260923-RIB-Lighting Control Devices-12-24-2025.pdf
PDF 102 KB Posted
- Attached to
- CBI GJ HVAC/Lighting Upgrade Project
- Solicitation number
- IFB1 REAA 2027000005 2
- Issued by
- Denver County, Denver City, Colorado
About this file
This is a technical specification document for lighting control devices as part of project 25-388, a CBI HVAC and Lighting Upgrade. The specification details requirements for occupancy sensors, outdoor motion sensors, time switches, outdoor photo controls, lighting contactors, and associated accessories. Acceptable manufacturers for occupancy sensors include Hubbell Incorporated and Lutron Electronics Company, Inc, while time switches may be supplied by Intermatic, Inc or Tork, a division of NSI Industries LLC. The specification requires wall switch occupancy sensors capable of detecting motion within 900 square feet for PIR units and 400 square feet for ultrasonic units, ceiling-mounted occupancy sensors with varying range capabilities up to 2,000 square feet, and directional sensors capable of detecting motion up to 80 feet depending on type. Outdoor motion sensors must detect motion within 50 feet at 8 feet mounting height with 270-degree field of view and include integral photocell for dusk-to-dawn operation. All devices must comply with applicable UL standards, NFPA 70, NECA standards, and ANSI specifications referenced in the document.
The specification mandates five-year manufacturer warranties for occupancy sensors and digital load controllers. Installation must comply with NECA 1 and NECA 130 standards for workmanship and mounting heights, with all devices properly grounded and bonded according to electrical code requirements. Submittals must include product data with detailed motion detection coverage range diagrams, manufacturer's installation instructions, and operation and maintenance data including device programming and setup details. Field quality control requires inspection and testing of all devices to verify proper operation, time delays, and coverage optimization, with written test reports required. The contractor must coordinate placement of all lighting control devices with building elements including millwork, furniture, windows, and ductwork to prevent obstructions and conflicts, and must train Owner's personnel on operation, adjustment, programming, and maintenance of all lighting control devices upon project completion.
View the file
Other files
Show all 41
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
25-388 CBI HVAC and Lighting Upgrade 260923 - 1 Lighting Control Devices
SECTION 260923
LIGHTING CONTROL DEVICES
PART 1 GENERAL
1.01 SECTION INCLUDES
A. Occupancy sensors.
B. Outdoor motion sensors.
C. Time switches.
D. In-wall time switches.
E. Outdoor photo controls.
F. Lighting contactors.
G. Accessories.
1.02 RELATED REQUIREMENTS
A. Section 253626 - Integrated Automation Lighting Relays.
B. Section 260519 - Low-Voltage Electrical Power Conductors and Cables.
C. Section 260526 - Grounding and Bonding for Electrical Systems.
D. Section 260529 - Hangers and Supports for Electrical Systems E. Section 260533.16 - Boxes for Electrical Systems.
F. Section 260553 - Identification for Electrical Systems: Identification products and requirements.
G. Section 260918 - Remote Control Switching Devices: Remotely controlled devices for lighting control, including networked lighting controls, programmable relay panels, and remote control switching relays.
H. Section 262726 - Wiring Devices: Devices for manual control of lighting, including wall switches, wall dimmers, and fan speed controllers.
I. Section 262813 - Fuses.
J. Section 262913 - Enclosed Controllers : General purpose contactors.
K. Section 265100 - Interior Lighting.
L. Section 265561 - Theatrical Lighting: Controls for stage lighting units.
M. Section 265600 - Exterior Lighting.
1.03 REFERENCE STANDARDS
A. 47 CFR 15 - Radio Frequency Devices; current edition.
B. ANSI C136.10 - American National Standard for Roadway and Area Lighting Equipment -
Locking-Type Photocontrol Devices and Mating Receptacles - Physical and Electrical Interchangeability and Testing; 2023.
C. ANSI C136.24 - American National Standard for Roadway and Area Lighting Equipment - Nonlocking (Button) Type Photocontrols; 2020.
D. NECA 1 - Standard for Good Workmanship in Electrical Construction; 2023.
E. NECA 130 - Standard for Installing and Maintaining Wiring Devices; 2016.
F. NEMA EN 10250 - Enclosures for Electrical Equipment (1000 Volts Maximum); 2024.
G. NEMA ICS 2 - Industrial Control and Systems Controllers, Contactors and Overload Relays
Rated 600 Volts; 2008 (Reaffirmed 2020).
