20260811_Revision_3_Asset_Protection_Volume_1_Approved.pdf
PDF 7 MB Posted
- Attached to
- Asset Protection - Painting and Coating
- Solicitation number
- 630-0923-27
- Issued by
- Trinity County, California
About this file
This is a design and engineering document set for the Downtown Fairfield Justice Campus Asset Protection Project, a multi-phase stormwater protection initiative developed for Solano County, California, in coordination with the City of Fairfield and Fairfield-Suisun Sewer District. The project encompasses flood protection measures for county properties located at multiple addresses along Union Avenue, Clay Street, Delaware Street, and Texas Street in Fairfield, including the installation of barrier walls, berms, landscaping, hardscape improvements, flood gates, underground utility reconfiguration, and pump systems designed to mitigate seasonal flooding damage. The design documents, prepared by Mead & Hunt, Inc., represent Revision 3 as of August 11, 2026, and include comprehensive civil, structural, mechanical, electrical, and landscaping drawings organized in multiple volumes. Volume 1 focuses on Asset Protection and consists of general notes, site plans, storm protection alignment details, structural specifications for walls and ramps, mechanical systems for pump stations and storm drainage vaults, and electrical systems including motor control centers, lift station controls, and power distribution. The project involves significant infrastructure work including three new 5,400 GPM submersible pump installations, precast sump pump vaults, HDPE discharge piping systems, flap gates, and associated electrical controls integrated with a county-operated building management system via BACnet communication protocols.
The design specifications mandate compliance with current California Building, Electrical, Mechanical, and Plumbing Codes, with additional structural and electrical requirements detailed on designated drawing sheets. The contractor assumes full responsibility for construction staking, record drawings, survey monument protection, excavation support and shoring in accordance with Cal/OSHA requirements, utility coordination, dewatering planning, traffic control, and erosion and sediment control measures per an approved Storm Water Pollution Prevention Plan. The project requires coordination with multiple utility providers including sanitary sewer system improvements being conducted separately by KSN, with assumptions that privatization of on-site sewer infrastructure will be completed prior to this project's construction. Electrical work encompasses the installation of a new Motor Control Center with 800-amp capacity, automated transfer switches for standby generator integration, soft starters for pump motors, and comprehensive control systems with multiple terminal junction boxes. All materials and workmanship must conform to the technical provisions and construction specifications provided in book form, with the contractor bearing responsibility for maintaining compliance with all federal, state, and local laws, obtaining required permits, and protecting existing facilities and adjacent properties throughout the construction period.
View the file
Other files
Show all 19
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
G-002
GENERAL NOTES AND
SHEET INDEX
SRS
MWR
JOH
X:
\1
\1
4.
\T
EC
H \C
AD
\P
H
AS
E 3\
G -0
L
EG
EN
D S.
D W
G
8/
/2
5:
:3
PM
1943400-190824.01
SEPTEMBER 29, 2026
SHEET CONTENTS
DO NOT SCALE DRAWINGS
M&H NO.:
DATE:
DESIGNED BY:
DRAWN BY:
CHECKED BY:
ISSUED
These documents shall not be used for any purpose or project for which it is not intended. Mead & Hunt shall be indemnified by the client and held harmless and defended from all claims, damages, liabilities, losses, and expenses, including attorneys' fees and costs, arising out of such misuse or reuse of the documents.
In addition, unauthorized reproduction of these documents, in part or as a whole, is prohibited.
Mead and Hunt, Inc.
180 Promenade Circle, Suite 240 Sacramento, CA 95834 phone: 916-971-3961 meadhunt.com
TE
XA
S
ST
R
EE
T
FA
IR
FI
EL
D
, C A
SO
LA
N O
C O
U N
TY
D
O W
N
TO
W N
F
AI
R
FI
EL
D
J U
ST
IC
E C
AM
PU
S
AS
SE
T
PR
O
TE
C
TI
O
N P
R O
JE
C
T
VOLUME 1
GENERAL NOTES
1. ALL MATERIALS AND WORKMANSHIP SHALL CONFORM TO THE THESE DRAWINGS,
GENERAL NOTES, AND TECHNICAL PROVISIONS, AS WELL AS THE CONSTRUCTION
SPECIFICATIONS FOR THIS PROJECT PRESENTED IN BOOK FORM.
2. THE CONTRACTOR SHALL BE RESPONSIBLE FOR MAINTAINING RECORD DRAWINGS
FOR ALL WORK THROUGHOUT THE COURSE OF CONSTRUCTION. SUCH DRAWINGS
SHALL RECORD THE LOCATION AND AS-BUILT CONDITION OF ALL PROJECT
ELEMENTS. COPIES SHALL BE DELIVERED TO THE ENGINEER PRIOR TO THE
ACCEPTANCE OF THE WORK, OR APPROVAL OF PAY APPLICATIONS, AS INDICATED IN
THE SPECIFICATIONS
3. THE CONTRACTOR SHALL EXAMINE THE DOCUMENTS AND SHALL NOTIFY THE
ENGINEER OF ANY DISCREPANCIES WHICH MAY BE FOUND PRIOR TO THE START OF
WORK.
4. DETAILS MARKED "TYPICAL" SHALL APPLY IN ALL CASES, UNLESS NOTED
OTHERWISE.
5. FOR CONDITIONS DEVIATING FROM THE TYPICAL AND NOT SPECIFICALLY DETAILED
IN THE PLANS, THE CONTRACTOR SHALL VERIFY CONSTRUCTION DETAILS WITH THE
ENGINEER PRIOR TO CONSTRUCTION.
6. DETAILS AND DIMENSIONS OF EXISTING CONDITIONS AS SHOWN ON THESE
DRAWINGS ARE FOR REFERENCE ONLY. THE CONTRACTOR SHALL FIELD VERIFY
AND RESOLVE ANY CONFLICTS WITH THE ENGINEER.
7. THE CONTRACTOR SHALL BE RESPONSIBLE FOR COORDINATING THE WORK OF ALL
TRADES AND SUBCONTRACTORS UNDER THE CONTRACTOR'S JURISDICTION.
8. THE ALIGNMENT SHOWN ON THE DRAWINGS IS THE CONSTRUCTION REFERENCE
LINE FOR THE PROJECT FACILITIES SHOWN. THE CONTRACTOR SHALL ESTABLISH
THE ALIGNMENT AND ANY OFFSETS REQUIRED UTILIZING THE MONUMENTS
PROVIDED.
9. THE CONTRACTOR IS RESPONSIBLE FOR THE PROTECTION OF ALL EXISTING
MONUMENTS AND OTHER SURVEY MARKERS. MONUMENTS AND SURVEY MARKERS
DESTROYED DURING CONSTRUCTION SHALL BE REPLACED BY A LICENSED LAND
SURVEYOR AT THE CONTRACTOR'S EXPENSE. CONTRACTOR SHALL PROVIDE
ENGINEER WITH AT LEAST 48 HOURS ADVANCE NOTICE PRIOR TO REPLACEMENT.
10. THE CONTRACTOR SHALL BE RESPONSIBLE FOR COMPLIANCE WITH ALL FEDERAL,
STATE AND LOCAL LAWS, RULES AND REGULATIONS APPLICABLE TO ALL WORK
PERFORMED UNDER THE CONTRACT.
11. THE CONTRACTOR SHALL NOT BEGIN ANY WORK SHOWN ON THESE PLANS UNTIL
ALL APPLICABLE PERMITS HAVE BEEN OBTAINED.
12. THE CONTRACTOR IS RESPONSIBLE FOR COMPLIANCE WITH ALL CURRENT AND
APPLICABLE SAFETY LAWS OF ALL JURISDICTIONAL BODIES. THE CONTRACTOR IS
DIRECTED TO CONTACT THE OFFICE OF SAFETY AND HEALTH ADMINISTRATION
(OSHA).
13. INFORMATION CONTAINED WITHIN THESE DOCUMENTS SHALL NOT BE CONSTRUED
TO PERMIT WORK NOT CONFORMING TO THE REFERENCED CODES.
14. FOR ALL TRENCH EXCAVATIONS THAT ARE 5 FEET OR MORE IN DEPTH, THE
CONTRACTOR SHALL OBTAIN A PERMIT FROM THE DIVISION OF INDUSTRIAL SAFETY.
PRIOR TO BEGINNING ANY EXCAVATION, A COPY OF THIS PERMIT SHALL BE MADE
AVAILABLE AND BE LOCATED ON THE CONSTRUCTION SITE AT ALL TIMES.
15. THE CONTRACTOR SHALL PREPARE A TRAFFIC CONTROL PLAN DESCRIBING
METHODS TO SAFELY CONTROL TRAFFIC ON PUBLIC ROADWAYS IN AND AROUND
THE SITE.
16. THE CONTRACTOR SHALL BE SOLELY AND COMPLETELY RESPONSIBLE FOR
FURNISHING AND MAINTAINING ALL WARNING SIGNS, DEVICES, AND FEATURES
NECESSARY TO PROTECT THE HEALTH AND SAFETY OF THE GENERAL PUBLIC AND
WORKERS AND TO PROVIDE FOR THE PROPER AND SAFE ROUTING OF VEHICULAR
AND PEDESTRIAN TRAFFIC DURING THE PERFORMANCE OF THE WORK.
17. THE CONTRACTOR SHALL PROTECT FROM DAMAGE ALL EXISTING FACILITIES. ANY
ITEMS DAMAGED BY THE CONTRACTOR OR HIS AGENTS SHALL BE REPLACED IN
EQUAL OR BETTER CONDITION AS APPROVED BY THE OWNER'S REPRESENTATIVE.
18. THE CONTRACTOR SHALL VERIFY ALL DIMENSIONS, SIZES AND LOCATIONS OF ALL
EXISTING FACILITIES, UNDERGROUND UTILITIES, AND FEATURES TO REMAIN
BEFORE STARTING WORK AND SHALL IMMEDIATELY NOTIFY THE ENGINEER OF ANY
DISCREPANCIES.
19. UTILITY INFORMATION WAS COMPILED FROM DATA PROVIDED BY THE UTILITY
OWNERS AND LOCATIONS ARE APPROXIMATE. THE ACTUAL LOCATIONS AND
ELEVATIONS OF THE EXISTING UTILITIES SHALL BE VERIFIED BY THE CONTRACTOR.
IF RELOCATION IS REQUIRED, THE CONTRACTOR IS RESPONSIBLE FOR
COORDINATING WITH THE APPROPRIATE UTILITY OWNER AT NO ADDITIONAL COST
TO THE OWNER.
20. THE CONTRACTOR IS TO REQUEST TO HAVE ALL UNDERGROUND UTILITIES THAT
MAY POSSIBLY CONFLICT WITH THE ABOVE OR BELOW GROUND IMPROVEMENTS,
LOCATED IN THE FIELD. THE CONTRACTOR AND ANY SUBCONTRACTOR ARE
REQUIRED TO NOTIFY THE USA NORTH 811, 48 HOURS IN ADVANCE OF PERFORMING
ANY EXCAVATION.
21. DRAWINGS SHOWN WITH AERIAL PHOTOS ARE PROVIDED FOR REFERENCE ONLY.
ALL FACILITIES MAY NOT BE SHOWN ON PHOTOS. THE CONTRACTOR SHALL SATISFY
THEMSELVES AS TO THE LOCATION OF EXISTING FACILITIES THAT MAY BE
AFFECTED BY THE CONSTRUCTION.
22. EXISTING GRADES AND CONDITIONS SHALL BE CONFORMED TO WHENEVER
POSSIBLE. ANY ADJACENT OR OFF SITE AREAS DISTURBED BY THE CONTRACTOR'S
OPERATIONS MUST BE RESTORED BY THE CONTRACTOR TO THE PRE DISTURBANCE
CONDITION, TO THE SATISFACTION OF THE ENGINEER AND OWNER'S
REPRESENTATIVE.
