26C6921023 Renovate Armory TC Drawings 3of4 FP M P.pdf

PDF 4 MB Posted

Attached to
511/22390. AGY; Traverse City Armory - Renovate Armory
Solicitation number
RFQ - 171 - 220000000489
Issued by
Grand Traverse County, Troy City, Michigan

About this file

This document contains the fire suppression and plumbing plans for the renovation of the Traverse City National Guard Armory in Traverse City, Michigan. The project is being managed by the Department of Military and Veterans Affairs, State of Michigan, Design and Construction Division.

The fire suppression plan indicates that a complete fire protection system is required, including reconnection to existing systems in areas of no work. The system is to be a wet pipe type with all required valves, backflow preventors, piping, pendent, sidewall, and upright heads. The design is to be based on FM Global and all federal, state, and local codes. The plumbing plan shows the layout of new sanitary sewer, cold water, hot water, and return hot water piping for the latrine and lactation room renovations. The contractor is responsible for flushing, testing, and chlorinating all new piping as required.

View the file

Other files

Show all 12

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

T

FIRE SUPPRESSION LACTATION ROOM AND

LATRINES REFERENCE PLAN

FIRST FLOOR

SCALE 1/2" = 1'-0"

REFLECTIVE CEILING PLAN IS SHOWN. COORDINATE WITH REFLECTIVE CEILING PLAN SHEET AS WELL AS THE MECHANICAL

EQUIPMENT AND LIGHTING FIXTURE LOCATIONS SPECIFIED.

FIRE PROTECTION GENERAL NOTES:

ROOMS TO BE ALTERED,

COORDINATE AND MODIFY

EXISTING FIRE SUPPRESSION

AND ALARM

LEGEND

EXISTING ROOMS TO BE

ALTERED, COORDINATE AND

MODIFY EXISTING FIRE

SUPPRESSION AND ALARM

NEW ROOMS TO BE ADDED,

COORDINATE AND MODIFY

EXISTING FIRE SUPPRESSION

AND ALARM WITH NEW

FIRE PROTECTION PLAN NOTES

1. LAY-IN CEILINGS: PROVIDE SPRINKLER SYSTEM WITH WHITE PENDENT HEADS AND TWO PIECE ESCUTCHEONS.

FIRE PROTECTION NOTES

1. PROVIDE A COMPLETE FIRE PROTECTION SYSTEM INCLUDING RECONNECTION TO EXISTING SYSTEMS IN AREAS OF NO WORK IN

THE ONE STORY FACILITY AS REQUIRED. SYSTEM SHALL BE A LIGHT, ORDINARY AND EXTRA HAZARD AS REQUIRED BY THE

DESIGN, SYSTEM IS TO BE WET PIPE TYPE WITH ALL REQUIRED VALVES, BACKFLOW PREVENTORS, PIPING, PENDENT, SIDEWALL, AND UPRIGHT HEADS. SYSTEM TO BE DESIGN TO PROVIDE FOR FUTURE RENOVATION OF AREAS OF NO WORK.

2. DESIGN SHALL BE BASED ON FM GLOBAL AND ALL FEDERAL, STATE, AND LOCAL CODES. DESIGN SHALL BE DONE BY A PERSON

REGISTER TO PERFORM SUCH SERVICES. PLANS AND CALCULATIONS SHALL BE SUBMITTED TO THE PROPER AUTHORITIES AND

SHALL BE APPROVED AND RETURNED BEFORE INSTALLATION IS BEGUN.

3. IT IS THE FIRE PROTECTION CONTRACTOR'S RESPONSIBILITY TO DESIGN THE SYSTEM REQUIRED FOR THIS FACILITY. THE

CONTRACTOR SHALL VERIFY THE CAPACITY OF THE EXISTING FIRE PUMP AND TANK CAPACITIES BY PERFORMING ALL TEST

REQUIRED TO DETERMINE WATER CAPACITY AND PRESSURE AVAILABLE AND DESIGN HIS SYSTEM USING THESE CAPACITIES.