H. NEMA IA 10030 - Industrial Control and Systems: Enclosures; 2024.
I. NFPA 70 - National Electrical Code; Most Recent Edition Adopted by Authority Having
Jurisdiction, Including All Applicable Amendments and Supplements.
Upgrade 260923 - 2 Lighting Control Devices
J. UL 773 - Plug-in, Locking Type Photocontrols for Use with Area Lighting; Current Edition, Including All Revisions.
K. UL 773A - Nonindustrial Photoelectric Switches for Lighting Control; Current Edition, Including All Revisions.
L. UL 916 - Energy Management Equipment; Current Edition, Including All Revisions.
M. UL 917 - Clock-Operated Switches; Current Edition, Including All Revisions.
N. UL 1472 - Solid-State Dimming Controls; Current Edition, Including All Revisions.
O. UL 60947-1 - Low-Voltage Switchgear and Controlgear - Part 1: General Rules; Current
Edition, Including All Revisions.
P. UL 60947-4-1 - Low-Voltage Switchgear and Controlgear - Part 4-1: Contactors and Motor-starters - Electromechanical Contactors and Motor-starters; Current Edition, Including All Revisions.
1.04 ADMINISTRATIVE REQUIREMENTS
A. Coordination:
1. Coordinate placement of lighting control devices with millwork, furniture, equipment and other potential conflicts.
2. Coordinate placement of wall switch occupancy sensors with installed door swings.
3. Coordinate placement of occupancy sensors with millwork, furniture, equipment and other potential obstructions to motion detection coverage.
4. Coordinate placement of photo sensors for daylighting controls with windows, skylights, and luminaires to achieve optimum operation. Coordinate placement with ductwork, piping, equipment, or other potential obstructions to light level measurement.
5. Coordinate lighting control device product selections with luminaire characteristics; see Section 265100 and lighting fixture schedule.
6. Notify Architect of conflicts or deviations from Contract Documents to obtain direction prior to proceeding with work.
1.05 SUBMITTALS
A. See Section 013000 - Administrative Requirements, for submittal procedures.
B. Product Data: Include ratings, operating modes or sequence of functions, configurations, standard wiring diagrams, dimensions, colors, service condition requirements, and installed features.
1. Occupancy Sensors: Include detailed motion detection coverage range diagrams.
C. Field quality control reports.
D. Manufacturer's Installation Instructions: Include application conditions and limitations of use stipulated by product testing agency. Include instructions for storage, handling, protection, examination, preparation, and installation of product.
E. Operation and Maintenance Data: Include detailed information on device programming and setup.
F. Maintenance Materials: Furnish the following for Owner's use in maintenance of project.
1. See Section 016000 - Product Requirements, for additional provisions.
G. Project Record Documents: Record actual installed locations and settings for lighting control devices.
1.06 QUALITY ASSURANCE
A. Comply with NFPA 70.
1.07 DELIVERY, STORAGE, AND PROTECTION
A. Store products in clean, dry space in original manufacturer's packaging in accordance with manufacturer's written instructions until ready for installation.
Upgrade 260923 - 3 Lighting Control Devices
1.08 FIELD CONDITIONS
A. Maintain field conditions within manufacturer's required service conditions during and after installation.
1.09 WARRANTY
A. See Section 017800 - Closeout Submittals, for additional warranty requirements.
B. Provide five year manufacturer warranty for occupancy sensors.
C. Provide five year manufacturer warranty for digital load controllers.
PART 2 PRODUCTS
2.01 LIGHTING CONTROL DEVICES - GENERAL REQUIREMENTS
A. Provide products listed, classified, and labeled as suitable for purpose intended.
B. Unless specifically indicated as excluded, provide components necessary for complete operating system including, but not limited to, conduit, wiring, connectors, hardware, and accessories.
2.02 OCCUPANCY SENSORS
A. Manufacturers:
1. Hubbell Incorporated: www.hubbell.com/#sle.
2. Lutron Electronics Company, Inc: www.lutron.com/#sle.
B. General Requirements:
1. Description: Factory-assembled commercial specification grade devices for indoor use capable of sensing both major motion, such as walking, and minor motion, such as small desktop level movements, according to published coverage areas, for automatic control of load indicated.
