3-SSLC SW Pump Stations Blair Jordan 100 FOR BID.pdf
PDF 8 MB Posted
- Solicitation number
- PN 2025-21
- Issued by
- Salt Lake County, Utah
About this file
These are engineering design drawings and specifications for the City of South Salt Lake's Storm Water Pump Stations Upgrades project, focusing on two specific locations: Blair Street and Jordan River pump stations. The project, issued for bid in August 2025, involves comprehensive electrical, structural, and civil upgrades to existing storm water infrastructure. The design documents, prepared by Hansen, Allen & Luce Design Team, include detailed site plans, electrical one-line diagrams, control wiring schematics, and technical specifications for demolition and reconstruction of the pump stations.
The project encompasses electrical system improvements, including new electrical controls, variable frequency drives (VFDs), motor controls, and updated power distribution panels for both pump stations. The designs specify new submersible pumps, electrical enclosures, conduit systems, and integration with existing infrastructure. Electrical components will be housed in NEMA 3R enclosures, with provisions for cellular antenna, RTU (Remote Telemetry Unit) connections, and float switch controls. The drawings indicate careful consideration of existing site conditions, with plans for reusing some existing conduits and mounting infrastructure while implementing modern electrical and control systems to improve the storm water pump stations' reliability and functionality.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 1-SSL Blair St and Jordan River - Public Notice.pdf | ||
| 2-SSL Blair St and Jordan River SPECS FOR BID.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
CITY OF SOUTH SALT LAKE
STORM WATER PUMP STATIONS
UPGRADES - BLAIR ST & JORDAN RIVER
AUGUST 2025
ISSUED FOR BID
NIG SREENE
AARON C.
SPENCER
7426128-2202
STATE OF UTAH
RE
G I
ST
ER
ED
PROFESSIONAL ENGINEER
8/21/2025
NIG SREENE
AARON C.
SPENCER
STA T E O F UTA H
G
IS
TE
RE
D PROFESS IONAL ENG
I NE ER
SPENCER
IS
TE
RE
D PROFESS IONAL ENG
INEER
SPENCER
IS
TE
RE
D PROFESS IONAL ENG
SPENCER
IS
TE
RE
D PROFESS IONAL ENG
SPENCER
IS
TE
RE
D PROFESS IONAL ENG
SPENCER
IS
TE
RE
D PROFESS IONAL ENG
SPENCER
IS
TE
RE
D PROFESS IONAL ENG
SPENCER
IS
TE
RE
D PROFESS IONAL ENG
SPENCER
IS
TE
RE
D PROFESS IONAL ENG
SPENCER
IS
TE
RE
D PROFESS IONAL ENG
A AMPERE
AFF ABOVE FINISHED FLOOR
AI ANALOG INPUT
AIC AMPS INTERRUPTING CAPACITY
AFD ADJUSTABLE FREQUENCY DRIVES
AO ANALOG OUTPUT
AS AIR SUPPLY
ATS AUTOMATIC TRANSFER SWITCH
BC BYPASS CONTACTOR
C CONDUIT
CB CIRCUIT BREAKER
CL2 CHLORINE
CON CONTACTOR
CU COPPER, BARE
CV CONTROL VALVE
DCS DISTRIBUTED CONTROL SYSTEM
DI DISCRETE INPUT
DO DISCRETE OUTPUT
DV/DT DIFFERENTIAL VOLTAGE/TIME
DWG DRAWING
ETM ELAPSED TIME METER
EOL ELECTRONIC OVERLOAD
EXIST EXISTING
FA FOUL AIR
FC FAIL CLOSED
FE FLOW ELEMENT
FLA FULL LOAD AMPS
FS FLOW SWITCH
FVNR FULL VOLTAGE NON-REVERSING
FW FINISHED WATER
GFCI GROUND FAULT CIRCUIT
GFP GROUND FAULT PROTECTION
GND GROUND
GPD GALLONS PER DAY
GPH GALLONS PER HOUR
GPM GALLONS PER MINUTE
GRS GALVANIZED RIGID STEEL
H, HI HIGH
H2S HYDROGEN SULFIDE
HMI HUMAN MACHINE INTERFACE
HOA HAND-OFF-AUTO
HOR HAND-OFF-REMOTE
I CURRENT
IC INSTRUMENTATION CABLE
ICR INTERMITTENT CYCLE REACTOR
IO INPUT/OUTPUT
INTRINSICALLY SAFE RELAY
JB JUNCTION BOX
L, LO LOW
LAN LOCAL AREA NETWORK
LC LOOP CONTROLLER
LCL LEVEL CONTROL, LOW
LCP LOCAL CONTROL PANEL
LOS LOCK-OUT-STOP
LR LOCAL/REMOTE
LS LEVEL SWITCH
LTC LIQUID TIGHT FLEXIBLE CONDUIT
M MOTOR
MA MANUAL/AUTO, MILLIAMP
MAX MAXIMUM
MC MANUFACTURER'S CABLE
MCB MAIN CIRCUIT BREAKER
MCC MOTOR CONTROL CENTER
MCP MOTOR CIRCUIT PROTECTOR
MFR(S) MANUFACTURER(S)
MGD MILLION GALLONS PER DAY
MGL MILLIGRAMS PER LITER
MH MANHOLE
MIN MINIMUM
MOV MOTOR OPERATED VALVE
MTU MASTER TELEMETRY UNIT
NEC NATIONAL ELECTRICAL CODE
NECA NATIONAL ELECTRICAL CONTRACTOR
NORMALLY OPEN TIMED CLOSED
NPW NON-POTABLE WATER
NS NITROGEN SUPPLY
NTS NOT TO SCALE
NTU TURBIDITY
OF OVERFLOW
OIT OPERATOR INTERFACE TERMINAL
