36C10F19R0040-019.pdf

PDF 23 MB Posted

Attached to
WESTERN NEW YORK NATIONAL CEMETERY PHASE 1A Federal contract opportunity
Solicitation number
36C10F19R0040
Issued by
Department of Veterans Affairs Headquarters

About this file

36C10F19R0040 C27 936PC2002_WNYNC_391-444-DWG.pdf

View the file

Other files for this federal contract opportunity

Other files attached to WESTERN NEW YORK NATIONAL CEMETERY PHASE 1A, newest first.
File Type Posted
36C10F19C0015-000.docx DOCX document
36C10F19R0040-0002001.pdf PDF
36C10F19R0040-0002002.pdf PDF
36C10F19R0040-0002000.docx DOCX document
36C10F19R0040-002.docx DOCX document
36C10F19R0040-013.pdf PDF
36C10F19R0040-008.pdf PDF
36C10F19R0040-014.pdf PDF
36C10F19R0040-011.pdf PDF
36C10F19R0040-012.pdf PDF
36C10F19R0040-009.pdf PDF
36C10F19R0040-003.docx DOCX document
36C10F19R0040-007.pdf PDF
36C10F19R0040-006.pdf PDF
36C10F19R0040-010.pdf PDF
36C10F19R0040-004.pdf PDF
36C10F19R0040-017.pdf PDF
36C10F19R0040-018.pdf PDF
36C10F19R0040-016.pdf PDF
36C10F19R0040-005.pdf PDF
36C10F19R0040-015.pdf PDF
36C10F19R0040-020.pdf PDF
36C10F19R0040-001.docx DOCX document
Show all 23

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

N O

R T

H

ABBREVIATIONS

STORM (ST)

LIQUID PROPANE GAS (LPG)

WASTE (W)

VENT (V)

HOT WATER RETURN (HWR)

HOT WATER (HW)

COLD WATER (CW)

BACKFLOW PREVENTER (BFP)

ELBOW DOWN

ELBOW UP

RISE OR DROP

PRESSURE GAUGE WITH GAUGE COCK (PG)

THERMOMETER (SPECIFY TYPE) (TH)

STRAINER

WALL CLEANOUT (CO)

CO CLEANOUT (CO)

FLOOR DRAIN (FD)

WH

HB

NON-FREEZE WALL HYDRANT (WH)

HOSE BIB (HB)

VALVE

UNION

CAPPED PIPING

CHECK VALVE (SHOWN W/FLOW)

BALANCING VALVE

FLOOR CLEANOUT (FCO)FCO

TRENCH DRAIN (TD)

SYMBOLS

BFP BACKFLOW PREVENTER

CFH CUBIC FEET PER HOUR

CO CLEANOUT

CONT. CONTINUED

CW COLD WATER

DN DOWN

DWG DRAWING

FCO FLOOR CLEANOUT

FD FLOOR DRAIN

GW GARAGE WASTE

HW HOT WATER

HWR HOT WATER RETURN

INV. ELEV. INVERT ELEVATION

LPG LIQUID PROPANE GAS

S.F. SQUARE FOOT

ST STORM SEWER

TD TRENCH DRAIN

TMV THERMOSTATIC MIXING VALVE

TW TEMPERED WATER

TYP TYPICAL

V VENT

VTR VENT THRU ROOF

W WASTE

W/ WITH

WCO WALL CLEANOUT

WH WATER HEATER

P-TRAP

BOTTOM DROP

ST

LPG

METER AND BACKFLOW

PREVENTER

OPEN OFFICE

A-105

DIRECTOR

A-111ASST. DIRECTOR

A-115

ELECTRICAL

A-118 GEN. STORAGE

A-116

CORRIDOR

A-110

DATA / I.T.

A-117

MECHANICAL

A-119

PASSAGE

A-114

WOMEN'S

A-112

LUNCH ROOM

A-120 MEN'S

A-113

SECURE STORAGE

A-127

SEATING

A-106

LOBBY

A-100CORRIDOR

A-107

MULTI-PURPOSE

A-108

RECYCLE

A-104

VESTIBULE

A-122

MEN'S

A-101

FAMILY RESTROOM

A-102

HAC

A-121

WOMEN'S

A-103

VESTIBULE

A-126

2" CW ENTRANCE

P-301

P-301

P-202

P-201 P-101 P-103

P-405

P-302 P-501

P-301

P-301

P-101P-101 P-103 P-302

P-302

P-501 P-401

FD-A

FD-A

FD-E

P-102

P-102

P-102 P-801

P-801

P-801

P-801 P-802

P-802

BFP-1

2" LPG CONT.

ON SITE PLAN

698 CFH

CENTERLINE. ELEV.

863.00'

(SEE DETAIL 1-P-201)FD-A

FD-A

FD-A

FD-A

862.20'

FINISHED FLOOR

G

HW

HWR

CW

G

METER WITH

REMOTE READER

1 1/2" 1 1/2"

2"G C

W H

W H

W

R FD-A

PLUMBING NOTES:

1. FOR PIPE SIZES SEE RISER DIAGRAM SHEET P-901

P-801

BUILDING DOUBLE

CLEANOUT

BOILER (B-A-1)

(300 CFH)

DWCP-1

1/2" CW TO

REFRIGERATOR

ICE MAKER

THERMOSTATIC MASTER

MIXING VALVE (MMV-1)

WH-2 (199 CFH)

WH-2 (199 CFH)

FLOW CONTROL VALVING

SET AT 2 GPM

SEE 2D/P201

4" STORM

CONNECT TO

DOWNSPOUT

WITH BOOT

4" STORM

CONNECT TO

DOWNSPOUT

WITH BOOT

4" STORM

CONNECT TO

DOWNSPOUT

WITH BOOT

STORM CLEANOUT

4" STORM

CONNECT TO

DOWNSPOUT

WITH BOOT

4" STORM

CONNECT TO

DOWNSPOUT

WITH BOOT

4" STORM

CONNECT TO

DOWNSPOUT

WITH BOOT

4" STORM

CONNECT TO

DOWNSPOUT

WITH BOOT

4" STORM

CONNECT TO

DOWNSPOUT

WITH BOOT

STORM CLEANOUT

STORM CLEANOUT

A.A

D.A

1.A 2.A 3.A 4.A

C.A

B.A

ELECTRONIC

TRAP SEAL

PRIMMER

(TP-1) ON

WALL

ELECTRONIC TRAP

SEAL PRIMMER

(TP-1) ON WALL

DOMESTIC WATER

BOOSTER PUMP

DWBP-1

3" VENT

THRU ROOF

DOMESTIC WATER

BOOSTER PUMP

ACCUMALATOR TANK

2" WASTE

UP TO P-501

3" WASTE

UP TO FD-A

3" WASTE

UP TO FD-A

4" WASTE UP TO

CLEANOUTS

3" WASTE

UP TO FD-A

3" WASTE

UP TO P-405

4" WASTE UP

2" WASTE UP

2" WASTE UP

4" WASTE UP

2" VENT UP3" WASTE

UP TO FD-A

4" WASTE UP

2" WASTE UP

3" WASTE

UP TO FD-B

2" VENT UP

4"

4" 4"

4" W CONT.

ON SITE PLAN

(I.E.= 856.70)

(80.5 DFU)

4"

3"

PLUMBING NOTES:

1. FOR PIPE SIZES SEE RISER DIAGRAM SHEET P-901

BUILDING

DOUBLE

CLEANOUT

2" CW CONT.

ON SITE PLAN

CENTERLINE. ELEV.

856.70

3" WASTE

UP TO FD-A

4" STORM

INV. ELEV. 859.00

(TYP AT ALL DOWNSPOUT

CONNECTIONS)

4" STORM UP

CONNECT TO

DOWNSPOUT

(763 SQ. FT.)

4" STORM UP

CONNECT TO

DOWNSPOUT

(729 SQ. FT.)

4" STORM UP

CONNECT TO

DOWNSPOUT

(729 SQ. FT.)

4" STORM UP

CONNECT TO

DOWNSPOUT

(763 SQ. FT)

4" STORM UP

CONNECT TO

DOWNSPOUT

(460 SQ. FT.)

4" STORM UP

TO CLEANOUT

4" STORM UP

TO CLEANOUT

4" STORM UP

TO CLEANOUT

4" 4"

4"

6"

6"

4"

6"

6"

6"

6" STORM CONNECT TO MAIN

STORM MAIN (I.E.=858.20)

(6038 SQ.FT.)

(SEE CIVIL FOR CONTINUATION)

4" SUBSOIL DRAIN

CONNECT INDEPENDENTLY TO

MAIN STORM MAIN (SEE CIVIL

FOR CONTINUATION)

4" SUBSOIL DRAINAGE PIPING

(I.E. = 857.70)

A.A

D.A

1.A 2.A 3.A 4.A

C.A

B.A

4" STORM UP

CONNECT TO

DOWNSPOUT

(460 SQ. FT.)

4" STORM UP

CONNECT TO

DOWNSPOUT

(1067 SQ. FT.)

4" STORM UP

CONNECT TO

DOWNSPOUT

(1067 SQ. FT.)

TRAP SEAL

PRIMMER PIPING

862.20'

FINISHED FLOOR

PROVIDE SLEEVE IN

SPREAD FOOTING

FOR DOMESTIC

WATER SERVICE

4 8 1608

1 inch = 8 feet

GRAPHIC SCALE

B

A

C

D

E

F

1 2 3 4 5 6 87 9

F

E

D

C

B

A

97 8654321

BID DOCUMENTS

ATIONAL

EMETERY

DMINISTRATIONA

C

N

Drawing Title

GENESEE COUNTY, NEW YORK

Project Title

Location

Date Checked Drawn

936PC2002

Drawing Number

Building Number

Project Number

Management

03-15-19 Dwg of

V

T

N T I

D

STA

E

U

E

N T

OF

I

C

ES OF

R I

AM

E

R

A

S

S

ETERAN

AF

F A

Revisions:

VA FORM 08-6231, OCT 1978

CONSULTANTS:

Date

ARCHITECT/ENGINEER:

ATIONAL

EMETERY

DMINISTRATIONA

C

N

WESTERN NEW YORK

NATIONAL CEMETERY

PHASE 1A DEVELOPMENT and Facilities

Office of

Construction

LEO A DALY Company 2017

/2

/2

:5

:3

A

M C

U s e rs

\m js p e lle rb e rg

\D o c u m e n ts

\A u to d e s k \R e v it

P ro je c ts

\V A

C e m e te ry W

N Y

P

P -2 m js p e lle rb e rg

.r v t

P-101

PLUMBING PLANS - ADMIN BLDG

DJD BDB

PLUMBING PLANS - ADMIN BLDG

ADMIN / PIC - PLUMBING

3401, 3001,1001

ADMIN / PIC SUBGRADE - PLUMBING

NORTH

Unoccupied

Unoccupied

PORCH

C-100

STORAGE

C-103

LOCKER

C-102

WOMEN'S

C-105

MECHANICAL

C-104

MEN'S

C-106

3/4" LPG CONT.

ON SITE PLAN

207 CFH

CENTERLINE. ELEV.

854.90'

(SEE DETAIL 2-P-201)

P-401

P-103

P-202

P-103

P-405

P-801

P-802

P-802

P-801

FD-A

FD-A

BFP-1

WH-1

854.60

FINISHED FLOOR

FD-E

FD-A

C W

H W

H W

R

G

REMOTE READ

WATER METER

P-501

BUILDING DOUBLE

CLEANOUT

P302

P302

P302

PLUMBING NOTES:

1. FOR PIPE SIZES SEE RISER DIAGRAM SHEET P-904

3/4" PROPANE

TO AHU-C-1

(300 MBH)

3/4" PROPANE TO

WH-1 (150 MBH)

FLOOR

C.O.

DWCP-3

FLOW

CONTROL

VALVING

SEE 2D/P201

4" STORM

CONNECT TO

DOWNSPOUT WITH

BOOT

4" STORM

CONNECT TO

DOWNSPOUT WITH

BOOT4" STORM

CONNECT TO

DOWNSPOUT WITH

BOOT

4" STORM

CONNECT TO

DOWNSPOUT

WITH BOOT

4.CD.GD.B1.C

E.C

D.C

MASTWER

MIXING VAVLE

(MMV-2)

2" CW CONT.

ON SITE PLAN

CENTER. ELEV.

849.60'

4" W CONT'D

ON SITE PLAN

(29.5 DFU)

BUILDING DOUBLE

CLEANOUT

2" WASTE UP

TO SINK

2" WASTE UP

TO DRINKING

FOUNTAIN

2" WASTE UP

TO MOP SINK

3" UP TO

FLOOR C.O.

