N 09/26/2022
117 Pass FD-10-13 10 Inside room 10137-N inside room 10136-N 09/13/2022
118 Pass FD-10-14 10 Inside patient room 10137-N 09/13/2022
121 Inaccessible FD-10-17 10 Above standpipe door 09/13/2022
122 Pass FD-10-18 10 Inside room 10017-W 09/13/2022
95 Pass FD-11-01 11 Shaft on the side of people's elevator across from room 11048-W 09/12/2022
96 Pass FD-11-02 11 Freight elevator shaft wall across from room
11057-S 09/12/2022
Inaccessible
FD-11-05 11 Above standpipe closet 11072-S 09/12/2022
308 Pass FD-11-06 11 Inside patient room 09/21/2022
100 Fail FD-11-06 11 Room 11079-S 09/13/2022
102 Pass FD-11-07 11 Patient area F by room 11132N 09/12/2022
213 Pass FD-11-08 11 Inside nurses station / CCU 09/12/2022
212 Pass FD-11-09 11 Inside nurses station CCU across from soiled utilities 11012-W 09/12/2022
105 Pass FD-11-10 11 Inside west stiarwell 09/12/2022
106 Pass FD-11-11 11 Inside stairwell west 09/12/2022
Inaccessible
FD-11-12 11 Above standpipe door next to west stairwell 09/12/2022
104 Pass FD-11-13 11 Inside patient room 11024-W 09/21/2022
85 Pass FD-12-01 12 Elevator shaft wall across from 12048-C 09/12/2022
84 Pass FD-12-02 12 Freight elevator shaft across from room 12057-
C 09/12/2022
Inaccessible
FD-12-03 12 Above standpipe next to room 12073-S 09/12/2022
94 Fail FD-12-04 12 Inside room 12073-S 09/12/2022
91 Pass FD-12-07 12 Above stand pipe across from room 12149-N 09/26/2022
92 Pass FD-12-08 12 Inside room 12130-N 09/13/2022
Inaccessible
FD-12-10 12 Above standpipe door way 12020-BW 09/12/2022
88 Pass FD-12-11 12 Inside office room 12020-W 09/12/2022
77 Pass FD-13-01 13 Shaft wall across from closest left of room
13052-C 09/07/2022
Inaccessible
FD-13-051 13 Above stand pipe in front of room 13098-S 09/07/2022
211 Pass FD-13-06 13 Inside copy room next to room 13076-S 09/07/2022
75 Pass FD-13-07 13 Inside south starewell on the 13th floor above stairs heading up 09/07/2022
76 Pass FD-13-09 13 Inside office room 13081-S 09/07/2022
286 Fail FD-13-10 13 Inside room 13081-S 09/07/2022
81 Pass FD-13-11 13 Above standpipe room 13138N 09/26/2022
Inaccessible
FD-13-12 13 Inside room 13139N 09/12/2022
Inaccessible
FD-13-13 13 Inside room 13139N 09/12/2022
Inaccessible
FD-13-16 13 Above stand pipe across from room 13019-W 09/07/2022
230 Pass FD-13-17 13 Inside room 13020W 09/07/2022
287 Fail FD-13-18 13 Inside room next fire door 13081W 09/07/2022
70 Pass FD-13?02 13 Shaft on the side of service elevator across from rm 13061-S 09/07/2022
62 Pass FD-14-01 14 Shaft across from room 14052W 09/07/2022
63 Pass FD-14-02 14 Coming out of shaft across from office desk
14107bS 09/07/2022
Inaccessible
FD-14-03 14 Above fire equipment closet 14096S 09/07/2022
65 Pass FD-14-04 14 Inside room 14097S 09/07/2022
67 Fail FD-14-05 14 Above standpipe next room 14135N 09/26/2022
68 Pass FD-14-06 14 Inside room 14138N 09/07/2022
Inaccessible
FD-14-07 14 Above stand pipe across room 14039W 09/07/2022
61 Pass FD-14-08 14 Inside room 14022W 09/07/2022
45 Pass FD-15-02 15 Shaft next to freight elevators near room 1506-
1S 09/06/2022
31 Fail FD-15-03 15 Above double doors near room 15046-W 09/07/2022
54 Pass FD-15-03 15 Above double doors outside work room
15108S 09/06/2022
Inaccessible
FD-15-04 15 Double doors outside room 15046-W 09/07/2022
Inaccessible
FD-15-06 15 Inside room 15077S 09/06/2022
50 Pass FD-15-09 15 Under double doors near room 15124N 09/06/2022
51 Fail FD-15-10 15 Above double doors outside room 15124N 09/26/2022
52 Fail FD-15-11 15 Above standpipe room 15133N 09/26/2022
33 Pass FD-15-12 15 Inside room 15019W 09/07/2022
285 Fail FD-15-13 15 Inside room 15019W 09/07/2022
Inaccessible
FD-15-14 15 Above standpipe door 09/07/2022
24 Fail FD-16-01 16 Shaft by people elevator lobby 09/01/2022
25 Pass FD-16-02 16 Shaft across from rm. 16060S 09/01/2022
20 Pass FD-16-03 16 Inside office rm. 16077S 09/01/2022
26 Pass FD-16-05 16 Above double doors next to mens bathroom 09/01/2022
Inaccessible
FD-16-07 16 Outside standpipe door 09/06/2022
21 Pass FD-16-08 16 Inside lab room 16021-W 09/06/2022
30 Pass FD-16-10 16 Outside standpipe closet by north stairwell 09/26/2022
66 Pass FD-16-11 16 Inside room left to standpipe closet 09/06/2022
Decommissioned
FD-16-X01 16 Hallway double doors by rm. 16063S 09/01/2022
36 Pass FD-15-01 17 On the side of elevators across from room
17040ac 09/26/2022
35 Fail FD-17-02 17 On the side of service elevator shaft across from room 17053S 09/26/2022
47 Inaccessible FD-17-03 17 Above standpipe door 09/26/2022
186 Pass FD-17-06 17 Inside South stairwell 09/26/2022
23 Pass FD-17-07 17 Above door to standpipe room 09/26/2022
206 Pass FD-17-11 17 Inside room 17087C 09/28/2022
207 Fail FD-17-12 17 Inside room 17087C 09/28/2022
5 Pass FD-18-01 18 Inside mechanical room across from service elevator 08/29/2022
Decommissioned
FD-18-034 18 Inside mechanical rm. 08/29/2022
69 Pass FD-18-05 18 Mechanical room across from service elevators 08/29/2022
1 Fail FD-18-07 18 Service lobby going above door to mechanical area 08/29/2022
