100 Percent Dwgs-Generac Generators Project.pdf

PDF 24 MB Posted

Attached to
Y1AZ--UPGRADE GENERAC GENERATORS PROJECT 526-20-107 Federal contract opportunity
Solicitation number
36C24224B0030
Issued by
Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 2

About this file

This document appears to be a set of 100% design drawings for the Generac Generators Project under Solicitation Number 36C24224B0030.

The solicitation is for the Upgrade Generac Generators project 526-20-107 at the James J. Peters DVA Medical Center in Bronx, NY. The Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 2 is the agency issuing the solicitation. The project involves upgrading the existing Generac generators at the medical center. The solicitation does not provide specific details on the products or services required, response dates, award dates, pricing terms, set asides, or any other salient information. This document appears to be solely the 100% design drawings for the project and does not contain the full solicitation details.

View the file

Other files for this federal contract opportunity

Show all 19

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

DocuSign Envelope ID: E53CF562-9CFF-44CF-9747-04347F4D7ADF

11/21/2023

DocuSign Envelope ID: E53CF562-9CFF-44CF-9747-04347F4D7ADF

11/21/2023

VA PROJECT NUMBER

Building Number

Drawing Number

Project Title

Date Checked Drawn

Drawing Title

Approved:

VA FORM 08-6231

A

B C

D E

21 4 5 6 7

321 4 5 6 7

A B

C D

E

Dwg. of

LocationLocation

Office of Construction and Facilities Management

PROJECT MANAGER: ACG Project NumberCONSULTANTS:

Headquarters:

Apogee Consulting Group, P.A.

1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 NC License #: C-1848

U.S. Department of Veterans Affairs

© COPYRIGHT Apogee Consulting Group, P.A.Revisions: Date#

D

NOVEMBER 21, 2023

SITE/100

REPLACE GENERAC

GENERATORS

526-20-107

James J. Peters VA Medical Center 130 West Kingsbridge Road

Bronx, New York 10468-3904

20-044

100% BID DOCUMENTS

Civil Engineer:

INTEGRITY

FEDERAL SERVICES

CIVIL ENGINEERING ● LANDSCAPE ARCHITECTURE ● PLANNING

148 S. Queen Street, Suite 201 Martinsburg, WV 25401

Phone: 304-725-8456 www.ifs-ae.com

IN

TE

GRITY FEDERA

L

SERV I CES

PC ES11/21/2023 11

GENERAL NOTES, LEGEND, AND

ABBREVIATIONS

REVERSE CURB

W W

OHE OHE

UGE UGE

TRANSCURB

x x x

OHC

UGC

FM FM FM

SSSS

G G

CIVIL LEGEND ABBREVIATIONS

EXISTING

BOUNDARY/RIGHT-OF-WAY LINE

ADJACENT BOUNDARY LINE

EASEMENT LINE

ROAD CENTERLINE

HEADER CURB

CURB & GUTTER

EDGE OF PAVEMENT

CHAIN LINK FENCE

OVERHEAD UTILITY LINE

UNDERGROUND UTILITY LINE

WATER MAIN

BUILDINGS

CONCRETE SIDEWALK

SANITARY SEWER MAIN

STORM SEWER LINE

TREES/SHRUBS

LIMITS OF GRADING

INDEX CONTOUR LINE

INTERMEDIATE CONTOUR LINE

SPOT ELEVATIONS

MISCELLANEOUS SIGNS

SITE LIGHT WITH POLE

DRIP LINE OF TREES

OHE

UGE

ORNAMENTAL FENCE

SOIL PROFILE BOUNDARY

WIRE FENCEXXXX

EDGE OF GRAVEL

GUARDRAIL

EDGE OF CONCRETE

SANITARY SEWER CLEANOUT

SANITARY SEWER MANHOLE

STORM SEWER MANHOLE

STORM SEWER INLET

STORM SEWER CATCH BASIN

STORM SEWER RIP-RAP

STORM SEWER END SECTION

FIRE HYDRANT

WATER VALVE

WATER METER

FLAG POLE

UTILITY POLE

FEATURE WALL

OHC

UGC

OVERHEAD COMMUNICATIONS LINE

UNDERGROUND COMMUNICATIONS LINE

GROUND LIGHT

UTILITY POLE GUY WIRE

SANITARY SEWER FORCE MAINFM FM FM

W W W

LIMITS OF WORK

G UNDERGROUND GAS LINE

DRIP LINE OF BRUSH

WETLANDS

ELECTRIC BOX / METER / MANHOLE

BOLLARD

MOUNTABLE CURB

STORM DRAINAGE CLEANOUT

DETAIL LABEL

SOIL PROFILE SYMBOL

PARKING COUNT

TEST-PIT

JERSEY BARRIER

GENERAL NOTES:

1. THE DEPARTMENT OF VETERANS AFFAIRS IS PROPOSING TWO NEW FUEL TANKS TO SUPPLY FIVE EXISTING GENERATORS. THE FUEL TANKS WILL BE INSTALLED AS CLOSE TO THE GENERATORS AS POSSIBLE. A WALL IS PROPOSED AROUND THE NEW FUEL TANKS AND EXISTING GENERATORS. THE PROPOSED SITE IMPROVEMENTS FOR JAMES J. PETERS DVA MEDICAL CENTER INCLUDES, BUT IS NOT LIMITED TO, DEMOLITION ACTIVITIES TO REMOVE EXISTING SITE FEATURES, CONSTRUCTION OF PAVEMENT, NEW CURBING, FUEL TANK INFRASTRUCTURE, AND ASSOCIATED ADJUSTMENTS TO

EXISTING UTILITY INFRASTRUCTURE.

2. TOPOGRAPHIC INFORMATION SHOWN HEREON WAS OBTAINED BY A FIELD RUN SURVEY BY CONTROL POINT ON MARCH 17, 2023. A COPY OF THE SURVEY IS PROVIDED WITH THIS PLAN. REFER TO THE SURVEY FOR THE VERTICAL AND HORIZONTAL DATUM.

3. SEE THIS SHEET FOR LEGEND OF SYMBOLS USED HEREIN.

4. DUE TO THE SENSITIVE NATURE OF THE SITE, CONTRACTOR SHALL MAINTAIN EACH WORK AREA IN A CLEAN AND ORDERLY APPEARANCE. TRASH AND WASTE MATERIALS SHALL BE STORED IN APPROVED CONTAINERS AND ROUTINELY DISPOSED OF OFF-SITE. CLEANUP SHALL BE REQUIRED AT THE END

OF EACH DAY AND/OR MORE FREQUENTLY AS REQUIRED.

5. AFFECT OF WORK ON PUBLIC ACCESS SHALL BE MINIMIZED AND SHALL BE COORDINATED WITH THE VA MEDICAL CENTER COR. ANY ALTERED PUBLIC TRAFFIC ROUTES SHALL BE WELL DEFINED WITH PROFESSIONALLY MADE SIGNAGE AND/OR OTHER APPROVED CONVENTIONAL METHODS.

6. THERE SHALL BE AT ALL TIMES WHEN WORK IS BEING DONE, A COMPETENT PERSON WHO IS APPRISED OF THE CONDITION AND PROGRESS OF ALL AREAS OF WORK ON SITE. THIS PERSON SHALL BE ABLE TO SPEAK FOR AND ACT IN THE BEHALF OF THE CONTRACTOR. THEY SHALL BE AWARE AND KNOWLEDGEABLE OF ALL THE SAFETY CONCERNS ON THE JOB SITE. THEY SHALL BE EMPOWERED TO IMMEDIATELY AND EFFECTIVELY MITIGATE THE

ACTIONS OF ANY WORKMAN ON SITE.

7. THE CONTRACTOR SHALL COORDINATE THE APPROPRIATE LOCATION FOR STAGING AND LAYDOWN AREAS WITH THE COR. SPACE IS LIMITED AND THE

DAILY ACTIVITIES AND DELIVERIES ARE TO REMAIN IN OPERATION DURING CONSTRUCTION.

CONSTRUCTION NOTES:

1. THE CONTRACTOR IS RESPONSIBLE FOR REVIEWING THE PLANS PRIOR TO CONSTRUCTION AND NOTIFYING THE U.S. DEPARTMENT OF VETERANS

AFFAIRS OF ANY CIRCUMSTANCES FOUND WITHIN THESE PLANS IN NEED OF VERIFICATION SO THAT APPROPRIATE REVISIONS CAN BE MADE, IF

WARRANTED.

2. DEVELOPMENT OF THE SITE INCLUDING CONSTRUCTION AND MATERIALS SHALL BE IN CONFORMANCE WITH THE U.S. DEPARTMENT OF VETERANS AFFAIRS REQUIREMENTS AND LOCAL/STATE CONSTRUCTION STANDARDS AND SPECIFICATIONS, WHERE APPLICABLE.

3. EROSION AND SEDIMENT CONTROL DEVICES ARE TO BE IN PLACE PRIOR TO ANY CONSTRUCTION. DUE TO THE LIMITED DISTURBANCE FOR THE PROJECT AN EROSION AND SEDIMENT CONTROL PLAN IS NOT PROVIDED. EROSION AND SEDIMENT CONTROL NOTES ARE PROVIDED ON THE SITE PLAN.

4. ALL LAND ON OR OFF-SITE WHICH IS DISTURBED BY CONSTRUCTION AND WHICH IS NOT BUILT UPON OR SURFACED SHALL BE ADEQUATELY STABILIZED TO CONTROL EROSION AND SEDIMENTATION. CONTRACTOR TO SUBMIT EROSION AND SEDIMENT CONTROL PLAN FOR REVIEW PRIOR TO START OF

WORK.

5. THE CONTRACTOR SHALL BE RESPONSIBLE FOR NOTIFYING THE U.S. DEPARTMENT OF VETERANS AFFAIRS OF ANY CHANGES OR CONDITIONS

ASSOCIATED WITH THE APPROVED PLANS FOR CONSTRUCTION.

6. THE CONTRACTOR SHALL PROVIDE ADEQUATE MEANS OF CLEANING TRUCKS AND/OR EQUIPMENT OF MUD AND DEBRIS, PRIOR TO ENTERING PAVED AREAS. IT IS THE CONTRACTOR'S RESPONSIBILITY TO CLEAN STREETS OF MUD AND/OR LAYING DUST AND TO TAKE ALL APPROPRIATE MEASURES NECESSARY TO ENSURE THAT STREETS ARE KEPT IN A CLEAN AND DUST FREE CONDITION AT ALL TIMES.