OL OVERLOAD
OO ON/OFF (MAINTAINED)
OR OFF-REMOTE
P PHASE OR POLE
PB PULL BOX
PCP PROCESS CONTROL PANEL
PFR PHAS/POWER FAILURE RELAY
PI PULSE INPUT
PLC PROGRAMMABLE LOGIC
PLI PLANT INFLUENT
PKG PACKAGE
PMP PUMP
PNL
PO PULSE OUTPUT
PPG POUNDS PER GALLON
PPH POUNDS PER HOUR
PPM PARTS PER MILLION
PR PAIR
PRES PRESSURE
PS PRESSURE SWITCH
PSH PRESSURE SWITCH, HIGH
PSI POUNDS PER SQUARE INCH
PV PROCESS VARIABLE
RAS RETURN ACTIVATED SLUDGE
RW RAW WATER
RCL REMOTE 1/0
RF RADIO FREQUENCY
RIO REMOTE INPUT/OUTPUT
RS RAW SEWAGE
RSP RAW SEWAGE PUMP
RST RESET
RTD RESISTANCE TEMPERATURE
RTU REMOTE TELEMETRY UNIT
RWT REFLECTED WAVE TRAP
SEQ SERVICE ENTRANCE EQUIPMENT
SES SERVICE ENTRANCE SECTION
SLC SINGLE LOOP CONTROLLER
SLOS START-LOCK-OFF-STOP
SMC SUBMERSIBLE MANUFACTURER
SO2 SULFUR DIOXIDE
SP SET POINT
SPC SPARE CONDUIT
SPR SPARE
SS START/STOP
SSS SOLID STATE STARTER
ST SHUNT TRIP
TC TELEPHONE CABLE
TS TEMPERATURE SWITCH
TYP TYPICAL
UG UNDERGROUND
V VOLT
VFD VARIABLE FREQUENCY DRIVE
W WATT, WIRE
WAS WASTE ACTIVATED SLUDGE
WP WEATHERPROOF
XFMR TRANSFORMER
XMTR TRANSMITTER
ZS POSITION SWITCH
ISR
NOTC
PANEL
TDOE TIME DELAY ON ENERGIZE
CPT CONTROL POWER TRANSFORMER
GES GROUNDING ELECTRODE SYSTEM
O.C. ON CENTER
CPM CUSTOMER POWER MONITORING
ES EMERGENCY STOP
N NEUTRAL
G GROUND
CONTROLLER
DETECTOR
CABLE
(SOFT START)
INTERRUPTER
L, LO
SHORT CIRCUIT CURRENTISC
ELR END OF LINE RESISTER
ML MIXED LIQUOR
ASSOCIATION
TSP TWISTED SHIELDED PAIR
TVSS TRANSIENT VOLTAGE
SURGE SUPPRESSION
ABBREVIATIONS
N: NUMBER - SIZE OF NEUTRAL CONDUCTOR(S) PER CONDUIT
P: NUMBER - SIZE OF PHASE CONDUCTORS PER CONDUIT
SIZE OF EACH CONDUIT IN INCHES
G: NUMBER- SIZE OF GROUND CONDUCTOR(S) PER CONDUIT
NUMBER OF CONDUITS
3.G: 4 4.
5.
P: 2 N:1 3 2.
1.
14 = #14 AWG COPPER
12 = #12 AWG COPPER
10 = #10 AWG COPPER
8 = #8 AWG COPPER
6 = #6 AWG COPPER
4 = #4 AWG COPPER
2 = #2 AWG COPPER
1/0 = 1/0 AWG COPPER
2/0 = 2/0 AWG COPPER
3/0 = 3/0 AWG COPPER
4/0 = 4/0 AWG COPPER
250 = 250 KCMIL COPPER
350 = 350 KCMIL COPPER
500 = 500 KCMIL COPPER
750 = 750 KCMIL COPPER
KEY TO CONDUCTOR SIZE & TYPE
FEEDER DESIGNATION LOGIC
EXPOSED CONDUIT
EXISTING EXPOSED CONDUIT
UNDERGROUND CONDUIT
EXISTING UNDERGROUND CONDUIT
BARE COPPER GROUND CONDUCTOR
FUTURE
NEW ELECTRICAL EQUIPMENT
DETAIL VIEW OR MATCHING
CAPPED UNDERGROUND CONDUIT OR STUBBUP
ELECTRICAL LINETYPES
CONDUIT DROP
CONDUIT RISE
SYMBOL DESCRIPTION
QUADRAPLEX RECEPTACLE
DUPLEX RECEPTACLE
GROUND FAULT CIRCUIT INTERRUPTER RECEPTACLE.
ISOLATED GROUND TYPE DUPLEX RECEPTACLE
SPECIAL PURPOSE OR WELDING OUTLET.
POWER
SYMBOL DESCRIPTION
DUPLEX RECEPTACLE, RECESSED FLOOR MOUNTED
DUPLEX RECEPTACLE, RECESSED CEILING MOUNTED
QUADRAPLEX RECEPTACLE, RECESSED FLOOR MOUNTED
QUADRAPLEX RECEPTACLE, RECESSED CEILING MOUNTED
GFCI
WEATHERPROOF CONVENIENCE OUTLETWP
HOME RUN TO PANEL - INDICATING 2 #12, #12 GND, 3/4" CONDUIT
HOME RUN TO PANEL - INDICATING NUMBER OF CONDUCTORS - #12
HOME RUN TO PANEL SHOWING BRANCH CIRCUIT NUMBERS.
OR AS SHOWN.
X-1,3,5
OR AS SHOWN.
HATCH MARKS IN CONDUIT RUN DENOTES NUMBER OF CONDUCTORS
UNLESS NOTED OTHERWISE. UNMARKED CONDUITS SHALL BE 3/4"
SIZE OF CONDUCTORS TO BE #12 AWG CONDUCTORS IN CONDUIT
IN CONDUIT. LONG HATCH MARK DENOTES GROUND CONDUCTOR.
WITH 3 #12.
FLUSH FLOOR DEVICE BOX
THERMOSTAT
M MOTOR, X = HORSE POWER
F CEILING EXHAUST FAN
DENOTES EXISTING EQUIPMENT OR DEVICES(E)
X
VOLTAGE RATING
NEMA ENCLOSURE
FUSE (NF-NO FUSE)
SIZE (AMPS)
DISCONNECT SWITCH.
POLES
ELECTRICAL PANEL, POWER OR LIGHTING
METER BASE
COMBINATION MOTOR STARTER, SEE SPECS
J JUNCTION BOX
DEVICE. IF NOT NOTED, THE MOUNTING HEIGHT TO CENTER SHALL BE
MOUNTING HEIGHT ABOVE FINISHED FLOOR TO CENTER OF OUTLET
AS DETAILED OR SPECIFIED.
THIS NOTATION ADJACENT TO WALL OUTLET SYMBOL DENOTES
+0'-0"
MANUAL MOTOR STARTER
MANUAL MOTOR STARTER WITH OVERLOADS
sM s T
SINGLE POLE SWITCH
3 WAY SWITCH
4 WAY SWITCH
s s 3 s 4
LIGHTING FIXTURE TYPE - SEE FIXTURE SCHEDULE.F#
DM DAMPER MOTOR
TELEPHONE JACK OUTLET. 1'-6". (SINGLE, DOUBLE, QUAD)
COMMUNICATION/DATA JACK. CONDUIT TO ABOVE CEILING.