1. THE CONTRACTOR SHALL NOT ADJUST GRADES ON THIS PLAN WITHOUT PRIOR
WRITTEN APPROVAL OF THE ENGINEER.
2. THE CONTRACTOR SHALL TAKE THE NECESSARY PRECAUTIONS REQUIRED TO
PROTECT ADJACENT PROPERTIES DURING THE GRADING OPERATIONS.
3. DURING CONSTRUCTION, THE CONTRACTOR SHALL PROPERLY GRADE ALL
EXCAVATED SURFACES TO PROVIDE POSITIVE DRAINAGE AND PREVENT PONDING
OF WATER. THE CONTRACTOR SHALL CONTROL SURFACE WATER TO AVOID
DAMAGE TO ADJOINING PROPERTIES OR TO FINISHED WORK ON THE SITE. .
4. WHEN IMPORTING OR EXPORTING OF ANY MATERIAL THE CONTRACTOR SHALL
MAINTAIN ALL PUBLIC ROADS USED AS A HAUL ROUTE SO THEY REMAIN DUST FREE
5. ALL CUT OR FILL SLOPES SHALL BE 3:1 OR FLATTER UNLESS OTHERWISE NOTED.
6. IMPLEMENT MEASURES TO PROTECT EXISTING STRUCTURES THAT ARE TO REMAIN
FROM OVERLOAD OR DAMAGE. REPAIR OR RECONSTRUCT ANY DAMAGED
FACILITIES AS DIRECTED BY THE OWNER AND OWNER'S REPRESENTATIVE.
7. EXCAVATION SUPPORT: EXCAVATIONS FOR STRUCTURE AND TRENCHES SHALL BE
SUPPORTED IN ACCORDANCE WITH THE REQUIREMENTS SPECIFIED IN 29CFR1926,
SUBPART P - EXCAVATIONS, CAL/OSHA REQUIREMENTS, AND THE GENERAL
CONDITIONS, TO PREVENT CAVING, SLIDING, AND SETTLEMENT. PROVIDE AN
ENGINEERED SOLUTION, STAMPED BY A CALIFORNIA REGISTERED ENGINEER, FOR
CONDITIONS BEYOND STANDARD SAFETY ORDERS AND PERMITTED TYPICAL
EXCAVATION.
8. THE CONTRACTOR IS RESPONSIBLE FOR THE SAFETY OF ALL TEMPORARY
EXCAVATIONS AND MUST PROVIDE TRENCH SLOPING AND/OR SHORING IN
ACCORDANCE WITH CURRENT CAL/OSHA REQUIREMENTS BASED ON EXPOSED
SOIL AND GROUNDWATER/SEEPAGE CONDITIONS. FACTORS THAT MAY AFFECT
EXCAVATION WALL STABILITY OR CAUSE EXCAVATION-RELATED DAMAGE TO
EXISTING FACILITIES AND IMPROVEMENTS (SUCH AS CONSTRUCTION VIBRATIONS
AND GROUNDWATER/SEEPAGE CONDITIONS) MUST BE EVALUATED AT THE TIME OF
CONSTRUCTION, AND THE CONSTRUCTOR MUST ADJUST EXCAVATION SLOPING OR
SHORING METHODS ACCORDINGLY.
9. THE CONTRACTOR IS RESPONSIBLE FOR SUBMITTING AND OBTAINING APPROVAL
FOR DEWATERING PLAN AND EXCAVATION AND SHORING PLAN PRIOR TO
COMMENCING WORK.
SURVEY NOTES
1. SURVEY (TOPOGRAPHY AND FEATURES) IS BASED ON A COMBINED FIELD SURVEY
PROVIDED BY PSOMAS, PERFORMED BETWEEN NOVEMBER 2020 AND FEBRUARY
2022 AND FIELD SURVEY BY MORROW LAND SURVEYING DATED FEBRUARY 2014.
THE HORIZONTAL DATUM OF THIS SURVEY IS THE NORTH AMERICAN DATUM
OF 1983 (NAD83) (1991.35 EPOCH) BEING THE CALIFORNIA COORDINATE
SYSTEM OF 1983 (CCS83) ZONE 2 (GRID SURFACE).
THE VERTICAL DATUM OF THIS SURVEY IS THE NORTH AMERICAN VERTICAL
DATUM OF 1988 (NAVD88). CONVERSION TO NAVD88 = NGVD + 2.611'.
NGS BENCHMARK 15.623 (JT0204) ELEV: 18.08 (ADJUSTED TO NAVD88 DATUM)
BENCH MARK DISK STAMPED "15.623" LOCATED AT 38°14' 58.60" (N) 122° 02'
25.08" (W) AND SET VERTICALLY IN THE SOUTH GRANITE WALL OF THE OLD
SOLANO COUNTY COURTHOUSE, NEAR THE SOUTHEAST CORNER OF THE
BUILDING, 66 FEET EAST OF THE MAIN (TEXAS STREET) ENTRANCE, AND 1.6
FEET ABOVE THE GROUND.
2. THE CONTRACTOR SHALL BE RESPONSIBLE FOR CONSTRUCTION STAKING LAYOUT.
CONSTRUCTION STAKING SHALL BE PERFORMED UNDER THE DIRECTION OF A
LICENSED PROFESSIONAL LAND SURVEYOR OR CIVIL ENGINEER.
EROSION AND SEDIMENT CONTROL NOTES
1. THE CONTRACTOR SHALL PROVIDE EROSION, SEDIMENT, AND WATER POLLUTION
CONTROL MEASURES IN ACCORDANCE WITH THE APPROVED STORM WATER
POLLUTION PREVENTION PLAN (SWPPP).
2. DUST CONTROL, EROSION CONTROL, AND SEDIMENT CONTROL MEASURES,
INCLUDING STREET CLEANING AT WORK AREA ENTRANCES SHALL BE
CONTINUOUSLY MAINTAINED.
3. THE CONTRACTOR SHALL CONDUCT OPERATIONS OUTSIDE OF AREAS DESIGNATED
TO BE PRESERVED OR PROTECTED ACCORDING TO THE PLANS.
4. ALL CONSTRUCTION OF OFF-SITE AND ON-SITE IMPROVEMENTS SHALL ADHERE TO
NPDES BEST MANAGEMENT PRACTICES TO PREVENT DELETERIOUS MATERIALS OR
POLLUTANTS FROM ENTERING THE COUNTY AND CITY STORM DRAIN SYSTEMS.
UTILITY TRENCH EXCAVATION AND BACKFILL
1. EXCAVATIONS SHALL BE CONSTRUCTED IN ACCORDANCE WITH THE CURRENT
CAL-OSHA SAFETY STANDARDS AND LOCAL JURISDICTION. THE STABILITY AND
SAFETY OF EXCAVATIONS, BRACED OR UN-BRACED, ARE THE RESPONSIBILITY OF
THE CONTRACTOR
2. TRENCH EXCAVATIONS ADJACENT TO EXISTING OR PROPOSED FOUNDATIONS
ABOVE AN IMAGINARY PLANE HAVING AN INCLINATION OF 1.5 HORIZONTAL TO 1
VERTICAL BELOW THE BOTTOM EDGE OF THE FOUNDATIONS SHALL BE PROPERLY
SHORED TO MAINTAIN SUPPORT OF EXISTING FACILITIES.
WATER SURFACE ELEVATION DESIGN CRITERIA
1. DESIGN STORM USED TO COMPUTE THE DESIGN WATER SURFACE ELEVATION
(WSEL) WAS THE MAXIMUM ELEVATION DURING THE DECEMBER 2005 STORM
EVENT WHICH HAD A RAINFALL DEPTH OF 4.4 INCHES IN 12 HOURS.
2. TOP OF BARRIER ELEVATION IS BASED ON COMPUTED MAX WSEL PLUS 1-FT
MINIMUM FREEBOARD.
EARTHWORK
PARKING AND SECURITY
1. REFER TO VOLUME 2 FOR ON-SITE TRAFFIC CIRCULATION AND PARKING LOT
IMPROVEMENTS.
2. REFER TO VOLUME 2 FOR SECURITY UPGRADES FOR THE JUSTICE CENTER
CAMPUS AND PARKING LOTS.
SANITARY SEWER
1. DESIGN IMPROVEMENTS TO THE SANITARY SEWER SYSTEM WILL BE PERFORMED
UNDER A SEPARATE PROJECT, BY KSN, WHICH INCLUDES REROUTING MAIN LINES
OFF COUNTY PROPERTY AND PRIVATIZING THE REMAINING INFRASTRUCTURE
LOCATED ON COUNTY-OWNED LAND. THE VOLUME 1 ASSET PROTECTION AND
VOLUME 2 PARKING AND SECURITY DESIGN AND DRAWINGS ASSUME THAT
PRIVATIZATION OF THE SYSTEM ON COUNTY PROPERTY WILL BE COMPLETED
PRIOR TO CONSTRUCTION.
2. REFER TO SANITARY SEWER NOTES ON DRAWINGS C-242 FOR REQUIREMENTS
THAT WILL APPLY IF OFFSITE SANITARY SEWER IMPROVEMENTS ARE NOT
COMPLETED PRIOR TO CONSTRUCTION OF THE VOLUME 1 ASSET PROTECTION
PROJECT. IF REQUIRED, TEMPORARY BYPASS SHALL CONFORM WITH ALL
REQUIREMENTS SHOWN ON KSN DRAWING SS1.
CODE REQUIREMENTS:
1. ALL WORK SHALL COMPLY WITH THE LATEST CALIFORNIA EDITION OF THE
BUILDING, ELECTRICAL, MECHANICAL & PLUMBING CODES. ADDITIONAL CODE
REQUIREMENTS FOR STRUCTURAL WORK ARE SHOWN ON SHEET S-001.
ADDITIONAL CODE REQUIREMENTS FOR ELECTRICAL WORK ARE SHOWN ON
SHEET E-001.
