20B3012vol3.pdf
PDF 8 MB Posted
- Solicitation number
- W912HN20B3012
About this file
This document package includes specifications and drawings for a solicitation to construct a Company Operations Facility at Fort Benning, Georgia. The specifications cover requirements for demolition, hazardous materials abatement, concrete, masonry, metals, wood, thermal and moisture protection, openings, finishes, specialties, equipment, earthwork, exterior improvements, utilities, and facility monitoring and control systems. Bids are due on August 19, 2020 with an anticipated award date to follow. The solicitation is being conducted by the Department of the Army Corps of Engineers Engineering District Savannah.
View the file
Other files
Show all 17
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Fort Benning, Georgia
Solicitation Number
W912HN-20B3012
Company Operations Facility Volume 3 of 3: Specification Divisions 25 - 33, Appendices
PN 89006
July 2020
U.S. ARMY ENGINEER DISTRICT, SAVANNAH
CORPS OF ENGINEERS
100 WEST OGLETHORPE AVENUE
SAVANNAH, GEORGIA 31401-3640
US Army Corps of Engineers Savannah District
COF C20B3012
Ft. Benning, GA
PROJECT TABLE OF CONTENTS
DI VI SI ON 01 - GENERAL REQUI REMENTS
01 30 00 ADMINISTRATIVE REQUIREMENTS
01 32 01 PROJECT SCHEDULE
01 33 00 SUBMITTAL PROCEDURES
01 33 29 SUSTAINABILITY REPORTING
01 35 26 GOVERNMENTAL SAFETY REQUIREMENTS
01 42 00 SOURCES FOR REFERENCE PUBLICATIONS
01 45 00 QUALITY CONTROL
01 45 00.15 RESIDENT MANAGEMENT SYSTEM CONTRACTOR MODE (RMS CM)
01 45 35 SPECIAL INSPECTIONS
01 50 00 TEMPORARY CONSTRUCTION FACILITIES AND CONTROLS
01 57 19 TEMPORARY ENVIRONMENTAL CONTROLS
01 74 19 CONSTRUCTION WASTE MANAGEMENT AND DISPOSAL
01 78 00 CLOSEOUT SUBMITTALS
01 78 23 OPERATION AND MAINTENANCE DATA
01 91 00.15 TOTAL BUILDING COMMISSIONING
DI VI SI ON 02 - EXI STI NG CONDI TI ONS
02 41 00 DEMOLITION
02 81 00 TRANSPORTATION AND DISPOSAL OF HAZARDOUS MATERIALS
02 82 00 ASBESTOS REMEDIATION
02 83 00 LEAD REMEDIATION
02 84 16 HANDLING OF LIGHTING BALLASTS AND LAMPS CONTAINING PCBs
AND MERCURY
DI VI SI ON 03 - CONCRETE
03 30 00 CAST-IN-PLACE CONCRETE
DI VI SI ON 04 - MASONRY
04 20 00 UNIT MASONRY
DI VI SI ON 05 - METALS
05 40 00 COLD-FORMED METAL FRAMING
05 50 13 MISCELLANEOUS METAL FABRICATIONS
DI VI SI ON 06 - WOOD, PLASTI CS, AND COMPOSI TES
06 10 00 ROUGH CARPENTRY
06 61 16 SOLID SURFACING FABRICATIONS
DI VI SI ON 07 - THERMAL AND MOI STURE PROTECTI ON
07 05 23 PRESSURE TESTING AN AIR BARRIER SYSTEM FOR AIR TIGHTNESS
07 21 13 BOARD AND BLOCK INSULATION
07 21 16 MINERAL FIBER BLANKET INSULATION
07 27 10 BUILDING AIR BARRIER SYSTEM
07 27 19.01 SELF-ADHERING AIR BARRIERS
07 27 26 FLUID-APPLIED MEMBRANE AIR BARRIERS
07 41 13 METAL ROOF PANELS
07 60 00 FLASHING AND SHEET METAL
07 84 00 FIRESTOPPING
07 92 00 JOINT SEALANTS
PROJECT TABLE OF CONTENTS Page 1
DI VI SI ON 08 - OPENI NGS
08 11 13 STEEL DOORS AND FRAMES
08 14 00 WOOD DOORS
08 41 13 ALUMINUM-FRAMED ENTRANCES AND STOREFRONTS
08 51 13 ALUMINUM WINDOWS
08 71 00 DOOR HARDWARE
08 81 00 GLAZING
08 91 00 METAL WALL LOUVERS
DI VI SI ON 09 - FI NI SHES
09 06 00 SCHEDULES FOR FINISHES
09 29 00 GYPSUM BOARD
09 30 10 CERAMIC, QUARRY, AND GLASS TILING
09 51 00 ACOUSTICAL CEILINGS
09 65 00 RESILIENT FLOORING
09 68 00 CARPETING
09 90 00 PAINTS AND COATINGS
DI VI SI ON 10 - SPECI ALTI ES
10 11 00 VISUAL DISPLAY UNITS
10 14 00.10 EXTERIOR SIGNAGE
10 14 00.20 INTERIOR SIGNAGE
10 21 13 TOILET COMPARTMENTS
10 28 13 TOILET ACCESSORIES
10 44 16 FIRE EXTINGUISHER CABINETS AND WALL BRACKETS
10 51 13 METAL LOCKERS
DI VI SI ON 12 - FURNI SHI NGS
12 21 00 WINDOW BLINDS
12 32 00 MANUFACTURED WOOD CASEWORK
12 48 13 ENTRANCE FLOOR MATS AND FRAMES
12 50 00.13 FURNITURE AND FURNITURE INSTALLATION
DI VI SI ON 13 - SPECI AL CONSTRUCTI ON
13 34 19 METAL BUILDING SYSTEMS
DI VI SI ON 21 - FI RE SUPPRESSI ON
21 13 13 WET PIPE SPRINKLER SYSTEM, FIRE PROTECTION
DI VI SI ON 22 - PLUMBI NG
22 00 00 PLUMBING, GENERAL PURPOSE
DI VI SI ON 23 - HEATI NG, VENTI LATI NG, AND AI R CONDI TI ONI NG ( HVAC)
23 00 00 AIR SUPPLY, DISTRIBUTION, VENTILATION, AND EXHAUST SYSTEMS
23 05 48.19 BRACING FOR HVAC
23 05 93 TESTING, ADJUSTING, AND BALANCING FOR HVAC
23 07 00 THERMAL INSULATION FOR MECHANICAL SYSTEMS
23 09 00 INSTRUMENTATION AND CONTROL FOR HVAC
23 09 13 INSTRUMENTATION AND CONTROL DEVICES FOR HVAC
23 09 23.01 LONWORKS DIRECT DIGITAL CONTROL FOR HVAC AND OTHER
PROJECT TABLE OF CONTENTS Page 2
BUILDING CONTROL SYSTEMS
23 11 25 FACILITY GAS PIPING
23 52 00 HEATING BOILERS
23 64 26 CHILLED, CHILLED-HOT, AND CONDENSER WATER PIPING SYSTEMS
23 81 00 DECENTRALIZED UNITARY HVAC EQUIPMENT
23 81 47 WATER-LOOP AND GROUND-LOOP HEAT PUMP SYSTEMS
DI VI SI ON 25 - I NTEGRATED AUTOMATI ON
25 05 11.01 CYBERSECURITY FOR HVAC CONTROL SYSTEMS
25 05 11.02 CYBERSECURITY FOR FIRE ALARM CONTROL SYSTEMS
