2508 LCSS Canopy Repair_V2 WP_FEB2026.pdf
PDF 2 MB Posted
- Attached to
- LCSS Canopy Repair RFP2026-18
- Solicitation number
- PE-68910-NONST-2026-000000048
- Issued by
- Lee County, Georgia
About this file
This is a construction document set for the LCSS Canopy Repair project, specifically for Volume II covering Waldo Pafford Elementary School located at 2550 W 15th Street, Hinesville, Georgia 31313. The project involves repair and replacement of existing canopies damaged by wind storms and the provision of canopy lighting at new canopies. The scope of work includes demolition of damaged canopy structures, installation of pre-engineered aluminum canopies with draining columns, new concrete sidewalks and foundations, and electrical lighting installation. The mandatory pre-bid conference is scheduled for March 12, 2026, at 9:00 A.M. at Button Gwinnett Elementary School, with attendance required for all prospective bidders. Bids will be accepted until 10:30 A.M. on March 30, 2026, at the Liberty County School System Board of Education office located at 200 Bradwell Street, Hinesville, Georgia 31313. The project is part of a larger RFP 2026-18 that includes canopy repairs at three elementary schools: Lyman Hall, Waldo Pafford, and Button Gwinnett. The advertising period runs from February 27, 2026, through March 30, 2026.
The construction documents were prepared by Cogdell & Mendrala Architects, PC, with structural engineering by Saussy Engineering and MEP engineering by Method Engineering Group. Design standards comply with the 2024 International Building Code with Georgia amendments and the 2023 National Electrical Code. The project design is based on a maximum allowable soil bearing pressure of 1,500 PSF, with wind loads calculated for a basic wind speed of 140 MPH and seismic design category C. Special structural inspections for concrete construction and soils are required per IBC 2024 Chapter 17. All shop drawings and calculations for pre-engineered canopies must be prepared, signed, and sealed by a professional engineer registered in Georgia. The contractor must coordinate with the canopy manufacturer for proper foundation design, verify existing site conditions, and perform all necessary demolition in accordance with NFPA 241, 2022 Edition. No specific contract pricing, funding sources, or award dates are indicated in the construction documents provided.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
COGDELL & MENDRALA ARCHITECTS, PC
LCSS CANOPY REPAIR
VOL. II - WALDO PAFFORD ELEMENTARY SCHOOL
ARCH. PROJECT NO. 2508
LIBERTY COUNTY SCHOOL SYSTEM
SAUSSY ENGINEERING
ARCHITECTS
OWNER
LIBERTY COUNTY SCHOOL SYSTEM
200 BRADWELL STREET, HINESVILLE, GA 31313
517 E CONGRESS ST. SAVANNAH, GEORGIA, 31401
912.234.6318
CONSULTANTS
400 JOHNNY MERCER BLVD. SUITE E SAVANNAH, GA 31410
912.898.8255
STRUCTURAL ENGINEERSSTRUCTURAL ENGINEERS
MEP ENGINEERSMEP ENGINEERS
SHEET
COPYRIGHT © 2025 COGDELL & MENDRALA ARCHITECTS, PC
METHOD ENGINEERING GROUP
1020 DRAYTON STREET, SUITE 101, SAVANNAH, GA 31401
912.963.1611
FACILITY NO. 689-0100
OWNER PROJECT NUMBER 2026-10
2550 W 15TH ST., HINESVILLE, GA 31313
1/
/2
3:
:3
PM
Au to de sk
D oc s:
//2
LC
SS
C an op y R ep ai r/2
8_
LC
SS
C an op y R ep ai r_ C
EN
TR
AL
.rv t
CONSTRUCTION DOCUMENTS
JANUARY 2026
T1.0
FEBRUARY 2026
517 EAST CONGRESS STREET
SAVANNAH, GEORGIA 31401
tel 912.234.6318 fax 912.236.8414 cogdellmendrala.com
SHEET TITLE
SHEET
KEY PLAN
TRUE NORTH PROJECT NORTHSCALE
COPYRIGHT © 2025 COGDELL & MENDRALA ARCHITECTS, PC
CogdellMendralaArchitects
N.T.S.
SCOPE OF WORK
WALDO PAFFORD
ELEMENTARY SCHOOL
PROJECT NO:
DRAWN BY:
DATE:
SCALE:
OWNER NO:
FACILITY NO.: 689-0100
2550 W 15TH ST, HINESVILLE, GA 31313
SEAL
STRUCTURAL ENGINEERS
SAUSSY ENGINEERINGSAUSSY ENGINEERING
400 JOHNNY MERCER BLVD, SUITE E,
SAVANNAH, GA 31410
M.E.P. ENGINEERS
METHOD ENGINEERING GROUPMETHOD ENGINEERING GROUP
1020 DRAYTON STREET, SUITE 101,
SAVANNAH, GA 31401
1/
/2
3:
:3
PM
Au to de sk
D oc s:
//2
LC
SS
C an op y R ep ai r/2
8_
LC
SS
C an op y R ep ai r_ C
EN
TR
AL
.rv t
G0.01
SHEET LIST
CONSTRUCTION
DOCUMENTS
MAB
JANUARY 2026
2026-10
LCSS CANOPY
REPAIR
LIBERTY COUNTY SCHOOL
SYSTEM
VOLUME II - WALDO
PAFFORD
ELEMENTARY
SCHOOL
VOLUME II SHEET LIST - GENERAL
Sheet
Number Sheet Name REV. DATE REV.
G0.01
SHEET LIST
G0.02
GENERAL PROJECT INFORMATION
VOLUME II SHEET LIST - ARCHITECTURAL
Sheet
Number Sheet Name REV. DATE REV.
A2.01
CANOPY FLOOR PLAN, REFLECTED CEILING PLAN, &
ROOF PLAN
A3.01
EXTERIOR ELEVATIONS
A3.11
BUILDING SECTIONS
A8.41
EXTERIOR DETAILS
VOLUME II SHEET LIST - DEMOLITION
Sheet
Number Sheet Name REV. DATE REV.
D2.01
DEMOLITION - FLOOR PLAN AND ROOF PLAN
REVISION SCHEDULE
NO DATE DESCRIPTION
VOLUME II SHEET LIST - STRUCTURAL
Sheet
Number Sheet Name REV. DATE REV.
S1.01 STRUCTURAL NOTES
A2 �A2 �A2
G
VOLUME II SHEET LIST - ELECTRICAL
Sheet
Number Sheet Name REV. DATE REV.
E1.01 ELECTRICAL PLAN
2026-18
DRAWING
TITLE TITLE OF DRAWING1
A0.1 1/8" = 1'-0"
100A
LOBBY
H100
A0.1 SHEET NO. WHERE
DWG NO.
SHEET NO. WHERE
ELEV. IS DRAWN
SHEET NO. WHERE
DRAWING NO.
SECT. LINESECT. IS DRAWN
SECT. IS DRAWN
DET. IS DRAWN
AREA
AROUND
DASHES
DETAILED
ROOM NAME
ROOM NO.
DOOR NO.
SHEET NO. WHERE
DWG NO.
DWG NO.
DWG NO.
CENTER LINE
DOOR TAG
EXTERIOR WALL TAG
SEE A0.03
MATCH LINE
BREAK LINE
REVISION TAG
DIMENSION
INDICATOR
X.X
16'-0"
BUILDING
SECTION
WALL
SECTION
PLAN OR
SECTION
DETAIL
ROOM TAG
EXTERIOR
ELEVATION
N O R T H
NORTH
ARROW
A0.1
A0.1
SECT. LINE
A0.1
S1
R1
FLOOR TAG
SEE A0.03
A0.1 A0.1
REVISION CLOUD
REVISION NUMBER
ROOF TAG
SEE A0.03
WINDOW TAG
SEE A8.X SERIES
C1
STOREFRONT TAG
SEE A8.X SERIES
CURTAIN WALL TAG
SEE A8.X SERIES
S1
W1
ROOF TYPE
FLOOR TYPE
EXTERIOR
WALL TYPE
VERTICAL HEIGHT
SPOT ELEVATION
MAIN LEVEL PLAN
0' - 0"
0' - 0"
TOILET & BATH
ACCESSORY TAG
TBA-1
KEYNOTE TAG 03 30 00.A CAST-IN-PLACE CONCRETE
SPECIFICATION SECTION
DESCRIPTION OF CONSTRUCTION
COMPONENT
CONSTRUCTION COMPONENT AS
LISTED IN LEGEND
PLAN NOTE TAG REFERS TO CORRESPONDING
NOTES ON SHEET
ELEV. IS DRAWN
SHEET NO. WHERE
DRAWING NO.INTERIOR
ELEVATION
A0.1 A0.1
INTERIOR PARTITION TAG
SEE A0.04
X.X.X INTERIOR
WALL TYPE
X.X
X X
REFERS TO CORRESPONDING
ITEM AS SCHEDULED
AIR CONDITION(ING)
ADMINISTRATION
ABOVE FINISHED FLOOR
ALTERNATE
ALUMINUM
APPROXIMATE(LY)
ARCHITECT(URAL)
AUTOMATIC
AUXILIARY
AUDIOVISUAL
BITUMINOUS
BUILDING LINE
BUILDING
BOTTOM OF STEEL
BOTTOM
CABINET
CONTRACTOR FURNISHED,
CONTRACTOR INSTALLED
CONTROL JOINT
CENTER LINE
CEILING
CEILING HEIGHT
CLOSET
CLEAR(ANCE)
CONCRETE MASONRY UNIT
COLUMN
CONCRETE
CONFERENCE
CONTINUE, CONTINUOUS
CORRIDOR
CUBIC FOOT
CUBIC YARD
DEMOLISH
DEPARTMENT
DETAIL
DRINKING FOUNTAIN
DIAMETER
DIAGONAL
DIMENSION
DIVISION
DOWN SPOUT
EAST
EACH
ELEVATION
ELECTRIC(AL)
ELEVATOR
EXPANSION JOINT
ENCLOSE(D)
EDGE OF SLAB
EQUAL
EQUIPMENT
ELECTRIC WATER COOLER
EXISTING
JT EXPANSION JOINT
EXTERIOR
FLOOR DRAIN
FIRE EXTINGUISHER
FIRE EXTINGUISHER ON
BRACKET
FIRE EXTINGUISHER CABINET
FACE TO FACE
FINISH FLOOR ELEVATION
FIRE HOSE CABINET
FINISHED FLOOR
FLOOR, FILLER
FACE OF CURB
FACE OF FINISH
FACE OF MASONRY
FACE OF SLAB
FACE OF WALL
FOOT, FEET
FOOTING
FURNISH, FURNITURE
GAGE
GALVANIZED
GENERAL CONTRACTOR
GYPSUM BOARD
GYPSUM PLASTER
HANDICAP
HEAVY DUTY
HARDWARE
HARDWOOD
HOLLOW METAL
HORIZONTAL
HEIGHT
HEATING, VENTILATION &
AIR CONDITIONING
INSIDE DIAMETER
