20251219_MHAFB B2318 Fire Alarm Repair_100 Design Drawings.pdf

PDF 8 MB Posted

Attached to
Fire Alarm Replacement Bldg 2318 & 2416
Solicitation number
FA489726Q0007
Issued by

About this file

This is a 100% Design Submittal for a fire alarm system replacement project at Mountain Home Air Force Base in Idaho. The project, identified as Delivery Order FA4897-25-F-0017 under Master Contract FA4897-20-D-0001, involves the complete demolition and replacement of the existing fire alarm system in Building 2318, a three-level dormitory facility. The design submittal, prepared by HDR Engineering, Inc., comprises 22 sheets of detailed architectural and engineering drawings, including demolition plans, floor plans with device locations, typical installation details, sequence of operations matrices, riser diagrams, and voice message schedules. The project includes installation of a Silent Knight 6820 EVS Fire Alarm and Mass Notification Control Unit, addressable smoke and heat detectors, manual pull stations, speaker systems for both fire alarm and mass notification purposes, notification appliance circuits, emergency voice systems, and base-wide monitoring integration via an existing AES IntelliNet 2.0 mesh network.

The design incorporates comprehensive fire alarm and mass notification capabilities across all building levels, with specific provisions for dormitory room sounder bases at 520 Hz frequency, low-frequency audible appliances in sleeping areas, and coordinated voice messaging for fire emergencies, carbon monoxide detection, active shooter lockdown, bomb threats, weather warnings, and system tests. The design includes dedicated 120 VAC power provisioning with surge protection, dedicated breaker protection, proper cable routing and separation per National Electrical Code standards, and firestopping for all fire and smoke-rated penetrations. Construction requirements specify full building vacation during work, restoration of staging areas to original condition, coordination of haul routes and laydown yards with the Contracting Officer, and implementation of best management practices for environmental protection.

View the file

Other files

Show all 19

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

IDAHO

MOUNTAIN HOME

BOISE

GRAND VIEW

BRUNEAU

NAMPA

TO

WINNEMUCCA, NV

TO PORTLAND, OR

SEATTLE, WA

TO ELKO, NV

MOUNTAIN

HOME AFB

IDAHO

TO SALT

LAKE

CITY, UT

PROJECT

LOCATION

D

EL

IV

ER

Y O

R D

ER

N

O

D

ES

IG

N

ED

B

Y:

D

ES

C R

IP

TI

O N

M

AR

K

SI

ZE

SU

BM

IT

TE

D B

Y:

D

AT

E

C O

N

TR

AC

T

N U

M

BE

R

C H

EC

KE

D B

Y:

D R

AW

N

B Y:

IS

SU

E D

AT

E:

G

2 3 4 5 6 7 8 9 10

F

E

D

C

B

A SHEET ID

H D

R E ng in ee rin g, In c.

E.

P

AR

KC

EN

TE

R B

LV

D

BO

IS

E, ID

(2

) 3

-7

U .S

. A

IR

F O

R C

E

C

ES

/C

EN

M O

U N

TA

IN

H O

M E

AI

R

F O

R C

E

BA

SE

M

O U

N

TA

IN

H

O M

E, ID

AH

O

FA

-2

0- D

-0

D

EC

EM

BE

R

PR

O

JE

C

T N

U M

BE

R

SH

EE

T N

U M

BE

R

AN

SI

D

FA

-2

5- F-

M O

U N

TA

IN

H O

M E

AI

R

F O

R C

E

BA

SE

B2

FI

R

E

AL

AR

M

R

EP

AI

R

100% DESIGN SUBMITTAL

O

F

Z.

S

AC

H

SE

N

M

AI

ER

W . C

U N

AR

D

R . R

IC

H

TE

R

P.

D

ER

R

C O

VE

R

S H

EE

T

G001 B2318

ISSUE DATE:

DELIVERY ORDER NO.:

CONTRACT NO.:

366 CES/CEN

FA4897-25-F-0017

19 DECEMBER 2025

FA4897-20-D-0001

MOUNTAIN HOME AIR FORCE BASE, ID

REPLACE FIRE ALARM SYSTEM, BLDG 2318

100% DESIGN SUBMITTAL

SHEET INDEX

NO. SHEET NO. SHEET NAME

1 G001 COVER SHEET

2 G002 CONTRACTOR HAUL ROUTE

3 FA001 GENERAL FIRE ALARM AND DEMOLITION NOTES

4 FA002 SYMBOLS LEGEND AND CODE ANALYSIS

5 FD101A LEVEL ONE DEMOLITION PLAN - AREA A - FIRE ALARM

6 FD101B LEVEL ONE DEMOLITION PLAN - AREA B - FIRE ALARM

7 FD102A LEVEL TWO DEMOLITION PLAN - AREA A - FIRE ALARM

8 FD102B LEVEL TWO DEMOLITION PLAN - AREA B - FIRE ALARM

9 FD103A LEVEL THREE DEMOLITION PLAN - AREA A - FIRE ALARM

10 FD103B LEVEL THREE DEMOLITION PLAN - AREA B - FIRE ALARM

11 FA101A LEVEL ONE FLOOR PLAN - AREA A - FIRE ALARM AND MASS NOTIFICATION SYSTEM

12 FA101B LEVEL ONE FLOOR PLAN - AREA B - FIRE ALARM AND MASS NOTIFICATION SYSTEM

13 FA102A LEVEL TWO FLOOR PLAN - AREA A - FIRE ALARM AND MASS NOTIFICATION SYSTEM

14 FA102B LEVEL TWO FLOOR PLAN - AREA B - FIRE ALARM AND MASS NOTIFICATION SYSTEM

15 FA103A LEVEL THREE FLOOR PLAN - AREA A - FIRE ALARM AND MASS NOTIFICATION SYSTEM

16 FA103B LEVEL THREE FLOOR PLAN - AREA B - FIRE ALARM AND MASS NOTIFICATION SYSTEM

17 FA501 FIRE ALARM AND MASS NOTIFICATION SYSTEM TYPICAL DETAILS

18 FA502 FIRE ALARM AND MASS NOTIFICATION SYSTEM TYPICAL DETAILS

19 FA503 FIRE ALARM AND MASS NOTIFICATION SYSTEM TYPICAL DETAILS

20 FA601 FIRE ALARM AND MASS NOTIFICATION SYSTEM SEQUENCE OF OPERATION MATRIX

21 FA602 FIRE ALARM AND MASS NOTIFICATION SYSTEM RISER DIAGRAM

22 FA603 FIRE ALARM AND MASS NOTIFICATION SYSTEM VOICE MESSAGES

12/19/2025

12 DEC 2025

LIBERATOR STREET

AARDVARK AVENUE

FALCON STREET

ALPINE STREET

BOMBER STREET

RUNWAY 12-30

PHANTOM AVENUE

CIVIL ENGINEERING

BUILDING 1300

SECURITY FORCES

FIRE DEPT.

BUILDING 206

RECYCLING CENTER

BASE EXCHANGE (BX)

HOSPITAL

AAFES SERVICE STATION

MAIN GATE

PERIMETER ROAD OFF HIGHWAY 167 (GRAND VIEW ROAD)

GRAND VIEW GATE

(CONTRACTOR ACCESS)

GUNFIG

HTER AVENUE

2N

D AVENUE

1S

T AVENUE

WING HQ

BUILDING 512

th

AVENUE

PROJECT AREA,

SEE ENLARGED

PLAN, THIS SHEET

PE

R

IM

ET

ER

R

O

AD

FAC 3490 HEADWORKS

B2318

D

EL

IV

ER

Y O

R D

ER

N

O

D

ES

IG

N

ED

B

Y:

D

ES

C R

IP

TI

O N

M

AR

K

SI

ZE

SU

BM

IT

TE

D B

Y:

D

AT

E

C O

N

TR

AC

T

N U

M

BE

R

C H

EC

KE

D B

Y:

D R

AW

N

B Y:

IS

SU

E D

AT

E:

G

2 3 4 5 6 7 8 9 10

F

E

D

C

B

A SHEET ID

H D

R E ng in ee rin g, In c.

E.

P

AR

KC

EN

TE

R B

LV

D

BO

IS

E, ID

(2

) 3

-7

U .S

. A

IR

F O

R C

E

C

ES

/C

EN

M O

U N

TA

IN

H O

M E

AI

R

F O

R C

E

BA

SE

M

O U

N

TA

IN

H

O M

E, ID

AH

O

FA

-2

0- D

-0

D

EC

EM

BE

R

PR

O

JE

C

T N

U M

BE

R

SH

EE

T N

U M

BE

R

AN

SI

D

FA

-2

5- F-

M O

U N

TA

IN

H O

M E

AI

R

F O

R C

E

BA

SE

B2

FI

R

E

AL

AR

M

R

EP

AI

R

100% DESIGN SUBMITTAL

O

F

Z.

S

AC

H

SE

N

M

AI

ER

B.

C

U N

AR

D

R . R

IC

H

TE

R

P.

D

ER

R

C O

N

TR

AC

TO

R H

AU

L

R O

U

TE

G002 B2318

CONTRACTOR ACCESS/HAUL ROUTE

BUILDING OF INTEREST

GENERAL NOTES

LEGEND

A1 CONTRACTOR ACCESS AND HAUL ROUTE

SCALE: 1" = 1000' 0 1000 2000 A6 PROJECT AREA

SCALE: 1" = 100' 0 100 200

PLAN

NORTH

PLAN

NORTH

1. RESTORE STAGING AND STORAGE AREAS TO ORIGINAL CONDITION AND TO THE

SATISFACTION OF THE CONTRACTING OFFICER.

2. 30 DAYS MINIMUM PRIOR TO MOBILIZATION, THE CONTRACTOR IS RESPONSIBLE

FOR SUBMITTING A CONTRACTOR LAYDOWN YARD REQUEST TO THE BASE

COMMUNITY PLANNER FOR COORDINATION AND APPROVAL (THIS INCLUDES

STOCKPILE LOCATIONS).

3. IMPLEMENT BEST MANAGEMENT PRACTICES (BMPS) PRIOR TO COMMENCING

CONSTRUCTION ACTIVITIES.

4. COORDINATE HAUL ROUTES, LAYDOWN AREAS, AND UTILITY CONNECTIONS

WITH THE CONTRACTING OFFICER FOR APPROVAL.

FALCON AVE.

B2318

D

EL

IV

ER

Y O

R D

ER

N

O

D

ES

IG

N

ED

B

Y:

D

ES

C R

IP

TI

O N

M

AR

K

SI

ZE

SU

BM

IT

TE

D B

Y:

D

AT

E

C O

N

TR

AC

T

N U

M

BE

R

C H

EC

KE

D B

Y:

D R

AW

N

B Y:

IS

SU

E D

AT

E:

G

2 3 4 5 6 7 8 9 10

F

E

D

C

B

A SHEET ID

H D

R E ng in ee rin g, In c.

E.

P

AR

KC

EN

TE

R B

LV

D

BO

IS

E, ID

(2

) 3

-7

U .S

. A

IR

F O

R C

E

C

ES

/C

EN

M O

U N

TA

IN

H O

M E

AI

R

F O

R C

E

BA

SE

M

O U

N

TA

IN

H

O M

E, ID

AH

O

FA

-2

0- D

-0

D

EC

EM

BE

R

PR

O

JE

C

T N

U M

BE

R

SH

EE

T N

U M

BE

R

AN

SI

D

FA

-2

5- F-

M O

U N

TA

IN

H O

M E

AI

R

F O

R C

E

BA

SE

B2

FI

R

E

AL

AR

M

R

EP

AI

R

100% DESIGN SUBMITTAL

O

F

Z.

S

AC

H

SE

N

M

AI

ER

W . C

U N

AR

D

R . R

IC

H

TE

R

P.

D

ER

R

D

EM

O

LI

TI

O

N N

O

TE

S G

EN

ER

AL

F

IR

E

AL

AR

M A

N D

FA001

B2318

GENERAL FIRE ALARM AND MASS NOTIFICATION NOTES GENERAL FIRE ALARM DEMOLITION NOTES

1. THE EXISTING CONDITIONS AND DEMOLITION PLANS WERE DEVELOPED BASED

ON RECORD DRAWINGS AND FIELD VERIFICATION WHERE POSSIBLE.

