25-8378_-_Exhibit_M_-_Sun_N_Fun_IWF_PLE_Drawings_-_100%_Bid_Set.pdf
PDF 4 MB Posted
- Attached to
- Sun-n-Fun Interactive Water Features Renovations
- Solicitation number
- 25-8378
- Issued by
- Collier County, Florida
About this file
The provided file is a set of electrical engineering drawings (PLE series) for the Sun-N-Fun Lagoon 2024 Renovations project located in Naples, Florida, specifically focusing on the Interactive Water Features (IWF) electrical systems. The drawings, prepared by Water Technology, Inc. on November 8, 2024, detail electrical demolition plans, new electrical layouts, equipment connection schedules, wiring schematics, and electrical details for Pool E and the associated mechanical room (PB1). The documents cover comprehensive electrical work including removing existing equipment, installing new pumps, water features, UV disinfection systems, flow meters, autofill controllers, and associated electrical infrastructure.
The electrical design follows the 2020 National Electrical Code and 2023 Florida Building Code, with specific attention to pool electrical requirements, equipotential bonding, and safety standards. The project involves replacing existing pumps with new 20 HP filtration/activity pumps, installing variable frequency drives (VFDs), implementing new control systems, and updating electrical panels and circuits. The electrical work is part of a broader renovation of the Sun-N-Fun Lagoon interactive water features, with careful consideration given to existing infrastructure, control integration, and compliance with national and local electrical and safety regulations. The drawings provide detailed specifications for conduit routing, wire sizing, equipment connections, and system interconnections to ensure a comprehensive and code-compliant electrical installation.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
1P 2P 3P 4P 1P, 1W 1P, 2W 2P, 2W 2P, 3W 3P, 2W 3P, 3W 3P, 4W 4P, 4W A
AC
AF
AFF
AFG
AIC
ANSI
AL
AS
AT
ARCH
ATS
A / V
AWG
B
BF
BFF
BFG
BLDG
C
CAM
CAT
CATV
CB
CKT
CLG
CO
CT
CU
CL
DC
DR
DISC
DW
DWG
E
EC
EMT
ETR
ER
ERL
ERLD
EWC
EX
FA
FLA
FO
FPC
GC
GFCI
GFPE
GND
GRC
HH
HP
HVAC
HZ
ISP
IT
JB
KVA
KVAR
KW
LP
LS
LTG
LV
MC
MCA
MCC
MDP
MISC
MH
MLO
MTD
MTG
MTS
MW
MV
N / A
NC
NEC
NIC
NO
NTS
OSP
P
PB
PC
PH
PNL
PP
PR
PRI
PROJ
PVC
REC
RE / CKT
REF
RSC
RVS
SC
SEC
SN
SP
SS
ST
STP
SUSP
SW
SWBD
T
TBB
TC
TCI
TELE / DATA
TEL
TELECOM
TGP
TMGB
TP
TYP
UG
UTP
UOI
V W
WA
WAP
WP
XFMR
XR
XV
Y
ZAM
- KILOVOLT AMPERE REACTIVE
- KILOWATT
- LIGHTING PANEL
- LIMIT SWITCH
- LIGHTING
- LOW VOLTAGE
- MECHANICAL CONTRACTOR
- MINIMUM CIRCUIT AMPS
- MOTOR CONTROL CENTER
- MAIN DISTRIBUTION PANEL
- MISCELLANEOUS
- MANHOLE
- MAIN LUGS ONLY
- MOUNTED
- MOUNTING
- MANUAL TRANSFER SWITCH
- MICROWAVE
- MEDIUM VOLTAGE
- NOT APPLICABLE
- NORMALLY CLOSED
- NATIONAL ELECTRIC CODE
- NOT IN CONTRACT
- NORMALLY OPEN
- NUMBER
- NOT TO SCALE
- OUTSIDE PLANT
- POLE
- PULL BOX
- PLUMBING SYSTEM CONTRACTOR
- PHASE
- PANEL OR PANELBOARD
- POWER PANEL
- PAIR
- PRIMARY
- PROJECTOR
- POLYVINYL CHLORIDE
- RECESSED
- REUSE EXISTING CIRCUIT
- REFRIGERATOR
- RIGID STEEL CONDUIT
- REDUCED VOLTAGE STARTER
- SECURITY CONTRACTOR
- SECONDARY
- SOLID NEUTRAL
- SPARE
- STAINLESS STEEL
- SHUNT TRIP
- SHIELDED TWISTED PAIR
- SUSPENDED
- SWITCH
- SWITCHBOARD
- TAMPER RESISTANT SAFETY RECEPTACLE
- TELECOMMUNICATIONS BONDING BACKBONE
- TELEPHONE CABINET
- TELECOMMUNICATIONS CABLING INSTALLER
- TELEPHONE / DATA
- TELEPHONE
- TELECOMMUNICATIONS
- TELECOMMUNICATIONS GROUNDING BUSBAR
- TELECOMMUNICATIONS MAIN GROUNDING BUSBAR
- TWISTED PAIR
- TYPICAL
- UNDERGROUND
- UNSHIELDED TWISTED PAIR
- UNLESS OTHERWISE INDICATED
- VOLT
- WATT
- WASHER
- WIRELESS ACCESS POINT
- WEATHERPROOF
- TRANSFORMER
- XRAY
- XRAY VIEWER
- WYE
- ZONE ADAPTER MODULE
- ONE POLE
- TWO POLE
- THREE POLE
- FOUR POLE
- ONE POLE, ONE WIRE
- ONE POLE, TWO WIRE
- TWO POLE, TWO WIRE
- TWO POLE, THREE WIRE
- THREE POLE, TWO WIRE
- THREE POLE, THREE WIRE
- THREE POLE, FOUR WIRE
- FOUR POLE, FOUR WIRE
- AMPERE
- ALTERNATING CURRENT
- AMPERE FRAME
- ABOVE FINISHED FLOOR
- ABOVE FINISHED GRADE
- AMPERE INTERRUPTING CAPACITY
- AMERICAN NATIONAL STANDARDS INSTITUTE
- ALUMINUM
- AMP SWITCH
- AMP TRIP
- ARCHITECT
- AUTOMATIC TRANSFER SWITCH
- AUDIO VISUAL
- AMERICAN WIRE GRADE
- PEDESTAL MOUNTED ON BENCH TOP
- BELOW FLOOR
- BELOW FINISHED FLOOR
- BELOW FINISHED GRADE
- BUILDING
- CONDUIT
- CAMERA
- CATALOG
- CABLE TELEVISION
- CIRCUIT BREAKER
- CIRCUIT
- CEILING MOUNTED
- COPIER
- CURRENT TRANSFORMER
- COPPER
- CENTERLINE
- DIRECT CURRENT
- DRYER
- DELTA
- DISCONNECT
- DISHWASHER
- DRAWING
- EMERGENCY
- ELECTRICAL CONTRACTOR
- ELECTRIC METALLIC TUBING
- EXISTING TO REMAIN
- EXISTING TO BE REMOVED
- EXISTING TO BE RELOCATED
- RELOCATED EQUIPMENT'S NEW LOCATION
- ELECTRIC WATER COOLER
- EXISTING
- FIRE ALARM
- FULL LOAD AMPS
- FIBER OPTIC
- FIRE PROTECTION CONTRACTOR
- GENERAL CONTRACTOR
- GROUND FAULT CIRCUIT INTERRUPTER
- GROUND FAULT PROTECTION EQUIPMENT
- GROUND
- GALVANIZED RIGID CONDUIT
- HANDHOLE
- HORSEPOWER
- HEATING, VENTILATING, AND AIR CONDITIONING
- HERTZ (CYCLE) PER SECOND
- INSIDE PLANT
- INFORMATION TECHNOLOGY
- JUNCTION BOX
- KILOVOLT AMPERE
ELECTRICAL ABBREVIATIONS
EQUIPMENT AND PANELBOARDS
METER
CURRENT TRANSFORMER
CABINET
TRANSFORMER
- (X) INDICATES
DESIGNATION
BRANCH PANELBOARD
- SURFACE MOUNTED
- (X) INDICATES
DESIGNATION
BRANCH PANELBOARD
- RECESSED MOUNTED
- (X) INDICATES
DESIGNATION
DISTRIBUTION PANELBOARD
- (X) INDICATES
DESIGNATION
CT
M
X
X
X
X
X
X
X
X
WAVE POOL CONTROL PANEL
WP
CP
POOL EQUIPMENT
PANEL/CONTROL DEVICE
- (X) INDICATES
DESIGNATIONX
X
XXX
X DETAIL REFERENCE
- TOP DESIGNATES DETAIL NUMBER
- BOTTOM DESIGNATES SHEET NUMBER
GENERAL SYMBOLS
LIGHTING FIXTURES
12 VOLT POOL LIGHT
- (X) INDICATES TRANSFORMER
POOL IS SERVED FROM
POOL LIGHTING TRANSFORMER
- SEE SPECIFICATION SECTION 26 27 26
- (X) INDICATES:
TRANSFORMER DESIGNATION
LT
LT-X X
MOTOR STARTERS AND DISCONNECTS
MOTOR CONTROLLER
- MANUAL
MAGNETIC MOTOR STARTER FUSED DISCONNECT
SWITCH
NON - FUSED
DISCONNECT SWITCH
MAGNETIC COMBINATION MOTOR
STARTER
M
F
INDICATES SPACE FOR VARIABLE FREQUENCY
DRIVE (VFD) MOTOR CONTROLLER.
DESIGNATION OF POOL MOTOR BEING
CONTROLLED CLEARANCE WORKING SPACE IN
FRONT OF ANY OBSTRUCTIONS FOR THE
WIDTH AND DEPTH OF THIS SPACE, FROM
FLOOR TO 6'-6" AFF OR TO THE HEIGHT OF
THE VFD, WHICHEVER IS HIGHER.
P1D
INDICATES SPACE FOR REDUCED VOLTAGE
STARTER (RVS) MOTOR CONTROLLER.
DESIGNATION OF POOL MOTOR BEING
CONTROLLED CLEARANCE WORKING SPACE IN
FRONT OF ANY OBSTRUCTIONS FOR THE
WIDTH AND DEPTH OF THIS SPACE, FROM
FLOOR TO 6'-6" AFF OR TO THE HEIGHT OF
THE RVS, WHICHEVER IS HIGHER.