INFORMATION
INCLUDE(D), (ING)
INSULATION
INTERIOR
JANITOR CLOSET
KITCHEN
KNOCKOUT
LABORATORY
LAMINATE
LAUNDRY
LAV LAVATORY
LF LINEAR FEET
LVR LOUVER
MAINTENANCE
MATERIAL
MAXIMUM
MECHANICAL
MEZZANINE
MANUFACTURING
MANUFACTURER
MINIMUM
MISCELLANEOUS
MASONRY OPENING
MOISTURE RESISTANT
MOUNTED
MOUNTING
METAL
NORTH
NOT IN CONTRACT
NON-COMBUSTIBLE
NOMINAL
NOT TO SCALE
ON CENTER
OUTSIDE DIAMETER
OWNER FURNISHED,
CONTRACTOR INSTALLED
OWNER FURNISHED, OWNER
INSTALLED
OPTION(AL)
OPPOSITE
POUNDS PER CUBIC FEET
PLASTIC LAMINATE
POUNDS PER LINEAR FOOT
PLYWOOD
PANEL
PAIR
PREFABRICATED
PREFINISH
PARKING
POUNDS PER SQUARE FOOT
POUNDS PER SQUARE INCH
PAINT, POST-TENSIONED,
PRE-TREATED
POLYVINYL CHLORIDE
(PLASTIC)
QUARTER
QUANTITY
RADIUS, RISER
REFLECTED CEILING PLAN,
REINFORCED CONCRETE
PIPE
ROOF DRAIN
REFRIGERATOR, REFERENCE
REQUIRED
ROOF LEADER
ROOM
ROUGH OPENING
RIGHT OF WAY
S SOUTH
SC SOLID CORE
SD STORM DRAIN
SECT SECTION
SF SQUARE FEET
SIM SIMILAR
SPEC SPECIFICATION
SPKR SPEAKER
SQ SQUARE
SS STAINLESS STEEL
STANDARD
STORAGE
SUSPENDED
SYSTEM
TREAD
TELEPHONE
TEMPORARY
TOP OF FINISH FLOOR
THICKNESS
THROUGH
TOP OF BEAM
TOP OF CONCRETE, TOP OF CURB
TOP OF FOOTING
TOP OF JOIST
TOP OF MASONRY
TOP OF PARAPET
TOS TOP OF SLAB
TOW TOP OF WALL
TREATED
TELEVISION
TYPICAL
UNDERWRITERS LABORATORIES
UNLESS NOTED OTHERWISE
VERTICAL
VESTIBULE
VERIFY IN FIELD
WEST, WIDE
WITH
WITHOUT
WATER CLOSET
WOOD
WORKING POINT, WATERPROOFING
WATER REPELLENT
WEIGHT
WALL TO WALL
WELDED WIRE FABRIC
YARD
A/C
ADMIN
AFF
ALT
ALUM
APPROX
ARCH
AUTO
AUX
AV
BITUM
BL
BLDG
BOS
BOT
CAB
CFCI
CJ
CL
CLG
CLG HT
CLO
CLR
CMU
COL
CONC
CONF
CONT
CORR
CU FT
CU YD
DEMO
DEPT
DET
DF
DIA
DIAG
DIM
DIV
DS
E
EA
EL
ELEC
ELEV
EJ
ENCL
EOS
EQ
EQUIP
EWC
EXIST
EXP JT
EXT
FD
FE
FEB
FEC
F/F
FF EL
FHC
FIN FLR
FLR
FOC
FOF
FOM
FOS
FOW
FT
FTG
FURN
GA
GALV
GC
GYP BD
GYP PLAS
HC
HD
HDWR
HDWD
HM
HORIZ
HT
HVAC
ID
INFO
INCL
INSUL
INT
JAN CLO
KIT
KO
LAB
LAM
LAU
LAV
LF
LVR
MAINT
MATL
MAX
MECH
MEZZ
MFG
MFR
MIN
MISC
MO
MR
MTD
MTG
MTL
N
NIC
NON
NOM
NTS
OC
OD
OFCI
OFOI
OPT
OPP
PCF
PLAM
PLF
PLYWD
PNL
PR
PREFAB
PREFIN
PRKG
PSF
PSI
PT
PVC
QTR
QTY
R
RCP
RD
REF
REQD
RL
RM
RO
ROW
S
SC
SD
SECT
SF
SIM
SPEC
SPKR
SQ
SS
STD
STOR
SUSP
SYS
T
TEL
TEMP
TFF
THK
THRU
TOB
TOC
TOF
TOJ
TOM
TOP
TOS
TOW
TRTD
TV
TYP
UL
UNO
VERT
VEST
VIF
W W/ W/O
WC
WD
WP
WR
WT
W/W
WWF
YD
EARTH/COMPACT FILL
POROUS FILL
CONCRETE
SAND, GYPSUM BOARD
MORTAR, PLASTER
CONCRETE MASONRY
ROUGH WOOD
WOOD BLOCKING
ASPHALT FILL
PLAN LEGEND
SECTION
BATT INSULATION
RIGID INSULATION
BRICK VENEER
STEEL/OTHER METALS
PLYWOOD
GYPSUM BOARD
ACOUSTICAL CLG. TILE
FINISH WOOD
EXISTING BUILDING
FOOTPRINT
ASPHALT
METAL STUD
PARTITION
CONCRETE MASONRY
PARTITION
EXISTING
CONSTRUCTION
CONSTRUCTION TO BE
REMOVED
PROJECT SCOPE AT WALDO PAFFORD ELEMENTARY SCHOOL CONSISTS OF
REPAIR/REPLACEMENT OF EXISTING CANOPIES THAT WERE DAMAGED BY
WIND STORMS, AND PROVIDING CANOPY LIGHTING AT NEW CANOPIES.
TYPICAL SLAB ON GRADE CONSTRUCTION
F103 30 00.BCAST-IN-PLACE CONCRETE SEE
STRUCT.
03 30 00.GWELDED WIRE MESH SEE STRUCT.
90% COMPACTED SUBGRADE
PROPERTY ADDRESS: WALDO PAFFORD
ELEMENTARY SCHOOL
2550 W 15TH ST.
HINESVILLE, GA 31313
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
APPLICABLE BUILDING CODES WITH GEORGIA AMENDMENTS:
(LIST IS NOT INCLUSIVE)
INTERNATIONAL BUILDING CODE, 2024 EDITION, WITH GEORGIA
AMENDMENTS (2026)
INTERNATIONAL FIRE CODE, 2024 EDITION, WITH GEORGIA
AMENDMENTS (2025)
INTERNATIONAL PLUMBING CODE, 2024 EDITION, WITH GEORGIA
AMENDMENTS (2026)
INTERNATIONAL MECHANICAL CODE, 2024 EDITION, WITH
GEORGIA AMENDMENTS (2026)
INTERNATIONAL FUEL GAS CODE, 2024 EDITION, WITH GEORGIA
AMENDMENTS (2026)
NATIONAL ELECTRICAL CODE, 2023 EDITION AND AMENDMENTS
(2026)
INTERNATIONAL ENERGY CONSERVATION CODE, 2015 EDITION,
WITH GEORGIA SUPPLEMENTS AND AMENDMENTS (2020), (2022),
(2023)
LIFE SAFETY CODE, NFPA 101, 2024 EDITION WITH GEORGIA
AMENDMENTS
NFPA 72 NATIONAL FIRE ALARM & SIGNALING CODE (2022) WITH
GA AMENDMENTS
NFPA 13 (2019) WITH GEORGIA AMENDMENTS (2020)
DOJ 2010 ADA STANDARDS FOR ACCESSIBLE DESIGN, WITH
GEORGIA ACCESSIBILITY CODE 120-3-20
517 EAST CONGRESS STREET
SAVANNAH, GEORGIA 31401
tel 912.234.6318 fax 912.236.8414 cogdellmendrala.com
SHEET TITLE
SHEET
KEY PLAN
TRUE NORTH PROJECT NORTHSCALE
COPYRIGHT © 2025 COGDELL & MENDRALA ARCHITECTS, PC
CogdellMendralaArchitects
N.T.S.
SCOPE OF WORK
WALDO PAFFORD
ELEMENTARY SCHOOL
PROJECT NO:
DRAWN BY:
DATE:
SCALE:
OWNER NO:
FACILITY NO.: 689-0100
2550 W 15TH ST, HINESVILLE, GA 31313
SEAL
STRUCTURAL ENGINEERS
SAUSSY ENGINEERINGSAUSSY ENGINEERING
400 JOHNNY MERCER BLVD, SUITE E,
SAVANNAH, GA 31410
M.E.P. ENGINEERS
METHOD ENGINEERING GROUPMETHOD ENGINEERING GROUP
1020 DRAYTON STREET, SUITE 101,
SAVANNAH, GA 31401
1/
/2
3:
:3
PM
Au to de sk
D oc s:
//2
LC
SS
C an op y R ep ai r/2
8_
LC
SS
C an op y R ep ai r_ C
EN
TR
AL
.rv t
As indicated
G0.02
GENERAL
PROJECT
INFORMATION
CONSTRUCTION
DOCUMENTS
MAB
JANUARY 2026
2026-10
LCSS CANOPY
REPAIR
LIBERTY COUNTY SCHOOL
SYSTEM
VOLUME II - WALDO
PAFFORD
ELEMENTARY
SCHOOL
GRAPHIC SYMBOLS
ABBREVIATIONS
MATERIAL LEGEND
PROJECT SUMMARY - VOLUME II
KEYNOTE LEGEND - MASTER
NO. NOTE
03 30 00.A CAST-IN-PLACE CONCRETE
03 30 00.B CAST-IN-PLACE CONCRETE SEE STRUCT.
03 30 00.G WELDED WIRE MESH SEE STRUCT.
03 30 00.P2 1/2" PEJ
03 48 16 PRECAST CONCRETE SPLASH BLOCKS
07 92 00 JOINT SEALANT
10 73 26 MANUF. WALKWAY COVERS
10 73 26.B1 MANUF. DRAINING COLUMN
10 73 26.F FLASHING
10 73 26.F1 FASCIA
10 73 26.H SUPPORT STRUT
32 93 00 MULCH
FLOOR TYPES
TAGDESCRIPTION FIRE RATING
REFERENCE
GENERAL INFORMATION - VOLUME IILOCATION MAP
SITE LOCATION
W 15
TH
ST
ELMA G MILES PKWY
TRUE NORTH
REVISION SCHEDULE
NO DATE DESCRIPTION
GENERAL NOTES
1 REFER TO SHEET G0.02 FOR SYMBOL LEGEND.
2 EXTERIOR CONCRETE SIDEWALKS/SURFACE SHALL SLOPE AWAY FROM THE BUILDING AT 1/4" PER FOOT MINIMUM FOR A DISTANCE OF 8'-0" MINIMUM.
BEYOND 8'-0" THEY SHALL SLOPE AWAY FROM THE BUILDING AT 1/8" PER FOOT MINIMUM TO 1/2" PER FOOT MAXIMUM. REFER TO CIVIL DRAWINGS FOR
EXTENT OF SIDEWALKS AND SPOT ELEVATIONS.
3 REFER TO DRAWINGS FOR DIMENSIONS BETWEEN COLUMN GRID LINES COLUMN DIMENSIONS ARE TO CENTERLINE OF COLUMN U.N.O.
4 REFER TO PLANS AND/OR SECTIONS FOR SUBSYSTEM TYPE
5 ALL EXPOSED, UNFINISHED EXTERIOR METAL SURFACES SHALL BE PAINTED.
6 NEW FINISHES SHALL BE INSTALLED FLUSH WITH EXISTING FINISHES.
7 WHERE A NOTE/DETAIL IS SHOWN FOR ONE CONDITION, IT SHALL APPLY TO ALL SIMILAR AND LIKE CONDITIONS, UNLESS NOTED OTHERWISE.
8 DEMOLITION PROCEDURES SHALL BE PERFORMED IN ACCORDANCE WITH NFPA 241, 2022 EDITION "STANDARD FOR SAFEGUARDING CONSTRUCTION, ALTERATION, AND DEMOLITION OPERATIONS".
9 WHERE MATERIALS ARE REMOVE OR DEMOLISHED, INFILL AND/OR PATCH TO MATCH EXISTING ADJACENT FINISH AND/OR STRUCTURAL MEMBER.
10 REFER TO ELECTRICAL DRAWINGS FOR ADDITIONAL INFORMATION REGARDING DEMOLITION.
11 AT CONCRETE WALK REMOVAL WHERE NEW WALKS ARE TO BE INSTALLED, CUT SLABS TO THE NEAREST CONTROL JOINT. THIS APPLIES AT THE NEW
WALKS ONLY, NOT STRIP FOOTING SECTIONS.
12 CONTRACTOR TO CONSULT WITH ARCHITECT PRIOR TO REMOVAL OF ANY DAMAMAGED CONCRETE SECTIONS.
FOUNDATIONS:
1. FOUNDATION DESIGN IS BASED ON A MAXIMUM ALLOWABLE SOIL BEARING PRESSURE
OF 1500 PSF. THE STRUCTURAL ENGINEER IS NOT RESPONSIBLE FOR SUBSURFACE
CONDITIONS ENCOUNTERED IN THE FIELD DIFFERENT FROM THOSE ASSUMED OR DESIGNED.
