S02 Damper List 523-24-004.pdf

PDF 8 MB Posted

Attached to
Z2DA--523-24-004 Fire Door and Damper Repairs
Solicitation number
36C24124B0013
Issued by

About this file

This document provides an inventory of fire doors and dampers at a Veterans Affairs medical center requiring repair or replacement. It identifies 103 total dampers in need of inspection, with 8 compliant and 96 non-compliant. Each non-compliant damper is listed with its location and issues noted such as being inaccessible, lacking proper size, or located in a non-rated barrier. The solicitation number and name provided indicate this inventory relates to an opportunity with the Department of Veterans Affairs for fire door and damper repairs under solicitation 36C24124B0013.

View the file

Other files

Show all 17

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

VA Jamaica Plain Fire and Smoke Dampers Jamaica, Vermont

Prepared by Bill Hoos 1 Created with PlanGrid

VA Jamaica Plain Fire and Smoke Damper Total Inventory. - Feb 11, 2022 Prepared by Bill Hoos

Feb 11, 2022

Description

Mr. Putnam, JHC Fire Containment Solutions, conducted a fire and smoke damper inspection and review from February 1st, 2022, thru February 8th, 2022.

We started with a total inventory of 370 dampers. After a thorough review, your actual inventory is 103 dampers, located in your rated barriers.

Out of 103 dampers that require inspection, 8 are compliant. 96 dampers that must be inspected are non-compliant.

Regards, Bill Hoos President JHC Fire Containment Solutions Inc.

Contents

#187 Fire Smoke Damper

#183 Fire Damper

#181 Fire Damper

#179 Fire Damper

#178 Fire Damper

#177 Fire Damper

#176 Fire Damper

#175 Fire Damper

#174 Fire Smoke Damper

#173 Fire Damper https://app.plangrid.com/projects/8f9c303d-bdcb-9566-27e4-d7984f6a7226/home

Prepared by Bill Hoos 2 Created with PlanGrid

#172 Fire Damper

#171 Fire Damper

#170 Fire Damper

#169 Fire Damper

#168 Fire Damper

#167 Fire Damper

#166 Smoke Damper

#165 Smoke Damper

#164 Fire Damper

#163 Fire Damper

#161 Fire Damper

#158 Fire Damper

#157 Fire Damper

#155 Fire Damper

#154 Fire Damper

#153 Fire Damper

#152 Fire Damper

#151 Fire Damper

#150 Fire Damper

#149 Fire Damper

#148 Fire Damper

#147 Fire Damper

#146 Fire Damper

#144 Fire Smoke Damper

#143 Fire Damper

#142 Fire Damper

Prepared by Bill Hoos 3 Created with PlanGrid

#141 Fire Damper

#140 Fire Damper

#136 Fire Smoke Damper

#130 Fire Smoke Damper

#129 Fire Damper

#127 Fire Damper

#126 Fire Damper

#122 Smoke Damper

#121 Fire Damper

#120 Exhaust damper

#119 Fire Damper

#113 Fire Smoke Damper

#112 Fire Smoke Damper

#111 Fire Smoke Damper

#106 Fire Damper

#105 Smoke Damper

#103 Fire Damper

#102 Fire Damper

#101 Fire Damper

#97 Fire Damper

#94 Fire Damper

#93 Fire Damper

#92 Fire Damper

#89 Fire Damper

#88 Fire Damper

#85 Fire Damper

Prepared by Bill Hoos 4 Created with PlanGrid

#84 Fire Smoke Damper

#83 Fire Damper

#81 Max Air Damper

#80 Fire Damper

#79 Fire Damper

#78 Fire Damper

#77 Fire Damper

#76 Fire Damper

#75 Fire Damper

#72 Fire Damper

#71 Fire Damper

#70 Fire Damper

#59 Fire Damper

#57 Fire Smoke Damper

#56 Fire Damper

#54 Fire Smoke Damper

#53 Fire Access

#52 Fire Damper

#51 Smoke Damper

#49 Fire Damper

#47 Fire Damper

#46 Fire Damper

#44 Fire Damper

#43 Fire Damper

#42 Fire Damper

#40 Fire Damper

Prepared by Bill Hoos 5 Created with PlanGrid

#39 Fire Damper

#35 Fire Damper

#31 Fire Damper

#29 Fire Damper

#28 Fire Damper

#26 Fire Damper

#25 Fire Damper

#24 Fire Damper

#18 Fire Damper

#17 Fire Damper

#16 Fire Damper

#15 Fire Damper

#11 Smoke Damper

#10 Smoke Damper

#5 Fire Damper

Prepared by Bill Hoos 6 Created with PlanGrid

Status Open

Type Issue

Description #187 Fire and Smoke Damper

Fire and Smoke Damper non-compliant, non-accessible, MEP in a way, electrical panel

Created Feb 7, 2022 4:39 PM bill.hoos@jhcfirestop.com

Last Updated Feb 10, 2022 7:56 PM

Sheet

JP-01-SBLS

#187 Fire Smoke Damper

Photos

Prepared by Bill Hoos 7 Created with PlanGrid

20220207_092908_photo Bill Hoos Feb 7, 2022 9:29 AM

Prepared by Bill Hoos 8 Created with PlanGrid

Status Open

Type Issue

Description #183 Fire Damper

Fire Damper non-compliant, non-accessible, MEP in way

Created Feb 7, 2022 4:38 PM bill.hoos@jhcfirestop.com

Last Updated Feb 10, 2022 7:56 PM

Sheet

JP-01-SBLS

#183 Fire Damper

Photos

20220207_092418_photo Bill Hoos Feb 7, 2022 9:24 AM

Prepared by Bill Hoos 9 Created with PlanGrid

Status Open

Type Issue

Description #181 Fire Damper

Fire Damper is accessible, can’t be shut down

Created Feb 7, 2022 4:38 PM bill.hoos@jhcfirestop.com

Last Updated Feb 10, 2022 7:57 PM

Sheet

JP-01-0BLS

#181 Fire Damper

Photos

20220207_085327_photo Bill Hoos Feb 7, 2022 8:53 AM

Prepared by Bill Hoos 10 Created with PlanGrid

Status Open

Type Issue

Description #179 Fire Damper

Fire Damper is accessible, can’t shut off

Created Feb 7, 2022 4:38 PM bill.hoos@jhcfirestop.com

Last Updated Feb 10, 2022 7:58 PM

Sheet

JP-01-0BLS

#179 Fire Damper

Photos

20220207_084845_photo Bill Hoos Feb 7, 2022 8:48 AM

Prepared by Bill Hoos 11 Created with PlanGrid

Status Open

Type Issue

Description #178 Fire Damper

Fire Damper accessible, can’t shut off

Created Feb 7, 2022 4:38 PM bill.hoos@jhcfirestop.com

Last Updated Feb 10, 2022 7:58 PM

Sheet

JP-01-0BLS

#178 Fire Damper

Photos

20220207_084736_photo Bill Hoos Feb 7, 2022 8:47 AM

Prepared by Bill Hoos 12 Created with PlanGrid

Status Open

Type Issue

Description #177 Fire Damper

Fire Damper out of arms reach, is accessible

Created Feb 7, 2022 4:37 PM bill.hoos@jhcfirestop.com

Last Updated Feb 10, 2022 7:59 PM

Sheet

JP-01-01LS

#177 Fire Damper

Photos

20220207_082437_photo Bill Hoos Feb 7, 2022 8:24 AM

Prepared by Bill Hoos 13 Created with PlanGrid

Status Closed

Type Issue

Description #176 Fire Damper

Fire Damper is accessible, operational, tested, and compliant.