4. ANY INFORMATION ON THESE DRAWING IS PURELY FOR REFERENCE ONLY. IT IS THE CONTRACTORS RESPONSIBILITY FOR

FINAL DESIGN OF THE SYSTEM TO BE INSTALLED.

5. HEAD TEMPERATURES SHALL BE 160° F. UNLESS OTHERWISE NOTED ON THE PLANS OR DEEMED TO BE OTHER BY THE DESIGN

ENGINEER.

6. THE FIRE SUPPRESSION CONTRACTOR SHALL PROVIDE THE REQUIRED DEVICES SUCH AS FLOW SWITCHES, PRESSURE

SWITCHES, AND TAMPER SWITCHES. THE DEVICES ARE TO BE INSTALLED BY THE FIRE SUPPRESSION CONTRACTOR. WIRING

AND CONNECTIONS TO THE BUILDING FIRE ALARM SYSTEM ARE TO BE PROVIDED BY THE ELECTRICAL CONTRACTOR OR THE

ALARM CONTRACTOR.

7. THE CONTRACTOR SHALL BE RESPONSIBLE FOR FLUSHING, TESTING AND CHLORINATING ANY

AND ALL PIPING AS REQUIRED FOR APPROVAL BY STATE AND LOCAL AUTHORITIES.

8. PROVIDE ANY ADDITIONAL EQUIPMENT AND MATERIALS AS NEEDED TO MEET THE NFPA

REQUIREMENTS.

