This is a technical specifications document for HVAC piping insulation work included in Project 25-388 CBI HVAC and Lighting Upgrade. The scope of work encompasses the installation of piping insulation, flexible removable and reusable blanket insulation, jacketing, and accessories for heating and cooling systems. The specifications detail materials and installation requirements for various piping applications including heating water supply and return lines, low-pressure steam piping, chilled water lines, condenser water piping, and refrigerant suction and hot gas lines. The document establishes minimum qualifications for applicators (minimum 3 years of experience) and manufacturers (minimum 3 years of documented experience) and requires compliance with multiple ASTM standards and UL testing protocols. Installation must maintain ambient conditions and temperature requirements for 24 hours before, during, and after application, with all work performed in accordance with manufacturer's instructions.
The specifications establish performance requirements for insulation products including thermal characteristics, maximum service temperatures, moisture absorption limits, and flame spread ratings of 25/50 maximum per ASTM E84 or UL 723. Approved manufacturers are identified for glass fiber flexible insulation, glass fiber rigid insulation, hydrous calcium silicate, and flexible elastomeric cellular insulation, with provisions for approved substitutions. The insulation schedule specifies thickness requirements based on fluid temperature ranges and pipe diameter, ranging from 0.5 inches for chilled water and condenser water applications to 5 inches for low-pressure steam piping. Exterior applications require vapor barrier jackets with aluminum covers, while buried piping requires factory-fabricated assemblies with bituminous compound protection. Heat-traced piping and piping in mechanical equipment rooms have specific finish and jacket requirements outlined in the execution section.
View the file
Other files
Show all 40
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
25-388 CBI HVAC and Lighting Upgrade 230719 - 1 HVAC Piping Insulation
SECTION 230719
HVAC PIPING INSULATION
PART 1 GENERAL
1.01 SECTION INCLUDES
A. Piping insulation.
B. Flexible removable and reusable blanket insulation.
C. Jacketing and accessories.
D. Engineered wall outlet seals and refrigerant piping insulation protection.
1.02 RELATED REQUIREMENTS
A. Section 078400 - Firestopping.
B. Section 232113 - Hydronic Piping: Placement of hangers and hanger inserts.
C. Section 232300 - Refrigerant Piping: Placement of inserts.
1.03 REFERENCE STANDARDS
A. ASTM C177 - Standard Test Method for Steady-State Heat Flux Measurements and Thermal
Transmission Properties by Means of the Guarded-Hot-Plate Apparatus; 2019, with Editorial Revision (2023).
B. ASTM C195 - Standard Specification for Mineral Fiber Thermal Insulating Cement; 2007 (Reapproved 2024).
C. ASTM C449 - Standard Specification for Mineral Fiber Hydraulic-Setting Thermal Insulating and Finishing Cement; 2007 (Reapproved 2024).
D. ASTM C518 - Standard Test Method for Steady-State Thermal Transmission Properties by Means of the Heat Flow Meter Apparatus; 2021.
E. ASTM C533 - Standard Specification for Calcium Silicate Block and Pipe Thermal Insulation;
2017 (Reapproved 2023).
F. ASTM C534/C534M - Standard Specification for Preformed Flexible Elastomeric Cellular Thermal Insulation in Sheet and Tubular Form; 2025.
G. ASTM C547 - Standard Specification for Mineral Fiber Pipe Insulation; 2022a.
H. ASTM C553 - Standard Specification for Mineral Fiber Blanket Thermal Insulation for
Commercial and Industrial Applications; 2024.
I. ASTM C795 - Standard Specification for Thermal Insulation for Use in Contact with Austenitic
Stainless Steel; 2008 (Reapproved 2023).
J. ASTM D570 - Standard Test Method for Water Absorption of Plastics; 2022.
K. ASTM E84 - Standard Test Method for Surface Burning Characteristics of Building Materials;
2024.
L. ASTM E96/E96M - Standard Test Methods for Gravimetric Determination of Water Vapor
Transmission Rate of Materials; 2024a.
M. ASTM E283/E283M - Standard Test Method for Determining Rate of Air Leakage Through
Exterior Windows, Skylights, Curtain Walls, and Doors Under Specified Pressure Differences Across the Specimen; 2019.
N. ASTM E331 - Standard Test Method for Water Penetration of Exterior Windows, Skylights, Doors, and Curtain Walls by Uniform Static Air Pressure Difference; 2000 (Reapproved 2023).
O. ASTM E2178 - Standard Test Method for Determining Air Leakage Rate and Calculation of Air Permeance of Building Materials; 2021a.
