25-8378_-_Exhibit_M_-_Sun_N_Fun_IWF_PLE_Drawings_-_100%_Bid_Set.pdf

PDF 4 MB Posted

Attached to
Sun-n-Fun Interactive Water Features Renovations
Solicitation number
25-8378
Issued by
Collier County, Florida

About this file

The provided file is a set of electrical engineering drawings (PLE series) for the Sun-N-Fun Lagoon 2024 Renovations project located in Naples, Florida, specifically focusing on the Interactive Water Features (IWF) electrical systems. The drawings, prepared by Water Technology, Inc. on November 8, 2024, detail electrical demolition plans, new electrical layouts, equipment connection schedules, wiring schematics, and electrical details for Pool E and the associated mechanical room (PB1). The documents cover comprehensive electrical work including removing existing equipment, installing new pumps, water features, UV disinfection systems, flow meters, autofill controllers, and associated electrical infrastructure.

The electrical design follows the 2020 National Electrical Code and 2023 Florida Building Code, with specific attention to pool electrical requirements, equipotential bonding, and safety standards. The project involves replacing existing pumps with new 20 HP filtration/activity pumps, installing variable frequency drives (VFDs), implementing new control systems, and updating electrical panels and circuits. The electrical work is part of a broader renovation of the Sun-N-Fun Lagoon interactive water features, with careful consideration given to existing infrastructure, control integration, and compliance with national and local electrical and safety regulations. The drawings provide detailed specifications for conduit routing, wire sizing, equipment connections, and system interconnections to ensure a comprehensive and code-compliant electrical installation.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

1P 2P 3P 4P 1P, 1W 1P, 2W 2P, 2W 2P, 3W 3P, 2W 3P, 3W 3P, 4W 4P, 4W A

AC

AF

AFF

AFG

AIC

ANSI

AL

AS

AT

ARCH

ATS

A / V

AWG

B

BF

BFF

BFG

BLDG

C

CAM

CAT

CATV

CB

CKT

CLG

CO

CT

CU

CL

DC

DR

DISC

DW

DWG

E

EC

EMT

ETR

ER

ERL

ERLD

EWC

EX

FA

FLA

FO

FPC

GC

GFCI

GFPE

GND

GRC

HH

HP

HVAC

HZ

ISP

IT

JB

KVA

KVAR

KW

LP

LS

LTG

LV

MC

MCA

MCC

MDP

MISC

MH

MLO

MTD

MTG

MTS

MW

MV

N / A

NC

NEC

NIC

NO

NTS

OSP

P

PB

PC

PH

PNL

PP

PR

PRI

PROJ

PVC

REC

RE / CKT

REF

RSC

RVS

SC

SEC

SN

SP

SS

ST

STP

SUSP

SW

SWBD

T

TBB

TC

TCI

TELE / DATA

TEL

TELECOM

TGP

TMGB

TP

TYP

UG

UTP

UOI

V W

WA

WAP

WP

XFMR

XR

XV

Y

ZAM

- KILOVOLT AMPERE REACTIVE

- KILOWATT

- LIGHTING PANEL

- LIMIT SWITCH

- LIGHTING

- LOW VOLTAGE

- MECHANICAL CONTRACTOR

- MINIMUM CIRCUIT AMPS

- MOTOR CONTROL CENTER

- MAIN DISTRIBUTION PANEL

- MISCELLANEOUS

- MANHOLE

- MAIN LUGS ONLY

- MOUNTED

- MOUNTING

- MANUAL TRANSFER SWITCH

- MICROWAVE

- MEDIUM VOLTAGE

- NOT APPLICABLE

- NORMALLY CLOSED

- NATIONAL ELECTRIC CODE

- NOT IN CONTRACT

- NORMALLY OPEN

- NUMBER

- NOT TO SCALE

- OUTSIDE PLANT

- POLE

- PULL BOX

- PLUMBING SYSTEM CONTRACTOR

- PHASE

- PANEL OR PANELBOARD

- POWER PANEL

- PAIR

- PRIMARY

- PROJECTOR

- POLYVINYL CHLORIDE

- RECESSED

- REUSE EXISTING CIRCUIT

- REFRIGERATOR

- RIGID STEEL CONDUIT

- REDUCED VOLTAGE STARTER

- SECURITY CONTRACTOR

- SECONDARY

- SOLID NEUTRAL

- SPARE

- STAINLESS STEEL

- SHUNT TRIP

- SHIELDED TWISTED PAIR

- SUSPENDED

- SWITCH

- SWITCHBOARD

- TAMPER RESISTANT SAFETY RECEPTACLE

- TELECOMMUNICATIONS BONDING BACKBONE

- TELEPHONE CABINET

- TELECOMMUNICATIONS CABLING INSTALLER

- TELEPHONE / DATA

- TELEPHONE

- TELECOMMUNICATIONS

- TELECOMMUNICATIONS GROUNDING BUSBAR

- TELECOMMUNICATIONS MAIN GROUNDING BUSBAR

- TWISTED PAIR

- TYPICAL

- UNDERGROUND

- UNSHIELDED TWISTED PAIR

- UNLESS OTHERWISE INDICATED

- VOLT

- WATT

- WASHER

- WIRELESS ACCESS POINT

- WEATHERPROOF

- TRANSFORMER

- XRAY

- XRAY VIEWER

- WYE

- ZONE ADAPTER MODULE

- ONE POLE

- TWO POLE

- THREE POLE

- FOUR POLE

- ONE POLE, ONE WIRE

- ONE POLE, TWO WIRE

- TWO POLE, TWO WIRE

- TWO POLE, THREE WIRE

- THREE POLE, TWO WIRE

- THREE POLE, THREE WIRE

- THREE POLE, FOUR WIRE

- FOUR POLE, FOUR WIRE

- AMPERE

- ALTERNATING CURRENT

- AMPERE FRAME

- ABOVE FINISHED FLOOR

- ABOVE FINISHED GRADE

- AMPERE INTERRUPTING CAPACITY

- AMERICAN NATIONAL STANDARDS INSTITUTE

- ALUMINUM

- AMP SWITCH

- AMP TRIP

- ARCHITECT

- AUTOMATIC TRANSFER SWITCH

- AUDIO VISUAL

- AMERICAN WIRE GRADE

- PEDESTAL MOUNTED ON BENCH TOP

- BELOW FLOOR

- BELOW FINISHED FLOOR

- BELOW FINISHED GRADE

- BUILDING

- CONDUIT

- CAMERA

- CATALOG

- CABLE TELEVISION

- CIRCUIT BREAKER

- CIRCUIT

- CEILING MOUNTED

- COPIER

- CURRENT TRANSFORMER

- COPPER

- CENTERLINE

- DIRECT CURRENT

- DRYER

- DELTA

- DISCONNECT

- DISHWASHER

- DRAWING

- EMERGENCY

- ELECTRICAL CONTRACTOR

- ELECTRIC METALLIC TUBING

- EXISTING TO REMAIN

- EXISTING TO BE REMOVED

- EXISTING TO BE RELOCATED

- RELOCATED EQUIPMENT'S NEW LOCATION

- ELECTRIC WATER COOLER

- EXISTING

- FIRE ALARM

- FULL LOAD AMPS

- FIBER OPTIC

- FIRE PROTECTION CONTRACTOR

- GENERAL CONTRACTOR

- GROUND FAULT CIRCUIT INTERRUPTER

- GROUND FAULT PROTECTION EQUIPMENT

- GROUND

- GALVANIZED RIGID CONDUIT

- HANDHOLE

- HORSEPOWER

- HEATING, VENTILATING, AND AIR CONDITIONING

- HERTZ (CYCLE) PER SECOND

- INSIDE PLANT

- INFORMATION TECHNOLOGY

- JUNCTION BOX

- KILOVOLT AMPERE

ELECTRICAL ABBREVIATIONS

EQUIPMENT AND PANELBOARDS

METER

CURRENT TRANSFORMER

CABINET

TRANSFORMER

- (X) INDICATES

DESIGNATION

BRANCH PANELBOARD

- SURFACE MOUNTED

- (X) INDICATES

DESIGNATION

BRANCH PANELBOARD

- RECESSED MOUNTED

- (X) INDICATES

DESIGNATION

DISTRIBUTION PANELBOARD

- (X) INDICATES

DESIGNATION

CT

M

X

X

X

X

X

X

X

X

WAVE POOL CONTROL PANEL

WP

CP

POOL EQUIPMENT

PANEL/CONTROL DEVICE

- (X) INDICATES

DESIGNATIONX

X

XXX

X DETAIL REFERENCE

- TOP DESIGNATES DETAIL NUMBER

- BOTTOM DESIGNATES SHEET NUMBER

GENERAL SYMBOLS

LIGHTING FIXTURES

12 VOLT POOL LIGHT

- (X) INDICATES TRANSFORMER

POOL IS SERVED FROM

POOL LIGHTING TRANSFORMER

- SEE SPECIFICATION SECTION 26 27 26

- (X) INDICATES:

TRANSFORMER DESIGNATION

LT

LT-X X

MOTOR STARTERS AND DISCONNECTS

MOTOR CONTROLLER

- MANUAL

MAGNETIC MOTOR STARTER FUSED DISCONNECT

SWITCH

NON - FUSED

DISCONNECT SWITCH

MAGNETIC COMBINATION MOTOR

STARTER

M

F

INDICATES SPACE FOR VARIABLE FREQUENCY

DRIVE (VFD) MOTOR CONTROLLER.

DESIGNATION OF POOL MOTOR BEING

CONTROLLED CLEARANCE WORKING SPACE IN

FRONT OF ANY OBSTRUCTIONS FOR THE

WIDTH AND DEPTH OF THIS SPACE, FROM

FLOOR TO 6'-6" AFF OR TO THE HEIGHT OF

THE VFD, WHICHEVER IS HIGHER.

P1D

INDICATES SPACE FOR REDUCED VOLTAGE

STARTER (RVS) MOTOR CONTROLLER.

DESIGNATION OF POOL MOTOR BEING

CONTROLLED CLEARANCE WORKING SPACE IN

FRONT OF ANY OBSTRUCTIONS FOR THE

WIDTH AND DEPTH OF THIS SPACE, FROM

FLOOR TO 6'-6" AFF OR TO THE HEIGHT OF

THE RVS, WHICHEVER IS HIGHER.

