This document is an amendment (A0002) to Invitation for Bid (IFB) Solicitation 36C24224B0030 for the Upgrade Generac Generators Project 526-20-107 at the James J. Peters VA Medical Center in Bronx, NY. The purpose of this amendment is to: 1) Provide remaining RFI responses, 2) Clarify the concrete scope and remove the requirement for "Blast Proof Doors", 3) Require bidders to include a $100,000 allowance line item in addition to the base bid amount, and 4) Confirm the Bid Due Date of 6/12/2024 at 2PM EST with no extension. The scope of work generally includes upgrading existing Generac generators, providing above ground fuel tanks, and modifying/extending exhaust stacks. The contractor must provide a proposed phasing plan to minimize disruption to the medical center's emergency power. The amendment also provides details on concrete pad requirements, screen wall height, and door specifications.

View the file

Other files for this federal contract opportunity

Show all 19

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

IFB 36C24224B0030- UPGRADE GENERAC GENERATORS-REMAINING RFI’S AND VA/AE RESPONSES

5. PROJECT NUMBER (if applicable)

CODE

7.

ADMINISTERED BY

2. AMENDMENT/MODIFICATION NUMBER

CODE

6. ISSUED BY

8. NAME AND ADDRESS OF CONTRACTOR

4. REQUISITION/PURCHASE REQ. NUMBER

3. EFFECTIVE DATE

9A. AMENDMENT OF SOLICITATION NUMBER

9B. DATED

PAGE OF

PAGES

10A. MODIFICATION OF CONTRACT/ORDER NUMBER

10B. DATED

BPA NO.

1. CONTRACT ID CODE

FACILITY CODE

CODE

Offers must acknowledge receipt of this amendment prior to the hour and date specified in the solicitation or as amended, by one of the following methods:

The above numbered solicitation is amended as set forth in Item 14. The hour and date specified for receipt of Offers

E. IMPORTANT:

is extended,

(a) By completing Items 8 and 15, and returning __________ copies of the amendment; (b) By acknowledging receipt of this amendment on each copy of the offer submitted; or (c) By separate letter or electronic communication which includes a reference to the solicitation and amendment numbers. FAILURE

OF YOUR

ACKNOWLEDGMENT TO BE RECEIVED AT THE PLACE DESIGNATED FOR THE RECEIPT OF OFFERS PRIOR TO THE HOUR AND DATE SPECIFIED MAY is not extended.

12. ACCOUNTING AND APPROPRIATION DATA

(REV. 11/2016)

is required to sign this document and return ___________ copies to the issuing office.

is not, A. THIS CHANGE ORDER IS ISSUED PURSUANT TO:

Specify authority) THE CHANGES SET FORTH IN ITEM 14 ARE MADE IN THE CONTRACT ORDER NO. IN ITEM 10A.

15C. DATE SIGNED

B. THE ABOVE NUMBERE

D CONTRACT/ORDER IS MODIFIED TO REFLECT THE ADMINISTRATIVE CHANGES

SET FORTH IN ITEM 14, PURSUANT TO THE AUTHORITY OF FAR 43.103(b).

RESULT IN REJECTION OF YOUR

OFFER. If by virtue of this amendment you desire to change an offer already submitted, such change may be made by letter or electronic communication, provided each letter or electronic communication makes reference to the solicitation and this amendmen t, and is received prior to the opening hour and date specified.

C. THIS SUPPLEMENTAL AGREEMENT IS ENTERED INTO PURSUANT TO AUTHORITY OF:

D. OTHER

Contractor

16C. DATE SIGNED

14. DESCRIPTION OF AMENDMENT/MODIFICATION

16B. UNITED

STATES OF AMERICA

Except as provided herein, all terms and conditions of the document referenced in Item 9A or 10A, as heretofore changed, remains unchanged and in full force and effect.

15A. NAME AND TITLE OF SIGNER

16A. NAME AND TITLE OF

CONTRACTING OFFICER

15B. CONTRACTOR/OFFEROR

STANDARD FORM 30

PREVIOUS EDITION NOT USABLE

Prescribed by GSA - FAR (48 CFR) 53.243 (Type or print) (Type or print) (Organized by UCF section headings, including solicitation/contract subject matter where feasible.)

(Number, street, county, State and ZIP Code) (If other than Item 6) (Specify type of modification and authority) such as changes in paying office, appropriation date, etc.)

(If required)

(SEE ITEM 11)

(SEE ITEM 13)

(X)

CHECK

ONE

13. THIS ITEM APPLIES ONLY TO MODIFICATIONS OF CONTRACTS/ORDERS,

IT MODIFIES THE CONTRACT/ORDER NO. AS DESCRIBED IN ITEM 14.