2. ALLOWABLE BEARING PRESSURE SHALL BE VERIFIED BY FIELD TESTING IN
ACCORDANCE WITH REQUIREMENTS OF THE PROJECT SPECIFICATIONS. A DYNAMIC
CONE PENETROMETER TEST (ASTM STP-399) SHALL BE PROVIDED AT EACH COLUMN
FOOTING EXCAVATION TO VERIFY AVAILABILITY OF THE DESIGN PRESSURE INDICATED.
3. ALL FOOTINGS AND SLABS SHALL BEAR ON SUBGRADE COMPACTED TO A MINIMUM 95%
ASTM D-1557. PROVIDE ONE COMPACTION TEST AT EACH COLUMN FOOTING EXCAVATION
TO VERIFY REQUIRED COMPACTION HAS BEEN OBTAINED.
4. NO FOOTINGS SHALL BEAR ON ROCK. UNDERCUT ROCK A MINIMUM OF 2 FEET BELOW
BOTTOM OF FOOTING AND REPLACE WITH STRUCTURAL FILL IN ACCORDANCE WITH
PROJECT SPECIFICATION REQUIREMENTS.
5. CONTRACTOR SHALL PROVIDE TEMPORARY DEWATERING AS REQUIRED TO INSTALL FOUNDATIONS.
ALL WATER SOFTENED SOILS IN FOUNDATION EXCAVATIONS SHALL BE REMOVED PRIOR TO
POURING CONCRETE. FILL OVER-EXCAVATED LIMITS WITH COMPACTED STRUCTURAL FILL OR
ADDITIONAL CONCRETE.
6. ALL BOTTOM REINFORCING IN FOOTINGS SHALL BE SUPPORTED ITH WHOLE CONCRETE BRICKS
OR PREFABRICATED ALL PLASTIC CHAIR SUPPORT AT MAXIMUM 48" O.C. BAR SUPPORTS
SHALL BE POSITIONED TO MAINTAIN NO LESS THAN 3" CLEAR TO BOTTOM OF LOWEST
REINFORCING BAR.
7. ALL FOOTING, PIER AND OTHER FOUNDATION TYPE REINFORCING SHALL BE TIED IN
PLACE PRIOR TO POURING CONCRETE.
CONCRETE:
1. UNLESS SPECIFIED OTHERWISE, CONCRETE COVER OVER REINFORCEMENT SHALL
CONFORM TO THE FOLLOWING:
A. ALL FOOTINGS AND OTHER CONCRETE CAST AGAINST AND PERMANENTLY
EXPOSED TO EARTH: 3"
B. FORMED CONCRETE EXPOSED TO EARTH OR WEATHER:
#5 BAR AND SMALLER: 1 1/2"
#6 BAR AND LARGER: 2"
2. ALL REINFORCING STEEL SHALL CONFORM TO ASTM A615, GRADE 60, UNLESS
NOTED OTHERWISE.
3. REINFORCEMENT SHALL BE SPLICED ONLY AT LOCATIONS SHOWN OR NOTED ON THE
STRUCTURAL DOCUMENTS, EXCEPT REINFORCING MARKED CONTINUOUS MAY BE SPLICED
AT LOCATIONS DETERMINED BY THE CONTRACTOR. SPLICES AT OTHER LOCATIONS
SHALL BE APPROVED IN WRITING BY THE STRUCTURAL ENGINEER.
4. ALL CONCRETE WORK SHALL CONFORM TO ACI 318 AND CRSI STANDARDS.
5. DEFECTIVE AREAS IN CONCRETE WORK INCLUDING, BUT NOT LIMITED TO,
HONEYCOMBING, SPALLS, AND CRACKS WITH WIDTHS EXCEEDING 0.10" SHALL BE
REPAIRED BY THE CONTRACTOR. THE EXTENT OF THE DEFECTIVE AREA SHALL BE
DETERMINED BY THE STRUCTURAL ENGINEER.
6. NO REINFORCING SHALL BE CUT IN FIELD. ADDITIONAL REINFORCING AND THAT
QUANTITY OF REINFORCING OCCURRING AT OPENINGS SHALL BE PLACED EQUALLY
EACH SIDE OF OPENING AS DETAILED.
7. UNLESS NOTED OTHERWISE, DETAILING AND FABRICATION OF REINFORCING STEEL
SHALL FOLLOW CRSI "MANUAL OF STANDARD PRACTICE".
8. REINFORCING SHALL BE SUPPORTED IN FORMS AND SPACED WITH WIRE BAR SUPPORTS
ACCORDING TO CRSI "PLACING REINFORCING BARS", UNLESS NOTED OTHERWISE.
BASIS OF DESIGN:
A. GRAVITY LOADS UNIFORM CONCENTRATED
ROOF LIVE LOADS 20 PSF
B. SNOW LOADS (REFERENCE: ASCE 7-22)
GROUND SNOW LOAD, Pg = 7 PSF (FIGURE 7.2-1)
Ce = 0.90 (TERRAIN CATEGORY C) (TABLE 7.3-1)
Ct = 1.0 (TABLE 7.3-2)
C. RAIN LOADS (REFERENCE: ASCE 7-22)
60 MINUTE RAINFALL INTENSITY 4.15 IN/H (NOAA NATIONAL WEATHER SERVICE)
D. WIND LOADS (REFERENCE: ASCE 7-22)
BASIC WIND SPEED (3 SECOND GUST), V = 140 MPH (FIGURE 26.5-1B)
NOMINAL WIND SPEED, Vasd = 117 MPH
RISK CATEGORY = III (TABLE 1.5-1)
EXPOSURE CATEGORY = C (SECTION 26.7)
INTERNAL PRESSURE COEFFICIENTS: +0.18,-0.18 (TABLE 26.13-1)
(ENCLOSED BUILDING TYPE)
E. SEISMIC LOADS (REFERENCE: ASCE 7-22)
BUILDING RISK CATEGORY = III (TABLE 1.5-1)
0.2 SEC SPECTRAL RESPONSE ACCELERATION: Ss = 0.250
1.0 SEC SPECTRAL RESPONSE ACCELERATION: S1 = 0.140
SPECTRAL RESPONSE ACCELERATION: Sds = 0.210
SPECTRAL RESPONSE ACCELERATION: Sd1 = 0.140
SITE CLASSIFICATION = D (ASSUMED) (SECTION 11.4)
BASIC SEISMIC-FORCE-RESISTING SYSTEM
SEISMIC DESIGN CATEGORY = C (SECTION 11.6)
SEISMIC IMPORTANCE FACTOR = 1.25 (TABLE 1.5-2)
ANALYSIS PROCEDURE: EQUIVALENT LATERAL FORCE (SECTION 12.8)
SPECIAL STRUCTURAL INSPECTIONS:
A. SPECIAL INSPECTIONS
1. SPECIAL STRUCTURAL TESTS AND INSPECTIONS SHALL BE PERFORMED ON THIS
PROJECT IN ACCORDANCE WITH THE REQUIREMENTS OF CHAPTER 17 OF THE
IBC 2024 BUILDING CODE AND ALL GEORGIA STATE ADMENDMENTS.
2. SPECIAL STRUCTURAL TESTS AND INSPECTIONS SHALL BE PERFORMED BY AN
AGENCY SELECTED BY THE DESIGN PROFESSIONAL WHICH MEETS ALL OF THE
REQUIREMENTS FOR APPROVAL INDICATED IN IBC 2024 SECTION 1704. SPECIAL
INSPECTORS SHALL BE QUALIFIED PERSONS WHO SHALL DEMONSTRATE COMPETENCE
FOR INSPECTION OF THE PARTICULAR TYPE OF CONSTRUCTION OR OPERATION
REQUIRING SPECIAL INSPECTION.
3. THE CONTRACTOR SHALL COORDINATE THE INSPECTION SERVICES IN
ACCORDANCE WITH THE PROGRESS OF THE WORK. THE CONTRACTOR SHALL
PROVIDE SUFFICIENT NOTICE TO THE INSPECTOR TO ALLOW PROPER
SCHEDULING OF PERSONNEL.
4. THE COSTS OF THE SPECIAL INSPECTOR'S SERVICES SHALL BE THE RESPONSIBILITY
OF THE OWNER. COSTS OF INSPECTION SERVICES WHICH ARE EXEMPTED UNDER
CHAPTER 17 AND SPECIFIED IN THE PROJECT SPECIFICATIONS, SHALL BE
PAID FOR BY THE CONSTRUCTION MANAGER AT RISK.
B. REPORTS
1. SPECIAL INSPECTORS SHALL KEEP A RECORD OF ALL INSPECTIONS PERFORMED.
COPIES OF ALL INSPECTIONS SHALL BE FURNISHED TO THE DESIGN PROFESSIONAL
WITHIN 48 HOURS OF THE INSPECTION.
2. REPORTS SHALL INDICATE THAT THE WORK WAS PERFORMED AND CONSTRUCTED
IN ACCORDANCE WITH THE CONTRACT DOCUMENTS. WORK WHICH DOES NOT
CONFORM TO THE CONTRACT DOCUMENTS SHALL BE IDENTIFIED IN THE REPORT
AND SHALL BE BROUGHT TO THE IMMEDIATE ATTENTION OF THE CONTRACTOR.
3. INTERIM REPORTS OF INSPECTIONS DOCUMENTING REQUIRED SPECIAL
INSPECTIONS INCLUDING ANY DISCREPANCIES NOTED IN THE INSPECTIONS
SHALL BE SUBMITTED TO THE DESIGN PROFESSIONAL PRIOR TO COMPLETION
OF THE STRUCTURAL SYSTEMS BUT AT A FREQUENCY NOT TO EXCEED 60 DAYS.
IF ITEMS IN THE SPECIAL INSPECTION SCHEDULE ARE NOT COMPLETED WHEN
REQUIRED OR, IN THE OPINION OF THE SPECIAL INSPECTOR ARE FOUND TO BE
NOT APPLICABLE, THE DESIGN PROFFESIONAL SHOULD BE NOTIFIED
IMMEDIATELY TO DISCUSS/RESOLVE SAID ISSUES. THE CONTRACTOR MUST
NOT WAIT UNTIL ISSUANCE OF THE FINAL REPORT TO BRING THIS TO THE
ATTENTION OF THE DESIGN PROFESSIONAL.
C. REQUIRED SPECIAL INSPECTIONS
IBC SPECIAL INSPECTION REQUIRED
SECTION DESCRIPTION OF WORK YES NO REMARKS
1704.2.5 INSPECTION OF FABRICATORS
1705.2 STEEL CONSTRUCTION
1705.3 CONCRETE CONSTRUCTION
1705.4 MASONRY CONSTRUCTION
1705.5 WOOD CONSTRUCTION
1705.6 SOILS
1705.7 DRIVEN DEEP FOUNDATIONS
1705.8 CAST-IN-PLACE DEEP FOUNDATIONS
1705.9 HELICAL PILE FOUNDATIONS
1705.10 DEEP FOUNDATION ELEMENTS
1705.11 FABRICATED ITEMS
1705.12 WIND RESISTANCE
1705.13 SEISMIC REISTANCE
1705.14 TESTING AND QUALIFICATION FOR
SEISMIC RESISTANCE
1705.15 SPRAYED FIRE-RESISTANT MATERIALS
1705.16 MASTIC AND INTUMESCENT FIRE-
RESISTANT COATINGS
1705.17 EXTERIOR INSULATION AND FINISH
SYSTEM (EIFS)
1705.18 FIRE-RESISTANT PENETRATIONS
AND JOINTS
1705.19 SPECIAL INSPECTION FOR
SMOKE CONTROL
1705.20 MASS TIMBER
X
X
X
X
X
X
X
X
X
X
X
X
X
SPECIAL STRUCTURAL INSPECTIONS (CONT.):
REMARKS:
1. CONCRETE SPECIAL INSPECTION:
CONTINUOUS AND PERIODIC INSPECTIONS, AS DEFINED BY SECTION 202 OF
THE IBC 2024 BUILDING CODE, SHALL BE PERFORMED BY THE SPECIAL INSPECTION
AGENCY IN ACCORDANCE WITH THE REQUIREMENTS OF SECTION 1705.3 AND TABLE
1705.3 INCLUDING ALL GEORGIA STATE AMMENDMENTS.
2. SOILS SPECIAL INSPECTION:
INSPECTION OF THE EXISTING SITE SOIL CONDITIONS, FILL PLACEMENT AND
LOAD BEARING REQUIREMENTS SHALL BE PERFORMED BY THE SPECIAL
INSPECTION AGENCY IN ACCORDANCE WITH THE REQUIREMENTS OF SECTION
1705.6 AND TABLE 1705.6.
PRE-ENGINEERED CANOPIES:
1. COORDINATE ALL CANOPY CONFIGURATIONS WITH ARCHITECTURAL DRAWINGS. ALL CANOPIES
SHALL BE DELEGATED DESIGNS AND SUBMITTALS SHALL INCLUDE SHOP DRAWINGS AND
CALCULATIONS SIGNED AND SEALED BY A PROFESSIONAL ENGINEER REGISTERED IN THE
STATE OF GEORGIA.