P1D

ELECTRICAL BOX

- FLOOR MOUNTED

- POKE THRU

- OUTLET TYPES REQUIRED

AT EACH BOX AS INDICATED

ON DRAWINGS

JUNCTION BOX

PULL BOX

HANDHOLE

MANHOLE

RACEWAYS AND BOXES

CABLE TAP BOX

MULTI-OUTLET RACEWAY

ASSEMBLY

- WALL MOUNTED 1'-6"

AFF, UOI

ELECTRICAL BOX

- FLOOR MOUNTED

- FLUSH

- OUTLET TYPES REQUIRED AT

EACH BOX AS INDICATED ON

DRAWINGS

BUSWAY

- RATING AND TYPE AS

INDICATED ON DRAWINGS

F

P

CTB

PB

HH

DEAD FRONT GFI

PROTECTIVE DEVICE

- (X) INDICATES CIRCUIT

NUMBER

GFIXOFF / BACKWASH /

FILTRATION SWITCH

Y X

WIRING DEVICES

DUPLEX RECEPTACLE

- MOUNTED 1'-6" AFF, UOI

- (X) INDICATES CIRCUIT NUMBER

(PANEL BOUNDARY AS

INDICATED ON DRAWINGS)

- (Y) INDICATES TYPE:

(GFCI) GROUND FAULT

CIRCUIT INTERRUPTING

(WP) WEATHERPROOF

(WR) WEATHER RESISTANT

MOTOR CONNECTION

- INDICATES MOTOR DESIGNATION

LOAD SIZE VOLTAGE / PHASE

SPECIAL PURPOSE OUTLET

- (X) INDICATES:

SPO DESIGNATIONX

PERMANENTLY-INSTALLED SWIMMING POOLS - POOL ELECTRICAL CONTRACTOR

1. ELECTRICAL INSTALLATIONS ASSOCIATED WITH PERMANENTLY-INSTALLED POOLS MUST COMPLY WITH NEC 680.20, 2020 EDITION.

2. EQUIPOTENTIAL BONDING: PER NEC 680.26. ALL METAL PARTS OF A PERMANENTLY-INSTALLED POOL STRUCTURE MUST BE BONDED TOGETHER WITH REBAR OR A #8 AWG SOLID COPPER CONDUCTOR. THIS INCLUDES CONCRETE-REBAR ASSOCIATED WITH POOL SHELL

CONSTRUCTION.

3. EQUIPOTENTIAL BONDING PERIMETER - POOL DECK: MUST EXTEND 3'-0" FROM BEYOND THE INSIDE WALL OF THE POOL. THE EQUIPOTENTIAL GRID MAY CONSIST OF REBAR OR A #8 AWG SOLID COPPER CONDUCTOR. POOL REINFORCING STEEL SHALL BE BONDED TO THE EQUIPOTENTIAL GRID AT A MINIMUM OF FOUR POINTS UNIFORMLY SPACED AROUND THE PERIMETER OF THE POOL.

4. METALLIC PARTS AND FITTINGS OF THE POOL STRUCTURE ARE PARTS TO BE BONDED TOGETHER IN ACCORDANCE WITH NEC ARTICLE 680.26.

5. METAL PARTS OF ELECTRICAL EQUIPMENT ASSOCIATED WITH WATER CIRCULATING SYSTEM MUST BE BONDED TOGETHER.

6. EXCEPTIONS: FIXED METAL PARTS GREATER THAN 5'-0" AWAY FROM POOL HORIZONTALLY, OR 12'-0" AWAY FROM POOL VERTICALLY, OR SEPARATED FROM POOL BY A BARRIER ARE NOT REQUIRED TO BE BONDED TO THE EQUIPOTENTIAL GRID.

7. REFER TO DRAWINGS, DETAILS, AND SPECIFICATIONS FOR AREAS OF DEMOLITION/CONSTRUCTION REQUIRING EQUIPOTENTIAL

BONDING PROVISIONS.

CONDUCTORS AND WIRING DEVICES - POOL ELECTRICAL CONTRACTOR

1. POOL ELECTRICAL CONTRACTOR SHALL FURNISH ALL CONDUCTORS, UNLESS OTHERWISE NOTED OR DIRECTED BY THE PROJECT MANAGER. ALL CONDUCTORS SHALL BEAR THE APPROVED UNDERWRITERS LABORATORIES, INC, U.L./ETL SEAL.

2. CONDUCTORS SHALL BE COLOR CODED AS REQUIRED BY SPECIFICATIONS.

3. NO SPLICING OF CONDUCTORS WITHIN RUNS OF CONDUIT WILL BE PERMITTED.

GENERAL PROJECT NOTES - POOL ELECTRICAL CONTRACTOR

1. NOT ALL SYMBOLS ON ELECTRICAL SYMBOLS SHEET ARE USED.

2. ALL MOUNTING HEIGHTS ARE TO THE CENTERLINE OF THE DEVICE BACKBOX UNLESS NOTED OTHERWISE.

3. ALL ELECTRICAL SYSTEMS INSTALLATIONS SHALL COMPLY WITH NFPA 70 (NATIONAL ELECTRICAL CODE, 2020 EDITION) AS WELL AS ALL

APPLICABLE LOCAL CODES.

4. POOL ELECTRICAL CONTRACTOR SHALL COORDINATE ALL WORK WITH OTHER TRADES PRIOR TO AND DURING INSTALLATION.

5. POOL ELECTRICAL CONTRACTOR SHALL NOT CUT, DRILL, OR IN ANY OTHER MANNER ALTER ANY STRUCTURAL MEMBER WITHOUT PRIOR

WRITTEN APPROVAL FROM THE STRUCTURAL ENGINEER.

6. POOL ELECTRICAL CONTRACTOR SHALL, BEFORE SUBMITTING PROPOSAL OR BID, EXAMINE ALL DRAWINGS AND SPECIFICATIONS RELATING TO THIS PROJECT, THE AMOUNT OF SPACE AVAILABLE FOR ELECTRICAL EQUIPMENT, THE PROJECT SITE, THE REQUIREMENTS TO CORRELATE THE ELECTRICAL WORK WITH ALL OTHER TRADES, AND THE TIME SCHEDULE NECESSARY TO PERFORM THAT WORK.

7. POOL ELECTRICAL CONTRACTOR SHALL, AFTER EXAMINATION OF ALL PLANS AND SPECIFICATIONS, INCLUDE ALL COSTS NECESSARY FOR ALTERATION OF, MODIFICATION OF, OR ADDITIONS TO THE ELECTRICAL SYSTEMS NECESSARY FOR A COMPLETE AND APPROVED INSTALLATION IN ALL ASPECTS. IT IS THE INTENT THAT ALL COSTS REQUIRED BE INCLUDED IN THE BID OF THIS TRADE.

8. POOL ELECTRICAL CONTRACTOR SHALL BASE THEIR PROPOSAL AND BID UPON THE EQUIPMENT AS SCHEDULED OR SPECIFIED, USING THE MANUFACTURERS AND MODEL NUMBERS AS CALLED FOR IN THE SPECIFICATIONS AND SCHEDULED ON THE DRAWINGS. IF MORE THAN ONE MANUFACTURER OF EQUIPMENT IS SPECIFIED, ANY ONE OF THE MANUFACTURERS OF EQUIPMENT MAY BE USED IN THIS CONTRACTOR'S

PROPOSAL.

9. POOL ELECTRICAL CONTRACTOR TO NOTIFY THE POOL DESIGN ENGINEER, IN WRITING, OF ANY DISCREPANCIES FOUND BETWEEN THESE ELECTRICAL PLANS AND OTHER ENGINEERING PLANS, ARCHITECTURAL PLANS, OR EXISTING FIELD CONDITIONS PRIOR TO FINAL BID PRICE

OR PERMITTING.

10. IN CASE OF DISPUTE OR DOUBT AS TO INTENT OF DRAWINGS OR SPECIFICATIONS, POOL ELECTRICAL CONTRACTOR SHALL CONTACT POOL ELECTRICAL ENGINEER AND OBTAIN WRITTEN CLARIFICATION PRIOR TO PROCEEDING WITH ANY BID OR CONSTRUCTION SCOPE INVOLVED.

11. POOL ELECTRICAL CONTRACTOR IS RESPONSIBLE FOR ORDERING ALL MATERIALS IN SUFFICIENT TIME TO AVOID DELAYING THE COMPLETION OF THE PROJECT. DELAY IN DELIVERIES SHALL NOT BE CONSIDERED A JUSTIFIABLE REASON FOR SUBMISSION OF

SUBSTITUTE MATERIALS.

12. ALL NOTES ON THE DRAWINGS INDICATED AS "TYPICAL" SHALL APPLY TO THE ENTIRE PROJECT, WHETHER OR NOT THE NOTES WRITTEN

ARE SPECIFICALLY INDICATED ON EACH DRAWING.

ELECTRICAL GENERAL NOTES

CODES, STANDARDS AND REGULATIONS:

POOL ELECTRICAL CONTRACTOR SHALL REVIEW AND BECOME FAMILIAR WITH ALL LOCAL CODES AND STANDARDS LISTED BELOW. IF THE POOL ELECTRICAL CONTRACTOR IDENTIFIES CONFLICTS BETWEEN THE CODE REQUIREMENTS AND THE PLANS OR SPECIFICATONS THEY SHALL

IMMEDIATELY ALERT THE POOL ELECTRICAL ENGINEER.

CODE JURISDICTION

USA / NAPLES / FL / COLLIER COUNTY

HEALTH & SAFETY CODE:

FLORIDA BUILDING CODE - BUILDING 8TH EDITION (2023): SECTION 454: SWIMMING POOLS AND BATHING PLACES (PUBLIC AND PRIVATE)

BUILDING CODES:

2023 FLORIDA BUILDING CODE

2020 NATIONAL ELECTRICAL CODE (NATIONAL FIRE PROTECTION CODE - NFPA CHAPTER 70)

ACCESSIBILITY STANDARDS AND REGULATIONS:

UNITED STATES:

2010 ADA STANDARDS FOR ACCESSIBLE DESIGN

World Leaders in Aquatic Planning, Design and Engineering

100 Park Avenue | Beaver Dam, WI 53916 t 920.887.7375 This Document and the ideas, renderings and other contents contained therein are the sole property of Water Technology, Inc. and may not be disseminated, copied, reproduced or otherwise used without prior written consent of Water Technology, Inc.

CONSULTANTS

PROJECT PHASE:

2300 Maitland Center Parkway Suite 210 Maitland, FL 32751 414.259.1500

DRAWINGS MUST BE

VIEWED AND PLOTTED

IN FULL COLOR.

S U

N -N

-F U

N L

A G

O O

N

R E

N O

V A

T

IO

N S

L iv in g st o n

R d

N a p le s, F L

PLE001.E

ELECTRICAL SYMBOLS,

ABBREVIATIONS, AND SHEET INDEX

ISSUE DATE: 11/08/2024

PROJECT NUMBER: 22567

DRAWN BY: JTO

CHECKED BY: RJJ

100% CONSTRUCTION DOCUMENTS

ELECTRICAL SYMBOLS AND ABBREVIATIONS

NOTE: NOT ALL SYMBOLS AND ABBREVIATIONS INDICATED HERE ARE USED IN DRAWINGS AND MAY NOT APPLY TO CURRENT PROJECT. ADDITIONAL SYMBOLS MAY BE INDICATED ON DRAWINGS.

ELECTRICAL SHEET INDEX - POOL E

PLE001.E ELECTRICAL SYMBOLS, ABBREVIATIONS, AND SHEET INDEX

ED110.E POOL E - IWF ELECTRICAL DEMOLITION PLAN

PLE110.E POOL E - IWF ELECTRICAL PLAN

PLE400.E PB1 - MECHANICAL ROOM ELECTRICAL PLAN

PLE501.E ELECTRICAL DETAILS

PLE601.E POOL E - ELECTRICAL WIRING SCHEMATIC

PLE701.E ELECTRICAL SCHEDULES

PLE702.E ELECTRICAL SCHEDULES

REVISION SCHEDULE

Number Description Date

Image

S

D01

D04

D03

D04

D03

D05

D06

(TYP.)