P1D
ELECTRICAL BOX
- FLOOR MOUNTED
- POKE THRU
- OUTLET TYPES REQUIRED
AT EACH BOX AS INDICATED
ON DRAWINGS
JUNCTION BOX
PULL BOX
HANDHOLE
MANHOLE
RACEWAYS AND BOXES
CABLE TAP BOX
MULTI-OUTLET RACEWAY
ASSEMBLY
- WALL MOUNTED 1'-6"
AFF, UOI
ELECTRICAL BOX
- FLOOR MOUNTED
- FLUSH
- OUTLET TYPES REQUIRED AT
EACH BOX AS INDICATED ON
DRAWINGS
BUSWAY
- RATING AND TYPE AS
INDICATED ON DRAWINGS
F
P
CTB
PB
HH
DEAD FRONT GFI
PROTECTIVE DEVICE
- (X) INDICATES CIRCUIT
NUMBER
GFIXOFF / BACKWASH /
FILTRATION SWITCH
Y X
WIRING DEVICES
DUPLEX RECEPTACLE
- MOUNTED 1'-6" AFF, UOI
- (X) INDICATES CIRCUIT NUMBER
(PANEL BOUNDARY AS
INDICATED ON DRAWINGS)
- (Y) INDICATES TYPE:
(GFCI) GROUND FAULT
CIRCUIT INTERRUPTING
(WP) WEATHERPROOF
(WR) WEATHER RESISTANT
MOTOR CONNECTION
- INDICATES MOTOR DESIGNATION
LOAD SIZE VOLTAGE / PHASE
SPECIAL PURPOSE OUTLET
- (X) INDICATES:
SPO DESIGNATIONX
PERMANENTLY-INSTALLED SWIMMING POOLS - POOL ELECTRICAL CONTRACTOR
1. ELECTRICAL INSTALLATIONS ASSOCIATED WITH PERMANENTLY-INSTALLED POOLS MUST COMPLY WITH NEC 680.20, 2020 EDITION.
2. EQUIPOTENTIAL BONDING: PER NEC 680.26. ALL METAL PARTS OF A PERMANENTLY-INSTALLED POOL STRUCTURE MUST BE BONDED TOGETHER WITH REBAR OR A #8 AWG SOLID COPPER CONDUCTOR. THIS INCLUDES CONCRETE-REBAR ASSOCIATED WITH POOL SHELL
CONSTRUCTION.
3. EQUIPOTENTIAL BONDING PERIMETER - POOL DECK: MUST EXTEND 3'-0" FROM BEYOND THE INSIDE WALL OF THE POOL. THE EQUIPOTENTIAL GRID MAY CONSIST OF REBAR OR A #8 AWG SOLID COPPER CONDUCTOR. POOL REINFORCING STEEL SHALL BE BONDED TO THE EQUIPOTENTIAL GRID AT A MINIMUM OF FOUR POINTS UNIFORMLY SPACED AROUND THE PERIMETER OF THE POOL.
4. METALLIC PARTS AND FITTINGS OF THE POOL STRUCTURE ARE PARTS TO BE BONDED TOGETHER IN ACCORDANCE WITH NEC ARTICLE 680.26.
5. METAL PARTS OF ELECTRICAL EQUIPMENT ASSOCIATED WITH WATER CIRCULATING SYSTEM MUST BE BONDED TOGETHER.
6. EXCEPTIONS: FIXED METAL PARTS GREATER THAN 5'-0" AWAY FROM POOL HORIZONTALLY, OR 12'-0" AWAY FROM POOL VERTICALLY, OR SEPARATED FROM POOL BY A BARRIER ARE NOT REQUIRED TO BE BONDED TO THE EQUIPOTENTIAL GRID.
7. REFER TO DRAWINGS, DETAILS, AND SPECIFICATIONS FOR AREAS OF DEMOLITION/CONSTRUCTION REQUIRING EQUIPOTENTIAL
BONDING PROVISIONS.
CONDUCTORS AND WIRING DEVICES - POOL ELECTRICAL CONTRACTOR
1. POOL ELECTRICAL CONTRACTOR SHALL FURNISH ALL CONDUCTORS, UNLESS OTHERWISE NOTED OR DIRECTED BY THE PROJECT MANAGER. ALL CONDUCTORS SHALL BEAR THE APPROVED UNDERWRITERS LABORATORIES, INC, U.L./ETL SEAL.
2. CONDUCTORS SHALL BE COLOR CODED AS REQUIRED BY SPECIFICATIONS.
3. NO SPLICING OF CONDUCTORS WITHIN RUNS OF CONDUIT WILL BE PERMITTED.
GENERAL PROJECT NOTES - POOL ELECTRICAL CONTRACTOR
1. NOT ALL SYMBOLS ON ELECTRICAL SYMBOLS SHEET ARE USED.
2. ALL MOUNTING HEIGHTS ARE TO THE CENTERLINE OF THE DEVICE BACKBOX UNLESS NOTED OTHERWISE.
3. ALL ELECTRICAL SYSTEMS INSTALLATIONS SHALL COMPLY WITH NFPA 70 (NATIONAL ELECTRICAL CODE, 2020 EDITION) AS WELL AS ALL
APPLICABLE LOCAL CODES.
4. POOL ELECTRICAL CONTRACTOR SHALL COORDINATE ALL WORK WITH OTHER TRADES PRIOR TO AND DURING INSTALLATION.
5. POOL ELECTRICAL CONTRACTOR SHALL NOT CUT, DRILL, OR IN ANY OTHER MANNER ALTER ANY STRUCTURAL MEMBER WITHOUT PRIOR
WRITTEN APPROVAL FROM THE STRUCTURAL ENGINEER.
6. POOL ELECTRICAL CONTRACTOR SHALL, BEFORE SUBMITTING PROPOSAL OR BID, EXAMINE ALL DRAWINGS AND SPECIFICATIONS RELATING TO THIS PROJECT, THE AMOUNT OF SPACE AVAILABLE FOR ELECTRICAL EQUIPMENT, THE PROJECT SITE, THE REQUIREMENTS TO CORRELATE THE ELECTRICAL WORK WITH ALL OTHER TRADES, AND THE TIME SCHEDULE NECESSARY TO PERFORM THAT WORK.
7. POOL ELECTRICAL CONTRACTOR SHALL, AFTER EXAMINATION OF ALL PLANS AND SPECIFICATIONS, INCLUDE ALL COSTS NECESSARY FOR ALTERATION OF, MODIFICATION OF, OR ADDITIONS TO THE ELECTRICAL SYSTEMS NECESSARY FOR A COMPLETE AND APPROVED INSTALLATION IN ALL ASPECTS. IT IS THE INTENT THAT ALL COSTS REQUIRED BE INCLUDED IN THE BID OF THIS TRADE.
8. POOL ELECTRICAL CONTRACTOR SHALL BASE THEIR PROPOSAL AND BID UPON THE EQUIPMENT AS SCHEDULED OR SPECIFIED, USING THE MANUFACTURERS AND MODEL NUMBERS AS CALLED FOR IN THE SPECIFICATIONS AND SCHEDULED ON THE DRAWINGS. IF MORE THAN ONE MANUFACTURER OF EQUIPMENT IS SPECIFIED, ANY ONE OF THE MANUFACTURERS OF EQUIPMENT MAY BE USED IN THIS CONTRACTOR'S
PROPOSAL.
9. POOL ELECTRICAL CONTRACTOR TO NOTIFY THE POOL DESIGN ENGINEER, IN WRITING, OF ANY DISCREPANCIES FOUND BETWEEN THESE ELECTRICAL PLANS AND OTHER ENGINEERING PLANS, ARCHITECTURAL PLANS, OR EXISTING FIELD CONDITIONS PRIOR TO FINAL BID PRICE
OR PERMITTING.
10. IN CASE OF DISPUTE OR DOUBT AS TO INTENT OF DRAWINGS OR SPECIFICATIONS, POOL ELECTRICAL CONTRACTOR SHALL CONTACT POOL ELECTRICAL ENGINEER AND OBTAIN WRITTEN CLARIFICATION PRIOR TO PROCEEDING WITH ANY BID OR CONSTRUCTION SCOPE INVOLVED.
11. POOL ELECTRICAL CONTRACTOR IS RESPONSIBLE FOR ORDERING ALL MATERIALS IN SUFFICIENT TIME TO AVOID DELAYING THE COMPLETION OF THE PROJECT. DELAY IN DELIVERIES SHALL NOT BE CONSIDERED A JUSTIFIABLE REASON FOR SUBMISSION OF
SUBSTITUTE MATERIALS.
12. ALL NOTES ON THE DRAWINGS INDICATED AS "TYPICAL" SHALL APPLY TO THE ENTIRE PROJECT, WHETHER OR NOT THE NOTES WRITTEN
ARE SPECIFICALLY INDICATED ON EACH DRAWING.
ELECTRICAL GENERAL NOTES
CODES, STANDARDS AND REGULATIONS:
POOL ELECTRICAL CONTRACTOR SHALL REVIEW AND BECOME FAMILIAR WITH ALL LOCAL CODES AND STANDARDS LISTED BELOW. IF THE POOL ELECTRICAL CONTRACTOR IDENTIFIES CONFLICTS BETWEEN THE CODE REQUIREMENTS AND THE PLANS OR SPECIFICATONS THEY SHALL
IMMEDIATELY ALERT THE POOL ELECTRICAL ENGINEER.
CODE JURISDICTION
USA / NAPLES / FL / COLLIER COUNTY
HEALTH & SAFETY CODE:
FLORIDA BUILDING CODE - BUILDING 8TH EDITION (2023): SECTION 454: SWIMMING POOLS AND BATHING PLACES (PUBLIC AND PRIVATE)
BUILDING CODES:
2023 FLORIDA BUILDING CODE
2020 NATIONAL ELECTRICAL CODE (NATIONAL FIRE PROTECTION CODE - NFPA CHAPTER 70)
ACCESSIBILITY STANDARDS AND REGULATIONS:
UNITED STATES:
2010 ADA STANDARDS FOR ACCESSIBLE DESIGN
World Leaders in Aquatic Planning, Design and Engineering
100 Park Avenue | Beaver Dam, WI 53916 t 920.887.7375 This Document and the ideas, renderings and other contents contained therein are the sole property of Water Technology, Inc. and may not be disseminated, copied, reproduced or otherwise used without prior written consent of Water Technology, Inc.
CONSULTANTS
PROJECT PHASE:
2300 Maitland Center Parkway Suite 210 Maitland, FL 32751 414.259.1500
DRAWINGS MUST BE
VIEWED AND PLOTTED
IN FULL COLOR.
S U
N -N
-F U
N L
A G
O O
N
R E
N O
V A
T
IO
N S
L iv in g st o n
R d
N a p le s, F L
PLE001.E
ELECTRICAL SYMBOLS,
ABBREVIATIONS, AND SHEET INDEX
ISSUE DATE: 11/08/2024
PROJECT NUMBER: 22567
DRAWN BY: JTO
CHECKED BY: RJJ
100% CONSTRUCTION DOCUMENTS
ELECTRICAL SYMBOLS AND ABBREVIATIONS
NOTE: NOT ALL SYMBOLS AND ABBREVIATIONS INDICATED HERE ARE USED IN DRAWINGS AND MAY NOT APPLY TO CURRENT PROJECT. ADDITIONAL SYMBOLS MAY BE INDICATED ON DRAWINGS.
ELECTRICAL SHEET INDEX - POOL E
PLE001.E ELECTRICAL SYMBOLS, ABBREVIATIONS, AND SHEET INDEX
ED110.E POOL E - IWF ELECTRICAL DEMOLITION PLAN
PLE110.E POOL E - IWF ELECTRICAL PLAN
PLE400.E PB1 - MECHANICAL ROOM ELECTRICAL PLAN
PLE501.E ELECTRICAL DETAILS
PLE601.E POOL E - ELECTRICAL WIRING SCHEMATIC
PLE701.E ELECTRICAL SCHEDULES
PLE702.E ELECTRICAL SCHEDULES
REVISION SCHEDULE
Number Description Date
Image
S
D01
D04
D03
D04
D03
D05
D06
(TYP.)
