This is a set of architectural and engineering drawings for the West Virginia Army National Guard Building 244 Renovation project located at Camp Dawson in Kingwood, West Virginia. The project involves comprehensive renovation of an existing dining facility with kitchen, storage, mechanical, electrical, and plumbing systems. The scope of work includes demolition of existing systems, installation of new roofing with standing seam metal material, replacement of exterior siding with fiber cement material, renovation of bathroom facilities to meet ADA accessibility guidelines, installation of new HVAC systems, plumbing upgrades including domestic water, sanitary, and vented piping systems, and electrical system updates. The building is classified as Type V-B construction with an Assembly occupancy designation. Key interior spaces include a 2,817 square foot dining area, 708 square foot kitchen, walk-in freezer and cooler units, two ADA-compliant unisex toilets, janitor closet, mechanical room, electrical room, and storage areas. The project includes two alternates: Alternate #1 involving kitchen hood replacement and Alternate #2 involving expansion of the freezer and cooler units with removal of existing equipment and a stair structure. The drawings are issued for bidding as of August 11, 2026, prepared by Montum Architecture LLC with offices in Pennsylvania and West Virginia.

The drawings specify detailed construction requirements conforming to the 2021 International Building Code, 2018 International Energy Conservation Code, 2015 ADA Accessibility Guidelines, and 2021 NFPA 101 Life Safety Code. Plumbing systems require Type L copper piping with soldered or mechanically pressed fittings, or cross-linked PEX piping for domestic water lines, with P40 PVC or cast iron no-hub piping for waste systems. Mechanical systems must comply with SMACNA standards for low-pressure ductwork with external insulation and include fire dampers at rated wall penetrations. The project requires coordination among all trades for MEP work, with specific attention to avoiding conflicts with drainage lines and structural integrity. A thermostatic mixing valve and domestic water recirculation system are specified, along with commercial-grade plumbing fixtures and a natural gas-fired water heater. All work must meet current International Plumbing Code, International Mechanical Code, and applicable state and local codes with final coordination responsibility assigned to the general contractor and all subcontractors prior to bidding.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

PA OFFICE:

PO BOX 42

GARARDS FORT, PA 15334

PH: (724) 966-5655

WV OFFICE:

54 WEST RUN RD

MORGANTOWN, WV 26508

PH: (304) 291-2234

PROJECT NUMBER:

ISSUE DATE:

CHECKED BY:

SHEET NUMBER:

S H

E E

T T

IT

L E

A

L L R

IG

H

T S

R E

S E

R V

E D

M O

N T

U M

A R

C H

IT

E

C T

U R

E L L C

SEAL:

CONSULTANTS:

G000

C O

V E

R S

H E

E T

M25019

B U

IL

D

IN

G

R

E N

O V

A T

IO

N

W E

S T

V

IR

G

IN

IA

A

R M

Y N

A T

IO

N

A L G

U A

R D

08/11/2026

TFP

IS

S

U E

D F

O R

B

ID

D

IN

G

C A

M P

D A

W S

O N

K

IN

G W

O O

D

W V

SHEET INDEX

Sheet Number Sheet Name

G000 COVER SHEET

G001 PROJECT GENERAL NOTES,

ABBREVATIONS, & SYMBOLS

G101 FIRST FLOOR LIFE SAFETY PLAN

A001 EXISTING & DEMOLITION PLANS

A101 FIRST FLOOR PLAN

A111 REFLECTED CEILING & ROOF PLAN

A201 BUILDING ELEVATIONS

A301 BUILDING SECTIONS

A302 WALL SECTIONS & DEATILS

A401 ENLARGED PLANS & ELEVATIONS

A601 PARTITION SCHEDULES & DETAILS

A701 FINISH PLANS

P000 PLUMBING ABBREVIATIONS

P001 DOMESTIC PLUMBING DEMO PLAN

P002 SANITARY PLUMBING DEMO PLAN

P101 DOMESTIC PLUMBING PLAN

P102 SANITARY PLUMBING PLAN

P201 PLUMBING SECTIONS

P401 ENLARGED PLUMBING PLANS

P501 PLUMBING DETAILS & SCHEDULES

M000 MECHANICAL ABBREVIATIONS

M001 MECHANICAL DEMO PLAN

M001A MECHANICAL DEMO PLAN - ALTERNATE

M002 MECHANICAL DEMO PLAN

M003 MECHANICAL PIPING DEMO PLAN

M101 MECHANICAL PLAN

M101A MECHANICAL PLAN - ALTERNATE

M102 MECHANICAL PLAN

M103 MECHANICAL PIPING PLAN

M501 MECHANICAL DETAILS

M601 MECHANICAL SCHEDULES

M901 MECHANICAL PERSPECTIVES

E000 ELECTRICAL ABBREVIATIONS

E001 ELECTRICAL DEMO PLAN

E002 ELECTRICAL DEMO PLAN

E003 LIGHTING DEMO PLAN

E004 FIRE ALARM / SECURITY DEMO PLAN

E101 ELECTRICAL PLAN

E101A ELECTRICAL PLAN - ALTERNATE

E102 ELECTRICAL PLAN

E102A ELECTRICAL PLAN - ALTERNATE

E103 LIGHTING PLAN

E104 FIRE ALARM / SECURITY PLAN

E601 ELECTRICAL SCHEDULES

PA OFFICE:

PO BOX 42

GARARDS FORT, PA 15334

PH: (724) 966-5655

WV OFFICE:

54 WEST RUN ROAD

MORGANTOWN, WV 26508

PH: (304) 291-2234

info@arwcg.com | 304.435.8828 | arwcg.com

WEST VIRGINIA ARMY NATIONAL GUARD

CAMP DAWSON BUILDING 244 RENOVATION

1001 ARMY RD

KINGWOOD, WV 26537

N o

D e s c ri p ti o n

D a te

08/11/2026 4:31:07 PM

CONCRETE

CLAY UNIT MASONRY

CONCRETE UNIT MASONRY

WOOD FRAMING

PLYWOOD

FINISHED WOOD

BATT INSULATION

RIGID INSULATION

GYPSUM BOARD

SOIL

CRUSHED STONE

MATERIAL HATCH DESCRIPTION

CENTER LINE

HIDDEN LINE

VIEW TITLE

ELEVATION MARKER

SECTION MARKER

DETAIL CALLOUT

ROOM TAG

GRID LINE MARKER

ELEVATION DATUM

SPOT ELEVATION MARK

WALL TAG

DOOR TAG

WINDOW TAG

CALL-OUT SYMBOL DESCRIPTION

View Name 1/8" = 1'-0"

A101

ROOM

NAME

A101

4 2

A101

A101

SIM

PROJECT NUMBER:

ISSUE DATE:

CHECKED BY:

SHEET NUMBER:

S H

E E

T T

IT

L E

A

L L R

IG

H

T S

R E

S E

R V

E D

M O

N T

U M

A R

C H

IT

E

C T

U R

E L L C

SEAL:

CONSULTANTS:

G001

P R

O J E

C T

G E

N E

R A

L N

O T

E S

A

B B

R E

V A

T

IO

N S

S Y

M B

O L

S

M25019

B U

IL

D

IN

G

R

E N

O V

A T

IO

N

W E

S T

V

IR

G

IN

IA

A

R M

Y N

A T

IO

N

A L G

U A

R D

08/11/2026

TFP

IS

S

U E

D F

O R

B

ID

D

IN

G

C A

M P

D A

W S

O N

K

IN

G W

O O

D

W V

DEFINITIONS

PROVIDE: FURNISH AND INSTALL, COMPLETE AND READY FOR THE INTENDED USE.

FURNISH: SUPPLY AND DELIVER TO PROJECT SITE, READY FOR UNLOADING, UNPACKING, ASSEMBLY, INSTALLATION, AND SIMILAR OPERATIONS.

INSTALL: UNLOAD, TEMPORARILY STORE, UNPACK, ASSEMBLE, ERECT, PLACE, ANCHOR, APPLY, WORK TO DIMENSION, FINISH, CURE, PROTECT, CLEAN, AND SIMILAR

OPERATIONS AT PROJECT SITE.

EXISTING TO REMAIN (OR EXISTING) (OR EX.): LEAVE EXISTING ITEMS THAT ARE NOT TO BE REMOVED AND THAT ARE NOT OTHERWISE INDICATED TO BE SALVAGED OR

REINSTALLED.

REMOVE (OR DEMOLISH) (OR DEMO): DETACH ITEMS FROM EXISTING CONSTRUCTION AND DISPOSE OF THEM OFF-SITE UNLESS INDICATED TO BE SALVAGED OR

REINSTALLED.

REMOVE AND SALVAGE: DETACH ITEMS FROM EXISTING CONSTRUCTION, IN A MANNER TO PREVENT DAMAGE, AND DELIVER TO OWNER READY FOR REUSE.

REMOVE AND REINSTALL (OR REMOVE AND REUSE): DETACH ITEMS FROM EXISTING CONSTRUCTION, IN A MANNER TO PREVENT DAMAGE, PREPARE FOR REUSE, AND

REINSTALL WHERE INDICATED.

DISMANTLE: TO REMOVE BY DISASSEMBLING OR DETACHING AN ITEM FROM A SURFACE, USING GENTLE METHODS AND EQUIPMENT TO PREVENT DAMAGE TO THE ITEM

AND SURFACES; DISPOSING OF ITEMS UNLESS INDICATED TO BE SALVAGED OR REINSTALLED.

DISPOSE: REMOVAL OFF-SITE OF DEMOLITION AND CONSTRUCTION WASTE AND SUBSEQUENT SALE, RECYCLING, REUSE, OR DEPOSIT IN LANDFILL OR INCINERATOR ACCEPTABLE TO AUTHORITIES HAVING JURISDICTION AND IN ACCORDANCE WITH PROJECT REQUIREMENTS.

# Number & And " Inch ' Foot @ At +/- Approximately

ABV Above ACM Aluminum Composite Material ACM Asbestos Containing Material ACT Acoustic Ceiling Tile AD Area Drain ADA Americans with Disabilities Act ADAAG Americans with Disabilities Act Architectural Guidelines ADD Addendum ADJ Adjustable AFF Above Finished Floor AHJ Authority Having Jurisdiction (Code Official, Fire Marshal, Etc.)

