23 09 23.27.pdf
PDF 158 KB Posted
- Attached to
- Y1DZ--Hines Finance Center Renovation
- Solicitation number
- 36C10E21R0009
About this file
This solicitation is for renovation services at the Hines Finance Center located in Hines, Illinois. The scope of work includes demolishing existing interior walls, ceilings, flooring and mechanical/electrical systems in approximately 7,651 square feet of office and break room space. New construction will include installing drywall, suspended ceiling tiles, carpet and luxury vinyl tiles, as well as replacing the access flooring system, mechanical equipment, ductwork, diffusers and controls. Electrical work consists of replacing three obsolete electrical panels and associated circuits, installing new lighting fixtures compatible with the Lutron controls system, and upgrading data cabling to category 6A. The security, fire alarm and VoIP systems will be modified as needed. The period of performance is 180 days after notice to proceed. The solicitation is expected to be released within 60 days by the Department of Veterans Affairs Veteran Benefits Administration for the Hines Finance Center Renovation project.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 23 31 13.pdf | ||
| 23 01 30.52.pdf | ||
| 36C10E21R0009 0005.docx | DOCX document | |
| 23 37 13.23.pdf | ||
| 23 09 93.11.pdf | ||
| 36C10E21R0009 0004.docx | DOCX document | |
| Site Visit Sign In Sheet Page 1_10-19-2021.pdf | ||
| 36C10E21R0009 0003.docx | DOCX document | |
| Site Visit Sign In Sheet Page 2_10-19-2021.pdf | ||
| 36C10E21R0009 0002.docx | DOCX document | |
| 36C10E21R0009 0001.docx | DOCX document | |
| Hines Finance Center - Drawings 6-14-2021.pdf | ||
| Wage Determination for Cook County 9-24-2021.pdf | ||
| 201VB3032 Hines Finance Center - Specifications_6-14-2021.pdf | ||
| 36C10E21R0009.docx | DOCX document |
Show all 15
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Veteran Benefits Administration June 14, 2021
201VB3032 | Hines Finance Center
Specifications – 100% Design
TEMPERATURE INSTRUMENTS
23 09 23.27 - Page 1 of 10
SECTION 23 09 23.27
PART 1 - GENERAL
1.1 RELATED DOCUMENTS
A. Drawings and general provisions of the Contract, including General and Supplementary
Conditions and Division 01 Specification Sections, apply to this Section.
1.2 SUMMARY
A. Section Includes:
1. Air temperature sensors.
2. Combination air temperature sensors and switches.
3. Air temperature switches.
4. Air temperature RTD transmitters.
5. Liquid and steam temperature sensors.
6. High-end, commercial-grade, liquid and steam temperature sensors.
7. Industrial-grade liquid and steam temperature sensors.
8. Liquid temperature switches.
9. High-end, commercial-grade, liquid and steam temperature transmitters.
10. Industrial-grade liquid and steam temperature transmitters.
B. Related Requirements:
1. Section 23 09 23 "Direct-Digital Control System for HVAC" for control equipment and software, relays, electrical power devices, uninterruptible power supply units, wire, and cable.
2. Section 23 09 93 "Sequence of Operations for HVAC Controls" for requirements that relate to Section 23 09 23.27.
1.3 DEFINITIONS
A. HART (Highway Addressable Remote Transducer) Protocol: The global standard for sending and receiving digital information across analog wires between smart devices and control or monitoring systems through bidirectional communication that provides data access between intelligent field instruments and host systems. A host can be any software application from a technician's hand-held device or laptop to a plant's process control, asset management, safety, or other system using any control platform.
B. RTD: Resistance temperature detector.
23 09 23.27 - Page 2 of 10
1.4 ACTION SUBMITTALS
A. Product Data: For each type of product, including the following:
1. Construction details, material descriptions, dimensions of individual components and profiles, and finishes.
2. Operating characteristics, electrical characteristics, and furnished accessories indicating process operating range, accuracy over range, control signal over range, default control signal with loss of power, calibration data specific to each unique application, electrical power requirements, and limitations of ambient operating environment, including temperature and humidity.
3. Product description with complete technical data, performance curves, and product specification sheets.
4. Installation operation and maintenance instructions, including factors affecting performance.
B. Shop Drawings:
1. Include plans, elevations, sections, and mounting details.
2. Include details of product assemblies. Indicate dimensions, weights, loads, required clearances, method of field assembly, components, and location and size of each field connection.