Created Feb 7, 2022 4:37 PM bill.hoos@jhcfirestop.com

Last Updated Feb 11, 2022 6:49 AM

Closed At Feb 7, 2022

Sheet

JP-01-01LS

#176 Fire Damper

Photos

20220207_082340_photo Bill Hoos Feb 7, 2022 8:23 AM

IMG_0061

Bill Hoos Feb 7, 2022 8:22 AM

Prepared by Bill Hoos 14 Created with PlanGrid

IMG_0060

Bill Hoos Feb 7, 2022 8:22 AM

Prepared by Bill Hoos 15 Created with PlanGrid

Status Open

Type Issue

Location D1-126

Description #175 Fire And Smoke Damper

Fire and Smoke Damper non compliant, non accessible, MEP in way , electrical panel access

Created Feb 7, 2022 4:37 PM bill.hoos@jhcfirestop.com

Last Updated Feb 10, 2022 7:59 PM

Sheet

JP-01-01LS

#175 Fire Damper

Prepared by Bill Hoos 16 Created with PlanGrid

20220207_080957_photo Bill Hoos Feb 7, 2022 8:09 AM

Prepared by Bill Hoos 17 Created with PlanGrid

Status Open

Type Issue

Location D1-126

Description #174 Fire and Smoke Damper

Fire and Smoke Damper non accessible, MEP in way, electrical panel access

Created Feb 7, 2022 4:37 PM bill.hoos@jhcfirestop.com

Last Updated Feb 10, 2022 8:00 PM

Sheet

JP-01-01LS

#174 Fire Smoke Damper

Prepared by Bill Hoos 18 Created with PlanGrid

20220207_080851_photo Bill Hoos Feb 7, 2022 8:08 AM

Prepared by Bill Hoos 19 Created with PlanGrid

Status Open

Type Issue

Location B1-60B

Description #173 Fire Damper

Fire Damper non accessible, MEP in way

Created Feb 7, 2022 4:36 PM bill.hoos@jhcfirestop.com

Last Updated Feb 10, 2022 8:00 PM

Sheet

JP-01-01LS

#173 Fire Damper

Prepared by Bill Hoos 20 Created with PlanGrid

20220207_080419_photo Bill Hoos Feb 7, 2022 8:04 AM

Prepared by Bill Hoos 21 Created with PlanGrid

Status Open

Type Issue

Location F1-39

Description #172 Fire Damper

Fire Damper non accessible, MEP in way

Created Feb 5, 2022 10:28 PM bill.hoos@jhcfirestop.com

Last Updated Feb 10, 2022 8:00 PM

Sheet

JP-01-01LS

#172 Fire Damper

Prepared by Bill Hoos 22 Created with PlanGrid

20220205_114227_photo Bill Hoos Feb 5, 2022 11:42 AM

Prepared by Bill Hoos 23 Created with PlanGrid

Status Open

Type Issue

Location F1-39

Description #171 Fire Damper

Fire Damper non accessible, framing in way

Created Feb 5, 2022 10:28 PM bill.hoos@jhcfirestop.com

Last Updated Feb 10, 2022 8:01 PM

Sheet

JP-01-01LS

#171 Fire Damper

Prepared by Bill Hoos 24 Created with PlanGrid

20220205_114112_photo Bill Hoos Feb 5, 2022 11:41 AM

Prepared by Bill Hoos 25 Created with PlanGrid

Status Open

Type Issue

Location F2-20

Description #170 Fire Damper

Fire Damper non accessible, out of arms reach

Created Feb 5, 2022 10:28 PM bill.hoos@jhcfirestop.com

Last Updated Feb 10, 2022 8:01 PM

Sheet

JP-01-02LS

#170 Fire Damper

Prepared by Bill Hoos 26 Created with PlanGrid

20220205_110406_photo Bill Hoos Feb 5, 2022 11:04 AM

Prepared by Bill Hoos 27 Created with PlanGrid

Status Open

Type Issue

Location C2-22

Description #169 Fire Damper

Fire Damper missing in fire rated barrier

Created Feb 5, 2022 10:10 PM bill.hoos@jhcfirestop.com

Last Updated Feb 10, 2022 8:02 PM

Sheet

JP-01-02LS

#169 Fire Damper

Prepared by Bill Hoos 28 Created with PlanGrid

20220205_091236_photo Bill Hoos Feb 5, 2022 9:12 AM

Prepared by Bill Hoos 29 Created with PlanGrid

Status Open

Type Issue

Location F3-63

Description #168 Fire Damper

Fire Damper is accessible, operational, wrong size damper, 1” gap

Created Feb 5, 2022 10:09 PM bill.hoos@jhcfirestop.com

Last Updated Feb 10, 2022 8:02 PM

Sheet

JP-01-03LS

#168 Fire Damper

Prepared by Bill Hoos 30 Created with PlanGrid

20220205_090004_photo Bill Hoos Feb 5, 2022 9:00 AM

IMG_0058

Bill Hoos Feb 5, 2022 8:59 AM

Prepared by Bill Hoos 31 Created with PlanGrid

IMG_0057

Bill Hoos Feb 5, 2022 8:59 AM

Prepared by Bill Hoos 32 Created with PlanGrid

Status Open

Type Issue

Location F3-50

Description #167 Fire Damper

Fire Damper is accessible, operational, wrong size fire Damper, 1” gap bottom of damper