7. THE CONTRACTOR SHALL VISIT THE SITE AND SHALL VERIFY EXISTING CONDITIONS PRIOR TO STARTING CONSTRUCTION ACTIVITIES.

8. THE CONTRACTOR SHALL CLEAR THE SITE OF ALL TREES, BUILDINGS, FOUNDATIONS, ETC. WITHIN THE LIMITS OF CONSTRUCTION AND SHALL BE RESPONSIBLE FOR COORDINATING ANY DISCONNECTION AND/OR ABANDONMENT OF EXISTING UTILITIES AND STRUCTURES. IF NECESSARY, THE CONTRACTOR SHALL BE RESPONSIBLE FOR LOCATING AND ABANDONING ALL EXISTING WELLS AND/OR SEPTIC DRAIN FIELDS AND COORDINATING

THEIR ABANDONMENT WITH THE HEALTH DEPARTMENT.

9. AT LEAST 2 FULL BUSINESS DAYS PRIOR TO STARTING ANY EARTH DISTURBANCE ACTIVITIES, OR EXPANDING INTO AN AREA PREVIOUSLY UNMARKED, CONTACT NEW YORK STATE "DIG SAFELY NEW YORK" AT 1-800-962-7962 OR 811 FOR THE LOCATING EXISTING UNDERGROUND UTILITIES.

10. THIS PLAN DOES NOT CERTIFY TO THE LOCATION OF OR THE EXISTENCE OF ANY EXISTING UNDERGROUND UTILITIES. ANY UNDERGROUND UTILITIES SHOWN HEREON ARE BASED UPON AVAILABLE RECORDS AND DISCUSSION WITH THE U.S. DEPARTMENT OF VETERANS AFFAIRS. THIS DOES NOT CONSTITUTE A GUARANTEE OF THEIR ACTUAL LOCATIONS OR THAT THEY HAVE ALL BEEN SHOWN. THE CONTRACTOR SHALL BE RESPONSIBLE FOR THE DIGGING OF TEST HOLES PRIOR TO BEGINNING ANY CONSTRUCTION. THESE TEST HOLES WILL BE MADE TO VERIFY ALL CROSSINGS BETWEEN NEW AND EXISTING FACILITIES AND AT CRITICAL GRADE CHANGES. IF CONDITIONS ARE FOUND IN THE FIELD, WHICH ARE MATERIALLY DIFFERENT FROM THE PLANS, THE CONTRACTOR SHALL NOTIFY INTEGRITY FEDERAL SERVICES SO THAT APPROPRIATE REVISIONS IF WARRANTED CAN BE MADE TO THE

PLANS AT THE GOVERNMENT'S EXPENSE.

11. THIS PLAN DOES NOT CERTIFY TO THE SUB-SURFACE CONDITIONS OF THE SITE, OR THE LOCATION OF UNDERLYING ROCK. THE CONTRACTOR SHALL BE RESPONSIBLE FOR THE DIGGING OF TEST HOLES TO VERIFY SUB-SURFACE CONDITIONS PRIOR TO BEGINNING ANY CONSTRUCTION.

12. ALL TESTS, STUDIES, ETC., REQUIRED DURING CONSTRUCTION WILL BE CARRIED OUT BY A THIRD PARTY ENGINEERING FIRM AND PAID FOR BY THE

CONTRACTOR.

13. ALL PROPOSED ELEVATIONS AS SHOWN HEREIN ARE FINISHED GRADE UNLESS OTHERWISE NOTED.

14. MAINTAIN A MINIMUM VERTICAL CLEARANCE OF ONE (1) FOOT SIX (6) INCHES BETWEEN CROSSING OF ALL UTILITY LINES UNLESS OTHERWISE NOTED.

15. EARTHWORK SHALL BE COMPACTED IN ACCORDANCE WITH SPECIFICATION 31 20 00.

16. THE CONTRACTOR SHALL BE RESPONSIBLE FOR NOTIFYING THE U.S. DEPARTMENT OF VETERANS AFFAIRS OF ANY CONDITIONS FOUND IN THE FIELD PRIOR TO STAKEOUT THAT VARY FROM THE APPROVED PLANS OR THAT MAKE CONSTRUCTABILITY IMPOSSIBLE SO THAT APPROPRIATE REVISIONS CAN BE MADE PRIOR TO STAKEOUT AND/OR CONSTRUCTION. ANY OBSERVATIONS REGARDING APPARENT INCONSISTENCIES IN THE PLANS SHALL BE BROUGHT TO THE U.S. DEPARTMENT OF VETERANS AFFAIRS ATTENTION FOR VERIFICATION PRIOR TO STAKEOUT.

17. THE CONTRACTOR SHALL BE RESPONSIBLE FOR INITIATING, MAINTAINING AND SUPERVISING ALL SAFETY PRECAUTIONS AND PROGRAMS IN CONNECTION WITH THE PERFORMANCE OF ITS WORK AND THE WORK OF ITS SUBCONTRACTORS. THE ENGINEER OF RECORD SHALL NOT HAVE CONTROL OVER, CHARGE OF, OR RESPONSIBILITY FOR THE CONSTRUCTION MEANS, METHODS, TECHNIQUES, SEQUENCES OR PROCEDURES OR FOR

SAFETY PRECAUTIONS AND PROGRAMS IN CONNECTION WITH THE WORK.

18. THE TRANSPORTATION AND STORAGE OF MATERIALS MUST BE COORDINATED WITH THE COR. THIS INCLUDE STAGING AREAS. THE SPACE AROUND THE WORK AREA IS VERY LIMITED AND IS A HIGH TRAFFIC AREA. OFFSITE STORAGE OF MATERIALS IS REQUIRED.

19. ACCESS AND PARKING FOR CONSTRUCTION STAFF MUST BE COORDINATED WITH THE COR. PARKING WILL NOT BE AVAILABLE IN CLOSE PROXIMITY TO

THE WORK AREAS. TEMPORARY PARKING FOR DELIVERIES IS TO BE EXPECTED.

20. INSTALLING CONSTRUCTION FENCE IS RECOMMENDED FOR SAFETY PURPOSES. A DETAIL IS PROVIDED WITH THE SITE DETAILS. LOCATION TO BE

COORDINATED WITH THE COR TO AVOID CONFLICTS WITH ACCESS AND PARKING.

NORTH ARROW

DEMOLISHED

EXISTING

PROPOSEDEXISTING

TO REMAIN

FAR FLOOR AREA RATIO

FC FACE OF CURB

FD FOUNTAIN DRAIN

FF FIRST FLOOR OR FINISHED FLOOR

FG FINISHED GRADE

FH FIRE HYDRANT

FIN FINISHED

FLR FLOOR

FN FENCE

FP FLOOD PLAIN

FOC FACE OF CURB

FOY FOYER

FP FLAG POLE OR FIRE PROTECTION

FPS FEET PER SECOND

FR FROM

FT FEET

FWS FLOWER WATERING STATION

G GAS

GAL GALLON

GDR GUARD RAIL

GEN GENERATOR

GFA GROSS FLOOR AREA

GIP GALVANIZED IRON PIPE

GL GROUND LEVEL

GOVT GOVERNMENT

GR GRADE

GR GUARD RAIL

GS GROUND SHOT

H HORIZONTAL

HC HANDICAP

HCP HANDICAPPED

HDPE HIGH DENSITY POLYETHYLENE

HDR HEADER

HDWL HEADWALL

HGL HYDRAULIC GRADE LINE

HH HAND HOLE

HP HIGH POINT OR HIGH PRESSURE

HR HAND RAIL

HT HEIGHT

HW HOT WATER

HWSR HOT WATER SUPPLY & RETURN

HWY HIGHWAY

HYD HYDRANT

HYDR HYDRAULIC

I RAINFALL INTENSITY

ID INSIDE DIAMETER

IN INCH

INV INVERT

IP IRON PIPE

IPF IRON PIPE FOUND

IPS IRON PIPE SET

IRR IRRIGATION

IW IRRIGATION WATER

JB JUNCTION BOX

K ONE THOUSAND (KILO)

