This federal contract opportunity notice solicits bids for the construction of a new cemetery in Elko, Nevada. The Department of Veterans Affairs National Cemetery Administration issued solicitation number 36C78623B0029 to procure cemetery construction services at location 943-001. Bidders must submit responses by the deadline of June 23, 2023 and provide the required bid documents and construction plans, which total 15MB across 8 files. The awarded contractor will be responsible for building a new burial ground to serve veterans in the Elko area. Pricing terms, response deadlines, and other contractual requirements are detailed in the solicitation documentation.

View the file

Other files

Show all 17

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

M-001

MECHANICAL GENERAL NOTES,

ABBREVIATIONS & SYMBOLS

A.ALL PIPING AND DUCTS IN FINISHED ROOMS OR SPACES SHALL BE

CONCEALED IN FURRED CHASES OR SUSPENDED CEILINGS,

UNLESS OTHERWISE NOTED.

B.PROVIDE ACCESS PANELS OR DOORS IN INACCESSIBLE CEILINGS

AND/OR CHASES FOR ALL VALVES, TRAPS, DAMPERS,

CLEANOUTS, COILS, FANS, CONTROLS, ETC. ACCESS DOOR

RATING SHALL MATCH CLASSIFICATION OF WALL AND CEILING

FIRE RATING.

C.COORDINATE THE LOCATION OF ALL DIFFUSERS, GRILLES,

REGISTERS, ACCESS DOORS, ETC., WITH THE ARCHITECTURAL

REFLECTED CEILING PLAN(S).

D. ALL ROUND RUN OUTS AND DROPS TO DIFFUSERS SHALL BE THE

SAME NOMINAL SIZE AS THE SCHEDULED DIFFUSER NECK SIZE.

E. THE FIRST FIGURE OF DUCT SIZE INDICATES DIMENSION OF FACE

SHOWN OR INDICATED. ALL DUCT SIZES SHOWN ON DRAWINGS

ARE NET INSIDE DIMENSIONS.

F. PROVIDE TURNING VANES IN ALL SQUARE ELBOWS. EXCEPT

TRANSFER AIR SOUND ELBOWS.

G.THE CFM OF EACH DIFFUSER, REGISTER, ETC., IS INDICATED IN

THE SYMBOL DESIGNATION ON THE DRAWINGS.

H.REFER TO THE ARCHITECTURAL DRAWINGS FOR EXACT

LOCATION OF ALL FIRE RATED AND/OR SMOKE RATED WALLS AND

ASSEMBLIES. PROVIDE APPROVED FIRE AND FIRE/SMOKE

DAMPERS IN ALL REQUIRED PENETRATIONS FOR DUCTWORK,

GRILLES, REGISTERS AND DIFFUSERS. ALL PIPE AND DUCTWORK

PENETRATIONS OF FIRE, SMOKE AND FULL HEIGHT WALLS SHALL

BE CAULKED AIR TIGHT TO THE ADJACENT STRUCTURE BY MEANS

OF U.L. APPROVED FIRE PROOF CAULKING MATERIAL.

I. CONTRACTOR SHALL COORDINATE ALL DUCTWORK, PIPING.

PLUMBING AND FIRE PROTECTION PIPING WITH STRUCTURAL AND

ELECTRICAL SYSTEMS AND SHALL PROVIDE NECESSARY

OFFSETS TO AVOID CONFLICTS AND TO MAINTAIN EQUIPMENT

ACCESS AND SERVICEABILITY.

J. CONTRACTOR SHALL FURNISH ALL NECESSARY STRUCTURES,

INSERTS, SLEEVES, AND HANGING DEVICES FOR INSTALLATION

OF MECHANICAL AND PLUMBING EQUIPMENT, DUCTWORK AND

PIPING. ETC. CONTRACTOR SHALL COORDINATE WITH GENERAL

CONTRACTOR AND ALL BUILDING TRADES TO AVOID CONFLICTS

AND TO MAINTAIN EQUIPMENT ACCESS AND SERVICEABILITY.

K. CONTRACTOR SHALL BE RESPONSIBLE FOR PROVIDING ALL

NECESSARY MISCELLANEOUS ANGLES, CHANNELS. UNISTRUT,

ETC., AS MAYBE REQUIRED TO ADEQUATELY SUPPORT THE

MECHANICAL PIPING. DUCTWORK, AND EQUIPMENT IN A MANNER

APPROVED BY THE ARCHITECT WHICH WILL NOT OVERLOAD THE

BUILDING STRUCTURAL SYSTEM.

L. SEAL ALL TRANSVERSE JOINTS, LONGITUDINAL SEAMS,

DUCTWALL PENETRATIONS AND FITTING CONNECTIONS ON ALL

DUCT SYSTEMS.

GENERAL NOTES

A/E ARCHITECT / ENGINEER

AAV AUTOMATIC AIR VENT

ACD AUTOMATIC CONTROL DAMPER,MODULATING

ACD-TP AUTOMATIC CONTROL DAMPER,TWO POSITION

AD ACCESS DOOR

AF AFTER FILTER

AFCV AIR FLOW CONTROL VALVE

AFF ABOVE FINISHED FLOOR

AFW AIR FOIL WHEEL (FAN)

AHU AIR-HANDLING UNIT

AMP AMPERAGE

AP ACCESS PANEL

APD AIR PRESSURE DROP

ARI AIR CONDITIONING AND REFRIGERATION INSTITUTE

AS AIR SEPARATOR

ASME AMERICAN SOCIETY OF MECHANICAL ENGINEERS

B BOILER

BD BUTTERFLY DAMPER

BDD BACKDRAFT DAMPER

BDR BASE BOARD RADIATOR

BFP BACKFLOW PREVENTER

BFT BOILER PLANT FIRE TUBE

BG BOTTOM GRILLE

BHP BRAKE HORSEPOWER

BHW HOT WATER HEATING BOILER

BHX BOILER BLOWDOWN HEAT EXCHANGER

BIW BACKWARD INCLINED WHEEL (FAN)

BMT BONE MARROW TRANSPLANT

BR BOTTOM REGISTER

BSC BIOLOGICAL SAFETY CABINETS

BT BLOWOFF TANK

BTC BLOWOFF TANK CONTROL VALVE

BTU BRITISH THERMAL UNIT

BTUH BRITISH THERMAL UNIT PER HOUR

BWT BOILER PLANT WATER TUBE

C CENTIGRADE (CELSIUS)

CC COOLING COIL

CCD COOLING COIL CONDENSATE DRAIN

CD CEILING DIFFUSER

CD-1 CONSTRUCTION DOCUMENTS (SUBMISSION1)

CD-2 CONSTRUCTION DOCUMENTS (SUBMISSION2)

CENT CENTRIFUGAL

CFH CUBIC FEET PER HOUR

CFM CUBIC FEET PER MINUTE

CFT CUBIC FEET

CFP CHEMICAL FEED PUMP

CG CEILING GRILLE

CH CHILLER

CHP CHILLED WATER PUMP

CHW CHILLER WATER

CHR CHILLED WATER RETURN

CHS CHILLED WATER SUPPLY

CI CAST IRON

CM CARBON MONOXIDE

CM CUBIC METER

CM/S CUBIC METER PER SECOND

CO CLEAN OUT

CO2 CARBON DIOXODE

COMP COMPRESSOR UNIT

COP COEFFICIENT OF PERFORMANCE

CP CONDENSATE PUMP

CR CEILING REGISTER

CS CONDENSATE STORAGE TANK

CSG CLEAN STEAM GENERATOR

CT COOLING TOWER

CU CONDENSING UNIT

CUH CABINET UNIT HEATER

CV CONSTANT VOLUME

CW COLD WATER (POTABLE)

CWCC CHILLED WATER COOLING COIL

CWP CONDENSER WATER PUMP

CWR CONDENSER WATER RETURN (TO COOLING TOWER)

CWS CONDENSER WATER SUPPLY (FROM COOLING TOWER)

D DAMPER - AUTOMATIC

D-1 OUTDOOR AIR DAMPER

D-2 RETURN AIR DAMPER

D-3 RELIEF AIR DAMPER

DB DECIBELS

Db DRY-BULB TEMPERATURE

DD-1 DESIGN DEVELOPMENT (SUBMISSION1)

DD-2 DESIGN DEVELOPMENT (SUBMISSION2)

DDC DIRECT DIGITAL CONTROLS

DEG DEGREE

DF DIFFUSER

DIA DIAMETER

DIW DEIONIZED WATER

DP DEW POINT TEMPERATURE

DP DIFFUSER PLATE

DPA DIFFERENTIAL PRESSURE ASSEMBLY

DPS DIFFERENTIAL PRESSURE SENSOR

DX DIRECT EXPANSION

DXCC DIRECT EXPANSION COOLING COIL

EA EXHAUST AIR

EAT ENTERING AIR TEMPERATURE

EC EVAPORATIVE COOLER

ECC ENGINEERING CONTROL CENTER

ECU EVAPORATIVE CONDENSER UNIT

EDH ELECTRIC DUCT HEATER

EER ENERGY EFFICIENCY RATIO

EF EXHAUST FAN

EG EXHAUST GRILLE

EGS EMERGENCY GAS SHUTOFF

EGT ENTERING GLYCOL TEMPERATURE

EH EXHAUST HOOD

EJ EXPANSION JOINT

EMD END OF MAIN DRIP (STEAM)

ENT ENTERING

ER EXHAUST REGISTER

ERC ELECTRIC REHEAT COIL

ERP ELECTRIC RADIANT PANEL

ESP EXTERNAL STATIC PRESSURE

ET EXPANSION TANK

ETO ETHYLENE OXIDE

EUH ELECTRIC UNIT HEATER

EWC EVAPORATIVE WATER COOLER

EWT ENTERING WATER TEMPERATURE

EX EXISTING

F FAHRENHEIT

F&T FLOAT AND THERMOSTATIC

F/SDPR COMBINATION FIRE SMOKE DAMPER

FA FREE AREA

FC FLEXIBLE CONNECTION

FCU FAN COIL UNIT (4 PIPE)

FCUC FAN COIL UNIT COOLING ONLY

FCUH FAN COIL UNIT HEATING ONLY

FCW FORWARD CURVED WHEEL (FAN)

FD FLOOR DRAIN

FD FIRE DAMPER

FF FINAL FILTER

FHX FLUE GAS/FEEDWATER HEAT EXCHANGER

FM FLOW METER

FOP FUEL OIL PUMP

FOT FUEL OIL TANK

FOHX FUEL OIL HEAT EXCHANGER

FPM FEET PER MINUTE

FPS FEET PER SECOND

FPTU FAN POWERED TERMINAL UNIT

FR FLOOR REGISTER

FRP FIBER REINFORCED POLYESTER

FS FLOW SWITCH

FSTAT FREEZESTAT

GA GAUGE

GAL GALLONS

GH GRAVITY HOOD

GPD GALLONS PER DAY

GPH GALLONS PER HOUR

GPM GALLONS PER MINUTE

GPR GAS PRESSURE REGULATOR

GS GALVANIZED STEEL

H HUMIDIFIER

H&CW HOT & COLD WATER

HAC HOUSEKEEPING AID CLOSET

HB HOSE BIBB

HC HEATING COIL

HD HEAD

HD HOOD

HOA HAND/OFF/AUTOMATIC

HP HEAT PUMP

HP HORSEPOWER

HPDT HIGH PRESSURE DRIP TRAP

HPR HIGH PRESSURE RETURN (STEAM CONDENSATE)