Created Feb 5, 2022 10:09 PM bill.hoos@jhcfirestop.com

Last Updated Feb 11, 2022 6:50 AM

Sheet

JP-01-03LS

#167 Fire Damper

Prepared by Bill Hoos 33 Created with PlanGrid

20220205_085307_photo Bill Hoos Feb 5, 2022 8:53 AM

20220205_085215_photo Bill Hoos Feb 5, 2022 8:52 AM

Prepared by Bill Hoos 34 Created with PlanGrid

20220205_085058_photo Bill Hoos Feb 5, 2022 8:52 AM

Prepared by Bill Hoos 35 Created with PlanGrid

Status Open

Type Issue

Location F3-41

Description #166 Smoke Damper

Smoke Damper non compliant, no damper in smoke rated barrier

Created Feb 5, 2022 10:08 PM bill.hoos@jhcfirestop.com

Last Updated Feb 11, 2022 6:50 AM

Sheet

JP-01-03LS

#166 Smoke Damper

Prepared by Bill Hoos 36 Created with PlanGrid

20220205_083422_photo Bill Hoos Feb 5, 2022 8:34 AM

Prepared by Bill Hoos 37 Created with PlanGrid

Status Open

Type Issue

Location F3-39

Description #165 Smoke Damper

Smoke Damper non compliant, no damper in rated barrier

Created Feb 5, 2022 10:08 PM bill.hoos@jhcfirestop.com

Last Updated Feb 11, 2022 6:50 AM

Sheet

JP-01-03LS

#165 Smoke Damper

Prepared by Bill Hoos 38 Created with PlanGrid

20220205_082054_photo Bill Hoos Feb 5, 2022 8:20 AM

Prepared by Bill Hoos 39 Created with PlanGrid

Status Open

Type Issue

Location C7-11

Description #164 Fire Damper

Fire Damper non accessible, MEP in way

Created Feb 5, 2022 10:07 PM bill.hoos@jhcfirestop.com

Last Updated Feb 11, 2022 6:50 AM

Sheet

JP-01-07LS

#164 Fire Damper

Prepared by Bill Hoos 40 Created with PlanGrid

20220205_075745_photo Bill Hoos Feb 5, 2022 7:57 AM

Prepared by Bill Hoos 41 Created with PlanGrid

Status Open

Type Issue

Location C7-11

Description #163 Fire Damper

Fire Damper non accessible, out of arms reach, needs bigger panel 8x8

Created Feb 5, 2022 10:07 PM bill.hoos@jhcfirestop.com

Last Updated Feb 11, 2022 6:51 AM

Sheet

JP-01-07LS

#163 Fire Damper

Prepared by Bill Hoos 42 Created with PlanGrid

20220205_075616_photo Bill Hoos Feb 5, 2022 7:56 AM

Prepared by Bill Hoos 43 Created with PlanGrid

Status Open

Type Issue

Description #161 Fire Damper

Fire Damper non accessible, panel to small, needs 8x8 access panel

Created Feb 4, 2022 10:45 PM bill.hoos@jhcfirestop.com

Last Updated Feb 11, 2022 6:51 AM

Sheet

JP-01-02LS

#161 Fire Damper

Photos

20220204_120911_photo Bill Hoos Feb 4, 2022 12:09 PM

Prepared by Bill Hoos 44 Created with PlanGrid

Status Open

Type Issue

Location D2-143

Description #158 Fire Damper

Fire Damper non compliant, non accessible, MEP in way

Created Feb 4, 2022 10:44 PM bill.hoos@jhcfirestop.com

Last Updated Feb 11, 2022 6:51 AM

Sheet

JP-01-02LS

#158 Fire Damper

Prepared by Bill Hoos 45 Created with PlanGrid

20220204_114521_photo Bill Hoos Feb 4, 2022 11:45 AM

Prepared by Bill Hoos 46 Created with PlanGrid

Status Open

Type Issue

Location D2-144A

Description #157 Fire Damper

Fire Damper non compliant, non accessible, MEP in way

Created Feb 4, 2022 10:44 PM bill.hoos@jhcfirestop.com

Last Updated Feb 11, 2022 6:51 AM

Sheet

JP-01-02LS

#157 Fire Damper

Prepared by Bill Hoos 47 Created with PlanGrid

20220204_114200_photo Bill Hoos Feb 4, 2022 11:42 AM

Prepared by Bill Hoos 48 Created with PlanGrid

Status Open

Type Issue

Description #155 Fire Damper

Fire Damper accessible, unable to test, computer issues, can’t turn of air

Created Feb 4, 2022 10:44 PM bill.hoos@jhcfirestop.com

Last Updated Feb 11, 2022 6:52 AM

Sheet

JP-01-02LS

#155 Fire Damper

Photos

20220204_112508_photo Bill Hoos Feb 4, 2022 11:25 AM

Prepared by Bill Hoos 49 Created with PlanGrid

Status Open

Type Issue

Location F2-97

Description #154 Fire Damper

Fire Damper accessible, unable to test, computer issues, can’t turn of air

Created Feb 4, 2022 10:43 PM bill.hoos@jhcfirestop.com

Last Updated Feb 11, 2022 6:52 AM

Sheet

JP-01-02LS

#154 Fire Damper

Prepared by Bill Hoos 50 Created with PlanGrid

20220204_112224_photo Bill Hoos Feb 4, 2022 11:22 AM

Prepared by Bill Hoos 51 Created with PlanGrid

Status Open

Type Issue

Location F2-97

Description #153 Fire Damper

Fire Damper accessible, unable to test, computer issues, can’t turn of air

Created Feb 4, 2022 10:43 PM bill.hoos@jhcfirestop.com

Last Updated Feb 11, 2022 6:52 AM

Sheet

JP-01-02LS

#153 Fire Damper

Prepared by Bill Hoos 52 Created with PlanGrid

20220204_112132_photo Bill Hoos Feb 4, 2022 11:21 AM

Prepared by Bill Hoos 53 Created with PlanGrid

Status Open

Type Issue

Location F2-97

Description #152 Fire Damper

Fire Damper non accessible, out of arms reach, MEP in way of ceiling grid

Created Feb 4, 2022 10:43 PM bill.hoos@jhcfirestop.com

Last Updated Feb 11, 2022 6:52 AM

Sheet

JP-01-02LS

#152 Fire Damper

Prepared by Bill Hoos 54 Created with PlanGrid

20220204_111822_photo Bill Hoos Feb 4, 2022 11:18 AM

Prepared by Bill Hoos 55 Created with PlanGrid

Status Open

Type Issue

Description #151 Fire Damper

Fire Damper non compliant, non accessible, MEP in way, out of arms reach

Created Feb 4, 2022 10:43 PM bill.hoos@jhcfirestop.com

Last Updated Feb 11, 2022 6:52 AM

Sheet

JP-01-02LS

#151 Fire Damper

Photos

20220204_111319_photo Bill Hoos Feb 4, 2022 11:13 AM

20220204_111249_photo Bill Hoos Feb 4, 2022 11:12 AM

Prepared by Bill Hoos 56 Created with PlanGrid

Status Open

Type Issue

Location F2-65

Description #150 Fire Damper

Fire Damper non compliant, is accessible, out of arms reach

Created Feb 4, 2022 10:43 PM bill.hoos@jhcfirestop.com

Last Updated Feb 11, 2022 6:53 AM

Sheet

JP-01-02LS

#150 Fire Damper

Prepared by Bill Hoos 57 Created with PlanGrid

20220204_111001_photo Bill Hoos Feb 4, 2022 11:10 AM

Prepared by Bill Hoos 58 Created with PlanGrid

Status Open

Type Issue

Location F2-20

Description #149 Fire Damper

Fire Damper accessible, unable to test, computer issues, can’t turn of air

Created Feb 4, 2022 10:43 PM bill.hoos@jhcfirestop.com

Last Updated Feb 11, 2022 6:53 AM

Sheet

JP-01-02LS

#149 Fire Damper

Prepared by Bill Hoos 59 Created with PlanGrid

20220204_110031_photo Bill Hoos Feb 4, 2022 11:00 AM

Prepared by Bill Hoos 60 Created with PlanGrid

Status Open

Type Issue

Location F2-20

Description #148 Fire Damper

Fire Damper accessible, unable to test, computer issues, can’t turn of air

Created Feb 4, 2022 10:43 PM bill.hoos@jhcfirestop.com

Last Updated Feb 11, 2022 6:53 AM

Sheet

JP-01-02LS

#148 Fire Damper

Prepared by Bill Hoos 61 Created with PlanGrid

20220204_105857_photo Bill Hoos Feb 4, 2022 10:59 AM

Prepared by Bill Hoos 62 Created with PlanGrid

Status Open

Type Issue

Location A2-35A

Description #147 Fire Damper

Fire Damper non compliant, non accessible, MEP in way

Created Feb 4, 2022 10:43 PM bill.hoos@jhcfirestop.com

Last Updated Feb 11, 2022 6:54 AM

Sheet

JP-01-02LS

#147 Fire Damper

Prepared by Bill Hoos 63 Created with PlanGrid

20220204_105148_photo Bill Hoos Feb 4, 2022 10:51 AM

Prepared by Bill Hoos 64 Created with PlanGrid

Status Open

Type Issue

Location F2-20

Description #146 Fire Damper

Fire Damper accessible, unable to test, computer issues, can’t turn of air

Created Feb 4, 2022 10:42 PM bill.hoos@jhcfirestop.com

Last Updated Feb 11, 2022 6:54 AM

Sheet

JP-01-02LS

#146 Fire Damper

Prepared by Bill Hoos 65 Created with PlanGrid

20220204_105629_photo Bill Hoos Feb 4, 2022 10:56 AM

Prepared by Bill Hoos 66 Created with PlanGrid

Status Open

Type Issue

Location D3-120A

Description #144 Fire and Smoke Damper

Fire and Smoke Damper non compliant, non accessible, ceiling grid in way, in non fire rated barrier

