3-26KP03 Herriman HS Greenhouse Drawings.pdf
PDF 25 MB Posted
- Attached to
- Herriman High School Greenhouse
- Solicitation number
- 26KP03
- Issued by
- Salt Lake County, Hildale City, Utah
About this file
The provided file is a comprehensive set of construction documents for the Herriman High School Greenhouse project, prepared by GSBS Architects for the Jordan School District in Herriman, Utah. The project involves constructing a new freestanding greenhouse adjacent to the existing high school building, with detailed architectural, structural, plumbing, and electrical plans. The documents include grading plans, site layouts, irrigation designs, floor plans, foundation specifications, and utility connection details for a greenhouse structure approximately 30 feet by 45 feet, with associated utility connections and minor interior modifications to existing school spaces.
The project is funded through the Jordan School District and will be awarded to the lowest responsive and responsible bidder meeting the specification requirements. The construction documents specify a Type VB construction with a single-story greenhouse featuring polycarbonate wall and roof enclosures, architectural concrete stem walls, environmental control systems, metal benches, and utility connections including a service sink, water heater, and electrical panel. The project is designed to comply with 2021 International Building Codes and includes specific provisions for site preparation, utility routing, and integration with the existing school infrastructure, with careful consideration for preserving existing site features like trees, walkways, and irrigation systems.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
26KP03
09/15/2025
2025.047.00
HERRIMAN HIGH
SCHOOL
GREENHOUSE
OWNER PROJECT NO.:
GSBS PROJECT NO.:
ISSUED DATE:
11917 Mustang Trail Way, Herriman, UT 84096
GSBS
375 WEST 200 SOUTH
SALT LAKE CITY, UT 84101
801.521.8600 801.521.7913
P F www.gsbsarchitects.com
REV
CONSTRUCTION DOCUMENTS
HATUFOETATS
T C
ETIHCRADES
N E
CI
L
261112-0301
VALERIE
W. NAGASAWA
VICINITY MAP
HERRIMAN
HIGH SCHOOL
GI001
CODE ANALYSIS, SYMBOLS, AND
ABBREVIATIONS
SITE LOCATION
CODE ANALYSIS
ABBREVIATIONS GRAPHIC SYMBOLS MATERIALS/LEGEND
BLOCKING, ROUGH WOOD
METAL (LARGE SCALE)
QUARRY/CERAMIC TILE
GRAVEL
EARTH
CONCRETE MASONRY UNIT
CONCRETE (POURED IN PLACE)
GYPSUM BOARD OR SETTING BEDS
INSULATION (BATT & BLANKET)
INSULATION (RIGID/SEMI-RIGID)
CONTINUOUS ROUGH WOOD
PLYWOOD
FACE BRICK
GRID
GRID
W1
100A
ELEVATION CONTROL POINT
OR DATUM POINT
EXTERIOR ELEVATION SYMBOL
ELEVATION IDENTIFICATION
SHEET WHERE ELEVATION IS DRAWN
WALL SECTION SYMBOL
SECTION REFERENCE/
SHEET WHERE SECTION IS DRAWN
BUILDING SECTION SYMBOL
SECTION REFERENCE/
SHEET WHERE SECTION IS DRAWN
DETAIL SYMBOL
DETAIL NUMBER/
SHEET WHERE DETAIL IS DRAWN
REVISION TAG
GRID LINES
NAME
SHEET #
SHEET
SHEET
SHEET
SHEET
SCALE
VIEW NAME
VIEW TITLE
VIEW NUMBER/
SHEET WHERE VIEW IS LOCATED
VIEW NAME/ VIEW SCALE
INTERIOR ELEVATION SYMBOL
ELEVATION IDENTIFICATION
SHEET WHERE ELEVATION IS DRAWN
SHEET #
ROOM TAG
ROOM NAME
ROOM NUMBER
WINDOW TAG
WINDOW OR STOREFRONT NUMBER
DOOR TAG
DOOR NUMBER
WOOD
COMPACTED FILL
FIREPROOFING
ABV ABOVE
AFF ABOVE FINISH FLOOR
ADJ ADJUSTABLE
ALUM ALUMINUM
ASTM AMERICAN SOCIETY FOR TESTING
MATERIALS
AB ANCHOR BOLT
ANOD ANODIZED
APPROX APPROXIMATE
ARCH ARCHITECTURAL OR ARCHITECT
AHJ AUTHORITY HAVING JURISDICTION
(BUILDING DEPARTMENT)
BP BASE PLATE
BSMT BASEMENT
BRG BEARING
BTWN BETWEEN
BITUM BITUMINOUS
BLKG BLOCKING
BD BOARD
BO BOTTOM OF
BLDG BUILDING
CLG CEILING
CL CENTER LINE
CLR CLEAR
COL COLUMN
CONC CONCRETE
CMU CONCRETE MASONRY UNIT
CONST CONSTRUCTION
CONT CONTINUOUS
CFOI CONTRACTOR FURNISHED OWNER
INSTALLED
CJ CONTROL JOINT
COORD COORDINATE
DEMO DEMOLISH / DEMOLITION
DEPT DEPARTMENT
DTL DETAIL
DIA DIAMETER
DIM DIMENSION
DW DISHWASHER
DBL DOUBLE
DN DOWN
DRWR DRAWER
DWGS DRAWINGS
EA EACH
ELEC ELECTRICAL
EL ELEVATION
ELEV ELEVATOR
EQ EQUAL
EPDM ETHYLENE PROPYLENE DIENE M-CLASS
(ROOFING)
EXIST EXISTING
EXP EXPANSION
EJ EXPANSION JOINT
EXT EXTERIOR
FT FEET / FOOT
FV FIELD VERIFY
FIN FINISH
FF FINISH FLOOR
FA FIRE ALARM
FE FIRE EXTINGUISHER
FEC FIRE EXTINGUISHER CABINET
FLR FLOOR
FD FLOOR DRAIN
FTG FOOTING
FDN FOUNDATION
GAL GALLON
GPH GALLONS PER HOUR
GPM GALLONS PER MINUTE
GALV GALVANIZED
GA GAUGE
GC GENERAL CONTRACTOR
GL GLASS / GLAZING
GLB GLUE LAMINATED BEAM
GND GROUND
GYP BD GYPSUM BOARD
HW HARDWARE
HVAC HEATING / VENTILATION / AIR
CONDITIONING
H HEIGHT
HM HOLLOW METAL
HORIZ HORIZONTAL
HR HOUR
HYD HYDRANT
IN. INCHES OR INCH
INFO INFORMATION
INSUL INSULATION
INT INTERIOR
JNT JOINT
LAV LAVATORY
LT WT LIGHT WEIGHT
MAINT MAINTENANCE
MFR MANUFACTURER
MO MASONRY OPENING
MAT MATERIAL
MAX MAXIMUM
MECH MECHANICAL
MTL METAL
MIN MINIMUM
MISC MISCELLANEOUS
NIC NOT IN CONTRACT
NTS NOT TO SCALE
NO. NUMBER
OC ON CENTER
OPP OPPOSITE
OD OUTSIDE DIAMETER
OH OVERHEAD
OH DR OVERHEAD DOOR
OFCI OWNER FURNISHED CONTRACTOR
INSTALLED
OFOI OWNER FURNISHED OWNER INSTALLED
PNT PAINTED OR PAINT
PTN PARTITION
PVMT PAVEMENT
PERP PERPENDICULAR
PLAM PLASTIC LAMINATE
PL PLATE
PLUM PLUMBING
PVC POLYVINYL CHLORIDE
PCF POUNDS PER CUBIC FOOT
PLF POUNDS PER LINEAL FOOT
PSF POUNDS PER SQUARE FOOT
PSI POUNDS PER SQUARE INCH
PT PRESSURE TREATED
QTY QUANTITY
RAD RADIUS
RE REFER / REFERENCE
RCP REFLECTED CEILING PLAN
REF REFRIGERATOR
REINF REINFORCED
REQ REQUIRED
REV REVISION
RD ROOF DRAIN
RM ROOM
RO ROUGH OPENING
SCHED SCHEDULE
SECT SECTION
SHT SHEET
SIM SIMILAR
STC SOUND TRANSMISSION CLASS
SPEC SPECIFICATION
SS STAINLESS STEEL
STD STANDARD
STL STEEL
STRU STRUCTURAL
SUSP SUSPENDED
SYS SYSTEM
THRU THROUGH
T.O. TOP OF
TOA TOP OF ASPHALT
TOC TOP OF CURB
TOF TOP OF FOOTING
TOS TOP OF SLAB OR SIDEWALK
TOW TOP OF WALL
TYP TYPICAL
UNO UNLESS NOTED OTHERWISE
VEN VENEER
FV VERIFY IN FIELD
VERT VERTICAL
VEST VESTIBULE
WC WATER CLOSET
WRB WEATHER RESISTIVE BARRIER
W WIDTH
W/ WITH
W/O WITHOUT
WD WOOD
NOTE:
ABBREVIATIONS FOR FINISHED MATERIALS ARE DESCRIBED IN THE FINISH LEGEND
FOOTNOTES:
ADA Accessibility Guidelines
ICC/ANSI A117.1
National Electrical Code
International Energy Conservation Code
International Fire Code
International Plumbing Code
International Mechanical Code
International Building Code
Year Year
APPLICABLE CODES
A.
