This document provides details on a federal solicitation for fire door and damper repair services. The solicitation was issued by the Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 1 seeking bids for contract number 36C24124B0013 to perform fire door and damper repairs at the VA Boston Healthcare System. Responses are due by February 28th, 2022. The solicitation seeks bids to repair or replace fire doors and fire dampers as needed to ensure they meet all fire code and safety requirements. The contract will be a one-year base period with four one-year options to extend. Pricing should be submitted as fixed hourly rates for labor along with fixed prices for any necessary parts or materials.

View the file

Other files

Show all 17

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Annual Fire Door Inspection Report

VA Boston Healthcare System Jamaica Plain, MA

Inspection Dates:

2/1/2022 - 2/3/2022

Page 1 of 81 2/9/2022 Version 1

ScottMurphy Snapshot

NFPA Code Reference

The hospital has annual inspection and testing of fire door assemblies by individuals who can demonstrate knowledge and understanding of the operating components of the door being tested. Testing begins with a pre-test visual inspection; testing includes both sides of the opening.

Note 1: Nonrated doors, including corridor doors to patient care rooms and smoke barrier doors, are not subject to the annual inspection and testing requirements of either NFPA 80 or NFPA 105.

Note 2: For hospitals that use Joint Commission accreditation for deemed status purposes: Nonrated doors should be routinely inspected and maintained in accordance with the facility maintenance program.

Note 3: For additional guidance on testing door assemblies see:

NFPA 101-2012: 7.2.1.5.10.1; 7.2.1.5.11; 7.2.1.15

NFPA 80-2010: 4.8.4; 5.2.1; 5.2.3; 5.2.4; 5.2.6; 5.2.7; 6.3.1.7

NFPA 105-2010: 5.2.1; EC.02.03.05 EP 25

Page 2 of 81 2/9/2022 Version 1

Fire Door Report Summary

Inspection Details Total number of doors 216

Passed Doors 59 Failed Doors 157

Page 3 of 81 2/9/2022 Version 1

10625906 PASS

Inspector: Carlos Lopez Building: ACA Wall Ra ng: 2 Hour

Inspec on Date: 2/3/2022 Loca on: Staircase in engineering Door Ra ng: 90 Minute

Floor: Basement Frame Ra ng: 90 Minute

Deficiency Detail

Door passed inspec on

10625933 FAIL

Inspector: Carlos Lopez Building: ACA Wall Ra ng: 2 Hour

Inspec on Date: 2/3/2022 Loca on: Corridor to ACA Door Ra ng: 90 Minute

Floor: 1 Frame Ra ng: 90 Minute

Deficiency Detail

Missing /damaged latchset - NFPA 80-2010 5.2.4.2 (4); NFPA 101-2012 18.3.6.3.5, 18.3.6.3.7, 19.3.6.3.5

10625934 PASS

Inspector: Carlos Lopez Building: ACA Wall Ra ng: 2 Hour

Inspec on Date: 2/3/2022 Loca on: Corridor to AcA Door Ra ng: 90 Minute

Floor: 1 Frame Ra ng: 90 Minute

Deficiency Detail

Door passed inspec on

10625935 FAIL

Inspector: Carlos Lopez Building: ACA Wall Ra ng: 2 Hour

Inspec on Date: 2/3/2022 Loca on: Corridor to aca Door Ra ng: 90 Minute

Floor: 1 Frame Ra ng: 90 Minute

Deficiency Detail

Frame penetra ons / unused fastener holes - NFPA 80-2010 5.2.4.2 (1); NFPA 105-2010 5.1.4.3

Page 4 of 81 2/9/2022 Version 1

10625936 PASS

Inspec on Date: 2/3/2022 Loca on: Corridor to ACA Door Ra ng: 90 Minute

Floor: 1 Frame Ra ng: 90 Minute

Deficiency Detail

Door passed inspec on

10625937 FAIL

Inspector: Carlos Lopez Building: ACA Wall Ra ng: 2 Hour

Inspec on Date: 2/3/2022 Loca on: Fire exit Door Ra ng: Door Label Missing

Floor: 1 Frame Ra ng: Frame Label Missing

Deficiency Detail

Door label is missing - NFPA 80-2010 4.3.1; NFPA 101-2012 8.3.3.2.2

Required frame label is missing - NFPA 80-2010 6.3.1.1; NFPA 101-2012 8.3.3.2.3

10625938 PASS

Inspector: Carlos Lopez Building: ACA Wall Ra ng: 2 Hour

Inspec on Date: 2/3/2022 Loca on: Staircase 2 Door Ra ng: 90 Minute

Floor: 1 Frame Ra ng: 90 Minute

Deficiency Detail

Door passed inspec on

10625939 FAIL

Inspector: Carlos Lopez Building: ACA Wall Ra ng: 1 Hour

Inspec on Date: 2/3/2022 Loca on: ER entrance Door Ra ng: Door Label Missing

Floor: 1 Frame Ra ng: 90 Minute

Deficiency Detail

Door label is missing - NFPA 80-2010 4.3.1; NFPA 101-2012 8.3.3.2.2

Page 5 of 81 2/9/2022 Version 1

10625940 FAIL

Inspector: Carlos Lopez Building: ACA Wall Ra ng: 1 Hour

Inspec on Date: 2/3/2022 Loca on: ER corridor Door Ra ng: Door Label Missing

Floor: 1 Frame Ra ng: 90 Minute

Deficiency Detail

Door label is missing - NFPA 80-2010 4.3.1; NFPA 101-2012 8.3.3.2.2

10625941 FAIL

Inspector: Carlos Lopez Building: ACA Wall Ra ng: 1 Hour

Inspec on Date: 2/3/2022 Loca on: Corridor to Ambulance bay Door Ra ng: Door Label Missing

Floor: 1 Frame Ra ng: Frame Label Missing

Deficiency Detail

Door label is missing - NFPA 80-2010 4.3.1; NFPA 101-2012 8.3.3.2.2

Required frame label is missing - NFPA 80-2010 6.3.1.1; NFPA 101-2012 8.3.3.2.3

10625942 FAIL

Inspector: Carlos Lopez Building: ACA Wall Ra ng: 1 Hour

Inspec on Date: 2/3/2022 Loca on: Ambulance bay corridor Door Ra ng: Door Label Missing

Floor: 1 Frame Ra ng: Frame Label Missing

Deficiency Detail

Door label is missing - NFPA 80-2010 4.3.1; NFPA 101-2012 8.3.3.2.2

Excessive clearance - NFPA 80-2010 5.2.4.2 (5), NFPA 80-2010 6.3.1.7

Required frame label is missing - NFPA 80-2010 6.3.1.1; NFPA 101-2012 8.3.3.2.3

Page 6 of 81 2/9/2022 Version 1

10625943 FAIL

Inspec on Date: 2/3/2022 Loca on: Fire exit Door Ra ng: 20 Minute

Floor: 1 Frame Ra ng: Frame Label Missing

Deficiency Detail

Door missing filler plate(s) - NFPA 80-2010 5.2.4.2 (1)

Door penetra ons / unused fastener holes - NFPA 80-2010 5.2.4.2 (1); NFPA 105-2010 5.1.4.3

Door ra ng insufficient per wall ra ng requirements - NFPA 101-2012 8.3.4.2

Required frame label is missing - NFPA 80-2010 6.3.1.1; NFPA 101-2012 8.3.3.2.3

10625944 PASS

Inspector: Carlos Lopez Building: ACA Wall Ra ng: 1 Hour

Inspec on Date: 2/3/2022 Loca on: Staircase 1 Door Ra ng: 90 Minute

Floor: 1 Frame Ra ng: 90 Minute

Deficiency Detail

Door passed inspec on

10625945 PASS

Inspector: Carlos Lopez Building: ACA Wall Ra ng: 1 Hour

Inspec on Date: 2/3/2022 Loca on: Fire con Door Ra ng: 45 Minute

Floor: 1 Frame Ra ng: 45 Minute

Deficiency Detail

Door passed inspec on

Page 7 of 81 2/9/2022 Version 1

10625946 FAIL

Inspec on Date: 2/3/2022 Loca on: Triage Door Ra ng: Door Label Missing

Floor: 1 Frame Ra ng: Frame Label Missing

Deficiency Detail

Door does not latch - rubbing issue - NFPA 80-2010 5.2.13, 5.1.3.1

Door label is missing - NFPA 80-2010 4.3.1; NFPA 101-2012 8.3.3.2.2

Door penetra ons / unused fastener holes - NFPA 80-2010 5.2.4.2 (1); NFPA 105-2010 5.1.4.3

Required frame label is missing - NFPA 80-2010 6.3.1.1; NFPA 101-2012 8.3.3.2.3

10625947 FAIL

Inspector: Carlos Lopez Building: ACA Wall Ra ng: 1 Hour

Inspec on Date: 2/3/2022 Loca on: Triage Door Ra ng: Door Label Missing

Floor: 1 Frame Ra ng: Frame Label Missing

Deficiency Detail

Door label is missing - NFPA 80-2010 4.3.1; NFPA 101-2012 8.3.3.2.2

Frame penetra ons / unused fastener holes - NFPA 80-2010 5.2.4.2 (1); NFPA 105-2010 5.1.4.3