3" UP TO

FLOOR DRAIN

3" UP TO

FLOOR DRAIN

2" WASTE

UP

4" WASTE

UP

3" UP TO

FLOOR DRAIN

PLUMBING NOTES:

1. FOR PIPE SIZES SEE RISER DIAGRAM SHEET P-904

4" STORM (2144 SQ.FT.)

CONNECT TO STORM MAIN (I.E.= 849.77)

(SEE CIVIL FOR CONTINUATION)

4" STORM

(I.E.= 851.30)

4" STORM UP CONNECT TO STORM

DOWNSPOUT WITH BOOT

(536 SQ.FT.)

4" STORM UP CONNECT TO

STORM DOWNSPOUT WITH BOOT

(536 SQ. FT.)

4" STORM UP

CONNECT TO STORM

DOWNSPOUT WITH

BOOT

(536 SQ.FT.)

4"

4"

4"

4" SUBSOIL DRAIN

CONNECT INDEPENDENTLY TO

STORM MAIN (I.E. = 850.10)

(SEE CIVIL FOR CONTINUATION)

4" SUBSOIL PIPE

SEE STRUCTRAL FOR

INVERT ELEVATION

4.CD.GD.B1.C

E.C

D.C

4" STORM UP CONNECT TO

STORM DOWNSPOUT WITH BOOT

(536 SQ.FT.)

I.E.=849.10

854.60'

FINISHED FLOOR

PROVIDE SLEEVE IN

SPREAD FOOTING

FOR DOMESTIC

WATER SERVICE

4" STORM

(I.E.= 851.30)

4 8 1608

1 inch = 8 feet

GRAPHIC SCALE

1.B 2B

A.B

D.B

B.B

C.B

1.2B 1.5B

1.4B

1.3B

4" STORM (493 SQ.FT.)

CONNECT TO DOWNSPOUT

WITH BOOT

4" SUBSOIL DRAINAGE PIPE

SEE STRUCTURAL FOR

INVERT ELEVATION

4" SUBSOIL DRAIN

(I.E. = 849.50

SEE CIVIL FOR

CONTINUATION

4" STORM DRAIN (1246 SQ.FT.)

(I.E. = 849.17)

SEE CIVIL FOR CONTINUATION

1.B 2B

A.B

B.B

5.B

4" STORM (493 SQ.FT.)

CONNECT TO

DOWNSPOUT WITH BOOT

4" STORM (130 SQ.FT.)

CONNECT TO DOWNSPOUT

WITH BOOT4" STORM (130 SQ.FT.)

CONNECT TO

DOWNSPOUT WITH BOOT

1.B 2B

A.B

D.B

B.B

C.B

1.2B 1.5B

1.4B

1.3B

4" STORM (493 SQ.FT.)

CONNECT TO DOWNSPOUT

WITH BOOT

4" SUBSOIL DRAINAGE PIPE

SEE STRUCTURAL FOR

INVERT ELEVATION

4" SUBSOIL DRAIN

(I.E. = 850.50)

SEE CIVIL FOR

CONTINUATION

4" STORM DRAIN (1246 SQ.FT)

(I.E. = 850.00)

SEE CIVIL FOR CONTINUATION

4" STORM (130 SQ.FT.)

CONNECT TO DOWNSPOUT

WITH BOOT

4" STORM (493 SQ.FT.)

CONNECT TO

DOWNSPOUT WITH BOOT

4" STORM (130 SQ.FT.)

CONNECT TO

DOWNSPOUT WITH BOOT

B

A

C

D

E

F

1 2 3 4 5 6 87 9

F

E

D

C

B

A

97 8654321

BID DOCUMENTS

ATIONAL

EMETERY

DMINISTRATIONA

C

N

Drawing Title

GENESEE COUNTY, NEW YORK

Project Title

Location

Date Checked Drawn

936PC2002

Drawing Number

Building Number

Project Number

Management

03-15-19 Dwg of

V

T

N T I

D

STA

E

U

E

N T

OF

I

C

ES OF

R I

AM

E

R

A

S

S

ETERAN

AF

F A

Revisions:

VA FORM 08-6231, OCT 1978

CONSULTANTS:

Date

ARCHITECT/ENGINEER:

ATIONAL

EMETERY

DMINISTRATIONA

C

N

WESTERN NEW YORK

NATIONAL CEMETERY

PHASE 1A DEVELOPMENT and Facilities

Office of

Construction

LEO A DALY Company 2017

/2

/2

:5

:3

A

M C

U s e rs

\m js p e lle rb e rg

\D o c u m e n ts

\A u to d e s k \R e v it

P ro je c ts

\V A

C e m e te ry W

N Y

P

P -2 m js p e lle rb e rg

.r v t

P-103

PLUMBING PLANS - HONOR GUARD

BLDG AND COMMITTAL SERVICE

SHELTER 1

DJD BDB

PLUMBING PLANS - HONOR GUARD

BLDG AND COMMITTAL SERVICE

SHELTER 1

HONOR GUARD - PLUMBING

HONOR GUARD SUBGRADE - PLUMBING COMMITTAL SERVICE SHELTER 1 - PLUMBING

COMMITTAL SERVICE SHELTER 2 - PLUMBING

1 VE OPTION NO. 8

ADD ALTERNATE 1

ADD ALTERNATE 1

N.I.C.

COMPACTED SUBGRADE

MINIMUM 12"

PEA GRAVEL

(STONE TYPE 1)

TURN-

BUCKLE

FRP STRAP

(TYPICAL)

EYELET

STRAP

PROPANE TANK

(SEE CIVIL DRAWINGS

FOR SIZE)

TANK BOTTOM

DEFLECTOR PLATE

(TYPICAL)

COMPACTED CRUSHED

AGGREGATE

1/2" BY 24" BENT

ANCHORS BOLTS (2

PER STRAP)

EMBED ANCHORS

INTO CONCRETE

PAD (TYP)

12".

12"(TYPICAL ALL 4 SIDES)

2 TO 6 INCHES MINIMUMTOP OF RELIEF VALVE

RISER HEIGHT 28"

PROVIDE TWO

17 POUND

MAGNESIUM

ANODES

ATTACHMENT

TO CADWELD

OR TANK RISER

18 INCHES MINIMUM

POLYETHYLENE TUBING

TO BUILDING (INCLUDE

TRACER WIRE AND

CAUTION TAPE

END OF REGULATOR VENT TUBE LOCATED

AT TOP INSIDE OF HOUSING DOME COVER.

SHOULD BE A MINIMUM OF 2" ABOVE

HIGHEST POSSIBLE WATER LEVEL.

GRADE GROUND DOWNWARD AND AWAY AROUND

HOUSING DOME A MINIMUM OF 3 INCHES. THIS

PREVENTS WATER COLLECTING AND RUNNING

INTO OR STANDING AROUND THE HOUSING DOME.

CONCRETE PAD WITH #6

REBAR 12" ON CENTER BOTH

WAYS - TOP AND BOTTOM

SECOND STAGE

REGULATOR (11" W.C.)

BUILDING

PROPANE VAPORIZER

(20 GAL/HR ADMIN BLDG)

SHUTOFF

VALVE

COORDINATE WIRE

SIZE WITH

MAGNESIUM ANODE

MANUFACTURER

25' MIN

FIRST STAGE REGULATOR

(10 PSI)

6" CONCRETE

PAD

SECOND STAGE

REGULATOR (11" W.C.)

DISTRIBUTION LINE

BUILDING

PROPANE VAPORIZER

(20 GAL/HR HONOR

GUARD BLDG)

(25 GAL.HR

MAINTENANCE BLDG)

SHUTOFF

VALVE

POLYETHYLENE TUBING

TO BUILDING (INCLUDE

TRACER WIRE AND

CAUTION TAPE

PROPANE TANK

(SEE CIVIL DRAWINGS

FOR SIZE)

BOLTED SUPPORTS W/

NEOPRENE PADS

(SEE MANUFACTURES

INSTALLATION)

25' MIN

MOISTURE SIGHT

GLASS INDICATOR

BALL VALVE (TYP)

DRYER BYPASS

PRESSURE GAGE

BRANCH WITH QUICK

CONNECT TO SERVE

MECH. RM.

REFRIGERATED AIR DRYER

DRAIN TO FLOOR DRAIN

D

4" HOUSEKEEPING PAD

OIL FILTER

COMPRESSED AIR

PRESSURE REGULATOR

SET AT 90 PSI

(ADJUSTABLE)

STRAINER

HW CIRCULATING PUMP W/

AQUASTAT CONTROLLER

CHECK VALVE (TYP.)

FLUE

SHUT-OFF VALVE (TYP.)

3/4" HWC

1" CW

UNION (TYP.)

5 GALLON

DIAPHRAGM TYPE

EXPANSION TANK

GAS COCK

DRAIN VALVE

WITH

HOSE

THREADS

TO FLOOR DRAIN

TEMPERATURE AND

PRESSURE RELIEF

VALVE

THERMOMETER (TYP.)

1" 140 DEGREE HW

LP

G

D

LP

G

D

OUTSIDE AIR

1-1/4" PROPANE

3/4"CONDENSATE DRAIN

TO FLOOR DRAIN

1" 130 DEGREE HW

1" CW

HI/LO THERMOSTATIC

MIXING VALVE

1" 140 DEGREE HW TO

EMERGENCY SHOWER ONLY

(MAINTENANCE BUILDING

ONLY)

1/2" HWC

1" PROPANE

1" PROPANE

1" 140 DEGREE HW

1" CW

1" CW

1" 140 DEGREE HW

FROM HW SOURCE

TO FINAL FIXTURE (OR

FIXTURE GROUP) ON BRANCH

TO CIRCULATING PUMPBALL VALVE

CIRCULATION CONTROL

VALVE WITH PETES PORTS

(SET TO 2 GPM)

CHECK VALVE

MARK

PLUMBING EQUIPMENT SCHEDULE

SAC-1

LOCATION

MAINTENANCE BLDG MEZZANINE

SERVES

MAINTENANCE BLDG

HP VOLT PH HZ

ELECTRICAL DATA

3.5 230 1 60

ACFM @

90 PSIG

MAX

PRESSURE

12.8 135

MMV-1 MECH ROOM

WATER FLOW

GPM

REMARKS

OUTPUT

TEMPERATURE

13011

AIR COMPRESSOR WITH 60 GALLON RECIEVER TANK AND REFRIGERATED DRYER

MMV-2 HONOR BLDG MECH ROOM 1304 LEAD FREE, LOW PRESSURE DROP HOT WATER MASTER MIXING VALVEDOMESTIC HOT WATER

DOMESTIC HOT WATER

DESCRIPTION

AIR COMPRESSOR

MASTER MIXING VALVE

MASTER MIXING VALVE

LEAD FREE, LOW PRESSURE DROP HOT WATER MASTER MIXING VALVE

BALL SHUTOFF

VALVE

AIR HOSE QUICK DISCONNECT

(MOUNT AT 72" (ADJUSTABLE)

CEILING

BALL STOP ON

AIR HOSE

(ADJUSTABLE)

HOSE REEL

MOUNT HOSE REEL TO STRUCTURAL

ROOF MEMBER PER

MANUFACTURERS RECOMMENDATION

AIR HOSE

3/4" CA

STRAINER

HW CIRCULATING PUMP W/

AQUASTAT CONTROLLER

CHECK VALVE (TYP.)

FLUE

SHUT-OFF VALVE (TYP.)

3/4" HWC

1" CW

UNION (TYP.)

5 GALLON

DIAPHRAGM TYPE

EXPANSION TANK

GAS COCK

DRAIN VALVE

WITH

HOSE

THREADS

TO FLOOR DRAIN

TEMPERATURE AND

PRESSURE RELIEF

VALVE

THERMOMETER (TYP.)