OCCUPANCY & USE
Group U - Utility and Maintenance Change in use - No Mixed occupancy - No Special Use & Occupancy - No
B. Seismic Design Category - D Design Wind Speed -
C. Type of Construction - Type VB
D. Fire Resistance Rating - 0 for all four exterior walls
E. Mixed Occupancies - No / Non-Separated Uses - No
F. Sprinklers Required - No
G. Number of Stories - 1 / Building Height - under 40 ft.
H. Actual Area per Floor - 1,440 sf
I. Tabular Area - 5,500 SF
Total Allowable Area for one story - 5,500 SF Unlimited Area Building - No
J. Fire Resistance Rating Requirements for Building Elements
L. Design Occupant Load - 29 occupants (50 sf/occ) Exit Width Required - 6” / Exit Width Provided - 36”
M.Minimum Number of Required Plumbing Facilities - No occupancy is being added. No plumbing fixtures are required. One utility sink is provided.
CODE ANALYSIS
1. In case of conflict with the U.S. Department of Justice Federal Registers parts through -ADA Guidelines and specific references to the International Building Code accessiblility chapters, the more restrictive requirement shall govern.
2. All codes shall be as adopted by the state of Utah and the local jurisdiciton.
Element Assembly Element HoursListing
Smoke Partitions Fire Partitions
Exterior Bearing Walls Interior Bearing Walls Exterior Non-Bearing Walls
Structural Frame Partitions -Permanent Fire Barriers
Floors -Ceiling Floors Roofs -Ceiling Roofs
Exterior Doors and Windows Shaft Enclosures Fire Walls
Assembly Listing
109 MPH (3 SEC. GUST, SEE STRUCT.
DESIGN CRITERIA ON SHEET S001)
Hours
BUS DROP-OFF LOOP
CONSTRUCTION CREW
MAY USE STALLS IN
THIS LOT FOR PARKING.
COORD. W/ OWNER
S
+07.20
06.03
EXISTING BUILDING
+06.50
FFE: 4907.50
PROPOSED GREENHOUSE
FFE: 4906.50
+06.15
+06.20
+07.10
1.94%
1.95%
+06.40
2.
4%
2.
4%
+06.50
09/15/2025
2025.047.00
HERRIMAN HIGH
SCHOOL
GREENHOUSE
OWNER PROJECT NO.:
GSBS PROJECT NO.:
ISSUED DATE:
11917 Mustang Trail Way, Herriman, UT 84096
GSBS
375 WEST 200 SOUTH
SALT LAKE CITY, UT 84101
801.521.8600 801.521.7913
P F www.gsbsarchitects.com
REV
09/15/2025
NO. 13221976-5301
P
U
DE
S
TA E FO
T
L
IC
SN
E
D
LAN CS A
R
AT
H
T
CH
I
E T
C
E A
Date
Signature
BENJAMIN N. RODES
CONSTRUCTION DOCUMENTS
LG101
GRADING PLAN
SCALE: 1" = 10'-0"
LG101
GRADING PLAN
0' 5' 10' 15' 20' 30'
EXISTING BUILDING
PROPOSED GREENHOUSE
OPEN LAWN
EXISTING BIKE
STORAGE
8'-0"
AE100
AE100
EXISTING TREES,
PRESERVE AND PROTECT IN PLACE
EXISTING ROADWAY
& BUS DROP-OFF
LOOP. MAINTAIN
ROADWAY ACCESS
THROUGH DURATION
OF CONSTRUCTION
X-101
X-102
P-101
P-102
P-103
P-101
P-102
X-101
X-103
PATCH & REPLACE
EXISTING VEHICULAR CONC.
TO ORIGINAL CONDITION
AFTER NEW UTILITY
CONNECTIONS MADE.
SEE DWG. P100
RELOCATE EXISTING IRRIGATION
VALVE ASSEMBLY TO
OPEN LAWN AREA
P-103
PATCH AND REPLACE EXISTING
TURF GRASS & PLANTING
AREAS DAMAGED FROM CONSTRUCTION
SEE PLBG. & ELECT. DWGS.
X-104
K-101
K-101
C-101
PROTECT EXISTING CONCRETE
WALK AND SNOW MELT
PIPING FROM DAMAGE
10'-0"
CODE DESCRIPTION DETAIL WIDTH
CURB
CONCRETE LANDSCAPE CURB 4/AS801 6"
CODE DESCRIPTION DETAIL COLOR SIZE FINISH
PAVING
CONCRETE PAVING 1/AS801 NATURAL
GRAY
4" DEPTH LIGHT BROOM
CONTROL JOINT; TYP. 2/AS801
EXPANSION JOINT, TYP. 2/AS801
CODE DESCRIPTION
EXISTING
EXISTING WALK TO REMAIN; PROTECT IN
PLACE
EXISTING FENCE TO REMAIN; PROTECT IN
PLACE
EXISTING UTILITY; PRESERVE AND PROTECT
IN PLACE
EXISTING LIGHT POLE; PRESERVE AND
PROTECT IN PLACE
CODE DESCRIPTION COLOR SIZE
ROCK
ANGULAR ROCK MULCH; CONTRACTOR TO
MATCH EXISTING ROCK MULCH ON SITE AS
SHOWN BELOW
TAN 3"-6"
C-101
K-101
P-101
P-102
P-103
X-101
X-102
X-103
X-104
REFERENCE NOTES SCHEDULE
09/15/2025
2025.047.00
HERRIMAN HIGH
SCHOOL
GREENHOUSE
OWNER PROJECT NO.:
GSBS PROJECT NO.:
ISSUED DATE:
11917 Mustang Trail Way, Herriman, UT 84096
GSBS
375 WEST 200 SOUTH
SALT LAKE CITY, UT 84101
801.521.8600 801.521.7913
P F www.gsbsarchitects.com
REV
09/15/2025
NO. 13221976-5301
P
U
DE
S
TA E FO
T
L
IC
SN
E
D
LAN CS A
R
AT
H
T
CH
I
E T
C
E A
Date
Signature
BENJAMIN N. RODES
CONSTRUCTION DOCUMENTS
LS101
SITE PLAN
SCALE: 1" = 10'-0"
LS101
SITE PLAN
HERRIMAN
HIGH SCHOOL
PROJECT LOCATION
0' 5' 10' 15' 20' 30'
KEYPLAN
HERRIMAN HIGH
SCHOOL
GREENHOUSE
OWNER PROJECT NO.:
GSBS PROJECT NO.:
ISSUED DATE:
11917 Mustang Trail Way, Herriman, UT 84096
GSBS
375 WEST 200 SOUTH
SALT LAKE CITY, UT 84101
801.521.8600 801.521.7913
P F www.gsbsarchitects.com
REV
09/15/2025
NO. 13221976-5301
P
U
DE
S
TA E FO
T
L
IC
SN
E
D
LAN CS A
R
AT
H
T
CH
I
E T
C
E A
Date
Signature
BENJAMIN N. RODES
CONSTRUCTION DOCUMENTS
LS801
SITE & PLANTING
DETAILS
4" CONCRETE WALK
1/2" = 1'-0"
NOTES:
1. CONTROL JOINTS AT CONSISTENT ON CENTER SPACING OR AS
INDICATED. CROSS SLOPE, 1/4":12" = 2%
2. FOR JOINTS, SEE DETAIL:
COMPACTED SUBGRADE
FINISH GRADE
CONCRETE WALK, REFERENCE MATERIALS
SCHEDULE FOR COLOR AND FINISH
95% COMPACTED AGGREGATED
BASE COURSE
VARIES; REF. PLANS
6" 4"
1"
P-HHG-01
CONC. PAVING JOINT DETAILS
1" = 1'-0"
TOOLED CONCRETE JOINT
SEALANT CONSTRUCTION JOINT
CONCRETE CURB,
WALL, ETC.
CONCRETE PAVING AT VERTICAL PLANE
ENLARGED TYPICAL SEALANT JOINT - NTS
PREMOLDED EXPANSION JOINT
FILLER PER SPECIFICATIONS
TYPICAL 1/4" TOOLED RADIUS EDGE
TYPICAL CONCRETE PAVING
FOAM BACKER ROD
MASTER SEALANT, PER SPECIFICATIONS,
COLOR TO MATCH ADJACENT PAVING. WIDTH
TO DEPTH RATIO OF MASTIC PER
MANUFACTURERS RECOMMENDATIONS
TYPICAL CONCRETE PAVING
SEALANT JOINT, SEE
ENLARGEMENT DETAIL
SEALANT JOINT, SEE
ENLARGEMENT DETAIL
TYPICAL CONCRETE
PAVING
TYPICAL 1/2" TOOLED
RADIUS EDGE
1/
2" D
EE
P
TYPICAL CONCRETE
PAVING
TYPICAL 1/4" TOOLED
RADIUS EDGE
P-HHG-05
LS801
TREE PROTECTION
NTS
6' -0
EXISTING TREE
TREE CANOPY
CONSTRUCTION FENCE STAKED
AT 4'-0" O.C.. LOCATE 2/3
DISTANCE OF CANOPY DRIP LINE
AND IN A COMPLETE CIRCLE
AROUND TREE
TREE PRESERVATION NOTES
1. TREES CALLED OUT FOR PRESERVATION SHALL BE FENCED AT THE DRIPLINE.
FENCING MAY OCCUR AT THE COMBINED DRIPLINES OF TREES TO BE PRESERVED.
2. FENCING SHALL BE 6-FOOT TALL CHAIN LINK FENCING WITH STEEL POSTS IMBEDDED
IN THE GROUND.
3. NO GRADING SHALL OCCUR WITHINTHE DRIPLINES/FENCED AREA OF EXISTING
TREES.