CONTRACTOR SHALL ALLOW FOR VARIANCES IN DEVICES DEPICTED ON

DEMOLITION DRAWINGS AND UNFORESEEN CONDITIONS.THE CONTRACTOR

SHALL NOTIFY THE CONTRACTING OFFICER OR CONTRACTING OFFICER'S

REPRESENTATIVE (COR) OF DISCREPANCIES AND UNDOCUMENTED

CONDITIONS PRIOR TO INITIATING WORK.

2. CONTRACTOR SHALL BE RESPONSIBLE FOR PROTECTING ALL EXISTING

CONDITIONS INCLUDING BUT NOT LIMITED TO: STRUCTURES, CEILINGS, WALLS,

FLOORS, FURNITURE, EQUIPMENT, UTILITIES, ETC. DAMAGE TO EXISTING

CONDITIONS SHALL BE REPAIRED AT NO ADDITIONAL COST TO THE

GOVERNMENT.

3. CONTRACTOR SHALL BE RESPONSIBLE FOR PATCHING AND PAINTING FLOORS,

CEILINGS, AND WALLS TO MATCH EXISTING CONDITIONS IN ALL AREAS

IMPACTED BY THE DEMOLITION OF THE EXISTING FIRE ALARM SYSTEM AND

INSTALLATION OF THE NEW FIRE ALARM AND MASS NOTIFICATION SYSTEM.

4. ALL FIRE ALARM CONDUIT NOT INCORPORATED WITHIN NEW FIRE ALARM AND

MASS NOTIFICATION SYSTEM SHALL BE REMOVED IN THEIR ENTIRETY, WITH

THE EXCEPTION OF CONDUIT CONCEALED WITHIN MASONRY WALLS, FINISHED

GYPSUM BOARD WALLS, FINISHED GYPSUM BOARD CEILING WITHOUT ACCESS

AS WELL AS THOSE CONCEALED BEHIND STRUCTURAL COMPONENTS. ALL

ABANDONED CONDUIT SHALL BE LABELED AND ITS OUTLET LOCATION

IDENTIFIED. ALL WIRING/CABLE SHALL BE REMOVED FROM ANY CONDUIT

ALLOWED TO REMAIN IN PLACE.

5. IONIZATION PRINCIPLE SMOKE DETECTORS CONTAIN THE RADIOACTIVE

ISOTOPE AMERICIUM 241. SEPARATE IONIZATION PRINCIPLE SMOKE

DETECTORS FROM OTHER ELECTRONIC WASTE AND DISPOSE OF IN

ACCORDANCE WITH FEDERAL, STATE AND LOCAL REGULATIONS.

6. ALL ABANDONED THROUGH- AND MEMBRANE-PENETRATIONS RESULTING

FROM THE EXISTING FIRE ALARM SYSTEM DEMOLITION WILL BE CLOSED AND

OR SEALED TO RESTORE FIRE-RESISTANCE AND SMOKE RATINGS.

7. INDIVIDUAL EXISTING SUSPENDED ACOUSTICAL CEILING TILES WILL BE

REMOVED AS REQUIRED TO COMPLETE THE DEMOLITION AND INSTALLATION

OF THE FIRE ALARM / MASS NOTIFICATION SYSTEM. NEW REPLACEMENT TILES

WILL MATCH EXISTING TILES. WHERE THE EXISTING CEILING TILES HAVE BEEN

DISCONTINUED, THE CONTRACTOR WILL IDENTIFY A DONOR ROOM FROM

WHICH TILES WILL BE REMOVED AND USED IN OTHER BUILDING AREAS TO

MATCH EXISTING TILES. ALL TILES WITHIN THE DONOR ROOM WILL BE

REPLACED WITH NEW TILES, CURRENTLY IN PRODUCTION HAVING SIMILAR

SALIENT FEATURES AND CLOSELY MATCHING THE ORIGINAL TILES. CARE

SHOULD BE TAKEN NOT TO ADVERSELY DISTURB THERMAL OR ACOUSTIC

INSULATION SUPPORTED BY CEILING TILES.

1. PROVIDE A COMPLETE ADDRESSABLE FIRE ALARM

AND MASS NOTIFICATION SYSTEM WITH

EMERGENCY VOICE COMMUNICATIONS

THROUGHOUT AS NOTED ON DRAWINGS. INSTALL

SILENT KNIGHT 6820EVS SERIES FIRE ALARM / MASS

NOTIFICATION CONTROL UNIT, SILENT KNIGHT

EVS-RCU SUPERVISED REMOTE COMMAND UNIT

(LOC), AND SILENT KNIGHT 5895 NOTIFICATION

APPLIANCE CIRCUIT (NAC) POWER SUPPLIES AS

DETAILED ON DRAWINGS AND AS REQUIRED.

PROVIDE COMPLETE OCCUPANT NOTIFICATION

THROUGHOUT. PROVIDE MANUAL PULL STATIONS AT

ALL EXITS. PROVIDE DUCT SMOKE DETECTION AND

HVAC SHUT-DOWN PER NFPA 90A, NFPA 90B, AND

UFC 3-600-01. MONITOR ALL FIRE PROTECTION

SYSTEMS INCLUDING BUT NOT LIMITED TO

AUTOMATIC SPRINKLERS.

2. THE NEW FIRE ALARM AND MASS NOTIFICATION

SYSTEM SHALL BE EQUIPPED WITH AN AES

INTELLINET 2.0 MESH NETWORK TRANSMITTER. THE

TRANSMITTER SHALL TRANSMIT THE FOLLOWING

POINTS.

1. GENERAL FIRE ALARM ACTIVATION OF DORM

ROOM SMOKE DETECTOR.

2. GENERAL FIRE ALARM ACTIVATION OF AREA

SMOKE/HEAT DETECTOR.

3.GENERAL FIRE ALARM ACTIVATION OF MANUAL

PULL STATION.

4. GENERAL FIRE ALARM ACTIVATION OF DUCT

SMOKE DETECTOR.

5. GENERAL ALARM ACTIVATION OF CARBON

MONOXIDE DETECTOR.

6. GENERAL SUPERVISORY ALARM.

7. GENERAL TROUBLE ALARM.

3. WORK SHALL BE INSTALLED IN ACCORDANCE WITH

NATIONAL ELECTRICAL CODE, NFPA 72, UFC 3-600-01

WITH CHANGE 6, 06 MAY 2021, UFC 4-021-01 AS

AMENDED BY US ARMY CORPS OF ENGINEERS

(USACE) DESIGN GUIDE FOR VISUAL NOTIFICATION

FOR MASS NOTIFICATION SYSTEM, USACE

ENGINEERING AND CONSTRUCTION BULLETIN (ECB)

REGARDING UFC 4-021-01 ISSUED 25-OCT-18, UFC

4-010-05, AND THE AUTHORITY HAVING

JURISDICTION (AHJ). A CERTIFICATE OF FINAL

INSPECTION SHALL BE PROVIDED BY THE

CONTRACTOR AT THE COMPLETION OF THE WORK

AND PRESENTED TO ENGINEER AND CONTRACTING

OFFICER AS THE COMPLETION OF EACH BUILDING.

4. THE CONTRACT DOCUMENTS ARE BASED ON

RECORD DRAWINGS AND LIMITED FIELD

OBSERVATIONS. IT IS THE CONTRACTOR'S

RESPONSIBILITY TO VERIFY ACTUAL CONDITIONS

AND MAKE NECESSARY CHANGES TO

ACCOMMODATE THE INSTALLATION OF NEW WORK

AT NO ADDITIONAL COST TO THE GOVERNMENT.

5. THE CONTRACTOR SHALL COMPLETE THE DESIGN

AS REQUIRED TO PROVIDE A COMPLETE AND

SATISFACTORILY FUNCTIONING SYSTEM AS

INDICATED ON THE CONTRACT DOCUMENTS AND AS

EVIDENTLY INTENDED. IT IS NOTED THAT THE

DRAWINGS ARE DIAGRAMMATIC IN NATURE AND

INDICATE GENERAL ARRANGEMENTS OF SYSTEMS

AND WORK. INTERCONNECTIONS HAVE NOT BEEN

SHOWN, AND THE CONTRACTOR SHALL FURNISH

AND INSTALL CONDUIT AND WIRING AS REQUIRED

ACCOMPLISHING THE FUNCTIONS INTENDED. THE

CONTRACTOR SHALL FURNISH AND INSTALL THE

REQUIRED QUANTITIES AND TYPES OF CABLES,

CONDUCTORS, RACEWAYS, REMOTE POWER

SUPPLIES AND INTERCONNECTIONS, SHIELDING

REQUIREMENTS, ETC., AS REQUIRED BY THE

SYSTEM MANUFACTURER, THE SPECIFICATIONS,

AND APPLICABLE CODES. ALL WIRING SHOWN ON

RISER DIAGRAMS SHALL ALSO BE FURNISHED AND

INSTALLED REGARDLESS OF WHETHER THESE

ITEMS ARE SHOWN ON THE FLOOR PLANS.

6. DEDICATED 120 VAC SHALL BE PROVIDED FOR FIRE

ALARM AND MASS NOTIFICATION SYSTEM CONTROL

UNITS, INCLUDING FA/MNS CONTROL UNIT, REMOTE

POWER SUPPLIES, NOTIFICATION DEVICE POWER

SUPPLIES, ALARM TRANSCEIVERS, ETC. COMPLY

WITH THE NATIONAL ELECTRICAL CODE, NFPA 72

AND UFC 3-520-01. ENLIST THE SERVICES OF AN

ELECTRICAL SUBCONTRACTOR AS MAY BE

REQUIRED TO ACCOMPLISH INSTALLATION AND

TESTING.

7. DUCT SMOKE DETECTORS SHALL BE PROVIDED FOR

HVAC UNITS EXCEEDING 2,000 CFM OR FOR UNITS

SHARING THE SAME PLENUM HAVING A COMBINED

CAPACITY EXCEEDING 2,000 CFM. DUCT SMOKE

DETECTORS ARE NOT REQUIRED WHERE AIR

DISTRIBUTION SYSTEMS ARE INCAPABLE OF

SPREADING SMOKE BEYOND THE ENCLOSING

WALLS, FLOORS AND CEILINGS OF THE ROOM OR

SPACE IN WHICH THE SMOKE IS GENERATED.

ADDRESSABLE FIRE ALARM MODULES SHALL BE

PROVIDED TO ACCOMPLISH HVAC UNIT SHUT DOWN.

8. FIRE/SMOKE DAMPERS AND SMOKE DAMPERS SHALL

BE INTERFACED WITH FIRE ALARM / MASS

NOTIFICATION SYSTEMS TO CLOSE IN THE EVENT OF

FIRE ALARM OR ASSOCIATED DUCT SMOKE

DETECTOR ACTIVATION. DUCT SMOKE DETECTOR

SHALL BE INSTALLED WITHIN 5 FT OF ALL

FIRE/SMOKE AND SMOKE DAMPERS PENETRATING

RATED CONSTRUCTION. CONTRACTOR TO ENLIST

THE SERVICES OF MECHANICAL AND ELECTRICAL

SUBCONTRACTORS AS MAY BE REQUIRED TO

ACCOMPLISH INSTALLATION AND TESTING.

9. THE DETECTOR PLACEMENT DETAILED ON

DRAWINGS IS BASED UPON SMOOTH CEILING

CONSTRUCTION. THE ACTUAL PLACEMENT OF

DETECTORS WILL BE DEPENDENT UPON THE

LOCATION AND ARRANGEMENT OF STRUCTURAL

COMPONENTS, ROOF.CEILING HEIGHT AND

ROOF/CEILING SLOPE.

10. DOORS EQUIPPED WITH ELECTRONIC LOCKING

HARDWARE (ELECTRONIC ACCESS CONTROL AND

DELAYED EGRESS) SHALL BE INTERFACED WITH

FIRE ALARM / MASS NOTIFICATION SYSTEMS TO

RELEASE DOORS IN THE EVENT OF FIRE ALARM

ACTIVATION. CONTRACTOR TO ENLIST THE

SERVICES OF ELECTRONIC SECURITY AND DOOR

HARDWARE SUBCONTRACTORS AS MAY BE

REQUIRED TO ACCOMPLISH INSTALLATION AND

TESTING.