2. SEE ARCHITECTURAL DOCUMENTS FOR MISCELLANEOUS METAL COMPONENTS NOT INCLUDED IN THE
STRUCTURAL DRAWINGS.
3. MATERIALS, FABRICATION AND CONSTRUCTION SHALL CONFORM TO IBC 2024.
4. THERE SHALL BE NO FIELD CUTTING OF MEMBERS FOR WORK OF OTHER TRADES WITHOUT
THE PRIOR WRITTEN APPROVAL OF THE DESIGN PROFESSIONAL.
5. WELDING OF ALUMINUM SHALL BE IN CONFORMANCE TO THE ALUMINUM DESIGN MANUAL AND
PERFORMED BY WELDERS CERTIFIED PER AWS D1.2 "STRUCTURAL WELDING CODE-ALUMINUM".
ALUMINUM PRESSURE VESSELS AND FLUID-CARRYING PIPE LINES ARE NOT MISCELLANEOUS
METALS.
6. CONTRACTOR SHALL SUBMIT SHOP DRAWINGS AND CALCULATION WITH THEIR APPROVAL STAMP
TO THE DESIGN PROFESSIONAL FOR REVIEW PRIOR TO FABRICATION AND CONSTRUCTION.
COMPLETE DETAILING OF SHOP AND FIELD WELDING USING AMERICAN WELDING SOCIETY SYMBOLS
SHALL BE SHOWN ON THE SHOP DRAWINGS. INCLUDE PLANS, ELEVATIONS, SECTIONS,
DETAILS, MATERIAL SPECIFICATIONS AND ATTACHMENTS TO OTHER WORK. ATTACHMENTS TO
OTHER WORK SHALL BE FULLY DETAILED FOR ALL CONDITIONS AND CONFIGURATIONS OF
EVERY CONNECTION.
7. ALL SHOP DRAWINGS AND CALCULATIONS ARE TO BE PREPARED, SIGNED, AND SEALED BY A
PROFESSIONAL ENGINEER REGISTERED IN THE STATE OF GEORGIA. DESIGN CALCULATIONS
SHALL ALSO INCLUDE CALCULATIONS FOR EACH CONNECTION CONDITION AND CONFIGURATION.
TO OTHER WORK INCLUDING SHOWING DESIGN FORCES APPLIED TO OTHER WORK.
8. SEE SPECIFICATION FOR ADDITIONAL REQUIREMENTS.
Not Valid Unless Signed
IRG
ED
TSIG ER
A
R
E G
No. 000432
E
O
I
,YN ER
SUSR A
G ENI
S
W H
T
U
N
STRUCTURAL
E
E
I I
SAUSSY ENGINEERING
400 Johnny Mercer Boulevard Suite E
P.O. Box 30597 Savannah, Georgia 31410
Phone: (912) 898-8255 Fax: (912) 898-1882
517 EAST CONGRESS STREET
SAVANNAH, GEORGIA 31401
tel 912.234.6318 fax 912.236.8414 cogdellmendrala.com
SHEET TITLE
SHEET
KEY PLAN
TRUE NORTH PROJECT NORTHSCALE
COPYRIGHT © 2025 COGDELL & MENDRALA ARCHITECTS, PC
Cogdell Mendrala Architects
N.T.S.
PROJECT NO:
DRAWN BY:
DATE:
SCALE:
OWNER NO:
FACILITY NO.:
SEAL
STRUCTURAL ENGINEERS
SAUSSY ENGINEERING
400 JOHNNY MERCER BLVD, SUITE E,
SAVANNAH, GA 31410
LCSS CANOPY
REPAIR
VOLUME II - WALDO
PAFFORD
ELEMENTARY
SCHOOL
2550 W 15TH ST, HINESVILLE, GA 31313
PROJECT NO.
689-0100
SCOPE OF WORK
WALDO PAFFORD
ELEMENTARY SCHOOL
M.E.P. ENGINEERS
METHOD ENGINEERING GROUP
1020 DRAYTON STREET, SUITE 101,
SAVANNAH, GA 31401
/1
/2
:2
:5
A
M F
J O
B S
\O
T H
E R
S \2
-L ib e rt y C o S c h o o ls
C a n o p y R e p a ir s \1
-R e v it \2
L ib e rt y C o C a n o p y R e p a ir s S
T R
U C
R
.r v t
1 : 1
S1.0
STRUCTURAL
NOTES
DESIGN
DEVELOPMENT
LIBERTY COUNTY SCHOOL
SYSTEM
JANUARY 2026
2026-10
JCG
25084
STRUCTURAL NOTES
REVISION SCHEDULE
NO DATE DESCRIPTION
E - 1E - 1 E - 1E - 1E - 1E - 1
E - 1 E - 1 E - 1 E - 1 E - 1E - 1
E - 2
EY1 EY2 EY3 EY4 EY5 EY6
EX2
EX1
CANOPY COVER WAS
COMPLETELY DESTROYED
THIS AREA
V.I.F.
9' - 1"
V.I.F.
8' - 1"
V.I.F.
8' - 8 1/2"
V.I.F.
8' - 6"
V.I.F.
8' - 4 1/2"
V.I.F.
4' - 2"
6' - 0" V.I.F.
4' - 0"
V.
I.F
8"
V.
I.F
1'
- 1 0"
V.
I.F
7'
- 0
V.
I.F
1'
- 1 0"
E - 1E - 1 E - 1
E - 3
EY1 EY2 EY3 EY4 EY5 EY6
EX2
EX1
CANOPY COVER WAS
COMPLETELY DESTROYED
THIS AREA
E - 1E - 1 E - 1
EXISTING CONSTRUCTION TO REMAIN
EXISTING CONSTRUCTION TO BE REMOVED
EXISTING BUILDING FOOTPRINT
517 EAST CONGRESS STREET
SAVANNAH, GEORGIA 31401
tel 912.234.6318 fax 912.236.8414 cogdellmendrala.com
SHEET TITLE
SHEET
KEY PLAN
TRUE NORTH PROJECT NORTHSCALE
COPYRIGHT © 2025 COGDELL & MENDRALA ARCHITECTS, PC
CogdellMendralaArchitects
N.T.S.
SCOPE OF WORK
WALDO PAFFORD
ELEMENTARY SCHOOL
PROJECT NO:
DRAWN BY:
DATE:
SCALE:
OWNER NO:
FACILITY NO.: 689-0100
2550 W 15TH ST, HINESVILLE, GA 31313
SEAL
STRUCTURAL ENGINEERS
SAUSSY ENGINEERINGSAUSSY ENGINEERING
400 JOHNNY MERCER BLVD, SUITE E,
SAVANNAH, GA 31410
M.E.P. ENGINEERS
METHOD ENGINEERING GROUPMETHOD ENGINEERING GROUP
1020 DRAYTON STREET, SUITE 101,
SAVANNAH, GA 31401
1/
/2
3:
:3
PM
Au to de sk
D oc s:
//2
LC
SS
C an op y R ep ai r/2
8_
LC
SS
C an op y R ep ai r_ C
EN
TR
AL
.rv t
As indicated
D2.01
DEMOLITION -
FLOOR PLAN AND
ROOF PLAN
CONSTRUCTION
DOCUMENTS
MAB
JANUARY 2026
2026-10
LCSS CANOPY
REPAIR
LIBERTY COUNTY SCHOOL
SYSTEM
VOLUME II - WALDO
PAFFORD
ELEMENTARY
SCHOOL
1/4" = 1'-0"D2.01
WALDO PAFFORD - DEMOLITION FLOOR PLAN1
1/4" = 1'-0"D2.01
WALDO PAFFORD - DEMOLITION ROOF PLAN2
GENERAL DEMOLITION NOTES
1 DEMOLITION PROCEDURES SHALL BE PERFORMED IN ACCORDANCE WITH NFPA 241, 2022 EDITION "STANDARD FOR SAFEGUARDING
CONSTRUCTION, ALTERATION, AND DEMOLITION OPERATIONS".
2 REFER TO ELECTRICAL DRAWINGS FOR SPECIFIC DEMOLITION OF ELEC EQUIPMENT AND FIXTURES. ELEC DEMOLITION SHOWN ON THE
ARCHITECTURAL DRAWINGS IS GENERAL.
3 WHERE A NOTE/DETAIL IS SHOWN FOR ONE CONDITION, IT SHALL APPLY TO ALL SIMILAR AND LIKE CONDITIONS.
4 ANY EQUIPMENT REMOVED FOR RE-INSTALLATION SHALL BE PROTECTED AND STORED BY THE CONTRACTOR.
5 REMOVE AND REPLACE PORTION(S) OF CONCRETE SLAB AS REQUIRED TO INSTALL FOOTINGS AND/OR MATERIAL BELOW.
6 NOTES AND NUMBER SEQUENCING SHOWN APPLY TO THIS SHEET ONLY.
7 DISCOVERY OF ASBESTOS: ALL MATERIALS KNOWN TO CONTAIN ASBESTOS AND THAT WILL BE IMPACTED BY DEMOLITION AND CONSTRUCTION
ACTIVITIES INCLUDED IN THE PROJECT SCOPE OF WORK HAVE BEEN REMOVED. IN EVENT CONCEALED CONDITIONS ARE ENCOUNTERED, NOTIFY THE ARCHITECT PRIOR TO PROCEEDING FURTHER WITH WORK.
8 PRIOR TO REMOVAL, COORDINATE WITH OWNER ALL MATERIAL TO BE TURNED OVER TO THE SCHOOL OR MAINTENANCE DEPARTMENT.
9 WHERE MATERIALS ARE REMOVED OR DEMOLISHED, INFILLL OR PATCH TO MATCH EXISTING ADJACENT FINISH AND/OR STRUCTURAL MEMBER.
10 ALL RENOVATION WORK IS TO BE PERFORMED IN COMPLIANCE WITH IFC 2024, SECTION 3304.2 WASTE DISPOSAL. ALL COMBUSTIBLE DEBRIS
AND WASTE MATERIAL SHALL BE REMOVED FROM THE BUILDING AT THE END OF EACH SHIFT OF WORK.
11 THE CONTRACTOR SHALL BE RESPONSIBLE FOR THE DESIGN AND ERECTION OF ALL SHORING NECESSARY TO SAFEGUARD THE EXISTING
STRUCTURE. ANY SHORING SHOWN HEREIN IS A PARTIAL AND SCHEMATIC REPRESENTATION OF THE REQUIRED. THE CONTRACTOR SHALL SUBMIT A DETAILED PLAN FOR SHORING, BRACING, AND PROTECTION OF THE EXISTING CONSTRUCTION. THIS PLAN SHALL INCLUDE A CONSTRUCTION SEQUENCE AND SHALL BEAR THE DEAL OF THE PROFFESIONAL ENGINEER REGISTERED IN THE STATE OF GEORGIA AND SHALL BE SUBMITTED TO THE ARCHITECT/EGINEER FOR REVIEW PRIOR TO THE BEGINNING OF THE WORK.
