26-059-ITB_-ADDENDUM_1_PLANS_-_11.20.26.pdf

PDF 5 MB Posted

Attached to
Police Department Rehabilitation Project
Solicitation number
26-059-ITB
Issued by
Kenton County, Kentucky

About this file

This is an Addendum #1 to the Invitation to Bid (ITB 26-059) for the Police Department Rehabilitation Project at Cincinnati/Northern Kentucky International Airport in Hebron, Kentucky, issued by the Kenton County Airport Board. The addendum contains electrical site plans, first floor electrical demolition plans, first floor electrical lighting plans, and first floor electrical power plans prepared by Emboss Design, P.S.C. The project involves comprehensive interior improvements to the Airport Police Department building, including electrical system upgrades, HVAC equipment replacement, perimeter fencing with motorized sliding fence gates and manual person gates, and finish work in multiple areas. Key electrical work includes providing power to new gate operators with full systems functionality including sensors and wiring per manufacturer recommendations; installing keypad and intercom devices per CVG standards connected to the CVG security system; providing temporary trailers with electrical pedestals; replacing water-damaged light fixtures; installing new lighting controls; disconnecting and removing existing HVAC equipment scheduled for demolition while retaining connections for new equipment; and cleaning and resecuring all wiring and conduit above accessible ceilings with an allowance of $25,000 for this work scope. The pre-bid meeting and mandatory site visit occurred on November 19, 2026 at 10:00 a.m., with questions due December 1, 2026 at 11:59 a.m. and bids due December 17, 2026 at 2:00 p.m. Eastern Time.

Substantial completion is required within 450 days with closeout within 30 days after, and work must proceed in four phases while maintaining 24-hour police operations and keeping the first-floor training area and second-floor lobby accessible. Electrical contractors must field-verify all existing loads, panels, circuit breakers, and utility routing prior to bid submission; provide temporary emergency exit lights at construction barriers; seal all building envelope penetrations water-tight; coordinate with other trades for equipment relocation; and comply with all federal, state, and local codes including NEC requirements. Mobilization is capped at 10 percent of total project cost, all work carries a one-year warranty from Final Acceptance, and Davis-Bacon prevailing wage rates apply under General Decision KY20260044. The project is funded through local operations and maintenance and CVG capital funds, with award anticipated within 120 calendar days of bid opening. All fees for utility companies, municipalities, inspectors, and reviewing agencies are included in the contract price, and contractors must provide evidence of Kentucky prequalification or certified financial statements demonstrating financial responsibility and competency.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

KP

K P

IR

IR

J J

PROPOSED LOCATION OF THE NEW

FENCE. REFER TO ARCHITECTURAL SITE

PLAN FOR EXACT LOCATION. SHOWN ON

THIS PLAN FOR REFERENCE ONLY.

PROPOSED LOCATION OF THE NEW

MOTORIZED SLIDING FENCE GATE.

REFER TO ARCHITECTURAL SITE PLAN

FOR EXACT LOCATION. SHOWN ON THIS

PLAN FOR REFERENCE ONLY.

PROPOSED LOCATION OF THE NEW

MOTORIZED SLIDING FENCE GATE.

REFER TO ARCHITECTURAL SITE PLAN

FOR EXACT LOCATION. SHOWN ON THIS

PLAN FOR REFERENCE ONLY.

PROPOSED LOCATION OF THE NEW

MANUAL PERSON FENCE GATE. REFER

TO ARCHITECTURAL SITE PLAN FOR

EXACT LOCATION. SHOWN ON THIS

PLAN FOR REFERENCE ONLY.

DOOR OPERATOR

DOOR OPERATOR

-23,25,27EMA

-29,31,33EMA

RR TRAILER

E12

E13

E12

E13

E14

-10EMB -12EMB

(2 SETS) (2) #6 CU AWG & #

8 CU AWG GND IN 1-1/4"C

COORDINATE WITH CVG

FOR ABOVE GROUND

TEMP CONDUITS AND

PATHWAYS.

POWER CORD TO TRAILER

CONNECTION BY OTHERS.

POWER CORD TO TRAILER

CONNECTION BY OTHERS.

CONTRACTOR TO MARK

AND AVOID ALL EXISTING

DUCTBANKS IN THIS AREA

FOR THE NEW FENCE

CONTRACTOR TO PROVIDE

CONNECTIONS FOR LIGHTNING

PROTECTIONS ON THE FENCE,

COORDINATE WITH FENCE

CONTRACTOR/MANUFACTURER.

DATE DESCRIPTION NO.

