20251219_MHAFB B2318 Fire Alarm Repair_100 Design Drawings.pdf
PDF 8 MB Posted
- Attached to
- Fire Alarm Replacement Bldg 2318 & 2416
- Solicitation number
- FA489726Q0007
About this file
This is a 100% Design Submittal for a fire alarm system replacement project at Mountain Home Air Force Base in Idaho. The project, identified as Delivery Order FA4897-25-F-0017 under Master Contract FA4897-20-D-0001, involves the complete demolition and replacement of the existing fire alarm system in Building 2318, a three-level dormitory facility. The design submittal, prepared by HDR Engineering, Inc., comprises 22 sheets of detailed architectural and engineering drawings, including demolition plans, floor plans with device locations, typical installation details, sequence of operations matrices, riser diagrams, and voice message schedules. The project includes installation of a Silent Knight 6820 EVS Fire Alarm and Mass Notification Control Unit, addressable smoke and heat detectors, manual pull stations, speaker systems for both fire alarm and mass notification purposes, notification appliance circuits, emergency voice systems, and base-wide monitoring integration via an existing AES IntelliNet 2.0 mesh network.
The design incorporates comprehensive fire alarm and mass notification capabilities across all building levels, with specific provisions for dormitory room sounder bases at 520 Hz frequency, low-frequency audible appliances in sleeping areas, and coordinated voice messaging for fire emergencies, carbon monoxide detection, active shooter lockdown, bomb threats, weather warnings, and system tests. The design includes dedicated 120 VAC power provisioning with surge protection, dedicated breaker protection, proper cable routing and separation per National Electrical Code standards, and firestopping for all fire and smoke-rated penetrations. Construction requirements specify full building vacation during work, restoration of staging areas to original condition, coordination of haul routes and laydown yards with the Contracting Officer, and implementation of best management practices for environmental protection.
View the file
Other files
Show all 19
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
IDAHO
MOUNTAIN HOME
BOISE
GRAND VIEW
BRUNEAU
NAMPA
TO
WINNEMUCCA, NV
TO PORTLAND, OR
SEATTLE, WA
TO ELKO, NV
MOUNTAIN
HOME AFB
IDAHO
TO SALT
LAKE
CITY, UT
PROJECT
LOCATION
D
EL
IV
ER
Y O
R D
ER
N
O
D
ES
IG
N
ED
B
Y:
D
ES
C R
IP
TI
O N
M
AR
K
SI
ZE
SU
BM
IT
TE
D B
Y:
D
AT
E
C O
N
TR
AC
T
N U
M
BE
R
C H
EC
KE
D B
Y:
D R
AW
N
B Y:
IS
SU
E D
AT
E:
G
2 3 4 5 6 7 8 9 10
F
E
D
C
B
A SHEET ID
H D
R E ng in ee rin g, In c.
E.
P
AR
KC
EN
TE
R B
LV
D
BO
IS
E, ID
(2
) 3
-7
U .S
. A
IR
F O
R C
E
C
ES
/C
EN
M O
U N
TA
IN
H O
M E
AI
R
F O
R C
E
BA
SE
M
O U
N
TA
IN
H
O M
E, ID
AH
O
FA
-2
0- D
-0
D
EC
EM
BE
R
PR
O
JE
C
T N
U M
BE
R
SH
EE
T N
U M
BE
R
AN
SI
D
FA
-2
5- F-
M O
U N
TA
IN
H O
M E
AI
R
F O
R C
E
BA
SE
B2
FI
R
E
AL
AR
M
R
EP
AI
R
100% DESIGN SUBMITTAL
O
F
Z.
S
AC
H
SE
N
M
AI
ER
W . C
U N
AR
D
R . R
IC
H
TE
R
P.