9. PROVIDE ANY MISSING WHITE TRIM RINGS ON THE EXISTING SPRINKLERS.

FP100

A

D E

P A

R T

M E

N

O

F

M

I L

I T

A R

Y

A

D

V

E T

E R

A N

S

A

F F

A I R

S

S T

A T

E

O

F

M

I C

H I G

A N

D E

S I G

N

A

C

N

S T

R U

C T

I O

N

D

I V

I S

I O

N

C

F P

A U

G

A

R E

N O

V A

A

R M

O R

Y

T R

A V

E R

S

I

Y

T

I O

N A

L

G

U A

M

O

A

V E

R S

E

C

I T

Y

M

I C

H I G

A N

ROOM TO STAY THE SAME

REUSE EXISTING FIRE

SUPPRESSION AND ALARM

SYSTEM. REPLACE ANY

COMPONENTS THAT NEED

REPAIR

ROOM IS NEW ADD

ALL COMPONENTS

NEEDED FOR FIRE

SUPPRESSION AND

ALARM SYSTEM

EXISTING ROOMS TO STAY THE

SAME, COORDINATE AND

REPAIR EXISTING FIRE

SUPPRESSION AND ALARM

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

TUEBOR

AutoCAD SHX Text U

AutoCAD SHX Text S

AutoCAD SHX Text Q

AutoCAD SHX Text U

AutoCAD SHX Text E

AutoCAD SHX Text R

AutoCAD SHX Text C

AutoCAD SHX Text I

AutoCAD SHX Text U

AutoCAD SHX Text P

AutoCAD SHX Text I

AutoCAD SHX Text S

AutoCAD SHX Text R

AutoCAD SHX Text C

AutoCAD SHX Text S

AutoCAD SHX Text N

AutoCAD SHX Text I

AutoCAD SHX Text E

AutoCAD SHX Text N

AutoCAD SHX Text M

AutoCAD SHX Text I

AutoCAD SHX Text S

AutoCAD SHX Text

KAB

AutoCAD SHX Text E

AutoCAD SHX Text R

AutoCAD SHX Text U

AutoCAD SHX Text P

AutoCAD SHX Text L

AutoCAD SHX Text S

AutoCAD SHX Text B

AutoCAD SHX Text U

AutoCAD SHX Text I

AutoCAD SHX Text A

AutoCAD SHX Text N

AutoCAD SHX Text E

AutoCAD SHX Text O

AutoCAD SHX Text E

AutoCAD SHX Text I

AutoCAD SHX Text M

AutoCAD SHX Text L

AutoCAD SHX Text A

AutoCAD SHX Text P

AutoCAD SHX Text A

AutoCAD SHX Text M

AutoCAD SHX Text C

AutoCAD SHX Text M

AutoCAD SHX Text M

AutoCAD SHX Text U

AutoCAD SHX Text U

AutoCAD SHX Text N

AutoCAD SHX Text

PRELIMINARY

AutoCAD SHX Text

CONSTRUCTION

AutoCAD SHX Text

FINAL RECORD

AutoCAD SHX Text

DATE

AutoCAD SHX Text

ISSUED FOR

AutoCAD SHX Text

INDEX CODE

AutoCAD SHX Text

PROJECT

AutoCAD SHX Text

IDENTIFICATION NO.

AutoCAD SHX Text

SHEET

AutoCAD SHX Text

DESIGNED

AutoCAD SHX Text

DRAWN

AutoCAD SHX Text

CHECKED

AutoCAD SHX Text

APPROVED

AutoCAD SHX Text

DEPARTMENT OF TECHNOLOGY, MANAGEMENT AND BUDGET

AutoCAD SHX Text

FACILITIES AND BUSINESS SERVICES ADMINISTRATION

AutoCAD SHX Text

ADAM LACH, RA, DIRECTOR

AutoCAD SHX Text

KMM

AutoCAD SHX Text

KMM

AutoCAD SHX Text

KMM

AutoCAD SHX Text

KMM

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

3/4" CW

3/4" HW

2"

2"

2"

4"

4"

3"

2"

2"

3"

3"

3/4" CW

3/4" HW

2 1/2" CW

1" HW

3/4" HWR

2" CW

3/4" HW

2" CW

T

3/4" CW

3/4" HW

2"

2"

2"

4"

4"

3"

2"

2"

3"

3"

3/4" CW

3/4" HW

2 1/2" CW

1" HW

3/4" HWR

2" CW

3/4" HW

2" CW

C.J.

C.J. C.J.

C.J.C.J. C.J.

(LAV) 3/8" CW

(LAV) 3/8" HW

(LAV) 3/8" CW

(LAV) 3/8" HW

(LAV) 3/8" HW

(LAV) 3/8" CW

(LAV) 3/8" HW

(LAV) 3/8" CW

3/4" HW

3/4" HWR

NEW 3/4" CWNEW 3/4" CW

NEW 3/4" CW

PLUMBING DEMO PLAN LATRINES

SCALE 3/8" = 1'-0"

THE EXACT LOCATION OF THE UNDERGROUND PIPING IS UNKNOWN. THE SHOWN LOCATIONS ARE BASED ON EXISTING

DRAWING FILES WHEN THE ORIGINAL BUILDING WAS BUILT, ALONG WITH ON SITE OBSERVATIONS.

COORDINATE THE LOCATION OF THE EXISTING CONCRETE FLOOR SAW CUTTING TO INSTALL NEW UG SANITARY PIPING.

WHERE APPLICIBLE, ALL VENT AND REVENT PIPING SHALL BE INSTALLED IN STUD WALLS OR ABOVE FINISHED CEILINGS.

WHERE EXPOSED, ALL VENT AND REVENT PIPING SHALL BE INSTALLED IN A MANNER THAT THEY ARE PARALLEL TO CEILINGS

AND WALLS AND TUCKED TIGHT INTO THOSE SPOTS.

ALL ABOVE GROUND PIPING SHALL BE INSULATED AND LABELED.