906 Monmouth Street, Newport, KY 41071

EmbossDesign.com

(859)431-8612

3222 Terminal Dr.

Hebron, KY 41015

POLICE DEPARTMENT

CINCINNATI/NORTHERN KY

INTERNATIONAL AIRPORT

TH

IS

D O

C U M

EN

T, A N

D T

H E

ID

EA

S A N

D D

ES

IG

N S

IN

C O

R

PO

R A

TE

D H

ER

EI

N , A

S A N

I N

ST

R U M

EN

T

O F

PR

O

FE

SS

IO

N

A L

SE

R V

IC

E, I S

TH

E

PR

O

PE

R

TY

O F

EM

BO

SS

D

ES

IG

N , P

.S .C

A N

D I S

N O

T

TO

B E

U

SE

D I N

W H

O

LE

O R I N

P A R T

FO

R A

N Y

O

TH

ER

P

R O

JE

C T, W

IT

H O

U T

TH

E

W R

IT

TE

N

A U

TH

O R

IZ

A

TI

O N

O F

EM

B O

SS

D

ES

IG

N , P

.S .C

C O

PY

R

IG

H T

-2

5:

E

M B O

SS

D

ES

IG

N , P

.S .C

A

LL

R

IG

H

TS

R

ES

ER

V

ED

151413 161110987654321

A

D

B

C

E

F

G

H

J

K

L

M

15141312 161110987654321

A

D

B

C

E

F

G

H

J

K

L

M

IS

SU

E

P

\P

R -0

C V

G P

O L

IC

E S

T A

T

IO

N \0

-D

R A

W

IN

G S

1100 Sycamore St Suite 400, Cincinnati, OH 45202

Interior Improvements

2023-047

E001

E L E C T R I C A L S I T E P L A N

TAGGED NOTES

E12 PROVIDE POWER TO NEW GATE OPERATORS. PROVIDE A FULL AND

COMPLETE SYSTEM TO FUNCTION AS INTENDED. PROVIDE ALL

SENSORS AND WIRING AS NECESSARY BY THE MANUFACTURER'S

RECOMMENDATIONS.

E13 PROVIDE KEYPAD AND INTERCOM DEVICES PER CVG STANDARDS FOR

GATE OPERATORS. CONNECT INTO CVG SECURITY

SYSTEM/MONITORING WITHIN AOC.

E14 PROVIDE TRAILER PEDESTAL FOR (2) TEMPORARY RR TRAILERS.

COORDINATE FINAL CONNECTION REQUIREMENTS AND LOCATION

WITH TRAILER MANUFACTURER PRIOR TO INSTALLATION. REFER TO

DETAIL 2 ON SHEET E501 FOR MORE INFORMATION.

GENERAL NOTES (SITE):

A. DO NOT SCALE FROM MECHANICAL AND ELECTRICAL DRAWINGS. FIELD VERIFY REQUIRED DIMENSIONS AND COORDINATE WITH CIVIL DRAWINGS AND SURVEYS.

B. REFER ALSO TO ALL OTHER PLANS AND THE SPECIFICATION, BUT ESPECIALLY TO: THE SITE SURVEY, THE ARCHITECTURAL SITE PLAN, THE SITE GRADING PLAN, THE PLANTING PLAN (WHERE AVAILABLE), FOUNDATION PLAN(S), APPROPRIATE MECHANICAL & ELECTRICAL FLOOR PLANS FOR SERVICE CONTINUATIONS, THE SITE UTILITY PLAN - MECHANICAL & ELECTRICAL. WHERE THERE ARE CONFLICTS AMONG THESE PLANS AND/OR RELATED SPECIFICATIONS, ADVISE THESE

ENGINEERS AT LEAST TEN DAYS PRIOR TO SUBMISSION OF BIDS.

C. ALL FEES AND ANY OTHER COSTS TO UTILITY COMPANIES, MUNICIPALITIES, INSPECTORS, REVIEWING AGENCIES, ETC. ARE TO BE INCLUDED AS A PART OF THIS

CONTRACT.

D. FEDERAL, STATE, LOCAL, MUNICIPALITY AND UTILITY COMPANY CODES, RULES, REGULATIONS AND REQUIREMENTS APPLY UNLESS EXCEEDED BY THIS DESIGN.

E. WHEN INTERRUPTION OF AN EXISTING UTILITY OR SERVICE IS PLANNED OR OCCURS ACCIDENTALLY, THE CONTRACTOR(S) SHALL WORK CONTINUOUSLY AS

NEEDED TO RESTORE SAME PROVIDING PREMIUM TIME AS NEEDED AT NO INCREASE IN THE CONTRACT PRICE.

F. LOCATIONS, DEPTHS, MATERIAL TYPES, ELEVATIONS, ETC. OF ALL APPURTENANCES, LINES, BUILDINGS, ETC. INDICATED ON THESE DRAWINGS WERE TAKEN

FROM VARIOUS SOURCES, ARE DIAGRAMMATIC ONLY AND ARE SUBJECT TO SUBSTANTIAL VARIATION FROM EXISTING CONDITIONS, EXISTING UTILITIES LOCATIONS MAY VARY. CONSEQUENTLY ALL CONTRACTORS SHALL EXERCISE EXTREME CARE IN THE COURSE OF THEIR WORK SO AS TO ENSURE THAT THEY DO NOT INTERRUPT ANY EXISTING SERVICE. FOR SAFETY PURPOSES, PAY PARTICULAR ATTENTION TO THIS PRECAUTION RELATIVE TO NATURAL GAS AND ELECTRICAL LINES. ALL WORK SHALL BE PERFORMED IN ACCORDANCE WITH ALL FEDERAL, STATE, AND/OR LOCAL RULES, REGULATIONS, STANDARDS AND

SAFETY REQUIREMENTS.

G. PROVIDE LONG RADIUS ELBOWS FOR UNDERGROUND CONDUIT BENDS. WHERE SERVING A UTILITY OWNED TRANSFORMER, THE UTILTY STANDARDS SHALL

TAKE PRECEDENCE.