1" 140 DEGREE HW

LP

G

D

OUTSIDE AIR

3/4" PROPANE

CONDENSATEDRAIN

TO FLOOR DRAIN

1" 130 DEGREE HW

1" CW

HI/LO THERMOSTATIC

MIXING VALVE

1/2" HWC

1" CW

B

A

C

D

E

F

1 2 3 4 5 6 87 9

F

E

D

C

B

A

97 8654321

BID DOCUMENTS

ATIONAL

EMETERY

DMINISTRATIONA

C

N

Drawing Title

GENESEE COUNTY, NEW YORK

Project Title

Location

Date Checked Drawn

936PC2002

Drawing Number

Building Number

Project Number

Management

03-15-19 Dwg of

V

T

N T I

D

STA

E

U

E

N T

OF

I

C

ES OF

R I

AM

E

R

A

S

S

ETERAN

AF

F A

Revisions:

VA FORM 08-6231, OCT 1978

CONSULTANTS:

Date

ARCHITECT/ENGINEER:

ATIONAL

EMETERY

DMINISTRATIONA

C

N

WESTERN NEW YORK

NATIONAL CEMETERY

PHASE 1A DEVELOPMENT and Facilities

Office of

Construction

LEO A DALY Company 2017

/2

/2

:5

:3

A

M C

U s e rs

\m js p e lle rb e rg

\D o c u m e n ts

\A u to d e s k \R e v it

P ro je c ts

\V A

C e m e te ry W

N Y

P

P -2 m js p e lle rb e rg

.r v t

P-201

PLUMBING DETAILS AND SCHEDULES

DJD BDB

PLUMBING DETAILS AND SCHEDULES

1/8" = 1'-0"

UNDERGROUND PROPANE TANK

1/8" = 1'-0"

ABOVE GROUND PROPANE TANK

PLUMBING FIXTURE CONNECTION SCHEDULE

ABBREV. FIXTURE

DRAINAGE WATER

REMARKSW V CW HW

FD-A FLOOR DRAIN 3" 2" WITH TRAP SEAL PRIMMER CONNECTION (INSTALL TOP OF GRATE 1\2" BELOW FINISHED FLOOR ELEVATION.)

FD-C TRENCH DRAIN 4" 2" 12" WIDE TRENCH DRAIN WITH 3'x3'x3' DEEP SUMP AT END

FD-E FLOOR DRAIN 4" 2" WITH TRAP SEAL PRIMMER CONNECTION (INSTALL TOP OF GRATE 1\2" BELOW FINISHED FLOOR ELEVATION.)

P-101 WATER CLOSET (PUBLIC) 4" 2" 1" WALL MOUNTED BACK OUTLET WITH HARD WIRED SENSOR FLUSH VALVE

P-102 WATER CLOSET (PRIVATE ADA) 4" 2" 1" WALL MOUNTED BACK OUTLET WITH MANUAL FLUSH VALVE

P-103 WATER CLOSET (PUBLIC ADA) 4" 2" 1" WALL MOUNTED BACK OUTLET WITH HARD WIRED SENSOR FLUSH VALVE

P-201 URINAL (PUBLIC) 2" 2" 3/4" WALL MOUNTED BACK OUTLET WITH HARD WIRED SENSOR FLUSH VALVE

P-202 URINAL (PUBLIC ADA) 2" 2" 3/4" WALL MOUNTED BACK OUTLET WITH HARD WIRED SENSOR FLUSH VALVE

P-301 LAVATORY (PUBLIC ADA) 2" 1 1/2" 1/2" 1/2" HARD WIRED SENSOR FAUCET

P-302 LAVATORY (PRIVATE ADA) 2" 1 1/2" 1/2" 1/2" HARD WIRED SENSOR FAUCET

P-401 SINK 2" 1 1/2" 1/2" 1/2"

P-402 SINK 2" 1 1/2" 1/2" 1/2"

P-405 MOP SINK 3" 1 1/2" 3/4" 3/4"

P-501 ELECTRIC WATER COOLER (ADA) 1 1/2" 1 1/2" 1/2"

P-601 SHOWER 2" 1 1/2" 1/2" 1/2" Modular ADA compliant roll-in enclosure

P-701 ADA COMBINATION EYE/FACEWASH 0" 0" 1" 1" WITH ANSI Z358.1 COMPLIANT EMERGENCY MIXING VALVE

P-801 WALL HYDRANT 3/4"

P-802 INTERIOR WALL HYDRANT 3/4"

P-901 SINK 3" 2" 1/2" 1/2"

WATER HEATER SCHEDULE

ABBREV. QTY.

MANUFACTURER (BASIS OF

DESIGN) MODEL NO. DESCRIPTION FLOW AT TEMPERATURE RISE V / ph / Hz BMS CONN. ACCESSORIES LOCATION INPUT

WH-1 1 NAVIEN NPE-180A PREMIUM CONDENSING TANKLESS WATER HEATER 2.9 GPM @100º F RISE 120 / 1 / 60 Yes CONCENTRIC VENT KIT, PROPANE CONVERSION KIT C-104 150000.0 Btu/h

WH-2 2 NAVIEN NPE-240A PREMIUM CONDENSING TANKLESS WATER HEATER 3.9 GPM @ 100º F RISE 120 / 1 / 60 Yes CONCENTRIC VENT KIT, PROPANE CONVERSION KIT A-121 199900.0 Btu/h

WH-2 2 NAVIEN NPE-240A PREMIUM CONDENSING TANKLESS WATER HEATER 3.9 GPM @ 100º F RISE 120 / 1 / 60 Yes CONCENTRIC VENT KIT, PROPANE CONVERSION KIT D-120 199900.0 Btu/h

BACKFLOW PREVENTER SCHEDULE

ABBREV. QTY. SIZE

MANUFACTURER (BASIS OF

DESIGN) MODEL NO. DESCRIPTION REMARKS LOCATION

BFP-1 1 2" WATTS LF009-M2-QT REDUCED PRESSURE ZONE ASSEMBLY PROVIDE WITH STRAINER AND AIR GAP FITTING A-119

BFP-1 1 2" WATTS LF009-M2-QT REDUCED PRESSURE ZONE ASSEMBLY PROVIDE WITH STRAINER AND AIR GAP FITTING C-104

BFP-1 1 2" WATTS LF009-M2-QT REDUCED PRESSURE ZONE ASSEMBLY PROVIDE WITH STRAINER AND AIR GAP FITTING D-120

NONE

AIR COMPRESSOR DETAIL

NONE

DUPLEX GAS DOMESTIC WATER HEATER WITH PUMP

PUMP SCHEDULE

MARK LOCATION SERVES TYPE GPM

TOTAL HEAD FT

WG

MOTOR DATA

MIN EFF % NOTESHP RPM VOL PH HZ

DWBP-1 SEE PLANS ADMINISTRATION BUILDING DOMESTIC WATER PACKAGED

DUPLEX

66 30.00 1.00 3500 460 3 60 0

DWCP-1 SEE PLANS DOMESTIC WATER HOT WATER INLINE 2 20.00 0.08 2650 115 1 60 0

DWCP-2 SEE PLANS DOMESTIC WATER HOT WATER INLINE 2 20.00 0.08 2650 115 1 60 0

DWCP-3 SEE PLANS DOMESTIC WATER HOT WATER INLINE 2 10.00 0.07 2800 115 1 60 0

NONE

DOMESTIC HOT WATER CIRCULATING CONTROL

NANA

NONE

COMPRESSED AIR HOSE REEL DETAIL

NONE

SIMPLEX GAS DOMESTIC WATER HEATER WITH PUMP

ADMINISTRATION

1 VE OPTION NO. 6

HONOR GUARD - ADD ALTERNATE 1

HONOR GUARD - ADD ALTERNATE 1

HONOR GUARD ADD ALTERNATE 1

HONOR GUARD ADD ALTERNATE 1

HONOR GUARD ADD ALTERNATE 1

HONOR GUARD ADD ALTERNATE 1

HONOR GUARD ADD ALTERNATE 1

MAINTENANCE BLDG - N.I.C.

HONOR GUARD - ADD ALTERNATE 1

HONOR GUARD - ADD ALTERNATE 1

HONOR GUARD - ADD ALTERNATE 1

HONOR GUARD - ADD ALTERNATE 1

HONOR GUARD - ADD ALTERNATE 1

MAINTENANCE BLDG - N.I.C.

MAINTENANCE BLDG - N.I.C.

MAINTENANCE BLDG - N.I.C.

MAINTENANCE BLDG - N.I.C.

MAINTENANCE BLDG - N.I.C.

MAINTENANCE BLDG - N.I.C.

MAINTENANCE BLDG - N.I.C.

MAINTENANCE BLDG - N.I.C.

MAINTENANCE BLDG - N.I.C.

MAINTENANCE BLDG - N.I.C.

HONOR GUARD ADD ALTERNATE 1

HONOR GUARD ADD ALTERNATE 1

WH-2

WH-2

BFP-1

METER

3/4"

3/4"

3/4"

2"

3/4"

3/4"

2"

2"

P-102

P-101

P-101

P-802

P-301

P-301 P-302

P-501

P-801

P-801

P-801

P-801

P-801

P-302

P-302 P-501

P-102

P-102

P-401

P-301

P-301

P-201

P-202

P-101

P-102

1 1/2"

1"

1/2"

1/2"

1/2"

1/2"

1 1/2"

2"

2"

2"

2"

2"

2"

2"

1 1/2"

1/2"

1/2"

2"

1/2"

1/2"

1/2" 3/4"

2" 2"

2"

2"

P-802

1" 3/4"

3/4"

3/4"

3/4"

3/4"

1"

3/4"

3/4"

1/2"

2"

3/4"

3/4"

3/4"

1/2"

1/2"

2"

1" 1/2"

1/2"

1/2"

1/2"

1/2" 3/4"

3/4"

2"

1/2"

3/4"

1"

3/4"

1"

P-405

1"

2"

1/2"

1/2"

WATER HAMMER

ARRESTOR (TYP)

3/4"

1/2" CW VALVED

CONNECTION TO

REFRIGERATOR ICE

MAKER

DWCP-1

FLOW CONTROL VALVING

SET AT 2 GPM

SEE 2D/P201

ELECTRONIC TRAP

SEAL PRIMMER (TP-1)

ELECTRONIC TRAP SEAL

PRIMMER PIPING

ELECTRONIC

TRAP SEAL

PRIMMER (TP-1)

BEHIND WATER

HEATER

2" ISOLATION

VALVE

DOMESTIC WATER

BOOSTER PUMP

DWBP-1

DOMESTIC WATER

BOOSTER PUMP

ACCUMALATOR

TANK

2"

2"

4"

4"

4"

2 1/2"

1 1/2"

1 1/4"

1 1/2"

3"

4"

4"

4" VENT

THRU ROOF

3" VENT

THRU ROOF

4" VENT

THRU ROOF

FD-A

FD-A

P-102

P-102

P-302

P-302

P-501

3"

3"

FD-E

FD-A

FD-A

FD-A

FD-A

FD-A P-102

P-102

P-405

P-101

P-101

P-101

P-202

P-201

P-301 P-301

P-301

P-301

P-501

BUILDING

DOUBLE

CLEANOUT

FLOOR

C.O.

4"

4"

4"

2"

2 1/2"

2"

2"

2"

1 1/2"

2"

1 1/2"

1 1/2"

1 1/2"

3"

3" 1 1/2"

3"

3"

2"

4"

4"4"

3"

4"

3"

1 1/2"

1 1/2"

1 1/2"

1 1/2"

B

A

C

D

E

F

1 2 3 4 5 6 87 9

F

E

D

C

B

A

97 8654321

BID DOCUMENTS

ATIONAL

EMETERY

DMINISTRATIONA

C N

Drawing Title

GENESEE COUNTY, NEW YORK

Project Title

Location

Date Checked Drawn

936PC2002

Drawing Number

Building Number

Project Number

Management

03-15-19 Dwg of

V

T

N

TI

D

STA

E

U

EN

T

OF

I

C

ES OF

R I

AM

E

R

A

S

S

ETERAN

AF

F A

Revisions:

VA FORM 08-6231, OCT 1978

CONSULTANTS:

Date

ARCHITECT/ENGINEER:

ATIONAL

EMETERY

DMINISTRATIONA

C N

WESTERN NEW YORK

NATIONAL CEMETERY

PHASE 1A DEVELOPMENT and Facilities

Office of Construction

LEO A DALY Company 2017

/2

/2

:1

:4

A

M C

U s e rs

\m js p e lle rb e rg

\D o c u m e n ts

\A u to d e s k \R e v it

P ro je c ts

\V A

C e m e te ry W

N Y

P

P -2 m js p e lle rb e rg

.r v t

P-901

ADMIN/PIC BLDG - PLUMBING RISER

DIAGRAMS

DJD BDB

ADMIN/PIC BLDG - PLUMBING RISER

DIAGRAMS

ADMIN/PIC BLDG WATER SUPPLY

3401,1001

ADMIN/PIC BLDG SANITARY

3/4"

2" 3/4"

3/4"WH-1

BFP-1

METER

P-401

P-501

P-601

P-302

P-302

P-102 P-302

P-102

P-202

P-801

P-801

2"

1/2"

1/2"

1/2" 1"

3/4"

2"

3/4"

1"

3/4"

2"

1"

3/4"

1"

3/4"1/2"

1/2"

1"

1 1/2"

2"

2"

1/2"

1/2"

1/2" 1/2"

3/4"

DWCP-3

FLOW CONTROL VALVING

SET AT 2 GPM

SEE 2D/P201

2" ISOLATION

VALVE

MASTER MIXING

VALVE (MMV-2)

