3 - Team Room Phone Locations.pdf

PDF 1 MB Posted

Attached to
Voice Over IP (VOIP) Phone Purchase and Installation
Solicitation number
RFP MAT 200000001386 5
Issued by
Van Buren County, Michigan

About this file

This is an electrical power plan document for an Athletic Team Room project at Mattawan Consolidated Schools in Mattawan, Michigan, prepared by Tower Pinkster architectural and engineering firm. The project involves comprehensive electrical infrastructure installation including power distribution, lighting, HVAC systems, security systems, and technology connectivity. The plan specifies the installation of panelboard P1 with a 400-ampere main breaker fed from transformer TX-P1, operating at 208/120 volts, three-phase, four-wire service. The document details circuit requirements for 84 individual breakers including receptacles, hand dryers, HVAC equipment, lighting systems, and specialized systems such as door security devices, cameras, and technology equipment. The total connected load is approximately 43,566 VA with an estimated demand of 42,536 VA and total amperage of 154 amperes at the main panel. The plan includes grounding specifications with multiple ground rods and connections to building structural steel, cable conduit routing requirements, and device mounting locations throughout the facility.

The electrical specifications require the contractor to perform all cutting, patching, and final connections to owner-provided equipment while maintaining fire ratings at all penetrations. The document specifies GFI protection on designated circuits, conduit sizing requirements ranging from 1/2-inch to 4-inch, and coordination requirements with furniture shop drawings and technology plans. Security system conduit work must be consolidated by type and routed to the central IT rack location with proper labeling. All exterior conduit must be buried below grade using trenching and directional boring methods to eliminate exposed exterior wiring. The plan includes load classifications for hand dryers (3,600 VA), technology systems (720 VA), HVAC equipment (various circuits), lighting (3,396 VA), and general receptacle loads (12,060 VA), with specific demand factors applied to calculate actual electrical requirements.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

M

HD HD

HD HD

JJ

J

J

JJ

J J J

PRJ

A/B/...

PRJ

A/B/...

M M

T

CR

CR

C R

C R

CR

CR

CR

CR

DC

D C

D C

DC

DC

D C

D C

D C

D C

E S

ES

E S

ES

E S

E S

E S

E

SDC

DC

DC

M M M

S S

S S

M

T.O.W.

110' - 0"

T.O.W.

110' - 0"

T.O.WALL

110' - 8"

T.O.WALL

110' - 8"

2" CONDUIT TO

DATA RACK

2" C.

COORDINATE DEVICE

LOCATIONS WITH

LAPTOP STAND.

MOUNT FLUSH INSIDE

ENCLOSURE.

2-GANG

DATA

FIRST FLOOR

100' - 0"

2" C.

1" C.

SPEAKER

PROVIDE SINGLE

GANG BOX.

TYPICAL

1" C.

18" X 18" X 6" NEMA 3R

HOFFMAN JUNCTION BOX

WITH HINGED COVER

CRESTRON AV

TOUCH SCREEN

3-GANG BOX

120V

/5

/3

P1

PANEL

SPD

8320V

480/277V

TX-PRI

GROUND BUS

10' SPACING (TYP)

WATER MAIN

#3/0 Cu GND (TYP)

10'-0"

GROUND ROD

CONTRACTOR TO TERMINATE

CONDUCTORS AT TRANSFORMER, UTILITY

METER TO BE INSTALLED ON

TRANSFORMER. COORDINATE WITH

UTILITY.

M

TO UTILITY POLE

145A

4 #600, 4" PVC

3 #1/0 15 kV 133%

PRIMARY W/CONCENTRIC

NEUTRAL, 4" PVC

24A

EXISTING

PANEL

P2

4 #1/0, 2" PVC

#3/0 Cu GND (TYP)

10'-0"

GROUND ROD PROVIDE NEW GROUND

ROD AND NEW BUILDING

GROUND BAR.

GROUND BUS

SERVICE

TRANSFORMER

GND.

TO BUILDING

STEEL

CONNECTIONS

TO GROUND MAT

NOTES:

1. ALL GROUNDING CONDUCTOR CONNECTIONS TO MAIN BUILDING GROUND BUS SHALL

BE EXOTHERMIC WELDED.