H. UTILITIES SHALL BE INSTALLED IN ACCORDANCE WITH THE APPLICABLE MUNICIPALITY OR UTILITY COMPANY STANDARDS. IN ALL CASES, THE MOST STRINGENT REQUIREMENT SHALL APPLY. IF ANY VARIATION OCCURS, CONSULT THE ENGINEER. CONTRACTOR SHALL VISIT THE SITE AND FIELD VERIFY THE ROUTING OF ALL UTILITIES NEW AND EXISTING PRIOR TO SUBMISSION OF BIDS. SUBMISSION OF A BID PROPOSAL INDICATES THAT THE CONTRACTOR IS FULLY AWARE OF ALL OBSTRUCTIONS AND WILL INSTALL ALL OF THE NEW UTILITIES WITHOUT REQUESTS FOR ANY ADDITIONAL CHANGES.

I. PROVIDE GALVANIZED RIGID CONDUIT FOR EXTERIOR UNDERGROUND TRANSITIONS TO ABOVE GRADE; EXTEND CONDUIT A MINIMUM OF 6” ABOVE GRADE.

J. CONTRACTOR SHALL CONTACT ENGINEER FOR INSPECTION OF TRENCHES PRIOR TO INSTALLATION OF CONDUITS OR RACEWAYS. PROVIDE PHOTOS UPON

REQUEST.

K. CONTRACTOR SHALL CUT AND PATCH ALL PAVEMENT, CURBING, ETC. AS REQUIRED FOR WORK. CONTRACTOR SHALL REPAIR ALL LANDSCAPING THAT IS

DAMAGED FOR WORK. FINISH GRADE, SEED AND STRAW ALL DISTURBED GREEN SPACES. ALL PATCH AND REPAIR WORK SHALL BE IN ACCORDANCE WITH BOTH

CIVIL AND LANDSCAPE DRAWINGS AND SPECIFICATIONS.

SCALE:E001 1" = 20'-0"

1 ELECTRICAL SITE PLAN

4/10/26 30% SET

6/30/26 60% SET

8/18/26 90% SET

10/28/26 Permit and Bidding

1 11/25/26 Addendum #1

ADDENDUM 1

J

J

F F

J J

F F

D D

TS

FS

F

FA

C

P

FITNESS

MECHANICAL

TRAINING

WOMEN

PHONE/

ALARM

PHONE/

ALARM

EXISTING

KENNEL

EXSITING

GARAGE

EXSITING

GARAGE

PHONE

MECHANICAL

CORR.

PATROL

ROOM

S-1

EVIDENCE

STORAGE

TRAINING

ELEV

X

ELEV.

EQIP

STORAGE

MEN

60x24

SHELVING

60x24

SHELVING

72x30

TABLE

74x22 METRO

STOR. CREDENZA

60x30

DESK

60x30

DESK

60x30

DESK

60x30

DESK

60x72

DESK

6'-0"

D D

FACP

M

MMM

M

(E)HPA

(E)T-PPF

(E)PPF

UPS-PPD

(E)EMB

(E)EMA

(E)LPA

(E)MDP

(E)T-EMB

(E)T-LPA

(E)PPA

(E)PPB

RADIANT

HEATING

PANELS

RADIANT

HEATING

PANELS

(D)EF-4

P-1

(D)AH-4

CH-2

OVERHEAD

DOOR

OVERHEAD

DOOR

UH-2

(E)EF-11

M

EXISTING

RADIO RACKS

EXISTING

RADIO RACKS

(E)PPE

OVERHEAD

DOOR

(E)G-1

(E)ATS-1

(E)ACU-7

(E)EMD

(E) CT

(D).

ACCU

(E} CU (E) CU

DSW-SERVICE

DSW-GENERATOR

(E)EMC

(E) EM

T-EMD

NOT IN SCOPE

NOT IN SCOPE

(E) B-2

(E)CUH-2-5

(E)B-1

(E) UH

(E)UH

(D) CH-IU

(E)CUH-2-4

E4

E11

E4

E11

(E)UT

OS

OS

(D) AH-1

(D)CP-2

(D)EF-9

E11

(E) UH

M

M

(E) UH

M

(E)P-1 (E)P-2

M

(E) P-3

P-2

UH

MDP-1

PPA-8,10,12

PPA-9,11,13

EMA-15

EMA-15

EMA-29,31,33

MDP-6 E4

E4

E11

E2

(TYP)

E1 DATE DESCRIPTION NO.