(TYP.)
D07 (TYP.)
EXISTING SPLASH PAD WET
DECK PLAY AREA
D08
EXISTING BURIED FIBERGLASS
COLLECTOR TANKS TO BE
REMOVED BY OTHERS. REFER
TO POOL PLAN SHEET D101.E
FOR ADDITIONAL INFORMATION.
EXISTING BURIED FIBERGLASS
COLLECTOR TANKS TO BE
REMOVED BY OTHERS. REFER
TO POOL PLAN SHEET D101.E
FOR ADDITIONAL INFORMATION.
D02
GENERAL DEMO NOTE
IT IS THE CONTRACTOR'S RESPONSIBILITY TO THOROUGHLY READ ALL DEMO
NOTES AND REVIEW ALONGSIDE THE KEYNOTES ON THE PLAN SHEETS. REFER
TO POOL AQUATICS DRAWINGS FOR ADDITIONAL DEMOLITION WORK AS PART
OF THE POOL SCOPE.
EXISTING WATER FEATURE, TO BE REMOVED
EXISTING SPRAY CAN TO BE REMOVED AND REPLACED WITH NEW
WATER FEATURE IN SAME LOCATION
EXISTING FLOOR DRAIN, TO BE REMOVED
- REFER TO SHEET D101.E AND PL130.E FOR ADDITIONAL INFORMATION
REGARDING EXISTING AND NEW WATER FEATURES
World Leaders in Aquatic Planning, Design and Engineering
100 Park Avenue | Beaver Dam, WI 53916 t 920.887.7375 This Document and the ideas, renderings and other contents contained therein are the sole property of Water Technology, Inc. and may not be disseminated, copied, reproduced or otherwise used without prior written consent of Water Technology, Inc.
CONSULTANTS
PROJECT PHASE:
2300 Maitland Center Parkway Suite 210 Maitland, FL 32751 414.259.1500
DRAWINGS MUST BE
VIEWED AND PLOTTED
IN FULL COLOR.
S U
N -N
-F U
N L
A G
O O
N
R E
N O
V A
T
IO
N S
L iv in g st o n
R d
N a p le s, F L
ED110.E
POOL E - IWF ELECTRICAL
DEMOLITION PLAN
ISSUE DATE: 11/08/2024
PROJECT NUMBER: 22567
DRAWN BY: JTO
CHECKED BY: RJJ
100% CONSTRUCTION DOCUMENTS
GENERAL SHEET NOTES
DEMO SHEET KEYNOTES
1/4" = 1'-0"A1
POOL E - IWF (INTERACTIVE WATER FEATURES) ELECTRICAL DEMOLITION PLAN
N
D01 THIS HALFTONE SOLID LINE REPRESENTS THE INSIDE EDGE OF THE EDGE OF
THE EXISTING IWF SPRAY PAD.
D02 EXTENT OF IWF CONCRETE PAD REMOVAL. SEE PL DEMOLITION PLANS FOR
ADDITIONAL INFORMATION.
D03 THIS BOLD LINE REPRESENTS THE INSIDE EDGE OF THE FIBERGLASS
COLLECTOR TANK TO BE REMOVED.
D04 THIS DASHED LINE REPRESENTS THE EXISTING FIBERGLASS COLLECTOR
TANK PERIMETER EQUIPOTENTIAL BONDING COPPER CONDUCTOR TO BE
REMOVED. POOL ELECTRICAL CONTRACTOR SHALL DISCONNECT EXISTING
EQUIPOTENTIAL BONDING CONDUCTOR TO ANY EXISTING FIXED METAL PART
TO FACILITATE ITS REMOVAL BY THE POOL GENERAL CONTRACTOR.
D05 EXISTING WATER SPRAY CAN WATER FEATURE SHALL BE REMOVED, TYPICAL
OF 45. (WATER SPRAY CAN IS FLUSH MOUNTED DEVICE ON THE SPRAY PAD
WITH A WATER SUPPLY, WATER DRAIN, AND A LIGHT SOURCE.). SEE NOTE
13/D101.E IN THE PL DRAWINGS SET FOR FOR ADDITIONAL INFORMATION. FOR
THE 45 EXISTING WATER SPRAY CANS TO BE REMOVED, BURY EXISTING
COPPER BONDING CONDUCTOR FOR FUTURE RE-USE.
D06 19 WATER SPRAY CANS SHALL BE DE-ENERGIZED, DISCONNECTED, AND
REMOVED. THOSE 19 LOCATIONS SHALL BE RE-USED FOR NEW WATER
FEATURES. FOR THE 19 LOCATIONS BEING RE-USED, POOL ELECTRICAL
CONTRACTOR SHALL DE-ENERGIZE, DISCONNECT, AND REMOVE WIRING
ASSOCIATED WITH WATER SPRAY CAN LIGHTING. REMOVE WIRING BACK TO
SOURCE PANEL. EXISTING CONDUIT MAY BE ABANDONED, CAPPED OFF IN
PLACE. EXISTING EQUIPOTENTIAL BONDING ASSOCIATED WITH THESE 19
LOCATIONS SHALL BE DISCONNECTED TO ACCOMMODATE WATER SPRAY CAN
REMOVAL BUT SHALL BE PROTECTED TO ALLOW BONDING TO BE
RE-CONNECTED TO METAL PARTS OF 19 NEW WATER FEATURES. SEE SHEET
D101.E FOR ADDITIONAL INFORMATION ON WATER SPRAY CAN REMOVAL AND
SHEET PL130.E FOR ADDITIONAL INFORMATION ON NEW WATER FEATURES.
D07 21 EXISTING METAL FLOOR DRAINS TO BE REMOVED. EXISTING BONDING
COPPER CONDUCTOR TO METAL FLOOR DRAINS TO BE BURIED FOR FUTURE
RE-USE.
D08 EXISTING AUTOFILL SENSOR TO BE DISCONNECTED AND REMOVED. REMOVE
EXISTING CABLE BACK TO SOURCE LOCATED IN MECHANICAL ROOM PB1. SEE
OVERALL SITE PLAN ON SHEET PL001.E FOR LOCATIONS OF EXISTING POOL E
AND EXISTING FILTERATION MECHANICAL ROOM PB1. EXISTING PIPE
BETWEEN TANK AND PB1 SHALL BE RE-USED AS A CONDUIT FOR THE 24V
SOLENOID VALVE WIRING. SEE SHEET 9/PL401.E AND DETAIL B3/PLE501.E FOR
ADDITIONAL INFORMATION.
WATER FEATURE LEGEND
REVISION SCHEDULE
Number Description Date
S
NEW POOL E
SURGE TANK
WATER
FEATURE (TYP.)
ACCESS
HATCH
LADDER
1 OF 4 09
09 4 OF 4
08060711
INDICATES NEW
EQUIPOTENTIAL BONDING
CONDUCTOR (TYP.)
D5
PLE501.E
C1
PLE501.E14
NEW WATER FEATURE
- REFER TO SHEET D101.E AND PL130.E FOR ADDITIONAL INFORMATION
REGARDING EXISTING AND NEW WATER FEATURES
World Leaders in Aquatic Planning, Design and Engineering
100 Park Avenue | Beaver Dam, WI 53916 t 920.887.7375 This Document and the ideas, renderings and other contents contained therein are the sole property of Water Technology, Inc. and may not be disseminated, copied, reproduced or otherwise used without prior written consent of Water Technology, Inc.
CONSULTANTS
PROJECT PHASE:
2300 Maitland Center Parkway Suite 210 Maitland, FL 32751 414.259.1500
DRAWINGS MUST BE
VIEWED AND PLOTTED
IN FULL COLOR.
S U
N -N
-F U
N L
A G
O O
N
R E
N O
V A
T
IO
N S
L iv in g st o n
R d
N a p le s, F L
PLE110.E
POOL E - IWF ELECTRICAL PLAN
ISSUE DATE: 11/08/2024
PROJECT NUMBER: 22567
DRAWN BY: JTO
CHECKED BY: RJJ
100% CONSTRUCTION DOCUMENTS
GENERAL SHEET NOTES
SHEET KEYNOTES
01 THIS HALFTONE SOLID LINE REPRESENTS THE INSIDE EDGE OF THE EXISTING
SPRAY PAD. USED, ALL LABOR AND MATERIALS TO BOND NEW FIXED METAL
PARTS OF NEW WATER FEATURES SHALL BE INCLUDED IN THE POOL
ELECTRICAL CONTRACTOR'S PRICE BID.
02 BONDING POINT BETWEEN EXISTING STRUCUTRAL REINFORCING STEEL AND
NEW STRUCTURAL REINFORCING STEEL. BONDING JUMPER SHALL BE SOLID,
#8 AWG, BARE COPPER CONDUCTOR. PROVIDE A MINIMUM OF FOUR (4)
UNIFORMLY SPACED BONDING CONNECTION POINTS AROUND THE
PERIMETER OF THE POOL IN ACCORDANCE WITH NEC 680.26(B)(2).
04 19 NEW WATER FEATURES TO BE BONDED TO EACH OTHER AND TO NEW
STRUCTURAL REINFORCING STEEL. BONDING SHALL BE SOLID, #8 AWG, BARE
COPPER CONDUCTOR. BONDING CONNECTIONS SHALL BE AS REQUIRED BY
THE NEC. RE-USE EXISTING BONDING CONDUCTOR FROM 19 EXISTING WATER
SPRAY CANS AS STATED ON KEYED NOTE D06 ON SHEET ED110.E. IF
NECESSARY, A NEW BONDING CONDUCTOR SHALL BE PROVIDED BETWEEN
NEW FIXED METAL PART AND NEW STRUCTURAL REINFORCING STEEL IN
ACCORDANCE WITH THE NEC AS SHOWN ON POOL PLANS. WHETHER NEW
CONDUCTOR IS REQUIRED OR EXISTING BONDING CONDUCTOR IS RE-USED,
ALL LABOR AND MATERIALS TO BOND THE NEW FIXED METAL PARTS OF NEW
WATER FEATURES SHALL BE INCLUDED IN THE POOL ELECTRICAL
CONTRACTOR'S PRICE. SEE DETAIL 1/ED101.E AND 1/PL130.E FOR ADDITIONAL
INFORMATION.
05 BONDING BETWEEN FIXED METAL PART AND NEW SURGE TANK PERIMETER
BONDING CONDUCTOR. BONDING SHALL BE SOLID, #8 AWG, BARE COPPER
CONDUCTOR. BONDING CONNECTIONS SHALL BE AS REQUIRED BY THE NEC.