1" 1"

2"2"

4"

4"

4"

2" 3"

4"

4"

3"

2"

1 1/2"

2"

1 1/4"

2"

4"

4"

1 1/2"

2"

2 1/2"3"

1 1/4"

1 1/4"1 1/4"

1 1/2"

1 1/2"

3"

4"4"

FD-A

P-102

P-401

P-501

P-601

FD-B

FD-A

FD-A

P-102

P-301

P-301

P-301

4" VENT

THRU ROOF

BUILDING

DOUBLE

CLEANOUT

CLEANOUT

B

A

C

D

E

F

1 2 3 4 5 6 87 9

F

E

D

C

B

A

97 8654321

BID DOCUMENTS

ATIONAL

EMETERY

DMINISTRATIONA

C

N

Drawing Title

GENESEE COUNTY, NEW YORK

Project Title

Location

Date Checked Drawn

936PC2002

Drawing Number

Building Number

Project Number

Management

03-15-19 Dwg of

V

T

N T I

D

STA

E

U

E

N T

OF

I

C

ES OF

R I

AM

E

R

A

S

S

ETERAN

AF

F A

Revisions:

VA FORM 08-6231, OCT 1978

CONSULTANTS:

Date

ARCHITECT/ENGINEER:

ATIONAL

EMETERY

DMINISTRATIONA

C

N

WESTERN NEW YORK

NATIONAL CEMETERY

PHASE 1A DEVELOPMENT and Facilities

Office of

Construction

LEO A DALY Company 2017

/2

/2

:5

:4

A

M C

U s e rs

\m js p e lle rb e rg

\D o c u m e n ts

\A u to d e s k \R e v it

P ro je c ts

\V A

C e m e te ry W

N Y

P

P -2 m js p e lle rb e rg

.r v t

P-904

HONOR GUARD BLDG - PLUMBING

RISER DIAGRAMS

DJD BDB

HONOR GUARD BLDG - PLUMBING

RISER DIAGRAMS

HONOR GUARD BLDG WATER SUPPLY 2

HONOR GUARD BLDG SANITARY

1 VE OPTION NO. 6

ADD ALTERNATE 1 ADD ALTERNATE 1

DUCT FURNACE

DF-D-1

(400 CFH)

WATER HEATER

WH-2

(199 CFH)

WATER HEATER

WH-2

(199 CFH)

BOILER

B-D-1

(190 CFH)

2"

2"

1 1/4"

1 1/4" 1 1/2"

1 1/4"

LPG TO TANK

988 CFH

(SEE DETAIL 2-P-201)

BOILER

B-A-1

(300 CFH)

WATER HEATER

WH-2

(199 CFH)

WATER HEATER

WH-2

(199 CFH)

GAS SHUT OFF

VALVE (TYP)

1 1/2"

1 1/2"

2"

1 1/2"

1 1/4"

LPG TO TANK

698 CFH

(SEE DETAIL 1-P-201)

3/4" PROPANE

TO AHU-C-1

(57 MBH)

1" TO WH-1

(150 MBH)

1" LPG CONT.

ON SITE PLAN

207 CFH

INV. ELEV. 854.90'

(SEE DETAIL 2-P-201)

1"

3/4"

1"

3/4" TO COMPRESSED

AIR OULTET WITH

QUICK CONNECT

3/4" COMPRESSED

AIR OULTET WITH

QUICK CONNECT

3/4" COMPRESSED

AIR OULTET WITH

QUICK CONNECT

3/4" COMPRESSED

AIR OULTET WITH

QUICK CONNECT

AIR COMPRESSOR

WITH DRYER

3/4" TO COMPRESSED AIR

HOSE REEL MOUNTED

BELOW CELING WITH QUICK

CONNECT HOSE AT 72" AFF

3/4" COMPRESSED AIR

FOR PRESSURE

WASHING SYSTEM

3/4"

1"

3/4"

3/4"

3/4"

3/4"

3/4"

1"

2"

1 1/2"

1 1/2"

1"

3/4"

3/4" 2"

3/4"

3/4" TO COMPRESSED AIR

HOSE REEL MOUNTED

BELOW CELING WITH QUICK

CONNECT HOSE AT 72" AFF

3/4" TO COMPRESSED AIR

HOSE REEL MOUNTED

BELOW CELING WITH QUICK

CONNECT HOSE AT 72" AFF

3/4" TO COMPRESSED AIR

HOSE REEL MOUNTED

BELOW CELING WITH QUICK

CONNECT HOSE AT 72" AFF

2"

B

A

C

D

E

F

1 2 3 4 5 6 87 9

F

E

D

C

B

A

97 8654321

BID DOCUMENTS

ATIONAL

EMETERY

DMINISTRATIONA

C

N

Drawing Title

GENESEE COUNTY, NEW YORK

Project Title

Location

Date Checked Drawn

936PC2002

Drawing Number

Building Number

Project Number

Management

03-15-19 Dwg of

V

T

N T I

D

STA

E

U

E

N T

OF

I

C

ES OF

R I

AM

E

R

A

S

S

ETERAN

AF

F A

Revisions:

VA FORM 08-6231, OCT 1978

CONSULTANTS:

Date

ARCHITECT/ENGINEER:

ATIONAL

EMETERY

DMINISTRATIONA

C

N

WESTERN NEW YORK

NATIONAL CEMETERY

PHASE 1A DEVELOPMENT and Facilities

Office of

Construction

LEO A DALY Company 2017

/2

/2

:5

:4

A

M C

U s e rs

\m js p e lle rb e rg

\D o c u m e n ts

\A u to d e s k \R e v it

P ro je c ts

\V A

C e m e te ry W

N Y

P

P -2 m js p e lle rb e rg

.r v t

P-905

PROPANE AND AIR COMPRESSOR

PIPING RISER DIAGRAMS

DJD BDB

PROPANE AND AIR COMPRESSOR

PIPING RISER DIAGRAMS

MAINTENANCE BLDG GAS

ADMIN/PIC BLDG GAS

HONOR GUARD BLDG GAS

MAINTENANCE BLDG AIR COMPRESSOR PIPING

1 VE OPTION NO. 6

ADD ALTERNATE 1

1. REFER TO ARCHITECTURAL REFLECTED CEILING PLANS FOR ALL

CEILING AIR DEVICE LOCATIONS.

2. REFER TO ARCHITECTURAL ELEVATION DRAWINGS FOR LOCATION

OF WALL MOUNTED MECHANICAL ITEMS.

3. LOCATE ALL DUCT BALANCING DAMPERS ABOVE ACCESSIBLE

CEILINGS. WHERE DAMPERS CANNOT BE INSTALLED ABOVE

ACCESSIBLE CEILINGS PROVIDE YOUNG OPERATOR WITH OPERATOR

LOCATED IN AN ACCESSIBLE LOCATION, OR PROVIDE ACCESS DOORS.

MINIMUM ACCESS DOOR SIZE SHALL BE 18x18 UNLESS OTHERWISE

APPROVED BY ENGINEER.

4. DUCTWORK NOT SIZED IS GENERALLY SMALLER BRANCH ZONE

DUCTS. COORDINATE ELEVATIONS AND PROVIDE NECESSARY

OFFSETS. DUCTWORK SHALL BE SIZED PER THE BRANCH

DUCTWORK SCHEDULE.

5. PROVIDE VOLUME DAMPERS AT ALL SUPPLY, RETURN AND EXHAUST

DUCT TAKE-OFFS. SEE DUCT CONSTRUCTION DETAILS.

6. BLANK-OFF AREAS OF LOUVERS NOT USED WITH 20 GAGE SHEET METAL

DOUBLE WALL BLANK-OFF PANEL INSULATED WITH 2" RIGID

FIBERBOARD. SEAL AIR TIGHT.

7. INSTALL RIGID 1/2"x1/2" GALVANIZED STEEL WIRE MESH AT ALL OPEN

ENDED DUCTS IN OCCUPIED AREAS OR EXPOSED TO VIEW.

8. ALL HWS AND HWR PIPING SERVING RADIATION SHALL BE

CONCEALED IN WALLS OR FINTUBE ENCLOSRES UNLESS

OTHERWISE NOTED.

9. COORDINATE INSTALLATION OF DUCTWORK AND PIPING WITH

BUILDING STRUCTURE, DUCTWORK, PIPING, ELECTRICAL CONDUIT,

LIGHTING, ETC.

10. INSTALL ALL FLOOR MOUNTED HVAC EQUIPMENT, INCLUDING AHUS,

PUMPS, ETC. ON 4" MINIMUM HEIGHT CONCRETE HOUSEKEEPING

PAD. EXTEND PAD MINIMUM 4" BEYOND EQUIPMENT AT ALL SIDES.

11. ALL HYDRONIC BRANCH PIPING SHALL BE 3/4" UNLESS NOTED

OTHERWISE.

12. PROVIDE POSITIVE DRAINAGE OF ALL PLENUMS CONNECTED TO

OUTSIDE LOUVERS. WATERPROOF BOTTOM OF PLENUMS. SLOPE

PLENUM BOTTOM TO LOUVER OR PROVIDE DRAIN POINTS WITH

DISCHARGE TO DRAIN.

13. THE MAINTENANCE - BUILDING 3001 STRUCTURE SUPPORTED

ATTACHMENTS OF PERMANENT EQUIPMENT AND NON-STRUCTURAL

COMPONENTS SHALL BE DESIGNED TO SEISMIC CATEGORY D

STANDARDS.

MECHANICAL ABBREVIATIONS

CD-2 CONSTRUCTION DOCUMENTS

(SUBMISSION2)

CENT CENTRIFUGAL

CFM CUBIC FEET PER MINUTE

CO CLEAN OUT

CO2 CARBON DIOXIDE

CU CONDENSING UNIT

CH CABINET UNIT HEATER

CV CONSTANT VOLUME

CW COLD WATER (POTABLE)

BAS BUILDING AUTOMATIC SYSTEM (DDC)

BDD BACKDRAFT DAMPER

BHP BRAKE HORSEPOWER

BTU BRITISH THERMAL UNIT

BTUH BRITISH THERMAL UNIT PER HOUR

A/E ARCHITECT / ENGINEER

AC AIR CONDITIONER

ACD AUTOMATIC CONTROL

DAMPER,MODULATING

ACD-TP AUTOMATIC CONTROL

DAMPER,TWO POSITION

AD ACCESS DOOR

AFF ABOVE FINISHED FLOOR

AFMD AIR FLOW MEASURING DEVICE

AHU AIR-HANDLING UNIT

AMP AMPERE

APD AIR PRESSURE DROP

ARI AIR CONDITIONING AND

REFRIGERATION INSTITUTE

AS AIR SEPARATOR

ASME AMERICAN SOCIETY OF MECHANICAL

ENGINEERS

C CENTIGRADE (CELCIUS)

CC COOLING COIL

CCD COOLING COIL CONDENSATE DRAIN

CD CEILING DIFFUSER

CD-1 CONSTRUCTION DOCUMENTS

(SUBMISSION1)

D DAMPER - AUTOMATIC

Db DECIBELS

DB DRY-BULB TEMPERATURE

DD-1 DESIGN DEVELOPMENT

(SUBMISSION1)

DD-2 DESIGN DEVELOPMENT

(SUBMISSION2)

DDC DIRECT DIGITAL CONTROLS

DEG DEGREE

DF DUCT FURNACE

DIA DIAMETER

DPS DIFFERENTIAL PRESSURE SENSOR

EA EXHAUST AIR

EAT ENTERING AIR TEMPERATURE

ECC ENGINEERING CONTROL CENTER

EF EXHAUST FAN

EG EXHAUST GRILLE

EJ EXPANSION JOINT

ENT ENTERING

ER EXHAUST REGISTER

ESP EXTERNAL STATIC PRESSURE

EWT ENTERING WATER TEMPERATURE

EX. EXISTING

F FAHRENHEIT

F&T FLOAT AND THERMOSTATIC

F/SDPR COMBINATION FIRE SMOKE DAMPER

FC FLEXIBLE CONNECTION

FCU FAN COIL UNIT

FD FLOOR DRAIN

FD FIRE DAMPER

FF FINAL FILTER

FM FLOW METER

FPM FEET PER MINUTE

FPS FEET PER SECOND

FR FLOOR REGISTER

FS FLOW SWITCH

FSTAT FREEZESTAT

GA GAUGE

GAL GALLONS

GPM GALLONS PER MINUTE

GS GALVANIZED STEEL

FT FEET

FT-LB FOOT-POUND

FV FACE VELOCITY

H HUMIDIFER

HAC HOUSEKEEPING AID CLOSET

HD HEAD

HOA HAND/OFF/AUTOMATIC

HP HORSEPOWER

HSTAT HUMIDISTAT

HTM HUMIDIFIER TERMINAL

HVU HEATING AND VENTILATING UNIT

HW HOT WATER

HWP HEATING HOT WATER PUMP

HWR HEATING HOT WATER RETURN

HWS HEATING HOT WATER SUPPLY

HX HEAT EXCHANGER

HZ HERTZ

MAX MAXIMUM

MBH 1000 BTUH

MCA MINIMUM BRANCH CIRCUIT AMPACITY

MER MECHANICAL EQUIPMENT ROOM

MERV MINIMUM EFFICIENCY REPORTING VALUE

MHP MOTOR HORSEPOWER

MIN MINIMUM

LAT LEAVING AIR TEMPERATURE

LF LINEAR FOOT (FEET)