1 02/23/2026 SANITARY SEWER
REVISION
SHEET INDEX
SHEET NUMBER SHEET TITLE
Sheet Files: GENERAL
G-001 COVER SHEET
G-002 GENERAL NOTES AND SHEET INDEX
G-003 LEGENDS AND ABBREVIATIONS
G-041 ALIGNMENTS
G-042 ALIGNMENT TABLES
G-061 PAINTING AND COATING SCHEDULE
Sheet Files: CIVIL
C-021 EROSION & SEDIMENT CONTROL STAGING PLAN I
C-022 EROSION & SEDIMENT CONTROL STAGING PLAN II
C-051 PLAN - DEMOLITION
C-052 PLAN - DEMOLITION
C-141 SITE OVERVIEW
C-142 SITE PLAN - NORTHWEST CORNER
C-143 SITE PLAN - SOUTHWEST CORNER
C-144 SITE PLAN - SOUTHEAST CORNER
C-145 SITE PLAN - NORTHEAST CORNER
C-151 SITE PLAN - UTILITIES
C-152 SITE PLAN - UTILITIES
C-201 PLAN AND PROFILE - STORM PROTECTION ALIGNMENT
C-202 PLAN AND PROFILE - STORM PROTECTION ALIGNMENT
C-203 PLAN AND PROFILE - STORM PROTECTION ALIGNMENT
C-204 PLAN AND PROFILE - STORM PROTECTION ALIGNMENT
C-205 PLAN AND PROFILE - STORM PROTECTION ALIGNMENT
C-211 PLAN AND PROFILE - WEST DELAWARE STREET RAMP
C-212 PLAN AND PROFILE - EAST DELAWARE STREET RAMP
C-213 PLAN AND PROFILE - WASHINGTON STREET RAMP
C-241 ENLARGED PLAN - PLAZA
C-242 ENLARGED PLAN - MEMORIAL AND MATERIALS USE AREAS
C-301 TYPICAL SECTIONS - FLOOD PROTECTION ALIGNMENT
C-311 TYPICAL SECTIONS - ROAD
C-312 TYPICAL SECTIONS - ROAD
C-313 TYPICAL SECTIONS - ROAD
C-411 PLAN AND PROFILE - EXTERIOR STORM DRAINAGE
C-412 PLAN AND PROFILE - EXTERIOR STORM DRAINAGE
C-501 TYPICAL DETAILS - STORM GATES
C-502 TYPICAL DETAILS - UTILITIES
C-503 TYPICAL DETAILS - PAVEMENT
C-504 TYPICAL DETAILS - ACCESSIBILITY
C-505 TYPICAL DETAILS - VEHICLE BARRIER
C-511 TYPICAL DETAILS - CITY DETAILS STREET
C-512 TYPICAL DETAILS - CITY DETAILS UTILITY
CG-141 GRADING PLAN - NORTHWEST BERM
CG-142 GRADING PLAN - PLAZA
CG-143 GRADING PLAN - MEMORIAL AREA
CG-144 GRADING PLAN - RAMP
CG-145 GRADING PLAN - MAINTENANCE BUILDING AREA
CG-146 GRADING PLAN - SOUTHEAST CORNER
Sheet Files: STRUCTURAL
S-001 GENERAL STRUCTURAL NOTES
S-002 STRUCTURAL SPECIAL INSPECTION TABLE AND NOTES
S-301 STRUCTURAL - WALLS
S-302 STRUCTURAL - RAMP WALLS
S-501 STRUCTURAL - TYPICAL DETAILS
S-502 STRUCTURAL - TYPICAL DETAILS
S-503 STRUCTURAL - TYPICAL DETAILS
S-504 STRUCTURAL - TYPICAL DETAILS
S-505 STRUCTURAL - TYPICAL DETAILS
S-531 STRUCTURAL - GATE FOUNDATIONS
S-551 STRUCTURAL - PRE-CAST VAULTS
S-552 STRUCTURAL - COLLECTION VAULT
S-553 SPOILS AREA PLANS, SECTIONS, AND DETAILS
Sheet Files: MECHANICAL
M-141 PLAN - PUMP STATION AND STORM DRAINAGE VAULTS
M-142 PLAN - COGENERATION PLANT STORM DRAINAGE LIFT STATION
M-301 PLAN AND SECTIONS - PUMP STATION
M-311 SECTIONS - INTERIOR AND EXTERIOR STORM DRAINAGE VAULTS
M-321 SECTIONS - COGENERATION PLANT STORM DRAINAGE LIFT STATION
M-501 ASSEMBLY - OUTLET PIPE
Sheet Files: ELECTRICAL
E-001 ELECTRICAL SYMBOLS AND LEGENDS
E-002 INSTRUMENT SYMBOLS AND LEGENDS
E-011 SINGLE LINE DIAGRAM - LIFTSTATION MCC
E-012 SINGLE LINE DIAGRAM - COGEN DEMO
E-013 SINGLE LINE DIAGRAM - COGEN NEW
E-021 LIFT STATION MCC LAYOUT AND SCHEDULE
E-022 MOTOR CONTROL DIAGRAMS
E-023A LIFT STATION PUMP CONTROL
E-023B LIFT STATION PUMP CONTROL
E-024 BLOCK DIAGRAM
E-111 POWER PLAN
E-112 ENLARGED POWER PLAN - PUMP STATION
E-113 ENLARGED POWER PLAN - CO-GEN INTERIOR
E-114 ENLARGED POWER PLAN - CO-GEN PUMP STATION
E-115 P&ID LIFT STATION 1 OF 3
E-116 P&ID LIFT STATION 2 OF 3
E-117 P&ID LIFT STATION 3 OF 3
E-118 CONDUIT & CONDUCTOR SCHEDULE
E-211 PLAZA LIGHTING PLAN
E-212 PLAZA LIGHTING SCHEDULE
E-213 LIFT STATION LIGHTING PLAN
E-214 LIFT STATION LIGHTING SCHEDULE
E-501 DETAILS 1
E-502 DETAILS 2
Sheet Files: LANDSCAPING
L-100 SITE OVERVIEW
L-201 LANDSCAPE PLAN - NORTHEAST ENTRY
L-202 LANDSCAPE PLAN - NORTHWEST CORNER
L-203 LANDSCAPE PLAN - SOUTHWEST CORNER
L-204 PLANTING LEGEND, DETAILS, AND NOTES
L-205 LANDSCAPE DETAILS
L-301 IRRIGATION PLAN - NORTHEAST ENTRY
L-302 IRRIGATION PLAN - NORTHWEST CORNER
L-303 IRRIGATION PLAN - SOUTHWEST CORNER
L-304 IRRIGATION NOTES AND LEGEND
L-305 IRRIGATION DETAILS
L-306 IRRIGATION DETAILS
L-307 IRRIGATION DETAILS
L-308 WATER USE CALCULATIONS
8/11/2026
07/17/2026 RFI 42
08/11/2026 RFI 22
8/13/26: Reviewed for Revision 3/RFI 22 only.
-All bolts installed in concrete -Structural Masonry -Reinforcing steel placement -See Volume 1 sheet S-002
City of Fairfield
Fairfield-Suisun Sewer District
E E
JB
E
E
E
E
E
E
E
E
E E
E
HH
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
JB
E E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E E
E E
E E
E E
E E
E
E
E
E
E
E
+0
+00
53+50
0+
0+57.10
SS
D
M-141
PLAN - PUMP STATION
AND STORM
DRAINAGE VAULTS
CHM
RJG
TED
X:
\1
\1
4.
\T
EC
H \C
AD
\P
H
AS
E 3\
M -5
D
ET
AI
LS
D
IS
C H
AR
G
E
PI
PI
N
G .D
W G
8/
/2
7:
:3
PM
SO
LA
N O
C O
U N
TY
D
O W
N
TO
W N
F
AI
R
FI
EL
D
J U
ST
IC
E C
AM
PU
S
AS
SE
T
PR
O
TE
C
TI
O
N P
R O
JE
C
T
1943400-190824.01
TE
XA
S
ST
R
EE
T
FA
IR
FI
EL
D
, C A
SHEET CONTENTS
DO NOT SCALE DRAWINGS
M&H NO.:
DATE:
DESIGNED BY:
DRAWN BY:
CHECKED BY:
ISSUED
These documents shall not be used for any purpose or project for which it is not intended. Mead & Hunt shall be indemnified by the client and held harmless and defended from all claims, damages, liabilities, losses, and expenses, including attorneys' fees and costs, arising out of such misuse or reuse of the documents.
In addition, unauthorized reproduction of these documents, in part or as a whole, is prohibited.
Mead and Hunt, Inc.
180 Promenade Circle, Suite 240 Sacramento, CA 95834 phone: 916-971-3961 meadhunt.com
TE
XA
S
ST
R
EE
T
FA
IR
FI
EL
D
, C A
SO
LA
N O
C O
U N
TY
D
O W
N
TO
W N
F
AI
R
FI
EL
D
J U
ST
IC
E C
AM
PU
S
AS
SE
T
PR
O
TE
C
TI
O
N P
R O
JE
C
T
VOLUME 1
2 07/17/2026 RFI 42
3 08/11/2026 RFI 22
EXISTING OUTFALL
PROPOSED
FENCE
00 5 10
16' Ø PRECAST SUMP
PUMP VAULT
SEE DETAIL 2/S-551
PROPERTY
LIMIT, TYP
(3) 5400 GPM
SUBMERSIBLE
PUMPS
EXISTING
30-IN PIPE
DELA
WARE STREET
U N
IO
N
A
VE
. C R
EE
K
48-IN Ø RCP
EXISTING
30-IN RCP
PIPE
96-IN SD MH
36-IN Ø RCP
WALL AT PIPE
INTERSECTION
SEE DETAIL 13/C-301
EXISTING PUMP
STATION
2' x 2' SD
GRATE
12-IN Ø
RCP
M-301
18-IN DIP
DISCHARGE
PIPE, TYP
SPOILS AREA - SEE C-144
AND S-553 FOR DETAILS
MOTOR CONTROL CENTER - SEE ELECTRICAL DRAWINGS
CONCRETE
EQUIPMENT PAD -
SEE DETAIL 2/C-503
EXISTING DUMPSTER
4-IN VAULT AIR VENT
(2 PLACES) SEE
DETAIL 2/M-301
KEY MAP
NOTES:
1. SEE C-152 FOR STORM DRAINAGE SYSTEM.
2. SEE C-203 AND S-301 FOR BARRIER IMPROVEMENTS.
3. SEE VOLUME 2: PARKING AND SECURITY FOR
PARKING LOT AND FENCING IMPROVEMENTS.
4. SEE SEWER BYPASS NOTES ON SHEET C-242. SEE
SHEET S-311 FOR ASSUMED SS LINE LOCATION IN
RELATION TO THE PREPACKAGED LIFT STATION.
5. FURNISH AND INSTALL THREE EACH NEW PUMP
COLUMNS, NEW FORMED SUCTION INTAKES, AND
NEW FLYGT PL7030-655 AXIAL FLOW COLUMN
PUMPS AND APPURTENANCES ACCORDING TO
XYLEM QUOTE #2026-FFB-0330 DATED 8/7/2026.
NEW AXIAL FLOW PUMP
ASSEMBLIES, SEE NOTE 5
A M-
1EX 24" VCP SS
(SEE NOTES)
SEPTEMBER 29, 2026
A M-
FOUNDATION SEE
DETAIL X/S-XXX
08/11/2026
02/23/2026 SANITARY SEWER
REVISION
M-301
PLAN AND SECTIONS -
PUMP STATION
CMH
RJG
TED
X:
\1
\1
4.
\T
EC
H \C
AD
\P
H
AS
E 3\
M -5
D
ET
AI
LS
D
IS
C H
AR
G
E
PI
PI
N
G .D
W G
8/
/2
7:
:0
PM
SO
LA
N O
C O
U N
TY
D
O W
N
TO
W N
F
AI
R
FI
EL
D
J U
ST
IC
E C
AM
PU
S
AS
SE
T
PR
O
TE
C
TI
O
N P
R O
JE
C
T
1943400-190824.01
SEPTEMBER 29, 2026
TE
XA
S
ST
R
EE
T
FA
IR
FI
EL
D
, C A
SHEET CONTENTS
DO NOT SCALE DRAWINGS
M&H NO.:
DATE:
DESIGNED BY:
DRAWN BY:
CHECKED BY:
ISSUED
These documents shall not be used for any purpose or project for which it is not intended. Mead & Hunt shall be indemnified by the client and held harmless and defended from all claims, damages, liabilities, losses, and expenses, including attorneys' fees and costs, arising out of such misuse or reuse of the documents.
In addition, unauthorized reproduction of these documents, in part or as a whole, is prohibited.
Mead and Hunt, Inc.
