This document package includes construction drawings and specifications for the relocation of police services at the Veterans Affairs Medical Center in Brockton, Massachusetts. Key details include mechanical, electrical, and plumbing plans for renovating approximately 5,100 square feet of existing building space to accommodate a new secure corridor, security command center, generator room, and associated support spaces. The project involves installing new ductwork, fire protection systems, electrical distribution and low voltage cabling. The construction drawings provide details on equipment specifications, mounting locations and circuiting diagrams. The related federal contract opportunity is a solicitation to relocate the police services as depicted in the construction documents. The soliciting agency is the Veterans Health Administration within the Department of Veterans Affairs.
View the file
Other files
Show all 34
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
M D
VD
VD
VD
MD
M D
TS
TS
TS
TS
VD
TS
FD
FD
TS
TS
L-1 48" W X 60" H
BOTTOM OF LOUVER AT 5" AFF
48" x 24" RECIRC DUCT
TIGHT TO ROOF JOIST
O.A INTAKE ON ROOF OAI-1
WITH 12" HIGH
INSULATED ROOF CURB
78" x 20" DN TO
5'-0" AFF
EU-102A
EU-102B
EU-101
EU-103
L-2 18" W X 18" H
TOP OF LOUVER 4" BELOW
CEILING
EF-1
8" ø
6"ø
8"ø
8" ø
4" ø
4" ø
5" ø
8"ø
GENERATOR
ERV-1
ERV-1 MOUNTED
ABOVE CEILING
8"Ø GALVANIZED
EXHAUST DUCT UP
THROUGH CONCRETE
ROOF TO GOOSENECK
8"Ø GALVANIZED
OUTSIDE AIR DUCT UP
THROUGH CONCRETE
ROOF TO GOOSENECK
1R1
25 CFM
45 CFM
45 CFM
25 CFM
M301
M301
L-3 18" W X 18" H
BOTTOM OF LOUVER 4" AFF
M301
MOTORIZED DAMPER
OUTSIDE AIR DUCTWORK SHALL
BE INSULATED PER SPECIFICATION
WITH RIGID INSULATION.
EUH-1, ELECTRIC WALL-
MOUNTED, CABINET
UNIT HEATER AT 2FT
AFF. UNIT TO HAVE
INTERNAL THERMOSTAT.
EUH-2, ELECTRIC WALL-
MOUNTED, CABINET
UNIT HEATER AT 2FT
AFF. UNIT TO HAVE
INTERNAL THERMOSTAT.
THERMOSTAT TO CONTROL
EF-1 AND ASSOCIATED
DAMPERS.
4"ø
4"ø
SEE DETAIL 10 ON
SHEET M301 FOR
INSTALLATION.
SEE DETAIL 10 ON
SHEET M301 FOR
INSTALLATION.
F- 1 1/2" F- 1 1/2" F- 1"
F- 1 1/2" F- 1 1/4"F- 1 1/2"
CONNECT UPRIGHT SPRINKLER
TO EXISTING BRANCHES
LOCATE TO ACCOMODATE
NEW WORK. (TYP OF 2)
CONNECT UPRIGHT SPRINKLER
TO EXISTING BRANCHES
LOCATE TO ACCOMODATE
NEW WORK. (TYP OF 4 )
CONNECT UPRIGHT SPRINKLER
TO EXISTING BRANCHES
LOCATE TO ACCOMODATE
NEW WORK. (TYP OF 2 )
200° F UPRIGHT SPRINKLER WITH
REED CAGE (TYP OF 5)
1" F DN BELOW DUCT
UPRIGHT BELOW DUCT
UPRIGHT BELOW DUCT
1" F DN BELOW DUCT
200° F UPRIGHT SPRINKLER WITH
REED CAGE (TYP OF 3)
F- 1 1/4"
XF
1/
2"
XF
1/ 2"
XF
1/
2"
XF
1/
2"
Drawing Title
Approved: Project Director
Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
Dwg. ofRevisions: Date
CONSULTANTS: ARCHITECT/ENGINEERS: Office of Construction and Facilities
Management on e ei gh th in ch o ne fo ot
B
A
C
D
E
F th re e in ch es o ne fo ot 6"
6" on e an d on e ha lf in ch es o ne fo ot on e in ch o ne fo ot
6" 6" th re e qu ar te rs in ch o ne fo ot on e ha lf in ch o ne fo ot th re e ei gh th s in ch o ne fo ot on e qu ar te r i nc h on e fo ot
VA FORM 08-6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
KEYPLAN:
Auburn, ME 207.784.5100
Portland, ME 207.775.0053
Manchester, NH 603.626.1242
"As-Built" Construction Documents
SEPTEMBER 25, 2018
HA PROJECT NUMBER: 13584
SITE SECURITY INSTALLATION
VAMC BROCKTON MA
13584
DBR MAM
M101
FIRST FLOOR DUCTWORK AND FIRE
PROTECTION BUILDING 25
MARCH 31, 2015
SCALE: 1/4" = 1'-0"1 FIRST FLOOR DUCTWORK
28 51
SCALE: 1/4" = 1'-0"2 FIRST FLOOR FIRE PROTECTION
DN.