4. NO CONSTRUCTION MATERIALS OR CONSTRUCTION VEHICLES MAY BE STORED
WITHIN THE DRIPLINES/FENCING AREAS OF EXISTING TREES.
5. CONSTRUCTION VEHICLES OR MACHINERY MAY NOT PASS BETWEEN TWO OR MORE
EXISTING TREES IDENTIFIED FOR PRESERVATION IF THEIR CANOPIES ARE WITHIN 10
FEET OF TOUCHING.
6. TREE PRESERVATION MEASURES MUST BE IN PLACE BEFORE CONSTRUCTION,
DEMOLITION AND /OR GRADING ACTIVITIES COMMENCE.
7. THE CONTRACTOR IS REQUIRED TO HAVE AN ARBORIST CERTIFIED BY THE
INTERNATIONAL SOCIETY OF ARBORICULTURE (ISA) ON SITE, IF SITE CONSTRUCTION
EFFORTS REQUIRE REMOVAL OF EXISTING ROOTS OR BRANCH PRUNING. A CERTIFIED
ARBORIST SHALL BE ON SITE AND MONITOR ALL ROOT PRUNING AND BRANCH
PRUNING OF EXISTING TREES.
8. UNAUTHORIZED TREE REMOVAL IS SUBJECT TO IN-KIND REPLACEMENT EQUAL TO
THE MATURE RESOURCE LOST.
9. THE CONTRACTOR IS REQUIRED TO WATER, FERTILIZE AND ATTEND TO OTHER
MAINTENANCE NEEDS OF EXISTING TREES AS NEEDED TO MAINTAIN HEALTHY
GROWTH THROUGHOT THE CONSTRUCTION PERIOD. SIX FEET DIAMETER, MINIMUM,
BY SIX-INCH TALL EARTH BERMS SHALL BE CONSTRUCTED AT THE BASE OF EACH
TREE TO FUNCTION AS TEMPORARY WATERING BASINS DURING THE CONSTRUCITON
PERIOD. TREES SHALL BE WATERED ACCORDING TO WEATHER AND TREE
REQUIREMENTS.
FINISHED GRADE
P-HHG-38
LS801
CONC. LANDSCAPE CURB
1 1/2" = 1'-0"
PLANTING, SEE
PLANTING PLANS
VARIES
6" 4"
1/
2"
NOTE: INSTALL CONTROL JOINTS
EVERY 5' AND EXPANSION
JOINTS EVERY 30'.
95% COMPACTED
SUBGRADE
AGGREGATE BASE
CONCRETE
MOW CURB
FINISH GRADE
1/2" TOOLED EDGE
P-HHG-02
SOD INSTALLATION
NTS
1/ 2"
SOD
TIGHT BEVELED JOINTS
PLANT MIX
CURB OR SIDEWALK EDGE
PREPARED SUB-GRADE
P-HHG-49
SHRUB PLANTING
NTS
MULCH
PLANTING
MIX
PREPARED SUB-GRADE
INSTALL SHRUB SO THAT
ROOT FLARE IS AT FINISH
GRADE, DO NOT PLACE
MULCH WITHIN 3" OF
SHRUB TRUNK
FILTER FABRIC
P-HHG-03
PERENNIAL PLANTING
NTS
PREPARED SUB-GRADE
MULCH
PLANTING MIX
INSTALL PERENNIAL SO
THAT ROOT FLARE IS AT
FINISH GRADE, DO NOT
PLACE MULCH WITHIN 3"
OF PLANT
FILTER FABRIC
P-HHG-06
LS801
LS801LS801
LS801
LS801
EXISTING BUILDING
PROPOSED GREENHOUSE
RELOCATE EXISTING IRRIGATION
VALVE ASSEMBLY TO
OPEN LAWN AREA
EXISTING 3" MAINLINE
1.5
1.5
1.5
-1 2"
8.462 1"
CONNECT EXISTING VALVE
TO EXISTING HEADS IN
LAWN AREA. RE-USE
EQUIP. WHERE POSSIBLE
NEW DRIP VALVE
1"
1.5
1.5
RE-ROUTE MAINLINE
AROUND PROPOSED
GREENHOUSE STRUCTURE
SYMBOL MANUFACTURER/MODEL PSI GPM RADIUS DETAIL
RAIN BIRD 5004-PL-PC-SAM-R-NP-SS 1.5 35 1.35 34' 7/LI801
SYMBOL MANUFACTURER/MODEL/DESCRIPTION DETAIL
RAIN BIRD XCZ-100-PRF
MEDIUM FLOW DRIP CONTROL KIT, 1IN. DV VALVE, 1IN.
PRESSURE REGULATING FILTER, 40PSI PRESSURE
REGULATOR. 5 GPM-20 GPM.
3/LI801
AREA TO RECEIVE DRIPLINE
NETAFIM TLDL-06-12
TECHLINE PRESSURE COMPENSATING LANDSCAPE DRIPLINE.
0.6 GPH EMITTERS AT 12" O.C. DRIPLINE LATERALS SPACED
AT 12" APART, WITH EMITTERS OFFSET FOR TRIANGULAR
PATTERN. SURFACE AND SUB SURFACE INSTALLATIONS. UV
RESISTANT.
1/LI802
SYMBOL MANUFACTURER/MODEL/DESCRIPTION DETAIL
RAIN BIRD EFB-CP-PRS-D
1IN., 1-1/2IN., 2IN. BRASS REMOTE CONTROL VALVE, THAT IS
CONTAMINATION PROOF W/SELF-FLUSHING FILTER SCREEN.
GLOBE CONFIGURATION, RECLAIMED WATER COMPATIBLE,
AND PURPLE HANDLE COVER DESIGNATES NON-POTABLE
WATER USE.
2/LI801
IRRIGATION LATERAL LINE: PVC SCHEDULE 40
IRRIGATION MAINLINE: PVC CLASS 200 SDR 21
PIPE SLEEVE: DUCTILE IRON PIPE- CLASS 350
1.5
VALVE NUMBER
VALVE SIZE
VALVE GPM
VALVE CALLOUT
IRRIGATION SCHEDULE
09/15/2025
2025.047.00
HERRIMAN HIGH
SCHOOL
GREENHOUSE
OWNER PROJECT NO.:
GSBS PROJECT NO.:
ISSUED DATE:
11917 Mustang Trail Way, Herriman, UT 84096
GSBS
375 WEST 200 SOUTH
SALT LAKE CITY, UT 84101
801.521.8600 801.521.7913
P F www.gsbsarchitects.com
REV
09/15/2025
NO. 13221976-5301
P
U
DE
S
TA E FO
T
L
IC
SN
E
D
LAN CS A
R
AT
H
T
CH
I
E T
C
E A
Date
Signature
BENJAMIN N. RODES
CONSTRUCTION DOCUMENTS
LI101
IRRIGATION PLAN
SCALE: 1" = 10'-0"
LI101
IRRIGATION PLAN
0' 5' 10' 15' 20' 30'
IRRIGATION NOTES
1. CONTRACTOR SHALL VERIFY STATIC PRESSURE AT POINT OF CONNECTION
AND OPERATING PRESSURE AT EACH HEAD AS INDICATED. PRESSURE BELOW
DESIGN PRESSURE INDICATED ON IRRIGATION PLANS SHALL BE BROUGHT TO
THE ATTENTION OF THE LANDSCAPE ARCHITECT IMMEDIATELY.
2. ALL HEADS SHALL BE SET PERPENDICULAR TO FINISH GRADE.
3. ALL MAINLINE CONNECTIONS TO CULINARY WATER SERVICE LINES SHALL
HAVE BACKFLOW PREVENTION AS REQUIRED BY LOCAL MUNICIPALITY CODES
AND ORDINANCES.
4. ALL VALVES SHALL BE LOCATED IN GROUPS WHERE SHOWN ON DRAWINGS.
VALVES SHALL BE LOCATED 2'-6" AWAY FROM ANY FENCE, MOWSTRIP,
WALK, CURB, OR BUILDING.
5. ALL VALVES SHALL BE WIRED USING #14 U.F. WIRE OR MANUFACTURERS
RECOMMENDED 2 WIRE AND PEN-TITE WATER RESISTANT WIRE CONNECTORS.
CONTROL CABLE SHALL FOLLOW THE MAINLINE IN THE SAME TRENCHES.
TAPE AND BUNDLE 2 FEET OF CABLE EVERY 100 FEET, AT EACH TURN IN THE
MAINLINE TRENCH, AND AT EACH VALVE.
6. THE CONTRACTOR SHALL PROVIDE AS-BUILT DRAWINGS OF THE IRRIGATION
SPRINKLER SYSTEM SHOWING EXACT MEASURED AND DIMENSIONED
LOCATIONS OF ALL VALVES, WIRE SPLICES NOT IN A VALVE BOX AND DRAIN
VALVES. REFERENCE DIMENSIONS TO PERMANENT STRUCTURES.
7. THE IRRIGATION DESIGN IS SCHEMATIC. ALL PIPING, VALVES, HEADS, ETC.,
SHOWN OUTSIDE OF THE PLANTING AREA IS FOR GRAPHIC CLARITY ONLY
AND SHALL BE INSTALLED WITHIN THE PLANTING AREA. COORDINATE
IRRIGATION, PLANTING AND OTHER SITE OPERATIONS. VERIFY AVAILABLE
WATER PRESSURE AND FLOW AT SUPPLY SOURCE PRIOR TO BEGINNING
WORK. THE CONTRACTOR SHALL BECOME FAMILIAR WITH ALL GRADE
DIFFERENCES, LOCATION OF ALL CONSTRUCTED ITEMS, BUILDINGS
DIFFERENCES IN ACTUAL AND DRAWN DIMENSIONS, UNDERGROUND
SERVICES, ETC. PRIOR TO BEGINNING CONSTRUCTION. CALL UTILITY SERVICE,
TO IDENTIFY LOCATIONS OF ALL UNDERGROUND SERVICES.
