This document is a technical specification for interior lighting systems, including requirements for lighting fixtures, ballasts, lamps, and emergency lighting. Key details include:

The specification covers the furnishing, installation, and connection of interior lighting systems, including lighting fixture types, construction requirements, ballast features, lamp types and mercury content limits, and requirements for radio-interference-free fluorescent and LED fixtures. It also includes requirements for fluorescent emergency ballasts, emergency lighting units, and LED exit light fixtures. Specific requirements are provided for wall-mounted fluorescent bedlight fixtures, X-ray film illuminators, and LED lighting fixtures. The document covers installation, testing, and acceptance procedures.

This specification is referenced in the attached federal contract opportunity for the renovation and upgrade of an Angio OR Suite construction project for the Department of Veterans Affairs, Veterans Integrated Service Network 1.

View the file

Other files

File Type Posted
36C24124R0065 0008.docx DOCX document
WAGE RATES RI20240001 MOD 14 09202024 SAM.gov.pdf PDF
36C24124R0065 0007.docx DOCX document
S04 650-CSI-351 Sign In_1SITE VISIT.pdf PDF
36C24124R0065 0006.docx DOCX document
M-601-PreBidRevisions.pdf PDF
36C24124R0065 0005.docx DOCX document
E501-PreBidRevisions.pdf PDF
36C24124R0065 0004.docx DOCX document
36C24124R0065 0003.docx DOCX document
S02 EXHIBIT A FACTOR 1 INFORMATION SHEET-R2.docx DOCX document
36C24124R0065 0002.docx DOCX document
S02 EXHIBIT A FACTOR 1 INFORMATION SHEET.pdf PDF
S02 EXHIBIT G ITEMIZED COST BREAKDOWN SHEET 650-CSI-351.pdf PDF
36C24124R0065 0001.docx DOCX document
S02 EXHIBIT F WAGE DETERMINATION R120240001 MOD 12 08232024.pdf PDF
S02 EXHIBIT E VAAR Clause 852.219-77 Certificate of Compliance.pdf PDF
S02 EXHIBIT C Past Performance Questionnaire.pdf PDF
650-CSI-351-BidSpecs-Vol2-Reno UpgradeAngioOR-ProvidenceVAMC-TMM2123.pdf PDF
36C24124R0065.docx DOCX document
S02 EXHIBIT B Subcontractor Information and Consent Form.pdf PDF
Directive 7715_1_D_2023-06-22.pdf PDF
S02 EXHIBIT I 9766_Providence_Angio_Rev1_UPS-24-07-12.pdf PDF
S02 EXHIBIT F WAGE DETERMINATION RI20240001 MOD 11 07122024.pdf PDF
S02 EXHIBIT G ITEMIZED COST BREAKDOWN SHEET 650-CSI-351.docx DOCX document
650-CSI-351-BidSpecs-Vol1-Reno UpgradeAngioOR-ProvidenceVAMC-TMM2123.pdf PDF
S02 EXHIBIT H 263353 SPECS UPS.pdf PDF
Full Set Combined Drwgs.pdf PDF
S02 EXHIBIT D Statement of Proposed Items_Aknowl of Amendments_Calculation Sheet.pdf PDF
S02 EXHIBIT A Past Performance Info Sheet for Contractors.docx DOCX document
Show all 30

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

03-01-24

SECTION 26 51 00

interior lighting

PART 1 GENERAL

1.1 DESCRIPTION:

A. This section specifies the furnishing, installation, and connection of the interior lighting systems. The terms “lighting fixture,” “fixture,” and “luminaire” are used interchangeably.

1.2 RELATED WORK

A.Section 01 74 19, CONSTRUCTION WASTE MANAGEMENT: Disposal of lamps.
B.Section 02 41 00, DEMOLITION: Removal and disposal of lamps and ballasts.
C.Section 13 05 41, SEISMIC RESTRAINT REQUIREMENTS FOR NON-STRUCTURAL COMPONENTS: Requirement for seismic restraint for nonstructural components.
D.Section 26 05 11, REQUIREMENTS FOR ELECTRICAL INSTALLATIONS: Requirements that apply to all sections of Division 26.
E.Section 26 05 19, LOW-VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES: Low-voltage conductors.
F.Section 26 05 26, GROUNDING AND BONDING FOR ELECTRICAL SYSTEMS: Requirements for personnel safety and to provide a low impedance path to ground for possible ground fault currents.
G.Section 26 27 26, WIRING DEVICES: Wiring devices used for control of the lighting systems.

