Amendment 0002 - RFQ 36C24225Q0447.pdf

PDF 134 KB Posted

Attached to
H259--FY25 Service - Station Wide Generator Maintenance (Base + 4)
Solicitation number
36C24225Q0447
Issued by

About this file

This document is an Amendment (Amendment 0002) to Solicitation 36C24225Q0447 for Station Wide Generator Maintenance at the Canandaigua VA Medical Center. The amendment addresses vendor questions about the solicitation, specifically clarifying details about load bank testing for a 500kW Cummins generator located in Building 12. Key clarifications include: only one generator requires load bank testing, the vendor is responsible for load bank equipment rental and high-voltage electrician coordination, and the cable tie-in point is in the same room as the generator.

The solicitation is a firm fixed-price contract for annual full service, inspection, load bank, and fuel testing of six station-wide generators, set aside for Service-Disabled Veteran-Owned Small Businesses (SDVOSB). The contract period is from 04/01/2025 to 04/31/2026, with four option years, using NAICS code 811310 with a $12.5 million size standard. Quote submissions are due by Friday, April 4th, 2025, at 12:00 PM EST, to be submitted to Contracting Officer Taylor Richter at the Department of Veterans Affairs.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

5. PROJECT NUMBER (if applicable)

CODE 7. ADMINISTERED BY

2. AMENDMENT/MODIFICATION NUMBER

CODE

6. ISSUED BY

8. NAME AND ADDRESS OF CONTRACTOR

4. REQUISITION/PURCHASE REQ. NUMBER 3. EFFECTIVE DATE

9A. AMENDMENT OF SOLICITATION NUMBER

9B. DATED

PAGE OF PAGES

10A. MODIFICATION OF CONTRACT/ORDER NUMBER

10B. DATED

BPA NO. 1. CONTRACT ID CODE

FACILITY CODE CODE

Offers must acknowledge receipt of this amendment prior to the hour and date specified in the solicitation or as amended, by one of the following methods:

The above numbered solicitation is amended as set forth in Item 14. The hour and date specified for receipt of Offers

E. IMPORTANT:

is extended,

(a) By completing Items 8 and 15, and returning __________ copies of the amendment; (b) By acknowledging receipt of this amendment on each copy of the offer submitted; or (c) By separate letter or electronic communication which includes a reference to the solicitation and amendment numbers. FAILURE OF YOUR ACKNOWLEDGMENT TO BE RECEIVED AT THE PLACE DESIGNATED FOR THE RECEIPT OF OFFERS PRIOR TO THE HOUR AND DATE SPECIFIED MAY is not extended.

12. ACCOUNTING AND APPROPRIATION DATA

(REV. 11/2016)

is required to sign this document and return ___________ copies to the issuing office. is not, A. THIS CHANGE ORDER IS ISSUED PURSUANT TO: (Specify authority) THE CHANGES SET FORTH IN ITEM 14 ARE MADE IN THE CONTRACT ORDER NO. IN ITEM 10A.

15C. DATE SIGNED

B. THE ABOVE NUMBERED CONTRACT/ORDER IS MODIFIED TO REFLECT THE ADMINISTRATIVE CHANGES SET FORTH IN ITEM 14, PURSUANT TO THE AUTHORITY OF FAR 43.103(b).

RESULT IN REJECTION OF YOUR OFFER. If by virtue of this amendment you desire to change an offer already submitted, such change may be made by letter or electronic communication, provided each letter or electronic communication makes reference to the solicitation and this amendment, and is received prior to the opening hour and date specified.

C. THIS SUPPLEMENTAL AGREEMENT IS ENTERED INTO PURSUANT TO AUTHORITY OF:

D. OTHER

Contractor

16C. DATE SIGNED

14. DESCRIPTION OF AMENDMENT/MODIFICATION

16B. UNITED STATES OF AMERICA

Except as provided herein, all terms and conditions of the document referenced in Item 9A or 10A, as heretofore changed, remains unchanged and in full force and effect.

