232123-RIB-Hydronic Pumps-12-24-2025.pdf

PDF 73 KB Posted

Attached to
CBI GJ HVAC/Lighting Upgrade Project
Solicitation number
IFB1 REAA 2027000005 1
Issued by
Denver County, Denver City, Colorado

About this file

This is a specification section document for the CBI HVAC and Lighting Upgrade project (25-388), specifically detailing requirements for hydronic pumps as part of a state and local contract opportunity. The specification outlines five primary pump types to be supplied: system-lubricated circulators, circulators, in-line pumps, end-suction pumps, and dual-drive pump systems. The document does not specify item quantities, response dates, due dates, site visits, bidders' meetings, award dates, or contract terms. Instead, it establishes technical and performance requirements for pump manufacturers and installation standards that bidders must meet.

The specification identifies three approved manufacturers: Armstrong Fluid Technology, Inc., Bell & Gossett (a Xylem Inc. brand), and Taco Comfort Solutions, with substitutions allowed per Section 016000. All pumps must meet UL 778 quality standards and operate within specified performance parameters, including pressure ratings up to 175 psi and temperature limitations up to 250 degrees Fahrenheit depending on pump type. The document requires comprehensive submittals including certified pump curves, manufacturer installation instructions, operation and maintenance data, and millwright certification for aligned base-mounted pumps. Installation requirements mandate proper piping support, valve installation, air cocks, drain connections, concrete bases with anchor bolts, and side-stream filtration systems for closed-loop applications. No pricing information, set-asides, incumbent contractors, or specific funding sources are detailed in this specification document.

View the file

Other files

File Type Posted
230529-RIB-Hangers and Supports for HVAC Piping and Equipment-12-24-2025.pdf PDF
221005-RIB-Plumbing Piping-12-24-2025.pdf PDF
235216-RIB-Condensing Boilers-12-24-2025.pdf PDF
260519-RIB-Low-Voltage Electrical Power Conductors and Cables-12-24-2025.pdf PDF
230719-RIB-HVAC Piping Insulation-12-24-2025.pdf PDF
221006-RIB-Plumbing Piping Specialties-12-24-2025.pdf PDF
265140-LUT-Luminaires-12-24-2025.pdf PDF
TYPE IU Sure-Lites-SLX-Surface-Mount-LED.pdf PDF
235100-RIB-Breechings, Chimneys, and Stacks-12-24-2025.pdf PDF
230923 Alerton Direct Digital Control System for HVAC.pdf PDF
TYPE P2 Metalux-Cruze-Linear-Bay-spec-sheet.pdf PDF
Bid Questions - BCE Response - 05012026.pdf PDF
230553-RIB-Identification for HVAC Piping and Equipment-12-24-2025.pdf PDF
265600-RIB-Exterior Lighting-12-24-2025.pdf PDF
230593-RIB-Testing, Adjusting, and Balancing for HVAC-12-24-2025.pdf PDF
260583-RIB-Wiring Connections-12-24-2025.pdf PDF
260553-RIB-Identification for Electrical Systems-12-24-2025.pdf PDF
230513-RIB-Common Motor Requirements for HVAC Equipment-12-24-2025.pdf PDF
220553-RIB-Identification for Plumbing Piping and Equipment-12-24-2025.pdf PDF
233100-RIB-HVAC Ducts and Casings-12-24-2025.pdf PDF
233423-RIB-HVAC Power Ventilators-12-24-2025.pdf PDF
265100-RIB-Interior Lighting-12-24-2025.pdf PDF
237413-RIB-Packaged Outdoor Central-Station Air-Handling Units-12-24-2025.pdf PDF
TYPE EMX CMB-ISOLITE-Specification.pdf PDF
230523-RIB-General-Duty Valves for HVAC Piping-12-24-2025.pdf PDF
25388-CBI 100% CD w Add1.pdf PDF
232113-RIB-Hydronic Piping-12-24-2025.pdf PDF
TYPE S1 iO-CoviO-Spec-Sheet.pdf PDF
262726-RIB-Wiring Devices-12-24-2025.pdf PDF
260923-RIB-Lighting Control Devices-12-24-2025.pdf PDF
TYPE P1 Corelite-Iridium-i3-Suspended-specification-sheet.pdf PDF
238126.13-RIB-Small-Capacity Split-System Air Conditioners-12-24-2025.pdf PDF
220529-RIB-Hangers and Supports for Plumbing Piping and Equipment-12-24-2025.pdf PDF
231123-RIB-Facility Natural-Gas Piping-12-24-2025.pdf PDF
232114-RIB-Hydronic Specialties-12-24-2025.pdf PDF
230913-RIB-Instrumentation and Control Devices for HVAC-12-24-2025.pdf PDF
260505-RIB-Selective Demolition for Electrical-12-24-2025.pdf PDF
CBI GJ Project Manual_VSS_R2.pdf PDF
230800-RIB-Commissioning of HVAC-12-24-2025.pdf PDF
TYPE D3 PrentaLux-CYL6-6-Sustainable-LED-Cylinder-Luminaire-Spec-Sheet.pdf PDF
Show all 40