CHASEPIPE SPACE
OFFICE
STORAGESTORAGE
CLOSET
31 S.F.
112A
STORAGE
Engineering
STORAGE
TOILET
SUPPLIESSUPPLIES
CORRIDOR
CORRIDOR
CORRIDOR
CLOSET
JANITOR
STORAGE
LOCKER
TEL/DATA CLOSET
FIRE CLOSET
ALCOVE
TOILET TOILET
STORAGE
Service
CLOSET
WOMENS
TOILET
MENSMENSWOMENS
IRM
TELEPHONE
FORMS ROOM
SUPPLIES
RECIEVING
RECORD STORAGE
OFFICEOFFICE
SUPPLIES
OFFICE
OFFICE
FIRE CLOSET
STORAGE
CORRIDOR
PATIENTSPATIENTSSTAFFSTAFF
ROOM
LOCKER
ROOM
MINI
SUBSTATION
GENERATOR
ROOM
SCC
RECORDING
SECURE
CORRIDOR
SCC
CONTROL
EQUIPMENT
STORAGE
A N
N
F E
C
Drawing Title
Approved: Project Director
Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
Dwg. ofRevisions: Date
CONSULTANTS:
o n e e i g h t h i n c h o n e f o o t 1
B
A
C
D
E
F t h r e e i n c h e s o n e f o o t o n e a n d o n e h a l f i n c h e s o n e f o o t o n e i n c h o n e f o o t t h r e e q u a r t e r s i n c h o n e f o o t o n e h a l f i n c h o n e f o o t t h r e e e i g h t h s i n c h o n e f o o t o n e q u a r t e r i n c h o n e f o o t
VA FORM 08-6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
Management and Facilities
Construction
Office ofARCHITECT/ENGINEERS:
HA PROJECT NUMBER: 13584
207.784.5100
Auburn, ME
207.775.0053
Portland, ME
603.626.1242
Manchester, NH
"As-Built" Construction Documents
SEPTEMBER 25, 2018
523A5-13-309
VAMC BROCKTON- MA
SITE SECURITY INSTALLATION
51SEPTEMBER 25, 2018
BUILDING 25 FIRST FLOOR ELECTRICAL PLAN
SCALE: 1/8" = 1'-0"
J
DPE
COPS
15kV MINI
SUBSTATION
F
F
J J
J
P01
P01
P01
P01
F
F
15 17 19 21
ANNUNCIATOR
GENERATOR
F
F
A N
N
P02
P02
P02
P02
P02
P02
180°
180°
S
S
WAP
MANAGEMENT
PROVIDE VERTICAL CABLE
75kW
GENERATOR
C25.4
C25.5
C25.6
C25.7
FOR SCC RACK LAYOUT
SEE DETAIL A2 ON DRAWING E702
LOCATION WITH VA OI&T
COORDINATE STUB-UP
J
J
@ 7'-0" AFF
PROVIDE CABLE-TRAY
DAMPER
CONNECT MOTORIZED
DAMPER
CONNECT MOTORIZED
EF-1
RUN TO PANEL COPS (TYPICAL)
CIRCUITS INDICATED SHALL
OU-1
COPS-44
WP
ABOVE
OU-1 ON ROOF W
P
G F
I
ERV-1
COPS-52
P09
P09
P09
P09
CIVIL DRAWINGS
MANHOLE. SEE
ELECTRICAL
COPS-43
COPS-45
J
COPS-29,31
COORDINATE WITH OWNER TO
EXTEND VERIZON DISPATCH LINE
FROM BUILDING 3 TO SCC CONTROL
15KV UNDERGROUND
SEE ONE-LINE DIAGRAM ON
DRAWING E501 AND CIVIL PLANS
ADDITIONAL REQUIREMENTS
ON DRAWING E701 FOR
SEE WORKSTATION DETAIL B4
PUBLIC ADDRESS SYSTEM 2#16AWG
CONNECT TO EXISTING BUILDING
ADDITIONAL GROUNDING REQUIREMENTS
GROUNDING BAR. SEE SPECIFICATIONS FOR
SEE DETAIL A4 ON DWG E702 FOR EQUIPMENT
CONFIGURATION. SEE DETAIL A2 / E702.