906 Monmouth Street, Newport, KY 41071

EmbossDesign.com

(859)431-8612

3222 Terminal Dr.

Hebron, KY 41015

POLICE DEPARTMENT

CINCINNATI/NORTHERN KY

INTERNATIONAL AIRPORT

TH

IS

D O

C U M

EN

T, A N

D T

H E

ID

EA

S A N

D D

ES

IG

N S

IN

C O

R

PO

R A

TE

D H

ER

EI

N , A

S A N

I N

ST

R U M

EN

T

O F

PR

O

FE

SS

IO

N

A L

SE

R V

IC

E, I S

TH

E

PR

O

PE

R

TY

O F

EM

BO

SS

D

ES

IG

N , P

.S .C

A N

D I S

N O

T

TO

B E

U

SE

D I N

W H

O

LE

O R I N

P A R T

FO

R A

N Y

O

TH

ER

P

R O

JE

C T, W

IT

H O

U T

TH

E

W R

IT

TE

N

A U

TH

O R

IZ

A

TI

O N

O F

EM

B O

SS

D

ES

IG

N , P

.S .C

C O

PY

R

IG

H T

-2

5:

E

M B O

SS

D

ES

IG

N , P

.S .C

A

LL

R

IG

H

TS

R

ES

ER

V

ED

151413 161110987654321

A

D

B

C

E

F

G

H

J

K

L

M

15141312 161110987654321

A

D

B

C

E

F

G

H

J

K

L

M

IS

SU

E

P

\P

R -0

C V

G P

O L

IC

E S

T A

T

IO

N \0

-D

R A

W

IN

G S

1100 Sycamore St Suite 400, Cincinnati, OH 45202

Interior Improvements

2023-047

E101

F I R S T F L O O R E L E C T R I C A L D E M O L I T I O N P L A N

SCALE:E101 1/8" = 1'-0"

1 FIRST FLOOR ELECTRICAL DEMOLITION PLAN

TAGGED NOTES

E1 REPLACE EXISTING WATER-DAMAGED LIGHT FIXTURE WITH NEW

REPLACEMENT FIXTURE. THIS IS INTENDED TO BE A 1-FOR-1

REPLACEMENT AND RECONNECTED TO THE SAME CIRCUIT AND

CONTROL. THIS IS TO BE COORDINATED WITH THE CEILING

REPLACEMENT WITHIN THE AREA.

E2 EXISTING HVAC EQUIPMENT ALONG WITH BRANCH CIRCUIT TO

REMAIN. CONTRACTOR SHALL FIELD VERIFY EXISTING LOAD, PANEL,

AND CIRCUIT BREAKER.

E4 DISCONNECT EXISTING HVAC EQUIPMENT SCHEDULED FOR

DEMOLITION. CONTRACTOR SHALL FIELD VERIFY EXISTING LOAD,

PANEL, AND CIRCUIT BREAKER. REMOVE WIRING BACK TO SERVING

PANEL.

E11 DISCONNECT EXISTING HVAC EQUIPMENT SCHEDULED FOR

DEMOLITION. CONTRACTOR SHALL FIELD VERIFY EXISTING LOAD,

PANEL, AND CIRCUIT BREAKER. RETAIN EXISTING ELECTRICAL

CONNECTIONS FOR NEW EQUIPMENT INSTALLED IN THE SAME

LOCATION.

ELECTRICAL DEMOLITION NOTES:

A. DOTTED LINES INDICATE ITEMS FOR REMOVAL (UON) AND THIN SOLID LINES INDICATE EXISTING ITEMS TO REMAIN.

B. THE CONTRACTOR SHALL MAINTAIN THE CONTINUITY OF EXISTING CIRCUITS THAT CONTAIN DEVICES OR EQUIPMENT THAT ARE TO REMAIN. WHEN DEMOLITION OF AN

ELECTRICAL DEVICE (OR CIRCUIT) IS INDICATED ON THE DRAWINGS: THE CONTRACTOR SHALL ENSURE THAT OTHER DEVICES OR EQUIPMENT "UPSTREAM" OR "DOWNSTREAM" ON THE CIRCUITS SHALL REMAIN IN "PRE- DEMOLITION" WORKING ORDER. "LEFT-OVER" CIRCUIT BREAKERS SHALL REMAIN, BE SWITCHED TO OFF POSITION, AND BE LABELED AS SPARES IN THEIR PANELS. PROVIDE NEW TYPEWRITTEN DIRECTORIES FOR ALL PANELS AFFECTED.

C. LOCATIONS OF DEVICES, CONNECTIONS, ETC., INDICATED ON THIS DRAWING WERE TAKEN FROM VARIOUS SOURCES. THEY ARE DIAGRAMMATIC ONLY AND ARE SUBJECT TO VARIATION FROM EXISTING CONDITIONS. CERTAIN EXISTING ELEMENTS MAY NOT BE INDICATED AT ALL. THE CONTRACTOR PROPOSING TO DO ANY PART OF THE WORK INDICATED HEREON SHALL VISIT THIS SITE AND DETERMINE TO HIS SATISFACTION THAT THEY MAY COMPLETE ALL WORK REQUIRED FOR THE BID WHICH HE PROPOSES.

D. REMOVE ALL ASSOCIATED BACKBOXES, CONDUIT AND CONDUCTORS FOR DEVICES / FIXTURES / ETC. BEING REMOVED (BACK TO SOURCE), WHETHER INDICATED OR NOT (UON). CONTRACTOR SHALL PATCH AND REPAIR ANY EXISTING WALLS, FLOORS OR CEILINGS WHERE DEVICES ARE SHOWN TO BE REMOVED (PATCH AND REPAIR TO

RECEIVE NEW FINISHES - SEE ARCHITECTURAL PLANS).

E. COORDINATE DISPOSAL OF ALL FIXTURES, DEVICES, ETC. (INDICATED FOR DEMOLITION) WITH OWNER. TURN OVER ITEMS REMOVED TO OWNER AT THEIR OPTION.

