Exhibit B NEO Device Profiles Example Monitoring Points.xlsx

XLSX spreadsheet 1 MB Posted

Attached to
C222--Site Surveys to Implement Data Center Facilities Monitoring Tool - RDCs and ITCs (VA-21-00012639)
Solicitation number
36C10B21R0006
Issued by

About this file

This document contains profiles for monitoring various types of equipment in a data center facility and related details of a federal contract opportunity. The Department of Veterans Affairs Technology Acquisition Center is seeking to issue a solicitation for site surveys to implement a data center facilities monitoring tool at the Orlando Regional Data Center in Orlando, Florida. The goal is to gather accurate site-specific data for the monitoring tool, which will provide single pane viewing and real-time monitoring of electrical, HVAC, and environmental conditions across all VA data center sites. An existing monitoring solution called Nlyte Energy Monitoring Optimizer has already been implemented at several VA data centers and will be expanded to additional sites. Interested parties should submit any questions by December 14, 2020 regarding solicitation number 36C10B21R0006, which will close for responses on December 21, 2020.

View the file

Other files

File Type Posted
RFP - 36C10B21R0006 - Final 22 DEC.pdf PDF
36C10B21R0006 0003.docx DOCX document
RFP QA December 16 updated.docx DOCX document
Exhibit A Preliminary Site Information ITCs_RDCs v4 21-NT0044 updated 16 Dec.xlsx XLSX spreadsheet
RFP - 36C10B21R0006 - Final 16 DEC.pdf PDF
36C10B21R0006 0002.docx DOCX document
RFP - 36C10B21R0006 - Final 8 DEC.pdf PDF
36C10B21R0006 0001.docx DOCX document
RFP - 36C10B21R0006 - Final.pdf PDF
36C10B21R0006_1.docx DOCX document
21-NT0044 Exhibit A Preliminary Site Information ITCs_RDCs v3.xlsx XLSX spreadsheet
Show all 11

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Summary

Summary of Points
[date]
Device Type #Device CategoryDevice QtyMonitoring Point Qty per DeviceTotal Points per Device Type
1UPS0
2PDU/RPP0
3CRAC/CRAH0
4ATS0
5Fire Alarm Panel0
6Leak Detection System0
7Generators0
8Building Management Control System0
9Emergency Master Control System0
10Power Meters0
11PDU Strips0
12Environmental Sensors0
13Battery Monitoring System0
14Chiller Plan0
15Others (AHU, Circuit Breakers, etc)0
New Total0

AHU

AHU Profile
ModbusSNMPBACNET
MONITORING POINTS
Unit Status
Space Temp
Outside Air Temp
Return Air Temp
Supply Air Temp
Cooling Capacity
Heating Capacity
Economizer Percentage
Pump Speed
Space Pressure
Space Relative Humidity
Space Dew Point
Return Relative Humidity
Return Dew Point
Cool On
Free Cool On
SETPOINTS
Supply Set Point
Space Set Point
Hum Set Point
ALARMS
Leak Alarm
High Temp (Return)
Low Temp (Return)
Hi Hum (Return)
Low Hum (Return)
Loss of Airflow
Loss of Flow
Comp 1 OL
Comp 1 Low Press
Comp 1 High Press
Comp 2 OL
Comp 2 Low Press
Comp 2 High Press
Common Aalrm

ATS

ATS ProfileDevice Locations
ModbusSNMPBACNETATSROOMGRID LOCATIONMANUFACTURERMODEL
MONITORING POINTSX
preferredX

back up

Source 1 Open/Closed
Source 1 Voltage
Source 1 Current
Source 2 Open/Closed
Source 2 Volatge
Source 2 Current
Voltage Phase A-BDevice QtyPoints per deviceTotal
Voltage Phase B-CAdd these:350
Voltage Phase C-AInput KW
Voltage Phase A-NInput KW/Hr
Voltage Phase B-NOutput KW/Hr
Voltage Phase C-N
Current Phase A
Current Phase B
Current Phase C
kVA Total
kW Total
KVAR Total
Power Factor
Normal Breaker
Emergency Breaker
ALARMS
Normal Under Volatage
Normal Over Voltage
Emerg Under Voltage
Emerg Over Voltae
Under Frequency
Over Frequency
Exerciser Fail
Phase Rotation Error
Voltage Ibalance
Common Alarm