OUTLET REQUIREMENTS WITH UPS PLUG
UPS UNITS PER SPECIFICATIONS. COORDINATE
VMS RACK UPS: PROVIDE (2) RACK MOUNT
REX
R E
X
CIRCUIT
CONNECT TO EXISTING
F
F
REQUIREMENTS (TYPICAL)
DOOR ACCESS CONTROL
SEE DETAIL C3 / E703 FOR
180°
C25.3
C25.2
+/- 10'-6" AFG
WITH FIRST FLOOR CEILING SPACE
COORDINATE MOUNTING HEIGHT
WALL MOUNT JUST BELOW CANOPY
F
COPS-47
EUH-1
HD
SEE RISER DIAGRAM ON DRAWING E703.
LOOPS AND CONNECT NEW DEVICES.
INTERUPT EXISTING FIRE ALARM
EXISTING FIRE ALARM DEVICES
L05...
CONNECT LIGHTING TO CIRCUIT INDICATED.
SEE LIGHTING CONTROL DETAIL A3 ON
DRAWING E702.
L06...
CONNECT LIGHTING VIA DIMMING SWITCHES.
CONNECT TO CIRCUIT INDICATED.
L07...
COORDINATE LOCATIONS OF LIGHTING FIXTURES
WITH MECHANICAL DUCTS AND PIPING (TYPICAL)
P01...
WALL BOX FOR WALL MOUNTED LARGE SCREEN
MONITOR. SEE WALL BOX DETAIL B2/E701. MOUNT
AT 5'-0" AFF, COORDINATE EXACT LOCATION
WITH MONITOR MOUNT LOCATIONS.CONNECT TO
CIRCUIT INDICATED.
P02...
ONE 2" CONDUIT FROM FLOOR BOX TO
WIREWAY IN CRAWLSPACE. SEE DETAIL B1
ON DRAWING E701 FOR WIREWAY REQUIRMENTS
AND DETAIL A2 / E701 FOR FLOOR BOX
REQUIREMNTS.
P09...
PROVIDE SERVICE SWITCH AND CONNECT
EVAP UNITS AND ASSOCIATED BRANCH
SELECTORS TO COPS-54 WITH 3#12&G-3/4"C.
COORDINATE WITH MECHANICAL DRAWINGS.
WAP...
WIRELESS ACCESS POINT - LOCATE DATA
OUTLET IN CEILING. COORDINATE EXACT
LOCATION WITH IRM.
F A
C P
DATA CLOSET, TERMINATE AND TEST PER SPECIFICATIONS.
RUN 1 CAT6 CABLE IN 3/4"C FROM CONTROL PANEL TO
PROVIDE ACCESS CONTROL PANEL AND POWER SUPPLY.
CABLING TO SIDE WALL
CONVERTER AND ASSOCIATED
ETHERNET SWITCH, AND FIBER
REWORK EXISTING PATCH PANEL,
CLOSET LOCATION
EXISTING TEL / DATA
TERMINATE AND TEST PER SPECIFICATIONS.
TELEPHONE / EMERGENCY CALL STATION INTERFACE CONNECTION
TO TOOLVOX X3 DEVICE AT RACK IN SCC RECORDING FOR
FROM TELEPHONE CLOSET RUN TWO CAT6 CABLES IN 3/4"C
C2/E703 FOR ADDITIONS / ALTERATIONS
PANEL LOCATION. SEE DETAIL
EXISTING FIRE ALARM CONTROL
OF CABLES TO DATA CLOSET.