DATA OR CATHODE RAY TUBE (CRT) TERMINAL OUTLET. +1'-6".
OWNER TO RUN WIRING.
(SINGLE, DOUBLE)2
2 POSITION SELECTOR SWITCH,
TERMINAL LUG OR STRIP
NODE OR CONNECTION
MC CONNECTION
THERMAL OVERLOAD RELAY
CIRCUIT BREAKER OR MOTOR CIRCUIT PROTECTOR, SHOWN WITH TRIP
POSITION LEGEND: X=CLOSED O=OPEN
NORMALLY OPEN CONTACT
GENERATOR
NORMALLY CLOSED PUSH BUTTON
TEMPERATURE SWITCH
LEVEL FLOAT SWITCH
FLOW SWITCH
GROUND CONNECTION
FUSEHOLDER OR FUSEBLOCK
SOLID STATE REDUCED VOLTAGE STARTER
HARMONIC FILTER
BOND TO METALLIC WATER PIPE
LOCKOUT STOP PUSH BUTTON
VARIABLE FREQUENCY DRIVE
MOTOR STARTER OR CONTACTOR COIL
ELAPSED TIME METER
ALARM RELAY
UTILITY METER
TRANSFORMER
FULL VOLTAGE NONREVERSING (FVNR) MOTOR STARTER OR
CONTACTER NUMBER DESIGNATES NEMA SIZE.
EOL ELECTRONIC OVERLOAD RELAY
LTC CONNECTION
MOTOR, X = HORSEPOWER
DEVICE LOCATED AT REMOTE LOCATION.
FUSE
ICTO TIMER RELAY CONTACT INSTANTANEOUS CLOSE TIME DELAY OPEN.
NOTC
NORMALLY CLOSED CONTACT
3 POSITION SELECTOR SWITCH HAND - OFF - AUTO,
POSITION LEGEND: X=CLOSED O=OPEN
NORMALLY OPEN PUSH BUTTON
CURRENT TRANSFORMER
LIMIT SWITCH
PRESSURE SWITCH LOW
EMERGENCY STOP PUSH BUTTON (MAINTAINED)
RTU, PLC, OR RIO CONTACT
SSRV
VFD
HF
ETM
BEACON ALARM LIGHT. LETTER INDICATES COLOR: R=RED,
A=AMBER, B=BLUE, G=GREEN
PILOT LIGHT. LETTER INDICATES COLOR: R=RED, A=AMBER,
B=BLUE, G=GREEN
TIME DELAY RELAY
T.C.
CONTACT - TIME DELAY
I.C. - T.O. = NORMALLY OPEN WITH INSTANT CLOSING AND
TIME DELAY OPENING.
T.C.-T.O. = NORMALLY OPEN W/TIME DELAY CLOSING AND
CONTACT - TIME DELAY
T.O.-T.C. = NORMALLY CLOSED WITH TIME DELAY OPENING AND
TIME DELAY CLOSING AFTER DEENERGIZATION.
I.O.-T.C. = NORMALLY CLOSED WITH INSTANT OPENING AND TIME DELAY
POLES
AMPS
AMPS / POLES
SCHEMATICS & DIAGRAMS
T.C. = NORMALLY OPEN W/TIME DELAY CLOSING.
TIME DELAY OPENING AFTER DEENERGIZATION.
T.0.
T.C. = NORMALLY CLOSED WITH TIME DELAY OPENING.
CLOSING.
PRESSURE SWITCH HIGH
DISCONNECT SWITCH SHOWN WITH RATING AND NUMBER OF POLES.
H O A
ON OFF
xo oox
TIMER RELAY CONTACT NORMALLY OPEN TIME DELAY CLOSE.
X
X
UM
R RELAY
TD
AR
ETM
M
CT'S
X
BOND TO METALLIC WATER PIPE
BOND TO BUILDING STEEL
RATING AND NUMBER OF POLES.
DESCRIPTIONSYMBOL
FLUORESCENT LIGHT FIXTURE, SEE FIXTURE SCHEDULE.
LIGHTING
SYMBOL DESCRIPTION
EMERGENCY LIGHTING, SEE FIXTURE SCHEDULE.
LIGHTING FIXTURE TYPE - SEE FIXTURE SCHEDULE.F#
SINGLE POLE SWITCHs
3 WAY SWITCHs3
WALL MOUNTED MOTION SWITCH - DUAL TECHNOLOGYsm
MOTOR RATED TOGGLE SWITCHs T
DIGITAL OVERRIDE SWITCHsD
RECESSED CEILING MOUNTED SPEAKER BY OTHERSSP
WALL MOUNTED MOTION SENSOR
CEILING MOUNTED MOTION SENSOR
CEILING-MOUNTED EXIT LIGHT, SEE FIXTURE SCHEDULE
WALL-MOUNTED EXIT LIGHT, SEE FIXTURE SCHEDULE
RECESSED CAN LIGHT, SEE FIXTURE SCHEDULE
ANALYZING INDICATING TRANSMITTER
ANALYZER ELEMENT
COMBUSTIBLE GAS DETECTOR
LEVEL ELEMENT
OVER TORQUE SWITCH
PRESSURE INDICATING TRANSMITTER
CONDUCTIVITY INDICATING TRANSMITTER
FLOW ELEMENT
FLOW INDICATING TRANSMITTER
MOTOR OPERATED VALVE OR GATE
SOLENOID OPERATED VALVE
TEMPERATURE ELEMENT
PRESSURE SWITCH
LEVEL SWITCH
CONTROLS & INSTRUMENTS
SYMBOL DESCRIPTION
AE
PS
AIT
FE
FS
LE
LS
ME
LT
PIT
TE
TS
TT
SV
CIT
FIT
LEVEL INDICATING TRANSMITTERLIT
OS
MV
FLOW SWITCH
LEVEL TRANSMITTER
MOISTURE ELEMENT
TEMPERATURE SWITCH
TEMPERATURE TRANSMITTER
CGD
ZS LIMIT OR POSITION SWITCH
SCHEMATICS & DIAGRAMS
DESCRIPTIONSYMBOL
SINGLE POLE SWITCH WITH PILOT LIGHTs P
CONDUIT NUMBER6.