HPS HIGH PRESSURE SUPPLY (STEAM)

HRC HEAT RECOVERY COIL

HRD HEAT RECOVERY DEVICE

HRP HYDRONIC RADIANT (CEILING) PANEL

HRW HEAT RECOVERY WHEEL

HSTAT HUMIDISTAT

HTM HUMIDIFIER TERMINAL

HUM HUMIDIFIER UNIT MOUNTED

HVU HEATING AND VENTILATING UNIT

HW HOT WATER

HWC HOT WATER COIL

HWHC HOT WATER HEATING COIL

HWP HEATING HOT WATER PUMP

HWR HEATING HOT WATER RETURN

HWS HEATING HOT WATER SUPPLY

HWUH HOT WATER UNIT HEATER

HVD HOISTWAY VENT DAMPER

HX HEAT EXCHANGER

HZ HERTZ

I/O INPUT/OUTPUT

IAQ INDOOR AIR QUALITY

IBT INVERTED BUCKET TRAP

ICF IN-LINE CENTRIFUGAL FAN

ICU INTENSIVE CARE UNIT

ID INSIDE DIAMETER

IFB INTEGRAL FACE AND BYPASS

IN INCHES

IN HG INCHES OF MERCURY

IN WC INCH WATER COLUMN

IN WG INCH WATER GAUGE

IN-LB INCH-POUND

IPLV INTEGRATED PART LOAD VALUE

IRH INFRARED HEATER

IS INSECT SCREEN

IU INDUCTION UNIT

IV INLET VANES

kg KILOGRAM kg/HR KILOGRAM PER HOUR kPa KILOPASCAL kW KILOWATT kWh KILOWATT HOUR

L LITER

L/h LITERS PER HOUR (OR LITERS/HOUR) L/m LITERS PER MINUTE (OR LITERS/MINUTE) L/s LITERS PER SECOND (OR LITERS/SECOND)

LAT LEAVING AIR TEMPERATURE

LBS/HR POUNDS PER HOUR

LF LINEAR FOOT (FEET)

LGT LEAVING GLYCOL TEMPERATURE

LH LATENT HEAT

LPG LIQUID PROPANE GAS

LPR LOW PRESSURE RETURN (STEAM CONDENSATE)

LPRC LOW PRESSURE STEAM RETURN (CLEAN)

LLHX LIQUID TO LIQUID HEAT EXCHANGER

LPS LOW PRESSURE STEAM

LPSC LOW PRESSURE STEAM (CLEAN)

LSD LINEAR SLOT DIFFUSER

LTCP LOCAL TEMPERATURE CONTROL PANEL

LVG LEAVING

LVR LOUVER

LWT LEAVING WATER TEMPERATURE

M METER, SI UNIT

M/s METERS PER SECOND (OR METERS/SECOND)

MA MIXED AIR

MAT MIXED AIR TEMPERATURE

MAU MAKE-UP AIR UNIT

MAV MANUAL AIR VENT

MAX MAXIMUM

MB MIXING BOX

MBH 1000 BTUH

MCA MINIMUM BRANCH CIRCUIT AMPACITY

MER MECHANICAL EQUIPMENT ROOM

MERV MINIMUM EFFICIENCY REPORTING VALUE

MH MANHOLE

MHP MOTOR HORSEPOWER

MIN MINIMUM

MM MILLIMETER

MOV MOTOR OPERATED VALVE

MPR MEDIUM PRESSURE RETURN (STEAM CONDENSATE)

MPS MEDIUM PRESSURE STEAM

MRI MAGNETIC RESONANCE IMAGING

MTD MEAN TEMPERATURE DIFFERENCE

MVD MANUAL VOLUME DAMPER

MZ MULTI-ZONE

NA NOT APPLICABLE

NC NOISE CRITERIA

NC NORMALLY CLOSED

NG NATURAL GAS

NGFM NATURAL GAS FLOWMETER

NO NORMALLY OPEN

NOAA NATIONAL OCEANIC & ATMOSPHERIC ADMINISTRATION

NOM NOMINAL

NPLV NON-STANDARD PART LOAD VALUE

NPSH NET POSITIVE SUCTION HEAD

NTS NOT TO SCALE

OA OUTSIDE AIR

OAG OUTSIDE AIR GRILLE

OAI OUTSIDE AIR INTAKE

OD OUTSIDE DIAMETER

OFM OIL FLOWMETER

OR OPERATING ROOM

P PUMP

PA PASCAL

PC PUMPED CONDENSATE

PCF POUNDS PER CUBIC FOOT (FEET)

PD PRESSURE DROP

PEF PROPELLER (TYPE) EXHAUST FAN

PF PRE-FILTER

PG PRESSURE GAGE

PGW PROPYLENE GLYCOL-WATER (SOLUTION)

PHC PREHEAT COIL

PPM PARTS PER MILLION

PRS PRESSURE REGULATING (VALVE) STATION

PRV PRESSURE REGULATING VALVE

PSI POUNDS PER SQUARE INCH

PSIA POUNDS PER SQUARE INCH – ABSOLUTE

PSIG POUNDS PER SQUARE INCH – GAGE

PSS PRIMARY SECONDARY SYSTEM

PSV PRESSURE SAFETY VALVE

PTAC PACKAGED TERMINAL AIR CONDITIONER

R RELOCATE

R/E RETURN OR EXHAUST

RA RETURN AIR

RAT RETURN AIR TEMPERATURE

RDS ROOM DATA SHEETS

RG RETURN GRILLE

RH RELATIVE HUMIDITY

RLA RUN LOAD AMPERE

RN NEW RELOCATED LOCATION

RPM REVOLUTIONS PER MINUTE

RR RETURN REGISTER

SA SUPPLY AIR

SAT SUPPLY AIR TEMPERATURE

SCFM STANDARD CUBIC FEET PER MINUTE

SD SMOKE DETECTOR

SD SUPPLY AIR DIFFUSER

SD-1 SCHEMATIC DESIGN (SUBMISSION1)

SD-2 SCHEMATIC DESIGN (SUBMISSION2)

SDPR SMOKE DAMPER

SEN SENSIBLE HEAT

SF SUPPLY FAN

SG SUPPLY AIR GRILLE

SI SQUARE INCHES

SP STATIC PRESSURE

SP GR SPECIFIC GRAVITY

SPD SUPPLY PROCESS AND DISTRIBUTION

SPS STATIC PRESSURE SENSOR

SQ FT SQUARE FOOT (FEET)

SR SUPPLY AIR REGISTER

T & PCV TEMPERATURE AND PRESSURE CONTROL VALVE

TAB TESTING, ADJUSTING, BALANCE

TD TEMPERATURE DIFFERENCE

TSP TOTAL STATIC PRESSURE

TSTAT THERMOSTAT

TU TERMINAL UNIT

TWU THRU-WALL UNIT

UC UNDER CUT

UL UNDERWRITERS LABORATORY

V VALVE

VAV VARIABLE AIR VOLUME

VD VOLUME DAMPER (MANUAL OPPOSED BLADE)

VFD VARIABLE FREQUENCY DRIVE

VHA VETERANS HEALTH ADMINISTRATION

VSD VARIABLE SPEED DRIVE

W WATTS

WB WET-BULB (TEMPERATURE)

WG WATER GAGE

WPD WATER SIDE PRESSURE DROP

YR YEAR

ABBREVIATIONS

LIMIT OF DEMOLITION

DNUP SUPPLY DUCT (UP & DOWN)

VANED ELBOW & AIR SPLIT TYPE DUCT TAKE-OFF

CONNECT NEW DUCT TO EXISTING DUCT

D

INCLINED RISE, IN DIRECTION OF AIR FLOW

INCLINED DROP, IN DIRECTION OF AIR FLOW

R

DNUP RETURN DUCT (UP & DOWN)

SECTION.)

FC

10x8

FLEXIBLE CONNECTION, EQUIPMENT,

VANED ELBOW (PROVIDE ALL SQUARE OR

RECTANGULAR ELBOWS WITH VANES EVEN IF

SYMBOL IS MISSING)

NEW DUCT (INSIDE DIMENSIONS: WIDTH x DEPTH)

EXISTING DUCT TO REMAIN

LOUVER (LOUVER SPECIFIED IN ARCHITECTURAL

SMOKE DAMPER

SD

VD

MANUAL VOLUME DAMPER

EXISTING DUCT TO BE REMOVED

VIBRATION, OR SEISMIC

SUPPLY

RETURN45°

RETURN, NO SPLITTER (45° TAP)

STANDARD BRANCH SUPPLY OR

45°

COMBINATION FIRE/SMOKE DAMPER

F/S DPR

AUTOMATIC CONTROL DAMPER MODULATING

DUCTWORK SYMBOLS

ANCHOR

REDUCER OR INCREASER

DIRECTION OF FLOW

SIDE CONNECTION

ECCENTRIC REDUCER

BOTTOM CONNECTION, 45° OR 90°

TOP CONNECTION, 45° OR 90°

DIRECTION OF PIPE PITCH (DOWN)

UNION

RISE OR DROP IN PIPE

CAPPED OUTLET

PRESSURE GAGE

THERMOMETER

FLOW ELEMENT

FLOAT & THERMOSTATIC TRAP SET INCLUDING

PIPING ACCESSORIES SEE DETAIL

PIPING ACCESSORIES SEE DETAIL

INVERTED BUCKET TRAP SET INCLUDING

FE

PIPE UP

PIPE DOWN

REFRIGERANT SIGHT GLASS

TEST PLUG (PRESSURE/TEMPERATURE)

AUTOMATIC AIR VENT

AV

MANUAL AIR VENTMV

THERMOSTATIC TRAP SET INCLUDING

PIPING ACCESSORIES SEE DETAIL

QUICK-COUPLE HOSE CONNECTOR

PIPING SYMBOLS

VENT LINE

CHILLED WATER SUPPLY

CHILLED WATER RETURN

DRAIN LINE

MAKE-UP WATER

EXISTING PIPE TO BE REMOVED

SHUT-OFF VALVE

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Fi le

P at h:

z

:\j ob s\ va el ko n at io na l c em et ar y\ 1b m ec h-pl bg \s he et s\ m

-0 ge ne ra l n ot es a nd a bb re vi at io ns

.d w g ed it:

ad m in s av ed :5

/2 /2

1:

P M p lo t:5 /2

/2

1:

P

M

Office of Design and Construction

Services

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

Project Director

Revisions:

1 3 6 0 5 1 s t A v e . N . # 1 0 0 P l y m o u t h , M N 5 5 4 4 1 P 7 6 3 . 4 1 2 . 4 0 0 0 | F 7 6 3 . 4 1 2 . 4 0 9 0 | a e - m n . c o m Anderson Engineering of Minnesota, LLC | Proj # 15795

ELKO NATIONAL CEMETERY

943-001

4/05/2023

3602 JENNINGS WAY, ELKO, NV 89801

100% CONSTRUCTION

DOCUMENTS

Date: Dwg. of 133

IRRIGATION: M.E.P.:GEOTECHNICAL :STRUCTURAL:

AST

7301 OHMS LANE, STE 215

EDINA, MN 55439

952-854-9302

MICHELLE SCHMIDT

WIM

175 JAMES AVE N.

MINNEAPOLIS, MN 55405

763-559-1010

TIM MALOOLY

TERRACON

6949 S. HIGH TECH DRIVE

MIDVALE, UT 84047

801-545-8500

JENNIFER DIERCKSEN

AESUS

1050 E. SOUTHERN AVE, STE 5

TEMPE, AZ 85282

480-454-2861

ORLANDO GONZALES

SPLIT SYSTEM HEAT PUMP SCHEDULE

MARK MANUFACTURER

CFM ESP

HEAT PUMP UNIT (COIL)

MOCP MCA

MODEL NUMBER

HEAT PUMPCONDENSER

UNIT HP MOCP VOLTS

CONDENSING UNIT

VOLT/Ø

MIN SEER CYCLE

COOLING CAPACITIES

DB WB TOTAL SENSIBLE

BTUHENT AIR

INDOOR

UNIT LBS

OUTDOOR

UNIT LBS REMARKSOA

CFM

HEATING CAPACITIES

BTUHENT AIR

1 DISCONNECT BY ELECTRICAL CONTRACTOR.

ALL REFRIGERANT PIPING FROM CONDENSING UNIT TO A/C UNITS SHALL BE DESIGNED AND SIZED BY EQUIPMENT MANUFACTURER. VERIFY THE INSULATION OF VAPOR LINE AND PROVIDE PROPER SUPPORT FOR REFRIGERATION LINES.

