3-SSLC SW Pump Stations Blair Jordan 100 FOR BID.pdf

PDF 8 MB Posted

Attached to
Storm Water Pump Stations Upgrades - Blair St. & Jordan River
Solicitation number
PN 2025-21
Issued by
Salt Lake County, Utah

About this file

These are engineering design drawings and specifications for the City of South Salt Lake's Storm Water Pump Stations Upgrades project, focusing on two specific locations: Blair Street and Jordan River pump stations. The project, issued for bid in August 2025, involves comprehensive electrical, structural, and civil upgrades to existing storm water infrastructure. The design documents, prepared by Hansen, Allen & Luce Design Team, include detailed site plans, electrical one-line diagrams, control wiring schematics, and technical specifications for demolition and reconstruction of the pump stations.

The project encompasses electrical system improvements, including new electrical controls, variable frequency drives (VFDs), motor controls, and updated power distribution panels for both pump stations. The designs specify new submersible pumps, electrical enclosures, conduit systems, and integration with existing infrastructure. Electrical components will be housed in NEMA 3R enclosures, with provisions for cellular antenna, RTU (Remote Telemetry Unit) connections, and float switch controls. The drawings indicate careful consideration of existing site conditions, with plans for reusing some existing conduits and mounting infrastructure while implementing modern electrical and control systems to improve the storm water pump stations' reliability and functionality.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

CITY OF SOUTH SALT LAKE

STORM WATER PUMP STATIONS

UPGRADES - BLAIR ST & JORDAN RIVER

AUGUST 2025

ISSUED FOR BID

NIG SREENE

AARON C.

SPENCER

7426128-2202

STATE OF UTAH

RE

G I

ST

ER

ED

PROFESSIONAL ENGINEER

8/21/2025

NIG SREENE

AARON C.

SPENCER

STA T E O F UTA H

G

IS

TE

RE

D PROFESS IONAL ENG

I NE ER

SPENCER

IS

TE

RE

D PROFESS IONAL ENG

INEER

SPENCER

IS

TE

RE

D PROFESS IONAL ENG

SPENCER

IS

TE

RE

D PROFESS IONAL ENG

SPENCER

IS

TE

RE

D PROFESS IONAL ENG

SPENCER

IS

TE

RE

D PROFESS IONAL ENG

SPENCER

IS

TE

RE

D PROFESS IONAL ENG

SPENCER

IS

TE

RE

D PROFESS IONAL ENG

SPENCER

IS

TE

RE

D PROFESS IONAL ENG

SPENCER

IS

TE

RE

D PROFESS IONAL ENG

A AMPERE

AFF ABOVE FINISHED FLOOR

AI ANALOG INPUT

AIC AMPS INTERRUPTING CAPACITY

AFD ADJUSTABLE FREQUENCY DRIVES

AO ANALOG OUTPUT

AS AIR SUPPLY

ATS AUTOMATIC TRANSFER SWITCH

BC BYPASS CONTACTOR

C CONDUIT

CB CIRCUIT BREAKER

CL2 CHLORINE

CON CONTACTOR

CU COPPER, BARE

CV CONTROL VALVE

DCS DISTRIBUTED CONTROL SYSTEM

DI DISCRETE INPUT

DO DISCRETE OUTPUT

DV/DT DIFFERENTIAL VOLTAGE/TIME

DWG DRAWING

ETM ELAPSED TIME METER

EOL ELECTRONIC OVERLOAD

EXIST EXISTING

FA FOUL AIR

FC FAIL CLOSED

FE FLOW ELEMENT

FLA FULL LOAD AMPS

FS FLOW SWITCH

FVNR FULL VOLTAGE NON-REVERSING

FW FINISHED WATER

GFCI GROUND FAULT CIRCUIT

GFP GROUND FAULT PROTECTION

GND GROUND

GPD GALLONS PER DAY

GPH GALLONS PER HOUR

GPM GALLONS PER MINUTE

GRS GALVANIZED RIGID STEEL

H, HI HIGH

H2S HYDROGEN SULFIDE

HMI HUMAN MACHINE INTERFACE

HOA HAND-OFF-AUTO

HOR HAND-OFF-REMOTE

I CURRENT

IC INSTRUMENTATION CABLE

ICR INTERMITTENT CYCLE REACTOR

IO INPUT/OUTPUT

INTRINSICALLY SAFE RELAY

JB JUNCTION BOX

L, LO LOW

LAN LOCAL AREA NETWORK

LC LOOP CONTROLLER

LCL LEVEL CONTROL, LOW

LCP LOCAL CONTROL PANEL

LOS LOCK-OUT-STOP

LR LOCAL/REMOTE

LS LEVEL SWITCH

LTC LIQUID TIGHT FLEXIBLE CONDUIT

M MOTOR

MA MANUAL/AUTO, MILLIAMP

MAX MAXIMUM

MC MANUFACTURER'S CABLE

MCB MAIN CIRCUIT BREAKER

MCC MOTOR CONTROL CENTER

MCP MOTOR CIRCUIT PROTECTOR

MFR(S) MANUFACTURER(S)

MGD MILLION GALLONS PER DAY

MGL MILLIGRAMS PER LITER

MH MANHOLE

MIN MINIMUM

MOV MOTOR OPERATED VALVE

MTU MASTER TELEMETRY UNIT

NEC NATIONAL ELECTRICAL CODE

NECA NATIONAL ELECTRICAL CONTRACTOR

NORMALLY OPEN TIMED CLOSED

NPW NON-POTABLE WATER

NS NITROGEN SUPPLY

NTS NOT TO SCALE

NTU TURBIDITY

OF OVERFLOW

OIT OPERATOR INTERFACE TERMINAL

OL OVERLOAD

OO ON/OFF (MAINTAINED)