ABOVE CABLE TRAY IN SCC RECORDING FOR EXTENSTION
AND SCC RECORDING PROVIDE TWO 3/4"C STUBBED TO
FOR EACH DATA OUTLET INDICATED IN SCC CONTROL
RUN CONDUIT IN CRAWLSPACE BELOW
TEL / DATA CLOSET FOR DATA CABLING.
PROVIDE THREE 4"C TO EXISTING
C R
CR
M L
ML DC
D C
Drawing Title
Approved: Project Director
Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
Dwg. ofRevisions: Date
CONSULTANTS:
o n e e i g h t h i n c h o n e f o o t 1
B
A
C
D
E
F t h r e e i n c h e s o n e f o o t o n e a n d o n e h a l f i n c h e s o n e f o o t o n e i n c h o n e f o o t t h r e e q u a r t e r s i n c h o n e f o o t o n e h a l f i n c h o n e f o o t t h r e e e i g h t h s i n c h o n e f o o t o n e q u a r t e r i n c h o n e f o o t
VA FORM 08-6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
Management and Facilities
Construction
Office ofARCHITECT/ENGINEERS:
HA PROJECT NUMBER: 13584
207.784.5100
Auburn, ME
207.775.0053
Portland, ME
603.626.1242
Manchester, NH
SITE SECURITY INSTALLATION
51SEPTEMBER 25, 2018
A N
N
F E
C
DPE
COPS
75kW
GENERATOR
a b a a a b b b b
OC
A A
A
A
A
A
A
B B
B
B
C C
C
C
C
C
C
D
D
Da
A
L05
COPS-25
L06
COPS-25
COPS-25
COPS-27
INSIDE BUILDING TYPICAL
WIRING SHALL BE CONCEALED
EXIT SIGN WIRING (TYPICAL)
FOR EMERGENCY LIGHTING AND
SEE DETAIL A1 ON DRAWING E701
L07
L07
SUPPLIES
OFFICE
MINI
SUBSTATION
GENERATOR
ROOM
SCC
RECORDING
SECURE
CORRIDOR
SCC
CONTROL
A N
N
F E
C
DPE
COPS
75kW
GENERATOR
REQUIREMENTS
FOR CRAWLSPACE WIREWAY
SEE DETAIL B1 ON DWG E701
F
J
F
F
J J
J
F
F
F
LEGEND
GROUND ROD - 3/4" x 10' COPPER CLAD w/EXOTHERMIC WELD TO CONDUCTORS.
GROUND CONNECTION - EXOTHERMIC WELD OF
BELOW GRADE CABLES TO GROUND RODS, CABLES, ETC
GROUND CONNECTION - CRIMP TYPE TO
GROUND/BOND EQUIPMENT, GROUND BARS, ETC
BELOW GRADE BARE COPPER (CU) GROUND
CONDUCTOR - 4/0 AWG UNLESS INDICATED OTHERWISE
GROUND BAR - 2' x 4" x 1/4" SOLID COPPER w/STANDOFF MOUNTS AND CONNECTIONS AS INDICATED
NOTES
ALL DRIVEN GROUND RODS SHALL BE LOCATED TO ALLOW INSPECTION.1.
ALL BELOW GRADE CONNECTIONS SHALL BE OF THE EXOTHERMIC TYPE.2.
3.GROUNDING AND BONDING CONNECTIONS TO BARS, BUSSES, EQUIPMENT, ETC...
SHALL BE MADE USING CRIMP TYPE CONNECTORS WITH MINIMUM TWO BOLT
PATTERN OR AS RECEOMMENDED BY THE EQUIPMENT MANUFACTURER.
