26B1516001 RENOVATE BUILDINGS 536Q+534Q DRAWINGS PART 1.pdf
PDF 3 MB Posted
- Solicitation number
- RFQ 171 260000000277 2
- Issued by
- Crawford County, Michigan
About this file
Summary
This is a set of construction drawings and specifications for the Department of Military and Veterans Affairs, State of Michigan, for the renovation of Buildings 536Q and 534Q at Camp Grayling Joint Maneuver Training Center in Grayling, Michigan (Project 26B1516001). The project involves comprehensive building renovations including structural, mechanical, plumbing, electrical, fire protection, and site work. The buildings are single-story dormitory facilities (R-2 occupancy classification, Construction Type IIIB) with a total gross area of 7,671 square feet each. Work includes installation of new masonry veneer, foundation insulation, landscaping, site utilities, concrete sidewalks and entrance slabs with steel grates, mechanical HVAC systems, plumbing for 52 maximum occupants with required fixtures, electrical service upgrades, fire suppression and alarm systems, and energy management systems. Both buildings contain lead and asbestos-containing materials requiring abatement. Contractors are required to visit the site prior to bidding and must maintain a knowledgeable company representative on-site during construction. A deductive alternate is available to eliminate all work pertaining to Building 534Q and associated site work.
The project must comply with the 2021 Michigan Building Code, 2021 Michigan Mechanical Code, 2021 Michigan Plumbing Code, 2023 National Electrical Code, and 2021 Michigan Energy Code. Key contacts include Architect Adam Pohl (517-481-7585) and Owner's Field Representative Melissa Mead (989-344-6386). Contractors are responsible for obtaining all required permits, coordinating with Camp Grayling Engineering (989-344-6184) before excavation work, and providing daily digital progress photographs. The project includes coordination with existing utilities including underground fiber optics, natural gas, domestic water, sanitary sewer, and electrical service. Work involves careful handling of existing infrastructure such as padmount transformer T-538, existing water and sewer lines, and concrete features to be protected or replaced if damaged during construction. All excess soils must be spread and graded on-site with seed and mulch applied to disturbed areas.
View the file
Other files
Show all 15
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
LAKE MARGRETHE
BRIGADE ROAD
HOWE ROAD
SO
U
TH
A
C C
ES
S
R O
AD
BULK DIESEL FUEL
POL OFFICE
BULK FUEL FACILITY
8t h
S
TR
EE
T
S O
U
TH
th
S
TR
EE
T
8t h
EE
T
N O
R
TH
EE
T
9t
EE
T
BRIGADE ROAD
7t h
S
TR
EE
T
S O
U
TH
6t h
S
TR
EE
T
5t h
S
TR
EE
T
HOWE ROAD
7t
R
TH
PARADE ROAD
REVIEW STAND
PARADE ROAD
EE
T
9t
EE
T
8t
R
TH
SOLDIERS DRIVE
SOLDIERS DRIVE
HOSPITAL
4t h
S
TR
EE
T
S O
U
TH
LO
O
P
4t
R
TH
HOWE R
OAD
KITCHEN ROAD
3rd STREET
SOLDIERS D
RIVE
KI
TC
HE
RO
AD
HO
W
E
R
OA
D
2nd STREET
W
ILSO
N HILL RO
AD
FAC
BEAVER CREEK ROAD
1st STREET
KI
TC
H
EN
AD
SOLDIERS DRIVE
ARMORY
HOWE
ROAD
ENG
SIMMS
Center
HOWE
ROAD
TRAILER PARK ROAD
FAC
ENVR
100A
11/21 0
7 MILE RD
FLETCHER RD
M
IL
IT
AR
Y R
O
AD
2 3 STATUTE MILES
HOWE RD
LAKE MARGRETHE
4 MILE RD
CAMP GRAYLING
GRAYLING
27MICHIGAN
Grayling
DRAWING SHEET CONTENTS
SHEET NO. DRAWING TITLE
G-0.0 TITLE SHEET
G-1.0 CODE COMPLIANCE PLAN AND INFORMATION
C-1.0 SITE UTILITIES PLAN
C-2.0 536Q FOUNDATION INSULATION & LANDSCAPING PLAN
C-3.0 534Q FOUNDATION INSULATION & LANDSCAPING PLAN
C-4.0 CIVIL DETAILS
S-1.0 FOUNDATION PLAN AND DETAILS
S-2.0 LINTEL PLAN, SCHEDULE, AND DETAILS
A-1.0 DEMOLITION PLANS
A-1.1 FLOOR PLAN AND DETAILS
A-1.2 ENLARGED FLOOR PLANS
A-1.3 CEILING PLAN AND MISCELLANEOUS DETAILS
A-1.4 ROOF PLAN AND DETAILS
A-2.0 EXISTING BUILDING ELEVATIONS - NEW MASONRY VENEER ANCHOR
DETAILS
A-2.1 BUILDING ELEVATIONS
A-3.0 BUILDING SECTION, MISC INTERIOR WALL ELEVATIONS
A-3.1 SECTIONS AND DETAILS
A-3.2 SECTIONS AND DETAILS
A-3.3 DETAILS
A-6.0 WINDOW, DOOR AND HARDWARE ELEVATIONS, SCHEDULES AND
DETAILS
A-6.1 DOOR DETAILS
A-6.2 ROOM FINISH SCHEDULE AND DETAILS
FP-1 PROPOSED FIRE PROTECTION PLANS AND DETAILS
P-1.0 PLUMBING DEMOLITION - WASTE PLANS
P-2.0 PLUMBING DEMOLITION - WATER PLANS
P-3.0 PLUMBING WASTE PLANS -536Q
P-4.0 PLUMBING WASTE PLANS -534Q
P-5.0 WASTE AND VENT PIPING SECTIONS
P-6.0 WATER PLUMBING PLANS
M-1.0 MECHANICAL DEMOLITION AND HVAC PLANS
M-2.0 MECHANICAL HVAC PIPING PLAN & DETAILS
M-3.0 MECHANICAL FAN ROOM DETAILS
M-4.0 MECHANICAL ROOM PLAN & DETAILS
M-5.0 MECHANICAL SCHEDULES
EM-1.0 ENERGY MANAGEMENT PLAN
EM-2.0 ENERGY MANAGEMENT DETAILS AND SCHEDULES
E-1.0 ELECTRICAL DEMOLITION PLANS
E-2.0 POWER PLANS
E-3.0 LIGHTING PLANS, SCHEDULES, AND NOTES
E-4.0 ELECTRICAL SITE PLANS
E-5.0 PROPOSED FIRE ALARM PLAN
E-6.0 PANEL SCHEDULES AND RISER DIAGRAM
Renovate Building 536Q/534Q Camp Grayling Joint Maneuver Training Center
Grayling, Michigan 26B1516001
AREA OF WORK - BUILDING 534Q
CANTONMENT PLAN
536Q/534Q BUILDING LOCATION PLAN
NO SCALE
MAIN GATE
GENERAL NOTES:
1. THE GENERAL CONTRACTOR AND HIS SUBCONTRACTORS AND/OR
SUPPLIERS ARE RESPONSIBLE FOR VISITING THE SITE PRIOR TO
BIDDING TO VERIFY ALL EXISTING CONDITIONS AND DIMENSIONS.
2. THE GENERAL CONTRACTOR IS RESPONSIBLE FOR FURNISHING
HIS SUBCONTRACTORS AND SUPPLIERS ALL THE NECESSARY
CONTRACT DOCUMENTS TO ENSURE THEY INCLUDE ALL ITEMS IN
THEIR BID THAT ARE WITHIN THEIR DISCIPLINE.
3. THE GENERAL CONTRACTOR IS RESPONSIBLE FOR ALL WORK
REQUIRED AND PERFORMED TO CARRY OUT THE INTENT OF THIS
PROJECT.
4. THE GENERAL CONTRACTOR SHALL HAVE A KNOWLEDGEABLE
REPRESENTATIVE FROM THEIR COMPANY ON SITE AT ALL TIMES
DURING HIS COMPANY'S WORK, OR THE WORK OF ONE OF THE
SUBCONTRACTORS. THIS REPRESENTATIVE SHALL HAVE ON
SITE, HIS OWN COPY OF THE CONTRACT SPECIFICATIONS,
DRAWINGS AND DMVA APPROVED SHOP DRAWINGS.
5. DISCREPANCIES FOUND WITH THE CONTRACT DOCUMENTS
SHALL BE SUBMITTED TO DMVA IN THE FORM OF AN RFI FOR
CLARIFICATION PRIOR TO ANY WORK INVOLVING THIS
DISCREPANCY.
6. THE CONTRACTOR IS RESPONSIBLE FOR APPLYING AND PAYING
FOR ALL REQUIRED PERMITS.
7. ALL WORK IS TO BE PERFORMED IN ACCORDANCE WITH ALL
APPLICABLE LAWS, CODES, AND REGULATIONS.
8. BOTH 536Q AND 534Q HAVE LEAD AND ASBESTOS CONTAINING
MATERIALS. REFER TO LEAD ASBESTOS REPORTS. THE
CONTRACTOR WILL BE RESPONSIBLE FOR CARRYING ABATEMENT
WORK AS REQUIRED BY THE LEAD AND ASBESTOS PROCEDURES
INCLUDED IN THE SPECIFICATIONS.
9. THE GENERAL CONTRACTOR WILL BE RESPONSIBLE FOR TAKING
DAILY DIGITAL PHOTOS OF THE CONSTRUCTION PROGRESS.
THESE DIGITAL PHOTOS WILL BE A PART OF THE WRITTEN DAILY
PROGRESS INSPECTION REPORTS SPECIFIED TO BE COMPLETED
EACH DAY. UPON COMPLETION OF THE PROJECT AND PRIOR TO
FINAL PAYMENT ALL DIGITAL PHOTOS (.JPG FORMAT PHOTO
FILES) SHALL BE TURNED OVER TO DMVA PROJECT MANAGER ON
DIGITAL MEDIA SUCH AS CDs OR DVDs INCLUDED IN THE
CLOSEOUT DOCUMENTS.
SOIL BORING #1
SOIL EVALUATION
NO SCALE
SOIL BORING #1
D
EP
AR
TM
EN
T
O F
M
IL
IT
AR
Y
AN
D V
ET
ER
AN
S
AF
FA
IR
S
ST
AT
E O
F M
IC
H
IG
AN
D
ES
IG
N
A N
D C
O N
ST
R
U C
TI
O
N D
IV
IS
IO
N
B1
G 0.
AP
R
EN
O
VA
TE
B
U
IL
D
IN
G
Q
/5
Q C
AM
P
G R
AY
LI
N G
J O
IN
T
M
AN
EU
VE
R T
R
AI
N
IN
G C
EN
TE
G
AY
LI
N G
, M
IC
H
IG
AN
UTILITIES
989-344-6184
72 HOURS
(3 WORKING DAYS)
CALL Mr. Halcomb
BEFORE YOU DIGC.G.
MICHAEL HALCOMB
CAMP GRAYLING ENGINEERING
KAB'17
KNOW WHAT'S BELOW.
CALL BEFORE YOU DIG.
AREA OF WORK - BUILDING 536Q
G-0
G-0
BUILDINGS 536Q/534Q BASE BID/ALTERNATE NOTES:
ALL DETAILS WITHIN ARE FOR BOTH 536Q AND 534Q UNLESS OTHERWISE NOTED.
UNLESS OTHERWISE NOTED, SCHEDULES SHOWN ARE FOR 1 EACH BUILDING.
CONTRACTOR SHALL BE RESPONSIBLE FOR THE QUANTITIES NEEDED AND
REQUIRED IF BOTH BUILDINGS 536Q AND 534Q ARE REMODELED.
DEDUCTIVE ALTERNATE NO. 1:
STATE THE AMOUNT TO BE DEDUCTED FROM THE BASE PROPOSAL SUM TO
ELIMINATE ALL WORK PERTAINING TO THE RENOVATION OF BUILDING 534Q AND
THE SITE WORK PERTAINING TO 534Q AND ALL RELATED WORK INDICATED IN
THE DRAWINGS AND SPECIFICATIONS.