ALT Alternate ALUM Aluminum ANOD Anodized APPROX Approximately

BFF Below Finished Floor BIT Bituminous BL Borrowed Lite, Hollow Metal BSMT Basement BYND Beyond BOT Bottom BUR Built-up Roof

C/C Center to Center CB Chalkboard CF Cubic Foot CFCI Contractor Furnished, Contractor Installed CFOI Contractor Furnished, Owner Installed CIP Cast In Place CIRC Circumference or Circulating CJ Control Joint CL Column Line CLG Ceiling CLR Clear CMU Concrete Masonry Unit COL Column COMPRCompressible CONC Concrete CONT Continuous CPT Carpet CT Ceramic Tile

D Deep DBL Double DEG Degree DEMO Demolish or Demolition DIA Diameter DIM Dimension DIMS Dimensions DN Down DS Down Spout DWG Drawing

EA Each EJ Expansion Joint EL Elevation ELEC Electrical ELEV Elevator or Elevation EOS Edge of Slab EPDM Ethylene Propylene Diene Monomer Membrane EQ Equal EX Existing EXIST Existing EXP JT Expansion Joint EXT Exterior EXT GDExterior Grade

FD Floor Drain or Fire Department FE Fire Extinguisher FEC Fire Extinguisher Cabinet FIXT Fixture FLR Floor FO Face Of FR Fire Retardant Treated FRP Fiberglass Reinforced Plastic FT Foot

GA Gauge GALV Galvanized GC General Contractor GFCI Ground Fault Circuit Interrupter GL Glass GWB Gypsum Wall Board

HC Hollow Core HM Hollow Metal HORIZ Horizontal HP High Point HR Hour HVAC Heating, Ventilating, And Air Conditioning

ID Inside Diameter IRGWB Impact Resistant Gypsum Wall Board ILO In Lieu Of INSUL Insulated or Insulation INT Interior JB Junction Box

L Long LAV Lavatory LBS Pounds

MAX Maximum MB Markerboard MO Masonry Opening MECH Mechanical MEMBR Membrane MEZZ Mezzanine MIN Minimum MISC Miscellaneous MRGWB Moisture-Resistant Gypsum Wall Board MTL Metal

NA Not Applicable NIC Not In Contract (See OFOI) NO Number NOM Nominal NTS Not to Scale

OC On Center OD Outside Diameter OFCI Owner Furnished, Contractor Installed OFOI Owner Furnished, Owner Installed OH Overhand OPP Opposite or Opposite Hand OZ Ounce

PCC Pre-Cast Concrete PLAM Plastic Laminate PLUMB Plumbing PLYD Plywood PT Pressure Treated PNT Paint or Painted PVC Polyvinyl Chloride

RBR Rubber RCP Reflected Ceiling Plan RB Rubber (Vinyl) Wall Base RD Roof Drain REBAR Reinforcing Bar REINF Reinforce REQD Required REV Revision RO Rough Opening RM Room

SB Splash Block SD Supplemental Document (Drawing Revision) SFM State Fire Marshal SQFT Square Foot SF Aluminum Storefront Framing SIM Similar SPEC Specified OR Specification SPK Speaker SSTL Stainless Steel STC Sound Transmission Coefficient STL Steel STRUC Structure or Structural

T Tall T&B Top and Bottom T&G Tongue and Groove TB Tackboard TELE Telephone TLT Toilet TME To Match Existing TO Top Of TOC Top Of Concrete TOS Top Of Steel TOW Top Of Wall T/D Telephone/Data TYP Typical

UL Underwriters Laboratory UNO Unless Noted Otherwise U/S Underside

VERT Vertical VIF Verify In Field VP Vision Panel

W Wide W/ With W/o Without WD Wood WP Weatherproof or Waterproof

GENERAL DRAWING SET NOTES

1. WRITTEN SPECIFICATIONS FOR THE PROJECT ARE PROVIDED IN THE PROJECT MANUAL AND REQUIREMENTS ARE COMPLEMENTARY.

2. CONTRACTOR SHALL BE RESPONSIBLE FOR ALL CONSTRUCTION METHODS, PROCEDURES AND SEQUENCES TO MAINTAIN AND PROTECT THE STRUCTURAL INTEGRITY OF ALL NEW AND EXISTING CONSTRUCTION AT ALL STAGES.

3. THE CONTRACTOR SHALL ABIDE BY ALL SAFETY RULES AND REGULATIONS IMPOSED BY OSHA AND THE OWNER AT ALL TIMES. IF THERE IS A CONFLICT BETWEEN THE TWO, THE STRICTER REGULATION SHALL APPLY.

4. SPECIFIC REQUIREMENTS SHALL SUPERSEDE GENERAL/GENERIC REQUIREMENTS.

5. DIMENSIONS SHALL SUPERSEDE DRAWINGS. DO NOT SCALE DRAWINGS. WHERE A MISSING OR CONFLICTING DIMENSION OCCURS, THE ARCHITECT SHALL BE CONTACTED IMMEDIATELY TO OBTAIN THE NECESSARY CLARIFICATION.

6. THE CONTRACTOR SHALL NOTIFY THE ARCHITECT OF ANY AND ALL DISCREPANCIES BETWEEN THE DRAWINGS AND ACTUAL FIELD CONDITIONS IMMEDIATELY UPON DISCOVERY.

7. COMMENCEMENT OF THE WORK SHALL SIGNIFY THE CONTRACTOR IS FAMILIAR WITH AND AGREES TO THE SCOPE OF WORK AS OUTLINED IN THE CONTRACT DOCUMENTS.

8. THE CONTRACTOR SHALL BE RESPONSIBLE FOR PROPER DISPOSAL OF ALL MATERIALS RESULTING FROM THE WORK OF THIS PROJECT.

WORK REQUIRING GRAVITY DRAINAGE WILL HAVE REASONABLE PRIORITY OF PLACEMENT. TRADES WILL COORDINATE PLACEMENT OF THEIR WORK TO AVOID CONFLICT WITH DRAINAGE LINES.

ABBREVATIONS AND SYMBOLS

N o

D e s c ri p ti o n

D a te

08/11/2026 4:31:14 PM

DN

ELEC

e108

WALK-IN

FRIDGE/FREEZER

STORAGE

e105

MECH

e104

STORAGE

e106

708 SF

KITCHEN

76 SF

TRAY DROP

2817 SF

DINING

ADA

UNISEX

TOILET

ADA

UNISEX

TOILET

111 STORAGE

e107

JANITOR

DATA

410 SF

SERVERY

VEST

101A

PROJECT NUMBER:

ISSUE DATE:

CHECKED BY:

SHEET NUMBER:

S H

E E

T T

IT

L E

A

L L R

IG

H

T S

R E

S E

R V

E D

M O

N T

U M

A R

C H

IT

E

C T

U R

E L L C

SEAL:

CONSULTANTS:

G101

F

IR

S T

F L O

O R

L

IF

E S

A F

E T

Y P

L A

N

M25019

B U

IL

D

IN

G

R

E N

O V

A T

IO

N

W E

S T

V

IR

G

IN

IA

A

R M

Y N

A T

IO

N

A L G

U A

R D

08/11/2026

TFP

IS

S

U E

D F

O R

B

ID

D

IN

G

C A

M P

D A

W S

O N

K

IN

G W

O O

D

W V

LIFE SAFETY AND BUILDING CODE ANALYSIS

AUTHORITY HAVING JURISDICTION

LOCAL REGULATIONS:

WEST VIRGINIA ARMY NATIONAL GUARD

CERTIFICATE OF OCCUPANCY:

WEST VIRGINIA STATE FIRE MARSHAL

1207 QUARRIER ST

SECOND FLOOR

CHARLESTON, WV 25301

JENNIFER PRICE, FIRE SAFETY PLANS EXAMINER SUPERVISOR

APPLICABLE CODES

WORK SHALL CONFORM TO ALL APPLICABLE BUILDING CODES, INCLUDING BUT NOT LIMITED TO:

INTERNATIONAL BUILDING CODE - 2021

INTERNATIONAL ENERGY CONSERVATION CODE - 2018

AMERICANS WITH DISABILITIES ACT ACCESSIBILITY GUIDELINES - 2015

NATIONAL FIRE PROTECTION ASSOCIATION 101 LIFE SAFETY CODE - 2021

NATIONAL ELECTRICAL CODE - 2020

CONSTRUCTION TYPE

INTERNATIONAL BUILDING CODE: TYPE V-B

NFPA 220 STANDARD ON TYPES OF BUILDING CONSTRUCTION AND NFPA 101 LIFE SAFETY CODE: TYPE V-000

FIRE RESISTANCE RATINGS:

ELEMENT REQUIRED PROVIDED

STRUCTURAL FRAME 0 0

EXTERIOR BEARING WALLS 0 0

INTERIOR BEARING WALLS 0 0

EXTERIOR NON-BEARING WALLS 0 0

INTERIOR NON-BEARING WALLS 0 0

FLOOR CONSTRUCTION 0 0

ROOF CONSTRUCTION 0 0

FIRE WALLS 0 0

OCCUPANCY CLASSIFICATION AND ALLOWABLE BUILDING AREAS

THE EXISTING BUILDING IS NFPA 101 OCCUPANCY TYPE ASSEMBLY.

THE EXISTING BUILDING IS NOT SPRINKLERED.

FIRE PROTECTION/ LIFE SAFETY SYSTEMS

SPRINKLER SYSTEM: NOT REQUIRED, NOT PROVIDED.

SMOKE DETECTION: REQUIRED BY IBC AND NFPA 101, PROVIDED.

EMERGENCY LIGHTING: REQUIRED BY IBC AND NFPA 101, PROVIDED.

PANIC HARDWARE: REQUIRED BY IBC AND NFPA 101 FOR OCCUPANT LOADS EXCEEDING 50, PROVIDED.

EXIT SIGNS: REQUIRED BY IBC AND NFPA 101, PROVIDED.

FIRE EXTINGUISHERS: REQUIRED BY NFPA 101, PROVIDED.

FINISH: CLASS A, B OR C FINISHES PERMITTED

N o

D e s c ri p ti o n

D a te

1/8" = 1'-0"

Level 1 LSP

08/11/2026 4:31:15 PM

DN

DN

WALK-IN

FRIDGE/FREEZER

4 4 4 4 4 1

14 17

DINING

MECH

STORAGE

ELEC

TOILET

TOILET

KITCHEN

JAN /

TRAY

DROP

EXISTING WALK-IN

FRIDGE/FREEZER

4" / 1'-0"

4" / 1'-0"

REMOVE CANOPY

PREP FOR NEW FASCIA AND GUTTER

REMOVE SHINGLE ROOF

AND UNDERLAYMENT

49 SF

ELEC

WALK-IN

FRIDGE/FREEZER

55 SF

STORAGE

48 SF

MECH

16 SF

TOILET

17 SF

TOILET

708 SF

KITCHEN

76 SF

JAN / TRAY DROP

3584 SF

DINING

PROJECT NUMBER:

ISSUE DATE:

CHECKED BY:

SHEET NUMBER:

S H

E E

T T

IT

L E

A

L L R

IG

H

T S

R E

S E

R V

E D

M O

N T

U M

A R

C H

IT

E

C T

U R

E L L C

SEAL:

CONSULTANTS:

A001

E X

IS

T

IN

G

D

E M

O L

IT

IO

N P

L A

N S

M25019

B U

IL

D

IN

G

R

E N

O V

A T

IO

N

W E

S T

V

IR

G

IN

IA

A

R M

Y N

A T

IO

N

A L G

U A

R D

08/11/2026

TFP

IS

S

U E

D F

O R

B

ID

D

IN

G

C A

M P

D A

W S

O N

K

IN

G W

O O

D

W V

DEMOLITION PLAN NOTES

KEYNOTES

1. REMOVE DOOR AND PREP FOR NEW DOOR.

2. PREP OPENING FOR NEW SIZE.

3. REMOVE DOOR PANEL.

4. REMOVE WINDOW AND PREP FOR NEW WINDOW OF THE SAME SIZE.

5. REMOVE WINDOW AND PREP FOR IN-FILL WALL.

6. REMOVE WINDOW AND PREP FOR NEW DOOR.

7. REMOVE WALLS AND SIDEWALK.

8. REMOVE PLUMBING FIXTURE AND CAP UTILITIES.

9. CUT FLOOR SLAB AS REQUIRED FOR MEP WORK AND PATCH BACK.

10. REMOVE CEILING.

11. PREP EXTERIOR FOR NEW PAINT.

12. REMOVE SIDEWALK AND PREP FOR NEW WORK.

13. PREP AREA FOR NEW CANOPY.

14. PREP FLOOR FOR NEW TILE.

15. REMOVE DOOR AND PREP FOR NEW DOOR OF THE SAME SIZE.

16. UNDER ALTERNATE #2, REMOVE EXISTING WALK-IN FREEZER/COOLER, AND STAIR, AND PREP FOR EXPANDED FREEZER AND COOLER.

17. REMOVE GYP CEILING WHERE NECESSARY FOR NEW WORK, PATCH ALL HOLES.

18. UNDER ALTERNATE #2, DOOR TO BE MOVE TO NEW EXTERIOR WALL AND MASONRY HEADER TO BE INSTALLED AT EXISTING OPENING.

19. UNDER ALTERNATE #1, REPLACE KITCHEN HOODS. SEE MEP FOR DETAILS.

20. KITCHEN HOOD TO BE REMOVED. SEE MEP FOR DETAILS.

GENERAL NOTES:

