This is Addendum No. 1 to the solicitation for Lamar Community College (LCC) project 2026-032M25, prepared by Schendt Engineering Corporation on February 20, 2026. The addendum addresses clarifications and provides documentation from a pre-bid walk-through meeting regarding the replacement of a natural gas line serving the Bowman and Trustees buildings at LCC's Colorado campus. The addendum includes four primary attachments: a pre-bid attendance sign-in sheet, responses to bidder questions and clarifications, a utility location map identifying irrigation mains, fiber optics, HVAC hydronic lines, and water mains, and a storage areas map designating available laydown space on campus. No revisions to project specifications or drawings were issued with this addendum.

Key clarifications from the pre-bid meeting address scope responsibilities, operational requirements, and site logistics. LCC will be responsible for relighting appliances affected by gas system shutdown and for purging interior building lines; the contractor is responsible for purging lines from the meter to building connections. Only exterior gas lines require pressure testing at four building locations (Trustees, Bowman, Administration, and CTE buildings). All potholing and boring activities, including spoils removal and off-site disposal, fall within the contractor's scope with no additional compensation permitted. Main campus sidewalks must remain accessible to student pedestrians throughout construction. The contractor must coordinate utility shutdowns with the facility owner 30 days in advance and may use any day or time weather permitting. Tracer wire continuity testing is required. Prevailing wage and wage reporting requirements apply only if the project exceeds $500,000.00 per Colorado Revised Statutes 24-92-201 through 210. Contact information for Atmos Energy coordination is provided as Thomas Gomez at thomas.gomez@atmosenergy.com, (719) 688-1603.

View the file

Other files

Show all 11

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Schendt Engineering Corporation

5145 Centennial Blvd. Suite 200 (719) 637-8850 Colorado Springs, CO 80919 www.secengr.com

2026-032M25 LCC Replace Gas Addendum no. 1.docx Page 1 of 1

Addendum No. 1

Date: 2-20-2026

Project: Lamar Community College Replace Natural Gas Line, Bowman & Trustees

Project No.: 2026-032M25 25173 (SEC Project No.)

GENERAL:

1. Providing prebid attendance sign in sheet

2. Answer to bidders questions and clarifications from the Prebid

3. Additional utility map provided by LCC

4. Staging and storage area map provided by LCC

ATTACHEMENTS:

1. Prebid walk through sign in sheet

2. Request for Clarification & Answers

3. LCC: General Utility Locations

4. LCC: Storage Areas

REVISIONS TO THE SPECIFICATIONS:

1. N/A

REVISIONS TO THE DRAWINGS:

1. N/A

Schendt Engineering Corporation 5145 Centennial Blvd. Suite 200., Colorado Springs, CO, 80919

Request for Clarifications Project: LCC Replace Natural Gas Line, Bowman & Trustees

Project No.: 2026-032M25 (25173 SEC)

Reported By: (LCC) Sean Lirley; (SMH) Brett Louk, PE; (SEC) Dane Oates, EIT; (SEC) Ken Merola, PE

Date: 2-20-2026

Question: Response:

1. Please confirm owner is responsible for relighting any appliances effected by the shutdown of the gas system

LCC will be responsible for relighting all appliances.

2. Will a licensed plumber will be required for pressure testing the existing building's interior piping?

a. Is there a rough count of how many valves will need to be closed and opened for these tests?

b. If there are leaks in the existing building piping will this be considered outside of the scope of work?

2. No interior gas piping is to be pressure tested, only exterior gas line being replaced need to be pressure tested.

a. (4) Valves at building exterior – Trustees, Bowman, Administration, & CTE buildings

b. Outside the scope of this project.

3. Is there a known number of mandatory pothole locations as discussed during the site walk?

a. Unit cost as alternate for additional required?

There is no known number of mandatory pothole locations. Contractor is responsible to include all potholing activities related to gas line installation. No additional cost for additional potholing is permitted. Ref: 33 05

23.13 3.1 B & C, 33 51 15 3.1 C.

4. Is there a rough map showing existing utilities? See attached map of approximate utility locations provided by the facility.

5. How much of the parking lot is available for laydown?

See attached map with storage and laydown areas available.

6. Is there a location on site to dispose of potholing and boring spoils?

No, potholing and boring spoils must be hauled off site. Ref: 33 05 23.13 3.1 A 11 & D 4.

7. Is there a contact at Atmos that we can talk with to coordinate the meter tie in?

Thomas Gomez thomas.gomez@atmosenergy.com

(719) 688-1603

8. Intent of project is to bore, should open trench be required what is expected level of restoration and will these be considered an add alt?

If trenched, LCC’s expectation is that grass sod be restored to original condition. Grass seed not acceptable. Ref: 32 90 00 2.10 A.

9. What days/times are allowed to shutdown buildings for new gas tie ins?

Any day or time, weather permitting.

Coordinate utility shutdowns with owner 30 days in advance of the utility outage. Ref: 01 10 00 1.7 A 6.

10. Is the contractor purging air from the line up to point of connection?

Contractor shall purge air from gas line meter to building connections. Owner to purge lines inside buildings for appliances.

Observation Report (continued)

Sheet 2 of 2

11. Is tracer wire testing required? Tracer wire continuity testing is required.

Ref: 33 05 23.13 3.4 B 1.

12. Will we be required to provide right of way paths for student pedestrians to traverse the campus?

Yes, the main sidewalks will need to remain open. Ref: 01 10 00 1.8 A 1.

13. Is the project prevailing wage and/or wage reporting?

Prevailing wage and wage reporting only applies if the project exceeds $500,000.00 C.R.S. 24-92-201 through 210.

End of Clarifications

F o r G e n e ra l L o c a ti o n

O n ly

G re e n

I rr ig a ti o n

M a in

R e d

F ib e r

O p ti c s

P u rp le

H

V A

C H y d ro n ic L in e

B lu e

W a te r M a in

S to ra ge

A re a

Addendum no. 1
PreBid Clarifications 2-20-2026
For General Utility Location Only
Storage Areas

File details come from the government source that posted it. Updated .