D
ER
R
C O
VE
R
S H
EE
T
G001 B2318
ISSUE DATE:
DELIVERY ORDER NO.:
CONTRACT NO.:
366 CES/CEN
FA4897-25-F-0017
19 DECEMBER 2025
FA4897-20-D-0001
MOUNTAIN HOME AIR FORCE BASE, ID
REPLACE FIRE ALARM SYSTEM, BLDG 2318
100% DESIGN SUBMITTAL
SHEET INDEX
NO. SHEET NO. SHEET NAME
1 G001 COVER SHEET
2 G002 CONTRACTOR HAUL ROUTE
3 FA001 GENERAL FIRE ALARM AND DEMOLITION NOTES
4 FA002 SYMBOLS LEGEND AND CODE ANALYSIS
5 FD101A LEVEL ONE DEMOLITION PLAN - AREA A - FIRE ALARM
6 FD101B LEVEL ONE DEMOLITION PLAN - AREA B - FIRE ALARM
7 FD102A LEVEL TWO DEMOLITION PLAN - AREA A - FIRE ALARM
8 FD102B LEVEL TWO DEMOLITION PLAN - AREA B - FIRE ALARM
9 FD103A LEVEL THREE DEMOLITION PLAN - AREA A - FIRE ALARM
10 FD103B LEVEL THREE DEMOLITION PLAN - AREA B - FIRE ALARM
11 FA101A LEVEL ONE FLOOR PLAN - AREA A - FIRE ALARM AND MASS NOTIFICATION SYSTEM
12 FA101B LEVEL ONE FLOOR PLAN - AREA B - FIRE ALARM AND MASS NOTIFICATION SYSTEM
13 FA102A LEVEL TWO FLOOR PLAN - AREA A - FIRE ALARM AND MASS NOTIFICATION SYSTEM
14 FA102B LEVEL TWO FLOOR PLAN - AREA B - FIRE ALARM AND MASS NOTIFICATION SYSTEM
15 FA103A LEVEL THREE FLOOR PLAN - AREA A - FIRE ALARM AND MASS NOTIFICATION SYSTEM
16 FA103B LEVEL THREE FLOOR PLAN - AREA B - FIRE ALARM AND MASS NOTIFICATION SYSTEM
17 FA501 FIRE ALARM AND MASS NOTIFICATION SYSTEM TYPICAL DETAILS
18 FA502 FIRE ALARM AND MASS NOTIFICATION SYSTEM TYPICAL DETAILS
19 FA503 FIRE ALARM AND MASS NOTIFICATION SYSTEM TYPICAL DETAILS
20 FA601 FIRE ALARM AND MASS NOTIFICATION SYSTEM SEQUENCE OF OPERATION MATRIX
21 FA602 FIRE ALARM AND MASS NOTIFICATION SYSTEM RISER DIAGRAM
22 FA603 FIRE ALARM AND MASS NOTIFICATION SYSTEM VOICE MESSAGES
12/19/2025
12 DEC 2025
LIBERATOR STREET
AARDVARK AVENUE
FALCON STREET
ALPINE STREET
BOMBER STREET
RUNWAY 12-30
PHANTOM AVENUE
CIVIL ENGINEERING
BUILDING 1300
SECURITY FORCES
FIRE DEPT.
BUILDING 206
RECYCLING CENTER
BASE EXCHANGE (BX)
HOSPITAL
AAFES SERVICE STATION
MAIN GATE
PERIMETER ROAD OFF HIGHWAY 167 (GRAND VIEW ROAD)
GRAND VIEW GATE
(CONTRACTOR ACCESS)
GUNFIG
HTER AVENUE
2N
D AVENUE
1S
T AVENUE
WING HQ
BUILDING 512
th
AVENUE
PROJECT AREA,
SEE ENLARGED
PLAN, THIS SHEET
PE
R
IM
ET
ER
R
O
AD
FAC 3490 HEADWORKS
B2318
D
EL
IV
ER
Y O
R D
ER
N
O
D
ES
IG
N
ED
B
Y:
D
ES
C R
IP
TI
O N
M
AR
K
SI
ZE
SU
BM
IT
TE
D B
Y:
D
AT
E
C O
N
TR
AC
T
N U
M
BE
R
C H
EC
KE
D B
Y:
D R
AW
N
B Y:
IS
SU
E D
AT
E:
G
2 3 4 5 6 7 8 9 10
F
E
D
C
B
A SHEET ID
H D
R E ng in ee rin g, In c.
E.
P
AR
KC
EN
TE
R B
LV
D
BO
IS
E, ID
(2
) 3
-7
U .S
. A
IR
F O
R C
E
C
ES
/C
EN
M O
U N
TA
IN
H O
M E
AI
R
F O
R C
E
BA
SE
M
O U
N
TA
IN
H
O M
E, ID
AH
O
FA
-2
0- D
-0
D
EC
EM
BE
R
PR
O
JE
C
T N
U M
BE
R
SH
EE
T N
U M
BE
R
AN
SI
D
FA
-2
5- F-
M O
U N
TA
IN
H O
M E
AI
R
F O
R C
E
BA
SE
B2
FI
R
E
AL
AR
M
R
EP
AI
R
100% DESIGN SUBMITTAL
O
F
Z.
