260583-RIB-Wiring Connections-12-24-2025.pdf
PDF 58 KB Posted
- Attached to
- CBI GJ HVAC/Lighting Upgrade Project
- Solicitation number
- IFB1 REAA 2027000005 2
- Issued by
- Denver County, Denver City, Colorado
About this file
This is a technical specification document for Section 260583 – Wiring Connections, part of Project 25-388 CBI HVAC and Lighting Upgrade. The specification outlines the requirements for electrical connections to equipment including the use of flexible conduit, cord and plug connections (NEMA 6-20R), and field-installed disconnect switches. The work encompasses the installation of wiring devices, flexible conduit, wire and cable, and boxes in accordance with referenced standards including NFPA 70 (National Electrical Code), NEMA WD 1, and NEMA WD 6. All electrical connections must be executed according to equipment manufacturer's instructions, with particular attention to proper conduit connections, strain-relief clamps, terminal block jumpers, and interconnecting conduit and wiring between devices. The specification requires that all materials comply with applicable standards for damp and wet locations where applicable, and that equipment be verified as ready for electrical connection prior to installation.
The specification establishes quality assurance requirements mandating full compliance with NFPA 70 and associated standards. Contractors must obtain and review shop drawings, product data, and manufacturer's wiring diagrams for equipment furnished under other sections to ensure proper coordination and determine connection locations. Materials specified include cords and caps matching receptacle configurations, flexible conduit for connections to equipment, and wire and cable as detailed in referenced sections. The document does not specify pricing, contract award dates, renewal options, funding sources, or set-asides, as it functions as a technical specification document rather than a solicitation or bid package document.
View the file
Other files
Show all 41
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
25-388 CBI HVAC and Lighting Upgrade 260583 - 1 Wiring Connections
SECTION 260583
WIRING CONNECTIONS
PART 1 GENERAL
1.01 SECTION INCLUDES
A. Electrical connections to equipment.
1.02 RELATED REQUIREMENTS
A. Section 260519 - Low-Voltage Electrical Power Conductors and Cables.
B. Section 260533.13 - Conduit for Electrical Systems.
C. Section 260533.16 - Boxes for Electrical Systems.
D. Section 262726 - Wiring Devices.
E. Section 262816.16 - Enclosed Switches.
F. Section 262913 - Enclosed Controllers.
1.03 REFERENCE STANDARDS
A. NEMA WD 1 - General Color Requirements for Wiring Devices; 1999 (Reaffirmed 2020).
B. NEMA WD 6 - Wiring Devices - Dimensional Specifications; 2021.
C. NFPA 70 - National Electrical Code; Most Recent Edition Adopted by Authority Having
Jurisdiction, Including All Applicable Amendments and Supplements.
1.04 ADMINISTRATIVE REQUIREMENTS
A. Coordination:
1. Obtain and review shop drawings, product data, manufacturer's wiring diagrams, and manufacturer's instructions for equipment furnished under other sections.
2. Determine connection locations and requirements.
1.05 SUBMITTALS
A. See Section 013000 - Administrative Requirements, for submittal procedures.
B. Product Data: Provide wiring device manufacturer’s catalog information showing dimensions, configurations, and construction.
1.06 QUALITY ASSURANCE
A. Comply with requirements of NFPA 70.
PART 2 PRODUCTS
2.01 MATERIALS
A. Cords and Caps: NEMA WD 6; match receptacle configuration at outlet provided for equipment.
1. Colors: Comply with NEMA WD 1.
2. Cord Construction: NFPA 70, Type SO, multiconductor flexible cord with identified equipment grounding conductor, suitable for use in damp locations.
3. Size: Suitable for connected load of equipment, length of cord, and rating of branch circuit overcurrent protection.
B. Disconnect Switches: As specified in Section 262816.16 and in individual equipment sections.
C. Wiring Devices: As specified in Section 262726.
D. Flexible Conduit: As specified in Section 260533.13.
E. Wire and Cable: As specified in Section 260519.
F. Boxes: As specified in Section 260533.16.
2.02 EQUIPMENT CONNECTIONS
A.
25-388 CBI HVAC and Lighting Upgrade 260583 - 2 Wiring Connections
1. Electrical Connection: Flexible conduit.
2. Electrical Connection: Cord and plug (NEMA 6-20R).
3. Provide field-installed disconnect switch.
PART 3 EXECUTION
3.01 EXAMINATION
A. Verify that equipment is ready for electrical connection, wiring, and energization.
3.02 ELECTRICAL CONNECTIONS
A. Make electrical connections in accordance with equipment manufacturer's instructions.
B. Make conduit connections to equipment using flexible conduit. Use liquidtight flexible conduit with watertight connectors in damp or wet locations.
C. Connect heat producing equipment using wire and cable with insulation suitable for temperatures encountered.
D. Provide receptacle outlet to accommodate connection with attachment plug.
E. Provide cord and cap where field-supplied attachment plug is required.
F. Install suitable strain-relief clamps and fittings for cord connections at outlet boxes and equipment connection boxes.
G. Install disconnect switches, controllers, control stations, and control devices to complete equipment wiring requirements.
H. Install terminal block jumpers to complete equipment wiring requirements.
I. Install interconnecting conduit and wiring between devices and equipment to complete equipment wiring requirements.
END OF SECTION