180 Promenade Circle, Suite 240 Sacramento, CA 95834 phone: 916-971-3961 meadhunt.com
TE
XA
S
ST
R
EE
T
FA
IR
FI
EL
D
, C A
SO
LA
N O
C O
U N
TY
D
O W
N
TO
W N
F
AI
R
FI
EL
D
J U
ST
IC
E C
AM
PU
S
AS
SE
T
PR
O
TE
C
TI
O
N P
R O
JE
C
T
VOLUME 1
2 07/17/2026 RFI 42
3 08/11/2026 RFI 22
EXISTING
30-IN SD PIPE
INV=-1.94
B
FLUME
INV EL = 11.6
TOP OF GRATING
INV EL = 16.0
TOP OF CONCRETE
INV EL = 12.6
NEW AXIAL PUMP
COLUMN, TYP X 3
NEW OUTLET
PIPE ASSEMBLY
SEE M-501
NOTES:
1. HDPE DISCHARGE PIPING, BIFURCATION, TRIFURCATION, AND NEW STEEL OUTLET PIPE
DIMENSIONS ARE APPROXIMATE. CONTRACTOR TO SUBMIT PIPING LAYOUT AND
FABRICATION DETAILS TO COUNTY FOR APPROVAL PRIOR TO FABRICATION. SEE SECTION
33 40 00 OF THE SPECIFICATIONS.
2. CONTRACTOR TO FIELD VERIFY DIMENSIONS OF EXISTING STRUCTURES.
18-IN DIA HDPE
DISCHARGE PIPES
36-IN DIA HDPE
LONG RADIUS
ELBOW
36-IN x 18-IN HDPE
REDUCER
36-IN HDPE SPOOL WITH
18-IN BRANCHES
INSTALL NEW PUMP
CANS AND NEW AXIAL
COLUMN PUMPS
BAR GRATING NOT
SHOWN FOR CLARITY
18-IN DIA HDPE
DISCHARGE PIPES
NEW OUTLET
PIPE ASSEMBLY
SEE M-501
EXISTING
30-IN DIA RCP
PIPE
PROVIDE FLEX MECH COUPLERS
TO CONNECT 18-IN DIP TO HDPE
AT SUMP WALL, TYP. SEE
SECTION A/M-311
EXISTING PUMP
STATION
AIR VENT, GALV SCH 40
PIPE, WITH STAINLESS
STEEL EXCLUSION
SCREEN IN OUTLET
STANDARD PIPE
STRAP
SPACER BLOCK
MIN 2-INCH
D
ES
IG
N
ED
M
AX
W
SE
1-
FT
1-5/8 METAL STRUT
DOUBLE CHANNEL, TYP
UNISTRUT PIPE
CLIP, TYP.
2'
D
ES
IG
N
ED
M
AX
W
SE
1' -6
9"
1' -3
3"
PIPE/STRUT FRAME
CAST-IN-PLACE
EQ
EQ
4-IN AIR VENT, TYP 2-PLACES
SEE DETAIL 2/M-301
4-IN LEVEL
TRANSDUCER WELL -
SEE DETAIL 4/M-321
EQ SPACED
AS REQUIRED
D
ES
IG
N
ED
M
AX
W
SE
1'
1-1/4 GALVANIZED
PIPE, TYP
AIR VENT, GALV SCH
40 PIPE, WITH
STAINLESS STEEL
EXCLUSION SCREEN IN
OUTLET
6"
UNISTRUT PIPE
CLAMP, TYP X2
A
SECTION A-A
A
SECTION A-A
36-IN HDPE PIPE FLANGE
(QTY 3), DIMENSIONS AND
BOLT PATTERN TO AWWA
C207 CLASS D
32-IN AWWA C207
CLASS D FLANGE
COUNTY PUMP STATION
1"=5'
M-141
COUNTY PUMP STATION
1"=5'
B
M-311
AIR VENT - STRUCTURE MOUNT DETAIL
1"=1'
M-311
AIR VENT - WALL MOUNT DETAIL
1"=1'
C M-311
NEW FLAP GATES
SEE M-502 AND M-503
NEW CONCRETE
FOUNDATION
SEE DETAIL X/S-5XX
REMOVE AND
REINSTALL
EXISTING BAR
SCREEN
NEW STAINLESS
STEEL FLASH BOARD
SEE DETAIL 1/S-554
NEW FLAP GATE, TYP X3
SEE M-502 AND M-503
SEE DETAIL X/S-554 FOR
MOUNTING BRACKET
DETAILS.
NEW FORMED SUCTION
INTAKE, TYP X3
08/11/2026
M-311
SECTIONS - INTERIOR
AND EXTERIOR
STORM DRAINAGE
VAULTS
CMH
RJG
TED
X:
\1
\1
4.
\T
EC
H \C
AD
\P
H
AS
E 3\
M -5
D
ET
AI
LS
D
IS
C H
AR
G
E
PI
PI
N
G .D
W G
8/
/2
7:
:3
PM
SO
LA
N O
C O
U N
TY
D
O W
N
TO
W N
F
AI
R
FI
EL
D
J U
ST
IC
E C
AM
PU
S
AS
SE
T
PR
O
TE
C
TI
O
N P
R O
JE
C
T
1943400-190824.01
TE
XA
S
ST
R
EE
T
FA
IR
FI
EL
D
, C A
SHEET CONTENTS
DO NOT SCALE DRAWINGS
M&H NO.:
DATE:
DESIGNED BY:
DRAWN BY:
CHECKED BY:
ISSUED
These documents shall not be used for any purpose or project for which it is not intended. Mead & Hunt shall be indemnified by the client and held harmless and defended from all claims, damages, liabilities, losses, and expenses, including attorneys' fees and costs, arising out of such misuse or reuse of the documents.
In addition, unauthorized reproduction of these documents, in part or as a whole, is prohibited.
Mead and Hunt, Inc.
180 Promenade Circle, Suite 240 Sacramento, CA 95834 phone: 916-971-3961 meadhunt.com
TE
XA
S
ST
R
EE
T
FA
IR
FI
EL
D
, C A
SO
LA
N O
C O
U N
TY
D
O W
N
TO
W N
F
AI
R
FI
EL
D
J U
ST
IC
E C
AM
PU
S
AS
SE
T
PR
O
TE
C
TI
O
N P
R O
JE
C
T
VOLUME 1
2 07/17/2026 RFI 42
3 08/11/2026 RFI 22
EX GROUND
EL VARIES
EQUIPMENT HATCH - SEE DETAIL 2/S-551
UNION AVENUE
CREEK DESIGN
WSEL=14.0'
36-IN RCP SD PIPE
INV=0.75
16' Ø DIA PRECAST SUMP PUMP VAULT
(3) 5400 GPM PUMPS
RIM=12.67
INV=-10.33
SEE VAULT DETAIL 2/S-551
36-IN HDPE SPOOL WITH
18-IN BRANCHES SEE
DETAIL 1/M-301
(3) 18-IN DIP TO HDPE ADAPTOR
COUPLING
(3) 18-IN DIP DISCHARGE PIPE
INV=8.19
PROPOSED OUTLET
PIPE ASSEMBLY
SEE M-501
INV 16.0
PUMP RAIL ASSEMBLY, TYP X3
(3) 18-IN CHAIN OPERATED
PLUG VALVE
(3) 18-IN CHECK VALVE
ELECTRICAL
CONDUIT PENETRATION
HIGH-HIGH LEVEL
ALARM FLOAT SWITCH
EL = 9.42
STAINLESS FLOAT SWITCH CHAIN
LOW-LOW LEVEL
ALARM/TRIP FLOAT SWITCH,
SEE NOTE 6
(3) 5400 GPM SUBMERSIBLE
SEWAGE PUMP. LIFT ROPE/CHAIN
AND ELECTRICAL CABLE NOT
SHOWN.
PRESSURE TRANSDUCER, STILLING
WELL NOT SHOWN FOR CLARITY
EXTERIOR SD LIFT STATION
(2) 4-IN DIA. AIR VENT,
SEE M-141 FOR
ROUTING
36-IN RCP SD PIPE
INV=0.75
(2) 4-IN DIA VENT PIPE -
SEE DETAILS 1 & 2/M-301
PLAN - EXTERIOR SD LIFT STATION
3" = 1'
FG = 12.67
18-IN DIP TO HDPE TRANSITION -
SEE SECTION A
BARRIER WALL - SEE
DETAIL 13/C-301
36-IN DIA LONG
RADIUS ELBOW
(3) MECHANICAL COUPLING
SEE NOTE 3
ACCESS HATCH - SEE DETAIL 2/S-551
CONCRETE
EQUIPMENT PAD -
SEE DETAIL 2/C-503
INV -10.33
HATCHES - SEE S-551
CONCRETE EQUIPMENT
PAD - SEE DETAIL 2/C-503
4-IN LEVEL TRANSDUCER -
SEE DETAIL 4/M-321
18-IN DIA HDPE
DISCHARGER PIPES
36-IN AWWA C207 CLASS D
FLANGE JOINT
32-IN AWWA C207
CLASS D FLANGE
JOINT
(3) 18X12 DIP ECC REDUCER
PACKAGED LIFT
STATION CONNECTION
(3) GARLOCK LINK-SEAL
SEE DETAIL 5/M-321
EXISTING
GROUND
A M-141
INTERIOR & EXTERIOR DRAINAGE SUMPS
GENERAL ARRANGEMENT SCHEMATIC SECTION
3"=1'
SEPTEMBER 29, 2026
C M-301
CLAY STREET PUMP STATION
SUMP PUMP PIPING ARRANGEMENT SECTION
3"=1'
4 NPS SCH 40 STEEL
DISCHARGE PIPE
4 NPS SWING CHECK
VALVE
NEW END SUCTION SUMP
PUMP
6 NPS SCH 40 STEEL
SUCTION PIPE
08/11/2026
M-501
ASSEMBLY - OUTLET
PIPE
CMH
RJG
TED
X:
\1
\1
4.
\T
EC
H \C
AD
\P
H
AS
E 3\
M -5
D
ET
AI
LS
D
IS
C H
AR
G
E
PI
PI
N
G .D
W G
8/
/2
7:
:3
PM
SO
LA
N O
C O
U N
TY
D
O W
N
TO
W N
F
AI
R
FI
EL
D
J U
ST
IC
E C
AM
PU
S
AS
SE
T
PR
O
TE
C
TI
O
N P
R O
JE
C
T
1943400-190824.01
SEPTEMBER 29, 2026
TE
XA
S
ST
R
EE
T
FA
IR
FI
EL
D
, C A
SHEET CONTENTS
DO NOT SCALE DRAWINGS
M&H NO.:
DATE:
DESIGNED BY:
DRAWN BY:
CHECKED BY:
ISSUED
These documents shall not be used for any purpose or project for which it is not intended. Mead & Hunt shall be indemnified by the client and held harmless and defended from all claims, damages, liabilities, losses, and expenses, including attorneys' fees and costs, arising out of such misuse or reuse of the documents.
In addition, unauthorized reproduction of these documents, in part or as a whole, is prohibited.
Mead and Hunt, Inc.
180 Promenade Circle, Suite 240 Sacramento, CA 95834 phone: 916-971-3961 meadhunt.com
TE
XA
S
ST
R
EE
T
FA
IR
FI
EL
D
, C A
SO
LA
N O
C O
U N
TY
D
O W
N
TO
W N
F
AI
R
FI
EL
D
J U
ST
IC
E C
AM
PU
S
AS
SE
T
PR
O
TE
C
TI
O
N P
R O
JE
C
T
VOLUME 1
2 07/17/2026 RFI 42
3 08/11/2026 RFI 22
NEW OUTLET PIPE1 1"=1'
32-IN STEEL PIPE WELDMENT
OUTLET PIPE
GRATING ASSEMBLY
32-IN AWWA C207
CLASS D FLANGE
36-IN AWWA C207 CLASS
D FLANGE
32-IN AWWA C207,
CLASS D FLANGE, TYP
32-IN x 36-IN
CONCENTRIC
REDUCER
32-IN STANDARD 90°
ELBOW, TYP
32-IN STEEL PIPE WITH CUT
WINDOW. ALL CORNERS TO BE
ROUNDED, MIN RADIUS OF 3-IN.