Created Feb 4, 2022 6:01 PM bill.hoos@jhcfirestop.com

Last Updated Feb 11, 2022 6:55 AM

Sheet

JP-01-03LS

#144 Fire Smoke Damper

Prepared by Bill Hoos 67 Created with PlanGrid

20220204_093459_photo Bill Hoos Feb 4, 2022 9:35 AM

Prepared by Bill Hoos 68 Created with PlanGrid

Status Open

Type Issue

Location C3-8

Description #143 Fire Damper

Fire Damper is accessible, operational, tested and passed

Created Feb 4, 2022 6:01 PM bill.hoos@jhcfirestop.com

Last Updated Feb 11, 2022 6:55 AM

Sheet

JP-01-03LS

#143 Fire Damper

Prepared by Bill Hoos 69 Created with PlanGrid

20220204_092615_photo Bill Hoos Feb 4, 2022 9:26 AM

20220204_092545_photo Bill Hoos Feb 4, 2022 9:25 AM

Prepared by Bill Hoos 70 Created with PlanGrid

Status Open

Type Issue

Description #142 Fire Damper

Fire Damper non compliant, non accessible, MEP in way

Created Feb 4, 2022 6:01 PM bill.hoos@jhcfirestop.com

Last Updated Feb 11, 2022 6:55 AM

Sheet

JP-01-03LS

#142 Fire Damper

Photos

20220204_091834_photo Bill Hoos Feb 4, 2022 9:18 AM

Prepared by Bill Hoos 71 Created with PlanGrid

Status Open

Type Issue

Location A3-37

Description #141 Fire Damper

Fire Damper non compliant, non accessible, MEP in way

Created Feb 4, 2022 6:01 PM bill.hoos@jhcfirestop.com

Last Updated Feb 11, 2022 6:55 AM

Sheet

JP-01-03LS

#141 Fire Damper

Prepared by Bill Hoos 72 Created with PlanGrid

20220204_090821_photo Bill Hoos Feb 4, 2022 9:08 AM

Prepared by Bill Hoos 73 Created with PlanGrid

Status Open

Type Issue

Location A3-37

Description #140 Fire Damper

Fire Damper non compliant, non accessible, MEP in way

Created Feb 4, 2022 6:01 PM bill.hoos@jhcfirestop.com

Last Updated Feb 11, 2022 6:55 AM

Sheet

JP-01-03LS

#140 Fire Damper

Prepared by Bill Hoos 74 Created with PlanGrid

20220204_090733_photo Bill Hoos Feb 4, 2022 9:07 AM

Prepared by Bill Hoos 75 Created with PlanGrid

Status Open

Type Issue

Location D4-128

Description #136 Fire and Smoke Damper

Fire and Smoke Damper non compliant, non accessible, electrical panel access, MEP in way

Created Feb 4, 2022 5:59 PM bill.hoos@jhcfirestop.com

Last Updated Feb 11, 2022 6:56 AM

Sheet

JP-01-04LS

#136 Fire Smoke Damper

Prepared by Bill Hoos 76 Created with PlanGrid

20220204_083333_photo Bill Hoos Feb 4, 2022 8:33 AM

Prepared by Bill Hoos 77 Created with PlanGrid

Status Open

Type Issue

Description #130 Smoke Damper

Smoke Damper non compliant, electrical panel access, in fire rated barrier

Created Feb 4, 2022 5:56 PM bill.hoos@jhcfirestop.com

Last Updated Feb 11, 2022 6:56 AM

Sheet

JP-01-04LS

#130 Fire Smoke Damper

Photos

20220204_075216_photo Bill Hoos Feb 4, 2022 7:52 AM

Prepared by Bill Hoos 78 Created with PlanGrid

Status Open

Type Issue

Location A4-45B

Description #129 Fire Damper

Fire Damper non compliant, non accessible, MEP in way

Created Feb 4, 2022 5:56 PM bill.hoos@jhcfirestop.com

Last Updated Feb 11, 2022 6:56 AM

Sheet

JP-01-04LS

#129 Fire Damper

Prepared by Bill Hoos 79 Created with PlanGrid

20220204_074206_photo Bill Hoos Feb 4, 2022 7:42 AM

Prepared by Bill Hoos 80 Created with PlanGrid

Status Open

Type Issue

Location 5B-54

Description #127 Fire Damper

Fire Damper non compliant, non accessible, access panel to small

Created Feb 3, 2022 2:03 PM bill.hoos@jhcfirestop.com

Last Updated Feb 11, 2022 6:56 AM

Sheet

JP-01-05LS

#127 Fire Damper

Prepared by Bill Hoos 81 Created with PlanGrid

20220203_140441_photo Bill Hoos Feb 3, 2022 2:04 PM

Prepared by Bill Hoos 82 Created with PlanGrid

Status Open

Type Issue

Location 5B-54

Description #126 Fire Damper

Fire Damper missing

Created Feb 3, 2022 2:00 PM bill.hoos@jhcfirestop.com

Last Updated Feb 11, 2022 6:57 AM

Sheet

JP-01-05LS

#126 Fire Damper

Photos

20220203_140320_photo Bill Hoos Feb 3, 2022 2:03 PM

Prepared by Bill Hoos 83 Created with PlanGrid

Status Open

Type Issue

Location A5-42

Description #122 Smoke Damper

Smoke Damper missing, MEP in way

Created Feb 3, 2022 1:35 PM bill.hoos@jhcfirestop.com

Last Updated Feb 11, 2022 6:57 AM

Sheet

JP-01-05LS

#122 Smoke Damper

Prepared by Bill Hoos 84 Created with PlanGrid

20220203_133614_photo Bill Hoos Feb 3, 2022 1:36 PM

Prepared by Bill Hoos 85 Created with PlanGrid

Status Open

Type Issue

Location A5-42

Description #121 Fire Damper

Fire Damper non compliant, non accessible, MEP in way

Created Feb 3, 2022 1:33 PM bill.hoos@jhcfirestop.com

Last Updated Feb 11, 2022 6:57 AM

Sheet

JP-01-05LS

#121 Fire Damper

Prepared by Bill Hoos 86 Created with PlanGrid

20220203_133405_photo Bill Hoos Feb 3, 2022 1:34 PM

Prepared by Bill Hoos 87 Created with PlanGrid

Status Open

Type Issue

Location C5-35

Description #120 Exhumed Damper

Exhaust Damper is non compliant, non accessible, electrical panel

Created Feb 3, 2022 1:30 PM bill.hoos@jhcfirestop.com

Last Updated Feb 11, 2022 6:57 AM

Sheet

JP-01-05LS

#120 Exhaust damper

Prepared by Bill Hoos 88 Created with PlanGrid

20220203_133132_photo Bill Hoos Feb 3, 2022 1:31 PM

Prepared by Bill Hoos 89 Created with PlanGrid

Status Open

Type Issue

Location C5-35

Description #119 Fire Damper

Fire Damper non accessible, out of arms reach

Created Feb 3, 2022 1:28 PM bill.hoos@jhcfirestop.com

Last Updated Feb 11, 2022 6:58 AM

Sheet

JP-01-05LS

#119 Fire Damper

Prepared by Bill Hoos 90 Created with PlanGrid

20220203_132857_photo Bill Hoos Feb 3, 2022 1:28 PM

Prepared by Bill Hoos 91 Created with PlanGrid

Status Open

Type Issue

Location C5-8

Description #113 Fire and Smoke Damper

Fire and Smoke Damper, electrical panel access, unable to activate switch off

Created Feb 3, 2022 1:15 PM bill.hoos@jhcfirestop.com

Last Updated Feb 11, 2022 6:58 AM

Sheet

JP-01-05LS

#113 Fire Smoke Damper

Prepared by Bill Hoos 92 Created with PlanGrid

20220203_131543_photo Bill Hoos Feb 3, 2022 1:15 PM

Prepared by Bill Hoos 93 Created with PlanGrid

Status Open

Type Issue

Location C5-8

Description #112 Fire and Smoke Damper

Fire and Smoke Damper non compliant, non accessible, MEP in way

Created Feb 3, 2022 1:13 PM bill.hoos@jhcfirestop.com

Last Updated Feb 11, 2022 6:59 AM

Sheet

JP-01-05LS

#112 Fire Smoke Damper

Prepared by Bill Hoos 94 Created with PlanGrid

20220203_131421_photo Bill Hoos Feb 3, 2022 1:14 PM

Prepared by Bill Hoos 95 Created with PlanGrid

Status Open

Type Issue

Location C5-8

Description #111 Fire and Smoke Damper

Fire and Smoke Damper, is accessible, electrical panel access, unable to activate switch

Created Feb 3, 2022 1:12 PM bill.hoos@jhcfirestop.com

Last Updated Feb 11, 2022 6:59 AM

Sheet

JP-01-05LS

#111 Fire Smoke Damper

Prepared by Bill Hoos 96 Created with PlanGrid

20220203_131243_photo Bill Hoos Feb 3, 2022 1:12 PM

Prepared by Bill Hoos 97 Created with PlanGrid

Status Open

Type Issue

Location E5 101A

Description #106 Fire Damper

Fire Damper non compliant, non accessible, Fire Damper in smoke rated barrier, access panel to small, needs a 8x8 panel