OR OFF-REMOTE

P PHASE OR POLE

PB PULL BOX

PCP PROCESS CONTROL PANEL

PFR PHAS/POWER FAILURE RELAY

PI PULSE INPUT

PLC PROGRAMMABLE LOGIC

PLI PLANT INFLUENT

PKG PACKAGE

PMP PUMP

PNL

PO PULSE OUTPUT

PPG POUNDS PER GALLON

PPH POUNDS PER HOUR

PPM PARTS PER MILLION

PR PAIR

PRES PRESSURE

PS PRESSURE SWITCH

PSH PRESSURE SWITCH, HIGH

PSI POUNDS PER SQUARE INCH

PV PROCESS VARIABLE

RAS RETURN ACTIVATED SLUDGE

RW RAW WATER

RCL REMOTE 1/0

RF RADIO FREQUENCY

RIO REMOTE INPUT/OUTPUT

RS RAW SEWAGE

RSP RAW SEWAGE PUMP

RST RESET

RTD RESISTANCE TEMPERATURE

RTU REMOTE TELEMETRY UNIT

RWT REFLECTED WAVE TRAP

SEQ SERVICE ENTRANCE EQUIPMENT

SES SERVICE ENTRANCE SECTION

SLC SINGLE LOOP CONTROLLER

SLOS START-LOCK-OFF-STOP

SMC SUBMERSIBLE MANUFACTURER

SO2 SULFUR DIOXIDE

SP SET POINT

SPC SPARE CONDUIT

SPR SPARE

SS START/STOP

SSS SOLID STATE STARTER

ST SHUNT TRIP

TC TELEPHONE CABLE

TS TEMPERATURE SWITCH

TYP TYPICAL

UG UNDERGROUND

V VOLT

VFD VARIABLE FREQUENCY DRIVE

W WATT, WIRE

WAS WASTE ACTIVATED SLUDGE

WP WEATHERPROOF

XFMR TRANSFORMER

XMTR TRANSMITTER

ZS POSITION SWITCH

ISR

NOTC

PANEL

TDOE TIME DELAY ON ENERGIZE

CPT CONTROL POWER TRANSFORMER

GES GROUNDING ELECTRODE SYSTEM

O.C. ON CENTER

CPM CUSTOMER POWER MONITORING

ES EMERGENCY STOP

N NEUTRAL

G GROUND

CONTROLLER

DETECTOR

CABLE

(SOFT START)

INTERRUPTER

L, LO

SHORT CIRCUIT CURRENTISC

ELR END OF LINE RESISTER

ML MIXED LIQUOR

ASSOCIATION

TSP TWISTED SHIELDED PAIR

TVSS TRANSIENT VOLTAGE

SURGE SUPPRESSION

ABBREVIATIONS

N: NUMBER - SIZE OF NEUTRAL CONDUCTOR(S) PER CONDUIT

P: NUMBER - SIZE OF PHASE CONDUCTORS PER CONDUIT

SIZE OF EACH CONDUIT IN INCHES

G: NUMBER- SIZE OF GROUND CONDUCTOR(S) PER CONDUIT

NUMBER OF CONDUITS

3.G: 4 4.

5.

P: 2 N:1 3 2.

1.

14 = #14 AWG COPPER

12 = #12 AWG COPPER

10 = #10 AWG COPPER

8 = #8 AWG COPPER

6 = #6 AWG COPPER

4 = #4 AWG COPPER

2 = #2 AWG COPPER

1/0 = 1/0 AWG COPPER

2/0 = 2/0 AWG COPPER

3/0 = 3/0 AWG COPPER

4/0 = 4/0 AWG COPPER

250 = 250 KCMIL COPPER

350 = 350 KCMIL COPPER

500 = 500 KCMIL COPPER

750 = 750 KCMIL COPPER

KEY TO CONDUCTOR SIZE & TYPE

FEEDER DESIGNATION LOGIC

EXPOSED CONDUIT

EXISTING EXPOSED CONDUIT

UNDERGROUND CONDUIT

EXISTING UNDERGROUND CONDUIT

BARE COPPER GROUND CONDUCTOR

FUTURE

NEW ELECTRICAL EQUIPMENT

DETAIL VIEW OR MATCHING

CAPPED UNDERGROUND CONDUIT OR STUBBUP

ELECTRICAL LINETYPES

CONDUIT DROP

CONDUIT RISE

SYMBOL DESCRIPTION

QUADRAPLEX RECEPTACLE

DUPLEX RECEPTACLE

GROUND FAULT CIRCUIT INTERRUPTER RECEPTACLE.

ISOLATED GROUND TYPE DUPLEX RECEPTACLE

SPECIAL PURPOSE OR WELDING OUTLET.

POWER

SYMBOL DESCRIPTION

DUPLEX RECEPTACLE, RECESSED FLOOR MOUNTED

DUPLEX RECEPTACLE, RECESSED CEILING MOUNTED

QUADRAPLEX RECEPTACLE, RECESSED FLOOR MOUNTED

QUADRAPLEX RECEPTACLE, RECESSED CEILING MOUNTED

GFCI

WEATHERPROOF CONVENIENCE OUTLETWP

HOME RUN TO PANEL - INDICATING 2 #12, #12 GND, 3/4" CONDUIT

HOME RUN TO PANEL - INDICATING NUMBER OF CONDUCTORS - #12

HOME RUN TO PANEL SHOWING BRANCH CIRCUIT NUMBERS.

OR AS SHOWN.

X-1,3,5

OR AS SHOWN.

HATCH MARKS IN CONDUIT RUN DENOTES NUMBER OF CONDUCTORS

UNLESS NOTED OTHERWISE. UNMARKED CONDUITS SHALL BE 3/4"

SIZE OF CONDUCTORS TO BE #12 AWG CONDUCTORS IN CONDUIT

IN CONDUIT. LONG HATCH MARK DENOTES GROUND CONDUCTOR.

WITH 3 #12.

FLUSH FLOOR DEVICE BOX

THERMOSTAT

M MOTOR, X = HORSE POWER

F CEILING EXHAUST FAN

DENOTES EXISTING EQUIPMENT OR DEVICES(E)

X

VOLTAGE RATING

NEMA ENCLOSURE

FUSE (NF-NO FUSE)

SIZE (AMPS)

DISCONNECT SWITCH.

POLES

ELECTRICAL PANEL, POWER OR LIGHTING

METER BASE

COMBINATION MOTOR STARTER, SEE SPECS

J JUNCTION BOX

DEVICE. IF NOT NOTED, THE MOUNTING HEIGHT TO CENTER SHALL BE

MOUNTING HEIGHT ABOVE FINISHED FLOOR TO CENTER OF OUTLET

AS DETAILED OR SPECIFIED.

THIS NOTATION ADJACENT TO WALL OUTLET SYMBOL DENOTES

+0'-0"

MANUAL MOTOR STARTER

MANUAL MOTOR STARTER WITH OVERLOADS

sM s T

SINGLE POLE SWITCH

3 WAY SWITCH

4 WAY SWITCH

s s 3 s 4

LIGHTING FIXTURE TYPE - SEE FIXTURE SCHEDULE.F#

DM DAMPER MOTOR

TELEPHONE JACK OUTLET. 1'-6". (SINGLE, DOUBLE, QUAD)

COMMUNICATION/DATA JACK. CONDUIT TO ABOVE CEILING.

