This document is a set of architectural and engineering drawings prepared by NORR for the County of Delaware, Pennsylvania Department of Public Works, specifically for the Voter Machine Warehouse Elevator Addition project located at 403 East 24th Street in Chester, PA. The project involves the installation of a service elevator to an existing two-story commercial warehouse building, classified as an Alteration Level II. The scope of work includes fire protection system modifications (sprinkler and standpipe systems), mechanical system installations (heating water supply and return piping, unit heaters, transfer fan, and sump pump), and related demolition of existing systems. The fire protection work requires compliance with NFPA 13 and NFPA 14 standards, with quick-response type sprinklers throughout the building. The mechanical work includes new hydronic piping at 1-1/2 inches with 2-inch fiberglass insulation, a transfer fan unit (TF-1) rated at 350 CFM, and a sump pump system (SP-1) for the elevator pit. A pre-bid conference is scheduled for October 20, 2026, at 11:00 AM, with invitations to bid (ITB) responses due November 10, 2026, at 11:00 AM via PennBid.

The contract documents indicate that all contractors must obtain approval of shop drawings from the owner's insurance carrier and the authority having jurisdiction prior to installation. The fire protection contractor bears sole responsibility for securing these approvals, with system pressure testing conducted at 200 PSI for 2 hours in the presence of the authority having jurisdiction. All work must comply with applicable NFPA standards, Pennsylvania Fire Safety Code, OSHA safety requirements, and local codes. The mechanical contractor must provide two filter changes prior to grand opening and coordinate all work with the structural, electrical, and fire protection trades. The contractor is responsible for obtaining necessary permits and paying all related fees, and all materials, equipment, and workmanship are guaranteed for one year after final acceptance. No specific pricing terms, set-asides, incumbent information, or funding sources are identified in these technical drawings.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

DSP

SPR/WSP

WSP

FDC

FPTH

SPR

F

TS

GENERAL NOTES

LEGEND

1. THESE GENERAL NOTES ARE APPLICABLE TO ALL FIRE PROTECTION DRAWINGS.

2. CONTRACTOR SHALL SUBMIT (2) SEPARATE HYDRAULIC CALCULATIONS.THE FIRST

CALCULATION IS FOR FIRE PUMP & SPRINKLER SYSTEM. THE SECOND IS FOR THE STANDPIPE

SYSTEM FROM THE FDC TO THE MOST REMOTE FHV COMPLYING WITH NFPA-14 (100PSI).

4.

THESE DRAWINGS ARE DIAGRAMMATIC IN NATURE AND SHOW THE GENERAL INTENT OF

WORK. SEE DETAILS, RISERS, AND SPECIFICATION FOR ADDITIONAL INFORMATION. THE

CONTRACTOR IS RESPONSIBLE FOR A COMPLETE SYSTEM FOR FULL BUILDING COVERAGE.

ADDITIONAL SRINKLERS AND PIPING MAY BE REQUIRED TO ACCOMMODATE CONDITIONS SUCH

AS SOFFITS, DUCTWORK, STRUCTURE, LIGHTING, EQUIPMENT, BOOK STACKS, ETC. THE

CONTRACTOR SHALL PROVIDE A COMPLETE SPRINKLER INSTALLATION IN CONFORMANCE WITH

NFPA 13, NFPA 14, FEDERAL AND STATE CODES AND THEIR APPLICABLE SUPPLEMENTS, AND

THE REQUIREMENTS OF THE OFFICE OF THE STATE FIRE MARSHAL.

5.

REFER TO NFPA 13 FOR EXACT SPACING, DENSITY, AND LOCATION REQUIREMENTS.

CONTRACTOR SHALL INSTALL QUICK RESPONSE TYPE SPRINKLER IN ENTIRE BUILDING. USE OF

EXTENDED COVERAGE, QUICK RESPONSE, TYPE SPRINKLER MAY BE USED WITH THE APPROVAL

OF THE AUTHORITY HAVING JURISDICTION.

6.

SPRINKLERS IN FINISHED LAYIN TILE CEILING AREAS SHALL ALWAYS BE LOCATED IN THE

CENTER OF CEILING TILES UNLESS INDICATED OTHERWISE.

7.

REVIEW THE ARCHITECTURAL REFLECTED CEILING, ELEVATION AND SECTION PLANS AS PART

OF THIS CONTRACT FOR ADDITIONAL INFORMATION SUCH AS CEILING HEIGHTS, TYPES, SOFFITS

AND OR OTHER DEVICE LOCATIONS.

8.

REVIEW THE ELECTRICAL DIVISION DRAWINGS AND COORDINATE THE FIRE PROTECTION

WORK WITH LOCATIONS OF LIGHT, AND CEILING MOUNTED DEVICES WHICH MAY INTERFERE

WITH SPRINKLER LOCATIONS OR SPRAY PATTERNS.

9.

REVIEW THE HVAC DIVISION DRAWINGS AND COORDINATE THE FIRE PROTECTION WORK WITH

LOCATIONS OF CEILING MOUNTED DEVICES SUCH AS DIFFUSERS, GRILLS, REGISTERS, AND

ALSO THE LOCATIONS OF HEAT PRODUCING EQUIPMENT AND DUCTWORK REQUIRING

SPRINKLER PROTECTION BELOW IT.

14.

15.

16.

FIRE SERVICE PIPING

EXISTING SIDE WALL TYPE SPRINKLER

PENDENT TYPE SPRINKLER

CONCEALLED SIDE WALL SPRINKLER

DOUBLE CHECK DETECTOR ASSEMBLY (DCDA)

DRY TYPE SPRINKLER

FIRE DEPARTMENT CONNECTION

CONCEALLED TYPE PENDENT SPRINKLER

UPRIGHT TYPE SPRINKLER PIPE DROP

PIPE UP OR DOWN

SPRINKLER PIPING

FIRE PUMP TEST HEADER PIPING

FIRE DEPARTMENT CONNECTION PIPING

COMBINATION SPRINKLER / STANDPIPE

CAPPED OUTLET

CHECK VALVE

BACKFLOW PREVENTION DEVICE

PRESSURE GAUGE

PIPE BREAK

WATER TIGHT PIPE SLEEVE

CONTROL VALVE W/ SUPERVIRORY SWITCH. VALVE GATE BALL

REMOVE EXISTING SPRINKLER

WET STANDPIPE

DRY STANDPIPE

SIDE WALL TYPE SPRINKLER

EXISTING SPRINKLER

FIRE HOSE VALVE

FIRE PROTECTION CONSTRUCTION PROCEDURES

1. IT IS SOLELY THE FIRE PROTECTION CONTRACTOR'S RESPONSIBILITY TO OBTAIN APPROVAL OF

SHOP DRAWINGS FROM THE OWNERS INSURANCE CARRIER AND THE AUTHORITY HAVING

JURISDICTION. ANY INSTALLATION OF THE SPRINKLER SYSTEM WITHOUT APPROVED PLANS

SHALL BE AT THE SOLE RISK AND EXPENSE OF THE CONTRACTOR.

2. THE FIRE PROTECTION CONTRACTOR MUST CONTACT THE OWNERS CONSTRUCTION

COORDINATOR AND REQUEST WHENEVER THE SPRINKLER MAIN IS TO BE ISOLATED AND/OR

DRAINED. THIS PROCEDURE MUST BE ADHERED TO WHEN PRESSURE TESTING AND/OR PLACING

ANY PORTION OF SYSTEM IN OR OUT OF SERVICE.

3. THE OWNER'S CONSTRUCTION COORDINATOR AND THE AUTHORITY HAVING JURISDICTION

SHALL WITNESS ALL SYSTEM PRESSURE TESTS. CONTRACTOR MAKING THE TEST SHALL

PROVIDE 24 HOURS NOTICE TO ALL REQUIRED TO BE IN ATTENDANCE.

4. ALL WORK SHALL MEET THE REQUIREMENTS OF NFPA STANDARDS. INSTALLATION

PROCEDURES SHALL COMPLY WITH THE SAFETY RULES OF OSHA AND THE STATE OF

PENNSYLVANIA FIRE SAFETY CODE.

