262726-RIB-Wiring Devices-12-24-2025.pdf

PDF 85 KB Posted

Attached to
CBI GJ HVAC/Lighting Upgrade Project
Solicitation number
IFB1 REAA 2027000005 1
Issued by
Denver County, Denver City, Colorado

About this file

This is a technical specification document for Section 262726 Wiring Devices, part of Project 25-388 CBI HVAC and Lighting Upgrade (GovTribe ID 262726), prepared for a state or local government entity. The specification outlines requirements for wall switches, wall dimmers, fan speed controllers, receptacles, wall plates and covers, floor box service fittings, poke-through assemblies, and access floor boxes. The document references related sections including access flooring, low-voltage electrical power conductors, grounding and bonding systems, electrical boxes, surface raceways, and lighting control devices. Manufacturers approved for supply include Hubbell Incorporated, Leviton Manufacturing Company, Lutron Electronics Company, Pass & Seymour (Legrand North America), Thomas & Betts Corporation, and Wiremold. The specification requires compliance with multiple standards including NFPA 70 (National Electrical Code), NECA standards, NEMA standards, FS standards, and UL standards for electrical safety and performance.

Product requirements specify industrial specification grade wiring devices with specific electrical ratings, configurations, and safety features. Wall switches must be 20A, 120/277V AC snap switches with silver alloy contacts complying with UL 20 standards. Wall dimmers require solid-state technology with continuous full-range control and UL 1472 compliance. Receptacles must be self-grounding with various configurations including standard convenience receptacles, isolated ground receptacles, weather-resistant receptacles, tamper-resistant receptacles, GFCI receptacles, and USB charging devices. Installation requirements mandate compliance with NECA 1 and NECA 130 standards, proper mounting heights, plumb and level installation, correct grounding procedures, and comprehensive field quality control testing including inspection for damage, operational verification of switches and dimmers, polarity testing of receptacles, and GFCI tripping functionality testing. All materials must be cleaned and restored to factory finish upon completion.

View the file

Other files

File Type Posted
230529-RIB-Hangers and Supports for HVAC Piping and Equipment-12-24-2025.pdf PDF
221005-RIB-Plumbing Piping-12-24-2025.pdf PDF
235216-RIB-Condensing Boilers-12-24-2025.pdf PDF
260519-RIB-Low-Voltage Electrical Power Conductors and Cables-12-24-2025.pdf PDF
230719-RIB-HVAC Piping Insulation-12-24-2025.pdf PDF
221006-RIB-Plumbing Piping Specialties-12-24-2025.pdf PDF
265140-LUT-Luminaires-12-24-2025.pdf PDF
TYPE IU Sure-Lites-SLX-Surface-Mount-LED.pdf PDF
235100-RIB-Breechings, Chimneys, and Stacks-12-24-2025.pdf PDF
230923 Alerton Direct Digital Control System for HVAC.pdf PDF
TYPE P2 Metalux-Cruze-Linear-Bay-spec-sheet.pdf PDF
Bid Questions - BCE Response - 05012026.pdf PDF
230553-RIB-Identification for HVAC Piping and Equipment-12-24-2025.pdf PDF
265600-RIB-Exterior Lighting-12-24-2025.pdf PDF
230593-RIB-Testing, Adjusting, and Balancing for HVAC-12-24-2025.pdf PDF
260583-RIB-Wiring Connections-12-24-2025.pdf PDF
260553-RIB-Identification for Electrical Systems-12-24-2025.pdf PDF
230513-RIB-Common Motor Requirements for HVAC Equipment-12-24-2025.pdf PDF
220553-RIB-Identification for Plumbing Piping and Equipment-12-24-2025.pdf PDF
233100-RIB-HVAC Ducts and Casings-12-24-2025.pdf PDF
233423-RIB-HVAC Power Ventilators-12-24-2025.pdf PDF
265100-RIB-Interior Lighting-12-24-2025.pdf PDF
237413-RIB-Packaged Outdoor Central-Station Air-Handling Units-12-24-2025.pdf PDF
TYPE EMX CMB-ISOLITE-Specification.pdf PDF
230523-RIB-General-Duty Valves for HVAC Piping-12-24-2025.pdf PDF
25388-CBI 100% CD w Add1.pdf PDF
232113-RIB-Hydronic Piping-12-24-2025.pdf PDF
TYPE S1 iO-CoviO-Spec-Sheet.pdf PDF
232123-RIB-Hydronic Pumps-12-24-2025.pdf PDF
260923-RIB-Lighting Control Devices-12-24-2025.pdf PDF
TYPE P1 Corelite-Iridium-i3-Suspended-specification-sheet.pdf PDF
238126.13-RIB-Small-Capacity Split-System Air Conditioners-12-24-2025.pdf PDF
220529-RIB-Hangers and Supports for Plumbing Piping and Equipment-12-24-2025.pdf PDF
231123-RIB-Facility Natural-Gas Piping-12-24-2025.pdf PDF
232114-RIB-Hydronic Specialties-12-24-2025.pdf PDF
230913-RIB-Instrumentation and Control Devices for HVAC-12-24-2025.pdf PDF
260505-RIB-Selective Demolition for Electrical-12-24-2025.pdf PDF
CBI GJ Project Manual_VSS_R2.pdf PDF
230800-RIB-Commissioning of HVAC-12-24-2025.pdf PDF
TYPE D3 PrentaLux-CYL6-6-Sustainable-LED-Cylinder-Luminaire-Spec-Sheet.pdf PDF
Show all 40