CONTRACTOR SHALL BE CERTIFIED BY EQUIPMENT MANUFACTURER FOR INSTALLATION OF SYSTEM & SHALL INSTALL ALL EQUIPMENT PER MANUFACTURERS RECOMMENDATION.

PROVIDE DIGITAL NON-PROGRAMMABLE THERMOSTAT, TRANE MODEL# TCONT401AN21MA (XR401).

PROVIDE LOW AMBIENT KIT AND HAIL GUARD.

SEE OUTSIDE AIR CALCULATION FOR MINIMUM OUTSIDE AIR PER UNIT.

13.2 KW ELECTRIC KW, 208V/1Ø, 80A MOCP

NOTE:

1IU-1

OU-1 GOODMAN 2 3 4 5800 0.5 3/4 15 14.2 25 208/1208/1 14 R-410A

COOLING 80 70.7 63.4 37.1 160 1466ASPT25B14GSZ140251 60 43.5

MCA

EXHAUST FAN SCHEDULE

MARK AIR VOLUME

CFM

STATIC

PRESSURE

VOLTAGE/

PHASELOCATION

TOILET ROOMS/

MOP SINK ROOMS

TYPE/

DRIVE

PROVIDE BACKDRAFT DAMPER WITH EXHAUST FAN.

EXHAUST FAN SHALL RUN ONLY WHILE OCCUPIED. SENSOR SWITCH SHALL ACTIVATE FAN AND LIGHT.

HORSE

POWER MFR./MODEL REMARKS

DRIVE

EF-1 450 0.1 120/1CEILING MOUNTED 118 W BROAN L500 DIRECT

NOTE:

1TOILET ROOMS/

MOP SINK ROOMS 2EF-2 450 0.1 120/1CEILING MOUNTED 118 W BROAN L500 DIRECT

ELECTRIC UNIT HEATER

UH-1 ELECTRIC UNIT

HEATER

VOLTAGE/Ø REMARKSMARK TYPE HPMANUFACTURER

& MODEL NUMBER

26,000

BTU

INPUT

PROVIDE DIGITAL, NON-PROGRAMMABLE THERMOSTAT, 40° F SETPOINT.

PROVIDE CEILING SUSPENSION OR WALL HANGER KIT AS DIRECTED BY MANUFACTURER.

PROVIDE CONCENTRIC AIR VENT KIT.

1 2

CFM

21,600

BTU

OUTPUT

NOTE:

1/30 208/1REZNOR

EGHB - AK3E-7 700

6 7

DIFFUSER & GRILLE SCHEDULE

MANUFACTURER

& MODEL NUMBER DAMPER REMARKSMARK TYPE BORDER COLOR

TG-1 PER ARCHTRANSFER GRILLE WALL MOUNTED NONE 12" X 12" STEEL GRILLE. MODIFY EXACT DIMENSIONS AS

REQUIRED TO FIT FIELD CONDITIONS.PRICE STG1

1TOILET ROOMS/

MOP SINK ROOMS 2EF-3 110 0.1 120/1CEILING MOUNTED 12 W SP-LP0511-1 DIRECT

4/05/2023

100% CD SUBMITTAL

BID DOCUMENTS

BID DOCUMENTS

5/5/2023

WH

MENS

WOMENS

STORAGE 103

PORTICO

TECH

CLOSET

HAC

M-101

PIC/BATHROOM BUILDING MECHANICAL

FLOOR PLAN

MECHANICAL FLOOR PLAN

SCALE: 1/4" = 1'-0"

GENERAL NOTES

1. LIGHTING AND SPRINKLER HEADS TAKE PRECEDENCE OVER

DIFFUSER LOCATION. CONTRACTOR SHALL MAKE NECESSARY

ADJUSTMENT TO DIFFUSERS TO AVOID ANY CONFLICT WITH

LIGHTING LAYOUT AND SPRINKLER HEADS.

2. THERMOSTATS SHALL BE MOUNTED PER ADA REQUIREMENTS.

MAXIMUM HEIGHT FOR FRONT ACCESS SHALL BE 48" AFF. DO

NOT MOUNT ABOVE FIXED COUNTER UNLESS KNEE HOLE

ACCESS IS PROVIDED.

3. CONTRACTOR SHALL COORDINATE ALL FINAL THERMOSTAT

LOCATIONS WITH OWNER AND ARCHITECT PRIOR TO

MOUNTING.

4. THE CONTRACTOR SHALL DO ALL NECESSARY CUTTING OF

WALL AND CEILINGS.

5. NO STRUCTURAL MEMBER SHALL BE CUT WITHOUT

PERMISSION FROM THE ENGINEER.

6. OPENINGS IN FLOORS, WALLS, CEILINGS, ROOFS, ETC. AS A

RESULT OF REMOVED PIPING, DUCTWORK, FLUES,

EQUIPMENT, FIXTURES, ETC SHALL BE PATCHED TO MATCH

EXISTING BUILDING CONSTRUCTION. WORK SHALL BE

PERFORMED BY CRAFTSMEN SKILLED IN THEIR RESPECTIVE

TRADES.

7. DUCTWORK CONSTRUCTION AND INSTALLATION INCLUDING

SHEET METAL GAUGES, REINFORCEMENT, JOINT SEALING, AIR

LEAKAGE, AND DETAILS NOT SPECIFICALLY SHOWN ON

DRAWINGS SHALL BE IN ACCORDANCE WITH CURRENT IMC &

VA DUCT CONSTRUCTION STANDARDS.

8. CONTRACTOR SHALL PROVIDE COORDINATION FOR

DUCTWORK ROUTE DRAWINGS, THIS MUST BE APPROVED BY

ENGINEER PRIOR TO CONSTRUCTION.

9. CONTRACTOR IS RESPONSIBLE FOR PROTECTING OPENING

AND RESPONSIBLE FOR ANY DAMAGE CAUSED BY

CONSTRUCTION METHODS.

10. CONTRACTOR SHALL PERFORM LEAK TEST ON ROOF AFTER

CONSTRUCTION IS COMPLETE AND REPAIR THE ROOF AS

NECESSARY.

KEY NOTES

1. SUPPLY AIR DIFFUSER, 400 CFM.

2. EXHAUST FLUE THRU GABLE WALL. PROVIDE TERMINATION PER

MANUFACTURE.

3. PROVIDE 36x36 ACCESS PANEL.

4. NEW CONDENSING UNIT MOUNTED ON NEW 6" HIGH CONCRETE

HOUSEKEEPING PAD. PROVIDE PROTECTIVE CAGE FOR

CONDENSING UNIT.

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Fi le

P at h:

z

:\j ob s\ va el ko n at io na l c em et ar y\ 1b m ec h-pl bg \s he et s\ m

-1 m ec ha ni ca l p la n.

dw ad av ed :4

/1 1/

:4

AM

lo t:5 /2

/2

1:

P

M

Office of Design and Construction

Services

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

Project Director

Revisions:

1 3 6 0 5 1 s t A v e . N . # 1 0 0 P l y m o u t h , M N 5 5 4 4 1 P 7 6 3 . 4 1 2 . 4 0 0 0 | F 7 6 3 . 4 1 2 . 4 0 9 0 | a e - m n . c o m Anderson Engineering of Minnesota, LLC | Proj # 15795

ELKO NATIONAL CEMETERY

943-001

2/10/2023

3602 JENNINGS WAY, ELKO, NV 89801

100% CONSTRUCTION

DOCUMENTS

Date: Dwg. of 133

IRRIGATION: M.E.P.:GEOTECHNICAL :STRUCTURAL:

AST

7301 OHMS LANE, STE 215

EDINA, MN 55439

952-854-9302

MICHELLE SCHMIDT

WIM

175 JAMES AVE N.

MINNEAPOLIS, MN 55405

763-559-1010

TIM MALOOLY

TERRACON

6949 S. HIGH TECH DRIVE

MIDVALE, UT 84047

801-545-8500

JENNIFER DIERCKSEN

AESUS

1050 E. SOUTHERN AVE, STE 5

TEMPE, AZ 85282

480-454-2861

ORLANDO GONZALES

IU-1

CU-1

UH-1

TG-1

T

T

12X12

10"Ø

10"Ø

TG-1

EF-1

EF-2

EF-3

4/05/2023

100% CD SUBMITTAL

BID DOCUMENTS

HANGAR

STRAPS

DUCT

1" MIN SCREWS

(TYPICAL)

60"

MAX

LOAD RATED

FASTENER

DUCT (24"Ø MAX)

HANGER

R

IG

ID

D

U C

T H

AN

G

ER

S

D

ET

AI

L

INTEGRAL

GRILLE

EXHAUST

FAN

CEILING

NOTE: INSTALL EXHAUST FAN PER

MANUFACTURER'S RECOMMENDATION.

EX

H

AU

ST

F

AN

R O

O F

D

IS

C H

AR

G

E D

ET

AI

L

O U

TD

O

O R

C U

M O

U N

TI

N

G D

ET

AI

L

RUBBER

SHEAR

ISOLATORS

(4 REQ'D)

REFRIGERANT LIQUID

& SUCTION LINES.

SIZE & INSTALL PER

MANUFACTURER'S

RECOMMENDATIONS.

NEW CURB

AT GRADE

REFRIGERANT LIQUID

& SUCTION LINES.

NOTE:

OUTDOOR

CONDENSING

UNIT

CONCRETE PAD. SEE

STRUCTURAL DRAWING

FOR DETAILS

C O

N D

EN

SA

TE

D

R

AI

N T

R

AP

D

ET

AI

L

BALL VALVE. PLACE AS NEAR TO UNIT

AS POSSIBLE. DO NOT PLACE ELBOW

BETWEEN BALL VALVE AND UNIT.

3/4" 90° ELBOWS (TYP BOTH DRAINS)

P-TRAPS. MAINTAIN MINIMUM 3: DROP

FOLLOWED BY 2" RISE.