P. ASTM G21 - Standard Practice for Determining Resistance of Synthetic Polymeric Materials to Fungi; 2015, with Editorial Revision (2021).
Upgrade 230719 - 2 HVAC Piping Insulation
Q. ASTM G153 - Standard Practice for Operating Enclosed Carbon Arc Light Apparatus for Exposure of Nonmetallic Materials; 2013 (Reapproved 2021).
R. UL 723 - Standard for Test for Surface Burning Characteristics of Building Materials; Current Edition, Including All Revisions.
1.04 SUBMITTALS
A. See Section 013000 - Administrative Requirements for submittal procedures.
B. Product Data: Provide product description, thermal characteristics, list of materials and thickness for each service, and locations.
1.05 QUALITY ASSURANCE
A. Manufacturer Qualifications: Company specializing in manufacturing the Products specified in this section with not less than three years of documented experience.
B. Applicator Qualifications: Company specializing in performing the type of work specified in this section with minimum 3 years of experience.
1.06 DELIVERY, STORAGE, AND HANDLING
A. Accept materials on site, labeled with manufacturer's identification, product density, and thickness.
1.07 FIELD CONDITIONS
A. Maintain ambient conditions required by manufacturers of each product.
B. Maintain temperature before, during, and after installation for minimum of 24 hours.
PART 2 PRODUCTS
2.01 REGULATORY REQUIREMENTS
A. Surface Burning Characteristics: Flame spread index/Smoke developed index of 25/50, maximum, when tested in accordance with ASTM E84 or UL 723.
2.02 GLASS FIBER, FLEXIBLE
A. Manufacturers:
1. JP Lamborn Co; Thermal Sleeve MT: www.jpflex.com/#sle.
2. Substitutions: See Section 016000 - Product Requirements.
B. Insulation: ASTM C553; flexible, noncombustible blanket.
1. K Value: 0.36 at 75 degrees F, when tested in accordance with ASTM C518.
2. Maximum Service Temperature: 1,200 degrees F.
3. Maximum Water Vapor Absorption: 5.0 percent by weight.
C. Vapor Barrier Jacket:
1. Kraft paper with glass fiber yarn and bonded to aluminized film.
2. Moisture Vapor Permeability: 0.02 perm inch, when tested in accordance with ASTM
E96/E96M.
3. Secure with pressure-sensitive tape.
D. Vapor Barrier Tape:
1. Kraft paper reinforced with glass fiber yarn and bonded to aluminized film with pressure-sensitive rubber-based adhesive.
E. Outdoor Vapor Barrier Mastic:
1. Vinyl emulsion type acrylic or mastic, compatible with insulation, black color.
F. Tie Wire: Annealed steel, 16 gauge, 0.0508 inch diameter.
2.03 GLASS FIBER, RIGID
A. Manufacturers:
1. CertainTeed Corporation: www.certainteed.com/#sle.
2. Johns Manville Corporation: www.jm.com/#sle.
Upgrade 230719 - 3 HVAC Piping Insulation
3. Knauf Insulation; Performance+ Earthwool 1000 Pipe Insulation:
www.knaufinsulation.com/#sle.
4. Owens Corning Corporation; Fiberglas Pipe Insulation ASJ: www.owenscorning.com/en-us/#sle.
5. Owens Corning Corporation; VaporWick Pipe Insulation: www.owenscorning.com/en-us/#sle.
6. Substitutions: See Section 016000 - Product Requirements.
B. Insulation: ASTM C547 and ASTM C795; rigid molded, noncombustible.
1. K Value: ASTM C177, 0.24 at 75 degrees F.
2. Maximum Service Temperature: 850 degrees F.
3. Maximum Moisture Absorption: 0.2 percent by volume.
C. Vapor Barrier Jacket: White kraft paper with glass fiber yarn, bonded to aluminized film;
moisture vapor transmission when tested in accordance with ASTM E96/E96M of 0.02 perm-inches.
D. Tie Wire: 0.048 inch stainless steel with twisted ends on maximum 12 inch centers.
E. Vapor Barrier Lap Adhesive: Compatible with insulation.
F. Insulating Cement/Mastic: ASTM C195; hydraulic setting on mineral wool.
G. Fibrous Glass Fabric:
1. Cloth: Untreated; 9 oz/sq yd weight.
2. Blanket: 1.0 pcf density.
3. Weave: 5 by 5.
H. Indoor Vapor Barrier Finish:
1. Cloth: Untreated; 9 oz/sq yd weight.
2. Vinyl emulsion type acrylic, compatible with insulation, black color.
I. Outdoor Vapor Barrier Mastic: Vinyl emulsion type acrylic or mastic, compatible with insulation, black color.
J. Insulating Cement: ASTM C449.
2.04 FLEXIBLE REMOVABLE AND REUSABLE BLANKET INSULATION
A. Manufacturers:
1. Substitutions: See Section 016000 - Product Requirements.
B. Description: Custom cut and fabricated, removable and reusable blanket insulation system, consisting of inner liner, insulation layer, outer protective jacket, and fastening system.