5. THE FIRE PROTECTION CONTRACTOR MUST PROVIDE A FIRE WATCH WHENEVER ANY WELDING

IS DONE WITHIN THE AREA BEING WORKED, DURING THE WIELDING OPERATION, AND FOR ONE

HOUR AFTER WELDING IS COMPLETE.

6. NO STOCK OF FURNISHINGS SHALL BE ALLOWED IN THE AREAS BEING WORKED UNTIL THE

ENTIRE SYSTEM IS COMPLETED IN ACCORDANCE WITH THE ABOVE NOTES AND APPROVED BY

THE AUTHORITY HAVING JURISDICTION.

7. PROVIDE A MATERIAL TEST AND CERTIFICATION FORM TO THE AUTHORITY HAVING

JURISDICTION AND OWNER'S INSURANCE CARRIER SO AS TO CERTIFY THAT THE SPRINKLER

SYSTEM WAS INSTALLED IN ACCORDANCE WITH THE CONTRACT DOCUMENTS, SPECIFICATIONS,

FEDERAL, STATE, AND LOCAL CODES AND PROCEDURES.

8. UPON COMPLETION OF SYSTEM INSTALLATION, PERFORM A HYDROSTATIC TEST ON ALL PIPING

AND ATTACHED APPURTENANCES IN THE PRESENCE OF AN AUTHORITY HAVING JURISDICTION.

THE SYSTEM SHALL BE HYDROSTATIC ALLY TESTED AT A PRESSURE OF 200 PSI AND SHALL

MAINTAIN THAT PRESSURE WITHOUT LOSS FOR 2 HOURS. TEST FAILURE SHALL BE DETERMINED

BY A DROP IN GAUGE PRESSURE OR VISUAL LEAKAGE. THE TEST PRESSURE SHALL READ FROM

A GAUGE LOCATED AT THE LOWEST ELEVATION POINT OF THE SYSTEM OR PORTION BEING

TESTED. ALL TESTING THE SYSTEM SHALL BE IN ACCORDANCE WITH NFPA 13 AND NFPA 25.

9. CONSTRUCTION PHASING OF THE PROJECT, THE EXISTING AREAS OF FIRE PROTECTION MUST

BE MAINTAINED. THE FIRE PROTECTION CONTRACTOR IS TO PROVIDE SERVICE TO THESE

AREAS FROM THE NEW FIRE PROTECTION SERVICE AS REQUIRED.

ABBREVIATIONS

LOW PRESSURE SWITCHLPS

PRESSURE SWITCHPS

PIV

PRFHV

NIC

POST INDICATOR VAVLE

PRESSURE REDUCING FIRE HOSE VALVE

NOT IN CONTRACT

JOCKEY PUMP CONTROLLER

JP

JPC

IT

JOCKEY PUMP

INTERMEDIATE TEMPERATUR (SPRINKLER)

HT

GPM

G

FPTH

GALLONS PER MINUTE

HIGH TEMPERATURE (SPRINKLER)

CAGE GUARD (SPRINKLER)

FIRE PUMP TEST HEADER

FIRE HOSE VALVE CABINET

FIRE VALVE CABINET

FHVC

FVC

FPC

FHV

FHR

FHC

FIRE PUMP CONTROLLER

FIRE HOSE VALVE

FIRE HOSE COBINET

FIRE HOSE RACK WITH HOSE

FDC

FS

FP

ELEV

FIRE DEPARTMENT CONNECTION

FLOW SWITCH

ELEVATION

FIRE PUMP

EC

DCVA

CTE

BFP

EXTENDED COVERAGE (SPRINKLER)

DOUBLE CHECK VALVE ASSEMBLY

CONNECT TO EXISTING

BACKFLOW PREVENTOR

ATS

AFF

AUTOMATIC TRANSFER SWITCH (FIRE PUMP)

ABOVE FINISHED FLOOR

POUNDS PER SQUARE INCHPSI

VERIFY IN FIELDVIF

TS

TYP

SV

TAMPER SWITCH

TYPICAL

SUPERVISORY VALVE

(E) EXISTING

WET STANDPIPEWSP

PIPING TO BE REMOVED(R)

AREA

SYSTEM TYPE

DENSITY

SPKR. TEMP MAX SF/HD

MIN. AREA

HAZARD

SPRINKLER SYSTEM DESIGN CRITERIA SYMBOLS

AREA OF

SCOPE

SYSTEM TYPE

DESIGNMDENSITY

GPM/SQ.FT.

SPRINKLER

ACTIVATION

TEMPERATURE

HAZARD

CLASSIFICATION

REMOTE

DESIGN AREA

MAXIMUM

SQ.FT. /

SPRINKLER

3.

MAKE PROVISIONS FOR DRAINING THE ENTIRE SYSTEM PER NFPA 13.

10. UNOCCUPIED SPACES WITHOUT CEILINGS SHALL BE PROVIDED WITH UPRIGHT SPRINKLERS.

11. SPRINKLERS SHALL BE INSTALLED UNDER FIXED OBSTRUCTIONS OVER 4 FEET (1.2M) WIDE

PER NFPA 13. THE CONTRACTOR SHALL VERIFY ALL DUCTWORK DIMENSIONS IN THE FIELD AND

INSTALL SPRINKLERS AS REQUIRED.

12.

13.

VERIFY THE DISTANCE BETWEEN CEILING AND BOTTOM OF STRUCTURAL BEAMS IN ALL AREAS

WITH REFLECTIVE CEILINGS.

ALL HORIZONTAL PIPING SHALL BE LOCATED ABOVE THE CEILING OR IN SOFFIT SPACES

UNLESS NOTED OTHERWISE.

VERIFY AND COORDINATE VALVE IDENTIFICATION REQUIREMENTS WITH OWNER STANDARDS

IN THE FIELD.

THE SPRINKLER EQUIPMENT ROOM AND FIRE PROTECTION EQUIPMENT COMPONENTS (E.G.

VALVES, PIPING, TAMPER SWITCHES, FLOW ALARMS, ECT..) SHALL REQUIRE PROPER

IDENTIFICATION AS PER THE REQUIREMENT OF NFPA13.

THE SUBMISSION OF AUTOMATIC FIRE SUPPRESSION (SPRINKLER) SYSTEM SHOP DRAWINGS

(E.G. INFORMATION RELATIVE TO SPRINKLERS, FITTINGS, CHECK VALVES, EXPOSURE TO

HAZARDS, EXTENT OF SYSTEM COVERAGE, SUPPRESSION SYSTEM DESIGN CRITERIA, WATER

SUPPLY SOURCE, SUPPLY AND EXTINGUISHING AGENTS, LOCATION AND METHOD OF

OPERATION FOR DETECTION AND ALARM DEVICES,ECT. ) SHALL BE REQUIRED FOR REVIEW AND

EVALUATION AS PER IBC, 2009: THE STANDARD FOR THE INSTALLATION OF SPRINKLER SYSTEMS

(NFPA-13) AND THE HUD MAP CHAPTER 5 GUIDELINES.

EXTENT OF DEMOLITION NEW CONNECTION SYMBOL

CL

THREADED SUPPORT ROD

PIPE

CLEVIS HANGER

BEAM CLAMP

TYPICAL

NUT AND

WASHER

TYPICAL

METAL CHANNEL

STRUT

METAL DECKING

STRUCTURAL STEEL OR

OPEN WEB STEEL

JOINTS

(TYPICAL)

C-CLAMP TOP BEAM

FOR PIPING 3" &

SMALLER

C-CLAMP FOR

PIPING

3" & SMALLER

SIDE BEAM

CLAMP

DOUBLE SIDED BEAM

CLAMP

HANGER ROD -

TYPICAL

(SEE NOTE 1)

EQUIPMENT PROVIDE MIN. 3/8" DIA. HANGER ROD

(REFER TO MANUFACTURER'S INSTALLATION

INSTRUCTIONS).

NOTES:

PIPE HANGER DETAIL

NTS

BRANCH LINE

NIPPLE

NEW CEILING

DROP NIPPLE

COVER PLATE

REDUCER

SPRINKLER HEAD

CONCEALED SPRINKLER TYPE DETAIL

NTS

AS PER

NFPA 13

UPRIGHT SPRINKLER

BRANCH TEE

UPRIGHT SPRINKLER DETAIL

NTS

NORR

One Penn Center 1617 JFK Blvd, Suite 1600 Philadelphia, PA 19103 norr.com

ARCH E Title Block - v.2023 - Rev (Sept/23) - Copyright © 2023

Drawing No.