3/4" "TEE"

3/4" "TEE"

3/4" FEMALE THREADED HOSE FITTING

WITH 3/4" THREADED REMOVABLE

AIRTIGHT CAP.

M-102

PIC/BATHROOM BUILDING MECHANICAL

DETAILS

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Fi le

P at h:

z

:\j ob s\ va el ko n at io na l c em et ar y\ 1b m ec h-pl bg \s he et s\ m

-1 m ec ha ni ca l p la n.

dw ad av ed :4

/1 1/

:4 lo t:5 /2

/2

1:

P

M

Office of Design and Construction

Services

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

Project Director

Revisions:

1 3 6 0 5 1 s t A v e . N . # 1 0 0 P l y m o u t h , M N 5 5 4 4 1 P 7 6 3 . 4 1 2 . 4 0 0 0 | F 7 6 3 . 4 1 2 . 4 0 9 0 | a e - m n . c o m Anderson Engineering of Minnesota, LLC | Proj # 15795

ELKO NATIONAL CEMETERY

943-001

2/10/2023

3602 JENNINGS WAY, ELKO, NV 89801

100% CONSTRUCTION

DOCUMENTS

Date: Dwg. of 133

IRRIGATION: M.E.P.:GEOTECHNICAL :STRUCTURAL:

AST

7301 OHMS LANE, STE 215

EDINA, MN 55439

952-854-9302

MICHELLE SCHMIDT

WIM

175 JAMES AVE N.

MINNEAPOLIS, MN 55405

763-559-1010

TIM MALOOLY

TERRACON

6949 S. HIGH TECH DRIVE

MIDVALE, UT 84047

801-545-8500

JENNIFER DIERCKSEN

AESUS

1050 E. SOUTHERN AVE, STE 5

TEMPE, AZ 85282

480-454-2861

ORLANDO GONZALES 1194/05/2023

100% CD SUBMITTAL

BID DOCUMENTS

COMMITTAL

SHELTER

STORAGE

M-103

COMMITTAL SHELTER BUILDING

MECHANICAL FLOOR PLAN

MECHANICAL FLOOR PLAN

SCALE: 1/4" = 1'-0"

GENERAL NOTES

1. LIGHTING AND SPRINKLER HEADS TAKE PRECEDENCE OVER

DIFFUSER LOCATION. CONTRACTOR SHALL MAKE NECESSARY

ADJUSTMENT TO DIFFUSERS TO AVOID ANY CONFLICT WITH

LIGHTING LAYOUT AND SPRINKLER HEADS.

2. THERMOSTATS SHALL BE MOUNTED PER ADA REQUIREMENTS.

MAXIMUM HEIGHT FOR FRONT ACCESS SHALL BE 48" AFF. DO

NOT MOUNT ABOVE FIXED COUNTER UNLESS KNEE HOLE

ACCESS IS PROVIDED.

3. CONTRACTOR SHALL COORDINATE ALL FINAL THERMOSTAT

LOCATIONS WITH OWNER AND ARCHITECT PRIOR TO

MOUNTING.

4. THE CONTRACTOR SHALL DO ALL NECESSARY CUTTING OF

WALL AND CEILINGS.

5. NO STRUCTURAL MEMBER SHALL BE CUT WITHOUT

PERMISSION FROM THE ENGINEER.

6. OPENINGS IN FLOORS, WALLS, CEILINGS, ROOFS, ETC. AS A

RESULT OF REMOVED PIPING, DUCTWORK, FLUES,

EQUIPMENT, FIXTURES, ETC SHALL BE PATCHED TO MATCH

EXISTING BUILDING CONSTRUCTION. WORK SHALL BE

PERFORMED BY CRAFTSMEN SKILLED IN THEIR RESPECTIVE

TRADES.

7. DUCTWORK CONSTRUCTION AND INSTALLATION INCLUDING

SHEET METAL GAUGES, REINFORCEMENT, JOINT SEALING, AIR

LEAKAGE, AND DETAILS NOT SPECIFICALLY SHOWN ON

DRAWINGS SHALL BE IN ACCORDANCE WITH CURRENT IMC &

VA DUCT CONSTRUCTION STANDARDS.

8. CONTRACTOR SHALL PROVIDE COORDINATION FOR

DUCTWORK ROUTE DRAWINGS, THIS MUST BE APPROVED BY

ENGINEER PRIOR TO CONSTRUCTION.

9. CONTRACTOR IS RESPONSIBLE FOR PROTECTING OPENING

AND RESPONSIBLE FOR ANY DAMAGE CAUSED BY

CONSTRUCTION METHODS.

10. CONTRACTOR SHALL PERFORM LEAK TEST ON ROOF AFTER

CONSTRUCTION IS COMPLETE AND REPAIR THE ROOF AS

NECESSARY.

KEY NOTES

1. CEILING MOUNTED ELECTRIC UNIT HEATER.

2. EXHAUST FLUE THRU GABLE WALL. PROVIDE TERMINATION PER

MANUFACTURE.

3. PROVIDE 36x36 ACCESS PANEL.

4. NEW CONDENSING UNIT MOUNTED ON NEW 6" HIGH CONCRETE

HOUSEKEEPING PAD. PROVIDE PROTECTIVE CAGE FOR

CONDENSING UNIT.

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Fi le

P at h:

z

:\j ob s\ va el ko n at io na l c em et ar y\ 1b m ec h-pl bg \s he et s\ m

-1 m ec ha ni ca l p la n.

dw ad av ed :4

/1 1/

:4 lo t:5 /2

/2

1:

P

M

Office of Design and Construction

Services

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

Project Director

Revisions:

1 3 6 0 5 1 s t A v e . N . # 1 0 0 P l y m o u t h , M N 5 5 4 4 1 P 7 6 3 . 4 1 2 . 4 0 0 0 | F 7 6 3 . 4 1 2 . 4 0 9 0 | a e - m n . c o m Anderson Engineering of Minnesota, LLC | Proj # 15795

ELKO NATIONAL CEMETERY

943-001

2/10/2023

3602 JENNINGS WAY, ELKO, NV 89801

100% CONSTRUCTION

DOCUMENTS

Date: Dwg. of 133

IRRIGATION: M.E.P.:GEOTECHNICAL :STRUCTURAL:

AST

7301 OHMS LANE, STE 215

EDINA, MN 55439

952-854-9302

MICHELLE SCHMIDT

WIM

175 JAMES AVE N.

MINNEAPOLIS, MN 55405

763-559-1010

TIM MALOOLY

TERRACON

6949 S. HIGH TECH DRIVE

MIDVALE, UT 84047

801-545-8500

JENNIFER DIERCKSEN

AESUS

1050 E. SOUTHERN AVE, STE 5

TEMPE, AZ 85282

480-454-2861

ORLANDO GONZALES

T

ELECTRIC UNIT HEATER

UH-2 ELECTRIC UNIT

HEATER 208/1

VOLTAGE/Ø REMARKSMARK TYPE

MANUFACTURER

& MODEL NUMBER

KW

PROVIDE DIGITAL, NON-PROGRAMMABLE THERMOSTAT, 40° F SETPOINT.

PROVIDE CEILING SUSPENSION OR WALL HANGER KIT AS DIRECTED BY MANUFACTURER.

1 2

CFM

14.5

AMPS

NOTE: NO SUBSTITUTIONS ARE ALLOWED.

UH-2

1204/05/2023

100% CD SUBMITTAL

BID DOCUMENTS

P-001

PLUMBING GENERAL NOTES,

ABBREVIATIONS & SYMBOLS

PLUMBING ABBREVIATIONS

AFF ABOVE FINISHED FLOOR

AFG ABOVE FINISHED GRADE

BFF BELOW FINISHED FLOOR

BFG BELOW FINISHED GRADE

BV BALANCING VALVE

CFR CLEAN FUEL OIL RETURN

CFS CLEAN FUEL OIL SUPPLY

CO CLEANOUT

COF COFFEE MACHINE

COMP COMPARTMENT

CW COLD WATER

DFU DRAINAGE FIXTURE UNIT

DI DEIONIZED WATER

DN DOWN

ELEV ELEVATION

EVS ENVIRONMENTAL SERVICES

EXT EXTERIOR

F FUTURE

FCO FLOOR CLEANOUT

FDC FIRE DEPARTMENT CONNECTION

FFE FINISHED FLOOR ELEVATION

FIN FINISHED

FLR FLOOR

FOR FUEL OIL RETURN

FOS FUEL OIL SUPPLY

FOV FUEL OIL VENT

FP FIRE PROTECTION/SPRINKLER

G GAS

GCO GRADE CLEANOUT

GV GREASE VENT

GVTR GREASE VENT THRU ROOF

GW GREASE WASTE

HUM HUMIDIFIER

HW HOT WATER (120F)

HWR HOT WATER RETURN (120)

ICE ICE MACHINE

IE INVERT ELEVATION

INT INTERIOR

INV INVERT

IV INDUSTRIAL WASTE VENT

IW INDUSTRIAL WASTE

LP LOW PRESSURE

LPG LOW PRESSURE GAS

M METER

MAX MAXIMUM

MH MANHOLE

MIN MINIMUM

MPG MEDIUM PRESSURE GAS

NAT NATURAL

NC NORMALLY CLOSED

NO NORMALLY OPEN

OD OVERFLOW DRAIN

ODL OVERFLOR DRAIN LEADER

OR OPERATING ROOM

PRV PRESSURE REDUCTING VALVE

RD ROOF DRAIN

RDL ROOF DRAIN LEADER

REF REFERENCE

RI&C ROUGH IN AND CONNECT

RO REVERSE OSMOSIS

SA SHOCK ARRESTOR

SCW SOFT COLD WATER

SF SQUARE FEET

SOV SHUT-OFF VALVE

SSD SUB-SOIL DRAIN

THRU THROUGH

U/G UNDERGROUND

ULT ULTRASONIC CLEANER

V VENT

VTR VENT THROUGH ROOF

WC WATER COLUMN

WCO WALL CLEANOUT

WM WATER METER

WSFU WATER SUPPLY FIXTURE UNIT

WTR WATER DISPENSER

A.

B.

C.

D.

E.

F.

G.

H.

I.

J.

K.

L.

M.

N.

O.

P.

Q.

R.

S.

T.

U.

V.

W.

X.

Y.

Z.

AA.

AB.

AC.

ALL WORK TO COMPLY WITH ALL VA TIL REQUIREMENTS AND LOCALLY ADOPTED

CODES.

REFER TO SPECIFICATIONS FOR MATERIALS AND METHODS FOR MECHANICAL

AND PLUMBING CONSTRUCTION.

OBTAIN ALL NECESSARY PERMITS, PAY ALL FEES, AND COMPLY WITH ALL

FEDERAL, STATE, AND MUNICIPAL LAWS, CODES, AND ORDINANCES RELATING

TO BUILDING AND PUBLIC SAFETY.

FURNISH ALL MATERIALS, EQUIPMENT, AND LABOR REQUIRED FOR A

COMPLETE WORKING AND COORDINATED SYSTEM.

COORDINATE THE EXACT LOCATION OF PLUMBING PIPING AND EQUIPMENT

WITH THE LOCATIONS OF LIGHT FIXTURES, MECHANICAL SYSTEMS, CONDUIT,

AND OTHER CONSTRUCTION, TO ALLOW FOR PROPER ACCESS TO SERVICE

EQUIPMENT.