1.3 qualITY ASSURANCE A. Quality Assurance shall be in accordance with Paragraph, QUALIFICATIONS (PRODUCTS AND SERVICES) in Section 26 05 11, REQUIREMENTS FOR ELECTRICAL INSTALLATIONS.

1.4 SUBMITTALS

A.Submit in accordance with Paragraph, SUBMITTALS in Section 26 05 11, REQUIREMENTS FOR ELECTRICAL INSTALLATIONS, and the following requirements:
1.Shop Drawings:
a.Submit the following information for each type of lighting fixture designated on the LIGHTING FIXTURE SCHEDULE, arranged in order of lighting fixture designation.
b.Material and construction details, include information on housing and optics system.
c.Physical dimensions and description.
d.Wiring schematic and connection diagram.
e.Installation details.
f.Energy efficiency data.
g.Photometric data based on laboratory tests complying with IES Lighting Measurements testing and calculation guides.
h.Lamp data including lumen output (initial and mean), color rendition index (CRI), rated life (hours), and color temperature (degrees Kelvin).
i.Ballast data including ballast type, starting method, ambient temperature, ballast factor, sound rating, system watts, and total harmonic distortion (THD).
j.For LED lighting fixtures, submit US DOE LED Lighting Facts label, and IES L70 rated life.
2.Manuals:
a.Submit, simultaneously with the shop drawings, complete maintenance and operating manuals, including technical data sheets, wiring diagrams, and information for ordering replacement parts.
b.If changes have been made to the maintenance and operating manuals originally submitted, submit updated maintenance and operating manuals two weeks prior to the final inspection.
3.Certifications: Two weeks prior to final inspection, submit the following.
a.Certification by the Contractor that the interior lighting systems have been properly installed and tested.

1.5 APPLICABLE PUBLICATIONS

A.Publications listed below (including amendments, addenda, revisions, supplements, and errata) form a part of this specification to the extent referenced. Publications are referenced in the text by designation only.
B.American Society for Testing and Materials (ASTM):
C635/C635M-22Manufacture, Performance, and Testing of Metal Suspension Systems for Acoustical Tile and Lay-in Panel Ceilings
C.Environmental Protection Agency (EPA):
40 CFR 261-21Identification and Listing of Hazardous Waste
D.Federal Communications Commission (FCC):
CFR Title 47, Part 15Radio Frequency Devices
CFR Title 47, Part 18Industrial, Scientific, and Medical Equipment
E.Illuminating Engineering Society of North America (IESNA):
LM-79-19Electrical and Photometric Measurements of Solid-State Lighting Products
LM-80-21Measuring Lumen Maintenance of LED Light Sources
LM-82-19Characterization of LED Light Engines and LED Lamps for Electrical and Photometric Properties as a Function of Temperature
F.Institute of Electrical and Electronic Engineers (IEEE):
C62.41-91(R1995)Surge Voltages in Low Voltage AC Power Circuits
G.International Code Council (ICC):
IBC-21International Building Code
H.National Electrical Manufacturer's Association (NEMA):
C78.376-14 (R2021)Chromaticity of Fluorescent Lamps
C82.1-04(S2021)Lamp Ballasts – Line Frequency Fluorescent Lamp Ballasts
C82.2-02(S2021)Method of Measurement of Fluorescent Lamp Ballasts
C82.4-17Lamp Ballasts - Ballasts for High-Intensity Discharge and Low-Pressure Sodium (LPS) Lamps (Multiple-Supply Type)
C82.11-17Lamp Ballasts - High Frequency Fluorescent Lamp Ballasts
LL 9-11Dimming of T8 Fluorescent Lighting Systems
SSL 1-16Electronic Drivers for LED Devices, Arrays, or Systems
I.National Fire Protection Association (NFPA):
70-23National Electrical Code (NEC)
101-21Life Safety Code
J.Underwriters Laboratories, Inc. (UL):
496-17Lampholders
542-05Fluorescent Lamp Starters
844-12Luminaires for Use in Hazardous (Classified) Locations
924-16Emergency Lighting and Power Equipment
935-01Fluorescent-Lamp Ballasts
1029-94High-Intensity-Discharge Lamp Ballasts