SEE NOTE 4
1-1/8 IN ASTM A193 B8S ROUND
BAR. THREAD BOTH ENDS WITH
A194 B8 NUTS, TYP. SEE NOTE 3
3 x 3 x 38 L WELDED
TO 32-IN PIPE
NOTES:
1. CONTRACTOR TO SUBMIT FABRICATION DRAWINGS TO COUNTY FOR
APPROVAL PRIOR TO COMMENCING WORK. SEE SECTION 33 40 00 OF
THE SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS.
2. DIMENSIONS SHOWN ARE APPROXIMATE. CONTRACTOR TO FIELD
VERIFY ALL EXISTING STRUCTURES.
3. MINIMUM BAR SPACING 3 INCHES. BARS TO BE DESIGNED TO ALLOW
REMOVAL/INSTALLATION WITHOUT DISASSEMBLY OF PIPE FLANGES.
4. CENTER SECTION TO BE JOINED WITH BOLTED FLANGES TO ALLOW
ROTATION OF THE WINDOW AFTER ASSEMBLY.
5. OUTLET PIPE FABRICATION TO BE WELDED, COATED, AND LINED IN
ACCORDANCE WITH SPECIFICATION REQUIREMENTS. SEE NOTE 1.
32-IN BLIND FLANGE
08/11/2026
HANDHOLE
MANHOLE
H
J
M
UNDERGROUND CONDUIT
ABOVEGROUND CONDUIT
JUNCTION BOX
CONCEALED CONDUIT IN CEILING OR WALL
WIREWAY, SIZE AND TYPE AS INDICATED ON DRAWINGS
CABLE TRAY, SIZE AND TYPE AS INDICATED ON DRAWINGS
UNDERFLOOR DUCT
DISTRIBUTION TRANSFORMER FOR NON-LINEAR LOADS
WALL MOUNTED LIGHTING AND POWER TRANSFORMER-DRY TYPE
GENERAL LIGHTING AND POWER TRANSFORMER-DRY TYPE
1. THE INFORMATION SHOWN IS BASED ON EXISTING DRAWINGS AND SITE
OBSERVATIONS TO ASSIST CONTRACTOR IN BIDDING. THE ELECTRICAL
DRAWINGS INDICATE EXISTING ELECTRICAL ITEMS TO BE REMOVED.
THE DRAWINGS ARE INTENDED TO INDICATE THE SCOPE OF WORK
REQUIRED AND DO NOT INDICATE EVERY BOX, CONDUIT, OR WIRE THAT
MUST BE REMOVED. THE CONTRACTOR SHALL VISIT THE SITE PRIOR
TO SUBMITTING A BID AND VERIFY EXISTING CONDITIONS. REFER TO
SPECIFICATION SECTION 26 05 00 FOR ADDITIONAL REQUIREMENTS FOR
COMMON WORK.
2. DASHED WALLS ON THE FLOOR PLANS INDICATE EXISTING WALLS
BEING DEMOLISHED. REFER TO THE ARCHITECTURAL DEMOLITION
PLANS FOR THE EXACT EXTENT OF WORK REQUIRED BY THIS PROJECT.
REMOVE ALL DEVICES ON DASHED WALLS NOT SHOWN ON THE
CONTRACT DRAWINGS. REFER TO DEMOLITION DRAWINGS OF OTHER
TRADES. WHERE MOTORS CONTROL PANELS, AND OTHER LOADS OR
APPARATUS THAT HAVE ELECTRICAL CONNECTION ARE BEING
REMOVED, INCLUDE DISCONNECTION AND REMOVAL OF ALL
ASSOCIATED CONDUIT, WIRING, ETC.
3. ELECTRICAL ITEMS (i.e., LIGHTING FIXTURES, PANELBOARDS, DISCONNECTS, MOTOR CONTROLLERS , ETC.) REMOVED AND NOT
RELOCATED REMAIN THE PROPERTY OF THE OWNER AND SHALL BE
TURNED OVER TO THE OWNER IN A STORAGE AREA TO BE DESIGNATED
BY THE OWNER. EQUIPMENT BEING REMOVED SHALL BE HANDLED SO
AS NOT TO FURTHER REDUCE ITS VALUE TO THE OWNER. THE
CONTRACTOR SHALL DISPOSE OF MATERIAL THE OWNER DOES NOT
WANT TO REUSE OR RETAIN FOR MAINTENANCE PURPOSES.
4. WHERE LIGHTS, SWITCHES, RECEPTACLES, ETC., ARE BEING REMOVED
ALL ASSOCIATED CONDUIT AND WIRE BACK TO THE PANELBOARD OR
FEEDER JUNCTION BOX SERVING THE DEVICE SHALL ALSO BE
REMOVED, UNLESS THE CONDUIT CAN BE REUSED FOR NEW
CONDUCTORS. THE CONTRACTOR SHALL DISPOSE OF MATERIAL THE
OWNER DOES NOT WANT TO REUSE OR RETAIN FOR MAINTENANCE
PURPOSES.
5. ALL BOXES THAT REMAIN IN PLACE IN EXISTING MASONRY WALLS THAT
ARE TO REMAIN SHALL BE PROVIDED WITH A BLANK COVERPLATE.
REFER TO SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS
ASSOCIATED WITH TYPE AND ATTACHMENT.
6. ALL CONDUIT SHALL BE REMOVED WHERE WALLS ARE BEING REMOVED.
WHERE CONDUIT IS IN THE CONCRETE SLAB, CUT OFF FLUSH, PULL OUT
WIRE, AND PLUG. WHERE CONDUIT IS RUN EXPOSED, ALL ASSOCIATED
CLAMPS, SUPPORTS, HANGERS, ETC., SHALL ALSO BE REMOVED.
CONDUIT CONCEALED IN WALL CONSTRUCTION MAY BE ABANDONED IN
PLACE IF NOT AFFECTED BY OTHER CONSTRUCTION.
7. THIS CONTRACTOR SHALL COORDINATE ALL HIS WORK, INCLUDING
PHASING WITH OTHER CONTRACTORS AT THE JOB SITE BEFORE
REMOVING EXISTING ELECTRICAL AND INSTALLING NEW ITEMS.
8. EXISTING CONDUIT IN GOOD CONDITION, MAY BE REUSED IN PLACE.
RELOCATED EXISTING CONDUIT SHALL NOT BE ALLOWED. BONDING
CONDUCTORS SHALL BE INSTALLED IN ALL REUSED CONDUIT TO
ASSURE PROPER GROUND PATH.
9. MAINTAIN CONTINUITY OF DEVICES LOCATED OUTSIDE OF
CONSTRUCTION AREA. DEVICE AND EQUIPMENT REMOVAL IN CERTAIN
LOCATIONS MAY REQUIRE THE INSTALLATION OF A JUNCTION BOX TO
RECONNECT CIRCUITS THAT REMAIN IN OPERATION. EXTEND CONDUIT
AND WIRING AS REQUIRED TO MAINTAIN POWER TO REMAINING
EQUIPMENT.
10. BALLASTS MANUFACTURED PRIOR TO 1980 CONTAIN PCBs AND SHALL
BE DISPOSED OF IN ACCORDANCE WITH SPECIFICATION 02 40 00.
11. HID AND FLUORESCENT LAMPS CONTAIN MERCURY AND SHALL BE
DISPOSED OF IN ACCORDANCE WITH SPECIFICATION 02 40 00.
12. CONTRACTOR SHALL REMOVE AND INSTALL ALL CEILING TILES AS
REQUIRED FOR THE EXECUTION OF ELECTRICAL WORK THAT IS
OUTSIDE THE CONTRACT LIMITS OF CONSTRUCTION. CONTRACTOR
SHALL REPLACE CEILING TILES WITH IDENTICAL MATERIAL WHERE
DAMAGED BY THIS CONTRACTOR.
13. PROVIDE REVISED TYPED CIRCUIT DIRECTORY IN PANELBOARDS THAT
HAVE CIRCUITS REMOVED OR ADDED CIRCUITS.
14. REMOVE, RELOCATE, AND EXTEND EXISTING INSTALLATIONS TO
ACCOMMODATE NEW CONSTRUCTION.
15. REMOVE EXPOSED ABANDONED CONDUIT, INCLUDING ABANDONED
CONDUIT ABOVE ACCESSIBLE CEILING FINISHES. CUT RACEWAY FLUSH
WITH WALLS AND FLOORS, PATCH SURFACES TO MATCH EXISTING.
REMOVE ALL ASSOCIATED CLAMPS, HANGERS, SUPPORTS, ETC.
ASSOCIATED WITH RACEWAY REMOVAL.
16. DISCONNECT AND REMOVE ABANDONED LUMINAIRES, INCLUDING
BRACKETS, STEMS, HANGERS, AND OTHER ACCESSORIES.
17. DISCONNECT AND REMOVE ELECTRICAL DEVICES AND EQUIPMENT
SERVING UTILIZATION EQUIPMENT THAT HAS BEEN REMOVED.
A/E
AFF
AFG
AHU
ACCU
C
ALT
CF
CHWP
DH
CUH
DO
EF
CP
DUCT HEATER
EXHAUST FAN
DOOR OPERATOR
ALTERNATE
CONDUIT
CHILLED WATER PUMP
CIRCULATION PUMP
CABINET UNIT HEATER
ARCHITECT/ENGINEER
AIR HANDLING UNIT
ABOVE FINISHED GRADE
ABOVE FINISHED FLOOR
AIR COOLED CONDENSING UNIT
CIRCULATION FAN
EMT
EWH
EWC
ETR
FA
FAF
GFI
GRS
FIRE ALARM
HD
HP
HWB
HVAC
IMC
IH
HWP
IEWH
HAND DRYER
HORSEPOWER
GWH
NL
NIC
NTS
NL/EL
SP
SF
RF
RCP
PVC
NIGHT LIGHT
NOT TO SCALE
RETURN FAN
SUPPLY FAN
RADIATE CEILING PANEL
SUMP PUMP
SS
TBR
TYP
UC
UH
VER
WFE
UNO
UG
TYPICAL
UNDERGROUND
UNIT HEATER
UNIT COOLER
TO BE REMOVED
MAU
HOT WATER PUMP
HOT WATER BOILER
HEATING, VENTILATION, AIR CONDITIONING
MAKE-UP AIR UNIT
INFRARED HEATER
POLYVINYL CHLORIDE
INTERMEDIATE METALLIC CONDUIT
INSTANTANEOUS ELECTRIC WATER HEATER
NOT IN CONTRACT
NIGHT LIGHT AND EMERGENCY LIGHT
STAINLESS STEEL
UNLESS NOTED OTHERWISE
WELDING FUME EXTRACTOR
VEHICLE EXHAUST REEL
EXISTING TO REMAIN
ELECTRICAL WATER HEATER
ELECTRICAL WATER COOLER
GROUND FAULT INTERRUPTER
GALVANIZED RIGID STEEL
GAS WATER HEATER
FORCED AIR FURNACE
ELECTRICAL METALLIC TUBING
WL
WP
4X 3R
WEATHERPROOF
WET LOCATION LISTED
NEMA 3R RATING
NEMA 4X RATING
EL EMERGENCY LIGHT
G
W
NL
PLUG-IN BUS DUCT
GROUNDING CONDUCTOR
FEEDER BUS DUCT
MOTOR CONTROL CENTER
PUSH BUTTON STATION
IWH INSTANTANEOUS WATER HEATER
SM SINGLE-MODE FIBER OPTIC CABLE
MM MULTI-MODE FIBER OPTIC CABLE
MNS MASS NOTIFICATION SYSTEM
REQ'D REQUIRED
PAD MOUNTED SWITCH
DEMOLITION GENERAL NOTES:
ELECTRICAL SYMBOL SCHEDULE
LUMINAIRE SYMBOLS
LUMINAIRE CONTROL SYMBOLS
RACEWAYS SYMBOLS
RECEPTACLE SYMBOLS FIRE ALARM SYMBOLS
MOTORS & MOTOR CONTROL SYMBOLS
SERVICE & DISTRIBUTION SYMBOLS
ABBREVIATIONS
FIRE ALARM CONTROL PANEL
FIRE ALARM PULL STATION
FIRE ALARM ANNUNCIATOR PANEL
FIRE ALARM HORN
SUPERVISED FIRE ALARM HORN LOUDSPEAKER
NEW CONTROL MODULE
NEW ELECTRIC DOOR STRIKE
NEW FIRE FIGHTERS TELEPHONE
NEW FIRE FIGHTERS TELEPHONE JACK
FIRE ALARM SPEAKER
FIRE ALARM HORN/STROBE, (##) IS CANDELA RATING
FIRE ALARM SPEAKER/STROBE, (##) IS CANDELA RATING
FIRE ALARM STROBE, (##) IS CANDELA RATING
FIRE ALARM BELL
INTELLIGENT PHOTOELECTRIC SMOKE DETECTOR
INTELLIGENT PHOTOELECTRIC SMOKE DETECTOR FOR
ELEVATOR RECALL
INTELLIGENT 135F FIXED & RATE OF RISE HEAT DETECTOR
CONVENTIONAL FIXED TEMP HEAT DETECTOR,
(##) IS TEMP RATING
INTELLIGENT PHOTOELECTRIC DUCT SMOKE DETECTOR
CEILING MOUNTED FIRE ALARM STROBE,
(##) IS CANDELA RATING
CEILING MOUNTED FIRE ALARM SPEAKER/STROBE,
(##) IS CANDELA RATING
CEILING MOUNTED FIRE ALARM SPEAKER
NEW SPRINKLER FLOW SWITCH
NEW FIRE HALON PULL STATION
NEW HALON AUDIBLE ALARM
NEW HALON STROBE
NEW PRE-ACTION SOLENOID
NEW ISOLATOR MODULE
NEW MAGNETIC DOOR HOLDER
NEW MONITOR MODULE
NEW PRESSURE SWITCH
NEW REMOTE TEST SWITCH WITH INDICATOR
NEW SPRINKLER TAMPER SWITCH
FIRE SUPPRESSION SYSTEM PANEL
CABINET FOR HOLDING FIRE DEPARTMENT DOCUMENTS &
KEYS WITH INTEGRAL TAMPER SWITCH. KNOX BRAND #4400
OR APPROVED EQUAL. SEE DRAWING ##.