12 THE CONTRACTOR SHALL FIELD VERIFY ALL DIMENSIONS, ELEVATION, ETC., NECESSARY FOR THE PROPER CONSTRUCTION AND ALIGNMENT OF THE NEW PORTIONS OF THE WORK TO THE EXISTING WORK. THE CONTRACTOR SHALL MAKE ALL FIELD MEASUREMENTS NECESSARY FOR THE COMPLETE DETAILING, FABIRCATION, AND ERECTION OF ALL STRUCTURAL MEMBERS. ANY DISCREPANCY NOTED BETWEEN ASSUMPTIONS MADE ON THE DRAWINGS OF EXISTING FREATURES AND THE ACTUAL CONDITIONS SHALL BE BROUGHT TO THE ATTENTION OF THE ARCHITECT/ENGINEER. ALL DIMENSIONS OBTAINED IN FIELD AND USED AS A BASIS OF DETAILING SHALL BE CLEARLY INDICATED ON THE SHOP
DRAWINGS.
DEMOLITION LEGEND DEMO NOTES - EXTERIOR
E-1 REMOVE EXISITING COLUMNS AS INDICATED. CUT COLUMN FLUSH WITH
TOP OF FOOTING. EXISTING FOOTING TO BE ABANDONED IN PLACE
E-2 REMOVE EXISITING SIDEWALK TO EXTENT SHOWN.
E-3 REMOVE EXISTING PORTION OF CANOPY TO EXTENT SHOWN.
REVISION SCHEDULE
NO DATE DESCRIPTION
AL
IGN
A3.11
A3.01
A3.01
A3.01 � 3
2' - 1" 12' - 0" 8' - 8" 8' - 8" 8' - 8" 8' - 11"
V.
I.F
7'
- 0
8"
V.I.F.
10' - 0" 4' - 1"
1' - 2" 2' - 11" 5' - 2" 3' - 6" 5' - 2 1/2" 3' - 5 1/2" 5' - 0 1/2" 3' - 7 1/2" 4' - 9" 4' - 2"
1 4
10 73 26.B1 MANUF. DRAINING COLUMN
TYP.
C J
C J
C J
Y1
X2
X1
M U
LC
H
3'
0"
M U
LC
H
3'
0"
EY2 EY3 EY4 EY5 EY6Y2 Y3 Y4 Y5
32 93 00 MULCH
03 48 16 PRECAST CONCRETE SPLASH BLOCKS
03 30 00.A CAST-IN-PLACE CONCRETE
A3.11
�A3.01
A3.01
A3.01 � 3
49' - 5 1/8"
8 1 /2"
10 73 26 MANUF. WALKWAY COVERS
Y1 EY2 EY3 EY4 EY5 EY6
X2
X1
Y2 Y3 Y4 Y5
CONTINUOUS CHANNEL RACEWAY
BY CANOPY MANUF.
SEE ELECTRICAL FOR DETAILS.
10 73 26 MANUF. WALKWAY COVERS
8' - 9"
B.O. CANOPY BEAMS
5' - 10" 5' - 10" 4' - 2" 4' - 2" 4' - 2 1/2" 4' - 2 1/2"
LIGHTING FIXTURE.
CENTERED IN BAY.
COORDINATE WITH
ELECTRICAL. TYP.
NEW PRE-ENGINEERED PRE-FINISHED ALUM. CANOPY WITH DRAINING COLUMNS - REFER TO
SHEET A8.41 FOR DETAILS.
NEW CONCRETE WALK TO MATCH EXISTING WIDTH.
FINISH FLUSH TO EXISTING CONCRETE CURB. SEE SLAB DETAILS REFER TO WALKWAY JOINT
LEGEND.
PROVIDE CLEAN ROUGH GRADING ± 6" TYP. REPAIR GRASSING/GROUND COVER AS REQUIRED.
PATCH / REPAIR EXISTING ASPHALT PAVING IF DAMAGED DURING INSTALLATION OF NEW
HARDSCAPE.
EXISTING BUILDING FOOTPRINT
NEW MULCH
CJ CMU CONTROL JOINT (3/8" TYP.)
A3.11
A3.01
A3.01
A3.01 � 3
C J
C J
C J
6' - 0" V.I.F.
4' - 0"
0"
2 3
NEW BROOM FINISH
CONCRETE SLAB W/
CONTROL JOINTS AS
INDICATED.
A8.41
A8.41
A8.41
3'
- 0
7'
- 0
3'
- 0
A8.41
1.
2.
3.
NOTE:
PROVIDE EXPANSION JOINT AT A MAXIMUM SPACING OF EVERY 50' - 0" AND WHENEVER
SIDEWALK BUTTS A VERTICAL SURFACE (BUILDING WALL, CURB, COLUMN, ETC.)
CENTERLINE.
CONTROL JOINTS ARE DIAGRAMMATIC AND ARE NOT TO EXCEED THE 1.5 TIMES WIDTH
OF WALK OR 8' - 0" WHICHEVER IS GREATER.
WHEN THE WIDTH EXCEEDS 10' - 0" PROVIDE ONE LONGITUDINAL CONTRACTION JOINT
AT THE CENTERLINE.
517 EAST CONGRESS STREET
SAVANNAH, GEORGIA 31401
tel 912.234.6318 fax 912.236.8414 cogdellmendrala.com
SHEET TITLE
SHEET
KEY PLAN
TRUE NORTH PROJECT NORTHSCALE
COPYRIGHT © 2025 COGDELL & MENDRALA ARCHITECTS, PC
CogdellMendralaArchitects
N.T.S.
SCOPE OF WORK
WALDO PAFFORD
ELEMENTARY SCHOOL
PROJECT NO:
DRAWN BY:
DATE:
SCALE:
OWNER NO:
FACILITY NO.: 689-0100
2550 W 15TH ST, HINESVILLE, GA 31313
SEAL
STRUCTURAL ENGINEERS
SAUSSY ENGINEERINGSAUSSY ENGINEERING
400 JOHNNY MERCER BLVD, SUITE E,
SAVANNAH, GA 31410
M.E.P. ENGINEERS
METHOD ENGINEERING GROUPMETHOD ENGINEERING GROUP
1020 DRAYTON STREET, SUITE 101,
SAVANNAH, GA 31401
1/
/2
3:
:4
PM
Au to de sk
D oc s:
//2
LC
SS
C an op y R ep ai r/2
8_
LC
SS
C an op y R ep ai r_ C
EN
TR
AL
.rv t
As indicated
A2.01
CANOPY FLOOR
PLAN,
REFLECTED
CEILING PLAN, &
ROOF PLAN
CONSTRUCTION
DOCUMENTS
MAB
JANUARY 2026
2026-10
LCSS CANOPY
REPAIR
LIBERTY COUNTY SCHOOL
SYSTEM
VOLUME II - WALDO
PAFFORD
ELEMENTARY
SCHOOL
1/4" = 1'-0"A2.01
WALDO PAFFORD - FLOOR PLAN1
1/4" = 1'-0"A2.01
WALDO PAFFORD - ROOF PLAN3
1/4" = 1'-0"A2.01
WALDO PAFFORD - CEILING PLAN4
REFLECTED CEILING PLAN NOTES
1 REFER TO ELECTRICAL DRAWINGS/SPECIFICATIONS FOR LIGHT FIXTURE TYPES.
2 CONTINUOUS CHANNEL RACEWAY BY CANOPY MANUFACTURER SHALL BE PROVIDED TO CONCEAL
ELECTRICAL CONDUIT. RACEWAY FINISH SHALL MATCH CANOPY.
GENERAL PLAN NOTES
1 REFER TO G0.02 SHEETS FOR GENERAL PROJECT NOTES, GRAPHIC SYMBOLS, EQUIPMENT
MOUNTING DIMENSIONS, AND GRAB BAR LENGTHS.
2 WHERE A NOTE/DETAIL IS SHOWN FOR ONE CONDITION IT SHALL APPLY TO ALL SIMILAR AND LIKE
CONDITIONS, UNLESS NOTED OTHERWISE.
3 FILL AND CAULK ANNULAR SPACES AROUND PIPE PENETRATIONS IN PARTITIONS.
4 WHERE MATERIALS ARE REMOVE OR DEMOLISHED, INFILL AND/OR PATCH TO MATCH EXISTING
ADJACENT FINISH AND/OR STRUCTURAL MEMBER.
5 CUTS AT EXISTING CONCRETE PAVING ARE TO BE STRAIGHT AND PARALLEL AND/OR
PERPENDICULAR TO PAVING EDGES. SEE STRUCTURAL SHEETS FOR ADDITIONAL INFORMATION.
6 PROVIDE P.E.J. AT JOINTS BETWEEN NEW AND EXISTING CONCRETE PAVING.
7 RELOCATE ANY EXISTING BUILDING-MOUNTED LIGHTS, SECURITY EQUIPMENT, ETC., THAT CONFLICT
WITH CONSTRUCTION / INSTALLATION OF NEW CANOPY. NOTIFY ARCHITECT OF CONFLICTS PRIOR
TO COMMENCING DEMOLITION.
WALDO PAFFORD - PLAN NOTES
LEGEND - SITE
GENERAL ROOF PLAN NOTES
1 NOT ALL PENETRATIONS ARE SHOWN ON ROOF PLAN.
SEE MECHANICAL & PLUMBING DRAWINGS FOR ACTUAL ROOF PENETRATION QUANTITIES.
NOTIFY ARCHITECT OF ANY PENETRATIONS NOT SHOWN ON ROOF PLAN TO COORDINATE
FINAL LOCATIONS.
2 WHERE SLOPE (X/X" / 1'-0") IS NOT INDICATED, SLOPE ROOF MIN. 1/4" PER FOOT. PROVIDE
SHOP DRAWINGS INDICATING ACTUAL SLOPES. 03 52 16 LWIC INSTALLER TO FOLLOW
APPROVED SHOP DRAWINGS.
3 INSTALL ALL SHEET METAL FLASHINGS AT ROOF PENETRATIONS IN ACCORDANCE WITH
SMACNA SHEET METAL MANUAL, CURRENT EDITION.
4 WHERE A NOTE/DETAIL IS SHOWN FOR ONE CONDITION IT SHALL APPLY TO ALL SIMILAR AND
LIKE CONDITIONS, UNLESS NOTED OTHERWISE.
5 INSTALL FLASHING AT ALL ROOF PENETRATIONS AND WHERE CANOPY ABUTS BUILDING
FACADE.
CONTROL JOINT LEGEND
1/4" = 1'-0"A2.01
WALDO PAFFORD - CONTROL JOINT PLAN2
KEYNOTE LEGEND - BY SHEET
NO. NOTE
03 30 00.A CAST-IN-PLACE CONCRETE
03 48 16 PRECAST CONCRETE SPLASH BLOCKS
10 73 26 MANUF. WALKWAY COVERS
10 73 26.B1 MANUF. DRAINING COLUMN
32 93 00 MULCH
WALKWAY JOINT LEGEND
PAVING NOTES
1 NEW PAVEMENT TO BE FLUSH WITH EDGE OF ADJACENT, EXISTING PAVEMENT.
2 CUTS IN EXISTING PAVEMENT TO BE SMOOTH AND PREPENDICULAR AND/OR PARALEL TO PAVEMENT
EDGES.
3 NEW CONCRETE TO HAVE BROOM FINISH.
4 EXTERIOR CONCRETE SIDEWALKS/SURFACE SHALL SLOPE AWAY FORM THE BUILDING AT 1/4" PER
FOOT MINIMUM FOR A DISTANCE OF 8' - 0" MINIMUM. BEYOND 8' - 0" THEY SHALL SLOPE AWAY FROM
THE BUILDING AT 1/8" PER FOOT MINIMUM RO 1/2" PER FOOT MAXIMUM.