279 Fail FD-18-08 18 Outside mechanical room in front of service elevator 08/29/2022
Decommissioned
FD-18-09 18 Above double 18093-S 08/29/2022
Inaccessible
FD-18-15 18 Inside room 18063-S 08/29/2022
Decommissioned
FD-18-17 18 Above double doors outside room 18151N 08/29/2022
Decommissioned
FD-18-18 18 Above double doors outside room 18151N 08/29/2022
FD-18-19 18 Above double doors outside room 18151N 08/29/2022
44 Pass FD-18-20 18 above door inside room 18111N 08/29/2022
Inaccessible
FD-18-21 18
Above door way to room 18122N next north stairwell 1
08/29/2022
41 Pass FD-18-22 18 Inside room 18123N 08/29/2022
43 Pass FD-18-23 18 Inside of room 18123N 08/30/2022
Decommissioned
FD-18-X02 18
Above double doors right next to room 18051- S
08/29/2022
Decommissioned
FD-18-x03 18 Above double doors next to room 18051-S 08/29/2022
260 Fail FD-19-02 19 Inside mechanical space by unit B 08/30/2022
265 Fail FD-19-027 19 Inside mechanical space on roof 08/31/2022
280 Fail FD-19-03 19 Inside mechanical space 08/30/2022
281 Fail FD-19-04 19 Inside mechanical space 08/30/2022
282 Pass FD-19-05 19 Inside mechanical space 08/30/2022
245 Fail FD-19-06 19 Inside mechanical room near A-unit 19S 08/30/2022
246 Fail FD-19-07 19 Inside mechanical room near A-unit 19S 08/30/2022
283 Pass FD-19-08 19 Inside mechanical space by unit A 08/30/2022
256 Pass FD-19-10 19 Inside mechanical space 09/01/2022
255 Pass FD-19-11 19 Inside mechanical space 09/01/2022
262 Fail FD-19-13 19 Inside mechanical space on roof 08/30/2022
264 Fail FD-19-14 19 Inside mechanical space on roof 09/01/2022
263 Fail FD-19-14 19 Inside mechanical space on roof 08/30/2022
267 Fail FD-19-15 19 Inside mechanical space on roof 09/01/2022
Decommissioned
FD-19-16 19 Inside mechanical space by unit B 08/30/2022
266 Pass FD-19-17 19 Inside mechanical space on roof 08/31/2022
Decommissioned
FD-19-17 19 Inside mechanical space by unit B 08/30/2022
Decommissioned
FD-19-X01 19 Inside mechanical space by A-unit 19S 08/30/2022
Decommissioned
FD-19-X02 19 Inside mechanical space 08/31/2022
Decommissioned
FD-19-X04 19 Inside mechanical space 08/30/2022
Smoke Damper
333 Fail SD-1-11 1 Inside mechanical space on roof through south stairwell 09/30/2022
334 Fail SD-1-12 1 Inside mechanical space on roof through south stairwell 09/30/2022
Inaccessible
SD-1-14 1
Inside mechanical space on roof through south stairwell
09/30/2022
301 Fail SD-2-06 2 Above double doors near room 2215N 09/21/2022
302 Fail SD-2-07 2 Above double doors near room 2215n 09/21/2022
305 Inaccessible SD-2-11 2 Inside mechanical room on roof thru room
2166n 09/21/2022
306 Pass SD-2-12 2 Inside mechanical space on roof through room
2166N or 2165N 09/21/2022
Inaccessible
SD-2-13 2
Inside mechanical room on roof thru room 2166n
09/28/2022
Inaccessible
SD-2-15 2 Inside mechanical room through room 2166N 09/28/2022
319 Fail SD-2-17 2 Inside mechanical space on roof through room
2166N 09/28/2022
320 Fail SD-2-18 2 Inside mechanical space on roof through room
2166N 09/28/2022
321 Fail SD-2-19 2 Inside through space on roof through room
2166N 09/28/2022
322 Fail SD-2-20 2 Inside mechanic roof through room 2166N 09/28/2022
Inaccessible
SD-5-17 5 Inside mechanical room 09/20/2022
Inaccessible
SD-5-18 5 Inside mechanical room 09/20/2022
296 Pass SD-5-28 5 Inside mechanical room 09/20/2022
299 Pass SD-5-31 5 Inside mechanical room 09/20/2022
327 Fail SD-8-19 8 Above standpipe fire door 09/28/2022
311 Fail SD-10-19 10 Above fire standpipe door 10134-N 09/27/2022
17 Fail SD-18-02 18 Inside mechanical rm. 08/31/2022
7 Fail SD-18-03 18 Inside mechanical room 08/31/2022
8 Fail SD-18-04 18 Inside mechanical room 08/31/2022
284 Fail SD-19-09 19 Inside mechanical space by unit A 08/30/2022
313 Fail SD-19-18 19 On top of roof inside the AHU unit 09/27/2022
312 Fail SD-19-19 19 On top of roof inside the AHU unit 09/27/2022
Fire+Smoke Damper
240 Fail FD-G-07 G Inside mechanical space 09/22/2022
Inaccessible
FSD-G-04 G Mecanical room G500A 09/22/2022
314 Fail FSD-1-05 1 Inside mechanical room 09/27/2022
315 Fail FSD-1-06 1 Inside mechanical room 09/27/2022
294 Fail FSD-5-23 5 Inside mechanical room 09/20/2022
295 Fail FSD-5-27 5 Inside mechanical room 09/20/2022
297 Fail FSD-5-29 5 Inside mechanical room 09/20/2022
Inaccessible
FD-6-07 6 Above double doors outside room 6138-N 09/19/2022
Inaccessible
FSD-6-06 6 Above double doors near room 6138-N 09/27/2022
Inaccessible
FSD-8-03 8 Double doors outside room 8104-S 09/14/2022
146 Fail FSD-8-04 8 Above double doors outside room 8103S 09/14/2022
Inaccessible
FD-10-16 10
Above double doors outside room 10046-W on other side of doors
09/13/2022
109 Fail FSD-10-05 10 Double doors outside room 10060-S 09/13/2022
Inaccessible
FSD-10-06 10 Double doors outside room 10060-S 09/13/2022
119 Fail FSD-10-15 10 Above smoke barrier doors by 10004-W 09/13/2022
Inaccessible
FD-11-03 11 Double doors outside of room 11102-S 09/12/2022
99 Fail FD-11-04 11 Above double doors next to room 11059-S 09/12/2022
89 Fail FD-12-05 12 Above double doors next to room 12115-N 09/12/2022