AREA LOCATION PLAN
NO SCALE
LOCATION MAP
NO SCALEG-0
G-0
DIRECTORY:
ARCHITECT:
ADAM POHL 517-481-7585
POHLA4@MICHIGAN.GOV
OWNER'S FIELD REPRESENTATIVE:
MELISSA MEAD 989-344-6386
MEADM4@MICHIGAN.GOV
TITLE SHEET
AutoCAD SHX Text N
AutoCAD SHX Text W
AutoCAD SHX Text E
AutoCAD SHX Text S
AutoCAD SHX Text N
AutoCAD SHX Text W
AutoCAD SHX Text E
AutoCAD SHX Text S
AutoCAD SHX Text
TUEBOR
AutoCAD SHX Text U
AutoCAD SHX Text S
AutoCAD SHX Text Q
AutoCAD SHX Text U
AutoCAD SHX Text E
AutoCAD SHX Text R
AutoCAD SHX Text C
AutoCAD SHX Text I
AutoCAD SHX Text U
AutoCAD SHX Text P
AutoCAD SHX Text I
AutoCAD SHX Text S
AutoCAD SHX Text R
AutoCAD SHX Text C
AutoCAD SHX Text S
AutoCAD SHX Text N
AutoCAD SHX Text I
AutoCAD SHX Text E
AutoCAD SHX Text N
AutoCAD SHX Text M
AutoCAD SHX Text I
AutoCAD SHX Text S
AutoCAD SHX Text
KAB
AutoCAD SHX Text E
AutoCAD SHX Text R
AutoCAD SHX Text U
AutoCAD SHX Text P
AutoCAD SHX Text L
AutoCAD SHX Text S
AutoCAD SHX Text B
AutoCAD SHX Text U
AutoCAD SHX Text I
AutoCAD SHX Text A
AutoCAD SHX Text N
AutoCAD SHX Text E
AutoCAD SHX Text O
AutoCAD SHX Text E
AutoCAD SHX Text I
AutoCAD SHX Text M
AutoCAD SHX Text L
AutoCAD SHX Text A
AutoCAD SHX Text P
AutoCAD SHX Text A
AutoCAD SHX Text M
AutoCAD SHX Text C
AutoCAD SHX Text M
AutoCAD SHX Text M
AutoCAD SHX Text U
AutoCAD SHX Text U
AutoCAD SHX Text N
AutoCAD SHX Text
PRELIMINARY
AutoCAD SHX Text
CONSTRUCTION
AutoCAD SHX Text
FINAL RECORD
AutoCAD SHX Text
DATE
AutoCAD SHX Text
ISSUED FOR
AutoCAD SHX Text
INDEX CODE
AutoCAD SHX Text
PROJECT
AutoCAD SHX Text
IDENTIFICATION NO.
AutoCAD SHX Text
SHEET
AutoCAD SHX Text
DESIGNED
AutoCAD SHX Text
DRAWN
AutoCAD SHX Text
CHECKED
AutoCAD SHX Text
APPROVED
AutoCAD SHX Text
DEPARTMENT OF TECHNOLOGY, MANAGEMENT AND BUDGET
AutoCAD SHX Text
PROCUREMENT AND REAL ESTATE SERVICES ADMINISTRATION
AutoCAD SHX Text
ADAM LACH RA, DIRECTOR
AutoCAD SHX Text
JDJ
AutoCAD SHX Text
AJP
AutoCAD SHX Text
KAB
AutoCAD SHX Text
KAB
AutoCAD SHX Text N
AutoCAD SHX Text W
AutoCAD SHX Text E
AutoCAD SHX Text S
AutoCAD SHX Text N
AutoCAD SHX Text W
AutoCAD SHX Text E
AutoCAD SHX Text
D
EP
AR
TM
EN
T
O F
M
IL
IT
AR
Y
AN
D V
ET
ER
AN
S
AF
FA
IR
S
ST
AT
E O
F M
IC
H
IG
AN
D
ES
IG
N
A N
D C
O N
ST
R
U C
TI
O
N D
IV
IS
IO
N
B1
G 1.
JU
L
R
EN
O
VA
TE
B
U
IL
D
IN
G
Q
/5
Q C
AM
P
G R
AY
LI
N G
J O
IN
T
M
AN
EU
VE
R T
R
AI
N
IN
G C
EN
AY
LI
N G
, M
IC
H
IG
AN
BUILDING CODE INFORMATION
CODES:
THE BUILDING SHALL BE CONSTRUCTED IN ACCORDANCE WITH:
2021 MICHIGAN BUILDING CODE
2021 MICHIGAN MECHANICAL CODE
2021 MICHIGAN PLUMBING CODE
2023 NATIONAL ELECTRICAL CODE
2021 MICHIGAN ENERGY CODE
OCCUPANCY:
R-2 BILLET (DORMITORY) MBC SECTION 310
INCIDENTAL USES TABLE 508.4
MECHANICAL ROOM 0 HR (SPRINKLERED)
LAUNDRY ROOM 0 HR (UNDER 100 SF)
ACCESSORY
JANITOR CLOSET 0 HR
CONSTRUCTION TYPE:
IIIB MBC SECTION 602
ALLOWABLE BUILDING HEIGHT & AREA:
GROSS AREA: 7,671 SF
ALLOWABLE AREA: 16,000 SQ FT TABLE 506.2
ACTUAL HEIGHT: 18'-4"
ALLOWABLE HEIGHT: 75' TABLE 506.2
NUMBER OF STORIES: 1 STORY
ALLOWABLE STORIES: 4 STORIES TABLE 504.4
BUILDING ELEMENTS TABLE 601
STRUCTURAL FRAME 0 HR
BEARING WALLS
EXTERIOR 2 HR
INTERIOR 0 HR
NONBEARING WALLS & PARTITIONS
INTERIOR 0 HR
FLOOR CONSTRUCTION 0 HR
ROOF CONSTRUCTION 0 HR
CORRIDOR WALLS: 1/2 HR RATED PER TABLE 1020.2
WALLS SEPARATING SLEEPING UNITS: 1/2 HR PER 420.2 & 708.3 EXCEPTION 2
INTERIOR DOOR OPENINGS: 1/3 HOUR IN 1/2 HR FIRE RATED WALLS PER TABLE 716.5
EXTERIOR WALL OPENINGS: FIRE RATING NOT REQUIRED WHERE BUILDING IS PROVIDED
WITH AN AUTOMATIC SPRINKLER SYSTEM PER 705.8.2 EXCEPTION AND 705.8.3
OCCUPANCY LOAD MBC TABLE 1004.1.2
ROOM NAME: ROOM FUNCTION: LOAD FACTOR OCC.
KITCHENETTE 100S DORMITORIES 50 GSF/PERSON 3
KITCHENETTE 100N DORMITORIES 50 GSF/PERSON 3
102S BILLET DORMITORIES 50 GSF/PERSON 30
102N BILLET DORMITORIES 50 GSF/PERSON 30
104S BILLET DORMITORIES 50 GSF/PERSON 30
104N BILLET DORMITORIES 50 GSF/PERSON 30
LAUNDRY 106S DORMITORIES (INCIDENTAL) 50 GSF/PERSON 2
LAUNDRY 106N DORMITORIES (INCIDENTAL) 50 GSF/PERSON 2
LATRINE 105S DORMITORIES 50 GSF/PERSON 8
LATRINE 105N DORMITORIES 50 GSF/PERSON 8
JANITOR 101S STORAGE (ACCESSORY) 300GSF/PERSON 1
JANITOR 101N STORAGE (ACCESSORY) 300GSF/PERSON 1
FAN ROOM S MECHANICAL 300GSF/PERSON 1
FAN ROOM N MECHANICAL 300GSF/PERSON 1
MECHANICAL MECHANICAL (INCIDENTAL) 300GSF/PERSON 1
TOTAL OCCUPANTS 151
FIRE PROTECTION SYSTEM:
SPRINKLER SYSTEM: REQUIRED & PROVIDED MBC 903.2.8
FIRE EXTINGUISHERS: REQUIRED & PROVIDED
MANUAL FIRE ALARM SYSTEM: PROVIDED
ACCESSIBILITY
MILITARY FACILITY EXEMPT PER MBC 1103.2.15
HOUSING , BATHING, TOILET, TRAINING, AND STORAGE AREAS INTENDED FOR USE AND
OCCUPANCY EXCLUSIVELY BY MILITARY, FIRE SERVICE, POLICE, OR SECURITY
PERSONNEL REQUIRED TO BE PHYSICALLY AGILE ARE NOT REQUIRED TO BE
ACCESSIBLE.
EGRESS COMPONENTS:
NUMBER OF EXITS PER FLOOR TABLE 1021.1
FIRST FLOOR 2 REQUIRED, 7 PROVIDED
EGRESS WIDTH FACTORS: SECTION 1005.3.2
0.15" / PERSON EXCEPTION 1
COMMON PATH OF TRAVEL: 125' TABLE 1006.2.1
EXIT TRAVEL ACCESS: 250' (SPRINKLERED) TABLE 1017.2
MAX. DEAD END CORRIDORS: 50' (SPRINKLERED) SECTION 1018.4
BILLET 104N
1455 SF
1/50 GROSS
30 OCUPS - 2 EXITS
BILLET 102N
1457 SF R-2
1/50 GROSS
30 OCUPS - 2 EXITS
MECHANICAL 107
204 SF
1/300 GROSS
1 OCUPS - 1 EXIT
FAN ROOM 103N
89 SF
1/300 GROSS
1 OCUPS - 2 EXITS
FAN ROOM 103S
90 SF
1/300 GROSS
1 OCUPS - 2 EXITS
LAUNDRY 106N
52 SF
1/50 GROSS
2 OCUPS - 1 EXIT
LAUNDRY 106S
52 SF
1/50 GROSS
2 OCUPS - 1 EXIT
LATRINE 105N
389 SF R-2
1/50 GROSS
8 OCUPS - 1 EXIT
JANITOR 101S
20 SF
1/300 GROSS
1 OCUPS - 1 EXIT
LATRINE 105S
378 SF R-2
1/50 GROSS
8 OCUPS - 1 EXIT
JANITOR 101N
20 SF
1/300 GROSS
1 OCUPS - 1 EXIT
ACCESSORY USE
ACCESSORY USE
EXIT
15 OCUPS
3 INCHES REQUIRED
36 INCHES PROVIDED
EXIT
15 OCUPS
3 INCHES REQUIRED
36 INCHES PROVIDED
EXIT
45 OCUPS
9 INCHES REQUIRED
72 INCHES PROVIDED
EXIT
45 OCUPS
9 INCHES REQUIRED
72 INCHES PROVIDED
EXIT
1 OCUPS
0.2 INCHES REQUIRED
72 INCHES PROVIDED
536Q/534Q CODE COMPLIANCE PLAN
SCALE 1/16" = 1'-0"G1.0
BILLET 104S
1457 SF R-2
1/50 GROSS
30 OCUPS - 2 EXITS
BILLET 102S
1457 SF R-2
1/50 GROSS
30 OCUPS - 2 EXITS
EXIT
15 OCUPS
3 INCHES REQUIRED
36 INCHES PROVIDED
EXIT
15 OCUPS
3 INCHES REQUIRED
36 INCHES PROVIDED
INCIDENTAL USE
B1
Q
INCIDENTAL USE
INCIDENTAL USE
R-2
PLUMBING FIXTURE COUNT
(MPC TABLE 403.1)
MAXIMUM NUMBER OF BEDS - 13 PER BAY PER NATIONAL GUARD
REGULATIONS = 52 OCCUPANTS
FIXTURE TYPE REQUIREMENT REQUIRED PROVIDED
WATER CLOSETS 1 PER 10 6 8
LAVATORIES 1 PER 10 6 8
SHOWERS 1 PER 10 6 8
DRINKING 1 PER 100 1 2
FOUNTAINS
SERVICE SINKS 1 1 2
KITCHENETTE 100N
128 SF
1/50 GROSS
3 OCUPS - 1 EXIT
KITCHENETTE 100S
128 SF
1/50 GROSS
3 OCUPS - 1 EXIT
R-2 R-2
R-2
R-2
R-2 R-2
1/2 HOUR RATED
2 HOUR RATED
WALL FIRE RATINGS1/2 HOUR FIRE RATED CORRIDOR LID
F.E.C.