GENERAL NOTES:

LEGEND:

NEW SANITARY SEWER PIPING

EXISTING U.G. SEWER PIPING, APPROXIMATE LOCATION

EXISTING COLD WATER PIPING, APPROXIMATE LOCATION

NEW COLD WATER PIPING

EXISTING HOT WATER PIPING

NEW HOT WATER PIPING

EXISTING RETURN HOT WATER PIPING

WC

EWC/BF

PLUMBING FIXTURE SCHEDULEPLUMBING FIXTURE

NOMENCLATURE

FIXTURE ITEM

LAVATORY

WATER CLOSET; FLOOR MOUNTED

FLOOR DRAIN

LAV

WC

MARK

FD

SK-1 LACTATION AREA SS SINK

ELECTRIC HAND DRYEREHD

ELECTRIC WATER COOLER/BOTTLEEWC/BF

URINAL; WALL MOUNTEDUR

CO CLEAN OUT

WALL CLEAN OUTWCO

*WHERE REQUIRED/ALLOWED BY THE CURRENT MI PLUMBING CODE, THE CONTRACTOR

HAS THE OPTION OF INSTALLING AN APPROVED WATERLESS TRAP SEALER.

FIXTURE ITEM

LAVATORY

WATER CLOSET

FLOOR DRAIN

LAV

WC

MARK

FD

SK-1 LACTATION AREA SS SINK

ELECTRIC WATER COOLER/BOTTLEEWC/BF

URINALUR

TRAPWASTE VENT CW HW

1 1/4"

1 1/4"

2"

1-1/2"

1 1/4" 1 1/2"

1 1/4"

3" 2"

1 1/2"

1-1/2" 1-1/2"

3/8" -

3/8"

3/8"

1/2" 1/2"

1-1/2" 1-1/2" 3/4"

1-1/2"

4" 4" 1" -4"

P100

D E

P A

R T

M E

M

I L

I T

A R

Y

A

T

E R

A N

S

A

F F

A I R

S

S T

A T

E

O

F

M

I C

H I G

A N

D E

S I G

N

A

N

S T

R U

C T

I O

N

D

I V

I S

I O

N

C

P

A

A

R E

N O

V A

M

O R

Y

T R

A V

E R

T

I O

N A

L

G

U A

M

O

A

V E

R S

E

C

I T

Y

M

I C

H I G

A N

WCO

FD

LAV

UR

WC

WC

WC

WC

WC

WC

WC

WC

UR

UR

FD

FD

FD

LAV

LAV

LAV

LAV

LAV

LAV

LAV

LAV

LAV

LAV

LAV

NEW PLUMBING PLAN LATRINES

SCALE 3/8" = 1'-0"

WC

EWC/BF

P100

WCO

WC

FD

LAV

UR

WC

WC

WC

WC

WC

WC

WC

WC

UR

UR

FD

FD

FD

LAV

LAV

LAV

LAV

LAVLAV

LAV

LAV

LAV

LAV

LAV

NEW PLUMBING PLAN ADDITIONAL

OUTDOOR WALL HYDRANT

SCALE 1/4" = 1'-0"

P100

TIE INTO EXISTING 1"

CW LINE. NEW 3/4" CW

LINE, SUPPLY SHUT OFF

VALVE

INSTALL NEW FREEZE

PROOF OUTDOOR WALL

HYDRANT. SEAL

WEATHER TIGHT

REUSE EXISTING FEED

AND DRAINAGE PIPING

IN WALL. TIE IN FOR

NEW FIXTURE FEEDS AT

NEW LOCATIONS

REUSE EXISTING FEED

AND DRAINAGE PIPING

IN WALL. TIE IN FOR

NEW FIXTURE FEEDS AT

NEW LOCATIONS

CW 3/8"

CW 3/8"

CW 3/8"

CW 3/8"

CW 3/8"

CW 3/8"

HW 3/8"

HW 3/8"

HW 3/8"

HW 3/8"

HW 3/8"

HW 3/8"

HW 3/8"

HW 3/8"

HW 3/8"

HW 3/8"

HW 3/8"

HW 3/8"

CW 3/8"

CW 3/8"

CW 3/8"

CW 3/8"

CW 3/8"

CW 3/8"

W

H W

CW 3/4"

CW 3/4"

CW 3/4"

CW 1"

CW 1"

CW 1"

CW 1"

CW 1"

CW 1"

CW 1"

CW 1"

CW 1"

REUSE EXISTING FEED

PIPING IN WALL. TIE IN

FOR NEW FIXTURE.

