2-2026-06-18 Delco WarehouseElevatorAddition REVBID E.pdf
PDF 582 KB Posted
- Solicitation number
- US.257928
- Issued by
- Delaware County, Pennsylvania
About this file
This document is a set of electrical construction drawings and specifications prepared by NORR for the County of Delaware, Pennsylvania Department of Public Works for the Voter Machine Warehouse Elevator Addition project located at 403 East 24th Street, Chester, Pennsylvania. The project involves the installation of a new service elevator in an existing two-story commercial warehouse building, classified as an Alteration Level II. The scope of electrical work includes providing a 60-ampere, three-phase feeder with appropriate disconnect switch and fuses for elevator power; supplying and installing all fire alarm devices including addressable pull stations, smoke detectors, strobe lights, speakers, and wiring to integrate with the existing fire alarm control panel; installing new strobe light power supplies and speaker amplifiers; relocating existing lighting fixtures as required; and performing all necessary demolition, rewiring, and coordination of existing electrical services to accommodate the new elevator installation. The electrical contractor must supply all manufacturer technician time, testing fees including local fire department smoke testing, software programming, and final system commissioning in the base price. The project requires compliance with the local building code, NFPA 72, and the National Electrical Code. The bid response deadline is November 10, 2026 at 11:00 a.m. via PennBid, with a highly recommended Pre-Bid Conference scheduled for October 20, 2026 at 11:00 a.m. at the project site.
The electrical plans specify connection to an existing 600-ampere, 208/120-volt, three-phase main distribution panel serving existing branch panels VM-1, VM-2, LP-1, and LP-2, with the new elevator requiring a dedicated 60-ampere feeder. All fire alarm work must utilize the existing addressable fire alarm control panel and extend the existing addressable loop using new three-conductor, number 16 shielded low impedance cable to all devices. The contractor is responsible for maintaining fire alarm system integrity throughout demolition and construction, verifying existing branch circuit wiring condition and replacing any non-functional wiring, coordinating all work with existing equipment and services to remain, and providing complete and accurate circuit directories upon project completion. No specific pricing information, set-asides, or incumbent contractor details are provided in the electrical construction drawings; these details would be contained in the separate Invitation to Bid documents available through PennBid.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
(RE)
(ER)
(R)
(E)
KEY NOTE
TERMINATION POINT OF DEMOLITION
CONNECT NEW TO EXISTING
RELOCATED EXISTING EQUIPMENT
EXISTING EQUIPMENT TO BE RELOCATED
EXISTING EQUIPMENT TO REMAIN
EXISTING EQUIPMENT TO BE REMOVED
N
HP MOTOR, HP = HORSEPOWER
TRANSFER SWITCH
L = LOAD
L
E = EMERGENCY SOURCE
N = NORMAL SOURCE
E
S
S
B
I INTERCOM
PUSH ALARM SWITCH
ELECTRIC DOOR STRIKE
CR CARD READER
120V/208V OR 277/480V
J JUNCTION BOX - SIZE AS REQUIRED
CLOCK OUTLET WALL MOUNTED
PHOTO ELECTRIC CELLPE
TRANSFORMER - SIZE AS INDICATED ON PLAN
DISTRIBUTION PANEL - 277/480V
LIGHTING OR POWER PANEL
LIGHTING
'A'
2 x 4 LIGHT FIXTURE
AS INDICATED
TRACK LIGHT
LIGHTING (NOTE: UPPER CASE LETTER INDICATES FIXTURE TYPE)
EXIT SIGN, WALL MOUNTED, ARROWS INDICATE DIRECTION OF EXIT
EXIT SIGN, CEILING MOUNTED, ARROWS INDICATE DIRECTION OF EXIT
EMERGENCY LIGHTING UNIT, BATTERY TYPE WITH NUMBER OF HEADS
LIGHTNING ARRESTER
CAPACITOR
THERMAL ELEMENT
FUSE
SWITCH
CIRCUIT BREAKER
FLOW SWITCH
TAMPER SWITCH
SMOKE DETECTOR - CEILING MOUNTED
FIRE ALARM - HORN
FIRE ALARM - PULL STATION
FIRE ALARM - CONTROL PANEL
SMOKE DETECTOR - WALL MOUNTED
FIRE ALARM - VISUAL LIGHT - WALL MOUNTED
GROUND
FS
EOL
F
F
F
HEAT DETECTOR - CEILING MOUNTED
FIRE ALARM SPEAKER
FIREMANS PHONE JACK
END OF LINE DEVICE
M
C CONTROL MODULE
MONITOR MODULE
T T
SMOKE DETECTOR - MOUNT ON AC DUCT
FIRE ALARM COMBINATION SPEAKER AND AV LIGHT
FIRE ALARM COMBINATION HORN AND AUDIO VISUAL LIGHT
TRANSFORMER - ISOLATED GROUND-SHIELDED(ISX)
CONTACTS - NORMALLY CLOSED
CONTACTS - NORMALLY OPEN
CIRCUIT BREAKER - DRAWOUT TYPE
TRANSFORMER - NORMAL- VOLTAGE AS INDICATED
SPEAKER - CEILING MOUNTED
MAGNETIC CONTACT SWITCH
SIGNAL - BUZZER OR CHIME
SPEAKER - WALL MOUNTED
PASSIVE INFARED DETECTOR
MAGNETIC LOCK
FIRE ALARM - REMOTE ANNUNCIATOR
DOOR HOLDER
ELECTRIC MOTOR
1. THE ELECTRICAL CONTRACTOR SHALL SUPPLY AND INSTALL ALL FIRE ALARM DEVICES INCLUDING
BUT NOT LIMITED TO:
A. PULL STATIONS - ADDRESSABLE TYPE
B. SMOKE DETECTORS - ADDRESSABLE TYPE
C. STROBE LIGHTS - (WALL MOUNTED) ADA TYPE - 80" A.F.F.
D. SPEAKERS - SET TO 15Db ABOVE AMBIENT SOUND.
E. WIRING FROM ALL DEVICES TO THE FACP
F. WIRING FROM THE FACP TO THE REMOTE ANNUNCIATOR
G. WIRING FROM THE FACP TO FLOW AND TAMPER SWITCHES INCLUDING ADDRESSABLE
MODULES.
2. ELECTRICAL CONTRACTOR SHALL INCLUDE ALL FIRE ALARM MANUFACTURER'S TECHNICIAN TIME IN
BASE PRICE.
3. ELECTRICAL CONTRACTOR SHALL INCLUDE FEES FOR ALL TESTING INCLUDING LOCAL FIRE
DEPARTMENT SMOKE TEST IN BASE PRICE.
4. ELECTRICAL CONTRACTOR SHALL INCLUDE ALL DEMOLITION AND REWIRING AS NECESSARY TO
MAINTAIN THE INTEGRITY OF THE FIRE ALARM SYSTEM DURING CONSTRUCTION.
5.
6.
7.
ELECTRICAL CONTRACTOR SHALL UTILIZE THE EXISTING ADDRESSABLE FACP AND INSTALL A NEW 3/C #16 SHIELDED LOW IMPEDANCE CABLE FROM THE ADDRESSABLE FACP TO ALL DEVICES (EXTEND THE
EXISTING ADDRESSABLE LOOP).
8.
ELECTRICAL CONTRACTOR SHALL SUPPLY AND INSTALL NEW STROBE LIGHT POWER SUPPLY AND
SPEAKER AMPLIFIERS AS REQUIRED INCLUDING ALL WIRING, CONTROL MODULES, HARDWARE AND
SOFTWARE.
9.
ELECTRICAL CONTRACTOR SHALL INCLUDE IN BASE PRICE ALL SOFTWARE PROGRAMMING AND FINAL
PROGRAM LOADED INTO THE EXISTING FIRE ALARM SYSTEM FOR A COMPLETE OPERATIONAL
SYSTEM.
ALL FIRE ALARM WORK SHALL COMPLY WITH THE LOCAL BUILDING CODE, NFPA 72, AND THE
NATIONAL ELECTRICAL CODE.
THE CONTRACTOR SHALL SUPPLY AND INSTALL ALL WIRING AND DEVICES TO PROVIDE A COMPLETE, OPERATING, AND APPROVED SYSTEM.