F.E.C. F.E.C. F.E.C.
F.E.C.
F.E.C.
F.E.C. F.E.C.
EXIT
15 OCUPS
3 INCHES REQUIRED
36 INCHES PROVIDED
EXIT
15 OCUPS
3 INCHES REQUIRED
36 INCHES PROVIDED
EXIT
15 OCUPS
3 INCHES REQUIRED
36 INCHES PROVIDED
EXIT
15 OCUPS
3 INCHES REQUIRED
36 INCHES PROVIDED
CODE COMPLIANCE PLAN AND INFORMATION
125' EXIT TRAVEL DISTANCE
F.E.
1/2 HOUR RATED CEILING
TABLE 722.6.2(1) CALCULATED METHOD:
5/8" TYPE X GYPSUM WALL BOARD 40 MINUTES,
INSTALLED ON FRAMING MEMBERS THAT ARE SPACED 16" O.C. OR LESS
ALL EDGES OF WALLBOARD MUST BE SUPPORTED,
GYPSUM BOARD SHALL BE INSTALLED WITH THE LONG DIMENSION
PERPENDICULAR TO FRAMING MEMBERS AND SHALL HAVE ALL JOINTS
FINISHED.
CONTRACTOR TO INSTALL 5/8" TYPE X GYPSUM BOARD ATTACHED TO 1
1/2" METAL HAT CHANNEL AT 16" O.C. MAX. HAT CHANNEL SECURED TO
UNDERSIDE OF EXISTING 4'-0" O.C. PRE-ENGINEERED ROOF TRUSSES OR
2'-0" O.C. DEPENDING ON LOCATION. EXISTING ROOF MATERIAL IS
ASPHALT SHINGLES ON 1/2" ROOF SHEATHING OVER 2X4 WD PURLINS AT
2'-0" O.C.
ATTIC DRAFT STOPS NOT REQUIRED
718.4-EXCEPTION
DRAFT STOPS ARE NOT REQUIRED WHERE THE BUILDING IS EQUIPPED
THROUGHOUT WITH AN AUTOMATIC SPRINKLER SYSTEM.
BUILDING IS FULLY SPRINKLERED INCLUDING ATTIC SPACE
F.E.C. = FIRE EXTINGUISHER CABINET
AutoCAD SHX Text 102N
AutoCAD SHX Text 100S
AutoCAD SHX Text 104N
AutoCAD SHX Text 105N
AutoCAD SHX Text
105NA
AutoCAD SHX Text
AutoCAD SHX Text 102S
AutoCAD SHX Text 104S
AutoCAD SHX Text 103S
AutoCAD SHX Text 101S
AutoCAD SHX Text 100N
AutoCAD SHX Text 105S
AutoCAD SHX Text
105SA
AutoCAD SHX Text 101N
AutoCAD SHX Text 106S
AutoCAD SHX Text 106N
AutoCAD SHX Text 103N
AutoCAD SHX Text
TUEBOR
AutoCAD SHX Text U
AutoCAD SHX Text S
AutoCAD SHX Text Q
AutoCAD SHX Text U
AutoCAD SHX Text E
AutoCAD SHX Text R
AutoCAD SHX Text C
AutoCAD SHX Text I
AutoCAD SHX Text U
AutoCAD SHX Text P
AutoCAD SHX Text I
AutoCAD SHX Text S
AutoCAD SHX Text R
AutoCAD SHX Text C
AutoCAD SHX Text S
AutoCAD SHX Text N
AutoCAD SHX Text I
AutoCAD SHX Text E
AutoCAD SHX Text N
AutoCAD SHX Text M
AutoCAD SHX Text I
AutoCAD SHX Text S
AutoCAD SHX Text
KAB
AutoCAD SHX Text E
AutoCAD SHX Text R
AutoCAD SHX Text U
AutoCAD SHX Text P
AutoCAD SHX Text L
AutoCAD SHX Text S
AutoCAD SHX Text B
AutoCAD SHX Text U
AutoCAD SHX Text I
AutoCAD SHX Text A
AutoCAD SHX Text N
AutoCAD SHX Text E
AutoCAD SHX Text O
AutoCAD SHX Text E
AutoCAD SHX Text I
AutoCAD SHX Text M
AutoCAD SHX Text L
AutoCAD SHX Text A
AutoCAD SHX Text P
AutoCAD SHX Text A
AutoCAD SHX Text M
AutoCAD SHX Text C
AutoCAD SHX Text M
AutoCAD SHX Text M
AutoCAD SHX Text U
AutoCAD SHX Text U
AutoCAD SHX Text N
AutoCAD SHX Text
PRELIMINARY
AutoCAD SHX Text
CONSTRUCTION
AutoCAD SHX Text
FINAL RECORD
AutoCAD SHX Text
DATE
AutoCAD SHX Text
ISSUED FOR
AutoCAD SHX Text
INDEX CODE
AutoCAD SHX Text
PROJECT
AutoCAD SHX Text
IDENTIFICATION NO.
AutoCAD SHX Text
SHEET
AutoCAD SHX Text
DESIGNED
AutoCAD SHX Text
DRAWN
AutoCAD SHX Text
CHECKED
AutoCAD SHX Text
APPROVED
AutoCAD SHX Text
DEPARTMENT OF TECHNOLOGY, MANAGEMENT AND BUDGET
AutoCAD SHX Text
FACILITIES AND BUSINESS SERVICES ADMINISTRATION
AutoCAD SHX Text
ADAM LACH RA, DIRECTOR
AutoCAD SHX Text
JDJ
AutoCAD SHX Text
AJP
AutoCAD SHX Text
KAB
AutoCAD SHX Text
KAB
AutoCAD SHX Text N
AutoCAD SHX Text W
AutoCAD SHX Text E
AutoCAD SHX Text S
AutoCAD SHX Text N
AutoCAD SHX Text W
AutoCAD SHX Text E
M
T
SF
SF
SF
SFSF
SF
SF
M R
R
SF
SF
SF SF SF SF
SF
SF
M
SITE UTILITIES PLAN
SCALE 1" = 20'
540Q
LEGEND
EXISTING UNDERGROUND FIBEROPTICS
EXISTING UNDERGROUND NATURAL GAS
EXISTING UNDERGROUND DOMESTIC WATER
NEW UNDERGROUND SANITARY SEWER
EXISTING UNDERGROUND SANITARY SEWER
EXISTING UNDERGROUND ELECTRICAL SERVICE
EXISTING SANITARY SEWER MANHOLE
NOT USED
EXISTING GUARD RAIL
MECH/
ELECT
RM
EXTG UG FIBER/COMM
8" WATER
N. GAS
EXISTING UG ELECTRIC
NEW UNDERGROUND DOMESTIC WATER SERVICE
NEW UNDERGROUND FIRE SUPPRESSION PIPING
EXISTING PADMOUNT TRANSFORMER T-538 TO REMAIN. COORDINATE
ELECTRICAL OUTAGES WITH CAMP GRAYLING ENGINEERING. CARE
MUST BE TAKEN NOT TO DAMAGE THIS EXISTING TRANSFORMER.
HAND DIG AROUND THIS TRANSFORMER.
9 EXISTING ELECTRICAL SERVICE PANEL. COORDINATE WITH THE
ELECTRICAL DISCIPLINE.
PROVIDE AND INSTALL NEW UNDERGROUND DIRECT BURY ELECTRICAL
FEEDER CABLE FOR BUILDING - SEE ELECTRICAL. COORDINATE THE
EXACT ROUTE OF THIS CABLE WITH CAMP GRAYLING ENGINEERING.
PROVIDE AND INSTALL CONDUIT BELOW THE CONCRETE SLAB IN THE
MECH/ELECT ROOM. PROVIDE A RIGID METALLIC CONDUIT NINETY
FITTING WHEN TURNING UP TO DISTRIBUTION PANEL MDP. INSTALL IN
METALLIC RACEWAY ABOVE THE SLAB.
NEW UNDERGROUND ELECTRICAL FEEDER CABLE
T-538
P-538
542Q
544MA 542MA
APPROX LOCATION
OF GATEGRAVEL ACCESS ROAD
APPROX LOCATION
OF EDGE OF
GRAVEL DRIVE
UTILITY KEY NOTES:
EX. N. GAS
EX. N. GAS
NEW UNDERGROUND NATURAL GAS
EXISTING GUARD RAIL;
DO NOT DISTURB
EXISTING GUARD RAIL;
DO NOT DISTURB
540MA 538MA
GRAVEL ACCESS ROAD
EXISTING
TRANSFORMER
PAD TO REMAIN
EXISTING
SWITCHBOARD,
SEE ELEC. FOR
MODIFICATIONS
D
EP
AR
TM
EN
T
O F
M
IL
IT
AR
Y
AN
D V
ET
ER
AN
S
AF
FA
IR
S
ST
AT
E O
F M
IC
H
IG
AN
D
ES
IG
N
A N
D C
O N
ST
R
U C
TI
O
N D
IV
IS
IO
N
B1
C -1
AR
R
EN
O
VA
TE
B
U
IL
D
IN
G
Q
/5
Q C
AM
P
G R
AY
LI
N G
J O
IN
T
M
AN
EU
VE
R T
R
AI
N
IN
G C
EN
AY
LI
N G
, M
IC
H
IG
AN
UTILITIES
989-344-6184
72 HOURS
(3 WORKING DAYS)
CALL Mr. Halcomb
BEFORE YOU DIGC.G.
MICHAEL HALCOMB
CAMP GRAYLING ENGINEERING
KAB'17
KNOW WHAT'S BELOW.
CALL BEFORE YOU DIG.
C-1
538Q 536Q 534Q
EX. N. GAS
EXISTING UNDERGROUND FIRE SUPPRESSION PIPING
GENERAL CONTRACTOR TO COVER THE FULL COST AND SCHEDULE
GAS SHUTOFF, REMOVAL AND REINSTALLATION OF GAS METER AS
PART OF NATURAL GAS ALLOWANCE: CONTRACTOR TO CONTACT DTE
ENERGY AND CONTRACT W/ A UTILITY APPROVED SUBCONTRACTOR
FOR GAS SHUTOFF, REMOVAL AND REINSTALLATION OF EXISTING GAS
REGULATOR.
APPROX LOCATION
OF EDGE OF
GRAVEL ACCESS
ROAD
EX. 8" SANITARY
SEWER
EX. 3" WATER
EXISTING
SIDEWALK TO
REMAIN
EX. WATER
EXTG UG FIBER/COMM
MH
EXISTING
SIDEWALK TO
REMAIN
IF EXISTING CONCRETE SIDEWALK IS TO REMAIN AND BECOMES
DAMAGED FROM THE CONSTRUCTION, THE CONTRACTOR SHALL
REMOVE ALL DAMAGED AREAS AND REPLACE WITH NEW
FOLLOWING DETAILS AND SPECIFICATIONS.
EX 8" SANITARY SEWER
MH
EXTG UG FIBER/COMM
EXISTING WATER SHUT OFF VALVE. CONTRACTOR SHALL UTILIZE THIS
VALVE AS REQUIRED TO INSTALL NEW WATER PIPING AND PLUMBING AS
DETAILED AND SPECIFIED; COORDINATE WITH PLUMBING DRAWINGS.
EXISTING 2" WATER PIPING. EXCAVATE AS REQUIRED TO REMOVE EXISTING 6"
TO 2" REDUCER AND THE EXISTING 2" PIPING. INSTALL NEW 6" PIPING MAKING
THE PROPER CONNECTION TO THE EXISTING 6" PIPING AND INSTALLING IT UP
INTO THE NEW MECHANICAL ROOM IN DESIGNATED LOCATION. AT SERVICE
INSIDE JUST ABOVE FLOOR ENTRANCE, TEE OFF THIS 6" TO A 4" FOR THE FIRE
SUPPRESSION AND A 2" FOR DOMESTIC WATER SUPPLY. SEE CIVIL DETAILS
AND PLUMBING DRAWINGS FOR THE REQUIRED WORK IN THESE AREAS.