KWY KEYWAY

L LENGTH

LAT LATERAL

LF LINEAR FEET

LOC LOCATION

LONG LONGITUDE

LOS LINE OF SIGHT

LP LOW POINT OR LOW PRESSURE

LT LIGHT OR LEFT

LL LOWER LEVEL

MAINT MAINTENANCE

MAT MATERIAL

MAX MAXIMUM

MB MAIL BOX

MECH MECHANICAL

MED MEDIUM

MEMO MEMORANDUM

MEP MECHANICAL, ELECTRICAL, PLUMBING

MFG MANUFACTURING

MGT MANAGEMENT

MH MANHOLE

MI MILE

MIN MINIMUM

MISC MISCELLANEOUS

ML MATERIALS LIST

MN MAGNETIC NORTH

MOD MODEL OR MODIFY

MON MONUMENT

MS MEDIAN STRIP

MSL MEAN SEA LEVEL

MTG MEETING

MTL MATERIAL

MULT MULTIPLE

MUNIC MUNICIPAL

N NORTH

N/F NOW OR FORMERLY

NA NOT APPLICABLE

NAT NATURAL

NATL NATIONAL

NBC NATIONAL BUILDING CODE

NBL NORTH BOUND LANE

NE NOT EXCEEDING

NFA NET FLOOR AREA

NIC NOT IN CONTRACT

NO NUMBER

NOM NOMINAL

NRCP NON-REINFORCED CONCRETE PIPE

NTP NOTICE TO PROCEED

NTS NOT TO SCALE

OC ON CENTER

OD OUTSIDE DIAMETER

OFD OVERFLOW DRAIN

OH OVERHANG

OHC OVERHEAD COMMUNICATIONS

OHE OVERHEAD ELECTRIC

OS OVER-SIZED

OZ OUNCE

P PERIMETER

PAR PARALLEL

PAT PATTERN

PB PULL BOX

PC POINT OF CURVATURE

PCA PORTLAND CEMENT ASSOCIATION

PCC POINT OF COMPOUND CURVE

PCEP POINT OF CURVE, EDGE OF PAVEMENT

PCT PERCENT

PCTC POINT OF CURVE, TOP OF CURB

PERF PERFORATED

PED PEDESTAL

PG PAGE

PGL POINT OF GRADE LINE

PH PROFILE HOLE

PI POINT OF INTERSECTION

A AREA OR ARC

AC ACRE

ADA AMERICANS WITH DISABILITIES ACT

AGE ABOVE GROUND ELECTRIC

AGEC ABOVE GROUND ELECTRIC CONDUIT

ANSI AMERICAN NATIONAL STANDARDS INSTITUTE

APPROX APPROXIMATE

ARCH ARCHITECTURAL

ASPH ASPHALT

AVE AVENUE

AWWA AMERICAN WATER WORKS ASSOCIATION

A/C AIR CONDITIONING

BC BOTTOM OF CURB

BF BASEMENT FLOOR

BFP BACKFLOW PREVENTER

BFV BUTTERFLY VALVE

BITUM BITUMINOUS

BL BASE LINE

BLDG BUILDING

BLVD BOULEVARD

BM BENCHMARK

BOE BOTTOM OF EXCAVATION

BOV BLOW OFF VALVE

BRG BEARING

BRL BUILDING RESTRICTION LINE

BV BALL VALVE

BW BOTTOM OF WALL

C COEFFICIENT OF RUNOFF

CALC CALCULATE

CB CATCH BASIN OR CHORD BEARING

CC CENTER TO CENTER

CCTV CLOSED CIRCUIT TELEVISION

CD CONSTRUCTION DOCUMENTS OR CONTRACT DOCUMENTS

CDW CHILLED DRINKING WATER

CDWR CHILLED DRINKING WATER RETURN

CDWS CHILLED DRINKING WATER SUPPLY

CEM CEMENT OR CEMETERY

CF CONTRACTOR FURNISHED

CFS CUBIC FEET PER SECOND

CG CURB AND GUTTER

CHD CHORD

CIP CAST IRON PIPE

CJ CONTRACTION JOINT

CL CENTERLINE

CMP CORRUGATED METAL PIPE

CMU CONCRETE MASONRY UNIT

CND CONDUIT

CNR CORNER

CO CLEANOUT

COL COLUMN

COMM COMMUNICATIONS

CONC CONCRETE

COND CONDITION OR CONDENSER

CONF CONFERENCE

CONN CONNECTION

CON CONTAMINATED

CONSTR CONSTRUCTION

CONT CONTINUATION

CONTR CONTRACT OR CONTRACTOR

COR CONTRACTING OFFICER'S REPRESENTATIVE

COTG CLEANOUT TO GRADE

COV COVER OF CUT OFF VALVE

CPP CORRUGATED PLASTIC PIPE

CRN CROWN

CSB CONCRETE SPLASH BLOCK

CSI CONSTRUCTION SPECIFICATIONS INSTITUTE

CSP CONCRETE SEWER PIPE

CT COURT

CTR CENTER OR CONTOUR

CTRL CONTROL

CTS COOLING TOWER SUPPLY

CTV CABLE TELEVISION

CV CONTROL VALVE

CW CLOCKWISE

CWP COLD WATER PIPING

D DEPTH

DAT DATUM

DB DEED BOOK OR DESIGN-BUILD

DBL DOUBLE

DEG DEGREE

DEMO DEMOLITION

DEPT DEPARTMENT

DEP DEPRESSED

DESC DESCRIPTION

DET DETAIL

DI DROP INLET

DIA DIAMETER

DIFF DIFFERENCE

DIP DUCTILE IRON PIPE

DIST DISTANCE

DM DROP MANHOLE

DOC DOCUMENT

DOM DOMESTIC

DR DRIVE

DRE DECOMPOSED ROCK ELEVATION

DS DOWNSPOUT

DWG DRAWING

D/W DRIVEWAY

D DELTA

EA EACH

EBL EAST BOUND LANE

EC EDGE OF CONCRETE

EG EDGE OF GUTTER

EJ EXPANSION JOINT

ELEV ELEVATION

ELEC ELECTRICAL

ENTR ENTRANCE

EOI END OF INFORMATION

EP EDGE OF PAVEMENT

EPA ENVIRONMENTAL PROTECTION AGENCY

ES END SECTION

ESMT EASEMENT

ETO EARLY TURNOVER

EPT EXTERNAL PIPE THREAD

EQ EQUAL

EW END WALL

EXP EXPANSION

EX EXISTING

EXT EXTERIOR

E&S EROSION AND SEDIMENT CONTROL

PIV POST INDICATOR VALVE

PL PROPERTY LINE

POTW POTABLE WATER

PP POLYPROPYLENE (PLASTIC)

PR PROPOSED

PRC POINT OF REVERSE CURVE

PRELIM PRELIMINARY

PROP PROPOSED

PSI POUNDS PER SQUARE INCH

PSL PIPE SLEEVE

PT POINT OF TANGENCY

PV PRIVATE VAULT

PVC POLY VINYL CHLORIDE (PLASTIC PIPE)

PVI POINT OF VERTICAL INTERSECTION

PVMT PAVEMENT

PVT POINT OF VERTICAL TANGENCY

P&P PLAN AND PROFILE

Q FLOW, AMOUNT OF RUNOFF

QTR QUARTER

QTY QUANTITY

QUAD QUADRANT

QUAL QUALITY

R RISER, RADIUS

RAD RADIANS

RCP REINFORCED CONCRETE PIPE

RD ROAD, ROOF DRAIN

RDC REDUCER

RE RESIDENT ENGINEER

REP REPAIR

REQ REQUIRED

REV REVISION

RGP ROUGH GRADING PLAN

RPA RESOURCE PROTECTION AREA

RR RAILROAD

RTE ROUTE

RT RIGHT

RV RELIEF VALVE

RW RETAINING WALL

R/W RIGHT-OF-WAY

SAN SANITARY

SB SPLASH BLOCK

SBL SOUTH BOUND LANE

SCHED SCHEDULE

SD STORM DRAIN

SDMH STORM DRAIN MANHOLE

SEC SECTION

SEG SEGMENT

SEL SELECT

SEW SEWER

SF SQUARE FEET

SJ SCORED JOINT

SLV SLEEVE

SMH STEAM MANHOLE

SOV SHUT OFF VALVE

SP SITE PLAN

SPEC SPECIFICATION

SPKLR SPRINKLER

SQ SQUARE

SS SANITARY SEWER, STORM SEWER OR STEAM SUPPLY

ST STREET

STA STATION

STD STANDARD

STE STEAM

STK STACK

STM STORM

SUPT SUPPORT

SURV SURVEY

SVC SERVICE

S/W SIDEWALK

SWG SEWAGE

Sx CROSS SLOPE

SYM SYMBOL

T TANGENT

T&M TIME AND MATERIALS

TB TEST BORE

TBRL TO BE RELOCATED

TC TOP OF CURB

TCP TERRA COTTA PIPE, TRAFFIC CONTROL PLAN

TELE TELEPHONE

TH TEST HOLE

TNL TUNNEL

TOB TOP OF BANK

TOC TOP OF CURB

TOP TOP OF PAVEMENT

TOPO TOPOGRAPHY

TP TEST PIT, TELEPHONE POLE

TW TOP OF WALL

TYP TYPICAL

UD UNDERDRAIN

U/G UNDERGROUND

UGC UNDERGROUND COMMUNICATIONS

UGE UNDERGROUND ELECTRIC

UFC UNIFORM FIRE CODE

UL UPPER LEVEL

UON UNLESS OTHERWISE NOTED

UP UTILITY POLE

UTIL UTILITY

V VERTICAL

VA VETERANS ADMINISTRATION

VAR VARIES

VC VERTICAL CURVE

VCP VITRIFIED CLAY PIPE

VEL VELOCITY

VERT VERTICAL

VF VERTICAL FOOT

VIC VICINITY

VID VIDEO

VIF VERIFY IN FIELD

VOL VOLUME

W WATER, WEST OR WIDE

W/ WITH

W/O WITHOUT

WBL WEST BOUND LANE

WI WROUGHT IRON

WL WATER LINE

WM WATER MAIN OR WATER METER

WO WORK ORDER

WSE WATER SURFACE ELEVATION

WT WATER TIGHT

WW WASTE WATER

X-ING CROSSING

YI YARD INLET

YR YEAR

Z SIDE SLOPES

GAS VALVE / METER / MANHOLE

FUEL TANK

LOCATION 1

VICINITY MAP

NOT TO SCALE

MAGNETIC

FUEL TANK

LOCATION 2

E-CI-001

MAGNETIC

AutoCAD SHX Text 8" W/M

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

TC

AutoCAD SHX Text

CO

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

INV

AutoCAD SHX Text

8" SAN. SEW.

AutoCAD SHX Text

15" HDPE

AutoCAD SHX Text

CO

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text A1

AutoCAD SHX Text E

AutoCAD SHX Text co

AutoCAD SHX Text xx

AutoCAD SHX Text

XXXX

AutoCAD SHX Text

DETAIL #

AutoCAD SHX Text

SHEET REFERENCE

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 543.6

AutoCAD SHX Text

TO REMAIN

AutoCAD SHX Text 8" W/M

AutoCAD SHX Text

8" SAN

AutoCAD SHX Text

15" RCP

AutoCAD SHX Text L

AutoCAD SHX Text P

AutoCAD SHX Text

CO

AutoCAD SHX Text

EX

AutoCAD SHX Text

AutoCAD SHX Text

EX.

AutoCAD SHX Text A

AutoCAD SHX Text 11B

AutoCAD SHX Text 10C

AutoCAD SHX Text F

AutoCAD SHX Text F

AutoCAD SHX Text E

AutoCAD SHX Text F

AutoCAD SHX Text L

AutoCAD SHX Text P

AutoCAD SHX Text

CO

AutoCAD SHX Text

GM

AutoCAD SHX Text E

AutoCAD SHX Text G

AutoCAD SHX Text S

AutoCAD SHX Text D

AutoCAD SHX Text E

AutoCAD SHX Text

EM

AutoCAD SHX Text D

AutoCAD SHX Text S

Drawing Number

Project Title

Date Checked Drawn

Drawing Title

Approved:

VA FORM 08-6231

A

B C

D E

21 4 5 6 7

321 4 5 6 7

A B

C D

E

Dwg. of

LocationLocation

Office of Construction and Facilities Management

PROJECT MANAGER: ACG Project NumberCONSULTANTS:

Headquarters:

Apogee Consulting Group, P.A.

1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 NC License #: C-1848

U.S. Department of Veterans Affairs

© COPYRIGHT Apogee Consulting Group, P.A.Revisions: Date#

D

NOVEMBER 21, 2023

SITE/100

REPLACE GENERAC

GENERATORS

526-20-107

James J. Peters VA Medical Center 130 West Kingsbridge Road

Bronx, New York 10468-3904

20-044

100% BID DOCUMENTS

Civil Engineer:

INTEGRITY

FEDERAL SERVICES

CIVIL ENGINEERING ● LANDSCAPE ARCHITECTURE ● PLANNING

148 S. Queen Street, Suite 201 Martinsburg, WV 25401

Phone: 304-725-8456 www.ifs-ae.com

IN

TE

GRI TY FEDERAL

SERV I CE S

PC ES11/21/2023 11

SITE SURVEY

SURVEY PROVIDED FOR

INFORMATIONAL PURPOSES ONLY.

GENERATOR

GENERATOR

E-XP-101

LIMITS OF

CONSTRUCTION

KEY DESCRIPTION

1. METAL SHIPPING CONTAINER TO BE RELOCATED.

2. DUMPSTERS, AND TRASH COMPACTOR TO BE

RELOCATED.