SEE A4/E702
(TYPICAL)
GROUND BAR
STEEL AS REQUIRED
CONNECT TO BUILDING
#4/0
ELECTRICAL PLANS
E110
DSHJWT
LIGHTING PART PLAN
SCALE: 1/8" = 1'-0"
BUILDING 25
RACEWAY AND GROUNDING PART PLAN
SCALE: 1/8" = 1'-0"
CONTRACTOR SHALL CONTRACT TECHNICIANS
CERTIFIED AND APPROVED BY VAMC BROCKTON
IT DEPARTMENT FOR EACH SYSTEM UTILIZED AND
MONITORED BY VA POLICE AND SHALL
COORDINATE THE MIGRATION OF EACH SYSTEM
FROM EXISTING POLICE DISPATCH CENTER(S) TO
THIS LOCATION, INCLUDING SOFTWARE LICENSES,
SOFTWARE AND HARDWARE INSTALLATION AND
CONFIGURATION WITHOUT INTERRUPTION OF
SYSTEM SERVICE. SEE SPECIFICATIONS SECTION
280500 FOR ADDITIONAL REQUIREMENTS
LAMPS, HANGERS, FITTINGS, ETC. FOR A COMPLETE AND PROPER INSTALLATION
ALL FIXTURES SHALL BE FURNISHED COMPLETE WITH ALL HARDWARE
LIGHTING FIXTURE SCHEDULE
TYPE MANUFACTURER CATALOG NO. MTG. VOLT
NO. WATT
LAMPS
TYPE
REMARKS/BALLAST INFORMATION
1UNIVR
A
APPROVED EQUAL
LEDLSER 24-35MLG-C-ED-UCOLUMBIA
2x4 LED LENSED FIXTURE
1UNIVR
B
APPROVED EQUAL
LEDLSER 14-35MLG-C-E-UCOLUMBIA
1X4 LED LENSED FIXTURE
322UNIVP
C
APPROVED EQUAL
T8 CHAIN HANG AT 7'-6" AFFIC4-232-U-EPU-ICWG4COLUMBIA
4' TURRET INDUSTRIAL
P C
1UNIVWALL
D
APPROVED EQUAL
LED WALL MOUNT AT 10'-0" AFGTRV-D-24NB-55-4K-T3-UNV-PEC-BZTBEACON
LED WALL PACK
Drawing Title
Approved: Project Director
Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
Dwg. ofRevisions: Date
CONSULTANTS:
o n e e i g h t h i n c h o n e f o o t 1
B
A
C
D
E
F t h r e e i n c h e s o n e f o o t o n e a n d o n e h a l f i n c h e s o n e f o o t o n e i n c h o n e f o o t t h r e e q u a r t e r s i n c h o n e f o o t o n e h a l f i n c h o n e f o o t t h r e e e i g h t h s i n c h o n e f o o t o n e q u a r t e r i n c h o n e f o o t
VA FORM 08-6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
Management and Facilities
Construction
Office ofARCHITECT/ENGINEERS:
HA PROJECT NUMBER: 13584
207.784.5100
Auburn, ME
207.775.0053
Portland, ME
603.626.1242
Manchester, NH
SITE SECURITY INSTALLATION
51SEPTEMBER 25, 2018
N G
260A
1000/5
L,S,G
200 AF
200 AT
L,S,I,G
DMP
225 AF
225 AT
L,S,I,G
100 AF
100 AT
L,S,I,G
100 AF
100 AT
L,S,I,G
13.8 KV TO
208/120 V, 150/200 KVA
LA
K
K
K
600 A SW 600 A SW
STD SPEED
MB
F1 F2 F3 F4
BUILDING #25 NEW SUBSTATION
W/ 600 AMPERE, 3 PHASE, 4 WIRE, SWITCHBOARD.
13.8 KV DELTA TO 208/120V WYE, 150/200 KVA (AA/FA), SUBSTATION
600 AF
400 AT
ATS
G
100 AF
100 AT
L,S,I,G
225 AF
225 AT
L,S,I,G
100 AF
100 AT
L,S,I,G
100 AF
100 AT
L,S,I,G
F1 F2 F3 F4
DISTRIBUTION BOARD "DPE"
400 AMPERE, 3 PHASE, 4 WIRE 208/120V WYE
STANDBY GENERATOR
75kW, 3 PHASE, 4 WIRE 208/120V WYE
PANEL COPS
225A
ELECTRICAL
ONE-LINE DIAGRAM
BUILDING 25
E501
DSHJWT
GENERATOR
ANNUNCIATOR
4#4/0&G-2 1/2"C
4#4/0&G-2 1/2"C
RUN UNDERGROUND
TO BUILDING 32
TRANSFORMERTO MANHOLE 24
SEE CIVIL DWGS
NEW MANHOLE
3#4/0CU&G-4"C
15 KV FEEDER
3#4/0CU&G-4"C
15 KV FEEDER
K
TVSS
250 AF
30 AT
F5
VENDOR TO ACCOMODATE TVSS
TRIP SETTING BY SUBSTATION
CIRCUIT BREAKER
4#4/0&G-3"C
RUN UNDERGROUND
S P
A C
E
250 AF
30 AT
F5
TVSS
S P
A C
E
AS REQUIRED
PROVIDE CONDUCTORS
4#4/0&G-2 1/2"C
RUN UNDERGROUND
7E
VENDOR TO ACCOMODATE TVSS
TRIP SETTING BY PANEL
CIRCUIT BREAKER
1.
a.
b.
