3-2-CR27000-27284500 Approved Plans.pdf

PDF 3 MB Posted

Attached to
DFCM Construction - Invitational - Department of Natural Resources- Trust Lands Office Remodel- Project #27284500
Solicitation number
CR27000
Issued by
Utah

About this file

This is an approved design and construction plan document prepared by the State of Utah's Division of Facilities Construction and Management (DFCM) for the DNR Trust Lands Office Remodel project (#27284500) located at 2031 Industrial Park Road, Richfield, Utah. The project involves the remodeling of existing office space to convert two offices into three offices within an 8,200 square foot building with an 18-foot ceiling height. The work includes demolition of existing walls, creation of new office spaces (Offices 122, 125, and 146), installation of new windows and doors to match existing specifications, interior wall finishes with paint and rubber base, carpet tile flooring, ceiling work including new sheetrock and grille relocation, and electrical upgrades. The approved plans were reviewed for code compliance on June 24, 2026, by Jason Van Ausdal and include detailed architectural schedules, floor plans, demolition plans, electrical plans, and specifications for wall types, door hardware, window glazing, and MEP (mechanical, electrical, plumbing) connections.

The construction cost estimate for this invitational project is $94,000.00, with an occupancy classification of Group B and construction type 5B in accordance with 2021 International Building Code and related standards. The project is an invitational bid opportunity restricted to three pre-selected contractors: PRT Builders, Rod Lewis Construction, and Tushar Contracting. The design incorporates specific material requirements including new 1-3/4-inch thick rotary-cut flush oak veneer doors with field-applied stain and varnish finishes, wrap-around hollow metal frames, Schlage brand locksets matching existing hardware, windows with Solarband 70 glazing, and matching existing knockdown ceiling and wall textures. The plans include specifications for wall bracing at four-foot on-center spacing, floor leveling for carpet installation, RFID card reader relocation as necessary, and sound and thermal insulation requirements. Prior to occupancy certification, the contractor must provide code inspection reports, special inspection certifications from structural and mechanical engineers, fire clearance from the State Fire Marshal, elevator and boiler inspector approvals, potable water system disinfection reports, and related final approval documentation.

View the file

Other files

File Type Posted
1-1-CR27000-27284500 Solicitation.pdf PDF
2-3-CR2700-27284500 Hazmat Survey.pdf PDF

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

IND

USTRY

TH

E

G R E A T

SE

AL

OF THE

STATE

O F

U

TA

H

State of Utah-Department of Administrative Services

DIVISION OF FACILITIES CONSTRUCTION

AND MANAGEMENT

4315 South 2700 West, Floor 3/Taylorsville, Utah 84129-2128

1535 SOUTH 100 WEST

RICHFIELD, UT 84701

(435).896.8266

46 NORTH 200 EAST

ST GEORGE, UT 84770

(435).628.5969

SHEET NO. |PROJECT NO. |

ARCHITECT & CONSULTANTS

SHEET INDEXCODE REVIEW & DESIGN CRITERIA

PLUMBING FIXTURE COUNT

DEFERRED SUBMITTALS

CODE REQUIREMENT ACTUAL BUILDING DESIGNCODE ITEM -

REFERENCE

Is su e D at e:

SYMBOLS

ROOM NUMBER

DOOR NUMBER

EXTERIOR ELEVATION

WALL SECTION

BUILDING SECTION

WALL TAG

DETAIL NUMBER

TYPE

INSULATION

HEIGHT OFtda

FIRE RATING

WALLWALL1si

SHEET NUMBER

DETAIL

SHEET NUMBER

SHEET NUMBER

DETAIL NUMBER

SECTION NUMBER

000 WINDOW NUMBER

KEYNOTE0000 VIEW NUMBER

SHEET NUMBER

0' - 0" C-0

CEILING TYPE

CEILING HEIGHT

CEILING TAG

0 GRIDLINE

LEVEL ELEVATION

SPOT ELEVATION

VICINITY MAP

SPECIAL INSPECTIONS AND DEFERRED SUBMITTALS

DEFERRED SUBMITTALS

SPECIAL INSPECTIONS

THE FOLLOWING DOCUMENTS ARE REQUIRED BEFORE A

CERTIFICATE OF OCCUPANCY IS ISSUED

CODE INSPECTION REPORT FOR CERTIFICATE OF OCCUPANCY

FINAL REPORT ON ALL SPECIAL INSPECTIONS

CERTIFICATE OF FIRE CLEARANCE FOR THE STATE FIRE MARSHALL

FINAL APPROVAL FORM THE STATE ELEVATOR INSPECTOR

FINAL APPROVAL FORM THE STATE BOILER INSPECTOR

REPORT OF THE DISINFECTION OF POTABLE WATER SYSTEMS

CERTIFICATE FOR THE APPROVED FABRICATOR

STAMPED SIGNED OBSERVATION REPORT FOR THE STRUCTURAL ENGINEER

FINAL REPORT FOR THE SPECIAL INSPECTOR, MECHANICAL ENGINEER WHEN

SMOKE

CONTROL IS REQUIRED

APPLICABLE CODES

CODE ANALYSIS

ADA Accessibility Guidelines

Uniform Code for Building Conservation

National Electrical Code

International Energy Conservation Code

International Fire Code

International Plumbing Code

International Mechanical Code

International Building Code

Year

Special Use and Occupancy (e.g. High Rise, Covered Mall): __________________

Design Wind Speed: ______ mphB. Seismic Design Category: ______

Change in Use: Yes ______ No ______ Mixed Occupancy: Yes ______ No ______

A. Occupancy and Group: ________ ________ ________ ________ ________

North: ______ South: ______ East: ______ West: ______

BAHTBABABA

Tabular Area: ____________________________________________I.

Actual Area per Floor (square feet): __________________________H.

Number of Stories: ______ Building Height: ______G.

Required: ______ Provided: ______ Type of Sprinkler System: ____________ Sprinklers:F.

Mixed Occupancies: ______ Nonseparated Uses: ______E.

Fire Resistance Rating Requirements for the Exterior Walls based on the fire separation distance (in hours):

D.

C. Type of Construction (circle one):

INTERIOR ELEVATION

VIEW NUMBER

SHEET NUMBER

6/ 2/

1:

:0

AM

2602-109 G-001

DFCM

DNR TRUST LANDS OFFICE REMODEL

N/A

Occupancy - Chapter 3 B

Construction Type - Section 602 5B

DFCM Project No.27284500

2031 INDUSTRIAL PARK RD, RICHFIELD, UT 84701

SHEET # DESCRIPTION

1-GENERAL

G-001 TITLE SHEET

4-ARCHITECTURAL

A-100 DEMOLITION PLAN

A-101 FLOOR PLAN & ELECTRICAL PLAN

A-601 ARCHITECTURAL SCHEDULES

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A N/A

B

X X

N/A

N/AN/A

N/A N/A N/A N/A

NO NO

NO NO N/A

N/A

8,200 S.F. ±

18'±

DIVISION OF FACILITIES

CONSTRUCTION AND

MANAGEMENT

Jason Van Ausdal

06/24/2026

REVIEWED FOR CODE

COMPLIANCE

E E

D D

C C

F F

10 10

9 9

EXISTING

OFFICE 122

EXISTING

OFFICE 125

EXISTING

DEMOLISHED

NEW CONSTRUCTION

FUTURE

PHASES

1 2 3 4 5

A

B

C

D

1 2 3 4 5

A

SHEET NUMBER

SHEET TITLE

COPYRIGHT:

C

DFCM STAMP:

D CREATED BY:

DESCRIPTIONMARK DATE

B

PROJECT TITLE:

CHK'D BY:

ISSUE TYPE:

ISSUE DATE:

CAD DWG FILE:

DRAWN BY:

DFCM PROJECT NO:

CAD PROJECT NO:

Phone: (801) 538 - 3018 Salt Lake City, Utah 84114 4110 State Office Building

DFCM

dfcm.utah.gov

2024 JONES &DEMILLE

ENGINEERING

27284500

H

-1

\D e s ig n \D e s ig n P r o c e s s D o c u m e n t a t io n (D

P D

A r c h it e c t u r e \0

_R

E V

IT

\0

_R e v it

\2

-1

D N

R T r u s t L a n d s O f f ic e R e m o d e l .r v t

DNR TRUST

LANDS OFFICE

REMODEL

2602-109

Author

A-100

DEMOLITION

PLAN

Checker

1/4" = 1'-0"1 DEMOLITON PLAN - TRUST LANDS OFFICE

DEMOLITION SCHEDULE

MARK DESCRIPTION OF WORK

1 DEMO WALL, PATCH WALL FINISHES TO MATCH EXISTING.

3 DEMO DOOR. IN-FILL WALL AND MATCH FINISHES TO EXISTING.

4 CREATE OPENING FOR WINDOW. WINDOW TO MATCH EXISTING.

PATCH WALL FINISHES TO MATCH EXISTING.