C. Provide insulation system based on surface temperature of piping, installed location of piping, and maximum safe-to-touch temperature of jacketing.
D. Performance Criteria:
1. Safe-to-Touch Temperature of Jacketing: 140 degrees F.
2.05 HYDROUS CALCIUM SILICATE
A. Manufacturers:
1. Johns Manville Corporation; ______: www.jm.com/#sle.
2. Substitutions: See Section 016000 - Product Requirements.
B. Insulation: ASTM C533 and ASTM C795; rigid molded, asbestos free, gold color.
1. K Value: 0.40 at 300 degrees F, when tested in accordance with ASTM C177 or ASTM
C518.
2. Maximum Service Temperature: 1200 degrees F.
3. Density: 15 pcf.
C. Tie Wire: 0.048 inch stainless steel with twisted ends on maximum 12 inch centers.
D. Insulating Cement: ASTM C449.
Upgrade 230719 - 4 HVAC Piping Insulation
2.06 FLEXIBLE ELASTOMERIC CELLULAR INSULATION
A. Manufacturers:
B. Insulation: Preformed flexible elastomeric cellular rubber insulation complying with ASTM
C534/C534M Grade 1; use molded tubular material wherever possible.
1. Minimum Service Temperature: Minus 40 degrees F.
2. Maximum Service Temperature: 180 degrees F.
3. Connection: Waterproof vapor barrier adhesive.
C. Elastomeric Foam Adhesive: Air dried, contact adhesive, compatible with insulation.
2.07 JACKETING AND ACCESSORIES
2.08 ENGINEERED WALL OUTLET SEALS AND REFRIGERANT PIPING INSULATION
PROTECTION
A. Manufacturers:
1. Airex Manufacturing, Inc; ____: www.airexmfg.com/#sle.
2. Substitutions: See Section 016000 - Product Requirements.
B. Basis of Design: Airex Manufacturing, Inc; www.airexmfg.com/#sle.
1. Pipe Penetration Wall Seal: Airex Titan Outlet.
2. Refrigeration Pipe Insulation Protection System: Airex E-Flex Guard.
3. Pipe Penetration Wall Seal and Insulation Protection System: Airex Pro-System Kit.
C. Pipe Penetration Wall Seal: Seals HVAC piping wall penetrations with compression gasket wall mounted rigid plastic outlet cover.
1. Wall Outlet Size, Stucco and Masonry Applications: 7-1/2 inch wide by 10 inch high.
a. Elastomeric Sleeve Diameter: 1-11/16 inch.
2. Wall Outlet Size, Siding and Compact Applications: 6-7/8 inch wide by 3-7/8 inch high.
a. Elastomeric Sleeve Diameter: 1-11/16 inch.
3. Outlet Cover Color: Gray.
4. Water Penetration: Comply with ASTM E331.
5. Air Leakage: Comply with ASTM E283/E283M.
6. Air Permeance: Comply with ASTM E2178.
D. Insulation Protection System: Refrigerant piping insulation PVC protective cover.
1. PVC Insulation Cover Color: Black with full-length velcro fastener.
2. Weatherization and Ultraviolet Exposure Protection: Comply with ASTM G153.
3. Water/Vapor Permeability: Comply with ASTM E96/E96M.
4. Anti-Fungal and Anti-Microbial Resistance: Comply with ASTM G21.
5. Flame Spread and Smoke Development Rating of 24/450: Comply with ASTM E84 or UL
723.
6. Water Absorption of Plastics: Comply with ASTM D570.
7. Adhesive free.
PART 3 EXECUTION
3.01 EXAMINATION
A. Test piping for design pressure, liquid tightness, and continuity prior to applying insulation materials.
B. Verify that surfaces are clean and dry, with foreign material removed.
3.02 INSTALLATION
A. Install in accordance with manufacturer's instructions.
B. Exposed Piping: Locate insulation and cover seams in least visible locations.
C. Insulated Pipes Conveying Fluids Below Ambient Temperature:
1. Insulate entire system, including fittings, valves, unions, flanges, strainers, flexible connections, pump bodies, and expansion joints.