NIG SREENE
I:\
7\
JO
RD
AN
R
IV
ER
-B
LA
IR
\0
1- D
W G\
EL
EC
\S H
EE
T\
7- E-
1-
(JR
-B
).d w g, /2 7/
:3
9:
P M
, k br ow n
PANEL BLAIR STREET
BUS AMPS: 125
VOLTAGE: 120/240 V 1Ø 3W MAIN BREAKER AMPS 100
ENCLOSURE: NEMA 3R BREAKER RATING % 80%
CIRCUIT BREAKER TYPE: BOLT-ON MOUNTING: SURFACE
INTERRUPTING CAPACITY: 10 KAIC COVER TYPE: DOOR-IN-DOOR
LOCATION: BLAIR STREET
BRANCH CIRCUIT BREAKER CONNECTION
DESCRIPTION
PHASE
DESCRIPTION
CONNECTION BRANCH CIRCUIT BREAKER
NOTES # AMP P. LOAD (VA) L1 L2 LOAD (VA) P. AMP # NOTES
1 30 2 2040 PUMP 1 3040 CONTROLLER 1000 1 20 2
3 -- -- 2040 ------ 2220 RECEPTACLE 180 1 20 4
5 30 2 2040 PUMP 2 2040 SPARE 1 20 6
7 -- -- 2040 ------ 2040 SPARE 1 20 8
9 20 1 SPARE 0 SPARE 1 20 10
11 20 1 SPARE 0 SPARE 1 20 12
PHASE SUBTOTALS (VA) 5080 4260
PHASE TOTALS (KVA) 5.1 4.3
PHASE TOTALS @ 120V (AMPS) 42.3 35.5
NOTES:
G PROVIDE WITH INTEGRAL SURGE PROTECTOR
PANEL JORDAN RIVER
BUS AMPS: 125
VOLTAGE: 120/240 V 1Ø 3W MAIN BREAKER AMPS 125
ENCLOSURE: NEMA 3R BREAKER RATING % 80%
CIRCUIT BREAKER TYPE: BOLT-ON MOUNTING: SURFACE
INTERRUPTING CAPACITY: 10 KAIC COVER TYPE: DOOR-IN-DOOR
LOCATION: JORDAN RIVER
BRANCH CIRCUIT BREAKER CONNECTION
DESCRIPTION
PHASE
DESCRIPTION
CONNECTION BRANCH CIRCUIT BREAKER
NOTES # AMP P. LOAD (VA) L1 L2 LOAD (VA) P. AMP # NOTES
1 60 2 5040 PUMP 1 6040 CONTROLLER 1000 1 20 2
3 -- -- 5040 ------ 5220 RECEPTACLE 180 1 20 4
5 60 2 5040 PUMP 2 5040 SPARE 1 20 6
7 -- -- 5040 ------ 5040 SPARE 1 20 8
9 20 1 SPARE 0 SPARE 1 20 10
11 20 1 SPARE 0 SPARE 1 20 12
PHASE SUBTOTALS (VA) 11080 10260
PHASE TOTALS (KVA) 11.1 10.3
PHASE TOTALS @ 120V (AMPS) 92.3 85.5
NOTES:
G PROVIDE WITH INTEGRAL SURGE PROTECTOR
C102 1 4 -#14
3/4" G: 1 -#14
C202 1 1"ANTENNA WIRE
C203 1 6 -#14
EXISTING
CONDUIT
G: 1 -#14
P104 1 P: 3 - #8
3/4"N: NONE
G: 1 - #10
P105 1 PUMP SUPPLIED CABLE
P106 1 P: 2 - #12
3/4"N: NONE
G: 1 - #12
P109 1 P: 2 - #12
EXISTING
CONDUITN: NONE
G: 1 - #12
P110 1 P: 3 - #8
EXISTING
CONDUITN: NONE
G: 1 - #10
P111 1 PUMP SUPPLIED CABLE
POWER CONDUIT SCHEDULECONTROL CONDUIT SCHEDULE
NIG SREENE
I:\
7\
JO
RD
AN
R
IV
ER
-B
LA
IR
\0
1- D
W G\
EL
EC
\S H
EE
T\
7- E-
2-
(JR
-B
).d w g, /2 7/
:3
9:
P M
, k br
SCALE: 1/8"=1'-0"
BLAIR STREET ELECTRICAL SITE PLAN
10 5 0 10 20
(E)POWER POLE
DRAWING NOTES
1 INSTALL GROUND RODS. SEE ONE-LINE DIAGRAM.
JUNCTION BOX
AS REQUIRED
PUMP STATION
TO RTU
C202
CELLULAR ANTENNA
NEW ELECTRICAL METER/MAIN
WP GFCI. RUN (2) #12, (1) #12 GND IN 3/4" CONDUIT TO
20A / 1P METER/MAIN BREAKER
NEW ELECTRICAL CONTROLS ENCLOSURE. MOTOR
CONTACTORS, AND RTU WITHIN ENCLOSURE. RUN (2) #12,
(1) #12 GND IN 3/4" CONDUIT TO 20A / 1P METER/MAIN
BREAKER FOR CONTROLLER.
(E) CONDUIT TO BE REUSED
4 POUR CONCRETE PAD OVER THE EXISTING CONDUIT.
ENSURE THE EXISTING CONDUIT IS EXPOSED THROUGH
THE NEW CONCRETE PAD AT ITS CURRENT LOCATION.
INSTALL UNISTRUT FRAME IN THE CONCRETE TO SUPPORT
THE ENCLOSURE AND PROVIDE MOUNTING FOR THE
ANTENNA. ROUTE EXISTING CONDUIT TO THE ENCLOSURE.
SEE UNISTRUT SUPPORT DETAIL AND UNISTRUT DETAIL IN
CIVIL SHEETS.
NIG SREENE
I:\
7\
JO
RD
AN
R
IV
ER
-B
LA
IR
\0
1- D
W G\
EL
EC
\S H
EE
T\
7- E-
1-
(JR
-B
).d w g, /2 7/
:3
9:
P M
, k br
SCALE: 1/8"=1'-0"
JORDAN RIVER ELECTRICAL SITE PLAN
10 5 0 10 20
(E)POWER POLE
AND TRANSFORMER
TO RTU
C202
CELLULAR ANTENNA
(E)METER TO REMAIN
(E)MAIN DISCONNECT TO REMAIN
(E)CONDUIT
(E)CONDUIT TO BE REUSED
DRAWING NOTES
WP GFCI. RUN (2) #12, (1) #12 GND IN 3/4" CONDUIT TO2
NEW ELECTRICAL CONTROLS ENCLOSURE. VFD'S, AND RTU
WITHIN ENCLOSURE. RUN (2) #12, (1) #12 GND IN 3/4"
CONDUIT TO 20A / 1P BREAKER FOR CONTROLLER.