1. SEE MEP PLANS FOR ADDITIONAL DEMOLITION REQUIREMENTS.

2. COORDINATE DEMOLITION WORK WITH CONTINUED OPERATIONS OF THE OWNER.

3. PROTECT OCCUPIED AREAS AND ROOMS UNAFFECTED BY THE CONSTRUCTION FROM DUST, FUMES, ETC.

N o

D e s c ri p ti o n

D a te

1/8" = 1'-0"

Level 1 Demo

1/8" = 1'-0"

Roof Demo Plan

1/8" = 1'-0"

Level 1 Existing

DN DN

A2013

A201

A201

49 SF

ELEC

e108

EXISTING WALK-IN

FRIDGE/FREEZER

55 SF

STORAGE

e105

48 SF

MECH

e104

STORAGE

e106

708 SF

KITCHEN

e103

76 SF

TRAY DROP

e102

2817 SF

DINING

ADA

UNISEX

TOILET

ADA

UNISEX

TOILET

STORAGE

e107

93 SF

VEST

101A

JANITOR

63 SF

DATA

101A

101B

410 SF

SERVERY

101B

CANOPY ROOF EDGE

F

E

A401

C6aC a

C6a

C a

C a

C a

C a

C a

C6a

C6a

C a

6' - 0"

/2

15' - 3 1/4"

A201 4

A

A

A

A A A

101D 103

101C

AAA A A

11' - 8"

:4

:4

:1

:1

WALK-OFF GRATE

WALK-OFF GRATE

A601

A601

A601

A302

WHITE

BOARD

WHITE

BOARD

3' - 4"

12' - 2 3/4"

A301

A301

A301

A302

Sim

A302

A302

A BDOOR TYPE

1 1FRAME TYPE

2" 2"

FLUSH

C

2"

FLUSH

GL1

GL1 = 1" INSULATED LOW-E BLAST RESISTANT SAFETY GLAZING

GL2 = 1" INSULATED LOW-E BLAST RESISTANT ANNEALED GLAZING

1. PROVIDE A THROUGH-PENETRATION FIRESTOP SYSTEM AT EVERY

PENETRATION OF FIRE RESISTANT RATED CONSTRUCTION AS

INDICATED ON G100 SERIES DRAWINGS. COORDINATE WITH MEP

AND OTHER SYSTEM DRAWINGS.

2. DIMENSIONS SHALL SUPERSEDE DRAWINGS. DO NOT SCALE

DRAWINGS. WHERE A MISSING OR CONFLICTING DIMENSION

OCCURS, THE ARCHITECT SHALL BE CONTACTED IMMEDIATELY TO

OBTAIN THE NECESSARY CLARIFICATION.

3. ALL DIMENSIONS OF MASONRY WALLS ASSUME ACTUAL DIMENSIONS

OF MASONRY UNITS. ALL DIMENSIONS TO GYPSUM BOARD AND STUD

PARTITIONS ARE TO THE FACE OF THE GYPSUM BOARD.

4. REFER TO G001 FOR ABBREVIATIONS AND SYMBOLS.

5. REFER TO A601 FOR PARTITION TYPES.

6. PROVIDE CONTROL JOINTS IN PARTITIONS AS INDICATED ON A601.

7. REFER TO A100 SERIES FOR OVERALL DIMENSIONS.

8. REFER TO A700 SERIES DRAWINGS FOR FINISH INFORMATION

INCLUDING SPECIALTY DRYWALL AND BLOCKING INFORMATION.

9. PROVIDE (24) 4'X4' ACOUSTICAL PANELS MOUNTED TO THE WALLS

AND CEILING OF THE DINING AREA AT LOCATIONS DIRECTED BY THE

ARCHITECT AND OWNER.

A201

WALK-IN FRIDGE

WALK-IN FREEZER

D7

4' - 8"

4' - 0"

A302

A302

Sim

VERIFY IN FIELD

A302

24' - 8"

4" X 8" PRECAST CONCRETE LINTEL

(1 PER 4" OF WALL THICKNESS),

BEARING 8" ON EACH END

MASONRY WALL,

TEMPORARILY SUPPORT

WHILE INSTALLING

LINTEL IN EXISTING

WALLS

DOOR FRAME

PROJECT NUMBER:

ISSUE DATE:

CHECKED BY:

SHEET NUMBER:

S H

E E

T T

IT

L E

A

L L R

IG

H

T S

R E

S E

R V

E D

M O

N T

U M

A R

C H

IT

E

C T

U R

E L L C

SEAL:

CONSULTANTS:

A101

F

IR

S T

F L O

O R

P L A

N

M25019

B U

IL

D

IN

G

R

E N

O V

A T

IO

N

W E

S T

V

IR

G

IN

IA

A

R M

Y N

A T

IO

N

A L G

U A

R D

08/11/2026

TFP

IS

S

U E

D F

O R

B

ID

D

IN

G

C A

M P

D A

W S

O N

K

IN

G W

O O

D

W V

DOOR SCHEDULE

FIRE

RATING WIDTH HEIGHT

PANEL FRAME

NOTES #TYPE MATL TYPE MATL

101A 6' - 2" 7' - 10" CC HM 2 HM 101A

101B 6' - 2" 7' - 10" CC HM 2 HM 101B

101C 3' - 0" 7' - 0" B HM 1 HM 101C

101D 3' - 0" 7' - 0" A HM 1 HM 101D

101E 3' - 0" 7' - 0" A HM 1 HM 101E

101F 6' - 0" 7' - 0" AA HM 1 HM 101F

103 3' - 0" 7' - 0" A HM 1 HM 103

104 2' - 6" 7' - 0" A HM 1 HM 104

110 3' - 0" 7' - 0" A HM 1 HM 110

111 3' - 0" 7' - 0" A HM 1 HM 111

112 3' - 0" 7' - 0" A HM 1 HM 112

113 3' - 0" 7' - 0" A HM 1 HM 113

1/8" = 1'-0"

Level 1

N o

D e s c ri p ti o n

D a te

1/8" = 1'-0"

Level 1 Stored Equipment Plan

DOOR TYPESGENERAL FLOOR PLAN NOTES

1/8" = 1'-0"

Level 1 ALTERNATE #2

1 1/2" = 1'-0"

MASONRY DOOR LINTEL DETAIL

SUPPLY DIFFUSER

RETURN GRILLE

EXHAUST GRILLE

SURFACE MOUNTED FLUORESCENT FIXTURE

2X2 RECESSED FLUORESCENT FIXTURE

DUAL HEAD EMERGENCY LIGHT

EXIT SIGN

EXTERIOR WALL PACK

SURFACE MOUNTED ROUND FLUORESCENT FIXTURE

PRE ENGINEERED CANOPY

A.F.F.

GWB on Mtl. Stud

8' - 0" A.F.F.

GWB on Mtl. Stud 8' - 0"

A.F.F.

GWB on Mtl. Stud

8' - 0" A.F.F.

GWB on Mtl. Stud 8' - 0"

A.F.F.

GWB on Mtl. Stud

8' - 0"

PRE ENGINEERED CANOPY

A.F.F.

2' x 2' ACT System

9' - 0"

A.F.F.

EXISTING GWB

10' - 0"

A.F.F.

EXISTING GWB

8' - 0"

A.F.F.

EXISTING GWB

10' - 0"A.F.F.

EXISTING GWB

10' - 0" A.F.F.

EXISTING GWB

10' - 0"

EXISTING GWB

10' - 0" A.F.F.

A.F.F.

EXISTING GWB

10' - 0"

SHEET METAL PIPE ENCLOSURE,

BY JC INNOVATIONS OR SIMILAR

13' - 0"

PRE ENGINEERED CANOPY

STANDING SEAM

METAL ROOF

PRE ENGINEERED CANOPY

9' - 4"

10' - 0"

A111

A111

REPLACE GUTTERS

AND DOWNSPOUTS

FALL

PROTECTION

RAILING

DS

DS

DSDS

DS

DS

DS DS DS

DS

SNOW RAIL

SNOW

RAIL

EXISTING ROOF DECK

NEW UNDERLAYMENT AND

STANDING SEAM METAL ROOF

STANDING SEAM SIDING

PLYWOOD SHEATHING

2X4 FRAMING

SOFFIT

METAL RAKE W/ DRIP EDGE

UNDERLAYMENT AND

STANDING SEAM METAL ROOF

SEE MEP FOR DETAILS.

DUCT

4" / 1

2" SLOPE

DRYWALL CEILING, ROOF JOISTS SHOWN ABOVE

FREEZER CEILING

COOLER CEILING

CANOPY CEILING

PROJECT NUMBER:

ISSUE DATE:

CHECKED BY:

SHEET NUMBER:

S H

E E

T T

IT

L E

A

L L R

IG

H

T S

R E

S E

R V

E D

M O

N T

U M

A R

C H

IT

E

C T

U R

E L L C

SEAL:

CONSULTANTS:

A111

R E

F L E

C T

E D

C E

IL

IN

G

R O

O F

P L A

N

M25019

B U

IL

D

IN

G

R

E N

O V

A T

IO

N

W E

S T

V

IR

G

IN

IA

A

R M

Y N

A T

IO

N

A L G

U A

R D

08/11/2026

TFP

IS

S

U E

D F

O R

B

ID

D

IN

G

C A

M P

D A

W S

O N

K

IN

G W

O O

D

W V

REFLECTED CEILING LEGEND

N o

D e s c ri p ti o n

D a te

1/8" = 1'-0"

Level 1

1/8" = 1'-0"

Roof Plan

1/8" = 1'-0"

Roof Plan ALT #2

1 1/2" = 1'-0"

DUCT DORMER DETAIL

1/8" = 1'-0"

Level 1 ALT #2

A A A

STANDING SEAM METAL ROOF

PAINTED

CEMENTITIOUS

SIDING

PRE ENGINEERED CANOPY

SNOW RAIL

A A A A A

PRE ENGINEERED CANOPY

PRE ENGINEERED

CANOPY

SNOW RAIL

SNOW RAIL

A A A

SNOW RAIL

3' - 4"

GL2

A

SINGLE HUNG

PROJECT NUMBER:

ISSUE DATE:

CHECKED BY:

SHEET NUMBER:

S H

E E

T T

IT

L E

A

L L R

IG

H

T S

R E

S E

R V

E D

M O

N T

U M

A R

C H

IT

E

C T

U R

E L L C

SEAL:

CONSULTANTS:

A201

B U

IL

D

IN

G

E L E

V A

T

IO

N S

M25019

B U

IL

D

IN

G

R

E N

O V

A T

IO

N

W E

S T

V

IR

G

IN

IA

A

R M

Y N

A T

IO

N

A L G

U A

R D

08/11/2026

TFP

IS

S

U E

D F

O R

B

ID

D

IN

G

C A

M P

D A

W S

O N

K

IN

G W

O O

D

W V

N o

D e s c ri p ti o n

D a te

1/8" = 1'-0"

North

1/8" = 1'-0"

South

1/8" = 1'-0"

East

1/8" = 1'-0"

West

WINDOW TYPE

1/8" = 1'-0"

North ALT #2

Level 1

0' - 0"

ROOF BEARING

10' - 0"

Level 1

0' - 0"

ROOF BEARING

10' - 0"

Level 1

0' - 0"

ROOF BEARING

10' - 0"

PA OFFICE:

PO BOX 42

GARARDS FORT, PA 15334

PH: (724) 966-5655

WV OFFICE:

54 WEST RUN RD

MORGANTOWN, WV 26508

PH: (304) 291-2234

PROJECT NUMBER:

ISSUE DATE:

CHECKED BY:

SHEET NUMBER:

S H

E E

T T

IT

L E

A

L L R

IG

H

T S

R E

S E

R V

E D

M O

N T

U M

A R

C H

IT

E

C T

U R

E L L C

SEAL:

CONSULTANTS:

A301

B U

IL

D

IN

G

S E

C T

IO

N

S

M25019

B U

IL

D

IN

G

R

E N

O V

A T

IO

N

W E

S T

V

IR

G

IN

IA

A

R M

Y N

A T

IO

N

A L G

U A

R D

08/11/2026

TFP

IS

S

U E

D F

O R

B

ID

D

IN

G

C A

M P

D A

W S

O N

K

IN

G W

O O

D

W V

N o

D e s c ri p ti o n

D a te

1/8" = 1'-0"

Detail 0

1/8" = 1'-0"

Detail 1

1/8" = 1'-0"

Detail 2

Level 1

0' - 0"

ROOF BEARING

10' - 0"

GRADE

HORIZONTAL FIBER

CEMENT SIDING

2X4 FURRING

1 1/2" SPRAY

FOAM INSULATION

DRIP EDGE

REMOVE EXISTING BATT

INSULATION AND INSTALL 6"

SPRAY FOAM ABOVE CEILING

METAL ROOFING

ATTIC VENTILATION BAFFLE

ROOF BEARING

10' - 0"

1/4" / 1'-0" EPDM ROOFING

ALUMINUM WRAPPED FASCIA

GUTTER

FIBER CEMENT SIDING

PLYWOOD SHEATHING

2X6 PT WALL W/ BATT INFILL

GRADE

WEATHER BARRIER

FILL

2" RIGID INSULATION

Level 1

0' - 0"

V E

R

IF

Y I N

F

IE

L D

V A

R

IE

S

1' - 0"

FILL

6" GRAVEL BASE

4" CONCRETE W/

REINFORCEMENT

Level 1

0' - 0"

WALK-IN COOLER

GRADE

FILL

GRAVEL

4" CONCRETE SLAB

W/ REINFORCEMENT

4,000 PSI SLAB W/ #4

BAR E.W. AT 12" O.C.6

" CRUSHER RUN

GRAVEL BASE

GRADE

COMPACTED EARTH

6"

FACE OF EQUIPMENT

PROJECT NUMBER:

ISSUE DATE:

CHECKED BY:

SHEET NUMBER:

S H

E E

T T

IT

L E

A

L L R

IG

H

T S

R E

S E

R V

E D

M O

N T

U M

A R

C H

IT

E

C T

U R

E L L C

SEAL:

CONSULTANTS:

A302

W A

L L

S E

C T

IO

N

S

D E

A T

IL

S

M25019

B U

IL

D

IN

G

R

E N

O V

A T

IO

N

W E

S T

V

IR

G

IN

IA

A

R M

Y N

A T

IO

N

A L G

U A

R D

08/11/2026

TFP

IS

S

U E

D F

O R

B

ID

D

IN

G

C A

M P

D A

W S

O N

K

IN

G W

O O

D

W V

N o

D e s c ri p ti o n

D a te

1" = 1'-0"

EXTERIOR WALL FURRING SECTION

1" = 1'-0"

ALTERNATE #2 SECTION

1" = 1'-0"

EXTERIOR STAIR SECTION

3/4" = 1'-0"

WALK-IN COOLER PAD EXTENSION

1 1/2" = 1'-0"

EQUIPMENT HOUSEKEEPING PAD

08/11/2026 4:31:16 PM

O

O O

O

C G

C G

G

G

M

DN

12" MAX

42" MIN

54" MIN

T

O

T O

T O

P O

F G

R A

B B

A R

T

O

T O

T O

P O

F S

E A

T

GENERAL NOTES:

1. GRAB BAR DIAMETER: 1-1/4" MIN TO 2" MAX WITH

1-1/2" SPACE BEHIND TO WALL

2. COVER ALL BELOW SINK PIPING WITH JACKETED

INSULATION.

3. COORDINATE PAPER TOWEL, TOILET PAPER, AND

LIQUID SOAP DISPENSER TYPES WITH OWNER.

39" to 41" TO CENTER

M

IN

T

O

56" MIN CLEAR FLOOR AREA

7" TO 9"

TO CENTER OF DISPENSER

24" MIN 18"

TOILET PAPER DISPENSER

MOUNTING RANGE,

"THROAT" OF DISCHARGE TO

BE COMPLETELY WITHIN

THIS AREA

24" 12"

M

IN

G R

A B

B A

R

/2

M

IN

C L E

A R

A N

C E

T O

24" MIN 12" MIN

16" TO 18"

60" MIN CLEAR FLOOR AREA

T

O

T O

T O

P O

F G

R A

B B

A R

FLUSH HANDLE MUST ON

SIDE AWAY FROM WALL

25" MAX

11" MIN 6" MAX

8" MIN

M

IN

M

IN

M A

X

48" MIN CLEAR FLOOR AREA

18" MIN

30" MIN CLEAR FLOOR AREA

M

IN

T O

R E

F L

E C

T

IN

G S

U R

F A

C E 18"X30"

MIRROR

T O

O P

E R

A T

O R

D

IS

C

H A

R G

E

P R

E F

E R

R E

D

M A

X

T O

O P

E R

A T

O R

D

IS

C

H A

R G

E

P R

E F

E R

R E

D

M A

X

PAPER

TOWEL

DISPENSER

LIQUID

SOAP

DISPENSER

DATA

ADA

UNISEX

TOILET

ADA

UNISEX

TOILET

JANITOR

7' - 2" 7' - 2"

/4

A401

A401 6

PTDPTDPTD PTD

5' - 0"

4' - 1 11/16"

LUG

SPD

MR1

PTD

LUG

SPD

GB1

TPD

GB1

TPD

LABEL DESCRIPTION

TOILET ACCESSORIES LEGEND

PTD

GB1

LUG

MR1

SPD

TPD

PAPER TOWEL DISPENSER (BY OWNER)

1 1/2" DIAMETER STAINLESS STEEL HORIZ/VERTICAL GRAB BAR

LAVATORY UNDERGUARD

24" X 40" MIRROR

SOAP DISPENSER (BY OWNER)

TOILET TISSUE DISPENSER (BY OWNER)

RHB SHELF, RAG, HOOK, AND BROOM HOLDER

RHB

PROJECT NUMBER:

ISSUE DATE:

CHECKED BY:

SHEET NUMBER:

S H

E E

T T

IT

L E

A

L L R

IG

H

T S

R E

S E

R V

E D

M O

N T

U M

A R

C H

IT

E

C T

U R

E L L C

SEAL:

CONSULTANTS:

A401

E N

L A

R G

E D

P L A

N S

E

L E

V A

T

IO

N S

M25019

B U

IL

D

IN

G

R

E N

O V

A T

IO

N

W E

S T

V

IR

G

IN

IA

A

R M

Y N

A T

IO

N

A L G

U A

R D

08/11/2026

TFP

IS

S

U E

D F

O R

B

ID

D

IN

G

C A

M P

D A

W S

O N

K

IN

G W

O O

D

W V

N o

D e s c ri p ti o n

D a te

1/2" = 1'-0"

TYPICAL BATHROOM ELEVATIONS

1/4" = 1'-0"

ENLARGED JAN & TOILETS

1/4" = 1'-0"

A 1/4" = 1'-0"

B

1/4" = 1'-0"

C 1/4" = 1'-0"

D

TYPICAL ADA UNISEX TOILET

1/4" = 1'-0"

E

JANITOR

UNBONDED

INTERSECTION

BONDED

INTERSECTION

AT CHANGE OF

WALL THICKNESS

AT RECESSES

AND CHASES

AT ONE SIDE

ABOVE OPENINGS

LESS THAN 6" WIDE

AT BOTH SIDES

ABOVE OPENINGS

OVER 6" WIDE

AT CHANGE OF

WALL

CONSTRUCTION

AT EXPANSION

OR

CONSTRUCTION

JOINTS IN FLOOR,

FND OR WALL

BELOW

AT CHANGES IN

HEIGHT OVER 16"

PROVIDE C.J. BELOW

OPENINGS THAT DO

NOT EXTEND TO FLOOR

NOTE: PROVIDE A CONTROL JOINT AT MAXIMUM SPACING

OF L & AT TYPICAL CONDITIONS INDICATED.

L = LESSOR OF 50' MAX. OR 3 TIMES WALL HEIGHT.

WHERE

STRUCTURE

INTERRUPTS WALL

THICKNESS

L L

/2

PLAN

BASE

CEILING

STRUCTURE

CEILING

# WIDTH

SOUND RATING

FIRE RATING

X NONE

9-5/8"

11-5/8"

3-5/8"

5-5/8"

7-5/8"

#C

CONCRETE MASONARY UNIT

a

NOTE: PROVIDE CAULKING

AROUND ALL WALL

PENETRATIONS

ACOUSTICAL

CAULKING

UNDERSIDE OF FLOOR/

ROOF DECK

MINERAL WOOL BATT

INSULATION

INTERIOR WALL

EXTERIOR WALL

NOTES:

1. SEE ARCH DRAWINGS FOR EXACT LOCATION OF CONTROL JOINTS.

2. HORIZONTAL REINFORCEMENT TO STOP AT EACH SIDE OF CONTROL

JOINT.

3. MAXIMUM SPACING OF CONTROL JOINTS SHALL NOT EXCEED 40'-0".

4. TYPICAL TRUSS TYPE HORIZONTAL REINFORCEMENT NOT SHOWN FOR

CLARITY. (SEE GENERAL NOTES)

5. DO NOT CUT CONTINUOUS BOND BEAMS OR BOND BEAM

REINFORCEMENT AT CONTROL JOINTS.

CONTROL JOINT

CONTROL JOINT

GROUT CELL EACH SIDE OF CONTROL

JOINT AND PLACE (1)-TYPICAL BAR

JOINT STABILIZATION ANCHOR @ 16"

O.C. IN HORIZONTAL MORTAR JOINT

GROUT CELL EACH SIDE OF CONTROL

JOINT AND PLACE (1)-TYPICAL BAR

NOTES:

1. CORNER/INTERSECTION REINFORCEMENT SHALL BE LAPPED WITH

THE TYPICAL TRUSS TYPE HORIZONTAL REINFORCEMENT & EXTEND A

MINIMUM OF 30" IN EACH DIRECTION AT THE INTERSECTION.

2. SEE GENERAL NOTES FOR SPACING OF TYPICAL HORIZONTAL

REINFORCEMENT.

3. TYPICAL TRUSS TYPE HORIZONTAL REINFORCEMENT NOT SHOWN FOR

CLARITY.