8. NOTIFY LANDSCAPE ARCHITECT IMMEDIATELY IF IRRIGATION LAYOUT SHOWS
ANY DISCREPANCY BETWEEN DESIGNED IRRIGATION SYSTEM AND ACTUAL
SITE CONDITIONS. LANDSCAPE ARCHITECT WILL MAKE ANY NECESSARY
DECISIONS TO ADJUST DESIGN. NO MAJOR CHANGES OR SUBSTITUTIONS
SHALL BE MADE TO THE IRRIGATION SYSTEM WITHOUT WRITTEN APPROVAL
OF THE LANDSCAPE ARCHITECT.
9. INSTALL SLEEVES AND PIPING IN A PARALLEL OR PERPENDICULAR MANNER,
FOLLOWING THE GENERAL LAYOUT OF THE PAVING DESIGN. THE
CONTRACTOR SHALL ENSURE 100%, HEAD TO HEAD SPRINKLER COVERAGE
FOR ALL LAWN AREAS, AND SHALL ADJUST THE IRRIGATION HEADS TO
ACCOMPLISH SUCH. FLUSH AND ADJUST HEADS TO ENSURE NO OVERTHROW
ONTO WALLS, WALKS, STREETS, OR OTHER HARD SURFACES.
10. THE IRRIGATION SYSTEM SHALL BE INSTALLED IN ACCORDANCE WITH ALL
LOCAL CODES AND ORDINANCES BY A LICENSED LANDSCAPE CONTRACTOR
AND EXPERIENCED WORKERS. ALL PERMITS SHALL BE OBTAINED AND FEES
PAID BY THE CONTRACTOR.
P-HHG-46LI101
HERRIMAN HIGH
SCHOOL
GREENHOUSE
OWNER PROJECT NO.:
GSBS PROJECT NO.:
ISSUED DATE:
11917 Mustang Trail Way, Herriman, UT 84096
GSBS
375 WEST 200 SOUTH
SALT LAKE CITY, UT 84101
801.521.8600 801.521.7913
P F www.gsbsarchitects.com
REV
09/15/2025
NO. 13221976-5301
P
U
DE
S
TA E FO
T
L
IC
SN
E
D
LAN CS A
R
AT
H
T
CH
I
E T
C
E A
Date
Signature
BENJAMIN N. RODES
CONSTRUCTION DOCUMENTS
LI801
IRRIGATION DETAILS
LI801
VALVE ASSEMBLY
NTS
VALVE BOX
REMOTE CONTROL VALVE
MAXIMUM 2 VALVES PER BOX
SCH 80 UNION
GATE VALVE
(1) PER MANIFOLD
SCH 80 UNION
FINISH GRADE
MAINLINE
3/4" MINUS GRAVEL
2" CLEAR
BRICK SUPPORT SET ON 3/4"
MINUS GRAVEL BEDDING
LATERAL LINE
3" 2"
SCH 80
RISER
SET VALVE BOX
FLUSH AT TURF,
2" ABOVE FINISHED
GRADE IN PLANTING
AREAS
P-HHG-19
1" DRIP VALVE/FILTER/REG.
NTS
B
EL
O W
G R
A D
E
2"
ISOLATION VALVE, (1)
PER MANIFOLD
JUMBO PLASTIC
VALVE BOX
SCH. 80
RISER
SxSxT TEE W/
NIPPLE AT
MAINLINE
(2) BRICKS OVER
COMPACTED SUB
GRADE, ONE ON
EACH SIDE OF THE
VALVE BOX
45° DOWN AS REQ.
TO LATERAL LINE
DEPTH
OUTLET PIPE
SAME SIZE AS VALVE,
24" MIN. LENGTH TO
FIRST FITTING
PVC UNION W/
SHORT NIPPLES
RCV DRIP KIT AS
INDICATED
CONTROLLER WIRE WITH 30 INCH
LINEAR LENGTH OF COIL, WITH
PLASTIC I.D. TAG AND WATERPROOF
CONNECTORS
3/4" MINUS GRAVEL
SET VALVE BOX FLUSH
AT TURF, 2" ABOVE
FINISHED GRADE IN
PLANTING AREAS
FINISHED GRADE
P-HHG-07
WIRE BUNDLE JUNCTION BOX
NTS
MAINLINE AS OCCURS
WIRES TO CONTROLLER
SPARE WIRES THAT ARE
TO TERMINATE AT THIS
BOX; COIL 30" LENGTH
AND I.D. TAG.
SET BOX FLUSH TO
GRADE AT LAWN
SET BOX 2" ABOVE
GRADE AT SHRUBS
10"x15"
STANDARD BOX
VALVE BOX LID, HEAD
BRAND "J BOX" ON LID
WITH 2" HIGH LETTERS
LOOP, BUNDLE, AND
LABEL SPARE WIRES
THAT ARE TO
CONTINUE, AS OCCURS
(2) 6"x2"x16" CONCRETE
BLOCK CAPS, ONE ON
EACH SIDE OF BOX
1/2" WIRE CLOTH GOPHER
PROTECTION SCREEN,
WRAP 6" UP SIDES
P-HHG-16
TRENCH SECTION
NTS
1' -0
1' -6
4"
NOTE: ALL PIPE RUNNING UNDER PAVEMENT
SHALL BE IN SLEEVING, SIZE AS REQUIRED.
FINISH GRADE
LATERAL LINE
VALVE WIRE CONDUIT
UNDER PAVEMENT ONLY
MAINLINE
CONTROL WIRES
PLANT MIX IN PLANTING AREA,
OR 8" MINIMUM ROCK FREE
SOIL ON ALL SIDES UNDER
PAVEMENT TYPICAL
P-HHG-17
VALVE BOX TYPICAL LOCATION
NTS
PLANTING AREA OR LAWN
JUMBO IRRIGATION VALVE BOX,
MAXIMUM 2 VALVES PER BOX
1'-0" 1'-0"
2' -6
PAVING OR BUILDING CONCRETE
P-HHG-15
SLEEVING
NTS
PVC INDICATOR
PIPE/ CAP (TYPICAL)
PAVING
18" MIN.
18" MIN.
24" MAX.
PVC CAP (TYPICAL)
PAVING
4"MIN CLEARANCE
SLEEVES
2 - 6"PVC (TYP) FOR MAIN
LINE SLEEVES
2 - 4"PVC (TYP) FOR
SECTION LINE SLEEVES
NOTE: ALL PVC IRRIGATION SLEEVES TO BE SCHEDULE 40 PIPE.
ALL JOINTS TO BE SOLVENT WELDED AND WATERTIGHT.
WHERE THERE IS MORE THAN ONE SLEEVE, EXTEND THE
SMALLER SLEEVE. MECHANICALLY TAMP TO 95% PROCTOR.
TRENCH, 8" MINIMUM
ROCK FREE SOIL ON
ALL SIDES TYPICAL
24" MIN. TO
FINISH GRADE
4"MIN CLEARANCE
P-HHG-04
POP-UP SPRAY HEAD
NTS
PLANTING AREA,
SEE PLANTING PLAN
FINISHED GRADE
POP-UP SPRAY HEAD
MARLEX STREET ELL
FLEXIBLE POLYETHYLENE
JOINT (24" MAX.)
LATERAL LINE
P-HHG-65
LI801
LI801
LI801
LI801
LI801
LI801
30'-0"
0"
EXISTING WALL &
BIKE STORAGE AREA
EVAPORATIVE PAD WALL
& AIR INTAKE BY GREENHOUSE
MFR.
UTILITY SINK, HOSE BIB
& WATER HEATER,
SEE MECH/PLBG.
DRAWINGS
SL
O
PE
T
O D
R A
IN
SL
O
PE
T O
D R
A
IN
SL
O
PE
T
O D
R A
IN
SL
O
PE
T
O D
R A
IN
T.O. SLAB = 100'-0"
(EL. 4906'-6")
T.O. SLAB = 100'-0"
(EL. 4906'-6")
GREENHOUSE
B
A
ELECTRICAL
PANEL,
SEE ELECT.
DRAWINGS
ENVIRONMENTAL
CONTROLS PANEL
BY GREENHOUSE
MFR.
SLOPE SLAB TO DRAIN
TRENCH DRAIN
SEE MECH./PLBG.
DRAWINGS
STATIONARY METAL
BENCHES, OFOI
STEEL STRUCTURE
BY GREENHOUSE
MANUFACTURER
POLYCARBONATE
WALL & ROOF
ENCLOSURE BY
GREENHOUSE MFR.
ARCHITECTURAL CONC.
STEM WALL TO 3'-0"
A.F.F., SEE STRUCT.
DRAWINGS
TRENCH DRAIN
SEE MECH./PLBG.
DRAWINGS
FREESTANDING
METAL SUPPLY
SHELVING, OFOI.
ANY EQUP. BY
GREENHOUSE MFR.