15KV NOTES:
PROVIDE A DETAILED NARRATIVE AND PROPOSED PROCEDURAL STEPS FOR
THE 15KV FEED INTERCEPT WORK. IT SHALL INCLUDE, BUT NOT BE LIMITED
TO, GENERAL INFORMATION REGARDING ALL PARTIES INVOLVED WITH THE
SHUTDOWN AND TIE-IN WITH IDENTIFIED ROLE(S), DETAILED DESCRIPTION OF
WORK PROPOSED TO BE COMPLETED (IN SEQUENTIAL ORDER), SWITCHING
ORDER REQUIRED FOR A SAFE WORKING CONDITION, CAMPUS IMPACT
(POWER OUTAGES) WITH APPROXIMATE LENGTH OF OUTAGE, DETAILED
PROPOSED PROCEDURAL STEPS TO COORDINATE UTILITY OUTAGE, A
DETAILED STEP-BY-STEP OUTAGE CHECKLIST, A FORMAL OUTAGE REQUEST,
A MEDIUM VOLTAGE LOCK-OUT/TAG-OUT PROCEDURE AND AHA, A CONFINED
SPACE PERMIT (COMPLETED), A CONFINED SPACE AHA, MEDIUM VOLTAGE
15KV FEED INTERCEPT AHA, ETC. ONCE OUTAGE IS APPROVED BY VA, THE
FOLLOWING SHALL OCCUR:
A PREPARATORY MEETING WILL BE CONDUCTED WITH ALL PARTIES TO
DISCUSS THE OUTAGE AND ALL HAZARDS AS OUTLINED IN THE REQUIRED
AHA.
VERIFY CABLE ROUTING AS SHOWN ON THE 15KV ONE-LINE DIAGRAM. THIS
VERIFICATION SHALL CONSIST OF PROVING CONDUITS AND CABLES WITHIN
THEM ARE AS SHOWN ON THE ONE-LINE DIAGRAM. CABLES AND CONDUITS
SHALL BE CLEARLY MARKED WHERE WORK IS TO BE PERFORMED.
EXISTING HANDHOLE
SERVING BUILDING 32
TRANSFORMER AS REQUIRED
PROVIDE NEW ELBOWS AT EXISTING
06-02-161. PRIMARY FEEDER CLARIFICATION
TRANSFORMER SIDE A
SWITCH A - TO BLDG 32
TRANSFORMER SIDE B
SWITCH B - TO BLDG 20
(4)#600MCM & (1)#4/0 GROUND
MH 24B
MH 24A
01-03-182. AS BUILT CONDITIONS
ID ID
WATT LOADS
MOUNTING:
LOCATION:
LOAD DESCRIPTION
A M
P
P O
L E
CRKT
DWG
NO. P
O
L E
WATTS
PH A PH B PH C
WATTS
P O
L E
CRKT
DWG
NO. P
O
L E
A M
P
LOAD DESCRIPTION
FEEDER:AIC RATING:
MAIN BREAKER:VOLTAGE:
BUSES:
PH & WIRES:
120/208
3P 4W
225A MAIN BRKR
65K AIC
SURFACE
SERVER ROOM
SEE RISERCOPS
TUB 1 OF 2 - REMARKS:
RCPTS - SCC 20 1 1 1 360 1360 --- --- 1000 2 2 1 20 RCPTS - MONITOR DESK
RCPTS - SCC 20 1 3 3 360 --- 1360 --- 1000 4 4 1 20 RCPTS - MONITOR DESK
RCPTS - SCC 20 1 5 5 360 --- --- 1360 1000 6 6 1 20 RCPTS - MONITOR DESK
RCPT - COPIER 20 1 7 7 1000 2000 --- --- 1000 8 8 1 20 RCPTS - MONITOR DESK
RCPT - ELEC RM 20 1 9 9 720 --- 1720 --- 1000 10 10 1 20 RCPTS - MONITOR DESK