90 Fail FD-12-06 12 Above double doors next to room 12115-N 09/12/2022
Inaccessible
FD-12-09 12 Double doors outside room 12043-W 09/12/2022
71 Fail FD-13-03 13 Double doors outside room 13105S 09/13/2022
Inaccessible
FSD-13-04 13 Double doors outside of room 13105-S 09/13/2022
Inaccessible
FSD-13-05 13 Double doors outside of room 13105-S 09/13/2022
28 Fail FSD-16-06 16 Above double doors in Corridor next to bathroom 09/26/2022
29 Pass FSD-16-09 16 Inside chapel rm. 16109 09/06/2022
48 Fail FSD-17-05 17 Above double door way with no door by room
17014W 09/26/2022
4 Pass FD-18-07 18 Inside mechanical room across from service elevator 08/29/2022
12 Fail FD-18-14 18 Inside room 18063-S 08/29/2022
257 Fail FSD-19-01 19 Inside mechanical space 08/30/2022
Unknown Damper
233 Fail FD-G-14 G Inside mechanical space in small room to the right 09/27/2022
234 Fail FD-G-15 G Inside mechanical space 09/27/2022
Decommissioned
FD-G-337 G Inside mechanical space 09/22/2022
Decommissioned
FD-G-366 G Inside mechanical space 09/22/2022
223 Fail FD-4-08 4 In corridor be for mechanical room 4142N 09/20/2022
Inaccessible
FD-4-11 4 Inside bathroom in room 4022W 09/21/2022
Inaccessible
FD-4-12 4 Inside bathroom in room 4022W 09/21/2022
Inaccessible
FD-6-17 6 Inside lab room 6023W 09/21/2022
152 Fail FD-7-04 7 Above sink in room 7062-AS 09/15/2022
209 Fail FD-7-08 7 Inside room 7024-AW 09/15/2022
49 Fail FD-15-01 15 Shaft A croos from room 15051C 09/06/2022
Inaccessible
FD-15-04 15
Above double doors outside work room 15108S
09/06/2022
55 Fail FD-15-05 15 Access panel inside room 15077S 09/06/2022
SD-15-X03 15 Room across from 15046W 09/06/2022
22 Fail FD-16-04 16 Inside room 16077S 09/01/2022
46 Fail FD-17-04 17 Inside womens rm. 09/26/2022
310 Fail FD-17-10 17 Inside laundry room 17135S 09/26/2022
Decommissioned
FD-18-036 18
Inside mechanical room across from service elevators
08/29/2022
Decommissioned
FD-18-13 18 In side lounge room 08/29/2022
Decommissioned
FD-18-13 18 Above door to staff lounge #18092-s 08/29/2022
Decommissioned
FD-18-16 18
Above bathroom 18087S across from equipment bay 18065S
08/29/2022
Decommissioned
FD-18-38 18 Inside telecom rm. 08/29/2022
Decommissioned
FD-18-39 18 Inside telecom rm. 08/29/2022
Decommissioned
FD-18-X08 18 Above door way into room 18010-W 08/30/2022
Decommissioned
FSD-18-12 18 Above door way into 08/29/2022
FD-19-X03 19 Inside mechanical space between the units 08/31/2022
DAMPER INACCESSIBLE REPORT
Damper Inspection 8.29.22 through 9.30.22
Client Name: VA Manhattan
Client Address:423 23rd Street, New York, NY 10010
Job #: JC21-C-4387
Total # of Inaccessible Dampers:62
Marker Label
Damper ID Floor Deficiency Description Comments Date
Building: Building 1
Category: Fire+Smoke Damper
309 FSD-G-04 G 09/22/2022
160 FSD-6-06 6
• Damper inaccessible due to obstructions
09/27/2022
162 FD-6-07 6
• Requires duct access door
• Damper inaccessible due to obstructions
09/19/2022
145 FSD-8-03 8 09/14/2022
120 FD-10-16 10 09/13/2022
110 FSD-10-06 10
• Requires duct access door
• Damper inaccessible due to obstructions
09/13/2022
97 FD-11-03 11 09/12/2022
86 FD-12-09 12 09/12/2022
73 FSD-13-05 13
• Damper inaccessible due to obstructions
09/13/2022
72 FSD-13-04 13 09/13/2022
Category: Fire Damper
204 FD-1-09 1 09/22/2022
202 FD-1-07 1 09/22/2022
316 FD-2-16 2
• Damper inaccessible due to obstructions
09/28/2022
270 FD-2-03 2
• Damper inaccessible due to obstructions
09/20/2022
200 FD-3-02 3 09/20/2022
194 FD-4-12 4 09/21/2022
195 FD-4-14 4 09/21/2022
221 FD-4-06 4
Not shown on fire safety blueprints
09/20/2022
219 FD-4-04 4 09/20/2022
298 FD-5-30 5 09/20/2022
182 FD-5-19 5 09/20/2022
173 FD-5-06 5 09/19/2022
159 FD-6-12 6
• Damper inaccessible due to obstructions
• Damper no longer in a rated barrier
09/19/2022
161 FD-6-11 6
• Damper inaccessible due to obstructions
Known damper on fire safety plan
09/19/2022
210 FD-7-07 7 09/15/2022
151 FD-7-03 7 09/15/2022
141 FD-8-17 8 09/14/2022
137 FD-8-13 8 09/14/2022
147 FD-8-05 8 09/14/2022
242 FD-9-10 9 09/14/2022
128 FD-9-05 9 09/14/2022
124 FD-9-03 9 09/13/2022
113 FD-10-03 10 09/13/2022
121 FD-10-17 10 09/13/2022
111 FD-10-07 10 09/13/2022
103 FD-11-12 11 09/12/2022
98 FD-11-05 11 09/12/2022
87 FD-12-10 12 09/12/2022
93 FD-12-03 12 09/12/2022
83 FD-13-13 13 09/12/2022
82 FD-13-12 13 09/12/2022
80 FD-13-16 13 • Requires duct access door 09/07/2022
74 FD-13-051 13 Requires AHU shutdown 09/07/2022
60 FD-14-07 14 09/07/2022
64 FD-14-03 14 09/07/2022
32 FD-15-04 15 09/07/2022
27 FD-15-14 15 09/07/2022
56 FD-15-06 15 09/06/2022
19 FD-16-07 16 09/06/2022
47 FD-17-03 17 09/26/2022
40 FD-18-21 18
• Damper inaccessible due to obstructions
08/29/2022
13 FD-18-15 18 08/29/2022
Category: Smoke Damper
336 SD-1-14 1 09/30/2022
317 SD-2-15 2 09/28/2022
307 SD-2-13 2 09/28/2022
305 SD-2-11 2 • Actuator requires adjustment 09/21/2022
291 SD-5-18 5 09/20/2022
290 SD-5-17 5 09/20/2022
Category: Unknown
197 FD-4-11 4 09/21/2022
198 FD-4-12 4 09/21/2022
300 FD-6-17 6
