221531_-_M0.0.pdf

PDF 221 KB Posted

Attached to
Collin County Courthouse Chilled Water Lines Replacement
Solicitation number
2024-419
Issued by
Collin County, Texas

About this file

This document is a Mechanical Legend and General Notes sheet (M0.0) for the Collin County Courthouse Chilled Water Piping Replacement project, prepared by MD Engineering. The project scope involves replacing the existing 18-inch underground black steel chilled water piping with 18-inch underground HDPE piping. The base plan includes piping replacement from a new vault to the building entrance, with 18-inch butterfly valves added for building isolation. Alternate 1 extends the replacement scope from Vault 5 to the new vault, which will house two 18-inch isolation valves for a future courthouse expansion.

The project requires significant temporary infrastructure, including providing a 500-ton air-cooled chiller with generator for temporary service during construction. The contractor must perform cryogenic freezing of existing chilled water lines to install valves for risers and temporary piping connections. Additional requirements include minimal disruption to neighboring tenants, performing saw cutting after hours, and coordinating with architectural, structural, civil, and electrical work. The project emphasizes careful verification of existing system information and adherence to SMACNA and manufacturer standards for installation.

View the file

Other files

Show all 12

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

1. PROVIDE ALL MATERIALS AND EQUIPMENT AND PERFORM ALL

LABOR REQUIRED TO INSTALL COMPLETE AND OPERABLE

MECHANICAL SYSTEM AS INDICATED ON THE DRAWINGS, AS

SPECIFIED AND AS REQUIRED BY ALL NATIONAL, STATE AND

LOCAL CODES.

2. CONTRACT DRAWINGS FOR MECHANICAL WORK ARE

DIAGRAMMATIC AND ARE INTENDED TO CONVEY SCOPE AND

GENERAL ARRANGEMENT ONLY. IT IS THE CONTRACTORS

RESPONSIBILITY FOR INSTALLING ALL MATERIALS PER SMACNA

STANDARDS AND THE MANUFACTURER'S STANDARDS.

3. ALL EXISTING SYSTEM INFORMATION AND/OR LOCATIONS

ARE PROVIDED BY THE OWNER OR BY A 3RD PARTY.

IT IS THE CONTRACTORS RESPONSIBILITY TO VERIFY ALL MEP

SERVICES ARE LOCATED AS DESIGNED BEFORE BIDDING THE

PROJECT. IN OCCURRENCES WHERE EXISTING DOES NOT

MATCH DESIGNED, IT IS THE CONTRACTORS RESPONSIBILITY

TO NOTIFY THE OWNER, ARCHITECT, & ENGINEER

BEFORE PROCEEDING. IF ANY DISCREPANCIES ARE NOT

IDENTIFIED AT BIDDING, THE COST SHALL BE ABSORBED BY

THE CONTRACTOR AND NOT PASSED ONTO THE OWNER OR

ENGINEER OF RECORD.

4. COORDINATE CONSTRUCTION OF ALL MECHANICAL WORK WITH

ARCHITECTURAL, STRUCTURAL, CIVIL, ELECTRICAL WORK, ETC.,

SHOWN ON THE OTHER CONTRACT DRAWINGS.

5. WHEN TWO OR MORE ITEMS OF THE SAME TYPE OF EQUIPMENT

ARE REQUIRED, THE PRODUCT OF ONE MANUFACTURE SHALL BE

USED.

6. ALL MISCELLANEOUS STEEL REQUIRED TO ENSURE PROPER

INSTALLATION AND AS SHOWN IN DETAILS FOR PIPING SHALL BE

FURNISHED AND INSTALLED BY THE MECHANICAL CONTRACTOR.

7. LOCATION AND SIZES OF ALL FLOOR, AND WALL, OPENINGS

SHALL BE COORDINATED WITH ALL OTHER TRADES.

8. ALL DEMOLITION ACTIVITIES SHALL BE PERFORMED SO AS TO

PROVIDE MINIMAL DISRUPTION TO THE NEIGHBORING TENANTS.

9. ALL SAW CUTTING SHALL BE PERFORMED AFTER HOURS SO THAT

OPERATION DOES NOT DISTURB NEIGHBORING TENANTS. THERE

SHALL BE NO GAS POWERED EQUIPMENT IN TENANT AREAS.

