S06 Yardney Filter DAta Sheet.pdf
PDF 113 KB Posted
- Attached to
- Z1DA--528A6-20-609 BOILER PLANT UPGRADES |
- Solicitation number
- 36C24221B0071
About this file
This document outlines a federal contract opportunity for boiler plant upgrades at the Bath VA Medical Center. The project consists of two tasks. Task 1 involves replacing water filtration tanks and appurtenances, with basis of design being Yardney Multi-Media Filter System, Model #MM5460-3A. This includes removing and disposing of existing filter media, re-bedding the tanks with specified quantities and sizes of new filter media including gravel, garnet and anthracite, re-insulating the tank, and ensuring proper backflush and operation. Task 2 is replacing four existing digital loop controllers with new state-of-the-art digital controllers including testing and calibration, and any necessary re-wiring. The solicitation will be posted on or about October 4, 2021. The contract will be awarded to the contractor whose total sum for both tasks is lowest. All work must be completed within 120 days of award. The NAICS code is 238220 with a small business size standard of $16.5 million. The project magnitude is between $100,000 and $250,000, and requires a 20% bid bond submitted with the bid. This opportunity is 100% set-aside for Service-Disabled Veteran-Owned Small Businesses.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| S06 Yardney Filter Tanks.jpg | JPG image | |
| 36C24221B0071 0004.docx | DOCX document | |
| 36C24221B0071 0003.docx | DOCX document | |
| P07 Wage Determination.docx | DOCX document | |
| 36C24221B0071 0002.docx | DOCX document | |
| 2021 Boiler Plant Upgrades SOW-r1.docx | DOCX document | |
| S06 Certification of Vaccination.pdf | ||
| S06 05779335 082621 003 CAO Memorandum - Attestation Guidance for Health and Safety Precautions for COVID-19 - Aug 25 2021 (1).pdf | ||
| 36C24221B0071 0001.docx | DOCX document | |
| 36C24221B0071_1.docx | DOCX document |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Asset #:
NORMAL OPERATING PARAMETERS UNIT CONFIGURATION
Operating Temperature °F Number of Tanks
Nominal Operating Press PSI Tank Size
Min. Inlet Operating Pressure PSI Tank Press Rating
Nominal Flow Rate / Range GPM Tank Design Temp
Backwash Flow Rate Per Tank GPM ASME Code Stamped
Control Operating Air Volume SCFM Process Inlet:
Control Operating Air Pressure Deg F Process Outlet:
Backwash Outlet:
POWER REQUIREMENTS Tank Drain Outlet:
GENERAL POWER VAC PH HZ Amps Src Internal Piping
High Voltage Main Valves Control Voltage 120 1 60 5 Backwash Control
INSTRUMENTS
Flow Filter Media 1 n/a cu. Ft. / vessel
Pressure Filter Media 2 n/a cu. Ft. / vessel ph / Cond Filter Media 3 48 cu. Ft. / vessel
1/4x1/8 Gravel Support 6 cu. Ft. / vessel
1/2x1/4 Gravel Support 8 cu. Ft. / vessel
3/4x1/2 Gravel Support n/a cu. Ft. / vessel
CONTROLS PHYSICAL SPECIFICATIONS
Main Controller Length 252 inches
HMI Width 72 inches
Other Type Of Control Height 102 inches
Skid Weight 4080 lbs. (empty)
Gravel Support Weight 4200 lbs. (3 tanks)
Total Ship Weight 8280 lbs. (skid) Total Oper Weight 34250 lbs. (skid)
AVAILABLE DOCUMENTATION
AVAIL AVAIL
N Y
Y N
N N
Yardney
726 Beacon St, Loves Park, IL 61111 | 815-636-8833 | 800-919-0888 | 815-636-8844 fx | www.watersurplus.com
EQUIPMENT DATA SHEET MEDIA FILTRATION SKID
Description MM5460-3AS Triplex Filter Skid FIT2400039R
Owner Mfg. Yr. EQUIPMENT TYPE OEM
240 - 716
Watersurplus 2008 Triplex Filter Skid n/a
Gate Valve
80 6" pipe
SUGGESTED MEDIA VOLUMES
n/a
Differential Pressure Switch n/a
4" pipe
1" Hose Connection
304 SST/PVC Bot & CS Top
Yardney 3-Way Valve
Description
54"dia x 60" Side Sht
80 psig
120 Deg F
No
6" pipe
Description
Process & Instrumentation Diagram - P&ID Electrical Schematics
Piping layout/General Arrangement Program Logic
Major Component List - MC List Operations/Maintenance Manuals
Yardney Ultra 116i NEMA 4x n/a
Yardney
726 Beacon St, Loves Park, IL 61111 | 815-636-8833 | 800-919-0888 | 815-636-8844 fx | www.watersurplus.com
EQUIPMENT DATA SHEET MEDIA FILTRATION SKID
Description MM5460-3AS Triplex Filter Skid FIT2400039R
Owner Mfg. Yr. EQUIPMENT TYPE OEM
Watersurplus 2008 Triplex Filter Skid
Feed Inlet
Product Outlet
Backwash Outlet
Drain Outlet
Vent
Place general arrangement/location drawing here.
MISCELLANEOUS INFORMATION
This triplex filter can be used for multi media filtration and carbon filtration. Yardney's unique 3-Way valve controls inlet feed water and outlet backwash water. These filters go into backwash based on DP or time settings by the user in the control panel. During backwash one filter is backwashed at a time using the filtrate from the other two units. This
PROCESS CONNECTIONS (SIZES & LOCATION SYMBOLS)
Location
Front Upper Right
Front Lower Left
Front Upper Right
Front Lower Right
Front Center Each Tank
Size & Type
6" ANSI Flanged
6" ANSI Flanged
4" ANSI Flanged
1" NPT Hose
3/4" NPT Hose
The quartz (support bed @ 100lb/ft3) will be loaded prior to shipment.
Next Sand (55lbs/ft3) and Carbon (27.5 lbs/ft3) will be shipped loose for loading on site.
sequence is repeated until all three units are backwashed. Manual rate set valve is used to control the backwash flow rate. Backwash rate to regulate flow for media protection.
Tank Access
Misc 12x16 Elliptical Bolted
Yardney
726 Beacon St, Loves Park, IL 61111 | 815-636-8833 | 800-919-0888 | 815-636-8844 fx | www.watersurplus.com
EQUIPMENT DATA SHEET MEDIA FILTRATION SKID
Description MM5460-3AS Triplex Filter Skid FIT2400039R
Owner Mfg. Yr. EQUIPMENT TYPE OEM
Watersurplus 2008 Triplex Filter Skid
Manway Location
Skid Fork Lift Access Skid
Top Head & Lower Side Sht
File details come from the government source that posted it. Updated .