H
S
H
S
S
B
ER
H
H
DS
S
S
CO
H
H
MM
CM
IM
DH
ES
FS
TS
PE
PS
RTS/I
HA
HP
HS
CARBON MONOXIDE DETECTOR
CEILING MOUNTED FIRE ALARM HORN/STROBE, (##) IS
CANDELA RATING
CEILING MOUNTED FIRE ALARM HORN
FMCP
FACP
FAAP
FSS
KNOX
FIRE & MASS NOTIFICATION CONTROL PANEL
S
SS
SWBK
SWITCHES, FOR MULTI-LEVEL SWITCHING. REFER TO FLOOR PLANS
AND FIXTURE SCHEDULE FOR EXACT CONTROL INTENT.
SINGLE POLE SWITCH
PHOTO ELECTRIC CONTROL
OCCUPANCY SENSOR CEILING MOUNT
(x REPRESENTS SCHEDULE DESIGNATION)
DAYLIGHT SENSOR , SEE OCCUPANCY SENSOR SCHEDULE
ELECTRONIC TIME CLOCK
LIGHTING CONTROL PANEL
(x REPRESENTS PANEL DESIGNATION)
LIGHTING CONTACTOR
UL 924 LISTED EMERGENCY LIGHTING BYPASS
CONTROL UNIT
OS1
DS
TC
PE
LC
LCPX
PT
OCCUPANCY SENSOR BRACKET MOUNT
(x REPRESENTS SCHEDULE DESIGNATION)OSX
POWER PACK USED IN CONJUNCTION WITH OCCUPANCY
SENSORS OR DAYLIGHT SENSORS
PP
REMOTE POWER SUPPLY OR DRIVERPS
DIMMER RACKDR
DIMMER CONTROL STATION MULTI-PRESET MODULAR
DIMMING SYSTEM
D
DIMMER NOTATIONS:
ES ENTRY STATION
PS PARTITION STATION
LOW VOLTAGE SWITCH
* DENOTES SWITCH NAME, SEE LIGHTING CONTROL PANEL &
SWITCH SCHEDULE.
L
SWITCH NOTATIONS:
3 DENOTES 3-WAY SWITCH
4 DENOTES 4-WAY SWITCH
WL DENOTES WET LOCATION SWITCH
D DENOTES DIMMER SWITCH
T DENOTES TIMMER SWITCH
K DENOTES KEY SWITCH
P DENOTES PILOT SWITCH
O DENOTES OCCUPANCY SENSOR
KEYED NOTE, USED TO DESCRIBE ADDITIONAL
INFORMATION OF WORK REQUIRED, SPECIFIC TO
THE SHEET AND/OR DETAIL IT IS SHOWN WITH.
DETAIL NUMBER / SHEET NUMBER#/E-###
9.###
GENERAL SYMBOLS
PANEL DESIGNATION KEY
FLOOR
2 L N L 1
TYPE
SYSTEM/SOURCE
VOLTAGE
SEQUENCE NUMBER OR LETTER
NUMBER OR LETTER IN SEQUENCE
I.E. 1,2,3 OR A,B,C
L - 208Y/120V H - 480Y/277V
N - NORMAL BRANCH
U - UNINTERRUPTIBLE
E - EMERGENCY BRANCH (NEC 700)
X - LEGALLY REQUIRED STANDBY BRANCH (NEC 701)
O - OPTIONAL STANDBY BRANCH (NEC 702)
L - LIGHTING PANEL BOARD
D - DISTRIBUTION PANEL BOARD
P - POWER/EQUIPMENT PANEL BOARD
R - RECEPTACLE PANEL BOARD
MS - MAIN SWITCHBOARD
MCC - MOTOR CONTROL CENTER
G - GROUND FLOOR
B - BASEMENT FLOOR
1 - FIRST FLOOR
P - PENTHOUSE
M - MEZZANINE
P
DUPLEX RECEPTACLE TEXT INDICATES MOUNTING HEIGHT
CEILING MOUNTED DOUBLE DUPLEX RECEPTACLE
SPLIT WIRED DUPLEX RECEPTACLE
SIMPLEX RECEPTACLE
DOUBLE DUPLEX RECEPTACLE
WELDING RECEPTACLE
DISCONNECT/WELDING RECEPTACLE
DISCONNECT/WELDING RECEPTACLE, NEMA 4X
CEILING MOUNTED DUPLEX RECEPTACLE
SPECIAL PURPOSE RECEPTACLE, NEMA TYPE ON
DRAWING
DATA/POWER POLE
ABOVE COUNTER DUPLEX RECEPTACLE
EMERGENCY SHADING MODIFIER
C
F FLOOR BOX
P POKE THRU
C
C
60"
DENOTES SWITCH LEG FOR SWITCHED OUTLETSa
RECEPTACLE NOTATIONS:
DENOTES DEDICATED OUTLETSD
DENOTES HORIZONTALLY MOUNTED OUTLETSH
DENOTES TAMPER RESISTANT SAFETY OUTLETSTR
DENOTES WEATHER PROOF OUTLETSWP
DENOTES EXPLOSION PROOF CLASS 1 DIVISION 2 OUTLETSX2
DENOTES EXPLOSION PROOF CLASS 1 DIVISION 1 OUTLETSX1
DENOTES GROUND FAULT INTERRUPTER OUTLETSGFCI
DENOTES COMBINATION DUPLEX/USB OUTLETSUSB
DENOTES ISOLATED GROUND OUTLETSIG
DENOTES ELECTRIC WATER COOLER OUTLETSEWC
4X
POWER FACTOR CORRECTION CAPACITORPFC
GROUND ACCESS WELL
GROUND ROD
ACTIVE HARMONIC FILTERAHF
NEW PANELBOARD
EXISTING PANELBOARD
EMERGENCY POWER OFFEPO
GENERATOR ANNUNCIATOR PANELGAP
LIGHTNING ROD
GROUND RECEPTACLE
GR
SWITCHBOARD (x REPRESENTS SWITCHBOARD DESIGNATION)SWBD-x
CUSTOMER METERING
UTILITY METER SOCKET
PMS
T
M
M
T
T
VFD
SS
M
SF
SM
1 PHASE MOTOR CONNECTION
EQUIPMENT CONNECTION
3 PHASE MOTOR CONNECTION
COMBINATION MAGNETIC MOTOR CONTROLLER
MANUAL MOTOR CONTROLLER (3 PHASE)
SOLID STATE MOTOR CONTROLLER
VARIABLE FREQUENCY MOTOR CONTROLLER
MAGNETIC MOTOR CONTROLLER
NON-FUSED DISCONNECT SWITCH
FUSED DISCONNECT SWITCH
DOUBLE THROW SWITCH
FUSED SINGLE POLE SWITCH
MOTOR RATED STARTER / DISCONNECT SWITCH
RECESSED LUMINAIRE
RECESSED TROFFER
RECESSED LINEAR
SURFACE LUMINAIRE
WALL MOUNTED EXIT SIGN
CEILING MOUNTED EXIT SIGN
SURFACE LINEAR
SURFACE COVE STRIP
PENDANT LUMINAIRE
ARROW DENOTES EXIT SIGN CHEVRON
EMERGENCY BATTERY UNIT
WALL WASH MODIFIER
EMERGENCY SHADING MODIFIER
(PARTIAL OR FULL SHADE)
PENDANT LINEAR
PENDANT INDUSTRIAL
TRACK
(# INDICATES NUMBER TRACK HEADS)
WALL BRACKET
WALL SURFACE LINEAR
WALL RECESSED LINEAR
RECESSED EMERGENCY BATTERY UNIT
A1 1Ra
LUMINAIRE TYPE
LUMINAIRE CIRCUITRY & CONTROL KEY:
LOWER CASE LETTER INDICATES SWITCHLEG CONTROL
"R" INDICATES LIGHTING CONTROL PANEL
REFER TO LIGHTING CONTROL PANEL SCHEDULE
NUMBER INDICATES BRANCH PANEL CIRCUIT NUMBER
NEW WORK BY THIS CONTRACTOR
(DARK SOLID LINE)
LINE TYPE KEY
EXISTING TO BE REMOVED BY THIS
CONTRACTOR (DARK DASHED LINE)
EXISTING TO REMAIN WORK
(THIN SOLID LINE)
NEW WORK UNDER FLOOR BY THIS
CONTRACTOR
SITE SYMBOLS
GROUND MOUNTED LIGHT
(ABOVE OR BELOW GRADE)
ELECTRIC HANDHOLE
HH HANDHOLE, GENERIC
SITE UNDERGROUND CONDUITCON
SITE REMOVED UNDERGROUND CONDUIT//CON//
SITE UNDERGROUND ELECTRICE
SITE OVERHEAD ELECTRICOHE
SITE REMOVED OVERHEAD ELECTRIC//OHE//
SITE REMOVED UNDERGROUND ELECTRIC//E//
E
E ELECTRIC MANHOLE
M ELECTRIC METER
TRANS
ELECTRIC SERVICE PANEL
ELECTRIC TRANSFORMER
ELECTRIC PEDESTAL BOX
FLOOD LIGHT POLE
BOLLARD LIGHT
DOUBLE LIGHT POLE
LIGHT POLE
POWER POLE
DOUBLE POWER POLE
POWER POLE WITH LIGHT
SURFACE METAL RACEWAY - REFER TO DRAWINGS
AND/OR SPECIFICATIONS, MOUNTED 6" ABOVE
COUNTER OR AT HEIGHT AS INDICATED.