5 CONTRACTOR TO REMOVE AND SALVAGE EXISTING FLOOR CARPET

TILE THAT IS IN CONFLICT WITH THE NEW CONSTRUCTION. PROVIDE

COVERINGS ON EXISTING FLOOR FOR PROTECTION DURING

CONSTRUCTION.

6 REMOVE SHEETROCK 1'-6"+/- ON BOTH SIDES OF EXISTING WALL

FOR A COMPLETE DEMO OF WALL THAT ATTACHES TO EXISTING

ROOF STRUCTURE.

7 EXISTING RFID CARD READER TO BE RELOCATED FROM NEW

WINDOW LOCATION IF NECESSARY.

8 REPLACE EXISTING DOOR WITH A NEW DOOR, SEE SCHEDULE.

9 REMOVE SHEETROCK 1'-6"+/- ON BOTH SIDES OF NEW WALL TO

ALLOW ATTACHEMENT OF NEW WALL TO EXISTING ROOF

STRUCTURE.

10 RELOCATE EXISTING HARDWARE AND DOOR 122 TO THIS LOCATION,

SEE DOOR SCHEDULE.

06/04/26

DIVISION OF FACILITIES

CONSTRUCTION AND

MANAGEMENT

Jason Van Ausdal

06/24/2026

1.

2.

3.

4.

5.

6.

7.

FURNITURE IS TO BE O.F.O.I.

NEW OFFICE INTERIOR WALL FINISH TO MATCH EXISTING. PAINT ALL

WALLS & CEILINGS OF 3 NEW OFFICES & EAST WALL OF HALL 124.

PROVIDE 4" RUBBER BASE IN ALL 3 NEW OFFICES & EAST WALL OF

HALL 124.

OWNER WILL PROVIDE SOME EXISTING MATCHING CARPET TILE

THAT CAN BE USED ALONG WITH THE SALVAGED CARPET TILE TO

COMPLETE FLOORING IN THE 3 NEW OFFICES.

BRACE TOP OF NEW WALLS TO EXISTING ROOF STRUCTURE ABOVE

@ 4' O.C. EACH WAY.

PROVIDE ANY FLOOR LEVELING NEEDED FOR CARPET.

MATCH EXISTING KNOCKDOWN CEILING & WALL FINISHES AND

TEXTURES. REMOVE ADJACENT TEXTURES SO THAT NEW TEXTURE

GOES FROM FLOOR-TO-CEILING AND WALL-TO-WALL.

GENERAL NOTES:

E E

D D

C C

F F

3' - 10 3/4" 20' - 10 11/16" 4' - 9 1/8" 7' - 0 5/16"

7'

9"

/2

/1

6"

11' - 8 3/16" ± 9' - 1 23/32" ± 10' - 6 9/32" ±

OFFICE

OFFICE

OFFICE

HALL

tc5 -si tc5 -si tc5 -si ttb10 if ti

REQ'D

1' - 6"

NEW WINDOW, MATCH EXISTING,

SEE DETAILS 3/A-601 & 4/A-601

146A122A 125A

DOOR MARK

WINDOW/STOREFRONT MARK

ROOM NUMBER MARK

101A

SIGN MARK

1.