25 10 10 UTILITY MONITORING AND CONTROL SYSTEM (UMCS) FRONT END
AND INTEGRATION
DI VI SI ON 26 - ELECTRI CAL
26 20 00 INTERIOR DISTRIBUTION SYSTEM
26 41 00 LIGHTNING PROTECTION SYSTEM
26 51 00 INTERIOR LIGHTING
DI VI SI ON 27 - COMMUNI CATI ONS
27 10 00 BUILDING TELECOMMUNICATIONS CABLING SYSTEM
DI VI SI ON 28 - ELECTRONI C SAFETY AND SECURI TY
28 31 76 INTERIOR FIRE ALARM AND MASS NOTIFICATION SYSTEM
DI VI SI ON 31 - EARTHWORK
31 00 00 EARTHWORK
31 05 19 GEOTEXTILE
31 31 16.13 CHEMICAL TERMITE CONTROL
DI VI SI ON 32 - EXTERI OR I MPROVEMENTS
32 05 33 LANDSCAPE ESTABLISHMENT
32 11 23 AGGREGATE BASE COURSES
32 12 13 BITUMINOUS TACK AND PRIME COATS
32 12 16 HOT-MIX ASPHALT (HMA) FOR ROADS
32 16 19 CONCRETE CURBS, GUTTERS AND SIDEWALKS
32 92 19 SEEDING
DI VI SI ON 33 - UTI LI TI ES
33 11 00 WATER UTILITY DISTRIBUTION PIPING
33 30 00 SANITARY SEWERAGE
33 40 00 STORM DRAINAGE UTILITIES
33 51 15 NATURAL-GAS / LIQUEFIED PETROLEUM GAS DISTRIBUTION
PIPELINES
33 71 02 UNDERGROUND ELECTRICAL DISTRIBUTION
33 82 00 TELECOMMUNICATIONS OUTSIDE PLANT (OSP)
APPENDICES
Appendix A ASBESTOS SURVEY Appendix B HAZARDOUS BUILDING MATERIALS SURVEY
PROJECT TABLE OF CONTENTS Page 3
-- End of Project Table of Contents --
PROJECT TABLE OF CONTENTS Page 4
SECTION 25 05 11.01
CYBERSECURITY FOR HVAC CONTROL SYSTEMS
11/17
PART 1 GENERAL
Many subparts in this Section contain text in curly braces ("{" and "}") indicating which cybersecurity control and control correlation identifier (CCI) the requirements of the subpart relate to. The text inside these curly braces is for Government reference only, and enables coordination of the requirements of this Section with the RMF process throughout the design and construction process. Text in curly braces are not contractor requirements.
This Section refers to Security Requirements Guide (SRGs) and Security Technical Implementation Guide (STIGs). STIGs and SRGs are are available online at the Information Assurance Support Environment (IASE) website at http://iase.disa.mil/stigs/Pages/index.aspx . Not all control system components have applicable STIGs or SRGs.
For items not having a specific Security Technical Implementation Guide (STIG) apply generic STIGS where practical to the lowest point on the control system. These devices generally consist of building points of connections and other IP addressable devices. Primary work will be completed from Control System Level 2 and below.
Disable all uneeded ports, protocols and services to the lowest point practical.
1.1 CONTROL SYSTEM APPLICABILITY
There are multiple versions of this Section associated with this project.
Different versions have requirements applicable to different control systems. This specific Section applies only to the following control systems: HVAC (Buildinge Level Controls Only).
1.2 RELATED REQUIREMENTS
All Sections containing facility-related control systems or control system components are related to the requirements of this Section. Review all specification sections to determine related requirements.
1.3 REFERENCES
The publications listed below form a part of this specification to the extent referenced. The publications are referred to within the text by the basic designation only.
AMERICAN SOCIETY OF HEATING, REFRIGERATING AND AIR-CONDITIONING
ENGINEERS (ASHRAE)
ASHRAE 135 (2016) BACnet—A Data Communication Protocol for Building Automation and Control Networks
SECTION 25 05 11.01 Page 1
INSTITUTE OF ELECTRICAL AND ELECTRONICS ENGINEERS (IEEE)
IEEE 802.1x (2010) Local and Metropolitan Area Networks - Port Based Network Access Control
U.S. DEPARTMENT OF DEFENSE (DOD)
DODI 8551.01 (2014) Ports, Protocols, and Services Management (PPSM)
DTM 08-060 (2008) Policy on Use of Department of Defense (DoD) Information Systems - Standard Consent Banner and User Agreement
1.4 DEFINITIONS
1.4.1 Computer
As used in this Section, a computer is one of the following:
a. a device running a non-embedded desktop or server version of Microsoft Windows
b. a device running a non-embedded version of MacOS
c. a device running a non-embedded version of Linux
d. a device running a version or derivative of the Android OS, where Android is considered separate from Linux
e. a device running a version of Apple iOS
1.4.2 Network Connected
A component is network connected (or "connected to a network") only when the device has a network transceiver which is directly connected to the network and implements the network protocol. A device lacking a network transceiver (and accompanying protocol implementation) can never be considered network connected. Note that a device connected to a non-IP network is still considered network connected (an IP connection or IP address is not required for a device to be network connected).