DATA OR CATHODE RAY TUBE (CRT) TERMINAL OUTLET. +1'-6".

OWNER TO RUN WIRING.

(SINGLE, DOUBLE)2

2 POSITION SELECTOR SWITCH,

TERMINAL LUG OR STRIP

NODE OR CONNECTION

MC CONNECTION

THERMAL OVERLOAD RELAY

CIRCUIT BREAKER OR MOTOR CIRCUIT PROTECTOR, SHOWN WITH TRIP

POSITION LEGEND: X=CLOSED O=OPEN

NORMALLY OPEN CONTACT

GENERATOR

NORMALLY CLOSED PUSH BUTTON

TEMPERATURE SWITCH

LEVEL FLOAT SWITCH

FLOW SWITCH

GROUND CONNECTION

FUSEHOLDER OR FUSEBLOCK

SOLID STATE REDUCED VOLTAGE STARTER

HARMONIC FILTER

BOND TO METALLIC WATER PIPE

LOCKOUT STOP PUSH BUTTON

VARIABLE FREQUENCY DRIVE

MOTOR STARTER OR CONTACTOR COIL

ELAPSED TIME METER

ALARM RELAY

UTILITY METER

TRANSFORMER

FULL VOLTAGE NONREVERSING (FVNR) MOTOR STARTER OR

CONTACTER NUMBER DESIGNATES NEMA SIZE.

EOL ELECTRONIC OVERLOAD RELAY

LTC CONNECTION

MOTOR, X = HORSEPOWER

DEVICE LOCATED AT REMOTE LOCATION.

FUSE

ICTO TIMER RELAY CONTACT INSTANTANEOUS CLOSE TIME DELAY OPEN.

NOTC

NORMALLY CLOSED CONTACT

3 POSITION SELECTOR SWITCH HAND - OFF - AUTO,

POSITION LEGEND: X=CLOSED O=OPEN

NORMALLY OPEN PUSH BUTTON

CURRENT TRANSFORMER

LIMIT SWITCH

PRESSURE SWITCH LOW

EMERGENCY STOP PUSH BUTTON (MAINTAINED)

RTU, PLC, OR RIO CONTACT

SSRV

VFD

HF

ETM

BEACON ALARM LIGHT. LETTER INDICATES COLOR: R=RED,

A=AMBER, B=BLUE, G=GREEN

PILOT LIGHT. LETTER INDICATES COLOR: R=RED, A=AMBER,

B=BLUE, G=GREEN

TIME DELAY RELAY

T.C.

CONTACT - TIME DELAY

I.C. - T.O. = NORMALLY OPEN WITH INSTANT CLOSING AND

TIME DELAY OPENING.

T.C.-T.O. = NORMALLY OPEN W/TIME DELAY CLOSING AND

CONTACT - TIME DELAY

T.O.-T.C. = NORMALLY CLOSED WITH TIME DELAY OPENING AND

TIME DELAY CLOSING AFTER DEENERGIZATION.

I.O.-T.C. = NORMALLY CLOSED WITH INSTANT OPENING AND TIME DELAY

POLES

AMPS

AMPS / POLES

SCHEMATICS & DIAGRAMS

T.C. = NORMALLY OPEN W/TIME DELAY CLOSING.

TIME DELAY OPENING AFTER DEENERGIZATION.

T.0.

T.C. = NORMALLY CLOSED WITH TIME DELAY OPENING.

CLOSING.

PRESSURE SWITCH HIGH

DISCONNECT SWITCH SHOWN WITH RATING AND NUMBER OF POLES.

H O A

ON OFF

xo oox

TIMER RELAY CONTACT NORMALLY OPEN TIME DELAY CLOSE.

X

X

UM

R RELAY

TD

AR

ETM

M

CT'S

X

BOND TO METALLIC WATER PIPE

BOND TO BUILDING STEEL

RATING AND NUMBER OF POLES.

DESCRIPTIONSYMBOL

FLUORESCENT LIGHT FIXTURE, SEE FIXTURE SCHEDULE.

LIGHTING

SYMBOL DESCRIPTION

EMERGENCY LIGHTING, SEE FIXTURE SCHEDULE.

LIGHTING FIXTURE TYPE - SEE FIXTURE SCHEDULE.F#

SINGLE POLE SWITCHs

3 WAY SWITCHs3

WALL MOUNTED MOTION SWITCH - DUAL TECHNOLOGYsm

MOTOR RATED TOGGLE SWITCHs T

DIGITAL OVERRIDE SWITCHsD

RECESSED CEILING MOUNTED SPEAKER BY OTHERSSP

WALL MOUNTED MOTION SENSOR

CEILING MOUNTED MOTION SENSOR

CEILING-MOUNTED EXIT LIGHT, SEE FIXTURE SCHEDULE

WALL-MOUNTED EXIT LIGHT, SEE FIXTURE SCHEDULE

RECESSED CAN LIGHT, SEE FIXTURE SCHEDULE

ANALYZING INDICATING TRANSMITTER

ANALYZER ELEMENT

COMBUSTIBLE GAS DETECTOR

LEVEL ELEMENT

OVER TORQUE SWITCH

PRESSURE INDICATING TRANSMITTER

CONDUCTIVITY INDICATING TRANSMITTER

FLOW ELEMENT

FLOW INDICATING TRANSMITTER

MOTOR OPERATED VALVE OR GATE

SOLENOID OPERATED VALVE

TEMPERATURE ELEMENT

PRESSURE SWITCH

LEVEL SWITCH

CONTROLS & INSTRUMENTS

SYMBOL DESCRIPTION

AE

PS

AIT

FE

FS

LE

LS

ME

LT

PIT

TE

TS

TT

SV

CIT

FIT

LEVEL INDICATING TRANSMITTERLIT

OS

MV

FLOW SWITCH

LEVEL TRANSMITTER

MOISTURE ELEMENT

TEMPERATURE SWITCH

TEMPERATURE TRANSMITTER

CGD

ZS LIMIT OR POSITION SWITCH

SCHEMATICS & DIAGRAMS

DESCRIPTIONSYMBOL

SINGLE POLE SWITCH WITH PILOT LIGHTs P

CONDUIT NUMBER6.