(TYP.)

D07 (TYP.)

EXISTING SPLASH PAD WET

DECK PLAY AREA

D08

EXISTING BURIED FIBERGLASS

COLLECTOR TANKS TO BE

REMOVED BY OTHERS. REFER

TO POOL PLAN SHEET D101.E

FOR ADDITIONAL INFORMATION.

EXISTING BURIED FIBERGLASS

COLLECTOR TANKS TO BE

REMOVED BY OTHERS. REFER

TO POOL PLAN SHEET D101.E

FOR ADDITIONAL INFORMATION.

D02

GENERAL DEMO NOTE

IT IS THE CONTRACTOR'S RESPONSIBILITY TO THOROUGHLY READ ALL DEMO

NOTES AND REVIEW ALONGSIDE THE KEYNOTES ON THE PLAN SHEETS. REFER

TO POOL AQUATICS DRAWINGS FOR ADDITIONAL DEMOLITION WORK AS PART

OF THE POOL SCOPE.

EXISTING WATER FEATURE, TO BE REMOVED

EXISTING SPRAY CAN TO BE REMOVED AND REPLACED WITH NEW

WATER FEATURE IN SAME LOCATION

EXISTING FLOOR DRAIN, TO BE REMOVED

- REFER TO SHEET D101.E AND PL130.E FOR ADDITIONAL INFORMATION

REGARDING EXISTING AND NEW WATER FEATURES

World Leaders in Aquatic Planning, Design and Engineering

100 Park Avenue | Beaver Dam, WI 53916 t 920.887.7375 This Document and the ideas, renderings and other contents contained therein are the sole property of Water Technology, Inc. and may not be disseminated, copied, reproduced or otherwise used without prior written consent of Water Technology, Inc.

CONSULTANTS

PROJECT PHASE:

2300 Maitland Center Parkway Suite 210 Maitland, FL 32751 414.259.1500

DRAWINGS MUST BE

VIEWED AND PLOTTED

IN FULL COLOR.

S U

N -N

-F U

N L

A G

O O

N

R E

N O

V A

T

IO

N S

L iv in g st o n

R d

N a p le s, F L

ED110.E

POOL E - IWF ELECTRICAL

DEMOLITION PLAN

ISSUE DATE: 11/08/2024

PROJECT NUMBER: 22567

DRAWN BY: JTO

CHECKED BY: RJJ

100% CONSTRUCTION DOCUMENTS

GENERAL SHEET NOTES

DEMO SHEET KEYNOTES

1/4" = 1'-0"A1

POOL E - IWF (INTERACTIVE WATER FEATURES) ELECTRICAL DEMOLITION PLAN

N

D01 THIS HALFTONE SOLID LINE REPRESENTS THE INSIDE EDGE OF THE EDGE OF

THE EXISTING IWF SPRAY PAD.

D02 EXTENT OF IWF CONCRETE PAD REMOVAL. SEE PL DEMOLITION PLANS FOR

ADDITIONAL INFORMATION.

D03 THIS BOLD LINE REPRESENTS THE INSIDE EDGE OF THE FIBERGLASS

COLLECTOR TANK TO BE REMOVED.

D04 THIS DASHED LINE REPRESENTS THE EXISTING FIBERGLASS COLLECTOR

TANK PERIMETER EQUIPOTENTIAL BONDING COPPER CONDUCTOR TO BE

REMOVED. POOL ELECTRICAL CONTRACTOR SHALL DISCONNECT EXISTING

EQUIPOTENTIAL BONDING CONDUCTOR TO ANY EXISTING FIXED METAL PART

TO FACILITATE ITS REMOVAL BY THE POOL GENERAL CONTRACTOR.

D05 EXISTING WATER SPRAY CAN WATER FEATURE SHALL BE REMOVED, TYPICAL

OF 45. (WATER SPRAY CAN IS FLUSH MOUNTED DEVICE ON THE SPRAY PAD

WITH A WATER SUPPLY, WATER DRAIN, AND A LIGHT SOURCE.). SEE NOTE

13/D101.E IN THE PL DRAWINGS SET FOR FOR ADDITIONAL INFORMATION. FOR

THE 45 EXISTING WATER SPRAY CANS TO BE REMOVED, BURY EXISTING

COPPER BONDING CONDUCTOR FOR FUTURE RE-USE.

D06 19 WATER SPRAY CANS SHALL BE DE-ENERGIZED, DISCONNECTED, AND

REMOVED. THOSE 19 LOCATIONS SHALL BE RE-USED FOR NEW WATER

FEATURES. FOR THE 19 LOCATIONS BEING RE-USED, POOL ELECTRICAL

CONTRACTOR SHALL DE-ENERGIZE, DISCONNECT, AND REMOVE WIRING

ASSOCIATED WITH WATER SPRAY CAN LIGHTING. REMOVE WIRING BACK TO

SOURCE PANEL. EXISTING CONDUIT MAY BE ABANDONED, CAPPED OFF IN

PLACE. EXISTING EQUIPOTENTIAL BONDING ASSOCIATED WITH THESE 19

LOCATIONS SHALL BE DISCONNECTED TO ACCOMMODATE WATER SPRAY CAN

REMOVAL BUT SHALL BE PROTECTED TO ALLOW BONDING TO BE

RE-CONNECTED TO METAL PARTS OF 19 NEW WATER FEATURES. SEE SHEET

D101.E FOR ADDITIONAL INFORMATION ON WATER SPRAY CAN REMOVAL AND

SHEET PL130.E FOR ADDITIONAL INFORMATION ON NEW WATER FEATURES.

D07 21 EXISTING METAL FLOOR DRAINS TO BE REMOVED. EXISTING BONDING

COPPER CONDUCTOR TO METAL FLOOR DRAINS TO BE BURIED FOR FUTURE

RE-USE.

D08 EXISTING AUTOFILL SENSOR TO BE DISCONNECTED AND REMOVED. REMOVE

EXISTING CABLE BACK TO SOURCE LOCATED IN MECHANICAL ROOM PB1. SEE

OVERALL SITE PLAN ON SHEET PL001.E FOR LOCATIONS OF EXISTING POOL E

AND EXISTING FILTERATION MECHANICAL ROOM PB1. EXISTING PIPE

BETWEEN TANK AND PB1 SHALL BE RE-USED AS A CONDUIT FOR THE 24V

SOLENOID VALVE WIRING. SEE SHEET 9/PL401.E AND DETAIL B3/PLE501.E FOR

ADDITIONAL INFORMATION.

WATER FEATURE LEGEND

REVISION SCHEDULE

Number Description Date

S

NEW POOL E

SURGE TANK

WATER

FEATURE (TYP.)

ACCESS

HATCH

LADDER

1 OF 4 09

09 4 OF 4

08060711

INDICATES NEW

EQUIPOTENTIAL BONDING

CONDUCTOR (TYP.)

D5

PLE501.E

C1

PLE501.E14

NEW WATER FEATURE

- REFER TO SHEET D101.E AND PL130.E FOR ADDITIONAL INFORMATION

REGARDING EXISTING AND NEW WATER FEATURES

World Leaders in Aquatic Planning, Design and Engineering

100 Park Avenue | Beaver Dam, WI 53916 t 920.887.7375 This Document and the ideas, renderings and other contents contained therein are the sole property of Water Technology, Inc. and may not be disseminated, copied, reproduced or otherwise used without prior written consent of Water Technology, Inc.

CONSULTANTS

PROJECT PHASE:

2300 Maitland Center Parkway Suite 210 Maitland, FL 32751 414.259.1500

DRAWINGS MUST BE

VIEWED AND PLOTTED

IN FULL COLOR.

S U

N -N

-F U

N L

A G

O O

N

R E

N O

V A

T

IO

N S

L iv in g st o n

R d

N a p le s, F L

PLE110.E

POOL E - IWF ELECTRICAL PLAN

ISSUE DATE: 11/08/2024

PROJECT NUMBER: 22567

DRAWN BY: JTO

CHECKED BY: RJJ

100% CONSTRUCTION DOCUMENTS

GENERAL SHEET NOTES

SHEET KEYNOTES

01 THIS HALFTONE SOLID LINE REPRESENTS THE INSIDE EDGE OF THE EXISTING

SPRAY PAD. USED, ALL LABOR AND MATERIALS TO BOND NEW FIXED METAL

PARTS OF NEW WATER FEATURES SHALL BE INCLUDED IN THE POOL

ELECTRICAL CONTRACTOR'S PRICE BID.

02 BONDING POINT BETWEEN EXISTING STRUCUTRAL REINFORCING STEEL AND

NEW STRUCTURAL REINFORCING STEEL. BONDING JUMPER SHALL BE SOLID,

#8 AWG, BARE COPPER CONDUCTOR. PROVIDE A MINIMUM OF FOUR (4)

UNIFORMLY SPACED BONDING CONNECTION POINTS AROUND THE

PERIMETER OF THE POOL IN ACCORDANCE WITH NEC 680.26(B)(2).

04 19 NEW WATER FEATURES TO BE BONDED TO EACH OTHER AND TO NEW

STRUCTURAL REINFORCING STEEL. BONDING SHALL BE SOLID, #8 AWG, BARE

COPPER CONDUCTOR. BONDING CONNECTIONS SHALL BE AS REQUIRED BY

THE NEC. RE-USE EXISTING BONDING CONDUCTOR FROM 19 EXISTING WATER

SPRAY CANS AS STATED ON KEYED NOTE D06 ON SHEET ED110.E. IF

NECESSARY, A NEW BONDING CONDUCTOR SHALL BE PROVIDED BETWEEN

NEW FIXED METAL PART AND NEW STRUCTURAL REINFORCING STEEL IN

ACCORDANCE WITH THE NEC AS SHOWN ON POOL PLANS. WHETHER NEW

CONDUCTOR IS REQUIRED OR EXISTING BONDING CONDUCTOR IS RE-USED,

ALL LABOR AND MATERIALS TO BOND THE NEW FIXED METAL PARTS OF NEW

WATER FEATURES SHALL BE INCLUDED IN THE POOL ELECTRICAL

CONTRACTOR'S PRICE. SEE DETAIL 1/ED101.E AND 1/PL130.E FOR ADDITIONAL

INFORMATION.

05 BONDING BETWEEN FIXED METAL PART AND NEW SURGE TANK PERIMETER

BONDING CONDUCTOR. BONDING SHALL BE SOLID, #8 AWG, BARE COPPER

CONDUCTOR. BONDING CONNECTIONS SHALL BE AS REQUIRED BY THE NEC.