4. SEE 5/S501 FOR TYPICAL CORNER BLOCK LAYUP PATTERN(S).

PRE-FAB TRUSS TYPE CORNER

HORIZONTAL REINFORCEMENT

(@ 8" O.C. @ EXTERIOR WALLS)

(@ 16" O.C. @ INTERIOR WALLS)

GROUT CELLS AS SHOWN

AND PLACE (1) TYPICAL BAR

(AT EXTERIOR WALLS ONLY)

PRE-FAB TRUSS TYPE CORNER

HORIZONTAL REINFORCEMENT

(@ 8" O.C. @ EXTERIOR WALLS)

(@ 16" O.C. @ INTERIOR WALLS)

GROUT CELLS AS SHOWN

AND PLACE (1) TYPICAL BAR

(AT EXTERIOR WALLS ONLY)

EXISTING CMU

4" X 4" X 1/4" ANGLE, WITH 6"

BEARING EACH SIDE OF

OPENING,

INSTALL BEFORE REMOVING

BLOCK BELOW

4" X 4" X 1/4" ANGLE, WITH 6"

BEARING EACH SIDE OF

OPENING,

INSTALL BEFORE REMOVING

BLOCK BELOW

DUCT

SEAL ALL AROUND DUCT

WITH SMOKE TIGHT OR

FIRE RATED SYSTEM,

ACCORDING TO PLANS

EXISTING WALL

INTERNAL RAIN DIVERTER

CANOPY FRAME

ALUM. SOFFIT PANEL

GUTTER BEAM

ANCHOR PER MANUFACTURE

FASHING PER MANUFACTURE

PROJECT NUMBER:

ISSUE DATE:

CHECKED BY:

SHEET NUMBER:

S H

E E

T T

IT

L E

A

L L R

IG

H

T S

R E

S E

R V

E D

M O

N T

U M

A R

C H

IT

E

C T

U R

E L L C

SEAL:

CONSULTANTS:

A601

P A

R T

IT

IO

N S

C H

E D

U L

E S

D

E T

A

IL

S

M25019

B U

IL

D

IN

G

R

E N

O V

A T

IO

N

W E

S T

V

IR

G

IN

IA

A

R M

Y N

A T

IO

N

A L G

U A

R D

08/11/2026

TFP

IS

S

U E

D F

O R

B

ID

D

IN

G

C A

M P

D A

W S

O N

K

IN

G W

O O

D

W V

N o

D e s c ri p ti o n

D a te

3/4" = 1'-0"

TYP CMU CONT JOINT

3/4" = 1'-0"

TYP NON-COL CMU WALL

CORNER-INTER

1/4" = 1'-0"

TYP CMU CONT JOINT DIAGRAM (PLAN)

1 1/2" = 1'-0"

CMU WALL PENETRATION DETAIL

1" = 1'-0"

PRE ENGINEERED METAL CANOPY

JANITOR

ADA

UNISEX

TOILET

ADA

UNISEX

TOILET

DATA

VEST

101A TRAY

DROP

e102

DINING

SERVERY

101B

STORAGE

e106

STORAGE

e107

MECH

e104

STORAGE

e105

ELEC

e108

KITCHEN

e103

P-1

P -1

P-1

P -1

EX

P-1

P -1

P-1

P -1

PT-1

PB-1

P-1

P -1

P-1

P -1

EX

P-1

P -1

P-1

P -1

EX

P-1

P -1

P-1

P -1

QT-1

QB-1

P-1

P -1

P-1

P -1

EX

P-1 P

-1

P-1 P

-1

EX

P-1

P -1

P-1

P -1

EX

P-1

P -1

P-1

P -1

EX

P-1

P -1

P-1

P -1

EX

P-1

P -1

P-1

P -1

EX P-1

P -1

P-1

P -1

EX

WALK-OFF GRATE

WALK-OFF GRATE

WALK-IN FRIDGE

WALK-IN FREEZER

P-1

P -1

P-1

P -1

CON

ADDITIVE ALTERNATE #2 ONLY

PROJECT NUMBER:

ISSUE DATE:

CHECKED BY:

SHEET NUMBER:

S H

E E

T T

IT

L E

A

L L R

IG

H

T S

R E

S E

R V

E D

M O

N T

U M

A R

C H

IT

E

C T

U R

E L L C

SEAL:

CONSULTANTS:

A701

F

IN

IS

H

P L A

N S

M25019

B U

IL

D

IN

G

R

E N

O V

A T

IO

N

W E

S T

V

IR

G

IN

IA

A

R M

Y N

A T

IO

N

A L G

U A

R D

08/11/2026

TFP

IS

S

U E

D F

O R

B

ID

D

IN

G

C A

M P

D A

W S

O N

K

IN

G W

O O

D

W V

INTERIOR FINISHS

FINISH TYPE LABEL MATERIAL

BASE

BASE PB-1 PORCELIN TILE BASE

BASE QB-1 QUARY TILE BASE

FLOOR

FLOOR PT-1 PORCELAIN TILE

FLOOR QT-1 QUARY TILE

FLOOR CON CONCRETE

MISCELLANEOUS

MISCELLANEOUS GT-1 GROUT

TRIM

TRIM TH-1 THRESHOLD TRIM

WALL

WALL P-1 PAINT

N o

D e s c ri p ti o n

D a te

1/4" = 1'-0"

Level 1 FINISH PLAN

GENERAL FINISH NOTES:

1. PAINT ALL DOOR FRAMES AND PANELS TO MATCH EXISTING COLOR

2. PAINT ALL CEILINGS P-1

1.

2.

3.

4.

5.

6.

7.

8.

9.

10.

11.

12.

13.

14.

15.

16.

17.

18.

19.

20.

21.

22.

23.

24.

25.

26.

PROVIDE ALL MATERIALS AND EQUIPMENT AND PERFORM ALL

LABOR REQUIRED TO INSTALL COMPLETE AND OPERABLE

PLUMBING SYSTEMS AS INDICATED ON THE DRAWING, AS

SPECIFIED, AND REQUIRED BY CODE.

RUN ALL SOIL WASTE AND VENT PIPING WITH 2% MIN. GRADE

UNLESS OTHERWISE NOTED. HORIZONTAL VENT PIPING SHALL

BE GRADED TO DRIP BACK TO THE SOIL OR WASTE PIPE BY

GRAVITY.

MAINTAIN A MIN. 3'-0" OF GROUND COVER OVER ALL

UNDERGROUND WATER MAINS AND A MIN. 3'-0" OF GROUND

COVER OVER ALL UNDERGROUND SEWERS AND DRAINS.

PROVIDE SHUTOFF VALVES IN ALL DOMESTIC WATER PIPING

SYSTEMS AT ALL SERVICE POINTS AND AT BRANCHES IN WHICH

PIPING SERVES TWO OR MORE FIXTURES.

UNLESS OTHERWISE NOTED, ALL DOMESTIC COLD AND HOT

WATER PIPING SHALL BE A MIN. OF 1/2" SIZE.

UNLESS OTHERWISE NOTED, ALL PIPING IS OVERHEAD, TIGHT TO

UNDERSIDE OF SLAB w/ SPACE FOR INSULATION IF REQUIRED.

PIPING IS TO BE "TOP DOWN".

INSTALL PIPING SO THAT ALL VALVES, STRAINERS, UNIONS,

TRAPS, FLANGES, AND OTHER APPURTENANCES REQUIRING

ACCESS ARE ACCESSIBLE.

WHERE DOMESTIC COLD AND HOT WATER PIPING DROPS INTO A

PIPE CHASE. THE SIZE SHOWN FOR THE PIPE DROPS SHALL BE

USED TO THE LAST FIXTURE.

ALL PIPING SHALL CLEAR DOORS AND WINDOWS.

ALL PIPING SHALL GRADE TO LOW POINTS. PROVIDE HOSE END

DRAINS VALVES AT THE BOTTOM OF ALL RISERS AND LOW

POINTS.

UNIONS AND/OR FLANGES SHALL BE INSTALLED AT EACH PIECE

OF EQUIPMENT, IN BYPASSES, AND IN LONG PIPING RUNS

(GREATER THAN 100 FEET) TO PERMIT DISASSEMBLY FOR

ALTERATIONS AND REPAIRS.

ALL VALVES SHALL BE ADJUSTED FOR SMOOTH AND EASY

OPERATION.

PROVIDE ALL PLUMBING FIXTURES AND EQUIPMENT w/

ACCESSIBLE STOPS.

PROVIDE CLEANOUTS IN SANITARY AND STORM DRAINAGE

SYSTEMS AT ENDS OF RUNS, AT CHANGES IN DIRECTIONS, NEAR

THE BASE OF STACKS, EVERY 50'-0" IN HORIZONTAL RUN AND

ELSEWHERE AS INDICATED.

ALL CLEANOUTS SHALL BE FULL SIZE OF PIPE FOR PIPE SIZES 4

INCHES AND SMALLER AND SHALL BE 4 INCHES FOR PIPE SIZES

LARGER THAN 4 INCHES.

ALL BALANCING VALVES AND BUTTERFLY VALVES SHALL BE

PROVIDED w/ POSITION INDICATORS AND MAXIMUM ADJUSTABLE

STOP (MEMORY STOPS).

ALL VALVES SHALL BE INSTALLED SO THAT THE VALVE REMAINS

IN SERVICE WHEN EQUIPMENT OR PIPING ON EQUIPMENT SIDE

OF VALVE IS REMOVED.

ALL PIPING WORK SHALL BE COORDINATED w/ ALL TRADES

INVOLVED. OFFSETS IN PIPING AROUND OBSTRUCTIONS SHALL

BE PROVIDED AT NO ADDITIONAL COST TO THE OWNER.

PROVIDE FLEXIBLE CONNECTIONS IN ALL PIPING SYSTEMS

CONNECTED TO PUMPS AND OTHER EQUIPMENT WHICH

REQUIRE VIBRATION ISOLATION. FLEXIBLE CONNECTIONS SHALL

BE PROVIDED AS CLOSE TO THE EQUIPMENT AS POSSIBLE OR AS

INDICATED ON THE DRAWINGS.

DOMESTIC WATER PIPING TO BE TYPE "L" COPPER w/ SOLDERED

OR MECHANICALLY PRESSED FITTINGS, OR CROS-LINKED PEX

PIPING USING BRONZE FITTINGS W/ STAINLESS STEEL BANDED

CLAMPS OR EXPANSION FITTINGS. WHERE PEX IS USED, COPPER

STUB-OUTS WILL BE INSTALLED AT ALL FIXTURE CONNECTIONS.

WASTE PIPING TO BE P40 PVC (BURIED OR CONCEALED), OR

CAST IRON NO-HUB (EXPOSED). VENT SANITARY PIPING AS

NECESSARY PER I.P.C. 2018. VENT THROUGH THE ROOF SUCH

THAT THE OUTSIDE AIR INTAKE IS MIN. OF 10'-0" FROM VENT.

COORDINATE ALL STUB-UPS, EXACT FIXTURE TYPE AND SIZES,

ETC. w/ GENERAL CONTRACTOR AND FOR FIT w GENERAL

CONTRACTOR INSTALLED CABINETRY, ETC. AND FOR FINAL WALL

LOCATIONS. FIELD ADJUST LOCATIONS FOR COORDINATION AS

NECESSARY. AVOID EXCESSIVE ADDITIONAL PIPE FITTINGS.

PRESSURE TEST ALL SUBGRADE PIPING AND MAINTAIN

PRESSURE TESTING DURING CONCRETE POURS.

PRESSURE TEST ALL DOMESTIC WATER PIPING w/ WATER. AIR

TESTING IS NOT PERMITTED.

FINAL COORDINATION OF SCOPE OF WORK, DIMENSIONS,

FIXTURE PLACEMENT, ROUTING, ETC. IS THE RESPONSIBILITY OF

THE GENERAL CONTRACTOR AND ALL SUB-CONTRACTORS

PRIOR TO BIDDING. VERIFY ALL FIELD CONDITIONS AND

MEASUREMENTS PRIOR TO BIDDING. COORDINATE ALL WORK w/ OTHER TRADES. COORDINATE ALL MOUNTED DEVICES w/ ALL

OTHER TRADES PRIOR TO INSTALLATION. FIRESTOP ALL

PENETRATIONS OF FIRE WALL (SEE ARCH. PLANS) AND FLOORS.

ALL WORK TO MEET REQUIREMENTS OF CURRENT

INTERVENTIONAL PLUMBING CODE, INTERNATIONAL

MECHANICAL CODE, STATE AND LOCAL CODES AND

REQUIREMENTS AND INTERNATIONAL FUEL GAS CODE.