RCPT - PRIM ELEC RM 20 1 11 11 720 --- --- 1720 1000 12 12 1 20 RCPTS - MONITOR DESK
RCPTS - SERVER RM 20 1 13 13 1000 2000 --- --- 1000 14 14 1 20 RCPTS - MONITOR DESK
RCPTS - SERVER RM 20 1 15 15 1000 --- 2000 --- 1000 16 16 1 20 RCPTS - MONITOR DESK
UPS#1 20 1 17 17 1000 --- --- 2000 1000 18 18 1 20 RCPTS - MONITOR DESK
RCPTS - SERVER RM 20 1 19 19 1000 2000 --- --- 1000 20 20 1 20 RCPTS - MONITOR DESK
UPS#2 20 1 21 21 1000 --- 2000 --- 1000 22 22 1 20 RCPTS - MONITOR DESK
RCPTS - SERVER RM 20 1 23 23 1000 --- --- 2000 1000 24 24 1 20 RCPTS - MONITOR DESK
LIGHTING 20 1 25 25 610 1110 --- --- 500 26 26 1 20 MONITOR - WALL
EXTERIOR LIGHTING 20 1 27 27 610 --- 1110 --- 500 28 28 1 20 MONITOR - WALL
GEN BATT CHARGER 20 1 29 29 500 --- --- 1000 500 30 30 1 20 MONITOR - WALL
GEN BATT CHARGER 20 1 31 31 1000 1500 --- --- 500 32 32 1 20 MONITOR - WALL
ACCESS CONTROL 20 1 33 33 0 --- 0 --- 0 34 34 3 20 SPARE
FIRE ALARM PANEL 20 1 35 35 0 --- --- 0 36 - - -
MODBUS 20 2 37 37 0 0 --- --- 38 - - -
- - - 39 --- 0 --- 0 40 40 1 20 SPARE
SPARE 20 1 41 41 0 --- --- 1200 1200 42 42 1 20 SPARE
TUB 2 OF 2 - REMARKS: TUB 2 REMARK
EF-1 20 1 43 43 250 4186 --- --- 11808 44 44 3 60 OU-1
GENERATOR DAMPER 20 1 45 45 250 --- 4186 --- 46 - - -
EUH-1 20 1 47 47 1500 --- --- 5436 48 - - -
EUH-2 20 1 49 49 1500 1680 --- --- 180 50 50 1 20 ROOF RCPT
SPARE 20 1 51 51 0 --- 250 --- 250 52 52 1 20 ERV-1
SIEMENS DAMPER PANEL 20 1 53 53 0 --- --- 0 0 54 54 2 20 EVAPS AND SELECTORS
SPARE 20 1 55 55 0 0 --- --- 56 - - -
SPARE 20 1 57 57 0 --- 0 --- 0 58 58 1 20 SPARE
SPARE 20 1 59 59 0 --- --- 0 0 60 60 1 20 SPARE
SPARE 20 1 61 61 0 0 --- --- 0 62 62 1 20 SPARE
SPARE 20 1 63 63 0 --- 0 --- 0 64 64 1 20 SPARE
SPARE 20 1 65 65 0 --- --- 0 0 66 66 1 20 SPARE
SPARE 20 1 67 67 0 0 --- --- 0 68 68 1 20 SPARE
SPARE 20 1 69 69 0 --- 0 --- 0 70 70 1 20 SPARE
SPARE 20 1 71 71 0 --- --- 0 0 72 72 1 20 SPARE
SPARE 20 1 73 73 0 0 --- --- 0 74 74 1 20 SPARE
SPARE 20 2 75 75 0 --- 0 --- 0 76 76 2 20 SPARE
- - - 77 --- --- 0 78 - - -
SPARE 20 3 79 79 0 0 --- --- 0 80 80 3 20 SPARE
- - - 81 --- 0 --- 82 - - -
- - - 83 --- --- 0 84 - - -
TOTAL AMPS: 119.9 15836 12626 14716 TOTAL WATTS: 43178
REMARKS:
VENDER TO PROVIDE TVSS AND BREAKER SIZE ACCORDINGLY