Summary
| Exhibit A |
| Regional Data Centers (RDCs) and Information Technology Centers (ITCs) |
| Preliminary Device List Summary |
| Base Task and Optional Tasks |
| Site | Task Type | Estimated Total Device Qty Per Site | Estimated Total Number of Monitoring Points Per Site |
| Orlando RDC | Base | 90 | 1692 |
| Cleveland RDC | Optional Task 5.4.1 | 233 | 4587 |
| Brooklyn RDC | Optional Task 5.4.2 | 12 | 746 |
| Temple RDC | Optional Task 5.4.3 | 79 | 1539 |
| Little Rock RDC | Optional Task 5.4.4 | 23 | 1021 |
| AITC | Optional Task 5.5.1 | 56 | 681 |
| HITC | Optional Task 5.5.2 | 37 | 878 |
| PITC | Optional Task 5.5.3 | 6 | 161 |
| CRRC | Optional Task 5.5.4 | 57 | 1042 |
| Orlando RDC | Optional Task 5.5.5 | 90 | 1692 |
| Cleveland RDC | Optional Task 5.5.6 | TBD | TBD |
| Brooklyn RDC | Optional Task 5.5.7 | TBD | TBD |
| Temple RDC | Optional Task 5.5.8 | TBD | TBD |
| Little Rock RDC | Optional Task 5.5.9 | TBD | TBD |
| TOTAL | | 683 | 14039 |
Base Task Orlando RDC
| Exhibit A |
| Orlando Regional Data Center |
| 2500 S Lakemont Avenue, Room 134 A/B, Orlando, Florida, 32814 |
| Preliminary Device List |
| Base Task |
| Site Category: New Deployment of Data Center Facilities Monitoring Tool - Full Survey |
| Device Type # | Qty | Device Category Name | Manufacturer | Model# | Existing IP Address | Estimated Number of Monitoring Points Per Device | Total Number of Monitoring Points Per Device | Comments |
| 1 | 2 | UPS | Eaton | 93PM | Yes | 35 | 70 | |
| 2 | 2 | PDU/RPP | Eaton | EMS-PDU | Yes | 96 | 192 | |
| 3 | 14 | CRAC | APC | ACRC100/ACPDX21-86 | Yes/No | 25 | 350 | 12-Yes, 2-No |
| 4 | 0 | ATS | | | | | | |
| 5 | 0 | Fire Alarm Panel | | | | | | |
| 6 | 0 | Leak Detection System | | | | | | |
| 7 | 0 | Generators | | | | | | |
| 8 | 0 | Building Management Control System | | | | | | |
| 9 | 0 | Emergency Power Master Control System | | | | | | |
| 10 | 0 | Power Meters | | | | | | |
| 11 | 72 | PDU Strips | APC | 7563/7862/7863/7864/8861/8863 | Yes/No | 15 | 1080 | 7-Yes, 65-No |
| 12 | 0 | Environmental Sensors | | | | | | |
| 13 | 0 | Battery Monitoring System | | | | | | |
| 14 | 0 | Chiller Plant | | | | | | |
| TOTAL | 90 | | | | | | 1692 | |
Optionl Tsk 5.4.1 Cleveland RDC
| Exhibit A |
| Cleveland Regional Data Center |
| 1620 E 105th Street, Building Data Center North, Room BM-660, Cleveland, Ohio, 44106 |
| Preliminary Device List |
| Optional Task 5.4.1 |
| Site Category: New Deployment of Data Center Facilities Monitoring Tool - Full Survey |
| Device Type # | Qty | Device Category Name | Manufacturer | Model# | Existing IP Address | Estimated Number of Monitoring Points Per Device | Total Number of Monitoring Points Per Device | Comments |
| 1 | 0 | UPS | | | | | | |
| 2 | 12 | PDU/RPP | Eaton | | No | 96 | 1152 | |
| 3 | 10 | CRAC | Liebert | DH267W-AAEI | No | 25 | 250 | |
| 4 | 1 | ATS | APC | AP7721/AP8965 | No | 35 | 35 | Rack ATS |
| 5 | 0 | Fire Alarm Panel | | | | | | |
| 6 | 0 | Leak Detection System | | | | | | |
| 7 | 0 | Generators | | | | | | |
| 8 | 0 | Building Management Control System | | | | | | |
| 9 | 0 | Emergency Power Master Control System | | | | | | |
| 10 | 0 | Power Meters | | | | | | |
| 11 | 210 | PDU Strips | APC | AP8965 | No | 15 | 3150 | |
| 12 | 0 | Environmental Sensors | | | | | | |
