Summary
| Device Type # | Device Category | Device Qty | Monitoring Point Qty per Device | Total Points per Device Type |
| 1 | UPS | | | 0 |
| 2 | PDU/RPP | | | 0 |
| 3 | CRAC/CRAH | | | 0 |
| 4 | ATS | | | 0 |
| 5 | Fire Alarm Panel | | | 0 |
| 6 | Leak Detection System | | | 0 |
| 7 | Generators | | | 0 |
| 8 | Building Management Control System | | | 0 |
| 9 | Emergency Master Control System | | | 0 |
| 10 | Power Meters | | | 0 |
| 11 | PDU Strips | | | 0 |
| 12 | Environmental Sensors | | | 0 |
| 13 | Battery Monitoring System | | | 0 |
| 14 | Chiller Plan | | | 0 |
| 15 | Others (AHU, Circuit Breakers, etc) | | | 0 |
| | | New Total | 0 |
AHU
| AHU Profile | | | |
| Modbus | SNMP | BACNET |
| MONITORING POINTS | | | |
| Unit Status | | | |
| Space Temp | | | |
| Outside Air Temp | | | |
| Return Air Temp | | | |
| Supply Air Temp | | | |
| Cooling Capacity | | | |
| Heating Capacity | | | |
| Economizer Percentage | | | |
| Pump Speed | | | |
| Space Pressure | | | |
| Space Relative Humidity | | | |
| Space Dew Point | | | |
| Return Relative Humidity | | | |
| Return Dew Point | | | |
| Cool On | | | |
| Free Cool On | | | |
| SETPOINTS |
| Supply Set Point |
| Space Set Point |
| Leak Alarm |
| High Temp (Return) |
| Low Temp (Return) |
| Hi Hum (Return) |
| Low Hum (Return) |
| Loss of Airflow |
| Loss of Flow |
| Comp 1 OL |
| Comp 1 Low Press |
| Comp 1 High Press |
| Comp 2 OL |
| Comp 2 Low Press |
| Comp 2 High Press |
| Common Aalrm |
ATS
| ATS Profile | | | | Device Locations | | | | |
| | Modbus | SNMP | BACNET | ATS | ROOM | GRID LOCATION | MANUFACTURER | MODEL |
| MONITORING POINTS | X | | | | | | | |
| preferred | X | | | | | | | | |
back up
| Source 1 Open/Closed | | | | |
| Source 1 Voltage | | | | |
| Source 1 Current | | | | |
| Source 2 Open/Closed | | | | |
| Source 2 Volatge | | | | |
| Source 2 Current | | | | |
| Voltage Phase A-B | | Device Qty | Points per device | Total |
| Voltage Phase B-C | Add these: | | 35 | 0 |
| Voltage Phase C-A | Input KW | | | |
| Voltage Phase A-N | Input KW/Hr | | | |
| Voltage Phase B-N | Output KW/Hr | | | |
| Voltage Phase C-N | | | | |
| Current Phase A | | | | |
| Current Phase B | | | | |
| Current Phase C | | | | |
| kVA Total | | | | |
| kW Total | | | | |
| KVAR Total | | | | |
| Power Factor | | | | |
| Normal Breaker | | | | |
| Emergency Breaker | | | | |
| ALARMS |
| Normal Under Volatage |
| Normal Over Voltage |
| Emerg Under Voltage |
| Emerg Over Voltae |
| Under Frequency |
| Over Frequency |
| Exerciser Fail |
| Phase Rotation Error |
| Voltage Ibalance |
| Common Alarm |
ATS Example
Battery Monitor
| Battery Monitoring Profile | | | | | | | | |
| Modbus | SNMP | BACNET | Battery Monitor | ROOM | GRID LOCATION | MANUFACTURER | MODEL |
| MONITORING POINTS | | | | | | | | |
| String 1 Voltage | | | | | | | | |
| String 1 Current | | | | | | | | |
| String 1 Temp | | | | | | | | |
| String 2 Voltage | | | | | | | | |
| String 2 Current | | | | | | | | |
| String 2 Temp | | | | | | | | |
| String 3 Voltage | | | | | | | | |
| String 3 Current | | | | | | | | |
| String 3 Temp | | | | | | | | |
| ALARMS |
| Common Alarm |
| High Current |
| Low Current |
| High Voltage |
| Low Voltage |
| High Temp |
| Low Temp |
Breakers
| Breaker Profile | | | |
| Modbus | SNMP | BACNET |