06 THIS BOLD LINE REPRESENTS THE INSIDE EDGE OF THE NEW SURGE TANK.
THE POOL ELECTRICAL CONTRACTOR (PEC) SHALL REFERENCE THIS EDGE
LINE FOR THE PURPOSE OF DETERMINING THE EXTENT OF THE WET DECK
AREA. POOL EQUIPOTENTIAL BONDING REQUIREMENTS IN ACCORDANCE
WITH NFPA-NEC 70, ARTICLE 680. PEC SHALL SPECIFICALLY REFERENCE THIS
EDGE FOR DETERMINING THE FOLLOWING: CONDUCTIVE POOL SHELL IN
REFERENCE TO NEC 680.26(B)(1). EXTENT OF POOL PERIMETER SURFACES IN
REFERENCE TO NEC 680.26(B)(2). EXTENT OF POOL RELATED FIXED METAL
PARTS TO BE BONDED IN REFERENCE TO NEC 680.26(B)(7). ADDITIONAL
EQUIPOTENTIAL BONDING REQUIREMENTS OF NEC ARTICLE 680.
07 SURGE TANK SHELL IS POURED CONCRETE WITH UNENCAPSULATED STEEL
REINFORCING, WITH STEEL BEING CONNECTED WITH STEEL TIE WIRES. POOL
SHELL REINFORCING STEEL SHALL BE BONDED TO OTHER METAL PARTS AS
INDICATED ON THESE PLANS AND AS REQUIRED BY NEC 680.26.
08 THIS DASHED LINE REPRESENTS A DIRECT BURIED, SOLID, #8 AWG BARE
COPPER CONDUCTOR. CONDUCTOR SHALL BE USED TO EQUIPOTENTIALLY
BOND THE POOL PERIMETER SURFACE TO OTHER METALLIC, CONDUCTIVE
POOL EQUIPMENT IN ACCORDANCE WITH NEC 680.26. CONDUCTOR SHALL BE
LOCATED HORIZONTALLY BETWEEN 18" AND 24" FROM INSIDE WALLS OF
POOL, AND LOCATED UNDER THE PERIMETER SURFACE BETWEEN 4" AND 6"
BELOW SUBGRADE. SEE NEC 680.26(B)(2) FOR ADDITIONAL INSTALLATION
REQUIREMENTS.
09 BONDING POINT BETWEEN POOL PERIMETER AND POOL SHELL REINFORCING
STEEL. BONDING CONDUCTOR SHALL BE DIRECT BURIED, SOLID, #8 AWG,
BARE COPPER CONDUCTOR. BONDING CONNECTIONS SHALL BE AS
REQUIRED BY THE NEC.
11 APPROXIMATE LOCATION OF NEW AUTOFILL SENSOR CABLE TERMINATION.
ROUTE AUTOFILL SENSOR CABLE IN EXISTING 6" PIPE BACK TO AUTOFILL
CONTROLLER IN THE MECHANICAL ROOM. SEE PL DRAWINGS FOR PIPE
LOCATION. VERIFY EXACT LOCATION OF CABLE TERMINATION WITH POOL
CONTRACTOR.
14 BELIMO CONTROL VALVE WITH 24V ACTUATOR. VERIFY EXACT LOCATION
WITH POOL CONTRACTOR.
1/4" = 1'-0"A1
POOL E - IWF (INTERACTIVE WATER FEATURES) ELECTRICAL PLAN
N
1. THE POOL ELECTRICAL CONTRACTOR SHALL PROVIDE AN EQUIPOTENTIAL
BOND GRID IN POOL STRUCTURE SURROUNDINGS OF ALL POOLS PER NFPA 70.
BOND AND GROUND ALL PARTS AND PIECES OF THE POOL MECHANICAL
EQUIPMENT, POOL, DECK EQUIPMENT, UNDERWATER POOL LIGHTS,
ACTIVITIES, PERIMETER SURFACES AND ALL OTHER EMBEDDED METALLIC
ITEMS IN ACCORDANCE WITH NFPA 70 ARTICLE 680.26. THIS INCLUDES BUT IS
NOT LIMITED TO THE FOLLOWING EQUIPMENT:
A. THROUGH-WALL LIGHTING ASSEMBLIES AND UNDERWATER LUMINARIES.
B. ALL ELECTRICAL EQUIPMENT LOCATED WITHIN 5' OF THE INSIDE WALL OF
THE SPECIFIED POOL EDGE.
C. ALL ELECTRICAL EQUIPMENT ASSOCIATED WITH THE RECIRCULATION
SYSTEM OF THE SPECIFIED BODY OF WATER.
D. METALLIC JUNCTION BOXES.
E. TRANSFORMERS AND POWER SUPPLY ENCLOSURES.
F. POWER DISTRIBUTION EQUIPMENT ASSOCIATED WITH THE SPECIFIED
BODY OF WATER.
2. PLE DRAWINGS ATTEMPT TO SHOW REQUIRED BONDING CONNECTIONS BUT
NOT ALL REQUIRED BONDING CONNECTIONS ARE SHOWN ON THESE
DOCUMENTS. FIELD CONDITIONS AND DRAWINGS OF OTHER DESIGNERS MAY
RESULT IN ADDITIONAL BONDING REQUIREMENTS. ALL CODE REQUIRED
BONDING SHALL BE PROVIDED WHETHER SHOWN ON THESE PLANS OR NOT,
AND THE COST FOR THESE CONNECTIONS SHALL BE INCLUDED IN THE PLE
CONTRACTOR'S BID.
3. REFER TO AQUATICS SERIES OF DRAWINGS FOR LOCATIONS OF ALL
CONDUCTIVE EMBEDDED METALLIC ITEMS IN AND AROUND POOL THAT SHALL
BE TIED TO THE EQUIPOTENTIAL GROUNDING GRID.
WATER FEATURE LEGEND
REVISION SCHEDULE
B3
FM
FM
FM
FM
FD FDFD FD
D10
D10
NOTE: UNLESS NOTED
OTHERWISE, ALL EQUIPMENT
IS EXISTING TO REMAIN.
D11
D12
PUMP 9
PUMP 8
15 HP
50 HP
PUMP 9
PUMP 8
ER
ER
ER
ER
P2E P1E
ETR
ETR
ETR
ETR
ETR ETR
ETR
ETR
ETR ETR
ETR
ETR
ETR
ETR
ETR
ETR
ETR
P1E
PP1
H2
PP1
H2
SECTION 1
ETR
SECTION 2
ETR
PP1
L1
SECTION 1
ETR
SECTION 2
ETR
UP1E
AF1E
C3
PLE501.E
B1
PLE501.E
3E 1E
4E 2E
FP1
C1
PLE501.E
4E
3E
1E
2E
C1
PLE501.E
(TYP.)
B3
PLE501.E
AUTOFILL CONTROL UNIT.
VERIFY EXACT LOCATION
WITH POOL CONTRACTOR.
PP1
L1
P2E
F1E
FILTRATION SELECTOR
SWITCH. VERIFY EXACT
LOCATION WITH POOL
CONTRACTOR.
D3
PLE501.E
World Leaders in Aquatic Planning, Design and Engineering
100 Park Avenue | Beaver Dam, WI 53916 t 920.887.7375 This Document and the ideas, renderings and other contents contained therein are the sole property of Water Technology, Inc. and may not be disseminated, copied, reproduced or otherwise used without prior written consent of Water Technology, Inc.
CONSULTANTS
PROJECT PHASE:
2300 Maitland Center Parkway Suite 210 Maitland, FL 32751 414.259.1500
DRAWINGS MUST BE
VIEWED AND PLOTTED
IN FULL COLOR.
S U
N -N
-F U
N L
A G
O O
N
R E
N O
V A
T
IO
N S
L iv in g st o n
R d
N a p le s, F L
PLE400.E
PB1 - MECHANICAL ROOM
ELECTRICAL PLAN
ISSUE DATE: 11/08/2024
PROJECT NUMBER: 22567
DRAWN BY: JTO
CHECKED BY: RJJ
100% CONSTRUCTION DOCUMENTS
1/8" = 1'-0"C1
PB1 MECHANICAL ROOM - ELECTRICAL DEMOLITION PLAN
1/8" = 1'-0"A1
PB1 MECHANICAL ROOM - ELECTRICAL PLAN
SHEET KEYNOTES
GENERAL SHEET NOTES
DEMO SHEET KEYNOTES
GENERAL DEMO NOTE:
IT IS THE CONTRACTOR'S RESPONSIBILITY TO THOROUGHLY READ ALL DEMO
NOTES AND REVIEW ALONGSIDE THE KEYNOTES ON PLAN. REFER TO POOL
AQAUTCS DRAWINGS FOR ADDITIONAL DEMOLITION WORK AS PART OF THE
POOL SCOPE.
10 PROVIDE NEW VFD CONTROLLER FOR NEW PUMP. PEC SHALL VERIFY
EXISTING CONDITIONS AND INSTALL VFD IN THE VICINITY OF THE LOCATION
SHOWN ON THE PLANS. EXACT LOCATION SHALL BE DETERMINED BY THE
POOL ELECTRICAL CONTRACTOR IN THE FIELD. EXACT LOCATION SHALL
PROVIDE MINIMUM WORKING CLEARANCES AS REQUIRED BY THE NEC.
D10 DE-ENERGIZE AND DISCONNECT EXISTING MOTOR POWER CONDUCTORS AS
REQUIRED TO ACCOMMODATE PUMP REMOVAL BY OTHERS. DISCONNECT
AND REMOVE ELECTRICAL CONDUCTORS BACK TO SOURCE PANEL. IN
ADDITION TO DISCONNECTING POWER CONDUCTORS, DISCONNECT EXISTING
POOL SYSTEM EQUIPOTENTIAL BONDING CONDUCTOR. SALVAGE AND
PROTECT BONDING CONDUCTOR AND RECONNECT TO NEW MOTOR BEING
PROVIDED AT THIS LOCATION.
D11 EXISTING PUMP COMBINATION MOTOR STARTER SHALL BE REMOVED.
DISCONNECT AND REMOVE FEEDERS BACK TO SOURCE PANEL. REFER TO
ONE-LINE DIAGRAM ON SHEET PLE701.E FOR ADDITIONAL INFORMATION.
D12 EXISTING PUMP MOTOR VFD SHALL BE REMOVED. DISCONNECT AND REMOVE
FEEDERS BACK TO SOURCE PANEL. REFER TO ONE-LINE DIAGRAM ON SHEET
PLE701.E FOR ADDITIONAL INFORMATION. PEC SHALL HAND OVER EXISTING
VFD TO THE OWNER FOR FUTURE RE-USE.
N
N
GENERAL DETAIL NOTES:
1. THIS DETAIL IS DIAGRAMMATIC IN NATURE. IT DOES NOT DEPICT SPECIFIC POOL CONSTRUCTION DETAILS, NOR ALL EQUIPMENT THAT MAY REQUIRE BONDING, BUT INSTEAD IS INTENDED TO INDICATE THE VARIOUS ITEMS AND EQUIPMENT THAT ARE REQUIRED TO BE BONDED. ACTUAL EQUIPMENT REQUIRED TO BE BONDED WILL VARY FROM POOL TO POOL. SEE POOL SERIES PLANS DEPICT ITEMS REQUIRED TO BE BONDED ON AN INDIVIDUAL BASIS BUT MAY OR MAY NOT SHOW ALL REQUIRED POOL EQUIPOTENTIAL BONDING CONNECTIONS. REFER TO POOL DRAWINGS, SLIDE CONTRACTOR DRAWINGS, AND ALL OTHER RELEVANT DRAWINGS THAT COMPRISE THE PROJECT CONSTRUCTION DOCUMENTS FOR ADDITIONAL EQUIPMENT THAT MAY BE REQUIRED TO BE BONDED. DURING CONSTRUCTION, FURTHER CONFIRM BONDING REQUIREMENTS WITH ACTUAL FIELD CONDITIONS. ALL REQUIRED EQUIPOTENTIAL BONDING
SHALL BE INCLUDED IN THE POOL ELECTRICAL CONTRACTORS BASE PRICE.