• Damper inaccessible due to obstructions
09/21/2022
53 FD-15-04 15 09/06/2022
DAMPER DEFICIENCY REPORT
Damper Inspection 8.29.22 through 9.30.22
Client Name: VA Manhattan
Client Address:423 23rd Street, New York, NY 10010
Job #: JC21-C-4387
Total # of Failed Dampers:109
Marker Label
Damper ID Floor Deficiency Description Comments Date
Building: Building 1
Category: Fire+Smoke Damper
240 FD-G-07 G • Requires duct access door 09/22/2022
314 FSD-1-05 1 • Damper outside of fire wall 09/27/2022
315 FSD-1-06 1 • Damper outside of fire wall 09/27/2022
294 FSD-5-23 5 09/20/2022
295 FSD-5-27 5 • No power to motor 09/20/2022
297 FSD-5-29 5
• Actuator requires adjustment
• Linkage requires adjustment
09/20/2022
146 FSD-8-04 8
• No power to motor
• Motor does not actuate
09/14/2022
109 FSD-10-05 10
• Motor does not actuate
• New motor required
09/13/2022
119 FSD-10-15 10
• Motor does not actuate
• New motor required
09/13/2022
99 FD-11-04 11
• No power to motor
• Motor does not actuate
• New motor required
09/12/2022
89 FD-12-05 12
• Motor does not actuate
• New motor required
09/12/2022
90 FD-12-06 12 • Requires duct access door 09/12/2022
71 FD-13-03 13
• Requires duct access door
• Motor does not actuate
• New motor required
09/13/2022
28 FSD-16-06 16
• Damper wedged/blocked open
• Link broken
• No power to motor
09/26/2022
48 FSD-17-05 17 • No power to motor 09/26/2022
12 FD-18-14 18
• Actuator requires adjustment
• Linkage requires adjustment
08/29/2022
257 FSD-19-01 19 • New motor required Shown on blueprint but in the wrong spot
08/30/2022
Category: Fire Damper
236 FD-G-10 G • Requires duct access door 09/22/2022
238 FD-G-12 G • Requires duct access door 09/22/2022
274 FD-1-01 1
• Damper outside of fire wall
• Requires duct access door
• New damper required
• Requires damper relocation
09/20/2022
275 FD-1-02 1
• Damper outside of fire wall
• Requires duct access door
• New damper required
09/20/2022
276 FD-1-03 1 • Requires duct access door 09/20/2022
277 FD-1-04 1 • Requires duct access door 09/20/2022
203 FD-1-08 1
• Damper does not fall
• Damper wedged/blocked open
09/27/2022
335 FD-1-13 1 • Requires duct access door 09/30/2022
330 FD-1-22 1
• Requires new link
• Requires damper to be secured to duct
09/29/2022
332 FD-1-24 1
• Link broken
• Requires new link
09/29/2022
272 FD-2-05 2 • Requires duct access door 09/21/2022
318 FD-2-14 2 • Requires duct access door 09/28/2022
323 FD-2-21 2 • Requires duct access door 09/28/2022
324 FD-2-22 2 • Requires duct access door 09/28/2022
325 FD-2-23 2 • Requires duct access door 09/28/2022
326 FD-2-24 2 • Requires duct access door 09/28/2022
273 FD-2-08 2
• Requires duct access door
• Requires non-rated access panel in Gypsum Wall/Ceiling
09/21/2022
278 FD-3-04 3 • Requires duct access door 09/27/2022
187 FD-4-01 4 • Requires duct access door 09/19/2022
218 FD-4-03 4
• No damper present
• New damper required
09/20/2022
222 FD-4-07 4 09/20/2022
191 FD-4-15 4
• No link present
• Link broken
09/21/2022
168 FD-5-02 5 • Requires duct access door 09/19/2022
184 FD-5-10 5
• Link broken
• Requires new link
Not shown on fire safety blueprints
09/19/2022
180 FD-5-15 5
• Damper does not fall
• Damper springs broken/twisted
09/20/2022
181 FD-5-16 5 • Link broken 09/20/2022
253 FD-5-21 5 • Requires duct access door 09/20/2022
193 FD-6-16 6 • Requires duct access door 09/19/2022
150 FD-7-02 7 • Requires duct access door 09/15/2022
131 FD-8-01 8 • Requires duct access door 09/14/2022
148 FD-8-06 8
• Link broken
• Requires new link
09/14/2022
143 FD-8-08 8
• Requires fire rated access panel in Gypsum Wall/Ceiling
09/14/2022
142 FD-8-09 8
• Requires duct access door
• Requires non-rated access panel in Gypsum Wall/Ceiling
• Requires fire rated access panel in Gypsum Wall/Ceiling
• Damper inaccessible due to obstructions
09/14/2022
133 FD-8-10 8
• Link broken
• Requires new link
09/26/2022
244 FD-8-15 8 • Requires duct access door 09/14/2022
139 FD-8-16 8
• Requires duct access door
• Requires fire rated access panel in Gypsum Wall/Ceiling
09/14/2022
130 FD-9-01 9
• Requires non-rated access panel in Gypsum Wall/Ceiling
09/13/2022
125 FD-9-04 9 09/13/2022
288 FD-9-11 9 • Requires duct access door 09/14/2022
289 FD-9-12 9 • Requires duct access door 09/14/2022
112 FD-10-08 10
• Requires damper to be secured to duct
09/13/2022
116 FD-10-10 10
• Requires fire rated access panel in Gypsum Wall/Ceiling
09/13/2022
100 FD-11-06 11 • Requires new link 09/13/2022
94 FD-12-04 12 • Link broken 09/12/2022
286 FD-13-10 13
• Requires duct access door
• Requires non-rated access panel in Gypsum Wall/Ceiling
09/07/2022
287 FD-13-18 13
• Requires duct access door
• Requires non-rated access panel in Gypsum Wall/Ceiling
Requires a 16x16 gypsum access panel in ceiling and 10x10 maybe patch to get in to duct
09/07/2022
67 FD-14-05 14
• Link broken
• Requires new link
09/26/2022
31 FD-15-03 15
• Damper wedged/blocked open
• No link present
09/07/2022
51 FD-15-10 15
• Damper wedged/blocked open
• No power to motor
09/26/2022
52 FD-15-11 15
• Link broken