PIPING SHALL BE INSTALLED A MINIMUM 6 FEET BELOW GRADE; INSTALL
INSULATION OVER PIPING (2" DOW BLUE BOARD DOUBLED TO 4", 2'-0" WIDE
OVER TOP OF PIPING FULL LENGTH)
EXISTING 6" PVC
WATER PIPING
536MA
534MA
7T H
S
TR
EE
T
EX. 8" SANITARY
SEWER
EX 2" WATER
NEW SIDEWALK -
SEE LANDSCAPE
PLAN
N. GAS
MECH/
ELECT
RM
5 THE EXACT LOCATION OF WHERE THE EXISTING 1962 BATH LATRINE UG
SEWER EXITS TO CONNECT TO THE EAST/WEST SEWER LINE INS UNKNOWN.
SEE PLUMBING SHEETS AND COORDINATE.
5 5
EXISTING 6" PVC
WATER PIPING
EXISTING CONCRETE
SIDEWALK TO BE REMOVED
EXISTING CONCRETE
SIDEWALK TO BE REMOVED
N. GAS
10 CONTRACTOR SHALL TAKE CAUTION WHEN EXCAVATING NEAR
EXISTING UNDERGROUND SANITARY SEWER PIPING THAT MAY REMAIN
RUNNING EAST/WEST. ANY DISTRUBANCE OF THIS PIPING OTHER THAN
THAT SPECIFIED TO BE COMPLETED MAY CAUSE THE PIPING TO MOVE
AND DISTURB THE EXISTING BUILDINGS FOOTINGS AND FOUNDATIONS.
10 10
SITE UTILITIES PLAN
EXISTING CONCRETE MH TO REMAIN; BUILDING'S NEW SEWER PIPING
SHALL BE CONNECTED TO THIS MH; EXISTING SEWER PIPING COMING
IN SHALL BE REMOVED AND HOLES PLUGGED; EXISTING 8" INV OUT
SHALL REMAIN OPERATIONAL FOR BOTH BUILDINGS' SEWER UTILITY;
COORDINATE W/ PLUMBING
NEW SIDEWALK -
SEE LANDSCAPE
PLAN
NEW SIDEWALK -
SEE LANDSCAPE
PLAN
NEW SIDEWALK -
SEE LANDSCAPE
PLAN
PROTECT THE EXISTING CONCRETE ROLLED CURB, INCLUDING CONCRETE
ROADWAY
PROTECT THE EXISTING CONCRETE RETAINING WALL, INCLUDING IT'S
FOOTING/FOUNDATION13
MH
AREA OF DISTURBED EARTH IS LESS THAN 1 ACRE. WHILE AN SESC AUTHORIZATION TO
PROCEED IS NOT REQUIRED, THE CONTRACTOR IS TO REGULARLY SWEEP STREETS AND
SIDEWALKS OF TRACKOFF AND RESTORE SITE WHERE IMPACTED BY CONSTRUCTION
ACTIVITIES. CONTRACTOR TO INSTALL SILT FENCE WHERE INDICATED ON PLANS
UPON COMPLETION, ALL EXISTING EXCESS SOILS SHALL BE SPREAD EVENLY ON THE
PROJECT SITE, GRADED ACCORDINGLY AND SEEDED TO ESTABLISH GRASS. THIS SOIL
DISTRIBUTION SHALL BE NOTED ON THE PROJECT AS-BUILTS.
IT IS THE INTENT TO INSTALL THE CONCRETE SIDEWALK SO THAT IT MEETS THE
ELEVATIONS OF THE EXISTING ABUTTING SIDEWALK/SLABS. IT IS THE INTENT TO INSTALL
THE CONCRETE SIDEWALKS WITH MINIMAL REGRADING, FOLLOWING THE EXISTING
NATURAL CONTOURS. PROVIDE GRANULAR FILL IN LOCATIONS NEEDING SOIL TO BRING
GRADES UP TO THE LEVEL THAT THIS CAN BE ACCOMPLISHED.
CARE SHALL BE TAKEN NOT TO DISTURB U.G. UTILITIES. COORDINATE WITH CAMP
GRAYLING ENGINEERING STAFF FOR LOCATIONS.
ALL DISTURBED AREAS SHALL BE REGRADED; INSTALL AS NEEDED TOPSOIL THEN APPLY
SEED AND MULCH.
GENERAL NOTES:
BURIAL DEPTHS BELOW GRADE*
*FOR ALL CAMP ELECTRICAL & COMMUNICATIONS SYSTEMS,
THESE MEASUREMENTS ARE BELOW FINISHED GRADE.
*TO BE USED FOR NEW INSTALLATIONS ONLY, VERIFY ALL EXISTING
DEPTHS AND LOCATIONS
ELECTRICAL
40" 36"
TELEPHONE
30"
CATV
30"
FIBER OPTIC
30"
PRIMARY
ELECTRICAL
SECONDARY
AutoCAD SHX Text edge of 544MA (72'-8" off 542Q)
AutoCAD SHX Text N
AutoCAD SHX Text W
AutoCAD SHX Text E
AutoCAD SHX Text S
AutoCAD SHX Text N
AutoCAD SHX Text W
AutoCAD SHX Text E
AutoCAD SHX Text S
AutoCAD SHX Text
TUEBOR
AutoCAD SHX Text U
AutoCAD SHX Text S
AutoCAD SHX Text Q
AutoCAD SHX Text U
AutoCAD SHX Text E
AutoCAD SHX Text R
AutoCAD SHX Text C
AutoCAD SHX Text I
AutoCAD SHX Text U
AutoCAD SHX Text P
AutoCAD SHX Text I
AutoCAD SHX Text S
AutoCAD SHX Text R
AutoCAD SHX Text C
AutoCAD SHX Text S
AutoCAD SHX Text N
AutoCAD SHX Text I
AutoCAD SHX Text E
AutoCAD SHX Text N
AutoCAD SHX Text M
AutoCAD SHX Text I
AutoCAD SHX Text S
AutoCAD SHX Text
KAB
AutoCAD SHX Text E
AutoCAD SHX Text R
AutoCAD SHX Text U
AutoCAD SHX Text P
AutoCAD SHX Text L
AutoCAD SHX Text S
AutoCAD SHX Text B
AutoCAD SHX Text U
AutoCAD SHX Text I
AutoCAD SHX Text A
AutoCAD SHX Text N
AutoCAD SHX Text E
AutoCAD SHX Text O
AutoCAD SHX Text E
AutoCAD SHX Text I
AutoCAD SHX Text M
AutoCAD SHX Text L
AutoCAD SHX Text A
AutoCAD SHX Text P
AutoCAD SHX Text A
AutoCAD SHX Text M
AutoCAD SHX Text C
AutoCAD SHX Text M
AutoCAD SHX Text M
AutoCAD SHX Text U
AutoCAD SHX Text U
AutoCAD SHX Text N
AutoCAD SHX Text
PRELIMINARY
AutoCAD SHX Text
CONSTRUCTION
AutoCAD SHX Text
FINAL RECORD
AutoCAD SHX Text
DATE
AutoCAD SHX Text
ISSUED FOR
AutoCAD SHX Text
INDEX CODE
AutoCAD SHX Text
PROJECT
AutoCAD SHX Text
IDENTIFICATION NO.
AutoCAD SHX Text
SHEET
AutoCAD SHX Text
DESIGNED
AutoCAD SHX Text
DRAWN
AutoCAD SHX Text
CHECKED
AutoCAD SHX Text
APPROVED
AutoCAD SHX Text
DEPARTMENT OF TECHNOLOGY, MANAGEMENT AND BUDGET
AutoCAD SHX Text
PROCUREMENT AND REAL ESTATE SERVICES ADMINISTRATION
AutoCAD SHX Text
ADAM LACH RA, DIRECTOR
AutoCAD SHX Text
JDJ
AutoCAD SHX Text
AJP
AutoCAD SHX Text
KAB
KAB
2 2
1 1
MM
TYPE A
GRATE
EXCAVATE AS NEEDED TO INSTALL 2" X 24"
RIGID BOARD INSULATION TO THE ENTIRE
PERIMETER OF THE FOUNDATION UNLESS
OTHERWISE NOTED ON THIS PLAN; INSTALL AS
DETAILED; BACKFILL; COORDINATE WITH NEW
SIDEWALK INSTALLATION AND THE
INSTALLATION OF NEW LANDSCAPING STONE
TYPE A
GRATE
TYPE A
GRATE
TYPE B
GRATE
TYPE B
GRATE
TYPE A
GRATE
FORM AND POUR GRATE
CONCRETE SLAB
INDEPENDENT OF NEW
SIDEWALK; GRATE OPENING
SHALL BE CENTERED IN THIS
NEW SLAB; SEE DETAILS
SHEET C-4; TYPICAL TYPE A
GRATE
POSSIBLE EXISTING DOWELS
APPROX. 18" O.C. AT DOOR
THRESHOLD - DO NOT
DISTURB; INCORPORATE INTO
NEW VENEER WALL
REMOVE EXISTING CONCRETE SLAB AND INSTALL
NEW CONCRETE SLAB AND STEEL GRATE TYPE B
AS DETAILED ON SHEET C-4 PRIOR TO INSTALLING
THE NEW CONCRETE SLAB, INSTALL 2" X 24"
FOUNDATION INSULATION UNDER NEW SLAB AT
PERIMETER AS SHOWN IN THE DETAIL, SHEET C-4
REMOVE EXISTING CONCRETE SLAB AND INSTALL
NEW CONCRETE SLAB AND STEEL GRATE TYPE B AS
DETAILED ON SHEET C-4 PRIOR TO INSTALLING THE
NEW CONCRETE SLAB, INSTALL 2" X 24" FOUNDATION
INSULATION UNDER NEW SLAB AT PERIMETER AS
SHOWN IN THE DETAIL, SHEET C-4
SIDEWALK TO REMAIN
SIDEWALK TO REMAIN
SIDEWALK TO REMAIN
EXCAVATE AS NEEDED TO INSTALL 2" X 24"
RIGID BOARD INSULATION TO THE ENTIRE
PERIMETER OF THE FOUNDATION UNLESS
OTHERWISE NOTED ON THIS PLAN; INSTALL AS
DETAILED; BACKFILL; COORDINATE WITH NEW
SIDEWALK INSTALLATION AND THE
INSTALLATION OF NEW LANDSCAPING STONE
FORM AND POUR GRATE CONCRETE
SLAB INDEPENDENT OF NEW
SIDEWALK; GRATE OPENING SHALL BE
CENTERED IN THIS NEW SLAB; SEE
DETAILS SHEET C-4; TYPICAL TYPE A
GRATE
EXCAVATE AS REQUIRED
TO INSTALL NEW
CONCRETE SLAB AND
STEEL GRATE AS DETAILED
EXCAVATE AS NEEDED TO INSTALL 2" X 24" RIGID
BOARD INSULATION TO THE ENTIRE PERIMETER OF
THE FOUNDATION UNLESS OTHERWISE NOTED ON
THIS PLAN; INSTALL AS DETAILED; BACKFILL;
COORDINATE WITH NEW SIDEWALK INSTALLATION
AND THE INSTALLATION OF NEW LANDSCAPING
STONE
EXCAVATE AS NEEDED TO INSTALL 2" X 24"
RIGID BOARD INSULATION TO THE ENTIRE
PERIMETER OF THE FOUNDATION UNLESS
OTHERWISE NOTED ON THIS PLAN; INSTALL AS
DETAILED; BACKFILL; COORDINATE WITH NEW
SIDEWALK INSTALLATION AND THE
INSTALLATION OF NEW LANDSCAPING STONE
AS NEEDED, SAWCUT AND
REMOVE PORTION OF
EXISTING SIDEWALK
LEADING TO 536Q; INSTALL
NEW SIDEWALK AS SHOWN;
MEET GRADE & ABUT TO
SIDEWALK TO REMAIN
AS NEEDED, SAWCUT
AND REMOVE PORTION
OF EXISTING SIDEWALK
LEADING TO 538Q;
INSTALL NEW
SIDEWALK AS SHOWN;
MEET GRADE & ABUT
TO SIDEWALK TO
REMAIN; INSTALL
STEP(S) AS NEEDED
AS NEEDED, SAWCUT AND REMOVE
PORTION OF EXISTING SIDEWALK
LEADING TO 536Q; INSTALL NEW
SIDEWALK AS SHOWN; MEET GRADE
& ABUT TO SIDEWALK TO REMAIN;
INSTALL A STEP(S) AS NEEDED
INSTALL LANDSCAPING METAL
EDGING AS SPECIFIED FROM BLDG
EDGE TO NEW CONCRETE SLAB; A
STONE TO GRASS BORDER
NEW CONCRETE ENTRANCE SLAB;
TYPICAL
NEW CONCRETE ENTRANCE SLAB;
TYPICAL
POSSIBLE EXISTING
DOWELS APPROX. 18" O.C.
