25-0014 SOW.pdf
PDF 102 KB Posted
- Attached to
- Building FC65 Exhaust System Repairs
- Solicitation number
- N4008526R9023
About this file
This is a Statement of Work for exhaust system repairs at Building FC65, a mess hall facility located on Gonzalez Boulevard West, Camp Lejeune, North Carolina. The project objective is to replace the exhaust systems and associated ductwork serving three dishwashers to eliminate condensation that currently drips onto ceilings.
The work encompasses four distinct tasks across fans F-12, F-7, F-11, and F-6. For F-12, the contractor shall demolish the existing fan and ductwork, cap the remaining ductwork in the female head above the sheetrock ceiling, remove all wiring and control connections to the Building Management System (BMS), replace the sheetrock ceiling with a new access door, and restore drop ceiling and tiles in the adjacent hallway. For F-7, F-11, and F-6, the contractor shall demolish existing equipment and install new stainless-steel ductwork with welded seams, properly sloped from the dishwashers to new roof-mounted exhaust fans equipped with backdraft dampers. All work requires installation of new properly-sized circuit breakers, electrical wiring, conduits, and disconnects mounted on the roof near the new exhaust fans. New control wiring must connect each dishwasher to its exhaust fan and the BMS for monitoring and alarms, with each exhaust fan configured to run an additional 15 minutes after dishwasher shutdown. Additional requirements include sealing ductwork and conduit exit points to match existing conditions, relocating lightning grounding cables as needed, and installing temporary walls in the storage room to separate the work area from operational mess hall areas. The contractor must follow Combined DIV 01 DBB Specifications and BACnet Direct Digital Control Systems for HVAC standards. All scheduling and access shall be coordinated with the Building Manager, and after-hours work may be required to prevent mess hall service interruptions.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Amend 0001.pdf | ||
| 25-0014 REVISED SOW 13APR2026.pdf | ||
| N4008525B0014 Specs.pdf | ||
| N4008525B0014 Dwgs.pdf | ||
| Mech MACC RFP.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
DISTRIBUTION: DoD COMMUNITY ONLY
TITLE: 25-0014 Building FC65 Exhaust System Repairs
ATTACHMENTS:
Contractor shall follow Combined DIV 01 DBB SPECS and BACnet DIRECT DIGITAL CONTROL SYSTEMS FOR HVAC
(CLGS-23-09-23.13 August 2024)
SCOPE OF WORK:
The contractor shall provide all material, labor, equipment, and supervision required to accomplish the following:
General Description:
The intent of this project is to replace the exhaust system and associated ductwork on all three dishwashers to prevent condensation from dripping on ceilings. FC65 is located on Gonzalez Blvd. West on Camp Lejeune, N.C.
28547.
REQUIREMENTS AND SPECIFICATIONS:
1. F-12 – Demo fan and associated ductwork. Cap existing ductwork where it enters female head above sheetrock ceiling. F-12 will no longer be used. Demo all wiring and conduit, including control wiring back to the BMS. Replace sheetrock ceiling and install new access door in Female Head after overhead work has been completed. Prep and paint with like color paint. Remove drop ceiling in hallway outside female head to access exhaust fan, ductwork, and wiring to be demoed. When overhead work is completed, reinstall drop ceiling and replace as necessary. Install new ceiling tiles.
2. F-7 – Demo F-7 and all associated ductwork from F-7 transition to exit point on the roof. Ensure remaining ductwork back to dishwasher is properly sloped. Demo existing wiring and conduit, including any control wiring. Install properly sized and sloped new stainless-steel ductwork, with welded seams, up to new properly sized roof-mounted exhaust fan with backdraft damper. Install new properly sized circuit breaker for new roof-mounted exhaust fan. Route properly sized electrical wiring and conduit to new properly sized disconnect for new exhaust fan. New disconnect shall be mounted on the roof near the new exhaust fan. Route properly sized new wiring and conduit from disconnect to exhaust fan. Install new control wiring and conduit connecting dishwasher to new exhaust fan and exhaust fan to BMS for monitoring and alarms. Ensure new exhaust fan runs an additional 15 minutes after dishwasher shuts off. Seal area where ductwork and conduit exit the building to match existing.
3. F-11— Demo F-11 and all associated ductwork from F-11 transition to the exit point on the roof.
Ensure remaining ductwork back to dishwasher is properly sloped. Demo existing wiring and conduit, including any control wiring. Install properly sized and sloped new stainless-steel ductwork, with welded seams, up to new properly sized roof-mounted exhaust fan with backdraft damper. Install new properly sized circuit breaker for new roof-mounted exhaust fan. Route properly sized electrical wiring and conduit to new properly sized disconnect for new exhaust fan. New disconnect shall be mounted on the roof near the new exhaust fan. Route properly sized new wiring and conduit from disconnect to exhaust fan. Install new control wiring and conduit connecting dishwasher to new exhaust fan and exhaust fan to BMS for monitoring and alarms. Ensure new exhaust fan runs an additional 15 minutes after dishwasher shuts off. Seal area where ductwork and conduit exit the building to match existing.
4. F-6 – Demo F-6 and install a new piece of stainless-steel ductwork. Weld seams to tie ductwork back together. Ensure ductwork is properly sloped from roof all the way back to the dishwasher. Adjust as needed. Install properly sized and sloped new stainless-steel ductwork, with welded seams, from the end of the existing ductwork to the new properly sized roof-mounted exhaust fan with backdraft
DISTRIBUTION: DoD COMMUNITY ONLY damper. Demo existing wiring and conduit, including control wiring. Install new properly sized circuit breaker for new roof-mounted exhaust fan. Route properly sized electrical wiring and conduit to new properly sized disconnect for new exhaust fan. New disconnect shall be mounted on the roof near the new exhaust fan. Route properly sized new wiring and conduit from disconnect to exhaust fan. Install new control wiring and conduit connecting dishwasher to new exhaust fan and exhaust fan to BMS for monitoring and alarms. Ensure new exhaust fan runs an additional 15 minutes after dishwasher shuts off. Seal area where ductwork and conduit exit the building to match existing. Relocate lightning grounding cable running across roof as needed. Temporary wall shall be installed in storage room to separate work area in storage room from the area that mess hall personnel will be continually using.
SPECIAL SCHEDULING AND ACCESS:
All scheduling and access shall be coordinated with the Building Manager.
SPECIAL CONDITIONS:
After hours work may be required to prevent Mess Hall service interruptions.
ENVIROMENTAL:
None