| 13 | 0 | Battery Monitoring System | | | | | | |
| 14 | 0 | Chiller Plant | | | | | | |
| TOTAL | 233 | | | | | | 4587 | |
Optional Tsk 5.4.2 Brooklyn RDC
| Exhibit A |
| Brooklyn Regional Data Center |
| 800 Poly Place, Building 14, Brooklyn, New York, 11209 |
| Preliminary Device List |
| Optional Task 5.4.2 |
| Site Category: New Deployment of Data Center Facilities Monitoring Tool - Full Survey |
| Device Type # | Qty | Device Category Name | Manufacturer | Model# | Existing IP Address | Estimated Number of Monitoring Points Per Device | Total Number of Monitoring Points Per Device | Comments |
| 1 | 2 | UPS | Liebert | | Yes | 35 | 70 | |
| 2 | 6 | PDU/RPP | Liebert | | Yes/No | 96 | 576 | 4-Networked 2-Not Networked |
| 3 | 4 | CRAC | Liebert | | Yes/No | 25 | 100 | 3-Networked 1-Not Networked |
| 4 | 0 | ATS | | | | | | |
| 5 | 0 | Fire Alarm Panel | | | | | | |
| 6 | 0 | Leak Detection System | | | | | | |
| 7 | 0 | Generators | | | | | | |
| 8 | 0 | Building Management Control System | | | | | | |
| 9 | 0 | Emergency Power Master Control System | | | | | | |
| 10 | 0 | Power Meters | | | | | | |
| 11 | 0 | PDU Strips | | | | | | |
| 12 | 0 | Environmental Sensors | | | | | | |
| 13 | 0 | Battery Monitoring System | | | | | | |
| 14 | 0 | Chiller Plant | | | | | | |
| TOTAL | 12 | | | | | | 746 | |
Optional Task 5.4.3 Temple RDC
| Exhibit A |
| Temple Regional Data Center |
| 1901 Veterans Memorial Drive, Building 222, Room 106, Temple, Texas, 76504 |
| Preliminary Device List |
| Optional Task 5.4.3 |
| Site Category: New Deployment of Data Center Facilities Monitoring Tool - Full Survey |
| Device Type # | Qty | Device Category Name | Manufacturer | Model# | Existing IP Address | Estimated Number of Monitoring Points Per Device | Total Number of Monitoring Points Per Device | Comments |
| 1 | 0 | UPS | | | | | | |
| 2 | 4 | PDU/RPP | Eaton | EMS-PDU | Yes | 96 | 384 | |
| 3 | 3 | CRAC | Liebert | CW181DC1A1A149 | No | 25 | 75 | No NIC Cards |
| 4 | 0 | ATS | | | | | | |
| 5 | 0 | Fire Alarm Panel | | | | | | |
| 6 | 0 | Leak Detection System | | | | | | |
| 7 | 0 | Generators | | | | | | |
| 8 | 0 | Building Management Control System | | | | | | |
| 9 | 0 | Emergency Power Master Control System | | | | | | |
| 10 | 0 | Power Meters | | | | | | |
| 11 | 72 | PDU Strips | APC | AP8965 | Yes | 15 | 1080 | |
| 12 | 0 | Environmental Sensors | | | | | | |
| 13 | 0 | Battery Monitoring System | | | | | | |
| 14 | 0 | Chiller Plant | | | | | | |
| TOTAL | 79 | | | | | | 1539 | |
Optnl Tsk 5.4.4 Little Rock RDC
| Exhibit A |
| Little Rock Regional Data Center |
| 2200 Fort Roots Drive, Building 102, Room 104, North Little Rock, Arkansas, 72114 |
| Preliminary Device List |
| Optional Task 5.4.4 |
| Site Category: New Deployment of Data Center Facilities Monitoring Tool - Full Survey |
| Device Type # | Qty | Device Category Name | Manufacturer | Model# | Existing IP Address | Estimated Number of Monitoring Points Per Device | Total Number of Monitoring Points Per Device | Comments |
| 1 | 2 | UPS | Eaton | 9395 | Yes | 35 | 70 | |
| 2 | 6 | PDU/RPP | Eaton | EMS-RPP | Yes | 96 | 576 | |
| 3 | 15 | CRAC | DataAire | gForceIR/gForce | No | 25 | 375 | |
| 4 | 0 | ATS | | | | | | |
| 5 | 0 | Fire Alarm Panel | | | | | | |
| 6 | 0 | Leak Detection System | | | | | | |