AT DOOR THRESHOLD - DO
NOT DISTURB;
INCORPORATE INTO NEW
VENEER WALL
EXISTING CONCRETE SLAB TO REMAIN;
CONTRACTOR SHALL TAKE PRECAUTIONS TO
PROTECT CONCRETE; THE CONTRACTOR SHALL
REPLACE AT HIS OWN COST IF DAMAGE
OCCURS DURING 536Q WORK
POSSIBLE EXISTING
ELECTRICAL/COMM
HANDHOLE TO REMAIN;
PRECAUTIONS SHOULD BE
TAKEN NOT TO DISTURB
EXISTING 538Q LANDSCAPE EDGING AND
LANDSCAPE STONE TO REMAIN; CONTRACTOR
SHALL TAKE PRECAUTIONS TO PROTECT; THE
CONTRACTOR SHALL REPLACE AT HIS OWN
COST IF DAMAGE OCCURS DURING 536Q WORK
(TYPICAL)
EXISTING 538Q LANDSCAPE EDGING AND
LANDSCAPE STONE TO REMAIN; CONTRACTOR
SHALL TAKE PRECAUTIONS TO PROTECT; THE
CONTRACTOR SHALL REPLACE AT HIS OWN
COST IF DAMAGE OCCURS DURING 536Q WORK
EDGE OF 534Q
EDGE OF 538Q
EDGE OF 538Q
INSTALL LANDSCAPING METAL
EDGING AS SPECIFIED FROM BLDG
EDGE TO NEW CONCRETE SLAB; A
STONE TO GRASS BORDER
EXISTING 538Q LANDSCAPE RETAINING WALL TO REMAIN;
CONTRACTOR SHALL TAKE PRECAUTIONS TO PROTECT; THE
CONTRACTOR SHALL REPLACE AT HIS OWN COST IF
DAMAGE OCCURS DURING 536Q WORK (TYPICAL)
AS NEEDED, SAWCUT AND
REMOVE PORTION OF EXISTING
SIDEWALK LEADING FROM 536Q;
INSTALL NEW SIDEWALK AS
SHOWN; MEET GRADE & ABUT TO
SIDEWALK TO REMAIN; REPLACE
EXISTING SIDEWALK TO REMAIN IF
IT BECOMES DAMAGED OCCURS
DURING 540Q WORK (TYPICAL)
EDGE OF 538Q
SIDEWALK TO REMAIN
**IF EXISTING SIDEWALK TO REMAIN BECOMES
DAMAGED DURING CONSTRUCTION, THE
CONTRACTOR SHALL REPLACE WITH NEW AS
DETAILED AND SPECIFIED
4'-0"
6' -0
4'-0"
6' -0
6' -0
4'-0"
6' -0
4'-0"
EDGE OF 534QEDGE OF 534Q
5'-0"
5'-0" 5'-0"6'-0"
EXISTING SURFACE SHUT OFF BOX TO
THE DOMESTIC WATER SERVICE; SEE
SITE UTILITIES
4' -0
7'-4"
5' -0
3 3
SIDEWALK TO REMAIN
INSTALL COLORED LANDSCAPING
INTERLOCKING RETAINING BLOCK
(12" X 6") WALL TO 24" HIGH;
TYPICAL 2 LOCATIONS
3'-6"
4' -0
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SILT FENCE SEE DETAILS
AND NOTES 2/C-2, TYP.
16'-0"
4' -0
16'-0"16'-0"
135° 135°
12'-8"
5'-2"
12'-8"
5'- 2"
7' -0
4' -0
7'
-0
3'-6"
190'-4" +/- FIELD VERIFY
4'-0"
'-0
FI
EL
D V
ER
IF
Y
'-0
FI
EL
D V
ER
IF
Y
536Q FOUNDATION INSULATION/LANDSCAPE PLAN
CONCRETE SIDEWALKS AND SLABS
SCALE 1/8" = 1'-0"
SHADED AREA REPRESENTS NEW CONCRETE SLAB, SIDEWALK OR
ENTRANCE SLAB.
AREA OF DISTURBED EARTH IS LESS THAN 1 ACRE. WHILE AN SESC
AUTHORIZATION TO PROCEED IS NOT REQUIRED, THE CONTRACTOR IS
TO REGULARLY SWEEP STREETS AND SIDEWALKS OF TRACKOFF AND
RESTORE SITE WHERE IMPACTED BY CONSTRUCTION ACTIVITIES.
CONTRACTOR TO INSTALL SILT FENCE WHERE INDICATED ON PLANS
UPON COMPLETION, ALL EXISTING EXCESS SOILS SHALL BE SPREAD
EVENLY ON THE PROJECT SITE, GRADED ACCORDINGLY AND SEEDED
TO ESTABLISH GRASS. THIS SOIL DISTRIBUTION SHALL BE NOTED ON
THE PROJECT AS-BUILTS.
IT IS THE INTENT TO INSTALL THE CONCRETE SIDEWALK SO THAT IT
MEETS THE ELEVATIONS OF THE EXISTING ABUTTING SIDEWALK/SLABS.
IT IS THE INTENT TO INSTALL THE CONCRETE SIDEWALKS WITH MINIMAL
REGRADING, FOLLOWING THE EXISTING NATURAL CONTOURS. PROVIDE
GRANULAR FILL IN LOCATIONS NEEDING SOIL TO BRING GRADES UP TO
THE LEVEL THAT THIS CAN BE ACCOMPLISHED.
CARE SHALL BE TAKEN NOT TO DISTURB U.G. UTILITIES. COORDINATE
WITH CAMP GRAYLING ENGINEERING STAFF FOR LOCATIONS.
ALL DISTURBED AREAS SHALL BE REGRADED; INSTALL AS NEEDED
TOPSOIL THEN APPLY SEED AND MULCH.
UTILITIES
989-344-6184
72 HOURS
(3 WORKING DAYS)
CALL Mr. Halcomb
BEFORE YOU DIGC.G.
MICHAEL HALCOMB
CAMP GRAYLING ENGINEERING
KAB'17
KNOW WHAT'S BELOW.
CALL BEFORE YOU DIG.
C-2
GENERAL NOTES:
MATCH LINE IF 534Q RENOVATIONS
BECOME A CONTRACT ADD ON
MATCH LINE IF 534Q RENOVATIONS
BECOME A CONTRACT ADD ON
D
EP
AR
TM
EN
T
O F
M
IL
IT
AR
Y
AN
D V
ET
ER
AN
S
AF
FA
IR
S
ST
AT
E O
F M
IC
H
IG
AN
D
ES
IG
N
A N
D C
O N
ST
R
U C
TI
O
N D
IV
IS
IO
N
B1
C -2
R
EN
O
VA
TE
B
U
IL
D
IN
G
Q
/5
Q C
AM
P
G R
AY
LI
N G
J O
IN
T
M
AN
EU
VE
R T
R
AI
N
IN
G C
EN
AY
LI
N G
, M
IC
H
IG
AN
B1
Q
FOUNDATION INSULATION/
LANDSCAPING KEY NOTES:
EXCAVATE AS REQUIRED TO INSTALL NEW WASHED AGGREGATE. AGGREGATE SIZE SHALL BE 100% PASSING THE 2" SIEVE TO 100% RETAINED ON 1-1/2" SIEVE; GRADE AREA AS REQUIRED TO SLOPE AWAY FROM BUILDING. COORDINATE W/ WALL SECTION DETAILS, DO NOT COVER WEEP HOLES IN
MASONRY WHEN BACKFILLING. SEE DETAIL SHEET C-4.
SEE GRATE DETAILS SHEET C-4.
NEW CONCRETE SLAB TO BE FORMED AND POURED INDEPENDENT OF CONCRETE SIDEWALKS.
NEW CONCRETE SIDEWALK, SEE DETAIL SHEET C-4
NEW CONDENSING UNIT CONCRETE MOUNTING SLAB, COORD W/ MECH CONTRACTOR AND SIZE TO
FIT CONDENSING UNIT AND ELEC. DISCONNECT RACK PLUS 4" ON ALL SIDES, SEE DETAIL SHEET C-4, AND DETAIL SHEET E-2
NEW 8"Ø MIN. PVC PIPE TRENCH. SEE DETAIL SHEET C-4
SILT FENCE DETAILS/NOTES
NTSC-2
2 536Q FOUNDATION INSULATION AND LANDSCAPE PLAN
AutoCAD SHX Text N
AutoCAD SHX Text W
AutoCAD SHX Text E
AutoCAD SHX Text S
AutoCAD SHX Text N
AutoCAD SHX Text W
AutoCAD SHX Text E
AutoCAD SHX Text S
AutoCAD SHX Text
TUEBOR
AutoCAD SHX Text U
AutoCAD SHX Text S
AutoCAD SHX Text Q
AutoCAD SHX Text U
AutoCAD SHX Text E
AutoCAD SHX Text R
AutoCAD SHX Text C
AutoCAD SHX Text I
AutoCAD SHX Text U
AutoCAD SHX Text P
AutoCAD SHX Text I
AutoCAD SHX Text S
AutoCAD SHX Text R
AutoCAD SHX Text C
AutoCAD SHX Text S
AutoCAD SHX Text N
AutoCAD SHX Text I
AutoCAD SHX Text E
AutoCAD SHX Text N
AutoCAD SHX Text M
AutoCAD SHX Text I
AutoCAD SHX Text S
AutoCAD SHX Text
KAB
AutoCAD SHX Text E
AutoCAD SHX Text R
AutoCAD SHX Text U
AutoCAD SHX Text P
AutoCAD SHX Text L
AutoCAD SHX Text S
AutoCAD SHX Text B
AutoCAD SHX Text U
AutoCAD SHX Text I
AutoCAD SHX Text A
AutoCAD SHX Text N
AutoCAD SHX Text E
AutoCAD SHX Text O
AutoCAD SHX Text E
AutoCAD SHX Text I
AutoCAD SHX Text M
AutoCAD SHX Text L
AutoCAD SHX Text A
AutoCAD SHX Text P
AutoCAD SHX Text A
AutoCAD SHX Text M
AutoCAD SHX Text C
AutoCAD SHX Text M
AutoCAD SHX Text M
AutoCAD SHX Text U
AutoCAD SHX Text U
AutoCAD SHX Text N
AutoCAD SHX Text
PRELIMINARY
AutoCAD SHX Text
CONSTRUCTION
AutoCAD SHX Text
FINAL RECORD
AutoCAD SHX Text
DATE
AutoCAD SHX Text
ISSUED FOR
AutoCAD SHX Text
INDEX CODE
AutoCAD SHX Text
PROJECT
AutoCAD SHX Text
IDENTIFICATION NO.