NOTE:

SEE ARCHITECTURAL SCHEDULES SHEET(S) FOR

WALL TYPES, DOOR TYPES, WINDOWS TYPES, AND

GLAZING TYPES.

tda 1si

FLOOR PLAN LEGEND

WALL HEIGHT

td = TO DECK tc = TO CEILING tt = TO TRUSS BOTTOM if = IN-FILL

FIRE RATING

- = NOT RATED

# = NO. HOURS RATED

INSULATION

si = SOUND INSULATION ti = THERMAL INSULATION

WALL TYPE

WALL TAG LEGEND

ROOM NAME

WALL TYPE

AIR BARRIER

1/2" OSB SHEATHING

2X6 STUD @ 16" OC

5/8" TYPE "X" GYP. BD

BATT INSULATION, SEE SPECS

WALL TYPE

5/8" TYPE "X" GYP. BD

2X4 STUD @ 16" OC

5/8" TYPE "X" GYP. BD

1/2" RESILIENT CLIP

2" RIGID INSULATION

WALL TYPE LEGEND

1/2" OSB SHEATHING

MFG STONE WAINSCOT

3" E.I.F.S. ABOVE WAINSCOT

E E

D D

C C

F F

OFFICE

OFFICE

OFFICE

MATCH

9' - 11 3/8"

MATCH

9' - 11 3/8"

MATCH

9' - 11 3/8"

SS S

NEW SHEETROCK CEILING,

SEE DEMO PLAN

EXISTING GRILLE TO REMAIN IN PLACE EXISTING GRILLE TO REMAIN IN PLACE

EXISTING GRILLE TO REMAIN IN PLACE

NEW GRILLE TO MATCH EXISTING

NEW GRILLE TO MATCH EXISTING EXISTING GRILLE TO BE RELOCATED

LIGHT FIXTURE - SEE LIGHTING PLAN

RECESSED LIGHT FIXTURE - SEE LIGHT PLAN

CEILING MOUNTED DUAL TECHNOLOGY

OCC. SENSOR

CEILING MOUNTED POWER PACK

CEILING MOUNTED EXHAUST FAN

PP

CEILING MOUNTED SUPPLY AIR DIFFUSER

CEILING MOUNTED RETURN AIR GRILLE

EXIT LIGHT

CEILING TYPE

CEILING HEIGHT

CEILING IDENTIFICATION

REFLECTED CEILING PLAN

LEGEND

X-X 0'-0"

DATA/PHONE OUTLET

S SWITCH

DUPLEX OUTLET

1.

2.

CONNECT RELOCATED CEILING GRILLES AS WELL AS NEW CEILING

GRILLES TO EXISTING DUCTWORK. PATCH DUCTWORK WHERE

RELOCATED GRILLES WERE REMOVED.

INSTALL NEW OUTLET, DATA/PHONE, AND SWITCH BOXES AND

DEVICES TO MATCH EXISTING COLOR AND QUALITY.

GENERAL MEP NOTES:

EXISTING

DEMOLISHED

NEW CONSTRUCTION

FUTURE

PHASES

1 2 3 4 5

A

B

C

D

1 2 3 4 5

A

SHEET NUMBER

SHEET TITLE

COPYRIGHT:

C

DFCM STAMP:

D CREATED BY:

DESCRIPTIONMARK DATE

B

PROJECT TITLE:

CHK'D BY:

ISSUE TYPE:

ISSUE DATE:

CAD DWG FILE:

DRAWN BY:

DFCM PROJECT NO:

CAD PROJECT NO:

Phone: (801) 538 - 3018 Salt Lake City, Utah 84114 4110 State Office Building

DFCM

dfcm.utah.gov

2024 JONES &DEMILLE

ENGINEERING

27284500

H

-1

\D e s ig n \D e s ig n P r o c e s s D o c u m e n t a t io n (D

P D

A r c h it e c t u r e \0

_R

E V

IT

\0

_R e v it

\2

-1

D N

R T r u s t L a n d s O f f ic e R e m o d e l .r v t

DNR TRUST

LANDS OFFICE

REMODEL

2602-109

MM

A-101

FLOOR PLAN &

ELECTRICAL

PLAN

KC

1/4" = 1'-0"1 MAIN FLOOR PLAN - TRUST LANDS OFFICE

1/4" = 1'-0"2 ELECTRICAL PLAN - TRUST LANDS OFFICE

06/04/26

DIVISION OF FACILITIES

CONSTRUCTION AND

MANAGEMENT

Jason Van Ausdal

06/24/2026

NEW WINDOW

NEW PRE-FINISHED METAL

FLASHING

EXISTING CULTURED STONE

EXISTING SHEATHING

EXISTING WALL

EXISTING GYP BD

NEW 2x

NEW GYP BD

NEW SILL, MATCH EXISTING

NEW CAULK

EXISTING GYP BD

NEW GYP BD

NEW 2x

NEW (2) 2x8 HEADER

NEW POLYISO INSULATION

NEW WINDOW

EXISTING WALL

EXISTING SHEATHING

EXISTING EIFS

NEW PRE-FINISHED METAL

FLASHING

NEW CAULK

EXISTING

DEMOLISHED

NEW CONSTRUCTION

FUTURE

PHASES

SE

E

SC

H

ED

U

LE

SEE SCHEDULE

WOOD DOOR, SEE DOOR NOTES WRAP-AROUND HOLLOW MTL

FRAME, SEE DOOR NOTES

2'

6" 5'

5"

3' - 0"

NEW INSULATED GLAZING TO MATCH

EXISTING GLAZING, MIN CRITERIA IS

SOLARBAND 70

451T STOREFRONT COLORED TO

MATCH EXISTING FRAMES

1 2 3 4 5

A

B

C

D

1 2 3 4 5

A

SHEET NUMBER

SHEET TITLE

COPYRIGHT:

C

DFCM STAMP:

D CREATED BY:

DESCRIPTIONMARK DATE

B

PROJECT TITLE:

CHK'D BY:

ISSUE TYPE:

ISSUE DATE:

CAD DWG FILE:

DRAWN BY:

DFCM PROJECT NO:

CAD PROJECT NO:

Phone: (801) 538 - 3018 Salt Lake City, Utah 84114 4110 State Office Building

DFCM

dfcm.utah.gov

2024 JONES &DEMILLE

ENGINEERING

27284500

H

-1

\D e s ig n \D e s ig n P r o c e s s D o c u m e n t a t io n (D

P D

A r c h it e c t u r e \0

_R

E V

IT

\0

_R e v it

\2

-1

D N

R T r u s t L a n d s O f f ic e R e m o d e l .r v t

DNR TRUST

LANDS OFFICE

REMODEL

2602-109

Author

A-601

ARCHITECTURAL

SCHEDULES

Checker

DOOR SCHEDULE

MARK ROOM

NUMBER DOOR TYPE FRAME TYPE DOOR HARDWARE GROUP REMARKSWIDTH HEIGHT

122A 122 SEE NOTES SEE NOTES 3' - 0" 7' - 0" LOCKSET TO MATCH EXISITNG SALVAGE EXISTING DOOR 122 AND REUSE HERE 125A 125 SEE NOTES SEE NOTES 3' - 0" 7' - 0" LOCKSET TO MATCH EXISITNG LOCATION OF EXISTING DOOR 122, SWITCH DOOR SWING

146A 146 SEE NOTES SEE NOTES 3' - 0" 7' - 0" LOCKSET TO MATCH EXISITNG

1.

2.

3.

PROVIDE WRAP-AROUND HOLLOW MTL FRAMES TO NEW OPENINGS.

NEW DOORS SHALL BE 1-3/4" THICK ROTARY-CUT FLUSH OAK VENEER

DOORS. NEW DOORS SHALL BE FIELD FINISHED W/ STAIN AND VARNISH

TO MATCH EXISTING DOORS.

NEW HARDWARE SHALL MATCH EXISTING. US26D FINISH, LEVER-STYLE

HANDLES, BUTTS, & SILENCERS. LOCKSETS FOR EACH DOOR SHALL

MATCH THE SCHLAGE BRAND AND DUTY THAT EXISTS.

DOOR & FRAME GENERAL NOTES

1 1/2" = 1'-0"3 SILL DETAIL

1 1/2" = 1'-0"4 HEAD/JAMB DETAIL

1/4" = 1'-0"1 DOOR TYPES

1/4" = 1'-0"2 FRAME TYPES

1/4" = 1'-0"5 WINDOW TYPES

06/04/26

DIVISION OF FACILITIES

CONSTRUCTION AND

MANAGEMENT

Jason Van Ausdal

06/24/2026

G-001 - TITLE SHEET
A-100 - DEMOLITION PLAN
A-101 - FLOOR PLAN & ELECTRICAL PLAN
A-601 - ARCHITECTURAL SCHEDULES

File details come from the government source that posted it. Updated .