1. ALL MOUNTING HEIGHTS LIST ARE TO CENTER OF DEVICE UNLESS
OTHERWISE NOTED AND MUST CONFORM TO ADA, NFPA, ANSI 117.1
REQUIREMENTS UNLESS OTHERWISE NOTED.
2. CONTRACTOR TO VERIFY FINAL LOCATION OF ALL DEVICES WITH
ARCHITECT AND/OR INTERIOR DESIGNER.
3. WHERE DEVICES FALL ON TWO SURFACE FINISHES, RAISE THE
DEVICE TO BE ON A SINGLE FINISH. COORDINATE WITH ARCHITECT.
FIRE ALARM GONG AND BELL
(WALL MOUNTED)
FIRE ALARM STROBE LIGHT & SIGNALING
DEVICES
TOP OF LIGHTING AND/OR POWER PANELS
IN COMMON BUILDING SPACES TOP OF
TELEPHONE CABINET(MAXIMUM)
TOP OF LIGHTING AND/OR POWER PANELS
IN LIVING UNITS
TOP OF BACK MOUNTED EXIT FIXTURE
(NOT LOCATED ABOVE DOORS)
TOP OF SAFETY DISCONNECT SWITCH,
CONTACTORS, MAGNETIC MOTOR STARTERS
TELEPHONE (TOP OF COIN SLOT)
TELEPHONE OUTLET (WALL), LIGHT
SWITCHES
MANUAL CONTROL DEVICES,
FIRE ALARM PULL STATION, FIRE PHONE
JACKS
RECEPTACLES, TELEPHONE OUTLETS (DESK)
TELEVISION OUTLETS COMPUTER OUTLETS
FINISHED FLOOR ELEV. (BASE)
6' - 2" AFF
4' - 6" AFF TO HIGHEST OPERABLE DEVICE
12" BELOW FINISHED CEILING TO CENTERLINE
6' - 0" MAXIMUM AFF
6" BELOW FINISHED CEILING
4' - 0" AFF OR 6" ABOVE COUNTER
BELOW COUNTER
1' - 6" (MIN.) AFF
0' - 0"
6'-8" MAX. HT. OR 6" BELOW CLG. WHICHEVER
IS LOWER
ENTIRE LENS IS NOT LESS THAN 80" AND
NOT GREATER 96" AFF. WHERE LOW
CEILINGS DO NOT PERMIT MOUNTING AT
MIN. 80", DEVICE SHALL BE MOUNTED
WITHIN 6" OF THE CEILING.
(WALL MOUNTED)
X
EXXX
DETAIL CALL OUT
DOUBLE DUPLEX RECEPTACLE - ISOLATED GROUND
DUPLEX RECEPTACLE CEILING MOUNTED
DUPLEX RECEPTACLE - SWITCHED
DUPLEX RECEPTACLE FLOOR MOUNTED
SINGLE RECEPTACLE FLOOR MOUNTED
DUPLEX RECEPTACLE - ISOLATED GROUND
DUPLEX RECEPTACLE
DOUBLE DUPLEX RECEPTACLE
SINGLE RECEPTACLE
SPECIAL PURPOSE RECEPTACLE - SEE PLAN FOR RATING
DUPLEX RECEPTACLE - GROUND FAULT INTERRUPTER
AT LIGHT
REFERENCE
SWITCH
INDICATES
LETTER
LOWER CASE
ON PLAN
SIZE AND
FIXTURE
No. OF
POLES
INDICATED
ON PLANS
S
S4a
3a
Sa
DaS
ST
SM(P)
DISCONNECT SWITCH - FUSED
DISCONNECT SWITCH - NONFUSED
SWITCH - SINGLE POLE TOGGLE
SWITCH - THREE WAY TOGGLE
SWITCH - FOUR WAY TOGGLE
SWITCH - TIMER
SWITCH - DIMMER
B
(P)
C
DOUBLE COMPUTER OUTLET FLUSH MOUNTED
TELEPHONE OUTLET FLUSH MOUNTED
MAGNETIC CONTACTOR OR MOTOR STARTER
DISCONNECT SWITCH
BREAKER, F = FUSED SWITCH, NF = NONFUSED
MANUAL MOTOR STARTER (1HP AND ABOVE)
("P" INDICATES PILOT LIGHT)
T
PUSH-BUTTON STATION SINGLE
TELEVISION OUTLET (CATV, MATV, SATV) AS INDICATED
MOTOR STARTER - COMBINATION TYPE C/B WITH CIRCUIT
FRACTIONAL HORSEPOWER MANUAL MOTOR STARTER WITH
OVERLOADS FOR MOTOR ("P" INDICATES PILOT LIGHT)
ENCLOSED CIRCUIT BREAKER TYPE DISCONNECT SWITCH
DOUBLE DATA/COMMUNICATIONS OUTLET
W=WALL PHONE
P=PAY PHONE
H=HOUSE PHONE
DOUBLE DUPLEX RECEPTACLE - GROUND FAULT INTERRUPTER
POWER
AMPERE(S)A
AMP FRAME
ALUMINUM
AMP TRIP
AFG
AF
AFF
AL
ATS
AT
CONDUIT
AWG
BOC
BFC
C
CB
CATV
AMERICAN WIRE GUAGE
BOTTOM OF CONDUIT
BELOW FINISHED CEILING
CIRCUIT BREAKER
CABLE TELEVISION
ABOVE FINISHED GRADE
AUTOMATIC TRANSFER SWITCH
ABOVE FINISHED FLOOR
CEILING
CIRCUIT
CCTV
CC
CLG
CO
CKT
COPPER
CT
CP
CU
DE
DC
CLOSED CIRCUIT TELEVISION
CONDUIT ONLY
CURRENT TRANSFORMER
CONTROL PANEL
DUAL ELEMENT
DIRECT CURRENT
CONTROL CABINET
DT
DS
E.HTR
EF
EC
FUSED
EM
EOL
EMT
EUH
EWC
F
ELECTRIC UNIT HEATER
ELECTRIC WATER COOLER
ELECTRIC HEATER
EMERGENCY LIGHTING
END OF LINE RESISTOR
ELECTRICAL METALLIC TUBING
ELECTRICAL CONTRACTOR
EXHAUST FAN
DOUBLE THROW
DISCONNECT SWITCH
FIRE ALARM
FLOOR
FEEDER
FA
FACP
FL
GC
FDR
GROUNDGND
GFI
HPS
HP
HID
GENERAL CONTRACTOR
FIRE ALARM CONTROL PANEL
HIGH PRESSURE SODIUM
HIGH INTENSITY DISCHARGE
HORSEPOWER
GROUND FAULT INTERRUPT
DP DOUBLE POLE
ALTERNATING CURRENTAC
INTERCOM
HT
HZ
HW
IMC
IG
I
KILOVAR(S)
JB
INC
KCMIL
KVA
KVAR
THOUSAND CIRCULAR MIL(S)
ELECTRIC HEAT TRACE
HEAVYWALL RIGID CONDUIT
JUNCTION BOX
KILOVOLT AMPERE(S)
INTERMEDIATE METALLIC CONDUIT
INCANDESCENT
ISOLATED GROUND
LP
LPS
MC
MCC
MATV
MANHOLE
MOUNTED
MH
MCM
MAGSTR
MIC
MTD
MICROPHONE
LIGHTING PANEL
LOW PRESSURE SODIUM
MECHANICAL CONTRACTOR
MASTER ANTENNA TELEVISION
MAGNETIC STARTER
THOUSAND CIRCULAR MIL(S)
MOTOR CONTROL CENTER
KILOWATT(S)KW
MOTOR
NONFUSED
NIGHT LIGHT
MTR
MUH
NF
NL
NIC
NC
OL
NO
NTS
PC
PF
PE
OVERLOAD ELEMENT
PLUMBING CONTRACTOR
POWER FACTOR
PHOTO ELECTRIC CELL
NORMALLY OPEN
NOT TO SCALE
NORMALLY CLOSED
NOT IN CONTRACT
MAKE-UP AIR UNIT
PRIMARY
RELAY
PRI
PP
R
PTZ
PS
RECEPTACLE
SECONDARY
RCP
RECPT
SP
SEC
SATV
RC
PULL SWITCH
POWER PANEL
SATELLITE ANTENNA TELEVISION
SINGLE POLE
REMOTE CONTROL
REFLECTED CEILING PLAN
PAN/TILT/ZOOM CAMERA
PL PILOT LIGHT
MOUNTINGMTG
HERTZ(FREQ. IN CYCLES PER SECOND)
SWITCH
SPEAKER
TELEPHONE
TIME CLOCK
SW
ST
SPKR
T
TC
SWBD
TIME DELAY
TDC
TD
TDO
TV
TYP
TIME DELAYED CLOSED
SWITCHBOARD
SHUNT TRIP
TIME DELAYED OPEN
VOLTS
UG
UON
UH
VAR
VA
V
WATTS
WP
W
XP
XFMR
VP
UNDER GROUND
UNIT HEATER
UNLESS OTHERWISE NOTED
VOLT AMPS REACTIVE
VOLT AMPERE(S)
WEATHERPROOF
VAPOR PROOF
EXPLOSION PROOF
TRANSFORMER
UNDERFLOOR DUCTUFD
TYPICAL
TELEVISION
GENERIC ELECTRICAL ABBREVIATIONS
POWER (CONTINUED)
FIRE ALARM SINGLE LINE SYMBOLS
AUDIO/VIDEO
SECURITY GENERALMOUNTING HEIGHTS
3' - 6" AFF
3' - 6" AFF
LIFE SAFETY SCOPE OF WORK
LEGEND NOTES
THIS SHEET IS A GENERAL LIST OF SYMBOLS AND ABBREVIATIONS AND SHALL BE
USED AS A DICTIONARY TO DEFINE ITEMS INDICATED ON DRAWINGS. NOT ALL
SYMBOLS OR ABBREVIATIONS ARE NECESSARILY USED ON THIS PROJECT.