AutoCAD SHX Text
SHEET
AutoCAD SHX Text
DESIGNED
AutoCAD SHX Text
DRAWN
AutoCAD SHX Text
CHECKED
AutoCAD SHX Text
APPROVED
AutoCAD SHX Text
DEPARTMENT OF TECHNOLOGY, MANAGEMENT AND BUDGET
AutoCAD SHX Text
PROCUREMENT AND REAL ESTATE SERVICES ADMINISTRATION
AutoCAD SHX Text
ADAM LACH RA, DIRECTOR
AutoCAD SHX Text
JDJ
AutoCAD SHX Text
AJP
AutoCAD SHX Text
KAB
AutoCAD SHX Text
KAB
AutoCAD SHX Text SILT FENCE NOTES 1. INSTALL PARALLEL TO A CONTOUR. INSTALL PARALLEL TO A CONTOUR. 2. SILT FENCE SHALL BE MADE OF WOVEN GEOTEXTILE FABRIC. SILT FENCE SHALL BE MADE OF WOVEN GEOTEXTILE FABRIC. 3. DIG A 6" TRENCH ALONG THE AREA WHERE THE FENCE IS TO BE DIG A 6" TRENCH ALONG THE AREA WHERE THE FENCE IS TO BE INSTALLED. 4. PLACE 6" OF THE SILT FENCE BOTTOM FLAP INTO THE TRENCH. PLACE 6" OF THE SILT FENCE BOTTOM FLAP INTO THE TRENCH. 5. BACKFILL THE TRENCH WITH SOIL AND COMPACT THE SOIL ON BOTH SIDES. BACKFILL THE TRENCH WITH SOIL AND COMPACT THE SOIL ON BOTH SIDES. CREATE A SMALL RIDGE ON THE UP-SLOPE SIDE OF THE FENCE. 6. INSTALL WOODEN STAKES 6 - 10' APART AND DRIVE INTO THE GROUND A INSTALL WOODEN STAKES 6 - 10' APART AND DRIVE INTO THE GROUND A MINIMUM OF 12". 7. STAPLE THE GEOTEXTILE FABRIC TO THE WOODEN STAKES. STAPLE THE GEOTEXTILE FABRIC TO THE WOODEN STAKES. 8. JOIN SECTIONS OF SILT FENCE BY WRAPPING ENDS TOGETHER (SEE JOIN SECTIONS OF SILT FENCE BY WRAPPING ENDS TOGETHER (SEE DRAWING). 9. INSPECT FREQUENTLY AND IMMEDIATELY AFTER EACH STORM EVENT. CHECK INSPECT FREQUENTLY AND IMMEDIATELY AFTER EACH STORM EVENT. CHECK SEVERAL TIMES DURING PROLONGED STORM EVENTS. IF NECESSARY, REPAIR IMMEDIATELY. 10. IF THE SEDIMENT HAS REACHED 1/3 THE HEIGHT OF THE FENCE, THE SOIL IF THE SEDIMENT HAS REACHED 1/3 THE HEIGHT OF THE FENCE, THE SOIL SHALL BE REMOVED AND DISPOSED OF IN A STABLE UPLAND SITE. 11. THE FENCE SHALL BE RE-INSTALLED IF WATER IS SEEPINGUNDERNEATH IT THE FENCE SHALL BE RE-INSTALLED IF WATER IS SEEPINGUNDERNEATH IT OR IF THE FENCE HAS BECOME INEFFECTIVE. 12. SILT FENCE SHALL BE REMOVED ONCE VEGETATION IS ESTABLISHED AND SILT FENCE SHALL BE REMOVED ONCE VEGETATION IS ESTABLISHED AND UP-SLOPE AREA HAS STABILIZED.
AutoCAD SHX Text
ROLL JOINTS
AutoCAD SHX Text
SILT FENCE B
AutoCAD SHX Text
SILT FENCE A
AutoCAD SHX Text
6" X 6" ANCHOR TRENCH
AutoCAD SHX Text
UNDISTURBED VEGETATION
AutoCAD SHX Text
SHEET FLOW
AutoCAD SHX Text
GEOTEXTILE FILTER FABRIC FASTENED ON UPHILL SIDE TOWARDS EARTH CHANGE
AutoCAD SHX Text
RIDGE OF COMPACTED EARTH ON UPHILL SIDE OF FILTER FABRIC
AutoCAD SHX Text
FABRIC TO BE WRAPPED AROUND FENCE POST
AutoCAD SHX Text
ROLL JOINT
FENCE POST DRIVEN INTO GROUND 1' MIN.
MM
4'-0"
6' -0
4'-0"
6' -0
6' -0
4'-0"
6' -0
4'-0"
5'-0"
5'-0" 5'-0"6'-0"
16'-0"
4' -0
16'-0"
4' -0
7'-4"
5' -0
2 2
1 1
3 3
TYPE A
GRATE
EXCAVATE AS NEEDED TO INSTALL 2" X 24"
RIGID BOARD INSULATION TO THE ENTIRE
PERIMETER OF THE FOUNDATION UNLESS
OTHERWISE NOTED ON THIS PLAN; INSTALL AS
DETAILED; BACKFILL; COORDINATE WITH NEW
SIDEWALK INSTALLATION AND THE
INSTALLATION OF NEW LANDSCAPING STONE
TYPE A
GRATE
TYPE A
GRATE
TYPE B
GRATE
TYPE B
GRATE
TYPE A
GRATE
FORM AND POUR GRATE
CONCRETE SLAB
INDEPENDENT OF NEW
SIDEWALK; GRATE OPENING
SHALL BE CENTERED IN THIS
NEW SLAB; SEE DETAILS
SHEET C-4; TYPICAL TYPE A
GRATE
POSSIBLE EXISTING DOWELS
APPROX. 18" O.C. AT DOOR
THRESHOLD - DO NOT
DISTURB; INCORPORATE INTO
NEW VENEER WALL
REMOVE EXISTING CONCRETE SLAB AND INSTALL
NEW CONCRETE SLAB AND STEEL GRATE TYPE B
AS DETAILED ON SHEET C-4 PRIOR TO INSTALLING
THE NEW CONCRETE SLAB, INSTALL 2" X 24"
FOUNDATION INSULATION UNDER NEW SLAB AT
PERIMETER AS SHOWN IN THE DETAIL, SHEET C-4
REMOVE EXISTING CONCRETE SLAB AND INSTALL
NEW CONCRETE SLAB AND STEEL GRATE TYPE B AS
DETAILED ON SHEET C-4 PRIOR TO INSTALLING THE
NEW CONCRETE SLAB, INSTALL 2" X 24" FOUNDATION
INSULATION UNDER NEW SLAB AT PERIMETER AS
SHOWN IN THE DETAIL, SHEET C-4
EXISTING CONCRETE RETAINING
WALL TO REMAIN
SEE C-2
EXCAVATE AS NEEDED TO INSTALL 2" X 24"
RIGID BOARD INSULATION TO THE ENTIRE
PERIMETER OF THE FOUNDATION UNLESS
OTHERWISE NOTED ON THIS PLAN; INSTALL AS
DETAILED; BACKFILL; COORDINATE WITH NEW
SIDEWALK INSTALLATION AND THE
INSTALLATION OF NEW LANDSCAPING STONE
FORM AND POUR GRATE
CONCRETE SLAB
INDEPENDENT OF NEW
SIDEWALK; GRATE
OPENING SHALL BE
CENTERED IN THIS NEW
SLAB; SEE DETAILS
SHEET C-4; TYPICAL
TYPE A GRATE
EXCAVATE AS REQUIRED
TO INSTALL NEW
CONCRETE SLAB AND
STEEL GRATE AS DETAILED
EXCAVATE AS NEEDED TO INSTALL 2" X 24" RIGID
BOARD INSULATION TO THE ENTIRE PERIMETER OF
THE FOUNDATION UNLESS OTHERWISE NOTED ON
THIS PLAN; INSTALL AS DETAILED; BACKFILL;
COORDINATE WITH NEW SIDEWALK INSTALLATION
AND THE INSTALLATION OF NEW LANDSCAPING
STONE
EXCAVATE AS NEEDED TO INSTALL 2" X 24"
RIGID BOARD INSULATION TO THE ENTIRE
PERIMETER OF THE FOUNDATION UNLESS
OTHERWISE NOTED ON THIS PLAN; INSTALL AS
DETAILED; BACKFILL; COORDINATE WITH NEW
SIDEWALK INSTALLATION AND THE
INSTALLATION OF NEW LANDSCAPING STONE
AS NEEDED, SAWCUT
AND REMOVE PORTION
OF EXISTING SIDEWALK
LEADING TO 538Q;
INSTALL NEW
SIDEWALK AS SHOWN;
MEET GRADE & ABUT
TO SIDEWALK TO
REMAIN; INSTALL
STEP(S) AS NEEDED
INSTALL LANDSCAPING METAL
EDGING FROM BLDG EDGE TO NEW
CONCRETE SLAB; A STONE TO GRASS
BORDER
NEW CONCRETE ENTRANCE SLAB;
TYPICAL
NEW CONCRETE ENTRANCE SLAB;
TYPICAL
POSSIBLE EXISTING
DOWELS APPROX. 18" O.C.
AT DOOR THRESHOLD - DO
NOT DISTURB;
INCORPORATE INTO NEW
VENEER WALL
SEE SHEET C-2 FOR WORK AT 536Q
EDGE OF 536Q
EDGE OF 536Q
INSTALL LANDSCAPING METAL
EDGING AS SPECIFIED FROM BLDG
EDGE TO NEW CONCRETE SLAB; A
STONE TO GRASS BORDER
SEE C-2
EDGE OF 536Q
**IF EXISTING CONCRETE RETAINING WALL OR IT'S
FOOTING/FOUNDATION BECOMES DAMAGED
DURING CONSTRUCTION, THE CONTRACTOR SHALL
REPLACE WITH NEW AS DETAILED AND SPECIFIED
EXISTING SURFACE SHUT OFF BOX TO
THE DOMESTIC WATER SERVICE; SEE
SITE UTILITIES
SIDEWALK TO REMAIN
EXISTING CONCRETE RETAINING
WALL TO REMAIN
16'-0"
INSTALL COLORED LANDSCAPING
INTERLOCKING RETAINING BLOCK (12" X
6") WALL TO 24" HIGH; TYPICAL 2
LOCATIONS, SEE DETAIL SHEET C-4
FORM AND POUR GRATE
CONCRETE SLAB
INDEPENDENT OF NEW
SIDEWALK; GRATE
OPENING SHALL BE
CENTERED IN THIS NEW
SLAB; SEE DETAILS
SHEET C-4; TYPICAL TYPE
A GRATE
NEW CONCRETE ENTRANCE SLAB;
TYPICAL
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
135° 135°
12'-8" 5'-2"
12'-8"
5'- 2"
7' -0
4' -0
7'
-0
'-1
0"
FI
EL
D
V
ER
IF
Y
'-0
8'
-1 0"
190'-4"
EXISTING SANITARY MANHOLE, SEE
SITE UTILITIES
SILT FENCE SEE
DETAILS AND
NOTES 2/C-2
EXISTING ROAD
4'-0"
5' -0
534Q FOUNDATION INSULATION/LANDSCAPING PLAN
CONCRETE SIDEWALKS AND SLABS
SCALE 1/8" = 1'-0"
UTILITIES
989-344-6184
72 HOURS
(3 WORKING DAYS)
CALL Mr. Halcomb
BEFORE YOU DIGC.G.
MICHAEL HALCOMB
CAMP GRAYLING ENGINEERING
KAB'17
KNOW WHAT'S BELOW.
CALL BEFORE YOU DIG.