11. THE QUANTITY AND PLACEMENT OF VISUAL

NOTIFICATION DEVICES IS DEPENDENT UPON THE

DEVICE'S CANDELA RATING. DEVICE PLACEMENT

SHALL BE BASED UPON ALLOWABLE DEVICE

COVERAGE ASSOCIATED WITH THE DEVICES

CANDELA RATING PER NFPA 72.

12. SPEAKER QUANTITIES, PLACEMENT AND TAP

SETTINGS SHALL BE SELECTED TO ENSURE VOICE

INTELLIGIBILITY IN ACCORDANCE WITH UFC 4-021-01

AND NFPA 72. ACOUSTIC MODELING SHALL BE

PROVIDED USING COMPUTER BASE SOFTWARE

SUCH AS, BUT NOT LIMITED TO, MODELER BY BOSE

AND EASE BY ADMG. SHOP DRAWINGS SHALL

DEFINE EACH ACOUSTICALLY DEFINED SPACE (ADS),

INTENDED SOUND PRESSURE LEVEL (SPL) AND

INTENDED INTELLIGIBILITY VALUE STI OR CIS. REFER

TO APPENDIX D OF NFPA 72 FOR INTELLIGIBILITY

GUIDANCE. ACCEPTANCE TESTING SHALL INCLUDE

VOICE INTELLIGIBILITY TESTING TO CONFIRM

INTELLIGIBLE SYSTEM DESIGN..

13. WEATHER PROOF FIRE ALARM DEVICES SHALL BE

PROVIDED AS REQUIRED, BASED UPON

OCCUPANCY, ENVIRONMENTAL CONDITIONS AND AS

NOTED ON DRAWINGS.

14. UNLESS OTHERWISE NOTED, ALL EQUIPMENT SHALL

BE NEW, SHALL BE SUITABLE FOR THE APPLICATION

INTENDED, AND SHALL BEAR LABELS OR MARKINGS

INDICATING THIRD PARTY TESTING LABORATORY

LISTINGS ACCEPTABLE TO THE AUTHORITY HAVING

JURISDICTION.

15. FIELD VERIFY LOCATIONS OF DEVICES IN FINISHED

SPACES, WITH WHITEBOARDS, BULLETIN BOARDS,

ELECTRONIC DISPLAYS, FURNITURE, CABINETS,

MILLWORK, AND CASEWORK PRIOR TO ROUGH-IN.

16. FIRE ALARM AND MASS NOTIFICATION CABLES WILL

BE INSTALLED IN METALLIC RACEWAYS. METALLIC

RACEWAYS, CONDUIT, BACK BOXES, AND JUNCTION

BOXES SHALL BE FACTORY PAINTED RED. RACEWAY

AND WIRING SHALL BE CONCEALED IN FINISHED

SPACES, AND MAY BE INSTALLED EXPOSED IN

UNFINISHED SPACES SUCH AS MECHANICAL AND

ELECTRICAL ROOMS. ALL RACEWAY AND WIRING,

WHETHER CONCEALED OR EXPOSED, SHALL BE

INSTALLED EITHER PERPENDICULAR OR PARALLEL

TO THE BUILDING'S STRUCTURAL COMPONENTS.

PROVIDE PULL AND JUNCTION BOXES AS REQUIRED

TO MEET CODE AND INSTALLATION REQUIREMENTS.

17. CONDUIT, BACKBOXES, AND JUNCTION BOXES

WITHIN FINISHED SPACES SHALL BE PAINTED TO

MATCH ADJACENT CEILING AND WALL SURFACES.

CONDUIT SHALL BE IDENTIFIED BY PAINTING 3/4 IN.

RED BANDS ON 20 FT. INTERVALS AND ON BOTH

SIDES OF WALL, FLOOR AND CEILING

PENETRATIONS. JUNCTION BOX COVERS SHALL BE

IDENTIFIED ON THEIR INTERIOR AS "FIRE ALARM".

18. THE CONTRACTOR MAY EXERCISE THE OPTION TO

RE-USE EXISTING CONDUIT, JUNCTION BOXES AND

BACK BOXES, PROVIDED THAT THE CONDUIT IS

INSTALLED IN ACCORDANCE WITH NATIONAL

ELECTRICAL CODE AND NFPA 72, IS FREE FROM

CORROSION, MECHANICAL DAMAGE AND MEETS THE

FIRE ALARM SYSTEM DESIGN INTENT. CONDUIT

RE-USED SHALL BE PAINTED IN ACCORDANCE WITH

PROJECT REQUIREMENTS. ALL RE-USED CONDUIT,

JUNCTION BOXES AND BACK BOXES SHALL BE

DEEMED PART OF THE SYSTEM INSTALLATION AND

BE WARRANTED IN ACCORDANCE WITH THE

CONTRACTS WARRANTY PROVISIONS (WARRANTED

AS NEW MATERIALS).

19. CONDUCTORS SHALL BE IDENTIFIED AT EACH

JUNCTION BOX, OUTLET BOX, CABINET, PULL BOX,

ETC., INDICATING PANEL AND CIRCUIT NUMBER,

CONTROL WIRE IDENTIFICATION NUMBER, OTHER

APPROPRIATE INFORMATION. ALL PULL AND

JUNCTION BOXES SHALL BE LABELED AS TO

FUNCTION. ALL CONDUCTORS SHALL BE IDENTIFIED

WITH PERMANENT MACHINE-PRINTED, HEAT-SHRINK

IDENTIFICATION LABELS MANUFACTURED FOR THE

PURPOSE OF CABLE IDENTIFICATION.

HAND-WRITTEN, ENGRAVED OR "P-TOUCH STYLE

LABELS ARE NOT ACCEPTABLE. IDENTIFICATION

HANDWRITTEN ON CABLE JACKET IS NOT

ACCEPTABLE.

20. EQUIPMENT SHALL BE SECURELY FASTENED BY

MEANS OF ANCHORS, RODS, HANGERS, SUPPORTS,

GUIDES, SWAY BRACES, ETC., MAINTAIN ALIGNMENT

AND PREVENT EQUIPMENT MOVEMENT.

21. THROUGH-AND MEMBRANE-PENETRATIONS OF FIRE

AND SMOKE RATED CONSTRUCTION SHALL BE

SEALED WITH FIRE STOPPING MATERIALS

APPROVED AND LISTED FOR THE RATING OF THE

CONSTRUCTION TO BE PENETRATED. PROVIDE

DOCUMENTATION ON ALL SUCH PENETRATION

SEALING SYSTEMS FOR VERIFICATION OF PROPER

INSTALLATION. CONTRACTOR SHOP DRAWINGS

SHALL SHOW THE LOCATION OF FIRE AND SMOKE

RATED CONSTRUCTION. SHOP DRAWINGS SHALL

INCLUDE FIRESTOPPING DETAILS FOR EACH TYPE

OF FIRESTOPPING MATERIAL USED IN THE PROJECT.

ONLY QUALIFIED CONTRACTOR AND INSTALLERS

SHALL INSTALL FIRESTOPPING. REFER TO 07 84 00

SPECIFICATIONS.

22. PENETRATIONS OF ROOFS, EXTERIOR WALLS,

FOUNDATIONS, OR OTHER WATER OR MOISTURE

PROOF CONSTRUCTION SHALL BE SEALED WITH

APPROPRIATE SEALING FITTINGS OR SEALED

CONSTRUCTION TO PREVENT THE INTRODUCTION

OF MOISTURE INTO THE BUILDING.

23. WHERE EMPTY RACEWAYS ARE INSTALLED FOR

FUTURE USE, THEY SHALL BE LABELED AT BOTH

ENDS AND FITTED WITH NYLON PULL STRINGS FOR

FUTURE USE.

24. WORK SHALL BE PERFORMED ON DE-ENERGIZED

SYSTEMS ONLY TO PREVENT PERSONNEL INJURY

AND POTENTIAL SYSTEM FAILURE. WHERE WORK ON

SYSTEMS WILL REQUIRE INTERRUPTION OF

ELECTRICAL SERVICE, TEMPORARY PROVISIONS

FOR TEMPORARY POWER SHALL BE PROVIDED

UNTIL THE WORK IS COMPLETE. ALL INTERRUPTIONS

TO BUILDING UTILITIES SHALL BE APPROVED IN

WRITING BY THE CONTRACTING OFFICERS

REPRESENTATIVE.

25. SHOP DRAWINGS AND CALCULATIONS MUST BE

PREPARED BY AN INDIVIDUAL WHO HAS OBTAINED

NATIONAL INSTITUTE FOR CERTIFICATION IN

ENGINEERING TECHNOLOGIES, FIRE ALARM

SYSTEMS, LEVEL III CERTIFICATION, AT A MINIMUM.

THE CONTRACTOR SHALL SECURE THE SERVICES

OF A QFPE AND THE QFPE MUST REVIEW THE SHOP

DRAWINGS, CALCULATIONS (INCLUDING, BATTERY

CALCULATIONS AND VOLTAGE DROP

CALCULATIONS), AUDIBILITY AND INTELLIGIBILITY

MODELING, AND MATERIAL SUBMITTALS. THE SHOP

DRAWINGS SHALL BEAR THE REVIEW STAMP OF THE

QFPE PRIOR TO SUBMITTING THE FIRE ALARM

SYSTEM SHOP DRAWINGS TO THE GOVERNMENT

(UFC 3-600-01 SECTION 9-18.2). SUBMIT SHOP

DRAWINGS AND CALCULATIONS TO THE

GOVERNMENT FOR REVIEW IN A MANNER AS

REQUIRED PER NFPA 72 AND UFC 3-600-01.

APPROVED SHOP DRAWINGS, DATA SHEETS, AND

CALCULATIONS SHALL BE REQUIRED PRIOR TO

COMMENCEMENT OF WORK.

26. PROVIDE SURGE PROTECTIVE DEVICES (SPDS) TO

PROTECT ALL POWER SUPPLY CIRCUITS TO THE

FA/MNS CONTROL UNIT, RADIO TRANSMITTER,

INCLUDING SUBPANELS (E.G. NOTIFICATION

APPLIANCE CIRCUIT (NAC) BOOSTER PANELS). SPDS

SHALL BE INSTALLED IN ACCORDANCE WITH UFC

3-520-01. ALL SPDS SHALL BE UL 1283 AND UL 1449

LISTED IN ACCORDANCE WITH UFC 3-600-01.

27. PROVIDE SURGE PROTECTIVE DEVICES (SPDS) FOR

ALL FIRE ALARM DATA, SLC AND NOTIFICATION

CIRCUITS THAT LEAVE THE BUILDING'S PROTECTIVE

ENVELOPE. PROVIDE SURGE PROTECTIVE DEVICES

FOR ALL FIRE ALARM NOTIFICATION DEVICES

INSTALLED ON THE BUILDING'S EXTERIOR WALL,

UNLESS THE BUILDING IS PROTECTED WITH AN

APPROVED LIGHTNING PROTECTION SYSTEM. ALL

SPDS SHALL BE UL 1283 AND UL 1449 LISTED IN

ACCORDANCE WITH UFC 3-600-01.

28. PROVIDE A LOCK-ON BREAKER IN THE BRANCH

PANELBOARD THAT SERVES AS PRIMARY POWER

FOR THE FIRE PROTECTION SYSTEMS. WHERE MORE

THAN ONE DEDICATED 120 VAC POWER CIRCUIT IS

REQUIRED FOR FIRE PROTECTION SYSTEMS, A

DEDICATED PANEL BOARD SIZED FOR A MINIMUM OF

SIX (6) CIRCUITS DEDICATED TO FIRE PROTECTION

AND LIFE SAFETY SYSTEMS POWERED FROM A

LOCK-ON BREAKER IN THE UPSTREAM DISTRIBUTION

EQUIPMENT SHALL BE PROVIDED.