DRAINAGE LOCATION IN

FLOOR STAYS THE

SAME FOR NEW

FIXTURE

NEW CW 3/4" AND

HW 3/4" IN WALL

NEW CW 1/2" AND

HW 1/2" IN WALL

NEW SANITARY

SEWER IN WALL,

TIE TO EXISTING

VENT SYSTEM

TIE INTO EXISTING

UNDERGROUND

SANITARY SEWER

TIE INTO EXISTING

UNDERGROUND

SANITARY SEWER

SAWCUT AND REMOVE

CONCRETE IN THIS

LOCATION TO EXPOSE

SANITARY SEWER

REMOVE ALL PIPING IN

WALL, CAP END WHERE

LEAVING PIPE FOR NEW

FEED

ALL PIPING IN WALL TO BE

REUSED FOR NEW

FIXTURES

ALL PIPING IN WALL TO BE

REUSED FOR NEW

FIXTURES

SK-1

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

TUEBOR

AutoCAD SHX Text U

AutoCAD SHX Text S

AutoCAD SHX Text Q

AutoCAD SHX Text U

AutoCAD SHX Text E

AutoCAD SHX Text R

AutoCAD SHX Text C

AutoCAD SHX Text I

AutoCAD SHX Text U

AutoCAD SHX Text P

AutoCAD SHX Text I

AutoCAD SHX Text S

AutoCAD SHX Text R

AutoCAD SHX Text C

AutoCAD SHX Text S

AutoCAD SHX Text N

AutoCAD SHX Text I

AutoCAD SHX Text E

AutoCAD SHX Text N

AutoCAD SHX Text M

AutoCAD SHX Text I

AutoCAD SHX Text S

AutoCAD SHX Text

KAB

AutoCAD SHX Text E

AutoCAD SHX Text R

AutoCAD SHX Text U

AutoCAD SHX Text P

AutoCAD SHX Text L

AutoCAD SHX Text S

AutoCAD SHX Text B

AutoCAD SHX Text U

AutoCAD SHX Text I

AutoCAD SHX Text A

AutoCAD SHX Text N

AutoCAD SHX Text E

AutoCAD SHX Text O

AutoCAD SHX Text E

AutoCAD SHX Text I

AutoCAD SHX Text M

AutoCAD SHX Text L

AutoCAD SHX Text A

AutoCAD SHX Text P

AutoCAD SHX Text A

AutoCAD SHX Text M

AutoCAD SHX Text C

AutoCAD SHX Text M

AutoCAD SHX Text M

AutoCAD SHX Text U

AutoCAD SHX Text U

AutoCAD SHX Text N

AutoCAD SHX Text

PRELIMINARY

AutoCAD SHX Text

CONSTRUCTION

AutoCAD SHX Text

FINAL RECORD

AutoCAD SHX Text

DATE

AutoCAD SHX Text

ISSUED FOR

AutoCAD SHX Text

INDEX CODE

AutoCAD SHX Text

PROJECT

AutoCAD SHX Text

IDENTIFICATION NO.