OS WALL MOUNTED DUAL TECHNOLOGY OCCUPANCY SENSOR
OS CEILING MOUNTED DUAL TECHNOLOGY OCCUPANCY SENSOR
F
WALL MOUNTED
FIRE ALARM COMBINATION HORN AND AUDIO VISUAL LIGHT
CEILING MOUNTED
'A'
2 x 2 LIGHT FIXTURE
RECESSED DOWNLIGHT FIXTURE
RECESSED WALLWASHER LIGHT FIXTURE
1 x 4 STRIP LIGHT FIXTURE 'A'
'A'
'A'
PENDANT LIGHT FIXTURE
WALL SCONCE LIGHT FIXTURE
'A'
'A'
'A'
LOW VOLTAGE ROPE LIGHT
'A'
UNDERCABINET LIGHT FIXTURE
'A'
'A'
'A'
'A'
FIRE ALARM - VISUAL LIGHT - CEILING MOUNTED
S
S
S
H
T
F
F
RANN
FACP
S
S
FIRE ALARM - SPEAKER STROBE - CEILING MOUNTEDSP
COMBINATION FIRE/SMOKE DAMPER
FB FLOORBOX
PT POKE-THRU
VS
WALL MOUNTED DUAL TECHNOLOGY VACANCY SENSOR
VS CEILING MOUNTED DUAL TECHNOLOGY VACANCY SENSOR
TWO WAY COMMUNICATION DEVICE2W
J SYSTEM FURNITURE FEED
FF
J POWER POLE
PP
'A'
'A'
SURFACE MOUNTED - ROUND FIXTURE
FL
FL
SOS
DUAL TECHNOLOGY WALL SWITCH OCCUPANCY SENSOR
SVS
DUAL TECHNOLOGY WALL SWITCH VACANCY SENSOR
SLV SWITCH - LOW VOLTAGE
(TO BE USED IN CONJUNCTION WITH LOW VOLTAGE SWITCH)
(TO BE USED IN CONJUNCTION WITH LOW VOLTAGE SWITCH)
V
AV VIDEO CAMERA
SECURITY CAMERA
ECB ENCLOSED CIRCUIT BREAKER
CEILING MOUNTED CORD REELC
NORR
One Penn Center 1617 JFK Blvd, Suite 1600 Philadelphia, PA 19103 norr.com
ARCH E Title Block - v.2023 - Rev (Sept/23) - Copyright © 2023
Drawing No.
Project No.
Drawing Title
Project
Seal
Design Team
Project Manager
Project Architect Checked
Drawn
Client
Architecture:
Structural:
Mechanical:
Electrical:
A
BD C
This drawing shall not be used for construction purposes until the seal appearing hereon is signed and dated by the Architect or Engineer
E
NORR
NORR
NORR
NORR
Au to de sk
D oc s:
//D el C o
- V ot in g M ac hi ne W ar eh ou se
E le va to r A dd iti on
/IN
-0
3_
EL
i_
D el co _W ar eh ou se
El ev at or
Ad di tio n_ v2 4.
rv t
6/
/2
:2 4:
A
M
IN2325-0323
E01-01
DRAWING LIST &
LEGENDS
VOTING MACHINE
WAREHOUSE ELEVATOR
ADDITION
COUNTY OF DELAWARE
DEPARTMENT OF PUBLIC
WORKS
403 EAST 24TH STREET, CHESTER, PA 19013
BM
MGOP
JV
This drawing has been prepared solely for the use of
COUNTY OF DELAWARE DEPARTMENT OF PUBLIC
WORKS and there are no representations of any kind made by NORR to any party with whom NORR has not entered into a contract.
DRAWING LIST - ELECTRICAL
E01-01 DRAWING LIST & LEGENDS
E01-02 ELECTRICAL DETAILS & SCHEDULES
ED10-01 OVERALL POWER & LIGHTING DEMOLITION PLAN - FIRST FLOOR
ED10-02 OVERALL POWER & LIGHTING DEMOLITION PLAN - SECOND FLOOR
E10-01 OVERALL POWER & LIGHTING PLAN - FIRST FLOOR
E10-02 OVERALL POWER & LIGHTING PLAN - SECOND FLOOR
DATE ISSUED FOR REV
2026.03.04 BIDDING A
2026.04.28 PLAN REVIEW B
2026.06.18 REISSUED FOR BID C
FE-4
B B
A A
4.5
4.5
(E) MDP
(E) PP1
M
(E) METER & CT CABINET
(E) SECURITY/TELECOM
PHASE I & II
M (E) UTILITY METER
(E) PAD MOUNTED UTILITY TRANSFORMER
(E) CT CABINET
(E) PANEL
PP-1
225A MLO
208/120V, 3P, 4W
42 POLE
225A 125A 125A 50A 100A 100A 30A
600A
(E) OVERHEAD DOOR (E) ELECTRIC HOIST
(E) PANEL
VM-2
125A MCB
208/120V, 3P, 4W
42 POLE
(E) PANEL
VM-1
125A MCB
208/120V, 3P, 4W
42 POLE
(E) PANEL
LP-2
225A MLO
208/120V, 3P, 4W
36 POLE
(E) PANEL
LP-1
225A MLO
208/120V, 3P, 4W
36 POLE
(E) 'MDP' MAIN DISTRIBUTION PANEL
600A, 208/120V, 3PH, 4W
(N) ELEVATOR
(3) #6 & (1) #10G IN 1"C 60AS
60AF
3P
FEEDER
AMPACITY
NO. OF
SETS
COPPER CONDUCTORS (THWN)
PHASE &
NEUTRAL
GROUND &
IG
3 PHASE CONDUCTORS
AND GROUND
TAG CONDUIT
3 PHASE CONDUCTORS,
NEUTRAL AND GROUND
TAG CONDUIT
FEEDER CONDUCTOR SIZE
(75 DEG C)
CONDUIT SIZE (EMT)
FEEDER SCHEDULE
20 1 12 12 20 3/4" 20N 3/4"
30 1 10 10 30 3/4" 30N 3/4"
50 1 8 10 50 3/4" 50N 3/4"
65 1 6 8 65 3/4" 65N 1"
85 1 4 8 85 1" 85N 1 1/4"
100 1 3 8 100 1 1/4" 100N 1 1/4"
115 1 2 6 115 1 1/4" 115N 1 1/2"
130 1 1 6 130 1 1/4" 130N 1 1/2"
150 1 1/0 6 150 1 1/2" 150N 1 1/2"
175 1 2/0 6 175 1 1/2" 175N 2"
200 1 3/0 6 200 2" 200N 2"
230 1 4/0 4 230 2" 230N 2 1/2"
255 1 250 KCMIL 2 255 2" 255N 2 1/2"
310 1 350 KCMIL 3 310 2 1/2" 310N 3"
380 1 500 KCMIL 3 380 3" 380N 3 1/2"
420 1 600 KCMIL 1/0 420 3 1/2" 420N 4"
460 2 4/0 2 460 2" 460N 2 1/2"
500 2 250 KCMIL 1 500 2 1/2" 500N 3"
620 2 350 KCMIL 1/0 620 2 1/2" 620N 3"
760 2 500 KCMIL 1/0 760 3 1/2" 760N 3 1/2"
855 3 300 KCMIL 2/0 855 2 1/2" 855N 2 1/2"
1000 3 400 KCMIL 3/0 1000 3" 1000N 3"
1340 4 400 KCMIL 4/0 1340 3" 1340N 3"
1675 4 600 KCMIL 250 KCMIL 1675 3" 1675N 3"