3. Include diagrams for power, signal, and control wiring.
4. Include number-coded identification system for unique identification of wiring, cable, and tubing ends.
C. Samples: For each exposed product installed in finished space.
1.5 INFORMATIONAL SUBMITTALS
A. Coordination Drawings: Plan drawings and corresponding product installation details, drawn to scale, on which the following items are shown and coordinated with each other, using input from installers of the items involved:
1. Product installation location shown in relationship to room, duct, pipe, and equipment.
2. Wall-mounted instruments located in finished space showing relationship to light switches, fire-alarm devices, and other installed devices.
3. Sizes and locations of wall access panels for instruments installed behind walls.
4. Sizes and locations of ceiling access panels for instruments installed in inaccessible ceilings.
B. Product Certificates: For each product requiring a certificate.
C. Product Test Reports: For each product, for tests performed by manufacturer and witnessed by a qualified testing agency.
D. Field quality-control reports.
23 09 23.27 - Page 3 of 10
1.6 MAINTENANCE MATERIAL SUBMITTALS
A. Furnish extra materials and parts that match products installed and that are packaged with protective covering for storage and identified with labels describing contents.
B. Provide two matching product(s) in Project inventory for each unique size and type of the following:
1. Air Temperature Sensor
PART 2 - PRODUCTS
2.1 PERFORMANCE REQUIREMENTS
A. Environmental Conditions:
1. Instruments shall operate without performance degradation under the ambient environmental temperature, pressure, humidity, and vibration conditions specified and encountered for installed location.
a. If instrument alone cannot meet requirement, install instrument in a protective enclosure that is isolated and protected from conditions impacting performance.
Enclosure shall be internally insulated, electrically heated and cooled, filtered, and ventilated as required by instrument and application.
2. Instruments and accessories shall be protected with enclosures satisfying the following minimum requirements unless more stringent requirements are indicated. Instruments not available with integral enclosures complying with requirements indicated shall be housed in protective secondary enclosures. Instrument's installed location shall dictate following
NEMA 250 enclosure requirements:
3.
a. Indoors, Heated with Filtered Ventilation: Type 1.
2.2 AIR TEMPERATURE SENSORS
A. Platinum RTDs: Common Requirements:
1. 100 or 1000 ohms at zero deg C and a temperature coefficient of 0.00385 ohm/ohm/deg C.
2. Two-wire, PTFE-insulated, 22-gage stranded copper leads.
3. Performance Characteristics:
a. Range: Minus 50 to 275 deg F (Minus 46 to 135 deg C).
b. Interchangeable Accuracy: At 32 deg F (zero deg C) within 0.5 deg F (0.3 deg C).
c. Repeatability: Within 0.5 deg F (0.3 deg C).
d. Self-Heating: Negligible.
4. Transmitter Requirements:
23 09 23.27 - Page 4 of 10
a. Transmitter required for each 100-ohm RTD.
b. Transmitter optional for 1000-ohm RTD, contingent on compliance with end-to-end control accuracy.
B. Space Air Temperature Sensors for Use with DDC Controllers Controlling Terminal Units:
1. 1000-ohm platinum RTD or thermistor.
2. Thermistor:
a. Pre-aged, burned in, and coated with glass; inserted in a metal sleeve; and entire unit encased in epoxy.
b. Thermistor drift shall be less than plus or minus 0.5 deg F (0.3 deg C) over 10 years.
3. Temperature Transmitter Requirements:
a. Mating transmitter required with each 100-ohm RTD.
b. Mating transmitters optional for 1000-ohm RTD and thermistor, contingent on compliance with end-to-end control accuracy.
4. Provide digital display of sensed temperature.
5. Provide sensor with local control.
a. Local override to turn HVAC on.
b. Local adjustment of temperature set point.
c. Both features shall be capable of manual override through control system operator.
PART 3 - EXECUTION
3.1 EXAMINATION
A. Examine substrates and conditions for compliance with requirements for installation tolerances and other conditions affecting performance of the Work.
B. Examine roughing-in for instruments installed in piping to verify actual locations of connections before installation.
C. Examine roughing-in for instruments installed in duct systems to verify actual locations of connections before installation.
D. Prepare written report, endorsed by Installer, listing conditions detrimental to performance.
E. Proceed with installation only after unsatisfactory conditions have been corrected.
3.2 TEMPERATURE INSTRUMENT APPLICATIONS
A. Air Temperature Sensors:
23 09 23.27 - Page 5 of 10
B.
1. Space,: 1000-ohm platinum RTD.
3.3 INSTALLATION, GENERAL
A. Install products level, plumb, parallel, and perpendicular with building construction.
B. Properly support instruments, tubing, piping, wiring, and conduit to comply with requirements indicated. Brace all products to prevent lateral movement and sway or a break in attachment when subjected to force.