C-3
MATCH LINE IF 534Q RENOVATIONS
BECOME A CONTRACT ADD ON
MATCH LINE IF 534Q RENOVATIONS
BECOME A CONTRACT ADD ON
D
EP
AR
TM
EN
T
O F
M
IL
IT
AR
Y
AN
D V
ET
ER
AN
S
AF
FA
IR
S
ST
AT
E O
F M
IC
H
IG
AN
D
ES
IG
N
A N
D C
O N
ST
R
U C
TI
O
N D
IV
IS
IO
N
B1
C -3
AJ
P
R
EN
O
VA
TE
B
U
IL
D
IN
G
Q
/5
Q C
AM
P
G R
AY
LI
N G
J O
IN
T
M
AN
EU
VE
R T
R
AI
N
IN
G C
EN
AY
LI
N G
, M
IC
H
IG
AN
SHADED AREA REPRESENTS NEW CONCRETE SLAB, SIDEWALK OR
ENTRANCE SLAB.
AREA OF DISTURBED EARTH IS LESS THAN 1 ACRE. WHILE AN SESC
AUTHORIZATION TO PROCEED IS NOT REQUIRED, THE CONTRACTOR IS
TO REGULARLY SWEEP STREETS AND SIDEWALKS OF TRACKOFF AND
RESTORE SITE WHERE IMPACTED BY CONSTRUCTION ACTIVITIES.
CONTRACTOR TO INSTALL SILT FENCE WHERE INDICATED ON PLANS
UPON COMPLETION, ALL EXISTING EXCESS SOILS SHALL BE SPREAD
EVENLY ON THE PROJECT SITE, GRADED ACCORDINGLY AND SEEDED
TO ESTABLISH GRASS. THIS SOIL DISTRIBUTION SHALL BE NOTED ON
THE PROJECT AS-BUILTS.
IT IS THE INTENT TO INSTALL THE CONCRETE SIDEWALK SO THAT IT
MEETS THE ELEVATIONS OF THE EXISTING ABUTTING SIDEWALK/SLABS.
IT IS THE INTENT TO INSTALL THE CONCRETE SIDEWALKS WITH MINIMAL
REGRADING, FOLLOWING THE EXISTING NATURAL CONTOURS. PROVIDE
GRANULAR FILL IN LOCATIONS NEEDING SOIL TO BRING GRADES UP TO
THE LEVEL THAT THIS CAN BE ACCOMPLISHED.
CARE SHALL BE TAKEN NOT TO DISTURB U.G. UTILITIES. COORDINATE
WITH CAMP GRAYLING ENGINEERING STAFF FOR LOCATIONS.
ALL DISTURBED AREAS SHALL BE REGRADED; INSTALL AS NEEDED
TOPSOIL THEN APPLY SEED AND MULCH.
GENERAL NOTES:
534Q FOUNDATION INSULATION AND LANDSCAPE PLAN
FOUNDATION INSULATION/
LANDSCAPING KEY NOTES:
EXCAVATE AS REQUIRED TO INSTALL NEW WASHED AGGREGATE OVER LANDSCAPING FABRIC.
AGGREGATE SIZE SHALL BE 100% PASSING THE 2" SIEVE TO 100% RETAINED ON 1-1/2" SIEVE; GRADE AREA AS REQUIRED TO SLOPE AWAY FROM BUILDING. COORDINATE W/ WALL SECTION DETAILS, DO
NOT COVER WEEP HOLES IN MASONRY WHEN BACKFILLING. SEE DETAIL SHEET C-4.
SEE GRATE DETAILS SHEET C-4.
NEW CONCRETE SLAB TO BE FORMED AND POURED INDEPENDENT OF CONCRETE SIDEWALKS.
NEW CONCRETE SIDEWALK, SEE DETAIL SHEET C-4
NEW CONDENSING UNIT CONCRETE MOUNTING SLAB, COORD W/ MECH CONTRACTOR AND SIZE TO
FIT CONDENSING UNIT AND ELEC. DISCONNECT RACK PLUS 4" ON ALL SIDES, SEE DETAIL SHEET C-4, AND DETAIL SHEET E-2
NEW 8"Ø MIN. PVC PIPE TRENCH. SEE DETAIL SHEET C-4
AutoCAD SHX Text N
AutoCAD SHX Text W
AutoCAD SHX Text E
AutoCAD SHX Text S
AutoCAD SHX Text N
AutoCAD SHX Text W
AutoCAD SHX Text E
AutoCAD SHX Text S
AutoCAD SHX Text
TUEBOR
AutoCAD SHX Text U
AutoCAD SHX Text S
AutoCAD SHX Text Q
AutoCAD SHX Text U
AutoCAD SHX Text E
AutoCAD SHX Text R
AutoCAD SHX Text C
AutoCAD SHX Text I
AutoCAD SHX Text U
AutoCAD SHX Text P
AutoCAD SHX Text I
AutoCAD SHX Text S
AutoCAD SHX Text R
AutoCAD SHX Text C
AutoCAD SHX Text S
AutoCAD SHX Text N
AutoCAD SHX Text I
AutoCAD SHX Text E
AutoCAD SHX Text N
AutoCAD SHX Text M
AutoCAD SHX Text I
AutoCAD SHX Text S
AutoCAD SHX Text
KAB
AutoCAD SHX Text E
AutoCAD SHX Text R
AutoCAD SHX Text U
AutoCAD SHX Text P
AutoCAD SHX Text L
AutoCAD SHX Text S
AutoCAD SHX Text B
AutoCAD SHX Text U
AutoCAD SHX Text I
AutoCAD SHX Text A
AutoCAD SHX Text N
AutoCAD SHX Text E
AutoCAD SHX Text O
AutoCAD SHX Text E
AutoCAD SHX Text I
AutoCAD SHX Text M
AutoCAD SHX Text L
AutoCAD SHX Text A
AutoCAD SHX Text P
AutoCAD SHX Text A
AutoCAD SHX Text M
AutoCAD SHX Text C
AutoCAD SHX Text M
AutoCAD SHX Text M
AutoCAD SHX Text U
AutoCAD SHX Text U
AutoCAD SHX Text N
AutoCAD SHX Text
PRELIMINARY
AutoCAD SHX Text
CONSTRUCTION
AutoCAD SHX Text
FINAL RECORD
AutoCAD SHX Text
DATE
AutoCAD SHX Text
ISSUED FOR
AutoCAD SHX Text
INDEX CODE
AutoCAD SHX Text
PROJECT
AutoCAD SHX Text
IDENTIFICATION NO.
AutoCAD SHX Text
SHEET
AutoCAD SHX Text
DESIGNED
AutoCAD SHX Text
DRAWN
AutoCAD SHX Text
CHECKED
AutoCAD SHX Text
APPROVED
AutoCAD SHX Text
DEPARTMENT OF TECHNOLOGY, MANAGEMENT AND BUDGET
AutoCAD SHX Text
PROCUREMENT AND REAL ESTATE SERVICES ADMINISTRATION
AutoCAD SHX Text
ADAM LACH RA, DIRECTOR
AutoCAD SHX Text
JDJ
AutoCAD SHX Text
AJP
AutoCAD SHX Text
KAB
1' -6
4"4" 4'-0"
10'-8"
6 X 6 - W2.9/W2.9 WWF
6'-0"
4" Min
GRATE DETAIL (TYP) - TYPE A
SCALE 3/4" = 1'-0"
GRATE SECTION (TYP) - TYPE A
(INCLUDING CONCRETE SLAB SECTION)
SCALE 3/4" = 1'-0"
4'-0"
1' -4
2" 1'
-6
4" Min
GRATE SECTION (TYP) - TYPE B
(INCLUDING CONCRETE SLAB SECTION)
SCALE 3/4" = 1'-0"
8" MIN. COMPACTED SAND
GRATE DETAIL (TYP) - TYPE B
SCALE 3/4" = 1'-0"
6'-0"
1' -4
2"
6'-0"
OPENOPEN
BLDG
EDGE
NEW SIDEWALK
CENTER GRATE IN
CENTER OF NEW SLAB
GRATE SHALL BE PLACED IN SLABS FOLLOWING
DIMENSIONS SHOWN ON SHEETS C-2 AND C-3
1-1/4" X 2" X 3/8" L FRAME
FORMED INTO CONCRETE W/
W/3/8"Ø STUD @ 12" O.C
8" MIN. COMPACTED SAND
WELDED STEEL BAR GRATE
(1 1/4" X 1/8") GRATES
SHALL BE REMOVABLE AND
ONE-PIECE UNITS
CONCRETE SIDEWALK
3500PSI MIN. BROOM
FINISH
GRADE
6 X 6 - W2.9/W2.9
WWF
CONCRETE SIDEWALK/SLAB
3500PSI MIN. BROOM
FINISH
4" CONCRETE SIDEWALK
6 X 6 - W2.9/W2.9 WWF
WELDED STEEL BAR GRATE
(1 1/4" X 1/8") GRATES SHALL
BE REMOVABLE AND
ONE-PIECE UNITS
WELDED STEEL BAR
GRATE (1 1/4" X 1/8")
GRATES SHALL BE
REMOVABLE AND
ONE-PIECE UNITS
1-1/4" X 2" X 3/8" L FRAME
FORMED INTO CONCRETE W/
W/3/8"Ø STUD @ 12" O.C
1-1/4" X 2" X 3/8" L FRAME
FORMED INTO CONCRETE W/
W/3/8"Ø STUD @ 12" O.C
1-1/4" X 2" X 3/8" L FRAME
FORMED INTO CONCRETE W/
W/3/8"Ø STUD @ 12" O.C
WELDED STEEL BAR GRATE
(1 1/4" X 1/8") GRATES
SHALL BE REMOVABLE AND
ONE-PIECE UNITS
5'-0"
SIDEWALK SECTION (TYP)
SCALE 3/4" = 1'-0"
4"
*4'-0"/
CONCRETE SIDEWALK
3500PSI MIN. BROOM
FINISH
6 X 6 - W2.9/W2.9 WWF REGRADE SOILS,
INSTALL TOP SOIL,
SEED & MULCH
EXCAVATE AS
NEEDED TO INSTALL
NEW SIDEWALK
8" MINIMUM COMPACTED SAND
*SEE SHEETS C2 & C3 FOR EXACT SIDEWALK WIDTHS
**NEW CONCRETE SIDEWALK AND OR CONCRETE SLAB
UNLESS OTHERWISE NOTED SHALL FOLLOW THE SAME MIN
THICKNESS AND CONCRETE STRENGTH AS SHOWN HERE
EXPANSION
JOINT (E.J.)
SCALE 1 1/2" = 1'-0"
1/2" JOINT W/
1/2" X 3/8" JOINT
SEALANT
4" CONCRETE SIDEWALK
REINFORCED WITH
6 X 6 - W2.9/W2.9 WWF
AT MIDSPAN
INSTALL EJ'S AT 30' INTERVALS
OR AT ANY POSITION WHERE
THERE IS A CHANGE IN
DIRECTION
PREMOLDED JOINT MATERIAL
4"
CONDENSATE SLAB DETAIL
CONCRETE SLAB 3500PSI MIN.
WITH 6 X 6 - W2.9/W2.9 WWF,
BROOM FINISH
8" MINIMUM
COMPACTED SAND
SIZE TO BE LARGER THAN
APPROVED CONDENSING
UNIT & RELATED ELEC.
EQPM. BY 4" ON ALL
SIDES
VARIES
BACKFILL WITH EXCAVATED MATERIAL
TO WITHIN 4" OF FINISH GRADE
INSTALL 1/8" X 4" STEEL PLANTING
BED EDGING
INSTALL 4" TOP SOIL AND SEED AND
MULCH AROUND AREA DISTURBED BY
EXCAVATION
EXCAVATE AND INSTALL 4" THICK WASHED
AGGREGATE (2" < 1-1/2") AROUND THE
PERIMETER OF THE BUILDING
GRADE LINE (VARIES SEE BLDG
ELEVATIONS)
EXCAVATE FOR FOUNDATION WORK AND
INSTALL 2" THICK X 24" FOUNDATION
INSULATION; ADHERE TO BUILDING
FOUNDATION WALL;
SEE STRUCTURAL FOR DETAILS
DOOR OPENING
SEE ARCH.
INSTALL NEW EXPANSION JOINT
MATERIAL AND BACKER ROD FULL
LENGTH OF ABUTTING WALL
INSTALL 8" MIN.
