This is a technical specifications document for Section 232123 (Hydronic Pumps) as part of project 25-388 CBI HVAC and Lighting Upgrade. The specification establishes requirements for five pump categories: system-lubricated circulators, circulators, in-line pumps, end-suction pumps, and dual-drive pump systems. System-lubricated circulators must be horizontal shaft, single-stage units rated for 140 psi maximum working pressure and 230 degrees Fahrenheit maximum water temperature with cast iron casings and stainless steel impellers and shafts. Circulators are specified as horizontal shaft, single-stage pumps with oil-lubricated motors rated up to 125 psi discharge pressure. In-line pumps are closed-coupled, vertical units rated to 175 psi with cast iron casings and mechanical seals rated to 225 degrees Fahrenheit. End-suction pumps must be base-mounted, split-coupled units with oil-lubricated bearings and similar temperature ratings. Dual-drive pump systems consist of horizontal split case, base-mounted pumps with two motors operating at 1,750 rpm and 1,150 rpm with a NEMA OS 1 control cabinet. All pumps must comply with UL 778 minimum quality standards and meet NEMA MG 00001 electrical requirements.
Approved manufacturers for this specification include Armstrong Fluid Technology, Inc., Bell & Gossett (a Xylem Inc. brand), and Taco Comfort Solutions, with substitutions permitted under Section 016000. All pumps must operate within 25 percent of the midpoint of the published maximum efficiency curve and be non-overloading in parallel or individual operation. Installation requirements include alignment certification by qualified millwrights for base-mounted pumps, proper support piping to eliminate weight on pump casings, inclusion of shut-off valves and strainers on suction lines, check valves and balancing valves on discharge lines, and installation on concrete housekeeping bases with anchor bolts. Manufacturers must demonstrate minimum three years of documented experience in pump manufacture, assembly, and field performance. Variable frequency drives must comply with Section 230934 where applicable.
View the file
Other files
Show all 41
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
25-388 CBI HVAC and Lighting Upgrade 232123 - 1 Hydronic Pumps
SECTION 232123
HYDRONIC PUMPS
PART 1 GENERAL
1.01 SECTION INCLUDES
A. System-lubricated circulators.
B. Circulators.
C. In-line pumps.
D. End-suction pumps.
E. Dual-drive pump systems.
1.02 RELATED REQUIREMENTS
A. Section 033000 - Cast-in-Place Concrete.
B. Section 230513 - Common Motor Requirements for HVAC Equipment.
C. Section 230716 - HVAC Equipment Insulation.
D. Section 230719 - HVAC Piping Insulation.
E. Section 232113 - Hydronic Piping.
F. Section 232114 - Hydronic Specialties.
1.03 REFERENCE STANDARDS
A. NEMA MG 00001 - Motors and Generators; 2024.
B. NEMA OS 1 - Sheet-Steel Outlet Boxes, Device Boxes, Covers, and Box Supports; 2013
(Reaffirmed 2020).
C. NFPA 70 - National Electrical Code; Most Recent Edition Adopted by Authority Having
Jurisdiction, Including All Applicable Amendments and Supplements.
D. UL 778 - Standard for Motor-Operated Water Pumps; Current Edition, Including All Revisions.
1.04 SUBMITTALS
A. See Section 013000 - Administrative Requirements for submittal procedures.
B. Product Data: Provide certified pump curves showing performance characteristics with pump and system operating point plotted. Include NPSH curve when applicable. Include electrical characteristics and connection requirements.
C. Millwright's Certificate: Certify that base mounted pumps have been aligned.
D. Manufacturer's Installation Instructions: Indicate hanging and support requirements and recommendations.
E. Operation and Maintenance Data: Include installation instructions, assembly views, lubrication instructions, and replacement parts list.
1.05 QUALITY ASSURANCE
A. Manufacturer Qualifications: Company specializing in manufacture, assembly, and field performance of pumps, with minimum three years of documented experience.
PART 2 PRODUCTS
2.01 MANUFACTURERS
A. Armstrong Fluid Technology, Inc: www.armstrongfluidtechnology.com/#sle.
B. Bell & Gossett, a Xylem Inc. brand: www.bellgossett.com/#sle.
C. Taco Comfort Solutions: www.tacocomfort.com D. Substitutions: See Section 016000 - Product Requirements.
2.02 GENERAL
Upgrade 232123 - 2 Hydronic Pumps
A. Provide pumps that operate at specified system fluid temperatures without vapor binding and cavitation, are non-overloading in parallel or individual operation, and operate within 25 percent of midpoint of published maximum efficiency curve.
B. Minimum Quality Standard: UL 778.
C. Base Mounted Pumps: Aligned by qualified millwright.
D. Electrical Requirements:
1. Listed and classified by UL or testing agency acceptable to authority having jurisdiction as suitable for the purpose specified and indicated.
2. Variable Frequency Drives (VFDs): Provide in accordance with Section 230934, except for integral-VFDs.
3. Enclosures: Provide unspecified product(s) required to fit motor:
2.03 SYSTEM-LUBRICATED CIRCULATORS
A. Horizontal shaft, single stage, direct connected with multiple speed wet rotor motor for in-line mounting, for 140 psi maximum working pressure, 230 degrees F maximum water temperature.