S
AC
H
SE
N
M
AI
ER
B.
C
U N
AR
D
R . R
IC
H
TE
R
P.
D
ER
R
C O
N
TR
AC
TO
R H
AU
L
R O
U
TE
G002 B2318
CONTRACTOR ACCESS/HAUL ROUTE
BUILDING OF INTEREST
GENERAL NOTES
LEGEND
A1 CONTRACTOR ACCESS AND HAUL ROUTE
SCALE: 1" = 1000' 0 1000 2000 A6 PROJECT AREA
SCALE: 1" = 100' 0 100 200
PLAN
NORTH
PLAN
NORTH
1. RESTORE STAGING AND STORAGE AREAS TO ORIGINAL CONDITION AND TO THE
SATISFACTION OF THE CONTRACTING OFFICER.
2. 30 DAYS MINIMUM PRIOR TO MOBILIZATION, THE CONTRACTOR IS RESPONSIBLE
FOR SUBMITTING A CONTRACTOR LAYDOWN YARD REQUEST TO THE BASE
COMMUNITY PLANNER FOR COORDINATION AND APPROVAL (THIS INCLUDES
STOCKPILE LOCATIONS).
3. IMPLEMENT BEST MANAGEMENT PRACTICES (BMPS) PRIOR TO COMMENCING
CONSTRUCTION ACTIVITIES.
4. COORDINATE HAUL ROUTES, LAYDOWN AREAS, AND UTILITY CONNECTIONS
WITH THE CONTRACTING OFFICER FOR APPROVAL.
FALCON AVE.
B2318
D
EL
IV
ER
Y O
R D
ER
N
O
D
ES
IG
N
ED
B
Y:
D
ES
C R
IP
TI
O N
M
AR
K
SI
ZE
SU
BM
IT
TE
D B
Y:
D
AT
E
C O
N
TR
AC
T
N U
M
BE
R
C H
EC
KE
D B
Y:
D R
AW
N
B Y:
IS
SU
E D
AT
E:
G
2 3 4 5 6 7 8 9 10
F
E
D
C
B
A SHEET ID
H D
R E ng in ee rin g, In c.
E.
P
AR
KC
EN
TE
R B
LV
D
BO
IS
E, ID
(2
) 3
-7
U .S
. A
IR
F O
R C
E
C
ES
/C
EN
M O
U N
TA
IN
H O
M E
AI
R
F O
R C
E
BA
SE
M
O U
N
TA
IN
H
O M
E, ID
AH
O
FA
-2
0- D
-0
D
EC
EM
BE
R
PR
O
JE
C
T N
U M
BE
R
SH
EE
T N
U M
BE
R
AN
SI
D
FA
-2
5- F-
M O
U N
TA
IN
H O
M E
AI
R
F O
R C
E
BA
SE
B2
FI
R
E
AL
AR
M
R
EP
AI
R
100% DESIGN SUBMITTAL
O
F
Z.
S
AC
H
SE
N
M
AI
ER
W . C
U N
AR
D
R . R
IC
H
TE
R
P.
D
ER
R
D
EM
O
LI
TI
O
N N
O
TE
S G
EN
ER
AL
F
IR
E
AL
AR
M A
N D
FA001
B2318
GENERAL FIRE ALARM AND MASS NOTIFICATION NOTES GENERAL FIRE ALARM DEMOLITION NOTES
1. THE EXISTING CONDITIONS AND DEMOLITION PLANS WERE DEVELOPED BASED
ON RECORD DRAWINGS AND FIELD VERIFICATION WHERE POSSIBLE.
CONTRACTOR SHALL ALLOW FOR VARIANCES IN DEVICES DEPICTED ON
DEMOLITION DRAWINGS AND UNFORESEEN CONDITIONS.THE CONTRACTOR
SHALL NOTIFY THE CONTRACTING OFFICER OR CONTRACTING OFFICER'S
REPRESENTATIVE (COR) OF DISCREPANCIES AND UNDOCUMENTED
CONDITIONS PRIOR TO INITIATING WORK.