NEW PANELBOARD
20A / 1P BREAKER.
NIG SREENE
I:\
7\
JO
RD
AN
R
IV
ER
-B
LA
IR
\0
1- D
W G\
EL
EC
\S H
EE
T\
7- E-
2-
(JR
-B
).d w g, /2 7/
:3
9:
P M
, k br
SCALE: 1/2"=1'-0"
BLAIR STREET PUMP STATION POWER PLAN
DRAWING NOTES
1 REMOVE EXISTING ELECTRICAL BOX. SEE REMODEL DRAWING.
SHARED CONDUIT WITH POWER CONDUCTORS.
SUPPORT PUMP CORD TO CEILING OR WALL OF VAULT.
SCALE: 1/2"=1'-0"
BLAIR STREET PUMP STATION CONTROLS PLAN
E-101
E-101SCALE: 1/2"=1'-0"
BLAIR STREET PUMP STATION DEMOLITION PLAN
E-101
(E)ELECTRICAL
CONTROL BOX
JUNCTION BOX
AS REQUIRED
SEE CONTINUATION
ON E-101
P111
P111
JUNCTION BOX
AS REQUIRED
LSHLSL
C102
TO CONTROLS
ENCLOSURE
C203
(E)METER AND
DISCONNECT BELOW
(E)CONTROL PANEL
(E)POWER POLE
SHARED
CONDUIT
EXISTING CONDUIT
TO BE REUSED EXISTING CONDUIT
TO BE REUSED
NIG SREENE
I:\
7\
JO
RD
AN
R
IV
ER
-B
LA
IR
\0
1- D
W G\
EL
EC
\S H
EE
T\
7- E-
1-
(JR
-B
).d w g, /2 7/
:3
9:
P M
, k br
SCALE: 1/2"=1'-0"
JORDAN RIVER PUMP STATION POWER PLAN
DRAWING NOTES
1 REMOVE EXISTING ELECTRICAL BOX. SEE REMODEL DRAWING.
NEW ELECTRICAL JUNCTION BOX FOR PUMP MOTOR
CONNECTIONS AND CONTROLS AS REQUIRED.
SUPPORT PUMP CORD TO CEILING OR WALL OF VAULT.
SCALE: 1/2"=1'-0"
JORDAN RIVER PUMP STATION CONTROLS PLAN
E-102
E-102
SCALE: 1/2"=1'-0"
JORDAN RIVER PUMP STATION DEMOLITION PLAN
E-102
2 P110
TO VFD
P105
LSH
LSL
LOW LEVEL FLOAT
TO CONTROLS
ENCLOSURE
C203
C102
HIGH LEVEL FLOAT
SHARED CONDUIT
SHARED CONDUIT WITH POWER CONDUCTORS.4
NIG SREENE
I:\
7\
JO
RD
AN
R
IV
ER
-B
LA
IR
\0
1- D
W G\
EL
EC
\S H
EE
T\
7- E-
2-
(JR
-B
).d w g, /2 7/
:3
9:
P M
, k br
VERTICAL CONDUIT
FIBER FILLER
SEALING COMPOUNDSEALING COMPOUND
HORIZONTAL CONDUIT
EXTERIOR WALL SURFACE OR
OZ/GEDNEY CSML WALL
SEAL OR LMK SEAL - SEE SPECS.
W/ NON-SHRINK
SPECS. PATCH
WALL-SEE
LC
CORE DRILL
* GROUT
LC SEALING
RING
NEOPRENE
HOUSEKEEPING CURB REQUIRED AT ALL INTERIOR WALL
CONDUIT RISERS SHALL BE COUPLED SO THAT SINGLE
LOCATIONS FOR SINGLE AND MULTIPLE CONDUIT RISERS.
CONDUITS ARE SIX FEET APART MINIMUM.
4"
3"
WASHDOWN AREA FLOOR
AS DIRECTED BY ENGINEER.
ARMOR ROD BACKING
CORE DRILL EXISTING
FLOOR OR WALL.
CALK SEALANT OR NON-SHRINK GROUT.
SECURE TAGS TO CONDUIT
WITH NYLON CABLE TIES
ALMETEX TYPE
EZ-V TAG TITLES
(BLACK OR YELLOW)
C1005
ALMETEX TYPE TH
TAG HOLDER
SECURE TAGS TO CONDUIT
WITH NYLON CABLE TIES
CONDUIT
SCALE: NONE
FLOOR PENETRATIONS1
E-501
EXISTING WALL/DRY
SCALE: NONE
DAMMING AND POURING2
E-501
TYPICAL CONDUIT SEAL
SCALE: NONE
CONCRETE HOUSEKEEPING CURB DETAIL3
E-501
SCALE: NONE
WALL SEAL OR WASHDOWN FLOOR4
E-501
UNDERGROUND CONDUIT
SCALE: NONE
CONDUIT MARKING SYSTEM5
E-501 TYPICAL OF ALL CONDUITS
1-1/4"
NOTES:
"EQUIPMENT NUMBER"
4. PROVIDE BLANK NAMEPLATES FOR ALL SPARE
3. ATTACH ALL NAMEPLATES WITH STAINLESS
VERTICAL CENTERLINE OF THE CUBICAL OR DEVICE.
2. ALL NAMEPLATES TO BE MOUNTED ON THE
1. ALL LETTERS TO BE 1/4" UNLESS NOTED
AND FUTURE DEVICES.
STEEL SCREWS.
OTHERWISE.
"EQUIPMENT NAME"
3" OR 4"
SCALE: NONE
NAMEPLATE DETAIL6
E-501 TYPICAL OF ALL EQUIPMENT
CONDUIT
SQUARE FENDER
WASHER TYPICAL
TYPICAL
LOCK WASHER,
NUT, TYPICAL
1/2" ALL THREAD
UNISTRUT CONDUIT
CLAMP, TYPICAL
CHANNEL
UNISTRUT
P1000
1/2" ALL THREAD
SCALE: NONE
CONDUIT SUPPORT DETAIL7
E-501 TYPICAL
(FLUSH WITH FINISHED
FLOOR OR FOUNDATION)
CONDUIT COUPLING
FINISHED FLOOR
OR EQUIPMENT
FOUNDATION
THREADED BRASS
PLUG
SCALE: NONE
FLUSH CONDUIT TERMINATION8
E-501 TYPICAL
NIG SREENE
I:\
7\
JO
RD
AN
R
IV
ER
-B
LA
IR
\0
1- D
W G\
EL
EC
\S H
EE
T\
7- E-
1-
(JR
-B
).d w g, /2 7/
:3
9:
P M
, k br
TO COMPUTER/POSITION CONTROLLER, GROUND
SHIELD AT CONTROLLER END ONLY.