2010 6 400 KCMIL 350 KCMIL 2010 3" 2010N 3"
2520 6 600 KCMIL 400 KCMIL 2520 3" 2520N 3 1/2"
400 1 600 KCMIL 3 400 3 1/2" 400N 4"
NO. OF
SETS
ALUMINUM CONDUCTORS (THWN)
PHASE &
NEUTRAL
GROUND &
IG
3 PHASE CONDUCTORS
AND GROUND
TAG CONDUIT
3 PHASE CONDUCTORS,
NEUTRAL AND GROUND
TAG CONDUIT
FEEDER CONDUCTOR SIZE
(75 DEG C)
CONDUIT SIZE (EMT)
1 1/0 4 115AL 1 1/2" 115ALN 1 1/2"
1 2/0 4 130AL 1 1/2" 130ALN 2"
1 3/0 4 150AL 2" 150ALN 2"
1 4/0 4 175AL 2" 175ALN 2 1/2"
1 250 KCMIL 4 200AL 2" 200ALN 2 1/2"
1 350 KCMIL 2 230AL 2 1/2" 230ALN 3"
1 500 KCMIL 2 310AL 3" 310ALN 3 1/2"
1 600 KCMIL 1/0 420 3 1/2" 420N 4"
2 350 KCMIL 1/0 500AL 2 1/2" 500ALN 3"
2 620ALN
2 750 KCMIL 3/0 760AL 4" 760ALN 4"
3 600 KCMIL 4/0 1000AL 3 1/2" 1000ALN 4"
5 600 KCMIL 350 KCMIL 1675AL 3 1/2" 1675ALN 4"
6 600 KCMIL 400 KCMIL 2010AL 3 1/2" 2010ALN 4"
7 750 KCMIL 600 KCMIL 2520AL 4" 2520ALN 4"
2 250 KCMIL 1/0 400AL 2 1/2" 400N 3"
410 2 250 KCMIL 1 410AL 2" 410N 2 1/2"
810 3 400 KCMIL 3/0 810AL 2 1/2" 810ALN 3"
1240 4 500 KCMIL 250 KCMIL 1240AL 3" 1240ALN 3 1/2"
NORR
One Penn Center 1617 JFK Blvd, Suite 1600 Philadelphia, PA 19103 norr.com
ARCH E Title Block - v.2023 - Rev (Sept/23) - Copyright © 2023
Drawing No.
Project No.
Drawing Title
Project
Seal
Design Team
Project Manager
Project Architect Checked
Drawn
Client
Architecture:
Structural:
Mechanical:
Electrical:
A
BD C
This drawing shall not be used for construction purposes until the seal appearing hereon is signed and dated by the Architect or Engineer
E
NORR
NORR
NORR
NORR
Au to de sk
D oc s:
//D el C o
- V ot in g M ac hi ne W ar eh ou se
E le va to r A dd iti on
/IN
-0
3_
EL
i_
D el co _W ar eh ou se
El ev at or
Ad di tio n_ v2 4.
rv t
6/
/2
:2 5:
A
M
IN2325-0323
E01-02
ELECTRICAL DETAILS &
SCHEDULES
VOTING MACHINE
WAREHOUSE ELEVATOR
ADDITION
COUNTY OF DELAWARE
DEPARTMENT OF PUBLIC
WORKS
403 EAST 24TH STREET, CHESTER, PA 19013
BM
MGOP
JV
This drawing has been prepared solely for the use of
COUNTY OF DELAWARE DEPARTMENT OF PUBLIC
WORKS and there are no representations of any kind made by NORR to any party with whom NORR has not entered into a contract.
SCALE: 3/16" = 1'-0"E01-02
PARTIAL BASEMENT MAIN ELECTRICAL ROOM1
SCALE: N.T.S.E01-02
One Line Diagram2
NOTES:
TOTAL EST. DEMAND: 67 A
TOTAL CONN.: 67 A
Spare 5040 VA 100.00% 5040 VA TOTAL EST. DEMAND: 24295 VA Receptacle 720 VA 100.00% 720 VA TOTAL CONN. LOAD: 24295 VA Power 18535 VA 100.00% 18535 VA
LOAD CLASSIFICATION CONNECTED LOAD DEMAND FACTOR ESTIMATED DEMAND PANEL TOTALS
A - ARC FAULT BREAKER, E - EXISTING BREAKER, EL - EXISTING LOAD AND BREAKER, G - GROUND FAULT BREAKER, L - LOCKED-ON BREAKER, S - SHUNT TRIP BREAKER
LEGEND (LG):
AMPS: 74 A 62 A 69 A
LOAD: 8725 VA 7405 VA 8165 VA
41 SPACE -- 1 -- -- 1 -- SPACE 42
39 200 -- 1 -- SPACE 40
37 TF-1 - ELEVATOR CLOSET 20 A 2 200 180 1 20 A ELEVATOR GENERAL RECEPT. 38
35 SHUNT TRIP -- 1 -- 180 1 20 A ELEVATOR GENERAL RECEPT. 36
33 5045 360 1 20 A ELEVATOR TELECOM QUAD RECEPT. 34
31 5045 1500 1 20 A ELEVATOR MISC. POWER 32
ELEVATOR 60 A 3
5045 1500 1 20 A ELEVATOR CAB LIGHTS 30
27 (E) RECEPT VIA CONT 2A 15 A 1 180 180 1 15 A (E) CONTACTORS FEED 28
25 (E) RECEPT VIA CONT 2D 15 A 1 180 180 1 15 A (E) RECEPT VIA CONT 2D 26
23 (E) RECEPT VIA CONT 2D 15 A 1 180 180 1 15 A (E) RECEPT VIA CONT 2D 24
21 (E) RECEPT VIA CONT 2D 15 A 1 180 180 1 15 A (E) RECEPT VIA CONT 2D 22
19 (E) RECEPT VIA CONT 2D 15 A 1 180 180 1 15 A (E) RECEPT VIA CONT 2D 20
17 (E) RECEPT VIA CONT 2C 15 A 1 180 180 1 15 A (E) RECEPT VIA CONT 2C 18
15 (E) RECEPT VIA CONT 2C 15 A 1 180 180 1 15 A (E) RECEPT VIA CONT 2C 16
13 (E) RECEPT VIA CONT 2C 15 A 1 180 180 1 15 A (E) RECEPT VIA CONT 2C 14
11 (E) RECEPT VIA CONT 2C 15 A 1 180 180 1 15 A (E) RECEPT VIA CONT 2C 12
9 (E) RECEPT VIA CONT 2B 15 A 1 180 180 1 15 A (E) RECEPT VIA CONT 2B 10
7 (E) RECEPT VIA CONT 2B 15 A 1 180 180 1 15 A (E) RECEPT VIA CONT 2B 8
5 (E) RECEPT VIA CONT 2B 15 A 1 180 180 1 15 A (E) RECEPT VIA CONT 2A 6
3 (E) RECEPT VIA CONT 2A 15 A 1 180 180 1 15 A (E) RECEPT VIA CONT 2B 4
1 SPARE 15 A 1 180 180 1 15 A (E) RECEPT VIA CONT 2B 2
CKT LG CIRCUIT DESCRIPTION TRIP POLE A (VA) B (VA) C (VA) POLE TRIP CIRCUIT DESCRIPTION LG CKT
EXISTING PANEL
NOTES:
ENCLOSURE: Type 1 MCB RATING: 125 A
MOUNTING: SURFACE WIRES: 4 BUS RATING: 125 A
SUPPLY FROM: MDP PHASES: 3 MAINS TYPE: MCB