Created Feb 3, 2022 12:42 PM bill.hoos@jhcfirestop.com

Last Updated Feb 11, 2022 7:00 AM

Sheet

JP-01-05LS

#106 Fire Damper

Prepared by Bill Hoos 98 Created with PlanGrid

20220203_124249_photo Bill Hoos Feb 3, 2022 12:42 PM

Prepared by Bill Hoos 99 Created with PlanGrid

Status Open

Type Issue

Location D5-132C

Description #105 Smoke Damper Observation missing smoke damper

Created Feb 3, 2022 12:38 PM bill.hoos@jhcfirestop.com

Last Updated Feb 11, 2022 7:00 AM

Sheet

JP-01-05LS

#105 Smoke Damper

Photos

20220203_123924_photo Bill Hoos Feb 3, 2022 12:39 PM

Prepared by Bill Hoos 100 Created with PlanGrid

Status Open

Type Issue

Description #103 Fire Damper

Fire Damper unable to shut off

Created Feb 3, 2022 12:27 PM bill.hoos@jhcfirestop.com

Last Updated Feb 11, 2022 7:00 AM

Sheet

JP-01-05LS

#103 Fire Damper

Photos

20220203_122810_photo Bill Hoos Feb 3, 2022 12:28 PM

Prepared by Bill Hoos 101 Created with PlanGrid

Status Open

Type Issue

Description #102 Fire Damper

Fire Damper non compliant , non accessible, MEP

Created Feb 3, 2022 12:26 PM bill.hoos@jhcfirestop.com

Last Updated Feb 11, 2022 7:00 AM

Sheet

JP-01-05LS

#102 Fire Damper

Photos

20220203_122712_photo Bill Hoos Feb 3, 2022 12:27 PM

Prepared by Bill Hoos 102 Created with PlanGrid

Status Open

Type Issue

Description #101 Fire Damper

Fire Damper unable to shut off

Created Feb 3, 2022 12:26 PM bill.hoos@jhcfirestop.com

Last Updated Feb 11, 2022 7:00 AM

Sheet

JP-01-05LS

#101 Fire Damper

Photos

20220203_122630_photo Bill Hoos Feb 3, 2022 12:26 PM

Prepared by Bill Hoos 103 Created with PlanGrid

Status Open

Type Issue

Location E6-118

Description #97 Fire Damper

Fire Damper non compliant, non accessible, MEP in way, out of arms reach

Created Feb 3, 2022 10:51 AM bill.hoos@jhcfirestop.com

Last Updated Feb 11, 2022 7:01 AM

Sheet

JP-01-06LS

#97 Fire Damper

Prepared by Bill Hoos 104 Created with PlanGrid

20220203_105159_photo Bill Hoos Feb 3, 2022 10:52 AM

Prepared by Bill Hoos 105 Created with PlanGrid

Status Open

Type Issue

Location D6-156

Description #94 Fire Damper

Fire Damper non compliant, non accessible, MEP in way

Created Feb 3, 2022 10:44 AM bill.hoos@jhcfirestop.com

Last Updated Feb 11, 2022 7:01 AM

Sheet

JP-01-06LS

#94 Fire Damper

Prepared by Bill Hoos 106 Created with PlanGrid

20220203_104454_photo Bill Hoos Feb 3, 2022 10:44 AM

Prepared by Bill Hoos 107 Created with PlanGrid

Status Open

Type Issue

Location C6-35

Description #93 Fire Damper

Fire Damper accessible, operational, tested passed

Created Feb 3, 2022 10:37 AM bill.hoos@jhcfirestop.com

Last Updated Feb 11, 2022 7:01 AM

Sheet

JP-01-06LS

#93 Fire Damper

Prepared by Bill Hoos 108 Created with PlanGrid

20220203_103739_photo Bill Hoos Feb 3, 2022 10:37 AM

Prepared by Bill Hoos 109 Created with PlanGrid

Status Open

Type Issue

Location C6-35

Description #92 Fire Damper

Fire Damper non compliant, non accessible, MEP in way

Created Feb 3, 2022 10:36 AM bill.hoos@jhcfirestop.com

Last Updated Feb 11, 2022 7:01 AM

Sheet

JP-01-06LS

#92 Fire Damper

Prepared by Bill Hoos 110 Created with PlanGrid

20220203_103651_photo Bill Hoos Feb 3, 2022 10:36 AM

Prepared by Bill Hoos 111 Created with PlanGrid

Status Open

Type Issue

Location A6-46

Description #89 Fire Damper

Fire Damper non compliant, non accessible, MEP in way

Created Feb 3, 2022 10:27 AM bill.hoos@jhcfirestop.com

Last Updated Feb 11, 2022 7:02 AM

Sheet

JP-01-06LS

#89 Fire Damper

Prepared by Bill Hoos 112 Created with PlanGrid

20220203_102804_photo Bill Hoos Feb 3, 2022 10:28 AM

Prepared by Bill Hoos 113 Created with PlanGrid

Status Open

Type Issue

Location A6-46

Description #88 Fire Damper

Fire Damper non compliant, non accessible, MEP in way

Created Feb 3, 2022 10:25 AM bill.hoos@jhcfirestop.com

Last Updated Feb 11, 2022 7:02 AM

Sheet

JP-01-06LS

#88 Fire Damper

Prepared by Bill Hoos 114 Created with PlanGrid

20220203_102622_photo Bill Hoos Feb 3, 2022 10:26 AM

Prepared by Bill Hoos 115 Created with PlanGrid

Status Open

Type Issue

Location B6-75

Description #85 Fire Damper

Fire Damper non compliant, non accessible, MEP in way

Created Feb 3, 2022 10:15 AM bill.hoos@jhcfirestop.com

Last Updated Feb 11, 2022 7:03 AM

Sheet

JP-01-06LS

#85 Fire Damper

Prepared by Bill Hoos 116 Created with PlanGrid

20220203_101625_photo Bill Hoos Feb 3, 2022 10:16 AM

Prepared by Bill Hoos 117 Created with PlanGrid

Status Open

Type Issue

Location D7-109

Description #84 Fire and Smoke Damper

Fire and Smoke Damper non compliant, non accessible, MEP in way, electrical panel access

Created Feb 3, 2022 9:52 AM bill.hoos@jhcfirestop.com

Last Updated Feb 11, 2022 7:03 AM

Sheet

JP-01-07LS

#84 Fire Smoke Damper

Prepared by Bill Hoos 118 Created with PlanGrid

20220203_095339_photo Bill Hoos Feb 3, 2022 9:53 AM

Prepared by Bill Hoos 119 Created with PlanGrid

Status Open

Type Issue

Location D7-109

Description #83 Fire Damper

Fire Damper non compliant, non accessible, access panel small

Created Feb 3, 2022 9:51 AM bill.hoos@jhcfirestop.com

Last Updated Feb 11, 2022 7:03 AM

Sheet

JP-01-07LS

#83 Fire Damper

Prepared by Bill Hoos 120 Created with PlanGrid

20220203_095213_photo Bill Hoos Feb 3, 2022 9:52 AM

Prepared by Bill Hoos 121 Created with PlanGrid

Status Open

Type Issue

Description #72

Max air damper in non rated barrier, for VAV (variable air volume)