2. CONTRACTOR SHALL BE RESPONSIBLE FOR PROTECTING ALL EXISTING
CONDITIONS INCLUDING BUT NOT LIMITED TO: STRUCTURES, CEILINGS, WALLS,
FLOORS, FURNITURE, EQUIPMENT, UTILITIES, ETC. DAMAGE TO EXISTING
CONDITIONS SHALL BE REPAIRED AT NO ADDITIONAL COST TO THE
GOVERNMENT.
3. CONTRACTOR SHALL BE RESPONSIBLE FOR PATCHING AND PAINTING FLOORS,
CEILINGS, AND WALLS TO MATCH EXISTING CONDITIONS IN ALL AREAS
IMPACTED BY THE DEMOLITION OF THE EXISTING FIRE ALARM SYSTEM AND
INSTALLATION OF THE NEW FIRE ALARM AND MASS NOTIFICATION SYSTEM.
4. ALL FIRE ALARM CONDUIT NOT INCORPORATED WITHIN NEW FIRE ALARM AND
MASS NOTIFICATION SYSTEM SHALL BE REMOVED IN THEIR ENTIRETY, WITH
THE EXCEPTION OF CONDUIT CONCEALED WITHIN MASONRY WALLS, FINISHED
GYPSUM BOARD WALLS, FINISHED GYPSUM BOARD CEILING WITHOUT ACCESS
AS WELL AS THOSE CONCEALED BEHIND STRUCTURAL COMPONENTS. ALL
ABANDONED CONDUIT SHALL BE LABELED AND ITS OUTLET LOCATION
IDENTIFIED. ALL WIRING/CABLE SHALL BE REMOVED FROM ANY CONDUIT
ALLOWED TO REMAIN IN PLACE.
5. IONIZATION PRINCIPLE SMOKE DETECTORS CONTAIN THE RADIOACTIVE
ISOTOPE AMERICIUM 241. SEPARATE IONIZATION PRINCIPLE SMOKE
DETECTORS FROM OTHER ELECTRONIC WASTE AND DISPOSE OF IN
ACCORDANCE WITH FEDERAL, STATE AND LOCAL REGULATIONS.
6. ALL ABANDONED THROUGH- AND MEMBRANE-PENETRATIONS RESULTING
FROM THE EXISTING FIRE ALARM SYSTEM DEMOLITION WILL BE CLOSED AND
OR SEALED TO RESTORE FIRE-RESISTANCE AND SMOKE RATINGS.
7. INDIVIDUAL EXISTING SUSPENDED ACOUSTICAL CEILING TILES WILL BE
REMOVED AS REQUIRED TO COMPLETE THE DEMOLITION AND INSTALLATION
OF THE FIRE ALARM / MASS NOTIFICATION SYSTEM. NEW REPLACEMENT TILES
WILL MATCH EXISTING TILES. WHERE THE EXISTING CEILING TILES HAVE BEEN
DISCONTINUED, THE CONTRACTOR WILL IDENTIFY A DONOR ROOM FROM
WHICH TILES WILL BE REMOVED AND USED IN OTHER BUILDING AREAS TO
MATCH EXISTING TILES. ALL TILES WITHIN THE DONOR ROOM WILL BE
REPLACED WITH NEW TILES, CURRENTLY IN PRODUCTION HAVING SIMILAR
SALIENT FEATURES AND CLOSELY MATCHING THE ORIGINAL TILES. CARE
SHOULD BE TAKEN NOT TO ADVERSELY DISTURB THERMAL OR ACOUSTIC
INSULATION SUPPORTED BY CEILING TILES.
1. PROVIDE A COMPLETE ADDRESSABLE FIRE ALARM
AND MASS NOTIFICATION SYSTEM WITH
EMERGENCY VOICE COMMUNICATIONS
THROUGHOUT AS NOTED ON DRAWINGS. INSTALL
SILENT KNIGHT 6820EVS SERIES FIRE ALARM / MASS
NOTIFICATION CONTROL UNIT, SILENT KNIGHT
EVS-RCU SUPERVISED REMOTE COMMAND UNIT
(LOC), AND SILENT KNIGHT 5895 NOTIFICATION
APPLIANCE CIRCUIT (NAC) POWER SUPPLIES AS
DETAILED ON DRAWINGS AND AS REQUIRED.