IT IS THE REQUIREMENT OF THESE DOCUMENTS TO ALLOW ALL CEILINGS TO BE

CONSTRUCTED AT HEIGHTS AS SHOWN ON THE ARCHITECTURAL DRAWINGS.

COORDINATE THE LOCATION OF PIPING AND PROVIDE OFFSETS IN PIPING AS

REQUIRED TO MEET THIS REQUIREMENT.

ALL PIPING SHALL BE INDEPENDENTLY SUPPORTED, AND EACH SUPPORT

SHALL BE INDEPENDENT OF PARTITION AND CEILING SYSTEM SUPPORTS.

WHERE INDEPENDENT SUPPORT IS NOT POSSIBLE AN ENGINEERED SUPPORT

SYSTEM SHALL BE UTILIZED.

ALL WORK SHALL BE SCHEDULED AND PERFORMED IN STRICT COORDINATION

WITH ARCHITECTURAL PLANS AND WITH FACILITY SCHEDULES, OCCUPANCIES,

AND WORK. COORDINATE WITH FACILITY REPRESENTATIVE.

PROTECT EQUIPMENT AND FIXTURES FROM DAMAGE DURING HANDLING AND

INSTALLATION UNTIL COMPLETION OF CONSTRUCTION.

REMOVE ALL EXCESS MATERIAL AND DEBRIS AND CLEAN ALL EQUIPMENT UPON

COMPLETION OF WORK. TOUCH UP WITH PAINT WHERE REQUIRED.

CONTRACTOR SHALL VISIT JOB SITE AND VERIFY SIZE AND LOCATION OF ALL

EXISTING ITEMS AND CONDITIONS.

ALL CONNECTIONS BETWEEN PIPES OF DISSIMILAR MATERIALS SHALL BE MADE

WITH DIELECTRIC UNIONS.

COORDINATE ALL NEW WORK WITH ALL TRADES. WORK SHOWN ON THESE

DRAWINGS ARE INTENDED TO PROVIDE THE OVERALL ENGINEERING DESIGN

CONCEPT AND DOES NOT PROVIDE FOR RELOCATIONS, OFFSETS, ETC., THAT

ARE REQUIRED BY THE COORDINATION OF TRADES SHALL BE PROVIDED BY

THE CONTRACTOR AT NO ADDITIONAL COST TO THE CONTRACT.

THE EXISTING FACILITIES SHALL BE PROTECTED DURING THE CONSTRUCTION

ACTIVITIES. IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO STORE,

RELOCATE, AND REUSE ITEMS WHICH ARE SUBJECT TO DAMAGE.

COORDINATE ALL WALL MOUNTED DEVICE LOCATIONS WITH ARCHITECTURAL

INTERIOR ELEVATIONS.

DEMOLITION OF THE AREA SHALL OCCUR AS PART OF THE WORK FOR THAT

AREA. REMOVE ONLY THE PLUMBING THAT SERVES THE AREA OF DEMOLITION.

PROVIDE ADDITIONAL VALVES, TAPS, TEMPORARY PIPING, ETC. AS NECESSARY

TO PROVIDE UNINTERRUPTED SERVICE TO AREAS OUTSIDE OF THE PROJECT

IN WHICH WORK IS BEING PERFORMED.

ALL NECESSARY SHUTDOWNS IN OR OUT OF THE WORK AREA SHALL BE

COORDINATED AND SCHEDULED WITH THE FACILITY REPRESENTATIVE.

LOCATE ISOLATION VALVES FOR EQUIPMENT AND FIXTURES AS CLOSE TO THE

MAIN AS POSSIBLE. PROVIDE CEILING OR WALL ACCESS PANELS AS NEEDED.

ALL PLUMBING EQUIPMENT OR VALVES REQUIRING ACCESS THAT IS LOCATED

ABOVE GYP. BOARD OR OTHERWISE INACCESSIBLE CEILING SHALL BE

PROVIDED WITH A CEILING ACCESS PANEL SUPPLIED AND INSTALLED BY THE

GENERAL CONTRACTOR. THE MECHANICAL CONTRACTOR SHALL COORDINATE

THE EXACT LOCATION OF THESE ACCESS PANELS WITH THE GENERAL

CONTRACTOR.

PROVIDE DETAILED AND DIMENSIONED PIPING FABRICATION DRAWINGS FOR

APPROVAL BY THE ARCHITECT/ENGINEER. ONE BLUE-LINE SET OF THE

APPROVED DRAWINGS SHALL BE KEPT ON-SITE AT ALL TIMES AND ANY

CHANGES REQUIRED IN THE FIELD SHALL BE MARKED ON THESE DRAWINGS. AT

THE END OF THE PROJECT, ALL CHANGES SHALL BE TRANSFERRED TO A

REPRODUCIBLE DRAWING TO BE GIVEN TO THE OWNER FOR "AS-BUILT"

DRAWINGS. REPRODUCTIONS OF THIS DRAWING WILL NOT BE CONSIDERED AS

PIPING FABRICATION DRAWINGS.

ALL PLUMBING PIPING SHALL BE IDENTIFIED IN ACCORDANCE WITH SECTION

220553 OF THE SPECIFICATIONS.

ALL MAJOR AND SECTIONAL BALANCING VALVES SHALL BE TAGGED AND NOTED

ON THE "AS-BUILT" DRAWINGS.

SLOPE AND ARRANGE WATER PIPING SYSTEMS TO ESTABLISH HIGH POINTS

FOR AIR ELIMINATION AND LOW POINTS TO PERMIT PROPER DRAINING OF EACH

LINE.

COORDINATE ALL PIPING ROOF PENETRATIONS AND FLOOR PENETRATIONS

WITH STRUCTURAL. DUCT OPENINGS THROUGH ROOF SHALL BE THE SAME

REQUIRED FOR THE DUCT AND INSULATION ONLY.

TEST ALL SEWER, WATER, AND MEDICAL GAS PRIOR TO BACKFILL AND COVER.

CALL FOR INSPECTION AND WITNESS TESTING PRIOR TO CONCEALING SEWER,

WATER, AND MEDICAL GAS PIPING.

PENETRATIONS THROUGH RATED WALLS AND FLOORS SHALL BE SEALED WITH

A MATERIAL CAPABLE OF PREVENTING THE PASSAGE OF FLAMES AND HOT

GASES. ALL MATERIALS TO BE APPROVED OR LISTED.

FLUSH AND DISINFECT ALL POTABLE WATER PIPING PRIOR TO OCCUPANCY.

ABOVE GROUND DOMESTIC WATER PIPING SHALL BE TYPE "L" HARD COPPER

TUBE.

GENERAL NOTES

HP

R

FCA

M

FLOOR CLEANOUT OR GRADE CLEANOUTFCO

GCO

DRY SPRINKLER PIPING

NON-POTABLE TEMPERED WATER

COMPRESSED AIR PIPING

EXPANSION LOOP

SLEEVE THRU WALL

YARD HYDRANT

PLUMBING SYMBOLS

SYMBOL DESCRIPTION

DOMESTIC COLD WATER

DOMESTIC HOT WATER RETURN (TEMP. AS NOTED)

DOMESTIC HOT WATER (TEMP. AS NOTED)

STORM DRAIN PIPING

CONNECT NEW TO EXISTING

BACKFLOW PREVENTER (RPZ)

COLD OR HOT REDUCED PRESSURE PRINCIPLE

EXISTING PIPING TO BE REMOVED

PIPING TO BE ELECTRICALLY HEAT TRACED

SANITARY SEWER PIPING (SOIL OR WASTE)

SUB-SOIL DRAIN PIPING, FOOTING DRAIN PIPING

SANITARY VENT PIPING

ACID WASTE PIPING

ACID VENT PIPING

INDIRECT WASTE

SEWAGE EJECTOR DISCHARGE PIPING (PUMPED SANITARY)

CONDENSATE DRAIN PIPING

DRAIN PIPING

SUMP PUMP DISCHARGE PIPING

STORM OVERFLOW DRAIN PIPING

NATURAL GAS PIPING

GAS PIPE UNDER THE JURISDICTION OF THE ARIZONA CORPORATION COMMISSION

SPRINKLER PIPING (SPRK.)

GATE VALVE

BUTTERFLY VALVE

BALL VALVE

GLOBE VALVE

TEMPERATURE AND PRESSURE RELIEF VALVE

SOLENOID VALVE

VALVE IN VERTICAL

GAS COCK / PLUG VALVE

PRESSURE REGULATION VALVE (PRV)

AQUASTAT

CHECK VALVE

CHECK VALVE WITH AUTOMATIC BALL DRIP

GAS PRESSURE REGULATOR VALVE

BALANCING VALVE

STRAINER WITH BLOW-OFF VALVE

STRAINER

SHOCK ARRESTOR SA-(A)

WATER FLOW METER

HUB DRAIN

FLOOR DRAIN

2-WAY CLEANOUT (GRADE) (GCO)

PRESSURE GAUGE WITH GAUGE COCK

THERMOMETER WITH SHUT-OFF COCK

HOSE BIBB (HB) OR WALL HYDRANT (WH)

SSD

AW

AV

IW

SED

SD

D

CD

OD

SPD

G

CA

SP

NPTW

DSP

SA-A

FLOOR SINK

FD

FS

HD

ROOF DRAINRD

OVERFLOW ROOF DRAINOD

HIGH PRESSURE COLD WATER

GREASY WASTE SEWER PIPINGGW

ACC

WALL CLEANOUT

CLEANOUT PLUG

WCO

CO

FS

UNION

CAP OUTLET OR PLUGGED OUTLET

DIRECTION OF FLOW

DIRECTION OF SLOPE

SIAMESE FIRE DEPARTMENT CONNECTION

FIRE HOSE VALVE

FLOW SWITCH

DOUBLE CHECK VALVE ASSEMBLY (DCVA) WITH OS & Y VALVES SUPERVISED

SPRINKLER SYSTEM FLOOR CONTROL VALVE ASSEMBLY (FCVA)

OS & Y VALVE SUPERVISED (HORIZ. POSITION/VERT. POSITION)

CO

CAP SANITARY SEWER OR STORM PIPING

DOWNSPOUT NOZZLE (18"A.F.F.)

PUMP

ALL SYMBOLS SHOWN MAY NOT APPEAR IN ALL DRAWINGS.

SYMBOLS ARE SHOWN SCHEMATICALLY AND MAY NOT BE TO SCALE.