NIG SREENE

I:\

7\

JO

RD

AN

R

IV

ER

-B

LA

IR

\0

1- D

W G\

EL

EC

\S H

EE

T\

7- E-

1-

(JR

-B

).d w g, /2 7/

:3

9:

P M

, k br ow n

PANEL BLAIR STREET

BUS AMPS: 125

VOLTAGE: 120/240 V 1Ø 3W MAIN BREAKER AMPS 100

ENCLOSURE: NEMA 3R BREAKER RATING % 80%

CIRCUIT BREAKER TYPE: BOLT-ON MOUNTING: SURFACE

INTERRUPTING CAPACITY: 10 KAIC COVER TYPE: DOOR-IN-DOOR

LOCATION: BLAIR STREET

BRANCH CIRCUIT BREAKER CONNECTION

DESCRIPTION

PHASE

DESCRIPTION

CONNECTION BRANCH CIRCUIT BREAKER

NOTES # AMP P. LOAD (VA) L1 L2 LOAD (VA) P. AMP # NOTES

1 30 2 2040 PUMP 1 3040 CONTROLLER 1000 1 20 2

3 -- -- 2040 ------ 2220 RECEPTACLE 180 1 20 4

5 30 2 2040 PUMP 2 2040 SPARE 1 20 6

7 -- -- 2040 ------ 2040 SPARE 1 20 8

9 20 1 SPARE 0 SPARE 1 20 10

11 20 1 SPARE 0 SPARE 1 20 12

PHASE SUBTOTALS (VA) 5080 4260

PHASE TOTALS (KVA) 5.1 4.3

PHASE TOTALS @ 120V (AMPS) 42.3 35.5

NOTES:

G PROVIDE WITH INTEGRAL SURGE PROTECTOR

PANEL JORDAN RIVER

BUS AMPS: 125

VOLTAGE: 120/240 V 1Ø 3W MAIN BREAKER AMPS 125

ENCLOSURE: NEMA 3R BREAKER RATING % 80%

CIRCUIT BREAKER TYPE: BOLT-ON MOUNTING: SURFACE

INTERRUPTING CAPACITY: 10 KAIC COVER TYPE: DOOR-IN-DOOR

LOCATION: JORDAN RIVER

BRANCH CIRCUIT BREAKER CONNECTION

DESCRIPTION

PHASE

DESCRIPTION

CONNECTION BRANCH CIRCUIT BREAKER

NOTES # AMP P. LOAD (VA) L1 L2 LOAD (VA) P. AMP # NOTES

1 60 2 5040 PUMP 1 6040 CONTROLLER 1000 1 20 2

3 -- -- 5040 ------ 5220 RECEPTACLE 180 1 20 4

5 60 2 5040 PUMP 2 5040 SPARE 1 20 6

7 -- -- 5040 ------ 5040 SPARE 1 20 8

9 20 1 SPARE 0 SPARE 1 20 10

11 20 1 SPARE 0 SPARE 1 20 12

PHASE SUBTOTALS (VA) 11080 10260

PHASE TOTALS (KVA) 11.1 10.3

PHASE TOTALS @ 120V (AMPS) 92.3 85.5

NOTES:

G PROVIDE WITH INTEGRAL SURGE PROTECTOR

C102 1 4 -#14

3/4" G: 1 -#14

C202 1 1"ANTENNA WIRE

C203 1 6 -#14

EXISTING

CONDUIT

G: 1 -#14

P104 1 P: 3 - #8

3/4"N: NONE

G: 1 - #10

P105 1 PUMP SUPPLIED CABLE

P106 1 P: 2 - #12

3/4"N: NONE

G: 1 - #12

P109 1 P: 2 - #12

EXISTING

CONDUITN: NONE

G: 1 - #12

P110 1 P: 3 - #8

EXISTING

CONDUITN: NONE

G: 1 - #10

P111 1 PUMP SUPPLIED CABLE

POWER CONDUIT SCHEDULECONTROL CONDUIT SCHEDULE

NIG SREENE

I:\

7\

JO

RD

AN

R

IV

ER

-B

LA

IR

\0

1- D

W G\

EL

EC

\S H

EE

T\

7- E-

2-

(JR

-B

).d w g, /2 7/

:3

9:

P M

, k br

SCALE: 1/8"=1'-0"

BLAIR STREET ELECTRICAL SITE PLAN

10 5 0 10 20

(E)POWER POLE

DRAWING NOTES

1 INSTALL GROUND RODS. SEE ONE-LINE DIAGRAM.

JUNCTION BOX

AS REQUIRED

PUMP STATION

TO RTU

C202

CELLULAR ANTENNA

NEW ELECTRICAL METER/MAIN

WP GFCI. RUN (2) #12, (1) #12 GND IN 3/4" CONDUIT TO

20A / 1P METER/MAIN BREAKER

NEW ELECTRICAL CONTROLS ENCLOSURE. MOTOR

CONTACTORS, AND RTU WITHIN ENCLOSURE. RUN (2) #12,

(1) #12 GND IN 3/4" CONDUIT TO 20A / 1P METER/MAIN

BREAKER FOR CONTROLLER.

(E) CONDUIT TO BE REUSED

4 POUR CONCRETE PAD OVER THE EXISTING CONDUIT.

ENSURE THE EXISTING CONDUIT IS EXPOSED THROUGH

THE NEW CONCRETE PAD AT ITS CURRENT LOCATION.

INSTALL UNISTRUT FRAME IN THE CONCRETE TO SUPPORT

THE ENCLOSURE AND PROVIDE MOUNTING FOR THE

ANTENNA. ROUTE EXISTING CONDUIT TO THE ENCLOSURE.

SEE UNISTRUT SUPPORT DETAIL AND UNISTRUT DETAIL IN

CIVIL SHEETS.

NIG SREENE

I:\

7\

JO

RD

AN

R

IV

ER

-B

LA

IR

\0

1- D

W G\

EL

EC

\S H

EE

T\

7- E-

1-

(JR

-B

).d w g, /2 7/

:3

9:

P M

, k br

SCALE: 1/8"=1'-0"

JORDAN RIVER ELECTRICAL SITE PLAN

10 5 0 10 20

(E)POWER POLE

AND TRANSFORMER

TO RTU

C202

CELLULAR ANTENNA

(E)METER TO REMAIN

(E)MAIN DISCONNECT TO REMAIN

(E)CONDUIT

(E)CONDUIT TO BE REUSED

DRAWING NOTES

WP GFCI. RUN (2) #12, (1) #12 GND IN 3/4" CONDUIT TO2

NEW ELECTRICAL CONTROLS ENCLOSURE. VFD'S, AND RTU

WITHIN ENCLOSURE. RUN (2) #12, (1) #12 GND IN 3/4"

CONDUIT TO 20A / 1P BREAKER FOR CONTROLLER.