29. LOCK-ON BREAKERS SHALL BE FACTORY OR FIELD

PAINTED RED. ADDITIONALLY, PROVIDE A

MECHANICALLY FASTENED RED LAMINATED PLASTIC

LABEL WITH WHITE CENTER CORE WITH THE

FOLLOWING INSCRIPTION: "FIRE PROTECTION/LIFE

SAFETY EQUIPMENT" FOR EACH LOCK-ON BREAKER.

30. FOR FACILITIES THAT ARE PROVIDED WITH STANDBY

EMERGENCY POWER SYSTEMS, FIRE PROTECTION

SYSTEMS SHALL BE POWERED BY THE EMERGENCY

POWER SYSTEM.

31. MULTIPLE PIECES OF FIRE ALARM AND MASS

NOTIFICATION CONTROL EQUIPMENT, POWER

SUPPLIES, ETC. MAY SHARE A DEDICATED POWER

CIRCUIT, PROVIDED THAT THE COMBINED CURRENT

LOAD DOES NOT EXCEED 80% OF THE CIRCUITS

RATING. CONTRACTOR SHALL PROVIDE

CALCULATIONS DEMONSTRATING THE CIRCUIT

LOADING DOES NOT EXCEED 80%.

32. ORIGINAL FIRE ALARM CONTROL UNIT ENCLOSURES

SHALL BE REMOVED AND SHALL NOT SERVE AS FIRE

ALARM TERMINAL CABINETS OR JUNCTION BOXES

FOR THE NEW WORK UNDER ANY CIRCUMSTANCES.

WHERE THE RE-USE OF EXISTING CONDUIT

PREVIOUSLY ENTERING THE ORIGINAL FIRE ALARM

CONTROL UNIT OR FIRE ALARM ENCLOSURE IS

REQUIRED, SUCH AS WHERE CONDUIT ENTERS

FROM BELOW GRADE, CONCEALED SPACE, ETC.

NEW TERMINAL CABINETS, CABLE TROUGHS, OR

NEMA ENCLOSURES RATED FOR THE ENVIRONMENT

PRESENT SHALL BE PROVIDED.

33. ALL CABLES TERMINATED WITHIN CONTROL

EQUIPMENT, REMOTE PANELS, POWER SUPPLIES,

TERMINAL CABINETS, ADDRESSABLE INTERFACE

MODULE ENCLOSURES, ETC. SHALL BE NEATLY

TERMINATED USING SCREWED TERMINALS STRIPS

OR SCREWED JUNCTION BLOCKS. NO WIRE NUTS,

CRIMP-ON, LATCHING, PUSH-ON OR SOLDERED

CONNECTORS SHALL BE ALLOWED.

34. HIGH VOLTAGE (120VAC), NON-POWER LIMITED AND

POWER LIMITED CABLE INSTALLED WITHIN

EQUIPMENT ENCLOSURES SHALL BE SEPARATED IN

ACCORDANCE WITHNATIONAL ELECTRICAL CODE

AND MANUFACTURER'S INSTALLATION

INSTRUCTIONS.

35. INDIVIDUAL EXISTING SUSPENDED ACOUSTICAL

CEILING TILES WILL BE REMOVED AS REQUIRED TO

COMPLETE THE DEMOLITION AND INSTALLATION OF

THE FIRE ALARM / MASS NOTIFICATION SYSTEM.

NEW REPLACEMENT TILES WILL MATCH EXISTING

TILES. WHERE THE EXISTING CEILING TILES HAVE

BEEN DISCONTINUED, THE CONTRACTOR WILL

IDENTIFY A DONOR ROOM FROM WHICH TILES WILL

BE REMOVED AND USED IN OTHER BUILDING AREAS

TO MATCH EXISTING TILES. ALL TILES WITHIN THE

DONOR ROOM WILL BE REPLACED WITH NEW TILES,

CURRENTLY IN PRODUCTION HAVING SIMILAR

SALIENT FEATURES AND CLOSELY MATCHING THE

ORIGINAL TILES. CARE SHOULD BE TAKEN NOT TO

ADVERSELY DISTURB THERMAL OR ACOUSTIC

INSULATION SUPPORTED BY CEILING TILES.

36. ANY ACCESS OPENINGS CUT INTO CEILINGS AND

WALLS TO ACCOMMODATE THE FA/MNS

INSTALLATION WILL BE REPAIRED IN A MANNER

THAT MAINTAINS THE FIRE-RESISTANCE AND SMOKE

RATINGS.

IV

ER

Y O

R D

ER

N

O

D

ES

IG

N

ED

B

Y:

D

ES

C R

IP

TI

O N

M

AR

K

SI

ZE

SU

BM

IT

TE

D B

Y:

D

AT

E

C O

N

TR

AC

T

N U

M

BE

R

C H

EC

KE

D B

Y:

D R

AW

N

B Y:

IS

SU

E D

AT

E:

G

2 3 4 5 6 7 8 9 10

F

E

D

C

B

A SHEET ID

H D

R E ng in ee rin g, In c.

E.

P

AR

KC

EN

TE

R B

LV

D

BO

IS

E, ID

(2

) 3

-7

U .S

. A

IR

F O

R C

E

C

ES

/C

EN

M O

U N

TA

IN

H O

M E

AI

R

F O

R C

E

BA

SE

M

O U

N

TA

IN

H

O M

E, ID

AH

O

FA

-2

0- D

-0

D

EC

EM

BE

R

PR

O

JE

C

T N

U M

BE

R

SH

EE

T N

U M

BE

R

AN

SI

D

FA

-2

5- F-

M O

U N

TA

IN

H O

M E

AI

R

F O

R C

E

BA

SE

B2

FI

R

E

AL

AR

M

R

EP

AI

R

100% DESIGN SUBMITTAL

O

F

Z.

S

AC

H

SE

N

M

AI

ER

W . C

U N

AR

D

R . R

IC

H

TE

R

P.

D

ER

R

SY

M

BO

LS

L

EG

EN

D

A N

D C

O D

E

AN

AL

YS

IS

FA002

B2318

FIRE ALARM AND MASS NOTIFICATION SYMBOLS LEGEND

FIRE ALARM AND MASS NOTIFICATION CONTROL UNIT

FIRE ALARM ANNUNCIATOR AND LOCAL OPERATORS CONSOLEFAA/LOC

ADDRESSABLE INPUT MODULE

ADDRESSABLE OUTPUT MODULE

AIM

AOM

GAS DETECTOR, SUBSCRIPT DEFINES TYPE

END OF LINE SUPERVISION DEVICE

WF FLOW SWITCH

RL NON-ADDRESSABLE OUTPUT RELAY

PS PRESSURE SWITCH

SS SURGE SUPPRESSOR

VS VALVE SUPERVISORY SWITCH

MANUAL STATION, FIRE ALARM

HEAT DETECTOR, SPECIFY TYPE

DUCT MOUNTED SMOKE DETECTOR

NAC EXTENDER BOOSTER POWER SUPPLYNAC

DH DOOR HOLDER

FIRE ALARM BELL, VIBRATING TYPE

REMOTE ALARM INDICATING AND TEST SWITCH

STROBE ONLY, WALL MOUNT

FMCU

- CONTROL EQUIPMENT -

- MANUAL STATIONS -

- DETECTION -

- ADDRESSABLE MODULES -

- NOTIFICATION APPLIANCES -

ADDRESSABLE DUAL INPUT MODULE

SPEAKER/STROBE COMBO, WALL MOUNT, CLEAR LENS

STROBE ONLY, CEILING MOUNT

SPEAKER ONLY, CEILING MOUNT

AHU AIR HANDLING UNIT

AUX AUXILIARY POWER

C CEILING MOUNT

CO CARBON MONOXIDE

DOD DEPARTMENT OF DEFENSE

FA FIRE ALARM

FA/MNS FIRE ALARM AND MASS NOTIFICATION SYSTEM

HPS HIGH POWER SPEAKER

MNS MASS NOTIFICATION SYSTEM

R RETURN AIR DUCT

RTS REMOTE TEST STATION

RTU ROOF TOP UNIT

S SUPPLY AIR DUCT

SB DORM ROOM SMOKE DETECTOR WITH SOUNDER BASE

SLA SEALED LINE CIRCUIT (BATTERY)

SLC SIGNALING LINE CIRCUIT

SF SUBFLOOR

TYP TYPICAL

VFD VARIABLE FREQUENCY DRIVE

nW WATTAGE SETTING (n=SPEAKER TAP)

WP WEATHERPROOF

XP EXPLOSION PROOF

NOTE: NOT ALL SUBSCRIPTS AND ABBREVIATIONS MAY BE USED.

F

SPEAKER ONLY, WALL MOUNT

SPEAKER/STROBE COMBO, CEILING MOUNT, CLEAR LENS

- PERIPHERAL DEVICES -

SPEAKER ONLY, EXTERIOR WEATHERPROOF, TAPPED AT 2 WATTS

K KNOX BOX

EXTERIOR MOUNTED ANTENNA FOR RF TRANSMISSION

-MANUAL STATIONS-

-DETECTION-

-FIRE ALARM NOTIFICATION APPLIANCES-

DETECTOR TO BE REMOVED

NOTIFICATION APPLIANCE TO BE REMOVED

FIRE ALARM CONTROL UNIT

FIRE ALARM ANNUNCIATOR PANEL

MANUAL STATION, FIRE ALARM

DUCT MOUNTED SMOKE DETECTOR, SPECIFY TYPE

REMOTE ALARM INDICATING AND TEST SWITCH

FLOW SWITCH

VALVE SUPERVISORY SWITCH

PRESSURE SWITCH

ADDRESSABLE INPUT MODULE

-FIRE ALARM DEMOLITION SYMBOLS LEGEND-

DOOR HOLDER

120/208 VAC ELECTRICAL DISTRIBUTION PANEL-

SOURCE OF DEDICATED 120 VAC

120/280 VAC ELECTRICAL DISTRIBUTION PANEL-

SOURCE OF DEDICATED 120 VAC

EOL

2AIM

DHWP

S

V F

CS

WS

C

ADDRESSABLE OUTPUT MODULE

- DEVICE SUBSCRIPTS & ABBREVIATIONS -

RF ALARM TRANSCEIVER

- ADDRESSABLE MODULES -

- CONTROL EQUIPMENT -

- PERIPHERAL DEVICES -

RF TRANSCEIVER ANTENNA, MOUNTING HARDWARE

AND ASSOCIATED CONDUIT

uu uu u u u

S S S SMOKE-RATED PARTITION

1-HOUR FIRE-RATED BARRIER

2-HOUR FIRE-RATED BARRIER

- WALL RATINGS -

SMOKE DETECTOR, SPECIFY TYPE

SMOKE DETECTOR, BEAM TYPE - RECEIVER

SMOKE DETECTOR, BEAM TYPE - TRANSMITTER

AOM

PS

VS

WF

RTS

AIM

F

DET

AES AES INTELLINET 2.0 MESH NETWORK ALARM TRANSMITTER

ROOM

ROOM

MAINT

OFFICE

ROOM

STORAGE

MECH

LAUNDRY

ROOM

ROOM

ROOM

ROOM

STAIRS

STAIRS

ROOM

ROOM

ROOM

ROOM

COMM

136 VESTIBULE

CENTER

LOBBY

VESTIBULE

BREAK

ROOM

1XX

JC

LINEN

CORRIDOR

CORRIDOR

u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u

AIR COOLED

CONDENSOR

MECH. YARD

DET

DET

DET

DET

DET

DET

DET

DET DET

DET DET

DET

F

F

F

F

DET DET DET DET

DET DET DET DET

DET DET DET DET DET DET

FD

1A M

AT

C

H

LI

N E

FD

1B

FD

1A

M

AT

C H

LI

N

E

FD

1B

ELECTRICAL PANELS

1C AND 1D

AC B

B B B B

A

B

B BA A

B B B B

A

B

B A A

B

B A

C C

B A B

B

A

B

B

B

A B

B

B B

A A AB

B

(NON-ENVIRONMENTALLY

CONTROLLED SPACE)

A B

0 8'4' 16'SCALE: 1/8" = 1'-0"

LEVEL ONE DEMOLITION PLAN - AREA A - FIRE ALARMA1

PLAN

NORTH

D

EL

IV

ER

Y O

R D

ER

N

O

D

ES

IG

N

ED

B

Y:

D

ES

C R

IP

TI

O N

M

AR

K

SI

ZE

SU

BM

IT

TE

D B

Y:

D

AT

E

C O

N

TR

AC

T

N U

M

BE

R

C H

EC

KE

D B

Y:

D R

AW

N

B Y:

IS

SU

E D

AT

E:

G

2 3 4 5 6 7 8 9 10

F

E

D

C

B

A SHEET ID

H D

R E ng in ee rin g, In c.