• Requires new link
09/26/2022
285 FD-15-13 15
• Requires duct access door
• Requires non-rated access panel in Gypsum Wall/Ceiling
09/07/2022
24 FD-16-01 16
• Requires duct access door
• Damper inaccessible due to obstructions
09/01/2022
35 FD-17-02 17 • Requires duct access door 09/26/2022
207 FD-17-12 17 • Requires duct access door 09/28/2022
1 FD-18-07 18
• Damper does not fall
• New damper required
08/29/2022
279 FD-18-08 18
• Damper does not fall
• New damper required
08/29/2022
260 FD-19-02 19 08/30/2022
265 FD-19-027 19
• No link present
• Requires new link
08/31/2022
280 FD-19-03 19
• Link broken
• Requires new link
Requires new fusible link but not much room to work
08/30/2022
281 FD-19-04 19
• Link broken
• Requires new link
Requires new fusible link but not much room to work
08/30/2022
245 FD-19-06 19
• Link broken
• Requires new link
Requires new fusible link but not much room to work
08/30/2022
246 FD-19-07 19
Requires new fusible link but not much room to work
08/30/2022
262 FD-19-13 19
• Damper does not fall
• Damper springs broken/twisted
• Damper wedged/blocked open
• New damper required
Requires new fire damper 08/30/2022
264 FD-19-14 19
• Damper does not fall
• Damper springs broken/twisted
• New damper required
Requires a new fire damper 09/01/2022
263 FD-19-14 19
• Damper does not fall
• Damper springs broken/twisted
• New damper required
Requires new fire damper 08/30/2022
267 FD-19-15 19
• Damper does not fall
• Damper springs broken/twisted
• New damper required
Requires a new fire damper 09/01/2022
Category: Unknown
233 FD-G-14 G • Requires duct access door 09/27/2022
234 FD-G-15 G • Requires duct access door 09/27/2022
223 FD-4-08 4 09/20/2022
152 FD-7-04 7 • Requires duct access door 09/15/2022
209 FD-7-08 7
• No damper present
• New damper required
09/15/2022
49 FD-15-01 15
• Requires duct access door
• Damper inaccessible due to obstructions
09/06/2022
55 FD-15-05 15
• No damper present
• New damper required
Requires a 11x36 fire damper vertical
09/06/2022
22 FD-16-04 16
• Requires non-rated access panel in Gypsum Wall/Ceiling
09/01/2022
46 FD-17-04 17
• Requires duct access door
• Requires non-rated access panel in Gypsum Wall/Ceiling
09/26/2022
310 FD-17-10 17 • Requires duct access door 09/26/2022
Category: Smoke Damper
333 SD-1-11 1
• Actuator requires adjustment
• Linkage requires adjustment
09/30/2022
334 SD-1-12 1
• Actuator requires adjustment
• Linkage requires adjustment
09/30/2022
301 SD-2-06 2 • No power to motor 09/21/2022
302 SD-2-07 2 • No power to motor 09/21/2022
319 SD-2-17 2
• Actuator requires adjustment
• Linkage requires adjustment
09/28/2022
320 SD-2-18 2
• Actuator requires adjustment
• Linkage requires adjustment
09/28/2022
321 SD-2-19 2
• Actuator requires adjustment
• Linkage requires adjustment
09/28/2022
322 SD-2-20 2
• Motor does not actuate
• New motor required
09/28/2022
327 SD-8-19 8
• Actuator requires adjustment
• Linkage requires adjustment
09/28/2022
311 SD-10-19 10
• Actuator requires adjustment
• Linkage requires adjustment
09/27/2022
17 SD-18-02 18
• Damper wedged/blocked open
• No power to motor
• Actuator requires adjustment
08/31/2022
7 SD-18-03 18
• Damper wedged/blocked open
• No power to motor
08/31/2022
8 SD-18-04 18
• Damper wedged/blocked open
• No power to motor
08/31/2022
284 SD-19-09 19
• Damper wedged/blocked open
• Actuator requires adjustment
• Linkage requires adjustment
08/30/2022
313 SD-19-18 19
• No power to motor
• Actuator requires adjustment
• Linkage requires adjustment
09/27/2022
312 SD-19-19 19
• No power to motor
• Actuator requires adjustment
• Linkage requires adjustment
09/27/2022
DAMPER DECOMMISSIONED REPORT
Damper Inspection 8.29.22 through 9.30.22
Client Name: VA Manhattan
Client Address:423 23rd Street, New York, NY 10010
Job #: JC21-C-4387
Total # of Decommissioned Dampers:30
Marker Label
Damper ID Floor Description Comments Date
Building: Building 1
Category: Unknown
231 FD-G-366 G
Shows damper on fire safety blueprints but there is no damper present
09/22/2022
232 FD-G-337 G
Shows damper on fire safety blueprints but there is no damper present
09/22/2022
34 SD-15-X03 15 09/06/2022
6 FD-18-X08 18
• No damper present
• Decommissioned
No damper present 08/30/2022
15 FD-18-16 18
• No damper present
• Decommissioned
Says on the the bule print there a damper here but there is no damper present in this location
08/29/2022
14 FD-18-13 18 • No damper present Says on the the bule print there a damper here but there is no damper present in this location
08/29/2022
2 FD-18-13 18
• No damper present
• Decommissioned
08/29/2022
3 FSD-18-12 18
• No damper present
• Damper inaccessible due to obstructions
• Decommissioned
08/29/2022
11 FD-18-036 18
• No damper present
• Decommissioned
No damper at this location specified on blueprint
10 FD-18-39 18
• No damper present
• Decommissioned
No damper at this location specified on blueprint
08/29/2022
9 FD-18-38 18
• No damper present
• Decommissioned
08/29/2022
261 FD-19-X03 19 • No damper present 08/31/2022