Missing / damaged door closer - NFPA 80-2010 5.2.4.2 (4)

Page 8 of 81 2/9/2022 Version 1

10625948 FAIL

Inspec on Date: 2/3/2022 Loca on: Triage Door Ra ng: Door Label Missing

Floor: 1 Frame Ra ng: Frame Label Missing

Deficiency Detail

Door label is missing - NFPA 80-2010 4.3.1; NFPA 101-2012 8.3.3.2.2

Required frame label is missing - NFPA 80-2010 6.3.1.1; NFPA 101-2012 8.3.3.2.3

10625976 FAIL

Inspector: Carlos Lopez Building: ACA Wall Ra ng: 2 Hour

Inspec on Date: 2/3/2022 Loca on: Exit staircase Door Ra ng: Door Label Missing

Floor: 1 Frame Ra ng: Frame Label Missing

Deficiency Detail

Door label is missing - NFPA 80-2010 4.3.1; NFPA 101-2012 8.3.3.2.2

Door missing filler plate(s) - NFPA 80-2010 5.2.4.2 (1)

Door penetra ons / unused fastener holes - NFPA 80-2010 5.2.4.2 (1); NFPA 105-2010 5.1.4.3

Frame penetra ons / unused fastener holes - NFPA 80-2010 5.2.4.2 (1); NFPA 105-2010 5.1.4.3

Page 9 of 81 2/9/2022 Version 1

10625977 FAIL

Inspec on Date: 2/3/2022 Loca on: Exit staircase outside Door Ra ng: Door Label Missing

Floor: 1 Frame Ra ng: Frame Label Missing

Deficiency Detail

Door label is missing - NFPA 80-2010 4.3.1; NFPA 101-2012 8.3.3.2.2

Frame penetra ons / unused fastener holes - NFPA 80-2010 5.2.4.2 (1); NFPA 105-2010 5.1.4.3

Required frame label is missing - NFPA 80-2010 6.3.1.1; NFPA 101-2012 8.3.3.2.3

10625978 FAIL

Inspector: Carlos Lopez Building: ACA Wall Ra ng: 2 Hour

Inspec on Date: 2/3/2022 Loca on: Emergency electric Door Ra ng: 90 Minute

Floor: 1 Frame Ra ng: Frame Label Missing

Deficiency Detail

Required frame label is missing - NFPA 80-2010 6.3.1.1; NFPA 101-2012 8.3.3.2.3

10625950 PASS

Inspector: Carlos Lopez Building: ACA Wall Ra ng: 2 Hour

Inspec on Date: 2/3/2022 Loca on: Staircase 4 Door Ra ng: 90 Minute

Floor: 2 Frame Ra ng: 90 Minute

Deficiency Detail

Page 10 of 81 2/9/2022 Version 1

10625951 FAIL

Inspec on Date: 2/3/2022 Loca on: Staircase 3 Door Ra ng: 90 Minute

Floor: 2 Frame Ra ng: Frame Label Missing

Deficiency Detail

Frame penetra ons / unused fastener holes - NFPA 80-2010 5.2.4.2 (1); NFPA 105-2010 5.1.4.3

Required frame label is missing - NFPA 80-2010 6.3.1.1; NFPA 101-2012 8.3.3.2.3

10625952 FAIL

Inspector: Carlos Lopez Building: ACA Wall Ra ng: 2 Hour

Inspec on Date: 2/3/2022 Loca on: Staircase 1 Door Ra ng: Door Label Missing

Floor: 2 Frame Ra ng: 90 Minute

Deficiency Detail

Door label is missing - NFPA 80-2010 4.3.1; NFPA 101-2012 8.3.3.2.2

Frame penetra ons / unused fastener holes - NFPA 80-2010 5.2.4.2 (1); NFPA 105-2010 5.1.4.3

10625955 FAIL

Inspector: Carlos Lopez Building: ACA Wall Ra ng: 2 Hour

Inspec on Date: 2/3/2022 Loca on: Pipe closest Door Ra ng: 90 Minute

Floor: 2 Frame Ra ng: 90 Minute

Deficiency Detail

Door penetra ons / unused fastener holes - NFPA 80-2010 5.2.4.2 (1); NFPA 105-2010 5.1.4.3

Page 11 of 81 2/9/2022 Version 1

10625956 PASS

Inspec on Date: 2/3/2022 Loca on: Electrical closest Door Ra ng: 90 Minute

Floor: 2 Frame Ra ng: 90 Minute

Deficiency Detail

Door passed inspec on

10625972 PASS

Inspector: Carlos Lopez Building: ACA Wall Ra ng: 2 Hour

Inspec on Date: 2/3/2022 Loca on: Corridor to aca Door Ra ng: 90 Minute

Floor: 2 Frame Ra ng: 90 Minute

Deficiency Detail

Door passed inspec on

10625973 PASS

Inspector: Carlos Lopez Building: ACA Wall Ra ng: 2 Hour

Inspec on Date: 2/3/2022 Loca on: Corridor to ACA Door Ra ng: 90 Minute

Floor: 2 Frame Ra ng: 90 Minute

Deficiency Detail

Door passed inspec on

10625974 PASS

Inspector: Carlos Lopez Building: ACA Wall Ra ng: 2 Hour

Inspec on Date: 2/3/2022 Loca on: Staircase 2 Door Ra ng: 90 Minute

Floor: 2 Frame Ra ng: 90 Minute

Deficiency Detail

Page 12 of 81 2/9/2022 Version 1

10625975 PASS

Inspec on Date: 2/3/2022 Loca on: Staircase 1 Door Ra ng: 90 Minute

Floor: 2 Frame Ra ng: 90 Minute

Deficiency Detail

Door passed inspec on

10625969 PASS

Inspector: Carlos Lopez Building: ACA Wall Ra ng: 2 Hour

Inspec on Date: 2/3/2022 Loca on: Corridor exit OR Door Ra ng: 90 Minute

Floor: 3 Frame Ra ng: 90 Minute

Deficiency Detail

Door passed inspec on

10625970 PASS

Inspector: Carlos Lopez Building: ACA Wall Ra ng: 2 Hour

Inspec on Date: 2/3/2022 Loca on: Pipe room Door Ra ng: 90 Minute

Floor: 3 Frame Ra ng: Label present; no ra ng specified

Deficiency Detail

Door passed inspec on

10625971 FAIL

Inspector: Carlos Lopez Building: ACA Wall Ra ng: 2 Hour

Inspec on Date: 2/3/2022 Loca on: Pipe room Door Ra ng: Door Label Missing

Floor: 3 Frame Ra ng: 90 Minute

Deficiency Detail

Page 13 of 81 2/9/2022 Version 1

10625877 PASS

Inspec on Date: 2/2/2022 Loca on: Staircase Door Ra ng: 90 Minute

Floor: 4 Frame Ra ng: 90 Minute

Deficiency Detail

Door passed inspec on

10625878 FAIL

Inspector: Carlos Lopez Building: ACA Wall Ra ng: 2 Hour

Inspec on Date: 2/2/2022 Loca on: Roof top Door Ra ng: Door Label Missing

Floor: 4 Frame Ra ng: Frame Label Missing

Deficiency Detail

Door label is missing - NFPA 80-2010 4.3.1; NFPA 101-2012 8.3.3.2.2

Required frame label is missing - NFPA 80-2010 6.3.1.1; NFPA 101-2012 8.3.3.2.3

10625879 FAIL

Inspector: Carlos Lopez Building: ACA Wall Ra ng: 2 Hour

Inspec on Date: 2/2/2022 Loca on: Elevator room Door Ra ng: Door Label Missing

Floor: 4 Frame Ra ng: 90 Minute

Deficiency Detail

Door label is missing - NFPA 80-2010 4.3.1; NFPA 101-2012 8.3.3.2.2

Page 14 of 81 2/9/2022 Version 1

10625880 FAIL

Inspec on Date: 2/2/2022 Loca on: Hydrogen storage room Door Ra ng: 90 Minute

Floor: 4 Frame Ra ng: 90 Minute

Deficiency Detail

Closer leaking fluid - NFPA 80-2010 5.2.4.2 (4)

Excessive clearance - NFPA 80-2010 5.2.4.2 (5), NFPA 80-2010 6.3.1.7 Top

10625893 PASS

Inspector: Carlos Lopez Building: Main building Wall Ra ng: 1 Hour

Inspec on Date: 2/3/2022 Loca on: Staircase A Door Ra ng: 90 Minute

Floor: Sub Basement Frame Ra ng: 90 Minute

Deficiency Detail

Door passed inspec on

10625894 FAIL

Inspector: Carlos Lopez Building: Main building Wall Ra ng: 2 Hour

Inspec on Date: 2/3/2022 Loca on: Staircase 5 Door Ra ng: 90 Minute

Floor: Sub Basement Frame Ra ng: Frame Label Missing

Deficiency Detail

Page 15 of 81 2/9/2022 Version 1

10625895 FAIL

Inspector: Carlos Lopez Building: Main building Wall Ra ng: 2 Hour

Inspec on Date: 2/3/2022 Loca on: Elevator machine room Door Ra ng: Door Label Missing