E.

P

AR

KC

EN

TE

R B

LV

D

BO

IS

E, ID

(2

) 3

-7

U .S

. A

IR

F O

R C

E

C

ES

/C

EN

M O

U N

TA

IN

H O

M E

AI

R

F O

R C

E

BA

SE

M

O U

N

TA

IN

H

O M

E, ID

AH

O

FA

-2

0- D

-0

D

EC

EM

BE

R

PR

O

JE

C

T N

U M

BE

R

SH

EE

T N

U M

BE

R

AN

SI

D

FA

-2

5- F-

M O

U N

TA

IN

H O

M E

AI

R

F O

R C

E

BA

SE

B2

FI

R

E

AL

AR

M

R

EP

AI

R

100% DESIGN SUBMITTAL

O

F

Z.

S

AC

H

SE

N

M

AI

ER

W . C

U N

AR

D

R . R

IC

H

TE

R

P.

D

ER

R

LE

VE

L O

N E

D

EM

O

LI

TI

O

N P

LA

N

AR

EA

A

FI

R E

AL

AR

M

FD101A

B2318

SHEET NOTES

1. REMOVE EXISTING FIRE ALARM SYSTEM IN ITS

ENTIRETY. PATCH AND PAINT WALL AND CEILING

OPENINGS NOT SLATED FOR RE-USE TO MATCH

SURROUNDING SURFACES.

2. DEMO EXISTING CEILING AND WALL MOUNTED

DEVICES, BACK BOXES, CONDUIT AND WIRE IN THEIR

ENTIRETY. ALTERNATELY, THE EXISTING BACK

BOXES MAY BE RE-USED FOR NEW DEVICES,

PROVIDED THAT THE BACK BOX DIMENSIONS ARE

COMPATIBLE WITH NEW DEVICES AND THE BACK BOX

IS IN THE CORRECT LOCATION. EXISTING CONDUIT

SERVING THE EXISTING BACK BOX MAY BE RE-USED

IF THE CONDUIT IS NO LESS THAN 3/4 IN., INSTALLED

IN ACCORDANCE WITH NEC AND IS WARRANTED AS

NEW.

3. THIS BUILDING WILL BE VACATED DURING

CONSTRUCTION.

4. UNLESS OTHERWISE NOTED, CEILING HEIGHTS ARE

LESS THAN 10FT.

5. UNLESS OTHERWISE NOTED, CEILINGS FEATURE

ACOUSTICAL CEILING TILES SUPPORTED BY METAL

GRIDDED FRAMES. REFER ALSO TO CEILING LEGEND.

6. THROUGH AND MEMBRANE PENETRATIONS OF FIRE

AND SMOKE RATED CONSTRUCTION SHALL BE

PERFORMED IN A MANNER THAT MAINTAINS THE

EXISTING RATINGS. LISTED FIRESTOPPING SYSTEMS

AND MATERIALS SHALL BE PROVIDED AS REQUIRED.

REFERENCE DIVISION 07 84 00.

SHEET KEY NOTES

1. DEMO EXISTING SILENT KNIGHT 5820XL FACU, NAC POWER

SUPPLY, MONACO ENTERPRISES TRANSCEIVER, CONDUIT

AND WIRE IN ITS ENTIRETY. THE NEW FMCU WILL NOT BE

REINSTALLED AT THIS LOCATION.

2. DEMO EXISTING REMOTE ANNUNCIATOR. PATCH AND PAINT

CMU WALL AS REQUIRED TO ACCOMODATE NEW COMBINED

REMOTE ANNUNCIATOR AND LOCAL OPERATORS CONSOLE.

3. DEMO EXISTING DEDICATED 120 VAC TO THE FACU. THE

NEW FMCU WILL NOT BE REINSTALLED AT THIS LOCATION.

4. DEMO EXISTING MONACO TRANSCEIVER ANTENNA,

CONDUIT, SURGE SUPPRESSOR, COAXIAL CABLE AND

MOUNTING HARDWARE.

5. DEMO EXISTING WINDOW AND FRAME COMPLETE,

MEASURING APPROXIMATLEY 48 IN, X 60IN. REMOVE

EXISTING DRYWALL TO NEAREST VERTICAL STUD AND INFILL

OPENING WITH NEW METAL FRAMING AT PERIMETER AND

CENTER OF OPENING MATCHING EXISTING DEPTH. FINISH

OPENING WITH GYPSUM WALL BOARD TO MATCH EXISTING

THICKNESS, TAPE, TEXTURE AND PAINT ENTIRE WALL FROM

CORNER TO CORNER AND FLOOR TO CEILING. INSTALL

METAL BLOCKING AS REQUIRED TO SUPPORT NEW FMCU

AND ASSOCIATED EQUIPMENT ENCLOSURES.

6. DEMO ABANDONED MATV RACK MOUNTED EQUIPMENT (PICO

MACOM MODULATORS, DIRECT TV RECEIVERS AND ABP

DIGITAL AMPLIERS), AND FLOOR RACK. DEMO WALL

MOUNTED SPLITTERS AND DIRECTIONAL COUPLERS.

COORDINATE DEMOLITION WITH COMMS SQUADRON.

7. DOORS SEPARATING CORRIDORS AND DAY ROOMS FROM

CENTER LOBBY WERE ONCE EQUIPPED WITH DOOR

HOLDERS. THE DOOR HOLDERS HAVE BEEN REMOVED AND

DOORS ARE CURRENTLY EQUIPPED WITH DOOR CLOSERS

TO KEEP DOORS CLOSED. SINGLE GANG BACK BOXES WITH

BLANK COVERS REMAIN. CONTRACTOR SHALL DEMO WIRE

AND BACK BOXES ASSOCIATED WITH THE ONCE INSTALLED

DOOR HOLDERS. CONTRACTOR SHALL PATCH AND PAINT

WALL OPENINGS TO MATCH SURROUNDING SURFACES.

CORRIDORS HAVE 1/2-HOUR RATED FIRE-WALLS

uu uu u u u

S S S SMOKE-RATED PARTITION

1-HOUR FIRE-RATED BARRIER

2-HOUR FIRE-RATED BARRIER

WALL RATINGS

SCALE: NTS

KEYPLANA9

PLAN

NORTH

ACT LIFT-OUT CEILING TILES

GYPSUM BOARD

OPEN TO DECK ABOVE

CEILING LEGEND

A

B

C

VESTIBULE

CORRIDOR

DAYROOM

ROOM

ROOM

ROOM

ROOM

ROOM

ROOM

ROOM

ROOM

ROOM

STORAGE

B

ROOM

ROOM

CORRIDOR

STAIRS

u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u

DET DET

DET

DET DET

DET DET

DETDETDETDET

DETDETDETDET

DET DET

DET DET

DET

F

FD

1A M

AT

C

H

LI

N E

FD

1B

FD

1A

M

AT

C H

LI

N

E

FD

1B

ELECTRICAL PANELS

1A AND 1B

DET

A

B

B

B

A

B

B

B

A

B

B

B

A A A

B

B

B

AAAA

AAA

A

A B B B

B B B B

B

B

B

BBB

BB

BB

A B

0 8'4' 16'SCALE: 1/8" = 1'-0"

LEVEL ONE DEMOLITION PLAN - AREA B - FIRE ALARMA1

PLAN

NORTH

D

EL

IV

ER

Y O

R D

ER

N

O

D

ES

IG

N

ED

B

Y:

D

ES

C R

IP

TI

O N

M

AR

K

SI

ZE

SU

BM

IT

TE

D B

Y:

D

AT

E

C O

N

TR

AC

T

N U

M

BE

R

C H

EC

KE

D B

Y:

D R

AW

N

B Y:

IS

SU

E D

AT

E:

G

2 3 4 5 6 7 8 9 10

F

E

D

C

B

A SHEET ID

H D

R E ng in ee rin g, In c.

E.

P

AR

KC

EN

TE

R B

LV

D

BO

IS

E, ID

(2

) 3

-7

U .S

. A

IR

F O

R C

E

C

ES

/C

EN

M O

U N

TA

IN

H O

M E

AI

R

F O

R C

E

BA

SE

M

O U

N

TA

IN

H

O M

E, ID

AH

O

FA

-2

0- D

-0

D

EC

EM

BE

R

PR

O

JE

C

T N

U M

BE

R

SH

EE

T N

U M

BE

R

AN

SI

D

FA

-2

5- F-

M O

U N

TA

IN

H O

M E

AI

R

F O

R C

E

BA

SE

B2

FI

R

E

AL

AR

M

R

EP

AI

R

100% DESIGN SUBMITTAL

O

F

Z.

S

AC

H

SE

N

M

AI

ER

W . C

U N

AR

D

R . R

IC

H

TE

R

P.

D

ER

R

LE

VE

L O

N E

D

EM

O

LI

TI

O

N P

LA

N

AR

EA

B

FI

R E

AL

AR

M

FD101B

B2318

SHEET NOTES

1. REMOVE EXISTING FIRE ALARM SYSTEM IN ITS

ENTIRETY. PATCH AND PAINT WALL AND CEILING

OPENINGS NOT SLATED FOR RE-USE TO MATCH

SURROUNDING SURFACES.

2. DEMO EXISTING CEILING AND WALL MOUNTED

DEVICES, BACK BOXES, CONDUIT AND WIRE IN THEIR

ENTIRETY. ALTERNATELY, THE EXISTING BACK

BOXES MAY BE RE-USED FOR NEW DEVICES,

PROVIDED THAT THE BACK BOX DIMENSIONS ARE

COMPATIBLE WITH NEW DEVICES AND THE BACK BOX

IS IN THE CORRECT LOCATION. EXISTING CONDUIT

SERVING THE EXISTING BACK BOX MAY BE RE-USED

IF THE CONDUIT IS NO LESS THAN 3/4 IN., INSTALLED

IN ACCORDANCE WITH NEC AND IS WARRANTED AS

NEW.

3. THIS BUILDING WILL BE VACATED DURING

CONSTRUCTION.

4. UNLESS OTHERWISE NOTED, CEILINGS HEIGHTS ARE

LESS THAN 10FT.

5. UNLESS OTHERWISE NOTED, CEILINGS FEATURE

ACOUSTICAL CEILING TILES SUPPORTED BY METAL

GRIDDED FRAMES. REFER ALSO TO CEILING LEGEND.

6. THROUGH AND MEMBRANE PENETRATIONS OF FIRE

AND SMOKE RATED CONSTRUCTION SHALL BE

PERFORMED IN A MANNER THAT MAINTAINS THE

EXISTING RATINGS. LISTED FIRESTOPPING SYSTEMS

AND MATERIALS SHALL BE PROVIDED AS REQUIRED.

REFERENCE DIVISION 07 84 00.

CORRIDORS HAVE 1/2-HOUR RATED FIRE-WALLS

uu uu u u u

S S S SMOKE-RATED PARTITION

1-HOUR FIRE-RATED BARRIER

2-HOUR FIRE-RATED BARRIER

WALL RATINGS

SCALE: NTS

KEYPLANA9

PLAN

NORTH

ACT LIFT-OUT CEILING TILES

GYPSUM BOARD

OPEN TO DECK ABOVE

CEILING LEGEND

A

B

C

ROOM

HOSPITALITY

ROOM

ROOM

ROOM

ROOM

ROOM

ROOM

ROOM

ROOM

STAIRS

STAIRS

ROOM

ROOM

ROOM

ROOM

STORAGE

CENTER

LOBBY

CORRIDOR

CORRIDOR

u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u uuu u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u

LODGING

COMM.

EQUIP.