11. THIS ITEM ONLY APPLIES TO AMENDMENTS OF

SOLICITATIONS

AMENDMENT OF SOLICITATION/MODIFICATION OF CONTRACT

(Signature of person authorized to sign) (Signature of Contracting Officer) A 526-20-107 36C242 Department of Veterans Affairs Network Contracting Office 2 James J. Peters VA Medical Center 130 West Kingsbridge Road Bronx NY 10468-3904 36C242 Department of Veterans Affairs James J. Peters VA Medical Center Network Contracting Office 2 130 West Kingsbridge Road Bronx NY 10468-3904 To all Offerors/Bidders

36C24224B0030

X X X

X This Amendment A0002 is for the Upgrade Generac Generators, IFB Solicitation 36C24224B0030, Project 526-20-107 at the James J. Peters DVA Medical Center, Bronx, NY 10468.

The purpose of this amendment is to provide the following information to bidding contractors:

1. Provide remaining RFI responses as per previous amendment.

2. Provide concrete scope clarification and remove revised scope requirement for "Blast Proof Doors". See attached addendum drawing AS1 fo r concrete details and enclosure doors. Please note added work as per RFI #22 response.

3. Provide direction for all bidding contractors to include a separate line-item allowance of $100,00 0.00 Bids MUST include:

Base Bid amount + Line item allowance of $100,000.00 = Total Bid (see revised bid sheet attached).

4. Confirm BOD of 6/12/2024 at 2PM EST. There is no extension. ALL amendments mustbe acknowledged with bid submission.

Patricia Cordero Contracting Officer

CONTINUATION PAGE

Project Number 526-20-127 Upgrade Generac Generators at the James J. Peters VAMC BID PRICING SHEET, Revision 1 Bids providing less than 120 Calendar Days of Government Acceptance after the date bids are due will not be considered and will be rejected.

The bidder agrees to perform the work required at the prices specified below in strict accordance with the terms of the solicitation if this bid is accepted by the Government in writing within 120 calendar days after the date bidders are due.

1. BASE BID (Line Item #1) General Construction - Contractor will furnish all labor, materials, and supervision to perform work for the Upgrade Generac Generators as required by the statement of work, specifications, solicitation drawings, RFI responses and any/all additional work as indicated in amendment responses provided to bidding contractors.

The scope of work shall generally consist of, but not limited to the following:

Contractor shall furnish all labor and materials and perform all work associated with the Upgrade Generac Generators statement of work.

The contractor will be required to provide above ground fuel tanks for five (5) existing generators behind the main hospital building with associated infrastructure for alarm controls, piping, wiring, maintenance, and access. In addition, the scope includes providing Physical Security Resiliency Design Manual (PSRDM) Fence requirements, Fuel Tank with 96-hours storage capacity, NFPA 99 Annunciator Panels, Commission system using natural gas and fuel. Work also includes the modification and extension of existing Generac exhaust/smokestacks to reduce fume intake to the Medical Center. A site investigation, topographic and utility survey were performed to assess the existing conditions. The contractor will be required to utilize a private utility locator for identifying the location of the existing utilities. Test pits are anticipated to be required to identify the size and depth of any utilities in conflict with the locations of the fuel tanks. Project will require heavy excavation, electrical, and masonry trades.

The period of performance for Base Bid (Item 1) construction will be 330 calendar days from Notice to Proceed (NTP)

There are no bid alternates for this solicitation.

BASE BID $ ______________________

2. ALLOWANCE (REQUIRED WITH BID) + $ 100,000.00

TOTAL BID: (BASE BID + ALLOWANCE 0F $100,000.00 =

Project No. 526-20-107; Upgrade Generac Generators ---REMAINING RFI’s and VA/AE Responses

RFI 17. Please confirm there is no phasing involved and all the work of both tanks can be done at the same time.

VA/AE Response: YES. Phasing is required as the Medical Center cannot be without sufficient emergency power. Contractor must work on Generac generators individually and ensure that generators are fully functional and operational prior to beginning work on remaining generators. It is recommended that contractor replace Generac #3 first, before moving on to upgrade work. A proposed phasing plan will be required by the contractor to ensure minimal disruption to the Medical Center’s emergency electrical distribution systems. The phasing plan will be reviewed by Engineering COR, and approved/disapproved during the pre-construction meeting and prior to start of any work. Contractor will be responsible for ensuring that the sequence of operations and PLC controls for the Generac generators are fully integrated and functional prior to starting work on remaining generators, as well as to ensure that all Generac generators are properly integrated and functioning as per Manufacturer recommendations once all contract work is completed.

RFI 22) Drawing E-CS-101 and E-CS-102 key note # 2 states Concrete pad. Contractor to provide a structural design that meets tank requirement. --- This is not a design-build project so agency’s A/E should provide a detail drawing showing the construction of concrete pad along with foundation and rebar details if any, so that all contractors can bid on the same information and this will impact the bid offer price.

