This is a specification document for Section 265100 - Interior Lighting, part of Project 25-388 CBI HVAC and Lighting Upgrade. The specification details the requirements for furnishing and installing interior lighting systems, including luminaires, emergency lighting units, exit signs, ballasts, drivers, and lamps. The project requires compliance with multiple reference standards including IES LM-79, IES LM-80, NECA/IESNA 500 and 502, NFPA 70, NFPA 101, UL 924, UL 1598, and UL 8750. Key product requirements include LED luminaires with a minimum estimated useful life of 50,000 hours at 70 percent lumen maintenance, emergency lighting units complying with NFPA 101 and UL 924 that automatically switch to battery power upon loss of normal power or voltage drop exceeding 20 percent, and exit signs meeting NFPA 101 and UL 924 standards. All luminaires must be UL listed and labeled as appropriate for their intended purpose, with LED components recognized or listed under UL 8750.
Installation requirements mandate compliance with NECA standards for workmanship, with luminaires installed securely, plumb, and square, aligned with building lines and adjacent fixtures. Recessed luminaires in fire-rated ceilings must include firestopping materials meeting regulatory requirements, while suspended luminaires of four feet or greater length require minimum two supports with no more than four feet between supports. Emergency lighting units and exit signs must connect to unswitched power sources, bypassing local switches and controls. Field quality control includes inspection for damage, operational testing of all luminaires, and specific testing of emergency and exit lighting units to verify proper battery operation. A three-year manufacturer warranty is required for all LED luminaires including drivers. The specification does not identify specific pricing, quantities, response dates, bidders meetings, award dates, or contract terms.
View the file
Other files
Show all 41
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
25-388 CBI HVAC and Lighting Upgrade 265100 - 1 Interior Lighting
SECTION 265100
INTERIOR LIGHTING
PART 1 GENERAL
1.01 SECTION INCLUDES
A. Interior luminaires.aaaaaa B. Emergency lighting units.
C. Exit signs.
D. Ballasts and drivers.
E. Lamps.
1.02 RELATED REQUIREMENTS
A. Section 260529 - Hangers and Supports for Electrical Systems.
B. Section 260533.16 - Boxes for Electrical Systems.
C. Section 260548 - Vibration and Seismic Controls for Electrical Systems.
D. Section 260553 - Identification for Electrical Systems: Identification products and requirements.
E. Section 260918 - Remote Control Switching Devices: Remote controls for lighting, including network lighting controls, programmable relay panels, and remote control switching relays.
F. Section 262726 - Wiring Devices: Manual wall switches and wall dimmers.
G. Section 265561 - Theatrical Lighting: Stage lighting units and associated controls.
H. Section 265600 - Exterior Lighting.
1.03 REFERENCE STANDARDS
A. IES LM-79 - Approved Method: Optical and Electrical Measurements of Solid-State Lighting
Products; 2024.
B. IES LM-80 - Approved Method: Measuring Maintenance of Light Output Characteristics of
Solid-State Light Sources; 2021.
C. NECA 1 - Standard for Good Workmanship in Electrical Construction; 2023.
D. NECA/IESNA 500 - Standard for Installing Indoor Lighting Systems; 2006.
E. NECA/IESNA 502 - Standard for Installing Industrial Lighting Systems; 2006.
F. NEMA LE 4 - Recessed Luminaires, Ceiling Compatibility; 2023.
G. NFPA 70 - National Electrical Code; Most Recent Edition Adopted by Authority Having
Jurisdiction, Including All Applicable Amendments and Supplements.
H. NFPA 101 - Life Safety Code; Most Recent Edition Adopted by Authority Having Jurisdiction, Including All Applicable Amendments and Supplements.
I. UL 924 - Emergency Lighting and Power Equipment; Current Edition, Including All Revisions.
J. UL 1598 - Luminaires; Current Edition, Including All Revisions.
K. UL 8750 - Light Emitting Diode (LED) Equipment for Use in Lighting Products; Current Edition, Including All Revisions.
1.04 ADMINISTRATIVE REQUIREMENTS
A. Coordination:
1. Coordinate the installation of luminaires with mounting surfaces installed under other sections or by others. Coordinate the work with placement of supports, anchors, etc.
required for mounting. Coordinate compatibility of luminaires and associated trims with mounting surfaces at installed locations.