2. INSTALLATION SHALL CONFORM TO NEC ARTICLE 680.
3. ALL BONDING CONNECTIONS SHALL BE CADWELD OR IRREVERSIBLE CLAMP AS STATED IN THE NEC.
4. ALL BONDING CONDUCTORS SHALL BE #8 AWG, BARE SOLID COPPER UNLESS OTHERWISE NOTED.
5. BOND ALL METAL DEVICES WITHIN 5' OF THE EDGE OF THE SPLASH PAD.
6. ISOLATED METAL PARTS THAT ARE NOT OVER 4 INCHES IN ANY DIMENSION AND DO NOT PENETRATE THE POOL STRUCTURE MORE THAN 1 INCH SHALL NOT
REQUIRE BONDING.
7. IN ADDITION TO REQUIREMENTS SHOWN HERE, SEE MOTOR CHASSIS EQUIPOTENTIAL BONDING DETAILS SHOWN ON PL PLANS FOR ADDITIONAL
INFORMATION.
8. NOT ALL EQUIPMENT REQUIRED TO BE BONDED IS PART OF THIS PROJECT SCOPE.
POOL WATER PUMP
MOTOR.
POOL PERIMETER BONDING
CONDUCTOR.
METAL POOL DRAIN COVER.
POOL ACTIVITY FEATURE STEEL
SUPPORT STRUCTURE.
THIS LINE REPRESENTS THE
BOUNDARY OR THE AREA 5'-0"
BEYOND THE INSIDE WALL OF THE
POOL.
POOL FEATURE FIXED METAL PART
POOL SHELL UN-ENCAPSULATED
STRUCTURAL REINFORCING STEEL.
ONE OF FOUR MINIMUM.
POOL METAL FENCING, BONDED AS
A FIXED METAL PART.
INTERIOR OF POOL
WALL
REINFORCING
STEEL (TYPICAL)
PLAN VIEW AT EXPANSION JOINT
EXPANSION
JOINT
POOL FINISH
REINFORCEMENT
STEEL
REINFORCEMENT
STEEL
BONDING
CONDUCTOR
6" M
IN
EXPANSION
JOINT
BONDING CONDUCTOR BELOW
WALKING SURFACE. LOOP AT
EXPANSION JOINT TO ALLOW FOR
MOVEMENT OF WALKING SURFACE.
WALKING SURFACE.
GENERAL DETAIL NOTES:
1. ALL BONDING CONNECTIONS SHALL BE CADWELD OR
IRREVERSIBLE CLAMP CONNECTIONS.
2. BONDING CONDUCTORS SHALL BE #8 AWG, SOLID, BARE,
COPPER.
3. ALL REINFORCING STEEL SHALL BE TIGHTLY TIED
TOGETHER COMPLETING BOND AS STATED PER NEC
680.26(B)(1).
4. REINFORCING STEEL THAT IS EFFECTIVELY INSULATED BY
AN ENCAPSULATING NON CONDUCTIVE COMPOUND AT THE
TIME OF MANUFACTURING SHALL NOT REQUIRE
GROUNDING PER NEC 680.26(B)(1).
DETAIL NOTES:
CADWELD OR CLAMP BONDING CONNECTION PER THE NEC.
BONDING CONDUCTOR.
POOL DECK
EXPANSION JOINT
STEGMEIER
DECK EDGE
POOL
REINFORCING
STEEL
INSIDE FACE
OF POOL
WALL
GRANULAR FILL
BONDING
WIRE
PER NEC 680
GENERAL DETAIL NOTES:
1. THIS DETAIL IS INTENDED TO ILLUSTRATE THE EQUIPOTENTIAL BONDING GRID AROUND EACH OUTDOOR POOL AS
REQUIRED BY NEC 680.
2. THE BONDING CONDUCTOR SHALL BE A DIRECT BURIED, SOLID, #8 AWG BARE COPPER CONDUCTOR. CONDUCTOR SHALL BE USED TO EQUIPOTENTIALLY BOND THE POOL PERIMETER SURFACE TO OTHER METALLIC, CONDUCTIVE POOL EQUIPMENT IN ACCORDANCE WITH NEC 680.26. CONDUCTOR SHALL BE LOCATED HORIZONTALLY BETWEEN 18" AND 24" FROM INSIDE WALLS OF POOL, AND LOCATED UNDER THE PERIMETER SURFACE BETWEEN 4" AND 6" BELOW SUBGRADE.
SEE NEC 680.26(B)(2) FOR ADDITIONAL INSTALLATION REQUIREMENTS.
3. THIS DETAIL IS NOT INTENDED TO DETAIL THE POOL WALLS OR THE DECKS. THE ABOVE POOL WALL IS GENERIC IN NATURE AND IS NOT TYPICAL FOR EACH POOL WALL. SEE POOL SECTIONS AND DECK SECTIONS FOR ADDITIONAL POOL
AND DECK CONSTRUCTION REQUIREMENTS.
4. SEE POOL ELECTRICAL DRAWINGS FOR ADDITIONAL BONDING & GROUNDING REQUIREMENTS.
POOL PERIMETER
SURFACE BONDING
CONDUCTOR
GENERAL DETAIL NOTES:
1. SEE DETAIL C3 ON THIS SHEET FOR LAMP & CABINET UV
SUPPORT FRAME INSTALLATION DETAIL.
UV PIPING LOOP BY POOL
MECHANICAL CONTRACTOR. UV
DISINFECTION UNIT. FURNISHED BY
OTHERS. INSTALLED BY POOL
MECHANICAL CONTRACTOR.
UV CONTROL CABINET. FURNISHED
BY OTHERS. INSTALLED AND
WIRED BY POOL ELECTRICAL
CONTRACTOR.
UV CABINET LINE VOLTAGE POWER
FEED CONDUIT BY POOL
ELECTRICAL CONTRACTOR. ROUTE
BETWEEN SOURCE PANEL AND UV
CABINET CONDUIT OVERHEAD.
UV UNIT WIRING, FURNISHED BY UV
EQUIPMENT MANUFACTURER,
INSTALLED BY OTHERS AS
DIRECTED BY UV EQUIPMENT
SUPPLIER.
2-HOLE, 90 FITTING
PART P1026
1 11/16"
6"
1/4"
6"
3 1/2"
(4) 3/4"
DIA HOLES
POST BASE - P2072ASQ
ADDITIONAL STRUT CHANNELS AND 90
FITTINGS TO SUPPORT CABLING, AS
REQUIRED.
FLOOR
2"
1 7/8"
UV
CONTROL
PANEL
POST BASE SPACING DEPENDENT ON CONTROL PANEL
WIDTH. REFER TO MANUFACTURER SHOP DRAWINGS FOR EXACT DIMENSIONS.
5' -6
R
E C
O M
M E
N D
E D
IN
S
T A
LL
H
E
IG
H T
T O
C E
N T
E R
O F
C O
N T
R O
L P
A N
E L.
ATTACH CONTROL
PANEL TO VERTICAL
STRUT LEGS.
DASHED LINE REPRESENTS
UV CONTROL CABINET.
REFER TO MANUFACTURER
SHOP DRAWINGS FOR
CONTROL PANEL
DIMENSIONS.
GENERAL DETAIL NOTES:
1. THIS DETAIL ILLUSTRATES THE MINIMUM SUPPORT AND BRACING REQUIREMENTS
FOR THE UV CONTROL PANEL INSTALLATION. THE INSTALLATION OF THE CONTROL
PANEL, SUPPORT FRAME, AND BRACING SHALL BE PROVIDED BY THE POOL
ELECTRICAL CONTRACTOR (PEC).
2. SEE THE "UV INSTALLATION DETAIL FOR ADDITIONAL PLUMBING AND THE UV LAMP
INSTALL REQUIREMENTS NOT SHOWN HERE.
3. COORDINATE WITH POOL MECHANICAL CONTRACTOR.
UV CABINET STRUT SUPPORT
FRAME. REFER TO SPEC
SECTION 26 05 29 FOR
ADDITIONAL REQUIREMENTS.
S
NEW SURGE
TANK LOCATED
NEAR POOL
NEW POOL WATER LEVEL SENSOR
UNIT (BY OTHERS) LOCATED
UNDER NEW WATER PARK SURGE
TANK ACCESS HATCH. PEC TO
INSTALL NEW CABLE TO NEW
AUTOFILL SENSOR.
GENERAL DETAIL NOTES:
1. REFER TO AQUATIC SERIES PLANS FOR EXACT LOCATIONS OF
EQUIPMENT PROVIDED BY THE POOL CONTRACTOR.
2. REFER TO AUTOFILL DETAIL 9/PL401.E ON AQUATIC DRAWINGS FOR
ADDITIONAL INFORMATION.
AquatiControl Tec hnology
POWERLEVELFILLING
MAN
CON TINUOUS
30 MINUTES
60 MINUTES
AUTO
15 5SEC SEC
DELAY
Model
ELC-800
ELC-800 WATER LEVEL
CONTROL UNIT PROVIDED BY
POOL CONTRACTOR.
BELIMO CONTROL VALVE WITH 24V
ACTUATOR PROVIDED AND INSTALLED
BY POOL CONTRACTOR. LOCATED IN
THE VICINITY OF THE SURGE TANK. SEE
PL PLANS FOR ADDITIONAL
INFORMATION.
120V/1PH/60 Hz
GROUND FAULT DUPLEX OUTLET
PROVIDED BY PEC
CONTROL CABLE FURNISHED
AND INSTALLED BY PEC, AND
TERMINATED BY POOL
CONTRACTOR. WIRING SHALL BE
(3) #14 AWG, 3/4" C.
6' CORD
PROVIDED WITH
CONTROLLER
NEW SENSOR CABLING IN
EXISTING 6" SKIMMER PIPE. PEC
TO INSTALL NEW CABLE TO NEW
AUTOFILL CONTROLLER AS
DIRECTED BY POOL
CONTRACTOR.
TO POOL
EQUIPMENT ROOM
AUTOFILL
CONTROLLER
POOL
EQUIPMENT
ROOM
GROUNDING TAB, HARDWARE
AND WIRE BY ELECTRICAL
CONTRACTOR
ANCHOR TOY TO BASE PLATE.