Created Feb 3, 2022 9:36 AM bill.hoos@jhcfirestop.com

Last Updated Feb 3, 2022 10:15 AM

Sheet

JP-01-07LS

#81 Max Air Damper

Photos

20220203_093747_photo Bill Hoos Feb 3, 2022 9:37 AM

Prepared by Bill Hoos 122 Created with PlanGrid

Status Open

Type Issue

Location B7-73

Description #80 Fire Damper

Fire Damper non compliant, non accessible

Created Feb 3, 2022 9:15 AM bill.hoos@jhcfirestop.com

Last Updated Feb 11, 2022 7:04 AM

Sheet

JP-01-07LS

#80 Fire Damper

Prepared by Bill Hoos 123 Created with PlanGrid

20220203_092051_photo Bill Hoos Feb 3, 2022 9:20 AM

20220203_091714_photo Bill Hoos Feb 3, 2022 9:17 AM

Prepared by Bill Hoos 124 Created with PlanGrid

Status Open

Type Issue

Location B7-73

Description #79 Fire Damper

Fire Damper non compliant, non accessible, MEP in way

Created Feb 3, 2022 9:14 AM bill.hoos@jhcfirestop.com

Last Updated Feb 11, 2022 7:04 AM

Sheet

JP-01-07LS

#79 Fire Damper

Prepared by Bill Hoos 125 Created with PlanGrid

20220203_091507_photo Bill Hoos Feb 3, 2022 9:15 AM

Prepared by Bill Hoos 126 Created with PlanGrid

Status Closed

Type Issue

Location 8D-101

Description #78 Fire Damper

Fire Damper is accessible, operational , tested and passed

Created Feb 3, 2022 9:05 AM bill.hoos@jhcfirestop.com

Last Updated Feb 11, 2022 7:04 AM

Closed At Feb 5, 2022

Sheet

JP-01-08LS

#78 Fire Damper

Prepared by Bill Hoos 127 Created with PlanGrid

20220205_101722_photo Bill Hoos Feb 5, 2022 10:17 AM

20220203_090626_photo Bill Hoos Feb 3, 2022 9:06 AM

Prepared by Bill Hoos 128 Created with PlanGrid

Status Open

Type Issue

Location 8D-113

Description #77 Fire Damper

Fire Damper access panel broken

Created Feb 3, 2022 9:04 AM bill.hoos@jhcfirestop.com

Last Updated Feb 11, 2022 7:04 AM

Sheet

JP-01-08LS

#77 Fire Damper

Prepared by Bill Hoos 129 Created with PlanGrid

20220203_090505_photo Bill Hoos Feb 3, 2022 9:05 AM

Prepared by Bill Hoos 130 Created with PlanGrid

Status Open

Type Issue

Location C8-8

Description #76 Fire Damper

Fire Damper non compliant, non accessible, MEP in way

Created Feb 3, 2022 8:52 AM bill.hoos@jhcfirestop.com

Last Updated Feb 11, 2022 7:04 AM

Sheet

JP-01-08LS

#76 Fire Damper

Prepared by Bill Hoos 131 Created with PlanGrid

20220203_085243_photo Bill Hoos Feb 3, 2022 8:52 AM

Prepared by Bill Hoos 132 Created with PlanGrid

Status Open

Type Issue

Location C8-8

Description #75 Fire Damper non compliant, non accessible, access panel to small, MEP in way

Created Feb 3, 2022 8:51 AM bill.hoos@jhcfirestop.com

Last Updated Feb 11, 2022 7:05 AM

Sheet

JP-01-08LS

#75 Fire Damper

Prepared by Bill Hoos 133 Created with PlanGrid

20220203_085218_photo Bill Hoos Feb 3, 2022 8:52 AM

Prepared by Bill Hoos 134 Created with PlanGrid

Status Open

Type Issue

Location A8-41

Description #64 Fire Damper

Fire Damper non compliant, non accessible, out of arms reach, MEPs in way, small access panel

Created Feb 3, 2022 8:40 AM bill.hoos@jhcfirestop.com

Last Updated Feb 11, 2022 7:05 AM

Sheet

JP-01-08LS

#72 Fire Damper

Prepared by Bill Hoos 135 Created with PlanGrid

20220203_084329_photo Bill Hoos Feb 3, 2022 8:43 AM

20220203_084234_photo Bill Hoos Feb 3, 2022 8:42 AM

Prepared by Bill Hoos 136 Created with PlanGrid

Status Open

Type Issue

Location B8-73

Description #71 Fire Damper

Fire Damper accessible, operational, tested and passed

Created Feb 3, 2022 8:28 AM bill.hoos@jhcfirestop.com

Last Updated Feb 11, 2022 7:05 AM

Sheet

JP-01-08LS

#71 Fire Damper

Prepared by Bill Hoos 137 Created with PlanGrid

20220203_083127_photo Bill Hoos Feb 3, 2022 8:31 AM

20220203_083058_photo Bill Hoos Feb 3, 2022 8:30 AM

Prepared by Bill Hoos 138 Created with PlanGrid

Status Open

Type Issue

Location B8-73

Description #70 Fire Damper

Fire Damper is accessible, operational, tested and passed

Created Feb 3, 2022 8:10 AM bill.hoos@jhcfirestop.com

Last Updated Feb 11, 2022 7:05 AM

Sheet

JP-01-08LS

#70 Fire Damper

Prepared by Bill Hoos 139 Created with PlanGrid

20220203_082215_photo Bill Hoos Feb 3, 2022 8:22 AM

20220203_082205_photo Bill Hoos Feb 3, 2022 8:22 AM

Prepared by Bill Hoos 140 Created with PlanGrid

Status Open

Type Issue

Location D9-130

Description #59 Fire Damper

Fire, 8172, can access needs tested

Created Feb 2, 2022 1:43 PM bill.hoos@jhcfirestop.com

Last Updated Feb 11, 2022 7:06 AM

Sheet

JP-01-09LS

#59 Fire Damper

Prepared by Bill Hoos 141 Created with PlanGrid

20220202_134755_photo Bill Hoos Feb 2, 2022 1:48 PM

Prepared by Bill Hoos 142 Created with PlanGrid

Status Open

Type Issue

Location C9-14

Description #57 Fire and Smoke Damper

Fire and Smoke Damper non compliant, non accessible, in non fire rated barrier, MEP in way

Created Feb 2, 2022 1:18 PM bill.hoos@jhcfirestop.com

Last Updated Feb 11, 2022 7:06 AM

Sheet

JP-01-09LS

#57 Fire Smoke Damper

Prepared by Bill Hoos 143 Created with PlanGrid

20220202_131923_photo Bill Hoos Feb 2, 2022 1:19 PM

Prepared by Bill Hoos 144 Created with PlanGrid

Status Open

Type Issue

Location C9-35

Description #56 Fire Damper

Fire Damper non compliant, non accessible, MEP in way

Created Feb 2, 2022 1:16 PM bill.hoos@jhcfirestop.com

Last Updated Feb 11, 2022 7:06 AM

Sheet

JP-01-09LS

#56 Fire Damper

Prepared by Bill Hoos 145 Created with PlanGrid

20220202_131718_photo Bill Hoos Feb 2, 2022 1:17 PM

Prepared by Bill Hoos 146 Created with PlanGrid

Status Open

Type Issue

Location C9-35

Description #54 Fire Damper

Fire Damper non compliant, non accessible, access door to small

Created Feb 2, 2022 1:15 PM bill.hoos@jhcfirestop.com

Last Updated Feb 11, 2022 7:06 AM

Sheet

JP-01-09LS

#54 Fire Smoke Damper

Prepared by Bill Hoos 147 Created with PlanGrid

20220202_131624_photo Bill Hoos Feb 2, 2022 1:16 PM

Prepared by Bill Hoos 148 Created with PlanGrid

Status Open

Type Issue

Location 9A-41A

Description #53 Fire Access Panel

Fire access panel no damper

Created Feb 2, 2022 1:02 PM bill.hoos@jhcfirestop.com

Last Updated Feb 11, 2022 7:07 AM

Sheet

JP-01-09LS

#53 Fire Access

Photos

20220202_130344_photo Bill Hoos Feb 2, 2022 1:04 PM

20220202_130309_photo Bill Hoos Feb 2, 2022 1:03 PM

Prepared by Bill Hoos 149 Created with PlanGrid

Status Open

Type Issue

Location A9-43

Description #52 Fire Damper

Fire Damper non compliant, non accessible, Created Feb 2, 2022 12:54 PM bill.hoos@jhcfirestop.com