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

25-388 CBI HVAC and Lighting Upgrade 262726 - 1 Wiring Devices

SECTION 262726

WIRING DEVICES

PART 1 GENERAL

1.01 SECTION INCLUDES

A. Wall switches.

B. Wall dimmers.

C. Fan speed controllers.

D. Receptacles.

E. Wall plates and covers.

F. Floor box service fittings.

G. Poke-through assemblies.

H. Access floor boxes.

1.02 RELATED REQUIREMENTS

A. Section 096900 - Access Flooring.

B. Section 260519 - Low-Voltage Electrical Power Conductors and Cables: Manufactured wiring systems for use with access floor boxes with compatible pre-wired connectors.

C. Section 260526 - Grounding and Bonding for Electrical Systems.

D. Section 260533.16 - Boxes for Electrical Systems.

E. Section 260533.23 - Surface Raceways for Electrical Systems: Surface raceway systems, including multioutlet assemblies.

F. Section 260553 - Identification for Electrical Systems: Identification products and requirements.

G. Section 260583 - Wiring Connections: Cords and plugs for equipment.

H. Section 260923 - Lighting Control Devices: Devices for automatic control of lighting, including occupancy sensors, in-wall time switches, and in-wall interval timers.

I. Section 262723 - Indoor Service Poles.

1.03 REFERENCE STANDARDS

A. FS W-C-596 - Connector, Electrical, Power, General Specification for; 2014h (Validated 2022).

B. FS W-S-896 - Switches, Toggle (Toggle and Lock), Flush Mounted (General Specification);

2017g (Validated 2023).

C. NECA 1 - Standard for Good Workmanship in Electrical Construction; 2023.

D. NECA 130 - Standard for Installing and Maintaining Wiring Devices; 2016.

E. NEMA WD 1 - General Color Requirements for Wiring Devices; 1999 (Reaffirmed 2020).

F. NEMA WD 6 - Wiring Devices - Dimensional Specifications; 2021.

G. NFPA 70 - National Electrical Code; Most Recent Edition Adopted by Authority Having

Jurisdiction, Including All Applicable Amendments and Supplements.

H. UL 20 - General-Use Snap Switches; Current Edition, Including All Revisions.

I. UL 498 - Attachment Plugs and Receptacles; Current Edition, Including All Revisions.

J. UL 514D - Cover Plates for Flush-Mounted Wiring Devices; Current Edition, Including All

Revisions.