EXTEND ALL VENTS THROUGH ROOF.

PLUMBING NOTES

L

--------------------A------------------------------------------------------------------------------------

AAV AUTOMATIC AIR VENT

ABV ABOVE

AD ACCESS DOOR

ADA AMERICANS WITH DISABLITIES ACT

AFF ABOVE FINISHED FLOOR

AFG ABOVE FINISHED GRADE

AHU AIR HANDLING UNIT

ALT ALTERNATE

ALUM ALUMINUM

AP ACCESS PANEL

APPROX APPROXIMATELY

ASSOC ASSOCIATED

ASSY ASSEMBLY

ATC AUTOMATIC TEMPERATURE CONTROL

AUTO AUTOMATIC

AUX AUXILIARY

AV AIR VENT

AVG AVERAGE

AWT AVERAGE WATER TEMPERATURE

---------------B----------------------------------------------------------------------------------------

BB BASEBOARD

BC BALANCING COCK

BD BLOW DOWN

BFF BELOW FINISHED FLOOR

BFG BELOW FINISHED GRADE

BFP BACKFLOW PREVENTER

BFV BUTTERFLY VALVE

BHP BRAKE HORESPOWER

BLDG BUILDING

BLR BOILER

BLW BELOW

BO BLOW OFF

BTM BOTTOM

BOP BOTTOM OF PIPE

BTUH BRITISH THERMAL UNIT PER HOUR

BV BALL VALVE

---------------C---------------------------------------------------------------------------------------

CA COMPRESSED AIR

CAP CAPACITY

CCW COUNTER CLOCKWISE

CDL CONDENSATE DRAIN LINE

CFH CUBIC FEET PER HOUR

CFM CUBIC FEET PER MINUTE

CFS CUBIC FEET PER SECOND

CHKV CHECK VALVE

CHWR CHILLED & HOT WATER RETURN

CHWS CHILLED & HOT WATER SUPPLY

CHWS&R CHILLED & HOT WATER SUPPLY AND RETURN

CIRC CIRCULATING

CI CAST IRON

CIRC CIRCULATING

CKT CIRCUIT

CLG CEILING

CL CENTER LINE

CMU CONCRETE MASONRY UNIT

C/O CLEAN OUT

COL COLUMN

COMB COMBINATION

COMP COMPRESSOR

CONC CONCRETE

COND CONDENSATE

CONN CONNECTION

CONT CONTINUATION

CONST CONSTRUCTION

COP COEFFICIENT OF PERFORMANCE

CORR CORRIDOR

CT COOLING TOWER

CU CONDENSING UNIT

CUH CABINET UNIT HEATER

Cv COEFFICIENT, VALVE FLOW

CW COLD WATER/CLOCKWISE

CWFT CONDENSER WATER FROM TOWER

CWR CHILLED WATER RETURN

CWS CHILLED WATER SUPPLY

CWS&R CHILLED WATER SUPPLY AND RETURN

CWTT CONDENSER WATER TO TOWER

---------------D----------------------------------------------------------------------

D DEEP

Db DRY BULB TEMPERATURE(ºF)

DCO DOUBLE CLEAN OUT

DEMO DEMOLISH

DEPT DEPARTMENT

DIA DIAMETER

DIAG DIAGRAM

DISCH DISCHARGE

DCW DOMESTIC COLD WATER

DHW DOMESTIC HOT WATER

DHWR DOMESTIC HOT WATER RETURN

DN DOWN

DP DIFFERENTIAL PRESSURE

DPT DEW POINT TEMPERATURE(ºF)

DR DRAIN

DWG DRAWING

DWH DOMESTIC WATER HEATER

DX DIRECT EXPANSION

----------------E----------------------------------------------------------------------

EA EACH

EC ELECTRICAL CONTRACTOR

EFF EFFICIENCY

ELEC ELECTRIC

ELEV ELEVATION

ENCL ENCLOSURE

ENT ENTERING

EP END PANEL/EXPLOSION PROOF

EQUIP EQUIPMENT

ER ECCENTRIC REDUCER(BOTTOMS FLAT)

ESP EXTERNAL STATIC PRESSURE

EXH EXHAUST

EXIST EXISTING

EXP EXPANSION

EWC ELECTRIC WATER COOLER

EWT ENTERING WATER TEMPERATUR(ºF)

----------------F----------------------------------------------------------------------

ºF FAHRENHEIT

FA FREE AREA

FB FREE BLOW

F&T FLOAT AND THERMOSTATIC TRAP

FC FLEXIBLE CONNECTION

FCD FLOW CONTROL DEVICE

FCO FLOOR CLEAN OUT

FCU FAN COIL UNIT

FD FIRE DAMPER/FLOOR DRAIN

FDN FOUNDATION

FF FOULING FACTOR

FIN FINISHED

FLA FULL LOAD AMPS

FLG FLANGE

FLR FLOOR

FNL FUNNEL

FOR FUEL OIL RETURN

FOS FUEL OIL SUPPLY

FOS&R FUEL OIL SUPPLY AND RETURN

FOV FUEL OIL VENT

FPB FAN POWERED BOX

FPM FEET PER MINUTE

FPS FEET PER SECOND

FT FIN-TUBE/FEET

FTG FITTING

FURN FURNISH

FV FACE VELOCITY

FW FEED WATER

----------------G----------------------------------------------------------------------

G GAS

GALV GALVANIZED

GA GAUGE, GAGE

GC GENERAL CONTRACTOR

GCWR GLYCOL CHILLED WATER RETURN

GCWS GLYCOL CHILLED WATER SUPPLY

GHWR GLYCOL HOT WATER RETURN

GHWS GLYCOL HOT WATER SUPPLY

GLV GLOBE VALVE

GPH GALLONS PER HOUR

GPM GALLONS PER MINUTE

GRAV GRAVITY

GRV GRAVITY ROOF VENTILATOR

GV GATE VALVE

----------------H----------------------------------------------------------------------

H HEIGHT

HB HOSE BIBB

HC HEATING CONTRACTOR;

HANICAPPED

HD HEAD/HUB DRAIN

HG MERCURY

HGR HANGER

HP HORSEPOWER/HEAT PUMP

HORIZ HORIZONTAL

HPD HIGH PRESSURE DRIP

HPR HIGH PRESSURE RETURN

HPS HIGH PRESSURE STEAM

HR HOUR

HTG HEATING

HTR HEATER

HUH HORIZONTAL UNIT HEATER

HV HIGH VELOCITY

HVAC HEATING, VENTILATING, AND AIR

CONDITIONING

HW HOT WATER

HWBG HOT WATER BELOW GRADE

HWOH HOT WATER OVER HEAD

HWR HOT WATER RETURN

HWS HOT WATER SUPPLY

HWS&R HOT WATER SUPPLY AND

RETURN

----------------I----------------------------------------------------------------------

ID INSIDE DIAMETER

IE INVERT ELEVATION

IN INCHES

INV INVERT

IN-WG INCHES-WATER GAGE

INSUL INSULATION

IPS IRON PIPE SIZE

IVS ISOLATION VALVE STATION

IW INDIRECT WASTE

----------------J----------------------------------------------------------------------

JT JOINT

----------------K ---------------------------------------------------------------------

KS KITCHEN SINK

----------------L----------------------------------------------------------------------

L LENGTH

LAV LAVATORY

LBS POUNDS

LBS/HR POUNDS PER HOUR

LF LINEAR FEET

LP LOW PRESSURE

LPD LOW PRESSURE DRIP

LPR LOW PRESSURE RETURN

LPG LOW PETROLEUM GAS

LPS LOW PRESSURE STEAM

LV LOW VELOCITY

LVG LEAVING

LWCO LOW WATER CUTOFF

LWT LEAVING WATER

TEMPERATURE(ºF)

----------------M----------------------------------------------------------------------

MAU MAKE-UP AIR UNIT

MAV MANUAL AIR VENT

MAX MAXIMUM

MBH THOUSAND BTUH

MC MECHANICAL CONTRACTOR

MCC MOTOR CONTROL CENTER

MECH MECHANICAL

MFG MANUFACTURER

MH MANHOLE

MIN MINIMUM

MISC MISCELLANEOUS

MPD MEDIUM PRESSURE DRIP

MPR MEDIUM PRESSURE RETURN

MPS MEDIUM PRESSURE STEAM

MS MINI-SPLIT SYSTEM

MTD MOUNTED

MTG MOUNTING

MTL METAL

MTR MOTOR

MWT MEAN WATER TEMPERATURE(ºF)

----------------N----------------------------------------------------------------------

N NORTH

N/A NOT APPLICABLE

NC NORMALLY CLOSED; NOISE CRITERIA

NEG NEGATIVE

NIC NOT IN CONTRACT

NM NONMETALLIC

NMAG NONMAGNETIC

NO NORMALLY OPEN

No NUMBER

NOM NOMINAL

NORM NORMAL

NPW NON POTABLE WATER

NTS NOT TO SCALE

NWL NORMAL WATER LEVEL

----------------O----------------------------------------------------------------------

OA OVERALL; OUTSIDE AIR

OC ON CENTER

OCC OCCUPANCY

OCPD OVERCURRENT PROTECTION DEVICE

OD OUTSIDE DIAMETER; OUTSIDE DIMENSION

ODS OXYGEN DEPRIVATION SENSOR

OF/CI OWNER FURNISHED / CONTRACTOR INSTALLED

OF/OI OWNER FURNISHED / OWNER INSTALLED

OFD OVER FLOW DRAIN

OH OVERHEAD

OPER OPERATED

OPP OPPOSITE

OPT OPTIONAL; OPTIMUM

OSHA OCCUPATIONAL SAFETY AND HEALTH

ADMINISTRATION

OSV OIL SAFETY VALVE

OUT OUTLET

OVC OVERCURRENT

OVF OVERFLOW

OZ OUNCE

----------------P----------------------------------------------------------------------

P PUMP

PC PLUMBING CONTRACTOR

PD PRESSURE DROP/PUMP

PE PNEUMATIC - ELECTRIC

PG PRESSURE DROP/PUMP DISCHARGE

PH PHASE

PLBG PLUMBING

PNL PANEL

PR PANEL RADIATOR

PRESS PRESSURE

PRV POWER ROOF VENTILATOR/PRESSURE REDUCING

VALVE

PS PIPE SUPPORT

PSI POUND PER SQUARE INCH

PSIA POUNDS PER SQUARE INCH ABSOLUTE

PSIG POUNDS PER SQUARE INCH GAGE

PT PRESSURE/TEMPERATURE TAP

PTAC PACKAGED TERMINAL AIR CONDITIONER

PVC POLYVINYL CHLORIDE

----------------Q----------------------------------------------------------------------

QTY QUANTITY

----------------R----------------------------------------------------------------------

RA RELIEF/RETURN AIR

RAD RADIATOR

RAF RETURN AIR FIXTURES

RCP RADIANT CEILING PANEL

RD ROOF DRAIN

REC RECESSED/RECEIVED

REFRIG REFRIGERANT

REG REGISTER

REINF REINFORCED

REQD REQUIRED

RET RETURN

REV REVISION

RF RETURN/RELIEF FAN

RH REHEAT COIL

RHG REFRIGERANT HOT

RL REFRIGERANT LIQUID

RM ROOM

RPM REVOLUTIONS PER MINUTE

RS REFRIGERANT SUCTION

RV RELIEF VALVE

RWC RAIN WATER CONDUCTOR

----------------S----------------------------------------------------------------------

SA SUPPLY AIR

SCH SCHEDULE

SDPR SMOKE DAMPER

SENS SENSIBLE

SEP SEPARATOR

SF SUPPLY FAN

SHT SHEET

SK SINK

SP STATIC PRESSURE (INCHES OF WATER)