VA/AE Response: Provide 18" thick concrete pads reinforced with #5@12" Top and Bottom EW. Equipment pad shall extend minimum of 3" beyond extent of equipment. At round tanks, pad shall be square and extend the minimum 3" beyond Equipment. Please reference ASI 01 included with this response for added pad detail.

*ADDITIONAL WORK PER THIS RFI*: If not already stated as a requirement, contractor MUST include #5, coated rebar in all roadway concrete being replaced, to be consistent with existing roadway surface throughout. Also, contractor must install ALL low voltage cables necessary for cameras, etc at least 6 inches away from the electrical wires at different conduits and concrete encase.

RFI 23) Drawing E-CS-101 and E-CS-102 keynote # 3 states 12” screen wall refer to structural drawing. --- But details on dwg S201 does not show the height of the new screen wall. Please provide a proper elevation drawing indicating height of the new screen wall.

VA/AE Response: Screen wall is 12FT in height from FFE. from PEC Blast Requirement Letter Summary. Please reference E-CS-101 & E-CS-102 Keynote 3 for wall height reference.

RFI 24) Drawing E-CS-101 and E-CS-102 keynote # 4 states Access Doors. --- Please provide door and frame elevation and sectional drawing along with a door and hardware schedule.

VA/AE Response: Same response as RFI 26: Door Openings: Single doors to have a masonry opening of 4'-0" wide x 7'-4" high. Single door opening is 3'-8" wide x 7'-0" high. Pair of doors to have a masonry opening of 8'-0" wide x 7'-4" high. Door opening at pair is 7'-8" wide x 7'-0" high. Hollow metal doors and frames: Doors to be hollow metal, 14 gauge galvanized sheet steel, 1 3/4" thick. Close top edge of doors flush and seal to prevent water intrusion. Doors to be shop-primed for field painting. Door frames are to be 14 gauge galvanized sheet steel, face welded, 2" wide jamb profile, 4" high head profile. Frame depth is to be 5 3/4". Frames are to be shop-primed for field painting. Door hardware: Single doors to have continuous hinges, storeroom lockset F07, and a closer with hold-open arm. Pair of doors to have continuous hinges, auto flush bolts, coordinator, storeroom lockset F07, and closers with hold-open arms.

RFI 25) There is a spec section 07 24 00 for Exterior Insulation and Finish System, but no work is shown on drawings. Please identity work of Exterior Insulation and Finish System on project drawings with detailed thickness of each coat.

VA/AE Response: There is no Exterior Insulation and Finish system on the project. The spec section can be deleted.

RFI 26. New doors are shown on Drawings CS-101 and CS-102. No door schedule regarding size or hardware is indicated, nor is a door or hardware specification provided. Please clarify door scope.

VA/AE Response: Door Openings: Single doors to have a masonry opening of 4'-0" wide x 7'-4" high. Single door opening is 3'-8" wide x 7'-0" high. Pair of doors to have a masonry opening of 8'-0" wide x 7'-4" high. Door opening at pair is 7'-8" wide x 7'-0" high. Hollow metal doors and frames: Doors to be hollow metal, 14 gauge galvanized sheet steel, 1 3/4" thick. Close top edge of doors flush and seal to prevent water intrusion. Doors to be shop-primed for field painting. Door frames are to be 14 gauge galvanized sheet steel, face welded, 2" wide jamb profile, 4" high head profile. Frame depth is to be 5 3/4". Frames are to be shop-primed for field painting. Door hardware: Single doors to have continuous hinges, storeroom lockset F07, and a closer with hold-open arm. Pair of doors to have continuous hinges, auto flush bolts, coordinator, storeroom lockset F07, and closers with hold-open arms. Doors are not required to be “blast proof” as previously indicated in Amendment A0001.

RFI 27: We will be providing 5 (five) exhaust fans to power vent and interlock with the existing generators. Is it the intent to have the existing generators handle the start/stop and status functions of the new exhaust fans?

VA RESPONSE: Yes, unless otherwise specified in the solicitation drawings and specifications.

RFI 28: There are several fuel transfer pumps being installed along with a fuel filtration system, day tanks and a leak containment/monitoring system. The sequence of operations mentions a touch screen display for these systems. Is this touch screen display coming with your fuel pump packages? There are several points to be monitored like high and low tank level, leaks, pump failure etc. Are these to be available from the touch screen display?

VA RESPONSE: Fuel tank display must include all monitored points as required in scope. Contractor is responsible for touch screen display and all required wiring and installation to ensure fully functional and operational leak detection/fuel monitoring system.

End of RFI’s and VA Responses

See attached document: Generacs_Addendum ASI-1.

This is Amendment #A0002 to IFB Solicitation 36C24224B0030, Upgrade Generac Generators, Project 526-20-107 at the James J. Peters DVA Medical DVA Medical Center, Bronx, NY 10468