(FOR TE SHIELD GROUND, SEE CONTROL CONNECTIONS)
ANALOG CONTROL SIGNAL
GROUND ROD
CONDUIT/4-WIRE CABLE
(L3)
GND.
(L1)
(L2)
VFD
GND.MOTOR FRAME
@ EACH END
BOND CONDUIT TO GROUND
GROUND PER
LOCAL CODES
SHIELD/CONDUIT
SHIELD/CONDUIT
(T3)
GND.
(T1)
(T2)
RGS W/ EXTERNAL
FLEX GROUNDING
JUMPER
P1200 SERIES CLAMP.
CLAMPED W/ UNISTRUT
BRANCH CIRCUIT CONDUIT
DOUBLE GALVANIZED
UNISTRUT P1001
CHANNEL.
ROD ANCHORED TO
CLAMP AS REQUIRED.
DECK WITH BEAM
CEILING STEEL OR
5/8" GALVANIZED THREADED
SWIVEL CEILING/
BEAM ATTACHMENT BEAM ATTACHMENT
SWIVEL CEILING/
SCALE: NONE
VFD GROUNDING DIAGRAM1
E-502
SCALE: NONE
CONDUIT SUPPORT DETAIL2
E-502 TYPICAL
LOCKWASHER
ANCHOR WITH NUT AND
3/4" SS ADHESIVE
AT A MAX OF 3'-0" O.C.
PROVIDE INTERMEDIATE SUPPORTS
WHERE LENGTH EXCEEDS 3'-0"
CONDUIT CLAMP (TYP.)
LENGTH TO SUIT
SCALE: NONE
CONDUIT SUPPORT DETAIL3
E-502 TYPICAL
MATCH BOLT
HOLE PATTERN OF
CONNECTOR TO
EQUIPMENT.
LONG BARREL LUGS (TYP.)
BURNDY HY GROUND
COMPRESSION FITTINGS
BURNDY HY GROUND
COMPRESSION FITTINGS
SCALE: NONE
EQUIPMENT GROUNDING CONNECTION4
E-502 TYPICAL
MOTOR FEEDER
COMPRESSION
RING LUG
SEALANT USE IN WET
HEAT-ACTIVATED MASTIC
MOTOR LEAD
LOCATIONS ONLY
POLYOLEFIN CAP
SHRINKABLE RAYCHEM
CROSS LINKED HEAT
LOCKNUT
ELECTRICAL ENCLOSURE
0-RING
CONNECTOR BODY
FERRULE
LIQUIDTIGHT FLEXIBLE METALLIC CONDUIT
COMPRESSION NUT
OR DEVICE
BUSHING WERE REQUIRED
INSULATED THROUGH
NOTES:
2. INSULATED BUSHING SHALL BE REQUIRED FOR
CONDUCTORS #4 OR LARGER.
1. PROVIDE LISTED GROUNDING TYPE CONNECTORS
WITH LUGS AND EXTERNAL BONDING JUMPER WHEN
CIRCUITS ARE RATED 20 AMPS OR MORE FOR 1/2",
MORE THAN 60 AMPS FOR 3/4" THROUGH 1-1/4",
AND FOR 1-1/2" AND LARGER WERE REQUIRED FOR
GROUNDING.
SCALE: NONE
TYPICAL MOTOR LEAD TERMINATION5
E-502 TYPICAL
SCALE: NONE
TYPICAL FLEXIBLE CONDUIT CONNECTION DETAIL6
E-502
NIG SREENE
I:\
7\
JO
RD
AN
R
IV
ER
-B
LA
IR
\0
1- D
W G\
EL
EC
\S H
EE
T\
7- E-
2-
(JR
-B
).d w g, /2 7/
:3
9:
P M
, k br
NOTES:
1. IN CORROSIVE AREAS PROVIDE STAINLESS STEEL U-CHANNEL.
2. OMIT POST BASE WHEN MOUNTING TO SIDE OF ABOVE GRADE STRUCTURE.
3. PROVIDE HARDWARE OF SAME MATERIAL AS U-CHANNEL.
SHALLOW U-CHANNEL.
P3300, AS MANUFACTURED
BY UNISTRUT OR EQUAL.
JUNCTION BOX.
MYERS HUB OR EQUAL.
CONDUIT CLAMP.
DOUBLE U-CHANNEL, P1001,
AS MANUFACTURED BY
UNISTRUT OR EQUAL.
AS MANUFACTURED
POST BASE, P2073 A, AS
MANUFACTURED BY
UNISTRUT OR EQUAL.
U-CHANNEL, P1000,
BY UNISTRUT OR EQUAL.
4 - 1/2"x4"
STAINLESS STEEL
ANCHOR BOLTS
PVC COATED GRC
SCALE: NONE
JUNCTION BOX MOUNTING DETAIL1
E-503
LONG BARREL LUGS (TYP.)
COMPRESSION FITTINGS
BURNDY HY GROUND
MIN.
1'-0" CONCRETE ENCASEMENT
3" MIN. ALL SIDES
M
IN
6"
FINISHED GRADE OR FLOOR
TO EQUIPMENT
PVC COATED RIGID
METAL CONDUIT,
FACTORY NINETY
PVC COATED RIGID
METAL COUPLING
PVC COATED RIGID
METAL CONDUIT
MALE PVC
ADAPTOR
CONDUIT
PVC COATED RIGID
METAL COUPLING
SCALE: NONE
BONDING LUG DETAIL2
E-503
SCALE: NONE
CONDUIT RISER DETAIL3
E-503 TYPICAL
REBAR
MAX. 1" CONDUIT
1" CLEAR MIN.
1" COVER MIN.
1" CONDUIT OR LARGER
METALLIC OR NON-
METALLIC
1" MIN. SLAB ON GRADE
3"
SCALE: NONE
CONDUIT PLACEMENT DETAIL4
E-503 TYPICAL
CONDUIT
FLASHING
BRANCH
CIRCUIT
TYP.