DET DET

DET DET DET

DET

DET

DET DET DET DET DET

DET DET DET DET

DET DET DET DET

DET DET DET DET

F

F

FD

2A M

AT

C

H

LI

N E

FD

2B

FD

2A

M

AT

C H

LI

N

E

FD

2B

ELECTRICAL PANELS

2C AND 2D

AB

B B B

A

B

B BA A

B B B B

A

B

B A A

B

B A

A B

B

A

B

B

B

A B

B

B B

A A AB

B

B

B

A

BB

A

DET

A B

B

A

A B

0 8'4' 16'SCALE: 1/8" = 1'-0"

LEVEL TWO DEMOLITION PLAN - AREA A - FIRE ALARMA1

PLAN

NORTH

D

EL

IV

ER

Y O

R D

ER

N

O

D

ES

IG

N

ED

B

Y:

D

ES

C R

IP

TI

O N

M

AR

K

SI

ZE

SU

BM

IT

TE

D B

Y:

D

AT

E

C O

N

TR

AC

T

N U

M

BE

R

C H

EC

KE

D B

Y:

D R

AW

N

B Y:

IS

SU

E D

AT

E:

G

2 3 4 5 6 7 8 9 10

F

E

D

C

B

A SHEET ID

H D

R E ng in ee rin g, In c.

E.

P

AR

KC

EN

TE

R B

LV

D

BO

IS

E, ID

(2

) 3

-7

U .S

. A

IR

F O

R C

E

C

ES

/C

EN

M O

U N

TA

IN

H O

M E

AI

R

F O

R C

E

BA

SE

M

O U

N

TA

IN

H

O M

E, ID

AH

O

FA

-2

0- D

-0

D

EC

EM

BE

R

PR

O

JE

C

T N

U M

BE

R

SH

EE

T N

U M

BE

R

AN

SI

D

FA

-2

5- F-

M O

U N

TA

IN

H O

M E

AI

R

F O

R C

E

BA

SE

B2

FI

R

E

AL

AR

M

R

EP

AI

R

100% DESIGN SUBMITTAL

O

F

Z.

S

AC

H

SE

N

M

AI

ER

W . C

U N

AR

D

R . R

IC

H

TE

R

P.

D

ER

R

LE

VE

L

TW

O D

EM

O

LI

TI

O N

P

LA

N

AR

EA

A

FI

R

E

AL

AR

M

FD102A

B2318

SHEET NOTES

1. REMOVE EXISTING FIRE ALARM SYSTEM IN ITS

ENTIRETY. PATCH AND PAINT WALL AND CEILING

OPENINGS NOT SLATED FOR RE-USE TO MATCH

SURROUNDING SURFACES.

2. DEMO EXISTING CEILING AND WALL MOUNTED

DEVICES, BACK BOXES, CONDUIT AND WIRE IN THEIR

ENTIRETY. ALTERNATELY, THE EXISTING BACK

BOXES MAY BE RE-USED FOR NEW DEVICES,

PROVIDED THAT THE BACK BOX DIMENSIONS ARE

COMPATIBLE WITH NEW DEVICES AND THE BACK BOX

IS IN THE CORRECT LOCATION. EXISTING CONDUIT

SERVING THE EXISTING BACK BOX MAY BE RE-USED

IF THE CONDUIT IS NO LESS THAN 3/4 IN., INSTALLED

IN ACCORDANCE WITH NEC AND IS WARRANTED AS

NEW.

3. THIS BUILDING WILL BE VACATED DURING

CONSTRUCTION.

4. UNLESS OTHERWISE NOTED, CEILINGS HEIGHTS ARE

LESS THAN 10FT.

5. UNLESS OTHERWISE NOTED, CEILINGS FEATURE

ACOUSTICAL CEILING TILES SUPPORTED BY METAL

GRIDDED FRAMES. REFER ALSO TO CEILING LEGEND.

6. THROUGH AND MEMBRANE PENETRATIONS OF FIRE

AND SMOKE RATED CONSTRUCTION SHALL BE

PERFORMED IN A MANNER THAT MAINTAINS THE

EXISTING RATINGS. LISTED FIRESTOPPING SYSTEMS

AND MATERIALS SHALL BE PROVIDED AS REQUIRED.

REFERENCE DIVISION 07 84 00.

SHEET KEY NOTES

1. DEMO EXISTING NAC POWER SUPPLY CONDUIT AND WIRE IN

ITS ENTIRETY.

2. DOORS SEPARATING CORRIDORS AND DAY ROOMS FROM

CENTER LOBBY WERE ONCE EQUIPPED WITH DOOR

HOLDERS. THE DOOR HOLDERS HAVE BEEN REMOVED AND

DOORS ARE CURRENTLY EQUIPPED WITH DOOR CLOSERS

TO KEEP DOORS CLOSED. SINGLE GANG BACK BOXES WITH

BLANK COVERS REMAIN. CONTRACTOR SHALL DEMO WIRE

AND BACK BOXES ASSOCIATED WITH THE ONCE INSTALLED

DOOR HOLDERS. CONTRACTOR SHALL PATCH AND PAINT

WALL OPENINGS TO MATCH SURROUNDING SURFACES.

CORRIDORS HAVE 1/2-HOUR RATED FIRE-WALLS

uu uu u u u

S S S SMOKE-RATED PARTITION

1-HOUR FIRE-RATED BARRIER

2-HOUR FIRE-RATED BARRIER

WALL RATINGS

SCALE: NTS

KEYPLANA9

PLAN

NORTH

ACT LIFT-OUT CEILING TILES

GYPSUM BOARD

OPEN TO DECK ABOVE

CEILING LEGEND

A

B

C

STAIRS

STORAGE

CORRIDOR

STORAGE

236 ROOM

ROOM

ROOM

ROOM

ROOM

ROOM

ROOM

ROOM

ROOM

DAYROOM

ROOM

ROOM

CORRIDOR

u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u uuuu u u

LODGING

COMM.

EQUIP.

2XX

DET

DET

DET DET

DET DET

DETDETDETDET

DETDETDETDET

DET DET

DET DET

DET

F

DETDET

DET

FD

2A M

AT

C

H

LI

N E

FD

2B

FD

2A

M

AT

C H

LI

N

E

FD

2B

ELECTRICAL PANELS

2A AND 2B

DET

A

B

B

B

A

B

B

B

A

B

B

B

A A A

B

B

B

AAAA

AAA

A B B B

B B B B

B

B

B

BBB

B C

A

A

A

A B

0 8'4' 16'SCALE: 1/8" = 1'-0"

LEVEL TWO DEMOLITION PLAN - AREA B - FIRE ALARMA1

PLAN

NORTH

D

EL

IV

ER

Y O

R D

ER

N

O

D

ES

IG

N

ED

B

Y:

D

ES

C R

IP

TI

O N

M

AR

K

SI

ZE

SU

BM

IT

TE

D B

Y:

D

AT

E

C O

N

TR

AC

T

N U

M

BE

R

C H

EC

KE

D B

Y:

D R

AW

N

B Y:

IS

SU

E D

AT

E:

G

2 3 4 5 6 7 8 9 10

F

E

D

C

B

A SHEET ID

H D

R E ng in ee rin g, In c.

E.

P

AR

KC

EN

TE

R B

LV

D

BO

IS

E, ID

(2

) 3

-7

U .S

. A

IR

F O

R C

E

C

ES

/C

EN

M O

U N

TA

IN

H O

M E

AI

R

F O

R C

E

BA

SE

M

O U

N

TA

IN

H

O M

E, ID

AH

O

FA

-2

0- D

-0

D

EC

EM

BE

R

PR

O

JE

C

T N

U M

BE

R

SH

EE

T N

U M

BE

R

AN

SI

D

FA

-2

5- F-

M O

U N

TA

IN

H O

M E

AI

R

F O

R C

E

BA

SE

B2

FI

R

E

AL

AR

M

R

EP

AI

R

100% DESIGN SUBMITTAL

O

F

Z.

S

AC

H

SE

N

M

AI

ER

W . C

U N

AR

D

R . R

IC

H

TE

R

P.

D

ER

R

LE

VE

L

TW

O D

EM

O

LI

TI

O N

P

LA

N

AR

EA

B

FI

R

E

AL

AR

M

FD102B

B2318

CORRIDORS HAVE 1/2-HOUR RATED FIRE-WALLS

SCALE: NTS

KEYPLANA9

PLAN

NORTH

SHEET NOTES

1. REMOVE EXISTING FIRE ALARM SYSTEM IN ITS

ENTIRETY. PATCH AND PAINT WALL AND CEILING

OPENINGS NOT SLATED FOR RE-USE TO MATCH

SURROUNDING SURFACES.

2. DEMO EXISTING CEILING AND WALL MOUNTED

DEVICES, BACK BOXES, CONDUIT AND WIRE IN THEIR

ENTIRETY. ALTERNATELY, THE EXISTING BACK

BOXES MAY BE RE-USED FOR NEW DEVICES,

PROVIDED THAT THE BACK BOX DIMENSIONS ARE

COMPATIBLE WITH NEW DEVICES AND THE BACK BOX

IS IN THE CORRECT LOCATION. EXISTING CONDUIT

SERVING THE EXISTING BACK BOX MAY BE RE-USED

IF THE CONDUIT IS NO LESS THAN 3/4 IN., INSTALLED

IN ACCORDANCE WITH NEC AND IS WARRANTED AS

NEW.

3. THIS BUILDING WILL BE VACATED DURING

CONSTRUCTION.

4. UNLESS OTHERWISE NOTED, CEILINGS HEIGHTS ARE

LESS THAN 10FT.

5. UNLESS OTHERWISE NOTED, CEILINGS FEATURE

ACOUSTICAL CEILING TILES SUPPORTED BY METAL

GRIDDED FRAMES. REFER ALSO TO CEILING LEGEND.

6. THROUGH AND MEMBRANE PENETRATIONS OF FIRE

AND SMOKE RATED CONSTRUCTION SHALL BE

PERFORMED IN A MANNER THAT MAINTAINS THE

EXISTING RATINGS. LISTED FIRESTOPPING SYSTEMS

AND MATERIALS SHALL BE PROVIDED AS REQUIRED.

REFERENCE DIVISION 07 84 00.

uu uu u u u

S S S SMOKE-RATED PARTITION

1-HOUR FIRE-RATED BARRIER

2-HOUR FIRE-RATED BARRIER

WALL RATINGS

ACT LIFT-OUT CEILING TILES

GYPSUM BOARD

OPEN TO DECK ABOVE

CEILING LEGEND

A

B

C

CHAIN LINK

FENCE

ROOM

STORAGE

ROOM

ROOM

ROOM

ROOM

ROOM

ROOM

ROOM

STAIRS

STAIRS

ROOM

ROOM

ROOM

ROOM

STORAGE

CENTER

LOBBY

DAYROOM

CORRIDOR

CORRIDOR

u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u uuu u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u

DET DET

DET DET DET

DET

DET

DET DET DET DET DET

DET DET DET DET

DET DET DET DET

DET DET DET DET

F

F

DET

FD

3A M

AT

C

H

LI

N E

FD

3B

FD

3A

M

AT

C H

LI

N

E

FD

3B

ELECTRICAL PANELS

3C AND 3D

AB

B B B

A

B

B BA A

B B B B

A

B

B A A

B

B A

A B

B

A

B

B

B

A B

B

B B

A A AB

B

B

B

A

BB

A

A B

B

A

C

A A

DET

DET

A B

0 8'4' 16'SCALE: 1/8" = 1'-0"

LEVEL THREE DEMOLITION PLAN - AREA A - FIRE ALARMA1

PLAN

NORTH

D

EL

IV

ER

Y O

R D

ER

N

O

D

ES

IG

N

ED

B

Y:

D

ES

C R

IP

TI

O N

M

AR

K

SI

ZE

SU

BM

IT

TE

D B

Y:

D

AT

E

C O

N

TR

AC

T

N U

M

BE

R

C H

EC

KE

D B

Y:

D R

AW

N

B Y:

IS

SU

E D

AT

E:

G

2 3 4 5 6 7 8 9 10

F

E

D

C

B

A SHEET ID

H D

R E ng in ee rin g, In c.