Upgrade 265100 - 2 Interior Lighting
2. Coordinate the placement of luminaires with structural members, ductwork, piping, equipment, diffusers, fire suppression system components, and other potential conflicts installed under other sections or by others.
3. Coordinate the placement of exit signs with furniture, equipment, signage or other potential obstructions to visibility installed under other sections or by others.
4. Notify Architect of any conflicts or deviations from Contract Documents to obtain direction prior to proceeding with work.
1.05 SUBMITTALS
A. See Section 013000 - Administrative Requirements, for submittal procedures.
B. Product Data: Provide manufacturer's standard catalog pages and data sheets including detailed information on luminaire construction, dimensions, ratings, finishes, mounting requirements, listings, service conditions, photometric performance, installed accessories, and ceiling compatibility; include model number nomenclature clearly marked with all proposed features.
1. LED Luminaires:
a. Include estimated useful life, calculated based on IES LM-80 test data.
1.06 QUALITY ASSURANCE
A. Comply with requirements of NFPA 70.
1.07 DELIVERY, STORAGE, AND PROTECTION
A. Receive, handle, and store products according to NECA/IESNA 500 (commercial lighting), NECA/IESNA 502 (industrial lighting), and manufacturer's written instructions.
B. Keep products in original manufacturer's packaging and protect from damage until ready for installation.
1.08 FIELD CONDITIONS
A. Maintain field conditions within manufacturer's required service conditions during and after installation.
1.09 WARRANTY
A. See Section 017800 - Closeout Submittals, for additional warranty requirements.
B. Provide 3-year manufacturer warranty for LED luminaires, including drivers.
PART 2 PRODUCTS
2.01 LUMINAIRE TYPES
A. Furnish products as indicated in luminaire schedule included on the drawings.
2.02 LUMINAIRES
A. Provide products that comply with requirements of NFPA 70.
B. Provide products that are listed and labeled as complying with UL 1598, where applicable.
C. Provide products listed, classified, and labeled as suitable for the purpose intended.
D. Unless otherwise indicated, provide complete luminaires including lamp(s) and all sockets, ballasts, reflectors, lenses, housings and other components required to position, energize and protect the lamp and distribute the light.
E. Unless specifically indicated to be excluded, provide all required conduit, boxes, wiring, connectors, hardware, supports, trims, accessories, etc. as necessary for a complete operating system.
F. Provide products suitable to withstand normal handling, installation, and service without any damage, distortion, corrosion, fading, discoloring, etc.
G. LED Luminaires:
1. Components: UL 8750 recognized or listed as applicable.
Upgrade 265100 - 3 Interior Lighting
2. Tested in accordance with IES LM-79 and IES LM-80.
3. LED Estimated Useful Life: Minimum of 50,000 hours at 70 percent lumen maintenance, calculated based on IES LM-80 test data.
H. LED Tape Lighting Systems: Provide all power supplies, drivers, cables, connectors, channels, covers, mounting accessories, and interfaces as necessary to complete installation.
1. LED Tape - General Requirements:
a. Listed.
b. Designed for field cutting in accordance with listing.
2.03 EMERGENCY LIGHTING UNITS
A. Manufacturers:
1. Acuity Brands, Inc: www.acuitybrands.com/#sle.
2. Cooper Lighting, a division of Cooper Industries: www.cooperindustries.com/#sle.
3. Hubbell Lighting, Inc: www.hubbelllighting.com/#sle.
B. Description: Emergency lighting units complying with NFPA 101 and all applicable state and local codes, and listed and labeled as complying with UL 924.
C. Operation: Upon interruption of normal power source or brownout condition exceeding 20 percent voltage drop from nominal, solid-state control automatically switches connected lamps to integral battery power for minimum of 90 minutes of rated emergency illumination, and automatically recharges battery upon restoration of normal power source.
D. Battery:
1. Size battery to supply all connected lamps, including emergency remote heads where indicated.
E. Diagnostics: Provide power status indicator light and accessible integral test switch to manually activate emergency operation.