Project No.

Drawing Title

Project

Seal

Design Team

Project Manager

Project Architect Checked

Drawn

Client

Architecture:

Structural:

Mechanical:

Electrical:

A

BD C

This drawing shall not be used for construction purposes until the seal appearing hereon is signed and dated by the Architect or Engineer

E

NORR

NORR

NORR

NORR

A u to d e s k D o c s

/D e lC o

V o ti n g M a c h in e W a re h o u s e E le v a to r A d d it io n /I N

-0

M

E i_

D e lc o W a re h o u s e E le v a to rA d d it io n v .r v t

/2

/2

:5 :1

A

M

IN2325-0323

FP00-01

COVER SHEET

VOTING MACHINE

WAREHOUSE ELEVATOR

ADDITION

COUNTY OF DELAWARE

DEPARTMENT OF PUBLIC

WORKS

403 EAST 24TH STREET, CHESTER, PA 19013

105 W 3RD ST, MEDIA, PA 19063

BM

ZHOP

SO

This drawing has been prepared solely for the use of

COUNTY OF DELAWARE DEPARTMENT OF PUBLIC

WORKS and there are no representations of any kind made by NORR to any party with whom NORR has not entered into a contract.

FIRE PROTECTION SHEET LIST

FP00-01 COVER SHEET

FP20-01 OVERALL FIRE PROTECTION PLAN - FIRST FLOOR

FP20-02 OVERALL FIRE PROTECTION PLAN -SECOND

FLOOR

DATE ISSUED FOR REV

2026.03.04 BIDDING A

2026.04.28 PLAN REVIEW B

2026.04.28 PLAN REVIEW B06 C1818 REISSUED FOR BID

D D

C C

B B

A A

2.5

2.5

3.5

3.5

4.5

4.5

C.7 C.7

D D

C C

B B

A A

2.5

2.5

3.5

3.5

4.5

4.5

C.7 C.7

NEW ELEVATOR

SHAFT

EXISTING STREET

LEVEL VOTING

MACHINES

STORAGE AREA

EXISTING MID LEVEL

VOTING MACHINES

STORAGE AREA

EXISTING OFFICE

(N.I.C.)

EXISTING LUNCH

ROOM (N.I.C.)

EXISTING CORRIDOR

(N.I.C.)

EXISTING TOILET

(N.I.C.)

SYSTEM TYPE

AREA

DENSITY (GPM/SQ.FT.)

SPRINKLER TEMP. MAXIMUM SQ.FT./ SPR

DESIGN AREA (SQ.FT.)

HAZARD

WAREHOUSE

WET LIGHT

0.10

155 255

CONTRACTOR SHALL MODIFY SPRINKLER

HEAD DROPS AS NEEDED FOR NEW

ELEVATOR LOCATION. CONTRACTOR SHALL

ADD HEADS TO MAINTAIN COVERAGE

(E) UPRIGHT HEAD (E) UPRIGHT HEAD (E) UPRIGHT HEAD (E) UPRIGHT HEAD

(E) UPRIGHT HEAD (E) UPRIGHT HEAD (E) UPRIGHT HEAD (E) UPRIGHT HEAD

(E) UPRIGHT HEAD (E)HEAD

TO BE

DEMO

(E) UPRIGHT HEAD (E) UPRIGHT HEAD

(E) UPRIGHT HEAD (E) UPRIGHT HEAD (E) UPRIGHT HEAD (E) UPRIGHT HEAD

(E) UPRIGHT HEAD (E) UPRIGHT HEAD (E) UPRIGHT HEAD (E) UPRIGHT HEAD

CONTRACTOR SHALL REMOVE

SPRINKLER PIPING AND HEAD

AS INDICATED. CAP END OF PIPE.

END DEMO HERE

(E )F

P W

(E )F

P W

(E )F

P W

(E )F

P W

(E )F

P W

(E )F

P W

(E )F

P W

(E )F

P W

(E )F

P W

(E )F

P W

(E )F

P W

(E )F

P W

D E

M O

P

IP

E

(E )F

P W

(E )F

P W

(E )F

P W

(E )F

P W

NORR

One Penn Center 1617 JFK Blvd, Suite 1600 Philadelphia, PA 19103 norr.com

ARCH E Title Block - v.2023 - Rev (Sept/23) - Copyright © 2023

KEY PLAN

Drawing No.

Project No.

Drawing Title

Project

Seal

Design Team

Project Manager

Project Architect Checked

Drawn

Client

Architecture:

Structural:

Mechanical:

Electrical:

A

BD C

This drawing shall not be used for construction purposes until the seal appearing hereon is signed and dated by the Architect or Engineer

E

NORR

NORR

NORR

NORR

A u to d e s k D o c s

/D e lC o

V o ti n g M a c h in e W a re h o u s e E le v a to r A d d it io n /I N

-0

M

E i_

D e lc o W a re h o u s e E le v a to rA d d it io n v .r v t

/2

/2

:5 :2

A

M

IN2325-0323

FP20-01

OVERALL FIRE

PROTECTION PLAN - FIRST

FLOOR

VOTING MACHINE

WAREHOUSE ELEVATOR

ADDITION

COUNTY OF DELAWARE

DEPARTMENT OF PUBLIC

WORKS

403 EAST 24TH STREET, CHESTER, PA 19013

105 W 3RD ST, MEDIA, PA 19063

BM

ZHOP

SO

This drawing has been prepared solely for the use of

COUNTY OF DELAWARE DEPARTMENT OF PUBLIC

WORKS and there are no representations of any kind made by NORR to any party with whom NORR has not entered into a contract.

SCALE: 3/16" = 1'-0"

OVERALL FIRE PROTECTION PLAN -FIRST FLOOR

DATE ISSUED FOR REV

2026.03.04 BIDDING A

FE-4

FE-4

FE-4

D D

C C

B B

A A

2.5

2.5

3.5

3.5

4.5

4.5

C.7 C.7

D D

C C

B B

A A

2.5

2.5

3.5

3.5

4.5

4.5

C.7 C.7

(E) UPRIGHT

HEAD

(E) UPRIGHT HEAD (E) UPRIGHT HEAD (E) UPRIGHT HEAD

(E) UPRIGHT

HEAD

(E) UPRIGHT HEAD (E) UPRIGHT HEAD

(E) UPRIGHT

HEAD

(E) UPRIGHT HEAD (E) UPRIGHT HEAD (E) UPRIGHT HEAD

(E) UPRIGHT HEAD (E) UPRIGHT HEAD (E) UPRIGHT HEAD (E) UPRIGHT HEAD

CONTRACTOR SHALL REMOVE

SPRINKLER PIPING AND HEAD

AS INDICATED. CAP END OF PIPE.

(E)HEAD

TO BE

DEMO

/2 "ø

F P

(E

P

IP

E

T O

B E

D E

M O

(E )F

P W

(E )F

P W

(E )F

P W

(E) UPRIGHT HEAD (E) UPRIGHT HEAD (E) UPRIGHT HEAD (E) UPRIGHT HEAD

(E )F

P W

(E )F

P W

(E )F

P W

(E )F

P W

(E )F

P W

(E )F

P W

WOMENS TOILET

MENS TOILET

OFFICE

UNASSIGNED AREA

VOTING MACHINES

STORAGE AREA

VOTING MACHINES

STORAGE AREA

NEW UPRIGHT HEAD

NEW ELEVATOR

SHAFT

NORR

One Penn Center 1617 JFK Blvd, Suite 1600 Philadelphia, PA 19103 norr.com

ARCH E Title Block - v.2023 - Rev (Sept/23) - Copyright © 2023

KEY PLAN

Drawing No.

Project No.