1029A-06................Outline of Investigation for Ignitors and Related Auxiliaries for HID Lamp Ballasts 1574-04.................Standard for Safety Track Lighting Systems 1598-21 Standard for Safety Luminaires 2108-15.................Standard for Safety Low-Voltage Lighting Systems 8750-15.................Standard for Safety Light Emitting Diode (LED) Light Sources for Use in Lighting Products

PART 2 PRODUCTS

2.1 LIGHTING FIXTURES

A.Shall be in accordance with NFPA, UL, as shown on drawings, and as specified.
B.Sheet Metal:
1.Shall be formed to prevent warping and sagging. Housing, trim and lens frame shall be true, straight (unless intentionally curved), and parallel to each other as designed.
2.Wireways and fittings shall be free of burrs and sharp edges, and shall accommodate internal and branch circuit wiring without damage to the wiring.
3.When installed, any exposed fixture housing surface, trim frame, door frame, and lens frame shall be free of light leaks.
4.Hinged door frames shall operate smoothly without binding. Latches shall function easily by finger action without the use of tools.
C.Ballasts and lamps shall be serviceable while the fixture is in its normally installed position. Ballasts shall not be mounted to removable reflectors or wireway covers unless so specified.
D.Lamp Sockets:
1.Fluorescent: Single slot entry type, requiring a one-quarter turn of the lamp after insertion. Lampholder contacts shall be the biting edge type.
2.Compact Fluorescent: 4-pin.
3.High Intensity Discharge (HID): Porcelain.
E.Recessed fixtures mounted in an insulated ceiling shall be listed for use in insulated ceilings.
F.Mechanical Safety: Lighting fixture closures (lens doors, trim frame, hinged housings, etc.) shall be retained in a secure manner by captive screws, chains, aircraft cable, captive hinges, or fasteners such that they cannot be accidentally dislodged during normal operation or routine maintenance.
G.Metal Finishes:
1.The manufacturer shall apply standard finish (unless otherwise specified) over a corrosion-resistant primer, after cleaning to free the metal surfaces of rust, grease, dirt and other deposits. Edges of pre-finished sheet metal exposed during forming, stamping or shearing processes shall be finished in a similar corrosion resistant manner to match the adjacent surface(s). Fixture finish shall be free of stains or evidence of rusting, blistering, or flaking, and shall be applied after fabrication.
2.Interior light reflecting finishes shall be white with not less than 85 percent reflectances, except where otherwise shown on the drawing.
3.Exterior finishes shall be as shown on the drawings.
H.Lighting fixtures shall have a specific means for grounding metallic wireways and housings to an equipment grounding conductor.
I.Light Transmitting Components for Fluorescent Fixtures:
1.Shall be 100 percent virgin acrylic.
2.Flat lens panels shall have not less than 3 mm (1/8 inch) of average thickness.
3.Unless otherwise specified, lenses, reflectors, diffusers, and louvers shall be retained firmly in a metal frame by clips or clamping ring in such a manner as to allow expansion and contraction without distortion or cracking.
J.Lighting fixtures in hazardous areas shall be suitable for installation in Class and Division areas as defined in NFPA 70.
K.Compact fluorescent fixtures shall be manufactured specifically for compact fluorescent lamps with ballast integral to the fixture. Assemblies designed to retrofit incandescent fixtures are prohibited except when specifically indicated for renovation of existing fixtures.