3. BOLLARDS TO BE REMOVED (TYP).

4. METAL GAURDRAIL TO BE REMOVED.

5. CONCRETE BLOCK TO BE REMOVED.

6. CHAINLINK FENCE TO BE REMOVED.

7. TREES AND VEGETATION TO BE REMOVED.

8. CURB TO BE REMOVED.

DEMOLITION

LEGEND:

CONCRETE PAVEMENT AND BASE MATERIAL

TO BE REMOVED

VA PROJECT NUMBER

Building Number

Drawing Number

Project Title

Date Checked Drawn

Drawing Title

Approved:

VA FORM 08-6231

A

B C

D E

21 4 5 6 7

SHEET NOTES:

KEY NOTES:

321 4 5 6 7

A B

C D

E

Dwg. of

LocationLocation

Office of Construction and Facilities Management

PROJECT MANAGER: ACG Project NumberCONSULTANTS:

Headquarters:

Apogee Consulting Group, P.A.

1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 NC License #: C-1848

U.S. Department of Veterans Affairs

© COPYRIGHT Apogee Consulting Group, P.A.Revisions: Date#

KEY PLAN

D

AREA OF WORK

NOVEMBER 21, 2023

SITE/100

REPLACE GENERAC

GENERATORS

526-20-107

James J. Peters VA Medical Center 130 West Kingsbridge Road

Bronx, New York 10468-3904

20-044

100% BID DOCUMENTS

Civil Engineer:

INTEGRITY

FEDERAL SERVICES

CIVIL ENGINEERING ● LANDSCAPE ARCHITECTURE ● PLANNING

148 S. Queen Street, Suite 201 Martinsburg, WV 25401

Phone: 304-725-8456 www.ifs-ae.com

IN

TE

GRI TY FEDERAL

SERV I CE S

PC ES11/21/2023 11

DEMOLITION PLAN

DEMOLITION NOTES:

1. WHERE A PORTION OF A CONCRETE AND ASPHALT AREA IS

BEING DEMOLISHED ALL EDGES TO BE SAW CUT.

2. ALL CONCRETE AND ASPHALT REMOVAL TO INCLUDE

PAVEMENT SUB BASE.

3. EXISTING GRASSED AREAS IMPACTED BY THIS PROJECT TO

BE REMOVED. ANY AREAS DISTURBED BY THIS PROJECT

SHALL BE TEMPORARILY STABILIZED DURING

CONSTRUCTION AND PERMANENTLY STABILIZED AT THE END

OF CONSTRUCTION.

4. FOR DEMOLITION AND CONSTRUCTION OF ELECTRICAL LINES

REFER TO ELECTRICAL SHEETS.

5. ALL EXISTING SITE FEATURES, UTILITIES, AND OTHER

EXISTING CONDITIONS NOT PROPOSED TO BE REMOVED OR

DEMOLISHED ARE TO REMAIN OR BE REPLACED IN KIND IF

DAMAGED.

6. ALL UTILITIES PROPOSED TO BE DEMOLISHED ARE TO BE

REMOVED WITHIN THE LIMITS OF DISTURBANCE AND THE

ENDS SHOULD BE CAPPED OR TERMINATED.

7. ALL EXCAVATED MATERIAL SHOULD BE REMOVED. ONSITE

STORAGE OF MATERIALS IS NOT PROPOSED.

8. TEST PITS FOR LOCATING EXISTING UTILITIES ARE PROVIDED

ON THE SITE PLAN.

9. CONTRACTOR IS REQUIRED TO USE A PRIVATE UTILITY

LOCATOR TO IDENTIFY THE LOCATIONS OF ALL EXISTING

UTILITIES WITHIN THE LIMITS OF DISTURBANCE.

10. CONTACT NEW YORK STATE "DIG SAFELY NEW YORK" AT

1-800-962-7962 OR 811 FOR UNDERGROUND UTILITY

CLEARANCE AND MARKOUT BEFORE EXCAVATION, NOTIFY

COR 72 HRS BEFORE EXCAVATION BEGINS. MARK OUT ALL

UTILITIES BEFORE EXCAVATING.

11. HAND DIG ALL EXCAVATION FOR TEST PITS AND AROUND

EXISTING UTILITIES.

12. COORDINATE DEMOLITION DEBRIS DUMPSTER LOCATION

WITH COR.

13. PROVIDE SAFETY AND TRAFFIC CONTROL PLAN. PROVIDE 8'

HIGH CHAIN LINK FENCE AROUND WORK AREAS.

14. SHOW AREA WITH STEEL PLATES OVER TRENCHING (TO

ALLOW TRUCK TRAFFIC ACCESS) IN TRAFFIC CONTROL PLAN.

15. THE SHIPPING CONTAINER, TRASH COMPACTOR, AND

DUMPSTERS ARE PROPOSED TO BE RELOCATED. THE

CONTRACTOR SHALL COORDINATE THE FINAL LOCATION

WITH THE COR.

GRAPHICAL SCALE: 1"=10'

10 5 0 10 20 30

MAGNETIC

E-CD-101

AutoCAD SHX Text

OVERHANG

AutoCAD SHX Text

CONC WALK

AutoCAD SHX Text

CONC WALK

AutoCAD SHX Text

CONC STEPS W/3' HIGH METAL RAILING

AutoCAD SHX Text

METAL RAMP W/3' HIGH METAL RAILING

AutoCAD SHX Text

CONC WALL W/4' HIGH CLF

AutoCAD SHX Text

8' HIGH CLF

AutoCAD SHX Text

CONC CURB W/GUTTER

AutoCAD SHX Text

MGR

AutoCAD SHX Text

COMPACTOR

AutoCAD SHX Text

COINTAINER

AutoCAD SHX Text

MEDICAL STORAGE CONTAINER

AutoCAD SHX Text

METAL SHIPPING COINTAINER (TBRL)

AutoCAD SHX Text

CONC CURB

AutoCAD SHX Text T14"

AutoCAD SHX Text T16"

AutoCAD SHX Text T8"

AutoCAD SHX Text T16"

AutoCAD SHX Text T2"

AutoCAD SHX Text T

AutoCAD SHX Text T

AutoCAD SHX Text

GENERATOR ON CONC PAD

AutoCAD SHX Text

RISER

AutoCAD SHX Text

RIM=153.22

AutoCAD SHX Text

RIM=153.27

AutoCAD SHX Text

RIM=153.34

AutoCAD SHX Text

GRT=152.52

AutoCAD SHX Text

GRT=151.54

AutoCAD SHX Text

RIM=139.93

AutoCAD SHX Text

TOWER

AutoCAD SHX Text

GRAVEL

AutoCAD SHX Text

GRAVEL

AutoCAD SHX Text

CONC

AutoCAD SHX Text

GRAVEL

AutoCAD SHX Text

GRAVEL

AutoCAD SHX Text

RD

AutoCAD SHX Text

LOADING DOCK

AutoCAD SHX Text

CONC CURB

AutoCAD SHX Text

CONC PAVEMENT

AutoCAD SHX Text

LOADING DOCK

AutoCAD SHX Text

GRASS

AutoCAD SHX Text

EOC

AutoCAD SHX Text

EOP

AutoCAD SHX Text a.INV=148.1±b.INV=148.0±BOS=147.6±

AutoCAD SHX Text 12"

AutoCAD SHX Text 18"

AutoCAD SHX Text 18"

AutoCAD SHX Text 18"

AutoCAD SHX Text a.INV=142.2±b.INV=131.5±c.INV=131.3±BOS=131.3±

AutoCAD SHX Text E

AutoCAD SHX Text E

AutoCAD SHX Text E

AutoCAD SHX Text

DC

AutoCAD SHX Text

CONC WALL W/6' HIGH CLF

AutoCAD SHX Text a

AutoCAD SHX Text b

AutoCAD SHX Text

CONC CURB

AutoCAD SHX Text

RIM=152.67

AutoCAD SHX Text

CS

AutoCAD SHX Text

CS

AutoCAD SHX Text

LIGHT POLE AND FIXTURE

AutoCAD SHX Text

8' HIGH CLF

AutoCAD SHX Text

DUMPSTER (TBRL)

AutoCAD SHX Text

DUMPSTER (TBRL)

AutoCAD SHX Text

TRASH COMPACTOR (TBRL)

AutoCAD SHX Text

DUMPSTER

AutoCAD SHX Text

DUMPSTER

AutoCAD SHX Text

DUMPSTER

AutoCAD SHX Text

CONC PAVEMENT

AutoCAD SHX Text

CONC PAVEMENT

AutoCAD SHX Text

MULTI STORY MASONRY BUILDING

AutoCAD SHX Text

MASONRY BUILDING

AutoCAD SHX Text

ROLL UP DOORS

AutoCAD SHX Text

DOORS

AutoCAD SHX Text

GENERATOR

AutoCAD SHX Text

GENERATOR

AutoCAD SHX Text

GENERATOR

AutoCAD SHX Text

DUMPSTER (TBRL)

X

KEY DESCRIPTION

1. BOLLARDS TO BE REMOVED (TYP).

2. METAL GAURDRAIL TO BE REMOVED.

3. PAVEMENT MARKINGS TO BE REMOVED.

DEMOLITION

LEGEND:

ASPHALT PAVEMENT AND AGGREGATE

BASE COURSE TO BE REMOVED

VA PROJECT NUMBER

Building Number

Drawing Number

Project Title

Date Checked Drawn

Drawing Title

Approved:

VA FORM 08-6231

A

B C

D E

21 4 5 6 7

SHEET NOTES:

KEY NOTES:

321 4 5 6 7

A B

C D

E

Dwg. of

LocationLocation

Office of Construction and Facilities Management

PROJECT MANAGER: ACG Project NumberCONSULTANTS:

Headquarters:

Apogee Consulting Group, P.A.

1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 NC License #: C-1848

U.S. Department of Veterans Affairs

© COPYRIGHT Apogee Consulting Group, P.A.Revisions: Date#

KEY PLAN

D

AREA OF WORK

NOVEMBER 21, 2023

SITE/100

REPLACE GENERAC

GENERATORS

526-20-107

James J. Peters VA Medical Center 130 West Kingsbridge Road

Bronx, New York 10468-3904

20-044

100% BID DOCUMENTS

Civil Engineer:

INTEGRITY

FEDERAL SERVICES

CIVIL ENGINEERING ● LANDSCAPE ARCHITECTURE ● PLANNING

148 S. Queen Street, Suite 201 Martinsburg, WV 25401

Phone: 304-725-8456 www.ifs-ae.com

IN

TE

GRI TY FEDERAL

SERV I CE S

PC ES11/21/2023 11

DEMOLITION PLAN

GRAPHICAL SCALE: 1"=10'

10 5 0 10 20 30

MAGNETIC

DEMOLITION NOTES:

1. WHERE A PORTION OF A CONCRETE AND ASPHALT AREA IS

BEING DEMOLISHED ALL EDGES TO BE SAW CUT.

2. ALL CONCRETE AND ASPHALT REMOVAL TO INCLUDE

PAVEMENT SUB BASE.