LOCATION: VOTING MACHINES STORAG... VOLTS: 120/208 Wye A.I.C. RATING:
BRANCH PANEL:VM2
NOTES:
TOTAL EST. DEMAND: 40 A
Spare 12780 VA 100.00% 12780 VA TOTAL CONN.: 40 A Receptacle 180 VA 100.00% 180 VA TOTAL EST. DEMAND: 14300 VA Power 1260 VA 100.00% 1260 VA TOTAL CONN. LOAD: 14300 VA Other 80 VA 100.00% 80 VA
LOAD CLASSIFICATION CONNECTED LOAD DEMAND FACTOR ESTIMATED DEMAND PANEL TOTALS
A - ARC FAULT BREAKER, E - EXISTING BREAKER, EL - EXISTING LOAD AND BREAKER, G - GROUND FAULT BREAKER, L - LOCKED-ON BREAKER, S - SHUNT TRIP BREAKER
LEGEND (LG):
AMPS: 38 A 46 A 36 A
LOAD: 4500 VA 5540 VA 4260 VA
41 SPACE -- 1 -- -- 1 -- SPACE 42
39 SPACE -- 1 -- -- 1 -- SPACE 40
37 SPACE -- 1 -- -- 1 -- SPACE 38
35 SPACE -- 1 -- -- 1 -- SPACE 36
33 SPACE -- 1 -- -- 1 -- SPACE 34
31 SPACE -- 1 -- -- 1 -- SPACE 32
29 SPACE -- 1 -- -- 1 -- SPACE 30
27 SP-1 - ELEVATOR PIT 20 A 1 1260 20 1 20 A EM LIGHTS (LEVEL 1&2) 28
25 ELEVATOR PIT LIGHT. 20 A 1 60 3000 26
23 ELEVATOR PIT GFCI RECEPT. 20 A 1 180 3000 24
21 (E) RECEPT VIA CONT 1A 15 A 1 180 3000
3 30 A (E) FORK LIFT BATTERY CHARGER
19 CONTACTORS FEED 15 A 1 180 180 1 15 A (E) RECEPT VIA CONT 1A 20
17 (E) RECEPT VIA CONT 1A 15 A 1 180 180 1 15 A (E) RECEPT VIA CONT 1A 18
15 (E) RECEPT VIA CONT 1C 15 A 1 180 180 1 15 A (E) RECEPT VIA CONT 1A 16
13 (E) RECEPT VIA CONT 1A 15 A 1 180 180 1 15 A (E) RECEPT VIA CONT 1E 14
11 (E) RECEPT VIA CONT 1E 15 A 1 180 180 1 15 A (E) RECEPT VIA CONT 1E 12
9 (E) RECEPT VIA CONT 1C 15 A 1 180 180 1 15 A (E) RECEPT VIA CONT 1C 10
7 (E) RECEPT VIA CONT 1D 15 A 1 180 180 1 15 A (E) RECEPT VIA CONT 1D 8
5 (E) RECEPT VIA CONT 1B 15 A 1 180 180 1 15 A (E) RECEPT VIA CONT 1B 6
3 (E) RECEPT VIA CONT 1D 15 A 1 180 180 1 15 A (E) RECEPT VIA CONT 1D 4
1 (E) RECEPT VIA CONT 1B 15 A 1 180 180 1 15 A (E) RECEPT VIA CONT 1B 2
CKT LG CIRCUIT DESCRIPTION TRIP POLE A (VA) B (VA) C (VA) POLE TRIP CIRCUIT DESCRIPTION LG CKT
EXISTING PANEL
NOTES:
ENCLOSURE: Type 1 MCB RATING: 125 A
MOUNTING: SURFACE WIRES: 4 BUS RATING: 125 A
SUPPLY FROM: PHASES: 3 MAINS TYPE: MCB
LOCATION: EXISTING STAIRS (N.I.C.) 110 VOLTS: 120/208 Wye A.I.C. RATING:
BRANCH PANEL:VM-1
LIGHT FIXTURE SCHEDULE
FIXTURE
TYPE DESCRIPTION MANUFACTURER MODEL NO. REMARKS
A ELM4L EMERGENCY LIGHT LITHONIA LIGHTING (OR SIMILAR) ELM4L
B 24" WET LOCATION RATED VAPOR TIGHT LUMINAIRE LITHONIA LIGHTING (OR SIMILAR) DMW2-L24-3000LM-ACL-WD-MVOLT-GZ10-35K-80CRI-E10WCP
EX EXISTING TO REMAIN - - -
DATE ISSUED FOR REV
2026.03.04 BIDDING A
C C C C C
D D
C C
B B
A A
2.5
2.5
3.5
3.5
4.5
4.5
C.7 C.7
C
C
C
C
C
C
(R)
(ETR)
(ETR)
(ETR)
(ETR)
(ETR)
(R)
(R)
D1
D2
D3
D5
EX EX EX EX EX EX EX EX EX
EX EX EX EX EX
EX EX EX EX EX EX EX EX EX
EX EX EX EX EX EX EX EX EX
EX EX EX EX EX EX EX EX EX
D4 D4 D4 D4
(E) LP1
(E) VM-1
(E) LIGHTING
CONTACTORS (TYP.)
(E) FACP
PHASE I
PHASE II
A. COORDINATE ALL WORK CONCERNING EXISTING EQUIPMENT AND
SERVICES TO REMAIN DE-ENERGIZE CIRCUITS AND MAKE THEM SAFE AS
REQUIRED. RECONNECT CIRCUITS THAT ARE TO REMAIN AND ARE DISRUPTED
DURING DEMOLITION.
B. REMOVE EXPOSED OR ACCESSIBLE WIRING, TO EQUIPMENT OR OUTLETS
TO BE REMOVED, UNLESS OTHERWISE INDICATED. LABEL AND TERMINATE
WIRING TO REMAIN.
C. WHERE EXISTING OUTLETS ARE TO REMAIN AND ARE CUT OFF BY THE
REMODELING THEY SHALL RE-CONNECTED TO CIRCUITS AS REQUIRED BY JOB
CONDITIONS.
D. LEGALLY DISPOSE OF EQUIPMENT WHERE EXISTING EQUIPMENT IS
INDICATED TO BE REMOVED. OFFER EQUIPMENT TO OWNER AND DISPOSE OF
EQUIPMENT THE OWNER DOES NOT WISH TO RETAIN. PROVIDE
DOCUMENTATION INDICATING LEGAL DISPOSAL OR RECYCLING OF MATERIALS
REMOVED. RECYCLE FLUORESCENT AND HID LAMPS, PROVIDE
DOCUMENTATION.
E. WIRING INDICATED TO BE REMOVED OR SERVING EQUIPMENT TO BE
REMOVED SHALL BE REMOVED BACK TO THE SOURCE OR TO THE NEXT
JUCNTION POINT IF THE WIRING SERVES OTHER OUTLETS THAT WILL REMAIN.
CONDUIT OVER UNDISTURBED CEILINGS SHALL REMAIN AND BE LABELED
ABANDONED ON EACH END WITH END POINTS INDICATED.
F. RECONNECT EXISTING CIRCUITRY WHICH ORIGINATES OR PASSES
THROUGH THE RENOVATED AREAS BUT SERVES OTHER AREAS NOT BEING
RENOVATED. EXTEND THESE CIRCUITS AS MAY BE NECESSARY TO THE
EXISTING PANELBOARDS.
G. COORDINATE WORK CONCERNING EXISTING EQUIPMENT AND SERVICES IN
THE BUILDING. COORDINATE REQUIRED POWER INTERRUPTIONS AND
PERFORM AT TIME CONVENIENT TO OWNER. INCLUDE COSTS FOR REQUIRED
PREMIUM TIME.