E.

P

AR

KC

EN

TE

R B

LV

D

BO

IS

E, ID

(2

) 3

-7

U .S

. A

IR

F O

R C

E

C

ES

/C

EN

M O

U N

TA

IN

H O

M E

AI

R

F O

R C

E

BA

SE

M

O U

N

TA

IN

H

O M

E, ID

AH

O

FA

-2

0- D

-0

D

EC

EM

BE

R

PR

O

JE

C

T N

U M

BE

R

SH

EE

T N

U M

BE

R

AN

SI

D

FA

-2

5- F-

M O

U N

TA

IN

H O

M E

AI

R

F O

R C

E

BA

SE

B2

FI

R

E

AL

AR

M

R

EP

AI

R

100% DESIGN SUBMITTAL

O

F

Z.

S

AC

H

SE

N

M

AI

ER

W . C

U N

AR

D

R . R

IC

H

TE

R

P.

D

ER

R

AR

EA

A

FI

R

E

AL

AR

M

LE

VE

L

TH

R

EE

D

EM

O

LI

TI

O

N P

LA

N

FD103A

CORRIDORS HAVE 1/2-HOUR RATED FIRE-WALLS

SCALE: NTS

KEYPLANA9

PLAN

NORTH

SHEET NOTES

1. REMOVE EXISTING FIRE ALARM SYSTEM IN ITS

ENTIRETY. PATCH AND PAINT WALL AND CEILING

OPENINGS NOT SLATED FOR RE-USE TO MATCH

SURROUNDING SURFACES.

2. DEMO EXISTING CEILING AND WALL MOUNTED

DEVICES, BACK BOXES, CONDUIT AND WIRE IN THEIR

ENTIRETY. ALTERNATELY, THE EXISTING BACK

BOXES MAY BE RE-USED FOR NEW DEVICES,

PROVIDED THAT THE BACK BOX DIMENSIONS ARE

COMPATIBLE WITH NEW DEVICES AND THE BACK BOX

IS IN THE CORRECT LOCATION. EXISTING CONDUIT

SERVING THE EXISTING BACK BOX MAY BE RE-USED

IF THE CONDUIT IS NO LESS THAN 3/4 IN., INSTALLED

IN ACCORDANCE WITH NEC AND IS WARRANTED AS

NEW.

3. THIS BUILDING WILL BE VACATED DURING

CONSTRUCTION.

4. UNLESS OTHERWISE NOTED, CEILINGS HEIGHTS ARE

LESS THAN 10FT.

5. UNLESS OTHERWISE NOTED, CEILINGS FEATURE

ACOUSTICAL CEILING TILES SUPPORTED BY METAL

GRIDDED FRAMES. REFER ALSO TO CEILING LEGEND.

6. THROUGH AND MEMBRANE PENETRATIONS OF FIRE

AND SMOKE RATED CONSTRUCTION SHALL BE

PERFORMED IN A MANNER THAT MAINTAINS THE

EXISTING RATINGS. LISTED FIRESTOPPING SYSTEMS

AND MATERIALS SHALL BE PROVIDED AS REQUIRED.

REFERENCE DIVISION 07 84 00.

SHEET KEY NOTES

1. DEMO EXISTING NAC POWER SUPPLY CONDUIT AND WIRE IN

ITS ENTIRETY.

2. DOORS SEPARATING CORRIDORS AND DAY ROOMS FROM

CENTER LOBBY WERE ONCE EQUIPPED WITH DOOR

HOLDERS. THE DOOR HOLDERS HAVE BEEN REMOVED AND

DOORS ARE CURRENTLY EQUIPPED WITH DOOR CLOSERS

TO KEEP DOORS CLOSED. SINGLE GANG BACK BOXES WITH

BLANK COVERS REMAIN. CONTRACTOR SHALL DEMO WIRE

AND BACK BOXES ASSOCIATED WITH THE ONCE INSTALLED

DOOR HOLDERS. CONTRACTOR SHALL PATCH AND PAINT

WALL OPENINGS TO MATCH SURROUNDING SURFACES.

uu uu u u u

S S S SMOKE-RATED PARTITION

1-HOUR FIRE-RATED BARRIER

2-HOUR FIRE-RATED BARRIER

WALL RATINGS

ACT LIFT-OUT CEILING TILES

GYPSUM BOARD

OPEN TO DECK ABOVE

CEILING LEGEND

A

B

C

370CORRIDOR

DAYROOM

336 ROOM

ROOM

ROOM

ROOM

ROOM

ROOM

ROOM

ROOM

ROOM

MECHANICAL

ROOM

ROOM

CORRIDOR

LAUNDRY

u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u uuuu u u

UTILITY

AHU-1

DET

DET

DET DET

DET DET

DETDETDETDET

DETDETDETDET

DET DET

DET DET

DET

F

DETDET

DET

DET

FD

3A M

AT

C

H

LI

N E

FD

3B

FD

3A

M

AT

C H

LI

N

E

FD

3B

ELECTRICAL PANELS

3A AND 3B

DET

AOM

A

B

B

B

A

B

B

B

A

B

B

B

A A A

B

B

B

AAAA

AAA

A B B B

B B B B

B

B

B

BBB

B C

B

A A

DET

A

DET

A B

0 8'4' 16'SCALE: 1/8" = 1'-0"

LEVEL THREE DEMOLITION PLAN - AREA B - FIRE ALARMA1

PLAN

NORTH

D

EL

IV

ER

Y O

R D

ER

N

O

D

ES

IG

N

ED

B

Y:

D

ES

C R

IP

TI

O N

M

AR

K

SI

ZE

SU

BM

IT

TE

D B

Y:

D

AT

E

C O

N

TR

AC

T

N U

M

BE

R

C H

EC

KE

D B

Y:

D R

AW

N

B Y:

IS

SU

E D

AT

E:

G

2 3 4 5 6 7 8 9 10

F

E

D

C

B

A SHEET ID

H D

R E ng in ee rin g, In c.

E.

P

AR

KC

EN

TE

R B

LV

D

BO

IS

E, ID

(2

) 3

-7

U .S

. A

IR

F O

R C

E

C

ES

/C

EN

M O

U N

TA

IN

H O

M E

AI

R

F O

R C

E

BA

SE

M

O U

N

TA

IN

H

O M

E, ID

AH

O

FA

-2

0- D

-0

D

EC

EM

BE

R

PR

O

JE

C

T N

U M

BE

R

SH

EE

T N

U M

BE

R

AN

SI

D

FA

-2

5- F-

M O

U N

TA

IN

H O

M E

AI

R

F O

R C

E

BA

SE

B2

FI

R

E

AL

AR

M

R

EP

AI

R

100% DESIGN SUBMITTAL

O

F

Z.

S

AC

H

SE

N

M

AI

ER

W . C

U N

AR

D

R . R

IC

H

TE

R

P.

D

ER

R

AR

EA

B

FI

R

E

AL

AR

M

LE

VE

L

TH

R

EE

D

EM

O

LI

TI

O

N P

LA

N

FD103B

CORRIDORS HAVE 1/2-HOUR RATED FIRE-WALLS

SCALE: NTS

KEYPLANA9

PLAN

NORTH

SHEET NOTES

1. REMOVE EXISTING FIRE ALARM SYSTEM IN ITS

ENTIRETY. PATCH AND PAINT WALL AND CEILING

OPENINGS NOT SLATED FOR RE-USE TO MATCH

SURROUNDING SURFACES.

2. DEMO EXISTING CEILING AND WALL MOUNTED

DEVICES, BACK BOXES, CONDUIT AND WIRE IN THEIR

ENTIRETY. ALTERNATELY, THE EXISTING BACK

BOXES MAY BE RE-USED FOR NEW DEVICES,

PROVIDED THAT THE BACK BOX DIMENSIONS ARE

COMPATIBLE WITH NEW DEVICES AND THE BACK BOX

IS IN THE CORRECT LOCATION. EXISTING CONDUIT

SERVING THE EXISTING BACK BOX MAY BE RE-USED

IF THE CONDUIT IS NO LESS THAN 3/4 IN., INSTALLED

IN ACCORDANCE WITH NEC AND IS WARRANTED AS

NEW.

3. THIS BUILDING WILL BE VACATED DURING

CONSTRUCTION.

4. UNLESS OTHERWISE NOTED, CEILINGS HEIGHTS ARE

LESS THAN 10FT.

5. UNLESS OTHERWISE NOTED, CEILINGS FEATURE

ACOUSTICAL CEILING TILES SUPPORTED BY METAL

GRIDDED FRAMES. REFER ALSO TO CEILING LEGEND.

6. THROUGH AND MEMBRANE PENETRATIONS OF FIRE

AND SMOKE RATED CONSTRUCTION SHALL BE

PERFORMED IN A MANNER THAT MAINTAINS THE

EXISTING RATINGS. LISTED FIRESTOPPING SYSTEMS

AND MATERIALS SHALL BE PROVIDED AS REQUIRED.

REFERENCE DIVISION 07 84 00.

uu uu u u u

S S S SMOKE-RATED PARTITION

1-HOUR FIRE-RATED BARRIER

2-HOUR FIRE-RATED BARRIER

WALL RATINGS

ACT LIFT-OUT CEILING TILES

GYPSUM BOARD

OPEN TO DECK ABOVE

CEILING LEGEND

A

B

ROOM

MAINT

OFFICE

ROOM

STORAGE

MECH

LAUNDRY

ROOM

ROOM

ROOM

ROOM

STAIRS

STAIRS

ROOM

ROOM

ROOM

ROOM

COMM

136 VESTIBULE

CENTER

LOBBY

VESTIBULE

BREAK

ROOM

1XX

JC

LINEN

CORRIDOR

CORRIDOR

u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u

AIR COOLED

CONDENSOR

N

AC

FM

CU

N

AC

FAA

/LO

C

CS CS CS CS

CS CS CS CS

CSCS

CS

C

C C

F C C

C C

C

C

WP

WP

F

F

FC

FA

1A M

AT

C

H

LI

N E

FA

1B

FA

1A

M

AT

C H

LI

N

E

FA

1B

ELECTRICAL PANELS

1C AND 1D

WP

A E S

SBSBSBSB

SBSBSBSB

SB

SB SB

AC B

B B B B

A

B

B BA A

B B B B

A

B

B A A

B

B A

C C

B A B

B

A

B

B

B

A B

B

B B

A A AB

B

MECH. YARD

WP

WP

WP

COF WP

(NON-ENVIRONMENTALLY

CONTROLLED SPACE)

A B

0 8'4' 16'SCALE: 1/8" = 1'-0"

LEVEL ONE FLOOR PLAN - AREA A - FIRE ALARM AND MASS NOTIFICATION SYSTEMA1

PLAN

NORTH

D

EL

IV

ER

Y O

R D

ER

N

O

D

ES

IG

N

ED

B

Y:

D

ES

C R

IP

TI

O N

M

AR

K

SI

ZE

SU

BM

IT

TE

D B

Y:

D

AT

E

C O

N

TR

AC

T

N U

M

BE

R

C H

EC

KE

D B

Y:

D R

AW

N

B Y:

IS

SU

E D

AT

E:

G

2 3 4 5 6 7 8 9 10

F

E

D

C

B

A SHEET ID

H D

R E ng in ee rin g, In c.

E.

P

AR

KC

EN

TE

R B

LV

D

BO

IS

E, ID

(2

) 3

-7

U .S

. A

IR

F O

R C

E

C

ES

/C

EN

M O

U N

TA

IN

H O

M E

AI

R

F O

R C

E

BA

SE

M

O U

N

TA

IN

H

O M

E, ID

AH

O

FA

-2

0- D

-0

D

EC

EM

BE

R

PR

O

JE

C

T N

U M

BE

R

SH

EE

T N

U M

BE

R

AN

SI

D

FA

-2

5- F-

M O

U N

TA

IN

H O

M E

AI

R

F O

R C

E

BA

SE

B2

FI

R

E

AL

AR

M

R

EP

AI

R

100% DESIGN SUBMITTAL

O

F

Z.

S

AC

H

SE

N

M

AI

ER

W . C

U N

AR

D

R . R

IC

H

TE

R

P.