3. EXISTING GRASSED AREAS IMPACTED BY THIS PROJECT TO

BE REMOVED. ANY AREAS DISTURBED BY THIS PROJECT

SHALL BE TEMPORARILY STABILIZED DURING

CONSTRUCTION AND PERMANENTLY STABILIZED AT THE END

OF CONSTRUCTION.

4. FOR DEMOLITION AND CONSTRUCTION OF ELECTRICAL LINES

REFER TO ELECTRICAL SHEETS.

5. ALL EXISTING SITE FEATURES, UTILITIES, AND OTHER

EXISTING CONDITIONS NOT PROPOSED TO BE REMOVED OR

DEMOLISHED ARE TO REMAIN OR BE REPLACED IN KIND IF

DAMAGED.

6. ALL UTILITIES PROPOSED TO BE DEMOLISHED ARE TO BE

REMOVED WITHIN THE LIMITS OF DISTURBANCE AND THE

ENDS SHOULD BE CAPPED OR TERMINATED.

7. ALL EXCAVATED MATERIAL SHOULD BE REMOVED. ONSITE

STORAGE OF MATERIALS IS NOT PROPOSED.

8. TEST PITS FOR LOCATING EXISTING UTILITIES ARE PROVIDED

ON THE SITE PLAN.

9. CONTRACTOR IS REQUIRED TO USE A PRIVATE UTILITY

LOCATOR TO IDENTIFY THE LOCATIONS OF ALL EXISTING

UTILITIES WITHIN THE LIMITS OF DISTURBANCE.

10. CONTACT NEW YORK STATE "DIG SAFELY NEW YORK" AT

1-800-962-7962 OR 811 FOR UNDERGROUND UTILITY

CLEARANCE AND MARKOUT BEFORE EXCAVATION, NOTIFY

COR 72 HRS BEFORE EXCAVATION BEGINS. MARK OUT ALL

UTILITIES BEFORE EXCAVATING.

11. HAND DIG ALL EXCAVATION FOR TEST PITS AND AROUND

EXISTING UTILITIES.

12. COORDINATE DEMOLITION DEBRIS DUMPSTER LOCATION

WITH COR.

13. PROVIDE SAFETY AND TRAFFIC CONTROL PLAN. PROVIDE 8'

HIGH CHAIN LINK FENCE AROUND WORK AREAS.

14. SHOW AREA WITH STEEL PLATES OVER TRENCHING (TO

ALLOW TRUCK TRAFFIC ACCESS) IN TRAFFIC CONTROL PLAN.

15. THE SHIPPING CONTAINER, TRASH COMPACTOR, AND

DUMPSTERS ARE PROPOSED TO BE RELOCATED. THE

CONTRACTOR SHALL COORDINATE THE FINAL LOCATION

WITH THE COR.

E-CD-102

AutoCAD SHX Text

EB

AutoCAD SHX Text

EB

AutoCAD SHX Text E

AutoCAD SHX Text E

AutoCAD SHX Text E

AutoCAD SHX Text E

AutoCAD SHX Text E

AutoCAD SHX Text

OVERHANG

AutoCAD SHX Text

8' HIGH CLF

AutoCAD SHX Text

GATE

AutoCAD SHX Text

ROLLING GATE

AutoCAD SHX Text

8' HIGH CLF

AutoCAD SHX Text

2' HIGH WOOD FENCE

AutoCAD SHX Text

COINTAINER

AutoCAD SHX Text

"FIRE DEPT. P.I.V. VALVE"

AutoCAD SHX Text

MGR

AutoCAD SHX Text

CONC WALL W/4' HIGH METAL FENCE

AutoCAD SHX Text

8' HIGH CLF

AutoCAD SHX Text

MGR

AutoCAD SHX Text

SWL

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

SWL

AutoCAD SHX Text

SYL

AutoCAD SHX Text

SWL

AutoCAD SHX Text

WHITE STRIPING

AutoCAD SHX Text

RIM=155.38

AutoCAD SHX Text

GENERATOR ON CONC PAD

AutoCAD SHX Text E

AutoCAD SHX Text

RIM=158.46

AutoCAD SHX Text

RIM=157.30

AutoCAD SHX Text

GENERATOR

AutoCAD SHX Text

ELEC BOX

AutoCAD SHX Text

GRT=151.50

AutoCAD SHX Text

RIM=158.77

AutoCAD SHX Text D

AutoCAD SHX Text

RIM=158.10

AutoCAD SHX Text

RIM=150.52

AutoCAD SHX Text

RIM=158.67

AutoCAD SHX Text D

AutoCAD SHX Text

RIM=158.65

AutoCAD SHX Text

GRT=158.79

AutoCAD SHX Text

RIM=157.09

AutoCAD SHX Text

CONC CURB

AutoCAD SHX Text

FRAME SHED

AutoCAD SHX Text

GARAGE DOOR

AutoCAD SHX Text

AutoCAD SHX Text

EOP

AutoCAD SHX Text

EOC

AutoCAD SHX Text

CONC WALK

AutoCAD SHX Text

CONC WALK

AutoCAD SHX Text

CONC

AutoCAD SHX Text

ASPHALT PAVEMENT

AutoCAD SHX Text 8"

AutoCAD SHX Text a.INV=146.2±b.INV=144.1±.c.INV=(COVERED) BOS=143.8±

AutoCAD SHX Text a

AutoCAD SHX Text

INV=148.5±BOS=148.5±

AutoCAD SHX Text 8"

AutoCAD SHX Text a.INV=(COVERED) b.INV=(COVERED) BOS=152.4±

AutoCAD SHX Text 3"

AutoCAD SHX Text 6"

AutoCAD SHX Text 8"

AutoCAD SHX Text a.INV=156.7±b.INV=155.1±BOS=155.0±

AutoCAD SHX Text a

AutoCAD SHX Text b

AutoCAD SHX Text b

AutoCAD SHX Text a.INV=154.9±b.INV=153.1±c.INV=153.0±d.INV=152.9±

AutoCAD SHX Text 10"

AutoCAD SHX Text a

AutoCAD SHX Text b

AutoCAD SHX Text c

AutoCAD SHX Text d

AutoCAD SHX Text 8"

AutoCAD SHX Text 10"

AutoCAD SHX Text 10"

AutoCAD SHX Text c

AutoCAD SHX Text

1 STORY MASONRY BUILDING

AutoCAD SHX Text

MULTI STORY MASONRY BUILDING

AutoCAD SHX Text

MULTI STORY MASONRY BUILDING

AutoCAD SHX Text

MULTI STORY MASONRY BUILDING

AutoCAD SHX Text

CONC CURB

AutoCAD SHX Text

EOP

AutoCAD SHX Text

BM-A

AutoCAD SHX Text

FABRIC COVERED STRUCTURE

AutoCAD SHX Text

EOP

AutoCAD SHX Text

EOC

AutoCAD SHX Text

DOOR

AutoCAD SHX Text

ROLL UP DOOR

AutoCAD SHX Text

GENERATOR

AutoCAD SHX Text

GENERATOR

AutoCAD SHX Text

AutoCAD SHX Text

APPROXIMATE LOCATION OF EX GAS LINES (PER VA RECORDS)

6.08'

7.2'

28.19'

47.24'

39.09'

40.04'

EX1

12" HDPE

" H

DP

E

12" HDPE

12" HDPE

12" HDPE

8" HDPE

53 20

TC

53 20

TC

54 10

TC

54 10

TC

53 10

GS

53 55

GS

54 10

GS

54 20

GS

53 50

LP

53 70

GS

54 10

GS

54 10

GS

53 70

GS

53 90

GS

53 70

GS

53 70

GS

54 00

GS

54 00

GS

53 90

GS

53 50

GS

53 70

GS

53 10

GS

53 60

GS

53 50

GS

53 20

53 40

GS

53 20

GS

51 10

GS

53 40

GS

53 50

GS

52 00

GS

52 00

GS

51 80

GS

51 60

GS

51 90

GS

54 10

GS

53 60

GS

52 60

GS

53 40

GS

53 60

GS

53 60

GS

53 20

GS

53 30

TC

53 45

GS

53 60

GS

53 20

GS53 10

GS

53 30

GS

53 40

GS 53 50

GS

53 50

GS

53 60

GS

53 65

GS

53 80

GS

54 00

GS

54 20

GS

54 20

GS

53 60

GS

53 00

LP

53 15

GS

CONCRETE PAVEMENT

KEY DESCRIPTION

1. 12,000 GAL. FUEL TANK. REFER TO MECHANICAL

DRAWINGS

2. CONCRETE PAD. CONTRACTOR TO PROVIDE A

STRUCTURAL DESIGN THAT MEETS THE TANK

MANUFACTURER SPECIFICATIONS.

3. 12' SCREEN WALL, REFER TO STRUCTURAL

DRAWINGS

4. ACCESS DOOR

5. FUEL LINE TO GENERATORS, PAVEMENT UTILITY

PATCH REQUIRED.

6. NEW CURB (MATCH EXISTING)

7. SEEDED AREA SHALL BE PROTECTED WITH

STRAW AND EROSION CONTROL NETTING OR

BLANKETS.

8. FENCE (MATCH EXISTING)

SITE PLAN:

LEGEND:

TEST PIT

GRASS (MATCH EXISTING SPECIES)

NYPLAST 2' X 2'

GRATE INLET

NYPLAST 24" STRUCTURE

SOLID COVER

SITE PLAN

VA PROJECT NUMBER

Building Number

Drawing Number

Project Title

Date Checked Drawn

Drawing Title

Approved:

VA FORM 08-6231

A

B C

D E

21 4 5 6 7

SHEET NOTES:

KEY NOTES:

321 4 5 6 7

A B

C D

E

Dwg. of

LocationLocation

Office of Construction and Facilities Management

PROJECT MANAGER: ACG Project NumberCONSULTANTS:

Headquarters:

Apogee Consulting Group, P.A.

1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 NC License #: C-1848

U.S. Department of Veterans Affairs

© COPYRIGHT Apogee Consulting Group, P.A.Revisions: Date#

KEY PLAN

D

AREA OF WORK

NOVEMBER 21, 2023

SITE/100

REPLACE GENERAC

GENERATORS

526-20-107

James J. Peters VA Medical Center 130 West Kingsbridge Road

Bronx, New York 10468-3904

20-044

100% BID DOCUMENTS

Civil Engineer:

INTEGRITY

FEDERAL SERVICES

CIVIL ENGINEERING ● LANDSCAPE ARCHITECTURE ● PLANNING

148 S. Queen Street, Suite 201 Martinsburg, WV 25401

Phone: 304-725-8456 www.ifs-ae.com

IN

TE

GRITY FEDERA

L

SERV I CES

PC ES11/21/2023 11

SITE PLAN NOTES:

1. CONTRACTOR TO MITIGATE AIR AND NOISE POLLUTION.

2. A GEOTECHNICAL REPORT WAS NOT PROVIDED.

3. CONTRACTOR TO PROVIDE A CONSTRUCTION PHASING,

PEDESTRIAN CIRCULATION AND TRAFFIC CONTROL PLAN.