2.2 ballasTS

A.Linear Fluorescent Lamp Ballasts: Ballasts shall be designed for full light output unless dimmer or bi-level control is indicated. Ballasts shall include the following features:
1.Lamp end-of-life detection and shutdown circuit (T5 lamps only).
2.Automatic lamp starting after lamp replacement.
3.Sound Rating: Class A.
4.Total Harmonic Distortion (THD): 10 percent or less.
5.Transient Voltage Protection: IEEE C62.41.1 and IEEE C62.41.2, Category A or better.
6.Operating Frequency: 20 kHz or higher.
7.Lamp Current Crest Factor: 1.7 or less.
8.Ballast Factor: 0.87 or higher unless otherwise indicated.
9.Power Factor: 0.98 or higher.
10.EMR/RFI Interference: Comply with CFR Title 47 Part 18 for limitations on electromagnetic and radio-frequency interference for non-consumer equipment.
11.To facilitate multi-level lamp switching, lamps within fixture shall be wired with the outermost lamp at both sides of the fixture on the same ballast, the next inward pair on another ballast and so on to the innermost lamp (or pair of lamps). Within a given room, each switch shall uniformly control the same corresponding lamp (or lamp pairs) in all fixture units that are being controlled.
12.Where three-lamp fixtures are indicated, unless switching arrangements dictate otherwise, utilize a common two-lamp ballast to operate the center lamp in pairs of adjacent units that are mounted in a continuous row. The ballast fixture and slave-lamp fixture shall be factory wired with leads or plug devices to facilitate this circuiting. Individually mounted fixtures and the odd fixture in a row shall utilize a single-lamp ballast for operation of the center lamp.
13.Dimming ballasts shall be as per above, except dimmable.Dimming ballasts shall be fully compatible with the dimming controls.
B.Low-Frequency Linear T8 Fluorescent Lamp Ballasts (allowed for Surgery Suites, Critical Care Units, and Animal Labs): Multi-voltage (120 – 277V), hybrid electronic-electromagnetic rapid-start type, designed for type and quantity of lamps indicated. Ballast shall be designed for full light output. Ballasts shall include the following features:
1.Automatic lamp starting after lamp replacement.
2.Sound Rating: Class A.
3.Total Harmonic Distortion (THD): 20 percent or less.
4.Transient Voltage Protection: IEEE C62.41.1 and IEEE C62.41.2, Category A or better.
5.Operating Frequency: 60 Hz.
6.Lamp Current Crest Factor: 1.7 or less.
7.Ballast Factor: 0.85 or higher unless otherwise indicated.
8.Power Factor: 0.90 or higher.
9.Interference: Comply with CFR Title 47 Part 18 for limitations on electromagnetic and radio-frequency interference for non-consumer equipment.
10.To facilitate multi-level lamp switching, lamps within fixture shall be wired with the outermost lamp at both sides of the fixture on the same ballast, the next inward pair on another ballast and so on to the innermost lamp (or pair of lamps). Within a given room, each switch shall uniformly control the same corresponding lamp (or lamp pairs) in all fixture units that are being controlled.
11.Where three-lamp fixtures are indicated, unless switching arrangements dictate otherwise, utilize a common two-lamp ballast to operate the center lamp in pairs of adjacent units that are mounted in a continuous row. The ballast fixture and slave-lamp fixture shall be factory wired with leads or plug devices to facilitate this circuiting. Individually mounted fixtures and the odd fixture in a row shall utilize a single-lamp ballast for operation of the center lamp.
C.Compact Fluorescent Lamp Ballasts: Multi-voltage (120 – 277V), electronic programmed rapid-start type, designed for type and quantity of lamps indicated. Ballast shall be designed for full light output unless dimmer or bi-level control is indicated. Ballasts shall include the following features:
1.Lamp end-of-life detection and shutdown circuit.
2.Automatic lamp starting after lamp replacement.
3.Sound Rating: Class A.
4.Total Harmonic Distortion (THD): 10 percent or less.
5.Transient Voltage Protection: IEEE C62.41.1 and IEEE C62.41.2, Category A or better.
6.Operating Frequency: 20 kHz or higher.
7.Lamp Current Crest Factor: 1.7 or less.
8.Ballast Factor: 0.95 or higher unless otherwise indicated.
9.Power Factor: 0.98 or higher.
10.Interference: Comply with CFR Title 47 Part 18 for limitations on electromagnetic and radio-frequency interference for non-consumer equipment.
11.Dimming ballasts shall be as per above. Dimming ballasts shall be fully compatible with the dimming controls.
D.Ballasts for HID fixtures: Multi-tap voltage (120 – 480V) electromagnetic ballast for high intensity discharge lamps. Include the following features unless otherwise indicated:
1.Ballast Circuit: Constant-wattage autotransformer or regulating high-power-factor type.
2.Minimum Starting Temperature: Minus 22 deg F (Minus 30 deg C) for single-lamp ballasts.
3.Rated Ambient Operating Temperature: 104 deg F (40 deg C).
4.Open-circuit operation that will not reduce average life.
5.Low-Noise Ballasts: Manufacturers' standard epoxy-encapsulated models designed to minimize audible fixture noise.
E.Electronic ballast for HID metal-halide lamps shall include the following features unless otherwise indicated:
1.Minimum Starting Temperature: Minus 20 deg F (Minus 29 deg C) for single-lamp ballasts.
2.Rated Ambient Operating Temperature: 130 deg F (54 deg C).
3.Lamp end-of-life detection and shutdown circuit.
4.Sound Rating: Class A.
5.Total Harmonic Distortion (THD): 20 percent or less.
6.Transient Voltage Protection: IEEE C62.41.1 and IEEE C62.41.2, Category A or better.
7.Lamp Current Crest Factor: 1.5 or less.
8.Power Factor: 0.90 or higher.
9.Interference: Comply with CFR Title 47 Part 18 for limitations on electromagnetic and radio-frequency interference for non-consumer equipment.
10.Protection: Resettable thermal.