PROVIDED AND INSTALLED BY
OTHERS
CONCRETE FOOTING BY OTHERS
EXISTING WATER FEATURE PIPE
FPX
FLOW METER POWER
SOURCE
5-#20 SHIELDED IN
1/2" PVC CONDUIT
LINE VOLTAGE CIRCUIT
BY PEC AS SHOWN ON
EQUIPMENT SCHEDULE
TO ADDITIONAL
FLOWMETER DISPLAYS
AND SENSORS2-#18 SHIELDED IN
1/2" PVC CONDUIT
2-#18 SHIELDED IN
1/2" PVC CONDUIT
FLOW METER DISPLAY
FLOW METER SENSOR
FLOW METER SENSOR
FLOW METER DISPLAY
FD
FDXX
FM
FMXX
GENERAL DETAIL NOTES:
1. WIRING CIRCUITS SHOWN SHALL BE PROVIDED BY THE PEC. FLOW METER POWER SUPPLIES, FLOW METERS, AND FLOW METER DISPLAYS SHALL BE PROVIDED BY OTHERS.
2. POWER SUPPLY LOCATIONS ARE SHOWN ON THE PLE PLANS. PEC SHALL REFER TO POOL PLANS, SHEETS PL400 AND PL401 FOR EXACT LOCATIONS OF POWER SUPPLIES AND FOR LOCATIONS OF
FLOW METERS AND FLOW METER DISPLAYS.
3. WIRING DIAGRAM IS TYPICAL FOR ALL FLOW METER POWER SUPPLIES, FLOW METERS, AND FLOW
METER DISPLAYS. SEE SCHEDULE ASSOCIATED WITH THIS WIRING DIAGRAM SHOWING WHICH
POWER SUPPLIES SERVE WHICH METERS AND WHICH DISPLAYS.
BACKWASH
OFF
WEATHERPROOF
BOX
PROVIDE LABELS
AS DIRECTED BY
THE OWNER.
GREEN WATER/
CLEAR WATER
SELECTOR SWITCH
FILTRATION
World Leaders in Aquatic Planning, Design and Engineering
100 Park Avenue | Beaver Dam, WI 53916 t 920.887.7375 This Document and the ideas, renderings and other contents contained therein are the sole property of Water Technology, Inc. and may not be disseminated, copied, reproduced or otherwise used without prior written consent of Water Technology, Inc.
CONSULTANTS
PROJECT PHASE:
2300 Maitland Center Parkway Suite 210 Maitland, FL 32751 414.259.1500
DRAWINGS MUST BE
VIEWED AND PLOTTED
IN FULL COLOR.
S U
N -N
-F U
N L
A G
O O
N
R E
N O
V A
T
IO
N S
L iv in g st o n
R d
N a p le s, F L
PLE501.E
ELECTRICAL DETAILS
ISSUE DATE: 11/08/2024
PROJECT NUMBER: 22567
DRAWN BY: JTO
CHECKED BY: RJJ
100% CONSTRUCTION DOCUMENTS
NTSA5
POOL EQUIPMENT EQUIPOTENTIAL BONDING DETAIL
NTSA3
POOL FLOOR EXPANSION JOINT BONDING JUMPER DETAIL
NTSA1
POOL EQUIPOTENTIAL BONDING
NTSB1
UV DISINFECTION CONTROL CABINET LARGE
SCALE PLAN VIEW
NTSC3
UV DISINFECTION CONTROL CABINET SUPPORT & BRACING DETAIL
NTSB3
AUTOFILL DETAIL - SURGE TANK
NTSD5
WATER FEATURE GROUNDING DETAIL
NTSC1
FLOW METER DETAIL
FP1 PB1
FM1E-FD1E FM2E-FD2E FM3E-FD3E FM4E-FD4E
FLOW METER POWER SUPPLY POWER SUPPLY LOCATION ASSOCIATED FLOW METERS AND FLOW METER DISPLAYS
FLOW METER SCHEDULE
REVISION SCHEDULE
Number Description Date
NTSD3
FILTRATION SELECTOR SWITCH ELEVATION
A. THIS DRAWING IS DIAGRAMMATIC IN NATURE AND IS NOT INTENDED TO
BE AN INSTALLATION DRAWING. THIS DIAGRAM SHALL BE USED TO
DETERMINE HOW VARIOUS POOL EQUIPMENT IS INTERCONNECTED AND
THE WIRING IS TO BE USED BETWEEN THE EQUIPMENT.
B. IT SHALL BE THE POOL ELECTRICAL CONTRACTOR'S RESPONSIBILITY TO
FURNISH AND INSTALL ALL THE WIRING INDICATED IN THIS DIAGRAM,
BOTH LINE VOLTAGE AND LOW VOLTAGE CONTROL WIRING. LOW
VOLTAGE WIRING IS DEFINED AS WIRING THAT CARRIES CIRCUITS
OPERATING AT LESS THAN 50 VOLTS.
C. CONTROL WIRING SHALL BE TERMINATED BY THE POOL CONTROLS
CONTRACTOR.
D. ALL WIRING SHALL BE ROUTED IN CONDUIT PROVIDED BY THE POOL
ELECTRICAL CONTRACTOR. MINIMUM 3/4" CONDUIT SHALL BE USED.
CONDUITS SHALL BE SIZED SO THAT THE AREA OF THE CONDUCTORS
CONTAINED DO NOT EXCEED 40% OF THE AREA OF THE CONDUIT
PROVIDED.
E. THERE ARE ADDITIONAL CONTROL CIRCUITS (CONDUIT AND
CONDUCTORS) THAT ARE TO BE PROVIDED BY THE POOL ELECTRICAL
CONTRACTOR THAT ARE NOT SHOWN ON THE PLE PLANS. POOL
ELECTRICAL CONTRACTOR SHALL REFER TO THE PLC SERIES PLANS FOR
ADDITIONAL ITEMS REQUIRED TO BE INCLUDED AS PART OF THE PLE'S
SCOPE OF WORK.
F. REFER TO EQUIPMENT SCHEDULES AND PANEL SCHEDULES ON THE
PLE700 SERIES SHEETS FOR LINE VOLTAGE EQUIPMENT WIRING
REQUIREMENTS AND ADDITIONAL CIRCUITING INFORMATION.
G. PEC SHALL PREPARE AND SUBMIT FOR APPROVAL, RACEWAY
INSTALLATION AND ROUTING SHOP DRAWINGS TO SUPPORT THE
CONTROL WIRING SHOWN ON THESE DIAGRAMS. SEE SPECIFICATIONS
FOR CONTROL CONDUIT SUBMITTAL REQUIREMENTS.
H. IN ADDITION TO THE CONTROL WIRING SHOWN ON THIS SHEET, THERE IS
ADDITIONAL CONTROL WIRING AND CONDUIT REQUIRED TO BE PROVIDED
BY THE POOL ELECTRICAL CONTRACTOR. THOSE CIRCUITS ARE SHOWN
ON THE PLC SERIES PLANS INCLUDED IN THIS PRICING SET. REFER TO
THE PLC PLANS FOR ADDITIONAL CONTROL WIRING AND RACEWAY
REQUIREMENTS TO BE PROVIDED AS PART OF THE PEC'S SCOPE OF
WORK.
1. WIRING (LAMP POWER CORD) FURNISHED WITH UV UNIT AND INSTALLED BY
THE POOL ELECTRICAL CONTRACTOR. FINAL CONNECTIONS TO UV
CHAMBER AND CONTROL CABINET BY POOL CONTRACTOR.
2. FURNISHED WITH UV UNIT AND INSTALLED BY POOL CONTRACTOR.
3. ELECTRICAL WIRING FROM THE FILTER PROGRAMMER TO THE CHEMICAL
CONTROLLER SHALL DISABLE THE CHEMICAL CONTROLLER AND INACTIVE
ALL CHEMICAL FEEDERS WHEN THE CHEMICAL CONTROLLER AND INACTIVE
ALL CHEMICAL FEEDERS WHEN THE FILTER PROGRAMMER IS IN BUMP,
PRECOAT, OR OFF MODE AS INDICATED ON THIS TABLE BELOW.
4. ELECTRICAL WIRING FROM THE UV CONTROL CABINET TO THE
FILTRATION/ACTIVITY PUMP VFD SHALL TURN THE PUMP ON/OFF FOR THE
VARIOUS FILTER MODE (OFF/BACKWASH/FILTRATION) AS INDICATED IN THE
TABLE BELOW.
480 V
480 V
120 V (EXISTING)
LV
120 V (NEW)
EXISTING 480 V
PANELBOARD
EXISTING 120 V
PANELBOARD
EXISTING CHEMICAL CONTROLLER
'C1E'
NEW OFF/BACKWASH/FILTRATION
SWITCH 'F1E'
NEW VFD
NEW FILTRATION/ACTIVITY
PUMP 'P2E' (REDUNDANT)
LEGEND:
LOW VOLTAGE
LINE VOLTAGE
SEQUENCE OF OPERATIONS - SWIMMING POOL WITH MANUAL BACKWASH SAND FILTER SYSTEM
FILTRATION PUMP MOTOR STARTER SELECTOR SWITCH ("OFF/BACKWASH/FILTRATION"):
• A THREE POSITION SELECTOR SWITCH SHALL BE PROVIDED FOR THE MOTOR STARTER/VFD WITH POSITIONS LABELED "OFF", "BACKWASH", AND "FILTRATION".
"FILTRATION" POSITION:
• PLACE THE SWITCH IN THE "FILTRATION" POSITION FOR THE NORMAL FILTRATION OPERATING MODE OF THE SYSTEM.
• WITH THE FILTRATION PUMP SELECTOR SWITCH IN THE “FILTRATION” POSITION, THE FILTRATION PUMP SHALL RUN AT DESIGN
FLOW (FREQUENCY) AND THE CHEMICAL CONTROLLER SHALL BE CAPABLE OF ENERGIZING THE CHEMICAL FEED SYSTEM
OUTLETS.
• THE ACTUAL FLOW INFORMATION SHALL BE PROVIDED TO THE VFD BY THE FM TRANSMITTER. THE VFD SHALL ADJUST
FREQUENCY AS REQUIRED TO ACHIEVE SYSTEM DESIGN FLOW.
• THE CHEMICAL CONTROLLER SHALL BE WIRED TO THE CHEMICAL FEED OUTLETS AND SHALL ENERGIZE/DE-ENERGIZE THESE
OUTLETS BASED UPON POOL WATER CHEMISTRY.
• THE ACCU-TAB POWERBASE CONTROLLER IS POWERED ON/OFF BY THE CHEMICAL CONTROLLER CHLORINE FEED OUTLET.
• THE ACCU-TAB POWERBASE CHLORINE FEED BOOSTER PUMP IS ACTIVATED BY THE ACCU-TAB POWERBASE CONTROLLER.
• THE ACID FEED PUMP IS POWERED ON/OFF BY THE CHEMICAL CONTROLLER PH FEED OUTLET.
• IF THE FILTRATION PUMP LOSES POWER WHILE IN THE "FILTRATION" MODE THE CHEMICAL CONTROLLER SHALL NOT BE CAPABLE
OF ENERGIZING THE CHEMICAL FEED OUTLETS AND THE POOL HEATER SHALL BE INACTIVE.
"BACKWASH" POSITION:
• PLACE THE SWITCH IN THE "BACKWASH" POSITION WHEN BACKWASHING THE FILTERS.