Any device that supports wireless communication is network connected, regardless of whether the device is communicating using wireless .
1.4.3 User Account Support Levels
The support for user accounts is categorized in this Section as one of three levels:
1.4.3.1 FULLY Supported
Device supports configurable individual accounts. Accounts can be created, deleted, modified, etc. Privileges can be assigned to accounts.
1.4.3.2 MINIMALLY Supported
Device supports a small, fixed number of accounts (perhaps only one).
SECTION 25 05 11.01 Page 2
Accounts cannot be modified. A device with only a "User" and an "Administrator" account would fit this category. Similarly, a device with two PINs for logon - one for restricted and one for unrestricted rights would fit here (in other words, the accounts do not have to be the traditional "user name and password" structure).
1.4.3.3 NOT Supported
Device does not support any Access Enforcement therefore the whole concept of "account" is meaningless.
1.4.4 User Interface
Generally, a user interface is hardware on a device allowing user interaction with that device via input (buttons, switches, sliders, keyboard, touch screen, etc.) and a screen. There are three types of user interfaces defined in this Section: Limited Local User Interface, Full Local User Interface and Remote User Interface. In this Section, when the term "User Interface" is used without specifying which type, it refers only to Full Local User Interface and Remote User Interface (NOT to Limited Local User Interface).
1.4.4.1 Limited Local User Interface
A Limited Local User Interface is a user interface where the interaction is limited, fixed at the factory, and cannot be modified in the field.
The user must be physically at the device to interact with it.
Examples of Limited Local User Interface include thermostats (Space Sensor Modules as defined in Section 23 09 13 INSTRUMENTATION AND CONTROL DEVICES
FOR HVAC).
1.4.4.2 Full Local User Interface
A Full Local User Interface is a user interface where the interaction and displays are field-configurable.
Examples of a Full Local User Interface include local applications on a user interfaces to Variable Speed Drives .
1.4.4.3 Remote User Interface
A Remote User Interface is a user interface on a Client device allowing user interaction with a different Server device. The user need not be physically at the Server device to interact with it.
Examples of Remote User Interfaces include web browsers and Local Display Panels as defined in Section 23 09 00 INSTRUMENTATION AND CONTROL FOR HVAC.
1.5 ADMINISTRATIVE REQUIREMENTS
1.5.1 Coordination
Coordinate the execution of this Section with the execution of all other Sections related to control systems as indicated in the paragraph RELATED REQUIREMENTS. Items that must be considered when coordinating project efforts include but are not limited to:
a. If requesting permission for wireless communication, the Wireless
SECTION 25 05 11.01 Page 3
Communication Request submittal must be approved prior to control system device selection and integration.
b. If requesting permission for alternate account lock permissions, the Device Account Lock Exception Request must be approved prior to control system device selection and integration.
c. If requesting permission for the use of a device with multiple IP connections, the Multiple IP Connection Device Request must be approved prior to control system device selection and integration.
d. Wireless testing may be required as part of the control system testing. See requirements for the Wireless Communication Test Report submittal.
e. If the Device Audit Record Upload Software is to be installed on a computer not being provided as part of the control system, coordination is required to identify the computer on which to install the software.
f. Cybersecurity Interconnection Schedule must be coordinated with other work that will be interconnected to, and interconnections must be approved by the Government before relying on them for system functionality.
g. Cybersecurity testing support must be coordinated across control systems and with the Government cybersecurity testing schedule.
h. Passwords must be coordinated with the indicated contact for the project site.
i. If applicable, HTTP web server certificates must be obtained from the indicated contact for the project site.
j. Contractor Computer Cybersecurity Compliance Statements for each contractor using contractor owned computers.
1.6 SUBMITTALS
Government approval is required for submittals with a "G" designation;
submittals not having a "G" designation are for Contractor Quality Control approval. When used, a designation following the "G" designation identifies the office that will review the submittal for the Government.
Submittals with an "S" are for inclusion in the Sustainability eNotebook, in conformance with Section 01 33 29 SUSTAINABILITY REPORTING. Submit the following in accordance with Section 01 33 00 SUBMITTAL PROCEDURES:
SD-01 Preconstruction Submittals
Contractor Computer Cybersecurity Compliance Statements ; G
Contractor Temporary Network Cybersecurity Compliance Statements ; G
SD-02 Shop Drawings
Network Communication Report ; G
Cybersecurity Riser Diagram ; G
SECTION 25 05 11.01 Page 4
Control System Inventory Report ; G
SD-03 Product Data
Control System Cybersecurity Documentation ; G
SD-07 Certificates
Software Licenses ; G
SD-11 Closeout Submittals
Password Summary Report ; G
Software Recovery And Reconstitution Images ; G
1.7 QUALITY CONTROL
1.7.1 Control System Cybersecurity Subject Matter Expert
The individual will oversee all work within this specification. This position requires that the individual currently meets Information Assurance Manager Level II Certification in accordance with DoDI 8570 Information Workforce Improvement Program.
Individuals for this position should have experience securing DoD systems and with Risk Management Framework. Control System Experience is highly desirable.
Resumes should be submitted to the Government within 14 days after notice to proceed. All certifications must be in effect prior to beginning work.
This position may serve across the contract for all control systems. There is no requirement to have one Cybersecurity SME per platform.
1.8 CYBERSECURITY DOCUMENTATION
1.8.1 Network Communication Report
{For Reference Only: This subpart (and its subparts) relates to CA-9;
CCI-002102, CCI-002103, CCI-002104, CCI-002105 and also the submittal requirements associated with CM-6, CM-7 and SC-41 }
Provide a network communication report. For each networked controller, document the communication characteristics of the controller including communication protocols, services used, and a general description of what information is communicated over the network. For each controller using IP, document all TCP and UDP ports used. If other control system Sections used on this project include submittals documenting this information, provide copies of those submittals to meet this requirement.