06 THIS BOLD LINE REPRESENTS THE INSIDE EDGE OF THE NEW SURGE TANK.

THE POOL ELECTRICAL CONTRACTOR (PEC) SHALL REFERENCE THIS EDGE

LINE FOR THE PURPOSE OF DETERMINING THE EXTENT OF THE WET DECK

AREA. POOL EQUIPOTENTIAL BONDING REQUIREMENTS IN ACCORDANCE

WITH NFPA-NEC 70, ARTICLE 680. PEC SHALL SPECIFICALLY REFERENCE THIS

EDGE FOR DETERMINING THE FOLLOWING: CONDUCTIVE POOL SHELL IN

REFERENCE TO NEC 680.26(B)(1). EXTENT OF POOL PERIMETER SURFACES IN

REFERENCE TO NEC 680.26(B)(2). EXTENT OF POOL RELATED FIXED METAL

PARTS TO BE BONDED IN REFERENCE TO NEC 680.26(B)(7). ADDITIONAL

EQUIPOTENTIAL BONDING REQUIREMENTS OF NEC ARTICLE 680.

07 SURGE TANK SHELL IS POURED CONCRETE WITH UNENCAPSULATED STEEL

REINFORCING, WITH STEEL BEING CONNECTED WITH STEEL TIE WIRES. POOL

SHELL REINFORCING STEEL SHALL BE BONDED TO OTHER METAL PARTS AS

INDICATED ON THESE PLANS AND AS REQUIRED BY NEC 680.26.

08 THIS DASHED LINE REPRESENTS A DIRECT BURIED, SOLID, #8 AWG BARE

COPPER CONDUCTOR. CONDUCTOR SHALL BE USED TO EQUIPOTENTIALLY

BOND THE POOL PERIMETER SURFACE TO OTHER METALLIC, CONDUCTIVE

POOL EQUIPMENT IN ACCORDANCE WITH NEC 680.26. CONDUCTOR SHALL BE

LOCATED HORIZONTALLY BETWEEN 18" AND 24" FROM INSIDE WALLS OF

POOL, AND LOCATED UNDER THE PERIMETER SURFACE BETWEEN 4" AND 6"

BELOW SUBGRADE. SEE NEC 680.26(B)(2) FOR ADDITIONAL INSTALLATION

REQUIREMENTS.

09 BONDING POINT BETWEEN POOL PERIMETER AND POOL SHELL REINFORCING

STEEL. BONDING CONDUCTOR SHALL BE DIRECT BURIED, SOLID, #8 AWG,

BARE COPPER CONDUCTOR. BONDING CONNECTIONS SHALL BE AS

REQUIRED BY THE NEC.

11 APPROXIMATE LOCATION OF NEW AUTOFILL SENSOR CABLE TERMINATION.

ROUTE AUTOFILL SENSOR CABLE IN EXISTING 6" PIPE BACK TO AUTOFILL

CONTROLLER IN THE MECHANICAL ROOM. SEE PL DRAWINGS FOR PIPE

LOCATION. VERIFY EXACT LOCATION OF CABLE TERMINATION WITH POOL

CONTRACTOR.

14 BELIMO CONTROL VALVE WITH 24V ACTUATOR. VERIFY EXACT LOCATION

WITH POOL CONTRACTOR.

1/4" = 1'-0"A1

POOL E - IWF (INTERACTIVE WATER FEATURES) ELECTRICAL PLAN

N

1. THE POOL ELECTRICAL CONTRACTOR SHALL PROVIDE AN EQUIPOTENTIAL

BOND GRID IN POOL STRUCTURE SURROUNDINGS OF ALL POOLS PER NFPA 70.

BOND AND GROUND ALL PARTS AND PIECES OF THE POOL MECHANICAL

EQUIPMENT, POOL, DECK EQUIPMENT, UNDERWATER POOL LIGHTS,

ACTIVITIES, PERIMETER SURFACES AND ALL OTHER EMBEDDED METALLIC

ITEMS IN ACCORDANCE WITH NFPA 70 ARTICLE 680.26. THIS INCLUDES BUT IS

NOT LIMITED TO THE FOLLOWING EQUIPMENT:

A. THROUGH-WALL LIGHTING ASSEMBLIES AND UNDERWATER LUMINARIES.

B. ALL ELECTRICAL EQUIPMENT LOCATED WITHIN 5' OF THE INSIDE WALL OF

THE SPECIFIED POOL EDGE.

C. ALL ELECTRICAL EQUIPMENT ASSOCIATED WITH THE RECIRCULATION

SYSTEM OF THE SPECIFIED BODY OF WATER.

D. METALLIC JUNCTION BOXES.

E. TRANSFORMERS AND POWER SUPPLY ENCLOSURES.

F. POWER DISTRIBUTION EQUIPMENT ASSOCIATED WITH THE SPECIFIED

BODY OF WATER.

2. PLE DRAWINGS ATTEMPT TO SHOW REQUIRED BONDING CONNECTIONS BUT

NOT ALL REQUIRED BONDING CONNECTIONS ARE SHOWN ON THESE

DOCUMENTS. FIELD CONDITIONS AND DRAWINGS OF OTHER DESIGNERS MAY

RESULT IN ADDITIONAL BONDING REQUIREMENTS. ALL CODE REQUIRED

BONDING SHALL BE PROVIDED WHETHER SHOWN ON THESE PLANS OR NOT,

AND THE COST FOR THESE CONNECTIONS SHALL BE INCLUDED IN THE PLE

CONTRACTOR'S BID.

3. REFER TO AQUATICS SERIES OF DRAWINGS FOR LOCATIONS OF ALL

CONDUCTIVE EMBEDDED METALLIC ITEMS IN AND AROUND POOL THAT SHALL

BE TIED TO THE EQUIPOTENTIAL GROUNDING GRID.

WATER FEATURE LEGEND

REVISION SCHEDULE

B3

FM

FM

FM

FM

FD FDFD FD

D10

D10

NOTE: UNLESS NOTED

OTHERWISE, ALL EQUIPMENT

IS EXISTING TO REMAIN.

D11

D12

PUMP 9

PUMP 8

15 HP

50 HP

PUMP 9

PUMP 8

ER

ER

ER

ER

P2E P1E

ETR

ETR

ETR

ETR

ETR ETR

ETR

ETR

ETR ETR

ETR

ETR

ETR

ETR

ETR

ETR

ETR

P1E

PP1

H2

PP1

H2

SECTION 1

ETR

SECTION 2

ETR

PP1

L1

SECTION 1

ETR

SECTION 2

ETR

UP1E

AF1E

C3

PLE501.E

B1

PLE501.E

3E 1E

4E 2E

FP1

C1

PLE501.E

4E

3E

1E

2E

C1

PLE501.E

(TYP.)

B3

PLE501.E

AUTOFILL CONTROL UNIT.

VERIFY EXACT LOCATION

WITH POOL CONTRACTOR.

PP1

L1

P2E

F1E

FILTRATION SELECTOR

SWITCH. VERIFY EXACT

LOCATION WITH POOL

CONTRACTOR.

D3

PLE501.E

World Leaders in Aquatic Planning, Design and Engineering

100 Park Avenue | Beaver Dam, WI 53916 t 920.887.7375 This Document and the ideas, renderings and other contents contained therein are the sole property of Water Technology, Inc. and may not be disseminated, copied, reproduced or otherwise used without prior written consent of Water Technology, Inc.

CONSULTANTS

PROJECT PHASE:

2300 Maitland Center Parkway Suite 210 Maitland, FL 32751 414.259.1500

DRAWINGS MUST BE

VIEWED AND PLOTTED

IN FULL COLOR.

S U

N -N

-F U

N L

A G

O O

N

R E

N O

V A

T

IO

N S

L iv in g st o n

R d

N a p le s, F L

PLE400.E

PB1 - MECHANICAL ROOM

ELECTRICAL PLAN

ISSUE DATE: 11/08/2024

PROJECT NUMBER: 22567

DRAWN BY: JTO

CHECKED BY: RJJ

100% CONSTRUCTION DOCUMENTS

1/8" = 1'-0"C1

PB1 MECHANICAL ROOM - ELECTRICAL DEMOLITION PLAN

1/8" = 1'-0"A1

PB1 MECHANICAL ROOM - ELECTRICAL PLAN

SHEET KEYNOTES

GENERAL SHEET NOTES

DEMO SHEET KEYNOTES

GENERAL DEMO NOTE:

IT IS THE CONTRACTOR'S RESPONSIBILITY TO THOROUGHLY READ ALL DEMO

NOTES AND REVIEW ALONGSIDE THE KEYNOTES ON PLAN. REFER TO POOL

AQAUTCS DRAWINGS FOR ADDITIONAL DEMOLITION WORK AS PART OF THE

POOL SCOPE.

10 PROVIDE NEW VFD CONTROLLER FOR NEW PUMP. PEC SHALL VERIFY

EXISTING CONDITIONS AND INSTALL VFD IN THE VICINITY OF THE LOCATION

SHOWN ON THE PLANS. EXACT LOCATION SHALL BE DETERMINED BY THE

POOL ELECTRICAL CONTRACTOR IN THE FIELD. EXACT LOCATION SHALL

PROVIDE MINIMUM WORKING CLEARANCES AS REQUIRED BY THE NEC.

D10 DE-ENERGIZE AND DISCONNECT EXISTING MOTOR POWER CONDUCTORS AS

REQUIRED TO ACCOMMODATE PUMP REMOVAL BY OTHERS. DISCONNECT

AND REMOVE ELECTRICAL CONDUCTORS BACK TO SOURCE PANEL. IN

ADDITION TO DISCONNECTING POWER CONDUCTORS, DISCONNECT EXISTING

POOL SYSTEM EQUIPOTENTIAL BONDING CONDUCTOR. SALVAGE AND

PROTECT BONDING CONDUCTOR AND RECONNECT TO NEW MOTOR BEING

PROVIDED AT THIS LOCATION.

D11 EXISTING PUMP COMBINATION MOTOR STARTER SHALL BE REMOVED.

DISCONNECT AND REMOVE FEEDERS BACK TO SOURCE PANEL. REFER TO

ONE-LINE DIAGRAM ON SHEET PLE701.E FOR ADDITIONAL INFORMATION.

D12 EXISTING PUMP MOTOR VFD SHALL BE REMOVED. DISCONNECT AND REMOVE

FEEDERS BACK TO SOURCE PANEL. REFER TO ONE-LINE DIAGRAM ON SHEET

PLE701.E FOR ADDITIONAL INFORMATION. PEC SHALL HAND OVER EXISTING

VFD TO THE OWNER FOR FUTURE RE-USE.

N

N

GENERAL DETAIL NOTES:

1. THIS DETAIL IS DIAGRAMMATIC IN NATURE. IT DOES NOT DEPICT SPECIFIC POOL CONSTRUCTION DETAILS, NOR ALL EQUIPMENT THAT MAY REQUIRE BONDING, BUT INSTEAD IS INTENDED TO INDICATE THE VARIOUS ITEMS AND EQUIPMENT THAT ARE REQUIRED TO BE BONDED. ACTUAL EQUIPMENT REQUIRED TO BE BONDED WILL VARY FROM POOL TO POOL. SEE POOL SERIES PLANS DEPICT ITEMS REQUIRED TO BE BONDED ON AN INDIVIDUAL BASIS BUT MAY OR MAY NOT SHOW ALL REQUIRED POOL EQUIPOTENTIAL BONDING CONNECTIONS. REFER TO POOL DRAWINGS, SLIDE CONTRACTOR DRAWINGS, AND ALL OTHER RELEVANT DRAWINGS THAT COMPRISE THE PROJECT CONSTRUCTION DOCUMENTS FOR ADDITIONAL EQUIPMENT THAT MAY BE REQUIRED TO BE BONDED. DURING CONSTRUCTION, FURTHER CONFIRM BONDING REQUIREMENTS WITH ACTUAL FIELD CONDITIONS. ALL REQUIRED EQUIPOTENTIAL BONDING

SHALL BE INCLUDED IN THE POOL ELECTRICAL CONTRACTORS BASE PRICE.