| 7 | 0 | Generators | | | | | | |
| 8 | 0 | Building Management Control System | | | | | | |
| 9 | 0 | Emergency Power Master Control System | | | | | | |
| 10 | 0 | Power Meters | | | | | | |
| 11 | 0 | PDU Strips | | | | | | |
| 12 | 0 | Environmental Sensors | | | | | | |
| 13 | 0 | Battery Monitoring System | | | | | | |
| 14 | 0 | Chiller Plant | | | | | | |
| TOTAL | 23 | | | | | | 1021 | |
Optional Task 5.5.1 AITC
| Exhibit A |
| Austin Information Technology Center (AITC) |
| 1615 Woodward Street, Austin, TX 78772 |
| Preliminary Device List |
| Optional Task 5.5.1 - Additional Devices |
| Site Category: Existing Deployment of Data Center Facilities Monitoring Tool - Partial Survey |
| Device Type # | Qty | Device Category Name | Manufacturer | Model# | Existing IP Address | Estimated Number of Monitoring Points Per Device | Total Number of Monitoring Points Per Device | Comments |
| 1 | 0 | UPS | | | | | | |
| 2 | 0 | PDU/RPP | | | | | | |
| 3 | 0 | CRAC | | | | | | |
| 4 | 5 | ATS | Unknown | Unknown | Unknown | 35 | 175 | Accessible through existing DMC interface |
| 5 | 0 | Fire Alarm Panel | | | | | | |
| 6 | 1 | Leak Detection System | Liebert | Liquitect | No | 6 | 6 | 160D |
| 7 | 0 | Generators | | | | | | |
| 8 | 0 | Building Management Control System | | | | | | |
| 9 | 0 | Emergency Power Master Control System | | | | | | |
| 10 | 0 | Power Meters | Schneider Electric | Unknown | No | | | |
| 11 | 50 | PDU Strips with Environmental Sensors | Various | | No | 10 | 500 | |
| 12 | 0 | Environmental Sensors | Unknown | Unknown | Yes | | | For Data Center Racks and HVAC Systems in Telecom Closets |
| 13 | 0 | Battery Monitoring System | Eaton | Cellwatch | No | | | 24 batteries |
| 14 | 0 | Chiller Plant | Trane | CVHF1070 | No | | | |
| TOTAL | 56 | | | | | | 681 | |
Optional Task 5.5.2 HITC
| Exhibit A |
| Hines Information Technology Center (HITC) |
| 5000 South 5th Avenue, Building 215, Hines, IL 60141 |
| Preliminary Device List |
| Optional Task 5.5.2 - Additional Devices |
| Site Category: Existing Deployment of Data Center Facilities Monitoring Tool - Partial Survey |
| Device Type # | Qty | Device Category Name | Manufacturer | Model# | Existing IP Address | Estimated Number of Monitoring Points Per Device | Total Number of Monitoring Points Per Device | Comments |
| 1 | 0 | UPS | | | | | | |
| 2 | 0 | PDU/RPP | APC | OG-PDRPPNX10/OG-PD80G6FK1-M1 | | | | |
| 3 | 19 | CRAC | Liebert/Schneider/Vertiv | DH267WVAAOGS984/Uniflair/DA085UP1AD299A | No | 25 | 475 | Available via new DDC System. 17 Lieberts, 1 Schneider, 1 Vertiv |
| 4 | 0 | ATS | | | | | | |
| 5 | 2 | Fire Alarm Panel | Fike/Kiddie | Cheeta XI | No | 6 | 12 | Determine dry contract status |
| 6 | 0 | Leak Detection System | | | | | | Multi Zone |
| 7 | 4 | Generators/Control Panel | Cummins/GE | 900DFJC/Series 90-30 PLC | No | 60 | 240 | Available via new DDC System |
| 8 | 0 | Building Management Control System | | | | | | |
| 9 | 0 | Emergency Power Master Control System | | | | | | |
| 10 | 0 | Power Meters | | | | | | |
| 11 | 0 | PDU Strips | | | | | | |
| 12 | 0 | Environmental Sensors | | | | | | |
| 13 | 1 | Battery Monitoring System | Eaton | Cellwatch | No | 30 | 30 | 3 Battery Chains. Available via new DDC System |