Drawing Title

Project

Seal

Design Team

Project Manager

Project Architect Checked

Drawn

Client

Architecture:

Structural:

Mechanical:

Electrical:

A

BD C

This drawing shall not be used for construction purposes until the seal appearing hereon is signed and dated by the Architect or Engineer

E

NORR

NORR

NORR

NORR

A u to d e s k D o c s

/D e lC o

V o ti n g M a c h in e W a re h o u s e E le v a to r A d d it io n /I N

-0

M

E i_

D e lc o W a re h o u s e E le v a to rA d d it io n v .r v t

/2

/2

:5 :2

A

M

IN2325-0323

FP20-02

OVERALL FIRE

PROTECTION PLAN

-SECOND FLOOR

VOTING MACHINE

WAREHOUSE ELEVATOR

ADDITION

COUNTY OF DELAWARE

DEPARTMENT OF PUBLIC

WORKS

403 EAST 24TH STREET, CHESTER, PA 19013

105 W 3RD ST, MEDIA, PA 19063

BM

ZHOP

SO

This drawing has been prepared solely for the use of

COUNTY OF DELAWARE DEPARTMENT OF PUBLIC

WORKS and there are no representations of any kind made by NORR to any party with whom NORR has not entered into a contract.

SCALE: 3/16" = 1'-0"

FIRE PROTECTION PLAN - LEVEL 2

DATE ISSUED FOR REV

2026.03.04 BIDDING A

S

CO

W

VB

FM

H

RS

P

T

TS

HWS

M.X

S/R

M.X

CALL OUT SYMBOLS

SUPPLY OR RETURN AIR RISER DESIGNATION

FOR CONTINUATION

REFER TO DRAWINGS (XXX)

SYMBOL DESIGNATES ASSOCIATED

SYSTEM OR SERVICE (ie LPS)

DIFFUSER, GRILLE, REGISTER LETTER

ALTERNATE CFM LOCATION

DESIGN CFM

DESIGNATOR

A(200)

(200)

DETAIL DESIGNATION

PIPING SYSTEM RISER DESIGNATION

SECTION DESIGNATION

SHEET NUMBER

SHEET NUMBER

REMOTE TEMPEATURE SENSOR

REVISION NUMBER

REVISION CLOUD

SMOKE DETECTOR

OR HUMIDISTAT

STATIC PRESSURE SENSOR

RETURN/EXHAUST AIR FLOW

HUMIDITY SENSOR

THERMOSTAT

SUPPLY AIR FLOW

TEMPERATURE SENSOR

CONNECT TO EXISTING

LIMIT OF REMOVAL

SUPPLY LINES (CHWS, HWS, CWS, ETC...)

RETURN LINES (CHWR, HWR, CWR, ETC...)

REDUCER (ECCENTRIC-FLAT ON BOTTOM OR FLAT ON TOP)

STRAINER WITH HOSE BIBB & CAP (GATE VALVE FOR STEAM)

UNION OR FLANGE (AS INDICATED BY PIPE SIZE - SEE SPEC.)

PITCH PIPE DOWN IN DIRECTION OF FLOW

DROP (DOUBLE LINE - PLAN VIEW)

PITCH PIPE UP IN DIRECTION OF FLOW

CLEAN-OUT FOR CONDENSATE DRAIN

RISE (DOUBLE LINE - PLAN VIEW)

DROP (SINGLE LINE - PLAN VIEW)

RISE (SINGLE LINE - PLAN VIEW)

PIPE BREAK (DOUBLE LINE)

"TD" THERMODYNAMIC

PUMPED CONDENSATE

STEAM PIPING

REFRIGERANT PIPING

HOT WATER PIPING

CHILLED WATER PIPING

CONDENSATE DRAIN PIPING

CONDENSER WATER PIPING

"T" THERMOSTATIC

"F&T" FLOAT & THERMOSTATIC

"IB" INVERTED BUCKET

DIRECTION OF FLOW IN PIPE

STEAM TRAP:

PIPE BREAK (SINGLE LINE)

WATER METER DIAL TYPE

DIRT LEG

TOP TAKEOFF

BOTTOM TAKEOFF

VALVE IN VERTICAL

CHWS

UP

DN

HWS

PC

LPS

CWS

R

D

"XX"

AUTOMATIC AIR VENT WITH ISOLATION VALVE

REFER TO SPECIFICATIONS FOR BODY STYLE

PRESSURE GAUGE WITH GAUGE CLOCK

BLIND FLANGE

END CAP

ANCHOR

PRESSURE/TEMPERATURE WELL

THERMOSTATIC AIR VENT

REDUCER (CONCENTRIC)

EXPANSION JOINT

PIPE GUIDE

FLEXIBLE CONNECTION

MANUAL AIR VENT

STRAINER

VACUUM BREAKER

THERMOMETER

M

PT

COMBINATION FLOWMETER/SHUT OFF/BALANCING VALVE

VALVE WITH MEMORY STOP; REFER TO SPEC FOR BODY STYLE

TWO WAY AUTOMATIC CONTROL VALVE, TWO POSITION ACTUATOR

THREE WAY AUTOMATIC CONTROL VALVE, TWO POSITION ACTUATOR

AUTOMATIC FLOW CONTROL VALVE (PRESSURE INDEPENDENT)

TWO WAY AUTOMATIC CONTROL VALVE, MODULATING ACTUATOR

THREE WAY AUTOMATIC CONTROL VALVE, MODULATING ACTUATOR

VALVE WITH HOSE BIBB, CAP & CHAIN (DRAIN VALVES)

VALVE; REFER TO SPECIFICATIONS FOR BODY STYLE

FLOW MEASURING DEVICE

FLOW SWITCH

SAFTEY RELIEF VALVE

BALANCING VALVE

PRESSURE REDUCING VALVE

CHECK VALVE

PIPING

(CIRCUIT SETTER)

HYDRONIC SYSTEM SPECIFIC ABBREVIATIONS

EXPANSION TANK

ENTERING WATER TEMPERATURE

HOSE BIBB CONN W/CHAINED CAP

HOT WATER

COOLING WATER RETURN

COOLING WATER SUPPLY

COOLING TOWER BLOW DOWN

CHILLED WATER RETURN

CHILLED WATER SUPPLY

CONDENSER WATER RETURN

CONDENSER WATER SUPPLY

DRAIN OFF VALVE

CHILLED WATER

COOLING TOWER

COMPRESSION TANK

AIR SEPARATOR

AUTOMATIC AIR VENT

CHILLER

CHWS

DOV

EWT

HW

ET

HB

CWS

CTBD

CTK

CWR

CR

CS

CT

AAV

CHW

CHWR

AS

CH

HOT WATER SUPPLY

PRIMARY CHILLED WATER SUPPLY

PRIMARY CHILLED WATER RETURN

NET POSITIVE SUCTION HEAD

LEAVING WATER TEMPERATURE

PLATE HEAT EXCHANGER

HOT WATER RETURN

MANUAL AIR VENT

PCHWS

PCHWR

PHX

P

MAV

NPSH

LWT

PUMP

HWR

HWS

LEGEND NOTES:

PROJECT NOTES:

HVAC GENERAL NOTES

THIS SHEET IS A GENERAL LIST OF SYMBOLS AND ABBREVIATIONS AND SHALL BE USED AS A DICTIONARY TO DEFINE ITEMS INDICATED ON DRAWINGS. NOT ALL SYMBOLS OR ABBREVIATIONS ARE NECESSARILY