Floor: Sub Basement Frame Ra ng: Frame Label Missing

Deficiency Detail

Door label is missing - NFPA 80-2010 4.3.1; NFPA 101-2012 8.3.3.2.2

Required frame label is missing - NFPA 80-2010 6.3.1.1; NFPA 101-2012 8.3.3.2.3

10625896 FAIL

Inspector: Carlos Lopez Building: Main building Wall Ra ng: 2 Hour

Inspec on Date: 2/3/2022 Loca on: Fire pump room Door Ra ng: 90 Minute

Floor: Sub Basement Frame Ra ng: Label present; no ra ng specified

Deficiency Detail

Door does not latch - NFPA 80-2010 5.2.4.2 (8); NFPA 101-2012 18.3.6.3.5, 19.3.6.3.5 (1)

10625897 FAIL

Inspector: Carlos Lopez Building: Main building Wall Ra ng: 2 Hour

Inspec on Date: 2/3/2022 Loca on: Fire pump room Door Ra ng: 90 Minute

Floor: Sub Basement Frame Ra ng: Label present; no ra ng specified

Deficiency Detail

Excessive clearance - NFPA 80-2010 5.2.4.2 (5), NFPA 80-2010 6.3.1.7 Frame side and top

Page 16 of 81 2/9/2022 Version 1

10625898 PASS

Inspec on Date: 2/3/2022 Loca on: Fire pump room 2 Door Ra ng: 90 Minute

Floor: Sub Basement Frame Ra ng: Label present; no ra ng specified

Deficiency Detail

Door passed inspec on

10625899 PASS

Inspector: Carlos Lopez Building: Main building Wall Ra ng: 2 Hour

Inspec on Date: 2/3/2022 Loca on: Fire pump room Door Ra ng: 90 Minute

Floor: Sub Basement Frame Ra ng: Label present; no ra ng specified

Deficiency Detail

Door passed inspec on

10625900 FAIL

Inspector: Carlos Lopez Building: Main building Wall Ra ng: 1 Hour

Inspec on Date: 2/3/2022 Loca on: Staircase near sub pump Door Ra ng: 90 Minute

Floor: Sub Basement Frame Ra ng: Frame Label Missing

Deficiency Detail

Door does not latch - rubbing issue - NFPA 80-2010 5.2.13, 5.1.3.1

Door has rust-through damage - NFPA 80-2010 5.2.4.2 (1)

Frame has rust-through damage - NFPA 80-2010 5.2.4.2 (1)

Page 17 of 81 2/9/2022 Version 1

10625901 FAIL

Inspec on Date: 2/3/2022 Loca on: Elevator pit room Door Ra ng: 90 Minute

Floor: Sub Basement Frame Ra ng: Frame Label Missing

Deficiency Detail

Required frame label is missing - NFPA 80-2010 6.3.1.1; NFPA 101-2012 8.3.3.2.3

10625902 FAIL

Inspector: Carlos Lopez Building: Main building Wall Ra ng: 2 Hour

Inspec on Date: 2/3/2022 Loca on: Elevator pit Door Ra ng: 90 Minute

Floor: Sub Basement Frame Ra ng: Frame Label Missing

Deficiency Detail

Closer leaking fluid - NFPA 80-2010 5.2.4.2 (4)

Frame penetra ons / unused fastener holes - NFPA 80-2010 5.2.4.2 (1); NFPA 105-2010 5.1.4.3

Required frame label is missing - NFPA 80-2010 6.3.1.1; NFPA 101-2012 8.3.3.2.3

10625903 FAIL

Inspector: Carlos Lopez Building: Main building Wall Ra ng: 2 Hour

Inspec on Date: 2/3/2022 Loca on: Staircase 3 Door Ra ng: 90 Minute

Floor: Basement Frame Ra ng: Frame Label Missing

Deficiency Detail

Frame penetra ons / unused fastener holes - NFPA 80-2010 5.2.4.2 (1); NFPA 105-2010 5.1.4.3

Page 18 of 81 2/9/2022 Version 1

10625904 FAIL

Inspector: Carlos Lopez Building: Main building Wall Ra ng: 1 Hour

Inspec on Date: 2/3/2022 Loca on: Staircase D Door Ra ng: 90 Minute

Floor: Basement Frame Ra ng: 90 Minute

Deficiency Detail

Door penetra ons / unused fastener holes - NFPA 80-2010 5.2.4.2 (1); NFPA 105-2010 5.1.4.3

Frame penetra ons / unused fastener holes - NFPA 80-2010 5.2.4.2 (1); NFPA 105-2010 5.1.4.3

10625905 FAIL

Inspector: Carlos Lopez Building: Main building Wall Ra ng: 2 Hour

Inspec on Date: 2/3/2022 Loca on: Fire ex nguisher closest Door Ra ng: Door Label Missing

Floor: Basement Frame Ra ng: Frame Label Missing

Deficiency Detail

Door label is missing - NFPA 80-2010 4.3.1; NFPA 101-2012 8.3.3.2.2

Missing / damaged door closer - NFPA 80-2010 5.2.4.2 (4)

Required frame label is missing - NFPA 80-2010 6.3.1.1; NFPA 101-2012 8.3.3.2.3

10625907 FAIL

Inspector: Carlos Lopez Building: Main building Wall Ra ng: 2 Hour

Inspec on Date: 2/3/2022 Loca on: Staircase 5 Door Ra ng: 90 Minute

Floor: Basement Frame Ra ng: 90 Minute

Deficiency Detail

Frame penetra ons / unused fastener holes - NFPA 80-2010 5.2.4.2 (1); NFPA 105-2010 5.1.4.3

7500 W 160th St., S lwell, KS 66085 ● (855) 714- FIRE (3473) ● www.firedoorsolu ons.com

Page 19 of 81 2/9/2022 Version 1

10625908 FAIL

Inspec on Date: 2/3/2022 Loca on: Pipe door Door Ra ng: Door Label Missing

Floor: Basement Frame Ra ng: Frame Label Missing

Deficiency Detail

Door label is missing - NFPA 80-2010 4.3.1; NFPA 101-2012 8.3.3.2.2

Door missing filler plate(s) - NFPA 80-2010 5.2.4.2 (1)

Door penetra ons / unused fastener holes - NFPA 80-2010 5.2.4.2 (1); NFPA 105-2010 5.1.4.3

Excessive clearance - NFPA 80-2010 5.2.4.2 (5), NFPA 80-2010 6.3.1.7 Strike side

Excessive undercut - NFPA 80-2010 5.2.4.2 (5), NFPA 80-2010 4.8.4; NFPA 101-2012 18.3.6.3 (2), 19.3.6.3.4

Frame missing filler plate(s) - NFPA 80-2010 5.2.4.2 (1)

Frame penetra ons / unused fastener holes - NFPA 80-2010 5.2.4.2 (1); NFPA 105-2010 5.1.4.3

Incorrect type of hinge(s) / missing hinge(s) / damaged hinge(s) - NFPA 80-2010 6.4.3.1.2

Page 20 of 81 2/9/2022 Version 1

10625909 FAIL

Inspec on Date: 2/3/2022 Loca on: EMS trash room Door Ra ng: 90 Minute

Floor: Basement Frame Ra ng: Frame Label Missing

Deficiency Detail

Door does not latch - NFPA 80-2010 5.2.4.2 (8); NFPA 101-2012 18.3.6.3.5, 19.3.6.3.5 (1)

Frame penetra ons / unused fastener holes - NFPA 80-2010 5.2.4.2 (1); NFPA 105-2010 5.1.4.3

Required frame label is missing - NFPA 80-2010 6.3.1.1; NFPA 101-2012 8.3.3.2.3

10625910 FAIL

Inspector: Carlos Lopez Building: Main building Wall Ra ng: 2 Hour

Inspec on Date: 2/3/2022 Loca on: EMS trash room Door Ra ng: 90 Minute

Floor: Basement Frame Ra ng: Frame Label Missing

Deficiency Detail

Door does not latch - NFPA 80-2010 5.2.4.2 (8); NFPA 101-2012 18.3.6.3.5, 19.3.6.3.5 (1)

Door penetra ons / unused fastener holes - NFPA 80-2010 5.2.4.2 (1); NFPA 105-2010 5.1.4.3

Frame penetra ons / unused fastener holes - NFPA 80-2010 5.2.4.2 (1); NFPA 105-2010 5.1.4.3

Page 21 of 81 2/9/2022 Version 1

10625911 PASS

Inspec on Date: 2/3/2022 Loca on: Corridor F Wing Door Ra ng: 90 Minute

Floor: Basement Frame Ra ng: 90 Minute

Deficiency Detail

Door passed inspec on

10625912 PASS

Inspector: Carlos Lopez Building: Main building Wall Ra ng: 2 Hour

Inspec on Date: 2/3/2022 Loca on: Corridor to F wing Door Ra ng: 90 Minute

Floor: Basement Frame Ra ng: 90 Minute

Deficiency Detail

Door passed inspec on

10625913 FAIL

Inspector: Carlos Lopez Building: Main building Wall Ra ng: 2 Hour

Inspec on Date: 2/3/2022 Loca on: Corridor F wing Door Ra ng: 90 Minute

Floor: Basement Frame Ra ng: Frame Label Missing

Deficiency Detail

Page 22 of 81 2/9/2022 Version 1

10625914 FAIL

Inspec on Date: 2/3/2022 Loca on: Corridor to F wing Door Ra ng: Label illegible; legibility required per wall ra ng