| MONITORING POINTS | | | |
| Breaker Status | | | |
| Breaker Voltage | | | |
| Breaker Current | | | |
Chillers
| Chiller Profile | | | |
| Modbus | SNMP | BACNET |
| MONITORING POINTS | | | |
| CHWS Temp | | | |
| CHWR Temp | | | |
| CWS Temp | | | |
| CWR Temp | | | |
| Chiller Status | | | |
| CHW Pump Status | | | |
| CW Pump Stauts | | | |
| Flow Switch | | | |
| Compressor Pressure | | | |
| Compressor Current | | | |
| Compressor Voltage | | | |
| SETPOINTS |
| CHWS Setpotint |
| CHWR Setpoint |
| CWS Setpoint |
| CWR Setpoint |
| ALARMS |
| Common Alarm |
| Compressor Alarm |
| High Temp Alarm |
| Low Temp Alarm |
| Pump Alarm |
CRAC
| CRAC Profile | | | | | | | | |
| Modbus | SNMP | BACNET | CRAC | ROOM | GRID LOCATION | MANUFACTURER | MODEL |
| MONITORING POINTS | | | | | | | | |
| Unit Status | | | | | | | | |
| Fan Status | | | | | | | | |
| Space Temp | | | | | | | | |
| Return Air Temp | | | | | | | | |
| Supply Air Temp | | | | | | | | |
| Cooling Capacity | | | | | | | | |
| Heating Capacity | | | | | | | | |
| Space Pressure (Static Pressure) | | | | | | | | |
| Space/Return Relative Humidity | | | | | | | | |
| Cool On | | | | | | | | |
| Free Cool On | | | | | | | | |
| SETPOINTS |
| Supply Set Point |
| Space Set Point |
| Hum Set Point |
| ALARMS |
| Leak Alarm |
| High Temp (Return) |
| Low Temp (Return) |
| Hi Hum (Return) |
| Low Hum (Return) |
| Loss of Airflow |
| Loss of Flow |
| Comp 1 OL |
| Comp 1 Low Press |
| Comp 1 High Press |
| Comp 2 OL |
| Comp 2 Low Press |
| Comp 2 High Press |
| Comp 2 High Press |
| Common Alarm |
CRAC NEO Example
Diesel Fuel Monitor
| Diesel Fuel Monitor Profile | | | | |
| MONITORING POINTS | Unit Description | Modbus | SNMP | BACNET |
| Alarm | | X | | |
| Preferred | | X | | | |
Secondary option
| Trouble |
| Tank Level |
| Total Gallons |
| Fuel Level |
| Temperature |
Diesel Fuel Monitor Example
Environmental Monitoring
| Environmental Monitor Profile | | | | | | | |
| MONITORING POINTS | Unit Description | Modbus | SNMP | BACNET | Room | MANUFACTURER | MODEL |
| Alarm | | | X | | | | |
| Trouble | | | | | | | |
| Temperature | | | | | | | |
| Humidity | | | | | | | |
| Sensor Offline | | | | | | | |
Environmental Monitor Example
Fire Protection
| Fire Protection Profile | | | | |
| MONITORING POINTS | Unit Description | Modbus | SNMP | BACNET |
| Alarm | | | | |
| Trouble | | | | |
| Alarm | X |
| Trouble | |
| Tank Level | |
| Total Gallons | |
| Sprinkler System | X |
| Alarm On/Off | |
| Water On/Water Off | |
Fire Protection Example
Floor_Rack UPS
| Floor or Rackmount UPS Profile | | | | | | | | |
| Modbus | SNMP | BACNET | UPS | ROOM | GRID LOCATION | MANUFACTURER | MODEL |
| MONITORING POINTS | | X | | | | | | |
| Input Voltage Phase A-B | | | | | | | | |
| Input Voltage Phase B-C | | | | | | | | |
| Input Voltage Phase C-A | | | | | | | | |
| Input Current Phase A | | | | | | | | |
| Input Current Phase B | | | | | | | | |
| Input Current Phase C | | | | | | | | |
| Input kVA Total | | | | | | | | |
| Input kW Total | | | | | | | | |
| Input KWH Total | | | | | | | | |
| Input Power Factor | | | | | | | | |
| Input Power | | | | | | | | |
| Input KW | | | | | | | | |
| Input KW/Hr | | | | | | | | |
| Output Voltage A-B (L1) | | | | | | | | |
| Output Voltage B-C (L2) | | | | | | | | |