PROVIDE COMPLETE OCCUPANT NOTIFICATION
THROUGHOUT. PROVIDE MANUAL PULL STATIONS AT
ALL EXITS. PROVIDE DUCT SMOKE DETECTION AND
HVAC SHUT-DOWN PER NFPA 90A, NFPA 90B, AND
UFC 3-600-01. MONITOR ALL FIRE PROTECTION
SYSTEMS INCLUDING BUT NOT LIMITED TO
AUTOMATIC SPRINKLERS.
2. THE NEW FIRE ALARM AND MASS NOTIFICATION
SYSTEM SHALL BE EQUIPPED WITH AN AES
INTELLINET 2.0 MESH NETWORK TRANSMITTER. THE
TRANSMITTER SHALL TRANSMIT THE FOLLOWING
POINTS.
1. GENERAL FIRE ALARM ACTIVATION OF DORM
ROOM SMOKE DETECTOR.
2. GENERAL FIRE ALARM ACTIVATION OF AREA
SMOKE/HEAT DETECTOR.
3.GENERAL FIRE ALARM ACTIVATION OF MANUAL
PULL STATION.
4. GENERAL FIRE ALARM ACTIVATION OF DUCT
SMOKE DETECTOR.
5. GENERAL ALARM ACTIVATION OF CARBON
MONOXIDE DETECTOR.
6. GENERAL SUPERVISORY ALARM.
7. GENERAL TROUBLE ALARM.
3. WORK SHALL BE INSTALLED IN ACCORDANCE WITH
NATIONAL ELECTRICAL CODE, NFPA 72, UFC 3-600-01
WITH CHANGE 6, 06 MAY 2021, UFC 4-021-01 AS
AMENDED BY US ARMY CORPS OF ENGINEERS
(USACE) DESIGN GUIDE FOR VISUAL NOTIFICATION
FOR MASS NOTIFICATION SYSTEM, USACE
ENGINEERING AND CONSTRUCTION BULLETIN (ECB)
REGARDING UFC 4-021-01 ISSUED 25-OCT-18, UFC
4-010-05, AND THE AUTHORITY HAVING
JURISDICTION (AHJ). A CERTIFICATE OF FINAL
INSPECTION SHALL BE PROVIDED BY THE
CONTRACTOR AT THE COMPLETION OF THE WORK
AND PRESENTED TO ENGINEER AND CONTRACTING
OFFICER AS THE COMPLETION OF EACH BUILDING.
4. THE CONTRACT DOCUMENTS ARE BASED ON
RECORD DRAWINGS AND LIMITED FIELD
OBSERVATIONS. IT IS THE CONTRACTOR'S
RESPONSIBILITY TO VERIFY ACTUAL CONDITIONS
AND MAKE NECESSARY CHANGES TO
ACCOMMODATE THE INSTALLATION OF NEW WORK
AT NO ADDITIONAL COST TO THE GOVERNMENT.
5. THE CONTRACTOR SHALL COMPLETE THE DESIGN
AS REQUIRED TO PROVIDE A COMPLETE AND
SATISFACTORILY FUNCTIONING SYSTEM AS
INDICATED ON THE CONTRACT DOCUMENTS AND AS
EVIDENTLY INTENDED. IT IS NOTED THAT THE
DRAWINGS ARE DIAGRAMMATIC IN NATURE AND
INDICATE GENERAL ARRANGEMENTS OF SYSTEMS
AND WORK. INTERCONNECTIONS HAVE NOT BEEN
SHOWN, AND THE CONTRACTOR SHALL FURNISH
AND INSTALL CONDUIT AND WIRING AS REQUIRED
ACCOMPLISHING THE FUNCTIONS INTENDED. THE
CONTRACTOR SHALL FURNISH AND INSTALL THE
REQUIRED QUANTITIES AND TYPES OF CABLES,
CONDUCTORS, RACEWAYS, REMOTE POWER
SUPPLIES AND INTERCONNECTIONS, SHIELDING
REQUIREMENTS, ETC., AS REQUIRED BY THE
SYSTEM MANUFACTURER, THE SPECIFICATIONS,
AND APPLICABLE CODES. ALL WIRING SHOWN ON
RISER DIAGRAMS SHALL ALSO BE FURNISHED AND
INSTALLED REGARDLESS OF WHETHER THESE
ITEMS ARE SHOWN ON THE FLOOR PLANS.