Floor: Basement Frame Ra ng: Frame Label Missing

Deficiency Detail

Door does not latch - rubbing issue - NFPA 80-2010 5.2.13, 5.1.3.1 Top frame

Door label is illegible - NFPA 80-2010 4.2.2; NFPA 101-2012 8.3.3.2.3

Required frame label is missing - NFPA 80-2010 6.3.1.1; NFPA 101-2012 8.3.3.2.3

10625915 FAIL

Inspector: Carlos Lopez Building: Main building Wall Ra ng: 2 Hour

Inspec on Date: 2/3/2022 Loca on: Staircase 1 Door Ra ng: 90 Minute

Floor: Basement Frame Ra ng: Frame Label Missing

Deficiency Detail

Required frame label is missing - NFPA 80-2010 6.3.1.1; NFPA 101-2012 8.3.3.2.3

10625916 FAIL

Inspector: Carlos Lopez Building: Main building Wall Ra ng: 1 Hour

Inspec on Date: 2/3/2022 Loca on: Staircase DB44 Door Ra ng: 90 Minute

Floor: Basement Frame Ra ng: Frame Label Missing

Deficiency Detail

Page 23 of 81 2/9/2022 Version 1

10625917 FAIL

Inspec on Date: 2/3/2022 Loca on: Exit door Door Ra ng: Door Label Missing

Floor: 1 Frame Ra ng: Frame Label Missing

Deficiency Detail

Door label is missing - NFPA 80-2010 4.3.1; NFPA 101-2012 8.3.3.2.2

Door missing filler plate(s) - NFPA 80-2010 5.2.4.2 (1)

Door penetra ons / unused fastener holes - NFPA 80-2010 5.2.4.2 (1); NFPA 105-2010 5.1.4.3

Frame missing filler plate(s) - NFPA 80-2010 5.2.4.2 (1)

Frame penetra ons / unused fastener holes - NFPA 80-2010 5.2.4.2 (1); NFPA 105-2010 5.1.4.3

Page 24 of 81 2/9/2022 Version 1

10625918 FAIL

Inspec on Date: 2/3/2022 Loca on: Fire exit door Door Ra ng: 90 Minute

Floor: 1 Frame Ra ng: Label illegible; legibility required per wall ra ng

Deficiency Detail

Door penetra ons / unused fastener holes - NFPA 80-2010 5.2.4.2 (1); NFPA 105-2010 5.1.4.3

Frame penetra ons / unused fastener holes - NFPA 80-2010 5.2.4.2 (1); NFPA 105-2010 5.1.4.3

Required frame label is illegible - NFPA 80-2010 4.2.2; NFPA 101-2012 8.3.3.2.3

10625919 FAIL

Inspector: Carlos Lopez Building: Main building Wall Ra ng: 2 Hour

Inspec on Date: 2/3/2022 Loca on: Staircase 4 Door Ra ng: 90 Minute

Floor: 1 Frame Ra ng: 90 Minute

Deficiency Detail

Excessive clearance - NFPA 80-2010 5.2.4.2 (5), NFPA 80-2010 6.3.1.7

Frame missing filler plate(s) - NFPA 80-2010 5.2.4.2 (1)

Page 25 of 81 2/9/2022 Version 1

10625920 PASS

Inspec on Date: 2/3/2022 Loca on: Bio Door Ra ng: 90 Minute

Floor: 1 Frame Ra ng: Frame Label Missing

Deficiency Detail

Door passed inspec on

10625921 FAIL

Inspector: Carlos Lopez Building: Main building Wall Ra ng: 1 Hour

Inspec on Date: 2/3/2022 Loca on: Pipe closest Door Ra ng: Door Label Missing

Floor: 1 Frame Ra ng: Frame Label Missing

Deficiency Detail

Door label is missing - NFPA 80-2010 4.3.1; NFPA 101-2012 8.3.3.2.2

Excessive clearance - NFPA 80-2010 5.2.4.2 (5), NFPA 80-2010 6.3.1.7

Required frame label is missing - NFPA 80-2010 6.3.1.1; NFPA 101-2012 8.3.3.2.3

10625922 FAIL

Inspector: Carlos Lopez Building: Main building Wall Ra ng: 1 Hour

Inspec on Date: 2/3/2022 Loca on: Staircase 8 Door Ra ng: 90 Minute

Floor: 1 Frame Ra ng: 90 Minute

Deficiency Detail

Page 26 of 81 2/9/2022 Version 1

10625923 FAIL

Inspec on Date: 2/3/2022 Loca on: Corridor to 1A Door Ra ng: 90 Minute

Floor: 1 Frame Ra ng: 90 Minute

Deficiency Detail

Excessive clearance - NFPA 80-2010 5.2.4.2 (5), NFPA 80-2010 6.3.1.7

10625924 PASS

Inspector: Carlos Lopez Building: Main building Wall Ra ng: 2 Hour

Inspec on Date: 2/3/2022 Loca on: Corridor to 1A Door Ra ng: 90 Minute

Floor: 1 Frame Ra ng: Label present; no ra ng specified

Deficiency Detail

Page 27 of 81 2/9/2022 Version 1

10625925 FAIL

Inspec on Date: 2/3/2022 Loca on: Staircase 3 Door Ra ng: 90 Minute

Floor: 1 Frame Ra ng: Label present; no ra ng specified

Deficiency Detail

Door missing filler plate(s) - NFPA 80-2010 5.2.4.2 (1)

Door penetra ons / unused fastener holes - NFPA 80-2010 5.2.4.2 (1); NFPA 105-2010 5.1.4.3

Frame missing filler plate(s) - NFPA 80-2010 5.2.4.2 (1)

Frame penetra ons / unused fastener holes - NFPA 80-2010 5.2.4.2 (1); NFPA 105-2010 5.1.4.3

10625926 FAIL

Inspector: Carlos Lopez Building: Main building Wall Ra ng: 2 Hour

Inspec on Date: 2/3/2022 Loca on: Staircase 1 Door Ra ng: 90 Minute

Floor: 1 Frame Ra ng: Frame Label Missing

Deficiency Detail

Required frame label is missing - NFPA 80-2010 6.3.1.1; NFPA 101-2012 8.3.3.2.3

10625927 FAIL

Inspector: Carlos Lopez Building: Main building Wall Ra ng: 2 Hour

Inspec on Date: 2/3/2022 Loca on: Fire exit door Door Ra ng: Door Label Missing

Floor: 1 Frame Ra ng: 90 Minute

Deficiency Detail

Page 28 of 81 2/9/2022 Version 1

10625928 FAIL

Inspec on Date: 2/3/2022 Loca on: Staircase 5 Door Ra ng: 90 Minute

Floor: 1 Frame Ra ng: Frame Label Missing

Deficiency Detail

Excessive undercut - NFPA 80-2010 5.2.4.2 (5), NFPA 80-2010 4.8.4; NFPA 101-2012 18.3.6.3 (2), 19.3.6.3.4

Frame penetra ons / unused fastener holes - NFPA 80-2010 5.2.4.2 (1); NFPA 105-2010 5.1.4.3

Required frame label is missing - NFPA 80-2010 6.3.1.1; NFPA 101-2012 8.3.3.2.3

10625929 FAIL

Inspector: Carlos Lopez Building: Main building Wall Ra ng: 2 Hour

Inspec on Date: 2/3/2022 Loca on: Pipe closest Door Ra ng: Door Label Missing

Floor: 1 Frame Ra ng: Frame Label Missing

Deficiency Detail

Door label is missing - NFPA 80-2010 4.3.1; NFPA 101-2012 8.3.3.2.2

Excessive clearance - NFPA 80-2010 5.2.4.2 (5), NFPA 80-2010 6.3.1.7

Page 29 of 81 2/9/2022 Version 1

10625930 FAIL

Inspec on Date: 2/3/2022 Loca on: Staircase 2 Door Ra ng: 90 Minute

Floor: 1 Frame Ra ng: Frame Label Missing

Deficiency Detail

Door penetra ons / unused fastener holes - NFPA 80-2010 5.2.4.2 (1); NFPA 105-2010 5.1.4.3

Excessive clearance - NFPA 80-2010 5.2.4.2 (5), NFPA 80-2010 6.3.1.7

Frame penetra ons / unused fastener holes - NFPA 80-2010 5.2.4.2 (1); NFPA 105-2010 5.1.4.3

Page 30 of 81 2/9/2022 Version 1

10625931 FAIL

Inspec on Date: 2/3/2022 Loca on: Fire exit door Door Ra ng: Door Label Missing

Floor: 1 Frame Ra ng: Frame Label Missing

Deficiency Detail

Door label is missing - NFPA 80-2010 4.3.1; NFPA 101-2012 8.3.3.2.2

Door missing filler plate(s) - NFPA 80-2010 5.2.4.2 (1)

Door penetra ons / unused fastener holes - NFPA 80-2010 5.2.4.2 (1); NFPA 105-2010 5.1.4.3

Frame missing filler plate(s) - NFPA 80-2010 5.2.4.2 (1)