4. ADA/ABA ACCESS AND EMERGENCY ACCESS TO BE

MAINTAINED THROUGHOUT CONSTRUCTION.

5. CONTRACTOR TO COORDINATE WITH VAMC AND COR ON

MAINTAINING PARKING, DELIVERIES, AND ACCESS TO

BUILDING DURING CONSTRUCTION.

6. CONTRACTOR MUST OBTAIN APPROVAL FROM THE VAMC

AND COR PRIOR TO ANY DISRUPTION IN DAILY ACTIVITIES,

UTILITIES, OR CIRCULATION PATTERNS.

7. CONTRACTOR TO ENSURE POSITIVE DRAINAGE

THROUGHOUT CONSTRUCTION.

8. WALL DESIGN TO INCLUDE UTILITY CROSSINGS BY

SLEEVE, BRIDGING, OR OTHER APPROVED METHOD.

9. PAVEMENT DETAILS PROVIDED ON SITE DETAILS SHEET.

10. PROVIDE SIGNAGE FOR TRAFFIC PERSONNEL SAFETY

AND CONSTRUCTION SIGN FOR THE PROJECT.

11. REFER TO ELECTRICAL AND MECHANICAL PLANS FOR

NEW LINES CONNECTING TO THE FUEL TANK AND

GENERATORS. INCLUDES UTILITY TRENCH DETAILS,

PUMPS, CONTROLS, ALARM SYSTEM, AND

SPECIFICATIONS.

12. EXISTING UTILITIES MAY NEED TO BE ADJUSTED

VERTICALLY AND OR HORIZONTALLY TO ACCOMMODATE

THE PROPOSE IMPROVEMENTS.

13. NEW PAVEMENT ELEVATIONS AND FINAL GRADES ARE TO

MATCH THE EXISTING ELEVATIONS.

14. THE PROPOSED ACCESS DOORS TO THE GENERATOR

SHALL BE A CONVENTIONAL 14-GA

VERTICALLY-STIFFENED HM DOOR. THE FRAMES WILL

NEED TO BE ANCHORED.

15. REFER TO EROSION AND SEDIMENT CONTROL NOTES AND

DETAILS FOR PROPOSED MEASURES.

16. CONTRACTOR SHALL REFER TO THE ELECTRICAL PLANS

FOR LOCATION OF THE NEW SERVICE LINES.

GRAPHICAL SCALE: 1"=10'

10 5 0 10 20 30

MAGNETIC

E-CS-101

AutoCAD SHX Text

OVERHANG

AutoCAD SHX Text

CONC WALK

AutoCAD SHX Text

CONC WALK

AutoCAD SHX Text

CONC STEPS W/3' HIGH METAL RAILING

AutoCAD SHX Text

METAL RAMP W/3' HIGH METAL RAILING

AutoCAD SHX Text

CONC WALL W/4' HIGH CLF

AutoCAD SHX Text

8' HIGH CLF

AutoCAD SHX Text

CONC CURB W/GUTTER

AutoCAD SHX Text

COMPACTOR

AutoCAD SHX Text

COINTAINER

AutoCAD SHX Text

MEDICAL STORAGE CONTAINER

AutoCAD SHX Text

CONC CURB

AutoCAD SHX Text

TOWER

AutoCAD SHX Text

GRAVEL

AutoCAD SHX Text

GRAVEL

AutoCAD SHX Text

CONC

AutoCAD SHX Text

GRAVEL

AutoCAD SHX Text

GRAVEL

AutoCAD SHX Text

RD

AutoCAD SHX Text

LOADING DOCK

AutoCAD SHX Text

CONC CURB

AutoCAD SHX Text

CONC PAVEMENT

AutoCAD SHX Text

LOADING DOCK

AutoCAD SHX Text

GRASS

AutoCAD SHX Text

EOC

AutoCAD SHX Text

EOP

AutoCAD SHX Text E

AutoCAD SHX Text E

AutoCAD SHX Text E

AutoCAD SHX Text

DC

AutoCAD SHX Text

CONC WALL W/6' HIGH CLF

AutoCAD SHX Text

CONC CURB

AutoCAD SHX Text

CS

AutoCAD SHX Text

CS

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

DUMPSTER

AutoCAD SHX Text

DUMPSTER

AutoCAD SHX Text

DUMPSTER

AutoCAD SHX Text

CONC PAVEMENT

AutoCAD SHX Text

CONC PAVEMENT

AutoCAD SHX Text

MULTI STORY MASONRY BUILDING

AutoCAD SHX Text

MASONRY BUILDING

AutoCAD SHX Text

ROLL UP DOORS

AutoCAD SHX Text

DOORS

8"

HDPE

9 EX3

EX2

57 30

GS

57 60

GS

58 50

GS

58 50

GS

57 80

GS

57 90

GS

58 60

GS

58 50

GS

57 80

GS

58 70

GS

58 75

GS

58 80

GS

58 70

GS

58 20

GS

58 40

GS

57 70

GS

58 20

GS

58 40

GS

58 80

GS

58 10

GS

58 00

GS

58 60

GS

58 20

GS

58 00

GS

57 90

GS

57 90

GS

57 90

GS

57 60

LP

57 90

GS

57 65

GS

58 70

GS

58 80

GS

58 60

GS

58 40

GS

58 80

GS

58 80

GS

58 60

LP

KEY DESCRIPTION

1. 8,000 GAL. FUEL TANK.

2. CONCRETE PAD. CONTRACTOR TO PROVIDE A

STRUCTURAL DESIGN THAT MEETS THE TANK

MANUFACTURER SPECIFICATIONS.

3. 12' SCREEN WALL, REFER TO STRUCTURAL

DRAWINGS

4. ACCESS DOOR

5. FUEL LINE TO GENERATORS, PAVEMENT UTILITY

PATCH REQUIRED.

SITE PLAN:

CONCRETE PAVEMENT

LEGEND:

ASPHALT PAVEMENT

TEST PIT

NYPLAST 2' X 2'

GRATE INLET

NYPLAST 24" STRUCTURE

SOLID COVER

VA PROJECT NUMBER

Building Number

Drawing Number

Project Title

Date Checked Drawn

Drawing Title

Approved:

VA FORM 08-6231

A

B C

D E

21 4 5 6 7

SHEET NOTES:

KEY NOTES:

321 4 5 6 7

A B

C D

E

Dwg. of

LocationLocation

Office of Construction and Facilities Management

PROJECT MANAGER: ACG Project NumberCONSULTANTS:

Headquarters:

Apogee Consulting Group, P.A.

1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 NC License #: C-1848

U.S. Department of Veterans Affairs

© COPYRIGHT Apogee Consulting Group, P.A.Revisions: Date#

KEY PLAN

D

AREA OF WORK

NOVEMBER 21, 2023

SITE/100

REPLACE GENERAC

GENERATORS

526-20-107

James J. Peters VA Medical Center 130 West Kingsbridge Road

Bronx, New York 10468-3904

20-044

100% BID DOCUMENTS

Civil Engineer:

INTEGRITY

FEDERAL SERVICES

CIVIL ENGINEERING ● LANDSCAPE ARCHITECTURE ● PLANNING

148 S. Queen Street, Suite 201 Martinsburg, WV 25401

Phone: 304-725-8456 www.ifs-ae.com

IN

TE

GRITY FEDERA

L

SERV I CES

PC ES11/21/2023 11

SITE PLAN

GRAPHICAL SCALE: 1"=10'

10 5 0 10 20 30

MAGNETIC

SITE PLAN NOTES:

1. CONTRACTOR TO MITIGATE AIR AND NOISE POLLUTION.

2. A GEOTECHNICAL REPORT WAS NOT PROVIDED.

3. CONTRACTOR TO PROVIDE A CONSTRUCTION PHASING,

PEDESTRIAN CIRCULATION AND TRAFFIC CONTROL PLAN.

4. ADA/ABA ACCESS AND EMERGENCY ACCESS TO BE

MAINTAINED THROUGHOUT CONSTRUCTION.

5. CONTRACTOR TO COORDINATE WITH VAMC AND COR ON

MAINTAINING PARKING, DELIVERIES, AND ACCESS TO

BUILDING DURING CONSTRUCTION.

6. CONTRACTOR MUST OBTAIN APPROVAL FROM THE VAMC

AND COR PRIOR TO ANY DISRUPTION IN DAILY ACTIVITIES,

UTILITIES, OR CIRCULATION PATTERNS.

7. CONTRACTOR TO ENSURE POSITIVE DRAINAGE

THROUGHOUT CONSTRUCTION.

8. WALL DESIGN TO INCLUDE UTILITY CROSSINGS BY

SLEEVE, BRIDGING, OR OTHER APPROVED METHOD.

9. PAVEMENT DETAILS PROVIDED ON SITE DETAILS SHEET.

10. PROVIDE SIGNAGE FOR TRAFFIC PERSONNEL SAFETY

AND CONSTRUCTION SIGN FOR THE PROJECT.

11. REFER TO ELECTRICAL AND MECHANICAL PLANS FOR

NEW LINES CONNECTING TO THE FUEL TANK AND

GENERATORS. INCLUDES UTILITY TRENCH DETAILS,

PUMPS, CONTROLS, ALARM SYSTEM, AND

SPECIFICATIONS.

12. EXISTING UTILITIES MAY NEED TO BE ADJUSTED

VERTICALLY AND OR HORIZONTALLY TO ACCOMMODATE

THE PROPOSE IMPROVEMENTS.

13. NEW PAVEMENT ELEVATIONS AND FINAL GRADES ARE TO

MATCH THE EXISTING ELEVATIONS.

14. THE PROPOSED ACCESS DOORS TO THE GENERATOR

SHALL BE A CONVENTIONAL 14-GA

VERTICALLY-STIFFENED HM DOOR. THE FRAMES WILL

NEED TO BE ANCHORED.

15. REFER TO EROSION AND SEDIMENT CONTROL NOTES AND

DETAILS FOR PROPOSED MEASURES.

16. CONTRACTOR SHALL REFER TO THE ELECTRICAL PLANS

FOR LOCATION OF THE NEW SERVICE LINES.