Last Updated Feb 11, 2022 7:07 AM

Sheet

JP-01-09LS

#52 Fire Damper

Prepared by Bill Hoos 150 Created with PlanGrid

20220202_125527_photo Bill Hoos Feb 2, 2022 12:55 PM

Prepared by Bill Hoos 151 Created with PlanGrid

Status Open

Type Issue

Location B9-73

Description #51 Smoke Damper

Smoke Damper, electrical panel access

Created Feb 2, 2022 12:43 PM bill.hoos@jhcfirestop.com

Last Updated Feb 11, 2022 7:07 AM

Sheet

JP-01-09LS

#51 Smoke Damper

Prepared by Bill Hoos 152 Created with PlanGrid

20220202_124345_photo Bill Hoos Feb 2, 2022 12:43 PM

Prepared by Bill Hoos 153 Created with PlanGrid

Status Open

Type Issue

Location D10-108

Description #49 Fire Damper

Fire Damper non compliant, non accessible, MEP in way, out of arms reach

Created Feb 2, 2022 12:06 PM bill.hoos@jhcfirestop.com

Last Updated Feb 11, 2022 7:08 AM

Sheet

JP-01-10LS

#49 Fire Damper

Prepared by Bill Hoos 154 Created with PlanGrid

20220202_120749_photo Bill Hoos Feb 2, 2022 12:07 PM

Prepared by Bill Hoos 155 Created with PlanGrid

Status Closed

Type Issue

Location C10-35

Description #47 Fire Damper

Fire Damper is accessible, operational, tested and passed

Created Feb 2, 2022 11:49 AM bill.hoos@jhcfirestop.com

Last Updated Feb 10, 2022 7:53 PM

Closed At Feb 5, 2022

Sheet

JP-01-10LS

#47 Fire Damper

Prepared by Bill Hoos 156 Created with PlanGrid

IMG_0063

Bill Hoos Feb 5, 2022 10:00 AM

IMG_0059

Bill Hoos Feb 5, 2022 10:00 AM

Prepared by Bill Hoos 157 Created with PlanGrid

20220202_115032_photo Bill Hoos Feb 2, 2022 11:50 AM

Prepared by Bill Hoos 158 Created with PlanGrid

Status Closed

Type Issue

Location C10-35

Description #46 Fire Damper

Fire Damper is accessible, operational, tested and passed

Created Feb 2, 2022 11:48 AM bill.hoos@jhcfirestop.com

Last Updated Feb 10, 2022 7:49 PM

Closed At Feb 5, 2022

Sheet

JP-01-10LS

#46 Fire Damper

Prepared by Bill Hoos 159 Created with PlanGrid

IMG_0062

Bill Hoos Feb 5, 2022 9:56 AM

IMG_0061

Bill Hoos Feb 5, 2022 9:56 AM

Prepared by Bill Hoos 160 Created with PlanGrid

20220202_114914_photo Bill Hoos Feb 2, 2022 11:49 AM

Prepared by Bill Hoos 161 Created with PlanGrid

Status Closed

Type Issue

Location B10-73

Description #44 Fire Damper

Fire Damper, accessible, operational, tested and passed

Created Feb 2, 2022 11:24 AM bill.hoos@jhcfirestop.com

Last Updated Feb 10, 2022 7:50 PM

Closed At Feb 5, 2022

Sheet

JP-01-10LS

#44 Fire Damper

Prepared by Bill Hoos 162 Created with PlanGrid

20220205_093828_photo Bill Hoos Feb 5, 2022 9:38 AM

20220205_093725_photo Bill Hoos Feb 5, 2022 9:37 AM

Prepared by Bill Hoos 163 Created with PlanGrid

20220205_093448_photo Bill Hoos Feb 5, 2022 9:34 AM

20220202_112433_photo Bill Hoos Feb 2, 2022 11:24 AM

Prepared by Bill Hoos 164 Created with PlanGrid

Status Closed

Type Issue

Location B10-73

Description #43 Fire Damper

Fire Damper, accessible, operational, tested and passed

Created Feb 2, 2022 11:23 AM bill.hoos@jhcfirestop.com

Last Updated Feb 10, 2022 7:48 PM

Closed At Feb 5, 2022

Sheet

JP-01-10LS

#43 Fire Damper

Prepared by Bill Hoos 165 Created with PlanGrid

20220205_094409_photo Bill Hoos Feb 5, 2022 9:44 AM

20220205_094318_photo Bill Hoos Feb 5, 2022 9:43 AM

Prepared by Bill Hoos 166 Created with PlanGrid

20220202_112348_photo Bill Hoos Feb 2, 2022 11:23 AM

Prepared by Bill Hoos 167 Created with PlanGrid

Status Open

Type Issue

Location D11-120

Description #42 Fire Damper

Fire Damper non compliant, non accessible, MEP in way

Created Feb 2, 2022 10:54 AM bill.hoos@jhcfirestop.com

Last Updated Feb 11, 2022 7:09 AM

Sheet

JP-01-11LS

#42 Fire Damper

Prepared by Bill Hoos 168 Created with PlanGrid

20220202_105531_photo Bill Hoos Feb 2, 2022 10:55 AM

Prepared by Bill Hoos 169 Created with PlanGrid

Status Closed

Type Issue

Location C11-11

Description #40 Fire Damper

Fire Damper operational, accessible, tested and passed

Created Feb 2, 2022 10:36 AM bill.hoos@jhcfirestop.com

Last Updated Feb 11, 2022 7:09 AM

Closed At Feb 5, 2022

Sheet

JP-01-11LS

#40 Fire Damper

Prepared by Bill Hoos 170 Created with PlanGrid

20220202_103728_photo Bill Hoos Feb 2, 2022 10:37 AM

Prepared by Bill Hoos 171 Created with PlanGrid

Status Open

Type Issue

Location C11-11

Description #39 Fire Damper

Fire Damper non compliant, no damper found

Created Feb 2, 2022 10:35 AM bill.hoos@jhcfirestop.com

Last Updated Feb 11, 2022 7:09 AM

Sheet

JP-01-11LS

#39 Fire Damper

Prepared by Bill Hoos 172 Created with PlanGrid

20220202_103833_photo Bill Hoos Feb 2, 2022 10:38 AM

20220202_103632_photo Bill Hoos Feb 2, 2022 10:36 AM

Prepared by Bill Hoos 173 Created with PlanGrid

Status Open

Type Issue

Location A11-39

Description #35 Fire Damper

Fire Damper non compliant, non accessible. Cannot open access panel

Created Feb 2, 2022 10:29 AM bill.hoos@jhcfirestop.com

Last Updated Feb 11, 2022 7:09 AM

Sheet

JP-01-11LS

#35 Fire Damper

Prepared by Bill Hoos 174 Created with PlanGrid

20220202_101212_photo Bill Hoos Feb 2, 2022 10:12 AM

Prepared by Bill Hoos 175 Created with PlanGrid

Status Open

Type Issue

Location B11-65

Description #31 Fire Damper

Fire Damper non compliant, non accessible, MEP in the way

Created Feb 2, 2022 10:29 AM bill.hoos@jhcfirestop.com

Last Updated Feb 11, 2022 7:09 AM

Sheet

JP-01-11LS

#31 Fire Damper

Prepared by Bill Hoos 176 Created with PlanGrid

20220202_094335_photo Bill Hoos Feb 2, 2022 9:43 AM

Prepared by Bill Hoos 177 Created with PlanGrid

Status Open

Type Issue

Location D12-95

Description #29 Fire Damper

No damper only access door

Created Feb 2, 2022 10:28 AM bill.hoos@jhcfirestop.com

Last Updated Feb 11, 2022 7:10 AM

Sheet

JP-01-12LS

#29 Fire Damper

Photos

20220201_135824_photo Bill Hoos Feb 1, 2022 1:58 PM

20220201_135817_photo Bill Hoos Feb 1, 2022 1:58 PM

Prepared by Bill Hoos 178 Created with PlanGrid

Status Open

Type Issue

Location D12-95

Description #28 Fire Damper

Fire Damper, need to be shut off for Saturday

Created Feb 2, 2022 10:28 AM bill.hoos@jhcfirestop.com

Last Updated Feb 11, 2022 7:10 AM

Sheet

JP-01-12LS

#28 Fire Damper

Prepared by Bill Hoos 179 Created with PlanGrid

Status Open

Type Issue

Location A12-42

Description #26 Fire Damper

Fire Damper non compliant, non accessible, can’t fully open access panel.