| Output Voltage C-A (L3) | | | | | | | | |
| Output Current Phase A | | | | | | | | |
| Output Current Phase B | | | | | | | | |
| Output Current Phase C | | | | | | | | |
| Output KVA Total | | | | | | | | |
| Power Factor | | | | | | | | |
| Frequency | | | | | | | | |
| Output KW Total | | | | | | | | |
| Output KWH Total | | | | | | | | |
| Output KW/Hr | | | | | | | | |
| Output Power Factor | | | | | | | | |
| Battery Voltage | | | | | | | | |
| ALARMS |
| On Bypass |
| On Battery |
| Battery Runtime remaining |
| Low Battery Shutdown |
| Inverter Fault |
| Rectifier Fault |
| Common Alarm |
Floor_Rack UPS Example
Generators
| Generator Profile | | | | | | | | |
| Modbus | SNMP | BACNET | Generator | ROOM | GRID LOCATION | MANUFACTURER | MODEL |
| MONITORING POINTS | | | | | | | | |
| Voltage Phase A-B | | | | | | | | |
| Voltage Phase B-C | | | | | | | | |
| Voltage Phase C-A | | | | | | | | |
| Voltage Avg. L-L | | | | | | | | |
| Current Phase A | | | | | | | | |
| Current Phase B | | | | | | | | |
| Current Phase C | | | | | | | | |
| Current Avg 3 Phase | | | | | | | | |
| kVA Total | | | | | | | | |
| kW Total | | | | | | | | |
| kVAR Total | | | | | | | | |
| KVAh Total | | | | | | | | |
| Oil Pressure | | | | | | | | |
| Engine Temperature (Oil Temp) | | | | | | | | |
| Frequency | | | | | | | | |
| Engine Run Hours | | | | | | | | |
| Controls In Auto | | | | | | | | |
| Battery Voltage | | | | | | | | |
| Generator Tank Fuel Level | | | | | | | | |
| ALARMS |
| OverSpeed Alarm |
| OverCrank Alarm |
| Overload Alarm |
| Coolant Temperature |
| Low Coolant Level Alarm |
| Low Coolant Temp Alarm |
| High Coolant Temp Alarm |
| Common Alarm |
Generators NEO Example
In-Rack PDU Strip
| In-Rack Profile (Power Strip) | | | | | | | | |
| Modbus | SNMP | BACNET | In Rack PDU | ROOM | GRID LOCATION | MANUFACTURER | MODEL |
| MONITORING POINTS | | X | | | | | | |
| Current Phase A | | | | | | | | |
| Current Phase B | | | | | | | | |
| Current Phase C | | | | | | | | |
| Circuit 1 Amps | | | | | | | | |
| Circuit 2 Amps | | | | | | | | |
| Circuit 3 Amps | | | | | | | | |
| Circuit 4 Amps | | | | | | | | |
| Circuit 5 Amps | | | | | | | | |
| Circuit 6 Amps | | | | | | | | |
| Real Power KW | same point | | | | | | | |
| Output Power | same point | | | | | | | |
| ALARMS | | | | | | | | |
| Critical High Alarm (45%) | | | | | | | | |
| Critical Warning Alarm (40%) | | | | | | | | |
| Loadbank 1, 2, 3 | | | | | | | | |
In-Rack PDU Strip Example
PDU-RPP
| PDU Profile | | | | | | | | | |
| Modbus | SNMP | BACNET | PDU | ROOM | GRID LOCATION | MANUFACTURER | MODEL | Comment |
| MONITORING POINTS | X | X | | | | | | | |
| Input Voltage Phase A-B | | | | | | | | | |
| Input Voltage Phase B-C | | | | | | | | | |
| Input Voltage Phase C-A | | | | | | | | | |
| Input Current Phase A | | | | | | | | | |
| Input Current Phase B | | | | | | | | | |
| Input Current Phase C | | | | | | | | | |
| Input kVA Total | | | | | | | | | |
| Input kW Total | | | | | | | | | |
| Input KWH Total | | | | | | | | | |
| Input Power Factor | | | | | | | | | |
| Input KW | | | | | | | | | |
| Input KW/Hr | | | | | | | | | |
| Output Voltage A-B (L1) | | | | | | | | | |
| Output Voltage B-C (L2) | | | | | | | | | |
| Output Voltage C-A (L3) | | | | | | | | | |