SPEC SPECIFICATION

SPGR SPECIFIC GRAVITY

SQ SQUARE

SQFT SQUARE FOOT

SS STAINLESS STEEL UNIT

STAT STATIC

STD STANDARD

STL STEEL

STR STRAINER

SUP SUPPLY

SV SAFETY VALVE

SW SWITCH

----------------T----------------------------------------------------------------------

TA THROW AWAY

TCV TEMPERATURE CONTROL VALVE

TD TEMPERATURE DIFFERENCE

TDV TRIPLE DUTY VALVE

TEMP TEMPERATURE

TH THERMOMETER

THK THICK

TK TANK

TMV THRTMOSTATIC MIXING VALVE

TOT TOTAL

TP TRAP PRIMER/TRAP PRIMER SUPPLY

TRANS TRANSITION

TSP TOTAL STATIC PRESSURE

TSTAT THERMOSTAT

TYP TYPICAL

----------------U----------------------------------------------------------------------

UC UNDERCUT

UF UNDER FLOOR

UG UNDERGROUND

UH UNIT HEATER

UR URINAL

----------------V----------------------------------------------------------------------

V VOLTAGE/VALVE/VENT

VAC VACUUM

VEL VELOCITY

VERT VERTICAL

VFD VARIABLE FREQUENCY DRIVE

VFS VENTURI FLOW STATION

VOL VOLUME

VRF VARIABLE REFRIGERANT FLOW

VTR VENT THROUGH ROOF

----------------W----------------------------------------------------------------------

W WIDTH

W/ WITH

W/O WITHOUT

WA WATER HAMMER ARRESTER

Wb WET BULB TEMPERATURE(ºF)

WC WATER COLUMN/WATER CLOSET

WCO WALL CLEANOUT

WG WATER GAUGE

WH WALL HEATER

WL WATER LEVEL

WP WEATHERPROOF

WT WEIGHT

----------------Y----------------------------------------------------------------------

YCO YARD CLEANOUT

----------------Z----------------------------------------------------------------------

Z ZONE

ZCV ZONE CONTROL VALVE

PA OFFICE:

PO BOX 42

GARARDS FORT, PA 15334

PH: (724) 966-5655

WV OFFICE:

54 WEST RUN RD

MORGANTOWN, WV 26508

PH: (304) 291-2234

PROJECT NUMBER:

ISSUE DATE:

CHECKED BY:

SHEET NUMBER:

SH

EE

T

TI

TL

E:

A

LL

R

IG

H

TS

R

ES

ER

VE

D

M

O N

TU

M

A R

C H

IT

EC

TU

R

E, L

LC

SEAL:

CONSULTANTS:

P000

PL

U

M

BI

N G

AB

BR

EV

IA

TI

O

N S

M25019

BU

IL

D

IN

G

R

EN

O

VA

TI

O N

W V

AR

M

Y N

AT

IO

N

AL

G U

AR

D

08/11/2026

BCM

IS

SU

ED

F

O R

B

ID

D

IN

G

C

AM

P D

AW

SO

N

KI

N G

W O

O D

, W V

PLUMBING ABBREVIATIONS

PLUMBING SYSTEM LEGEND

ABBREVIATION SYSTEM TYPE

DCW Domestic Cold Water DHW Domestic Hot Water SAN Sanitary THW Tempered Hot Water

THWR Tempered Hot Water Return VEN Vent

N o.

D es cr ip tio n

D at e

3.

4.

5.

6.

7.

8.

9.

10.

11.

12.

13.

14.

15.

16.

17.

18.

19.

20.

21.

22.

23.

24.

25.

26.

PROVIDE ALL MATERIALS AND EQUIPMENT AND PERFORM ALL

LABOR REQUIRED TO INSTALL COMPLETE AND OPERABLE

PLUMBING SYSTEMS AS INDICATED ON THE DRAWING, AS

SPECIFIED, AND REQUIRED BY CODE.

RUN ALL SOIL WASTE AND VENT PIPING WITH 2% MIN. GRADE

UNLESS OTHERWISE NOTED. HORIZONTAL VENT PIPING SHALL

BE GRADED TO DRIP BACK TO THE SOIL OR WASTE PIPE BY

GRAVITY.

MAINTAIN A MIN. 3'-0" OF GROUND COVER OVER ALL

UNDERGROUND WATER MAINS AND A MIN. 3'-0" OF GROUND

COVER OVER ALL UNDERGROUND SEWERS AND DRAINS.

PROVIDE SHUTOFF VALVES IN ALL DOMESTIC WATER PIPING

SYSTEMS AT ALL SERVICE POINTS AND AT BRANCHES IN WHICH

PIPING SERVES TWO OR MORE FIXTURES.

UNLESS OTHERWISE NOTED, ALL DOMESTIC COLD AND HOT

WATER PIPING SHALL BE A MIN. OF 1/2" SIZE.

UNLESS OTHERWISE NOTED, ALL PIPING IS OVERHEAD, TIGHT TO

UNDERSIDE OF SLAB w/ SPACE FOR INSULATION IF REQUIRED.

PIPING IS TO BE "TOP DOWN".

INSTALL PIPING SO THAT ALL VALVES, STRAINERS, UNIONS,

TRAPS, FLANGES, AND OTHER APPURTENANCES REQUIRING

ACCESS ARE ACCESSIBLE.

WHERE DOMESTIC COLD AND HOT WATER PIPING DROPS INTO A

PIPE CHASE. THE SIZE SHOWN FOR THE PIPE DROPS SHALL BE

USED TO THE LAST FIXTURE.

ALL PIPING SHALL CLEAR DOORS AND WINDOWS.

ALL PIPING SHALL GRADE TO LOW POINTS. PROVIDE HOSE END

DRAINS VALVES AT THE BOTTOM OF ALL RISERS AND LOW

POINTS.

UNIONS AND/OR FLANGES SHALL BE INSTALLED AT EACH PIECE

OF EQUIPMENT, IN BYPASSES, AND IN LONG PIPING RUNS

(GREATER THAN 100 FEET) TO PERMIT DISASSEMBLY FOR

ALTERATIONS AND REPAIRS.

ALL VALVES SHALL BE ADJUSTED FOR SMOOTH AND EASY

OPERATION.

PROVIDE ALL PLUMBING FIXTURES AND EQUIPMENT w/

ACCESSIBLE STOPS.

PROVIDE CLEANOUTS IN SANITARY AND STORM DRAINAGE

SYSTEMS AT ENDS OF RUNS, AT CHANGES IN DIRECTIONS, NEAR

THE BASE OF STACKS, EVERY 50'-0" IN HORIZONTAL RUN AND

ELSEWHERE AS INDICATED.

ALL CLEANOUTS SHALL BE FULL SIZE OF PIPE FOR PIPE SIZES 4

INCHES AND SMALLER AND SHALL BE 4 INCHES FOR PIPE SIZES

LARGER THAN 4 INCHES.

ALL BALANCING VALVES AND BUTTERFLY VALVES SHALL BE

PROVIDED w/ POSITION INDICATORS AND MAXIMUM ADJUSTABLE

STOP (MEMORY STOPS).

ALL VALVES SHALL BE INSTALLED SO THAT THE VALVE REMAINS

IN SERVICE WHEN EQUIPMENT OR PIPING ON EQUIPMENT SIDE

OF VALVE IS REMOVED.

ALL PIPING WORK SHALL BE COORDINATED w/ ALL TRADES

INVOLVED. OFFSETS IN PIPING AROUND OBSTRUCTIONS SHALL

BE PROVIDED AT NO ADDITIONAL COST TO THE OWNER.

PROVIDE FLEXIBLE CONNECTIONS IN ALL PIPING SYSTEMS

CONNECTED TO PUMPS AND OTHER EQUIPMENT WHICH

REQUIRE VIBRATION ISOLATION. FLEXIBLE CONNECTIONS SHALL

BE PROVIDED AS CLOSE TO THE EQUIPMENT AS POSSIBLE OR AS

INDICATED ON THE DRAWINGS.

DOMESTIC WATER PIPING TO BE TYPE "L" COPPER w/ SOLDERED

OR MECHANICALLY PRESSED FITTINGS, OR CROS-LINKED PEX

PIPING USING BRONZE FITTINGS W/ STAINLESS STEEL BANDED

CLAMPS OR EXPANSION FITTINGS. WHERE PEX IS USED, COPPER

STUB-OUTS WILL BE INSTALLED AT ALL FIXTURE CONNECTIONS.

WASTE PIPING TO BE P40 PVC (BURIED OR CONCEALED), OR

CAST IRON NO-HUB (EXPOSED). VENT SANITARY PIPING AS

NECESSARY PER I.P.C. 2018. VENT THROUGH THE ROOF SUCH

THAT THE OUTSIDE AIR INTAKE IS MIN. OF 10'-0" FROM VENT.

COORDINATE ALL STUB-UPS, EXACT FIXTURE TYPE AND SIZES,

ETC. w/ GENERAL CONTRACTOR AND FOR FIT w GENERAL

CONTRACTOR INSTALLED CABINETRY, ETC. AND FOR FINAL WALL

LOCATIONS. FIELD ADJUST LOCATIONS FOR COORDINATION AS

NECESSARY. AVOID EXCESSIVE ADDITIONAL PIPE FITTINGS.

PRESSURE TEST ALL SUBGRADE PIPING AND MAINTAIN

PRESSURE TESTING DURING CONCRETE POURS.

PRESSURE TEST ALL DOMESTIC WATER PIPING w/ WATER. AIR

TESTING IS NOT PERMITTED.

FINAL COORDINATION OF SCOPE OF WORK, DIMENSIONS,

FIXTURE PLACEMENT, ROUTING, ETC. IS THE RESPONSIBILITY OF

THE GENERAL CONTRACTOR AND ALL SUB-CONTRACTORS

PRIOR TO BIDDING. VERIFY ALL FIELD CONDITIONS AND

MEASUREMENTS PRIOR TO BIDDING. COORDINATE ALL WORK w/ OTHER TRADES. COORDINATE ALL MOUNTED DEVICES w/ ALL

OTHER TRADES PRIOR TO INSTALLATION. FIRESTOP ALL

PENETRATIONS OF FIRE WALL (SEE ARCH. PLANS) AND FLOORS.

ALL WORK TO MEET REQUIREMENTS OF CURRENT

INTERVENTIONAL PLUMBING CODE, INTERNATIONAL

MECHANICAL CODE, STATE AND LOCAL CODES AND

REQUIREMENTS AND INTERNATIONAL FUEL GAS CODE.

EXTEND ALL VENTS THROUGH ROOF.

PLUMBING NOTES

DEMO BATHROOM FIXTURES. CAP PIPING AT WALL OR AT GRADE.

DEMO GAS-FIRED WATER HEATERS

PA OFFICE:

PO BOX 42

GARARDS FORT, PA 15334

PH: (724) 966-5655

WV OFFICE:

54 WEST RUN RD

MORGANTOWN, WV 26508

PH: (304) 291-2234

PROJECT NUMBER:

ISSUE DATE:

CHECKED BY:

SHEET NUMBER:

SH

EE

T

TI

TL

E:

A

LL

R

IG

H

TS

R

ES

ER

VE

D

M

O N

TU

M

A R

C H

IT

EC

TU

R

E, L

LC

SEAL:

CONSULTANTS:

P001

D O

M

ES

TI

C

PL

U

M

BI

N G

D

EM

O P

LA

N

M25019

BU

IL

D

IN

G

R

EN

O

VA

TI

O N

W V

AR

M

Y N

AT

IO

N

AL

G U

AR

D

08/11/2026

BCM

IS

SU

ED

F

O R

B

ID

D

IN

G

C

AM

P D

AW

SO

N

KI

N G

W O

O D

, W V

PLUMBING SYSTEM LEGEND

ABBREVIATION SYSTEM TYPE

DCW Domestic Cold Water DHW Domestic Hot Water SAN Sanitary THW Tempered Hot Water

THWR Tempered Hot Water Return VEN Vent

3/16" = 1'-0"1

FISRT FLOOR DOMESTIC PLUMBING DEMO PLAN

N o.