H. VERIFY THE INTEGRITY AND CONDITION OF THE EXISTING BRANCH CIRCUIT
WIRING THAT IS TO BE RE-USED. REPLACE WIRING FOUND TO BE NON-
FUNCTIONAL.
GENERAL DEMOLITION NOTES
NORR
One Penn Center 1617 JFK Blvd, Suite 1600 Philadelphia, PA 19103 norr.com
ARCH E Title Block - v.2023 - Rev (Sept/23) - Copyright © 2023
KEY PLAN
Drawing No.
Project No.
Drawing Title
Project
Seal
Design Team
Project Manager
Project Architect Checked
Drawn
Client
Architecture:
Structural:
Mechanical:
Electrical:
A
BD C
This drawing shall not be used for construction purposes until the seal appearing hereon is signed and dated by the Architect or Engineer
E
NORR
NORR
NORR
NORR
Au to de sk
D oc s:
//D el C o
- V ot in g M ac hi ne W ar eh ou se
E le va to r A dd iti on
/IN
-0
3_
EL
i_
D el co _W ar eh ou se
El ev at or
Ad di tio n_ v2 4.
rv t
6/
/2
:2 5:
A
M
IN2325-0323
ED10-01
OVERALL POWER &
LIGHTING DEMOLITION
PLAN - FIRST FLOOR
VOTING MACHINE
WAREHOUSE ELEVATOR
ADDITION
COUNTY OF DELAWARE
DEPARTMENT OF PUBLIC
WORKS
403 EAST 24TH STREET, CHESTER, PA 19013
BM
MGOP
JV
This drawing has been prepared solely for the use of
COUNTY OF DELAWARE DEPARTMENT OF PUBLIC
WORKS and there are no representations of any kind made by NORR to any party with whom NORR has not entered into a contract.
SCALE: 3/16" = 1'-0"ED10-01
OVERALL POWER & LIGHTING DEMOLITION PLAN - FIRST
FLOOR1
DEMOLITION KEYNOTES
D1 REMOVE AND DISCONNECT POWER FOR CORD REEL AT THE AREA
INDICATED. EXISTING CIRCUIT FOR CORD REELS TO REMAIN.
D2 REMOVE AND DISCONNECT POWER TO EXISTING MECHANICAL LIFT. REMOVE
ASSOCIATED WIRING BACK TO SOURCE AND MARK AS SPARE.
D3 REMOVE AND DISCONNECT CONTROLLER FOR MECHANICAL LIFT AND
ASSOCIATED WIRING BACK TO SOURCE.
D4 REMOVE AND DISCONNECT LIGHT FIXTURES INDICATED IN THE AREA.
EXISTING CIRCUIT TO LIGHT FIXTURES IN THE AREA OF WORK TO REMAIN.
D5 REROUTE EXISTING CONDUITS, FIRE ALARM CABLES, SECURITY CABLES, AND
TELECOMMUNICATION CABLES TO ACCOMMODATE FOR NEW ELEVATOR.
D6 EXISTING LIGHT FIXTURE TO BE RELOCATED PER NEW WORK PLAN. MAINTAIN
ELECTRICAL CIRCUIT TO EQUIPMENT TO REMAIN.
DATE ISSUED FOR REV
2026.03.04 BIDDING A
D D
C C
B B
A A
2.5
2.5
3.5
3.5
4.5
4.5
C.7 C.7
D5
EX EX EX EX EX EX
EX EX EX EX EX EXEXEXEX
EX EX EX EX EX EXEXEXEX
EX EX EX EX EX EXEXEXEX
(ER)D4 D4
(E) LP2 (E) VM2
PHASE I
PHASE II
PHASE I & II
D6
A. COORDINATE ALL WORK CONCERNING EXISTING EQUIPMENT AND
SERVICES TO REMAIN DE-ENERGIZE CIRCUITS AND MAKE THEM SAFE AS
REQUIRED. RECONNECT CIRCUITS THAT ARE TO REMAIN AND ARE DISRUPTED
DURING DEMOLITION.
B. REMOVE EXPOSED OR ACCESSIBLE WIRING, TO EQUIPMENT OR OUTLETS
TO BE REMOVED, UNLESS OTHERWISE INDICATED. LABEL AND TERMINATE
WIRING TO REMAIN.
C. WHERE EXISTING OUTLETS ARE TO REMAIN AND ARE CUT OFF BY THE
REMODELING THEY SHALL RE-CONNECTED TO CIRCUITS AS REQUIRED BY JOB
CONDITIONS.
D. LEGALLY DISPOSE OF EQUIPMENT WHERE EXISTING EQUIPMENT IS
INDICATED TO BE REMOVED. OFFER EQUIPMENT TO OWNER AND DISPOSE OF
EQUIPMENT THE OWNER DOES NOT WISH TO RETAIN. PROVIDE
DOCUMENTATION INDICATING LEGAL DISPOSAL OR RECYCLING OF MATERIALS
REMOVED. RECYCLE FLUORESCENT AND HID LAMPS, PROVIDE
DOCUMENTATION.
E. WIRING INDICATED TO BE REMOVED OR SERVING EQUIPMENT TO BE
REMOVED SHALL BE REMOVED BACK TO THE SOURCE OR TO THE NEXT
JUCNTION POINT IF THE WIRING SERVES OTHER OUTLETS THAT WILL REMAIN.
CONDUIT OVER UNDISTURBED CEILINGS SHALL REMAIN AND BE LABELED
ABANDONED ON EACH END WITH END POINTS INDICATED.
F. RECONNECT EXISTING CIRCUITRY WHICH ORIGINATES OR PASSES
THROUGH THE RENOVATED AREAS BUT SERVES OTHER AREAS NOT BEING
RENOVATED. EXTEND THESE CIRCUITS AS MAY BE NECESSARY TO THE
EXISTING PANELBOARDS.
G. COORDINATE WORK CONCERNING EXISTING EQUIPMENT AND SERVICES IN
THE BUILDING. COORDINATE REQUIRED POWER INTERRUPTIONS AND
PERFORM AT TIME CONVENIENT TO OWNER. INCLUDE COSTS FOR REQUIRED
PREMIUM TIME.
H. VERIFY THE INTEGRITY AND CONDITION OF THE EXISTING BRANCH CIRCUIT
WIRING THAT IS TO BE RE-USED. REPLACE WIRING FOUND TO BE NON-
FUNCTIONAL.
GENERAL DEMOLITION NOTES
NORR
One Penn Center 1617 JFK Blvd, Suite 1600 Philadelphia, PA 19103 norr.com
ARCH E Title Block - v.2023 - Rev (Sept/23) - Copyright © 2023
KEY PLAN
Drawing No.
Project No.
Drawing Title
Project
Seal
Design Team
Project Manager
Project Architect Checked
Drawn
Client
Architecture:
Structural:
Mechanical:
Electrical:
A
BD C
This drawing shall not be used for construction purposes until the seal appearing hereon is signed and dated by the Architect or Engineer
E
NORR
NORR
NORR
NORR
Au to de sk
D oc s:
//D el C o
- V ot in g M ac hi ne W ar eh ou se
E le va to r A dd iti on
/IN
-0
3_
EL
i_
D el co _W ar eh ou se
El ev at or
Ad di tio n_ v2 4.
rv t
6/
/2
:2 5:
A
M
IN2325-0323
ED10-02
OVERALL POWER &
LIGHTING DEMOLITION
PLAN - SECOND FLOOR
VOTING MACHINE
WAREHOUSE ELEVATOR
ADDITION
COUNTY OF DELAWARE
DEPARTMENT OF PUBLIC
WORKS
403 EAST 24TH STREET, CHESTER, PA 19013
BM
MGOP
JV
This drawing has been prepared solely for the use of
COUNTY OF DELAWARE DEPARTMENT OF PUBLIC
WORKS and there are no representations of any kind made by NORR to any party with whom NORR has not entered into a contract.
SCALE: 3/16" = 1'-0"ED10-02
OVERALL POWER & LIGHTING DEMOLITION PLAN - SECOND
FLOOR1
DEMOLITION KEYNOTES
D1 REMOVE AND DISCONNECT POWER FOR CORD REEL AT THE AREA
INDICATED. EXISTING CIRCUIT FOR CORD REELS TO REMAIN.