2. INSTALLATION SHALL CONFORM TO NEC ARTICLE 680.

3. ALL BONDING CONNECTIONS SHALL BE CADWELD OR IRREVERSIBLE CLAMP AS STATED IN THE NEC.

4. ALL BONDING CONDUCTORS SHALL BE #8 AWG, BARE SOLID COPPER UNLESS OTHERWISE NOTED.

5. BOND ALL METAL DEVICES WITHIN 5' OF THE EDGE OF THE SPLASH PAD.

6. ISOLATED METAL PARTS THAT ARE NOT OVER 4 INCHES IN ANY DIMENSION AND DO NOT PENETRATE THE POOL STRUCTURE MORE THAN 1 INCH SHALL NOT

REQUIRE BONDING.

7. IN ADDITION TO REQUIREMENTS SHOWN HERE, SEE MOTOR CHASSIS EQUIPOTENTIAL BONDING DETAILS SHOWN ON PL PLANS FOR ADDITIONAL

INFORMATION.

8. NOT ALL EQUIPMENT REQUIRED TO BE BONDED IS PART OF THIS PROJECT SCOPE.

POOL WATER PUMP

MOTOR.

POOL PERIMETER BONDING

CONDUCTOR.

METAL POOL DRAIN COVER.

POOL ACTIVITY FEATURE STEEL

SUPPORT STRUCTURE.

THIS LINE REPRESENTS THE

BOUNDARY OR THE AREA 5'-0"

BEYOND THE INSIDE WALL OF THE

POOL.

POOL FEATURE FIXED METAL PART

POOL SHELL UN-ENCAPSULATED

STRUCTURAL REINFORCING STEEL.

ONE OF FOUR MINIMUM.

POOL METAL FENCING, BONDED AS

A FIXED METAL PART.

INTERIOR OF POOL

WALL

REINFORCING

STEEL (TYPICAL)

PLAN VIEW AT EXPANSION JOINT

EXPANSION

JOINT

POOL FINISH

REINFORCEMENT

STEEL

REINFORCEMENT

STEEL

BONDING

CONDUCTOR

6" M

IN

EXPANSION

JOINT

BONDING CONDUCTOR BELOW

WALKING SURFACE. LOOP AT

EXPANSION JOINT TO ALLOW FOR

MOVEMENT OF WALKING SURFACE.

WALKING SURFACE.

GENERAL DETAIL NOTES:

1. ALL BONDING CONNECTIONS SHALL BE CADWELD OR

IRREVERSIBLE CLAMP CONNECTIONS.

2. BONDING CONDUCTORS SHALL BE #8 AWG, SOLID, BARE,

COPPER.

3. ALL REINFORCING STEEL SHALL BE TIGHTLY TIED

TOGETHER COMPLETING BOND AS STATED PER NEC

680.26(B)(1).

4. REINFORCING STEEL THAT IS EFFECTIVELY INSULATED BY

AN ENCAPSULATING NON CONDUCTIVE COMPOUND AT THE

TIME OF MANUFACTURING SHALL NOT REQUIRE

GROUNDING PER NEC 680.26(B)(1).

DETAIL NOTES:

CADWELD OR CLAMP BONDING CONNECTION PER THE NEC.

BONDING CONDUCTOR.

POOL DECK

EXPANSION JOINT

STEGMEIER

DECK EDGE

POOL

REINFORCING

STEEL

INSIDE FACE

OF POOL

WALL

GRANULAR FILL

BONDING

WIRE

PER NEC 680

GENERAL DETAIL NOTES:

1. THIS DETAIL IS INTENDED TO ILLUSTRATE THE EQUIPOTENTIAL BONDING GRID AROUND EACH OUTDOOR POOL AS

REQUIRED BY NEC 680.

2. THE BONDING CONDUCTOR SHALL BE A DIRECT BURIED, SOLID, #8 AWG BARE COPPER CONDUCTOR. CONDUCTOR SHALL BE USED TO EQUIPOTENTIALLY BOND THE POOL PERIMETER SURFACE TO OTHER METALLIC, CONDUCTIVE POOL EQUIPMENT IN ACCORDANCE WITH NEC 680.26. CONDUCTOR SHALL BE LOCATED HORIZONTALLY BETWEEN 18" AND 24" FROM INSIDE WALLS OF POOL, AND LOCATED UNDER THE PERIMETER SURFACE BETWEEN 4" AND 6" BELOW SUBGRADE.

SEE NEC 680.26(B)(2) FOR ADDITIONAL INSTALLATION REQUIREMENTS.

3. THIS DETAIL IS NOT INTENDED TO DETAIL THE POOL WALLS OR THE DECKS. THE ABOVE POOL WALL IS GENERIC IN NATURE AND IS NOT TYPICAL FOR EACH POOL WALL. SEE POOL SECTIONS AND DECK SECTIONS FOR ADDITIONAL POOL

AND DECK CONSTRUCTION REQUIREMENTS.

4. SEE POOL ELECTRICAL DRAWINGS FOR ADDITIONAL BONDING & GROUNDING REQUIREMENTS.

POOL PERIMETER

SURFACE BONDING

CONDUCTOR

GENERAL DETAIL NOTES:

1. SEE DETAIL C3 ON THIS SHEET FOR LAMP & CABINET UV

SUPPORT FRAME INSTALLATION DETAIL.

UV PIPING LOOP BY POOL

MECHANICAL CONTRACTOR. UV

DISINFECTION UNIT. FURNISHED BY

OTHERS. INSTALLED BY POOL

MECHANICAL CONTRACTOR.

UV CONTROL CABINET. FURNISHED

BY OTHERS. INSTALLED AND

WIRED BY POOL ELECTRICAL

CONTRACTOR.

UV CABINET LINE VOLTAGE POWER

FEED CONDUIT BY POOL

ELECTRICAL CONTRACTOR. ROUTE

BETWEEN SOURCE PANEL AND UV

CABINET CONDUIT OVERHEAD.

UV UNIT WIRING, FURNISHED BY UV

EQUIPMENT MANUFACTURER,

INSTALLED BY OTHERS AS

DIRECTED BY UV EQUIPMENT

SUPPLIER.

2-HOLE, 90 FITTING

PART P1026

1 11/16"

6"

1/4"

6"

3 1/2"

(4) 3/4"

DIA HOLES

POST BASE - P2072ASQ

ADDITIONAL STRUT CHANNELS AND 90

FITTINGS TO SUPPORT CABLING, AS

REQUIRED.

FLOOR

2"

1 7/8"

UV

CONTROL

PANEL

POST BASE SPACING DEPENDENT ON CONTROL PANEL

WIDTH. REFER TO MANUFACTURER SHOP DRAWINGS FOR EXACT DIMENSIONS.

5' -6

R

E C

O M

M E

N D

E D

IN

S

T A

LL

H

E

IG

H T

T O

C E

N T

E R

O F

C O

N T

R O

L P

A N

E L.

ATTACH CONTROL

PANEL TO VERTICAL

STRUT LEGS.

DASHED LINE REPRESENTS

UV CONTROL CABINET.

REFER TO MANUFACTURER

SHOP DRAWINGS FOR

CONTROL PANEL

DIMENSIONS.

GENERAL DETAIL NOTES:

1. THIS DETAIL ILLUSTRATES THE MINIMUM SUPPORT AND BRACING REQUIREMENTS

FOR THE UV CONTROL PANEL INSTALLATION. THE INSTALLATION OF THE CONTROL

PANEL, SUPPORT FRAME, AND BRACING SHALL BE PROVIDED BY THE POOL

ELECTRICAL CONTRACTOR (PEC).

2. SEE THE "UV INSTALLATION DETAIL FOR ADDITIONAL PLUMBING AND THE UV LAMP

INSTALL REQUIREMENTS NOT SHOWN HERE.

3. COORDINATE WITH POOL MECHANICAL CONTRACTOR.

UV CABINET STRUT SUPPORT

FRAME. REFER TO SPEC

SECTION 26 05 29 FOR

ADDITIONAL REQUIREMENTS.

S

NEW SURGE

TANK LOCATED

NEAR POOL

NEW POOL WATER LEVEL SENSOR

UNIT (BY OTHERS) LOCATED

UNDER NEW WATER PARK SURGE

TANK ACCESS HATCH. PEC TO

INSTALL NEW CABLE TO NEW

AUTOFILL SENSOR.

GENERAL DETAIL NOTES:

1. REFER TO AQUATIC SERIES PLANS FOR EXACT LOCATIONS OF

EQUIPMENT PROVIDED BY THE POOL CONTRACTOR.

2. REFER TO AUTOFILL DETAIL 9/PL401.E ON AQUATIC DRAWINGS FOR

ADDITIONAL INFORMATION.

AquatiControl Tec hnology

POWERLEVELFILLING

MAN

CON TINUOUS

30 MINUTES

60 MINUTES

AUTO

15 5SEC SEC

DELAY

Model

ELC-800

ELC-800 WATER LEVEL

CONTROL UNIT PROVIDED BY

POOL CONTRACTOR.

BELIMO CONTROL VALVE WITH 24V

ACTUATOR PROVIDED AND INSTALLED

BY POOL CONTRACTOR. LOCATED IN

THE VICINITY OF THE SURGE TANK. SEE

PL PLANS FOR ADDITIONAL

INFORMATION.

120V/1PH/60 Hz

GROUND FAULT DUPLEX OUTLET

PROVIDED BY PEC

CONTROL CABLE FURNISHED

AND INSTALLED BY PEC, AND

TERMINATED BY POOL

CONTRACTOR. WIRING SHALL BE

(3) #14 AWG, 3/4" C.

6' CORD

PROVIDED WITH

CONTROLLER

NEW SENSOR CABLING IN

EXISTING 6" SKIMMER PIPE. PEC

TO INSTALL NEW CABLE TO NEW

AUTOFILL CONTROLLER AS

DIRECTED BY POOL

CONTRACTOR.

TO POOL

EQUIPMENT ROOM

AUTOFILL

CONTROLLER

POOL

EQUIPMENT

ROOM

GROUNDING TAB, HARDWARE

AND WIRE BY ELECTRICAL

CONTRACTOR

ANCHOR TOY TO BASE PLATE.