| Output Current Phase A | | | | | | | | | |
| Output Current Phase B | | | | | | | | | |
| Output Current Phase C | | | | | | | | | |
| Power Factor | | | | | | | | | |
| Frequency | | | | per panel | 48 | | | | |
| Output KVA Total | | | | per pdu | 25 | | | | |
| Output KW Total | | | | | 73 | | | | |
| Output KW/Hr | | | | | | | | | |
| Output KWH Total | | | | | | | | | |
| Output Power Factor | | | | | | | | | |
| ALARMS |
| High Current |
| High Voltage |
| Common Alarm |
PDU NEO Example
PDU_RPP Panel CKTS (42)
| Panel Profile | | | |
| Modbus | SNMP | BACNET |
| MONITORING POINTS | | | |
| CT01 | | | |
| CT02 | | | |
| CT03 | | | |
| CT04 | | | |
| CT05 | | | |
| CT06 | | | |
| CT07 | | | |
| CT08 | | | |
| CT09 | | | |
| CT10 | | | |
| CT11 | | | |
| CT12 | | | |
| CT13 | | | |
| CT14 | | | |
| CT15 | | | |
| CT16 | | | |
| CT17 | | | |
| CT18 | | | |
| CT19 | | | |
| CT20 | | | |
| CT21 | | | |
| CT22 | | | |
| CT23 | | | |
| CT24 | | | |
| CT25 | | | |
| CT26 | | | |
| CT27 | | | |
| CT28 | | | |
| CT29 | | | |
| CT30 | | | |
| CT31 | | | |
| CT32 | | | |
| CT33 | | | |
| CT34 | | | |
| CT35 | | | |
| CT36 | | | |
| CT37 | | | |
| CT38 | | | |
| CT39 | | | |
| CT40 | | | |
| CT41 | | | |
| CT42 | | | |
| *Panel Phase A | | | |
| *Panel Phase B | | | |
| *Panel Phase C | | | |
| *RealPower KW | | | |
PDU_RPP Panel CKTS Example
UPS
| UPS Profile | | | | | | | | |
| Modbus | SNMP | BACNET | UPS | ROOM | GRID LOCATION | MANUFACTURER | MODEL |
| MONITORING POINTS | | | | | | | | |
| Input Voltage Phase A-B | | | | | | | | |
| Input Voltage Phase B-C | | | | | | | | |
| Input Voltage Phase C-A | | | | | | | | |
| Input Current Phase A | | | | | | | | |
| Input Current Phase B | | | | | | | | |
| Input Current Phase C | | | | | | | | |
| Input kVA Total | | | | | | | | |
| Input kW Total | | | | | | | | |
| Input KWH Total | | | | | | | | |
| Input Power Factor | | | | | | | | |
| Input KW | | | | Device Qty | Points per Device | Total | | |
| Input KW/Hr | | | | | 35 | | | |
| Output Voltage A-B (L1) | | | | | | | | |
| Output Voltage B-C (L2) | | | | | | | | |
| Output Voltage C-A (L3) | | | | | | | | |
| Output Current Phase A | | | | | | | | |
| Output Current Phase B | | | | | | | | |
| Output Current Phase C | | | | | | | | |
| Output KVA Total | | | | | | | | |
| Power Factor | | | | | | | | |
| Frequency | | | | | | | | |
| Output KW/Hr | | | | | | | | |
| Output KW Total | | | | | | | | |
| Output KWH Total | | | | | | | | |
| Output Power Factor | | | | | | | | |
| Battery Voltage | | | | | | | | |
| ALARMS |
| On Bypass |
| On Battery |
| Battery Runtime remaining |
| Low Battery Shutdown |
| Inverter Fault |
| Rectifier Fault |
| Common Alarm |
UPS NEO Example
Water Leak Detection
| Water Leak Detection Profile | | | | |
| MONITORING POINTS | Unit Description | Modbus | SNMP | BACNET |
| Alarm | | X | | |
| Trouble | | | | |
| Sprinkler System | | | | |
| Alarm On/Off | | | | |
| Water On/Water Off | | | | |
| Leak is Detected | | | | |
| Cable Break Alarm | | | | |
| Contamination is Detected | | | | |
Water Leak Detection Example image1.png image2.png image3.png image4.png image5.png image6.png image7.png image8.png image9.png image10.png image11.png image12.png image13.png image14.png image15.png image16.png image17.png image18.png image19.png image20.png