2.3 FLUORESCENT EMERGENCY BALLAST

A.Self-contained, modular, battery-inverter unit, factory mounted within lighting fixture housing and compatible with ballast.
1.Emergency Connection: Connect unswitched circuit to battery-inverter unit and switched circuit to fixture ballast.
2.Test Push Button and Indicator Light: Visible and accessible without opening fixture or entering ceiling space.
a.Push Button: Push-to-test type, in unit housing, simulates loss of normal power and demonstrates unit operability.
b.Indicator Light: LED indicates normal power on. Normal glow indicates trickle charge; bright glow indicates charging at end of discharge cycle.
3.Battery: Sealed, maintenance-free, nickel-cadmium type.
4.Charger: Fully automatic, solid-state, constant-current type with sealed power transfer relay.
5.Integral Self-Test: Automatically initiates test of unit emergency operation at required intervals. Test failure is annunciated by an integral audible alarm and a flashing LED.

2.4 EMERGENCY LIGHTING UNIT

A.Complete, self-contained unit with batteries, battery charger, one or more local or remote lamp heads with lamps, under-voltage relay, and test switch.
1.Enclosure: Enclosure shall be suitable for the environmental conditions in which installed.
2.Lamp Heads: Horizontally and vertically adjustable, mounted on the face of the unit, except where otherwise indicated.
3.Lamps: Shall be sealed-beam MR-16 halogen, rated not less than 12 watts at the specified DC voltage.
4.Battery: Shall be maintenance-free nickel-cadmium. Minimum normal life shall be minimum of 10 years.
5.Battery Charger: Dry-type full-wave rectifier with charging rates to maintain the battery in fully-charged condition during normal operation, and to automatically recharge the battery within 12 hours following a 1-1/2 hour continuous discharge.
6.Integral Self-Test: Automatically initiates test of unit emergency operation at required intervals. Test failure is annunciated by an integral audible alarm and a flashing LED.

2.5 lamps

A.Linear and U-shaped T5 and T8 Fluorescent Lamps:
1.Except as indicated below, lamps shall have the following characteristics: energy saving type, color temperature between 3500 - 5000K and as specified in the drawing’s LIGHTING FIXTURE SCHEDULE, a Color Rendering Index (CRI) equal or greater than 80, and be suitable for use with dimming ballasts, unless otherwise indicated.
2.Lamps shall comply with EPA Toxicity Characteristic Leachate Procedure (TCLP) requirements.
3.Maximum level of mercury content (in milligram or mg) and rated life of lamp (in hours or hrs) shall be:
Lamp
Maximum Level of Mercury (mg)
Rated Life of Lamp based on 3-hours stats (hrs)
T-8, eight-foot
10 mg
24,000 hrs on instant start ballasts
T-8, four-foot
3.5 mg
30,000 hrs on instant start ballasts, or 36,000 rated hours on program start ballasts
T-8, two-foot and three-foot
3.5 mg
24,000 hrs on instant start ballasts or program start ballasts
T-8, U-bent
6 mg
18,000 hrs on instant start ballasts, or 24,000 hrs on program start ballasts
T-5, linear
2.5 mg
25,000 hrs on program start ballasts
B.Compact Fluorescent Lamps:
1.T4, CRI 80 (minimum), color temperature 3500K, average rated life equal to or greater than 12,000 hours (based on 3 hour starts), and suitable for use with dimming ballasts, unless otherwise indicated.
2.Lamps shall comply with EPA Toxicity Characteristic Leachate Procedure (TCLP) requirements.
3.Lamps shall be Energy-Star rated.
4.Lamps shall have a maximum level of mercury content of 3.5 mg.
C.High Intensity Discharge Lamps:
1.High-Pressure Sodium Lamps (HPS): non-cycling type, CRI 21 (minimum), color temperature determined by COR, and average rated life of 24,000 hours.
a.Lamps shall comply with EPA Toxicity Characteristic Leachate Procedure (TCLP) requirements.
b.Maximum levels of mercury content (in milligram, or mg) shall be:
Lamp
Maximum Level of

Mercury (mg)

HPS, up to 400 watts
10 mg
HPS, above 400 watts
32 mg
2.Pulse-Start, Metal-Halide Lamps: Minimum CRI 65 (minimum), color temperature determined by COR, and average rated life of 15,000 hours (based on 10 hour starts).
3.Ceramic, Pulse-Start, Metal-Halide Lamps: CRI 80 (minimum), color temperature determined by COR, and average rated life of 12,000 hours (based on 10 hour starts).