D

ER

R

AN

D

M

AS

S N

O

TI

FI

C

AT

IO

N S

YS

TE

M

LE

VE

L

O N

E

FL

O O

R P

LA

N

AR

EA

A

FI

R E

AL

AR

M

FA101A

B2318

CORRIDORS HAVE 1/2-HOUR RATED FIRE-WALLS

SHEET NOTES

1. THIS BUILDING WILL BE VACATED DURING

CONSTRUCTION.

2. UNLESS OTHERWISE NOTED, CEILINGS HEIGHTS ARE

LESS THAN 10FT.

3. UNLESS OTHERWISE NOTED, CEILINGS FEATURE

ACOUSTICAL CEILING TILES SUPPORTED BY METAL

GRIDDED FRAMES. REFER ALSO TO CEILING LEGEND.

4. AUDIBLE APPLIANCES INSTALLED WITHIN SLEEPING

ROOMS SHALL HAVE A SOUND LEVEL OF AT LEAST 15

DB ABOVE THE AVERAGE AMBIENT SOUND LEVEL OR

5 DB ABOVE THE MAXIMUM SOUND LEVEL HAVING A

DURATION OF AT LEAST 60 SECONDS OR A SOUND

LEVEL OF AT LEAST 75 DBA, WHICHEVER IS GREATER,

MEASURED AT THE PILLOW LEVEL USING THE

A-WEIGHTED SCALE (DBA) (REFERENCE NFPA 72

§18.4.6).

5. AUDIBLE APPLIANCES INSTALLED WITHIN SLEEPING

ROOMS SHALL BE LOW FREQUENCY (520HZ) DEVICES.

6. UPON DETECTION OF SMOKE WITHIN A SINGLE DORM

ROOM, THE SOUNDER BASE SHALL INITIATE 520 HZ

TEMPORAL 3 ALARM TONE. UPON ACTIVATION OF

TWO OR MORE ROOM SMOKE DETECTORS,

ACTIVATION OF COMMON AREA SMOKE OR HEAT

DETECTOR OR ACTIVATION OF MANUAL PULL

STATION, DORM ROOM SOUNDER BASE SHALL

SILENCE, ALLOWING SPEAKERS TO INITIATE GENERAL

AUDIO EVACUATION MESSAGES.

7. SPEAKERS WITHIN THE DORM ROOM SHALL SOUND

UPON ACTIVATION OF SECOND DORM ROOM SMOKE

DETECTOR, ACTIVATION OF COMMON AREA HEAT OR

SMOKE DETECTION, SPRINKLER SYSTEM WATER

FLOW, ACTIVATION OF MANUAL PULL STATION OR

ACTIVATION OF CARBON MONOXIDE DETECTION.

8. CENTER SPEAKERS WITHIN DORM ROOMS TO ALLOW

FOR THE GREATEST FLEXIBILITY WITH RESPECT TO

FURNITURE PLACEMENT.

9. THROUGH AND MEMBRANE PENETRATIONS OF FIRE

AND SMOKE RATED CONSTRUCTION SHALL BE

PERFORMED IN A MANNER THAT MAINTAINS THE

EXISTING RATINGS. LISTED FIRESTOPPING SYSTEMS

AND MATERIALS SHALL BE PROVIDED AS REQUIRED.

REFERENCE DIVISION 07 84 00.

SHEET KEY NOTES

1. INSTALL NEW FMCU, NAC POWER SUPPLIES, AES

TRANSMITTERS AND SURGE SUPPRESSORS. INSTALL

ENGRAVED PLASTIC SIGN IDENTIFYING FIRE ALARM/MASS

NOTIFICATION CONTROL UNIT, NOTIFICATION APPLIANCE

POWER SUPPLIES, AND SURGE SUPPRESSOR ENCLOSURE.

INSTALL ENGRAVED SIGNAGE INDICATING DEDICATED

120VAC SOURCE, TO INCLUDE PANEL NUMBER/NAME AND

CIRCUIT NUMBER(S).

2. DEDICATED 120 VAC POWER SHALL BE INSTALLED IN

ACCORDANCE WITH THE NATIONAL ELECTRICAL CODE,

NFPA 72, AND UFC 3-520-01 §3-2.7 - INTERIOR ELECTRICAL

SYSTEMS. WHERE MORE THAN ONE DEDICATED CIRCUIT IS

REQUIRED, INSTALL DEDICATED FIRE PROTECTION

SUB-PANEL HAVING NO FEWER THAN 6 CIRCUITS.

3. INSTALL EXTERIOR OMNIDIRECTIONAL VHF ANTENNA FOR

AES RADIO TRANSMITTER. COORDIANTE LOCATION WITH

GOVERNMENT. ANTENNA MOUNTING LOCATION SHALL BE

BASED UPON SIGNAL STRENGTH.

uu uu u u u

S S S SMOKE-RATED PARTITION

1-HOUR FIRE-RATED BARRIER

2-HOUR FIRE-RATED BARRIER

WALL RATINGS

SCALE: NTS

KEYPLANA9

PLAN

NORTH

ACT LIFT-OUT CEILING TILES

GYPSUM BOARD

OPEN TO DECK ABOVE

CEILING LEGEND

A

B

C

VESTIBULE

CORRIDOR

DAYROOM

ROOM

ROOM

ROOM

ROOM

ROOM

ROOM

ROOM

ROOM

ROOM

STORAGE

B

ROOM

ROOM

CORRIDOR

STAIRS

u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u

CS CS

CS CS

CSCSCSCS

CSCSCS

C CC

CC

C

C

WP

F

FA

1A M

AT

C

H

LI

N E

FA

1B

FA

1A

M

AT

C H

LI

N

E

FA

1B

ELECTRICAL

PANELS

1A AND 1B

C

SB SB

SB SB

SBSBSBSB

SBSBSB

A

B

B

B

A

B

B

B

A

B

B

B

A A A

B

B

B

AAAA

AAA

A

A B B B

B B B B

B

B

B

BBB

BB

BB

A B

0 8'4' 16'SCALE: 1/8" = 1'-0"

LEVEL ONE FLOOR PLAN - AREA B - FIRE ALARM AND MASS NOTIFICATION SYSTEMA1

PLAN

NORTH

D

EL

IV

ER

Y O

R D

ER

N

O

D

ES

IG

N

ED

B

Y:

D

ES

C R

IP

TI

O N

M

AR

K

SI

ZE

SU

BM

IT

TE

D B

Y:

D

AT

E

C O

N

TR

AC

T

N U

M

BE

R

C H

EC

KE

D B

Y:

D R

AW

N

B Y:

IS

SU

E D

AT

E:

G

2 3 4 5 6 7 8 9 10

F

E

D

C

B

A SHEET ID

H D

R E ng in ee rin g, In c.

E.

P

AR

KC

EN

TE

R B

LV

D

BO

IS

E, ID

(2

) 3

-7

U .S

. A

IR

F O

R C

E

C

ES

/C

EN

M O

U N

TA

IN

H O

M E

AI

R

F O

R C

E

BA

SE

M

O U

N

TA

IN

H

O M

E, ID

AH

O

FA

-2

0- D

-0

D

EC

EM

BE

R

PR

O

JE

C

T N

U M

BE

R

SH

EE

T N

U M

BE

R

AN

SI

D

FA

-2

5- F-

M O

U N

TA

IN

H O

M E

AI

R

F O

R C

E

BA

SE

B2

FI

R

E

AL

AR

M

R

EP

AI

R

100% DESIGN SUBMITTAL

O

F

Z.

S

AC

H

SE

N

M

AI

ER

W . C

U N

AR

D

R . R

IC

H

TE

R

P.

D

ER

R

AN

D

M

AS

S N

O

TI

FI

C

AT

IO

N S

YS

TE

M

LE

VE

L

O N

E

FL

O O

R P

LA

N

AR

EA

B

FI

R E

AL

AR

M

FA101B

B2318

CORRIDORS HAVE 1/2-HOUR RATED FIRE-WALLS

SHEET NOTES

1. THIS BUILDING WILL BE VACATED DURING

CONSTRUCTION.

2. UNLESS OTHERWISE NOTED, CEILINGS HEIGHTS ARE

LESS THAN 10FT.

3. UNLESS OTHERWISE NOTED, CEILINGS FEATURE

ACOUSTICAL CEILING TILES SUPPORTED BY METAL

GRIDDED FRAMES. REFER ALSO TO CEILING LEGEND.

4. AUDIBLE APPLIANCES INSTALLED WITHIN SLEEPING

ROOMS SHALL HAVE A SOUND LEVEL OF AT LEAST 15

DB ABOVE THE AVERAGE AMBIENT SOUND LEVEL OR

5 DB ABOVE THE MAXIMUM SOUND LEVEL HAVING A

DURATION OF AT LEAST 60 SECONDS OR A SOUND

LEVEL OF AT LEAST 75 DBA, WHICHEVER IS GREATER,

MEASURED AT THE PILLOW LEVEL USING THE

A-WEIGHTED SCALE (DBA) (REFERENCE NFPA 72

§18.4.6).

5. AUDIBLE APPLIANCES INSTALLED WITHIN SLEEPING

ROOMS SHALL BE LOW FREQUENCY (520HZ) DEVICES.

6. UPON DETECTION OF SMOKE WITHIN A SINGLE DORM

ROOM, THE SOUNDER BASE SHALL INITIATE 520 HZ

TEMPORAL 3 ALARM TONE. UPON ACTIVATION OF

TWO OR MORE ROOM SMOKE DETECTORS,

ACTIVATION OF COMMON AREA SMOKE OR HEAT

DETECTOR OR ACTIVATION OF MANUAL PULL

STATION, DORM ROOM SOUNDER BASE SHALL

SILENCE, ALLOWING SPEAKERS TO INITIATE GENERAL

AUDIO EVACUATION MESSAGES.

7. SPEAKERS WITHIN THE DORM ROOM SHALL SOUND

UPON ACTIVATION OF SECOND DORM ROOM SMOKE

DETECTOR, ACTIVATION OF COMMON AREA HEAT OR

SMOKE DETECTION, SPRINKLER SYSTEM WATER

FLOW, ACTIVATION OF MANUAL PULL STATION OR

ACTIVATION OF CARBON MONOXIDE DETECTION.

8. CENTER SPEAKERS AND SMOKE DETECTORS WITHIN

DORM ROOMS TO ALLOW FOR THE GREATEST

FLEXIBILITY WITH RESPECT TO FURNITURE

PLACEMENT.

9. THROUGH AND MEMBRANE PENETRATIONS OF FIRE

AND SMOKE RATED CONSTRUCTION SHALL BE

PERFORMED IN A MANNER THAT MAINTAINS THE

EXISTING RATINGS. LISTED FIRESTOPPING SYSTEMS

AND MATERIALS SHALL BE PROVIDED AS REQUIRED.

REFERENCE DIVISION 07 84 00.

(TYPICAL)

uu uu u u u

S S S SMOKE-RATED PARTITION

1-HOUR FIRE-RATED BARRIER

2-HOUR FIRE-RATED BARRIER

WALL RATINGS

SCALE: NTS

KEYPLANA9

PLAN

NORTH

ACT LIFT-OUT CEILING TILES

GYPSUM BOARD

OPEN TO DECK ABOVE

CEILING LEGEND

A

B

C

SHEET KEY NOTES

1. INSTALL EXTERIOR OMNIDIRECTIONAL VHF ANTENNA FOR

AES RADIO TRANSMITTER. COORDIANTE LOCATION WITH

GOVERNMENT. ANTENNA MOUNTING LOCATION SHALL BE

BASED UPON SIGNAL STRENGTH.

ROOM

HOSPITALITY

ROOM

ROOM

ROOM

ROOM

ROOM

ROOM

ROOM

ROOM

STAIRS

STAIRS

ROOM

ROOM

ROOM

ROOM

STORAGE

CENTER

LOBBY

CORRIDOR

CORRIDOR

u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u uuu u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u

LODGING

FAA

/LO

C

CS CS CS CS

CS…

This is the start of the file's text. The full file is on GovTribe.

File details come from the government source that posted it. Updated .