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

25-388 CBI HVAC and Lighting Upgrade 232123 - 1 Hydronic Pumps

SECTION 232123

HYDRONIC PUMPS

PART 1 GENERAL

1.01 SECTION INCLUDES

A. System-lubricated circulators.

B. Circulators.

C. In-line pumps.

D. End-suction pumps.

E. Dual-drive pump systems.

1.02 RELATED REQUIREMENTS

A. Section 033000 - Cast-in-Place Concrete.

B. Section 230513 - Common Motor Requirements for HVAC Equipment.

C. Section 230716 - HVAC Equipment Insulation.

D. Section 230719 - HVAC Piping Insulation.

E. Section 232113 - Hydronic Piping.

F. Section 232114 - Hydronic Specialties.

1.03 REFERENCE STANDARDS

A. NEMA MG 00001 - Motors and Generators; 2024.

B. NEMA OS 1 - Sheet-Steel Outlet Boxes, Device Boxes, Covers, and Box Supports; 2013

(Reaffirmed 2020).

C. NFPA 70 - National Electrical Code; Most Recent Edition Adopted by Authority Having

Jurisdiction, Including All Applicable Amendments and Supplements.

D. UL 778 - Standard for Motor-Operated Water Pumps; Current Edition, Including All Revisions.

1.04 SUBMITTALS

A. See Section 013000 - Administrative Requirements for submittal procedures.

B. Product Data: Provide certified pump curves showing performance characteristics with pump and system operating point plotted. Include NPSH curve when applicable. Include electrical characteristics and connection requirements.

C. Millwright's Certificate: Certify that base mounted pumps have been aligned.

D. Manufacturer's Installation Instructions: Indicate hanging and support requirements and recommendations.

E. Operation and Maintenance Data: Include installation instructions, assembly views, lubrication instructions, and replacement parts list.

1.05 QUALITY ASSURANCE

A. Manufacturer Qualifications: Company specializing in manufacture, assembly, and field performance of pumps, with minimum three years of documented experience.

PART 2 PRODUCTS

2.01 MANUFACTURERS

A. Armstrong Fluid Technology, Inc: www.armstrongfluidtechnology.com/#sle.

B. Bell & Gossett, a Xylem Inc. brand: www.bellgossett.com/#sle.

C. Taco Comfort Solutions: www.tacocomfort.com D. Substitutions: See Section 016000 - Product Requirements.

2.02 GENERAL

Upgrade 232123 - 2 Hydronic Pumps

A. Provide pumps that operate at specified system fluid temperatures without vapor binding and cavitation, are non-overloading in parallel or individual operation, and operate within 25 percent of midpoint of published maximum efficiency curve.

B. Minimum Quality Standard: UL 778.

C. Base Mounted Pumps: Aligned by qualified millwright.

D. Electrical Requirements:

1. Listed and classified by UL or testing agency acceptable to authority having jurisdiction as suitable for the purpose specified and indicated.

2. Variable Frequency Drives (VFDs): Provide in accordance with Section 230934, except for integral-VFDs.

3. Enclosures: Provide unspecified product(s) required to fit motor:

2.03 SYSTEM-LUBRICATED CIRCULATORS

A. Horizontal shaft, single stage, direct connected with multiple speed wet rotor motor for in-line mounting, for 140 psi maximum working pressure, 230 degrees F maximum water temperature.

B. Casing: Cast iron with flanged pump connections.

C. Impeller, Shaft, Rotor: Stainless Steel.

D. Bearings: Metal Impregnated carbon (graphite) and ceramic.

E. Motor: Impedance protected, multiple speed, with external speed selector.

2.04 CIRCULATORS

A. Horizontal shaft, single-stage pump with direct connected, resilient-mount, oil lubricated motor for discharge pressures of up to 125 psi.