PROVIDED AND INSTALLED BY

OTHERS

CONCRETE FOOTING BY OTHERS

EXISTING WATER FEATURE PIPE

FPX

FLOW METER POWER

SOURCE

5-#20 SHIELDED IN

1/2" PVC CONDUIT

LINE VOLTAGE CIRCUIT

BY PEC AS SHOWN ON

EQUIPMENT SCHEDULE

TO ADDITIONAL

FLOWMETER DISPLAYS

AND SENSORS2-#18 SHIELDED IN

1/2" PVC CONDUIT

2-#18 SHIELDED IN

1/2" PVC CONDUIT

FLOW METER DISPLAY

FLOW METER SENSOR

FLOW METER SENSOR

FLOW METER DISPLAY

FD

FDXX

FM

FMXX

GENERAL DETAIL NOTES:

1. WIRING CIRCUITS SHOWN SHALL BE PROVIDED BY THE PEC. FLOW METER POWER SUPPLIES, FLOW METERS, AND FLOW METER DISPLAYS SHALL BE PROVIDED BY OTHERS.

2. POWER SUPPLY LOCATIONS ARE SHOWN ON THE PLE PLANS. PEC SHALL REFER TO POOL PLANS, SHEETS PL400 AND PL401 FOR EXACT LOCATIONS OF POWER SUPPLIES AND FOR LOCATIONS OF

FLOW METERS AND FLOW METER DISPLAYS.

3. WIRING DIAGRAM IS TYPICAL FOR ALL FLOW METER POWER SUPPLIES, FLOW METERS, AND FLOW

METER DISPLAYS. SEE SCHEDULE ASSOCIATED WITH THIS WIRING DIAGRAM SHOWING WHICH

POWER SUPPLIES SERVE WHICH METERS AND WHICH DISPLAYS.

BACKWASH

OFF

WEATHERPROOF

BOX

PROVIDE LABELS

AS DIRECTED BY

THE OWNER.

GREEN WATER/

CLEAR WATER

SELECTOR SWITCH

FILTRATION

World Leaders in Aquatic Planning, Design and Engineering

100 Park Avenue | Beaver Dam, WI 53916 t 920.887.7375 This Document and the ideas, renderings and other contents contained therein are the sole property of Water Technology, Inc. and may not be disseminated, copied, reproduced or otherwise used without prior written consent of Water Technology, Inc.

CONSULTANTS

PROJECT PHASE:

2300 Maitland Center Parkway Suite 210 Maitland, FL 32751 414.259.1500

DRAWINGS MUST BE

VIEWED AND PLOTTED

IN FULL COLOR.

S U

N -N

-F U

N L

A G

O O

N

R E

N O

V A

T

IO

N S

L iv in g st o n

R d

N a p le s, F L

PLE501.E

ELECTRICAL DETAILS

ISSUE DATE: 11/08/2024

PROJECT NUMBER: 22567

DRAWN BY: JTO

CHECKED BY: RJJ

100% CONSTRUCTION DOCUMENTS

NTSA5

POOL EQUIPMENT EQUIPOTENTIAL BONDING DETAIL

NTSA3

POOL FLOOR EXPANSION JOINT BONDING JUMPER DETAIL

NTSA1

POOL EQUIPOTENTIAL BONDING

NTSB1

UV DISINFECTION CONTROL CABINET LARGE

SCALE PLAN VIEW

NTSC3

UV DISINFECTION CONTROL CABINET SUPPORT & BRACING DETAIL

NTSB3

AUTOFILL DETAIL - SURGE TANK

NTSD5

WATER FEATURE GROUNDING DETAIL

NTSC1

FLOW METER DETAIL

FP1 PB1

FM1E-FD1E FM2E-FD2E FM3E-FD3E FM4E-FD4E

FLOW METER POWER SUPPLY POWER SUPPLY LOCATION ASSOCIATED FLOW METERS AND FLOW METER DISPLAYS

FLOW METER SCHEDULE

REVISION SCHEDULE

Number Description Date

NTSD3

FILTRATION SELECTOR SWITCH ELEVATION

A. THIS DRAWING IS DIAGRAMMATIC IN NATURE AND IS NOT INTENDED TO

BE AN INSTALLATION DRAWING. THIS DIAGRAM SHALL BE USED TO

DETERMINE HOW VARIOUS POOL EQUIPMENT IS INTERCONNECTED AND

THE WIRING IS TO BE USED BETWEEN THE EQUIPMENT.

B. IT SHALL BE THE POOL ELECTRICAL CONTRACTOR'S RESPONSIBILITY TO

FURNISH AND INSTALL ALL THE WIRING INDICATED IN THIS DIAGRAM,

BOTH LINE VOLTAGE AND LOW VOLTAGE CONTROL WIRING. LOW

VOLTAGE WIRING IS DEFINED AS WIRING THAT CARRIES CIRCUITS

OPERATING AT LESS THAN 50 VOLTS.

C. CONTROL WIRING SHALL BE TERMINATED BY THE POOL CONTROLS

CONTRACTOR.

D. ALL WIRING SHALL BE ROUTED IN CONDUIT PROVIDED BY THE POOL

ELECTRICAL CONTRACTOR. MINIMUM 3/4" CONDUIT SHALL BE USED.

CONDUITS SHALL BE SIZED SO THAT THE AREA OF THE CONDUCTORS

CONTAINED DO NOT EXCEED 40% OF THE AREA OF THE CONDUIT

PROVIDED.

E. THERE ARE ADDITIONAL CONTROL CIRCUITS (CONDUIT AND

CONDUCTORS) THAT ARE TO BE PROVIDED BY THE POOL ELECTRICAL

CONTRACTOR THAT ARE NOT SHOWN ON THE PLE PLANS. POOL

ELECTRICAL CONTRACTOR SHALL REFER TO THE PLC SERIES PLANS FOR

ADDITIONAL ITEMS REQUIRED TO BE INCLUDED AS PART OF THE PLE'S

SCOPE OF WORK.

F. REFER TO EQUIPMENT SCHEDULES AND PANEL SCHEDULES ON THE

PLE700 SERIES SHEETS FOR LINE VOLTAGE EQUIPMENT WIRING

REQUIREMENTS AND ADDITIONAL CIRCUITING INFORMATION.

G. PEC SHALL PREPARE AND SUBMIT FOR APPROVAL, RACEWAY

INSTALLATION AND ROUTING SHOP DRAWINGS TO SUPPORT THE

CONTROL WIRING SHOWN ON THESE DIAGRAMS. SEE SPECIFICATIONS

FOR CONTROL CONDUIT SUBMITTAL REQUIREMENTS.

H. IN ADDITION TO THE CONTROL WIRING SHOWN ON THIS SHEET, THERE IS

ADDITIONAL CONTROL WIRING AND CONDUIT REQUIRED TO BE PROVIDED

BY THE POOL ELECTRICAL CONTRACTOR. THOSE CIRCUITS ARE SHOWN

ON THE PLC SERIES PLANS INCLUDED IN THIS PRICING SET. REFER TO

THE PLC PLANS FOR ADDITIONAL CONTROL WIRING AND RACEWAY

REQUIREMENTS TO BE PROVIDED AS PART OF THE PEC'S SCOPE OF

WORK.

1. WIRING (LAMP POWER CORD) FURNISHED WITH UV UNIT AND INSTALLED BY

THE POOL ELECTRICAL CONTRACTOR. FINAL CONNECTIONS TO UV

CHAMBER AND CONTROL CABINET BY POOL CONTRACTOR.

2. FURNISHED WITH UV UNIT AND INSTALLED BY POOL CONTRACTOR.

3. ELECTRICAL WIRING FROM THE FILTER PROGRAMMER TO THE CHEMICAL

CONTROLLER SHALL DISABLE THE CHEMICAL CONTROLLER AND INACTIVE

ALL CHEMICAL FEEDERS WHEN THE CHEMICAL CONTROLLER AND INACTIVE

ALL CHEMICAL FEEDERS WHEN THE FILTER PROGRAMMER IS IN BUMP,

PRECOAT, OR OFF MODE AS INDICATED ON THIS TABLE BELOW.

4. ELECTRICAL WIRING FROM THE UV CONTROL CABINET TO THE

FILTRATION/ACTIVITY PUMP VFD SHALL TURN THE PUMP ON/OFF FOR THE

VARIOUS FILTER MODE (OFF/BACKWASH/FILTRATION) AS INDICATED IN THE

TABLE BELOW.

480 V

480 V

120 V (EXISTING)

LV

120 V (NEW)

EXISTING 480 V

PANELBOARD

EXISTING 120 V

PANELBOARD

EXISTING CHEMICAL CONTROLLER

'C1E'

NEW OFF/BACKWASH/FILTRATION

SWITCH 'F1E'

NEW VFD

NEW FILTRATION/ACTIVITY

PUMP 'P2E' (REDUNDANT)

LEGEND:

LOW VOLTAGE

LINE VOLTAGE

SEQUENCE OF OPERATIONS - SWIMMING POOL WITH MANUAL BACKWASH SAND FILTER SYSTEM

FILTRATION PUMP MOTOR STARTER SELECTOR SWITCH ("OFF/BACKWASH/FILTRATION"):

• A THREE POSITION SELECTOR SWITCH SHALL BE PROVIDED FOR THE MOTOR STARTER/VFD WITH POSITIONS LABELED "OFF", "BACKWASH", AND "FILTRATION".

"FILTRATION" POSITION:

• PLACE THE SWITCH IN THE "FILTRATION" POSITION FOR THE NORMAL FILTRATION OPERATING MODE OF THE SYSTEM.

• WITH THE FILTRATION PUMP SELECTOR SWITCH IN THE “FILTRATION” POSITION, THE FILTRATION PUMP SHALL RUN AT DESIGN

FLOW (FREQUENCY) AND THE CHEMICAL CONTROLLER SHALL BE CAPABLE OF ENERGIZING THE CHEMICAL FEED SYSTEM

OUTLETS.

• THE ACTUAL FLOW INFORMATION SHALL BE PROVIDED TO THE VFD BY THE FM TRANSMITTER. THE VFD SHALL ADJUST

FREQUENCY AS REQUIRED TO ACHIEVE SYSTEM DESIGN FLOW.

• THE CHEMICAL CONTROLLER SHALL BE WIRED TO THE CHEMICAL FEED OUTLETS AND SHALL ENERGIZE/DE-ENERGIZE THESE

OUTLETS BASED UPON POOL WATER CHEMISTRY.

• THE ACCU-TAB POWERBASE CONTROLLER IS POWERED ON/OFF BY THE CHEMICAL CONTROLLER CHLORINE FEED OUTLET.

• THE ACCU-TAB POWERBASE CHLORINE FEED BOOSTER PUMP IS ACTIVATED BY THE ACCU-TAB POWERBASE CONTROLLER.

• THE ACID FEED PUMP IS POWERED ON/OFF BY THE CHEMICAL CONTROLLER PH FEED OUTLET.

• IF THE FILTRATION PUMP LOSES POWER WHILE IN THE "FILTRATION" MODE THE CHEMICAL CONTROLLER SHALL NOT BE CAPABLE

OF ENERGIZING THE CHEMICAL FEED OUTLETS AND THE POOL HEATER SHALL BE INACTIVE.

"BACKWASH" POSITION:

• PLACE THE SWITCH IN THE "BACKWASH" POSITION WHEN BACKWASHING THE FILTERS.