AutoCAD SHX Text

SHEET

AutoCAD SHX Text

DESIGNED

AutoCAD SHX Text

DRAWN

AutoCAD SHX Text

CHECKED

AutoCAD SHX Text

APPROVED

AutoCAD SHX Text

DEPARTMENT OF TECHNOLOGY, MANAGEMENT AND BUDGET

AutoCAD SHX Text

FACILITIES AND BUSINESS SERVICES ADMINISTRATION

AutoCAD SHX Text

ADAM LACH, RA, DIRECTOR

AutoCAD SHX Text

KMM

AutoCAD SHX Text

KMM

AutoCAD SHX Text

KMM

KMM

MENS LOCKER/

SHOWER

306SF

JANITOR

66SF

OFFICE

42SF

JANITOR

IT/ELEC

92SF

WOMENS LOCKER/

SHOWER

262SF

WOMENS

185SF

KITCHEN

787SF

DRILL HALL

5616SF

MENS

191SF

TRAINING

PERSONAL

EQUIPMENT

STORAGE

836SF

KITCHEN

221SF

CHAIR/TABLE

STORAGE

284SF

PHYSICAL

TRAINING

688SF

80 lockers (42"x24") double stacked

PASSAGE

274SF

U P

UP

SCULLERY

221SF

D E

P A

R T

M E

M

I L

I T

A R

Y

A

T

E R

A N

S

A

F F

A I R

S

S T

A T

E

O

F

M

I C

H I G

A N

D E

S I G

N

A

N

S T

R U

C T

I O

N

D

I V

I S

I O

N

C

P

A

A

R E

N O

V A

M

O R

Y

T R

A V

E R

T

I O

N A

L

G

U A

M

O

A

V E

R S

E

C

I T

Y

M

I C

H I G

A N

ROOF DRAINAGE PLAN

SCALE 3/16" = 1'-0"

P300

ALL SECONDARY PIPING TO BE INSTALLED IN THE STEEL TRUSS SPACE.

ALL HORIZONTAL ROOF STORM WATER PIPING TO BE INSTALLED IN THE STEEL TRUSS SPACE.

ALL VERTICAL ROOF STORM WATER PIPING TO BE INSTALLED TIGHT AND CLOSE TO ABUTTING WALLS. AS NEEDED, INSTALL

THE APPROPRIATE ELBOWS TO OFFSET THE CONCRETE FOOTINGS AS THE PIPE PASSES BELOW GRADE.

ALL SECONDARY PIPING TO BE INSULATED WITH PROPER ELBOWS AND ADHESIVE TAPE.

ALL ABOVE GRADE STORM SEWER/DRAIN PIPING SHALL BE LABELED.

MINIMUM SLOPE OF ALL HORIZONTAL ABOVE GRADE STORM DRAIN PIPING SHALL BE 1/8" PER FOOT, UNLESS OTHERWISE

NOTED.

SLOPE OF ALL HORIZONTAL BELOW GRADE STORM DRAIN PIPING SHALL BE 1/4" PER FOOT OR 2 PERCENT SLOPE (1/4 UNIT

VERTICAL IN 12 UNITS HORIZONTAL), UNLESS OTHERWISE NOTED.

GENERAL NOTES:

4" RS

4" RS

4" RS

4" RS

4" RS

4" RS

CO

CO

CO

ROOF B

4" C.I. PIPING (INSULATE) INSTALL

IN STEEL TRUSS SPACE (TYP)

5" C.I. PIPING (INSULATE) INSTALL

IN STEEL TRUSS SPACE (TYP)

6" C.I. PIPING (INSULATE) INSTALL

IN STEEL TRUSS SPACE (TYP)

4" C.I. PIPING (INSULATE) INSTALL

IN STEEL TRUSS SPACE (TYP)

5" C.I. PIPING (INSULATE) INSTALL

IN STEEL TRUSS SPACE (TYP)

8" C.I. PIPING (INSULATE) INSTALL

IN STEEL TRUSS SPACE (TYP)

STEEL ROOF TRUSS (TYP)

STEEL ROOF TRUSS (TYP)

STEEL ROOF TRUSS BRACING TYP)

STEEL ROOF TRUSS BRACING TYP)