LSD LINEAR SLOT DIFFUSER

LVG LEAVING

LVR LOUVER

LWT LEAVING WATER TEMPERATURE

kW KILOWATT kWh KILOWATT HOUR

I/O INPUT/OUTPUT

IAQ INDOOR AIR QUALITY

ICF IN-LINE CENTRIFUGAL FAN

ID INSIDE DIAMETER

IN INCHES

IN HG INCHES OF MERCURY

IN WC INCH WATER COLUMN

IN WG INCH WATER GAUGE

IN-LB INCH-POUND

OA OUTSIDE AIR

OAI OUTSIDE AIR INTAKE

OD OUTSIDE DIAMETER

NA NOT APPLICABLE

NC NOISE CRITERIA

NC NORMALLY CLOSED

NO NORMALLY OPEN

NPLV NON-STANDARD PART LOAD VALUE

NPSH NET POSITIVE SUCTION HEAD

NTS NOT TO SCALE

RA RETURN AIR

RDS ROOM DATA SHEETS

REA RELIEF AIR

RET COMMON RETURN WATER

RG RETURN GRILLE

RH RELATIVE HUMIDITY

RHC REHEAT COIL

RPM REVOLUTIONS PER MINUTE

RR RETURN REGISTER

RV RELIEF VALVE

P PUMP

PCF POUNDS PER CUBIC FOOT (FEET)

PD PRESSURE DROP

PF PRE-FILTER

PG PRESSURE GAGE

PHC PREHEAT COIL

PPM PARTS PER MILLION

PRS PRESSURE REGULATING (VALVE) STATION

PRV PRESSURE REGULATING VALVE

PSI POUNDS PER SQUARE INCH

PSIA POUNDS PER SQUARE INCH ?ABSOLUTE

PSIG POUNDS PER SQUARE INCH ?GAGE

PSV PRESSURE SAFETY VALVE

T & PCV TEMPERATURE AND PRESSURE

CONTROL VALVE

TAB TESTING, ADJUSTING, BALANCE

TD TEMPERATURE DIFFERENCE

TSP TOTAL STATIC PRESSURE

TSTAT THERMOSTAT

TU TERMINAL UNIT

SA SUPPLY AIR

SAD SOUND ATTENUATING DEVICE

SAT SUPPLY AIR TEMPERATURE

SCFM STANDARD CUBIC FEET PER MINUTE

SD SMOKE DETECTOR

SAD SUPPLY AIR DIFFUSER

SDPR SMOKE DAMPER

SEN SENSIBLE HEAT

SF SUPPLY FAN

SG SUPPLY AIR GRILLE

SP STATIC PRESSURE

SP GR SPECIFIC GRAVITY

SPS STATIC PRESSURE SENSOR

SQ FT SQUARE FOOT (FEET)

SR SUPPLY AIR REGISTER

SS STAINLESS STEEL

YR YEAR

W WATTS

Wb WET-BULB (TEMPERATURE)

WG WATER GAGE

WPD WATER SIDE PRESSURE DROP

V VALVE

VAV VARIABLE AIR VOLUME

VD VOLUME DAMPER (MANUAL OPPOSED BLADE)

VFD VARIABLE FREQUENCY DRIVE

VA VETERANS ADMINISTRATION

VI VIBRATION ISOLATOR

VSD VARIABLE SPEED DRIVE

UL UNDERWRITERS LABORATORY

DPR DAMPER

SAE SOUND ATTENUATOR - EXHAUST

SAS SOUND ATTENUATOR - SUPPLY

B BOILER

DH DUCT HEATER

ERV ENERGY RECOVERY VENTILATOR

ET EXPANSION TANK

HC HEATING COIL

IDU INDOOR UNIT (VRF)

ODU OUTDOOR UNIT (VRF)

UH UNIT HEATER

VRF VARIABLE REFRIGERANT FLOW

BMS BUILDING MANAGEMENT SYSTEM

PIPING SYMBOLS VALVE SYMBOLS CONTROLS SYMBOLS

DRAWING SYMBOLS DUCTWORK SYMBOLS

M

1-MH101

1-MH101

GATE VALVE WITH GLOBE-VALVED BYPASS

PLUG VALVE

CONTROL VALVE (CV) - FLOAT-OPERATED

PRESSURE REDUCING VALVE (PRV)

HOSE CONNECTOR

WYE STRAINER WITH VALVED DRAIN AND QUICK-COUPLE

FLOW METER

IDU-C-I

DETAIL NUMBER

DRAWING NUMBER WHERE SHOWN

SECTION LETTER

ITEM NUMBER (UNIT NO. 1)

EQUIPMENT ABBREVIATION

(INDOOR UNIT SHOWN)

BUILDING DESIGNATION

A - ADMIN/PC

C - HONOR GUARD

D - MAINTENANCE

DRAWING NUMBER WHERE DRAWN

(WALL TYPE)

(WALL TYPE)

DN

DN

UP

UP

SUPPLY DUCT (UP & DOWN)

EXHAUST DUCT (UP & DOWN)

SQUARE 4-WAY CEILING DIFFUSERS

SUPPLY TOP REGISTER OR GRILLE (WALL TYPE)

EXHAUST OR RETURN CEILING REGISTER OR GRILLE

EXHAUST OR RETURN BOTTOM REGISTER OR GRILLE

EXHAUST OR RETURN REGISTER OR TOP GRILLE

VANED ELBOW & AIR SPLIT TYPE DUCT TAKE-OFF

D

INCLINED RISE, IN DIRECTION OF AIR FLOW

INCLINED DROP, IN DIRECTION OF AIR FLOW

R

DNUP RETURN DUCT (UP & DOWN)

LINEAR SLOT DIFFUSER

FC

10x8

FLEXIBLE CONNECTION, EQUIPMENT,

VANED ELBOW (PROVIDE ALL SQUARE OR

RECTANGULAR ELBOWS WITH VANES EVEN IF

SYMBOL IS MISSING)

STANDARD RADIUS ELBOW (LONG RADIUS)

NEW DUCT (INSIDE DIMENSIONS: WIDTH x DEPTH)

COMBINATION SMOKE/FIRE DAMPER

F/S DPR

VIBRATION, OR SEISMIC

DUCT MOUNTED COIL (HOT WATER OR STEAM COIL)

SUPPLY

RETURN45°

RETURN, NO SPLITTER (45° TAP)

STANDARD BRANCH SUPPLY OR

MANUAL SPLITTER DAMPER

45°

2 1

POINT OF CHANGE IN DUCT CONSTRUCTION BY

STATIC PRESSURE CLASS. THE NUMBER ASSIGNS

PRESSURE CLASS (IN. OF WATER) WHICH WILL

ACCOMMODATE MAXIMUM OPERATING PRESSURE 1/24

IN THE DUCT SUBSECTION. THE SYMBOL CONTINUES

THE ASSIGNMENT UNTIL THE DUCT TERMINATES OR

ANOTHER SYMBOL APPEARS. A "N" SUPERSCRIPT

INDICATES NEGATIVE PRESSURE.

AUTOMATIC CONTROL DAMPER MODULATING

AUTOMATIC CONTROL DAMPER TWO POSITION

CONVECTOR OR RADIATOR (RECESSED)

CONVECTOR OR RADIATOR (WALL HUNG)

HEATING HOT WATER RETURN

HEATING HOT WATER SUPPLYHWS

HWR

ANCHOR

REDUCER OR INCREASER

DIRECTION OF FLOW

SIDE CONNECTION

ECCENTRIC REDUCER

BOTTOM CONNECTION, 45° OR 90°

TOP CONNECTION, 45° OR 90°

UNION

RISE OR DROP IN PIPE

CAPPED OUTLET

PRESSURE GAGE

THERMOMETER

FLOW ELEMENTFE

PIPE UP

PIPE DOWN

TEST PLUG (PRESSURE/TEMPERATURE)

AUTOMATIC AIR VENT

AV

MANUAL AIR VENT

MV

BALL VALVE

GATE VALVE WITH 3/4" HOSE ADAPTER

CHECK VALVE

ANGLE GLOBE VALVE

MODULATING CONTROL VALVE

TWO POSITION CONTROL VALVE

THREE-WAY MODULATING CONTROL VALVE

AUTOMATIC BALANCING CONTROL VALVE

PRESSURE SAFETY VALVE

GATE VALVE - THREADED/FLANGED

GLOBE VALVE - THREADED/FLANGED

PRESSURE REGULATING VALVE

THREE-WAY TWO POSITION CONTROL VALVE

WYE STRAINER (WITH BALL VALVE & HOSE CONNECTION)

FLEXIBLE CONNECTION

WATER BALANCE DEVICE

MODULATING CONTROL BUTTERFLY VALVE

CIRCUIT SETTER VALVE

T ROOM TEMPERATURE SENSOR/TRANSMITTER - WALL MOUNT

TT TEMPERATURE TRANSMITTER

M ROOM HUMIDISTAT (MOISTURE)/TRANSMITTER - WALL MOUNT

MT MOISTURE (HUMIDITY) TRANSMITTER

PT PRESSURE TRANSMITTER

TT TEMPERATURE TRANSMITTER, AVERAGING ELEMENT

FT FLOW TRANSMITTER

IT CURRENT TRANSMITTER

SPS STATIC PRESSURE SENSOR

SD SMOKE DETECTOR

PDT PRESSURE DIFFERENTIAL TRANSMITTER

TSL TEMPERATURE SWITCH, LOW (FREEZESTAT)

HS HAND SWITCH (HAND-OFF-AUTO SWITCH)

ZC VALVE OR DAMPER POSITION CONTROLLER

PDS PRESSURE DIFFERENTIAL SWITCH

TSH TEMPERATURE SWITCH, HIGH

LTCP LOCAL TEMPERATURE CONTROL PANEL

HVAC HVAC CONTROL PANEL

ECC INTEGRATE CONTROL POINT ON REMOTE GRAPHICS

WORKSTATION AT ENERGY CONTROL CENTER

TC

TEMPERATURE CONTROLLER. SEE SEQUENCE OF

OPERATION

VSMC VARIABLE SPEED MOTOR CONTROLLER

M ELECTRIC OPERATED CONTROL DAMPER/OR VALVE

AFS AIR FLOW SWITCH

PC ATU/ CONTROLLER

TE THERMOSTAT/TEMPERATURE SENSOR

FE FLOW ELEMENT

CS CURRENT SENSOR

SST START STOP

ALM ALARM

STA STATUS

LENGTH IN DUCT WHEN SPACE PERMITS.)