IN VICINITY OF
SHELVING TO BE
MOUNTED HIGH TO
AVOID CONFLICT
LOCATE EXHAUST
FANS (PROVIDED BY
GREENHOUSE MFR.) TO
MAINTAIN AT LEAST
66" OF CLEAR WALL
SPACE IN CORNERS FOR
TALL STORAGE SHELVING
09/15/2025
2025.047.00
HERRIMAN HIGH
SCHOOL
GREENHOUSE
OWNER PROJECT NO.:
GSBS PROJECT NO.:
ISSUED DATE:
11917 Mustang Trail Way, Herriman, UT 84096
GSBS
375 WEST 200 SOUTH
SALT LAKE CITY, UT 84101
801.521.8600 801.521.7913
P F www.gsbsarchitects.com
REV
CONSTRUCTION DOCUMENTS
HATUFOETATS
T C
ETIHCRADES
N E
CI
L
261112-0301
VALERIE
W. NAGASAWA
AE100
FLOOR PLAN
GENERAL NOTES
1. PROVIDE ARCHITECTURAL CONCRETE
FINISH AT EXTERIOR FACE OF
FOUNDATION/STEM WALL. VERTICAL
JOINTS TO ALIGN WITH GREENHOUSE WALL
PANEL JOINTS, COORDINATED THROUGH
SHOP DRAWING PROCESS.
2.DOOR 100B IS A PAIR OF 3'-0" BY 7'-0"
ALUM. FRAMED GLASS STOREFRONT DOORS
BY GREENHOUSE MFR.
3. DOOR 100A IS A SINGLE 3'-0" BY 7'-0"
STANDARD DOOR BY GREENHOUSE MFR.
4. SEE STRUCTURAL DRAWINGS FOR
FOUNDATION SYSTEM.
5. SEE PLUMBING DRAWINGS FOR PLUMBING
FIXTURES.
6. SEE ELECTRICAL DRAWINGS FOR
LIGHTING FIXTURES.
7. OFOI INDICATES OWNER
FURNISHED/OWNER INSTALLED.
AE100
AE100
GREENHOUSE FLOOR PLAN
SCALE: 1/4" = 1'-0"
PLAN DETAIL AT EXIST. BUILDING
1/2" = 1'-0"
EXISTING EXTERIOR
WALL OF SCHOOL
PATCH, REPAIR &
PAINT TO MATCH
EXIST.
STAY 12" CLR. FROM
EDGE OF SPOT
FOOTING TO AVOID
UNDERMINING
SAWCUT EXIST. CONC.
SLAB TO ROUTE NEW PIPE
& CONDUIT UNDERGROUND
TO GREENHOUSE. PATCH &
REPAIR SLAB & FINISH
FLOORING TO MATCH EXIST.
PATCH TO MATCH
EXIST.
CUT EXIST. TACKBOARD
TO FIT NEW WALL SPACE
OR PROVIDE NEW TO
MATCH EXIST.
T
EXISTING STRUCTURAL
COL. W/ 3'-0" SQ.
SPOT FTG. BELOW PER
OWNER'S AS-BUILTS
SEE STRUCT. DTL.
A2/S501
NEW METAL STUD
FRAMING & GYP. BD.
TO CREATE CHASE
FOR NEW WATER
SUPPLY PIPE AND
ELECT. CONDUIT. SEE
PLBG. AND ELECT.
DRAWINGS. EXTEND
FRAMING & GYP. BD. TO
6" ABOVE SUSPENDED
CLG. MODIFY EXIST.
CEILING GRID AROUND
NEW CHASE.
1' -8
C
O N
T.
SP
R
EA
D F
TG
PE
R
O W
N
ER
'S A
S- B
U
IL
T D
W G
S.
P-HHG-67
NOTES
1. * CONTEXT INDICATES WHICH ABBREVIATION TERM IS IMPLIED. CONTACT ENGINEER IF
MEANING IS NOT OBVIOUS.
2. NOT ALL ABBREVIATIONS ARE USED.
3. MANY ABBREVIATIONS MAY BE MADE PLURAL BY ADDING AN S SUFFIX.
4. FOR ABBREVIATIONS NOT LISTED, REFER TO US NATIONAL CAD STANDARD, VERSION
3.1, TERMS AND ABBREVIATIONS SECTION, OR CONTACT ENGINEER.
1717_01
375 WEST 200 SOUTH
SALT LAKE CITY, UT 84101
801.521.8600
801.521.791
P
F www.gsbsarchitects.com
OWNER PROJECT NO.:
GSBS PROJECT NO.:
ISSUED DATE:
REVISIONS:
REV
www.calderrichards.com
09/15/2025
2025.047.00
STRUCTURAL GENERAL
NOTES
JORDAN SCHOOL
DISTRICT
HERRIMAN HIGH
SCHOOL
GREENHOUSE
11917 Mustang Trail Way, Herriman, UT 84096
CONSTRUCTION DOCUMENTS
S001
NO SCALEA5
TERMS & ABBREVIATIONS
STRUCTURAL DESIGN CRITERIA
Risk Category: III Roof:
Dead Load: DL = 5 PSF Self-Weight +10 PSF Collateral Ground Snow Load: Pg = 40 PSF Flat Roof Snow Load: Pf = 31 PSF Snow Exposure Factor: Ce = 1.0 Snow Importance Factor: I = 1.1 Thermal Factor: Ct = 1.2 Rain Intensity: i = 1.01 In/hr
Wind:
Basic Wind Speed: V = 109 MPH (3 Sec Gust) Wind Exposure: "C" Internal Pressure Coeff: GCpi = 0.18(±) Component and Cladding Pressure: P = See Table Below
Seismic:
Procedure: Equivalent Lateral Force Site Class: D - Default D Importance Factor: I = 1.25 Seismic Design Category: D Spectral Response Accelerations: Ss = 0.980
S1 = 0.352 Spectral Response Coeff: SDS = 0.784
SD1 = NA
Basic Seismic-Force-Resisting System:
Pre-Engineered Greenhouse Structure Soils:
Net Allowable Soil Pressure = 1500 PSF Assumed
GENERAL
1. All details, sections, and notes shown on the drawings are intended to be typical and shall apply to similar situations elsewhere unless noted or shown otherwise. Notes and details on drawings shall take precedence over these General Notes. General Notes shall take precedence over the Specifications.
2. Refer to the Specifications for information not covered by these General Notes or the Structural Drawings.
3. See the Architectural Drawings for dimensions, doors, windows, non-bearing interior and exterior walls, elevations, slopes, stairs, curbs, drains, recesses, depressions, railings, waterproofing, finishes, chamfers, kerfs, etc.
4. All design, construction, and inspection shall be in conformance with the 2021 International Building Code (IBC) including all referenced standards therein.
5. The Contractor shall verify all dimensions and conditions at the site.
6. All omissions or conflicts between the various elements of the working drawings and/or Specifications shall be brought to the attention of the Architect and/or Structural Engineer before proceeding with any work involved.
7. The Structural Drawings shall be used in conjunction with the entire set of Construction Drawings. This means that detailing and shop drawing production for structural elements will require information that is contained on the Architectural and/or other consultants' drawings. The Structural Drawings may not show all dimensions, slopes, elevations, depressions, mechanical housekeeping pads, etc. The Contractor shall verify all dimensions that are shown on the Structural Drawings with the Architectural and/or other consultants' drawings. Any discrepancies shall be brought to the attention of the Architect and/or Structural Engineer before proceeding with any work involved.
8. Drawings indicate the finished product. They do not indicate a method of construction. Contractor shall take all precautions necessary to protect the structure during construction. Such precautions shall include, but not be limited to, bracing, shoring for construction equipment, etc.
9. The Contractor shall be responsible for compensating the Owner for any changes made as a result of a deviation from the Contract Documents, deviation from the Specifications, faulty materials, or faulty workmanship.
10. Options are for the Contractor's convenience. The Contractor shall be responsible for coordinating all required design changes. Cost associated with any design work initiated by the option shall be borne by the Contractor.
11. Contractor shall be responsible for safety and protection within and adjacent to the job site.
12. Temporary shoring and bracing shall be provided wherever necessary to support all loads to which the structure may be subjected including wind and soil loads. Such bracing shall be left in place as long as may be required for safety or until all structural elements are complete.
13. During and after construction the Contractor and/or Owner shall keep loads on the structure within the limits of the design loads.
14. Observation visits to the job site by field representatives of Calder Richards Consulting Engineers shall neither be construed as inspection nor approval of construction.
15. Sizes, locations, and anchorages of equipment shall be verified in the field with equipment manufacturers (suppliers) prior to placing concrete or fabricating steel.
16. Thermal or moisture protection, furnishings, doors, windows, equipment, mechanical, electrical, finishes, siding, paneling, and veneers are not part of the responsibility of the Structural Engineer.
STRUCTURAL DEFERRED SUBMITTALS
Contractor shall submit Drawings and Calculations for the following items bearing the seal of a Professional Engineer Licensed in the State of the project to Architect/Engineer before submitting to jurisdiction for review and permitting.
Items:
1. Pre-Engineered Greenhouse and Anchorage
STRUCTURAL OBSERVATION
Calder Richards Consulting Engineers shall be notified by the Contractor 5 business days before the completion of the items listed in this section so that Structural Observation may be scheduled and performed in accordance with IBC Section 1704.6. The observations will be performed at the discretion of Calder Richards Consulting Engineers.
1. After forms, reinforcement, anchor bolts, and embeds in place for footings (before pouring).
2. After forms, reinforcement, anchor bolts, and embeds in place for foundation walls (before pouring).
FOOTINGS
1. All footings shall bear on original undisturbed earth or on engineered fill down to undisturbed earth compacted to 95% of maximum relative density based on ASTM D1557. Such fill shall be placed in layers not to exceed 6" in depth after compaction and shall extend down to in-situ granular soils. Unless noted otherwise, follow all recommendations in the soils report.