2. Sensor Technology:
a. Passive Infrared (PIR) Occupancy Sensors: Designed to detect occupancy by sensing movement of thermal energy between zones.
b. Ultrasonic Occupancy Sensors: Designed to detect occupancy by sensing frequency shifts in emitted and reflected inaudible sound waves.
c. Passive Infrared/Ultrasonic Dual Technology Occupancy Sensors: Designed to detect occupancy using combination of both passive infrared and ultrasonic technologies.
3. Provide LED to visually indicate motion detection with separate color LEDs for each sensor type in dual technology units.
4. Operation: Unless otherwise indicated, occupancy sensor to turn load on when occupant presence is detected and to turn load off when no occupant presence is detected during adjustable turn-off delay time interval.
5. Dual Technology Occupancy Sensors: Field configurable turn-on and hold-on activation with settings for activation by either or both sensing technologies.
6. Turn-Off Delay: Field adjustable, with time delay settings up to 30 minutes.
7. Sensitivity: Field adjustable.
8. Adaptive Technology: Field selectable; capable of self-adjusting sensitivity and time delay according to conditions.
9. Compatibility (Non-Dimming Sensors): Suitable for controlling incandescent lighting, low-voltage lighting with electronic and magnetic transformers, fluorescent lighting with electronic and magnetic ballasts, and fractional motor loads, with no minimum load requirements.
10. Load Rating for Line Voltage Occupancy Sensors: As required to control load indicated on drawings.
11. Where wired sensors are indicated, wireless sensors are acceptable provided that components and wiring modifications necessary for proper operation are included.
12. Wireless Sensors:
Upgrade 260923 - 4 Lighting Control Devices
a. RF Range: 30 feet through typical construction materials.
b. Electromagnetic Interference/Radio Frequency Interference (EMI/RFI) Limits:
Comply with FCC requirements of 47 CFR 15, for Class B application.
c. Power: Battery-operated with minimum ten-year battery life.
C. Wall Switch Occupancy Sensors:
1. General Requirements:
a. Description: Occupancy sensors designed for installation in standard wall box at standard wall switch mounting height with field of view of 180 degrees, integrated manual control capability, and no leakage current to load in off mode.
b. Manual-Off Override Control: When used to turn off load while in automatic-on mode, unit to revert back to automatic mode after no occupant presence is detected during delayed-off time interval.
2. Passive Infrared (PIR) Wall Switch Occupancy Sensors: Capable of detecting motion within area of 900 square feet.
3. Ultrasonic Wall Switch Occupancy Sensors: Capable of detecting motion within area of 400 square feet.
4. Passive Infrared/Ultrasonic Dual Technology Wall Switch Occupancy Sensors: Capable of detecting motion within area of 900 square feet.
D. Wall Dimmer Occupancy Sensors:
1. General Requirements:
a. Description: Occupancy sensors designed for installation in standard wall box at standard wall switch mounting height with field of view of 180 degrees, integrated dimming control capability, and no leakage current to load in off mode.
b. Dimmer: Solid-state with continuous full-range even control following square law dimming curve, integral radio frequency interference filtering, power failure preset memory, air gap switch accessible without removing wall plate, and listed as complying with UL 1472; type and rating suitable for load controlled.
2. Passive Infrared (PIR) Wall Dimmer Occupancy Sensors: Capable of detecting motion within area of 900 square feet.
E. Ceiling Mounted Occupancy Sensors:
1. General Requirements:
a. Description: Low profile occupancy sensors designed for ceiling installation.
2. Passive Infrared (PIR) Ceiling Mounted Occupancy Sensors:
a. Standard Range Sensors: Capable of detecting motion within area of 450 square feet at mounting height of 9 feet, with field of view of 360 degrees.
b. Extended Range Sensors: Capable of detecting motion within area of 1,200 square feet at mounting height of 9 feet, with field of view of 360 degrees.
3. Ultrasonic Ceiling Mounted Occupancy Sensors:
a. Standard Range Sensors: Capable of detecting motion within area of 500 square feet at mounting height of 9 feet, with field of view of 360 degrees.
b. Medium Range Sensors: Capable of detecting motion within area of 1,000 square feet at mounting height of 9 feet, with field of view of 360 degrees.
c. Extended Range Sensors: Capable of detecting motion within area of 2,000 square feet at mounting height of 9 feet.
4. Passive Infrared/Ultrasonic Dual Technology Ceiling Mounted Occupancy Sensors:
a. Standard Range Sensors: Capable of detecting motion within area of 450 square feet at mounting height of 9 feet, with field of view of 360 degrees.
b. Extended Range Sensors: Capable of detecting motion within area of 1,200 square feet at mounting height of 9 feet, with field of view of 360 degrees.