2. FOR QUANTITIES AND LOCATIONS AT STEEL COLUMNS, SEE FLOOR PLANS. FOR EACH

COLUMN CONNECTION, PROVIDE 1"C, 1#3/0 GROUND WIRE TO MAIN BUILDING BUS. (TYP.

FOR EVERY OTHER COLUMN @ PERIMETER)

3. ALL NEW TRANSFORMERS SHALL HAVE SEPARATE GROUND ROUTED BACK TO THE MAIN

SERVICE PANEL, BONDING TO NEARBY STEEL WILL NOT BE ACCEPTABLE.

TO MAIN

WATER PIPE

#3/0 GND. 1" C

TYPICAL

ELECTRICAL GROUND BUS

TO TRANSFORMER

GNDS.

IT GROUND BUS

120 VOLT

N

L

STARTER

MANUAL MOTOR

DISCONNECT

FAN BY DIV. 23

SWITCH W/

CONTACTS BY DIV. 23

OR TEMP. CONTROL

REVERSE ACT. STAT.

G FAN

#12

120V, 1Ø

208V, 3Ø

#10

FURNACE

CONDENSING

UNIT

MANUAL MOTOR

STARTER SWITCH

W/ LOCKOUT

6- #18

3- #18

T

30/3 NFDS

NEMA 3R

DOOR

CONTACTS

TO SECURITY CONTROL PANEL

CEILING

1/2" C

1" C

1" CONDUIT BETWEEN

WHERE LESS THAN 60"

REFER TO SECURITY DOOR

SCHEDULE FOR DEVICE

REQUIREMENTS AT EACH DOOR

3/4" FLEX CONDUIT TO BE RUN INSIDE

DOOR FRAMES TO STRIKEPLATE

3/4" CONDUIT

ELECTRIC STRIKE

RECESSED IN FRAME

CARD READER SINGLE GANG BOX

POWER SUPPLIES TO BE CENTRALLY LOCATED NEXT TO NEAREST

ACCESS CONTROL PANEL UNLESS OTHERWISE INDICATED.

REFER TO TECHNOLOGY PLAN FOR EXACT LOCATIONS.

SEAL ALL CONDUITS THROUGH CEILING

CORNER BRACKET

AND FASTENERS

EXTERIOR PENETRATION SHALL

BE CONCEALED BY MOUNTING

BRACKET. RUN 1" CONDUIT

BACK TO IT RACK.

3/4" LIQUID TIGHT CONDUIT

SHALL BE RUN FROM INTERIOR

MOUNTED SG BACKBOX

THROUGH PENETRATION TO

CAMERA MOUNTING BRACKET.

CAMERA MOUNTING

BRACKET

REFER TO FLOOR PLAN OR

CAMERA SCHEDULE FOR

ELEVATION REQUIREMENTS.

CEILING

EXTERIOR CORNER MOUNT CAMERAS

P1

BUILDING

GROUND BAR

TX-P1

10' GROUND

ROD (TYPICAL)

WH-1

F-3

F-2

F-1

ACCU-1 ACCU-2 ACCU-3

STORAGE

HOME LOCKER

ROOM

VISITOR

LOCKER ROOM

TRAINING

STORAGE

TLT

OFFICIALS

WOMENS

RESTROOMS

J.C./MECH.