GENERAL PROJECT NOTES:

FLOOR CONTROL VALVE

TEE

TEE, UP

TEE, DOWN

SINGLE SWEEP TEE

CROSS

LATERAL

45 DEGREE ELBOW

90 DEGREE ELBOW

90 DEGREE ELBOW UP

CAP

HVAC VALVE

VENT THRU ROOF

BUTTERFLY VALVE

SOLENOID VALVE

EXPANSION JOINT

FLOAT AND THERM. TRAP

BUCKET STEAM TRAP

FLOOR CLEAN OUT

FIRE HOSE CABINET

PRESSURE RELIEF VALVE

CONTROL, 2 WAY VALVE

CONTROL, 3 WAY VALVE

STRAINER & BLOW OFF VALVE

PRESSURE GAUGE & COCK

UNION OR COMPANION FLANGES

PRESSURE & TEMPERATURE TAP (PETES PLUG)

MANUAL AIR VENT

TEMPERATURE SENSOR

PRESSURE SENSOR

THERMOMETER & WELL

HOSE END DRAIN

AUTOMATIC AIR VENT

FLOW METER

T S

F FLOW SWITCH

ANCHOR (PIPE)

HOSE BIBB

B

B

T

H

F

F.H.C.

D.S.

CO

CO

OR

R.D.

V.T.R.

HUMIDISTAT

CLEAN OUT

GATE VALVE

FLOOR DRAIN

HUB DRAIN

DOWN SPOUT

ROOF DRAIN

CHECK VALVE

GLOBE VALVE

BALL VALVE

PLUG VALVE

THERMOMETER

THERMOSTAT

OS & Y VALVE

& FITTINGS SYMBOLS

ALL SYMBOLS ON THIS LIST ARE NOT NECESSARILY USED ON THIS JOB.

BALANCING VALVE (WITH PETE'S PLUG EITHER SIDE)

SINGLE W.F. LATERAL STUB

DOUBLE W.F. LATERAL STUB

DOUBLE W.F. LAT & TRAP

FLOOR DRAIN RISER W/TRAP

SINGLE W.F. LAT. & TRAP

O.D. OVERFLOW ROOF DRAIN

PIPE GUIDE

COMPRESSED AIR TAP

MOTORIZED ISOLATION VALVE (2-POSITION-24v)

MANUALLY CALIBRATED BALANCING VALVE

AUTOMATIC FLOW CONTROL VALVE

PIPE SIZE REDUCER (CONCENTRIC)

90 DEGREE ELBOW DOWN

ANGLE GATE VALVE

ANGLE GLOBE VALVE

PIPE SIZE REDUCER (ECCENTRIC)

MOTORIZED CONTROL VALVE (MODULATING-24v)

EXISTING PIPING

EXISTING PIPING TO BE REMOVED

UNDERFLOOR

CONNECT TO NEW OR EXISTING

CHILLED WATER SUPPLY

CHILLED WATER RETURN

SYMBOL DESCRIPTION

X X X

CHWS

CHWR

ABOVE

ALTERNATING CURRENT

AIR CONDITIONER

ABOVE FINISHED FLOOR

ABOVE GRADE AND GFI

AIR HANDLING UNIT

ALTERNATE

AMPERE

APPROXIMATELY

ARCHITECTURAL

AVERAGE

BOILER

BAROMETRIC RELIEF DAMPER

BRITISH THERMAL UNIT

CUBIC FEET PER MINUTE

CONSTRUCTION DOCUMENTS

CHILLER

CHEMICAL

CHILLED WATER PUMP

CEILING

COMPRESSOR

COOLING TOWER

CONDENSER WATER PUMP

DRY BULB

DETAIL

DIAMETER

DIMENSION

DESIGN DEVELOPMENT

ENTERING DRY BULB

ELECTRICAL

ELEVATION

ENTERING WET BULB

ENTERING WATER TEMPERATURE

EXHAUST

EXISTING

DEGREES FAHRENHEIT

GROUND FAULT INTERRUPTER

GALLONS PER MINUTE

FEET PER MINUTE

FEET PER SECOND

FOOT OR FEET

HEAD

HEAT PUMP UNIT

HOUR(S)