In addition to the requirements of Section 01 33 00 SUBMITTAL PROCEDURES, provide the Network Communication Report as an editable Microsoft Excel file.
1.8.2 Control System Inventory Report
{For Reference Only: This subpart (and its subparts) relates to CM-8(a), SECTION 25 05 11.01 Page 5
CP-12, SI-17, IA-3; CCI-000389, CCI-000392, CCI-000398, CCI-002855,
CCI-002856, CCI-002857, CCI-002773, CCI-002774, CCI-002775, CCI-000777,
CCI-000778, CCI-001958}
Provide a Control System Inventory report using the Inventory Spreadsheet listed under this Section at http://www.wbdg.org/FFC/NAVGRAPH/graphtoc.pdf documenting all devices, including networked devices, network infrastructure devices, non-networked devices, input devices (e.g.
sensors) and output devices (e.g. actuators). For each device provide all applicable information for which there is a field on the spreadsheet in accordance with the instructions on the spreadsheet.
In addition to the requirements of Section 01 33 00 SUBMITTAL PROCEDURES, provide the Control System Inventory Report as an editable Microsoft Excel file.
1.8.3 Software Recovery and Reconstitution Images
{For Reference Only: This subpart (and its subparts) relates to CP-10;
CCI-000550, CCI-000551, CCI-000552}
For each control system device on which software is installed under this project, provide a recovery image of the final as-built control device .
This image must allow for bare-metal restore such that restoration of the image is sufficient to restore system operation to the imaged state without the need for re-installation of software.
If additional user permissions are required to meet this requirement, coordinate the creation of the image with the Government.
1.8.4 Cybersecurity Riser Diagram
{For Reference Only: This subpart (and its subparts) relates to PL-2(a);
CCI-003051, CCI-003053}
Provide a cybersecurity riser diagram of the complete control system including all network and controller hardware. If the control system specifications require a riser diagram submittal, provide a copy of that submittal as the cybersecurity riser diagram. Otherwise, provide a riser diagram in one-line format overlayed on a facilityschematic. Drawing to be submitted in digital format.
1.8.5 Control System Cybersecurity Documentation
This subpart (and its subparts) relates to SA-5 (a),(b),(c); CCIs:
CCI-003124, CCI-003125, CCI-003126, CCI-003127, CCI-003128, CCI-003129,
CCI-003130, CCI-003131}
Provide a Control System Cybersecurity Documentation submittal containing the indicated information for each device and software application.
1.8.5.1 For HVAC Control System Devices
1.8.5.1.1 HVAC Control System Devices FULLY Supporting User Accounts
For all HVAC Control System Devices which FULLY support user accounts, provide:
a. Documentation that describes secure configuration of the device {for
SECTION 25 05 11.01 Page 6 reference only: relates to CCI-003124}
b. Documentation that describes secure operation of the device {for reference only: relates to CCI-003124}
c. Documentation that describes effective use and maintenance of security functions or mechanisms for the device {for reference only: relates to
CCI-003127}
d. Documentation that describes known vulnerabilities regarding configuration and use of administrative (i.e. privileged) functions for the device {for reference only: relates to CCI-003128}
e. Documentation that describes user-accessible security functions or mechanisms in the device and how to effectively use those security functions or mechanisms; or a specific indication that there are no user-accessible security functions or mechanisms in the device {for reference only: relates to CCI-003129}
f. Documentation that describes methods for user interaction which enables individuals to use the device in a more secure manner {for reference only: relates to CCI-003130}
1.8.5.1.2 All Other HVAC Control System Devices
For all HVAC Control System Devices which do not FULLY support user accounts, provide:
a. Documentation that describes secure configuration of the device; or a specific indication that there are no secure configuration steps that apply {for reference only: relates to CCI-003124}
b. Documentation that describes effective use and maintenance of security functions or mechanisms for the device; or a specific indication that there are no security functions or mechanisms in the device {for reference only: relates to CCI-003127}
c. For devices which include a user interface, documentation that describes methods for user interaction which enables individuals to use the device in a more secure manner {for reference only: relates to
CCI-003130}
1.9 SOFTWARE UPDATE LICENSING
{For Reference Only: This subpart (and its subparts) relates to SI-2 (a),(c); CCI-001227, CCI-002605}
In addition to all other licensing requirements, all software licensing must include licensing of the following software updates for a period of no less than 5 years:
a. Security and bug-fix patches issued by the software manufacturer.
b. Security patches to address any vulnerability identified in the National Vulnerability Database at http://nvd.nist.gov with a Common Vulnerability Scoring System (CVSS) severity rating of MEDIUM or higher.
Provide a single Software Licenses submittal with documentation of the
SECTION 25 05 11.01 Page 7 software licenses for all software provided
1.10 CYBERSECURITY DURING CONSTRUCTION
{For Reference Only: This subpart (and its subparts) relates to AC-18, SA-3, CCI-00258}
In addition to the control system cybersecurity requirements indicated in this section, meet following requirement throughout the construction process.
1.10.1 Contractor Computer Equipment
Contractor owned computers may be used for construction. When used, contractor computers must meet the following requirements:
1.10.1.1 Operating System
The operating system must be an operating system currently supported by the manufacturer of the operating system. The operating system must be current on security patches and operating system manufacturer required updates.
1.10.1.2 Anti-Malware Software
The computer must run anti-malware software from a reputable software manufacturer. Anti-malware software must be a version currently supported by the software manufacturer, must be current on all patches and updates, and must use the latest definitions file. All computers used on this project must be scanned using the installed software at least once per day.
1.10.1.3 Passwords and Passphrases
The passwords and passphrases for all computers must be changed from their default values. Passwords must be a minimum of eight characters with a minimum of one uppercase letter, one lowercase letter, one number and one special character.
1.10.1.4 Contractor Computer Cybersecurity Compliance Statements
Provide a single submittal containing completed Contractor Computer Cybersecurity Compliance Statements for each company using contractor owned computers. Contractor Computer Cybersecurity Compliance Statements must use the template published at http://www.wbdg.org/FFC/NAVGRAPH/graphtoc.pdf . Each Statement must be signed by a cybersecurity representative for the relevant company.