B. Casing: Cast iron, with flanged pump connections.

C. Impeller: Non-ferrous keyed to shaft.

D. Bearings: Oil-lubricated bronze sleeve.

E. Shaft: Alloy steel with bronze sleeve, integral thrust collar.

F. Seal: Mechanical seal, 225 degrees F maximum continuous duty temperature.

G. Drive: Flexible coupling.

H. Electrical:

1. Wiring Terminations: Provide terminal lugs to match branch circuit conductor quantities, sizes, and materials indicated. Enclose terminal lugs in terminal box sized to NFPA 70.

2.05 IN-LINE PUMPS

A. Closed-Coupled, Single-Stage Pump: Vertical pump with radially- or horizontally-split casing;

rated for discharge pressures up to 175 psi.

B. Casing: Cast iron with seal flush connection, threaded suction, and discharge ports with gauge port and drain plug.

C. Impeller: Bronze, fully enclosed, keyed directly to motor shaft or extension.

D. Shaft: Stainless steel with stainless steel impeller cap screw or nut and bronze sleeve.

E. Seal: Mechanical seal, 225 degrees F maximum continuous duty temperature.

F. Electrical:

1. Wiring Terminations: Provide terminal lugs to match branch circuit conductor quantities, sizes, and materials indicated. Enclose terminal lugs in terminal box sized to NFPA 70.

2.06 END-SUCTION PUMPS

A. Split-Coupled Pump: Base-mounted, single-stage pump with horizontal shaft and radially- or horizontally-split casing rated for discharge pressures up to 175 psi.

Upgrade 232123 - 3 Hydronic Pumps

B. Casing: Cast iron or ductile iron with renewable bronze casing wearing rings, seal flush connection, drain plug, flanged suction, and discharge flanged connections with gauge ports.

C. Impeller: Stainless steel, balanced, fully enclosed, keyed to shaft.

D. Bearings: Oil lubricated roller or ball bearings.

E. Shaft: Alloy steel with copper, bronze, or stainless steel shaft sleeve.

F. Seal: Mechanical, 225 degrees F maximum continuous duty temperature.

G. Seal: Packing gland with minimum four rings graphite impregnated packing and bronze lantern rings, 250 degrees F maximum continuous duty temperature.

H. Drive: Flexible coupling with coupling guard.

I. Baseplate: Cast iron or fabricated steel with integral drain rim.

J. Electrical:

1. Wiring Terminations: Provide terminal lugs to match branch circuit conductor quantities, sizes, and materials indicated. Enclose terminal lugs in terminal box sized to NFPA 70.

2.07 DUAL-DRIVE PUMP SYSTEMS

A. Horizontal split case, base-mounted pump with two motors, operating at 1,750 rpm and 1,150 rpm, assembled on integral base with control cabinet.

B. Control Cabinet: NEMA OS 1, UL approved enclosure with individual circuit breakers, magnetic starters with overload protection, running lights, separate 115V fused control circuit, hands-off-automatic switches, motor failure alarm with manual reset, pre-wired.

C. Electrical Characteristics:

1. Motor:

a. Comply with NEMA MG 00001.

2. Wiring Terminations: Provide terminal lugs to match branch circuit conductor quantities, sizes, and materials indicated. Enclose terminal lugs in terminal box sized to NFPA 70.

PART 3 EXECUTION

3.01 PREPARATION

A. Verify that electric power is available and of the correct characteristics.

3.02 INSTALLATION

A. Install in accordance with manufacturer's instructions.

B. Provide access space around pumps for service. Provide no less than minimum space recommended by manufacturer.

C. Decrease from line size with long radius reducing elbows or reducers. Support piping adjacent to pump such that no weight is carried on pump casings. For close-coupled or base-mounted pumps, provide supports under elbows on pump suction and discharge line sizes 4 inches and over.

D. Provide line sized shut-off valve and strainer on pump suction, and line sized soft seat check valve and balancing valve on pump discharge.

E. Provide air cock and drain connection on horizontal pump casings.

F. Provide drains for bases and seals, piped to and discharging into floor drains.

G. Check, align, and certify alignment of base-mounted pumps prior to start-up.

H. Install close-coupled and base-mounted pumps on concrete housekeeping base, with anchor bolts, set and level, and grout in place. See Section 033000.

I. Lubricate pumps before start-up.

J. Provide side-stream filtration system for closed loop systems. Install across pump with flow from pump discharge to pump suction from pump tappings.

Upgrade 232123 - 4 Hydronic Pumps

K. Controls Human-Machine Interface (HMI): HVAC operator terminal; see Section 253500.

END OF SECTION

232123 - Hydronic Pumps