HEIGHT

HEATER

HEAT,VENT AND AIR CONDITIONING

HOT WATER PUMP

HEAT EXCHANGER

FREQUENCY (HERTZ)

INSIDE DIAMETER OR DIMENSION

INCHES

KILOWATT

KILOWATT HOUR

MAXIMUM

LEAVING WATER TEMPERATURE

1000 BTU PER HOUR

MECHANICAL

MANUFACTURER

MINIMUM

NUMBER

NOT APPLICABLE

NOISE CRITERIA

NECK DIMENSION

OPPOSED BLADE DAMPER

OUTSIDE DIAMETER

OUTSIDE AIR

ORIGINAL

PHASE

POWERED MIXING BOX

PLUMBING

PRESSURE

PANEL

REFERENCE

RETURN AIR

RETURN AIR GRILLE

ROOF TOP UNIT

STAND ALONE DIGITAL CONTROLLER

SENSIBLE

SQUARE

SUPPLY AIR

STATIC PRESSURE

SINGLE SPEED MOTOR

START/STOP/STATUS

TEMPERATURE

VOLT

VARIABLE AIR VALVE

VELOCITY

WATT

WITH

WEATHERPROOF

WATER PRESSURE DROP

WEATHERPROOF GFI

TRANSFORMER

ABV.

AC

A/C

AFF

AG

AHU

ALT.

AMP.

APPROX.

ARCH.

AVG.

B

BRD

BTU

CFM

CD

CH.

CHEM.

CHP

CLG.

CMPR.

CT

CWP

DB

DET.

DIA.

DIM.

DD

EDB

ELEC.

ELEV.

EWB

EWT

EXH.

EXIST.

DEG. F

GFI

GPM

FPM

FPS

FT.

HD.

HPU

HR.

HT.

HTR.

HVAC

HWP

HX

HZ.

ID

IN.

KW

KWH

MAX.

LWT

MBH

MECH.

MFR.

MIN.

NO.

N/A

NC

NK

OBD

OD

OA

ORIG.

PH.

PMB

PLBG.

PRESS.

PNL.

RE.

RA

RAG

RTU

SDC

SENS.

SQ.

SA

SP

S/S S/S/S

TEMP.

V

VAV

VEL.

W W/

WP.

WPD

WPG

XFMR.

AFG ABOVE FINISHED GRADE

CKT. CIRCUIT

DEFL. DEFLECTION

MVD MANUAL VOLUME DAMPER

WB WET BULB

MEP ABBREVIATIONS

WITHOUTW/O

UNO UNLESS NOTED OTHERWISE

UH UNIT HEATER

SAG SUPPLY AIR GRILLE

LAT LEAVING AIR TEMPERATURE

HP HORSE POWER

FLR. FLOOR

FAN COIL UNITFCU

EF EXHAUST FAN

CONDENSING UNITCU

RD. RADIUS

HOA HANDS/OFF/AUTO. MOTOR STARTER

HTG. HEATING

EA EXHAUST AIR

F/A FREE AREA OPENING (SQ. FT.)

ABOVE FINISHED CEILINGAFC

NOT IN CONSTRUCTIONNIC

W.G. WATER GUAGE

TOTAL STATIC PRESSURE (IN. W.G.)T.S.P.

MOTOR STARTERSTR.

SEER SEASON ENERGY EFFICIENCY RATIO

AMB. AMBIENT TEMPERATURE (F. DEGREE)

BUILDING MANAGEMENT SYSTEM BMS

CUBIC FEET PER HOURCFH

DISC. DISCONNECT SWITCH

ENERGY MGMT. CONTROL SYSTEM

EXTERNAL STATIC PRESS. (IN. W.G.)E.S.P.

EMCS.

P.D. PRESSURE DROP (FT)

RPM REVOLUTIONS PER MINUTE

FRACTIONAL HORSE POWERFHP

COIL FINS PER INCH.FPI

MCA

MOCP

MINIMUM CURRENT AMPS.

MAX. OVER CURRENT PROTECTION

BELOW GRADEB.G.