D2 REMOVE AND DISCONNECT POWER TO EXISTING MECHANICAL LIFT. REMOVE
ASSOCIATED WIRING BACK TO SOURCE AND MARK AS SPARE.
D3 REMOVE AND DISCONNECT CONTROLLER FOR MECHANICAL LIFT AND
ASSOCIATED WIRING BACK TO SOURCE.
D4 REMOVE AND DISCONNECT LIGHT FIXTURES INDICATED IN THE AREA.
EXISTING CIRCUIT TO LIGHT FIXTURES IN THE AREA OF WORK TO REMAIN.
D5 REROUTE EXISTING CONDUITS, FIRE ALARM CABLES, SECURITY CABLES, AND
TELECOMMUNICATION CABLES TO ACCOMMODATE FOR NEW ELEVATOR.
D6 EXISTING LIGHT FIXTURE TO BE RELOCATED PER NEW WORK PLAN. MAINTAIN
ELECTRICAL CIRCUIT TO EQUIPMENT TO REMAIN.
DATE ISSUED FOR REV
2026.03.04 BIDDING A
C C C C C
S
S
D D
C C
B B
A A
2.5
2.5
3.5
3.5
4.5
4.5
C.7 C.7
(E) FACP
(E) LP1
(E) VM-1
(E) LIGHTING
CONTACTORS (TYP.)
SP-1(N)
(N)
(E)
(E)
(E)
(E)
(E)
B(N)
(N)
EX EX EX EX
EXEX EXEXEXEXEXEXEX
EX EX EX EX EX EXEX EX EX
EXEXEXEXEXEXEXEXEX
EX
PHASE I
PHASE I
PHASE I
VM-1 - 23
VM-1 - 25
VM-1 - 27
(N)
(N)
P5
A(N)
VM-1 - 28
A. FOR ELECTRICAL SYMBOLS, ABBREVIATIONS, REFER TO DRAWING E0.1.
B. CONTRACTOR SHALL PROVIDE COMPLETE AND ACCURATE CIRCUIT
DIRECTORIES FOR ALL NEW AND EXISTING PANELS AFTER NEW WORK IS
COMPLETED.
C. CONTRACTOR SHALL COORDINATE ALL TELE/DATA REQUIREMENTS WITH
OWNER'S TELE/DATA VENDOR.
D. PROVIDE A JUNCTION BOX AND PULL STRING FROM EACH CARD
READER/ELECTRIC DOOR STRIKE TO SECURITY EQUIPMENT RACK IN IDF
ROOM. PROVIDE FIRE ALARM CONTACT AT SECURITY EQUIPMENT RACK FOR
CARD READERS/ELECTRIC DOOR TO RELEASE UPON GENERAL ALARM OF
FIRE ALARM SYSTEM.
E. FIRE ALARM SHALL BE OPERATIONAL AND MAINTAINED DURING ALL
ASPECTS OF DEMOLITION AND NEW CONSTRUCTION.
F. MAINTAIN THE CONTINUITY OF ALL EXISTING TO REMAIN OUTSIDE THE
SCOPE OF WORK AREA.
G. ALL ELECTRICAL OUTLETS AND JUNCTION BOXES SHALL BE STAGGERED
WITHIN THE WALL TO AVOID SOUND TRANSMISSION.
H. ALL NEW FIRE ALARM DEVICES TO BE CONNECTED TO EXISTING FIRE
ALARM SYSTEM. PROVIDE NEW WIRING AND CONDUIT TO ALL NEW FIRE
ALARM DEVICES. NEW DEVICES SHALL MATCH EXISTING SYSTEM DEVICES.
PROVIDE NEW BATTERIES, STROBE SYNC MODULES, HARDWARE, SOFTWARE,
ETC AT THE FIRE ALARM CONTROL PANEL NECESSARY TO SUPPORT NEW
FIRE ALARM DEVICES.
I. ALL RECEPTACLES SHALL BE LABELED INDICATING CIRCUIT NUMBER AND
PANEL NAME.
GENERAL POWER NOTES
A. FOR ELECTRICAL SYMBOLS, ABBREVIATIONS, REFER TO DRAWING E0.1.
B. FOR LIGHTING FIXTURE DESCRIPTIONS, REFER TO LIGHTING FIXTURE
SCHEDULE ON DRAWING E601.
C. FOR ACTUAL LOCATION OF CEILING MOUNTED LIGHTING FIXTURES,
REFER TO ARCHITECTURAL REFLECTED CEILING DRAWING(S). FOR ACTUAL
LOCATION OF WALL MOUNTED LIGHTING FIXTURES AND TASK LIGHTING,
REFER TO ARCHITECTURAL ELEVATIONS AND DETAILS.
D. CONNECT EXIT SIGNS, EMERGENCY BATTERY UNITS AND EMERGENCY
BATTERY BALLAST UNITS TO THE UNSWITCHED SIDE OF LOCAL EMERGENCY
LIGHTING CIRCUIT OR CIRCUIT INDICATED, TO MONITOR AC CIRCUIT AND
FOR CONTINUOUS BATTERY CHARGING.
E. ALL LIGHTING FIXTURES WITHIN A SPACE SHALL BE CONTROLLED BY
INDICATED SWITCH AND/OR SENSOR WITHIN THAT SPACE.
F. THE TOTAL CONNECTED LOAD SHALL NOT EXCEED 1600 WATTS FOR A
20A, 120V CIRCUIT OR 3600W FOR A 20A, 277V CIRCUIT.
GENERAL LIGHTING NOTES
NORR
One Penn Center 1617 JFK Blvd, Suite 1600 Philadelphia, PA 19103 norr.com
ARCH E Title Block - v.2023 - Rev (Sept/23) - Copyright © 2023
KEY PLAN
Drawing No.
Project No.
Drawing Title
Project
Seal
Design Team
Project Manager
Project Architect Checked
Drawn
Client
Architecture:
Structural:
Mechanical:
Electrical:
A
BD C
This drawing shall not be used for construction purposes until the seal appearing hereon is signed and dated by the Architect or Engineer
E
NORR
NORR
NORR
NORR
Au to de sk
D oc s:
//D el C o
- V ot in g M ac hi ne W ar eh ou se
E le va to r A dd iti on
/IN
-0
3_
EL
i_
D el co _W ar eh ou se
El ev at or
Ad di tio n_ v2 4.
rv t
6/
/2
:2 5:
A
M
IN2325-0323
E10-01
OVERALL POWER &
LIGHTING PLAN - FIRST
FLOOR
VOTING MACHINE
WAREHOUSE ELEVATOR
ADDITION
COUNTY OF DELAWARE
DEPARTMENT OF PUBLIC
WORKS
403 EAST 24TH STREET, CHESTER, PA 19013
BM
MGOP
JV
This drawing has been prepared solely for the use of
COUNTY OF DELAWARE DEPARTMENT OF PUBLIC
WORKS and there are no representations of any kind made by NORR to any party with whom NORR has not entered into a contract.
SCALE: 3/16" = 1'-0"E10-01
OVERALL POWER & LIGHTING PLAN - FIRST FLOOR1
ELECTRICAL KEYNOTES
P1 PROVIDE 60AF/60AS/3P DISCONNECT SWITCH WITH RK1 FUSES FOR POWER
TO ELEVATOR. REFER TO SINGLE LINE DIAGRAM ON SHEET E01-02 FOR
POWER AND CONDUIT SIZING TO ELEVATOR.
P2 PROVIDE (1) 20A/1P DISCONNECT SWITCH FOR ELEVATOR CAB LIGHTS.
P3 PROVIDE (1) 20A/1P DISCONNECT SWITCH FOR MISC. POWER FOR ELEVATOR.
P4 DEDICATED QUADRUPLEX RECEPTACLE FOR TELECOM.
P5 PROVIDE CONTACTS TO NEW ELEVATOR. RECALL ELEVATOR TO OWNER
DESIGNATED LEVEL WHERE FIRE ALARM IS IN ALARM. RECERTIFY FIRE
ALARM CONTROL PANEL ONCE WORK IS COMPLETE. FIRE ALARM
MANUFACTURER IS NOTIFIER SFP-1 OUD.