1.10.2 Temporary IP Networks
Temporary contractor-installed IP networks may be used during construction. When used, temporary contractor-installed IP networks must meet the following requirements:
1.10.2.1 Network Boundaries and Connections
The network must not extend outside the project site and must not connect to any IP network other than IP networks provided under this project or Government furnished IP networks provided for this purpose. Any and all network access from outside the project site is prohibited.
SECTION 25 05 11.01 Page 8
1.10.3 Government Access to Network
Government personnel must be allowed to have complete and immediate access to the network at any time in order to verify compliance with this specification
1.10.4 Temporary Wireless IP Networks
In addition to the other requirements on temporary IP networks, temporary wireless IP (WiFi) networks must not interfere with existing wireless network and must use WPA2 security. Network names (SSID) for wireless networks must be changed from their default values.
1.10.5 Passwords and Passphrases
The passwords and passphrases for all network devices and network access must be changed from their default values. Passwords must be a minimum 8 characters with a minimum of one uppercase letter, one lowercase letter, one number and one special character.
1.10.6 Contractor Temporary Network Cybersecurity Compliance Statements
Provide a single submittal containing completed Contractor Temporary Network Cybersecurity Compliance Statements for each company implementing a temporary IP network. Contractor Temporary Network Cybersecurity Compliance Statements must use the template published at http://www.wbdg.org/FFC/NAVGRAPH/graphtoc.pdf . Each Statement must be signed by a cybersecurity representative for the relevant company. If no temporary IP networks will be used, provide a single copy of the Statement indicating this.
1.11 CYBERSECURITY DURING WARRANTY PERIOD
All work performed on the control system after acceptance must be performed using Government Furnished Equipment or equipment specifically and individually approved by the Government.
PART 2 PRODUCTS
(NOT USED)
PART 3 EXECUTION
3.1 ACCESS CONTROL REQUIREMENTS
3.1.1 User Accounts
{For Reference Only: This subpart (and its subparts) relate to AC-2(a)and
AC-3; CCI-002110, CCI-000213.}
Any device supporting user accounts (either FULLY or MINIMALLY) must limit access to the device according to specified limitations for each account.
Install and configure any device having a STIG or SRG in accordance with that STIG or SRG.
3.1.1.1 For HVAC Control System Devices
Devices with web interfaces must either FULLY support user accounts or
SECTION 25 05 11.01 Page 9 have their web interface disabled. Field devices with full local user interfaces allowing modification of data must at least MINIMALLY support user accounts.
3.1.2 Unsuccessful Logon Attempts
{For Reference Only: This subpart (and its subparts) relate AC-7 (a), AC-7 (b); CCI-000043, CCI-000044, CCI-001423, CCI-002236, CCI-002237, CCI-002238}
Except for high availability user interfaces indicated as exempt, devices must meet the indicated requirements for handling unsuccessful logon attempts.
3.1.2.1 Devices MINIMALLY Supporting Accounts
Devices which MINIMALLY support accounts must lock the user input when _3 unsuccessful attempts within 15 minutes and must support unlocking of the user input when an administrator unlocks the account or thirty minutes passes.
3.1.2.2 Devices FULLY Supporting Accounts
Devices which FULLY support accounts must meet the following requirements. If a device cannot meet these requirements, document device capabilities to protect from subsequent unsuccessful logon attempts and propose alternate protections in a Device Account Lock Exception Request submittal. Do not implement alternate protection measures without explicit permission from the Government.
a. It must lock the user account when three unsuccessful logon attempts occur within a 15 minuteinterval.
b. Once an account is locked, the account must stay locked until unlocked by an administrator.
c. Once the indicated number of unsuccessful logon attempts occurs, delay further logon prompts by 5 seconds.
3.1.2.3 High Availability Interfaces Exempt from Unsuccessful Logon Attempts Requirements
There are no high availability interfaces which are exempt from unsuccessful logon attempts requirements.
3.1.3 System Use Notification
{For Reference Only: This subpart (and its subparts) relates to AC-8;
CCI-000048, CCI-002247, CCI-002243, CCI-002244, CCI-002245, CCI-002246,
CCI-000050, CCI-002248}
Web interfaces must display a warning banner meeting the requirements of
DTM 08-060 .
Devices which are connected to a network and have a user interface must display a warning banner meeting the requirements of DTM 08-060 if capable of doing so. Devices which are connected to a network and have a user interface but are not capable of displaying a banner must have a permanently affixed label displaying an approved banner from DTM 08-060 .Labels
SECTION 25 05 11.01 Page 10 must be machine printed or engraved, plastic or metal, designed for permanent installation, must use a font no smaller than 14 point, and must provide a high contract between font and background colors.
3.1.4 Permitted Actions Without Identification or Authentication
{For Reference Only: This subpart (and its subparts) relates to AC-14;
CCI-000061, CCI-000232}
The control system must require identification and authentication before allowing any actions by a user acting from a user interface which MINIMALLY or FULLY supports accounts.
3.1.5 Wireless Access
{For Reference Only: This subpart (and its subparts) relates to AC-18;
CCI-001438, CCI-001439, CCI-002323, CCI-001441}
Unless explicitly authorized by the Government, do not use any wireless communication. Any device with wireless communication capability is considered to be using wireless communication, regardless of whether or not the device is actively communicating wirelessly, except when wireless communication has been physically permanently disabled (such as through the removal of the wireless transceiver).
3.1.5.1 Wireless IP Communications
Do not install wireless IP networks, including: do not install a wireless access point; do not install or configure an ad-hoc wireless network; do not install or configure a WiFi Direct communication.
When explicitly authorized by the Government, wireless IP communication may be used to communicate with an existing wireless network.
3.2 CYBERSECURITY AUDITING
3.2.1 Audit Events, Content of Audit Records, and Audit Generation
{For Reference Only: This subpart (and its subparts) relates to AU-2(a),(c),(d), AU-3, AU-12; CCI-000123, CCI-001571, CCI-000125, CCI-001485, CCI-000130, CCI-000131, CCI-000132, CCI-00133, CCI-000134, CCI-001487, CCI-000169, CCI-001459, CCI-000171, CCI-000172, CCI-001910}
For devices that have STIG/SRGs related to audit events, content of audit records or audit generation, comply with the requirements of those STIG/SRGs.