K. UL 943 - Ground-Fault Circuit-Interrupters; Current Edition, Including All Revisions.

L. UL 1310 - Class 2 Power Units; Current Edition, Including All Revisions.

M. UL 1449 - Standard for Surge Protective Devices; Current Edition, Including All Revisions.

Upgrade 262726 - 2 Wiring Devices

N. UL 1472 - Solid-State Dimming Controls; Current Edition, Including All Revisions.

O. UL 1917 - Solid-State Fan Speed Controls; Current Edition, Including All Revisions.

1.04 ADMINISTRATIVE REQUIREMENTS

A. Coordination:

1. Coordinate the placement of outlet boxes with millwork, furniture, equipment, etc. installed under other sections or by others.

2. Coordinate wiring device ratings and configurations with the electrical requirements of actual equipment to be installed.

3. Coordinate the installation and preparation of uneven surfaces, such as split face block, to provide suitable surface for installation of wiring devices.

4. Coordinate the core drilling of holes for poke-through assemblies with the work covered under other sections.

5. Notify Architect of any conflicts or deviations from Contract Documents to obtain direction prior to proceeding with work.

1.05 SUBMITTALS

A. See Section 013000 - Administrative Requirements, for submittal procedures.

B. Product Data: Provide manufacturer's catalog information showing dimensions, colors, and configurations.

1.06 QUALITY ASSURANCE

A. Comply with requirements of NFPA 70.

B. Products: Listed, classified, and labeled as suitable for the purpose intended.

PART 2 PRODUCTS

2.01 WIRING DEVICES - GENERAL REQUIREMENTS

A. Provide wiring devices suitable for intended use with ratings adequate for load served.

2.02 WALL SWITCHES

A. Manufacturers:

1. Hubbell Incorporated: www.hubbell.com/#sle.

2. Leviton Manufacturing Company, Inc: www.leviton.com/#sle.

3. Pass & Seymour, a brand of Legrand North America, Inc: www.legrand.us/#sle.

B. General Requirements: AC only, quiet operating, general-use snap switches with silver alloy contacts, complying with NEMA WD 1 and NEMA WD 6, and listed as complying with UL 20 and where applicable, FS W-S-896; types as indicated on the drawings.

1. Wiring Provisions: Terminal screws for side wiring and screw actuated binding clamp for back wiring with separate ground terminal screw.

C. Standard Wall Switches: Industrial specification grade, 20 A, 120/277 V with standard toggle type switch actuator and maintained contacts; single pole single throw, double pole single throw, three way, or four way as indicated on the drawings.

2.03 WALL DIMMERS

A. Manufacturers:

1. Leviton Manufacturing Company, Inc: www.leviton.com/#sle.

2. Lutron Electronics Company, Inc: www.lutron.com/#sle.

3. Pass & Seymour, a brand of Legrand North America, Inc: www.legrand.us/#sle.

B. General Requirements: Solid-state with continuous full-range even control following square law dimming curve, integral radio frequency interference filtering, power failure preset memory, air gap switch accessible without removing wall plate, complying with NEMA WD 1 and NEMA WD 6, and listed as complying with UL 1472; types and ratings suitable for load controlled as indicated on the drawings.

C. Control: Slide control type with separate on/off switch.

Upgrade 262726 - 3 Wiring Devices

2.04 FAN SPEED CONTROLLERS

A. Manufacturers:

1. Leviton Manufacturing Company, Inc: www.leviton.com/#sle.

2. Lutron Electronics Company, Inc: www.lutron.com/#sle.

3. Pass & Seymour, a brand of Legrand North America, Inc: www.legrand.us/#sle.

B. Description: 120 V AC, solid-state, full-range variable speed, slide control type with separate on/off switch, with integral radio frequency interference filtering, fan noise elimination circuitry, power failure preset memory, complying with NEMA WD 1 and NEMA WD 6, and listed as complying with UL 1917.