USED ON THIS PROJECT.EXHAUST

GENERAL CONTRACTOR

GALLONS PER MINUTE

GALLONS PER HOUR

GYPSUM WALL BOARD

HEAT EXCHANGER

HORSEPOWER

HEIGHT

FINNED TUBE RADIATION

FEET PER SECOND

FLOW CONTROL VALVE

FEET PER MINUTE

GALVANIZED

GALLONS

FURNISHED

FLEXIBLE

FIRE PROTECTION

DRY BULB TEMPERATURE

ELECTRIC CABINET UNIT HEATER

ENTERING AIR TEMPERATURE

DIRECT DIGITAL CONTROL

ENTERING

EQUIPMENT

ELEVATION

ELECTRICAL

EFFICIENCY

DRAWING

DIMENSION

DIAMETER

CABINET UNIT HEATER

CORRIDOR

CONTRACTOR

CUBIC FEET

COLUMN

CONCRETE

CLEAN-OUT

CEILING FAN

CENTERLINE

CEILING

BRITISH THERMAL UNIT PER HOUR

BRITISH THERMAL UNIT

BELOW FINISHED FLOOR

BRAKE HORSEPOWER

BASEMENT

BUILDING

BOILER

BOTTOM OF PIPE

BOTTOM OF DUCT

GC

HR HOUR

HZ

HX

HERTZ

GWB

HP

H

HD

GPM

GPH

HEAD

FT/SEC

GAL

GALV

G

FURN

FT

GAS

FEET

FLEX

FPM

FLR

FP

FCV

FTR

FLOOR

EXH

ENT

EQUIP

ELEV

ELEC

ECUH

EA

EFF

EAT

DWG

DIM

DN

DIA

EACH

DOWN

CO

DB

DDC

CUH

D DRAIN

CONTR

CORR

CUF

COL

CONC

BTU

CLG

CF

CL

BTUH

BLR

BOD

BSMT

BOP

BLDG

BFF

BHP

W/O WITHOUT

WET BULB TEMPERATURE

WATER GAUGEWG

WB

VARIABLE FREQUENCY DRIVE

REVOLUTIONS PER MINUTE

VENT THROUGH ROOF

UNIT HEATER

TOP OF DUCT

TOP OF PIPE

TEMPERATURE

STAINLESS STEEL

STANDARD

SPECIFICATIONS

SQUARE FEET

RELATIVE HUMIDITY

UH

W/

VTR

W

VFD

VEL

V

WIDTH

WITH

VENT

VELOCITY

TOD

TYP

TOP

TEMP

TYPICAL

STDBY

SUP

SS

STD

SQFT

SQ

STANDBY

SUPPLY

SQUARE

SPECS

RH

RM

RPM

ROOM

POUNDS PER SQUARE INCH GAUGE

POUNDS PER SQUARE INCH ABSOLUTE

POUNDS PER CUBIC FOOT

POLYVINYL CHLORIDE

PLUMBING

PRESSURE

PRESSURE DROP

OUTLET VELOCITY

OPEN DRIP PROOF

OUTSIDE DIAMETER

NOT TO SCALE

NOT IN CONTRACT

NOISE CRITERIA

NOT APPLICABLE

OCTAVE BAND

REQD

RET

PVC

PSIG

PSIA

REQUIRED

RETURN

PD

PRESS

PLBG

PH

OV

PCF

PHASE

ODP

OD

NTS

OB

NIC

NOM

NC

N/A

NOMINAL

BUILDING AUTOMATION SYSTEM

AIR SEPARATOR

AVERAGE

ABOVE FINISHED GRADE

AUTOMATIC TEMPERATURE CONTROL

ABOVE FINISHED FLOOR

AUTOMATIC CONTROL VALVE

DEGREES FAHRENHEIT

ARCHITECT

ACCESS PANEL

ACCESS DOOR

DEGREES CELSIUS

DIAMETER

AFF

AVG

BAS

AS

ARCH

ATC

AP

AFG

ACV

AD

°F °C

THOUSAND BRITISH THERMAL UNITS / Hr.

MOTOR CONTROL CENTER

GENERIC HVAC ABBREVIATIONS

MECHANICAL

MAKEUP WATER

MEZZANINE

MANUFACTURER

MINIMUM CIRCUIT AMPS

ONE THOUSAND

LINEAR FEET

KILOVOLT AMPERE

INSULATION

INSIDE DIAMETER

LB POUND

MCC

MTD

MU

MIN

MECH

MEZZ

MFR

MOUNTED

MINIMUM

MAX

MBH

MCA

LVG

LF

M

MAXIMUM

LEAVING

KVA

KW

L

INSUL

ID

IN

LENGTH

KILOWATT

INCHES

ELECTRIC UNIT HEATEREUH

EXISTING TO BE REMOVED(ER)

(E) EXISTING

(RE) RELOCATED EXISTING

LD LINEAR DIFFUSER

NEW(N)

INSTALL ALL EQUIPMENT IN ACCORDANCE WITH MANUFACTURER'S INSTALLATION INSTRUCTIONS. INSTALL UNITS PLUMB AND LEVEL, FIRMLY ANCHORED IN LOCATIONS INDICATED, AND MAINTAIN MANUFACTURER'S

RECOMMENDED CLEARANCES.

ALL MATERIAL SHALL BE SUBMITTED TO THE A/E VERIFYING IT IS ADEQUATE FOR INSTALLATION PER THE SPECIFICATIONS AND DRAWING. VERIFY DIMENSIONS AND CLEARANCES AT BUILDING BEFORE COMMENCING

WORK.

MECHANICAL CONTRACTOR SHALL PROVIDE TWO FILTER CHANGES PRIOR TO GRAND OPENING.

IT IS THE RESPONSIBILITY OF THE CONTRACTOR TO VERIFY THE ACTUAL LOCATION OF EXISTING

STRUCTURAL MEMBERS AND COORDINATE INSTALLATION OF THE EQUIPMENTS ACCORDINGLY.

THE CONTRACTOR SHALL FULFILL ALL REQUIREMENTS OF THE CONTRACT DOCUMENTS AND SHALL COMPLETE THE IMPROVEMENTS SHOWN ON THE DRAWINGS. ALL SYSTEMS SHALL BE FINISHED, TESTED, AND BALANCED, ADJUSTED, AND PROVEN FULLY OPERATIONAL AND USEABLE.

EXCEPT WHERE SPECIFICALLY SHOWN OR SPECIFIED OTHERWISE, EXISTING WORK IS TO REMAIN.

WHERE PIPES, CONTROL DEVICES AND WIRING WHICH ARE TO REMAIN IN-SERVICE ARE DISCONNECTED FOR THE REMOVAL OR RELOCATION OF EQUIPMENT OR BECAUSE OF BUILDING ALTERATIONS, THEY SHALL BE RE-

CONNECTED.

TRANSITION RECTANGULAR DUCTWORK ON BOTTOM AND SIDES. MAINTAIN TOP OF DUCTWORK LEVEL AND

AS HIGH AS POSSIBLE. PROVIDE VOLUME DAMPER AT EACH BRANCH DUCTWORK.

CONTRACTOR SHALL COORDINATE VOLTAGE AND PHASE OF EACH PIECE OF EQUIPMENT WITH THE

ELECTRICAL CONTRACTOR PRIOR TO ORDERING.

MOUNT THERMOSTATS AND FAN SWITCHES WHERE INDICATED ON PLANS 48" AFF UNLESS NOTED

OTHERWISE.

COORDINATE DUCTWORK AND PIPING WITH PLUMBING, FIRE PROTECTION AND ELECTRICAL.

MAKE OFFSETS AND TRANSITIONS TO COORDINATE WITH OTHER TRADES WITHOUT ADDITIONAL EXPENSE TO

THE OWNER.

PROVIDE FIRE DAMPERS OR FIRE SMOKE DAMPERS WHERE INDICATED ON THE PLANS. PROVIDE DUCT ACCESS PANELS FOR SERIVCING AND COORDINATE WITH ARCHITECT FOR WALL OR CEILING ACCESS PANEL

LOCATIONS.

EXACT LOCATIONS OF ALL CEILING AIR DEVICES SHALL BE COORDINATED WITH LIGHT FIXTURES, SPRINKLER HEADS AND OTHER CEILING MOUNTED FIXTURES AT JOB SITE. REFER TO ARCHITECTURAL REFLECTED

CEILING PLAN.

THE SCOPE OF WORK SHALL INCLUDE PROVIDING ALL WORK INDICATED, AND COORDINATION

WITH ALL TRADES. SCOPE OF WORK IS INDICATED ON THE CONTRACT DOCUMENTS INCLUDING

THE DRAWINGS AND THE SPECIFICATIONS, WHICH ARE COMPLIMENTARY. WORK INDICATED IN

ANY CONTRACT DOCUMENT SHALL BE CONSIDERED PART OF THE SCOPE OF WORK. IN

GENERAL, WORK REQUIREMENTS ARE NOT INDICATED IN BOTH DOCUMENTS. WHERE

DOCUMENTS CONFLICT WITHIN THEMSELVES OR WITH CODES AND REGULATIONS, PROVIDE

THE HIGHER QUANTITY AND QUALITY AND FOLLOW THE STRICTER REQUIREMENTS.

ALL MOUNTING HEIGHTS ARE TO BOTTOM UNLESS OTHERWISE INDICATED.