2.6 RADIO-INTERFERENCE-FREE FLUORESCENT and LED FIXTURES

A.Shall be specially designed for suppressing radio-frequency energy and electromagnetic interference produced within the fixtures, and shall comply with Department of Defense MIL-STD-461G, and IEC IP65.
B.Lenses shall have metal mesh to prevent or reduce radio-frequency interference. The effective light transmittance of the lenses shall be a minimum of 75 percent.
C.Fixture finish shall be anti-microbial.
D.Provide RFI line filters integral to the fixtures and wired in series with the supply circuit conductors.
E.Ballasts, or LED drivers shall be as specified in this specification.

2.7 wall mounted fluorescent bedlight fixtures

A.Fixtures shall be lensed.
B.Fixtures shall be rated for 120 Volt operation, and be powered through the patient wall unit per Section 10 25 13, PATIENT BED SERVICE WALLS.
C.Provide 4-position, pull cord switch to control the upward and downward portion of the light separately and simultaneously. Include an off position, except in single bed rooms where the switch shall energize and de-energize the downward light only. In the single bed rooms, provide a 2-position pull cord switch for "on-off" control of the downward lamps.

2.8 X-RAY FILM ILLUMINATORS

A.Shall be the high-intensity type, flush-mounted in the walls. Multiples of the basic unit may be combined in a common housing.
B.Shall have the following features:
1.Fluorescent lighting, designed to provide uniform diffusion of the light.
2.Box dimensions approximately 530 mm (21 inches) high, 355 mm (14 inches) wide and 100 mm (4 inches) deep.
3.Housing shall be steel. Trim shall be stainless steel and shall extend approximately 40 mm (1-1/2 inches) from the edges of the housing.
4.Viewing panel shall thermoplastic, not less than 3 mm (1/8 inch) thick.
5.Viewing panel shall have adequate dimensions so the films will not overlap the frame and will be positioned with respect to the light source for even illumination without shadows.
6.An ON-OFF double-pole, double-throw switch.

2.9 LED exit light fixtures

A.Exit light fixtures shall meet applicable requirements of NFPA and UL.
B.Housing and door shall be die-cast aluminum.
C.For general purpose exit light fixtures, door frame shall be hinged, with latch. For vandal-resistant exit light fixtures, door frame shall be secured with tamper-resistant screws.
D.Finish shall be satin or fine-grain brushed aluminum.
E.There shall be no radioactive material used in the fixtures.
F.Fixtures:
1.Inscription panels shall be cast or stamped aluminum a minimum of 2.25 mm (0.090 inch) thick, stenciled with 150 mm (6 inch) high letters, baked with red color stable plastic or fiberglass. Lamps shall be luminous Light Emitting Diodes (LED) mounted in center of letters on red color stable plastic or fiberglass.
2.Double-Faced Fixtures: Provide double-faced fixtures where required or as shown on drawings.
3.Directional Arrows: Provide directional arrows as part of the inscription panel where required or as shown on drawings. Directional arrows shall be the "chevron-type" of similar size and width as the letters and meet the requirements of NFPA 101.
G.Voltage: Multi-voltage (120 – 277V).
2.10led light fixtures
A.General:
1.LED light fixtures shall be in accordance with IES, NFPA, UL, as shown on the drawings, and as specified.
2.LED light fixtures shall be Reduction of Hazardous Substances (RoHS)-compliant.
3.LED drivers shall include the following features unless otherwise indicated:
a.Minimum efficiency: 85% at full load.
b.Minimum Operating Ambient Temperature: -20˚ C. (-4˚ F.)
c.Input Voltage: 120 - 277V (±10%) at 60 Hz.
d.Integral short circuit, open circuit, and overload protection.
e.Power Factor: ≥ 0.95.
f.Total Harmonic Distortion: ≤ 20%.
g.Comply with FCC 47 CFR Part 15.
4.LED modules shall include the following features unless otherwise indicated:
a.Comply with IES LM-79 and LM-80 requirements.
b.Minimum CRI: 80 or higher. Minimum Color Fidelity Index (IES Rf): 80 or higher.
c.Color temperature between 3500 - 5000K and as specified in the drawings’ LIGHTING FIXTURE SCHEDULE.
d.Minimum Rated Life: 50,000 hours per IES L70.
e.Light output lumens as indicated in the LIGHTING FIXTURE SCHEDULE.
B.LED Downlights:
1.Housing, LED driver, and LED module shall be products of the same manufacturer.
C.LED Troffers:
1.LED drivers, modules, and reflector shall be accessible, serviceable, and replaceable from below the ceiling.
2.Housing, LED driver, and LED module shall be products of the same manufacturer.
D.LED Emergency Battery Driver:
1.Input voltage: 120-277 Volt at 60Hz.
2.Illumination time: 90 minutes.
3.Operating temperature: 0˚C to 55˚C (32˚F to 131˚F).
4.Battery: Lithium Ferro Phosphate (LIF)technology, maintenance-free, and high-temperature. Battery shall be integral with the LED Emergency Battery Driver unit.
5.Test switch: IP65 rated to protect against dust and water.