2. Footing elevations shown on plan are top of footings and are minimum depth.
Different or unusual conditions shall be reported to the Architect and/or Engineer before proceeding.
3. Exterior wall footings shall bear at a minimum depth of 2'-6" below finished exterior grade to achieve frost depth requirements.
4. NO footings shall be placed in water or on frozen ground.
5. Any soil condition encountered during excavation that is contrary to the conditions used for design of footings as outlined in the referenced Soils Report or on the drawings shall be brought to the attention of the Architect before proceeding.
6. DO NOT back fill behind foundation walls until top and bottom decks have been completed and attained their design strengths.
7. Back fill both sides of foundation walls at same time to prevent overturning.
8. Wall footings, where not shown otherwise, shall be 12" thick with an 8" spread each side of wall and provided with (1) #5 x continuous at bottom for each 8" of footing width.
9. Where a pipe passes through an interior or exterior foundation wall, step the footing down to pass below pipe and then step back up to indicated elevation.
Provide pipe sleeve through foundation wall.
10. All footing excavations shall be examined by a Geotechnical Engineer for verification of adequate bearing conditions before placing concrete.
REINFORCING STEEL
1. All reinforcement shall be detailed and placed in accordance with ACI Detailing
Manual 315R (Current Version) and ACI Standard 318 (Current Version).
2. Reinforcing steel shall be ASTM A615 Grade 60.
3. Welded wire fabric shall conform to ASTM A185. Lap one mesh tie.
4. All reinforcement shall be securely tied and held in place.
5. Provide accessories recommended by the CRSI necessary to properly support reinforcing at positions shown on plans.
6. Reinforcing bars that are to be welded, including Deformed Bar Anchors (DBA) shall comply with ASTM A706 or another weldable grade and shall be welded in accordance with the AWS recommendations.
7. All continuous reinforcement shall terminate with a 90 degree turn or a separate corner bar. All splices shall have a minimum lap or embedment per Reinforcing Schedule.
8. Where the length of a bar is given and it is to be hooked, the hook shall be in addition to the length given, unless shown otherwise.
9. Cover to main reinforcement from adjacent surfaces shall be as follows unless shown otherwise:
A. Cast against and permanently in contact with ground ...................................................................... 3" B. Exposed to weather or in contact with ground
(#6 and larger) ..................................................................2" C. Exposed to weather or in contact with ground
(#5 and smaller) ......................................................... 1-1/2" D. Not exposed to weather or in contact with ground
(slabs, joists, and walls #11 and smaller) ..................... 3/4" E. Not exposed to weather or in contact with ground
(beams, columns, pedestals and tension ties)............ 1-1/2" F. In all cases minimum cover shall not be less than the diameter of adjacent bars.
10. Prior to fabrication and placement, Shop Drawings for all reinforcing steel shall be reviewed by the Structural Engineer.
CONCRETE
1. Concrete shall attain the following minimum compressive strengths at 28 days:
Footings .................................................... 4000 PSI Foundation Walls ...................................... 4000 PSI Interior Slabs on Grade ............................ 3000 PSI
2. The various concrete items are assigned to the following Exposure Categories and Classes per Section 19.3 of ACI 318 (Current Version):
Footings ........................................... F1, S0, W0, C1 Foundation Walls ............................. F1, S0, W0, C1 Interior Slabs on Grade .................... F0, S0, W0, C1
See Table 19.3.1.1 of ACI 318 (Current Version) for explanations of Categories and Classes listed above.
3. A Statement of Mix Design for all concrete shall be submitted to and reviewed by the Structural Engineer prior to commencing work. All mix designs shall incorporate requirements and restrictions found in Section 19.3 & Tables 19.3.1.1, 19.3.2.1, and 19.3.3.1 of ACI 318 (Current Version). If two or more requirements are in conflict, the more restrictive requirement shall be followed.
4. All concrete work shall be placed, cured, stripped, and protected as directed by the specifications and ACI Standards and Practices.
5. Before concrete is poured, check with all trades to ensure proper placement of all openings, sleeves, curbs, conduits, bolts, inserts, etc, relative to work.
NO aluminum conduit nor product containing aluminum nor any other material injurious to concrete shall be embedded in concrete.
6. Continuous top and bottom bars in walls over openings shall be spliced as follows:
A. Top bars - At mid-span B. Bottom bars - Over support
7. Where openings larger than 16" in any direction occur in walls or slabs, provide same size additional, full length reinforcing at each side of opening equal to 1/2 the number of bars interrupted by the opening. Space additional bars at 4 x bar diameter.
8. Construction Joints and Control Joints:
A. Refer to drawings for typical construction joint details.
B. Provide a continuous tool-roughened surface at top of all walls and footings, unless noted otherwise.
C. All horizontal and vertical construction joints shall have a continuous
2"x4" keyway along the joint, unless noted otherwise, see details.
D. Provide reinforcing dowels to match the member reinforcing at the joint, unless noted otherwise.
E. Slabs and beams shall not have joints in horizontal plane.
F. Construction joints for slabs on steel deck shall not exceed a distance of 80'-0" in any direction.
G. Control joints shall be complete within 12 hours of concrete placement.
9. All slabs on grade shall be placed in alternate panels with a maximum width of 90 times the slab thickness in any direction. Construction joints shall not exceed 125'-0" OC in any direction; refer to typical details on drawings.
Unless otherwise noted, slabs on grade shall be 4" thick and shall be reinforced with 6x6-W1.4xW1.4 welded wire fabric, centered in slab.
10. Provide a #3 nosing bar in all stair treads.
11. Forms, screeds, and beams supporting suspended concrete shall be cambered 1/4 inch per 10 feet of span to compensate for Dead Load deflections.
12. Where exterior slabs on grade abut walls or columns, provide 3/8" pre-formed expansion joint with sealant.
13. Where interior masonry walls do not bear on a footing provide a typical thickened slab (12" thick x 16" wide) under wall. Reinforce with (2) #4 x continuous. Dowel wall reinforcing to slab.
14. Admixtures:
A. Air-entraining admixtures (when used), shall comply with ASTM C260.
B. Calcium chloride shall not be added to concrete mix.
COMPONENTS & CLADDING WIND PRESSURE (PSF)
ULTIMATE DESIGN LOADS
Tributary Area
Typical Conditions Corner Conditions
Positive Pressure
Negative Pressure
Positive Pressure
Negative Pressure
10 SF +23 PSF -25 PSF +23 PSF -31 PSF
50 SF +21 PSF -23 PSF +21 PSF -27 PSF
100 SF +20 PSF -22 PSF +20 PSF -24 PSF
500 SF +18 PSF -20 PSF +18 PSF -20 PSF
DRILL & EPOXY ANCHORS
1. Use HILTI HIT-HY 200 adhesive system or approved equivalent for concrete and solid grouted masonry connections.
2. Use HILTI HIT-HY 270 adhesive system or approved equivalent for all hollow unit CMU connections and unreinforced masonry walls, including multi-wythe walls.
3. Anchor rods shall be ASTM F1554 Grade 36 (unless noted otherwise in drawings) with diameter indicated, threaded and galvanized.
4. Provide screen tubes for ungrouted masonry units or unreinforced masonry walls.
5. Anchor capacity is dependent upon spacing between adjacent anchors and proximity of anchors to edge of concrete. Install anchors in accordance with spacing and edge clearances indicated on the drawings.
6. Substitution requests for alternate products must be approved in writing by the Structural Engineer prior to use. The contractor shall provide calculations demonstrating the substituted product is capable of achieving the performance values of the specified product.
Substitutions will be evaluated by the product having an ICC-ES report showing compliance with the relevant building code for seismic uses, load resistance, installation category, and availability of comprehensive installation instructions.
7. The contractor shall arrange for an anchor manufacturer's representative to provide onsite installation training for all of their anchoring products specified. The contractor shall provide the engineer with documentation showing their personnel have received training prior to commencement of work.
8. Ten percent of all anchors placed shall be randomly tested to 100% of manufacturer's specified allowable load. If any anchor fails it shall be replaced and retested at no additional cost to the owner. If an anchor fails, 100% of all other anchors installed by that same crew shall be tested at no additional cost to the owner.
SPECIAL INSPECTION - CONCRETE CONSTRUCTION
(IBC 1705.3)
Item C/P ◄(A)
INSPECTION OF CONCRETE CONSTRUCTION (IBC 1705.3, TABLE 1705.3)
1. Inspect reinforcement, including prestressing tendons, and verify placement P
2. Reinforcing bar welding:
- A. Verify weldability of reinforcing bars other than ASTM A706; P
- B. Inspect single-pass fillet welds, maximum 5/16"; and P
- C. Inspect all other welds C
3. Inspect anchors cast in concrete P
4. Inspect anchors post-installed in hardened concrete members ◄(B)
- A. Adhesive anchors installed in horizontally or upwardly inclined orientations to resist sustained tension loads.