15A. NAME AND TITLE OF SIGNER 16A. NAME AND TITLE OF CONTRACTING OFFICER

15B. CONTRACTOR/OFFEROR

STANDARD FORM 30 PREVIOUS EDITION NOT USABLE

Prescribed by GSA - FAR (48 CFR) 53.243

(Type or print) (Type or print)

(Organized by UCF section headings, including solicitation/contract subject matter where feasible.)

(Number, street, county, State and ZIP Code)

(If other than Item 6)

(Specify type of modification and authority)

(such as changes in paying office, appropriation date, etc.)

(If required)

(SEE ITEM 11)

(SEE ITEM 13)

(X)

CHECK

ONE

13. THIS ITEM APPLIES ONLY TO MODIFICATIONS OF CONTRACTS/ORDERS,

IT MODIFIES THE CONTRACT/ORDER NO. AS DESCRIBED IN ITEM 14.

11. THIS ITEM ONLY APPLIES TO AMENDMENTS OF SOLICITATIONS

AMENDMENT OF SOLICITATION/MODIFICATION OF CONTRACT

(Signature of person authorized to sign) (Signature of Contracting Officer)

1 2 None

0002 04-02-2025

None

None

Department of Veterans Affairs Network Contracting Office (NCO) 2 2875 Union Road Suite 3500 Cheektowaga NY 14227

Department of Veterans Affairs Network Contracting Office (NCO) 2 2875 Union Road Suite 3500 Cheektowaga NY 14227

To all Offerors/Bidders

36C24225Q0447

04-02-2025

X

X X

See CONTINUATION Page

X 1

The purpose of this amendment is to answer vendor questions pertaining to solicitation 36C24225Q0447. Quote submissions shall be submitted on or before Friday, April 4th, 2025, at 12:00 PM EST.

Taylor Richter Contracting Officer

The purpose of this amendment is to answer vendor questions pertaining to Solicitation 36C24225Q0447.

1. The scope appears to indicate that only one generator—the Cummins 500kW unit—is required to undergo load bank testing. Another contractor on site referenced potential testing of the 1MW CAT generator, but our reading of the solicitation does not support that. Could you please confirm whether: Items a) and b) under B.3.5 Item 3 are both referring to the same 500kW Cummins generator? There is only one (1) generator requiring load bank testing. It is the 500kw Cummins located in Building 12.

2. If load bank testing is indeed only required for the 500kW Cummins unit, that simplifies the logistical requirements. However, we would still need to coordinate:

a. Rental of the appropriate load bank equipment (4160V power potentially ~$18k/day high dollar cost rental single day event) This is the responsibility of the vendor.

b. A third-party high-voltage qualified electrician for hookup and disconnect if one is not provided. A third-party electrician is not provided by VA. This is the responsibility of vendor.

3. To plan accordingly, could you please confirm the following for the Cummins 500kW generator located at Building 12, South End:

• Where will the cable tie-in point be? The tie in point is in the same room as the generator located in Building 12.

• What is the proximity of this tie-in point to the generator? The tie in point is in the same room as the generator in Building 12.

• Will a VA-provided or on-site high-voltage qualified electrician be available to assist with the cable hookup and disconnection? An electrician is not provided by VA. This is the responsibility of the vendor.

4. To properly do the annual services, we would need the actual Engine Serial Numbers on the generators. All serial numbers are located in Section B.3.4 Table 1 of the Scope of Work (SOW).

5. Are there any additional documents with information on the Generators? Gen’s may have whatever ever engine the mfg. had access to at that time, so we need this info in order to make sure we have all the supplies needed. There are no additional manuals/ documents.

6. For the Load Bank Testing of the Cummins unit since it is 4160V unit a step-down transformer is required to load bank the unit since the load banks are 480V. Does the VA have an electrical contractor they normally contract with that we could work with to hook up the transformer for the testing every three years? Otherwise, additional charges would need to be included. The VA does not have a contractor they normally contract.