3.2.1.1 For HVAC Control System Devices
3.2.1.1.1 HVAC Control System Devices FULLY Supporting User Accounts
For devices FULLY supporting accounts, provide the capability to select audited events, and the contents of audit logs. Configure devices to audit the following events:
a. Successful and unsuccessful logon attempts to the device
b. Starting and ending time for user access to the device
SECTION 25 05 11.01 Page 11
c. All account creations, modifications, disabling, and terminations
d. All device shutdown and startup
Configure the device to record for each event the following information (as applicable): the type of event, when the event occurred and the identity of any individuals or subjects associated with the event
3.2.1.1.2 Other HVAC Control System Devices
There are no requirements to perform auditing at HVAC field devices that do not FULLY support accounts. 3.2.2 Time Stamps
{For Reference Only: This subpart (and its subparts) relates to AU-8;
CCI-000159, CCI-001889, CCI-001890}
3.2.2.1 For HVAC Control System Devices
Time stamp requirements for HVAC Control Systems are as indicated in the HVAC Control System specifications. Devices generating audit records must have internal clocks capable of providing time with a resolution of 1 second. Clocks cannot drift more than 10 seconds per day. Configure the system so that each device generating audit records maintains accurate time to within 1 second.
3.3 REQUIREMENTS FOR LEAST FUNCTIONALITY
{For Reference Only: This subpart (and its subparts), along with the network communication report submittal specified elsewhere in this section, relates to CM-6 (a), (c), CM-7, CM-7 (1)(b), SC-41; CCI-000363, CCI-000364, CCI-000365, CCI-001588, CCI-001755, CCI-000381, CCI-000380, CCI-00382, CCI-001761, CCI-001762, CCI-002544, CCI-002545, CCI-002546.}
For devices that have a STIG or SRG related to Requirements for Least Functionality (such as configuration settings and port and device I/O access for least functionality), install and configure the device in accordance with that STIG or SRGs.
For HVAC Control Systems: Do not provide devices with user interfaces where one was not required. Do not use a networked sensor or actuator where a non-networked sensor or actuator would suffice.
3.3.1 Non-IP Control Networks
When control system specifications require particular communication protocols, use only those communication protocols and only as specified.
Do not implement any other communication protocol, or use any protocol on ports other than those specified.
When control system specifications do not indicate requirements for communication protocols, use only those protocols required for operation of the system as specified.
3.3.2 IP Control Networks
Do not use nonsecure functions, ports, protocols and services as defined in DODI 8551.01 unless those ports, protocols and services are specifically required by the control system specifications or otherwise specifically authorized by the Government. Do not use ports, protocols
SECTION 25 05 11.01 Page 12 and services that are not specified in the control system specifications or required for operation of the control system.
3.4 SAFE MODE AND FAIL SAFE OPERATION
{For Reference Only: This subpart (and its subparts) relates to CP-12, SI-17; CCI-002855, CCI-002856, CCI-002857, CCI-002773, CCI-002774, CCI-002775}
For all control system components with an applicable STIG or SRG, configure the component in accordance with all applicable STIGs and SRGs.
3.5 IDENTIFICATION AND AUTHENTICATION
3.5.1 User Identification and Authentication
{For Reference Only: This subpart (and its subparts) relates to
IA-2,(1),(12); CCI-000764, CCI-000765, CCI-001953, CCI-001954}
a. Devices that FULLY support accounts must uniquely identify and authenticate organizational users.
b. Devices which allow network access to privileged accounts must implement multifactor authentication for network access to privileged accounts.
3.5.1.1 HVAC Control Systems Devices
Identification and Authentication for network access to privileged accounts must be implemented by either accepting and electronically verify Personal Identity Verification (PIV) credentials or inheriting identification and authentication from the operating system.
3.5.2 Authenticator Management
{For Reference Only: This subpart (and its subparts) relates to IA-5 (b),(c),(e),(g),(1),(11); CCI-000176, CCI-001544, CCI-001989, CCI-000182, CCI-001610, CCI-000192, CCI-000193, CCI-000194, CCI-000205, CCI-001619, CCI-001611, CCI-001612, CCI-001613, CCI-001614, CCI-000195, CCI-001615, CCI-000196, CCI-000197, CCI-000199, CCI-000198, CCI-001616, CCI-001617, CCI-000200, CCI-001618, CCI-002041, CCI-002002, CCI-002003}
3.5.2.1 Authentication Type
3.5.2.1.1 For HVAC Control System Devices
Unless otherwise indicated:
a. Other devices which FULLY support accounts must use password-based authentication.
b. Devices MINIMALLY supporting accounts must use password-based authentication.
3.5.2.1.2 Password Configuration and Reporting
For all devices with a password, change the password from the default password. Coordinate selection of passwords with the Installation. Do not use the same password for more than one device unless specifically
SECTION 25 05 11.01 Page 13 instructed to do so. Provide a Password Summary Report documenting the password for each device and describing the procedure to change the password for each device.
Do not provide the Password Summary Report in electronic format. Provide two hardcopies of the Password Summary Report, each copy in its own sealed envelope.
3.5.2.2 Hardware Token-Based Authentication Requirements
Devices supporting hardware token-based authentication must use Personal Identity Verification (PIV) credentials for the hardware token.
3.5.3 Authenticator Feedback
{For Reference Only: This subpart relates to IA-6; CCI-000206}
Devices must never show authentication information, including passwords, on a display. Devices that momentarily display a character as it is entered, and then obscure the character, are acceptable. For devices that have STIGs or SRGs related to obscuring of authenticator feedback (CCI-000206), comply with the requirements of those STIGS/SRGs.
3.5.4 Device Identification and Authentication
{For Reference Only: This subpart (and its subparts) relates to IA-3;
CCI-000777, CCI-000778, CCI-001958}
3.5.4.1 For HVAC Control System Devices
Devices using Fox Protocol must use HTTPS using a web server certificate obtained from a Government Trust Agent or approved source. Devices using Ethernet must support IEEE 802.1x . Devices using BACnet must support Network Security as specified in Clause 24 of ASHRAE 1353.5.5
Cryptographic Module Authentication
{For Reference Only: This subpart (and its subparts) relates to IA-7;
CCI-000803}
For devices that have STIG/SRGs related to cryptographic module authentication (CCI-000803), comply with the requirements of those STIG/SRGs.