D es cr ip tio n

D

3.

4.

5.

6.

7.

8.

9.

10.

11.

12.

13.

14.

15.

16.

17.

18.

19.

20.

21.

22.

23.

24.

25.

26.

PROVIDE ALL MATERIALS AND EQUIPMENT AND PERFORM ALL

LABOR REQUIRED TO INSTALL COMPLETE AND OPERABLE

PLUMBING SYSTEMS AS INDICATED ON THE DRAWING, AS

SPECIFIED, AND REQUIRED BY CODE.

RUN ALL SOIL WASTE AND VENT PIPING WITH 2% MIN. GRADE

UNLESS OTHERWISE NOTED. HORIZONTAL VENT PIPING SHALL

BE GRADED TO DRIP BACK TO THE SOIL OR WASTE PIPE BY

GRAVITY.

MAINTAIN A MIN. 3'-0" OF GROUND COVER OVER ALL

UNDERGROUND WATER MAINS AND A MIN. 3'-0" OF GROUND

COVER OVER ALL UNDERGROUND SEWERS AND DRAINS.

PROVIDE SHUTOFF VALVES IN ALL DOMESTIC WATER PIPING

SYSTEMS AT ALL SERVICE POINTS AND AT BRANCHES IN WHICH

PIPING SERVES TWO OR MORE FIXTURES.

UNLESS OTHERWISE NOTED, ALL DOMESTIC COLD AND HOT

WATER PIPING SHALL BE A MIN. OF 1/2" SIZE.

UNLESS OTHERWISE NOTED, ALL PIPING IS OVERHEAD, TIGHT TO

UNDERSIDE OF SLAB w/ SPACE FOR INSULATION IF REQUIRED.

PIPING IS TO BE "TOP DOWN".

INSTALL PIPING SO THAT ALL VALVES, STRAINERS, UNIONS,

TRAPS, FLANGES, AND OTHER APPURTENANCES REQUIRING

ACCESS ARE ACCESSIBLE.

WHERE DOMESTIC COLD AND HOT WATER PIPING DROPS INTO A

PIPE CHASE. THE SIZE SHOWN FOR THE PIPE DROPS SHALL BE

USED TO THE LAST FIXTURE.

ALL PIPING SHALL CLEAR DOORS AND WINDOWS.

ALL PIPING SHALL GRADE TO LOW POINTS. PROVIDE HOSE END

DRAINS VALVES AT THE BOTTOM OF ALL RISERS AND LOW

POINTS.

UNIONS AND/OR FLANGES SHALL BE INSTALLED AT EACH PIECE

OF EQUIPMENT, IN BYPASSES, AND IN LONG PIPING RUNS

(GREATER THAN 100 FEET) TO PERMIT DISASSEMBLY FOR

ALTERATIONS AND REPAIRS.

ALL VALVES SHALL BE ADJUSTED FOR SMOOTH AND EASY

OPERATION.

PROVIDE ALL PLUMBING FIXTURES AND EQUIPMENT w/

ACCESSIBLE STOPS.

PROVIDE CLEANOUTS IN SANITARY AND STORM DRAINAGE

SYSTEMS AT ENDS OF RUNS, AT CHANGES IN DIRECTIONS, NEAR

THE BASE OF STACKS, EVERY 50'-0" IN HORIZONTAL RUN AND

ELSEWHERE AS INDICATED.

ALL CLEANOUTS SHALL BE FULL SIZE OF PIPE FOR PIPE SIZES 4

INCHES AND SMALLER AND SHALL BE 4 INCHES FOR PIPE SIZES

LARGER THAN 4 INCHES.

ALL BALANCING VALVES AND BUTTERFLY VALVES SHALL BE

PROVIDED w/ POSITION INDICATORS AND MAXIMUM ADJUSTABLE

STOP (MEMORY STOPS).

ALL VALVES SHALL BE INSTALLED SO THAT THE VALVE REMAINS

IN SERVICE WHEN EQUIPMENT OR PIPING ON EQUIPMENT SIDE

OF VALVE IS REMOVED.

ALL PIPING WORK SHALL BE COORDINATED w/ ALL TRADES

INVOLVED. OFFSETS IN PIPING AROUND OBSTRUCTIONS SHALL

BE PROVIDED AT NO ADDITIONAL COST TO THE OWNER.

PROVIDE FLEXIBLE CONNECTIONS IN ALL PIPING SYSTEMS

CONNECTED TO PUMPS AND OTHER EQUIPMENT WHICH

REQUIRE VIBRATION ISOLATION. FLEXIBLE CONNECTIONS SHALL

BE PROVIDED AS CLOSE TO THE EQUIPMENT AS POSSIBLE OR AS

INDICATED ON THE DRAWINGS.

DOMESTIC WATER PIPING TO BE TYPE "L" COPPER w/ SOLDERED

OR MECHANICALLY PRESSED FITTINGS, OR CROS-LINKED PEX

PIPING USING BRONZE FITTINGS W/ STAINLESS STEEL BANDED

CLAMPS OR EXPANSION FITTINGS. WHERE PEX IS USED, COPPER

STUB-OUTS WILL BE INSTALLED AT ALL FIXTURE CONNECTIONS.

WASTE PIPING TO BE P40 PVC (BURIED OR CONCEALED), OR

CAST IRON NO-HUB (EXPOSED). VENT SANITARY PIPING AS

NECESSARY PER I.P.C. 2018. VENT THROUGH THE ROOF SUCH

THAT THE OUTSIDE AIR INTAKE IS MIN. OF 10'-0" FROM VENT.

COORDINATE ALL STUB-UPS, EXACT FIXTURE TYPE AND SIZES,

ETC. w/ GENERAL CONTRACTOR AND FOR FIT w GENERAL

CONTRACTOR INSTALLED CABINETRY, ETC. AND FOR FINAL WALL

LOCATIONS. FIELD ADJUST LOCATIONS FOR COORDINATION AS

NECESSARY. AVOID EXCESSIVE ADDITIONAL PIPE FITTINGS.

PRESSURE TEST ALL SUBGRADE PIPING AND MAINTAIN

PRESSURE TESTING DURING CONCRETE POURS.

PRESSURE TEST ALL DOMESTIC WATER PIPING w/ WATER. AIR

TESTING IS NOT PERMITTED.

FINAL COORDINATION OF SCOPE OF WORK, DIMENSIONS,

FIXTURE PLACEMENT, ROUTING, ETC. IS THE RESPONSIBILITY OF

THE GENERAL CONTRACTOR AND ALL SUB-CONTRACTORS

PRIOR TO BIDDING. VERIFY ALL FIELD CONDITIONS AND

MEASUREMENTS PRIOR TO BIDDING. COORDINATE ALL WORK w/ OTHER TRADES. COORDINATE ALL MOUNTED DEVICES w/ ALL

OTHER TRADES PRIOR TO INSTALLATION. FIRESTOP ALL

PENETRATIONS OF FIRE WALL (SEE ARCH. PLANS) AND FLOORS.

ALL WORK TO MEET REQUIREMENTS OF CURRENT

INTERVENTIONAL PLUMBING CODE, INTERNATIONAL

MECHANICAL CODE, STATE AND LOCAL CODES AND

REQUIREMENTS AND INTERNATIONAL FUEL GAS CODE.

EXTEND ALL VENTS THROUGH ROOF.

PLUMBING NOTES

DEMO PLUMBING FIXTURES. CAP SANITARY PIPING AT WALL. INSTALL

CLEAN-OUTS (CO-1) AT WATER CLOSET SAN PIPING.

DEMO EXPOSED SANITARY PIPING FROM RINSE SINK &

DISHWASHWER & CAP AT CONNECTION TO EXISTING SAN

LINE TO GREASE INTERCEPTOR.

DEMO MOP SINK. INSTALL CLEAN-OUT (CO-1) AT SAN CONNECTION IN FLOOR.

DEMO GREASE INTERCEPTOR

PA OFFICE:

PO BOX 42

GARARDS FORT, PA 15334

PH: (724) 966-5655

WV OFFICE:

54 WEST RUN RD

MORGANTOWN, WV 26508

PH: (304) 291-2234

PROJECT NUMBER:

ISSUE DATE:

CHECKED BY:

SHEET NUMBER:

SH

EE

T

TI

TL

E:

A

LL

R

IG

H

TS

R

ES

ER

VE

D

M

O N

TU

M

A R

C H

IT

EC

TU

R

E, L

LC

SEAL:

CONSULTANTS:

P002

SA

N

IT

AR

Y

PL

U M

BI

N

G D

EM

O

P

LA

N

M25019

BU

IL

D

IN

G

R

EN

O

VA

TI

O N

W V

AR

M

Y N

AT

IO

N

AL

G U

AR

D

08/11/2026

BCM

IS

SU

ED

F

O R

B

ID

D

IN

G

C

AM

P D

AW

SO

N

KI

N G

W O

O D

, W V

PLUMBING SYSTEM LEGEND

ABBREVIATION SYSTEM TYPE

DCW Domestic Cold Water DHW Domestic Hot Water SAN Sanitary THW Tempered Hot Water

THWR Tempered Hot Water Return VEN Vent

3/16" = 1'-0"1

FIRST FLOOR SANITARY PLUMBING DEMO PLAN

N o.

D es cr ip tio n

D

3.

4.

5.

6.

7.

8.

9.

10.

11.

12.

13.

14.

15.

16.

17.

18.

19.

20.

21.

22.

23.

24.

25.

26.

PROVIDE ALL MATERIALS AND EQUIPMENT AND PERFORM ALL

LABOR REQUIRED TO INSTALL COMPLETE AND OPERABLE

PLUMBING SYSTEMS AS INDICATED ON THE DRAWING, AS

SPECIFIED, AND REQUIRED BY CODE.

RUN ALL SOIL WASTE AND VENT PIPING WITH 2% MIN. GRADE

UNLESS OTHERWISE NOTED. HORIZONTAL VENT PIPING SHALL

BE GRADED TO DRIP BACK TO THE SOIL OR WASTE PIPE BY

GRAVITY.

MAINTAIN A MIN. 3'-0" OF GROUND COVER OVER ALL

UNDERGROUND WATER MAINS AND A MIN. 3'-0" OF GROUND

COVER OVER ALL UNDERGROUND SEWERS AND DRAINS.

PROVIDE SHUTOFF VALVES IN ALL DOMESTIC WATER PIPING

SYSTEMS AT ALL SERVICE POINTS AND AT BRANCHES IN WHICH

PIPING SERVES TWO OR MORE FIXTURES.

UNLESS OTHERWISE NOTED, ALL DOMESTIC COLD AND HOT

WATER PIPING SHALL BE A MIN. OF 1/2" SIZE.

UNLESS OTHERWISE NOTED, ALL PIPING IS OVERHEAD, TIGHT TO

UNDERSIDE OF SLAB w/ SPACE FOR INSULATION IF REQUIRED.

PIPING IS TO BE "TOP DOWN".

INSTALL PIPING SO THAT ALL VALVES, STRAINERS, UNIONS,

TRAPS, FLANGES, AND OTHER APPURTENANCES REQUIRING

ACCESS ARE ACCESSIBLE.

WHERE DOMESTIC COLD AND HOT WATER PIPING…