P6 RELOCATED EXISTING LIGHT FIXTURE. EXTEND CONDUIT AND WIRING AS
REQUIRED TO NEW LOCATION.
DATE ISSUED FOR REV
2026.03.04 BIDDING A
FE-4
H
S
S
D D
C C
B B
A A
2.5
2.5
3.5
3.5
4.5
4.5
C.7 C.7
(E) LP2 (E) VM2
EX EX EX EX EX EX
EX EX EX EX EX EXEXEXEX
EX EX EX EX EX EXEXEXEX
EX EX EX EX EX EXEXEXEX
PHASE I
PHASE I
SIM2
E10-02
A. FOR ELECTRICAL SYMBOLS, ABBREVIATIONS, REFER TO DRAWING E0.1.
B. CONTRACTOR SHALL PROVIDE COMPLETE AND ACCURATE CIRCUIT
DIRECTORIES FOR ALL NEW AND EXISTING PANELS AFTER NEW WORK IS
COMPLETED.
C. CONTRACTOR SHALL COORDINATE ALL TELE/DATA REQUIREMENTS WITH
OWNER'S TELE/DATA VENDOR.
D. PROVIDE A JUNCTION BOX AND PULL STRING FROM EACH CARD
READER/ELECTRIC DOOR STRIKE TO SECURITY EQUIPMENT RACK IN IDF
ROOM. PROVIDE FIRE ALARM CONTACT AT SECURITY EQUIPMENT RACK FOR
CARD READERS/ELECTRIC DOOR TO RELEASE UPON GENERAL ALARM OF
FIRE ALARM SYSTEM.
E. FIRE ALARM SHALL BE OPERATIONAL AND MAINTAINED DURING ALL
ASPECTS OF DEMOLITION AND NEW CONSTRUCTION.
F. MAINTAIN THE CONTINUITY OF ALL EXISTING TO REMAIN OUTSIDE THE
SCOPE OF WORK AREA.
G. ALL ELECTRICAL OUTLETS AND JUNCTION BOXES SHALL BE STAGGERED
WITHIN THE WALL TO AVOID SOUND TRANSMISSION.
H. ALL NEW FIRE ALARM DEVICES TO BE CONNECTED TO EXISTING FIRE
ALARM SYSTEM. PROVIDE NEW WIRING AND CONDUIT TO ALL NEW FIRE
ALARM DEVICES. NEW DEVICES SHALL MATCH EXISTING SYSTEM DEVICES.
PROVIDE NEW BATTERIES, STROBE SYNC MODULES, HARDWARE, SOFTWARE,
ETC AT THE FIRE ALARM CONTROL PANEL NECESSARY TO SUPPORT NEW
FIRE ALARM DEVICES.
I. ALL RECEPTACLES SHALL BE LABELED INDICATING CIRCUIT NUMBER AND
PANEL NAME.
GENERAL POWER NOTES
A. FOR ELECTRICAL SYMBOLS, ABBREVIATIONS, REFER TO DRAWING E0.1.
B. FOR LIGHTING FIXTURE DESCRIPTIONS, REFER TO LIGHTING FIXTURE
SCHEDULE ON DRAWING E601.
C. FOR ACTUAL LOCATION OF CEILING MOUNTED LIGHTING FIXTURES,
REFER TO ARCHITECTURAL REFLECTED CEILING DRAWING(S). FOR ACTUAL
LOCATION OF WALL MOUNTED LIGHTING FIXTURES AND TASK LIGHTING,
REFER TO ARCHITECTURAL ELEVATIONS AND DETAILS.
D. CONNECT EXIT SIGNS, EMERGENCY BATTERY UNITS AND EMERGENCY
BATTERY BALLAST UNITS TO THE UNSWITCHED SIDE OF LOCAL EMERGENCY
LIGHTING CIRCUIT OR CIRCUIT INDICATED, TO MONITOR AC CIRCUIT AND
FOR CONTINUOUS BATTERY CHARGING.
E. ALL LIGHTING FIXTURES WITHIN A SPACE SHALL BE CONTROLLED BY
INDICATED SWITCH AND/OR SENSOR WITHIN THAT SPACE.
F. THE TOTAL CONNECTED LOAD SHALL NOT EXCEED 1600 WATTS FOR A
20A, 120V CIRCUIT OR 3600W FOR A 20A, 277V CIRCUIT.
GENERAL LIGHTING NOTES
B B
P1 P2
P3 P4
(RE)
VM2 - 38 VM2 - 34
VM2 - 36
VM2 - 29,31,33 VM2 - 30
VM2 - 32
TF-1
VM2 - 37,39
P6
VM-1 - 28
A
VM-1 - 28
A
NORR
One Penn Center 1617 JFK Blvd, Suite 1600 Philadelphia, PA 19103 norr.com
ARCH E Title Block - v.2023 - Rev (Sept/23) - Copyright © 2023
KEY PLAN
Drawing No.
Project No.
Drawing Title
Project
Seal
Design Team
Project Manager
Project Architect Checked
Drawn
Client
Architecture:
Structural:
Mechanical:
Electrical:
A
BD C
This drawing shall not be used for construction purposes until the seal appearing hereon is signed and dated by the Architect or Engineer
E
NORR
NORR
NORR
NORR
Au to de sk
D oc s:
//D el C o
- V ot in g M ac hi ne W ar eh ou se
E le va to r A dd iti on
/IN
-0
3_
EL
i_
D el co _W ar eh ou se
El ev at or
Ad di tio n_ v2 4.
rv t
6/
/2
:2 5:
A
M
IN2325-0323
E10-02
OVERALL POWER &
LIGHTING PLAN - SECOND
FLOOR
VOTING MACHINE
WAREHOUSE ELEVATOR
ADDITION
COUNTY OF DELAWARE
DEPARTMENT OF PUBLIC
WORKS
403 EAST 24TH STREET, CHESTER, PA 19013
BM
MGOP
JV
This drawing has been prepared solely for the use of
COUNTY OF DELAWARE DEPARTMENT OF PUBLIC
WORKS and there are no representations of any kind made by NORR to any party with whom NORR has not entered into a contract.
SCALE: 3/16" = 1'-0"E10-02
OVERALL POWER & LIGHTING PLAN - SECOND FLOOR1
ELECTRICAL KEYNOTES
P1 PROVIDE 60AF/60AS/3P DISCONNECT SWITCH WITH RK1 FUSES FOR POWER
TO ELEVATOR. REFER TO SINGLE LINE DIAGRAM ON SHEET E01-02 FOR
POWER AND CONDUIT SIZING TO ELEVATOR.
P2 PROVIDE (1) 20A/1P DISCONNECT SWITCH FOR ELEVATOR CAB LIGHTS.
P3 PROVIDE (1) 20A/1P DISCONNECT SWITCH FOR MISC. POWER FOR ELEVATOR.
P4 DEDICATED QUADRUPLEX RECEPTACLE FOR TELECOM.
P5 PROVIDE CONTACTS TO NEW ELEVATOR. RECALL ELEVATOR TO OWNER
DESIGNATED LEVEL WHERE FIRE ALARM IS IN ALARM. RECERTIFY FIRE
ALARM CONTROL PANEL ONCE WORK IS COMPLETE. FIRE ALARM
MANUFACTURER IS NOTIFIER SFP-1 OUD.
P6 RELOCATED EXISTING LIGHT FIXTURE. EXTEND CONDUIT AND WIRING AS
REQUIRED TO NEW LOCATION.
SCALE: 3/8" = 1'-0"E10-02
ENLARGED ELEVATOR CLOSET2
DATE ISSUED FOR REV
2026.03.04 BIDDING A
| E01-01 - DRAWING LIST & LEGENDS |
| E01-02 - ELECTRICAL DETAILS & SCHEDULES |
| ED10-01 - OVERALL POWER & LIGHTING DEMOLITION PLAN - FIRST FLOOR |
| ED10-02 - OVERALL POWER & LIGHTING DEMOLITION PLAN - SECOND FLOOR |
| E10-01 - OVERALL POWER & LIGHTING PLAN - FIRST FLOOR |
| E10-02 - OVERALL POWER & LIGHTING PLAN - SECOND FLOOR |
File details come from the government source that posted it. Updated .