• WITH THE FILTRATION PUMP SELECTOR SWITCH IN THE "BACKWASH" POSITION, THE FILTRATION PUMP SHALL RUN, BUT THE
CHEMICAL CONTROLLER SHALL NOT BE CAPABLE OF ENERGIZING THE CHEMICAL FEED SYSTEM OUTLETS AND THE POOL
HEATER SHALL BE INACTIVE.
"OFF" POSITION:
• PLACE THE SWITCH IN THE "OFF" POSITION TO TURN THE PUMP AND FILTRATION SYSTEM OFF.
• WITH THE FILTRATION PUMP SELECTOR SWITCH IN THE "OFF" POSITION, THE FILTRATION PUMP SHALL BE OFF AND THE
CHEMICAL CONTROLLER SHALL NOT BE CAPABLE OF ENERGIZING THE CHEMICAL FEED SYSTEM OUTLETS AND THE POOL
HEATER SHALL BE INACTIVE.
CHEMICAL CONTROLLER & CHEMICAL FEED OUTLETS:
• THE CHEMICAL CONTROLLER CPU SHALL BE POWERED AT ALL TIMES.
• THE CHEMICAL FEED OUTLETS SHALL BE INTERLOCKED SUCH THAT IF THE FILTRATION PUMP LOSES POWER WHILE IN THE
"FILTRATION" MODE, THE IN-LINE FLOW SWITCH IS NOT MADE OR THE SELECTOR SWITCH IS IN THE OFF OR BACKWASH
POSITIONS; THE FEED OUTLETS ARE INACTIVE.
• CHEMICAL CONTROLLER FEED OUTLETS ENERGIZES / DE-ENERGIZES SANITIZER AND pH FEED BASED UPON POOL WATER
CHEMISTRY.
• SWITCH BETWEEN ACID OUTLET AND CO2 OUTLET IS ACCOMPLISHED MANUALLY BY OPERATOR. LABEL OUTLETS AND SWITCH
AS CO2 AND ACID, RESPECTIVELY.
• CHEMICAL CONTROLLER FEED OUTLETS ENERGIZES / DE-ENERGIZES ENZYME FEED BASED UPON TIMED DELIVERY.
CHEMICAL FEED PUMPS
• THE CHEMICAL FEED PUMPS ARE ENERGIZED BY THE CHEMICAL FEED OUTLETS.
208 V
LV
NEW UV CONTROL
CABINET 'UP1E'
NEW UV CHAMBER 'UV1E'
2 1 A
LV
NEW VFD
480 V
NEW FILTRATION/ACTIVITY
PUMP 'P1E'
LV
FLOW METER POWER
SUPPLY 'FP1'
120 V
FLOW METER DISPLAY
'F1DE', 'F2DE', 'F3DE', 'F4DE',
CO2 FEED SOLENOID
• THE CO2 FEED SOLENOID IS ACTIVATED BY THE CHEMICAL FEED OUTLETS.
POOL HEATER:
• THE POOL HEATER SHALL BE INTERLOCKED SUCH THAT IF THE FILTRATION PUMP LOSES POWER WHILE IN THE FILTRATION MODE
OR IF THE SELECTOR SWITCH IS IN THE OFF OR BACKWASH POSITIONS; THE HEATER IS INACTIVE.
• THE POOL HEATER CIRCULATING PUMP IS CONTROLLED BY THE POOL HEATER CONTROLLER.
• POOL HEATER CYCLES ON AND OFF AS NEEDED BASED UPON POOL WATER TEMPERATURE.
• POOL HEATER IS INTERLOCKED WITH MANUFACTURER SUPPLIED FLOW SWITCH AND HI-LIMIT TEMP SENSORS.
FLOW METER:
• WHEN FLOW METER POWER SUPPLY IS ENERGIZED, THE FLOW METER SENSOR SHALL PROVIDE THE FLOW READOUT IN GPM.
• THE FLOW METER SHALL PROVIDE FLOW DATA TO THE INDICATED VFD AND CONTROL SPEED OF THE VFD BASED ON FLOW.
ULTRAVIOLET (UV) DISINFECTION UNIT:
• THE UV UNIT IS NORMALLY ON.
• THE UV UNIT SHALL BE INTERLOCKED SUCH THAT IF THE SELECTOR SWITCH IS IN THE BACKWASH POSITION THE UV SHALL BE
TURNED OFF.
• THE UV NORMALLY RUNS IN VARIABLE POWER MODE.
• COMBINED CHLORINE UV CONTROL: WITH FREE AND TOTAL CHLORINE SENSORS, THE CONTROLLER SHALL PROVIDE UV BOOST
CONTROL OF A UV SYSTEM BASED UPON THE COMBINED CHLORINE SET POINT. WHEN COMBINED CHLORINE IS ABOVE THE SET POINT THE UV SYSTEM SHALL BOOST TO 100% TO INCREASE THE CHLORAMINE DESTRUCTION RATE. THE UV SHALL RETURN TO
VARIABLE POWER MODE ONCE COMBINED CHLORINE DROPS BELOW THE SET POINT.
"X" INDICATES THE EQUIPMENT IS ENERGIZED/RUNNING.
"O" INDICATES THE EQUIPMENT IS NOT ENERGIZED.
FILTRATION
SELECTOR SWITCH
POSITION
FILTRATION
PUMP
CHEMICAL
CONTROLLER
CHLORINE
FEED
ACID FEED
HEATER OR HEAT
EXCHANGER
OFF O X O O
BACKWASH X X O O
FILTRATION
O
O
UV
X X X X X
O
O
X
C1
PLE501.E
SEE DETAIL FOR EXACT
CONFIGURATION
AUTOFILL RELAY 'AF1E'
120 V
SOLENOID VALVE
ELECTRODE ASSEMBLY
120 V
LV
LV
LV
FLOW METER SENSOR
'F1ME', 'F2ME', 'F3ME', 'F4ME',
C
World Leaders in Aquatic Planning, Design and Engineering
100 Park Avenue | Beaver Dam, WI 53916 t 920.887.7375 This Document and the ideas, renderings and other contents contained therein are the sole property of Water Technology, Inc. and may not be disseminated, copied, reproduced or otherwise used without prior written consent of Water Technology, Inc.
CONSULTANTS
PROJECT PHASE:
2300 Maitland Center Parkway Suite 210 Maitland, FL 32751 414.259.1500
DRAWINGS MUST BE
VIEWED AND PLOTTED
IN FULL COLOR.
S U
N -N
-F U
N L
A G
O O
N
R E
N O
V A
T
IO
N S
L iv in g st o n
R d
N a p le s, F L
PLE601.E
POOL E - ELECTRICAL WIRING
SCHEMATIC
ISSUE DATE: 11/08/2024
PROJECT NUMBER: 22567
DRAWN BY: JTO
CHECKED BY: RJJ
100% CONSTRUCTION DOCUMENTS
GENERAL SHEET NOTES
SHEET KEYNOTES
NTSA1
ELECTRICAL WIRING DIAGRAM - SYSTEM E
C 18 AWG 6 CONDUCTOR NON-SHIELDED PLENUM WINDY CITY WIRE 002391 PEC PEC POOL CONTRACTOR DEFENDER TO VFD
A 18 AWG 2 CONDUCTOR NON-SHIELDED PLENUM WINDY CITY WIRE 002360 PEC PEC POOL CONTRACTOR TEMPERATURE SENSORS
CABLE
DESIGNATION
DESCRIPTION MANUFACTURER MODEL NUMBER
FURNISHED
BY
INSTALLED
BY
TERMINATED BY TYPICAL USE
POOL FILTERING SYSTEM CONTROL CABLE SCHEDULE
EXISTING PANEL 'PP1/H2 - SECTION 1'
480Y/277 VOLT, 3 PHASE, 4 WIRE
NEW
PUMP P1E
(20 HP)
EXISTING 15 HP
FILTRATION
PUMP 9
40A 3P
CUT OFF EXISTING
CONDUIT AT FLOOR
(TYP.)
MINIMUM 18" LIQUID
TIGHT FLEXIBLE
METAL CONDUIT AT
MOTOR TERMINALS.
(TYP.)
JUNCTION BOX
IF NECESSARY
(TYP.)
4 5
3-#8
1-#10 GRD.,
3/4" C.
VFD CABLE
50A 3P
VFD
NEW
PUMP P2E
(20 HP) -
REDUNDANT
EXISTING 50 HP
FEATURE
PUMP 8
VFD
2 6
EXISTING COMBINATION
MOTOR STARTER TO BE
REMOVED
3-#8
1-#10 GRD.,
3/4" C.
EXISTING TO REMAIN
EXISTING TO BE REMOVED
NEW
3-#8
1-#10 GRD.,
3/4" C.
VFD CABLE
50A 3P
VFD
3-#8
1-#10 GRD.,
3/4" C.
150A 3P
EQUIPMENT CONNECTION SCHEDULE GENERAL NOTES:
A. VERIFY ALL MCA AND MOCP REQUIREMENTS WITH SUBMITTED AND APPROVED
EQUIPMENT PRIOR TO ELECTRICAL ROUGH-IN. ADJUST CIRCUIT SIZES
ACCORDINGLY.
B. REFER TO SPECIFICATIONS FOR SPECIFIC REQUIREMENTS AND SCOPE FOR
CONTROL WIRING, LINE WIRING, CONTROLLERS, AND DISCONNECTS.
C. VERIFY ALL INSTALLATION REQUIREMENTS WITH EQUIPMENT INSTALLER PRIOR
TO ROUGH-IN.
D. LOCATIONS OF DISCONNECTS FOR EACH PIECE OF EQUIPMENT MAY NOT BE
SHOWN ON PLANS. IF DISCONNECT FOR EQUIPMENT IS NOT SHOWN,
CONTRACTOR TO FIELD COORDINATE LOCATION IN ACCORDANCE WITH CODE.
E. FOR FUSED DISCONNECTS, IF FUSE SIZE IS NOT LISTED IT SHALL MATCH THE
AMPERAGE RATING OF THE FUSIBLE DISCONNECT.
F. FOR ALL EQUIPMENT WITH NON-INTEGRAL CONTROLLER/DISCONNECTS/VFD,
CONTRACTOR SHALL RUN CONDUIT AND WIRE FROM PANEL TO
CONTROLLER/DISCONNECT/VFD AND THEN FROM
CONTROLLER/DISCONNECT/VFD TO EQUIPMENT ITEM.