A

TEMPERATURE SENSING ELEMENT FOR

TRANSMITTING TEMPERATURE TO EMCS

(PROVIDE 12 INCHES MINIMUM

SENSOR WITH AVERAGING ELEMENT TO TRANSMIT

TEMPERATURE TO EMCS

MOTOR STARTER

VD

MANUAL VOLUME DAMPER

FIRE DAMPER

FD

M0101

SECTION INDICATOR TOP INDICATES

SECTION NUMBER BOTTOM

INDICATES SHEET NUMBER

200-5

200-2

SUPPLY AIR DEVICE -

(REFER TO SCHEDULE FOR SIZE)

FIRST NO. CFM, SECOND NO. TYPE

(REFER TO SPECIFICATION FOR AIR DEVICE TYPE)

LINEAR DIFFUSER

200-14 10x8

SUPPLY/ RETURN/EXHAUST SIDEWALL GRILLE-

FIRST NO. CFM, SECOND NO. TYPE

BOTTOM NO. WIDTH BY HEIGHT OF GRILLE

(REFER TO SPECIFICATION FOR AIR DEVICE TYPE)

RETURN AIR DEVICE -

(REFER TO SCHEDULE FOR SIZE)

FIRST NO. CFM, SECOND NO. TYPE

(REFER TO SPECIFICATION FOR AIR DEVICE TYPE)

EXHAUST AIR DEVICE -

(REFER TO SCHEDULE FOR SIZE)

FIRST NO. CFM, SECOND NO. TYPE

(REFER TO SPECIFICATION FOR AIR DEVICE TYPE)

CALLOUT INDICATOR TOP INDICATES

NUMBER ON THE SHEET BOTTOM

INDICATES SHEET NUMBER

M0101

200-5

250-7

CFM

TYPE

LENGTH

NO. OF SLOTS

SLOT WIDTH (INCHES)

4LF-2-1

B

A

C

D

E

F

1 2 3 4 5 6 87 9

F

E

D

C

B

A

97 8654321

BID DOCUMENTS

ATIONAL

EMETERY

DMINISTRATIONA

C

N

Drawing Title

GENESEE COUNTY, NEW YORK

Project Title

Location

Date Checked Drawn

936PC2002

Drawing Number

Building Number

Project Number

Management

03-15-19 Dwg of

V

T

N T I

D

STA

E

U

E

N T

OF

I

C

ES OF

R I

AM

E

R

A

S

S

ETERAN

AF

F A

Revisions:

VA FORM 08-6231, OCT 1978

CONSULTANTS:

Date

ARCHITECT/ENGINEER:

ATIONAL

EMETERY

DMINISTRATIONA

C

N

WESTERN NEW YORK

NATIONAL CEMETERY

PHASE 1A DEVELOPMENT and Facilities

Office of

Construction

LEO A DALY Company 2017

/2

/2

:1

:5 P

M C

U s e rs

\m js p e lle rb e rg

\D o c u m e n ts

\A u to d e s k \R e v it

P ro je c ts

\V A

C e m e te ry W

N Y

M

H -2 m js p e lle rb e rg

.r v t

M-001

SYMBOLS, ABBREVIATIONS AND

GENERAL NOTES

DJD MJB

SYMBOLS, ABBREVIATIONS AND

GENERAL NOTES

GENERAL NOTES

1001, 3001, 3401

VD

V D

VD

VD

VD

V D

VD

V D

VD VD

VD

V D V D

VD

VD

V D

V D

V D

V D

V D

VD

VD

V D

VD

VD

VD

VD

V D

1A

MH101

ELECTRICAL

A-118

ASST. DIRECTOR

A-115

DIRECTOR

A-111

OPEN OFFICE

A-105

SECURE STORAGE

A-127

C O

R R

ID

O

R

A -1

OPERATIONAL CENTER

A-109

MULTI-PURPOSE

A-108

MEN'S

A-113

WOMEN'S

A-112

CORRIDOR

A-110

PASSAGE

A-114LUNCH ROOM

A-120

DATA / I.T.

A-117

MECHANICAL

A-119

IN

F

O R

M A

T

IO

N

A -1

RECYCLE

A-104

RECEPTION

A-124

GRAVE LOC. CL.

A-125

LOBBY

A-100

FAMILY RESTROOM

A-102

HAC

A-121

MEN'S

A-101

WOMEN'S

A-103IDU-A-8

IDU-A-9

IDU-A-7

IDU-A-5

IDU-A-4

IDU-A-3

IDU-A-1

ERV-A-1

EXHAUST

AIR

OUTSIDE

AIR

VRF INDOOR UNIT

LOCATE IN

CEILING SPACE

(TYP)

GEN. STORAGE

A-116

MH301

VESTIBULE

A-126

VESTIBULE

A-122

ALCOVE

A-130

LOCKERS

A-128

ROUTE DUCT IN

2 HR ENCLOSURE

AT HIGH LEVEL IN

ELECTRICAL

ROOM

IDU-A-6

IDU-A-2

305-4

370-5

305-4

350-5

75-14

100-15 70-15

180-4

180-4

165-4

225-5230-5

75-5

SEATING

A-106

160-4

315-5

345-4

340-4

COMBINATION

COMBUSTION

AIR AND FLUE

75-5

240-4

315-4

255-5

75-5

275-4

275-5

285-4 280-4

285-5

280-5 75-5

75-5

150-2

165-2

HC-A-2

AC-A-1

FD FD

75-5

175-14 12x6

150-15 12x6

80-5

315-5

60-5

BLANK OFF

UNUSED PORTION

OF LOUVER (TYP)

ERV-A-2

14/8 OA 16/8 SA

12/8 EA

FILTER

BOX (TYP)

10/8 RA

14/8 OA

18/8 SA 16/8 SA

12/10 SA

14ø EA

14/10 RA

16/8 SA

16/8 SA

14ø OA

14ø EA

16/8 SA

10/10

10/10

315-5

10/8 RA

16/8 RA8/6 SA

10ø EA

14/6 SA

14/6 SA

8ø SA

8/4 OA

6ø EA

10/8 EA

14/6 SA

6ø EA

8ø SA

14/6 SA

12/6 SA

6ø EA

8/6 OA

8/4 RA

12/6 RA

8ø SA

8ø SA

10/8 RA

8/6 EA 8/6 OA

14/10 SA

6ø SA

6ø EA

10/8 OA

8ø EA

10/8 EA

6ø EA

10/8 OA

8/6 OA (TYP)

240-5

75-4

8/6 SA

8/8 SA

10/6 RA

(TYP)

(TYP)

8/6 SA

8/6 EA

16/8 RA

16/8 SA

380-5

(BELOW)

14/10 OA

685-16

(BELOW)

FD

6 5

8 3 4

12ø SA

A.A

B.A

C.A

4.A3.A2.A1.A

D.A

14/6 SA

8x6

12/12

RA

12/6 RA

18/12 OA18"x12" OUTSIDE AIR LOUVER

(SEE ARCHITECTURAL)

ODU-A-2

18/12 EA

18"X12" EXHAUST LOUVER

(SEE ARCHITECTURAL) 36/16 OA

36/16 EA

ODU-A-1

FD

FD

FD

FD

FD

FD

FD

PORCH

C-100

MECHANICAL

C-104

STORAGE

C-103

HONOR GUARD

C-101

WOMEN'S

C-105

L O

C K

E R

C -1

MEN'S

C-106

VAULT

C-108

CLOSET

C-1078

MH301

250-4

305-5

305-5

75-4

95-15

EF-C-1

175-15

16"X16" EXHAUST

AIR LOUVER (SEE

ARCHITECTURAL)

50-15 10x6

50-2

70-2

70-15

14/10 RA

14/10 SA

18/10 SA

14/10 RA

MH301

MH301

250-4

255-4

12/6 RA

10ø SA10ø SA

8/6 EA

12/6 EA

8/8 SA

8/6 EA

12/10 SA

10ø SA

12/8 RA

12/6 RA

6ø SA

8/6 RA

50-4

1.C D.B D.G 4.C

E.C

D.C

16/16 EA

FD

(TYP.)

VEHICLE - EQUIP

STORAGE

D-122

WASH BAY

D-123

MECHANICAL

D-120

WORK AREA

D-119

TELECOM

D-113

PARTS & TOOL

STORAGE

D-112

CORRIDOR

D-127

BOOT HOLDING / WASH

D-109

MULTI-PURPOSE ROOM

D-106

W O

M E

N 'S

D -1

FOREMAN

D-105

STORAGE RM

D-115

CARETAKER

WORKSTATIONS

D-102

ERV-D-2

IDU-D-1

IDU-D-2

IDU-D-4

IDU-D-5

STAINLESS STEEL

12 INCHES AFF

(TYP OF 4)

VEHICLE - EQUIP

D-121 ALCOVE

D-128

E L E

C T

R

IC

A L

D -1

LOCKER RM

D-118

CORRIDOR

D-126

CORRIDOR

D-101

COTR OFFICE

D-103

295-4 290-4 295-4

290-4

385-5 380-5 380-5

75-4

205-4

HC-D-1

125-4

215-5

215-5

130-4

150-2

165-5

65-2

200-4

50-5

155-5 185-4

225-5

265-4

215-5

65-15

ALCOVE

D-125

375-14 14x8

330-15 14x8

MH301

H.A.C.

D-104

MEN'S

D-117

2A

MH101

16/8 SA16/10 SA

18/12 SA

1500-8 18x30

MH301

12/8 SA

18/10 EA 16/10 EA

18/10 EA

16/12 OA

10/10 SA

10ø SA

10ø RA

18/12 OA

12/12 SA

10/10 RA

16/10 OA

14/6 SA

AC-D-1

10ø SA

6ø SA 10ø SA

10ø SA

10ø SA10ø SA

10ø SA

8ø SA

14/6 SA

25/10 RA

10ø EA

8ø EA

8/6 EA

12/8 SA

8/6 SA

12/6 EA

12/8 EA

36/10 RA

8/6 OA

12/8 RA

12/10 RA

16/12 OA

8ø OA

10ø OA

6ø OA

8ø OA

/8

O A

8/6 EA

8/6 EA

8/6 EA

65-15

70-15

12/10 SA

48/14 RA

IDU-D-3

14/12 RA

(TYP)

165-7

280-4

14/6 SA

8ø SA

12/6 SA

900-14 16x10

UP

12/12 EA

900-15 12x12

1.D 2.D 3.D 4.D 5.D 6.D 7.D 9.D 11.D 14.D 16.D

H.D

I.D

G.D

F.D

D.D

B.D

A.D

14/10 RA

FD

FD

FD

FD

50-2

FD

6ø SA

FD

156"X26" OUTSIDE

AIR INTAKE

LOUVER

(SEE

ARCHITECTURAL)

24x10 STAINLESS

STEEL RA RISER

DOWN (TYP OF 4)

MECHANICAL

D-202

WASH BAY

D-123

VEHICLE - EQUIP

STORAGE

D-122

VEHICLE - EQUIP

D-121

SD

SD

MH301

120"X30" EXHAUST AIR

LOUVER (DISCHARGE

OUT THE SIDE AT HIGH

LEVEL)

18/10 EA

22/16 SA

26/16 EA

30/26 OA

/1

E

A

26/26 SA26/22 SA22/22 SA18/16 SA

/1

E

A

600-14 12x10

(TYP OF 10)

156"x26"x36"

DEEP INSULATED

INTAKE PLENUM

18/12 OA

30/26 EA

24/10 EA

6000-8 60x24

60/24 RA

26/30 OA

12/12 EA

EF-D-3

12/12 EA

DOWN

1.D 2.D 3.D 4.D 5.D 6.D 7.D

G.D

F.D

D.D

B.D

A.D

FD

FD FD

FD

ERV-A-2

IDU-A-3

IDU-A-6

OPERATIONAL CENTER

A-109

CORRIDOR

A-110

GEN. STORAGE

A-116

D.A

315-460-5

6ø EA

6/8 OA

8/12 EA

IDU-A-7

315-5

16/8 RA

75-575-5

10/8 EA

36/10 RA

MEZZ LEVEL

10' - 0"

ERV-D-2

IDU-D-1

LOCKER RM

D-118

H.A.C.

D-104

CORRIDOR

D-127

BOOT HOLDING / WASH

D-109

H.D

65-15

65-15 75-4

70-15

75-5

10/18 EA

10/14 RA

HC-D-1

16/10 EA

6/8 SA

B

A

C

D

E

F

1 2 3 4 5 6 87 9

F

E

D

C

B

A

97 8654321

BID DOCUMENTS

ATIONAL

EMETERY

DMINISTRATIONA

C

N

Drawing Title

GENESEE COUNTY, NEW YORK

Project Title

Location

Date Checked Drawn

936PC2002

Drawing Number

Building Number

Project Number

Management

03-15-19 Dwg of

V

T

N T I

D

STA

E

U

E

N T

OF

I

C

ES OF

R I

AM

E

R

A

S

S

ETERAN

AF

F A

Revisions:

VA FORM 08-6231, OCT 1978

CONSULTANTS:

Date

ARCHITECT/ENGINEER:

ATIONAL

EMETERY

DMINISTRATIONA

C

N

WESTERN NEW YORK

NATIONAL CEMETERY

PHASE 1A DEVELOPMENT and Facilities

Office of

Construction

LEO A DALY Company 2017

/2

/2

:1

:0 P

M C

U s e rs

\m js p e lle rb e rg

\D o c u m e n ts

\A u to d e s k \R e v it

P ro je c ts

\V A

C e m e te ry W

N Y

M

H -2 m js p e lle rb e rg

.r v t

MH101

LEVEL ONE - HVAC DUCTWORK

PLANS

DJD MJB

LEVEL ONE - HVAC DUCTWORK

PLANS

1/8" = 1'-0"

ADMIN/PIC - BUILDING 1001

1/8" = 1'-0"

HONOR GUARD - BUILDING 3401

1/8" = 1'-0"

MAINTENANCE - BUILDING 3001 - GROUND FLOOR PLAN

1/8" = 1'-0"

MAINTENANCE - BUILDING 3001 - MEZZANINE PLAN

1001, 3001, 3401

1/8" = 1'-0" 1A

ADMIN/PIC - BUILDING 1001 - DUCTWORK SECTION

1/8" = 1'-0" 2A

MAINTENANCE - BUILDING 3001 - DUCTWORK SECTION

KEYED NOTES:

14x10 VOLUME DAMPER, BALANCE OUTSIDE AIR TO 685 CFM.