F. Provide low-voltage disconnect to prevent battery damage from deep discharge.
2.04 EXIT SIGNS
A. Description: Exit signs complying with NFPA 101 and applicable state and local codes, and listed and labeled as complying with UL 924.
1. Number of Faces: Single- or double-face as indicated or as required for installed location.
2. Directional Arrows: As indicated or as required for installed location.
2.05 BALLASTS AND DRIVERS
A. Ballasts/Drivers - General Requirements:
1. Provide ballasts containing no polychlorinated biphenyls (PCBs).
2. Minimum Efficiency/Efficacy: Provide ballasts complying with all current applicable federal and state ballast efficiency/efficacy standards.
B. Dimmable LED Drivers:
1. Dimming Range: Continuous dimming from 100 percent to five percent relative light output unless dimming capability to lower level is indicated, without flicker.
2. Control Compatibility: Fully compatible with the dimming controls to be installed.
a. Wall Dimmers: See Section 262726.
PART 3 EXECUTION
3.01 EXAMINATION
A. Verify that field measurements are as indicated.
B. Verify that outlet boxes are installed in proper locations and at proper mounting heights and are properly sized to accommodate conductors in accordance with NFPA 70.
C. Verify that suitable support frames are installed where required.
D. Verify that branch circuit wiring installation is completed, tested, and ready for connection to luminaires.
Upgrade 265100 - 4 Interior Lighting
E. Verify that conditions are satisfactory for installation prior to starting work.
3.02 INSTALLATION
A. Coordinate locations of outlet boxes provided under Section 260533.16 as required for installation of luminaires provided under this section.
B. Install products in accordance with manufacturer's instructions.
C. Install luminaires securely, in a neat and workmanlike manner, as specified in NECA 500
(commercial lighting) and NECA 502 (industrial lighting).
D. Provide required support and attachment in accordance with Section 260529.
E. Install luminaires plumb and square and aligned with building lines and with adjacent luminaires.
F. Recessed Luminaires:
1. Install trims tight to mounting surface with no visible light leakage.
2. Non-IC Rated Luminaires: Maintain required separation from insulation and combustible materials according to listing.
3. Luminaires Recessed in Fire-Rated Ceilings: Install using accessories and firestopping materials to meet regulatory requirements for fire rating.
G. Suspended Luminaires:
1. Install using the suspension method indicated, with support lengths and accessories as required for specified mounting height.
2. Provide minimum of two supports for each luminaire equal to or exceeding 4 feet nominal length, with no more than 4 feet between supports.
H. Install accessories furnished with each luminaire.
I. Bond products and metal accessories to branch circuit equipment grounding conductor.
J. Emergency Lighting Units:
K. Exit Signs:
1. Unless otherwise indicated, connect unit to unswitched power from same circuit feeding normal lighting in same room or area. Bypass local switches, contactors, or other lighting controls.
L. Install lamps in each luminaire.
3.03 FIELD QUALITY CONTROL
A. See Section 014000 - Quality Requirements, for additional requirements.
B. Inspect each product for damage and defects.
C. Operate each luminaire after installation and connection to verify proper operation.
D. Test self-powered exit signs, emergency lighting units, and fluorescent emergency power supply units to verify proper operation upon loss of normal power supply.
E. Correct wiring deficiencies and repair or replace damaged or defective products. Repair or replace excessively noisy ballasts as determined by Architect.
3.04 ADJUSTING
A. Aim and position adjustable luminaires to achieve desired illumination as indicated or as directed by Architect. Secure locking fittings in place.
B. Aim and position adjustable emergency lighting unit lamps to achieve optimum illumination of egress path as required or as directed by Architect or authority having jurisdiction.
C. Exit Signs with Field-Selectable Directional Arrows: Set as indicated or as required to properly designate egress path as directed by Architect or authority having jurisdiction.
3.05 CLEANING
Upgrade 265100 - 5 Interior Lighting
A. Clean surfaces according to NECA 500 (commercial lighting), NECA 502 (industrial lighting), and manufacturer's instructions to remove dirt, fingerprints, paint, or other foreign material and restore finishes to match original factory finish.
3.06 PROTECTION
A. Protect installed luminaires from subsequent construction operations.
END OF SECTION
265100 - Interior Lighting