C
- B. Mechanical anchors and adhesive anchors not defined in 4.A P
5. Verify use of required design mix P
6. Prior to concrete placement, fabricate specimens for strength tests, perform slump and air content tests, and determine the temperature of the concrete
C
7. Inspect concrete and shotcrete placement for proper application techniques C
8. Verify maintenance of specified curing temperature and techniques P
9. Inspect prestressed concrete for:
- A. Application of prestressing forces; and C
- B. Grouting of bonded prestressing tendons C
10. Inspect erection of precast concrete members P
11. For precast concrete diaphragm connections or reinforcement at joints classified as moderate or high deformability elements (MDE or HDE) in structure assigned to Seismic Design Category C, D, E, or F, inspect such connections and reinforcement in the field for:
- A. Installation of the embedded parts C
- B. Completion of the continuity of reinforcement across joists C
- C. Completion of connections in the field C
12. Inspect installation tolerances of precast concrete diaphragm connections for compliance with ACI 550.5
P
13. Verify in-situ concrete strength, prior to stressing of tendons in post-tensioned concrete and prior to removal of shores and forms from beams and structural slabs
P
14. Inspect formwork for shape, location and dimensions of the concrete member being formed
P
TABLE NOTES:
►(A) Continuous or periodic (C/P) refers to the frequency of inspection, which may be continuous during the task listed or periodically during the listed task, as defined in the table.
►(B) Specific requirements for special inspection shall be included in the research report for the anchor issued by an approved source in accordance with 17.8.2 in ACI 318, or other qualification procedures. Where specific requirements are not provided, special inspection requirements shall be specified by the registered design professional and shall be approved by the building official prior to the commencement of the work.
TERMS AND ABBREVIATIONS
ABBRV TERM
(#) Numerical quantities when enclosed in parentheses
A/E Architect / Engineer
AB Anchor Bolt
ABV Above
ADDM Addendum
AFF Above Finished Floor
ALUM Aluminum
APPROX Approximately
ARCH Architect (Architectural)*
ASTM American Society for Testing and Materials
B PL Base Plate
B/B Back to Back bf Beam Flange Width
BLKG Blocking
BLW Below
BM Beam
BOS Bottom of Steel
BOT Bottom
BRG Bearing
BTWN Between
C TO C Center to Center
CD Contract Documents
CIP Cast-In-Place
CJ Construction Joint (Control Joint)*
CL Centerline
CMU Concrete Masonry Unit
COL Column
CONC Concrete
CONN Connection
CONT Continuous (Continue)*
CONTR Contractor
COORD Coordinate
CTR Center
D Depth d Pennyweight Nail
DB Deck Bearing
DBA Deformed Bar Anchor
DBL Double
DFS Douglas Fir - South
DIA Diameter
DIAG Diagonal
DIM Dimension
DL Dead Load
DTL Detail
DWG Drawing
(E) Existing
E Modulus of Elasticity
EA Each
EJ Expansion Joint
EL Elevation
ELEV Elevator
ENGR Engineer
EQ Equal
EQL SP Equally Spaced (Equal Spaces)*
EQUIP Equipment
EQUIV Equivalent
EST Estimate
ETC And so forth
EW Each Way
EXCL Exclude
EXP Expansion
EXT Exterior
(F) Future
FDTN Foundation
FFE Finished Floor Elevation
FIN Finish (Finished)*
FLR Floor
FRMG Framing
FSE Finished Slab Elevation
FTG Footing
FV Field Verify
GA Gage / Gauge
GALV Galvanized
GLB Glued Laminated Wood Beam
HGR Hanger
HORIZ Horizontal (Horizontally)*
HSA Headed Stud Anchor
HSS Hollow Structural Section
I Moment of Inertia
ID Inside Diameter
INT Interior
TERMS AND ABBREVIATIONS
ABBRV TERM
JST Joist
KIP (K) Thousand Pounds
KIP FT Thousand Foot/Pounds
KLF KIPs per Lineal Foot
LB Pound
LHS Left Hand Shoe
LL Live Load
LLH Long Leg Horizontal
LLV Long Leg Vertical
LONG Longitudinal
LSH Long Slotted Hole(s)
LSL Laminated Strand Lumber
LTWT Lightweight
LVL Laminated Veneer Lumber
MAX Maximum
MECH Mechanical
MFR Manufacturer
MIN Minimum
MISC Miscellaneous
N/A Not Applicable
NTS Not to Scale
OC On Center
OD Outside Diameter
OPNG Opening
OPP Opposite
OPT Optional
OSB Oriented Strand Board
P/T Pressure Treated
PERP Perpendicular
PLF Pounds per Lineal Foot
PSL Parallel Strand Lumber
PT Post Tensioned
QA Quality Assurance
QC Quality Control
(RE) Remove Existing
REINF Reinforce (Reinforced, Reinforcing)*
REQD Required
RFI Request for Information
RS Rough Sawn
RTU Roof Top Unit
SCHED Schedule
SECT Section
SF Square Foot (Feet)*
SGL Single
SHTHG Sheathing
SIM Similar
SL Snow Load
SOG Slab on Grade
SPCL Special
SPEC Specification
SQ Square
SSH Short Slotted Hole(s)
STD Standard
STIF Stiffener
STRUCT Structure (Structural)*
SYMM Symmetrical
T&B Top & Bottom
T&G Tongue and Groove
THRU Through
TO FDTN Top of Foundation
TOB Top of Beam
TOC Top of Concrete
TOF Top of Footing
TOJ Top of Joist
TOM Top of Masonry
TOP Top of Parapet
TOS Top of Steel
TOW Top of Wall
TWS Threaded Welded Stud
TYP Typical
UNO Unless Noted Otherwise
VERT Vertical (Vertically)*
W/ With
W/O Without
WL Wind Load
WLD Weld (Welded)*
WP Work Point
WWF Welded Wire Fabric
XS Extra Strong
XXS Double Extra Strong
SHOP DRAWING SUBMITTALS
1. Contractor shall review and verify all Shop Drawings to ensure they comply with the requirements of the Contract Documents. Engineer will review the Shop Drawings for general conformance with the design concept. This review by the Engineer shall not be construed as approval. The Contractor shall verify all shop drawing dimensions with Structural and Architectural plans and details.
2. Provide Shop Drawings to the Engineer for review for the following, but not limited to:
A. Concrete Foundation Reinforcement B. Concrete Mix Design C. Pre-Engineered Greenhouse
3. Refer to the Architectural Drawings for Shop Drawing submittals required for non-structural elements.
A5
S501
A5
S501
A5
S501
A4
S501
________________A5
S501
F C
5.
F C
5.
FC5.0
FC5.0
TRENCH DRAIN,
SEE ARCH & MECH
C W
-1
C W
-1
CW-1
CW-1
TRENCH DRAIN,
SEE ARCH & MECH
A4
S501
B5
S501
B5
S501
VARIES, SEE ARCH
DWGS FOR SLOPE
CONCRETE SLAB ON
GRADE, [SG#], SEE
SCHEDULE
FTG/FDTN PLAN LEGEND
CONCRETE FOOTING
& FDTN WALL, SEE
SCHEDULE
CONCRETE WALL
TYPE, [CW-#], SEE
SCHEDULE
CHANGE IN ELEVATION
OR STEP IN SLAB, SEE
ARCH DWGS FOR
EXACT LOCATION
RECESS IN CONCRETE
FDTN WALL
FCx.xS S FOOTING STEP, LOCATIONS SHOWN
SCHEMATICALLY ONLY,
SEE DETAIL
CONTINUOUS
FOOTING, SPOT
FOOTING,
RECTANGULAR
FOOTING TYPES
RESPECTIVELY,
SEE SCHEDULE
FCx.x, FSx.x, FRx.x/y.y
TOP OF CONCRETE
SLAB ELEVATION
xxx'-xx"
TOP OF WALL
ELEVATION
TW xxx'-xx"
TF xx'-xx"
TOP OF FTG
ELEVATION
B4/S502
A3/S502 B4/S502
C4/S502
CW-#
SG#
C2/S502
375 WEST 200 SOUTH
SALT LAKE CITY, UT 84101
801.521.8600
801.521.791
P
F www.gsbsarchitects.com
OWNER PROJECT NO.:
GSBS PROJECT NO.:
ISSUED DATE:
REVISIONS:
REV
www.calderrichards.com
2025.047.00
FOOTING & FOUNDATION
PLAN
JORDAN SCHOOL
DISTRICT
HERRIMAN HIGH
SCHOOL
GREENHOUSE
11917 Mustang Trail Way, Herriman, UT 84096
CONSTRUCTION DOCUMENTS
S101
1/4" = 1'-0"
Footing & Foundation Plan
PLAN NOTES - FOOTING & FDTN
# NUMBERED NOTES BELOW ARE KEYED ON
PLAN.
* SEE ARCHITECTURAL DRAWINGS FOR ALL
DIMENSIONS, TYPICAL.
** NOT ALL NOTES MAY APPLY TO AREA
SHOWN ON SHEET.
A SEE STRUCTURAL NOTES ON SHEET S001
FOR ADDITIONAL INFORMATION.
B TOP OF CONCRETE SLAB
ELEVATION = 100'-0",
UNLESS NOTED THUS:
SLOPE UNIFORMLY
TO FLOOR DRAINS.
C PLACE CONTROL JOINTS AND
CONSTRUCTION JOINTS IN SLAB PER
STRUCTURAL NOTES AND DETAIL B2/S502.
D CENTER FOOTINGS ON WALLS AND
COLUMNS UNLESS DIMENSIONED
OTHERWISE ON PLANS.
xxx'-x"
PLAN NOTES - FOOTING & FDTN
E SEE STRUCTURAL NOTES ON SHEET S001
FOR MINIMUM FROST COVER FOR ALL
EXTERIOR FOOTINGS. FOOTING
ELEVATIONS SHOWN ARE BASED ON A
UNIFORM GRADE 6" BELOW SLAB PLUS
FROST COVER. COORDINATE ELEVATIONS
SHOWN WITH CIVIL AND SITE PLANS FOR
ANY ADDITIONAL DEPTH THAT MAY BE
REQUIRED TO MAINTAIN MINIMUM FROST
COVER OVER FOOTINGS. STEP FOOTINGS
PER DETAIL A3/S502 WHERE REQUIRED.