F. COORDINATE WITH OTHER TRADES FOR THE REMOVAL AND/OR RELOCATION OF ELECTRICAL DEVICES AND CONNECTIONS ASSOCIATED WITH THEIR EQUIPMENT.

G. PROVIDE TEMPORARY EMERGENCY EXIT LIGHTS AT CONSTRUCTION BARRIERS AS REQUIRED.

H. CONTRACTOR SHALL PATCH AND REPAIR ALL EXISTING WALLS / CEILINGS AS REQUIRED WHERE DEVICES ARE BEING REMOVED OR INSTALLED.

I. UNUSED/ABANDONED CONDUCTORS DISCOVERED ABOVE ACCESSIBLE CEILINGS SHALL BE REMOVED IN ACCORDANCE WITH NEC REQUIREMENTS.

J. EXISTING ELECTRICAL SYSTEMS IN CONFLICT WITH CONSTRUCTION SHALL BE RELOCATED TO PERMIT INSTALLATION OF DEVICES AND EQUIPMENT SHOWN ON PLANS.

K. CONTRACTOR SHALL SEAL ALL EXISTING AND NEW PENETRATIONS OF BUILDING ENVELOPE (EXTERIOR WALLS, ROOF, ETC.) WATER-TIGHT AND AS APPROVED BY

ARCHITECT AND ENGINEER. ROOFING SHALL BE RESTORED BY A LICENSED ROOFING CONTRACTOR BASED ON WRITTEN INSTRUCTIONS AND DETAILS FROM ROOFING MANUFACTURER AS REQUIRED TO MAINTAIN ROOF WARRANTY. REFER TO ARCHITECTURAL AND ENGINEERING PLANS AND SPECIFICATIONS FOR FURTHER

REQUIREMENTS.

L. DEVICES INDICATED WITH AN ''R'' SHALL BE RELOCATED. REMOVE, PROTECT, AND REINSTALL IN NEW LOCATION INDICATED ON NEW WORK PLANS. INTERCEPT AND EXTEND ALL EXISTING CABLING TO NEW LOCATION. CLEAN AND RE-LAMP RELOCATED LUMINAIRES.

M. ALL EXISTING PANELS AFFECTED BY THIS CONTRACTOR'S WORK SHALL BE PROVIDED WITH NEW TYPE-WRITTEN PANEL DIRECTORIES AND INSERT SLEEVES. PANEL DIRECTORIES SHALL NOT USE ROOM NAMES OR NUMBERS FROM THESE DRAWINGS. DIRECTORIES SHALL BE DETAILED AND COORDINATED WITH OWNER'S SUITE NUMBERS, FINAL ROOM NUMBERS, IT RACK NAMES, WORKSTATION DESIGNATIONS, ETC. UNUSED BREAKERS SHALL BE IN OFF POSITION.

4/10/26 30% SET

6/30/26 60% SET

8/18/26 90% SET

10/28/26 Permit and Bidding

GENERATOR

FITNESS

MECHANICAL

MECHANICAL

TRAINING

WOMEN

PHONE/

ALARM

PHONE/

ALARM

EXISTING

KENNEL

EXSITING

GARAGE

EXSITING

GARAGE

PHONE

MECHANICAL

CORR.

PATROL

ROOM

S-1

EVIDENCE

STORAGE

TRAINING

ELEV

X

ELEV.

EQIP

STORAGE

MEN

60x24

SHELVING

60x24

SHELVING

72x30

TABLE

74x22 METRO

STOR. CREDENZA

60x30

DESK

60x30

DESK

60x30

DESK

60x30

DESK

60x72

DESK

6'-0"

NOT IN SCOPE

NOT IN SCOPE

(TYP)

E1

E9

OS

OS

D4S

D4S

D4S D4S

F22F22

F22

F22

F22

F24CV

CV

CV

F24

F24

D4

D4

F24

F24

F24 F24

F24

F24 F24 F24

F24 F24 F24

F24

F24

F24

F24 F24

F24 F24

F24 F24

F24

D4S

(TYP)

E16

(TYP)

E17

(TYP)

E16

(TYP)

E17

(TYP)

E16

(TYP)

E17

6' - 8"

6' - 8" NL

NL

NL

NL

NL

NL

F24

F24

NL

E24

DATE DESCRIPTION NO.

906 Monmouth Street, Newport, KY 41071

EmbossDesign.com

(859)431-8612

3222 Terminal Dr.

Hebron, KY 41015

POLICE DEPARTMENT

CINCINNATI/NORTHERN KY

INTERNATIONAL AIRPORT

TH

IS

D O

C U M

EN

T, A N

D T

H E

ID

EA

S A N

D D

ES

IG

N S

IN

C O

R

PO

R A

TE

D H

ER

EI

N , A

S A N

I N

ST

R U M

EN

T

O F

PR

O

FE

SS

IO

N

A L

SE

R V

IC

E, I S

TH

E

PR

O

PE

R

TY

O F

EM

BO

SS

D

ES

IG

N , P

.S .C

A N

D I S

N O

T

TO

B E

U

SE

D I N

W H

O

LE

O R I N

P A R T

FO

R A

N Y

O

TH

ER

P

R O

JE

C T, W

IT

H O

U T

TH

E

W R

IT

TE

N

A U

TH

O R

IZ

A

TI

O N

O F

EM

B O

SS

D

ES

IG

N , P

.S .C

C O

PY

R

IG

H T

-2

5:

E

M B O

SS

D

ES

IG

N , P

.S .C

A

LL

R

IG

H

TS

R

ES

ER

V

ED

151413 161110987654321

A

D

B

C

E

F

G

H

J

K

L

M

15141312 161110987654321

A

D

B

C

E

F

G

H

J

K

L

M

IS

SU

E

P

\P

R -0

C V

G P

O L

IC

E S

T A

T

IO

N \0

-D

R A

W

IN

G S

1100 Sycamore St Suite 400, Cincinnati, OH 45202

Interior Improvements

2023-047

E201

F I R S T F L O O R E L E C T R I C A L L I G H T I N G P L A N

SCALE:E201 1/8" = 1'-0"

1 FIRST FLOOR ELECTRICAL LIGHTING PLAN

TAGGED NOTES

E1 REPLACE EXISTING WATER-DAMAGED LIGHT FIXTURE WITH NEW

REPLACEMENT FIXTURE. THIS IS INTENDED TO BE A 1-FOR-1

REPLACEMENT AND RECONNECTED TO THE SAME CIRCUIT AND

CONTROL. THIS IS TO BE COORDINATED WITH THE CEILING

REPLACEMENT WITHIN THE AREA.

E9 PROVIDE NEW LIGHT FIXTURE WITHIN AREA. EXISTING LIGHT FIXTURE

WAS REMOVED AND NEVER REPLACED. WIRE TO CIRCUIT WITHIN THE

AREA.

E16 WHILE CEILING IS UNINSTALLED AND MORE ACCESSIBLE TO

EQUIPMENT AND WIRING ABOVE, CONTRACTOR TO CLEAN UP AND

RESECURE WITH J-HOOKS AND HANGERS ALL WIRING AND CONDUIT

AS NECESSARY. CONTRACTOR TO CARRY AN ALLOWANCE OF $25,000

FOR THIS SCOPE OF WORK AS IT IS UNKNOWN THE FULL EXTEND OF

THE WORK INVOLVED.

E17 ELECTRICAL CONTRACTOR TO COORDINATE THE PHASING OF THIS

WORK WITH THE MECHANICAL CONTRACTOR. REFER TO THEIR

PHASING PLANS.

E24 INSTALL NEW 2-ZONE DIMMABLE LIGHTING CONTROL IN THIS ROOM.

ENSURE NEW LIGHTING CONTROL WORKS WITH EXISTING LIGHTING

AND PROVIDE A STAND-ALONE SYSTEM.

GENERAL NOTES (LIGHTING):

A. REFER TO THE ARCHITECT'S REFLECTED CEILING PLANS, ELEVATIONS, AND CASEWORK DETAILS FOR EXACT LOCATIONS OF ALL WALL AND CEILING MOUNTED ELECTRICAL

DEVICES.

B. CONTRACTOR SHALL FOLLOW BRANCH CIRCUITING LAY-OUT, AS INDICATED ON THE FLOOR PLANS, WITH A MAXIMUM OF THREE (3) BRANCH CIRCUITS PER

HOMERUN. EACH BRANCH CIRCUIT SHALL BE PROVIDED WITH A DEDICATED NEUTRAL CONDUCTOR. DEDICATED NEUTRAL CONDUCTORS SHALL BE CONSIDERED CURRENT CARRYING. IF ADDITIONAL CONDUCTORS ARE RAN IN THE SAME CONDUIT WITH THOSE INDICATED, CONTRACTOR SHALL DERATE ALL CURRENT CARRYING CONDUCTORS PER N.E.C. #310.15(B)(3), AND UPSIZE CONDUIT AS REQUIRED PER N.E.C. #300.17 AND ANNEX C. MULTIWIRE BRANCH CIRCUITS AS DEFINED IN N.E.C #100 /

210.4 (CIRCUITS SHARING A COMMON NEUTRAL CONDUCTOR) SHALL NOT BE PERMITTED.

C. IDENTIFY THE PANEL AND CIRCUIT NUMBER FOR ALL RECEPTACLES, SWITCHES, ETC. IN AREA OF CONSTRUCTION. PROVIDE CLEAR ADHESIVE LABELS WITH BLACK

LETTERING.

D. LOCATE EXIT SIGNS FOR MAXIMUM VIEWING AREA TO IDENTIFY EGRESS PATHS AS INDICATED ON PLANS. COORDINATE LOCATIONS SUCH THAT ARCHITECTURAL FEATURES

OR EQUIPMENT FROM OTHER TRADES DO NOT OBSTRUCT VIEW.

E. WHERE EXIT SIGNS OR EMERGENCY BATTERY PACKS ARE PROVIDED, THEY SHALL BE CONNECTED TO AN UNSWITCHED LINE.

F. ALL LIGHTING FIXTURE LENSES AND DOWNLIGHTING ALZAK CONES SHALL BE HANDLED WITH COTTON GLOVES DURING INSTALLATION AND LAMPING TO AVOID

FINGERPRINTS OR DIRT DEPOSITS. IT IS PREFERRED THAT FIXTURES BE SHIPPED AND INSTALLED WITH CLEAR PLASTIC BAGS TO PROTECT LOUVERS. AT CLOSE OF PROJECT, AND AFTER CONSTRUCTION AIR FILTERS ARE CHANGED, REMOVE BAGS. ANY LOUVER OR CONE SHOWING DIRT OR FINGER PRINTS SHALL BE CLEANED WITH SOLVENT RECOMMENDED BY THE MANUFACTURER, OR REPLACED AS NECESSARY IN ORDER TO TURN OVER TO THE OWNER NEW FIXTURES AT OCCUPANCY.