COMPACTED SAND
BASE
FLOOR
BACKFILL WITH EXCAVATED MATERIAL
INSTALL GEOTEXTILE FABRIC;
OVERLAP JOINTS 8" MIN. SECURE IN
PLACE PRIOR TO INSTALLING STONE
INSTALL FOUNDATION
BOARD INSULATION
UNDER EXTENDED
FLASHING AS SPECIFIED
4" CONCRETE ENTRANCE SLAB W/ 6 X 6 - W2.9/W2.9 WWF, BROOM FINISH,
SLOPE AWAY FROM BLDG. 1/4"/1'-0" MIN.; REFER TO STRUCTURAL FOR
DOWELS TO FOUNDATION
SEE LANDSCAPE DRAWINGS FOR ENTRANCE
SLABS REQUIRING GRATES AND REFER TO
GRATE DETAILS THIS SHEET
INSTALL DAMPPROOFING
INSTALL DAMPPROOFING
FOUNDATION WALL;
SEE STRUCTURAL FOR DETAILS
FLOOR
DO NOT COVER WEEP HOLES AND
FLASHING WHEN BACKFILLING AND
ISNTALLING AGGREGATE
BACKFILL WITH EXCAVATED MATERIAL
EXCAVATE FOR FOUNDATION WORK AND
INSTALL 2" THICK X 24" FOUNDATION
INSULATION; ADHERE TO BUILDING
SLOPE AWAY
FROM BLDG.
1/2"/1'-0" MIN.
CONTROL
JOINT (C.J.)
SCALE 1 1/2" = 1'-0"
1/4" X 1" DEEP
SAWED JOINT
INSTALL CJ'S AT 5'
INTERVALS OR AS
SHOWN ON THE
PLAN ABOVE & ON
OTHER C SHEETS
4" CONCRETE SIDEWALK
REINFORCED WITH
6 X 6 - W2.9/W2.9 WWF
AT MIDSPAN
11" 1"
7" 7"
4"1"
** TWO STEPS ARE SHOWN HERE; AT EACH
LOCATION NEEDED, ADJUST THE STEPS
REQUIRED COORDINATING NUMBER WITH
GRADES, ALLOWING NEW SIDEWALK TO MEET
EXISTING NATURAL CONTOURS AS MUCH AS
POSSIBLE.
**2 STEPS SHOWN HERE; VERIFY ON SIDE WITH
EXISTING GRADES; ON-SITE CONDITIONS MAY
REQUIRE MORE OR LESS STEPS AT EACH LOCATION
6 X 6 - W2.9/W2.9 WWF
8" MINIMUM COMPACTED SAND
CONCRETE STEP
3500PSI MIN.
BROOM FINISH
EXCAVATE AND INSTALL 4" THICK
WASHED AGGREGATE (2" < 1-1/2")
AROUND THE PERIMETER OF THE
BUILDING
INSTALL
GEOTEXTILE
FABRIC; OVERLAP
JOINTS 8" MIN.
SECURE IN PLACE
GEOTEXTILE FABRIC
NEW 4" THICK WASHED
AGGREGATE (2" < 1-1/2")
AROUND THE PERIMETER OF
THE BUILDING; SEE
LANDSCAPING PLANS
INSTALL 8"Ø MIN PVC (UTILITY
TRENCH) FOR CONDENSING
UNIT'S ELECTRICAL AND
CONDENSING LINES
INSTALL RUBBER
WEATHERPROOF CAP; SECURE
IN PLACE WITH BAND CLAMP
GAS & LIQUID LINES TO
CONDENSING UNITS
EXTEND PVC PIPE A MINIMUM
24" THRU THE BUILDING'S
FOUNDATION WALL INTO
TRENCHED AREA SHOWN ON
ADDITIONAL DRAWING SHEETS
INSTALL 8"Ø MIN PVC
(UTILITY TRENCH)
FOR CONDENSING
UNIT'S ELECTRICAL
AND CONDENSING
LINES
3"
CLASS II FILL
6" 6"
2'-0" MDOT 21AA (CRUSHED LIMESTONE) LEVELING PAD
COMPACTED TO 95% MAX DENSITY; CONTRACTOR TO
COMPACT EXISTING BASE MATERIAL TO 95% MAX DENSITY
PRIOR TO PLACING LEVELING PAD MATERIAL; ON SITE
COMPACTION TESTING OF THE SOIL IS REQUIRED
BLOCK VENDOR: VERSA-LOK RETAINING WALL SYSTEMS
BLOCK TYPE: STANDARD
OFFSET PER BLOCK: 3/4"
INSTALLATION OF WALL SYSTEM TO BE IN ACCORDANCE WITH ALL
MANUFACTURER'S RECOMMENDATIONS
GRADE
RETAINING WALL BLOCK TOP CAP; ADHERE INTO PLACE
SLOPE AWAY FROM
BUILDING 1/4" PER 1'-0"
MIN.
EXACT HEIGHT WILL BE DETERMINED ON SITE; HEIGHT STATED IS AN
ESTIMATE AND WILL NOT BE ANY HIGHER REGARDLESS
BLOCK SHALL BE PINNED TOGETHER USING
VERSA-TUFF PINS; 2 PINS PER BLOCK
6"
1' -1
0"
GRANULAR FILL
EXCAVATE AS REQUIRED TO
UPGRADE SERVICE AND CURB
STOP; BACKFILL WITH
COMPACTED GRANULAR FILL,
TOPSOIL, SEED AND MULCH
PER SPECIFICATIONS
UPGRADE EXISTING 2"
WATER SERVICE TO
BUILDING TO NEW 6"
WATER SERVICE; SEE
UTILITY PLAN SHEET C1
AND SEE SHEETS C2 & C3
FOR LOCATIONS
EXISTING CURB STOP
SERVICE BOX
INVERTED KEY CURB STOP
GRADE
EXISTING 1'-4" X 1'-4" X 4"
CONCRETE SLAB
EXISTING SERVICE BOX DROP
LOCK COVER
INSULATE OVER PIPING (2"
DOW BLUE BOARD
DOUBLED TO 4", 2'-0" WIDE
OVER TOP OF PIPING FULL
LENGTH)
6' -0
" M
IN
5'-4"
8"
2'-0"
4'-0"
HEAVY DUTY FRAME
AND COVER
EXTG GRADE
PRE CAST UNITS
SHALL MEET ASTM
C-478-68
APPLY BITUMINOUS
MASTIC AT JOINT
Ø" ASTM D3034-SDR35
PVC SEWER PIPE
MIN. REINF. #3 GA. 6"
x 6" MESH OR
EQUIVALENT
CONCRETE FLOW
CHANNEL
INV OUT
TO
TA
L H
EI
G
H T
VE
R
IE
SPREMIUM O-RING
JOINT
PIPE CONNECTOR
SEALS AT ALL PIPES
NON-SHRINK
GROUT (TYP)
(2) LAYERS OF 2" EXTRUDED
POLYSTYRENE INSULATION
2 FT WIDE CENTERED OVER
NEW PIPE; SET INSULATION
BOARD DIRECTLY ON TOP
OF NEW PIPE
UNDISTURBED
SOILS
FINISHED GRADE
INVERT
TR
EN
C H
A R
EA
(D
EP
TH
V
AR
IE
S)
BE
D
D
IN
G
AR
EA
SP
EC
IA
L
FO
U N
D
AT
IO
N
AR
EA
TRENCH WIDTH AT
UTILITY PIPE CROWN
CLASS II MATERIAL,
BACKFILL IN COMPACTED
LIFTS
6" to
2"
4"/ 6"/ 8" ASTM D3034-SDR35
GRAVITY SEWER PIPE
TO INCLUDE ALL NEW
WATER PIPING TOO
SERVICE BOX DROP LOCK COVER
TYP. SIDEWALK STEPS
AS NEEDED
SCALE 3/4" = 1'-0"
FOUNDATION SECTION AT DOOR
ENTRANCES
SCALE 1 1/2" = 1'-0"
FOUNDATION SECTION
TYPICAL PERIMETER
SCALE 1 1/2" = 1'-0"
CONDENSATE
SLAB DETAIL
SCALE 1" = 1'-0"
PVC UTILITY TRENCH DETAILS
SCALE 1" = 1'-0"
C-4
C-4
C-4
C-4
C-4
C-4
C-4
C-4
C-4
C-4
C-4
C-4
RETAINING WALL BLOCK - SCREEN WALL SECTION
SCALE 1/2" = 1'-0"C-4
BUILDING CURB STOP
WATER SERVICE ENTRANCE
SCALE 1/2" = 1'-0"
C4
2.15 MANHOLES
A. STANDARD PRECAST CONCRETE MANHOLES - ASTM C 478, PRECAST, REINFORCED CONCRETE, OF
DEPTH INDICATED, WITH PROVISION FOR SEALANT JOINTS.
1. DIAMETER, 48" MINIMUM, UNLESS OTHERWISE INDICATED.
2. BALLAST - INCREASE THICKNESS OF PRECAST CONCRETE SECTIONS OR ADD CONCRETE TO BASE
SECTION, AS REQUIRED TO PREVENT FLOTATION.
3. BASE SECTION - 6" MINIMUM THICKNESS FOR FLOOR SLAB AND 4" MINIMUM THICKNESS FOR WALLS
AND BASE RISER SECTION, AND HAVING A SEPARATE BASE SLAB OR BASE SECTION WITH INTEGRAL
FLOOR.
4. RISER SECTIONS - 4" MINIMUM THICKNESS, AND LENGTHS TO PROVIDE DEPTH INDICATED.
5. TOP SECTION - ECCENTRIC CONE TYPE, UNLESS CONCENTRIC CONE OR FLAT-SLAB-TOP IS
INDICATED. TOP OF CONE OF SIZE THAT MATCHES GRADE RINGS.
6. JOINT SEALANT - ASTM C 990, BITUMEN OR BUTYL RUBBER.
7. RESILIENT PIPE CONNECTORS - ASTM C 923, CAST OR FITTED INTO MANHOLE WALLS, FOR EACH
PIPE CONNECTION.
8. STEPS INDIVIDUAL FRP STEPS OR FRP LADDER. WIDE ENOUGH TO ALLOW A WORKER TO PLACE
BOTH FEET ON ONE STEP AND DESIGNED TO PREVENT LATERAL SLIPPAGE OFF THE STEP. CAST OR ANCHOR STEPS OR LADDER TO SIDEWALL AT 12 TO 16" INTERVALS. OMIT STEPS IF TOTAL DEPTH
FROM FLOOR OF MANHOLE TO FINISHED GRADE IS LESS THAN 60".
9 GRADE RINGS - INCLUDE 2 OR 3 REINFORCED-CONCRETE RINGS, OF 6 TO 9" TOTAL THICKNESS, THAT MATCH A 24" DIAMETER FRAME AND COVER.
10. PROTECTIVE COATING - PLANT-APPLIED, SSPC-PAINT 16 MINIMUM THICKNESS APPLIED TO
EXTERIOR SURFACES.
11. MANHOLE FRAMES AND COVERS - FERROUS, 24” ID BY 7” TO 9” RISER WITH 4” MINIMUM WIDTH FLANGE AND 26” DIAMETER COVER. INCLUDE INDENTED TOP DESIGN WITH LETTERING CAST INTO
COVER, USING WORKING EQUIVALENT TO "SANITARY SEWER".
a. MATERIAL -ASTM A 536, GRADE 60-40-18 DUCTILE IRON, UNLESS OTHERWISE INDICATED.
12. MANHOLE COVER INSERTS - MANUFACTURED, PLASTIC FORM, OF SIZE TO FIT BETWEEN MANHOLE
FRAME AND COVER AND DESIGNED TO PREVENT STORM WATER INFLOW. INCLUDE HANDLE FOR
REMOVAL AND GASKET FOR GAS TIGHT SEALING.
PRE-CAST MANHOLE
SCALE 1/2" = 1'-0"
PIPE TRENCH W/
INSULATION SADDLE
SCALE 1/2" =…
This is the start of the file's text. The full file is on GovTribe.
File details come from the government source that posted it. Updated .