ATS Example

Battery Monitor

Battery Monitoring Profile
ModbusSNMPBACNETBattery MonitorROOMGRID LOCATIONMANUFACTURERMODEL
MONITORING POINTS
String 1 Voltage
String 1 Current
String 1 Temp
String 2 Voltage
String 2 Current
String 2 Temp
String 3 Voltage
String 3 Current
String 3 Temp
ALARMS
Common Alarm
High Current
Low Current
High Voltage
Low Voltage
High Temp
Low Temp

Breakers

Breaker Profile
ModbusSNMPBACNET
MONITORING POINTS
Breaker Status
Breaker Voltage
Breaker Current
ALARMS
Common Alarm

Chillers

Chiller Profile
ModbusSNMPBACNET
MONITORING POINTS
CHWS Temp
CHWR Temp
CWS Temp
CWR Temp
Chiller Status
CHW Pump Status
CW Pump Stauts
Flow Switch
Compressor Pressure
Compressor Current
Compressor Voltage
SETPOINTS
CHWS Setpotint
CHWR Setpoint
CWS Setpoint
CWR Setpoint
ALARMS
Common Alarm
Compressor Alarm
High Temp Alarm
Low Temp Alarm
Pump Alarm

CRAC

CRAC Profile
ModbusSNMPBACNETCRACROOMGRID LOCATIONMANUFACTURERMODEL
MONITORING POINTS
Unit Status
Fan Status
Space Temp
Return Air Temp
Supply Air Temp
Cooling Capacity
Heating Capacity
Space Pressure (Static Pressure)
Space/Return Relative Humidity
Cool On
Free Cool On
SETPOINTS
Supply Set Point
Space Set Point
Hum Set Point
ALARMS
Leak Alarm
High Temp (Return)
Low Temp (Return)
Hi Hum (Return)
Low Hum (Return)
Loss of Airflow
Loss of Flow
Comp 1 OL
Comp 1 Low Press
Comp 1 High Press
Comp 2 OL
Comp 2 Low Press
Comp 2 High Press
Comp 2 High Press
Common Alarm

CRAC NEO Example

Diesel Fuel Monitor

Diesel Fuel Monitor Profile
MONITORING POINTSUnit DescriptionModbusSNMPBACNET
AlarmX
PreferredX

Secondary option

Trouble
Tank Level
Total Gallons
Fuel Level
Temperature

Diesel Fuel Monitor Example

Environmental Monitoring

Environmental Monitor Profile
MONITORING POINTSUnit DescriptionModbusSNMPBACNETRoomMANUFACTURERMODEL
AlarmX
Trouble
Temperature
Humidity
Sensor Offline

Environmental Monitor Example

Fire Protection

Fire Protection Profile
MONITORING POINTSUnit DescriptionModbusSNMPBACNET
Alarm
Trouble
AlarmX
Trouble
Tank Level
Total Gallons
Sprinkler SystemX
Alarm On/Off
Water On/Water Off

Fire Protection Example

Floor_Rack UPS

Floor or Rackmount UPS Profile
ModbusSNMPBACNETUPSROOMGRID LOCATIONMANUFACTURERMODEL
MONITORING POINTSX
Input Voltage Phase A-B
Input Voltage Phase B-C
Input Voltage Phase C-A
Input Current Phase A
Input Current Phase B
Input Current Phase C
Input kVA Total
Input kW Total
Input KWH Total
Input Power Factor
Input Power
Input KW
Input KW/Hr
Output Voltage A-B (L1)
Output Voltage B-C (L2)
Output Voltage C-A (L3)
Output Current Phase A
Output Current Phase B
Output Current Phase C
Output KVA Total
Power Factor
Frequency
Output KW Total
Output KWH Total
Output KW/Hr
Output Power Factor
Battery Voltage
ALARMS
On Bypass
On Battery
Battery Runtime remaining
Low Battery Shutdown
Inverter Fault
Rectifier Fault
Common Alarm