NEW PANELBOARD

20A / 1P BREAKER.

NIG SREENE

I:\

7\

JO

RD

AN

R

IV

ER

-B

LA

IR

\0

1- D

W G\

EL

EC

\S H

EE

T\

7- E-

2-

(JR

-B

).d w g, /2 7/

:3

9:

P M

, k br

SCALE: 1/2"=1'-0"

BLAIR STREET PUMP STATION POWER PLAN

DRAWING NOTES

1 REMOVE EXISTING ELECTRICAL BOX. SEE REMODEL DRAWING.

SHARED CONDUIT WITH POWER CONDUCTORS.

SUPPORT PUMP CORD TO CEILING OR WALL OF VAULT.

SCALE: 1/2"=1'-0"

BLAIR STREET PUMP STATION CONTROLS PLAN

E-101

E-101SCALE: 1/2"=1'-0"

BLAIR STREET PUMP STATION DEMOLITION PLAN

E-101

(E)ELECTRICAL

CONTROL BOX

JUNCTION BOX

AS REQUIRED

SEE CONTINUATION

ON E-101

P111

P111

JUNCTION BOX

AS REQUIRED

LSHLSL

C102

TO CONTROLS

ENCLOSURE

C203

(E)METER AND

DISCONNECT BELOW

(E)CONTROL PANEL

(E)POWER POLE

SHARED

CONDUIT

EXISTING CONDUIT

TO BE REUSED EXISTING CONDUIT

TO BE REUSED

NIG SREENE

I:\

7\

JO

RD

AN

R

IV

ER

-B

LA

IR

\0

1- D

W G\

EL

EC

\S H

EE

T\

7- E-

1-

(JR

-B

).d w g, /2 7/

:3

9:

P M

, k br

SCALE: 1/2"=1'-0"

JORDAN RIVER PUMP STATION POWER PLAN

DRAWING NOTES

1 REMOVE EXISTING ELECTRICAL BOX. SEE REMODEL DRAWING.

NEW ELECTRICAL JUNCTION BOX FOR PUMP MOTOR

CONNECTIONS AND CONTROLS AS REQUIRED.

SUPPORT PUMP CORD TO CEILING OR WALL OF VAULT.

SCALE: 1/2"=1'-0"

JORDAN RIVER PUMP STATION CONTROLS PLAN

E-102

E-102

SCALE: 1/2"=1'-0"

JORDAN RIVER PUMP STATION DEMOLITION PLAN

E-102

2 P110

TO VFD

P105

LSH

LSL

LOW LEVEL FLOAT

TO CONTROLS

ENCLOSURE

C203

C102

HIGH LEVEL FLOAT

SHARED CONDUIT

SHARED CONDUIT WITH POWER CONDUCTORS.4

NIG SREENE

I:\

7\

JO

RD

AN

R

IV

ER

-B

LA

IR

\0

1- D

W G\

EL

EC

\S H

EE

T\

7- E-

2-

(JR

-B

).d w g, /2 7/

:3

9:

P M

, k br

VERTICAL CONDUIT

FIBER FILLER

SEALING COMPOUNDSEALING COMPOUND

HORIZONTAL CONDUIT

EXTERIOR WALL SURFACE OR

OZ/GEDNEY CSML WALL

SEAL OR LMK SEAL - SEE SPECS.

W/ NON-SHRINK

SPECS. PATCH

WALL-SEE

LC

CORE DRILL

* GROUT

LC SEALING

RING

NEOPRENE

HOUSEKEEPING CURB REQUIRED AT ALL INTERIOR WALL

CONDUIT RISERS SHALL BE COUPLED SO THAT SINGLE

LOCATIONS FOR SINGLE AND MULTIPLE CONDUIT RISERS.

CONDUITS ARE SIX FEET APART MINIMUM.

4"

3"

WASHDOWN AREA FLOOR

AS DIRECTED BY ENGINEER.

ARMOR ROD BACKING

CORE DRILL EXISTING

FLOOR OR WALL.

CALK SEALANT OR NON-SHRINK GROUT.

SECURE TAGS TO CONDUIT

WITH NYLON CABLE TIES

ALMETEX TYPE

EZ-V TAG TITLES

(BLACK OR YELLOW)

C1005

ALMETEX TYPE TH

TAG HOLDER

SECURE TAGS TO CONDUIT

WITH NYLON CABLE TIES

CONDUIT

SCALE: NONE

FLOOR PENETRATIONS1

E-501

EXISTING WALL/DRY

SCALE: NONE

DAMMING AND POURING2

E-501

TYPICAL CONDUIT SEAL

SCALE: NONE

CONCRETE HOUSEKEEPING CURB DETAIL3

E-501

SCALE: NONE

WALL SEAL OR WASHDOWN FLOOR4

E-501

UNDERGROUND CONDUIT

SCALE: NONE

CONDUIT MARKING SYSTEM5

E-501 TYPICAL OF ALL CONDUITS

1-1/4"

NOTES:

"EQUIPMENT NUMBER"

4. PROVIDE BLANK NAMEPLATES FOR ALL SPARE

3. ATTACH ALL NAMEPLATES WITH STAINLESS

VERTICAL CENTERLINE OF THE CUBICAL OR DEVICE.

2. ALL NAMEPLATES TO BE MOUNTED ON THE

1. ALL LETTERS TO BE 1/4" UNLESS NOTED

AND FUTURE DEVICES.

STEEL SCREWS.

OTHERWISE.

"EQUIPMENT NAME"

3" OR 4"

SCALE: NONE

NAMEPLATE DETAIL6

E-501 TYPICAL OF ALL EQUIPMENT

CONDUIT

SQUARE FENDER

WASHER TYPICAL

TYPICAL

LOCK WASHER,

NUT, TYPICAL

1/2" ALL THREAD

UNISTRUT CONDUIT

CLAMP, TYPICAL

CHANNEL

UNISTRUT

P1000

1/2" ALL THREAD

SCALE: NONE

CONDUIT SUPPORT DETAIL7

E-501 TYPICAL

(FLUSH WITH FINISHED

FLOOR OR FOUNDATION)

CONDUIT COUPLING

FINISHED FLOOR

OR EQUIPMENT

FOUNDATION

THREADED BRASS

PLUG

SCALE: NONE

FLUSH CONDUIT TERMINATION8

E-501 TYPICAL

NIG SREENE

I:\

7\

JO

RD

AN

R

IV

ER

-B

LA

IR

\0

1- D

W G\

EL

EC

\S H

EE

T\

7- E-

1-

(JR

-B

).d w g, /2 7/

:3

9:

P M

, k br

TO COMPUTER/POSITION CONTROLLER, GROUND

SHIELD AT CONTROLLER END ONLY.