MULTI-OUTLET RACEWAY - OUTLETS ON CENTER AS
INDICATED ON DRAWINGS AND IN THE SPECIFICATIONS,
MOUNTED 6" ABOVE COUNTER OR AT HEIGHT AS
INDICATED.
DENOTES 2'-0" LENGTH, RECEPTACLES 6" O.C.A
MULTI-OUTLET RACEWAY NOTATIONS:
DENOTES 3'-0" LENGTH, RECEPTACLES 6" O.C.B
DENOTES 6'-0" LENGTH, RECEPTACLES 6", 12", 18" OR 24" O.C.D
DENOTES X'-X" LENGTH, RECEPTACLES X" O.C.F
DENOTES 5'-0" LENGTH, RECEPTACLES 6" OR 12" O.C.C
CORD REELE
SWP STORM WATER PUMP
LSIG LONG, SHORT, INSTANTANEOUS, & GROUND FAULT TRIP
SPD SURGE PROTECTION DEVICE
RVSS REDUCED VOLTAGE SOFT STARTER
CD CONTROL DIAGRAM
NEW PUMP PROTECTION MODULEPPM
ONE-LINE SYMBOLS
N
L
E
ATO
MPR
AUTOMATIC THROW OVER
LOW VOLTAGE CIRCUIT BREAKER
CURRENT TRANSFORMER
(# DENOTES QUANTITY)
MULTI FUNCTION PROTECTIVE RELAY
DPM
DRAWOUT BREAKER WITH
CURRENT LIMITING FUSE
DRAWOUT BREAKER
LOW VOLTAGE FUSE
ST
PANELBOARD (ELEVATION VIEW)
# POTENTIAL TRANSFORMER
(# DENOTES QUANTITY)
ST
SPD
TRANSFORMER
MO
52 MEDIUM VOLTAGE DRAW-OUT CIRCUIT
BREAKER
MEDIUM VOLTAGE FUSED SWITCH
MEDIUM VOLTAGE SWITCH
MEDIUM VOLTAGE TERMINATION
N
NON-FUSED DISCONNECT SWITCH
NORMALLY CLOSED CONTACT
NORMALLY OPEN CONTACT
LA
EARTH GROUND
K# KEY INTERLOCK
LIGHTNING ARRESTORS
LOAD BREAK ELBOW
M
GF GROUND FAULT SHUNT TRIP SWITCH
GROUND FAULT SHUNT TRIP BREAKER
G C P
FUSED DISCONNECT SWITCH
GENERATOR
AUTOMATIC TRANSFER SWITCH
UNINTERRUPTIBLE POWER SUPPLY
(UPS)
UTILITY CONNECTION
DIGITAL POWER METER
METER
MOTOR OPERATOR
NEUTRAL BOND
OVERCURRENT PROTECTIVE RELAY
SHUNT TRIP
SURGE PROTECTIVE DEVICE
RS
MCS MASTER CONTROL STATION
REMOTE STATION
SWITCHBANK
SPECIAL PURPOSE CONNECTION, SEE EQUIPMENT
WIRING SCHEDULE
E-001
ELECTRICAL
SYMBOLS AND
LEGENDS
RJT
JCB
CZR
X :\1
\1
4.
\T E
C H
\C A
D \P
H A
S E
\E
-0
E
LE
C
TR
IC
A
L S
Y M
B O
LS
A
N D
L E
G E
N D
S .D
W G
8/
/2
5:
:0
P
M
1943400-190824.01
SEPTEMBER 29, 2026
SHEET CONTENTS
DO NOT SCALE DRAWINGS
M&H NO.:
DATE:
DESIGNED BY:
DRAWN BY:
CHECKED BY:
ISSUED
These documents shall not be used for any purpose or project for which it is not intended. Mead & Hunt shall be indemnified by the client and held harmless and defended from all claims, damages, liabilities, losses, and expenses, including attorneys' fees and costs, arising out of such misuse or reuse of the documents.
In addition, unauthorized reproduction of these documents, in part or as a whole, is prohibited.
Mead and Hunt, Inc.
180 Promenade Circle, Suite 240 Sacramento, CA 95834 phone: 916-971-3961 meadhunt.com
TE
X
A S
S
TR
E E
T
FA
IR
FI
E
LD
, C A
S O
LA
N
O C
O U
N
TY
D O
W N
TO
W
N F
A
IR
FI
E
LD
J
U S
TI
C
E C
A M
P U
S A
S S
E T
P R
O
TE
C
TI
O N
P R
O
JE
C T
VOLUME 1
2 07/17/2026 RFI 42
3 08/11/2026 RFI 22
8/11/2026
E-002
INSTRUMENT
SYMBOLS AND
LEGENDS
RJT
JCB
CZR
X :\1
\1
4.
\T E
C H
\C A
D \P
H A
S E
\E
-0
E
LE
C
TR
IC
A
L S
Y M
B O
LS
A
N D
L E
G E
N D
S .D
W G
8/
/2
5:
:0
P
M
1943400-190824.01
SEPTEMBER 29, 2026
SHEET CONTENTS
DO NOT SCALE DRAWINGS
M&H NO.:
DATE:
DESIGNED BY:
DRAWN BY:
CHECKED BY:
ISSUED
These documents shall not be used for any purpose or project for which it is not intended. Mead & Hunt shall be indemnified by the client and held harmless and defended from all claims, damages, liabilities, losses, and expenses, including attorneys' fees and costs, arising out of such misuse or reuse of the documents.
In addition, unauthorized reproduction of these documents, in part or as a whole, is prohibited.
Mead and Hunt, Inc.
180 Promenade Circle, Suite 240 Sacramento, CA 95834 phone: 916-971-3961 meadhunt.com
TE
X
A S
S
TR
E E
T
FA
IR
FI
E
LD
, C A
S O
LA
N
O C
O U
N
TY
D O
W N
TO
W
N F
A
IR
FI
E
LD
J
U S
TI
C
E C
A M
P U
S A
S S
E T
P R
O
TE
C
TI
O N
P R
O
JE
C T
VOLUME 1
2 07/17/2026 RFI 42
3 08/11/2026 RFI 22
1. THIS IS A GENERAL LEGEND SHEET. SOME SYMBOLS AND
ABBREVIATIONS MAY NOT APPLY TO THIS SPECIFIC
PROJECT.
2. THE SYMBOLS SHOWN ARE GENERALLY BASED ON THE
INSTRUMENT SOCIETY OF AMERICA'S STANDARDS. SOME
ADDITIONS AND ALTERATIONS MAY HAVE BEEN MADE TO
ACCOMMODATE SPECIFIC PROJECT REQUIREMENTS.
3. SOME PROCESS ITEMS (EQUIPMENT, VALVES, LINES,
FITTINGS, ETC.) THAT ARE NOT CRITICAL FOR THE OVERALL
UNDERSTANDING OF THE INSTRUMENTATION AND CONTROL
SYSTEM FUNCTIONS ARE NOT SHOWN FOR CLARITY.
4. REFER TO THE ELECTRICAL DRAWINGS AND
SPECIFICATIONS FOR ADDITIONAL CONTROLS, INTERLOCKS
AND OTHER REQUIREMENTS FOR EQUIPMENT THAT MAY
NOT BE SUPPLIED BY THE SYSTEMS INTEGRATOR.
GENERAL NOTES:
INSTRUMENTATION & CONTROL SYMBOL SCHEDULE
ABBREVIATIONS
A AUTOMATIC
ABS ABSOLUTE
AI ANALOG INPUT
AO ANALOG OUTPUT
ALT ALTERNATE
AS AIR SUPPLY
AVG AVERAGE
CAP CAPACITANCE
CHW CHILLED WATER
CO CARBON MONOXIDE
CO2 CARBON DIOXIDE
COND CONDUCTIVITY
COR CORIOLIS
CP CONTROL PANEL
CS CONTROL STATION
DEN DENSITY
DI DIGITAL INPUT
DO DIGITAL OUTPUT
DO DISSOLVED OXYGEN
DOP DOPPLER
DP DIFFERENTIAL PRESSURE
DW DRINKING WATER
ETR EXISTING TO REMAIN
FC FAIL CLOSED
FO FAIL OPEN
GC GAS CHROMATOGRAPH
GWR GUIDED WAVE RADAR
H HAND
H2S HYDROGEN SULFIDE
H2O WATER
HMI HUMAN MACHINE INTERFACE
HOA HAND - OFF - AUTO
HP HORSEPOWER
IR INFRARED
L LOCAL
LC LIQUID CHROMATOGRAPH
LC LOAD CELL
LEL LOWER EXPLOSIVE LIMIT
LOR LOCAL - OFF - REMOTE
LSI LONG, SHORT, & INSTANTANEOUS
M MODULATE
MAG MAGNETIC
MCC MOTOR CONTROL CENTER
MM MULTI-MODE FIBER OPTIC CABLE
MS MASS SPECTROMETER
NIC NOT IN CONTRACT
NC NETWORK CABINET OR NORMALLY CLOSED
NTS NOT TO SCALE
NUC NUCLEAR
O2 OXYGEN
OP OPACITY
ORP OXIDATION REDUCTION POTENTIAL
PE PHOTOELECTRIC
pH HYDROGEN ION CONCENTRATION
PLC PROGRAMMABLE LOGIC CONTROLLER
PROX PROXIMITY
RAD RADAR
REF REFRACTOMETER
REQ'D REQUIRED
RI REFRACTIVE INDEX
RTD RESISTANCE TEMPERATURE DETECTOR
RTU REMOTE TELEMETRY UNIT
RW RAW WATER
SCADA SUPERVISORY CONTROL AND DATA ACQUISITION
SG SPECIFIC GRAVITY
SG STRAIN GAUGE
SM SINGLE-MODE FIBER OPTIC CABLE
SNR SONAR
SON SONIC
SP SET POINT
SPD SURGE PROTECTION DEVICE
SS STAINLESS STEEL
TC THERMAL CONDUCTIVITY
TC THERMOCOUPLE
TYP TYPICAL
UON UNLESS OTHERWISE NOTED
US ULTRASONIC
UV ULTRAVIOLET
VAC VACUUM
VENT VENTURI TUBE
VIS VISIBLE LIGHT
VISC VISCOSITY
VFD VARIABLE FREQUENCY DRIVE
VOR VORTEX SHEDDING
WS WEIGH SCALE
WW WASTEWATER
WP WEATHERPROOF
XP EXPLOSION PROOF
LINE TYPESGENERAL SYMBOLS
INSTRUMENT - FIELD MOUNTED
YY = INSTRUMENT IDENTIFCATION
XXXX = LOOP NUMBER
Z = IDENTIFIER FOR MEASUREMENT/ANALYSIS
INSTRUMENT - PANEL MOUNTED
INSTRUMENTS SHARING A COMMON HOUSING
CONTROL INTERLOCK (HARDWIRE)
I/O POINT FOR SHARED CONTROL & DISPLAY IN
SCADA/DCS
CONTROL SEQUENCE OF OPERATIONS FOR
EQUIPMENT AS DETAILED IN THE SPECIFICATIONS
PROCESS/SIGNAL LINE OFF PAGE
CONTINUATION
YYY = SERVICE, XXX = SHEET NUMBER
DDD = DESCRIPTION
TIE-IN POINT
VALVES
GATE
PLUG
GLOBE
BALL
BUTTERFLY
3-WAY
4-WAY
CHECK
DIAPHRAGM
PINCH
NEEDLE
ANGLE
SOLENOID
CONCENTRIC REDUCERMOTOR OPERATED
