RFIs Elwood IL combined.pdf

PDF 165 KB Posted

Attached to
Elwood, Il - Fence Replacement and Lighting (JOL) ARSR in Elwood, IL
Solicitation number
25-21003734
Issued by

About this file

This document is a Request for Information (RFI) for a Federal Aviation Administration (FAA) project in Elwood, IL involving fence replacement and lighting upgrades. The solicitation (SIR # 25-21003734) seeks a small business contractor to replace a security fence and upgrade lighting at a facility, with a total project scope including 42 light fixture replacements, new fence installation with specific post spacing (10 feet maximum) and foundation depth requirements (5.5 feet for corner/terminal posts, 4 feet for others), and manual gate operation. The project is estimated to be between $100,000-$250,000, with a projected completion timeframe of 31 days from notice to proceed.

Key submission details include a quote deadline of March 19, 2025, at 5:00 p.m. CST, with mandatory requirements such as SAM.gov registration, Davis-Bacon Act compliance, and submission of a schedule of values. The contract will be a firm-fixed-price type, set aside for small businesses under NAICS code 236220. Contractors must perform at least 51% of the work with their own organization, and bids exceeding $150,000 will require payment and performance bonds. The RFI provides detailed technical specifications and clarifications about electrical, grounding, and construction requirements for potential bidders.

View the file

Other files

Show all 12

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Elwood, IL RFIs

1. Can you please identify what the required spacing is for the Ground Rods ?

Ground spacing should be no greater than 100 feet, spacing to vary 10 to 20%

Do we go by Drawings , Specs. or The FAA Grounding and Bonding Standard, which standard?

Drawings, Specs and FAA standard should all agree, if you notice any conflict, point it out and we will clarify accordingly. The FAA standard for grounding and bonding is FAA-STD-19G.

The current Standard now or the one identified with the specification?

FAA-STD-19G is the latest edition

What prevails for this requirement of work?

Specifications prevails (typical)

2. There are references in various spec. sections that the C.O.'s approval is required for all Submittals?

Are all Submittals required to be only sent to the C.O.?

When sending submittals, please CC the CO on the email.

3. Spec. Section 01 33 00, 3.1 identifies multiple hard copies of submittals are to be submitted? Or do we send one copy electronically?

Unless specifically specified, electronic copies are acceptable. For this project in particular, construction red-lines and third-party ground penetrating radar report survey report before trenching should be the only ones where hard copies are required.

4. Spec. Section 26 05 26, 2.2, C - Please confirm every Ground Rod is to have a Access Well or a specific quantity?

No, the security fence grounding will not require a ground access well. There is zero new ground access wells for this project.

Spec. Section 26 05 26, 1.1 , A-D - references grounding of equipment, however none is shown on the drawings?

This is mainly for lighting portion of the project, when lighting fixtures are being grounded. Note:

each specification section is only applicable to the extent of scope of work for the project, otherwise, disregard.

Spec. Section 26 05 26 - Is a new EES required to be installed at the fence?

No, the scope of work does not call for a new EES. The only ground rods to be interconnected by 4/0 AWG bare copper are the ones across the gate posts.

Spec. Section 26 05 26 - Is a new EES required to be installed around the existing Buildings?

No

5. Spec. Section 26 05 33 - Specifies Raceways and Boxes. Under this contract are we required to replace these or are we only to remove and replace Lite Fixtures only?

The scope of work is to replace existing lighting fixtures with new, using existing wiring and conduits unless the letter are damaged during construction activities or violate NEC.

6. Spec. Section 26 05 53 - This spec. section is not applicable to this project I assume?

It is very much applicable as we expect the installer to verify wiring being disconnected and reconnected from demolished light fixtures to new LED lighting.

7. Spec. Section 26 08 00 - Specifies a testing service to be required to make sure our new lite fixtures turn off and on after their replaced by the Electrician, is this for sure required?

Yes

8. Spec. Section 26 27 26 - Are we required to replace these items or are we only to remove and replace Lite Fixtures?

In this case, specifications are referring to the light fixtures along with their accessories wiring.

9. What are the exact post spacing and foundation depth requirements?

Maximum post spacing for the fence is 10 feet

Foundation depth requirements is 5.5 feet for corner and terminal posts and 4 feet for others

10. Will the rolling gate require electrical provisions?

No, the gate will be manually operated only.

Lighting Replacement:

11. How many fixtures need replacement?

Total number of light fixtures to be replaced is 42 around the facility

12. Will the existing wiring support the new LED lights, or is rewiring needed?

No new wiring needed, existing wiring should be able to support the new LED light fixtures.

13. Do we need to perform nighttime testing to verify lighting coverage?

Not necessarily, Although, installed lights will be tested for proper functionality

14. What are the insurance requirements for the Subs and Prime Contractor?

If your bid exceeds $150,000 you will need to supply payment and performance bonds if you are awarded the contract. Certificate of Insurance will be required.

15. Since there is an existing fence that needs to be replaced, is a soil test required?

it is not

16. During Fence Demo, Can we leave existing concrete footings and remove post, corner posts and gate posts flush to grade and pour soil to save time and money.

the demolition of the old fence includes footings as well.

17. Can you please provide building blueprints?

Design drawings and pre-bid site survey provides enough information to accurately estimate work to be done. There is specific information you need, please let us know, we will provide it.

18. Does contractor need to furnish temporary fence during construction of new fence or demo of old fence ?

No, they do not have to.

19. Electrical suppliers informed us that Lithonia specs given for EPANL are being phased out and will not be under warranty, can we provide their replacement equivalents?

Yes, all material specified are for design purpose only, when awarded you are welcome to submit materials for review and the FAA will approve accordingly.

20. Some Acoustical Ceiling Tiles are missing in areas of lighting and Exit sign replacements, is contractor expected to replace or install new ACT Tiles in facility? if so can you please provide specs Missing tiles, and under sized tiles are very few and are covered under miscellaneous items. They do not constitute a significant portion of the scope of work. And yes, the contractor is expected to replace those missing few and undersized ones.

21. Referring to existing site layout plan page, KEY NOTES 1 states that the contractor has to move the new rolling gate 5 (five) feet from the original location TOWARDS the facility to increase entry delivery truck turning radius.

21a. We are interpreting this as to move/install new gate 5 feet back / behinds original position. If this is the case, there are existing Cement Bollards on both sides of the entryway 3-5 Feet behind the gate. In this case do you want the contractor to remove the ballasts that are in the way of installing the new fence? Or do you want to leave existing Bollards and install new gate behind it (if that is the case then it will be approximately 6-8 feet behind original gate location and not 5)?

This is a minor item that can be field adjusted, for the moment, assume you will demolish the bollard out of the way.

22. Is there a solicitation / Proposal / Bid form to fill out or do we just use the excel spreadsheet provided in the attachments in SAM website?

Please submit your bid on company letterhead along with the Schedule of Values spreadsheet.

23. Can we demo the entire fence all at once or do we have to replace the fence section by section?

Yes, you can demo the whole fence all at once

24. Is a site assessment / soil test necessary or can we reuse existing assessment from the installation of first fence?

Existing assessment is acceptable

25. Some testing facilities for concrete pour require 28 plus days to provide results, given that we need to test for every concrete pour we do, it is not feasible to do so within the allotted timeframe to finish the project. In this case will an extension to project be granted?

After review and approval of the mix design, construction can proceed. Testing results will be looked at when they are available and dealt accordingly.

26. Can we reuse existing grounding system such as #6 awg spanning perimeter of existing fence and gate as well as ground rods already in place and bonded?

No, the new fence is to have new grounding components.