REVISION SCHEDULE
NO DATE DESCRIPTION
A3.11
10 73 26.B1 MANUF. DRAINING COLUMN
TYP.
10 73 26 MANUF. WALKWAY COVERS
B.
O.
C
AN
OP
Y
BE
AM
8'
- 9
2' - 4 1/4"
Y1EY2EY3EY4EY5EY6 Y2Y3Y4Y5
10 73 26.F FLASHING
NEW AT EXISTING WALL
BY CANOPY MFR. WITH
TERM. BAR.
A3.11
2' - 4 1/4"
B.
O.
C
AN
OP
Y
BE
AM
8'
- 9
10 73 26 MANUF. WALKWAY COVERS
10 73 26.B1MANUF. DRAINING COLUMN
TYP.
Y1 EY2 EY3 EY4 EY5 EY6Y2 Y3 Y4 Y5
10 73 26.FFLASHING
NEW AT EXISTING WALL
BY CANOPY MFR. WITH
TERM. BAR.
B.
O.
C
AN
OP
Y
BE
AM
8'
- 9
10 73 26 MANUF. WALKWAY COVERS
10 73 26.B1MANUF. DRAINING COLUMN
TYP.
X2X1
517 EAST CONGRESS STREET
SAVANNAH, GEORGIA 31401
tel 912.234.6318 fax 912.236.8414 cogdellmendrala.com
SHEET TITLE
SHEET
KEY PLAN
TRUE NORTH PROJECT NORTHSCALE
COPYRIGHT © 2025 COGDELL & MENDRALA ARCHITECTS, PC
CogdellMendralaArchitects
N.T.S.
SCOPE OF WORK
WALDO PAFFORD
ELEMENTARY SCHOOL
PROJECT NO:
DRAWN BY:
DATE:
SCALE:
OWNER NO:
FACILITY NO.: 689-0100
2550 W 15TH ST, HINESVILLE, GA 31313
SEAL
STRUCTURAL ENGINEERS
SAUSSY ENGINEERINGSAUSSY ENGINEERING
400 JOHNNY MERCER BLVD, SUITE E,
SAVANNAH, GA 31410
M.E.P. ENGINEERS
METHOD ENGINEERING GROUPMETHOD ENGINEERING GROUP
1020 DRAYTON STREET, SUITE 101,
SAVANNAH, GA 31401
1/
/2
3:
:4
PM
Au to de sk
D oc s:
//2
LC
SS
C an op y R ep ai r/2
8_
LC
SS
C an op y R ep ai r_ C
EN
TR
AL
.rv t
1/2" = 1'-0"
A3.01
EXTERIOR
ELEVATIONS
CONSTRUCTION
DOCUMENTS
MAB
JANUARY 2026
2026-10
LCSS CANOPY
REPAIR
LIBERTY COUNTY SCHOOL
SYSTEM
VOLUME II - WALDO
PAFFORD
ELEMENTARY
SCHOOL
KEYNOTE LEGEND - BY SHEET
NO. NOTE
10 73 26 MANUF. WALKWAY COVERS
10 73 26.B1 MANUF. DRAINING COLUMN
10 73 26.F FLASHING
GENERAL ELEVATION NOTES
1 FASCIA, SOFFIT PANELS, CANOPY, COLUMNS, AND ALL NEW CANOPY COMPONENTS TO MATCH
EXISTING U.N.O.
2 ALL EXPOSED LINTELS, STRUCTURE, RAILINGS, ETC. TO BE PAINTED UNLESS PREFINISHED OR NOTED
OTHERWISE.
1/2" = 1'-0"A3.01
WALDO PAFFORD - NORTH ELEVATION1
1/2" = 1'-0"A3.01
WALDO PAFFORD - SOUTH ELEVATION2
1/2" = 1'-0"A3.01
WALDO PAFFORD - WEST ELEVATION3
REVISION SCHEDULE
NO DATE DESCRIPTION
CONTINUOUS CHANNEL
RACEWAY BY CANOPY
MANUF. SEE ELECTRICAL
FOR DETAIL.
TYP.
10 73 26 MANUF. WALKWAY COVERS
10 73 26.B1 MANUF. DRAINING COLUMN
10 73 26 MANUF. WALKWAY COVERS
4" 4"
A8.41
A8.41
10 73 26.F1 FASCIA
(NEW)
CONCRETE
CANOPY FOOTING
X1X2
6"
03 48 16
PRECAST
CONCRETE SPLASH
BLOCKS
32 93 00 MULCH
517 EAST CONGRESS STREET
SAVANNAH, GEORGIA 31401
tel 912.234.6318 fax 912.236.8414 cogdellmendrala.com
SEAL
SHEET TITLE
SHEET
KEY PLAN
TRUE NORTH PROJECT NORTHSCALE
COPYRIGHT © 2025 COGDELL & MENDRALA ARCHITECTS, PC
CogdellMendralaArchitects
N.T.S.
STRUCTURAL ENGINEERS
SAUSSY ENGINEERINGSAUSSY ENGINEERING
400 JOHNNY MERCER BLVD, SUITE E,
SAVANNAH, GA 31410
SCOPE OF WORK
LYMAN HALL
ELEMENTARY SCHOOL
PROJECT NO:
DRAWN BY:
DATE:
SCALE:
OWNER NO:
FACILITY NO.: 689-0183
1396 SHAW RD, HINESVILLE, GA 31313
M.E.P. ENGINEERS
METHOD ENGINEERING GROUPMETHOD ENGINEERING GROUP
1020 DRAYTON STREET, SUITE 101,
SAVANNAH, GA 31401
1/
/2
3:
:4
PM
Au to de sk
D oc s:
//2
LC
SS
C an op y R ep ai r/2
8_
LC
SS
C an op y R ep ai r_ C
EN
TR
AL
.rv t
3/4" = 1'-0"
A3.11
BUILDING
SECTIONS
CONSTRUCTION
DOCUMENTS
MAB
JANUARY 2026
2026-10
LCSS CANOPY
REPAIR
LIBERTY COUNTY SCHOOL
SYSTEM
VOLUME II - WALDO
PAFFORD
ELEMENTARY
SCHOOL
KEYNOTE LEGEND - BY SHEET
NO. NOTE
03 48 16 PRECAST CONCRETE SPLASH BLOCKS
10 73 26 MANUF. WALKWAY COVERS
10 73 26.B1 MANUF. DRAINING COLUMN
10 73 26.F1 FASCIA
32 93 00 MULCH
GENERAL SECTION NOTES
1 WHERE A NOTE/DETAIL IS SHOWN FOR ONE CONDITION, IT SHALL APPLY TO ALL SIMILAR AND LIKE
CONDITIONS, UNLESS NOTED OTHERWISE.
2 CONTRACTOR TO VERIFY ANCHORAGE AND FOUNDATION DETAILS W/ CANOPY MFR. PROVIDE
CANOPY REACTIONS TO ARCHITECT FOR VERIFICATION OF FOUNDATION SIZES.
3/4" = 1'-0"A3.11
WALDO PAFFORD - CANOPY CROSS SECTION1
REVISION SCHEDULE
NO DATE DESCRIPTION
3'
6"
3"
2"
2"
2' - 0" Ø
3'
6"
PRE MANUFACTURED ALUMINUM
CANOPY COLUMN - TO MATCH
EXISTING SIZE & FINISH
PYRAMID STYROFOAM
BLOCKOUT BY
CANOPY MFR.
FINISHED GRADE
3"
2"
COMPACTED
SUBGRADE
2"
2' - 0" Ø
#3 CIRCULAR
TIES @ 12" O.C.
(LAP 1' - 0")
6#4
EQUALLY SPACED IN
CIRCULAR PATTERN
INSTALL COLUMN PER CANOPY
MFR. DETAILS AND GROUT SOLID
WITH 5000 PSI NON-SHRINK
NON-METALLIC GROUT (FILL ALL
VOIDS SOLID)
AT TOP: 4#3 TIES @
4" O.C. MAX (LAP 1'-0")
DEFLECTOR PLATE
OPENING AT WET COLUMNS,
TYP. ALL COLUMNS
FINISHED GRADE / MULCH
PROTECTIVE COATING AT
COLUMN BASE AS SPECIFIED
BY CANOPY MFR.
1/2" PEJ AROUND COLUMN
CONCRETE ENCASEMENT
AROUND CANOPY COLUMN
CONCRETE SPLASH BLOCK
6"
(E) SIDWALK - SEE
ARCH. DRAWINGS
C
AN
O
PY
M
FR
AS
S
PE
C
IF
IE
D B
Y
8"
3'
0"
PRE MANUFACTURED
ALUMINUM CANOPY
COLUMN - TO MATCH
EXISTING SIZE &
FINISH
PYRAMID STYROFOAM
BLOCKOUT BY
CANOPY MFR.
SIDWALK - SEE
ARCH. DRAWINGS
FINISHED GRADE
3"
2"
COMPACTED
SUBGRADE
#3 CIRCULAR
TIES @ 12" O.C.
(LAP 1' - 0")
2"
6#4
EQUALLY SPACED IN
CIRCULAR PATTERN
2' - 0" Ø
PLANS
REFER TO
4" MIN
INSTALL COLUMN PER CANOPY MFR.
DETAILS AND GROUT SOLID WITH 5000
PSI NON-SHRINK NON-METALLIC
GROUT (FILL ALL VOIDS SOLID)
AT TOP: 4#3 TIES @
4" O.C. MAX (LAP 1'-0")
PROTECTIVE
COATING AT COLUMN
BASE AS SPECIFIED
BY CANOPY MFR.
CONTRACTOR TO SAW
CUT, REMOVE AND
REPLACE EXISTING
SIDEWALK AS
REQUIRED TO INSTALL
NEW CANOPY COLUMN
AND FOUNDATION
4"
4" 4"
DEFLECTOR PLATE
OPENING AT WET COLUMNS,
TYP. ALL COLUMNS
3/8" WIDE X 1" DEEP GROOVE WITH
1/4" RADIUS 0' - 0 1/2"
07 92 00 JOINT SEALANT
03 30 00.P2 1/2" PEJ
2" SMOOTH DOWEL No. 3
MIN. 1 1/2" DEEP
CONTROL JOINT SECTION EXPANSION JOINT SECTION
NOTES:
1. OMIT DOWEL WHERE CONCRETE WALK ABUTS EXIST. CURB
2. OMIT DOWEL WHERE CONCRETE WALK ABUTS VERTICAL CONSTRUCTION.
3. CONNECTION AT EJ AT JOINT WITH EXISTING CONCRETE SIMILAR.
TYPICAL SIDEWALK CONSTRUCTION
03 30 00.BCAST-IN-PLACE CONCRETE SEE
STRUCT.
03 30 00.GWELDED WIRE MESH SEE STRUCT.
MI
N.4"
SUBGRADE. COMPACT TO 90% PROCTOR DENSITY
SAW-CUT EDGE
X X X X X
X
EXIST. CONC. SLAB
+/- 4"
0'
- 4
0' - 4" 0' - 4" 10 73 26
CONDUIT, SEE ELECTRICAL. PAINT ALL EXPOSED
CONDUIT FO MATCH CANOPY.
LIGHT FIXTURE, SEE ELECTRICAL
NOTE: THIS DETAIL TYP. AT ALL WALKWAY COVERS
CONTINUOUS CHANNEL RACEWAY BY CANOPY MFG. MATCH
FINISH OF CANOPY
MANUF. WALKWAY COVERS
2"
LINE OF CANOPY BEAM BEYOND
2'
- 0
0'
- 6
6'
- 0
SEE PLAN
ADA COMPLIANT, DETECTABLE
WARNING, TRUNCATED DOME OVER
4" CONCRETE BASE. COLOR TO BE
APPROVED BY ARCHITECT.
SLOPE DN.
SL
OP
E
DN
SLOPE DN.
1:10 MAX. 1:10 MAX
1 :
M
AX
SIDEWALK
PAVING
CURB
KEYNOTE LEGEND - BY SHEET
NO. NOTE
03 30 00.B CAST-IN-PLACE CONCRETE SEE STRUCT.