C. Fastening Hardware:
1. Stillson wrenches, pliers, and other tools that cause injury to or mar surfaces of rods, nuts, and other parts are prohibited for work of assembling and tightening nuts.
2. Tighten bolts and nuts firmly and uniformly. Do not overstress threads by excessive force or by oversized wrenches.
3. Lubricate threads of bolts, nuts, and screws with graphite and oil before assembly.
D. Install products in locations that are accessible and that permit calibration and maintenance from floor, equipment platforms, or catwalks. Where ladders are required for Owner's access, confirm unrestricted ladder placement is possible under occupied condition.
E. Corrosive Environments:
1. Use products that are suitable for environment to which they are subjected.
2. If possible, avoid or limit use of materials in corrosive environments.
3. When conduit is in contact with a corrosive environment, use Type 316 stainless-steel conduit and fittings or conduit and fittings that are coated with a corrosive-resistant coating that is suitable for environment.
4. Where instruments are located in a corrosive environment and are not corrosive resistant from manufacturer, field install products in a NEMA 250, Type 4X enclosure constructed of Type 316L stainless steel.
3.4 ELECTRIC POWER
A. Furnish and install electrical power to products requiring electrical connections.
B. Furnish and install circuit breakers. Comply with requirements in Section 26 28 16 "Enclosed
Switches and Circuit Breakers."
C. Furnish and install power wiring. Comply with requirements in Section 26 05 19 "Low-Voltage
Electrical Power Conductors and Cables."
D. Furnish and install raceways. Comply with requirements in Section 26 05 33 "Raceways and
Boxes for Electrical Systems."
23 09 23.27 - Page 6 of 10
3.5 TEMPERATURE INSTRUMENT INSTALLATIONS
A. Mounting Location:
1. Roughing In:
a. Outline instrument mounting locations before setting instruments and routing cable, wiring, tubing, and conduit to final location.
b. Provide independent inspection to confirm that proposed mounting locations comply with requirements indicated and approved submittals.
1) Indicate dimensioned locations with mounting height for all surface-mounted products on Shop Drawings.
2) Do not begin installation without submittal approval of mounting location.
c. Complete installation rough-in only after confirmation by independent inspection is complete and approval of location is documented for review by Owner and Architect on request.
2. Install switches and transmitters for air and liquid temperature associated with individual air-handling units and associated connected ductwork and piping near air-handling units co-located in air-handling unit system control panel to provide service personnel a single and convenient location for inspection and service.
3. Install liquid and steam temperature switches and transmitters for indoor applications in mechanical equipment rooms. Do not locate in user-occupied space unless indicated specifically on Drawings.
4. Install air temperature switches and transmitters for indoor applications in mechanical equipment rooms. Do not locate in user-occupied space unless indicated specifically on
Drawings.
5. Mount switches and transmitters on walls, floor-supported freestanding pipe stands, or floor-supported structural support frames. Use manufacturer's mounting brackets to accommodate field mounting. Securely support and brace products to prevent vibration and movement.
B. Special Mounting Requirements:
1. Protect products installed outdoors from solar radiation, building and wind effect with stand-offs and shields constructed of Type 316 stainless.
2. Temperature instruments having performance impacted by temperature of mounting substrate shall be isolated with an insulating barrier located between instrument and substrate to eliminate effect. Where instruments requiring insulation are located in finished space, conceal insulating barrier in a cover matching the instrument cover.
C. Mounting Height:
1. Mount temperature instruments in user-occupied space to match mounting height of light switches unless otherwise indicated on Drawings. Mounting height shall comply with codes and accessibility requirements.
2. Mount switches and transmitters located in mechanical equipment rooms and other similar space not subject to code or state and Federal accessibility requirements within a range of
23 09 23.27 - Page 7 of 10
42 to 72 inches (1.1 to 1.6 m) above the adjacent floor, grade, or service catwalk or platform.
a. Make every effort to mount at 60 inches (1500 mm).
D. Seal penetrations to ductwork, plenums, and air-moving equipment to comply with duct static-pressure class and leakage and seal classes indicated using neoprene gaskets or grommets.
E. Space Temperature Sensor Installation:
1. Conceal assembly in an electrical box of sufficient size to house sensor and transmitter, if provided.
2. Install electrical box with a faceplate to match sensor cover if sensor cover does not completely cover electrical box.
3. In finished areas, recess electrical box within wall.
4. In unfinished areas, electrical box may be surface mounted if electrical light switches are surface mounted. Use a cast-aluminum electric box for surface-mounted installations.
5. Align electrical box with other electrical devices such as visual alarms and light switches located in the vicinity to provide a neat and well-thought-out arrangement. Where possible, align in both horizontal and vertical axis.