• WITH THE FILTRATION PUMP SELECTOR SWITCH IN THE "BACKWASH" POSITION, THE FILTRATION PUMP SHALL RUN, BUT THE

CHEMICAL CONTROLLER SHALL NOT BE CAPABLE OF ENERGIZING THE CHEMICAL FEED SYSTEM OUTLETS AND THE POOL

HEATER SHALL BE INACTIVE.

"OFF" POSITION:

• PLACE THE SWITCH IN THE "OFF" POSITION TO TURN THE PUMP AND FILTRATION SYSTEM OFF.

• WITH THE FILTRATION PUMP SELECTOR SWITCH IN THE "OFF" POSITION, THE FILTRATION PUMP SHALL BE OFF AND THE

CHEMICAL CONTROLLER SHALL NOT BE CAPABLE OF ENERGIZING THE CHEMICAL FEED SYSTEM OUTLETS AND THE POOL

HEATER SHALL BE INACTIVE.

CHEMICAL CONTROLLER & CHEMICAL FEED OUTLETS:

• THE CHEMICAL CONTROLLER CPU SHALL BE POWERED AT ALL TIMES.

• THE CHEMICAL FEED OUTLETS SHALL BE INTERLOCKED SUCH THAT IF THE FILTRATION PUMP LOSES POWER WHILE IN THE

"FILTRATION" MODE, THE IN-LINE FLOW SWITCH IS NOT MADE OR THE SELECTOR SWITCH IS IN THE OFF OR BACKWASH

POSITIONS; THE FEED OUTLETS ARE INACTIVE.

• CHEMICAL CONTROLLER FEED OUTLETS ENERGIZES / DE-ENERGIZES SANITIZER AND pH FEED BASED UPON POOL WATER

CHEMISTRY.

• SWITCH BETWEEN ACID OUTLET AND CO2 OUTLET IS ACCOMPLISHED MANUALLY BY OPERATOR. LABEL OUTLETS AND SWITCH

AS CO2 AND ACID, RESPECTIVELY.

• CHEMICAL CONTROLLER FEED OUTLETS ENERGIZES / DE-ENERGIZES ENZYME FEED BASED UPON TIMED DELIVERY.

CHEMICAL FEED PUMPS

• THE CHEMICAL FEED PUMPS ARE ENERGIZED BY THE CHEMICAL FEED OUTLETS.

208 V

LV

NEW UV CONTROL

CABINET 'UP1E'

NEW UV CHAMBER 'UV1E'

2 1 A

LV

NEW VFD

480 V

NEW FILTRATION/ACTIVITY

PUMP 'P1E'

LV

FLOW METER POWER

SUPPLY 'FP1'

120 V

FLOW METER DISPLAY

'F1DE', 'F2DE', 'F3DE', 'F4DE',

CO2 FEED SOLENOID

• THE CO2 FEED SOLENOID IS ACTIVATED BY THE CHEMICAL FEED OUTLETS.

POOL HEATER:

• THE POOL HEATER SHALL BE INTERLOCKED SUCH THAT IF THE FILTRATION PUMP LOSES POWER WHILE IN THE FILTRATION MODE

OR IF THE SELECTOR SWITCH IS IN THE OFF OR BACKWASH POSITIONS; THE HEATER IS INACTIVE.

• THE POOL HEATER CIRCULATING PUMP IS CONTROLLED BY THE POOL HEATER CONTROLLER.

• POOL HEATER CYCLES ON AND OFF AS NEEDED BASED UPON POOL WATER TEMPERATURE.

• POOL HEATER IS INTERLOCKED WITH MANUFACTURER SUPPLIED FLOW SWITCH AND HI-LIMIT TEMP SENSORS.

FLOW METER:

• WHEN FLOW METER POWER SUPPLY IS ENERGIZED, THE FLOW METER SENSOR SHALL PROVIDE THE FLOW READOUT IN GPM.

• THE FLOW METER SHALL PROVIDE FLOW DATA TO THE INDICATED VFD AND CONTROL SPEED OF THE VFD BASED ON FLOW.

ULTRAVIOLET (UV) DISINFECTION UNIT:

• THE UV UNIT IS NORMALLY ON.

• THE UV UNIT SHALL BE INTERLOCKED SUCH THAT IF THE SELECTOR SWITCH IS IN THE BACKWASH POSITION THE UV SHALL BE

TURNED OFF.

• THE UV NORMALLY RUNS IN VARIABLE POWER MODE.

• COMBINED CHLORINE UV CONTROL: WITH FREE AND TOTAL CHLORINE SENSORS, THE CONTROLLER SHALL PROVIDE UV BOOST

CONTROL OF A UV SYSTEM BASED UPON THE COMBINED CHLORINE SET POINT. WHEN COMBINED CHLORINE IS ABOVE THE SET POINT THE UV SYSTEM SHALL BOOST TO 100% TO INCREASE THE CHLORAMINE DESTRUCTION RATE. THE UV SHALL RETURN TO

VARIABLE POWER MODE ONCE COMBINED CHLORINE DROPS BELOW THE SET POINT.

"X" INDICATES THE EQUIPMENT IS ENERGIZED/RUNNING.

"O" INDICATES THE EQUIPMENT IS NOT ENERGIZED.

FILTRATION

SELECTOR SWITCH

POSITION

FILTRATION

PUMP

CHEMICAL

CONTROLLER

CHLORINE

FEED

ACID FEED

HEATER OR HEAT

EXCHANGER

OFF O X O O

BACKWASH X X O O

FILTRATION

O

O

UV

X X X X X

O

O

X

C1

PLE501.E

SEE DETAIL FOR EXACT

CONFIGURATION

AUTOFILL RELAY 'AF1E'

120 V

SOLENOID VALVE

ELECTRODE ASSEMBLY

120 V

LV

LV

LV

FLOW METER SENSOR

'F1ME', 'F2ME', 'F3ME', 'F4ME',

C

World Leaders in Aquatic Planning, Design and Engineering

100 Park Avenue | Beaver Dam, WI 53916 t 920.887.7375 This Document and the ideas, renderings and other contents contained therein are the sole property of Water Technology, Inc. and may not be disseminated, copied, reproduced or otherwise used without prior written consent of Water Technology, Inc.

CONSULTANTS

PROJECT PHASE:

2300 Maitland Center Parkway Suite 210 Maitland, FL 32751 414.259.1500

DRAWINGS MUST BE

VIEWED AND PLOTTED

IN FULL COLOR.

S U

N -N

-F U

N L

A G

O O

N

R E

N O

V A

T

IO

N S

L iv in g st o n

R d

N a p le s, F L

PLE601.E

POOL E - ELECTRICAL WIRING

SCHEMATIC

ISSUE DATE: 11/08/2024

PROJECT NUMBER: 22567

DRAWN BY: JTO

CHECKED BY: RJJ

100% CONSTRUCTION DOCUMENTS

GENERAL SHEET NOTES

SHEET KEYNOTES

NTSA1

ELECTRICAL WIRING DIAGRAM - SYSTEM E

C 18 AWG 6 CONDUCTOR NON-SHIELDED PLENUM WINDY CITY WIRE 002391 PEC PEC POOL CONTRACTOR DEFENDER TO VFD

A 18 AWG 2 CONDUCTOR NON-SHIELDED PLENUM WINDY CITY WIRE 002360 PEC PEC POOL CONTRACTOR TEMPERATURE SENSORS

CABLE

DESIGNATION

DESCRIPTION MANUFACTURER MODEL NUMBER

FURNISHED

BY

INSTALLED

BY

TERMINATED BY TYPICAL USE

POOL FILTERING SYSTEM CONTROL CABLE SCHEDULE

EXISTING PANEL 'PP1/H2 - SECTION 1'

480Y/277 VOLT, 3 PHASE, 4 WIRE

NEW

PUMP P1E

(20 HP)

EXISTING 15 HP

FILTRATION

PUMP 9

40A 3P

CUT OFF EXISTING

CONDUIT AT FLOOR

(TYP.)

MINIMUM 18" LIQUID

TIGHT FLEXIBLE

METAL CONDUIT AT

MOTOR TERMINALS.

(TYP.)

JUNCTION BOX

IF NECESSARY

(TYP.)

4 5

3-#8

1-#10 GRD.,

3/4" C.

VFD CABLE

50A 3P

VFD

NEW

PUMP P2E

(20 HP) -

REDUNDANT

EXISTING 50 HP

FEATURE

PUMP 8

VFD

2 6

EXISTING COMBINATION

MOTOR STARTER TO BE

REMOVED

3-#8

1-#10 GRD.,

3/4" C.

EXISTING TO REMAIN

EXISTING TO BE REMOVED

NEW

3-#8

1-#10 GRD.,

3/4" C.

VFD CABLE

50A 3P

VFD

3-#8

1-#10 GRD.,

3/4" C.

150A 3P

EQUIPMENT CONNECTION SCHEDULE GENERAL NOTES:

A. VERIFY ALL MCA AND MOCP REQUIREMENTS WITH SUBMITTED AND APPROVED

EQUIPMENT PRIOR TO ELECTRICAL ROUGH-IN. ADJUST CIRCUIT SIZES

ACCORDINGLY.

B. REFER TO SPECIFICATIONS FOR SPECIFIC REQUIREMENTS AND SCOPE FOR

CONTROL WIRING, LINE WIRING, CONTROLLERS, AND DISCONNECTS.

C. VERIFY ALL INSTALLATION REQUIREMENTS WITH EQUIPMENT INSTALLER PRIOR

TO ROUGH-IN.

D. LOCATIONS OF DISCONNECTS FOR EACH PIECE OF EQUIPMENT MAY NOT BE

SHOWN ON PLANS. IF DISCONNECT FOR EQUIPMENT IS NOT SHOWN,

CONTRACTOR TO FIELD COORDINATE LOCATION IN ACCORDANCE WITH CODE.

E. FOR FUSED DISCONNECTS, IF FUSE SIZE IS NOT LISTED IT SHALL MATCH THE

AMPERAGE RATING OF THE FUSIBLE DISCONNECT.

F. FOR ALL EQUIPMENT WITH NON-INTEGRAL CONTROLLER/DISCONNECTS/VFD,

CONTRACTOR SHALL RUN CONDUIT AND WIRE FROM PANEL TO

CONTROLLER/DISCONNECT/VFD AND THEN FROM

CONTROLLER/DISCONNECT/VFD TO EQUIPMENT ITEM.