16x8 VOLUME DAMPER, BALANCE OUTSIDE AIR TO 305 CFM.

8x6 VOLUME DAMPER, BALANCE OUTSIDE AIR TO 90 CFM.

8x6 VOLUME DAMPER, BALANCE OUTSIDE AIR TO 105 CFM.

8x6 VOLUME DAMPER, BALANCE OUTSIDE AIR TO 45 CFM.

8x6 VOLUME DAMPER, BALANCE OUTSIDE AIR TO 25 CFM.

8x6 VOLUME DAMPER, BALANCE OUTSIDE AIR TO 85 CFM.

8x6 VOLUME DAMPER, BALANCE OUTSIDE AIR TO 45 CFM.

8x6 VOLUME DAMPER, BALANCE OUTSIDE AIR TO 40 CFM.

14/8 OA ABOVE AND 14/8 EA BELOW.

INSTALL SIDEWALL BAR GRILLE 12" ABOVE ALCOVE CEILING. SIDEWALL

GRILLE SHALL BE 9LF LONG, TYPE-16, AND BALANCE TO 685 CFM.

AIRFLOW MEASURING STATION.

8X6 VOLUME DAMPER, BALANCE OUTSIDE AIR TO 45 CFM.

16x8 VOLUME DAMPER, BALANCE OUTSIDE AIR TO 685 CFM.

8"Ø VOLUME DAMPER, BALANCE OUTSIDE AIR TO 230 CFM.

6"Ø VOLUME DAMPER, BALANCE OUTSIDE AIR TO 50 CFM.

6"Ø VOLUME DAMPER, BALANCE OUTSIDE AIR TO 70 CFM.

GRILLE TYPE -5. BALANCE TO 75 CFM.

DUCTWORK CONTINUED ON 4/MH301.

PROVIDE VOLUME DAMPER AT 6'-0" AFF.

AIR TRANSFER DUCT AND GRILLES. GRILLE TYPE SHALL BE TYPE-5

WITH 10" NECK ON EACH SIDE OF WALL.

KEYED NOTES:

12/12 EA DN TO EF-D-3 ON STEEL FRAMED STAND 30" A.F.F.

KEYED NOTES:

GENERAL NOTES:

BALANCE RETURN AIR DAMPERS TO AIRFLOWS SHOWN AT GRILLES.

GENERAL NOTES:

BALANCE RETURN AIR DAMPERS TO AIRFLOWS SHOWN AT GRILLES.

N.I.C.

N.I.C.

T

MH301

MH301

COMBINATION

COMBUSTION AIR

AND FLUE

ERV-D-1

14x12 OA INTAKE

LOUVER

275-15 10x6

EF-D-4

EF-D-2

10/6 EA

10/6 EA

MECHANICAL

D-202

120"X30" EXHAUST AIR

LOUVER (DISCHARGE

OUT THE SIDE AT HIGH

LEVEL)

EF-D-1

FD

26/26 SA

FD

10/6 EA

CONCENTRIC

ADAPTER

INSULATED EXHAUST

PLENUMVFD FOR EF-D-1

VFD FOR AHU-D-1

26/30 EA

AHU-D-1

30/26 OA

(BELOW)

18/10 EA 12/12 EA

34/26 EA

6.D 7.D

G.D

M

M

LEVEL 01

100'-0"

MEZZANINE

110'-0"

MH301

COMBINED

COMBUSTION

AIR AND FLUE

EF-D-4

10/18 EA

10/6 EA

10/6 EA

B-D-1

FD

FD

EF-D-1

MECHANICAL

D-202

MECHANICAL

D-120

26/26 SA

FD

12/12 EA

G.D

3"Ø COMBUSTION

AIR AND VENT

AHU-D-1

6"Ø

COMBUSTION

AIR AND VENT

LEVEL 01

100'-0"

MEZZANINE

110'-0"

MH301

6.D 7.D

ERV-D-1

MECHANICAL

D-202

MECHANICAL

D-120

EXHAUST AIR LOUVER

(DISCHARGE OUT THE

SIDE AT HIGH LEVEL)

6"Ø COMBINATION

COMBUSTION AIR

AND VENT

EF-D-4275-15

10x6

250-7 10x6

18/42 SA

6/10 EA

EF-D-2

EF-D-1OA

EA

24" SERVICE CLEARANCE

30/26 EA

INSULATED EXHAUST

PLENUM

6/10 EA

B-D-1

COMBINATION

COMBUSTION AIR

AND VENT

FD

AHU-D-1

10/16 OA

26/26 SA

14/64 EA

6.D 7.D

3"Ø

COMBUSTION AIR

AND VENT

FD

MECHANICAL

A-119

B-A-1 75-15 8x670-14

8x6

COMBINED

COMBUSTION

AIR AND VENT

MH301

3"Ø BOILER

COMBUSTION

AND VENT

FD

(TYP.)

LEVEL 02

111'-0"

MEZZANINE

110'-0"

B-A-1

75-15 8x6

70-14 8x6

MECHANICAL

A-119

3"Ø BOILER

COMBUSTION

AIR AND VENT

1.C

D.C

MH301

16x16 OUTSIDE AIR INTAKE LOUVER

AND INSULATED PLENUM

AHU-C-1

MECHANICAL

C-104

MH301

10/8 OA

18/10 SA

1.C

D.C

LEVEL 01

100'-0"

AHU-C-1

/1

S

A

8/10 OA

/1

R

A /1

R

A

MH301

16x16 OUTSIDE AIR

INTAKE LOUVER

AND INSULATED

PLENUM

MECHANICAL

C-104

1.C

LEVEL 01

100'-0"

MH301

/1

S

A

/1

R

A

8/10 OA

14/10 RA

AHU-C-1

MECHANICAL

C-104

MP301

D.C

MH301

MH301

16/10 OA

10/6 EA

250-7 10x6

FD

B-D-1

EA UP WITH

FD AT SLAB

COMBINED BOILER

AIR INTAKE AND

VENT.

36x12 OA INTAKE

LOUVER

MECHANICAL

D-120

16/10 OA

14/12 OA

6.D 7.D

G.D

3"Ø BOILER

COMBUSTION

AIR AND VENT

MM

B

A

C

D

E

F

1 2 3 4 5 6 87 9

F

E

D

C

B

A

97 8654321

BID DOCUMENTS

ATIONAL

EMETERY

DMINISTRATIONA

C

N

Drawing Title

GENESEE COUNTY, NEW YORK

Project Title

Location

Date Checked Drawn

936PC2002

Drawing Number

Building Number

Project Number

Management

03-15-19 Dwg of

V

T

N T I

D

STA

E

U

E

N T

OF

I

C

ES OF

R I

AM

E

R

A

S

S

ETERAN

AF

F A

Revisions:

VA FORM 08-6231, OCT 1978

CONSULTANTS:

Date

ARCHITECT/ENGINEER:

ATIONAL

EMETERY

DMINISTRATIONA

C

N

WESTERN NEW YORK

NATIONAL CEMETERY

PHASE 1A DEVELOPMENT and Facilities

Office of

Construction

LEO A DALY Company 2017

/2

/2

:1

:1 P

M C

U s e rs

\m js p e lle rb e rg

\D o c u m e n ts

\A u to d e s k \R e v it

P ro je c ts

\V A

C e m e te ry W

N Y

M

H -2 m js p e lle rb e rg

.r v t

MH301

ENLARGED DUCTWORK PLANS AND

SECTIONS

DJD MJB

ENLARGED DUCTWORK PLANS AND

SECTIONS

1/4" = 1'-0"

MAINTENANCE - BUILDING 3001 - MECHANICAL ROOM D-202 - PLAN

1/4" = 1'-0"

MAINTENANCE - BUILDING 3001 - MECHANICAL ROOMS

D-120/D-202 - SECTION

1/4" = 1'-0"

MAINTENANCE - BUILDING 3001 - MECHANICAL ROOMS

D-120/D-202 - SECTION

1/4" = 1'-0"

ADMIN/PIC - BUILDING 1001 - MECHANICAL ROOM A-119 - PLAN

1/4" = 1'-0"

ADMIN/PIC - BUILDING 1001 - MECHANICAL ROOM A-119 - SECTION

1/4" = 1'-0"

HONOR GUARD - BUILDING 3401 - MECHANICAL ROOM C-104 -

PLAN

1/4" = 1'-0"

HONOR GUARD - BUILDING 3401 - MECHANICAL ROOM C-104 -

SECTION

1/4" = 1'-0"

HONOR GUARD - BUILDING 3401 - MECHANICAL ROOM C-104 -

SECTION

1. LOCATE UNIT ON 4" CONCRETE PAD.

NOTES:

1001, 3001, 3401

1/4" = 1'-0"

MAINTENANCE - BUILDING 3001 - MECHANICAL ROOM D-102 - PLAN

ADD ALTERNATE 1 ADD ALTERNATE 1 ADD ALTERNATE 1

N.I.C.

N.I.C.

DISTANCE = NECK

SIZE (8" TYP.)

AIR

FLOW

BRANCH

DUCT

METAL OR PLASTIC

SECURING BAND

FLEX (NO BENDS GREATER THAN 45°)

(MAX 4'-0")

OPPOSED BLADE DAMPER(WHERE

SCHEDULED)CEILING

DIFFUSER OR

REGISTER

AIR

FLOW

METAL OR PLASTIC

SECURING BAND (TYP)

CEILING

DIFFUSER OR

REGISTER

RIGID METAL ELBOW,

SECURED AND SEALED TO

DIFFUSER

FLEX

(MAX. 4'-0")

* ENSURE ADEQUATE

ACCESS FOR

MAINTENANCE

FLEX HOSE (TYP.)

CONDENSATE DRAIN TRAP

ACCESS

(VARIES)

1" PLEATED FILTER, 2" MERV

8 FILTER: CAMFIL 30/30

(VERTICAL UNITS) OR

EQUIVALENT (SEE CHART)

SIDE/BOTTOM

FILTER ACCESS

FAN, MOTOR

ACCESS

(VARIES)*

CEILING

VRF UNIT

SECTION "A"

RETURN

"A"

VRF UNIT

SUPPLY

"A"

PLAN VIEW

V A

R

IE

S

CFM FILTER SIZE

NOTES:

1. PROVIDE UNIT DUCT CONFIGURATIONS AS INDICATED ON

THE FLOOR PLANS.

2. PROVIDE CONCRETE HOUSEKEEPING PADS FOR ALL

VERTICAL UNITS.

3. PROVIDE 1" FLEXIBLE DUCTWORK CONNECTION.

0-475 20x14

476-1000 24x20

1001-1200 24x24

1201-1920 40x24

ACOUSTICALLY LINED DUCT

(AS APPLICABLE)

B

A

C

D

E

F

1 2 3 4 5 6 87 9

F

E

D

C

B

A

97 8654321

BID DOCUMENTS

ATIONAL

EMETERY

DMINISTRATIONA

C

N

Drawing Title

GENESEE COUNTY, NEW YORK

Project Title

Location

Date Checked Drawn

936PC2002

Drawing Number

Building Number

Project Number

Management

03-15-19 Dwg of

V

T

N T I

D

STA

E

U

E

N T

OF

I

C

ES OF

R I

AM

E

R

A

S

S

ETERAN

AF

F A

Revisions:

VA FORM 08-6231, OCT 1978

CONSULTANTS:

Date

ARCHITECT/ENGINEER:

ATIONAL

EMETERY

DMINISTRATIONA

C

N

WESTERN NEW YORK

NATIONAL CEMETERY

PHASE 1A DEVELOPMENT and Facilities

Office of

Construction

LEO A DALY Company 2017

/2

/2

:1

:1 P

M C

U s e rs

\m js p e lle rb e rg

\D o c u m e n ts

\A u to d e s k \R e v it

P ro je c ts

\V A

C e m e te ry W

N Y

M

H -2 m js p e lle rb e rg

.r v t

MH501

DUCTWORK DETAILS

DJD MJB

DUCTWORK DETAILS

1001, 3001, 3401

SCALE: NONE1

DIFFUSER CONNECTION

SCALE: NONE2

DIFFUSER CONNECTION

SCALE: NONE3

INDOOR UNIT DETAIL

BRANCH DUCTWORK SCHEDULE

DUCT CFM SQUARE INCHES MINIMUM

RECOMMENDED DUCT SIZE (INCHES)