Upgrade 230719 - 5 HVAC Piping Insulation
D. Glass Fiber Insulated Pipes Conveying Fluids Below Ambient Temperature:
1. Provide vapor barrier jackets, factory-applied or field-applied; secure with self-sealing longitudinal laps and butt strips with pressure-sensitive adhesive. Secure with outward clinch expanding staples and vapor barrier mastic.
2. Insulate fittings, joints, and valves with molded insulation of like material and thickness as adjacent pipe. Finish with glass cloth and vapor barrier adhesive or PVC fitting covers.
E. For hot piping conveying fluids 140 degrees F or less, do not insulate flanges and unions at equipment, but bevel and seal ends of insulation.
F. For hot piping conveying fluids over 140 degrees F, insulate flanges and unions at equipment.
G. Glass Fiber Insulated Pipes Conveying Fluids Above Ambient Temperature:
1. Provide standard jackets, with or without vapor barrier, factory-applied, or field-applied.
Secure with self-sealing longitudinal laps and butt strips with pressure-sensitive adhesive.
Secure with outward clinch expanding staples.
2. Insulate fittings, joints, and valves with insulation of like material and thickness as adjoining pipe. Finish with glass cloth and adhesive or PVC fitting covers.
H. Inserts and Shields:
1. Application: Piping 1-1/2 inches diameter or larger.
2. Shields: Galvanized steel between pipe hangers or pipe hanger rolls and inserts.
3. Insert location: Between support shield and piping and under the finish jacket.
4. Insert Configuration: Minimum 6 inches long, of same thickness and contour as adjoining insulation; may be factory fabricated.
5. Insert Material: Hydrous calcium silicate insulation or other heavy density insulating material suitable for the planned temperature range.
I. Continue insulation through walls, sleeves, pipe hangers, and other pipe penetrations. Finish at supports, protrusions, and interruptions. At fire separations, see Section 078400.
J. Pipe Exposed in Mechanical Equipment Rooms or Finished Spaces (less than 10 feet above finished floor): Finish with ASJ vapor retarder jacket and longitudinal self sealing closure.
K. Exterior Applications: Provide vapor barrier jacket. Insulate fittings, joints, and valves with insulation of like material and thickness as adjoining pipe, and finish with glass mesh reinforced vapor barrier cement. Cover with aluminum jacket with seams located on bottom side of horizontal piping. Provide two coats of UV-resistant finish for flexible elastomeric cellular insulation without jacketing.
L. Buried Piping: Provide factory-fabricated assembly with inner all-purpose service jacket with self-sealing lap, and asphalt impregnated open mesh glass fabric, with 1 mil, 0.001 inch thick aluminum foil sandwiched between three layers of bituminous compound; outer surface faced with polyester film.
M. Heat Traced Piping: Insulate fittings, joints, and valves with insulation of like material, thickness, and finish as adjoining pipe. Size large enough to enclose pipe and heat tracer.
Cover with aluminum jacket with seams located on bottom side of horizontal piping.
3.03 SCHEDULE
A. Heating Systems:
1. Heating Water Supply and Return: Fluid range: 105-140 deg F - less than 1.5" diameter:
1" rigid glass fiber, 1-1/2" and greater diameter piping: 1.5" rigid glass fiber. Fluid range:
141-200 deg F - less than 1.5" diameter: 1.5" rigid glass fiber, 1-1/2" and greater diameter piping: 2" rigid glass fiber.
2. Low Pressure Steam Piping: Less than 1.0" diameter: 4.5" rigid glass fiber, 1.0-8" diameter piping: 5" rigid glass fiber.
3. Low Pressure Steam Condensate: Less than 1.0" diameter: 4.5" rigid glass fiber, 1.0-8" diameter piping: 5" rigid glass fiber.
B. Cooling Systems:
Upgrade 230719 - 6 HVAC Piping Insulation
1. Chilled Water: Fluid range: 40-60 deg F - less than 1.5" diameter: 0.5" rigid glass fiber, 1- 1/2" and greater diameter piping: 1" rigid glass fiber.
2. Condenser Water: Less than 1.5" diameter: 0.5" rigid glass fiber, 1-1/2" and greater diameter piping: 1" rigid glass fiber.
3. Refrigerant Suction: Less than 1" diameter piping: 0.5" flexible elastomeric, 1" and greater diameter piping: 1" flexible elastomeric insulation.
4. Refrigerant Hot Gas: Less than 1" diameter piping: 0.5" flexible elastomeric, 1" and greater diameter piping: 1" flexible elastomeric insulation.
END OF SECTION
230719 - HVAC Piping Insulation