MENS

RESTROOMS

CONCESSIONS

ELEC/IT

P1- 6

GFI

P1- 7

GFI

P1- 8

GFIP1- 9

GFI

P1- 10

GFI

P1- 11

GFI

P1- 12

GFI

P1- 13

GFI

P1- 14

GFIP1- 15 P1- 16

P1- 4

P1- 3 P1- 2

P1- 5

P1- 5

P1- 5

P1- 5

P1- 33

P1- 17

P1- 18

GFI

P1- 18

GFI

2 2

2 2

P1- 19

GFI

P1- 19

GFI

P1- 19

GFI

P1- 19

GFI

P1- 19

GFI

P1- 21

P1- 20

P1- 19

P1- 22 P1- 23

P1- 26

GFI

P1- 25P1- 24

P1- 27

GFI

P1- 27 P1- 27

P1- 27

P1- 27 P1- 27

P1- 31

P1- 60 P1- 31

P1- 60

P1- 31

P1- 33

P1- 33

P1- 62P1- 62

P1- 37

GFI

P1- 30

GFI

P1- 30

GFI

P1- 32

GFI

P1- 32

GFI

P1- 32

GFI

P1- 35

P1- 34

WP

P1- 34

WP

P1- 34

WP

P1- 29

WP

P1- 29

WP

P1- 28

WP

P1- 28

WP

P1- 47,49P1- 43,45P1- 39,41

E 101

W

W

P1- 26

GFI

P1- 48P1- 44 P1- 46

P1- 7

GFI

P1- 8

GFI

P1- 50

GFI

P1- 1

GFIP1- 14

GFI

P1- 52

GFI

P1- 51

GFI

#3/0 GND. WIRE

(TYPICAL)

IT GROUND BAR

4'x8' FIRE RATED

PLYWOOD

WALL MOUNTED

PHONE

WALL MOUNTED

PHONE

WALL MOUNTED

PHONE

UTILITY PAD

P1- 31

GFI

P1- 33

GFI

19' - 0"

W

W

60/2 NEMA 3R NFD

TYPICAL OF 3

#6 WIRE, 1" C.

P1- 56

GFI

WALL MOUNTED

PHONE

CP-1

P1- 53

EF-1 EF-2 EF-3P1- 46

WP

P1- 28

FEED FROM LOAD

SIDE OF GFI OUTLET

E a s t K a la m a z o o A v e n u e S u it e

K a la m a z o o M ic h ig a n

-5

.3

.6

P H

O N

E

.3

.6

F A

X

T O

W E

R P

IN

K

S T

E R

.C O

M

A L L R

IG

H

T S

R E

S E

R V

E D

E a s t

F u lt o n S tr e e t, S u it e

G ra n d R a p id s M ic h ig a n

.4

.9

P H

O N

E

.4

.5

F A

X

S H

E E

T T

IT

L

E

S H

E E

T N

U M

B E

R

O W

N E

R P

R O

J E

C T

T

IT

L E

D A

T E

P O

W E

R P

L A

N

-1

.4

E

M A

Y

A T

H L E

T

IC

T E

A M

R O

O M

M a tt a w a n M

I

M A

T T

A W

A N

C O

N S

O L

ID

A T

E D

S C

H O

O L S

GENERAL ELECTRICAL NOTES

ELECTRICAL KEYED NOTES

1 ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR ALL CUTTING

AND PATCHING REQUIRED FOR NEW WORK OR WHERE DEVICES ARE

REMOVED AND NOT REPLACED.

2 PROVIDE FINAL CONNECTION TO ALL OWNER/CONTRACTOR PROVIDED

EQUIPMENT. COORDINATE RECEPTACLE SIZES AND TYPE WITH

EQUIPMENT, ADJUST CIRCUIT SIZE AS REQUIRED.

3 PATCH ALL PENETRATIONS AS REQUIRED TO MAINTAIN FIRE RATING.

4 REFER TO INTERIOR ELEVATIONS, SECTIONS, ARCHITECTURAL

ELEVATIONS AND RELATED DRAWINGS FOR EXACT DEVICE LOCATIONS

AND MOUNTING HEIGHTS. WHERE DEVICES ARE MOUNTED UNDER OR

ABOVE TACK BOARDS, DOORS, WINDOWS, OR ANY PIECE OF

EQUIPMENT, THE ELECTRICAL DEVICE SHALL BE CENTERED AS SHOWN.

COORDINATE LOCATION OF FURNITURE CONNECTIONS AND/OR

RECEPTACLES AND DATA RACEWAYS WITH APPROVED FURNITURE

SHOP DRAWINGS, FINAL CONNECTIONS TO FURNITURE BY ELECTRICAL

CONTRACTOR.