8" C.I. PIPING DOWN

W/ CO @ 16" AFF

8" U.G. PIPING

SEE CIVIL SHEET FOR CONTINUATION

AutoCAD SHX Text

TUEBOR

AutoCAD SHX Text U

AutoCAD SHX Text S

AutoCAD SHX Text Q

AutoCAD SHX Text U

AutoCAD SHX Text E

AutoCAD SHX Text R

AutoCAD SHX Text C

AutoCAD SHX Text I

AutoCAD SHX Text U

AutoCAD SHX Text P

AutoCAD SHX Text I

AutoCAD SHX Text S

AutoCAD SHX Text R

AutoCAD SHX Text C

AutoCAD SHX Text S

AutoCAD SHX Text N

AutoCAD SHX Text I

AutoCAD SHX Text E

AutoCAD SHX Text N

AutoCAD SHX Text M

AutoCAD SHX Text I

AutoCAD SHX Text S

AutoCAD SHX Text

KAB

AutoCAD SHX Text E

AutoCAD SHX Text R

AutoCAD SHX Text U

AutoCAD SHX Text P

AutoCAD SHX Text L

AutoCAD SHX Text S

AutoCAD SHX Text B

AutoCAD SHX Text U

AutoCAD SHX Text I

AutoCAD SHX Text A

AutoCAD SHX Text N

AutoCAD SHX Text E

AutoCAD SHX Text O

AutoCAD SHX Text E

AutoCAD SHX Text I

AutoCAD SHX Text M

AutoCAD SHX Text L

AutoCAD SHX Text A

AutoCAD SHX Text P

AutoCAD SHX Text A

AutoCAD SHX Text M

AutoCAD SHX Text C

AutoCAD SHX Text M

AutoCAD SHX Text M

AutoCAD SHX Text U

AutoCAD SHX Text U

AutoCAD SHX Text N

AutoCAD SHX Text

PRELIMINARY

AutoCAD SHX Text

CONSTRUCTION

AutoCAD SHX Text

FINAL RECORD

AutoCAD SHX Text

DATE

AutoCAD SHX Text

ISSUED FOR

AutoCAD SHX Text

INDEX CODE

AutoCAD SHX Text

PROJECT

AutoCAD SHX Text

IDENTIFICATION NO.

AutoCAD SHX Text

SHEET

AutoCAD SHX Text

DESIGNED

AutoCAD SHX Text

DRAWN

AutoCAD SHX Text

CHECKED

AutoCAD SHX Text

APPROVED

AutoCAD SHX Text

DEPARTMENT OF TECHNOLOGY, MANAGEMENT AND BUDGET

AutoCAD SHX Text

FACILITIES AND BUSINESS SERVICES ADMINISTRATION

AutoCAD SHX Text

ADAM LACH, RA, DIRECTOR

AutoCAD SHX Text

KMM

AutoCAD SHX Text

KMM

AutoCAD SHX Text

KMM

KMM

26C6921023 Renovate Armory TC FP100 Fire Suppression
Sheets and Views
SHEET FP100
26C6921023 Renovate Armory TC M1 Demo Plan
26C6921023 Renovate Armory TC M2 HVAC Plan
26C6921023 Renovate Armory TC M3 Schedules and Details
26C6921023 Renovate Armory TC M4 Energy Management Plan
26C6921023 Renovate Armory TC P100 Plumbing Plan
Sheets and Views
P100
26C6921023 Renovate Armory TC P300 Roof Drainage Plan
Sheets and Views
P300 ROOF PLAN
26C6921023 Renovate Armory TC E200 Electrical Bldg One line Panels.pdf
Sheets and Views
E200
26C6921023 Renovate Armory TC E100 Electrical Plan.pdf
Sheets and Views
E100
26C6921023 Renovate Armory TC E010 Site Electrical Plan.pdf
Sheets and Views
Elec E010

File details come from the government source that posted it. Updated .