BOLT TO
NEW
ROOF
1-5/8"x1-5/8"
MOUNTING
CHANNEL
48"±
MOTOR
COMBINATION
DISCONNECT
STARTER
NEMA 3R
3/8" CONCRETE
ANCHORS WITH
SS BOLTS
SCALE: NONE
DISCONNECT STARTER DETAIL5
E-503
MOTOR COMBINATION
HATCH OPENING
FLOAT CABLE
SUBMERSIBLE LEVEL FLOAT
PVC CONDUIT
AND MALE ADAPTOR
PVC BELL END
CABLE WEIGHT
1OPERATING WATER LEVEL FOR INSTALLATION OF FLOATS WITHOUT A
CONCRETE DECK CONSTRUCT A 3/8"x12"x8" SS
PLATE SUPPORT ANCHORED TO WALL AT
MINIMUM 4 PLACES. WELD A 3/8"x6"x12" SS
GUSSET TO THE BOTTOM OF PLATE SUPPORT.
PVC COATED GRS COUPLING AND
CONDUIT TO VFD OVERSIZED TO RUN
SUBMERSIBLE PUMP CABLE TO VFD.
RUN CONDUIT WITHIN CONCRETE LID
WHERE PRACTICABLE.
SCALE: NONE
LEVEL FLOAT MOUNTING DETAIL6
E-503
(TYPICAL OF TWO)
TRANSDUCER CABLE. ORDER WITH
LENGTH TO REACH LEVEL METER.
VAULT WALL
WALL MOUNTED BRACKET.
EXTENDED AS REQUIRED.
LEVEL TRANSDUCER
PVC BELL END
1" PVC CONDUIT
SCALE: NONE
TRANSDUCER MOUNTING DETAIL7
E-503
SJE RHOMBUS 4 FLOAT BRACKET WITH
MOUNTING DEVICE AND STRAIN RELIEF
CONNECTORS TO MATCH FLOAT WIRE
CGB
NIG SREENE
I:\
7\
JO
RD
AN
R
IV
ER
-B
LA
IR
\0
1- D
W G\
EL
EC
\S H
EE
T\
7- E-
3-
(JR
-B
).d w g, /2 7/
:3
9:
P M
, k br
BACKFILL BORROW
IMPORTED GRANULAR
GRADE SS-1 TACK COAT
SAWCUT EXISTING ASPHALT TO 8" MINIMUM
6" TYP.
SURFACE COURSE,
AC-10, DM-3/4 CLASS IV
CONDUITS AS PER PLANS.
7" THICK BITUMINOUS
12" MIN.
3'- 0"
GRADE SS-1 TACK COAT
SAWCUT EXISTING ASPHALT
TO 8" MINIMUM
ASPHALT
EXISTING
210 JOINT SEALANT
SEAL WITH CRAFT-CO
LINE MARKER
EXISTING ASPHALT
02206 8" IN DEPTH - COMPACT
GRADE 1 UTBC.
EXISTING CONCRETE
CONDUIT INSTALLATION.
REMOVE STONES LARGER
THAN 1" OR OTHER HARD
TRENCH PRIOR TO
SMOOTH BOTTOM OF
BACKFILL BORROW
SAW-CUT & REMOVE
SIDEWALK SECTION
ENTIRE SECTION
18" MIN.
3'- 0"
LINE MARKER
COMPACT
GRADE 1 UTBC
IMPORTED GRANULAR
MATTER THAT COULD
DAMAGE CONDUIT FROM
AREAS ADJACENT TO
CONDUIT.
NEW CONCRETE
EXISTING BETWEEN
EXPANSION
JOINTS. REPLACE
PER CITY STANDARD
OR RED CONCRETE AS
INDICATED. MINIMUM
BEDDING SAND
3" AROUND EACH
CONDUIT.
OR RED CONCRETE AS
INDICATED. MINIMUM
BEDDING SAND
3" AROUND EACH
CONDUIT.
LINE MARKER
8" IN DEPTH - COMPACT
OTHER HARD MATTER THAT
BORROW SMOOTH BOTTOM OF
COULD DAMAGE CONDUIT FROM
STONES LARGER THAN 1" OR
INSTALLATION. REMOVE
TRENCH PRIOR TO CONDUIT
GRADE 1 UTBC
6" TYP.
7" THICK BITUMINOUS
AC-10, DM-3/4 CLASS IV
SURFACE COURSE,
ROADWAY RESTORATION
CURBS. DO NOT DISTURB CURBS.
INSTALL CONDUIT BENEATH AND
RESTORE AS DETAILED.
SIMILAR WHEN CROSSING EXISTING
18" MIN.
SAWCUT EXISTING ASPHALT TO 8" MINIMUMEXISTING CURB
DO NOT DAMAGE
SEAL WITH CRAFT-CO
210 JOINT SEALANT
GRADE SS-1 TACK COAT
IMPORTED GRANULAR BACKFILL
AREAS ADJACENT TO CONDUIT.
3'- 0"
OR RED CONCRETE AS
INDICATED. MINIMUM
BEDDING SAND
3" AROUND EACH
CONDUIT.
SCALE: NONE
TRENCH DETAIL-ROADWAY RESTORATION1
E-504
SCALE: NONE
TRENCH DETAIL-SIDEWALK RESTORATION2
E-504
SCALE: NONE
TRENCH DETAIL-ROADWAY RESTORATION3
E-504
SURFACE
WIREWAY
SURFACE
WIREWAY
2" MINIMUM
CLEARANCE
2" MINIMUM
CLEARANCE
SCALE: NONE
TERMINAL BLOCK CLEARANCE DETAIL4
E-504
HATCH OPENING
PVC COATED GRS COUPLING AND CONDUIT
TO VFD OVERSIZED TO RUN SUBMERSIBLE
S.S. HOOK AND ANCHOR
S.S. KELLUMS GRIP
MOTOR LEAD CABLE ORDER WITH
ENOUGH LENGTH TO REACH VFD
PVC BELL END
PUMP CABLE TO VFD.
CONNECTOR
3/4" GROUND ROD
ROD TYPE EXOTHERMIC
SCALE: NONE
PUMP MOTOR LEAD MOUNTING DETAIL5
E-504 (MOTOR MONITORING CABLE SIMILAR)
SCALE: NONE
CABLE TO ROD CONNECTION DETAIL6
E-504 TYPICAL
3/4" GALVANIZED COUPLING OR
METALLIC SLEEVE
ENCLOSURE
BACK PANEL
DIN RAIL
THREADED
BACK PANEL
#10-32
PAN HEAD
SCREW
1" FROM END
OF DIN RAIL
18" MAXIMUM
SCALE: NONE
DIN RAIL MOUNTING DETAIL7
E-504
SCALE: NONE
UNISTRUT SUPPORT DETAIL
DETAIL NOTES
MAST, 1" RGS.