AQ

SS

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Fi le

P at h:

z

:\j ob s\ va el ko n at io na l c em et ar y\ 1b m ec h-pl bg \s he et s\ p-

- g en er al n ot es a nd a bb re vi at io ns

.d w ad av ed :4

/1 1/

:4 lo t:5 /2

/2

1:

P

M

Office of Design and Construction

Services

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

Project Director

Revisions:

1 3 6 0 5 1 s t A v e . N . # 1 0 0 P l y m o u t h , M N 5 5 4 4 1 P 7 6 3 . 4 1 2 . 4 0 0 0 | F 7 6 3 . 4 1 2 . 4 0 9 0 | a e - m n . c o m Anderson Engineering of Minnesota, LLC | Proj # 15795

ELKO NATIONAL CEMETERY

943-001

2/10/2023

3602 JENNINGS WAY, ELKO, NV 89801

100% CONSTRUCTION

DOCUMENTS

Date: Dwg. of 133

IRRIGATION: M.E.P.:GEOTECHNICAL :STRUCTURAL:

AST

7301 OHMS LANE, STE 215

EDINA, MN 55439

952-854-9302

MICHELLE SCHMIDT

WIM

175 JAMES AVE N.

MINNEAPOLIS, MN 55405

763-559-1010

TIM MALOOLY

TERRACON

6949 S. HIGH TECH DRIVE

MIDVALE, UT 84047

801-545-8500

JENNIFER DIERCKSEN

AESUS

1050 E. SOUTHERN AVE, STE 5

TEMPE, AZ 85282

480-454-2861

ORLANDO GONZALES

L-1 LAVATORY

(WALL HUNG)

MARK FIXTURE TYPE VENT SUPPLY

CW HWDESCRIPTION WASTE VENT

LAVATORY: AMERICAN STANDARD #0124.024 COMRADE WALL HUNG LAVATORY: VITREOUS CHINA, 4" CENTERS FAUCET

HOLES.

FAUCET: DELTA 523-HDF-DST 4" CENTERS CHROME FAUCET, 0.5, GPM, VANDAL RESISTANT AERATOR, GRID STRAINER, &

CONCEALED ARM SUPPORT.

ACCESSORIES: PROVIDE WITH 1/2" X 3/8" ANGLE STOPS WITH FLEXIBLE TUBE RISERS. OFFSET P-TRAP AND INSULATED WASTE AND WATER PIPING WITH TRUEBRO MODEL #102 E-Z LAV GUARD. PROVIDE TWO (2) SETS OF FAUCET WASHERS

TO OWNER FOR EACH FAUCET ON PROJECT.

3/4"2" 3/4"

EDF-1 ELECTRIC

WATER COOLER 3/4"2"

MOP SINK 2"2" 3/4" 3/4"MS-1 SINK: FIAT MSB2424, 24x24 MOLDED STONE MOP SINK WITH INTEGRAL STAINLESS STEEL STRAINER EXTENSION.

FAUCET: FIAT SERVICE SINK FAUCET MN: 830-AA CHROME PLATES FAUCET WITH INTEGRAL STOPS, VACUUM BREAKER, 3/4" HOSE THREAD AND WALL BRACE. MOUNT FITTING 24" AFF.

ACCESSORIES: FIAT #832-AA BRACKET, S.S., FIAT #833-AA SILICONE SEALANT INSTALLED PER MANUFACTURER. 50" COMMERCIAL GRADE RUBBER HOSE WITH 400# BURST TEST RATING WITH PISTOL GRIP TRIGGER NOZZLE AND INSULATED NOZZLE. FIAT #889-CC S.S. MOP HANGER, TRIPLE. FIAT #QDC3XH MOP SINK DRAIN GASKET, AND. PROVIDE 'P'

TRAP.

-3/4"FREEZE

PROOF

HOSE BIB

HB-1 --HOSE BIBB: WOODFORD MODEL 24, BRASS BODY WITH INTEGRAL MOUNTING FLANGE, REPLACEABLE HEXAGONAL DISK, THREADED HOSE SPOUT, INTEGRAL VACUUM BREAKER, ANSI/ASSE 1011 CONFORMANT, CHROME PLATED WHERE

EXPOSED WITH HANDWHEEL.

ELKAY, EZ8, SINGLE LEVEL WALL MOUNTED @ ADA COMPLIANT HEIGHT WITH STAINLESS STEEL TOP, INTEGRAL REFRIGERATION SYSTEM TO PROVIDE 8.0 GPH OF 50° F DRINKING WATER @ 90° F AMBIENT TEMPERATURE. SYSTEM

SHALL OPERATE @ 115 VOLT, FLA: 4.0, 370 WATTS, 55 LBS.

PROVIDE WITH EZ-FLO/EASTMAN #04322 1/2" X 3/8" ANGLE STOPS WITH FLEXIBLE TUBE RISER AND LOOSE KEY MOUNTED

BEHIND FIXTURE AND 1-1/2" P-TRAP ASSEMBLY.

WC-1

TOILET

(FLOOR MTD.)

ADA 1" -2"3"

WATER CLOSET: AMERICAN STANDARD VORMAX HET RIGHT HEIGHT ELONGATED TOILET. #238AA.104, VITREOUS CHINA, LOW-CONSUMPTION FLUSH TOILET, FLUSH 1.28 GPF, MEETS EPA WATERSENSE CRITERIA, 16-1/2" RIM HEIGHT FOR

ACCESSIBLE APPLICATIONS, OPEN FRONT SEAT, 2 YEAR WARRANTY.

ACCESSORIES: PROVIDE WITH TWO (2) SETS OF FLUSH VALVE SERVICE KITS FOR EACH WATERCLOSET ON PROJECT.

UR-1 URINAL

ADA 1" -2"3"

URINAL: AMERICAN STANDARD MAYBROOK UNIVERSAL URINAL, VITREOUS CHINA, LOW-CONSUMPTION FLUSH, 0.5 GPF, MEETS EPA WATERSENSE CRITERIA, PERMANENT EVERCLEAN SURFACE, INTEGRAL STRINER, 2 YEAR WARRANTY. FLUSH

VALVE: AMERICAN STANDARD 6045.051.002.

ACCESSORIES: PROVIDE WITH TWO (2) SETS OF FLUSH VALVE SERVICE KITS FOR EACH WATERCLOSET ON PROJECT.

WC-2 TOILET

(FLOOR MTD.)

1" -2"3"

WATER CLOSET: AMERICAN STANDARD PRIOLO FLOW WISE, 16-1/2" ELONGATED FLUSHOMETER TOILET, VITREOUS CHINA, LOW-CONSUMPTION, 1.6 GPF, ELONGATED WASH DOWN BOWL, CONCEALED TRAPWAY BOWL, FOR ACCESSIBLE

APPLICATIONS, OPEN FRONT SEAT, 2 YEAR WARRANTY.

ACCESSORIES: PROVIDE WITH TWO (2) SETS OF FLUSH VALVE SERVICE KITS FOR EACH WATERCLOSET ON PROJECT.

2"

2"

REDUCED

PRESSURE

BACKFLOW

PREVENTER

BFP ZURN WILKINS MODEL # 975XL, AWWA COMPLIANT C511, ASSE® LISTED 1013, IAPMO® LISTED, BRONZE BODY WITH BRONZE AND PLASTIC INTERNAL PARTS AND SS SPRINGS. TWO (2) INDEPENDENTLY OPERATING SPRING LOADED CHECK VALVES, THIRD CHECK VALVE WHICH OPENS UNDER PRESSURE IN CASE OF DIAPHRAGM FAILURE, NON-THREADED VENT

OUTLET: ASSEMBLED WITH TWO (2) GATE VALVES, STRAINER AND FOUR (4) TEST COCKS.

-1/2"--

ELECTRIC WATER HEATER SCHEDULE

MANUFACTURER MODEL STORAGE

CAPACITY

CAPACITY

EWT

F°

LWT

F°

WATTS

(KW) VOLT/Ø

RECOVERY

100 DEGREE

RISE (GPH)

REMARKS

NOTES:

NO SUBSTITUTIONS ARE ALLOWED.

WATER HEATER SHALL BE PROVIDED WITH ASME RATED T&P RELIEF VALVE.

PER DETAIL, PROVIDE THERMOSTATIC MIXING VALVE MODEL # POWERS LM49 WITH INTEGRAL CHECK VALVES AND INLET SCREENS.

PER DETAIL, PROVIDE EXPANSION TANK MODEL # WATTS PLT-5 OR EQUAL, WELDED STEEL, TESTED AND STAMPED IN ACCORDANCE WITH IAMPO AND CERTIFIED TO ANSI/NSF-61, RATED FOR 125 PSI, WITH FLEXIBLE DIAPHRAGM SEALED INTO TANK AND STEEL LEGS OR SADDLE. PROVIDE WITH PRESSURE GAUGE AND AIR CHARGE FITTING, TANK DRAIN & PRECHARGED TO 12 PSI.

STATEWH-1 40PATRIOT

PCE 40-20LSA 14040 4.5 18 240/1 1 2 3

FLOOR

DRAIN

FD-1 WADE MODEL 1100-STD FLOOR DRAIN, 5" TOP SIZE, DURA-COATED CAST IRON BODY WITH BOTTOM OUTLET, WITH

POLISHED BRONZE TOP AND LIGHT DUTY STRAINER.

PROVIDE WITH WADE "TRAP GUARD" INSERT FOR ACTUAL FLOOR DRAIN MODEL AND SIZE PROVIDED, FLEXIBLE ELASTOMERIC PVC MATERIAL MOLDED INTO SHAPE OF DUCK'S BILL, OPEN TOP WITH CURL AT CLOSURE AT BOTTOM, ALLOWS WASTE WATER TO OPEN AND ADEQUATELY DISCHARGE FLOOR DRAIN THROUGH ITS INTERIOR. CLOSES AND

RETURNS TO ORIGINAL MOLDED SHAPE AFTER WASTE WATER DISCHARGE IS COMPLETE.

-2"2" -

SYSTEM TYPE

NEW FIXTURES

41 FU =

MECH GPM REQUIREMENT

TOTAL CURRENT DEMAND (GPM)=

SITE PRESSURE (PSI)

PRESSURE LOSS THRU WATER METER (PSI)

PRESSURE REQUIRED AT FIXTURE (PSI)

PRESSURE LOSS THRU BACKFLOW (PSI)

AVAILABLE PRESSURE (PSI)

FURTHEST FIXTURE DISTANCE (FT)

VERTICAL LENGTH (FT)

ALLOWANCE FOR FITTINGS (FT)

TOTAL DEVELOPED LENGTH (FT)

MAXIMUM ALLOWABLE LOSS PER 100 FT OF

PIPE = 23.6 X 100 / 205 FT =

STATIC LOSS 30 x 0.43 (PSI)

41 FU

26.3 GPM

26.3 GPM

20.5

6.5

23.6

12.9

11.5

LEVEL NAME TOTAL FOR LEVEL

FLUSH VALVE

FUTURE FIXTURES

TOTAL FIXTURES

0 FU

41 FU

FIXTURE UNIT SCHEDULE

QTY

WC

FIXTURE FU/EACH TOTAL FU FU/EACH TOTAL FU

DOMESTIC

WATER WASTE

4 6 24 4 16

L 4 2 8 1 4

EDF 1 1 1 1 1

UR 1 5 5 4 4

41 31

FD 2 0 4

MS

0 2

1 3 3 2 2

BOOSTER

PUMP

BP-1 THE TW1000-10W-40 FLAG FRAME BOOSTER SYSTEM IS EQUIPPED WITH A CENTRIFUGAL PUMP REGULATED BY A VARIABLE FREQUENCY DRIVE THAT CONTROLS PUMP OPERATION TO MAINTAIN CONSTANT PRESSURE REGARDLESS OF VARYING DEMAND OR FLUCTUATION IN INCOMING PRESSURE. THIS SYSTEM WILL SUPPLY 10 GPM WITH A 40 PSI

OVERBOOST. PROVIDE PNEUMATIC EXPANSION TANK PLT-5.