G. ABBREVIATIONS USED IN THESE SCHEDULES ARE AS FOLLOWS:

CP - CONTROL PANEL

CS - COMBINATION MAGNETIC CONTROLLER

CR - CONTROL RELAY

CW - CONTROL WIRING (REGARDLESS OF VOLTAGE)

DR - 20 AMP, 120 VOLT DUPLEX RECEPTACLE REQUIRED

ECM - ELECTRONICALLY COMMUTATED MOTOR

F - FURNISHED BY

GFI - GROUND FAULT CIRCUIT INTERRUPTER

I - INSTALLED BY

IU - IN UNIT

LOC - LOCATION

MAG - MAGNETIC STARTER

MCA - MINIMUM CIRCUIT AMPACITY

MOCP - MAXIMUM OVERCURRENT PROTECTION DEVICE

MTR CKT - MOTOR CIRCUIT CONDUCTORS (REFERS TO POWER WIRING

BETWEEN THE CONTROLLER AND THE MOTOR HOUSING TERMINALS)

NA - NOT APPLICABLE

NG - NEUMAN GROUP

NU - NEAR UNIT

PEC - POOL ELECTRICAL CONTRACTOR

PMC - POOL MECHANICAL CONTRACTOR

RVS - REDUCED VOLTAGE STARTER

UM - UNIT MANUFACTURER

VFD - VARIABLE FREQUENCY DRIVE CONTROLLER

KEYNOTES:

AT THEIR OPTION, CONTRACTOR MAY RE-USE EXISTING RACEWAY WHERE

POSSIBLE AND PRACTICAL. CASUAL SITE OBSERVATION ON THE PART OF THE

ENGINEER INDICATES THAT RACEWAYS BETWEEN WALL MOUNTED

CONTROLLERS AND FLOOR MOUNTED PUMPS IS ROUTED BELOW THE

BUILDING FLOOR SLAB. PRIOR TO PULLING NEW CONDUCTORS IN EXISTING

RACEWAYS, CONTRACTOR SHALL EXAMINE THE CONDITION OF THE EXISTING

RACEWAYS AND CONFIRM THEY ARE NOT DAMAGED OR COMPROMISED IN ANY

WAY. FINAL INSTALLATION SHALL MEET ALL REQUIREMENTS OF THESE

DOCUMENTS (UNLESS OTHERWISE APPROVED IN WRITING BY THE ENGINEER)

AND ALL APPLICABLE CODES. ALL WORK AND ANY ASSOCIATED COSTS

REQUIRED TO MODIFY OR REPLACE EXISTING RACEWAYS SHALL BE INCLUDED

IN THE CONTRACTOR'S BASE BID. SEE KEYNOTE 2 ON THIS SHEET FOR

ADDITIONAL INFORMATION.

LOCATE NEW MOTOR CONTROLLER AT SAME LOCATION AS EXISTING

CONTROLLER. ASSOCIATED MOTOR FEEDER CONDUITS MAY BE RE-USED

WHERE POSSIBLE AND PRACTICAL AS INDICATED ON NOTES FOUND

ELSEWHERE ON THIS SHEET. CONTRACTOR SHALL MODIFY EXISTING

RACEWAYS AS REQUIRED TO ACCOUNT FOR SIZE AND MOUNTING

DIFFERENCES BETWEEN EXISTING CONTROLLERS BEING REMOVED AND NEW

CONTROLLERS REQUIRED BY THESE DOCUMENTS.

PROVIDE NEW CIRCUIT BREAKER IN EXISTING PANEL TO SERVE NEW MOTOR AS

INDICATED. NEW BREAKER SHALL OF SAME MANUFACTURER, TYPE, AND IC

RATING TO MATCH EXISTING. EXISTING, ABANDONED CIRCUIT BREAKER SHALL

BE REMOVED AS REQUIRED TO CREATE SPACE FOR NEW CIRCUIT BREAKER.

TURN REMOVED BREAKERS OVER TO THE OWNER. CONTRACTOR'S SCOPE OF

WORK SHALL INCLUDE ANY REQUIRED MODIFICATIONS TO THE PANEL

ENCLOSURE AND BREAKER COVERS TO ACCOMMODATE THE REMOVAL OF AND

INSTALLATION OF CIRCUIT BREAKERS. ANY REQUIRED MODIFICATIONS SHALL

BE PERFORMED AT THE DIRECTION AND APPROVAL OF THE PANEL

MANUFACTURER.

THIS PANEL CONTAINS ADDITIONAL BREAKERS THAT ARE NOT SHOWN ON THIS

ONE-LINE DIAGRAM. EXISTING BREAKERS THAT ARE NOT SHOWN ARE

"EXISTING TO REMAIN".

EXISTING POWER PANEL AS MANUFACTURED BY SIEMENS. ELECTRICAL

CONTRACTOR SHALL VERIFY EXACT SERIES AND MODEL NUMBER AND SHALL

PROVIDE NEW BREAKERS AS REQUIRED, COMPATIBLE WITH THE EXISTING

DISTRIBUTION PANEL. SEE KEYNOTE 3 ON THIS SHEET FOR ADDITIONAL

INFORMATION.

EXISTING VFD SHALL BE REMOVED. DISCONNECT AND REMOVE FEEDERS BACK

TO SOURCE PANEL. PEC SHALL HAND OVER EXISTING VFD TO OWNER FOR

FUTURE RE-USE.

World Leaders in Aquatic Planning, Design and Engineering

100 Park Avenue | Beaver Dam, WI 53916 t 920.887.7375 This Document and the ideas, renderings and other contents contained therein are the sole property of Water Technology, Inc. and may not be disseminated, copied, reproduced or otherwise used without prior written consent of Water Technology, Inc.

CONSULTANTS

PROJECT PHASE:

2300 Maitland Center Parkway Suite 210 Maitland, FL 32751 414.259.1500

DRAWINGS MUST BE

VIEWED AND PLOTTED

IN FULL COLOR.

S U

N -N

-F U

N L

A G

O O

N

R E

N O

V A

T

IO

N S

L iv in g st o n

R d

N a p le s, F L

PLE701.E

ELECTRICAL SCHEDULES

ISSUE DATE: 11/08/2024

PROJECT NUMBER: 22567

DRAWN BY: JTO

CHECKED BY: RJJ

100% CONSTRUCTION DOCUMENTS

EQUIPMENT CONNECTION SCHEDULE - POOL E

# SERVING LOCATION

LOAD

(AMPS-HP-

WATTS)

LOAD

(VA)

VOLTAGE PHASE

CIRCUIT

BREAKER

FEED FROM WIRING MOTOR CONTROLLER INFO

MOTOR

DISCONNECT

MEANS

SEE NOTE

PANEL CIRCUIT

PHASE &

NEUTRAL

QTY.

PHASE

SIZE

GROUND

SIZE

CONDUIT

SIZE

TYPE FB IB

MTR

CKT

CW LOC

DISC

MEANS

AF1E AUTOFILL CONTROLLER PB1 - 500 VA 120 V 1 20 A

PP1/L1 - SECTION 2

(NEW CONDITION)

61 1 12 12 3/4" - - - - - - - - 3

FP1 FLOW METER POWER SUPPLY PB1 - 500 VA 120 V 1 20 A

PP1/L1 - SECTION 2

(NEW CONDITION)

67 1 12 12 3/4" - - - - - - - -

P1E FILTRATION/ACTIVITY PUMP PB1 20 HP 22447 VA 480 V 3 50 A

PP1/H2 - SECTION 1

(NEW CONDITION)

1,3,5 3 8 10 3/4" VFD PEC PEC PEC PEC NU - - 1, 2, 4, 6

P2E

FILTRATION/ACTIVITY PUMP

(REDUNDANT)

PB1 20 HP 22447 VA 480 V 3 50 A

PP1/H2 - SECTION 1

(NEW CONDITION)

7,9,11 3 8 10 3/4" VFD PEC PEC PEC PEC NU - - 1, 2, 5, 6

UP1E ULTRA VIOLET DISINFECTION PANEL PB1 1.5 KW 1664 VA 208 V 1 20 A

PP1/L1 - SECTION 2

(NEW CONDITION)

63,65 2 12 12 3/4" - - - - - - - -

PUMP BUILDING PB-1 - PARTIAL ONE-LINE DIAGRAM - POOL E

EQUIPMENT CONNECTION SCHEDULE NOTES:

1. PROVIDE 18" MINIMUM OF FLEXIBLE CONDUIT AT MOTOR TO FACILITATE FUTURE REMOVAL. PROVIDE FULL INSTALLATION AND WIRING OF PUMP VFD, INCLUDING UNISTRUT

FRAMING AS NECESSARY.

2. NEW REPLACEMENT PUMP. REPLACE EXISTING PUMP MOTOR STARTER WITH NEW VFD. REFER TO PARTIAL ONE-LINE DIAGRAM ON THIS SHEET FOR ADDITIONAL INFORMATION.

3. PROVIDE GFI PROTECTED DUPLEX OUTLET AT CONTROLLER LOCATION AS SHOWN ON DETAIL B3/PLE501.E.

4. ELECTRICAL WIRING INTERLOCK IS REQUIRED BETWEEN EXISTING FILTER PROGRAMMER AND FILTRATION PUMP. SEE ELECTRICAL WIRING DIAGRAM ON SHEET PLE601.E FOR

ADDITIONAL INFORMATION.

5. ELECTRICAL WIRING INTERLOCK IS REQUIRED BETWEEN FILTRATION PUMP AND ACTIVITY PUMP. SEE ELECTRICAL WIRING DIAGRAM ON SHEET PLE601.E FOR ADDITIONAL

INFORMATION.

6. VERIFY EXACT CONFIGURATION OF EXISTING EM STOP WIRING. IF POSSIBLE, CONNECT EXISTING EM STOP TO NEW PUMP CONTROLS AS NECESSARY. FOR BIDDING PURPOSES, ASSUME 50' OF 3/4" CONDUIT WILL BE REQUIRED BETWEEN EXISTING PUMP EM STOP AND PUMP VFD'S. COORDINATE EXACT EM STOP REQUIREMENTS AND LOCATION WITH

OWNER.

World Leaders in Aquatic Planning, Design and Engineering

100 Park Avenue | Beaver Dam, WI 53916 t 920.887.7375 This Document and the ideas, renderings and other contents contained therein are the sole property of Water Technology, Inc. and may not be disseminated, copied, reproduced or otherwise used without prior written consent of Water Technology, Inc.

CONSULTANTS

PROJECT PHASE:

2300 Maitland Center Parkway Suite 210 Maitland, FL 32751 414.259.1500

DRAWINGS MUST BE

VIEWED AND PLOTTED

IN FULL COLOR.

S U

N -N

-F U

N L

A G

O O

N

R E

N O

V A

T

IO

N S

L iv in g st o n

R d

N a p le s, F L

PLE702.E

ELECTRICAL SCHEDULES

ISSUE DATE: 11/08/2024

PROJECT NUMBER: 22567

DRAWN BY: JTO

CHECKED BY: RJJ

100% CONSTRUCTION DOCUMENTS

HB = HAND-BLOCKING DEVICE

HACR = HEATING AND AIR-CONDITIONING RATED

GFCI = GROUND FAULT CIRCUIT INTERRUPTER

ST = SHUNT TRIP

ABBREVIATIONS:

29 0 -- 30

27 0 -- 28

EXISTING 25 HP PUMP-11A

(ETR)

60 A

(ETR)

0 --

3 -- EXISTING SPACE

23 0 0 24

21 0 0 22

EXISTING 20 HP PUMP-12A

(ETR)

100 A

(ETR)

0 0

40 A

(ETR)

EXISTING 15 HP PUMP-14B

(ETR)

17 0 0 18

15 0 0 16

EXISTING 15 HP PUMP-12B

(ETR)

40 A

(ETR)

0 0

100 A

(ETR)

EXISTING 20 HP PUMP-13A

(ETR)

11 5,850 0 12

9 5,850 0 10

EXIS…