Frame penetra ons / unused fastener holes - NFPA 80-2010 5.2.4.2 (1); NFPA 105-2010 5.1.4.3

Required frame label is missing - NFPA 80-2010 6.3.1.1; NFPA 101-2012 8.3.3.2.3

10625932 FAIL

Inspector: Carlos Lopez Building: Main building Wall Ra ng: 2 Hour

Inspec on Date: 2/3/2022 Loca on: Fire exit Door Ra ng: Door Label Missing

Floor: 1 Frame Ra ng: Frame Label Missing

Deficiency Detail

Door label is missing - NFPA 80-2010 4.3.1; NFPA 101-2012 8.3.3.2.2

Page 31 of 81 2/9/2022 Version 1

10625949 FAIL

Inspec on Date: 2/3/2022 Loca on: Wing D Door Ra ng: Label illegible; legibility required per wall ra ng

Floor: 2 Frame Ra ng: Label illegible; legibility required per wall ra ng

Deficiency Detail

Door label is illegible - NFPA 80-2010 4.2.2; NFPA 101-2012 8.3.3.2.3

Required frame label is illegible - NFPA 80-2010 4.2.2; NFPA 101-2012 8.3.3.2.3

10625953 PASS

Inspector: Carlos Lopez Building: Main building Wall Ra ng: 2 Hour

Inspec on Date: 2/3/2022 Loca on: Staircase 2 Door Ra ng: 90 Minute

Floor: 2 Frame Ra ng: 90 Minute

Deficiency Detail

Door passed inspec on

10625954 FAIL

Inspector: Carlos Lopez Building: Main building Wall Ra ng: 2 Hour

Inspec on Date: 2/3/2022 Loca on: Pipe closest Door Ra ng: Door Label Missing

Floor: 2 Frame Ra ng: 90 Minute

Deficiency Detail

Door label is missing - NFPA 80-2010 4.3.1; NFPA 101-2012 8.3.3.2.2

Door penetra ons / unused fastener holes - NFPA 80-2010 5.2.4.2 (1); NFPA 105-2010 5.1.4.3

Missing / damaged door closer - NFPA 80-2010 5.2.4.2 (4)

Page 32 of 81 2/9/2022 Version 1

10625957 PASS

Inspec on Date: 2/3/2022 Loca on: Staircase 5 Door Ra ng: 90 Minute

Floor: 2 Frame Ra ng: 90 Minute

Deficiency Detail

Door passed inspec on

10625958 FAIL

Inspector: Carlos Lopez Building: Main building Wall Ra ng: 2 Hour

Inspec on Date: 2/3/2022 Loca on: Chase door Door Ra ng: Door Label Missing

Floor: 2 Frame Ra ng: Frame Label Missing

Deficiency Detail

Door label is missing - NFPA 80-2010 4.3.1; NFPA 101-2012 8.3.3.2.2

Missing / damaged door closer - NFPA 80-2010 5.2.4.2 (4)

Required frame label is missing - NFPA 80-2010 6.3.1.1; NFPA 101-2012 8.3.3.2.3

10625881 PASS

Inspector: Carlos Lopez Building: Main building Wall Ra ng: 2 Hour

Inspec on Date: 2/3/2022 Loca on: Corridor by elevator Door Ra ng: 90 Minute

Floor: 3 Frame Ra ng: 90 Minute

Deficiency Detail

Page 33 of 81 2/9/2022 Version 1

10625882 PASS

Inspec on Date: 2/3/2022 Loca on: Corridor by elevator Door Ra ng: 90 Minute

Floor: 3 Frame Ra ng: 90 Minute

Deficiency Detail

Door passed inspec on

10625883 PASS

Inspector: Carlos Lopez Building: Main building Wall Ra ng: 2 Hour

Inspec on Date: 2/3/2022 Loca on: Staircase 4 Door Ra ng: 90 Minute

Floor: 3 Frame Ra ng: 90 Minute

Deficiency Detail

Door passed inspec on

10625884 FAIL

Inspector: Carlos Lopez Building: Main building Wall Ra ng: 2 Hour

Inspec on Date: 2/3/2022 Loca on: Staircase 3 Door Ra ng: 90 Minute

Floor: 3 Frame Ra ng: Label illegible; legibility required per wall ra ng

Deficiency Detail

Door does not latch - rubbing issue - NFPA 80-2010 5.2.13, 5.1.3.1 Rubs on frame

Frame penetra ons / unused fastener holes - NFPA 80-2010 5.2.4.2 (1); NFPA 105-2010 5.1.4.3

Required frame label is illegible - NFPA 80-2010 4.2.2; NFPA 101-2012 8.3.3.2.3

Page 34 of 81 2/9/2022 Version 1

10625885 FAIL

Inspec on Date: 2/3/2022 Loca on: Staircase 1 Door Ra ng: 90 Minute

Floor: 3 Frame Ra ng: Frame Label Missing

Deficiency Detail

Excessive clearance - NFPA 80-2010 5.2.4.2 (5), NFPA 80-2010 6.3.1.7

Required frame label is missing - NFPA 80-2010 6.3.1.1; NFPA 101-2012 8.3.3.2.3

10625886 PASS

Inspector: Carlos Lopez Building: Main building Wall Ra ng: 2 Hour

Inspec on Date: 2/3/2022 Loca on: Staircase 5 Door Ra ng: 90 Minute

Floor: 3 Frame Ra ng: 90 Minute

Deficiency Detail

Page 35 of 81 2/9/2022 Version 1

10625887 FAIL

Inspec on Date: 2/3/2022 Loca on: Trash chute Door Ra ng: 60 Minute

Floor: 3 Frame Ra ng: Frame Label Missing

Deficiency Detail

Door ra ng insufficient per wall ra ng requirements - NFPA 101-2012 8.3.4.2

Excessive clearance - NFPA 80-2010 5.2.4.2 (5), NFPA 80-2010 6.3.1.7 Strike side of door

Major damage / exposed mineral core - NFPA 80-2010 5.2.4.2 (3); NFPA 105-2010 5.1.4

Missing / damaged door closer - NFPA 80-2010 5.2.4.2 (4)

Required frame label is missing - NFPA 80-2010 6.3.1.1; NFPA 101-2012 8.3.3.2.3

10625888 FAIL

Inspector: Carlos Lopez Building: Main building Wall Ra ng: 1 Hour

Inspec on Date: 2/3/2022 Loca on: Staircase in store Door Ra ng: 90 Minute

Floor: 3 Frame Ra ng: Frame Label Missing

Deficiency Detail

Page 36 of 81 2/9/2022 Version 1

10625889 FAIL

Inspec on Date: 2/3/2022 Loca on: Storage Door Ra ng: Door Label Missing

Floor: 3 Frame Ra ng: Frame Label Missing

Deficiency Detail

Door does not latch - NFPA 80-2010 5.2.4.2 (8); NFPA 101-2012 18.3.6.3.5, 19.3.6.3.5 (1)

Door label is missing - NFPA 80-2010 4.3.1; NFPA 101-2012 8.3.3.2.2

Missing / damaged door closer - NFPA 80-2010 5.2.4.2 (4)

Required frame label is missing - NFPA 80-2010 6.3.1.1; NFPA 101-2012 8.3.3.2.3

10625890 PASS

Inspector: Carlos Lopez Building: Main building Wall Ra ng: 2 Hour

Inspec on Date: 2/3/2022 Loca on: Staircase 2 Door Ra ng: 90 Minute

Floor: 3 Frame Ra ng: 90 Minute

Deficiency Detail

Page 37 of 81 2/9/2022 Version 1

10625891 FAIL

Inspec on Date: 2/3/2022 Loca on: Fire ex nguisher closest Door Ra ng: 90 Minute

Floor: 3 Frame Ra ng: Frame Label Missing

Deficiency Detail

Excessive clearance - NFPA 80-2010 5.2.4.2 (5), NFPA 80-2010 6.3.1.7

Missing / damaged door closer - NFPA 80-2010 5.2.4.2 (4)

Required frame label is missing - NFPA 80-2010 6.3.1.1; NFPA 101-2012 8.3.3.2.3

10625892 FAIL

Inspector: Carlos Lopez Building: Main building Wall Ra ng: 2 Hour

Inspec on Date: 2/3/2022 Loca on: Soiled linen Door Ra ng: 90 Minute

Floor: 3 Frame Ra ng: Frame Label Missing

Deficiency Detail

Missing / damaged door closer - NFPA 80-2010 5.2.4.2 (4)

Page 38 of 81 2/9/2022 Version 1

10625961 FAIL

Inspector: Carlos Lopez Building: Main building Wall Ra ng: Smoke Barrier

Inspec on Date: 2/3/2022 Loca on: Storage Door Ra ng: 45 Minute

Floor: 3 Frame Ra ng: Frame Label Missing

Deficiency Detail

Excessive clearance - NFPA 80-2010 5.2.4.2 (5), NFPA 80-2010 6.3.1.7

Required frame label is missing - NFPA 80-2010 6.3.1.1; NFPA 101-2012 8.3.3.2.3

10625962 PASS

Inspector: Carlos Lopez Building: Main building Wall Ra ng: Smoke Barrier

Inspec on Date: 2/3/2022 Loca on: Housekeeping Door Ra ng: 45 Minute

Floor: 3 Frame Ra ng: 90 Minute

Deficiency Detail

Door passed inspec on

10625963 FAIL

Inspector: Carlos Lopez Building: Main building Wall Ra ng: Smoke Barrier

Inspec on Date: 2/3/2022 Loca on: Control center corridor Door Ra ng: Door Label Missing