5. Passive Infrared/Acoustic Dual Technology Ceiling Mounted Occupancy Sensors:
a. Standard Range Sensors: Capable of detecting motion within area of 450 square feet at mounting height of 9 feet, with field of view of 360 degrees.
Upgrade 260923 - 5 Lighting Control Devices
b. Extended Range Sensors: Capable of detecting motion within area of 1,200 square feet at mounting height of 9 feet.
F. Directional Occupancy Sensors:
1. General Requirements:
a. Description: Occupancy sensors designed for wall or ceiling mounting, with integral swivel for field adjustment of motion detection coverage.
b. Unless otherwise indicated or required to control the load indicated on drawings, provide low voltage units, for use with separate compatible accessory power packs.
2. Passive Infrared (PIR) Directional Occupancy Sensors:
a. Standard Range Sensors: Capable of detecting motion within distance of 40 feet at mounting height of 10 feet.
b. Long Range Sensors: Capable of detecting motion within distance of 80 feet at mounting height of 10 feet.
c. High Bay Sensors: Capable of detecting motion within distance of 50 feet at mounting height of 30 feet.
3. Passive Infrared/Ultrasonic Dual Technology Directional Occupancy Sensors: Capable of detecting motion within distance of 40 feet at mounting height of 10 feet.
G. Luminaire Mounted Occupancy Sensors: Designed for direct luminaire installation and control, suitable for use with specified luminaires.
H. Power Packs for Low-Voltage Occupancy Sensors:
1. Description: Plenum rated, self-contained low-voltage class 2 transformer and relay compatible with specified low-voltage occupancy sensors for switching of line-voltage loads.
2. Provide quantity and configuration of power and slave packs with associated wiring and accessories as required to control load indicated on drawings.
3. Input Supply Voltage: Dual rated for 120/277 V ac.
I. Power Packs for Wireless Occupancy Sensors:
1. Description: Plenum rated, self-contained relay compatible with specified wireless occupancy sensors for switching of line-voltage loads.
2. Input Supply Voltage: Dual rated for 120/277 V ac.
3. Load Rating: As required to control load indicated on drawings.
2.03 OUTDOOR MOTION SENSORS
A. Description: Factory-assembled wet location listed device suitable for wall or ceiling/eave mounting, with integral swivel for field adjustment of coverage, capable of detecting motion for automatic control of load indicated.
B. Sensor Technology: Passive Infrared (PIR) designed to detect occupancy by sensing movement of thermal energy between zones.
C. Operation: Unless otherwise indicated, motion sensor to turn load on when motion is detected and to turn load off when no motion is detected during adjustable turn-off delay time interval.
D. Turn-Off Delay: Field adjustable, with time delay settings available up to 15 minutes.
E. Integral Photocell: For dusk to dawn operation.
F. Manual Override: Activated by switching power off to unit and then back on.
G. Load Rating: 1,000 W incandescent and fluorescent load at 120 V ac.
H. Coverage: Capable of detecting motion within distance of 50 feet at mounting height of 8 feet, with field of view of 270 degrees.
2.04 TIME SWITCHES
A. Manufacturers:
1. Intermatic, Inc: www.intermatic.com/#sle.
2. Tork, a division of NSI Industries LLC: www.tork.com/#sle.
Upgrade 260923 - 6 Lighting Control Devices
B. Digital Electronic Time Switches:
1. Description: Factory-assembled solid state programmable controller with LCD display, listed and labeled as complying with UL 916 or UL 917.
2. Program Capability:
3. Schedule Capacity: Not less than 16 programmable on/off operations.
4. Provide automatic daylight savings time and leap year compensation.
5. Provide power outage backup to retain programming and maintain clock.
6. Manual override: Capable of overriding current schedule both permanently and temporarily until next scheduled event.
7. Input Supply Voltage: As indicated on the drawings.
8. Provide lockable enclosure; environmental type per NEMA EN 10250 as specified for the following installation locations:
C. Electromechanical Time Switches:
1. Description: Factory-assembled controller with motor-operated timing dial mechanism and adjustable trippers for setting on/off operations, listed and labeled as complying with
UL 917.
2. Program Capability:
a. Astronomic Time Switches: With same schedule for each day of week and skip-a-day feature to omit selected days with automatic adjustment for seasonal changes in sunrise and sunset times.