IF EXACT MOUNTING OR RACEWAY ROUTINGS ARE NOT INDICATED (LOCATION OR HEIGHT)

COORDINATE WITH OTHER TRADES AND REQUEST CLARIFICATION PRIOR TO ROUGHING, OR

INSTALLATION.

A

T

BALL VALVE; REFER TO SPEC FOR BODY STYLE

LEGEND

STORM PIPE STORM

PART 1 - GENERAL

1.1 SCOPE OF WORK

A. PROVIDE ALL LABOR, MATERIALS, AND EQUIPMENT NECESSARY FOR

THE INSTALLATION OF A COMPLETE PLUMBING SYSTEMS AS

INDICATED ON DRAWINGS.

1.2 RELATED DOCUMENTS

A. DRAWINGS AND GENERAL PROVISIONS OF THE CONTRACT,

INCLUDING GENERAL AND SUPPLEMENTARY CONDITIONS AND

DIVISION 1 SPECIFICATION SECTIONS, APPLY TO THIS DRAWING

SPECIFICATIONS.

1.3 REGULATIONS

A. ENTIRE INSTALLATION, INCLUDING MATERIALS, EQUIPMENT AND

WORKMANSHIP, SHALL CONFORM WITH ALL APPLICABLE LAWS,

CODES AND REGULATIONS OF MUNICIPAL, STATE AND FEDERAL

AUTHORITIES.

B. THE CONTRACTOR SHALL MAKE TESTS FOR ACCEPTANCE AND

APPROVAL AS REQUIRED BY THE CODE AND THE OWNER'S

REPRESENTATIVE.

1.4 PERMITS

A. THE CONTRACTOR SHALL OBTAIN ALL NECESSARY PERMITS,

APPROVALS AND PAY ALL RELATED FEES AS REQUIRED BY THE LOCAL

MUNICIPALITY.

1.5 PROTECTION

A. EFFECTIVELY PROTECT ALL MATERIALS AND EQUIPMENT FROM DUST,

DIRT, AND DAMAGE UNTIL FINAL ACCEPTANCE.

1.6 SAFETY

A. DURING CONSTRUCTION, THE CONTRACTOR(S) SHALL BE

RESPONSIBLE FOR PROVIDING ALL HIS EMPLOYEES WITH SAFE AND

HEALTHFUL WORKING CONDITIONS AS PRESCRIBED IN THE "SAFETY

AND HEALTH REGULATIONS FOR CONSTRUCTION" OF THE

OCCUPATIONAL SAFETY AND HEALTH ADMINISTRATION OF THE U.S.

DEPARTMENT OF LABOR.

1.7 GUARANTEE

A. ALL MATERIALS, EQUIPMENT, AND WORKMANSHIP SHALL BE

GUARANTEED IN WRITING FOR ONE (1) YEAR AFTER FINAL

ACCEPTANCE BY OWNER.

1.8 COORDINATION

A. IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR(S) TO VERIFY

FIELD CONDITIONS AT THE SITE AND NOTIFY THE OWNER'S

REPRESENTATIVE OF ANY DISCREPANCIES.

B. ANY CHANGES AND/OR MODIFICATIONS MUST BE REVIEWED AND

APPROVED BY OWNER'S REPRESENTATIVE PRIOR TO CONSTRUCTION.

1.9 SHOP DRAWINGS

A. THE CONTRACTOR(S) SHALL SUBMIT THE REQUIRED COPIES OF SHOP

DRAWINGS FOR ALL SYSTEM COMPONENTS TO OWNER'S

REPRESENTATIVE FOR APPROVAL.

B. PROVIDE A STAMP ON EACH SUBMITTAL INDICATING CONTRACTOR'S

REVIEW AND APPROVAL IN ACCORDANCE WITH THE CONTRACT

DOCUMENTS.

1.10 DRAWINGS

A. THE DRAWINGS INDICATE DIAGRAMMATICALLY THE EXTENT, GENERAL

CHARACTER AND LOCATION OF THE WORK INCLUDED. OFFSETS OR

CHANGES IN DIRECTION TO AVOID STRUCTURAL OR OTHER

INTERFERENCES, AND WORK INDICATED BUT HAVING MINOR DETAILS

OBVIOUSLY OMITTED SHALL BE PROVIDED WITHOUT EXTRA COST.

B. FINAL PIPING CONNECTIONS TO FIXTURES, EQUIPMENT, PIPING BY

OTHERS, ETC., WHERE NOT SPECIFICALLY SHOWN, SHALL BE

NCLUDED AT NO ADDITIONAL COST.

1.11 RECORD DRAWINGS

A. DURING CONSTRUCTION, THE CONTRACTOR(S) SHALL MAINTAIN A

RECORD SET OF INSTALLATION PRINTS. RECORD ON THESE PRINTS

ALL DEVIATIONS FROM THE CONTRACT DRAWINGS IN SIZES,

LOCATIONS, AND DETAILS.

B. AT THE COMPLETION OF THE WORK, THE CONTRACTOR SHALL

FORWARD THESE PRINTS TO OWNER.

1.12 GENERAL REQUIREMENTS

A. THE CONTRACTOR(S) SHALL FIELD COORDINATE WITH MECHANICAL,

ELECTRICAL CONTRACTORS.

B. ALL EQUIPMENT SHALL BE INSTALLED IN STRICT ACCORDANCE WITH

MANUFACTURER'S INSTRUCTIONS.

C. CONTRACTOR(S) SHALL PROVIDE ALL ITEMS, ASSEMBLIES, FITTINGS,

SUPPLIES, AND ACCESSORIES REQUIRED FOR THE INSTALLATION OF

THEIR WORK.

D. FURNISH AND INSTALL SUITABLE AND SUBSTANTIAL HANGERS AND

SUPPORTS FOR ALL HORIZONTAL AND VERTICAL PIPING. HANGERS

MAY BE DIRECTLY MOUNTED TO BEAMS OF BUILDING CONSTRUCTION.

THE INTENTION IS TO PROVIDE SUPPORTS WHICH IN EACH CASE

SHALL BE AMPLY STRONG AND RIGID FOR THE LOAD BUT WHICH

SHALL NOT WEAKEN OR UNDULY STRESS THE BUILDING

CONSTRUCTION.

E. THE CONTRACTOR(S) SHALL BE RESPONSIBLE FOR ALL CUTTING AND

PATCHING REQUIRED FOR THE INSTALLATION OF THEIR RESPECTIVE

WORK.

F. DEMOLITION SHALL INCLUDE COMPLETE REMOVAL OF EXISTING

PLUMBING SYSTEMS OR BRANCH PIPING INDICATED. CAP WASTE

PIPING AND WATER PIPING BEHIND WALLS, BELOW FLOORS OR OUT

OF VIEW. WORK IN THE CEILING SPACE BELOW THE FLOOR FOR

REMOVAL OF WATER AND WASTE PIPING SHALL BE COORDINATED

WITH THE BUILDING MANAGER OR OWNER.

PLUMBING SPECIFICATIONS

NORR

One Penn Center 1617 JFK Blvd, Suite 1600 Philadelphia, PA 19103 norr.com

ARCH E Title Block - v.2023 - Rev (Sept/23) - Copyright © 2023

Drawing No.

Project No.

Drawing Title

Project

Seal

Design Team

Project Manager

Project Architect Checked

Drawn

Client

Architecture:

Structural:

Mechanical:

Electrical:

A

BD C

This drawing shall not be used for construction purposes until the seal appearing hereon is signed and dated by the Architect or Engineer

E

NORR

NORR

NORR

NORR

A u to d e s k D o c s

/D e lC o

V o ti n g M a c h in e W a re h o u s e E le v a to r A d d it io n /I N

-0

M

E i_

D e lc o W a re h o u s e E le v a to rA d d it io n v .r v t

/2

/2

:5 :2

A

M

IN2325-0323

M00-01

MECHANICAL COVER

SHEET

VOTING MACHINE

WAREHOUSE ELEVATOR

ADDITION

COUNTY OF DELAWARE

DEPARTMENT OF PUBLIC

WORKS

403 EAST 24TH STREET, CHESTER, PA 19013

105 W 3RD ST, MEDIA, PA 19063

BM

ZHOP

SO

This drawing has been prepared solely for the use of

COUNTY OF DELAWARE DEPARTMENT OF PUBLIC

WORKS and there are no representations of any kind made by NORR to any party with whom NORR has not entered into a contract.