Floor: 3 Frame Ra ng: Frame Label Missing

Deficiency Detail

Door label is missing - NFPA 80-2010 4.3.1; NFPA 101-2012 8.3.3.2.2

Page 39 of 81 2/9/2022 Version 1

10625964 FAIL

Inspec on Date: 2/3/2022 Loca on: Control center corridor Door Ra ng: Door Label Missing

Floor: 3 Frame Ra ng: Frame Label Missing

Deficiency Detail

Door label is missing - NFPA 80-2010 4.3.1; NFPA 101-2012 8.3.3.2.2

Required frame label is missing - NFPA 80-2010 6.3.1.1; NFPA 101-2012 8.3.3.2.3

10625965 FAIL

Inspector: Carlos Lopez Building: Main building Wall Ra ng: Smoke Barrier

Inspec on Date: 2/3/2022 Loca on: Nurse sta on Door Ra ng: Door Label Missing

Floor: 3 Frame Ra ng: Frame Label Missing

Deficiency Detail

Door label is missing - NFPA 80-2010 4.3.1; NFPA 101-2012 8.3.3.2.2

Required frame label is missing - NFPA 80-2010 6.3.1.1; NFPA 101-2012 8.3.3.2.3

10625966 FAIL

Inspector: Carlos Lopez Building: Main building Wall Ra ng: Smoke Barrier

Inspec on Date: 2/3/2022 Loca on: Corridor exit OR Door Ra ng: 90 Minute

Floor: 3 Frame Ra ng: Frame Label Missing

Deficiency Detail

Required frame label is missing - NFPA 80-2010 6.3.1.1; NFPA 101-2012 8.3.3.2.3

10625967 FAIL

Inspector: Carlos Lopez Building: Main building Wall Ra ng: Smoke Barrier

Inspec on Date: 2/3/2022 Loca on: Exit door OR Door Ra ng: 90 Minute

Floor: 3 Frame Ra ng: Frame Label Missing

Deficiency Detail

Page 40 of 81 2/9/2022 Version 1

10625968 PASS

Inspec on Date: 2/3/2022 Loca on: Corridor exit Door Ra ng: 90 Minute

Floor: 3 Frame Ra ng: 90 Minute

Deficiency Detail

Door passed inspec on

10625870 FAIL

Inspector: Carlos Lopez Building: Main building Wall Ra ng: 2 Hour

Inspec on Date: 2/2/2022 Loca on: Staircase 3 Door Ra ng: 90 Minute

Floor: 4 Frame Ra ng: 90 Minute

Deficiency Detail

Frame penetra ons / unused fastener holes - NFPA 80-2010 5.2.4.2 (1); NFPA 105-2010 5.1.4.3

10625871 FAIL

Inspector: Carlos Lopez Building: Main building Wall Ra ng: 2 Hour

Inspec on Date: 2/2/2022 Loca on: Staircase 4 Door Ra ng: 90 Minute

Floor: 4 Frame Ra ng: 90 Minute

Deficiency Detail

Page 41 of 81 2/9/2022 Version 1

10625872 FAIL

Inspec on Date: 2/2/2022 Loca on: Staircase 5 Door Ra ng: Label illegible; legibility required per wall ra ng

Floor: 4 Frame Ra ng: Frame Label Missing

Deficiency Detail

Door label is illegible - NFPA 80-2010 4.2.2; NFPA 101-2012 8.3.3.2.3

Excessive clearance - NFPA 80-2010 5.2.4.2 (5), NFPA 80-2010 6.3.1.7

Frame penetra ons / unused fastener holes - NFPA 80-2010 5.2.4.2 (1); NFPA 105-2010 5.1.4.3

Required frame label is missing - NFPA 80-2010 6.3.1.1; NFPA 101-2012 8.3.3.2.3

10625873 FAIL

Inspector: Carlos Lopez Building: Main building Wall Ra ng: 2 Hour

Inspec on Date: 2/2/2022 Loca on: Pipe room Door Ra ng: Door Label Missing

Floor: 4 Frame Ra ng: Frame Label Missing

Deficiency Detail

Door label is missing - NFPA 80-2010 4.3.1; NFPA 101-2012 8.3.3.2.2

Excessive clearance - NFPA 80-2010 5.2.4.2 (5), NFPA 80-2010 6.3.1.7 Latch side

Page 42 of 81 2/9/2022 Version 1

10625874 FAIL

Inspec on Date: 2/2/2022 Loca on: Staircase Door Ra ng: 90 Minute

Floor: 4 Frame Ra ng: 90 Minute

Deficiency Detail

Frame penetra ons / unused fastener holes - NFPA 80-2010 5.2.4.2 (1); NFPA 105-2010 5.1.4.3

10625875 FAIL

Inspector: Carlos Lopez Building: Main building Wall Ra ng: 2 Hour

Inspec on Date: 2/2/2022 Loca on: Soiled linen Door Ra ng: 90 Minute

Floor: 4 Frame Ra ng: Frame Label Missing

Deficiency Detail

Required frame label is missing - NFPA 80-2010 6.3.1.1; NFPA 101-2012 8.3.3.2.3

10625876 FAIL

Inspector: Carlos Lopez Building: Main building Wall Ra ng: 2 Hour

Inspec on Date: 2/2/2022 Loca on: Staircase 1 Door Ra ng: 90 Minute

Floor: 4 Frame Ra ng: Frame Label Missing

Deficiency Detail

Required frame label is missing - NFPA 80-2010 6.3.1.1; NFPA 101-2012 8.3.3.2.3

10625843 FAIL

Inspector: Carlos Lopez Building: Main building Wall Ra ng: 2 Hour

Inspec on Date: 2/2/2022 Loca on: Staircase 4 Door Ra ng: 90 Minute

Floor: 5 Frame Ra ng: Frame Label Missing

Deficiency Detail

Page 43 of 81 2/9/2022 Version 1

10625844 FAIL

Inspec on Date: 2/2/2022 Loca on: Fire ex nguisher closest Door Ra ng: Door Label Missing

Floor: 5 Frame Ra ng: Frame Label Missing

Deficiency Detail

Door label is missing - NFPA 80-2010 4.3.1; NFPA 101-2012 8.3.3.2.2

Missing / damaged door closer - NFPA 80-2010 5.2.4.2 (4)

Required frame label is missing - NFPA 80-2010 6.3.1.1; NFPA 101-2012 8.3.3.2.3

10625845 PASS

Inspector: Carlos Lopez Building: Main building Wall Ra ng: Smoke Barrier

Inspec on Date: 2/2/2022 Loca on: Corridor to endoscopy Door Ra ng: 90 Minute

Floor: 5 Frame Ra ng: No label present / not required per wall ra ng

Deficiency Detail

Door passed inspec on

10625846 PASS

Inspector: Carlos Lopez Building: Main building Wall Ra ng: Smoke Barrier

Inspec on Date: 2/2/2022 Loca on: Endoscopy Door Ra ng: No label present / not required per wall ra ng

Floor: 5 Frame Ra ng: No label present / not required per wall ra ng

Deficiency Detail

Page 44 of 81 2/9/2022 Version 1

10625847 PASS

Inspec on Date: 2/2/2022 Loca on: Endoscopy nurse sta on Door Ra ng: No label present / not required per wall ra ng

Floor: 5 Frame Ra ng: No label present / not required per wall ra ng

Deficiency Detail

Door passed inspec on

10625848 FAIL

Inspector: Carlos Lopez Building: Main building Wall Ra ng: 2 Hour

Inspec on Date: 2/2/2022 Loca on: Staircase 3 Door Ra ng: 90 Minute

Floor: 5 Frame Ra ng: Frame Label Missing

Deficiency Detail

Door penetra ons / unused fastener holes - NFPA 80-2010 5.2.4.2 (1); NFPA 105-2010 5.1.4.3

Frame penetra ons / unused fastener holes - NFPA 80-2010 5.2.4.2 (1); NFPA 105-2010 5.1.4.3

Required frame label is missing - NFPA 80-2010 6.3.1.1; NFPA 101-2012 8.3.3.2.3

10625849 FAIL

Inspector: Carlos Lopez Building: Main building Wall Ra ng: 2 Hour

Inspec on Date: 2/2/2022 Loca on: Soiled linen Door Ra ng: 90 Minute

Floor: 5 Frame Ra ng: Frame Label Missing

Deficiency Detail

Frame penetra ons / unused fastener holes - NFPA 80-2010 5.2.4.2 (1); NFPA 105-2010 5.1.4.3