3.6 DURABILITY TO VULNERABILITY SCANNING
{For Reference Only: This subpart (and its subparts) relates to RA-5 (a),(b),(c),(d); CCI-001054, CCI-001055, CCI-0010156, CCI-001641, CCI-001643, CCI-001057, CCI-001058, CCI-001059}
All IP devices must be scannable, such that the device can be scanned by industry standard IP network scanning utilities without harm to the device, application, or functionality.
3.6.1 HVAC Control System Devices Other Than Computers
HVAC control system devices other than computers are not required to respond to scans.
SECTION 25 05 11.01 Page 14
3.7 DEVICES WITH CONNECTION TO MULTIPLE IP NETWORKS
Except for Ethernet switches, do not use more than one physical connection to IP networks on the same device unless doing so is both required by the project specifications and the specific application is approved. If a device with multiple IP connections is required, provide a Multiple IP Connection Device Request using the Multiple IP Connection Device Request Schedule at http://www.wbdg.org/FFC/NAVGRAPH/graphtoc.pdf to request approval for each device.
3.8 SYSTEM AND COMMUNICATION PROTECTION
3.8.1 Denial of Service Protection, Process Isolation and Boundary Protection
{For Reference Only: This subpart (and its subparts) relates to SC-5, SC-39, SC-7(a); CCI-001093, CCI-002385, CCI-002386, CCI-002430, CCI-001097}
To the greatest extent practical, implement control logic in non-computer hardware and without reliance on the network.
3.8.2 Cryptographic Protection
{For Reference Only: This subpart (and its subparts) relates to SC-13;
CCIs: CCI-002449, CCI-002450}
For devices that have STIG/SRGs related to cryptographic protection (CCI-002450), comply with the requirements of those STIG/SRGs. Ensure that allnetwork traffic is encrypted using NSA-approved cryptography;
provision of digital signatures and hashing, and FIPS-validated cryptography.
3.9 FIELD QUALITY CONTROL
3.9.1 Tests
In addition to testing and testing support required by other Sections, provide a minimum of 24 hours of technical support for cybersecurity testing of control systems.
-- End of Section --
SECTION 25 05 11.01 Page 15
SECTION 25 05 11.02
CYBERSECURITY FOR FIRE ALARM CONTROL SYSTEMS
11/17
PART 1 GENERAL
Many subparts in this Section contain text in curly braces ("{" and "}") indicating which cybersecurity control and control correlation identifier (CCI) the requirements of the subpart relate to. The text inside these curly braces is for Government reference only, and enables coordination of the requirements of this Section with the RMF process throughout the design and construction process. Text in curly braces are not contractor requirements.
This Section refers to Security Requirements Guide (SRGs) and Security Technical Implementation Guide (STIGs). STIGs and SRGs are are available online at the Information Assurance Support Environment (IASE) website at http://iase.disa.mil/stigs/Pages/index.aspx . Not all control system components have applicable STIGs or SRGs.
1.1 CONTROL SYSTEM APPLICABILITY
There are multiple versions of this Section associated with this project.
Different versions have requirements applicable to different control systems. This specific Section applies only to the following control systems: Fire Reporting/Mass Notification (Building Level Controls Only).
The components invovled are for the Fire Reporting System. There is no Operational or Traditional IT involved in this project. The installer should apply cybersecurity to the lowest point practical on the control system. Primary work will be conducted at Control System Levels 0 thru 1.
1.2 RELATED REQUIREMENTS
All Sections containing facility-related control systems or control system components are related to the requirements of this Section. Review all specification sections to determine related requirements.
1.3 REFERENCES
The publications listed below form a part of this specification to the extent referenced. The publications are referred to within the text by the basic designation only.
INSTITUTE OF ELECTRICAL AND ELECTRONICS ENGINEERS (IEEE)
IEEE 802.1x (2010) Local and Metropolitan Area Networks - Port Based Network Access Control
U.S. DEPARTMENT OF DEFENSE (DOD)
DODI 8551.01 (2014) Ports, Protocols, and Services Management (PPSM)
DTM 08-060 (2008) Policy on Use of Department of Defense (DoD) Information Systems - Standard Consent Banner and User Agreement
SECTION 25 05 11.02 Page 1
1.4 DEFINITIONS
1.4.1 Computer
As used in this Section, a computer is one of the following:
a. a device running a non-embedded desktop or server version of Microsoft Windows
b. a device running a non-embedded version of MacOS
c. a device running a non-embedded version of Linux
d. a device running a version or derivative of the Android OS, where Android is considered separate from Linux
e. a device running a version of Apple iOS
1.4.2 Network Connected
A component is network connected (or "connected to a network") only when the device has a network transceiver which is directly connected to the network and implements the network protocol. A device lacking a network transceiver (and accompanying protocol implementation) can never be considered network connected. Note that a device connected to a non-IP network is still considered network connected (an IP connection or IP address is not required for a device to be network connected).
Any device that supports wireless communication is network connected, regardless of whether the device is communicating using wireless .
1.4.3 User Account Support Levels
The support for user accounts is categorized in this Section as one of three levels:
1.4.3.1 FULLY Supported
Device supports configurable individual accounts. Accounts can be created, deleted, modified, etc. Privileges can be assigned to accounts.
1.4.3.2 MINIMALLY Supported
Device supports a small, fixed number of accounts (perhaps only one).
Accounts cannot be modified. A device with only a "User" and an "Administrator" account would fit this category. Similarly, a device with two PINs for logon - one for restricted and one for unrestricted rights would fit here (in other words, the accounts do not have to be the traditional "user name and password" structure).
1.4.3.3 NOT Supported
Device does not support any Access Enforcement therefore the whole concept of "account" is meaningless.