G. ABBREVIATIONS USED IN THESE SCHEDULES ARE AS FOLLOWS:
CP - CONTROL PANEL
CS - COMBINATION MAGNETIC CONTROLLER
CR - CONTROL RELAY
CW - CONTROL WIRING (REGARDLESS OF VOLTAGE)
DR - 20 AMP, 120 VOLT DUPLEX RECEPTACLE REQUIRED
ECM - ELECTRONICALLY COMMUTATED MOTOR
F - FURNISHED BY
GFI - GROUND FAULT CIRCUIT INTERRUPTER
I - INSTALLED BY
IU - IN UNIT
LOC - LOCATION
MAG - MAGNETIC STARTER
MCA - MINIMUM CIRCUIT AMPACITY
MOCP - MAXIMUM OVERCURRENT PROTECTION DEVICE
MTR CKT - MOTOR CIRCUIT CONDUCTORS (REFERS TO POWER WIRING
BETWEEN THE CONTROLLER AND THE MOTOR HOUSING TERMINALS)
NA - NOT APPLICABLE
NG - NEUMAN GROUP
NU - NEAR UNIT
PEC - POOL ELECTRICAL CONTRACTOR
PMC - POOL MECHANICAL CONTRACTOR
RVS - REDUCED VOLTAGE STARTER
UM - UNIT MANUFACTURER
VFD - VARIABLE FREQUENCY DRIVE CONTROLLER
KEYNOTES:
AT THEIR OPTION, CONTRACTOR MAY RE-USE EXISTING RACEWAY WHERE
POSSIBLE AND PRACTICAL. CASUAL SITE OBSERVATION ON THE PART OF THE
ENGINEER INDICATES THAT RACEWAYS BETWEEN WALL MOUNTED
CONTROLLERS AND FLOOR MOUNTED PUMPS IS ROUTED BELOW THE
BUILDING FLOOR SLAB. PRIOR TO PULLING NEW CONDUCTORS IN EXISTING
RACEWAYS, CONTRACTOR SHALL EXAMINE THE CONDITION OF THE EXISTING
RACEWAYS AND CONFIRM THEY ARE NOT DAMAGED OR COMPROMISED IN ANY
WAY. FINAL INSTALLATION SHALL MEET ALL REQUIREMENTS OF THESE
DOCUMENTS (UNLESS OTHERWISE APPROVED IN WRITING BY THE ENGINEER)
AND ALL APPLICABLE CODES. ALL WORK AND ANY ASSOCIATED COSTS
REQUIRED TO MODIFY OR REPLACE EXISTING RACEWAYS SHALL BE INCLUDED
IN THE CONTRACTOR'S BASE BID. SEE KEYNOTE 2 ON THIS SHEET FOR
ADDITIONAL INFORMATION.
LOCATE NEW MOTOR CONTROLLER AT SAME LOCATION AS EXISTING
CONTROLLER. ASSOCIATED MOTOR FEEDER CONDUITS MAY BE RE-USED
WHERE POSSIBLE AND PRACTICAL AS INDICATED ON NOTES FOUND
ELSEWHERE ON THIS SHEET. CONTRACTOR SHALL MODIFY EXISTING
RACEWAYS AS REQUIRED TO ACCOUNT FOR SIZE AND MOUNTING
DIFFERENCES BETWEEN EXISTING CONTROLLERS BEING REMOVED AND NEW
CONTROLLERS REQUIRED BY THESE DOCUMENTS.
PROVIDE NEW CIRCUIT BREAKER IN EXISTING PANEL TO SERVE NEW MOTOR AS
INDICATED. NEW BREAKER SHALL OF SAME MANUFACTURER, TYPE, AND IC
RATING TO MATCH EXISTING. EXISTING, ABANDONED CIRCUIT BREAKER SHALL
BE REMOVED AS REQUIRED TO CREATE SPACE FOR NEW CIRCUIT BREAKER.
TURN REMOVED BREAKERS OVER TO THE OWNER. CONTRACTOR'S SCOPE OF
WORK SHALL INCLUDE ANY REQUIRED MODIFICATIONS TO THE PANEL
ENCLOSURE AND BREAKER COVERS TO ACCOMMODATE THE REMOVAL OF AND
INSTALLATION OF CIRCUIT BREAKERS. ANY REQUIRED MODIFICATIONS SHALL
BE PERFORMED AT THE DIRECTION AND APPROVAL OF THE PANEL
MANUFACTURER.
THIS PANEL CONTAINS ADDITIONAL BREAKERS THAT ARE NOT SHOWN ON THIS
ONE-LINE DIAGRAM. EXISTING BREAKERS THAT ARE NOT SHOWN ARE
"EXISTING TO REMAIN".
EXISTING POWER PANEL AS MANUFACTURED BY SIEMENS. ELECTRICAL
CONTRACTOR SHALL VERIFY EXACT SERIES AND MODEL NUMBER AND SHALL
PROVIDE NEW BREAKERS AS REQUIRED, COMPATIBLE WITH THE EXISTING
DISTRIBUTION PANEL. SEE KEYNOTE 3 ON THIS SHEET FOR ADDITIONAL
INFORMATION.
EXISTING VFD SHALL BE REMOVED. DISCONNECT AND REMOVE FEEDERS BACK
TO SOURCE PANEL. PEC SHALL HAND OVER EXISTING VFD TO OWNER FOR
FUTURE RE-USE.
World Leaders in Aquatic Planning, Design and Engineering
100 Park Avenue | Beaver Dam, WI 53916 t 920.887.7375 This Document and the ideas, renderings and other contents contained therein are the sole property of Water Technology, Inc. and may not be disseminated, copied, reproduced or otherwise used without prior written consent of Water Technology, Inc.
CONSULTANTS
PROJECT PHASE:
2300 Maitland Center Parkway Suite 210 Maitland, FL 32751 414.259.1500
DRAWINGS MUST BE
VIEWED AND PLOTTED
IN FULL COLOR.
S U
N -N
-F U
N L
A G
O O
N
R E
N O
V A
T
IO
N S
L iv in g st o n
R d
N a p le s, F L
PLE701.E
ELECTRICAL SCHEDULES
ISSUE DATE: 11/08/2024
PROJECT NUMBER: 22567
DRAWN BY: JTO
CHECKED BY: RJJ
100% CONSTRUCTION DOCUMENTS
EQUIPMENT CONNECTION SCHEDULE - POOL E
# SERVING LOCATION
LOAD
(AMPS-HP-
WATTS)
LOAD
(VA)
VOLTAGE PHASE
CIRCUIT
BREAKER
FEED FROM WIRING MOTOR CONTROLLER INFO
MOTOR
DISCONNECT
MEANS
SEE NOTE
PANEL CIRCUIT
PHASE &
NEUTRAL
QTY.
PHASE
SIZE
GROUND
SIZE
CONDUIT
SIZE
TYPE FB IB
MTR
CKT
CW LOC
DISC
MEANS
AF1E AUTOFILL CONTROLLER PB1 - 500 VA 120 V 1 20 A
PP1/L1 - SECTION 2
(NEW CONDITION)
61 1 12 12 3/4" - - - - - - - - 3
FP1 FLOW METER POWER SUPPLY PB1 - 500 VA 120 V 1 20 A
PP1/L1 - SECTION 2
(NEW CONDITION)
67 1 12 12 3/4" - - - - - - - -
P1E FILTRATION/ACTIVITY PUMP PB1 20 HP 22447 VA 480 V 3 50 A
PP1/H2 - SECTION 1
(NEW CONDITION)
1,3,5 3 8 10 3/4" VFD PEC PEC PEC PEC NU - - 1, 2, 4, 6
P2E
FILTRATION/ACTIVITY PUMP
(REDUNDANT)
PB1 20 HP 22447 VA 480 V 3 50 A
PP1/H2 - SECTION 1
(NEW CONDITION)
7,9,11 3 8 10 3/4" VFD PEC PEC PEC PEC NU - - 1, 2, 5, 6
UP1E ULTRA VIOLET DISINFECTION PANEL PB1 1.5 KW 1664 VA 208 V 1 20 A
PP1/L1 - SECTION 2
(NEW CONDITION)
63,65 2 12 12 3/4" - - - - - - - -
PUMP BUILDING PB-1 - PARTIAL ONE-LINE DIAGRAM - POOL E
EQUIPMENT CONNECTION SCHEDULE NOTES:
1. PROVIDE 18" MINIMUM OF FLEXIBLE CONDUIT AT MOTOR TO FACILITATE FUTURE REMOVAL. PROVIDE FULL INSTALLATION AND WIRING OF PUMP VFD, INCLUDING UNISTRUT
FRAMING AS NECESSARY.
2. NEW REPLACEMENT PUMP. REPLACE EXISTING PUMP MOTOR STARTER WITH NEW VFD. REFER TO PARTIAL ONE-LINE DIAGRAM ON THIS SHEET FOR ADDITIONAL INFORMATION.
3. PROVIDE GFI PROTECTED DUPLEX OUTLET AT CONTROLLER LOCATION AS SHOWN ON DETAIL B3/PLE501.E.
4. ELECTRICAL WIRING INTERLOCK IS REQUIRED BETWEEN EXISTING FILTER PROGRAMMER AND FILTRATION PUMP. SEE ELECTRICAL WIRING DIAGRAM ON SHEET PLE601.E FOR
ADDITIONAL INFORMATION.
5. ELECTRICAL WIRING INTERLOCK IS REQUIRED BETWEEN FILTRATION PUMP AND ACTIVITY PUMP. SEE ELECTRICAL WIRING DIAGRAM ON SHEET PLE601.E FOR ADDITIONAL
INFORMATION.
6. VERIFY EXACT CONFIGURATION OF EXISTING EM STOP WIRING. IF POSSIBLE, CONNECT EXISTING EM STOP TO NEW PUMP CONTROLS AS NECESSARY. FOR BIDDING PURPOSES, ASSUME 50' OF 3/4" CONDUIT WILL BE REQUIRED BETWEEN EXISTING PUMP EM STOP AND PUMP VFD'S. COORDINATE EXACT EM STOP REQUIREMENTS AND LOCATION WITH
OWNER.
World Leaders in Aquatic Planning, Design and Engineering
100 Park Avenue | Beaver Dam, WI 53916 t 920.887.7375 This Document and the ideas, renderings and other contents contained therein are the sole property of Water Technology, Inc. and may not be disseminated, copied, reproduced or otherwise used without prior written consent of Water Technology, Inc.
CONSULTANTS
PROJECT PHASE:
2300 Maitland Center Parkway Suite 210 Maitland, FL 32751 414.259.1500
DRAWINGS MUST BE
VIEWED AND PLOTTED
IN FULL COLOR.
S U
N -N
-F U
N L
A G
O O
N
R E
N O
V A
T
IO
N S
L iv in g st o n
R d
N a p le s, F L
PLE702.E
ELECTRICAL SCHEDULES
ISSUE DATE: 11/08/2024
PROJECT NUMBER: 22567
DRAWN BY: JTO
CHECKED BY: RJJ
100% CONSTRUCTION DOCUMENTS
HB = HAND-BLOCKING DEVICE
HACR = HEATING AND AIR-CONDITIONING RATED
GFCI = GROUND FAULT CIRCUIT INTERRUPTER
ST = SHUNT TRIP
ABBREVIATIONS:
29 0 -- 30
27 0 -- 28
EXISTING 25 HP PUMP-11A
(ETR)
60 A
(ETR)
0 --
3 -- EXISTING SPACE
23 0 0 24
21 0 0 22
EXISTING 20 HP PUMP-12A
(ETR)
100 A
(ETR)
0 0
40 A
(ETR)
EXISTING 15 HP PUMP-14B
(ETR)
17 0 0 18
15 0 0 16
EXISTING 15 HP PUMP-12B
(ETR)
40 A
(ETR)
0 0
100 A
(ETR)
EXISTING 20 HP PUMP-13A
(ETR)
11 5,850 0 12
9 5,850 0 10
EXIS…