UNLABELED DUCTS ARE GENERALLY SMALLER BRANCH DUCTS. COORDINATE ELEVATIONS AND PROVIDE ALL NECESSARY OFFSETS, UNLESS OTHERWISE INDICATED. DUCTS SHALL BE SQUARE, RECTANGULAR, OR ROUND OF THE

FOLLOWING CROSS SECTIONAL AREA:

0 - 100 28 8x4

RECTANGULAR ROUND (Ø)

125 - 225 48 8x6 8

250 - 400 78 10x8 10

425 - 650 128 16x8 12

675 - 950 180 18x10 14

975 - 1300 216 18x12 16

AIR DEVICE SCHEDULE

TYPE

1, 2, 3, 4

1, 2, 3, 4

1, 2, 3, 4

1, 2, 3, 4

1, 2, 3, 4

SERVICE STYLE

SUPPLY

RETURN/EXHAUST

PERFORATED

FACE

SIZE

(IN)

24 x 24

NECK

SIZE

(IN)

6" Ø

AIR FLOW

RANGE

(CFM)

0 - 100

REMARKS

PERFORATED 24 x 24 8" Ø 101 - 175

PERFORATED 24 x 24 10" Ø 176 - 250

PERFORATED 24 x 24 12" Ø 251 - 350

PERFORATED 24 x 24 14" Ø 351 - 450

SUPPLY

SUPPLY

SUPPLY

SUPPLY

RETURN/EXHAUST

RETURN/EXHAUST

RETURN/EXHAUST

RETURN/EXHAUST

PERFORATED

PERFORATED

PERFORATED

PERFORATED

PERFORATED

24 x 24

24 x 24

24 x 24

24 x 24

24 x 24

10" Ø

12" Ø

14" Ø

15 x 15

6" Ø

201 - 325

326 - 450

451 - 600

601 - 950

0 - 100

15 RETURN/EXHAUST LOUVERED 8 x 8 8 x 8 0 - 100

15 RETURN/EXHAUST 12 x 8 12 x 8 101 - 200

15 RETURN/EXHAUST 14 x 10 201 - 400

15 RETURN/EXHAUST 16 x 12 401 - 600

LOUVERED

LOUVERED

LOUVERED

14 x 10

16 x 12

5 RETURN/EXHAUST PERFORATED 24 x 24 8" Ø 101 - 200

7 RETURN/EXHAUST SINGLE FIXED BLADE 10 x 6 10 x 6 75 - 175

8 RETURN/EXHAUST SINGLE FIXED BLADE - - -

16 SUPPLY - -LINEAR BAR -

ALUMINUM CONSTRUCTION 35º BLADE

ALUMINUM CONSTRUCTION 35º BLADE

14 SUPPLY DOUBLE DEFLECTION - - -

4" HIGH 7/32" BLADE THICKNESS

SEE PLANS FOR SIZE, PROVIDE W/ O.B.D.

B

A

C

D

E

F

1 2 3 4 5 6 87 9

F

E

D

C

B

A

97 8654321

BID DOCUMENTS

ATIONAL

EMETERY

DMINISTRATIONA

C

N

Drawing Title

GENESEE COUNTY, NEW YORK

Project Title

Location

Date Checked Drawn

936PC2002

Drawing Number

Building Number

Project Number

Management

03-15-19 Dwg of

V

T

N T I

D

STA

E

U

E

N T

OF

I

C

ES OF

R I

AM

E

R

A

S

S

ETERAN

AF

F A

Revisions:

VA FORM 08-6231, OCT 1978

CONSULTANTS:

Date

ARCHITECT/ENGINEER:

ATIONAL

EMETERY

DMINISTRATIONA

C

N

WESTERN NEW YORK

NATIONAL CEMETERY

PHASE 1A DEVELOPMENT and Facilities

Office of

Construction

LEO A DALY Company 2017

/2

/2

:1

:1 P

M C

U s e rs

\m js p e lle rb e rg

\D o c u m e n ts

\A u to d e s k \R e v it

P ro je c ts

\V A

C e m e te ry W

N Y

M

H -2 m js p e lle rb e rg

.r v t

MH601

SCHEDULES

DJD MJB

SCHEDULES

BOILER SCHEDULE

UNIT

NO. TYPE

MIN.

BOILER

EFFICIENCY

(% AFUE)

BURNER CAPACITY

FLUE

VENT

DIA. (IN)

HOT WATER

RELIEF

VALVE

SETTING

(PSI)

ELECTRICAL DATA

MAX

OPERATING

WEIGHT (LBS) REMARKS

INPUT

(MBH)

GROSS

OUTPUT

(MBH)

MIN. INLET

PROPANE

PRESS. (IN.

WG) FUEL GPM EWT (ºF) LWT (ºF)

MAX

PRESS.

DROP

(FT) V/PH/HZ

CONTROL

VOLTAGE

UNIT

FLA

UNIT

MCA

UNIT

MOCP

B-A-1 CONDENSING 95 155 144 10 PROPANE 3 17 120 140 6.0 30 120/1/60 24 15A 300 1

B-D-1 CONDENSING 95 155 144 10 PROPANE 3 13 120 140 4.0 30 120/1/60 24 15A 300 1

PUMP SCHEDULE

UNIT

NO. SYSTEM TYPE

FLUID

TYPE

CAPACITY

(GPM)

HEAD

(FT)

EFFICIENCY

(%) SUCTION (IN)

DISCHARGE

(IN)

MOTOR

REMARKSHP RPM VSD (1) V/PH/HZ

P-A-1 ADMIN. VARIABLE SPEED WET ROTOR WATER 17 42 41 1.5 1.5 0.5 3600 YES 208/1/60 PROVIDE WITH ECM MOTOR

P-A-2 ADMIN. VARIABLE SPEED WET ROTOR WATER 17 42 41 1.5 1.5 0.5 3600 YES 208/1/60 PROVIDE WITH ECM MOTOR

P-D-1 MAINT. VARIABLE SPEED WET ROTOR WATER 13 36 41 1.5 1.5 0.5 3600 YES 208/1/60 PROVIDE WITH ECM MOTOR

P-D-2 MAINT. VARIABLE SPEED WET ROTOR WATER 13 36 41 1.5 1.5 0.5 3600 YES 208/1/60 PROVIDE WITH ECM MOTOR

ENERGY RECOVERY VENTILATOR SCHEDULE

UNIT

NO.

SUPPLY FAN EXHAUST FAN OUTSIDE AIR CONDITIONS (SUPPLY) EXHAUST AIR CONDITIONS FILTER ELECTRICAL

UNIT

DIMENSIONS

(LxWxH)

UNIT

WEIGHT

(LBS) REMARKSCFM

ESP (IN

WC) DRIVE HP CFM

ESP (IN

WC) DRIVE HP

SUMMER WINTER SUMMER WINTER

NO. MERV FLA MCA MOPD V/PH/HZ

INLET OUTLET INLET OUTLET INLET OUTLET INLET OUTLET

DB (ºF) WB (ºF) DB (ºF) WB (ºF)

TOTAL

EFF. DB (ºF) WB (ºF) DB (ºF) WB (ºF)

TOTAL

EFF. DB (ºF) WB (ºF) DB (ºF) WB (ºF) DB (ºF) WB (ºF) DB (ºF) WB (ºF)

ERV-A-1 990 0.5 DIRECT 1.0 890 1.0 DIRECT 1.0 85 73 78.2 68.1 56% 6 0 49.7 36.1 72% 75 62.5 - - 70 50 - - 2 8 2x2.2 5.0 15 208/3/60 35x54x54 340

ERV-A-2 455 1.0 DIRECT 0.75 355 1.25 DIRECT 0.75 85 73 78.3 67.7 69% 6 0 48.8 36.0 83% 75 62.5 - - 70 50 - - 2 8 2x2.2 5.2 15 208/3/60 24x55x36 211

ERV-D-1 6000 1.27 6000 1.27 85 73 85 73 0 6 0 43.8 31.4 67 85 73 85 73 60 43.9 - - 16 8 - - - - 36x74x86 700

ERV-D-2 1080 1.5 DIRECT 1.5 985 1.5 DIRECT 1.5 85 73 77.9 67.9 60% 6 0 51.6 37.6 60% 75 62.5 - - 70 50 - - 4 8 2x4.5 5.2 15 208/3/60 61x3x36 414 WITH INTEGRAL VFD

VARIABLE REFRIGERANT FLOW SYSTEM (VRF) INDOOR UNIT

UNIT NO. AREA SERVED ESP CFM MIN OA CFM

COOLING COIL HEATING COIL ELECTRICAL DATA

DIMENSIONS

(WxHxD)

WEIGHT

(LBS) REMARKS

EAT DB/WB

(°F)

TOTAL

CAPACITY

(MBH) EAT (°F)

HEATING

(MBH) V/PH/HZ MOCP

IDU-A-1 TOILET ROOMS 0.6 685 475 78.2/68.1 24.1 70 26.9 208/1/60 15 56x12x28 79

IDU-A-2 LOBBY 0.6 685 450 78.2/68.1 24.1 70 26.9 208/1/60 15 40x12x28 79

IDU-A-3 OPEN OFFICE 0.6 685 95 76.0/63.6 21.1 70 26.9 208/1/60 15 40x12x28 79

IDU-A-4 OPERATIONAL CENTER 0.4 315 30 76.0/63.6 6.6 70 8.4 208/1/60 15 22x12x28 55

IDU-A-5 MULTI-PURPOSE 0.6 685 80 76.0/63.6 21.1 70 26.9 208/1/60 15 40x12x28 79

IDU-A-6 DIRECTOR 0.4 315 35 76.0/63.6 8.3 70 19.5 208/1/60 15 40x12x28 55

IDU-A-7 CORRIDOR 0.4 315 150 76.0/63.6 6.6 70 8.4 208/1/60 15 22x12x28 55

IDU-A-8 LUNCH ROOM 0.6 685 75 76.0/63.6 15.8 70 19.9 208/1/60 15 40x12x28 79

IDU-A-9 ASSISTANT DIIRECTOR 0.4 450 50 76.0/63.6 10.5 70 13.5 208/1/60 15 28x12x28 62

IDU-D-1 WORK AREA 0.4 450 175 76.0/63.0 10.3 70 13.5 208/1/60 15 40x12x28 62

IDU-D-2 WOMEN'S/MEN'S 0.6 685 400 77.0/67.6 24.0 70 26.9 208/1/60 15 56x12x28 79

IDU-D-3 MULTI-PURPOSE 0.6 1375 205 76.0/63.0 41.2 70 53.9 208/1/60 15 56x12x28 101

IDU-D-4 FOREMAN 0.4 315 50 76.0/63.0 8.1 70 10.5 208/1/60 15 28x12x28 62

IDU-D-5 CARETAKER/COTR 0.4 450 60 76.0/63.0 10.3 70 13.5 208/1/60 15 28x12x28 62

VARIABLE REFRIGERANT FLOW SYSTEM (VRF) OUTDOOR UNIT

UNIT NO.

COOLING

(MBH)

HEATING

(MBH) IEER

ELECTRICAL DIMENSIONS

(WxHxD)

WEIGHT

(LBS) NOTESMCA V/PH/HZ

ODU-A-1 48.3 37.9 16.0 29.1 208/1/60 37x39x12 176 95°F AMBIENT, R410A

ODU-A-2 102.7 84.9 21.4 36.3 208/3/60 50x68x30 527 95°F AMBIENT, R410A

ODU-D-1 105.1 84.9 21.4 36.3 208/3/60 50x68x30 527 95°F AMBIENT, R410A

FAN SCHEDULE

UNIT

NO. TYPE CFM

SP (IN.

WC)

WHEEL

TYPE

MIN

WHEEL

DIA (IN)

FAN

RPM DRIVE CLASS

SOUND DATA (AT FAN INLET) MOTOR

WEIGHT REMARKSSONES

SOUND POWER AT OCTAVE BAND (Db), RE 10 ̄¹² W

BHP HP RPM VSD V/PH/HZ1/63 2/125 3/250 4/500 5/1K 6/2K 7/4K 8/8K

CF-B-1 CEILING 19,000 0.1 PROP 72 140 DIRECT - - - - - - - - - - - 0.25 140 YES 120/1/60 52 1

EF-C-1 CABINET 270 0.625 FC 6.75 1220 DIRECT 1 3.5 60 59 55 56 55 49 46 41 - - - NO 120/1/60 23 2

EF-D-1 IN-LINE 6000 2.25 MIXED 24.5 1575 BELT 2 - 74 78 78 77 76 74 68 62 3.5 5.0 1725 YES 480/3/60 500

EF-D-2 IN-LINE 250 1.0 BI…

This is the start of the file's text. The full file is on GovTribe.

File details come from the government source that posted it.