-2"2" -

PACKAGE BOOSTER PUMP SCHEDULE

MANUFACTURER MODEL

PRESSURE

TRANSMITTER

SETPOINT

FLOW WATTS

(KW) VOLT/Ø

RECOVERY

100 DEGREE

RISE (GPH)

REMARKS

TOWLE WHITNEYBP-1 60TW1000-10W-40 10

GPM 0.75 18 208/1

HORSE

POWER

1/2

RE-CIRCULATION PUMP

MANUFACTURER MODEL MAX FT HEAD FLOW AMPS VOLT/Ø REMARKS

TACOCP-1 15 FT008-SF6 10

GPM 0.84 115V AC

HORSE

POWER

1/25

1214/05/2023

100% CD SUBMITTAL

BID DOCUMENTS

WH

MENS

WOMENS

STORAGE

PORTICO

TECH

CLOSET

HAC

STANDING SEAM

METAL ROOF

RIDGE

ROOF SLOPE

6:12

DASHED LINE

INDICATES EXTERIOR

FACE OF WALL BELOW

WOOD FRAMING

SL

OP

E

ROOF SLOPE

6:12

GUTTER

GUTTER

1/2 / 1

METAL SNOW GUARD

TYPICAL

P-101

PIC/BATHROOM BUILDING PLUMBING

FLOOR PLAN & DETAILS

PLUMBING FLOOR PLAN

SCALE: 1/4" = 1'-0"

GENERAL NOTES

1. LIGHTING AND SPRINKLER HEADS TAKE PRECEDENCE OVER

DIFFUSER LOCATION. CONTRACTOR SHALL MAKE NECESSARY

ADJUSTMENT TO DIFFUSERS TO AVOID ANY CONFLICT WITH

LIGHTING LAYOUT AND SPRINKLER HEADS.

2. THERMOSTATS SHALL BE MOUNTED PER ADA REQUIREMENTS.

MAXIMUM HEIGHT FOR FRONT ACCESS SHALL BE 48" AFF. DO

NOT MOUNT ABOVE FIXED COUNTER UNLESS KNEE HOLE

ACCESS IS PROVIDED.

3. CONTRACTOR SHALL COORDINATE ALL FINAL THERMOSTAT

LOCATIONS WITH OWNER AND ARCHITECT PRIOR TO

MOUNTING.

4. THE CONTRACTOR SHALL DO ALL NECESSARY CUTTING OF

WALL AND CEILINGS.

5. NO STRUCTURAL MEMBER SHALL BE CUT WITHOUT

PERMISSION FROM THE ENGINEER.

6. OPENINGS IN FLOORS, WALLS, CEILINGS, ROOFS, ETC. AS A

RESULT OF REMOVED PIPING, DUCTWORK, FLUES,

EQUIPMENT, FIXTURES, ETC SHALL BE PATCHED TO MATCH

EXISTING BUILDING CONSTRUCTION. WORK SHALL BE

PERFORMED BY CRAFTSMEN SKILLED IN THEIR RESPECTIVE

TRADES.

7. DUCTWORK CONSTRUCTION AND INSTALLATION INCLUDING

SHEET METAL GAUGES, REINFORCEMENT, JOINT SEALING, AIR

LEAKAGE, AND DETAILS NOT SPECIFICALLY SHOWN ON

DRAWINGS SHALL BE IN ACCORDANCE WITH CURRENT IMC &

VA DUCT CONSTRUCTION STANDARDS.

8. CONTRACTOR SHALL PROVIDE COORDINATION FOR

DUCTWORK ROUTE DRAWINGS, THIS MUST BE APPROVED BY

ENGINEER PRIOR TO CONSTRUCTION.

9. CONTRACTOR IS RESPONSIBLE FOR PROTECTING OPENING

AND RESPONSIBLE FOR ANY DAMAGE CAUSED BY

CONSTRUCTION METHODS.

10. CONTRACTOR SHALL PERFORM LEAK TEST ON ROOF AFTER

CONSTRUCTION IS COMPLETE AND REPAIR THE ROOF AS

NECESSARY.

KEY NOTES

1. 2-WAY CLEAN OUT

2. BOOSTER PUMP, REFER TO DETAIL 4.

3. REFER TO CIVIL PLANS FOR CONTINUATION.

4. GRADE CLEAN-OUT.

5. PROVIDE 0.5 GPM HW RE-CIRCULATION PUMP.

3 3

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Fi le

P at h:

z

:\j ob s\ va el ko n at io na l c em et ar y\ 1b m ec h-pl bg \s he et s\ p-

- p lu m bi ng p la n.

dw ad av ed

:5 /2

/2

1:

lo t:5

/2 /2

1:

P M

Office of Design and Construction

Services

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

Project Director

Revisions:

1 3 6 0 5 1 s t A v e . N . # 1 0 0 P l y m o u t h , M N 5 5 4 4 1 P 7 6 3 . 4 1 2 . 4 0 0 0 | F 7 6 3 . 4 1 2 . 4 0 9 0 | a e - m n . c o m Anderson Engineering of Minnesota, LLC | Proj # 15795

ELKO NATIONAL CEMETERY

943-001

2/10/2023

3602 JENNINGS WAY, ELKO, NV 89801

100% CONSTRUCTION

DOCUMENTS

Date: Dwg. of 133

IRRIGATION: M.E.P.:GEOTECHNICAL :STRUCTURAL:

AST

7301 OHMS LANE, STE 215

EDINA, MN 55439

952-854-9302

MICHELLE SCHMIDT

WIM

175 JAMES AVE N.

MINNEAPOLIS, MN 55405

763-559-1010

TIM MALOOLY

TERRACON

6949 S. HIGH TECH DRIVE

MIDVALE, UT 84047

801-545-8500

JENNIFER DIERCKSEN

AESUS

1050 E. SOUTHERN AVE, STE 5

TEMPE, AZ 85282

480-454-2861

ORLANDO GONZALES

WH-1

L-1 L-1

L-1 L-1

UR-1

WC-2 WC-1

WC-2 WC-1

EDF-1

MS-1

HB-1

NOT LESS THAN 2"

(TYPICAL)

GRADE

SURFACE CLEANOUT SEE

SPECIFICATIONS (TYPICAL)

CONCRETE SLAB- EXTEND

MINIMUM OF 6" BEYOND

PERIMETER OF CLEANOUTS

FLOWMAIN SEWER

TW

O

-W

AY

C

LE

AN

O

U T

D

ET

AI

L

SEE SPECIFICATIONS FOR PIPE

AND FITTING TYPE.

W

AT

ER

H

EA

TE

R D

IA

G

R

AM

ANCHOR OR SUPPORT WATER HEATER IN SEISMIC AREAS.2.

SEE FLOOR PLAN FOR CONTINUATION AND PIPE SIZES.1.

NOTE:

SUPPORT STAND MIN 18" HIGH

DRAIN VALVE

CHECK VALVE

(TYP)

HOT WATER

SUPPLY

COLD WATER

SUPPLY

ISOLATION VALVE

(TYP)

FINISHED FLOOR

VACUUM RELIEF

VALVE

THERMOMETER

(TYP)

ASME APPROVED

TEMPERATURE &

PRESSURE RELIEF

VALVE

RELIEF PIPE- FULL

SIZE OF

DISCHARGE

OPENING

WATER

HEATER

ET

THERMOSTATIC

MIXING VALVE

DIELECTRIC UNION

EXPANSION TANK

NOTE: NOT TO SCALE

H O

T

AN

D C

O

LD

W

AT

ER

H

O

SE

B

IB

B D

ET

AI

L

FULL PORT BALL VALVES

SHUT-OFF VALVES @ +48" A.F.F.

3/4" HOSE BIBB @ +25" A.F.F.

3/4" CW3/4" HW

UNISTRUT MOUNTING BRACKET

TYPICAL EVERY 5 FEET

3/4" ARMAFLEX

INSULATION

3/4" HOSE BIBB

CHECK VALVE

FD-1

FD-1

CHECK VALVE

NORMALLY CLOSED

SHUT-OFF VALVE

2" BYPASSBOOSTER PUMP

SHUT-OFF VALVE

UNION (TYP.)

PRESSURE GAUGE/TRANSDUCER (TYPE)

CONCRETE HOUSEKEEPING PAD

BLADDER TYPE

DIAPHRAM TANK

PR

ES

SU

R

E

BO

O

ST

ER

D

ET

AI

L

BP-1

PLUMBING ROOF PLAN - PIC/BATHROOM

SCALE: 1/4" = 1'-0"

NOTE:

ROOF DRAIN PIPE SIZED

BASED ON 2018 IPC TITLE

1106.6 AND 1" RAINFALL

2" VERTICAL GUTTER

CAN HANDLE UP TO 30

GPM.

2X2 HORIZONTAL

GUTTER CAN HANDLE UP

TO 26 GPM.

BASED ON MY

CALCULATION.

2"X2" GUTTER 2" DOWNSPOUT2" DOWNSPOUT 2"X2" GUTTER

2"X2" GUTTER 2" DOWNSPOUT2" DOWNSPOUT 2"X2" GUTTER

2" DOWNSPOUT

2"X2" GUTTER

2" DOWNSPOUT

2"X2" GUTTER

PLUMBING ROOF PLAN - COMMITTAL SHELTER

SCALE: 1/4" = 1'-0"

NOTE:

ROOF DRAIN PIPE SIZED

BASED ON 2018 IPC TITLE

1106.6 AND 1" RAINFALL

2" VERTICAL GUTTER

CAN HANDLE UP TO 30

GPM.

2X2 HORIZONTAL

GUTTER CAN HANDLE UP

TO 26 GPM.

BASED ON MY

CALCULATION.

1224/05/2023

100% CD SUBMITTAL

BID DOCUMENTS

SEE CIVIL PLANS

FOR CONTINUATION

3" V

ROOF

PENETRATION

(TYP).

2" W

4" W

MS-1

FD-1

WC-2

WC-1

WC-2

WC-1

FD-1

UR-1

L-1

EDF-1

WCO

WCO

L-1

WCO

3" W

3" W

3" V

2" V

L-1 L-1

EDF-1

L-1 L-1

HB-1

WH-1

MS-1

1-1/2" CW

3/4" CW

3/4" HW

3/4" CW

3/4" HW

1" CW

1" CW

3/4" CW

3/4" HW

3/4" HW3/4" CW

3/4" CW

BALL

VALVE

(TYP)

1-1/4" CW

3/4" HW

1-1/4" CW

DOMESTIC WATER PIPING SCHEMATIC

NTS

WASTE WATER PIPING SCHEMATIC

NTS

NOTE:

2" AND 3" WASTE PIPE

SHALL BE SLOPED 1/4"

PER FOOT.

4" WASTE PIPE SHALL BE

SLOPED 1/8" PER FOOT.