(FOR TE SHIELD GROUND, SEE CONTROL CONNECTIONS)

ANALOG CONTROL SIGNAL

GROUND ROD

CONDUIT/4-WIRE CABLE

(L3)

GND.

(L1)

(L2)

VFD

GND.MOTOR FRAME

@ EACH END

BOND CONDUIT TO GROUND

GROUND PER

LOCAL CODES

SHIELD/CONDUIT

SHIELD/CONDUIT

(T3)

GND.

(T1)

(T2)

RGS W/ EXTERNAL

FLEX GROUNDING

JUMPER

P1200 SERIES CLAMP.

CLAMPED W/ UNISTRUT

BRANCH CIRCUIT CONDUIT

DOUBLE GALVANIZED

UNISTRUT P1001

CHANNEL.

ROD ANCHORED TO

CLAMP AS REQUIRED.

DECK WITH BEAM

CEILING STEEL OR

5/8" GALVANIZED THREADED

SWIVEL CEILING/

BEAM ATTACHMENT BEAM ATTACHMENT

SWIVEL CEILING/

SCALE: NONE

VFD GROUNDING DIAGRAM1

E-502

SCALE: NONE

CONDUIT SUPPORT DETAIL2

E-502 TYPICAL

LOCKWASHER

ANCHOR WITH NUT AND

3/4" SS ADHESIVE

AT A MAX OF 3'-0" O.C.

PROVIDE INTERMEDIATE SUPPORTS

WHERE LENGTH EXCEEDS 3'-0"

CONDUIT CLAMP (TYP.)

LENGTH TO SUIT

SCALE: NONE

CONDUIT SUPPORT DETAIL3

E-502 TYPICAL

MATCH BOLT

HOLE PATTERN OF

CONNECTOR TO

EQUIPMENT.

LONG BARREL LUGS (TYP.)

BURNDY HY GROUND

COMPRESSION FITTINGS

BURNDY HY GROUND

COMPRESSION FITTINGS

SCALE: NONE

EQUIPMENT GROUNDING CONNECTION4

E-502 TYPICAL

MOTOR FEEDER

COMPRESSION

RING LUG

SEALANT USE IN WET

HEAT-ACTIVATED MASTIC

MOTOR LEAD

LOCATIONS ONLY

POLYOLEFIN CAP

SHRINKABLE RAYCHEM

CROSS LINKED HEAT

LOCKNUT

ELECTRICAL ENCLOSURE

0-RING

CONNECTOR BODY

FERRULE

LIQUIDTIGHT FLEXIBLE METALLIC CONDUIT

COMPRESSION NUT

OR DEVICE

BUSHING WERE REQUIRED

INSULATED THROUGH

NOTES:

2. INSULATED BUSHING SHALL BE REQUIRED FOR

CONDUCTORS #4 OR LARGER.

1. PROVIDE LISTED GROUNDING TYPE CONNECTORS

WITH LUGS AND EXTERNAL BONDING JUMPER WHEN

CIRCUITS ARE RATED 20 AMPS OR MORE FOR 1/2",

MORE THAN 60 AMPS FOR 3/4" THROUGH 1-1/4",

AND FOR 1-1/2" AND LARGER WERE REQUIRED FOR

GROUNDING.

SCALE: NONE

TYPICAL MOTOR LEAD TERMINATION5

E-502 TYPICAL

SCALE: NONE

TYPICAL FLEXIBLE CONDUIT CONNECTION DETAIL6

E-502

NIG SREENE

I:\

7\

JO

RD

AN

R

IV

ER

-B

LA

IR

\0

1- D

W G\

EL

EC

\S H

EE

T\

7- E-

2-

(JR

-B

).d w g, /2 7/

:3

9:

P M

, k br

NOTES:

1. IN CORROSIVE AREAS PROVIDE STAINLESS STEEL U-CHANNEL.

2. OMIT POST BASE WHEN MOUNTING TO SIDE OF ABOVE GRADE STRUCTURE.

3. PROVIDE HARDWARE OF SAME MATERIAL AS U-CHANNEL.

SHALLOW U-CHANNEL.

P3300, AS MANUFACTURED

BY UNISTRUT OR EQUAL.

JUNCTION BOX.

MYERS HUB OR EQUAL.

CONDUIT CLAMP.

DOUBLE U-CHANNEL, P1001,

AS MANUFACTURED BY

UNISTRUT OR EQUAL.

AS MANUFACTURED

POST BASE, P2073 A, AS

MANUFACTURED BY

UNISTRUT OR EQUAL.

U-CHANNEL, P1000,

BY UNISTRUT OR EQUAL.

4 - 1/2"x4"

STAINLESS STEEL

ANCHOR BOLTS

PVC COATED GRC

SCALE: NONE

JUNCTION BOX MOUNTING DETAIL1

E-503

LONG BARREL LUGS (TYP.)

COMPRESSION FITTINGS

BURNDY HY GROUND

MIN.

1'-0" CONCRETE ENCASEMENT

3" MIN. ALL SIDES

M

IN

6"

FINISHED GRADE OR FLOOR

TO EQUIPMENT

PVC COATED RIGID

METAL CONDUIT,

FACTORY NINETY

PVC COATED RIGID

METAL COUPLING

PVC COATED RIGID

METAL CONDUIT

MALE PVC

ADAPTOR

CONDUIT

PVC COATED RIGID

METAL COUPLING

SCALE: NONE

BONDING LUG DETAIL2

E-503

SCALE: NONE

CONDUIT RISER DETAIL3

E-503 TYPICAL

REBAR

MAX. 1" CONDUIT

1" CLEAR MIN.

1" COVER MIN.

1" CONDUIT OR LARGER

METALLIC OR NON-

METALLIC

1" MIN. SLAB ON GRADE

3"

SCALE: NONE

CONDUIT PLACEMENT DETAIL4

E-503 TYPICAL

CONDUIT

FLASHING

BRANCH

CIRCUIT

TYP.