MECHANICAL SHEET LIST

M00-01 MECHANICAL COVER SHEET

M03-01 SCHEDULES AND DETAILS

MD20-01 OVERALL MECHANICAL DEMOLITION PLAN -FIRST

FLOOR

M20-01 OVERALL MECHANICAL PLAN - FIRST FLOOR

M20-02 OVERALL MECHANICAL PLAN -SECOND FLOOR

DATE ISSUED FOR REV

2026.03.04 BIDDING A

PLUMBING EQUIPMENT SCHEDULE

SYMBOL DESCRIPTION BASIS OF DESIGN SYSTEM DESIGN CAPICTY ELECTRICAL

CHARACTERISTICS

REMARKS

ELEVATOR

SHAFT

24x24x24STEEL GRATEBASIN WITH

LEVEL

LEVELTURN ON

TURN-OFF

BASIN COVER

1-1/2" COPPER PIPING

PERFORATED

MIN. 4'-0"

SUMP PIT

ELEVATOR

5"

ABOVE

FLOOR

STEEL PULL

PUMP CABLE

CABLE HOOK

EMERGENCY

POWER GROUNDED

WALL RECEPTACLE

GRADE

BASEMENT

SP-1 SUMP PUMP ZOELLER 940-0013 OIL GUARD SYSTEM

10.5 AMPS

115/1/60

PUMP 153, 50 GPM AT 20 FT TDH

3600 RPM, 1/2 HP

SCHEDULE/

SERVICE SIZE MATERIAL

TYPETYPE

INSULATION

THICK

REMARKS

SANITARY AND VENT PIPING ALL CAST IRON -SERVICE WEIGHT - -

PIPE MATERIAL SCHEDULE

UNIT NO. SERVICE

AIR FLOW

(CFM)

(ON/OFF)

EXTERNAL

STATIC

PRESSURE

TF-1 ELEVATOR

CONTROL RM

TRANSFER FAN SCHEDULE

PROVIDE UNIT MOUNTED SPEED CONTROLLER AND STANDARD DISCONNECT.

NOTES:

1.

2.

UNIT TO BE INSTALLED LEVEL. ALL STARTERS SHALL BE PROVIDED BY THE MECHANICAL CONTRACTOR AND INSTALLED BY THE ELECTRICAL CONTRACTOR.

3. FAN SHALL OPERATE VIA LINE VOLTAGE THERMOSTAT SET FOR 80 DEGREES

POWER FAN WEIGHT

ROOF OR

WALL CAP

MANUFACTURER & MODEL NOTESHORSEPOWER

0.375"350 208/1 55 LBS WALL COOK 12XW32D17 1, 2, 31/8 HP

DISCONNECT SWITCH: FURNISHED

BY

MECHANICAL CONTRACTOR OR FAN

MANUFACTURER

VARIABLE SPEED CONTROLLER

MARK

WITH THE "AS BALANCED POSITION"

(DIRECT DRIVE UNITS)

INTEGRAL BACKDRAFT DAMPER

FAN

HANGER

SUPPORTS:

1" X 22 GA, DO NOT

SUPPORT FROM

CEILING.

CEILING

ADJUSTABLE CLEVIS HANGER

TYPE 1 IN SPECIFICATIONS

MAXIMUM PIPE SUPPORT SPACING, FEET

NOM. SIZE 3

PIPE

THRU 3/4 1 1.25

6 FT 6

1.5 2

106 10

2.5 4 5 6 8

INSULATION SHIELD

PROVIDE HIGH COMPRESSIVE

HANGER ROD

10 10 10 10 10 10

COPPER PIPE ONLY

AT HANGER

STRENGTH INSULATION INSERT

BLOCKS UNDER INSULATION

SHIELD

MAXIMUM PIPE SUPPORT SPACING, FEET

NOM. SIZE 3

PIPE

THRU 3/4 1 1.25

12 FT

1.5 2

2.5 4 5 6 8

STEEL PIPE PIPE ONLY

12 12 12 12 12 12121212

PIPE

HANGER

NTS

PIPE HANGER DETAIL

NTS

TRANSFER FAN DETAIL

NTS

ELEVATOR SUMP PUMP DETAIL

FCO CLEAN OUT JAY R. SMITH MODEL #4313

NORR

One Penn Center 1617 JFK Blvd, Suite 1600 Philadelphia, PA 19103 norr.com

ARCH E Title Block - v.2023 - Rev (Sept/23) - Copyright © 2023

Drawing No.

Project No.

Drawing Title

Project

Seal

Design Team

Project Manager

Project Architect Checked

Drawn

Client

Architecture:

Structural:

Mechanical:

Electrical:

A

BD C

This drawing shall not be used for construction purposes until the seal appearing hereon is signed and dated by the Architect or Engineer

E

NORR

NORR

NORR

NORR

A u to d e s k D o c s

/D e lC o

V o ti n g M a c h in e W a re h o u s e E le v a to r A d d it io n /I N

-0

M

E i_

D e lc o W a re h o u s e E le v a to rA d d it io n v .r v t

/2

/2

:5 :2

A

M

IN2325-0323

M03-01

SCHEDULES AND DETAILS

VOTING MACHINE

WAREHOUSE ELEVATOR

ADDITION

COUNTY OF DELAWARE

DEPARTMENT OF PUBLIC

WORKS

403 EAST 24TH STREET, CHESTER, PA 19013

105 W 3RD ST, MEDIA, PA 19063

BM

ZHOP

SO

This drawing has been prepared solely for the use of

COUNTY OF DELAWARE DEPARTMENT OF PUBLIC

WORKS and there are no representations of any kind made by NORR to any party with whom NORR has not entered into a contract.

DATE ISSUED FOR REV

2026.03.04 BIDDING A

D D

C C

B B

A A

2.5

2.5

3.5

3.5

4.5

4.5

C.7 C.7

CONTRACTOR SHALL REMOVE EXISTING

PIPING LOCATED IN PROPOSED ELEVATOR

SHAFT LOCATION.

EXISTING STREET

LEVEL VOTING

MACHINES

STORAGE AREA

EXISTING MID LEVEL

VOTING MACHINES

STORAGE AREA

EXISTING OFFICE

(N.I.C.)

EXISTING LUNCH

ROOM (N.I.C.)

EXISTING CORRIDOR

(N.I.C.)

EXISTING TOILET

(N.I.C.)

(E)1-1/2" SUPPLY AND

RETURN UP

(E) 1-1/2" SUPPLY AND

RETURN UP

(E) 1-1/2" SUPPLY

AND RETURN UP

(E) 1-1/2" SUPPLY AND

RETURN UP

(E) 1-1/2" HWS/R UP

(E) HWS/R UP

(E)1-1/2" SUPPLY

AND RETURN UP

(E) UH

(E) UH

(E) UH

(E) UH (E) UH

(E) UH

(E) HYDRONIC SUPPLY AND RETURN PIPES

(E) HYDRONIC SUPPLY AND RETURN PIPES

(E) HYDRONIC SUPPLY AND RETURN PIPES

(E) HWS/R PIPES (TYPICAL)

NORR

One Penn Center 1617 JFK Blvd, Suite 1600 Philadelphia, PA 19103 norr.com

ARCH E Title Block - v.2023 - Rev (Sept/23) - Copyright © 2023

KEY PLAN

Drawing No.

Project No.

Drawing Title

Project

Seal

Design Team

Project Manager

Project Architect Checked

Drawn

Client

Architecture:

Structural:

Mechanical:

Electrical:

A

BD C

This drawing shall not be used for construction purposes until the seal appearing hereon is signed and dated by the Architect or Engineer

E

NORR

NORR

NORR

NORR

A u to d e s k D o c s

/D e lC o

V o ti n g M a c h in e W a re h o u s e E le v a to r A d d it io n /I N

-0

M

E i_

D e lc o W a re h o u s e E le v a to rA d d it io n v .r v t

/2

/2

:5 :2

A

M

IN2325-0323

MD20-01

OVERALL MECHANICAL

DEMOLITION PLAN -FIRST

FLOOR

VOTING MACHINE

WAREHOUSE ELEVATOR

ADDITION

COUNTY OF DELAWARE

DEPARTMENT OF PUBLIC

WORKS

403 EAST 24TH STREET, CHESTER, PA 19013

105 W 3RD ST, MEDIA, PA 19063

BM

ZHOP

SO

This drawing has been prepared solely for the use of

COUNTY OF DELAWARE DEPARTMENT OF PUBLIC

WORKS and there are no representations of any kind made by NORR to any party with whom NORR has not entered into a contract.