03 30 00.G WELDED WIRE MESH SEE STRUCT.
03 30 00.P2 1/2" PEJ
07 92 00 JOINT SEALANT
1 1/2" = 1'-0"A8.41
TYPICAL CANOPY COLUMN FOOTING AT SIDEWALK DETAIL1
1 1/2" = 1'-0"A8.41
TYPICAL CANOPY COLUMN FOOTING AT GRASS DETAIL2
517 EAST CONGRESS STREET
SAVANNAH, GEORGIA 31401
tel 912.234.6318 fax 912.236.8414 cogdellmendrala.com
SHEET TITLE
SHEET
KEY PLAN
TRUE NORTH PROJECT NORTHSCALE
COPYRIGHT © 2025 COGDELL & MENDRALA ARCHITECTS, PC
CogdellMendralaArchitects
N.T.S.
SCOPE OF WORK
WALDO PAFFORD
ELEMENTARY SCHOOL
PROJECT NO:
DRAWN BY:
DATE:
SCALE:
OWNER NO:
FACILITY NO.: 689-0100
2550 W 15TH ST, HINESVILLE, GA 31313
SEAL
STRUCTURAL ENGINEERS
SAUSSY ENGINEERINGSAUSSY ENGINEERING
400 JOHNNY MERCER BLVD, SUITE E,
SAVANNAH, GA 31410
M.E.P. ENGINEERS
METHOD ENGINEERING GROUPMETHOD ENGINEERING GROUP
1020 DRAYTON STREET, SUITE 101,
SAVANNAH, GA 31401
1/
/2
3:
:4
PM
Au to de sk
D oc s:
//2
LC
SS
C an op y R ep ai r/2
8_
LC
SS
C an op y R ep ai r_ C
EN
TR
AL
.rv t
As indicated
A8.41
EXTERIOR
DETAILS
CONSTRUCTION
DOCUMENTS
MAB
JANUARY 2026
2026-10
LCSS CANOPY
REPAIR
LIBERTY COUNTY SCHOOL
SYSTEM
VOLUME II - WALDO
PAFFORD
ELEMENTARY
SCHOOL
KEYNOTE LEGEND - BY SHEET
NO. NOTE
03 30 00.B CAST-IN-PLACE CONCRETE SEE STRUCT.
03 30 00.G WELDED WIRE MESH SEE STRUCT.
03 30 00.P2 1/2" PEJ
07 92 00 JOINT SEALANT
3" = 1'-0"A8.41
CONCRETE PAVING DETAILS3
1 1/2" = 1'-0"A8.41
EXISTING SLAB ABUDMENT DETAIL4
1 1/2" = 1'-0"A8.41
LIGHTING CHASE DETAIL5
3/4" = 1'-0"A8.41
CURB RAMP DETAIL6
REVISION SCHEDULE
NO DATE DESCRIPTION
K T
T D
TC
1P 1 POLE (2P, 3P, 4P, ETC.)
A, AMP AMPERE
AC ABOVE COUNTER
ACLG ABOVE CEILING
ADO AUTOMATIC DOOR OPENER
AF AMP FRAME
AFF ABOVE FINISHED FLOOR
AFG ABOVE FINISHED GRADE
AFI ARC FAULT CIRCUIT
INTERRUPTER
AHU AIR HANDLING UNIT
AL ALUMINUM
ALT ALTERNATE
AMP AMPERE
AMPL AMPLIFIER
ANNUN ANNUNCIATOR
APPROX APPROXIMATELY
AQ-STAT AQUASTAT
ARCH ARCHITECT, ARCHITECTURAL
AS AMP SWITCH
AT AMP TRIP
ATS AUTOMATIC TRANSFER SWITCH
AUTO AUTOMATIC
AUX AUXILIARY
AV AUDIO VISUAL
AWG AMERICAN WIRE GAUGE
BATT BATTERY
BD BOARD
BLDG BUILDING
BMS BUILDING MANAGEMENT SYSTEM
C CONDUIT
CAB CABINET
CAT CATALOG
CATV CABLE TELEVISION
CB CIRCUIT BREAKER
CCTV CLOSED CIRCUIT TELEVISION
CKT CIRCUIT
CLG CEILING
COMB COMBINATION
CMPR COMPRESSOR
CONN CONNECTION
CONST CONSTRUCTION
CONT CONTINUATION OR CONTINUOUS
CONTR CONTRACTOR
CONV CONVECTOR
CP CIRCULATING PUMP
CRT CATHODE-RAY TUBE
CT CURRENT TRANSFORMER
CTR CENTER
CU COPPER
DCP DOMESTIC WATER CIRCULATING PUMP
DEPT DEPARTMENT
DET DETAIL
DIA DIAMETER
DISC DISCONNECT
DIST DISTRIBUTION
DN DOWN
DPR DAMPER
DS SAFETY DISCONNECT SWITCH
DT DOUBLE THROW
DWG DRAWING
EC ELECTRICAL CONTRACTOR
ELEC ELECTRIC, ELECTRICAL
ELEV ELEVATOR
ELU EMERGENCY LIGHTING UNIT
EM EMERGENCY
EMS ENERGY MANAGEMENT SYSTEM
EMT ELECTRICAL METALLIC TUBING
EP ELECTRIC PNEUMATIC
EQUIP EQUIPMENT
EWC ELECTRIC WATER COOLER
EXIST EXISTING
EXH EXHAUST
EXP EXPLOSION PROOF
FA FIRE ALARM
FABP FIRE ALARM BOOSTER POWER
SUPPLY PANEL
FACP FIRE ALARM CONTROL PANEL
FCU FAN COIL UNIT
FIXT FIXTURE
FLR FLOOR
FLUOR FLUORESCENT
FU FUSE
FUDS FUSED SAFETY DISCONNECT SWITCH
GA GAUGE
GAL GALLON
GALV GALVANIZED
GC GENERAL CONTRACTOR
GEN GENERATOR
GFI GROUND FAULT CIRCUIT INTERRUPTER
GFP GROUND FAULT PROTECTOR
GND GROUND
GRS GALVANIZED RIGID STEEL (CONDUIT)
GYP BD GYPSUM BOARD
HOA HANDS-OFF-AUTOMATIC SWITCH
HORIZ HORIZONTAL
HP HORSEPOWER
HPF HIGH POWER FACTOR
HT HEIGHT
HTG HEATING
HTR HEATER
HV HIGH VOLTAGE
HVAC HEATING, VENTILATING AND AIR
CONDITIONING
IC INTERRUPTING CAPACITY
IG ISOLATED GROUND
IMC INTERMEDIATE METAL CONDUIT
INCAND INCANDESCENT
IR INFRARED
I/W INTERLOCK WITH
J-BOX JUNCTION BOX
KV KILOVOLT
KVA KILOVOLT-AMPERE
KVAR KILOVOLT-AMPERE REACTIVE
KW KILOWATT
KWH KILOWATT HOUR
LOC LOCATE OR LOCATION
LT LIGHT
LTG LIGHTING
LTNG LIGHTNING
LV LOW VOLTAGE
MAX MAXIMUM
MAG.S MAGNETIC STARTER
M/C MOMENTARY CONTACT
MC MECHANICAL CONTRACTOR
ELECTRICAL ABBREVIATIONS LIST
CONDUIT SHOWN WITHOUT SLASH MARKS SHALL
CONTAIN 1 # 12 CONDUCTOR PER PHASE, NEUTRAL, AND
GROUND IN 1/2" CONDUIT UNLESS SPECIFIC EQUIPMENT
REQUIRES A DIFFERENT SIZE.
CONDUIT SHOWN SHALL CONTAIN 1 # 10 CONDUCTOR
PER PHASE IN ELECTRICAL CODE SIZED MINIMUM
CONDUIT UNLESS A CONDUCTOR AND CONDUIT SIZE IS
SHOWN ADJACENT.
HOME RUN TO BRANCH CIRCUIT PANELBOARD. THE
PANELBOARD DESIGNATION IS SHOWN ADJACENT TO
THE HOME RUN ARROW AS A NUMERATOR AND THE
CIRCUIT DESIGNATION IS SHOWN AS THE DENOMINATOR.
CIRCUIT BREAKER SIZES (AMPS/NUMBER OF POLES) ARE
SHOWN IN THE PANELBOARD SCHEDULE WITH THE
CORRESPONDING PANELBOARD AND CIRCUIT
DESIGNATION. EXAMPLE: HOME RUN TO PANELBOARD
P4N-102; CIRCUITS 1, 3, 5. LONG TICKMARKS INDICATE
NUMBER OF PHASE CONDUCTORS. SHORT TICK MARKS
INDICATE NUMBER OF GROUNDED CONDUCTORS
(NEUTRALS). AN EQUIPMENT GROUNDING CONDUCTOR
IS NOT INDICATED BUT SHALL BE INSTALLED. NUMBER
OF ARROWHEADS INDICATE NUMBER OF CIRCUITS.
LIGHTING SYMBOLS
ELECTRICAL SYMBOL LEGEND
TIME CONTROL SWITCH
TIME DELAY SWITCH
TIMER SWITCH
KEYED SWITCH
4-WAY SWITCH
3-WAY SWITCH
SINGLE POLE SWITCH
KEY NOTE (SEE SCHEDULE)
NUMBER OF SHEET WHERE DETAIL APPEARS
NUMBER OF DETAIL ON SHEET
REVISION NUMBER - SHOWN ON PLANS
ROOM NAME AND NUMBER
EXISTING TO BE DEMOLISHED
AREA NOT IN CONTRACT
CONDUIT IN CEILING, FLOOR OR WALL AS REQUIRED BY
FIELD CONDITIONS
CONDUIT IN FLOOR
P4N-102 1, 3, 5
#10
EXISTING TO REMAIN
EXISTING TO BE REMOVED
NEW
MCB MAIN CIRCUIT BREAKER
MCC MOTOR CONTROL CENTER
MDC MAIN DISTRIBUTION CENTER
MDP MAIN DISTRIBUTION PANEL
MFR MANUFACTURER
MFS MAIN FUSED DISCONNECT SW
MH MANHOLE
MIC MICROPHONE
MIN MINIMUM
MISC MISCELLANEOUS
MLO MAIN LUGS ONLY
MMS MANUAL MOTOR STARTER
MOA MULTIOUTLET ASSEMBLY
MSP MOTOR STARTER PANELBOARD
MSBD MAIN SWITCHBOARD
MT MOUNT
MT.C EMPTY CONDUIT
MTS MANUAL TRANSFER SWITCH
MTR MOTOR, MOTORIZED
N.C. NORMALLY CLOSED
NEC NATIONAL ELECTRICAL CODE
NEMA NATIONAL ELECTRICAL
MANUFACTURER'S ASSOCIATION
NFDS NON-FUSED SAFETY DISCONNECT
SWITCH
NIC NOT IN CONTRACT
NL NIGHT LIGHT
N.O. NORMALLY OPEN
NPF NORMAL POWER FACTOR
NTS NOT TO SCALE
OH OVERHEAD
OL OVERLOADS
PA PUBLIC ADDRESS
PB PULL BOX OR PUSHBUTTON
PE PNEUMATIC ELECTRIC
PED PEDESTAL
PF POWER FACTOR
PH PHASE
PIV POST INDICATING VALVE
PNL PANEL
PP POWER POLE
PR PAIR
PRI PRIMARY
PROJ PROJECTION
PRV POWER ROOF VENTILATOR
PT POTENTIAL TRANSFORMER
PVC POLYVINYL CHLORIDE (CONDUIT)
PWR POWER
QUAN QUANTITY
RCPT RECEPTACLE
REQD REQUIRED
RM ROOM
RSC RIGID STEEL CONDUIT
RTU ROOF TOP UNIT
SABC SMALL APPLICANCE BRANCH
CIRCUIT
SC SURFACE CONDUIT
SEC SECONDARY
SHT SHEET
SIM SIMILAR
S/N SOLID NEUTRAL
SPEC SPECIFICATION
SPKR SPEAKER
SP SPARE
SPD SURGE PROTECTION DEVICE
SR SURFACE RACEWAY
SS STAINLESS STEEL
SSW SELECTOR SWITCH
S/S STOP/START PUSHBUTTONS
STA STATION
STD STANDARD
SURF SURFACE MOUNTED
SW SWITCH
SWBD SWITCHBOARD
SYM SYMMETRICAL
SYS SYSTEM
TEL TELEPHONE
TEL/DATA TELEPHONE/DATA
TERM TERMINAL
TL TWIST LOCK
TR TAMPER RESISTANT
T-STAT THERMOSTAT
TTC TELEPHONE TERMINAL CABINET
TV TELEVISION
TVTC TELEVISION TERMINAL CABINET
TYP TYPICAL
UC UNDER COUNTER
UE UNDERGROUND ELECTRICAL
UG UNDERGROUND
UH UNIT HEATER
UNO UNLESS NOTED OTHERWISE
UT UNDERGROUND TELEPHONE
UTIL UTILITY
UV ULTRAVIOLET
V VOLT
VA VOLT-AMPERES
VDT VIDEO DISPLAY TERMINAL
VERT VERTICAL
VFD VARIABLE FREQUENCY DRIVE
VOL VOLUME
W WATT
W/ WITH
WG WIRE GUARD
WH WATER HEATER
W/O WITHOUT
WP WEATHERPROOF
XFMR TRANSFORMER
XFR TRANSFER
∠ ANGLE
@ AT
▲ DELTA
' FEET
" INCHES
# NUMBER
Ø PHASE
C CENTER LINE
P PLATE
WALL-MOUNTED FIXTURES, TYPICAL
ABSENCE OF A SWITCH ID INDICATES FIXTURE IS CONTROLLED BY THE
ONLY SWITCH IN THE SPACE. AN "nl" IN PLACE OF THE SWITCH ID
INDICATES NIGHT LIGHT (UNSWITCHED).