AHAP AS HIGH AS POSSIBLE

OWNERS AUTHORIZED REPRESENTATIVEOAR

OWNER FURNISHED CONTRACTOR INSTALLEDOFCI

SECTION

DETAIL SYMBOL

(ALL SYMBOLS MAY NOT APPEAR ON DRAWINGS)

DRAWING SYMBOLS

NOTE BY SYMBOL

AIR DISTRIBUTION DEVICE

SUBTITLE

X

XX

XX

XX

XX

XX XX

NUMBER

DESCRIPTION

SCALE

DETAIL #

DRAWING NO. TO REFER TO

AIR QUANTITY

ARROWS INDICATE

THROW PATTERN

G-R-D

DESIGNATION

DRAWING NUMBER WHERE

SECTION IS LOCATED

SECTION NUMBER

GAS PRESSURE REDUCING VALVE

WATER PRESSURE REDUCING VALVE

ELEVATION/ RISER DIAGRAM SYMBOL

XX

XX

DRAWING NUMBER

POINTS TO ELEVATION/ RISER AREA

ELEVATION/ RISER #

(ALL DESIGNATIONS MAY NOT APPEAR ON DRAWINGS.)

PIPING DESIGNATIONS

DEMO TO THIS POINT

EXISTING CHILLED WATER SUPPLY

EXISTING CHILLED WATER RETURN

CHWS(E)

CHWR(E)

SCOPE OF WORK

THE EXISTING 18-INCH BLACK STEEL UNDERGROUND CHILLED WATER PIPING WILL BE

REPLACED WITH 18-INCH UNDERGROUND HDPE CHILLED WATER PIPING IN SAME LOCATION.

BASE PLAN INCLUDES THE PIPING BEGINNING AT THE NEW VAULT AND EXTENDING TO THE

UNDERSIDE OF THE BUILDING ENTRANCE. BLACK STEEL WILL CONNECT AT THE BUIILDING

ENTRANCE WHERE THE 18-INCH CHILLED WATER SUPPLY AND RETURN RISERS WILL HAVE

18-INCH BUTTERFLY VALVES ADDED FOR THE BUILDING ISOLATION. ALTERNATE 1 WILL

INCLUDE ADDITIONAL DISTANCE FOR THE CHILLED WATER REPLACEMENT SCOPE OF WORK.

THIS WORK INCLUDES THE UNDERGROUND PIPING FROM THE EXISTING VAULT 5 TO THE

NEW VAULT.

THE NEW VAULT WILL HOUSE TWO 18-INCH ISOLATION VALVES TO SERVE THE FUTURE

COURT HOUSE EXPANSION.

THE COURTHOUSE BUILDING WILL REQUIRE TEMPORARY COOLING FOR THE DURATION OF

THE CHILLED WATER REPLACEMENT PROJECT. THE BUILDING WILL REQUIRE STAGING

WORK FOR THE CONNECTION TO THE TEMPORARY CHILLER. WORK INCLUDES SETTING UP

CHILLED WATER PIPING CONNECTIONS FOR A TEMPORARY CHILLER. INSTALLATION OF

VALVES WILL REQUIRE CRYOGENIC FREEZING OF EXISTING CHILLED WATER LINES FOR THE

INSTALLATION OF VALVES FOR BOTH THE RISERS AND ALSO THE TEMPORARY PIPING

CONNECTIONS TO THE TEMPORARY CHILLER EXPANSION.

CONTRACTOR TO PROVIDE 500 TON AIR COOLED CHILLER WITH GENERATOR FOR

TEMPORARY SERVICE DURING CONSTRUCTION.

M0.0

LEGEND AND

GENERAL NOTES

- MECHANICAL

Project No.

221531

Sheet No.

Re vi si o ns

B

LO

O M

D A

LE

R D

M cK

IN

N

EY

, T

EX

A S

Te xa s Re g is te re d F irm N o

F

-7

W e st th S tr e e t, S u it e

Pl a no

, T X

.4

.0

Em a il:

m d e ng c a m d

-e ng

.c o m Pr o je c t N um b e r:

C C

C O

U

RT

H O

U

SE

C H

W W

A

TE

R

PI

PI

N

G

AutoCAD SHX Text 03/22/2024

AutoCAD SHX Text

CONSTRUCTION DOCUMENTS

AutoCAD SHX Text

DATE

AutoCAD SHX Text

DESCRIPTION

Sheets and Views
221531 - M0.0

File details come from the government source that posted it. Updated .