1. Current Rating: 1.5 A unless otherwise indicated or required to control the load indicated on the drawings.

2.05 RECEPTACLES

A. Manufacturers:

1. Hubbell Incorporated: www.hubbell.com/#sle.

2. Leviton Manufacturing Company, Inc: www.leviton.com/#sle.

3. Lutron Electronics Company, Inc: www.lutron.com/#sle.

4. Pass & Seymour, a brand of Legrand North America, Inc: www.legrand.us/#sle.

B. General Requirements: Self-grounding, complying with NEMA WD 1 and NEMA WD 6, and listed as complying with UL 498, and where applicable, FS W-C-596; types as indicated on the drawings.

1. Wiring Provisions: Terminal screws for side wiring or screw actuated binding clamp for back wiring with separate ground terminal screw.

2. NEMA configurations specified are according to NEMA WD 6.

C. Convenience Receptacles:

1. Standard Convenience Receptacles: Industrial specification grade, 20A, 125V, NEMA 5-

20R; single or duplex as indicated on the drawings.

2. Isolated Ground Convenience Receptacles: Industrial specification grade, 20A, 125V, NEMA 5-20R, with ground contacts isolated from mounting strap; isolated ground triangle mark on device face; single or duplex as indicated on the drawings.

3. Weather Resistant Convenience Receptacles: Industrial specification grade, 20A, 125V, NEMA 5-20R, listed and labeled as weather resistant type complying with UL 498 Supplement SE suitable for installation in damp or wet locations; single or duplex as indicated on the drawings.

4. Tamper Resistant Convenience Receptacles: Industrial specification grade, 20A, 125V, NEMA 5-20R, listed and labeled as tamper resistant type; single or duplex as indicated on the drawings.

D. GFCI Receptacles:

1. General Requirements: Self-testing, with feed-through protection and light to indicate ground fault tripped condition and loss of protection; listed as complying with UL 943, class A.

2. Weather Resistant GFCI Receptacles: Industrial specification grade, duplex, 20A, 125V, NEMA 5-20R, rectangular decorator style, listed and labeled as weather resistant type complying with UL 498 Supplement SD suitable for installation in damp or wet locations.

3. Tamper Resistant GFCI Receptacles: Industrial specification grade, duplex, 20A, 125V, NEMA 5-20R, rectangular decorator style, listed and labeled as tamper resistant type.

E. USB Charging Devices:

1. General Requirements: Listed as complying with UL 1310.

2.06 WALL PLATES AND COVERS

A. Manufacturers:

1. Hubbell Incorporated: www.hubbell-wiring.com/#sle.

2. Leviton Manufacturing Company, Inc: www.leviton.com/#sle.

Upgrade 262726 - 4 Wiring Devices

3. Lutron Electronics Company, Inc: www.lutron.com/#sle.

4. Pass & Seymour, a brand of Legrand North America, Inc: www.legrand.us/#sle.

B. Wall Plates: Comply with UL 514D.

1. Configuration: One piece cover as required for quantity and types of corresponding wiring devices.

2. Size: Standard.

3. Screws: Metal with slotted heads finished to match wall plate finish.

C. Nylon Wall Plates: Smooth finish, high-impact thermoplastic.

D. Stainless Steel Wall Plates: Brushed satin finish, Type 302 stainless steel.

E. Weatherproof Covers for Wet Locations: Gasketed, cast aluminum, with hinged lockable cover and corrosion-resistant screws; listed as suitable for use in wet locations while in use with attachment plugs connected and identified as extra-duty type.

2.07 FLOOR BOX SERVICE FITTINGS

A. Manufacturers:

1. Hubbell Incorporated: www.hubbell.com/#sle.

2. Thomas & Betts Corporation: www.tnb.com/#sle.

3. Wiremold, a brand of Legrand North America, Inc: www.legrand.us/#sle.

B. Description: Service fittings compatible with floor boxes provided under Section 260533.16 with components, adapters, and trims required for complete installation.

2.08 POKE-THROUGH ASSEMBLIES

A. Manufacturers:

1. Hubbell Incorporated: www.hubbell.com/#sle.

2. Thomas & Betts Corporation: www.tnb.com/#sle.

3. Wiremold, a brand of Legrand North America, Inc: www.legrand.us/#sle.

B. Description: Assembly comprising floor service fitting, poke-through component, fire stops and smoke barriers, and junction box for conduit termination; fire rating listed to match fire rating of floor and suitable for floor thickness where installed.