3.6 IDENTIFICATION
A. Identify system components, wiring, cabling, and terminals. Each piece of wire, cable, and tubing shall have the same designation at each end for operators to determine continuity at points of connection. Comply with requirements for identification specified in Section 26 05 53
"Identification for Electrical Systems."
B. Install engraved phenolic nameplate with instrument identification.
3.7 CLEANING
A. Remove grease, mastic, adhesives, dust, dirt, stains, fingerprints, labels, and other foreign materials from exposed interior and exterior surfaces.
B. Wash and shine glazing.
C. Polish glossy surfaces to a clean shine.
3.8 CHECK-OUT PROCEDURES
A. Check installed products before continuity tests, leak tests, and calibration.
B. Check temperature instruments for proper location and accessibility.
C. Verify sensing element type and proper material.
23 09 23.27 - Page 8 of 10
D. Verify location and length.
E. Verify that wiring is correct and secure.
3.9 ADJUSTMENT, CALIBRATION, AND TESTING
A. Description:
1. Calibrate each instrument installed that is not factory calibrated and provided with calibration documentation.
2. Provide a written description of proposed field procedures and equipment for calibrating each type of instrument. Submit procedures before calibration and adjustment.
3. For each analog instrument, make a three-point test of calibration for both linearity and accuracy.
4. Equipment and procedures used for calibration shall meet instrument manufacturer's written instructions.
5. Provide diagnostic and test equipment for calibration and adjustment.
6. Field instruments and equipment used to test and calibrate installed instruments shall have accuracy at least twice the instrument accuracy being calibrated. For example, an installed instrument with an accuracy of 1 percent shall be checked by an instrument with an accuracy of 0.5 percent.
7. Calibrate each instrument according to instrument instruction manual supplied by manufacturer.
8. If after calibration indicated performance cannot be achieved, replace out-of-tolerance instruments.
9. Comply with field-testing requirements and procedures indicated by ASHRAE
Guideline 11, "Field Testing of HVAC Control Components," in the absence of specific requirements and to supplement requirements indicated.
B. Analog Signals:
1. Check analog voltage signals using a precision voltage meter at zero, 50, and 100 percent.
2. Check analog current signals using a precision current meter at zero, 50, and 100 percent.
3. Check resistance signals for temperature sensors at zero, 50, and 100 percent of operating span using a precision-resistance source.
C. Digital Signals:
1. Check digital signals using a jumper wire.
2. Check digital signals using an ohmmeter to test for contact.
D. Sensors: Check sensors at zero, 50, and 100 percent of Project design values.
E. Switches: Calibrate switches to make or break contact at set points indicated.
F. Transmitters:
1. Check and calibrate transmitters at zero, 50, and 100 percent of Project design values.
23 09 23.27 - Page 9 of 10
2. Calibrate resistance temperature transmitters at zero, 50, and 100 percent of span using a precision-resistance source.
3.10 FIELD QUALITY CONTROL
A. Testing Agency: Engage a qualified testing agency to perform tests and inspections.
B. Manufacturer's Field Service: Engage a factory-authorized service representative to test and inspect components, assemblies, and installations, including connections.
C. Perform the following tests and inspections with the assistance of a factory-authorized service representative:
1. Perform according to manufacturer's written instruction.
2. Test and adjust controls and safeties. Replace damaged and malfunctioning controls and equipment.
D. Prepare test and inspection reports.
3.11 ADJUSTING
A. Occupancy Adjustments: When requested within 12 months from date of Substantial Completion, provide on-site assistance in adjusting system to suit actual occupied conditions. Provide up to two visits to Project during other-than-normal occupancy hours for this purpose.
3.12 MAINTENANCE SERVICE
A. Maintenance Service: Beginning at Substantial Completion, maintenance service shall include three months' full maintenance by manufacturer's authorized service representative. Include monthly preventive maintenance, repair, or replacement of worn or defective components, cleaning and adjusting as required for proper operation. Parts and supplies shall be manufacturer's authorized replacement parts and supplies.
3.13 DEMONSTRATION
A. Engage a factory-authorized service representative to train Owner's maintenance personnel to adjust, operate, and maintain temperature instruments.
B. Provide a complete set of instructional videos covering each product specified and installed and showing the following:
1. Software programming.
2. Calibration and test procedures.
3. Operation and maintenance requirements and procedures.
4. Troubleshooting procedures.
23 09 23.27 - Page 10 of 10
C. Coordinate video with operation and maintenance manuals and classroom instruction for use by
Owner in operating, maintaining, and troubleshooting.
D. Record videos on DVD disks.
E. Owner shall have right to make additional copies of video for internal use without paying royalties.
END OF SECTION 23 09 23.27