Category: Fire Damper
196 FD-4-327 4
• No damper present
• Decommissioned
09/19/2022
189 FD-4-325 4
• No damper present
• Decommissioned
09/19/2022
185 FD-5-12 5 • Decommissioned Known damper on fire safety plan
09/19/2022
217 FD-5-09 5 • Decommissioned 09/19/2022
156 FD-6-04 6 • Decommissioned 09/15/2022
18 FD-16-X01 16
• Damper wedged/blocked open
• Decommissioned
09/01/2022
37 FD-18-19 18 • Decommissioned 08/29/2022
39 FD-18-18 18 • Decommissioned 08/29/2022
38 FD-18-17 18 • Decommissioned 08/29/2022
58 FD-18-X02 18 • Decommissioned 08/29/2022
59 FD-18-x03 18 • Decommissioned 08/29/2022
57 FD-18-09 18 • Decommissioned 08/29/2022
16 FD-18-034 18
• No damper present
• Decommissioned
254 FD-19-X02 19 • No damper present 08/31/2022
247 FD-19-X01 19
• No damper present
• Decommissioned
08/30/2022
268 FD-19-X04 19
Not Shown on blueprint but damper is not present anymore
08/30/2022
259 FD-19-16 19
• No damper present
• Decommissioned
Shown on blueprint but damper is not present anymore
08/30/2022
258 FD-19-17 19
• No damper present
• Decommissioned
Shown on blueprint but damper is not present anymore
08/30/2022
FAIL/INACCESSIBLE DAMPER DETAIL REPORT
Damper Inspection 8.29.22 through 9.30.22
Client Name: VA Manhattan
Client Address: 423 23rd Street, New York, NY 10010
Job #: JC21-C-4387
Legend
- Pass
- Pass (Repair)
- Fail
- Decommissioned
- No Longer in Rated Barrier(NLR)
- Inaccessible
Building 1, Ground(G)
Damper Details Marker Label:233
Area #: Building 1, Ground(G) Tech: Jason Noyes
Result: Fail Damper ID: FD-G-14
Building: Building 1 Floor: G
Location:
Inside mechanical space in small room to the right
Category: Unknown
AHUdown: No Orientation: Vertical
Link: Unknown Design: Unknown
Damper Manufacturer: Unknown Deficiencies:
• Requires duct access door
Date: 09/27/2022
Attachment #447609
Attachment #0000 a
Attachment #0000 b
Attachment #0000 c
Attachment #0000 c
Marker Label:234
Area #: Building 1, Ground(G) Tech: Jason Noyes
Result: Fail Damper ID: FD-G-15
Building: Building 1 Floor: G
Location: Inside mechanical space Category: Unknown
AHUdown: No Orientation: Vertical
Link: Unknown Design: Unknown
Damper Manufacturer: Unknown Deficiencies: • Requires duct access door
Date: 09/27/2022
Attachment #447610
Attachment #0000 a
Attachment #0000 b
Attachment #0000 c
Marker Label:238
Area #: Building 1, Ground(G) Tech: Jason Noyes
Result: Fail Damper ID: FD-G-12
Building: Building 1 Floor: G
Location: Inside sprinkler pump room G128W Category: Fire Damper
AHUdown: No Orientation: Vertical
Motor: N/A Link: Yes
Design: Curtain Damper Manufacturer: Arlan
Deficiencies: • Requires duct access door Date: 09/22/2022
Attachment #445845 Attachment #445846
Attachment #445847
Attachment #445848
Marker Label:236
Area #: Building 1, Ground(G) Tech: Jason Noyes
Result: Fail Damper ID: FD-G-10
Building: Building 1 Floor: G
Location: Inside sprinkler pump room G128W Category: Fire Damper
AHUdown: No Orientation: Vertical
Link: Yes Design: Curtain
Damper Manufacturer: Arlan Access Door Size: 10"x10"
Deficiencies: • Requires duct access door Date: 09/22/2022
Attachment #445819 Attachment #445820 Attachment #445821 Attachment #445822
Marker Label:240
Area #: Building 1, Ground(G) Tech: Jason Noyes
Result: Fail Damper ID: FD-G-07
Building: Building 1 Floor: G
Location: Inside mechanical space Category: Fire+Smoke Damper
AHUdown: No Orientation: Vertical
Motor: N/A Motor Voltage: 120
Link: Unknown Design: Unknown
Damper Manufacturer: Unknown Damper Size (i.e. 24"x12"): 20x18
Deficiencies: • Requires duct access door Date: 09/22/2022
Attachment #460678
Attachment #460679
Attachment #460680
Attachment #0000 a
Marker Label:309
Area #: Building 1, Ground(G) Tech: Jason Noyes
Result: Inaccessible Damper ID: FSD-G-04
Building: Building 1 Floor: G
Location: Mecanical room G500A Category: Fire+Smoke Damper
AHUdown: Yes Orientation: Unknown
Motor: Belimo Motor Voltage: 120
Link: Yes Design: Blade
Damper Manufacturer: No ID Labels Date: 09/22/2022
Attachment #445782 Attachment #445783 Attachment #445784
Attachment #0000 a
Building 1, 1st Floor(1)
Marker Label:336
Area #: Building 1, 1st Floor(1) Tech: Jason Noyes
Result: Inaccessible Damper ID: SD-1-14
Building: Building 1 Floor: 1
Location:
Inside mechanical space on roof through south stairwell
Category: Smoke Damper
AHUdown: No Orientation: Vertical
Motor: Belimo Motor Voltage: 24
Link: N/A Design: Blade
Damper Manufacturer: No ID Labels Date: 09/30/2022
Attachment #449647
Attachment #449648
Attachment #449651
Attachment #0000 a
Marker Label:335
Area #: Building 1, 1st Floor(1) Tech: Jason Noyes
Result: Fail Damper ID: FD-1-13
Building: Building 1 Floor: 1
Location:
Inside mechanical space on roof through south stairwell
Category: Fire Damper
AHUdown: No Orientation: Horizontal
Link: Yes Design: Curtain
Damper Manufacturer: No ID Labels Deficiencies:
• Requires duct access door
Date: 09/30/2022
Attachment #449643 Attachment #449644
Attachment #0000 a
Attachment #0000 b
Marker Label:334
Area #: Building 1, 1st Floor(1) Tech: Jason Noyes