5 SEAL ALL CONDUITS PENETRATING ATTIC SPACE TO ENSURE NO AIR

TRANSFER.

6 HOME RUN ALL DATA CONDUITS BACK TO IT RACK. LABEL EACH

CONDUIT AND DEVICE. CONSOLIDATE ALL SECURITY CONDUITS BY

TYPE, I.E. CAMERA CONDUITS AND DOOR SECURITY CONDUITS.

7 ALL CONDUITS SHALL ENTER/EXIT THE BUILDING BELOW GRADE.

PROVIDE TRENCHING AND DIRECTIONAL BORING AS REQUIRED. CUT

AND PATCH AS REQUIRED. NO EXPOSED CONDUIT SHALL BE ALLOWED

ON EXTERIOR OF BUILDING.

8 PROVIDE 4" HOUSEKEEPING PADS FOR TRANSFORMER. PROVIDE

FLEXIBLE CONNECTION TO TRANSFORMERS AND SIMILAR EQUIPMENT

PER SPECIFICATIONS.

1 PROVIDE 1" CONDUIT FROM DOOR CONTACT BACK TO IT RACK.

2 PROVIDE ROUGH IN FOR AUTOMATIC FLUSH VALVE. COORDINATE

LOCATION WITH SHOP DRAWING. THERE SHALL BE NO EXPOSED

CONDUIT OR JUNCTION BOX. PROVIDE ALL REQUIRED LOW VOLTAGE

WIRING BETWEEN VALVE AND TRANSFORMER.

3 FEED FROM GFI TYPE CIRCUIT BREAKER. LABEL DEVICE ON COVER

PLATE.

4 PROVIDE 2-GANG FLUSH MOUNTED BACKBOX AND 1" CONDUIT BACK

TO DATA RACK FOR WIRELESS ACCESS POINT.

5 PROVIDE WEATHER PROOF ENCLOSURE IN ATTIC SPACE WITH 1"

CONDUIT HOME RUN BACK TO IT RACK. REFER TO DETAIL

6 PROVIDE 1" CONDUIT TO IT RACK FOR CAMERA.

7 PROVIDE WALL MOUNTED LOCKING DESK. GLOBAL INDUSTRIAL

#WB249997. PROVIDE POWER AND DATA DEVICE CENTER INSIDE.

DEVICES SHALL BE FLUSH MONTED IN WALL AND FLUSH INSIDE THE

CABINET. MODIFY BACK OF CABINET AS REQUIRED FOR JUNCTION

BOXES.