BP-1

1" CW

3/4" HW

2" W

2" V

CO

P-101

PIC/BATHROOM BUILDING PLUMBING

SCHEMATIC

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Fi le

P at h:

z

:\j ob s\ va el ko n at io na l c em et ar y\ 1b m ec h-pl bg \s he et s\ p-

- p lu m bi ng p la n.

dw ad av ed

:5 /2

/2

1:

lo t:5

/2 /2

1:

P M

Office of Design and Construction

Services

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

Project Director

Revisions:

1 3 6 0 5 1 s t A v e . N . # 1 0 0 P l y m o u t h , M N 5 5 4 4 1 P 7 6 3 . 4 1 2 . 4 0 0 0 | F 7 6 3 . 4 1 2 . 4 0 9 0 | a e - m n . c o m Anderson Engineering of Minnesota, LLC | Proj # 15795

ELKO NATIONAL CEMETERY

943-001

2/10/2023

3602 JENNINGS WAY, ELKO, NV 89801

100% CONSTRUCTION

DOCUMENTS

Date: Dwg. of 133

IRRIGATION: M.E.P.:GEOTECHNICAL :STRUCTURAL:

AST

7301 OHMS LANE, STE 215

EDINA, MN 55439

952-854-9302

MICHELLE SCHMIDT

WIM

175 JAMES AVE N.

MINNEAPOLIS, MN 55405

763-559-1010

TIM MALOOLY

TERRACON

6949 S. HIGH TECH DRIVE

MIDVALE, UT 84047

801-545-8500

JENNIFER DIERCKSEN

AESUS

1050 E. SOUTHERN AVE, STE 5

TEMPE, AZ 85282

480-454-2861

ORLANDO GONZALES 1234/05/2023

100% CD SUBMITTAL

BID DOCUMENTS

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Fi le

P at h:

z

:\j ob s\ va el ko n at io na l c em et ar y\ 1c e le ct ric al \s he et s\ e0 ge ne ra l n ot es a nd a bb re vi at io ns .d w ae su s de si gn sa ve d:

5/

3/

0:

A lo t:5 /3

/2

:2

AM

Office of Design and Construction

Services

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

Project Director

Revisions:

1 3 6 0 5 1 s t A v e . N . # 1 0 0 P l y m o u t h , M N 5 5 4 4 1 P 7 6 3 . 4 1 2 . 4 0 0 0 | F 7 6 3 . 4 1 2 . 4 0 9 0 | a e - m n . c o m Anderson Engineering of Minnesota, LLC | Proj # 16735

ELKO NATIONAL CEMETERY

943-001

5/5/2023

3602 JENNINGS WAY, ELKO, NV 89801

BID DOCUMENTS

Date: Dwg. of 133

BID DOCUMENTS

IRRIGATION: M.E.P.:GEOTECHNICAL :STRUCTURAL:

AST

7301 OHMS LANE, STE 215

EDINA, MN 55439

952-854-9302

MICHELLE SCHMIDT

WIM

175 JAMES AVE N.

MINNEAPOLIS, MN 55405

763-559-1010

TIM MALOOLY

TERRACON

6949 S. HIGH TECH DRIVE

MIDVALE, UT 84047

801-545-8500

JENNIFER DIERCKSEN

AESUS

1050 E. SOUTHERN AVE, STE 5

TEMPE, AZ 85282

480-454-2861

ORLANDO GONZALES

EP-001

ELECTRICAL GENERAL NOTES,

ABBREVIATIONS & SYMBOLS

1. THE COMPLETE INSTALLATION SHALL BE IN ACCORDANCE WITH THE ADA STANDARDS FOR

ACCESSIBLE DESIGN. REFER TO THE ADA GUIDELINES F0R ALL CONFIGURATIONS DETAIL ON

THIS PAGE FOR ADDITIONAL INFORMATION.

2. CIRCUIT NUMBERS ARE SHOWN FOR CIRCUIT IDENTIFICATION. CIRCUITING SHALL AGREE WITH

NUMBERING ONT HE PANEL PROVIDED. COMMON NEUTRALS MAY NOT BE USED FOR BRANCH

CIRCUITS. BALANCE THE LOAD ON PANEL AS EVENLY AS POSSIBLE BETWEEN EACH PHASE.

3. MOUNT ALL DUPLEX RECEPTACLES OUTLETS AT +24" FROM GROUND/FLOOR (CENTERLINE

DIMENSION) EXCEPT WHERE OTHERWISE NOTED.

4. CONTRACTOR SHALL VERIFY ALL EQUIPMENT LOCATIONS WITH ARCHITECTURAL/CIVIL PLANS, ELEVATIONS, IRRIGATION PLANS, AND REVIEWED SHOP DRAWINGS. PRIOR TO MAKING THE

ACTUAL ELECTRICAL INSTALLATION, THIS CONTRACTOR SHALL ADJUST RECEPTACLES,

OUTLETS, OR CONNECTION LOCATIONS TO ACCOMMODATE FURNITURE AND/OR EQUIPMENT.

5. ELECTRICAL EQUIPMENT SHALL BE MOUNTED TO AVOID IMPEDANCE OF, OPERATION 0F,

AND/OR ACCESS TO ELECTRICAL EQUIPMENT ALL MOUNTING OF ELECTRICAL EQUIPMENT, 0N

EQUIPMENT SUPPLIED BY ANOTHER CONTRACTOR, SHALL BE APPROVED IN ADVANCE BY THE

OTHER CONTRACTOR,

ELECTRICAL INSTALLATION NOTES:

ABBREVIATIONS

@ AT

A/C AIR CONDITIONING(ER)

A (AMP) AMPERE

AC ABOVE COUNTER, ALTERNATING

CURRENT

ADJ ADJUSTABLE

ADJT ADJACENT

AFF ABOVE FINISHED FLOOR

AIC AMPERE INTERRUPTING CAPACITY

ARCH ARCHITECT; ARCHITECTURAL

ATS AUTOMATIC TRANSFER SWITCH

AUTO AUTOMATIC

AWG AMERICAN WIRE GAUGE

BKBD BACKBOARD

BKR BREAKER

BLDG BUILDING

C CONDUIT

CAP CAPACITY

CB CIRCUIT BREAKER

CKT CIRCUIT

CLG CEILING

CLR CLEAR

COL COLUMN

CT CURRENT TRANSFORMER

CTL CONTROL

CU COPPER

DISC SW DISCONNECT SWITCH

DISC DISCONNECT

DN DOWN

DWG DRAWING

(E) EXISTING TO REMAIN

(EL) EXISTING TO BE RELOCATED

(ER) EXISTING TO BE REMOVED

(RE) RELOCATED ITEM PER (EL)

E EAST

EC ELECTRICAL CONTRACTOR

EDH ELECTRIC DUCT HEATER

EF EXHAUST FAN

EGC EQUIPMENT GROUNDING CONDUCTOR

EL ELEVATION

ELEC ELECTRIC(AL)

EM EMERGENCY

EMT ELECTRICAL METALLIC TUBING

ENCL ENCLOSURE

ENTR ENTRANCE

EP EXPLOSION PROOF

EPO EMERGENCY POWER OFF

EQUIP/EQP EQUIPMENT

EWC ELECTRIC WATER COOLER

EWH ELECTRIC WATER HEATER

EXH EXHAUST

EXT EXTERIOR

EXIST EXISTING

F FAHRENHEIT/FUSE

FA FIRE ALARM

FAA FIRE ALARM ANNUNCIATOR

FACP FIRE ALARM CONTROL PANEL

FC FOOTCANDLE

FCU FAN COIL UNIT

FDR FEEDER

FIXT FIXTURE

FLA FULL LOAD AMPS

FSD FIRE/SMOKE DAMPER

GEC GROUNDING ELECTRODE CONDUCTOR

GEN GENERATOR

GFI GROUND FAULT CIRCUIT INTERRUPTER

GFR GROUND FAULT RELAY

H HEIGHT

HP HORSEPOWER

HR HOUR

HT HEIGHT

HW HOT WATER

HZ HERTZ

IBC INTERNATIONAL BUILDING CODE

IC INTERCOM

IES ILLUMINATING ENGINEERING SOCIETY

IG ISOLATED GROUND

IMC INTERMEDIATE METAL CONDUIT

IN INCH

JB JUNCTION BOX

KCMIL THOUSAND CIRCULAR MILLS

KVA KILOVOLT AMPERES

KVAR KILOVOLT AMPERES REACTIVE

KW KILOWATT

KWH KILOWATT HOUR

LBS POUNDS

LF LINEAR FEET (FEET)

LRA LOCKED ROTOR AMPS

LS LIFE SAFETY

LT LIGHT

LTG LIGHTING

LV LOW VOLTAGE

MAG MAGNETIC

MAN MANUAL

MAT MATERIAL

MAX MAXIMUM

MCA MINIMUM CIRCUIT AMPACITY

MCB MAIN CIRCUIT BREAKER

MECH MECHANICAL

MEZZ MEZZANINE

MG MOTOR GENERATOR

MH MANHOLE

MIN MINIMUM

MISC MISCELLANEOUS

MLO MAIN LUG ONLY

MOCP MAXIMUM OVERCURRENT

PROTECTION

MS MAGNETIC STARTER

MTD MOUNTED

MTG MOUNTING

MTR MOTOR

N NORTH; NEUTRAL

N/A NOT APPLICABLE

NC NORMALLY CLOSED

NEC NATIONAL ELECTRICAL CODE

NEMA NATIONAL ELECTRICAL

MANUFACTURERS

ASSOCIATION

NESC NATIONAL ELECTRICAL

SAFETY CODE

NEUT NEUTRAL

NFPA NATIONAL FIRE PROTECTION

ASSOCIATION

NIC NOT IN CONTRACT

NO NORMALLY OPEN

NTS NOT TO SCALE

OC ON CENTER

OFCI OWNER FURNISHED

CONTRACTOR INSTALLED

OFOI OWNER FURNISHED OWNER

INSTALLED

OL OVERLOAD

OS OPTIONAL STANDBY

P PRIMARY

PA PUBLIC ADDRESS

PAR PARALLEL

PB PULL BOX

PE PHOTO ELECTRIC

PF POWER FACTOR

PH PHASE

PHH POWER HAND-HOLE

PIV POST INDICATOR VALVE

PNL PANEL

POC POINT OF CONNECTION

PWR POWER

QTY QUANTITY

R (R) RELOCATE (D)

RAD RADIUS

RECPT RECEPTACLE

REF REFRIGERATOR

RLA RATED LOAD AMPS

S SOUTH

SC SECURITY

SCCR SHORT CIRCUIT CURRENT

RATING

SD SMOKE DETECTOR

SECT SECTION

SF SUPPLY FAN

STOR STORAGE

SW SWITCH

SWBD SWITCHBOARD

SYM SYMMETRICAL

SYS SYSTEM

T THERMOSTAT

TC TIME CLOCK

TYP TYPICAL

UC UNDER COUNTER

UG UNDERGROUND

UH UNIT HEATER

UL UNDERWRITERS

LABORATORIES

UON UNLESS OTHERWISE NOTED

UV UNIT VENTILATOR

V VOLT

VEL VELOCITY

VM VOLTMETER

W WATT, WEST

W/ WITH

W/O WITHOUT

WH WATER HEATER

WHM WATT HOUR METER

WP WEATHERPROOF

X REACTANCE

XFMR TRANSFORMER

XMTR TRANSMITTER

Z(%) IMPEDANCE

& AND

I.E.: THAT IS

E.G. FOR EXAMPLE

SYMBOLS LEGEND - WIRING DEVICES

DESCRIPTIONSYMBOL

SINGLE-POLE WALL SWITCH. MOUNT AT 48" AFF. TO TOP (PER ADA) , UON.

WALL SWITCH - SUBSCRIPT

SPECIAL PURPOSE…