BOLT TO

NEW

ROOF

1-5/8"x1-5/8"

MOUNTING

CHANNEL

48"±

MOTOR

COMBINATION

DISCONNECT

STARTER

NEMA 3R

3/8" CONCRETE

ANCHORS WITH

SS BOLTS

SCALE: NONE

DISCONNECT STARTER DETAIL5

E-503

MOTOR COMBINATION

HATCH OPENING

FLOAT CABLE

SUBMERSIBLE LEVEL FLOAT

PVC CONDUIT

AND MALE ADAPTOR

PVC BELL END

CABLE WEIGHT

1OPERATING WATER LEVEL FOR INSTALLATION OF FLOATS WITHOUT A

CONCRETE DECK CONSTRUCT A 3/8"x12"x8" SS

PLATE SUPPORT ANCHORED TO WALL AT

MINIMUM 4 PLACES. WELD A 3/8"x6"x12" SS

GUSSET TO THE BOTTOM OF PLATE SUPPORT.

PVC COATED GRS COUPLING AND

CONDUIT TO VFD OVERSIZED TO RUN

SUBMERSIBLE PUMP CABLE TO VFD.

RUN CONDUIT WITHIN CONCRETE LID

WHERE PRACTICABLE.

SCALE: NONE

LEVEL FLOAT MOUNTING DETAIL6

E-503

(TYPICAL OF TWO)

TRANSDUCER CABLE. ORDER WITH

LENGTH TO REACH LEVEL METER.

VAULT WALL

WALL MOUNTED BRACKET.

EXTENDED AS REQUIRED.

LEVEL TRANSDUCER

PVC BELL END

1" PVC CONDUIT

SCALE: NONE

TRANSDUCER MOUNTING DETAIL7

E-503

SJE RHOMBUS 4 FLOAT BRACKET WITH

MOUNTING DEVICE AND STRAIN RELIEF

CONNECTORS TO MATCH FLOAT WIRE

CGB

NIG SREENE

I:\

7\

JO

RD

AN

R

IV

ER

-B

LA

IR

\0

1- D

W G\

EL

EC

\S H

EE

T\

7- E-

3-

(JR

-B

).d w g, /2 7/

:3

9:

P M

, k br

BACKFILL BORROW

IMPORTED GRANULAR

GRADE SS-1 TACK COAT

SAWCUT EXISTING ASPHALT TO 8" MINIMUM

6" TYP.

SURFACE COURSE,

AC-10, DM-3/4 CLASS IV

CONDUITS AS PER PLANS.

7" THICK BITUMINOUS

12" MIN.

3'- 0"

GRADE SS-1 TACK COAT

SAWCUT EXISTING ASPHALT

TO 8" MINIMUM

ASPHALT

EXISTING

210 JOINT SEALANT

SEAL WITH CRAFT-CO

LINE MARKER

EXISTING ASPHALT

02206 8" IN DEPTH - COMPACT

GRADE 1 UTBC.

EXISTING CONCRETE

CONDUIT INSTALLATION.

REMOVE STONES LARGER

THAN 1" OR OTHER HARD

TRENCH PRIOR TO

SMOOTH BOTTOM OF

BACKFILL BORROW

SAW-CUT & REMOVE

SIDEWALK SECTION

ENTIRE SECTION

18" MIN.

3'- 0"

LINE MARKER

COMPACT

GRADE 1 UTBC

IMPORTED GRANULAR

MATTER THAT COULD

DAMAGE CONDUIT FROM

AREAS ADJACENT TO

CONDUIT.

NEW CONCRETE

EXISTING BETWEEN

EXPANSION

JOINTS. REPLACE

PER CITY STANDARD

OR RED CONCRETE AS

INDICATED. MINIMUM

BEDDING SAND

3" AROUND EACH

CONDUIT.

OR RED CONCRETE AS

INDICATED. MINIMUM

BEDDING SAND

3" AROUND EACH

CONDUIT.

LINE MARKER

8" IN DEPTH - COMPACT

OTHER HARD MATTER THAT

BORROW SMOOTH BOTTOM OF

COULD DAMAGE CONDUIT FROM

STONES LARGER THAN 1" OR

INSTALLATION. REMOVE

TRENCH PRIOR TO CONDUIT

GRADE 1 UTBC

6" TYP.

7" THICK BITUMINOUS

AC-10, DM-3/4 CLASS IV

SURFACE COURSE,

ROADWAY RESTORATION

CURBS. DO NOT DISTURB CURBS.

INSTALL CONDUIT BENEATH AND

RESTORE AS DETAILED.

SIMILAR WHEN CROSSING EXISTING

18" MIN.

SAWCUT EXISTING ASPHALT TO 8" MINIMUMEXISTING CURB

DO NOT DAMAGE

SEAL WITH CRAFT-CO

210 JOINT SEALANT

GRADE SS-1 TACK COAT

IMPORTED GRANULAR BACKFILL

AREAS ADJACENT TO CONDUIT.

3'- 0"

OR RED CONCRETE AS

INDICATED. MINIMUM

BEDDING SAND

3" AROUND EACH

CONDUIT.

SCALE: NONE

TRENCH DETAIL-ROADWAY RESTORATION1

E-504

SCALE: NONE

TRENCH DETAIL-SIDEWALK RESTORATION2

E-504

SCALE: NONE

TRENCH DETAIL-ROADWAY RESTORATION3

E-504

SURFACE

WIREWAY

SURFACE

WIREWAY

2" MINIMUM

CLEARANCE

2" MINIMUM

CLEARANCE

SCALE: NONE

TERMINAL BLOCK CLEARANCE DETAIL4

E-504

HATCH OPENING

PVC COATED GRS COUPLING AND CONDUIT

TO VFD OVERSIZED TO RUN SUBMERSIBLE

S.S. HOOK AND ANCHOR

S.S. KELLUMS GRIP

MOTOR LEAD CABLE ORDER WITH

ENOUGH LENGTH TO REACH VFD

PVC BELL END

PUMP CABLE TO VFD.

CONNECTOR

3/4" GROUND ROD

ROD TYPE EXOTHERMIC

SCALE: NONE

PUMP MOTOR LEAD MOUNTING DETAIL5

E-504 (MOTOR MONITORING CABLE SIMILAR)

SCALE: NONE

CABLE TO ROD CONNECTION DETAIL6

E-504 TYPICAL

3/4" GALVANIZED COUPLING OR

METALLIC SLEEVE

ENCLOSURE

BACK PANEL

DIN RAIL

THREADED

BACK PANEL

#10-32

PAN HEAD

SCREW

1" FROM END

OF DIN RAIL

18" MAXIMUM

SCALE: NONE

DIN RAIL MOUNTING DETAIL7

E-504

SCALE: NONE

UNISTRUT SUPPORT DETAIL

DETAIL NOTES

MAST, 1" RGS.