1/4" = 1'-0"E 101

2 TYPICAL LOCKER ROOM ELEVATIONNOTES:

HAND DRYER - 3600 VA 100.00% 3600 VA

TECHNOLOGY - 720 VA 100.00% 720 VA

RECEPTACLE - 12060 VA 91.46% 11030 VA TOTAL ESTIMATED DEMAND... 118 A

POWER - 23222 VA 100.00% 23222 VA TOTAL CONNECTED LOAD (A): 121 A

Other 568 VA 100.00% 568 VA TOTAL ESTIMATED DEMAND: 42536 VA

LIGHTING - 3396 VA 100.00% 3396 VA TOTAL CONNECTED LOAD: 43566 VA

HVAC - 0 VA 0.00% 0 VA

LOAD CLASSIFICATION CONNECTED LOAD DEMAND FACTOR ESTIMATED DEMAND PANEL TOTALS

TOTAL AMPS: 154 A 102 A 109 A

TOTAL LOAD: 18419 VA 12194 VA 12953 VA

83 SPARE 20 1 0 0 1 20 SPARE 84

81 SPARE 20 1 0 0 1 20 SPARE 82

79 SPARE 20 1 0 0 1 20 SPARE 80

77 SPARE 20 1 0 0 1 20 SPARE 78

75 SPARE 20 1 0 0 1 20 SPARE 76

73 SPARE 20 1 0 0 1 20 SPARE 74

71 SPARE 20 1 0 0 1 20 SPARE 72

69 SPARE 20 1 0 0 1 20 SPARE 70

67 SPARE 20 1 0 0 1 20 SPARE 68

65 SPARE 20 1 0 0 1 20 SPARE 66

63 -- -- -- 0 0 1 20 SPARE 64

61 -- -- -- 0 540 1 20 62

59 PUMP HOUSE PANEL P2 100 3 0 540 1 20 60

57 SPARE 20 1 0 0 1 20 SPARE 58

55 180 1 20 RECEPTACLE - 56

53 HVAC - 20 1 0 436 1 20 Other 54

51 RECEPTACLE - 20 1 180 180 1 20 RECEPTACLE - 52

49 -- -- -- 3037 180 1 20 RECEPTACLE - 50

47 POWER - ACCU-3 20 2 3037 0 1 20 HVAC - EF-3 48

45 -- -- -- 3037 180 1 20 HVAC - EF-2 46

43 POWER - ACCU-2 20 2 3037 0 1 20 HVAC - EF-1 44

41 -- -- -- 3037 538 1 20 LIGHTING - 42

39 POWER - ACCU-1 20 2 3037 720 1 20 LIGHTING - 40

37 RECEPTACLE - 20 1 180 1225 1 20 LIGHTING - 38

35 RECEPTACLE - 20 1 180 1045 1 20 LIGHTING - 36

33 RECEPTACLE - 20 1 720 540 1 20 RECEPTACLE - 34

31 RECEPTACLE - 20 1 720 540 1 20 RECEPTACLE - 32

29 RECEPTACLE - 20 1 360 360 1 20 RECEPTACLE - 30

27 RECEPTACLE - 20 1 1080 540 1 20 RECEPTACLE - 28

25 HAND DRYER - 20 1 900 360 1 20 RECEPTACLE - 26

23 HAND DRYER - 20 1 900 900 1 20 HAND DRYER - 24

21 HVAC - F-2 20 1 0 900 1 20 HAND DRYER - 22

19 RECEPTACLE - 20 1 5900 0 1 20 HVAC - F-1 20

17 HVAC - F-3 20 1 0 360 1 20 RECEPTACLE - 18

15 RECEPTACLE - 20 1 180 180 1 20 RECEPTACLE - 16

13 RECEPTACLE - 20 1 180 360 1 20 RECEPTACLE - 14

11 RECEPTACLE - 20 1 180 180 1 20 RECEPTACLE - 12

9 RECEPTACLE - 20 1 180 180 1 20 RECEPTACLE - 10

7 RECEPTACLE - 20 1 360 360 1 20 RECEPTACLE - 8

5 RECEPTACLE - 20 1 720 180 1 20 RECEPTACLE - 6

3 RECEPTACLE - 20 1 180 180 1 20 RECEPTACLE - 4

1 RECEPTACLE - 20 1 180 180 1 20 RECEPTACLE - 2

CIRCUIT DESCRIPTION

TRIP

(A) POLES A B C POLES

TRIP

(A) CIRCUIT DESCRIPTION

ADDED ACCESSORIES: SPD I.C. RATING: 35,000

LOCATION: FIRST FLOOR AMPS: 400 A MB , ULSE RATED FED FROM: TX-P1

PANEL: P1 MOUNTING: SURFACE VOLTAGE: 208/120V, 3PH, 4W

PANELBOARD "P1" LOAD SCHEDULE

SCALE: NONE

ONE LINE

SCALE: NONE

BUILDING GROUND DETAIL

SCALE: NONE

EXHAUST FAN CONTROL

SCALE: NONE

FURNACE/CONDENSING UNIT

SCALE: NONE

TYPICAL SECURITY DOOR DETAIL

SCALE: NONE

EXTERIOR CORNER MOUNT CAMERA

1/4" = 1'-0"

POWER PLAN

ISSUED FOR DATE

Tony Nuismer

WP

Tony Nuismer

WP

Tony Nuismer

WP

Tony Nuismer

WP

Tony Nuismer Wall Phone (WP) - 4

Sheets
ES 101 - ELECTRICAL SITE PLAN
E 101 - POWER PLAN
E 201 - LIGHTING PLAN

File details come from the government source that posted it. Updated .