2.09 ACCESS FLOOR BOXES

A. Manufacturers - Access Floor Boxes:

1. Hubbell Incorporated: www.hubbell-wiring.com/#sle.

2. Thomas & Betts Corporation: www.tnb.com/#sle.

3. Wiremold, a brand of Legrand North America, Inc: www.legrand.us/#sle.

B. Description: Metallic multi-service box suitable for mounting in access floor system.

C. Configuration:

PART 3 EXECUTION

3.01 EXAMINATION

A. Verify that field measurements are as indicated.

B. Verify that outlet boxes are installed in proper locations and at proper mounting heights and are properly sized to accommodate devices and conductors in accordance with NFPA 70.

C. Verify that wall openings are neatly cut and will be completely covered by wall plates.

D. Verify that final surface finishes are complete, including painting.

E. Verify that branch circuit wiring installation is completed, tested, and ready for connection to wiring devices.

F. Verify that conditions are satisfactory for installation prior to starting work.

3.02 PREPARATION

A. Provide extension rings to bring outlet boxes flush with finished surface.

Upgrade 262726 - 5 Wiring Devices

B. Clean dirt, debris, plaster, and other foreign materials from outlet boxes.

3.03 INSTALLATION

A. Perform work in accordance with NECA 1 (general workmanship) and, where applicable, NECA 130, including mounting heights specified in those standards unless otherwise indicated.

B. Coordinate locations of outlet boxes provided under Section 260533.16 as required for installation of wiring devices provided under this section.

C. Install wiring devices in accordance with manufacturer's instructions.

D. Install permanent barrier between ganged wiring devices when voltage between adjacent devices exceeds 300 V.

E. Where required, connect wiring devices using pigtails not less than 6 inches long. Do not connect more than one conductor to wiring device terminals.

F. Connect wiring devices by wrapping conductor clockwise 3/4 turn around screw terminal and tightening to proper torque specified by the manufacturer. Where present, do not use push-in pressure terminals that do not rely on screw-actuated binding.

G. Unless otherwise indicated, connect wiring device grounding terminal to branch circuit equipment grounding conductor and to outlet box with bonding jumper.

H. For isolated ground receptacles, connect wiring device grounding terminal only to identified branch circuit isolated equipment grounding conductor. Do not connect grounding terminal to outlet box or normal branch circuit equipment grounding conductor.

I. Install wiring devices plumb and level with mounting yoke held rigidly in place.

J. Install wall switches with OFF position down.

K. Install wall dimmers to achieve full rating specified and indicated after derating for ganging as instructed by manufacturer.

L. Do not share neutral conductor on branch circuits utilizing wall dimmers.

M. Install vertically mounted receptacles with grounding pole on top and horizontally mounted receptacles with grounding pole on left.

N. Install wall plates to fit completely flush to wall with no gaps and rough opening completely covered without strain on wall plate. Repair or reinstall improperly installed outlet boxes or improperly sized rough openings. Do not use oversized wall plates in lieu of meeting this requirement.

O. Install blank wall plates on junction boxes and on outlet boxes with no wiring devices installed or designated for future use.

P. Install poke-through closure plugs in each unused core holes to maintain fire rating of floor.

3.04 FIELD QUALITY CONTROL

A. See Section 014000 - Quality Requirements, for additional requirements.

B. Inspect each wiring device for damage and defects.

C. Operate each wall switch, wall dimmer, and fan speed controller with circuit energized to verify proper operation.

D. Test each receptacle to verify operation and proper polarity.

E. Test each GFCI receptacle for proper tripping operation according to manufacturer's instructions.

F. Correct wiring deficiencies and replace damaged or defective wiring devices.

3.05 ADJUSTING

A. Adjust devices and wall plates to be flush and level.

3.06 CLEANING

Upgrade 262726 - 6 Wiring Devices

A. Clean exposed surfaces to remove dirt, paint, or other foreign material and restore to match original factory finish.

END OF SECTION

262726 - Wiring Devices