S3 1d
LIGHTING FIXTURES, TYPICAL, RECTANGULAR
(VARIOUS SYMBOLS)
FILLED CIRCLES INDICATE RECESSED,
OPEN CIRCLES INDICATE SURFACE-MOUNTED
DIAGONAL LINE INDICATES LENSED
OUTER DOTS INDICATE SUSPENDED
LIGHTING FIXTURES, TYPICAL, ROUND
CENTER DOT INDICATES PENDANT
DIAGONAL LINE INDICATES LENSED
CHEVRON INDICATES WALL WASH
STRIP FIXTURE
DIRECTIONAL LIGHT, TRACK, FLOOD
LINEAR LIGHT, TAPE LIGHT
(E)
WIRING
CONSTRUCTION PHASING
(TYPICAL ALL SYMBOLS AND EQUIPMENT)
MISCELLANEOUS
LIGHTING TAGS
TOP VALUE: FIXTURE TYPE ID
BOTTOM VALUE: LOWERCASE LETTER: SWITCH ID
BOTTOM VALUE: NUMBER(S): CIRCUIT NUMBER
OAOAOA
517 EAST CONGRESS STREET
SAVANNAH, GEORGIA 31401
tel 912.234.6318 fax 912.236.8414 cogdellmendrala.com
SHEET TITLE
SHEET
KEY PLAN
TRUE NORTH PROJECT NORTHSCALE
COPYRIGHT © 2025 COGDELL & MENDRALA ARCHITECTS, PC
Cogdell Mendrala Architects
N.T.S.
SCOPE OF WORK
WALDO PAFFORD
ELEMENTARY SCHOOL
PROJECT NO:
DRAWN BY:
DATE:
SCALE:
OWNER NO:
FACILITY NO.: 689-0100
2550 W 15TH ST, HINESVILLE, GA 31313
SEAL
STRUCTURAL ENGINEERS
SAUSSY ENGINEERING
400 JOHNNY MERCER BLVD, SUITE E,
SAVANNAH, GA 31410
M.E.P. ENGINEERS
METHOD ENGINEERING GROUP
1020 DRAYTON STREET, SUITE 101,
SAVANNAH, GA 31401
/1
/2
:0 :0
P
M A u to d e s k D o c s /2
L C
S S
C a n o p y R e p a ir /2
-L C
S S
C a n o p y R e p a ir -M
E P
-R V
.r v t
As indicated
E1.01
ELECTRICAL
PLAN
CONSTRUCTION
DOCUMENTS
CGS
JANUARY 2026
2026-10
LCSS CANOPY
REPAIR
LIBERTY COUNTY SCHOOL
SYSTEM
VOLUME II - WALDO
PAFFORD
ELEMENTARY
SCHOOL
ELECTRICAL GENERAL NOTES
A THE SYMBOLS AND ABBREVIATIONS SHOWN ON THIS SHEET MAY OR MAY NOT BE
USED IN THIS SET OF DRAWINGS.
B COORDINATE LOCATIONS OF DEVICES WITH ARCHITECTURAL ELEVATIONS AND
DETAILS. ARCHITECTURAL ELEVATIONS AND DETAILS TAKE PRECEDENCE OVER
LOCATIONS SHOWN ON ELECTRICAL DRAWINGS.
C PROVIDE CABLE OR CONDUIT AND WIRE AS REQUIRED TO ACHIEVE CIRCUITING
SHOWN. SIZE CONDUCTORS PER NEC AMPACITY AND WIRE FILL CRITERIA. PROVIDE
DEDICATED NEUTRAL AND GROUND CONDUCTORS FOR CIRCUITING ,UNLESS NOTED
OTHERWISE. INCREASE BRANCH CIRCUIT AND/OR FEEDER CONDUCTORS INCLUDING
EQUIPMENT GROUNDING CONDUCTORS PROPORTIONALLY FOR NO MORE THAN 3%
VOLTAGE DROP ON BRANCH CIRCUITS AND 2% ON FEEDERS PER ENERGY CODE.
D IT IS THE RESPONSIBILITY OF THIS CONTRACTOR TO COORDINATE INSTALLATION OF
ELECTRICAL SYSTEMS AND THOSE REQUIRING ELECTRICAL CONNECTIONS TO
MAINTAIN NEC REQUIRED CLEARANCES, INCLUDED BY NOT LIMITED TO AREAS ABOVE
ACCESSIBLE CEILINGS.
E COORDINATE WITH OTHER TRADES FOR PROPER INSTALLATION OF EQUIPMENT.
CONSULT THE DRAWINGS OF OTHER TRADES OR CRAFTS TO AVOID CONFLICTS WITH
EQUIPMENT, ETC. CONFLICTS SHALL BE RESOLVED PRIOR TO ROUGH-IN AND AT NO
ADDITIONAL COST TO THE OWNER.
F LEAVE THE SITE CLEAN AND READY FOR OCCUPANCY. REMOVE DIRT, DEBRIS, EMPTY
CARTONS, TOOLS, CONDUIT AND WIRE SCRAPS AND MISCELLANEOUS SPARE
EQUIPMENT AND MATERIALS USED IN THIS DIVISION OF THE WORK DURING
CONSTRUCTION. COMPONENTS SHALL BE FREE OF DUST, GRIT AND FOREIGN
MATERIALS AND LEFT AS NEW BEFORE FINAL ACCEPTANCE OF WORK.
G CONDUCTORS OPERATING AT 50 VOLTS OR GREATER SHALL BE IN RACEWAY.
RACEWAY WITHIN THE STRUCTURE ABOVE THE FLOOR SLAB SHALL BE METAL.
RACEWAY BELOW THE FLOOR SLAB AND UNDERGROUND RACEWAY OUTSIDE THE
STRUCTURE SHALL BE PVC.
H PERFORM WORK TO COMPLY WITH THE STANDARD PRACTICES FOR GOOD
WORKMANSHIP PUBLISHED BY NATIONAL ELECTRICAL CONTRACTORS ASSOCIATION
(NECA). COMPLY WITH THE LATEST ENFORCED EDITION OF THE NATIONAL
ELECTRICAL CODE (NEC), LOCAL CODES, AMENDMENTS, AND ORDINANCES.
I ELECTRICAL WORK SHALL BE PERFORMED UNDER THE SUPERVISION OF A LICENSED
MASTER ELECTRICIAN. PROCURE PERMITS AND LICENSES AND PAY FEES
ASSOCIATED WITH THIS WORK.
J MATERIALS FURNISHED FOR THIS PROJECT SHALL BE NEW, COMMERCIAL GRADE,
FREE OF DEFECTS, AND LISTED BY A NATIONALLY RECOGNIZED TESTING
LABORATORY UNO.
K PROVIDE COMPLETE OPERATION & MAINTENANCE MANUAL INCLUDING APPROVED
SUBMITTAL DRAWINGS, WARRANTY INFORMATION FOR PRODUCT SUPPLIED,AND
MANUFACTURER'S OPERATION AND MAINTENANCE INSTRUCTIONS.
ELECTRICAL REMODEL NOTES
A BRANCH CIRCUITING INDICATED ON PLANS AND SCHEDULES IS BASED UPON EXISTING
PLANS AND SITE OBSERVATION, CONTRACTOR TO FIELD VERIFY.
B PROVIDE TYPED CIRCUIT BOARD DIRECTORIES TO REFLECT AS-CONSTRUCTED
CONDITIONS. FIELD VERIFY DURING CONSTRUCTION AND REVISE ACCORDINGLY.
C PROVIDE NECESSARY DEMOLITION TO FACILITATE NEW CONSTRUCTION WORK
ASSOCIATED WITH THIS PROJECT. COORDINATE OUTAGES WITH OWNER MINIMUM 72
HOURS IN ADVANCE. OWNER RETAINS RIGHT TO FIRST SALVAGE. PROVIDE DISPOSAL
OF REMOVED MATERIAL. MAINTAIN CIRCUIT CONTINUITY AS REQUIRED.
D IT IS THE INTENT OF THESE DIAGRAMMATIC DRAWINGS TO PROVIDE THE PROJECT
SCOPE INCLUDING, BUT NOT LIMITED TO PHASED DEMOLITION AND NEW
CONSTRUCTION. EXISTING INFORMATION INDICATED ON THESE PLANS DOES NOT
REPRESENT ALL EXISTING CONDITIONS. THIS CONTRACTOR SHALL BECOME FAMILIAR
WITH EXISTING CONDITIONS, SCOPE OF PHASING, AND PROJECT INTENT PRIOR TO BID
SUBMISSION.
E PROVIDE CUTTING, PATCHING, AND RESTORATION OF FINISHES NECESSARY FOR
WORK SURFACES DAMAGED BY THIS WORK. SPACES AROUND CONDUITS PASSING
THROUGH FLOORS AND WALLS SHALL BE NEATLY PATCHED AND FINISHED TO MATCH
NEW/EXISTING. STRUCTURAL MEMBERS SHALL NOT BE CUT OR PENETRATED IN ANY
MANNER. THE SPACES AROUND THE CONDUITS SHALL BE SEALED TO PREVENT
ENTRANCE OF MOISTURE. PROVIDE FIRE STOPPING PER UL APPROVED METHODS.
F REMOVE ABANDONED WIRING COMPLETE. AT CONTRACTORS OPTION, UTILIZE
EXISTING ABANDONED RACEWAY TO EXTENT AVAILABLE. EXPOSED ABANDONED
RACEWAY SHALL BE REMOVED.
G COORDINATE WORK IN PHASES WITH GENERAL CONTRACTOR AND OWNER TO
FACILITATE DEMOLITION AND NEW CONSTRUCTION.
H REMOVE ELECTRICAL RELATED EQUIPMENT (I.E JUNCTION BOXES, RECEPTACLES,
SWITCHES, DEVICES, ETC... ) AFFECTED/ABANDONED AS A RESULT OF DEMOLITION
AND NEW CONSTRUCTION.
KEYNOTES
1 CONNECT NEW EXTERIOR FIXTURES TO EXISTING EXTERIOR LIGHTING CIRCUIT.
NEW FIXTURES SHALL BE CONTROLLED WITH EXISTING EXTERIOR LIGHT
FIXTURES. ELECTRICAL RACEWAY AND…