B. Casing: Cast iron with flanged pump connections.
C. Impeller, Shaft, Rotor: Stainless Steel.
D. Bearings: Metal Impregnated carbon (graphite) and ceramic.
E. Motor: Impedance protected, multiple speed, with external speed selector.
2.04 CIRCULATORS
A. Horizontal shaft, single-stage pump with direct connected, resilient-mount, oil lubricated motor for discharge pressures of up to 125 psi.
B. Casing: Cast iron, with flanged pump connections.
C. Impeller: Non-ferrous keyed to shaft.
D. Bearings: Oil-lubricated bronze sleeve.
E. Shaft: Alloy steel with bronze sleeve, integral thrust collar.
F. Seal: Mechanical seal, 225 degrees F maximum continuous duty temperature.
G. Drive: Flexible coupling.
H. Electrical:
1. Wiring Terminations: Provide terminal lugs to match branch circuit conductor quantities, sizes, and materials indicated. Enclose terminal lugs in terminal box sized to NFPA 70.
2.05 IN-LINE PUMPS
A. Closed-Coupled, Single-Stage Pump: Vertical pump with radially- or horizontally-split casing;
rated for discharge pressures up to 175 psi.
B. Casing: Cast iron with seal flush connection, threaded suction, and discharge ports with gauge port and drain plug.
C. Impeller: Bronze, fully enclosed, keyed directly to motor shaft or extension.
D. Shaft: Stainless steel with stainless steel impeller cap screw or nut and bronze sleeve.
E. Seal: Mechanical seal, 225 degrees F maximum continuous duty temperature.
F. Electrical:
1. Wiring Terminations: Provide terminal lugs to match branch circuit conductor quantities, sizes, and materials indicated. Enclose terminal lugs in terminal box sized to NFPA 70.
2.06 END-SUCTION PUMPS
A. Split-Coupled Pump: Base-mounted, single-stage pump with horizontal shaft and radially- or horizontally-split casing rated for discharge pressures up to 175 psi.
Upgrade 232123 - 3 Hydronic Pumps
B. Casing: Cast iron or ductile iron with renewable bronze casing wearing rings, seal flush connection, drain plug, flanged suction, and discharge flanged connections with gauge ports.
C. Impeller: Stainless steel, balanced, fully enclosed, keyed to shaft.
D. Bearings: Oil lubricated roller or ball bearings.
E. Shaft: Alloy steel with copper, bronze, or stainless steel shaft sleeve.
F. Seal: Mechanical, 225 degrees F maximum continuous duty temperature.
G. Seal: Packing gland with minimum four rings graphite impregnated packing and bronze lantern rings, 250 degrees F maximum continuous duty temperature.
H. Drive: Flexible coupling with coupling guard.
I. Baseplate: Cast iron or fabricated steel with integral drain rim.
J. Electrical:
1. Wiring Terminations: Provide terminal lugs to match branch circuit conductor quantities, sizes, and materials indicated. Enclose terminal lugs in terminal box sized to NFPA 70.
2.07 DUAL-DRIVE PUMP SYSTEMS
A. Horizontal split case, base-mounted pump with two motors, operating at 1,750 rpm and 1,150 rpm, assembled on integral base with control cabinet.
B. Control Cabinet: NEMA OS 1, UL approved enclosure with individual circuit breakers, magnetic starters with overload protection, running lights, separate 115V fused control circuit, hands-off-automatic switches, motor failure alarm with manual reset, pre-wired.
C. Electrical Characteristics:
1. Motor:
a. Comply with NEMA MG 00001.
2. Wiring Terminations: Provide terminal lugs to match branch circuit conductor quantities, sizes, and materials indicated. Enclose terminal lugs in terminal box sized to NFPA 70.
PART 3 EXECUTION
3.01 PREPARATION
A. Verify that electric power is available and of the correct characteristics.
3.02 INSTALLATION
A. Install in accordance with manufacturer's instructions.
B. Provide access space around pumps for service. Provide no less than minimum space recommended by manufacturer.
C. Decrease from line size with long radius reducing elbows or reducers. Support piping adjacent to pump such that no weight is carried on pump casings. For close-coupled or base-mounted pumps, provide supports under elbows on pump suction and discharge line sizes 4 inches and over.
D. Provide line sized shut-off valve and strainer on pump suction, and line sized soft seat check valve and balancing valve on pump discharge.
E. Provide air cock and drain connection on horizontal pump casings.
F. Provide drains for bases and seals, piped to and discharging into floor drains.
G. Check, align, and certify alignment of base-mounted pumps prior to start-up.
H. Install close-coupled and base-mounted pumps on concrete housekeeping base, with anchor bolts, set and level, and grout in place. See Section 033000.
I. Lubricate pumps before start-up.
J. Provide side-stream filtration system for closed loop systems. Install across pump with flow from pump discharge to pump suction from pump tappings.
Upgrade 232123 - 4 Hydronic Pumps
K. Controls Human-Machine Interface (HMI): HVAC operator terminal; see Section 253500.
END OF SECTION