Result: Fail Damper ID: SD-1-12
Building: Building 1 Floor: 1
Location:
Inside mechanical space on roof through south stairwell
Category: Smoke Damper
AHUdown: No Orientation: Vertical
Motor: N/A Motor Voltage: 24
Link: N/A Design: Blade
Damper Manufacturer: No ID Labels Deficiencies:
• Actuator requires adjustment
• Linkage requires adjustment
Date: 09/30/2022
Attachment #449639 Attachment #449640 Attachment #449641 Attachment #449642
Marker Label:333
Area #: Building 1, 1st Floor(1) Tech: Jason Noyes
Result: Fail Damper ID: SD-1-11
Building: Building 1 Floor: 1
Location:
Inside mechanical space on roof through south stairwell
Category: Smoke Damper
AHUdown: No Orientation: Vertical
Motor: N/A Motor Voltage: 24
Link: No Design: Blade
Damper Manufacturer: No ID Labels Deficiencies:
• Actuator requires adjustment
• Linkage requires adjustment
Date: 09/30/2022
Attachment #449618 Attachment #449619
Attachment #449620
Attachment #449621
Marker Label:332
Area #: Building 1, 1st Floor(1) Tech: Jason Noyes
Result: Fail Damper ID: FD-1-24
Building: Building 1 Floor: 1
Location:
Inside bathroom Inside kitchen Inside daycare center
Category: Fire Damper
AHUdown: No Orientation: Vertical
Link: Yes Design: Curtain
Damper Manufacturer: No ID Labels Deficiencies:
• Link broken
• Requires new link
Date: 09/29/2022
Attachment #448948 Attachment #448949
Attachment #0000 a
Attachment #0000 b
Marker Label:330
Area #: Building 1, 1st Floor(1) Tech: Jason Noyes
Result: Fail Damper ID: FD-1-22
Building: Building 1 Floor: 1
Location: Inside daycare center in hallway Category: Fire Damper
AHUdown: No Orientation: Vertical
Link: Yes Design: Curtain
Damper Manufacturer: No ID Labels Deficiencies:
• Requires new link
• Requires damper to be secured to duct
Date: 09/29/2022
Attachment #448896 Attachment #448897
Attachment #0000 a
Attachment #0000 b
Marker Label:315
Area #: Building 1, 1st Floor(1) Tech: Vinny Healy
Result: Fail Damper ID: FSD-1-06
Building: Building 1 Floor: 1
Location: Inside mechanical room Category: Fire+Smoke Damper
AHUdown: No Orientation: Vertical
Motor: NO ID LABELS Motor Voltage: 120
Link: Yes Design: Blade
Damper Manufacturer: No ID Labels Deficiencies: • Damper outside of fire wall
Date: 09/27/2022
Attachment #461638
Attachment #461639
Attachment #0000 a
Attachment #0000 b
Marker Label:314
Area #: Building 1, 1st Floor(1) Tech: Vinny Healy
Result: Fail Damper ID: FSD-1-05
Building: Building 1 Floor: 1
Location: Inside mechanical room Category: Fire+Smoke Damper
AHUdown: No Orientation: Vertical
Motor: N/A Motor Voltage: 120
Link: Yes Design: Blade
Damper Manufacturer: No ID Labels Deficiencies: • Damper outside of fire wall
Date: 09/27/2022
Attachment #461633 Attachment #461634
Attachment #0000 a
Attachment #0000 b
Marker Label:203
Area #: Building 1, 1st Floor(1) Tech: Jason Noyes
Result: Fail Damper ID: FD-1-08
Building: Building 1 Floor: 1
Location: Inside room 1070s Category: Fire Damper
AHUdown: No Orientation: Vertical
Link: Yes Design: Blade
Damper Manufacturer: Unknown Damper Size (i.e. 24"x12"): 32x12
Deficiencies:
• Damper does not fall
• Damper wedged/blocked open
Date: 09/27/2022
Attachment #447070 Attachment #447071 Attachment #447072 Attachment #447073 Attachment #447074
Attachment #447075
Attachment #0000 a
Attachment #0000 b
Attachment #0000 c
Marker Label:204
Area #: Building 1, 1st Floor(1) Tech: Jason Noyes
Result: Inaccessible Damper ID: FD-1-09
Building: Building 1 Floor: 1
Location: Above standpipe closet by stairwell Category: Fire Damper
AHUdown: No Orientation: Vertical
Motor: N/A Link: Unknown
Design: Unknown Damper Manufacturer: Unknown
Access Door Size: 14" Round Date: 09/22/2022
Attachment #445755
Attachment #445756
Attachment #445757
Attachment #445758
Marker Label:202
Area #: Building 1, 1st Floor(1) Tech: Jason Noyes
Result: Inaccessible Damper ID: FD-1-07
Building: Building 1 Floor: 1
Location:
Above standpipe closet next to South stairwell
Category: Fire Damper
AHUdown: Yes Orientation: Vertical
Link: Unknown Design: Unknown
Damper Manufacturer: Unknown Access Door Size: 10"x10"
Date: 09/22/2022
Attachment #445751 Attachment #445752 Attachment #445753
Attachment #445754
Marker Label:277
Area #: Building 1, 1st Floor(1) Tech: Vinny Healy
Result: Fail Damper ID: FD-1-04
Building: Building 1 Floor: 1
Location: Inside mechanical room G1002 Category: Fire Damper
AHUdown: No Orientation: Vertical
Link: Unknown Design: Unknown
Damper Manufacturer: Unknown Deficiencies: • Requires duct access door
Date: 09/20/2022
Attachment #461614 Attachment #461615
Attachment #0000 a
Attachment #0000 b
Marker Label:276
Area #: Building 1, 1st Floor(1) Tech: Jason Noyes
Result: Fail Damper ID: FD-1-03
Building: Building 1 Floor: 1
Location: Inside mechanical room G1002 Category: Fire Damper
AHUdown: No Orientation: Vertical
Link: Unknown Design: Unknown
Damper Manufacturer: Unknown Deficiencies: • Requires duct access door
Date: 09/20/2022
Attachment #444947 Attachment #444948
Attachment #0000 a
Attachment #0000 b