CONDUIT CLAMPS
BOND TO CABINET AND TO SURGE SUPPRESSORS
AND POWER SUPPLIES WITHIN CABINET.
#6 B.C. SOLID COPPER GROUND.
BOND TO MAST.
S.O. EXTERIOR ARRAY CABLE / WIRING HARNESS.
ENCLOSURE. NEMA 12.
E-504
FROM FIELD
DEVICE
HOME RUN
SIDE VIEW
FRONT VIEW
TO GROUND GRID. SEE SITE PLAN.8
2 3
ANTENNA
WEATHER HEAD
SPEC.
NIG SREENE
I:\
7\
JO
RD
AN
R
IV
ER
-B
LA
IR
\0
1- D
W G\
EL
EC
\S H
EE
T\
7- E-
4-
(JR
-B
).d w g, /2 7/
:3
9:
P M
, k br
SCALE: NONE
BLAIR STREET PUMP STATION ELECTRICAL ONE-LINE DIAGRAM1
E-601
2.3
EOL EOL
P106
EXISTING ROCKY MOUNTAIN
POWER SECTIONALIZER
OR PRIMARY VOLTAGE
SOURCE
EXISTING POLE-MOUNT
TRANSFORMER, OVERHEAD FEED.
MOTOR CONTACTORS AND
CONTROLS IN SAME NEMA 3R
ENCLOSURE
NG
100/2
30/2
125A 240/120V, 1Ø
EUSERC METER MAIN
#6 B.C.
10' x 3/4"
GROUND RODS
P111
1 PHASE 240 VOLT, 2.3
HP SUBMERSIBLE PUMP
30/2
P106
P111
2.3
1 PHASE 240 VOLT, 2.3
HP SUBMERSIBLE PUMP
SEE PANEL SCHEDULE FOR
ADDITIONAL LOADS
20/1
JUNCTION BOXES AS REQUIRED
P109SHARED CONDUIT
NIG SREENE
I:\
7\
JO
RD
AN
R
IV
ER
-B
LA
IR
\0
1- D
W G\
EL
EC
\S H
EE
T\
7- E-
1-
(JR
-B
).d w g, /2 7/
:3
9:
P M
, k br
SCALE: NONE
JORDAN RIVER PUMP STATION ELECTRICAL ONE-LINE DIAGRAM1
E-603
M
(E)EUSERC
METER
P104 P104
P105 P105
240V, 1Ø INPUT
OUTPUT FOR
240V, 3Ø, 3W
MOTOR CONTROL
20HP. DERATE FOR
ELEVATION
VFDVFD
EXISTING ROCKY MOUNTAIN
POWER SECTIONALIZER
OR PRIMARY VOLTAGE
SOURCE
EXISTING POLE-MOUNT
TRANSFORMER, OVERHEAD FEED.
COORDINATE REQUIREMENTS WITH
UTILITY.
N G 60/2
PANEL 'JORDAN RIVER'
125/2
240 / 120V, 125A
NEMA 3R, 10 KAIC
SEE PANEL SCHEDULE
FOR ADDITIONAL LOADS VFD'S AND CONTROLS
IN SAME NEMA 3R
ENCLOSURE
240V, 1Ø INPUT
OUTPUT FOR
240V, 3Ø, 3W
MOTOR CONTROL
20HP. DERATE FOR
ELEVATION
240V, 3Ø, 10 HP PUMP240V, 3Ø, 10 HP PUMP
60/2
G N
(E)SERVICE
DISCONNECT
FIELD VERIFY NEUTRAL
GROUND BOND
20/1
JUNCTION BOXES AS REQUIRED
P110SHARED CONDUIT
NIG SREENE
I:\
7\
JO
RD
AN
R
IV
ER
-B
LA
IR
\0
1- D
W G\
EL
EC
\S H
EE
T\
7- E-
2-
(JR
-B
).d w g, /2 7/
:3
9:
P M
, k br
240V, 1Ø
PUMP
MOTOR
SCALE: NONE
PUMP VFD CONTROLS DIAGRAM1
E-603
VFD WITH
HARMONICS
MITIGATION
TO CONTROLLER
RUN STATUS
JORDAN RIVER STORM WATER
C
F1 F2
240V, 1Ø
PUMP
MOTOR
MOTOR STARTER
O / L
ELECTRONIC OVERLOADS
AUX
SCALE: NONE
PUMP CONTROLS DIAGRAM3
E-603
BLAIRE STREET STORM WATER
TO CONTROLLER
RUN STATUS
R
OOX
HAND
XOO
OFF
AUTO
R2
RUN CMD
PUMP 1
15A
120VAC PANEL
R18-1
R6
PUMP RUNNING
G
TO RTU
RUNNING
STATUS
PUMP RUNNING PILOT
R12
HIGH FLOAT R12-4
TO RTU HIGH
FLOAT ALARM
R12 R12-1
LOW FLOAT LOW LEVEL FLOAT ELEVATION TO BE SET
BELOW ALL PUMPS OFF ELEVATION. HIGH
LEVEL FLOAT TO BE SET ABOVE ALL PUMPS
ON ELEVATION. SEE CIVIL SHEETS FOR
ELEVATIONS.
ALTERNATING
RELAY
18 71
20 82
R R18
R R20
R12-2
R12-3
SCALE: NONE
CONTROLS WIRING DIAGRAM4
E-603
TYPICAL OF 2
TYPICAL OF 2
FROM CONTROLLER
RUN CMD
C
FROM CONTROLLER
RUN CMD
TO RTU
VFD FAIL
TO STARTER/VFD
RUN CMD
R2-1
R6
R6-1
R
OOX
HAND
XOO
OFF
AUTO
R8
RUN CMD
PUMP 2
R20-1
R10
PUMP RUNNING
G
TO RTU
RUNNING
STATUS
PUMP RUNNING PILOT
TO STARTER/VFD
RUN CMD
R8-1
R10
R10-1
TYPICAL OF 2
20A, 120V
DUPLEX OUTLET
WP, GFCI
H
G
N
RTU / HMI
POWER
SUPPLY
R24-1
TO RTU
POWER FAIL
SUPPLY
NIG SREENE
I:\
7\
JO
RD
AN
R
IV
ER
-B
LA
IR
\0
1- D
W G\
EL
EC
\S H
EE
T\
7- E-
3-
(JR
-B
).d w g, /2 7/
:4
0:
P M
, k br
File details come from the government source that posted it. Updated .