| 14 | 0 | Chiller Plant | Trane | CVHF1070 | No | | | |
| 15 | 1 | Mechanical Plant Control | Unknown | Unknown | No | 25 | 25 | Available via new DDC System |
| 16 | 1 | Sprinkler System | Viking | Totak Pak 2 Preaction System | No | 6 | 6 | Available via new DDC System |
| 17 | 6 | Transient Voltage Suppression Switches | Liebert/Surgelogic | | No | 10 | 60 | Require extensive new conduit/cabling to monitor |
| 18 | 3 | Air Handler Unit | American Auto-Matrix | | No | 10 | 30 | Available via new DDC System |
| TOTAL | 37 | | | | | | 878 | |
Optional Task 5.5.3 PITC
| Exhibit A |
| Philadelphia Information Technology Center (PITC) |
| 5000 Wissahickon Avenue, Philadelphia, PA 19144 |
| Preliminary Device List |
| Optional Task 5.5.3 - Additional Devices |
| Site Category: Existing Deployment of Data Center Facilities Monitoring Tool - Partial Survey |
| Device Type # | Qty | Device Category Name | Manufacturer | Model# | Existing IP Address | Estimated Number of Monitoring Points Per Device | Total Number of Monitoring Points Per Device | Comments |
| 1 | 0 | UPS | | | | | | |
| 2 | 0 | PDU/RPP | | | | | | |
| 3 | 0 | CRAC | | | | | | |
| 4 | 1 | ATS | Unknown | | | 35 | 35 | Modbus connection |
| 5 | 0 | Fire Alarm Panel | | | | | | |
| 6 | 1 | Leak Detection System | | | | 6 | 6 | |
| 7 | 0 | Generators | | | | | | |
| 8 | 0 | Building Management Control System | | | | | | |
| 9 | 0 | Emergency Power Master Control System | | | | | | |
| 10 | 0 | Power Meters | | | | | | |
| 11 | 0 | PDU Strips | | | | | | |
| 12 | 0 | Environmental Sensors | | | | | | |
| 13 | 0 | Battery Monitoring System | | | | | | |
| 14 | 2 | Chiller Plant & Chilled Water Loop Pumps | Unknown | | | 50 | 100 | Chiller 4 & 5. Bacnet connection |
| 18 | 2 | Air Handler Unit | Unknown | | | 10 | 20 | Existing and new |
| TOTAL | 6 | | | | | | 161 | |
Optional Task 5.5.4 CRRC
| Exhibit A | | | | | | | | |
| Capital Regional Readiness Center (CRRC), Martinsburg, West Virginia | | | | | | | | |
| 221 Butler Ave, Bldg. 511, Martinsburg, WV 25405 | | | | | | | | |
| Preliminary Device List | | | | | | | | |
| Optional Task 5.5.4 - Additional Devices | | | | | | | | |
| Site Category: Existing Deployment of Data Center Facilities Monitoring Tool - Partial Survey | | | | | | | | |
| Device Type # | Qty | Device Category Name | Manufacturer | Model# | Existing IP Address | Estimated Number of Monitoring Points Per Device | Total Number of Monitoring Points Per Device | Comments |
| 1 | 0 | UPS | Unknown | Unknown | Yes | 35 | 0 | |
| 2 | 0 | PDU/RPP | Unknown | Unknown | Yes | 96 | 0 | |
| 3 | 0 | CRAC | Unknown | Unknown | Unknown | 25 | 0 | |
| 4 | 4 | ATS | Unknown | Unknown | Unknown | 35 | 140 | |
| 5 | 1 | Fire Alarm Panel | Unknown | Unknown | Yes | 6 | 6 | |
| 6 | 1 | Leak Detection System | Unknown | Unknown | Unknown | 6 | 6 | |
| 7 | 0 | Generators | Unknown | Unknown | Yes | 60 | 0 | |
| 8 | 1 | Building Management Control System | Unknown | Unknown | Yes | 100 | 100 | |
| 9 | 1 | Emergency Power Master Control System | Unknown | Unknown | Yes | 100 | 100 | |
| 10 | 0 | Power Meters | Unknown | Unknown | Yes | 35 | 0 | |
| 11 | 40 | PDU Strips | APC | 7811/7863/7961 | Yes | 15 | 600 | |
| 12 | 9 | Environmental Sensors | Unknown | Unknown | Yes | 10 | 90 | |
| TOTAL | 57 | | | | | | 1042 | |