Floor_Rack UPS Example

Generators

Generator Profile
ModbusSNMPBACNETGeneratorROOMGRID LOCATIONMANUFACTURERMODEL
MONITORING POINTS
Voltage Phase A-B
Voltage Phase B-C
Voltage Phase C-A
Voltage Avg. L-L
Current Phase A
Current Phase B
Current Phase C
Current Avg 3 Phase
kVA Total
kW Total
kVAR Total
KVAh Total
Oil Pressure
Engine Temperature (Oil Temp)
Frequency
Engine Run Hours
Controls In Auto
Battery Voltage
Generator Tank Fuel Level
ALARMS
OverSpeed Alarm
OverCrank Alarm
Overload Alarm
Coolant Temperature
Low Coolant Level Alarm
Low Coolant Temp Alarm
High Coolant Temp Alarm
Common Alarm

Generators NEO Example

In-Rack PDU Strip

In-Rack Profile (Power Strip)
ModbusSNMPBACNETIn Rack PDUROOMGRID LOCATIONMANUFACTURERMODEL
MONITORING POINTSX
Current Phase A
Current Phase B
Current Phase C
Circuit 1 Amps
Circuit 2 Amps
Circuit 3 Amps
Circuit 4 Amps
Circuit 5 Amps
Circuit 6 Amps
Real Power KWsame point
Output Powersame point
ALARMS
Critical High Alarm (45%)
Critical Warning Alarm (40%)
Loadbank 1, 2, 3

In-Rack PDU Strip Example

PDU-RPP

PDU Profile
ModbusSNMPBACNETPDUROOMGRID LOCATIONMANUFACTURERMODELComment
MONITORING POINTSXX
Input Voltage Phase A-B
Input Voltage Phase B-C
Input Voltage Phase C-A
Input Current Phase A
Input Current Phase B
Input Current Phase C
Input kVA Total
Input kW Total
Input KWH Total
Input Power Factor
Input KW
Input KW/Hr
Output Voltage A-B (L1)
Output Voltage B-C (L2)
Output Voltage C-A (L3)
Output Current Phase A
Output Current Phase B
Output Current Phase C
Power Factor
Frequencyper panel48
Output KVA Totalper pdu25
Output KW Total73
Output KW/Hr
Output KWH Total
Output Power Factor
ALARMS
High Current
High Voltage
Common Alarm

PDU NEO Example

PDU_RPP Panel CKTS (42)

Panel Profile
ModbusSNMPBACNET
MONITORING POINTS
CT01
CT02
CT03
CT04
CT05
CT06
CT07
CT08
CT09
CT10
CT11
CT12
CT13
CT14
CT15
CT16
CT17
CT18
CT19
CT20
CT21
CT22
CT23
CT24
CT25
CT26
CT27
CT28
CT29
CT30
CT31
CT32
CT33
CT34
CT35
CT36
CT37
CT38
CT39
CT40
CT41
CT42
*Panel Phase A
*Panel Phase B
*Panel Phase C
*RealPower KW

PDU_RPP Panel CKTS Example

UPS

UPS Profile
ModbusSNMPBACNETUPSROOMGRID LOCATIONMANUFACTURERMODEL
MONITORING POINTS
Input Voltage Phase A-B
Input Voltage Phase B-C
Input Voltage Phase C-A
Input Current Phase A
Input Current Phase B
Input Current Phase C
Input kVA Total
Input kW Total
Input KWH Total
Input Power Factor
Input KWDevice QtyPoints per DeviceTotal
Input KW/Hr35
Output Voltage A-B (L1)
Output Voltage B-C (L2)
Output Voltage C-A (L3)
Output Current Phase A
Output Current Phase B
Output Current Phase C
Output KVA Total
Power Factor
Frequency
Output KW/Hr
Output KW Total
Output KWH Total
Output Power Factor
Battery Voltage
ALARMS
On Bypass
On Battery
Battery Runtime remaining
Low Battery Shutdown
Inverter Fault
Rectifier Fault
Common Alarm

UPS NEO Example

Water Leak Detection

Water Leak Detection Profile
MONITORING POINTSUnit DescriptionModbusSNMPBACNET
AlarmX
Trouble
Sprinkler System
Alarm On/Off
Water On/Water Off
Leak is Detected
Cable Break Alarm
Contamination is Detected

Water Leak Detection Example image1.png image2.png image3.png image4.png image5.png image6.png image7.png image8.png image9.png image10.png image11.png image12.png image13.png image14.png image15.png image16.png image17.png image18.png image19.png image20.png