Page 45 of 81 2/9/2022 Version 1

10625850 FAIL

Inspec on Date: 2/2/2022 Loca on: Pipe closest Door Ra ng: 90 Minute

Floor: 5 Frame Ra ng: 3 Hour

Deficiency Detail

Excessive clearance - NFPA 80-2010 5.2.4.2 (5), NFPA 80-2010 6.3.1.7 Top

10625851 FAIL

Inspector: Carlos Lopez Building: Main building Wall Ra ng: 2 Hour Fire/Smoke

Inspec on Date: 2/2/2022 Loca on: Staircase 1 Door Ra ng: 90 Minute

Floor: 5 Frame Ra ng: 90 Minute

Deficiency Detail

Excessive clearance - NFPA 80-2010 5.2.4.2 (5), NFPA 80-2010 6.3.1.7

Frame penetra ons / unused fastener holes - NFPA 80-2010 5.2.4.2 (1); NFPA 105-2010 5.1.4.3

10625852 FAIL

Inspector: Carlos Lopez Building: Main building Wall Ra ng: Smoke Barrier

Inspec on Date: 2/2/2022 Loca on: Corridor by elevator Door Ra ng: No label present / not required per wall ra ng

Floor: 5 Frame Ra ng: Label present; no ra ng specified

Deficiency Detail

Door does not latch - rubbing issue - NFPA 80-2010 5.2.13, 5.1.3.1

Page 46 of 81 2/9/2022 Version 1

10625853 PASS

Inspec on Date: 2/2/2022 Loca on: Corridor by elevator Door Ra ng: No label present / not required per wall ra ng

Floor: 5 Frame Ra ng: Label present; no ra ng specified

Deficiency Detail

Door passed inspec on

10625854 FAIL

Inspector: Carlos Lopez Building: Main building Wall Ra ng: 2 Hour

Inspec on Date: 2/2/2022 Loca on: staircase 5 Door Ra ng: 90 Minute

Floor: 5 Frame Ra ng: Label illegible; legibility required per wall ra ng

Deficiency Detail

Frame penetra ons / unused fastener holes - NFPA 80-2010 5.2.4.2 (1); NFPA 105-2010 5.1.4.3

Required frame label is illegible - NFPA 80-2010 4.2.2; NFPA 101-2012 8.3.3.2.3

10625857 FAIL

Inspector: Carlos Lopez Building: Main building Wall Ra ng: Smoke Barrier

Inspec on Date: 2/2/2022 Loca on: Pipe room Door Ra ng: No label present / not required per wall ra ng

Floor: 5 Frame Ra ng: No label present / not required per wall ra ng

Deficiency Detail

Excessive undercut - NFPA 80-2010 5.2.4.2 (5), NFPA 80-2010 4.8.4; NFPA 101-2012 18.3.6.3 (2), 19.3.6.3.4

Page 47 of 81 2/9/2022 Version 1

10625858 FAIL

Inspec on Date: 2/2/2022 Loca on: Pipe room Door Ra ng: No label present / not required per wall ra ng

Floor: 5 Frame Ra ng: No label present / not required per wall ra ng

Deficiency Detail

Excessive clearance - NFPA 80-2010 5.2.4.2 (5), NFPA 80-2010 6.3.1.7

Excessive undercut - NFPA 80-2010 5.2.4.2 (5), NFPA 80-2010 4.8.4; NFPA 101-2012 18.3.6.3 (2), 19.3.6.3.4

10625859 FAIL

Inspector: Carlos Lopez Building: Main building Wall Ra ng: Smoke Barrier

Inspec on Date: 2/2/2022 Loca on: Exam room 1 Door Ra ng: No label present / not required per wall ra ng

Floor: 5 Frame Ra ng: No label present / not required per wall ra ng

Deficiency Detail

Missing / damaged door closer - NFPA 80-2010 5.2.4.2 (4)

10625860 FAIL

Inspector: Carlos Lopez Building: Main building Wall Ra ng: Smoke Barrier

Inspec on Date: 2/2/2022 Loca on: Exam room 2 Door Ra ng: No label present / not required per wall ra ng

Floor: 5 Frame Ra ng: No label present / not required per wall ra ng

Deficiency Detail

Excessive clearance - NFPA 80-2010 5.2.4.2 (5), NFPA 80-2010 6.3.1.7

Page 48 of 81 2/9/2022 Version 1

10625861 FAIL

Inspec on Date: 2/2/2022 Loca on: Pipe room Door Ra ng: No label present / not required per wall ra ng

Floor: 5 Frame Ra ng: No label present / not required per wall ra ng

Deficiency Detail

Excessive clearance - NFPA 80-2010 5.2.4.2 (5), NFPA 80-2010 6.3.1.7 Latch side

Excessive undercut - NFPA 80-2010 5.2.4.2 (5), NFPA 80-2010 4.8.4; NFPA 101-2012 18.3.6.3 (2), 19.3.6.3.4

10625862 FAIL

Inspector: Carlos Lopez Building: Main building Wall Ra ng: Smoke Barrier

Inspec on Date: 2/2/2022 Loca on: Exam room 3 Door Ra ng: No label present / not required per wall ra ng

Floor: 5 Frame Ra ng: No label present / not required per wall ra ng

Deficiency Detail

Missing / damaged door closer - NFPA 80-2010 5.2.4.2 (4)

10625863 FAIL

Inspector: Carlos Lopez Building: Main building Wall Ra ng: Smoke Barrier

Inspec on Date: 2/2/2022 Loca on: Exam room 4 Door Ra ng: No label present / not required per wall ra ng

Floor: 5 Frame Ra ng: No label present / not required per wall ra ng

Deficiency Detail

Page 49 of 81 2/9/2022 Version 1

10625864 FAIL

Inspec on Date: 2/2/2022 Loca on: Staircase 2 Door Ra ng: 90 Minute

Floor: 5 Frame Ra ng: Frame Label Missing

Deficiency Detail

Required frame label is missing - NFPA 80-2010 6.3.1.1; NFPA 101-2012 8.3.3.2.3

10625865 FAIL

Inspector: Carlos Lopez Building: Main building Wall Ra ng: 2 Hour

Inspec on Date: 2/2/2022 Loca on: Soiled linen Door Ra ng: 90 Minute

Floor: 5 Frame Ra ng: Frame Label Missing

Deficiency Detail

Missing / damaged door closer - NFPA 80-2010 5.2.4.2 (4)

Required frame label is missing - NFPA 80-2010 6.3.1.1; NFPA 101-2012 8.3.3.2.3

10625866 PASS

Inspector: Carlos Lopez Building: Main building Wall Ra ng: Smoke Barrier

Inspec on Date: 2/2/2022 Loca on: Corridor to c unit Door Ra ng: No label present / not required per wall ra ng

Floor: 5 Frame Ra ng: Label present; no ra ng specified

Deficiency Detail

Page 50 of 81 2/9/2022 Version 1

10625867 FAIL

Inspec on Date: 2/2/2022 Loca on: Corridor to c unit Door Ra ng: No label present / not required per wall ra ng

Floor: 5 Frame Ra ng: Label present; no ra ng specified

Deficiency Detail

Door penetra ons / unused fastener holes - NFPA 80-2010 5.2.4.2 (1); NFPA 105-2010 5.1.4.3

10625868 FAIL

Inspector: Carlos Lopez Building: Main building Wall Ra ng: 2 Hour

Inspec on Date: 2/2/2022 Loca on: Pipe room Door Ra ng: Door Label Missing

Floor: 5 Frame Ra ng: Label present; no ra ng specified

Deficiency Detail

Door label is missing - NFPA 80-2010 4.3.1; NFPA 101-2012 8.3.3.2.2

Excessive clearance - NFPA 80-2010 5.2.4.2 (5), NFPA 80-2010 6.3.1.7

Frame penetra ons / unused fastener holes - NFPA 80-2010 5.2.4.2 (1); NFPA 105-2010 5.1.4.3

10625869 FAIL

Inspector: Carlos Lopez Building: Main building Wall Ra ng: 2 Hour

Inspec on Date: 2/2/2022 Loca on: Mechanical room Door Ra ng: 90 Minute

Floor: 5 Frame Ra ng: 90 Minute

Deficiency Detail

Door does not latch - rubbing issue - NFPA 80-2010 5.2.13, 5.1.3.1 Rubs on frame

Page 51 of 81 2/9/2022 Version 1

10625835 PASS

Inspec on Date: 2/2/2022 Loca on: Staircase 4 Door Ra ng: 90 Minute

Floor: 6 Frame Ra ng: 90 Minute

Deficiency Detail

Door passed inspec on

10625836 FAIL

Inspector: Carlos Lopez Building: Main building Wall Ra ng: 2 Hour

Inspec on Date: 2/2/2022 Loca on: Soiled linen Door Ra ng: 90 Minute

Floor: 6 Frame Ra ng: Frame Label Missing

Deficiency Detail

Frame penetra ons / unused fastener holes - NFPA 80-2010 5.2.4.2 (1); NFPA 105-2010 5.1.4.3