Created Feb 2, 2022 10:28 AM bill.hoos@jhcfirestop.com

Last Updated Feb 11, 2022 7:11 AM

Sheet

JP-01-12LS

#26 Fire Damper

Prepared by Bill Hoos 180 Created with PlanGrid

20220201_134630_photo Bill Hoos Feb 1, 2022 1:46 PM

Prepared by Bill Hoos 181 Created with PlanGrid

Status Open

Type Issue

Location A12-42

Description #25 Fire Damper

Fire Damper non compliant, non accessible, MEP’s in way

Created Feb 2, 2022 10:28 AM bill.hoos@jhcfirestop.com

Last Updated Feb 11, 2022 7:11 AM

Sheet

JP-01-12LS

#25 Fire Damper

Prepared by Bill Hoos 182 Created with PlanGrid

20220201_134531_photo Bill Hoos Feb 1, 2022 1:45 PM

Prepared by Bill Hoos 183 Created with PlanGrid

Status Open

Type Issue

Location A12-79

Description #24 Fire Damper

Fire Damper non compliant, non accessible, out of arms reach

Created Feb 2, 2022 10:27 AM bill.hoos@jhcfirestop.com

Last Updated Feb 11, 2022 7:11 AM

Sheet

JP-01-12LS

#24 Fire Damper

Prepared by Bill Hoos 184 Created with PlanGrid

20220201_134415_photo Bill Hoos Feb 1, 2022 1:44 PM

Prepared by Bill Hoos 185 Created with PlanGrid

Status Open

Type Issue

Location C12-34

Description #18 Fire Damper

Fire Damper non compliant, non accessible, needs at least an 8x8 Access panel

Created Feb 2, 2022 10:26 AM bill.hoos@jhcfirestop.com

Last Updated Feb 11, 2022 7:11 AM

Sheet

JP-01-12LS

#18 Fire Damper

Prepared by Bill Hoos 186 Created with PlanGrid

20220201_131928_photo Bill Hoos Feb 1, 2022 1:19 PM

Prepared by Bill Hoos 187 Created with PlanGrid

Status Open

Type Issue

Location C12-34

Description #17 Fire Damper

Fire damper non compliant, non accessible

Created Feb 2, 2022 10:26 AM bill.hoos@jhcfirestop.com

Last Updated Feb 11, 2022 7:11 AM

Sheet

JP-01-12LS

#17 Fire Damper

Prepared by Bill Hoos 188 Created with PlanGrid

20220201_131908_photo Bill Hoos Feb 1, 2022 1:19 PM

Prepared by Bill Hoos 189 Created with PlanGrid

Status Open

Type Issue

Location C12-15

Description #16 Fire Damper

Fire Damper, non compliant, is accessible, needs to be unconnected to alarm panel to decommision

Created Feb 2, 2022 10:26 AM bill.hoos@jhcfirestop.com

Last Updated Feb 11, 2022 7:18 AM

Sheet

JP-01-12LS

#16 Fire Damper

Prepared by Bill Hoos 190 Created with PlanGrid

20220201_130402_photo Bill Hoos Feb 1, 2022 1:04 PM

Prepared by Bill Hoos 191 Created with PlanGrid

Status Open

Type Issue

Location C12-15

Description #15 Fire Damper

Fire Damper, non compliant, no access, Created Feb 2, 2022 10:25 AM bill.hoos@jhcfirestop.com

Last Updated Feb 11, 2022 7:16 AM

Sheet

JP-01-12LS

#15 Fire Damper

Prepared by Bill Hoos 192 Created with PlanGrid

20220201_130300_photo Bill Hoos Feb 1, 2022 1:03 PM

Prepared by Bill Hoos 193 Created with PlanGrid

Status Open

Type Issue

Location 13C-13

Description #11 Smoke damper

Smoke Damper non compliant, non accessible, out of reach

Created Feb 1, 2022 7:26 PM bill.hoos@jhcfirestop.com

Last Updated Feb 11, 2022 7:12 AM

Sheet

JP-01-13LS

#11 Smoke Damper

Prepared by Bill Hoos 194 Created with PlanGrid

20220201_121531_photo Bill Hoos Feb 1, 2022 12:15 PM

Prepared by Bill Hoos 195 Created with PlanGrid

Status Open

Type Issue

Location 13C-13

Description #10 Smoke Dampe

Smoke damper non compliant, non accessible, out of arms reach

Created Feb 1, 2022 7:26 PM bill.hoos@jhcfirestop.com

Last Updated Feb 11, 2022 7:12 AM

Sheet

JP-01-13LS

#10 Smoke Damper

Prepared by Bill Hoos 196 Created with PlanGrid

20220201_121014_photo Bill Hoos Feb 1, 2022 12:10 PM

Prepared by Bill Hoos 197 Created with PlanGrid

Status Open

Type Issue

Description #5 Fire Damper

Fire damper noncompliant No damper in the plain rated barrier

Created Feb 1, 2022 7:25 PM bill.hoos@jhcfirestop.com

Last Updated Feb 11, 2022 7:13 AM

Sheet

JP-01-15LS

#5 Fire Damper

Photos

20220201_101639_photo Bill Hoos Feb 1, 2022 10:16 AM https://app.plangrid.com/projects/8f9c303d-bdcb-9566-27e4-d7984f6a7226/home

VA Jamaica Plain Fire and Smoke Damper Total Inventory. - Feb 11, 2022
Description
Contents
#187 Fire Smoke Damper
#183 Fire Damper
#181 Fire Damper
#179 Fire Damper
#178 Fire Damper
#177 Fire Damper
#176 Fire Damper
#175 Fire Damper
#174 Fire Smoke Damper
#173 Fire Damper
#172 Fire Damper
#171 Fire Damper
#170 Fire Damper
#169 Fire Damper
#168 Fire Damper
#167 Fire Damper
#166 Smoke Damper
#165 Smoke Damper
#164 Fire Damper
#163 Fire Damper
#161 Fire Damper
#158 Fire Damper
#157 Fire Damper
#155 Fire Damper
#154 Fire Damper
#153 Fire Damper
#152 Fire Damper
#151 Fire Damper
#150 Fire Damper
#149 Fire Damper
#148 Fire Damper
#147 Fire Damper
#146 Fire Damper
#144 Fire Smoke Damper
#143 Fire Damper
#142 Fire Damper
#141 Fire Damper
#140 Fire Damper
#136 Fire Smoke Damper
#130 Fire Smoke Damper
#129 Fire Damper
#127 Fire Damper
#126 Fire Damper
#122 Smoke Damper
#121 Fire Damper
#120 Exhaust damper
#119 Fire Damper
#113 Fire Smoke Damper
#112 Fire Smoke Damper
#111 Fire Smoke Damper
#106 Fire Damper
#105 Smoke Damper
#103 Fire Damper
#102 Fire Damper
#101 Fire Damper
#97 Fire Damper
#94 Fire Damper
#93 Fire Damper
#92 Fire Damper
#89 Fire Damper
#88 Fire Damper
#85 Fire Damper
#84 Fire Smoke Damper
#83 Fire Damper
#81 Max Air Damper
#80 Fire Damper
#79 Fire Damper
#78 Fire Damper
#77 Fire Damper
#76 Fire Damper
#75 Fire Damper
#72 Fire Damper
#71 Fire Damper
#70 Fire Damper
#59 Fire Damper
#57 Fire Smoke Damper
#56 Fire Damper
#54 Fire Smoke Damper
#53 Fire Access
#52 Fire Damper
#51 Smoke Damper
#49 Fire Damper
#47 Fire Damper
#46 Fire Damper
#44 Fire Damper
#43 Fire Damper
#42 Fire Damper
#40 Fire Damper
#39 Fire Damper
#35 Fire Damper
#31 Fire Damper
#29 Fire Damper
#28 Fire Damper
#26 Fire Damper
#25 Fire Damper
#24 Fire Damper
#18 Fire Damper
#17 Fire Damper
#16 Fire Damper
#15 Fire Damper
#11 Smoke Damper
#10 Smoke Damper
#5 Fire Damper

File details come from the government source that posted it. Updated .