CONDUIT CLAMPS

BOND TO CABINET AND TO SURGE SUPPRESSORS

AND POWER SUPPLIES WITHIN CABINET.

#6 B.C. SOLID COPPER GROUND.

BOND TO MAST.

S.O. EXTERIOR ARRAY CABLE / WIRING HARNESS.

ENCLOSURE. NEMA 12.

E-504

FROM FIELD

DEVICE

HOME RUN

SIDE VIEW

FRONT VIEW

TO GROUND GRID. SEE SITE PLAN.8

2 3

ANTENNA

WEATHER HEAD

SPEC.

NIG SREENE

I:\

7\

JO

RD

AN

R

IV

ER

-B

LA

IR

\0

1- D

W G\

EL

EC

\S H

EE

T\

7- E-

4-

(JR

-B

).d w g, /2 7/

:3

9:

P M

, k br

SCALE: NONE

BLAIR STREET PUMP STATION ELECTRICAL ONE-LINE DIAGRAM1

E-601

2.3

EOL EOL

P106

EXISTING ROCKY MOUNTAIN

POWER SECTIONALIZER

OR PRIMARY VOLTAGE

SOURCE

EXISTING POLE-MOUNT

TRANSFORMER, OVERHEAD FEED.

MOTOR CONTACTORS AND

CONTROLS IN SAME NEMA 3R

ENCLOSURE

NG

100/2

30/2

125A 240/120V, 1Ø

EUSERC METER MAIN

#6 B.C.

10' x 3/4"

GROUND RODS

P111

1 PHASE 240 VOLT, 2.3

HP SUBMERSIBLE PUMP

30/2

P106

P111

2.3

1 PHASE 240 VOLT, 2.3

HP SUBMERSIBLE PUMP

SEE PANEL SCHEDULE FOR

ADDITIONAL LOADS

20/1

JUNCTION BOXES AS REQUIRED

P109SHARED CONDUIT

NIG SREENE

I:\

7\

JO

RD

AN

R

IV

ER

-B

LA

IR

\0

1- D

W G\

EL

EC

\S H

EE

T\

7- E-

1-

(JR

-B

).d w g, /2 7/

:3

9:

P M

, k br

SCALE: NONE

JORDAN RIVER PUMP STATION ELECTRICAL ONE-LINE DIAGRAM1

E-603

M

(E)EUSERC

METER

P104 P104

P105 P105

240V, 1Ø INPUT

OUTPUT FOR

240V, 3Ø, 3W

MOTOR CONTROL

20HP. DERATE FOR

ELEVATION

VFDVFD

EXISTING ROCKY MOUNTAIN

POWER SECTIONALIZER

OR PRIMARY VOLTAGE

SOURCE

EXISTING POLE-MOUNT

TRANSFORMER, OVERHEAD FEED.

COORDINATE REQUIREMENTS WITH

UTILITY.

N G 60/2

PANEL 'JORDAN RIVER'

125/2

240 / 120V, 125A

NEMA 3R, 10 KAIC

SEE PANEL SCHEDULE

FOR ADDITIONAL LOADS VFD'S AND CONTROLS

IN SAME NEMA 3R

ENCLOSURE

240V, 1Ø INPUT

OUTPUT FOR

240V, 3Ø, 3W

MOTOR CONTROL

20HP. DERATE FOR

ELEVATION

240V, 3Ø, 10 HP PUMP240V, 3Ø, 10 HP PUMP

60/2

G N

(E)SERVICE

DISCONNECT

FIELD VERIFY NEUTRAL

GROUND BOND

20/1

JUNCTION BOXES AS REQUIRED

P110SHARED CONDUIT

NIG SREENE

I:\

7\

JO

RD

AN

R

IV

ER

-B

LA

IR

\0

1- D

W G\

EL

EC

\S H

EE

T\

7- E-

2-

(JR

-B

).d w g, /2 7/

:3

9:

P M

, k br

240V, 1Ø

PUMP

MOTOR

SCALE: NONE

PUMP VFD CONTROLS DIAGRAM1

E-603

VFD WITH

HARMONICS

MITIGATION

TO CONTROLLER

RUN STATUS

JORDAN RIVER STORM WATER

C

F1 F2

240V, 1Ø

PUMP

MOTOR

MOTOR STARTER

O / L

ELECTRONIC OVERLOADS

AUX

SCALE: NONE

PUMP CONTROLS DIAGRAM3

E-603

BLAIRE STREET STORM WATER

TO CONTROLLER

RUN STATUS

R

OOX

HAND

XOO

OFF

AUTO

R2

RUN CMD

PUMP 1

15A

120VAC PANEL

R18-1

R6

PUMP RUNNING

G

TO RTU

RUNNING

STATUS

PUMP RUNNING PILOT

R12

HIGH FLOAT R12-4

TO RTU HIGH

FLOAT ALARM

R12 R12-1

LOW FLOAT LOW LEVEL FLOAT ELEVATION TO BE SET

BELOW ALL PUMPS OFF ELEVATION. HIGH

LEVEL FLOAT TO BE SET ABOVE ALL PUMPS

ON ELEVATION. SEE CIVIL SHEETS FOR

ELEVATIONS.

ALTERNATING

RELAY

18 71

20 82

R R18

R R20

R12-2

R12-3

SCALE: NONE

CONTROLS WIRING DIAGRAM4

E-603

TYPICAL OF 2

TYPICAL OF 2

FROM CONTROLLER

RUN CMD

C

FROM CONTROLLER

RUN CMD

TO RTU

VFD FAIL

TO STARTER/VFD

RUN CMD

R2-1

R6

R6-1

R

OOX

HAND

XOO

OFF

AUTO

R8

RUN CMD

PUMP 2

R20-1

R10

PUMP RUNNING

G

TO RTU

RUNNING

STATUS

PUMP RUNNING PILOT

TO STARTER/VFD

RUN CMD

R8-1

R10

R10-1

TYPICAL OF 2

20A, 120V

DUPLEX OUTLET

WP, GFCI

H

G

N

RTU / HMI

POWER

SUPPLY

R24-1

TO RTU

POWER FAIL

SUPPLY

NIG SREENE

I:\

7\

JO

RD

AN

R

IV

ER

-B

LA

IR

\0

1- D

W G\

EL

EC

\S H

EE

T\

7- E-

3-

(JR

-B

).d w g, /2 7/

:4

0:

P M

, k br

File details come from the government source that posted it. Updated .