3. Schedule Capacity:
a. Astronomic Time Switches: Capable of turning load on at sunset and off at either sunrise or selected fixed time.
4. Manual override: Capable of overriding current schedule both permanently and temporarily until next scheduled event.
5. Input Supply Voltage: As indicated on the drawings.
6. Provide lockable enclosure; environmental type per NEMA EN 10250 as specified for the following installation locations:
2.05 OUTDOOR PHOTO CONTROLS
A. Stem-Mounted Outdoor Photo Controls:
1. Description: Direct-wired photo control unit with threaded conduit mounting stem and field-adjustable swivel base, listed and labeled as complying with UL 773A.
2. Housing: Weatherproof, impact resistant polycarbonate.
3. Photo Sensor: Cadmium sulfide.
4. Provide external sliding shield for field adjustment of light level activation.
5. Light Level Activation: 1 to 5 footcandles turn-on and 3 to 1 turn-off to turn-on ratio with delayed turn-off.
6. Voltage: As required to control load indicated on drawings.
7. Failure Mode: Fails to the on position.
8. Load Rating: As required to control load indicated on drawings.
B. Locking Receptacle-Mounted Outdoor Photo Controls
1. Description: Plug-in locking type photo control unit complying with ANSI C136.10 for mounting on compatible receptacle, listed and labeled as complying with UL 773.
2. Housing: Weatherproof, impact resistant UV stabilized polypropylene, color to be selected.
3. Photo Sensor: Cadmium sulfide.
4. Light Level Activation: 1 to 3 footcandles turn-on and 1.5 to 1 turn-off to turn-on ratio with instant turn-on and delayed turn-off.
5. Voltage: As required to control load indicated on drawings.
6. Failure Mode: Fails to the on position.
7. Load Rating: As required to control load indicated on drawings.
8. Surge Protection: 160 joule metal oxide varistor.
Upgrade 260923 - 7 Lighting Control Devices
C. Button Type Outdoor Photo Controls
1. Description: Direct-wired photo control unit complying with ANSI C136.24 with weatherproof gasketed wall plate where required or indicated, listed and labeled as complying with UL 773A.
2. Housing: Weather resistant polycarbonate.
3. Photo Sensor: Cadmium sulfide.
4. Light Level Activation: 1 to 3 footcandles turn-on and 3 to 1 turn-off to turn-on ratio with delayed turn-off.
5. Voltage: As required to control load indicated on drawings.
6. Failure Mode: Fails to the on position.
7. Load Rating: As required to control load indicated on drawings.
2.06 LIGHTING CONTACTORS
A. Description: Magnetic lighting contactors complying with NEMA ICS 2, and listed and labeled as complying with UL 60947-1 and UL 60947-4-1; noncombination type unless otherwise indicated; ratings, configurations and features as indicated on drawings.
B. Short Circuit Current Rating:
1. Provide contactors with listed short circuit current rating not less than available fault current at installed location as indicated on the drawings.
C. Enclosures:
1. Comply with NEMA IA 10030.
2. Environment Type per NEMA EN 10250: Unless otherwise indicated, as specified for the following installation locations:
3. Finish: Manufacturer's standard unless otherwise indicated.
PART 3 EXECUTION
3.01 EXAMINATION
A. Verify that field measurements are as indicated.
B. Verify that outlet boxes are installed in proper locations and at proper mounting heights and are properly sized to accommodate devices and conductors in accordance with NFPA 70.
C. Verify that openings for outlet boxes are neatly cut and will be completely covered by devices or wall plates.
D. Verify that final surface finishes are complete, including painting.
E. Verify that branch circuit wiring installation is completed, tested, and ready for connection to lighting control devices.
F. Verify that service voltage and ratings of lighting control devices are appropriate for service voltage and load requirements at location to be installed.
G. Verify that conditions are satisfactory for installation prior to starting work.
3.02 INSTALLATION
A. Install lighting control devices in accordance with NECA 1 (general workmanship) and, where applicable, NECA 130, including mounting heights specified in those standards unless otherwise indicated.
B. Coordinate locations of outlet boxes as required for installation of lighting control devices; see Section 260533.16.
C. Maintain separation of remote-control, signaling, and power-limited circuits.
1. See manufacturer instructions and Section 260519 for control wiring conductors, wiring methods, and identification requirements.