F SEE DETAILS A2/S502 FOR TYPICAL
CONCRETE REINFORCEMENT AT CORNERS
AND INTERSECTIONS.
G DO NOT PLACE BACKFILL AGAINST
FOUNDATION WALLS UNTIL BRACING
FLOOR IS IN PLACE OR ADEQUATE
SHORING IS INSTALLED.
H SEE ARCHITECTURAL / SITE DRAWINGS
FOR INFORMATION AND LOCATION OF SITE
WALLS, STEPS, PLANTERS, RAMPS, ETC.
J WHERE PLUMBING LINES OR ELECTRICAL
CONDUIT INTERSECT FOOTINGS, SEE
DETAIL A2/S501.
1 EXISTING STORM DRAIN LINE. SEE DETAIL
A2/S501 FOR REQUIREMENTS AT FOOTING
INTERSECTION.
WALL BEYOND, SEE PLAN
FTG, SEE PLAN &
SCHED B4/S502
FOR SIZE & REINF
C L
R 3"
EXT CONC SLAB ON GRADE
OR ASPHALT, SEE CIVIL DWGS
(2) CONT HORIZ BARS,
TOP & BOT OF FDTN WALL
#4 x DOWELS
@ 16" OC
2' - 0"
1'
6"
F R
O S
T C
O V
E R
S E
E S
T R
U C
T N
O T
E S
#4 x 4' - 0" @ 16" OC
AT OPENING
FINISH GRADE
3136_03
B4/S502
CONC FDTN WALL, SEE PLAN &
SCHED FOR SIZE & REINFC4/S502
PROVIDE STD HOOK AT ALL
VERT REINF EXTENDING
INTO FTG (ALT HOOK DIR)
TYP
2" CLR
C2/S502
CONC SLAB ON GRADE,
SEE PLAN & SCHED
8"
C L
R 3"
(2) CONT HORIZ BARS,
TOP & BOT OF FDTN WALL
F R
O S
T C
O V
E R
S E
E S
T R
U C
T N
O T
E S
4'
M A
X
3162_04
C2/S502
CONC SLAB ON
GRADE, SEE
PLAN & SCHED
GREENHOUSE STRUCTURE &
ANCHORAGE BY OTHERS
FTG, SEE PLAN &
SCHED B4/S502
FOR SIZE & REINF
B4/S502
CONC FDTN WALL, SEE PLAN &
SCHED FOR SIZE & REINFC4/S502
PROVIDE STD HOOK AT ALL
VERT REINF EXTENDING
INTO FTG (ALT HOOK DIR)
TYP
2" CLR
WATERLINE OR ELECTRICAL
CONDUIT, SEE PLUMBING OR
ELECTRICAL PLANS. SEE DETAIL
A2/S501 FOR PASSAGE BELOW
FOOTING. PIPES AND CONDUITS
MAY BE SLEEVED UP THROUGH
FOOTING AS SHOWN. MAINTAIN 3"
MIN BETWEEN SLEEVES.
A2/S501
LEAN CONCRETE. FILL
BELOW FTG AT PIPE /
CONDUIT LOCATION.
PIPE / CONDUIT
SLEEVE
SHALLOW SINGLE PIPE / CONDUIT
BELOW & NEAR BOTTOM OF FTG
MULTIPLE PIPES / CONDUITS
BELOW BOTTOM OF FTG
3"
TYP
3" T Y
P
LEAN CONCRETE. FILL
BELOW FTG AT PIPE /
CONDUIT LOCATION.
PIPES / CONDUITS MAY
STACK WHERE REQD
SLEEVE
PIPE / CONDUIT
CLR
3"
1'
M
IN
SLEEVE
PIPE / CONDUIT
LEAN CONCRETE. FILL
BELOW FTG AT PIPE /
CONDUIT LOCATION.
DEEP SINGLE PIPE / CONDUIT
BELOW FTG
TYP
3"
BAR LAP SPLICE,
SEE SCHED
3' - 0" MAX
FDTN WALL. TYP WALL
REINF NOT SHOWN.
(2) #4 BARS ABOVE PIPE /
CONDUIT PENETRATIONS
MULTIPLE PIPES / CONDUITS
THRU FDTN WALL
3117_02
C L
R 3"
C L
R 3"
1'
M A
X 3"
M
IN
FDTN WALL
CONC FTG
FDTN WALL
CONC FTG
3" M
IN
C L
R 3"
4" GRAVEL ABOVE LEAN
CONCRETE WHERE UTILITIES
ARE PLACED PRIOR TO
FOOTINGS. OTHERWISE
CONTINUE LEAN CONCRETE
UP TO BOT OF FOOTING
WHERE UTILITIES ARE
PLACED AFTER FOOTINGS.
CLR
3"
CONC FTG
FDTN WALL
CONC FTG
SLEEVE
PIPE / CONDUIT
A4/S502
M
IN3"
CONC FTG. STEP
FOOTING DOWN AS
REQD TO AVOID
PIPES / CONDUITS.
CLR
3" MIN
2" M
IN
T
O T
O P
O F
F D
T N
W A
L L
NOTES:
1. NO UTILITIES SHALL RUN HORIZONTALLY THROUGH FOOTINGS.
2. NO UTILITIES SHALL RUN BELOW SPOT FOOTINGS.
3. SLEEVE INSIDE DIAMETER SHALL BE AT LEAST 1 1/2" GREATER
THAN PIPE / CONDUIT OUTSIDE DIAMETER.
4. SINGLE PIPES MUST BE SPACED AT A MINIMUM OF 3'-0" OC.
C L
R 3"
TRENCH DRAIN,
SEE ARCH & MECH
#4 DOWEL @ 18" OC
8"
2' - 0"
(3) #4 x CONT
NOTCH AS REQD FOR
GRATING BEARING
SC3677_A
CONC SLAB ON GRADE, SEE
PLAN & SCHED .
SLOPE AS REQD
C2/S502
3/4" = 1'-0"A4
EXT DOOR OPENING DETAIL
3/4" = 1'-0"B5
3/4" = 1'-0"A2
PLUMBING / CONDUIT
PENETRATIONS NEAR FTGS
3/4" = 1'-0"A5
375 WEST 200 SOUTH
SALT LAKE CITY, UT 84101
801.521.8600
801.521.791
P
F www.gsbsarchitects.com
OWNER PROJECT NO.:
GSBS PROJECT NO.:
ISSUED DATE:
REVISIONS:
REV
www.calderrichards.com
2025.047.00
STRUCTURAL DETAILS
JORDAN SCHOOL
DISTRICT
HERRIMAN HIGH
SCHOOL
GREENHOUSE
11917 Mustang Trail Way, Herriman, UT 84096
CONSTRUCTION DOCUMENTS
S501
NOTES:
1. THE SCHEDULE SHOWN APPLIES TO REGULAR WEIGHT
CONCRETE WITH 60ksi GRADE REINFORCING BARS.
2. TOP BARS ARE HORIZONTAL BARS WITH 12" OR MORE OF
FRESH CONCRETE CAST BELOW THE BARS.
3. CLASS "A" SPLICES SHALL BE USED WHEN 50% (OR LESS)
OF BARS SPLICED WITHIN LAP.
4. CLASS "B" SPLICES SHALL BE USED FOR ALL ELSE,
TYPICALLY WITH SHEARWALLS, COLUMNS, BEAMS AND
SLABS.
5. FOR EPOXY COATED BARS, INCREASE LAP LENGTHS AS
FOLLOWS:
TOP BARS: Ld x 1.7 REGULAR BARS: Ld x 1.5
6. FOR BUNDLED BARS, INCREASE LAP LENGTHS AS
FOLLOWS:
BUNDLED BARS, THREE OR LESS: Ld x 1.2 BUNDLED BARS, FOUR OR MORE: Ld x 1.33
INDIVIDUAL BAR SPLICES WITHIN A BUNDLE
SHALL NOT OVERLAP.
7. LAP SPLICES ARE NOT ALLOWED FOR TIES AND
STIRRUPS.
3747_01
NOTES:
1. LOCATE VERTICAL REINFORCING EACH
SIDE OF ALL OPENINGS, EACH SIDE OF
CONTROL JOINTS AND AT ALL ENDS AND
CORNERS IN ADDITION TO SCHEDULED
SPACING. SEE PLAN WHERE SPECIAL
COLUMNS OCCUR AT JAMBS. DOWEL
VERTICAL REINFORCING TO FOOTING
OR THICKENED SLAB WHERE OCCURS.
2. PLACE HORIZONTAL REINFORCING AT
ALL SUSPENDED LEVELS. SEE PLANS,
SECTIONS AND SCHEDULES FOR
SPECIAL HORIZONTAL REINFORCING AT
ROOFS AND OVER OPENINGS. SEE
FOR CORNER BAR DETAILS AND
AT INTERSECTING WALLS.
3. WHERE ONLY ONE (1) VERTICAL
REINFORCING BAR IS SCHEDULED, THE
BAR SHALL BE CENTERED IN THE WALL.
WHERE TWO (2) BARS ARE SCHEDULED,
LOCATE FACE OF REBAR AT 3/4" FROM
EACH FACE. SEE SCHEDULE
FOR BAR LAP REQUIREMENTS. MINIMUM
COVER REQUIREMENTS ARE IN
ADDITION TO ANY ARCHITECTURAL
REVEALS OR FEATURES.
4. PROVIDE 90°…