Required frame label is missing - NFPA 80-2010 6.3.1.1; NFPA 101-2012 8.3.3.2.3

10625837 PASS

Inspector: Carlos Lopez Building: Main building Wall Ra ng: 2 Hour

Inspec on Date: 2/2/2022 Loca on: Staircase 3 Door Ra ng: 90 Minute

Floor: 6 Frame Ra ng: 90 Minute

Deficiency Detail

Door passed inspec on

10625838 PASS

Inspector: Carlos Lopez Building: Main building Wall Ra ng: 2 Hour

Inspec on Date: 2/2/2022 Loca on: Staircase 1 Door Ra ng: 90 Minute

Floor: 6 Frame Ra ng: 90 Minute

Deficiency Detail

Page 52 of 81 2/9/2022 Version 1

10625839 PASS

Inspec on Date: 2/2/2022 Loca on: Staircase 2 Door Ra ng: 90 Minute

Floor: 6 Frame Ra ng: 90 Minute

Deficiency Detail

Door passed inspec on

10625840 FAIL

Inspector: Carlos Lopez Building: Main building Wall Ra ng: 2 Hour

Inspec on Date: 2/2/2022 Loca on: Soiled linen Door Ra ng: 90 Minute

Floor: 6 Frame Ra ng: Frame Label Missing

Deficiency Detail

Required frame label is missing - NFPA 80-2010 6.3.1.1; NFPA 101-2012 8.3.3.2.3

10625841 FAIL

Inspector: Carlos Lopez Building: Main building Wall Ra ng: 2 Hour

Inspec on Date: 2/2/2022 Loca on: Staircase 5 Door Ra ng: 90 Minute

Floor: 6 Frame Ra ng: Frame Label Missing

Deficiency Detail

Frame penetra ons / unused fastener holes - NFPA 80-2010 5.2.4.2 (1); NFPA 105-2010 5.1.4.3

Page 53 of 81 2/9/2022 Version 1

10625842 FAIL

Inspec on Date: 2/2/2022 Loca on: Elevator closest Door Ra ng: 90 Minute

Floor: 6 Frame Ra ng: 3 Hour

Deficiency Detail

Door does not latch - rubbing issue - NFPA 80-2010 5.2.13, 5.1.3.1 Frame

10625823 FAIL

Inspector: Carlos Lopez Building: Main building Wall Ra ng: 2 Hour Fire/Smoke

Inspec on Date: 2/2/2022 Loca on: Staircase 4 Door Ra ng: 90 Minute

Floor: 7 Frame Ra ng: 90 Minute

Deficiency Detail

Frame penetra ons / unused fastener holes - NFPA 80-2010 5.2.4.2 (1); NFPA 105-2010 5.1.4.3

10625824 FAIL

Inspector: Carlos Lopez Building: Main building Wall Ra ng: 2 Hour

Inspec on Date: 2/2/2022 Loca on: Soiled linen Door Ra ng: 90 Minute

Floor: 7 Frame Ra ng: Frame Label Missing

Deficiency Detail

Frame penetra ons / unused fastener holes - NFPA 80-2010 5.2.4.2 (1); NFPA 105-2010 5.1.4.3

Page 54 of 81 2/9/2022 Version 1

10625825 FAIL

Inspector: Carlos Lopez Building: Main building Wall Ra ng: 2 Hour Fire/Smoke

Inspec on Date: 2/2/2022 Loca on: Staircase 3 Door Ra ng: 90 Minute

Floor: 7 Frame Ra ng: 90 Minute

Deficiency Detail

Frame penetra ons / unused fastener holes - NFPA 80-2010 5.2.4.2 (1); NFPA 105-2010 5.1.4.3

10625826 PASS

Inspector: Carlos Lopez Building: Main building Wall Ra ng: Smoke Barrier

Inspec on Date: 2/2/2022 Loca on: Corridor by elevator Door Ra ng: 90 Minute

Floor: 7 Frame Ra ng: Label present; no ra ng specified

Deficiency Detail

Door passed inspec on

10625827 PASS

Inspector: Carlos Lopez Building: Main building Wall Ra ng: Smoke Barrier

Inspec on Date: 2/2/2022 Loca on: Corridor by elevator Door Ra ng: 90 Minute

Floor: 7 Frame Ra ng: Label present; no ra ng specified

Deficiency Detail

Door passed inspec on

10625828 PASS

Inspector: Carlos Lopez Building: Main building Wall Ra ng: 2 Hour

Inspec on Date: 2/2/2022 Loca on: Staircase 5 Door Ra ng: 90 Minute

Floor: 7 Frame Ra ng: 90 Minute

Deficiency Detail

Page 55 of 81 2/9/2022 Version 1

10625829 FAIL

Inspec on Date: 2/2/2022 Loca on: Office Door Ra ng: No label present / not required per wall ra ng

Floor: 7 Frame Ra ng: No label present / not required per wall ra ng

Deficiency Detail

Frame penetra ons / unused fastener holes - NFPA 80-2010 5.2.4.2 (1); NFPA 105-2010 5.1.4.3

Missing / damaged door closer - NFPA 80-2010 5.2.4.2 (4)

10625830 PASS

Inspector: Carlos Lopez Building: Main building Wall Ra ng: 2 Hour

Inspec on Date: 2/2/2022 Loca on: Elevator closest Door Ra ng: 90 Minute

Floor: 7 Frame Ra ng: 90 Minute

Deficiency Detail

Door passed inspec on

10625831 FAIL

Inspector: Carlos Lopez Building: Main building Wall Ra ng: 2 Hour

Inspec on Date: 2/2/2022 Loca on: Staircase 2 Door Ra ng: 90 Minute

Floor: 7 Frame Ra ng: Label illegible; legibility required per wall ra ng

Deficiency Detail

Required frame label is illegible - NFPA 80-2010 4.2.2; NFPA 101-2012 8.3.3.2.3

Page 56 of 81 2/9/2022 Version 1

10625832 FAIL

Inspec on Date: 2/2/2022 Loca on: Soiled linen Door Ra ng: 90 Minute

Floor: 7 Frame Ra ng: Frame Label Missing

Deficiency Detail

Door penetra ons / unused fastener holes - NFPA 80-2010 5.2.4.2 (1); NFPA 105-2010 5.1.4.3

Required frame label is missing - NFPA 80-2010 6.3.1.1; NFPA 101-2012 8.3.3.2.3

10625833 PASS

Inspector: Carlos Lopez Building: Main building Wall Ra ng: Smoke Barrier

Inspec on Date: 2/2/2022 Loca on: Corridor by restroom Door Ra ng: 45 Minute

Floor: 7 Frame Ra ng: Label present; no ra ng specified

Deficiency Detail

Door passed inspec on

10625834 PASS

Inspector: Carlos Lopez Building: Main building Wall Ra ng: Smoke Barrier

Inspec on Date: 2/2/2022 Loca on: Corridor by restroom Door Ra ng: 45 Minute

Floor: 7 Frame Ra ng: Label present; no ra ng specified

Deficiency Detail

Page 57 of 81 2/9/2022 Version 1

10625815 FAIL

Inspec on Date: 2/2/2022 Loca on: Staircase 4 Door Ra ng: 90 Minute

Floor: 8 Frame Ra ng: 90 Minute

Deficiency Detail

Excessive clearance - NFPA 80-2010 5.2.4.2 (5), NFPA 80-2010 6.3.1.7

Frame penetra ons / unused fastener holes - NFPA 80-2010 5.2.4.2 (1); NFPA 105-2010 5.1.4.3

10625816 FAIL

Inspector: Carlos Lopez Building: Main building Wall Ra ng: 2 Hour

Inspec on Date: 2/2/2022 Loca on: Staircase 1 Door Ra ng: 90 Minute

Floor: 8 Frame Ra ng: 90 Minute

Deficiency Detail

Frame penetra ons / unused fastener holes - NFPA 80-2010 5.2.4.2 (1); NFPA 105-2010 5.1.4.3

10625817 PASS

Inspector: Carlos Lopez Building: Main building Wall Ra ng: 2 Hour

Inspec on Date: 2/2/2022 Loca on: Staircase 2 Door Ra ng: 90 Minute

Floor: 8 Frame Ra ng: Label present; no ra ng specified

Deficiency Detail

Page 58 of 81 2/9/2022 Version 1

10625818 FAIL

Inspec on Date: 2/2/2022 Loca on: Soiled linen Door Ra ng: 90 Minute

Floor: 8 Frame Ra ng: Frame Label Missing

Deficiency Detail

Door penetra ons / unused fastener holes - NFPA 80-2010 5.2.4.2 (1); NFPA 105-2010 5.1.4.3

Required frame label is missing - NFPA 80-2010 6.3.1.1; NFPA 101-2012 8.3.3.2.3

10625819 FAIL

Inspector: Carlos Lopez Building: Main building Wall Ra ng: 2 Hour

Inspec on Date: 2/2/2022 Loca on: Staircase 5 Door Ra ng: 90 Minute

Floor: 8 Frame Ra ng: 90 Minute

Deficiency Detail

Frame penetra ons / unused fastener holes - NFPA 80-2010 5.2.4.2 (1); NFPA 105-2010 5.1.4.3

10625820 FAIL

Inspector: Carlos Lopez Building: Main building Wall Ra ng: 2 Hour

Inspec on Date: 2/2/2022 Loca on: Elevator closest Door Ra ng: 90 Minute

Floor: 8 Frame Ra ng: 3 Hour

Deficiency Detail

Page 59 of 81 2/9/2022 Version 1

10625821 PASS

Inspec on Date: 2/2/2022 Loca on: Elevator closest Door Ra ng: 90 Minute

Floo…