Marker Label:275
Area #: Building 1, 1st Floor(1) Tech: Jason Noyes
Result: Fail Damper ID: FD-1-02
Building: Building 1 Floor: 1
Location: Inside mechanical room G1002 Category: Fire Damper
AHUdown: No Orientation: Vertical
Link: Yes Design: Curtain
Damper Manufacturer: No ID Labels Deficiencies:
• Damper outside of fire wall
• Requires duct access door
• New damper required
Date: 09/20/2022
Attachment #444943 Attachment #444944 Attachment #444945 Attachment #444946
Marker Label:274
Area #: Building 1, 1st Floor(1) Tech: Jason Noyes
Result: Fail Damper ID: FD-1-01
Building: Building 1 Floor: 1
Location: Inside mechanical room G1002 Category: Fire Damper
AHUdown: No Orientation: Vertical
Link: Yes Design: Curtain
Damper Manufacturer: Unknown Deficiencies:
• Damper outside of fire wall
• Requires duct access door
• New damper required
• Requires damper relocation
Date: 09/20/2022
Attachment #444938 Attachment #444939 Attachment #444940
Attachment #0000 a
Building 1, 2nd Floor N&E(2)
Marker Label:326
Area #: Building 1, 2nd Floor N&E(2) Tech: Jason Noyes
Result: Fail Damper ID: FD-2-24
Building: Building 1 Floor: 2
Location:
Inside mechanical space on roof through room 2166N
Category: Fire Damper
AHUdown: No Orientation: Vertical
Link: Yes Design: Curtain
Damper Manufacturer: No ID Labels Deficiencies:
• Requires duct access door
Date: 09/28/2022
Attachment #448226
Attachment #448227 Attachment #448228
Attachment #0000 a
Marker Label:317
Area #: Building 1, 2nd Floor N&E(2) Tech: Jason Noyes
Result: Inaccessible Damper ID: SD-2-15
Building: Building 1 Floor: 2
Location:
Inside mechanical room through room 2166N
Category: Smoke Damper
AHUdown: No Orientation: Horizontal
Motor: Barber Coleman Motor Voltage: 120
Link: Yes Design: Blade
Damper Manufacturer: No ID Labels Date: 09/28/2022
Attachment #448030 Attachment #448031 Attachment #448032
Attachment #0000 a
Marker Label:272
Area #: Building 1, 2nd Floor N&E(2) Tech: Jason Noyes
Result: Fail Damper ID: FD-2-05
Building: Building 1 Floor: 2
Location: Inside room 2165N Category: Fire Damper
AHUdown: No Orientation: Vertical
Link: Yes Design: Curtain
Damper Manufacturer: No ID Labels Deficiencies: • Requires duct access door
Date: 09/21/2022
Attachment #445185 Attachment #445186 Attachment #445187
Attachment #0000 a
Marker Label:301
Area #: Building 1, 2nd Floor N&E(2) Tech: Jason Noyes
Result: Fail Damper ID: SD-2-06
Building: Building 1 Floor: 2
Location:
Above double doors near room 2215N
Category: Smoke Damper
AHUdown: No Orientation: Vertical
Motor: Barber Coleman Motor Voltage: 120
Link: N/A Design: Blade
Damper Manufacturer: No ID Labels Deficiencies: • No power to motor
Enter Repairs: • *Repaired motor Date: 09/21/2022
Attachment #445243 Attachment #445244
Attachment #445245
Attachment #0000 a
Marker Label:302
Area #: Building 1, 2nd Floor N&E(2) Tech: Jason Noyes
Result: Fail Damper ID: SD-2-07
Building: Building 1 Floor: 2
Location: Above double doors near room 2215n Category: Smoke Damper
AHUdown: No Orientation: Vertical
Motor: Barber Coleman Motor Voltage: 120
Link: N/A Design: Blade
Damper Manufacturer: No ID Labels Deficiencies: • No power to motor
Date: 09/21/2022
Attachment #460809
Attachment #460810
Attachment #0000 a
Attachment #0000 b
Marker Label:305
Area #: Building 1, 2nd Floor N&E(2) Tech: Jason Noyes
Result: Inaccessible Damper ID: SD-2-11
Building: Building 1 Floor: 2
Location:
Inside mechanical room on roof thru room 2166n
Category: Smoke Damper
AHUdown: No Orientation: Horizontal
Motor: Siemens Motor Voltage: 120
Link: No Design: Blade
Damper Manufacturer: Arlan Deficiencies:
• Actuator requires adjustment
Date: 09/21/2022
Attachment #460675 Attachment #460676
Attachment #460677
Attachment #0000 a
Marker Label:307
Area #: Building 1, 2nd Floor N&E(2) Tech: Jason Noyes
Result: Inaccessible Damper ID: SD-2-13
Building: Building 1 Floor: 2
Location:
Inside mechanical room on roof thru room 2166n
Category: Smoke Damper
AHUdown: Yes Orientation: Horizontal
Motor: Barber Coleman Motor Voltage: 120
Link: Yes Design: Blade
Damper Manufacturer: Arlan Date: 09/28/2022
Attachment #447998 Attachment #447999
Attachment #0000 a
Attachment #0000 b
Marker Label:316
Area #: Building 1, 2nd Floor N&E(2) Tech: Jason Noyes
Result: Inaccessible Damper ID: FD-2-16
Building: Building 1 Floor: 2
Location:
Inside mechanical room on roof through room 2166N
Category: Fire Damper
AHUdown: Yes Orientation: Horizontal
Link: Yes Design: Curtain
Damper Manufacturer: No ID Labels Deficiencies:
• Damper inaccessible due to obstructions
Date: 09/28/2022
Attachment #448015 Attachment #448017 Attachment #448019
Attachment #0000 a
Marker Label:318
Area #: Building 1, 2nd Floor N&E(2) Tech: Jason Noyes
Result: Fail Damper ID: FD-2-14
Building: Building 1 Floor: 2
Location:
Inside mechanical room on roof through room 2166N
Category: Fire Damper
AHUdown: No Orientation: Horizontal
Link: Yes Design: Curtain
Damper Manufacturer: No ID Labels Deficiencies:
• Requires duct access door
Date: 09/28/2022
Atta…