E-CS-102

AutoCAD SHX Text

EB

AutoCAD SHX Text

EB

AutoCAD SHX Text E

AutoCAD SHX Text E

AutoCAD SHX Text E

AutoCAD SHX Text E

AutoCAD SHX Text E

AutoCAD SHX Text

OVERHANG

AutoCAD SHX Text

8' HIGH CLF

AutoCAD SHX Text

GATE

AutoCAD SHX Text

ROLLING GATE

AutoCAD SHX Text

8' HIGH CLF

AutoCAD SHX Text

2' HIGH WOOD FENCE

AutoCAD SHX Text

COINTAINER

AutoCAD SHX Text

"FIRE DEPT. P.I.V. VALVE"

AutoCAD SHX Text

MGR

AutoCAD SHX Text

CONC WALL W/4' HIGH METAL FENCE

AutoCAD SHX Text

8' HIGH CLF

AutoCAD SHX Text

AutoCAD SHX Text

SWL

AutoCAD SHX Text

SYL

AutoCAD SHX Text

SWL

AutoCAD SHX Text

WHITE STRIPING

AutoCAD SHX Text

GENERATOR ON CONC PAD

AutoCAD SHX Text E

AutoCAD SHX Text

RIM=157.30

AutoCAD SHX Text

GENERATOR

AutoCAD SHX Text D

AutoCAD SHX Text D

AutoCAD SHX Text

RIM=158.67

AutoCAD SHX Text D

AutoCAD SHX Text

RIM=158.65

AutoCAD SHX Text

GRT=158.79

AutoCAD SHX Text

CONC CURB

AutoCAD SHX Text

FRAME SHED

AutoCAD SHX Text

GARAGE DOOR

AutoCAD SHX Text

AutoCAD SHX Text

EOP

AutoCAD SHX Text

EOC

AutoCAD SHX Text

CONC WALK

AutoCAD SHX Text

CONC WALK

AutoCAD SHX Text

CONC

AutoCAD SHX Text

ASPHALT PAVEMENT

AutoCAD SHX Text a.INV=(COVERED) b.INV=(COVERED) BOS=152.4±

AutoCAD SHX Text a.INV=156.7±b.INV=155.1±BOS=155.0±

AutoCAD SHX Text

1 STORY MASONRY BUILDING

AutoCAD SHX Text

MULTI STORY MASONRY BUILDING

AutoCAD SHX Text

MULTI STORY MASONRY BUILDING

AutoCAD SHX Text

MULTI STORY MASONRY BUILDING

AutoCAD SHX Text

CONC CURB

AutoCAD SHX Text

EOP

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

BM-A

AutoCAD SHX Text

FABRIC COVERED STRUCTURE

AutoCAD SHX Text

EOP

AutoCAD SHX Text

EOC

AutoCAD SHX Text

DOOR

AutoCAD SHX Text

ROLL UP DOOR

3.82'

23.17'

23'

27.21'

71.48'

REFER TO STRUCTURAL

DESIGN DRAWINGS FOR

WALL TYPE AND DETAILS.

.55

25.49'

62.65'

5.12'

22.86'

4.87'

23.67'

22.19'

6'

6'

N: 255,690.79 E: 1,010,285.16

6.62'

6.97'

17.75'

7.21'

6.08'

1.37'

VA PROJECT NUMBER

Building Number

Drawing Number

Project Title

Date Checked Drawn

Drawing Title

Approved:

VA FORM 08-6231

A

B C

D E

21 4 5 6 7

321 4 5 6 7

A B

C D

E

Dwg. of

LocationLocation

Office of Construction and Facilities Management

PROJECT MANAGER: ACG Project NumberCONSULTANTS:

Headquarters:

Apogee Consulting Group, P.A.

1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 NC License #: C-1848

U.S. Department of Veterans Affairs

© COPYRIGHT Apogee Consulting Group, P.A.Revisions: Date#

D

NOVEMBER 21, 2023

SITE/100

REPLACE GENERAC

GENERATORS

526-20-107

James J. Peters VA Medical Center 130 West Kingsbridge Road

Bronx, New York 10468-3904

20-044

100% BID DOCUMENTS

Civil Engineer:

INTEGRITY

FEDERAL SERVICES

CIVIL ENGINEERING ● LANDSCAPE ARCHITECTURE ● PLANNING

148 S. Queen Street, Suite 201 Martinsburg, WV 25401

Phone: 304-725-8456 www.ifs-ae.com

IN

TE

GRI TY FEDERAL

SERV I CE S

PC ES11/21/2023 11

SITE DETAILS

MAP UNIT LEGEND

UGBI

URBAN LAND-GREENBELT COMPLEX, 3 TO

8 PERCENT SLOPES, LOW IMPERVIOUS

SURFACE

UGC URBAN LAND-GREENBELT COMPLEX, 8 TO

15 PERCENT SLOPES

UGD URBAN LAND-GREENBELT COMPLEX, 15

TO 25 PERCENT SLOPES

SOIL MAP

NTS

NOTE: THE FUEL TANK DETAILS ARE PROVIDED FOR INFORMATIONAL

PURPOSES ONLY. REFER TO MECHANICAL DRAWINGS AND DESIGN.

2.85'

E-GI-501

AutoCAD SHX Text

MEDICAL STORAGE CONTAINER

AutoCAD SHX Text

CONC CURB

AutoCAD SHX Text

TOWER

AutoCAD SHX Text

CONC CURB

AutoCAD SHX Text E

AutoCAD SHX Text E

AutoCAD SHX Text E

AutoCAD SHX Text

CONC WALL W/6' HIGH CLF

AutoCAD SHX Text

DOORS

AutoCAD SHX Text

12,000 GAL. FUEL TANK LAYOUT DETAIL

AutoCAD SHX Text

NTS

AutoCAD SHX Text

AutoCAD SHX Text

GI-501

AutoCAD SHX Text

12,000 GALLON TANK DETAIL

AutoCAD SHX Text

NTS

AutoCAD SHX Text

GI-501

REFER TO STRUCTURAL

DESIGN DRAWINGS FOR

WALL TYPE AND DETAILS.

.37

N: 255,058.78 E: 1,009,933.41

1.99'

27.5'

20.67'

.03

.86

VA PROJECT NUMBER

Building Number

Drawing Number

Project Title

Date Checked Drawn

Drawing Title

Approved:

VA FORM 08-6231

A

B C

D E

21 4 5 6 7

321 4 5 6 7

A B

C D

E

Dwg. of

LocationLocation

Office of Construction and Facilities Management

PROJECT MANAGER: ACG Project NumberCONSULTANTS:

Headquarters:

Apogee Consulting Group, P.A.

1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 NC License #: C-1848

U.S. Department of Veterans Affairs

© COPYRIGHT Apogee Consulting Group, P.A.Revisions: Date#

D

NOVEMBER 21, 2023

SITE/100

REPLACE GENERAC

GENERATORS

526-20-107

James J. Peters VA Medical Center 130 West Kingsbridge Road

Bronx, New York 10468-3904

20-044

100% BID DOCUMENTS

Civil Engineer:

INTEGRITY

FEDERAL SERVICES

CIVIL ENGINEERING ● LANDSCAPE ARCHITECTURE ● PLANNING

148 S. Queen Street, Suite 201 Martinsburg, WV 25401

Phone: 304-725-8456 www.ifs-ae.com

IN

TE

GRI TY FEDERAL

SERV I CE S

PC ES11/21/2023 11

SITE DETAILS

NOTE: THE FUEL TANK DETAILS ARE PROVIDED FOR INFORMATIONAL

PURPOSES ONLY. REFER TO MECHANICAL DRAWINGS AND DESIGN.

TYPICAL ASPHALT PAVEMENT SECTION:

NOT TO SCALE

NOTES:

1. SOILS TESTS OF SUBGRADE MUST BE SUBMITTED FOR ACTUAL

DETERMINATION BASED ON CBR OF REQUIRED PAVEMENT SECTION

THICKNESS PRIOR TO CONSTRUCTION.

2. ALL BASE AND SUBGRADE MATERIAL SHALL BE COMPACTED TO 98%

THEORETICAL MAXIMUM DRY DENSITY AS DETERMINED BY AASHTO T99

METHOD C, WITHIN 2% OF OPTIMUM MOISTURE CONTENT.

2.5" BINDER COURSE

(CLASS 1 ASPHALT)

1.5" SURFACE COURSE

(CLASS 2 ASPHALT)

8" PROCESSED AGGREGATE

AND GRAVEL BASE COURSE

(PLACED IN 2 LIFTS)

COMPACTED SUBGRADE

98% PER AASHTO-T99C

ASPHALT PAVEMENT

CONCRETE CURB & GUTTER DETAILS:

NOT TO SCALE

NOTES:

1. 6" GRADED AGGREGATE BASE AND COMPACTED SUBGRADE SHALL BE INSTALLED UNDER CURB CONSISTENT WITH

PAVEMENT TYPICAL SECTIONS.

2. CONSTRUCTION OF CONCRETE CURBING SHALL BE BY THE "SEPARATE METHOD" WHEN SAWED JOINTS ARE

CONSTRUCTED IN THE PAVEMENT.

3. ALL CURB JOINTS SHALL BE MADE BY ACCEPTABLE FORMING METHODS.

4. *WHEN ABUTTING CONCRETE PAVEMENT, THICKNESS SHALL MATCH THICKNESS OF CONCRETE PAVEMENT.

5. **WHEN ABUTTING CONCRETE PAVEMENT, A LONGITUDINAL JOINT WITH TIE BARS OR TIE BOLT ASSEMBLIES SHALL

BE CONSTRUCTED AT THIS LOCATION IN LIEU OF PAINTED BITUMINOUS MATERIAL.

6. MATCH EXISTING CURB AND GUTTER DIMENSIONS.

COMBINATION CONCRETE

CURB & GUTTER

TYPE I-BARRIER TYPE

EDGE TO BE

PAINTED WITH

BITUMINOUS

MATERIAL

SLOPE TO MATCH

PAVEMENT SLOPEBACK OF CURB TO

MATCH FINAL GRADE

THIS ITEM MAY BE

PRECAST OR CAST

IN PLACE.

CONCRETE TO BE

CLASS A3 IF CAST

IN PLACE, 4000 PSI

IF PRECASE.

NOTES:

1. CONTRACTOR TO PROVIDE CONTROL AND EXPANSION JOINT PLANS TO THE EOR FOR APPROVAL. THE JOINT

PATTERN SHOULD MATH THE EXISTING PATTER AS BEST AS POSSIBLE. MAXIMUM SPACING BETWEEN JOINTS IS 20 FT.

2. PAVEMENT SECTIONS ARE BASED ON A CBR OF 6. CONTRACTOR TO PROVIDE CBR TESTS FOR FINAL PAVEMENT

DESIGN.