SCALE: 3/16" = 1'-0"

OVERALL MECHANICA DEMOLITIONL PLAN -FIRST FLOOR

DATE ISSUED FOR REV

2026.03.04 BIDDING A

D D

C C

B B

A A

2.5

2.5

3.5

3.5

4.5

4.5

C.7 C.7

NEW ELEVATOR

SHAFT

SP-1

(E)1-1/2" SUPPLY AND

RETURN UP

(E) 1-1/2" SUPPLY AND

RETURN UP

(E) UH

(E) UH

(E) UH

(E) UH

(E) UH (E) UH

(E) 1-1/2" SUPPLY

AND RETURN UP

(E) 1-1/2" SUPPLY AND

RETURN UP

(E) 4" SAN FROM ABOVE (E) 4" SAN DOWN

(E) 4" STORM

FROM ROOF

(E) 1-1/2" SUPPLY AND

RETURN UP (E) 1-1/2" SUPPLY AND

RETURN UP

CO

CO 2"ø

"ø

(E)1-1/2" SUPPLY

AND RETURN UP

CONNECT TO TOP

OF STORM PIPE.

PROVIDE INDIRECT

CONNECTION

PROVIDE NEW 1-1/2" HEATING

WATER SUPPLY AND RETURN.

PROVIDE 2" PREFORMED FIBERGLASS

INSULATION WITH ASJ JACKET.

EXISTING OFFICE

(N.I.C.)

EXISTING LUNCH

ROOM (N.I.C.)

EXISTING STREET

LEVEL VOTING

MACHINES

STORAGE AREA

EXISTING MID LEVEL

VOTING MACHINES

STORAGE AREA

EXISTING CORRIDOR

(N.I.C.)

EXISTING TOILET

(N.I.C.)

S T

O R

M

STORM

(E) HYDRONIC SUPPLY AND RETURN PIPES

(E) HYDRONIC SUPPLY AND RETURN PIPES

(E) HYDRONIC SUPPLY AND RETURN PIPES

(E )R

E T

U R

N

T Y

P

(E )S

U P

P L

Y

T Y

P

(E) HYDRONIC RETURN PIPE

(E) HYDRONIC SUPPLY PIPE

(E

H Y

D R

O N

IC

R

E T

U R

N P

IP

E(E

H

Y D

R O

N

IC

S U

P P

L Y

P

IP

E

(E) HYDRONIC RETURN PIPE

(E) HYDRONIC SUPPLY PIPE

(E

H Y

D R

O N

IC

R

E T

U R

N P

IP

E

(E

H Y

D R

O N

IC

S

U P

P L

Y P

IP

E

2" PIPE COMES UP FROM

SUMP PUMP

2" PIPE WILL RUN

UNDERNEATH SUPPLY

AND RETURN PIPES

NORR

One Penn Center 1617 JFK Blvd, Suite 1600 Philadelphia, PA 19103 norr.com

ARCH E Title Block - v.2023 - Rev (Sept/23) - Copyright © 2023

KEY PLAN

Drawing No.

Project No.

Drawing Title

Project

Seal

Design Team

Project Manager

Project Architect Checked

Drawn

Client

Architecture:

Structural:

Mechanical:

Electrical:

A

BD C

This drawing shall not be used for construction purposes until the seal appearing hereon is signed and dated by the Architect or Engineer

E

NORR

NORR

NORR

NORR

A u to d e s k D o c s

/D e lC o

V o ti n g M a c h in e W a re h o u s e E le v a to r A d d it io n /I N

-0

M

E i_

D e lc o W a re h o u s e E le v a to rA d d it io n v .r v t

/2

/2

:5 :2

A

M

IN2325-0323

M20-01

OVERALL MECHANICAL

PLAN - FIRST FLOOR

VOTING MACHINE

WAREHOUSE ELEVATOR

ADDITION

COUNTY OF DELAWARE

DEPARTMENT OF PUBLIC

WORKS

403 EAST 24TH STREET, CHESTER, PA 19013

105 W 3RD ST, MEDIA, PA 19063

BM

ZHOP

SO

This drawing has been prepared solely for the use of

COUNTY OF DELAWARE DEPARTMENT OF PUBLIC

WORKS and there are no representations of any kind made by NORR to any party with whom NORR has not entered into a contract.

SCALE: 3/16" = 1'-0"M20-01

OVERALL MECHANICAL PLAN -FIRST FLOOR1

DATE ISSUED FOR REV

2026.03.04 BIDDING A

D D

C C

B B

A A

2.5

2.5

3.5

3.5

4.5

4.5

C.7 C.7

NEW ELEVATOR

SHAFT

FDFD

10X10 TRANFER DUCT

WITH FIRE DAMPER.

COVER OPENING WITH

WIRE MESH.

10X10 TRANFER DUCT

WITH FIRE DAMPER.

COVER OPENING WITH

WIRE MESH.

TF-1

(E) UH

(E) UH

(E) UH

(E) UH

(E) UH

(E) UH

(E) UH(E) UH

1-1/2" SUPPLY AND

RETURN UP FROM BELOW

(E) 1-1/2" SUPPLY AND

RETURN UP FROM BELOW

(E) 1-1/2" SUPPLY

AND RETURN UP

FROM BELOW

(E) 1-1/2" SUPPLY AND

RETURN UP FROM BELOW

(E) 1-1/2" SUPPLY AND

RETURN UP FROM BELOW

(E) 1-1/2" SUPPLY AND

RETURN UP FROM BELOW

(E)1-1/2" SUPPLY

AND RETURN UP

FROM BELOW

WOMENS TOILET

OFFICE

UNASSIGNED AREA

MENS TOILET

VOTING MACHINES

STORAGE AREA

VOTING MACHINES

STORAGE AREA

(E)RD(E)RD

(E)RD(E)RD

(E)RD

(E)RD

PROVIDE 2" PREFORMED

FIBERGLASS INSULATION

WITH ASJ JACKET.

NEW REMOTE

CONTROL CLOSET

VOTING MACHINES

STORAGE AREA

NORR

One Penn Center 1617 JFK Blvd, Suite 1600 Philadelphia, PA 19103 norr.com

ARCH E Title Block - v.2023 - Rev (Sept/23) - Copyright © 2023

KEY PLAN

Drawing No.

Project No.

Drawing Title

Project

Seal

Design Team

Project Manager

Project Architect Checked

Drawn

Client

Architecture:

Structural:

Mechanical:

Electrical:

A

BD C

This drawing shall not be used for construction purposes until the seal appearing hereon is signed and dated by the Architect or Engineer

E

NORR

NORR

NORR

NORR

A u to d e s k D o c s

/D e lC o

V o ti n g M a c h in e W a re h o u s e E le v a to r A d d it io n /I N

-0

M

E i_

D e lc o W a re h o u s e E le v a to rA d d it io n v .r v t

/2

/2

:5 :2

A

M

IN2325-0323

M20-02

OVERALL MECHANICAL

PLAN -SECOND FLOOR

VOTING MACHINE

WAREHOUSE ELEVATOR

ADDITION

COUNTY OF DELAWARE

DEPARTMENT OF PUBLIC

WORKS

403 EAST 24TH STREET, CHESTER, PA 19013

105 W 3RD ST, MEDIA, PA 19063

BM

ZHOP

SO

This drawing has been prepared solely for the use of

COUNTY OF DELAWARE DEPARTMENT OF PUBLIC

WORKS and there are no representations of any kind made by NORR to any party with whom NORR has not entered into a contract.

SCALE: 3/16" = 1'-0"

OVERALL MECHANICAL PLAN - SECOND FLOOR

DATE ISSUED FOR REV

2026.03.04 BIDDING A

Sheets
FP00-01 - COVER SHEET
FP20-01 - OVERALL FIRE PROTECTION PLAN - FIRST FLOOR
FP20-02 - OVERALL FIRE PROTECTION PLAN -SECOND FLOOR