D. Install lighting control devices in accordance with manufacturer's instructions.
E. Unless otherwise indicated, connect lighting control device grounding terminal or conductor to branch circuit equipment grounding conductor and to outlet box with bonding jumper.
Upgrade 260923 - 8 Lighting Control Devices
F. Install lighting control devices plumb and level, and held securely in place.
G. Where required and not furnished with lighting control device, provide wall plate; see Section
262726.
H. Provide required supports; see Section 260529.
I. Where applicable, install lighting control devices and associated wall plates to fit completely flush to mounting surface with no gaps and rough opening completely covered without strain on wall plate. Repair or reinstall improperly installed outlet boxes or improperly sized rough openings. Do not use oversized wall plates in lieu of meeting this requirement.
J. Occupancy Sensor Locations:
1. Locate ultrasonic and dual technology passive infrared/ultrasonic occupancy sensors minimum of 4 feet from air supply ducts or other sources of heavy air flow and as per manufacturer's recommendations, in order to minimize false triggers.
K. Outdoor Photo Control Locations:
1. Where possible, locate outdoor photo controls with photo sensor facing north. If north facing photo sensor is not possible, install with photo sensor facing east, west, or down.
2. Locate outdoor photo controls so that photo sensors do not face artificial light sources, including light sources controlled by photo control itself.
L. Install outdoor photo controls so that connections are weatherproof. Do not install photo controls with conduit stem facing up in order to prevent infiltration of water into photo control.
M. Daylighting Control Photo Sensor Locations:
1. Unless otherwise indicated, locate photo sensors for closed loop systems to accurately measure light level controlled at designated task location, while minimizing measured amount of direct light from natural or artificial sources such as windows or pendant luminaires.
2. Unless otherwise indicated, locate photo sensors for open loop systems to accurately measure the level of daylight coming into space, while minimizing measured amount of lighting from artificial sources.
N. Lamp Burn-In: Operate lamps at full output for minimum of 100 hours or prescribed period per manufacturer's recommendations prior to use with dimming controls. Replace lamps that fail prematurely due to improper lamp burn-in.
3.03 FIELD QUALITY CONTROL
A. See Section 014000 - Quality Requirements, for additional requirements.
B. Inspect each lighting control device for damage and defects.
C. Test occupancy sensors to verify proper operation, including time delays and ambient light thresholds where applicable. Verify optimal coverage for entire room or area. Record test results in written report to be included with submittals.
D. Test time switches to verify proper operation.
E. Test outdoor photo controls to verify proper operation, including time delays where applicable.
F. Test daylighting controls to verify proper operation, including light level measurements and time delays where applicable. Record test results in written report to be included with submittals.
G. Correct wiring deficiencies and replace damaged or defective conductors, cables, and lighting control devices.
3.04 ADJUSTING
A. Adjust devices and wall plates to be flush and level.
B. Adjust occupancy sensor settings to minimize undesired activations while optimizing energy savings, and to achieve desired function as indicated or as directed by Architect.
C. Adjust position of directional occupancy sensors and outdoor motion sensors to achieve optimal coverage as required.
Upgrade 260923 - 9 Lighting Control Devices
D. Where indicated or as directed by Architect, install factory masking material or adjust integral blinders on passive infrared (PIR) and dual technology occupancy sensor lenses to block undesired motion detection.
E. Adjust time switch settings to achieve desired operation schedule as indicated or as directed by Architect. Record settings in written report to be included with submittals.
F. Adjust external sliding shields on outdoor photo controls under optimum lighting conditions to achieve desired turn-on and turn-off activation as indicated or as directed by Architect.
G. Adjust daylighting controls under optimum lighting conditions after all room finishes, furniture, and window treatments have been installed to achieve desired operation as indicated or as directed by Architect. Record settings in written report to be included with submittals. Readjust controls calibrated prior to installation of final room finishes, furniture, and window treatments that do not function properly as determined by Architect.
3.05 CLEANING
A. Clean exposed surfaces to remove dirt, paint, or other foreign material and restore to match original factory finish.
3.06 CLOSEOUT ACTIVITIES
A. See Section 017900 - Demonstration and Training, for additional requirements.
B. Demonstration: Demonstrate proper operation of lighting control devices to Architect, and correct deficiencies or make adjustments as directed.
C. Training: Train Owner's personnel on operation, adjustment, programming, and maintenance of lighting control devices.
1. Use operation and maintenance manual as training reference, supplemented with additional training materials as required.
END OF SECTION
260923 - Lighting Control Devices