G. RECESSED LUMINAIRES SHALL BE SECURED SUCH THAT THE FORCE REQUIRED INSERTING LAMPS, TRIMS, LENSES, LOUVERS, OR DOOR FRAMES DOES NOT SHIFT HOUSING. ALL TRIMS SHALL BE COMPLETELY FLUSH WITH FINISHED CEILINGS AT COMPLETION OF CONSTRUCTION.

H. CONTRACTOR SHALL PROVIDE UNSWITCHED CONDUCTOR TO ALL EXIT SIGNS, EMERGENCY INVERTER BATTERY PACKS, AND NIGHT LIGHTS AS REQUIRED.

4/10/26 30% SET

6/30/26 60% SET

8/18/26 90% SET

10/28/26 Permit and Bidding

F F

J J

F F

TS

FS

F

FA

C

P

FITNESS

MECHANICAL

TRAINING

PHONE/

ALARM

PHONE/

ALARM

EXISTING

KENNEL

EXSITING

GARAGE

EXSITING

GARAGE

PHONE

MECHANICAL

CORR.

PATROL

ROOM

EXISTING

STAIR

S-1

EVIDENCE

STORAGE

TRAINING

ELEV

X

ELEV.

EQIP

CORRIDOR

STORAGE

MEN

60x24

SHELVING

60x24

SHELVING

72x30

TABLE

74x22 METRO

STOR. CREDENZA

CHARGING

CART/CABINET

60x30

DESK

60x30

DESK

60x30

DESK

60x30

DESK

60x72

DESK

6'-0"

DD

DD

DD

DD

J

J

FACP

PHONE/

ALARM

CORRIDOR

T

(E)PPB

(E)G-1

(E)PPE

(E)CUH-2-4

VAV-5 VAV-15

VAV-17

VAV-16

VAV-4

(E} CU (E) CU

VAV-3

(E) B-2

(E)EF-11

(E)B-1

WH

(E)CUH-2-5M

M

M

M

M

M

M

M

FCU-1

FCU-2 ERV-1

FCU-3

AH-4

VAV-21

VAV-22

M

M

NOT IN SCOPE

NOT IN SCOPE

M

M

M

M

(E)UT

CH-1

E301

(E)ACU-7

(TYP)

E3

-26,28,30HPA

E10

-1MDP

-38,40,42HPA

E10

HPB

-21,23,25PPA

-19,21,23HPB

-8,10,12HPA

-27HPA

-16PPA

-18PPA

-29HPA

-36HPA

EF-12

EF-9

RCP-1

CP-2

CP-1

EF-10

M

M M

M

(E)P-1

(E)P-2

(E) UH

AH-1

M

(E) UH

RCP-2

(E) P-3

AH-1 RETURN

AH-1 SUPPLY

AH-4 SUPPLY

AH-4 RETURN

M

MOTOR DAMPER

MOTOR DAMPERM

LPA-7

LPA-13

-31LPA

-33LPA

E18

E19

E20

E20

2D

2D

2D

4D

4D

2D

-35LPA

UH

-8,10,12PPA

E10

E10

-9,11,13PPA

-2,4,6EMA

-36PPB

M

-35PPB

-37PPB

-38PPB

-39PPB

-34LPA

-40PPB

NEMA 3R,

125AT/200AF

30AF/NF

30AF/NF

M

M

E22

E22

WP

-5PPF

E25

(E)PPA(E) EM

(E) CT

(E)MDP

(E)LPA

(E)T-LPA

(E)EMA

(E)T-EMB

(E)EMC

(E)EMD

(E)T-EMD

(E)EMB

(E)HPA

(E)ATS-1

(E)T-PPF

(E)UPS-PPD

HPB

(E)PPF

DATE DESCRIPTION NO.

906 Monmouth Street, Newport, KY 41071

EmbossDesign.com

(859)431-8612

3222 Terminal Dr.

Hebron, KY 41015

POLICE DEPARTMENT

CINCINNATI/NORTHERN KY

INTERNATIONAL AIRPORT

TH

IS

D O

C U M

EN

T, A N

D T

H E

ID

EA

S A N

D D

ES

IG

N S

IN

C O

R

PO

R A

TE

D H

ER

EI

N , A

S A N

I N

ST

R U M

EN

T

O F

PR

O

FE

SS

IO

N

A L

SE

R V

IC

E, I S

TH

E

PR

O

PE

R

TY

O F

EM

BO

SS

D

ES

IG

N , P

.S .C

A N

D I S

N O

T

TO

B E

U

SE

D I N

W H

O

LE

O R I N

P A R T

FO

R A

N Y

O

TH

ER

P

R O

JE

C T, W

IT

H O

U T

TH

E

W R

IT

TE

N

A U

TH

O R

IZ

A

TI

O N

O F

EM

B O

SS

D

ES

IG

N , P

.S .C

C O

PY

R

IG

H T

-2

5:

E

M B O

SS

D

ES

IG

N , P

.S .C

A

LL

R

IG

H

TS

R

ES

ER

V

ED

151413 161110987654321

A

D

B

C

E

F

G

H

J

K

L

M

15141312 161110987654321

A

D

B

C

E

F

G

H

J

K

L

M

IS

SU

E

P

\P

R -0

C V

G P

O L

IC

E S

T A

T

IO

N \0

-D

R A

W

IN

G S

1100 Sycamore St Suite 400, Cincinnati, OH 45202

Interior Improvements

2023-047

E301

F I R S T F L O O R E L E C T R I C A L P O W E R P L A N

SCALE:E301 1/8" = 1'-0"

1 FIRST FLOOR ELECTRICAL POWER PLAN

TAGGED NOTES

E3 PROVIDE NEW POWER FEED TO NEW VAV WITH REHEAT.

E10 WIRE NEW HVAC EQUIPMENT TO EXISTING CIRCUIT MADE AVAILABLE

DURING DEMOLITION.

E18 CONTRACTOR TO PROVIDE AND INSTALL CHARGING CABINET FOR

BODYCAM CHARGERS. THIS WILL BE COMPRISED OF 6 DOCKING

STATIONS (8 PORTS PER STATION). BOD: CABINET IS A 19" WALL

MOUNT L-SHAPED RACK, 12" DEEP. COORDINATE WITH CVG PRIOR TO

ORDERING AND INSTALLATION.

E19 CONTRACTOR TO PROVIDE AND INSTALL IT RACK ABOVE CHARGING

CABINET. COORDINATE WITH CVG PRIOR TO ORDERING AND

INSTALLATION.

E20 EXTEND EXISTING CIRCUIT SERVING ROOM. EXTEND WIRING AS

NECESSARY.

E22 PROVIDE DUCT DETECTOR ON SUPPLY AND RETURN OF AIR HANDLING

UNIT. PROVIDE ALL WIRING TO SHUTDOWN UNIT WHEN SMOKE IS

DETECTED. COORDINATE LOCATION WITH MECHANICAL CONTRACTOR.

E25 CONTRACTOR TO COORDINATE FINAL LOCATION OF PANEL IN THE

FIELD. THE OLD HVAC CONTROLS CABINET CAN BE REMOVED AND

REWORK OF THE FACP AND POWER SUPPLY MAY NEED TO BE

SHIFTED. CVG IS COORDINATING TO REMOVE THE SECTION OF THE IT

RACK THAT IS IN THE WAY OF THE PANEL CLEARANCE.

GENERAL NOTES (POWER):

A. REFER TO THE ARCHITECT'S REFLECTED CEILING PLANS, ELEVATIONS, AND CASEWORK DETAILS FOR EXACT LOCATIONS OF ALL WALL AND CEILING MOUNTED ELECTRICAL

DEVICES.

B. CONTRACTOR SHALL FOLLOW BRANCH CIRCUITING LAY-OUT, AS INDICATED ON THE FLOOR PLANS, WITH A MAXIMUM OF THREE (3) BRANCH CIRCUITS PER HOMERUN. EACH

BRANCH CIRCUIT SHALL BE PROVIDED WITH A DEDICATED NEUTRAL CONDUCTOR. DEDICATED NEUTRAL CONDUCTORS SHALL BE CONSIDERED CURRENT CARRYING. IF ADDITIONAL CONDUCTORS ARE RAN IN THE SAME CONDUIT WITH THOSE INDICATED, CONTRACTOR SHALL DERATE ALL CURRENT CARRYING CONDUCTORS PER NEC 310.15(B) (3), AND UPSIZE CONDUIT AS REQUIRED PER NEC 300.17 AND ANNEX C. MULTIWIRE BRANCH CIRCUITS AS DEFINED IN NEC 100 / 210.4 (CIRCUITS SHARING A COMMON NEUTRAL

CONDUCTOR) SHALL NOT BE PERMITTED.

C. IDENTIFY THE PANEL AND CIRCUIT NUMBER FOR ALL RECEPTACLES, SWITCHES, ETC. IN AREA OF CONSTRUCTION. PROVIDE CLEAR ADHESIVE LABELS WITH BLACK LETTERING.

D. LOCATIONS OF ELECTRICAL CONNECTIONS AND LOCAL DISCONNECTS SHALL BE COORDINATED WITH MECHANICAL AND PLUMBING CONTRACTORS TO ENSURE ACCESS AND

WORKING CLEARANCE IS MAINTAINED PER NEC. NOTIFY OTHER TRADES OF REQUIRED CLEARANCE AREAS TO AVOID ROUTING OF OTHER SYSTEMS IN THESE AREAS. DO NOT INSTALL ELECTRICAL EQUIPMENT OVER EQUIPMENT NAMEPLATES OR ACCESS PANELS OR THROUGH ACCESS/MAINTENANCE CLEARANCES OF EQUIPMENT BY OTHER TRADES.

SCALE:E301 1/4" = 1'-0"

2 ENLARGED ELECTRICAL ROOM

4/10/26 30% SET

6/30/26 60% SET

8/18/26 90% SET

10/28/26 Permit and Bidding