E-GI-502

AutoCAD SHX Text

EB

AutoCAD SHX Text

EB

AutoCAD SHX Text E

AutoCAD SHX Text E

AutoCAD SHX Text E

AutoCAD SHX Text E

AutoCAD SHX Text

AutoCAD SHX Text

SWL

AutoCAD SHX Text

WHITE STRIPING

AutoCAD SHX Text

GENERATOR ON CONC PAD

AutoCAD SHX Text E

AutoCAD SHX Text

RIM=158.67

AutoCAD SHX Text

RIM=158.65

AutoCAD SHX Text

GRT=158.79

AutoCAD SHX Text

FRAME SHED

AutoCAD SHX Text a.INV=(COVERED) b.INV=(COVERED) BOS=152.4±

AutoCAD SHX Text a.INV=156.7±b.INV=155.1±BOS=155.0±

AutoCAD SHX Text

BM-A

AutoCAD SHX Text

DOOR

AutoCAD SHX Text

8,000 GAL. FUEL TANK LAYOUT DETAIL

AutoCAD SHX Text

NTS

AutoCAD SHX Text

AutoCAD SHX Text

GI-501

AutoCAD SHX Text

8,000 GALLON TANK DETAIL

AutoCAD SHX Text

NTS

AutoCAD SHX Text

GI-501

Drawing Number

Project Title

Date Checked Drawn

Drawing Title

Approved:

VA FORM 08-6231

A

B C

D E

21 4 5 6 7

321 4 5 6 7

A B

C D

E

Dwg. of

LocationLocation

Office of Construction and Facilities Management

PROJECT MANAGER: ACG Project NumberCONSULTANTS:

Headquarters:

Apogee Consulting Group, P.A.

1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 NC License #: C-1848

U.S. Department of Veterans Affairs

© COPYRIGHT Apogee Consulting Group, P.A.Revisions: Date#

D

NOVEMBER 21, 2023

SITE/100

REPLACE GENERAC

GENERATORS

526-20-107

James J. Peters VA Medical Center 130 West Kingsbridge Road

Bronx, New York 10468-3904

20-044

100% BID DOCUMENTS

Civil Engineer:

INTEGRITY

FEDERAL SERVICES

CIVIL ENGINEERING ● LANDSCAPE ARCHITECTURE ● PLANNING

148 S. Queen Street, Suite 201 Martinsburg, WV 25401

Phone: 304-725-8456 www.ifs-ae.com

IN

TE

GRI TY FEDERAL

SERV I CE S

PC ES11/21/2023 11

SITE DETAILS

NOTE: CONTRACTOR MAY SUBMIT ALTERNATIVE DRAINAGE SYSTEM FOR

APPROVAL BY THE EOR/COR. MUST COMPLY WITH THE PROJECT SPECIFICATIONS.

E-GI-503

Drawing Number

Project Title

Date Checked Drawn

Drawing Title

Approved:

VA FORM 08-6231

A

B C

D E

21 4 5 6 7

321 4 5 6 7

A B

C D

E

Dwg. of

LocationLocation

Office of Construction and Facilities Management

PROJECT MANAGER: ACG Project NumberCONSULTANTS:

Headquarters:

Apogee Consulting Group, P.A.

1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 NC License #: C-1848

U.S. Department of Veterans Affairs

© COPYRIGHT Apogee Consulting Group, P.A.Revisions: Date#

D

NOVEMBER 21, 2023

SITE/100

REPLACE GENERAC

GENERATORS

526-20-107

James J. Peters VA Medical Center 130 West Kingsbridge Road

Bronx, New York 10468-3904

20-044

100% BID DOCUMENTS

Civil Engineer:

INTEGRITY

FEDERAL SERVICES

CIVIL ENGINEERING ● LANDSCAPE ARCHITECTURE ● PLANNING

148 S. Queen Street, Suite 201 Martinsburg, WV 25401

Phone: 304-725-8456 www.ifs-ae.com

IN

TE

GRI TY FEDERAL

SERV I CE S

PC ES11/21/2023 11

EROSION AND SEDIMENT

CONTROL NOTES AND DETAILS

CONSTRUCTION SAFETY FENCE NOTES:

1. CONTRACTOR SHALL ERECT CONSTRUCTION SAFETY FENCE AROUND THE PERIMETER OF ALL DEMOLITION AND SITE CONSTRUCTION

ACTIVITIES. FENCE TO HAVE LIMITED ACCESS FOR CONSTRUCTION PERSONNEL AND ASSOCIATED VEHICLES AND EQUIPMENT.

2. IT SHALL BE THE CONTRACTORS OPTION TO RELOCATE/REARRANGE CONSTRUCTION SAFETY FENCING IN ORDER TO MAINTAIN VARIOUS

CONSTRUCTION OPERATIONS AND ANTICIPATED PHASING OF CONSTRUCTION ACTIVITIES.

3. SAFETY FENCES SHOULD BE INSTALLED PRIOR TO SEDIMENT CONTROL MEASURES BECOMING ACCESSIBLE. FENCING SHALL REMAIN IN PLACE

UNTIL REMOVAL IS APPROVED BY THE COR.

4. SIGNS NOTING POTENTIAL HAZARDS SUCH AS "DANGER" OR "HAZARDOUS AREA--KEEP OUT" SHOULD BE POSTED AND EASILY SEEN BY

ANYONE APPROACHING THE PROTECTED AREA.

5. PLASTIC (POLYETHYLENE) FENCE MAY BE USED A SAFETY FENCING PRIMARILY IN SITUATIONS WHERE THE NEED IS FOR A TEMPORARY

BARRIER. THE RECOMMENDED COLOR IS INTERNATIONAL ORANGE. THE PHYSICAL REQUIREMENTS SHALL COMPLY WITH VA STANDARDS.

6. CHAIN LINK FENCE SHOULD BE USED FOR PERMANENT STRUCTURES (GREATER THAN ONE YEAR) OR WHEN A POTENTIALLY DANGEROUS

CONTROL MEASURE WILL REMAIN IN PLACE PERMANENTLY.

EROSION AND SEDIMENT CONTROL NARRATIVE

PROJECT DESCRIPTION:

THE DEPARTMENT OF VETERANS AFFAIRS IS PROPOSING TWO NEW FUEL TANKS TO SUPPLY FIVE EXISTING GENERATORS. THE FUEL TANKS WILL BE INSTALLED AS CLOSE TO THE GENERATORS AS POSSIBLE. A WALL IS PROPOSED AROUND THE NEW FUEL TANKS AND EXISTING GENERATORS. THE PROPOSED SITE IMPROVEMENTS FOR 'VAMC' INCLUDES, BUT IS NOT LIMITED TO, DEMOLITION ACTIVITIES TO REMOVE EXISTING SITE FEATURES, CONSTRUCTION OF PAVEMENT, NEW CURBING, FUEL TANK INFRASTRUCTURE, AND ASSOCIATED ADJUSTMENTS TO EXISTING

UTILITY INFRASTRUCTURE

EXISTING SITE CONDITIONS:

THE PROJECT AREAS FOR THE NEW FUEL TANKS ARE BEHIND THE MAIN HOSPITAL BUILDING IN THE LOADING/DELIVERY AREAS ADJACENT TO THE EXISTING GENERATORS. THE EXISTING CONDITIONS INCLUDE BUT ARE NOT LIMITED TO UTILITIES, HARDSCAPE, LANDSCAPING, STORAGE EQUIPMENT, MECHANICAL EQUIPMENTS, ANCILLARY STRUCTURES, PARKING, AND OTHER SITE

INFRASTRUCTURE.

ADJACENT PROPERTY:

THE SITE IS BOUNDED BY THE EXISTING FACILITIES AND INFRASTRUCTURE FOR THE SITE AND SEDGWICK AVENUE TO THE WEST.

OFFSITE AREAS:

IT IS NOT ANTICIPATED, AT THIS TIME, THAT THERE WILL BE A NEED TO BORROW SOIL FROM OFFSITE AREAS; THEREFORE, NO OFFSITE DISTURBANCES ARE EXPECTED. IF IT IS DETERMINED THAT THERE IS A NEED TO BORROW SOIL FROM OFFSITE AREAS, THE CONTRACTOR WILL BE RESPONSIBLE FOR OBTAINING THE REQUIRED GRADING PERMITS.

CRITICAL EROSION AREAS:

CRITICAL EROSION AREAS ON SITE CONSISTS OF STEEP SLOPES. SOILS STABILIZATION MATTING AND CROWN VETCH SHALL BE UTILIZED IN AREAS OF SLOPES EQUAL TO OR GREATER THAN 3:1.

SOILS:

FOR SOILS INFORMATION, SEE SHEET 7. THE SOILS ARE ANTICIPATED TO BE URBAN FILL GIVEN THE WORK AREA IS AN EXISTING BACK OF HOUSE USED OF LOADING AND DELIVERIES.

STORMWATER AND BMP MANAGEMENT PRACTICES:

THIS PROJECT IS CONSIDERED A MAINTENANCE IMPROVEMENT FOR MISSION CRITICAL SERVICES. THE DISTURBED AREA PROPOSED WITH THIS PROJECT IS UNDER 1 (ONE) ACRE. THE PROJECT WILL NOT ADVERSELY IMPACT THE CURRENT DRAINAGE SYSTEM. THERE ARE NO PROPOSED CHANGES TO THE WATER QUALITY OR QUANTITY VOLUMES. AS SUCH, NO STORMWATER OR

BMP MANAGEMENT PRACTICES ARE REQUIRED.

SEDIMENT CONTROL PROGRAM:

THE EROSION AND SEDIMENT CONTROL PROGRAM FACILITIES SHALL BE INSTALLED BEFORE OTHER CLEARING, GRADING AND CONSTRUCTION STARTS. CONTROLS INSTALLED ARE INTENDED TO REMAIN FOR THE DURATION OF THE PROJECT. ADDITIONAL CONTROLS WILL BE PROVIDED AS NEEDED OR REQUESTED BY THE SITE INSPECTOR.

EROSION AND SEDIMENT CONTROL MEASURES INCLUDE:

1. CONTRACTOR TO MINIMIZE THE AMOUNT OF SEDIMENT/MUD CARRIED FROM THE SITE ONTO PUBLIC AND PRIVATE ROADS. IF SEDIMENT IS TRANSPORTED ONTO A PAVED OR PUBLIC ROAD

SURFACE, THE ROAD SURFACE SHALL BE CLEANED THOROUGHLY AT THE END OF EACH WORKING DAY, OR IMMEDIATELY IF PUBLIC SAFETY IS HINDERED IN ANY WAY. SEDIMENT SHALL BE REMOVED FROM ROADS BY SHOVELING OR SWEEPING AND TRANSPORTED TO A SEDIMENT CONTROL DISPOSAL AREA. STREET WASHING SHALL BE ALLOWED ONLY AFTER SEDIMENT IS REMOVED IN THIS MANNER. IT IS THE CONTRACTOR'S RESPONSIBILITY TO DETERMINE IF A VEHICLE WASHING STATION OR CONSTRUCTION ENTRANCE IS REQUIRED TO KEEP THE

SITE/ROADS…

This is the start of the file's text. The full file is on GovTribe.

File details come from the government source that posted it. Updated .