PRESSURE REGULATING
TP
XX
INSULATED PROCESS LINE
YxX
ECCENTRIC REDUCER
YxX
YY
XXXX
YY
XXXX
YY
XXXX
YY
XXXX
CS
YY
XXXX
PILOT LIGHT
FLOW METERS
ORIFICE PLATEFE
XXXX
M
MAGNETIC
FE
XXXX
TURBINE
FE
XXXX
VORTEX
FE
XXXX
ROTAMETER
FE
XXXX
ULTRASONICFE
XXXX
VENTURIFE
XXXX
PARSHALL FLUMEFE
XXXX
WEIRFE
XXXX
AIR RELEASE (AR)
AIR/VACUUM (AV)
COMBINATION (CAV)
PRESSURE SUSTAINING
SLIDE GATE (SLG)
KNIFE GATE (KNG)
SLUICE GATE (SCG)
PNEUMATIC OPERATED
HYDRAULIC OPERATED
CONTROL STATIONS
SELECTOR SWITCH, YYY = FUNCTION DESCRIPTION
FOR FORWARD-OFF-REVERSE
FOJR FORWARD-OFF-JOG REVERSE
HOA HAND-OFF-AUTO
HOR HAND-OFF-REMOTE
HOSB HAND-OFF-STANDBY
LOR LOCAL-OFF-REMOTE
KYPD KEYPAD
MOA MANUAL-OFF-AUTO
OC OPEN-CLOSE
OCR OPEN-CLOSE-REMOTE
OO ON-OFF
OSC OPEN-STOP-CLOSE
RO RUN-OFF
TOD TRANSFER-OFF-DILUTION
HS
HK
YL
YYY
YYY
PUSH BUTTON, YYY = FUNCTION DESCRIPTION
CLS CLOSE
ESTOP EMERGENCY STOP
LT LAMP TEST
OPN OPEN
RS RESET FAULT
SIL SILENCE ALARM
STR START
STP STOP
STPL STOP WITH LOCOUT
SK
SPEED CONTROL POTENTIOMETER
INDICATING LIGHT, YY = COLOR CODE
GR GREEN (OFF, STOP, CLOSED)
RD RED (RUN, START, OPEN)
WH WHITE (POWER ON)
BL BLUE (STATUS)
AM AMBER (ALARM CONDITION)
YY
YL
STROBE LIGHT, YY = COLOR CODEYY
ELECTRONIC HORN
EYEWASH STATION
PROCESS EQUIPMENT
PIPING
CENTRIFUGAL PUMP
HORIZONTAL TANK
VERTICAL TANK
Y-STRAINER
VENT
DIAPHRAGM SEAL WITH
ISOLATION VALVE
FLEXIBLE CONNECTION
QUICK CONNECT
PERISTALTIC PUMP
ROTARY LOBE PUMP
SUBMERSIBLE PUMP
LEVEL
VERTICAL
TURBINE PUMP
METERING PUMP
DRAIN
LS
FLOAT SWITCH
MIXER
LE
XXXX
NON CONTACT TYPE
(ULTRASONIC OR RADAR)
AIR RELIEF VALVE (ARV)
BLOWER
SIGHT GAUGE
PULSATION DAMPENER
WITH ISOLATION VALVE
CALIBRATION COLUMN
LG
XXXX
MAGNETIC
LEVEL GAUGE
LG
XXXX
EXTERNAL
CHAMBER
LE
XXXX
M MOTOR
M
M
M
M
M
M
M
M
XXXYYY DDD
Z
XXXX
Z
ACS
ACTUATOR CONTROL STATION
CONTROL STATION SYMBOL USED FOR AUTOMATED
VALVES AND/OR ACTUATORS. FUNCTIONS
INDICATED ON THE P&ID
YYY = MOD = MODULATING VALVE OPERATION
YYY = O/O = ON/OFF VALVE OPERATION
YYY = 3W = 3-WAY VALVE OPERATION
VFD
VARIABLE FREQUENCY DRIVE
SYMBOL USED TO INDICATE CONNECTION TO A
VARIABLE FREQUENCY DRIVE. INCLUDES THE
FOLLOWING TYPICAL FUNCTIONS:
STR
STP
HS
IN
AUTO
YIA
RUN
IND
YIR
MOTOR
OL
XA
SPD
CTRL
SC SI
SPD
IND
MOTOR STARTER
VFD
XXXX
STR
SYMBOL USED TO INDICATE CONNECTION TO A
MOTOR STARTER. INCLUDES THE FOLLOWING
TYPICAL FUNCTIONS:
STR
STP
HS
IN
AUTO
YIA
RUN
IND
YIR
MOTOR
OL
XA
STR
XXXX
YYY
PRIMARY PROCESS LINE
SECONDARY PROCESS LINE
EXISTING PROCESS LINE
ELECTRIC SIGNAL (ANALOG)
SOFTWARE LINK, COMMUNICATION LINK
FIBER OPTIC COMMUNICATIONFOC
ELECTRIC SIGNAL (DISCRETE)
ARROWHEAD INDICATES DIRECTION OF FLOW OR INPUT VS OUTPUT
ELECTRIC SIGNAL (DISCRETE & ANALOG)
INSTRUMENT IDENTIFICATION MATRIX
FIRST LETTER SUCCEEDING LETTERS
A ANALYSIS
8/11/2026
E-011
SINGLE LINE DIAGRAM
- LIFTSTATION MCC
RJT
JCB
CZR
X :\1
\1
4.
\T E
C H
\C A
D \P
H A
S E
\E
-0
S
IN
G
LE
L
IN
E D
IA
G
R A
M
N E
W M
C C
.D W
G
8/
/2
5:
:0
P
M
1943400-190824.01
SEPTEMBER 29, 2026
SHEET CONTENTS
DO NOT SCALE DRAWINGS
M&H NO.:
DATE:
DESIGNED BY:
DRAWN BY:
CHECKED BY:
ISSUED
These documents shall not be used for any purpose or project for which it is not intended. Mead & Hunt shall be indemnified by the client and held harmless and defended from all claims, damages, liabilities, losses, and expenses, including attorneys' fees and costs, arising out of such misuse or reuse of the documents.
In addition, unauthorized reproduction of these documents, in part or as a whole, is prohibited.
Mead and Hunt, Inc.
180 Promenade Circle, Suite 240 Sacramento, CA 95834 phone: 916-971-3961 meadhunt.com
TE
X
A S
S
TR
E E
T
FA
IR
FI
E
LD
, C A
S O
LA
N
O C
O U
N
TY
D O
W N
TO
W
N F
A
IR
FI
E
LD
J
U S
TI
C
E C
A M
P U
S A
S S
E T
P R
O
TE
C
TI
O N
P R
O
JE
C T
VOLUME 1
2 07/17/2026 RFI 42
3 08/11/2026 RFI 22
SINGLE LINE DIAGRAM - LIFT STATION MCC1 SCALE: NTS
NOTES:
1. SEE SHEET E-021 FOR PNL #1 PANEL SCHEDULE.
2. MOTOR POWER CABLES TO BE ROUTED INTO NEARBY JUNCTION
BOX AND ROUTED BACK TO MCC.
3. GENERATOR LOAD TO BE CONTROLLED BY COUNTY BMS.
BACNET CONNECTION TO RUN FROM MCC TO CO-GEN PLANT.
4. CONTRACTOR TO INTERCEPT EXISTING 500KW GENERATOR
CONDUIT AND INSTALL JUNCTION BOX. CONTRACTOR TO PULL
CONDUIT BACK TO EXISTING JUNCTION BOX. CONTRACTOR TO
PULL CONDUCTORS BACK TO GENERATOR. SEE SHEET E-111
FOR PLAN VIEW.
5. CONTRACTOR TO SPLICE MANUFACTURER PROVIDED CABLES
TO CONTRACTOR PROVIDED CABLES IN JUNCTION BOX.
6. SEE E-118 FOR CONDUIT AND CONDUCTOR SCHEDULE.
150A 3P
480V, 3 PHASE, 3 WIRE, 800AMP BUS, 42kAIC
150A 3P
30A 3P
SWP 4
(BASIN SUMP)
EXTERIOR LIFT STATION CONTROL PANELCOUNTY PUMP STATION CONTROL PANEL
150A 3P
TAG: LS-T1
SIZE: 15KVA,
PRI: 480V, 1PH, 2-WIRE
SEC: 120-240V, 1PH, 3-WIRE
70A 2P
40A 2P 150A
3P 150A 3P
150A 3P
TERMINAL JUNCTION BOX 2
SWP 5 SWP 6 SWP 7SWP 3
10HP 50HP50HP 50HP50HP
P106 P104 P102P105P108P107
CONTROL POWER FROM PNL #1, CIRCUIT 7CONTROL POWER FROM PNL #1, CIRCUIT 9
RVSS RVSS RVSSRVSS RVSS RVSS
POWER
METER
SEE NOTE 6SEE NOTE 6
TERMINAL JUNCTION BOX 3
SWP 2
50HP
SWP 1
50HP
FVNR
PROVIDED BY MANUFACTURER (TYP)
SEE NOTE 2
PANEL #1
SPD
GROUND
P100
ATS
800 AMP
3-POLE
G
SEE NOTES 3 AND 4
PROVIDE ALL REQUIRED
STARTING CIRCUITS
BETWEEN ATS AND
GENERATOR IN CONDUIT.
TERMINAL JUNCTION BOX 1
P101
SEE NOTE 5
CONNECTED LOAD: 374KVA, 449.8AMPS
DEMAND LOAD: 375KVA, 451AMPS
P109
PUMP MCC, NEMA 3R ENCLOSURE
800A 3P
LSIG
POWER
METER
CT AND METER CABINET
IN ACCORDANCE WITH COUNTY
STANDARDS
SEE NOTE 1
120/240V, 1 PH, 3W
EXISTING 500KVA
DIESEL STANDBY GENERATOR,
480V 3PH 3 W
FROM EXISTING CO-GEN BOARD
SEE E-013 FOR CONTINUATION
30A 3P
8/11/2026
E-021
LIFT STATION MCC
LAYOUT AND
SCHEDULE
RJT
JCB
CZR
X :\1
\1
4.
\T E
C H
\C A
D \P
H A
S E
\E
-0
M C
C L
A Y
O U
T A
N D
S C
H E
D U
LE
.D
W G
8/
/2
5:
:1
P
M
1943400-190824.01
SEPTEMBER 29, 2026
SHEET CONTENTS
DO NOT SCALE DRAWINGS
M&H NO.:
DATE:
DESIGNED BY:
DRAWN BY:
CHECKED BY:
ISSUED
These documents shall not be used for any purpose or project for which it is not intended. Mead & Hunt shall be indemnified by the client and held harmless and defended from all claims, damages, liabilities, losses, and expenses, including attorneys' fees and costs, arising out of such misuse or reuse of the documents.
In addition, unauthorized reproduction of these documents, in part or as a whole, is prohibited.
Mead and Hunt, Inc.
180 Promenade Circle, Suite 240 Sacramento, CA 95834 phone: 916-971-3961 meadhunt.com
TE
X
A S
S
TR
E E
T
FA
IR
FI
E
LD
, C A
S O
LA
N
O C
O U
N
TY
D O
W N
TO
W
N F
A
IR
FI
E
LD
J
U S
TI
C
E C
A M
P U
S A
S S
E T
P R
O
TE
C
TI
O N
P R
O
JE
C T
VOLUME 1
2 07/17/2026 RFI 42
3 08/11/2026 RFI 22
LIFT STATION MCC - NEMA 3R ENCLOSURE NOT SHOWN
FRONT VIEW1
PNL #1 LOAD SCHEDULE2
PANELBOARD…