PART 3 EXECUTION

3.1 INSTALLATION

A.Installation shall be in accordance with the NEC, manufacturer's instructions, and as shown on the drawings or specified.
B.Align, mount, and level the lighting fixtures uniformly.
C.Wall-mounted fixtures shall be attached to the studs in the walls, or to a 20 gauge metal backing plate that is attached to the studs in the walls. Lighting fixtures shall not be attached directly to gypsum board.
D.Lighting Fixture Supports:
1.Shall provide support for all of the fixtures. Supports may be anchored to channels of the ceiling construction, to the structural slab or to structural members within a partition, or above a suspended ceiling.
2.Shall maintain the fixture positions after cleaning and relamping.
3.Shall support the lighting fixtures without causing the ceiling or partition to deflect.
4.Hardware for recessed fluorescent fixtures:
a.Where the suspended ceiling system is supported at the four corners of the fixture opening, hardware devices shall clamp the fixture to the ceiling system structural members, or plaster frame at not less than four points in such a manner as to resist spreading of the support members and safely lock the fixture into the ceiling system.
b.Where the suspended ceiling system is not supported at the four corners of the fixture opening, hardware devices shall independently support the fixture from the building structure at four points.
5.Hardware for surface mounting fluorescent fixtures to suspended ceilings:
a.In addition to being secured to any required outlet box, fixtures shall be bolted to a grid ceiling system at four points spaced near the corners of each fixture. The bolts shall be not less than 6 mm (1/4 inch) secured to channel members attached to and spanning the tops of the ceiling structural grid members. Non-turning studs may be attached to the ceiling structural grid members or spanning channels by special clips designed for the purpose, provided they lock into place and require simple tools for removal.
b.In addition to being secured to any required outlet box, fixtures shall be bolted to ceiling structural members at four points spaced near the corners of each fixture. Pre-positioned 6 mm (1/4 inch) studs or threaded plaster inserts secured to ceiling structural members shall be used to bolt the fixtures to the ceiling. In lieu of the above, 6 mm (1/4 inch) toggle bolts may be used on new or existing ceiling provided the plaster and lath can safely support the fixtures without sagging or cracking.
6.Hardware for recessed lighting fixtures:
a.All fixture mounting devices connecting fixtures to the ceiling system or building structure shall have a capacity for a horizontal force of 100 percent of the fixture weight and a vertical force of 400 percent of the fixture weight.
b.Mounting devices shall clamp the fixture to the ceiling system structure (main grid runners or fixture framing cross runners) at four points in such a manner as to resist spreading of these supporting members. Each support point device shall utilize a screw or approved hardware to "lock" the fixture housing to the ceiling system, restraining the fixture from movement in any direction relative to the ceiling. The screw (size No. 10 minimum) or approved hardware shall pass through the ceiling member (Tbar, channel or spline), or it may extend over the inside of the flange of the channel (or spline) that faces away from the fixture, in a manner that prevents any fixture movement.
c.In addition to the above, the following is required for fixtures exceeding 9 kg (20 pounds) in weight.
1)Where fixtures mounted in ASTM Standard C635 "Intermediate Duty" and "Heavy Duty" ceilings and weigh between 9 kg and 25 kg (20 pounds and 56 pounds), provide two 12 gauge safety hangers hung slack between diagonal corners of the fixture and the building structure.
2)Where fixtures weigh over 25 kg (56 pounds), they shall be independently supported from the building structure by approved hangers. Twoway angular bracing of hangers shall be provided to prevent lateral motion.
d.Where ceiling cross runners are installed for support of lighting fixtures, they must have a carrying capacity equal to that of the main ceiling runners and be rigidly secured to the main runners.
7.Surface mounted lighting fixtures:
a.Fixtures shall be bolted against the ceiling independent of the outlet box at four points spaced near the corners of each unit. The bolts (or studclips) shall be minimum 6 mm (1/4 inch) bolt, secured to main ceiling runners and/or secured to cross runners. Nonturning studs may be attached to the main ceiling runners and cross runners with special nonfriction clip devices designed for the purpose, provided they bolt through the runner, or are also secured to the building structure by 12 gauge safety hangers. Studs or bolts securing fixtures weighing in excess of 25 kg (56 pounds) shall be supported directly from the building structure.
b.Where ceiling cross runners are installed for support of lighting fixtures, they must have a carrying capacity equal to that of the main ceiling runners and be rigidly secured to the main runners.
c.Fixtures less than 6.8 kg (15 pounds) in weight and occupying less than 3715 sq cm (two square feet) of ceiling area may, when designed for the purpose, be supported directly from the outlet box when all the following conditions are met.
1)Screws attaching the fixture to the outlet box pass through round holes (not keyhole slots) in the fixture body.
2)The outlet box is attached to a main ceiling runner (or cross runner) with approved hardware.
3)The outlet box is supported vertically from the building structure.
d.Fixtures mounted in open construction shall be secured directly to the building structure with approved bolting and clamping devices.
8.Single or double pendantmounted lighting fixtures:
a.Each stem shall be supported by an approved outlet box mounted swivel joint and canopy which holds the stem captive and provides spring load (or approved equivalent) dampening of fixture oscillations. Outlet box shall be supported vertically from the building structure.
9.Outlet boxes for support of lighting fixtures (where permitted) shall be secured directly to the building structure with approved devices or supported vertically in a hung ceiling from the building structure with a nine gauge wire hanger, and be secured by an approved device to a main ceiling runner or cross runner to prevent any horizontal movement relative to the ceiling.
E.Furnish and install the new lamps as specified for all lighting fixtures installed under this project, and for all existing lighting fixtures reused under this project.
F.The electrical and ceiling trades shall coordinate to ascertain that approved lighting fixtures are furnished in the proper sizes and installed with the proper devices (hangers, clips, trim frames, flanges, etc.), to match the ceiling system being installed.
G.Bond lighting fixtures to the grounding system as specified in Section 26 05 26, GROUNDING AND BONDING FOR ELECTRICAL SYSTEMS.
H.At completion of project, replace all defective components of the lighting fixtures at no cost to the Government.
I.Dispose of lamps per requirements of Section 01 74 19, CONSTRUCTION WASTE MANAGEMENT, and Section 02 41 00, DEMOLITION.

3.2 Acceptance Checks and Tests

A.Perform the following:
1.Visual Inspection:
a.Verify proper operation by operating the lighting controls.
b.Visually inspect for damage to fixtures, lenses, reflectors, diffusers, and louvers. Clean fixtures, lenses, reflectors, diffusers, and louvers that have accumulated dust, dirt, or fingerprints during construction.
2.Electrical tests:
a.Exercise dimming components of the lighting fixtures over full range of dimming capability by operating the control devices(s) in the presence of the COR Observe for visually detectable flicker over full dimming range, and replace defective components at no cost to the Government.
b.Burn-in all lamps that require specific aging period to operate properly, prior to occupancy by Government. Burn-in period to be 40 hours minimum, unless specifically recommended otherwise by the lamp manufacturer. Burn-in dimmed fluorescent and compact fluorescent lamps for at least 100 hours at full voltage, unless specifically recommended otherwise by the lamp manufacturer. Replace any lamps and ballasts which fail during burn-in.

3.3 Follow-Up Verification

A. Upon completion of acceptance checks and tests, the Contractor shall show by demonstration in service that the lighting systems are in good operating condition and properly performing the intended function.

---END---