1.4.4 User Interface
Generally, a user interface is hardware on a device allowing user
SECTION 25 05 11.02 Page 2 interaction with that device via input (buttons, switches, sliders, keyboard, touch screen, etc.) and a screen. There are three types of user interfaces defined in this Section: Limited Local User Interface, Full Local User Interface and Remote User Interface. In this Section, when the term "User Interface" is used without specifying which type, it refers only to Full Local User Interface and Remote User Interface (NOT to Limited Local User Interface).
1.4.4.1 Limited Local User Interface
A Limited Local User Interface is a user interface where the interaction is limited, fixed at the factory, and cannot be modified in the field.
The user must be physically at the device to interact with it.
Examples of Limited Local User Interface include thermostats .
1.4.4.2 Full Local User Interface
A Full Local User Interface is a user interface where the interaction and displays are field-configurable.
Examples of a Full Local User Interface include local applications on a computer .
1.4.4.3 Remote User Interface
A Remote User Interface is a user interface on a Client device allowing user interaction with a different Server device. The user need not be physically at the Server device to interact with it.
Examples of Remote User Interfaces include web browsers.
1.5 ADMINISTRATIVE REQUIREMENTS
1.5.1 Coordination
Coordinate the execution of this Section with the execution of all other Sections related to control systems as indicated in the paragraph RELATED REQUIREMENTS. Items that must be considered when coordinating project efforts include but are not limited to:
a. If requesting permission for wireless communication, the Wireless Communication Request submittal must be approved prior to control system device selection and integration.
b. If requesting permission for alternate account lock permissions, the Device Account Lock Exception Request must be approved prior to control system device selection and integration.
c. If requesting permission for the use of a device with multiple IP connections, the Multiple IP Connection Device Request must be approved prior to control system device selection and integration.
d. Wireless testing may be required as part of the control system testing. See requirements for the Wireless Communication Test Report submittal.
e. If the Device Audit Record Upload Software is to be installed on a computer not being provided as part of the control system, SECTION 25 05 11.02 Page 3 coordination is required to identify the computer on which to install the software.
f. Cybersecurity Interconnection Schedule must be coordinated with other work that will be interconnected to, and interconnections must be approved by the Government before relying on them for system functionality.
g. Cybersecurity testing support must be coordinated across control systems and with the Government cybersecurity testing schedule.
h. Passwords must be coordinated with the indicated contact for the project site.
i. If applicable, HTTP web server certificates must be obtained from the indicated contact for the project site.
j. Contractor Computer Cybersecurity Compliance Statements for each contractor using contractor owned computers.
1.6 SUBMITTALS
Government approval is required for submittals with a "G" designation;
submittals not having a "G" designation are for information only. When used, a designation following the "G" designation identifies the office that will review the submittal for the Government. Submittals with an "S" are for inclusion in the Sustainability eNotebook, in conformance with Section 01 33 29 SUSTAINABILITY REPORTING. Submit the following in accordance with Section 01 33 00 SUBMITTAL PROCEDURES:
SD-01 Preconstruction Submittals
Wireless Communication Request ; G
Device Account Lock Exception Request ; G
Contractor Computer Cybersecurity Compliance Statements ; G
Contractor Temporary Network Cybersecurity Compliance Statements ; G
SD-02 Shop Drawings
User Interface Banner Schedule ; G
Network Communication Report ; G
Cybersecurity Riser Diagram ; G
Control System Inventory Report ; G
SD-03 Product Data
Control System Cybersecurity Documentation ; G
SD-06 Test Reports
Wireless Communication Test Report ; G
SECTION 25 05 11.02 Page 4
SD-07 Certificates
Software Licenses ; G
SD-11 Closeout Submittals
Password Summary Report ; G
Software Recovery And Reconstitution Images ; G
Device Audit Record Upload Software ; G
1.7 QUALITY CONTROL
1.7.1 Control System Cybersecurity Subject Matter Expert
The individual will oversee all work within this specification. This position requires that the individual currently meet Information Assurance Manager Level II Certification requirements in accordance with DoDI 8570 Information Workforce Improvement Program.
Individuals for this poistion should have experience securing DoD systems and with Risk Management Framework. Control System experience is highly desirable.
Resumes should be submitted to the Government within 14 days after notice to proceed. All certifications must be in effect prior to beginning work.
This position may serve across the contract for all control systems. There is no requirement to have one Cybersecurity SME per platform.
1.8 CYBERSECURITY DOCUMENTATION
1.8.1 Network Communication Report
{For Reference Only: This subpart (and its subparts) relates to CA-9;
CCI-002102, CCI-002103, CCI-002104, CCI-002105 and also the submittal requirements associated with CM-6, CM-7 and SC-41 }
Provide a network communication report. For each networked controller, document the communication characteristics of the controller including communication protocols, services used, and a general description of what information is communicated over the network. For each controller using IP, document all TCP and UDP ports used. If other control system Sections used on this project include submittals documenting this information, provide copies of those submittals to meet this requirement.
In addition to the requirements of Section 01 33 00 SUBMITTAL PROCEDURES, provide the Network Communication Report as an editable Microsoft Excel file.
1.8.2 Control System Inventory Report
{For Reference Only: This subpart (and its subparts) relates to CM-8(a), CP-12, SI-17, IA-3; CCI-000389, CCI-000392, CCI-000398, CCI-002855, SECTION 25 05 11.02 Page 5
CCI-002856, CCI-002857, CCI-002773, CCI-002774, CCI-002775, CCI-000777,
CCI-000778, CCI-001958}
Provide a Control System Inventory report using the Inventory Spreadsheet listed under this Section at http://www.wbdg.org/ffc/dod/unified-facilities-guide-specifications-ufgs/forms-graphics-tables documenting all devices, including networked devices, network infrastructure devices, non-networked devices, input devices (e.g.
sensors) and output devices (e.g. actuators). For each device provide all applicable information for which there is a field on the spreadsheet in accordance with the instructions on the spreadsheet.
In addition to the requirements of Section 01 33 00 SUBMITTAL PROCEDURES, provide the Control System Inventory Report as an editable Microsoft Excel file.
1.8.3 Software Recovery and Reconstitution Images
{For Reference…
This is the start of the file's text. The full file is on GovTribe.
File details come from the government source that posted it. Updated .