6. DEDICATED 120 VAC SHALL BE PROVIDED FOR FIRE
ALARM AND MASS NOTIFICATION SYSTEM CONTROL
UNITS, INCLUDING FA/MNS CONTROL UNIT, REMOTE
POWER SUPPLIES, NOTIFICATION DEVICE POWER
SUPPLIES, ALARM TRANSCEIVERS, ETC. COMPLY
WITH THE NATIONAL ELECTRICAL CODE, NFPA 72
AND UFC 3-520-01. ENLIST THE SERVICES OF AN
ELECTRICAL SUBCONTRACTOR AS MAY BE
REQUIRED TO ACCOMPLISH INSTALLATION AND
TESTING.
7. DUCT SMOKE DETECTORS SHALL BE PROVIDED FOR
HVAC UNITS EXCEEDING 2,000 CFM OR FOR UNITS
SHARING THE SAME PLENUM HAVING A COMBINED
CAPACITY EXCEEDING 2,000 CFM. DUCT SMOKE
DETECTORS ARE NOT REQUIRED WHERE AIR
DISTRIBUTION SYSTEMS ARE INCAPABLE OF
SPREADING SMOKE BEYOND THE ENCLOSING
WALLS, FLOORS AND CEILINGS OF THE ROOM OR
SPACE IN WHICH THE SMOKE IS GENERATED.
ADDRESSABLE FIRE ALARM MODULES SHALL BE
PROVIDED TO ACCOMPLISH HVAC UNIT SHUT DOWN.
8. FIRE/SMOKE DAMPERS AND SMOKE DAMPERS SHALL
BE INTERFACED WITH FIRE ALARM / MASS
NOTIFICATION SYSTEMS TO CLOSE IN THE EVENT OF
FIRE ALARM OR ASSOCIATED DUCT SMOKE
DETECTOR ACTIVATION. DUCT SMOKE DETECTOR
SHALL BE INSTALLED WITHIN 5 FT OF ALL
FIRE/SMOKE AND SMOKE DAMPERS PENETRATING
RATED CONSTRUCTION. CONTRACTOR TO ENLIST
THE SERVICES OF MECHANICAL AND ELECTRICAL
SUBCONTRACTORS AS MAY BE REQUIRED TO
ACCOMPLISH INSTALLATION AND TESTING.
9. THE DETECTOR PLACEMENT DETAILED ON
DRAWINGS IS BASED UPON SMOOTH CEILING
CONSTRUCTION. THE ACTUAL PLACEMENT OF
DETECTORS WILL BE DEPENDENT UPON THE
LOCATION AND ARRANGEMENT OF STRUCTURAL
COMPONENTS, ROOF.CEILING HEIGHT AND
ROOF/CEILING SLOPE.
10. DOORS EQUIPPED WITH ELECTRONIC LOCKING
HARDWARE (ELECTRONIC ACCESS CONTROL AND
DELAYED EGRESS) SHALL BE INTERFACED WITH
FIRE ALARM / MASS NOTIFICATION SYSTEMS TO
RELEASE DOORS IN THE EVENT OF FIRE ALARM
ACTIVATION. CONTRACTOR TO ENLIST THE
SERVICES OF ELECTRONIC SECURITY AND DOOR
HARDWARE SUBCONTRACTORS AS MAY BE
REQUIRED TO ACCOMPLISH INSTALLATION AND
TESTING.
11. THE QUANTITY AND PLACEMENT OF VISUAL
NOTIFICATION DEVICES IS DEPENDENT UPON THE
DEVICE'S CANDELA RATING. DEVICE PLACEMENT
SHALL BE BASED UPON ALLOWABLE DEVICE
COVERAGE ASSOCIATED WITH THE DEVICES
CANDELA RATING PER NFPA 72.
12. SPEAKER QUANTITIES, PLACEMENT AND TAP
SETTINGS SHALL BE SELECTED TO ENSURE VOICE
INTELLIGIBILITY IN ACCORDANCE WITH UFC 4-021-01
AND NFPA 72. ACOUSTIC MODELING SHALL BE
PROVIDED USING COMPUTER BASE SOFTWARE
SUCH AS, BUT NOT LIMITED TO, MODELER BY BOSE
AND EASE BY ADMG. SHOP DRAWINGS SHALL
DEFINE EACH ACOUSTICALLY DEFINED SPACE (ADS),
INTENDED SOUND PRESSURE LEVEL (SPL) AND
INTENDED INTELLIGIBILITY VALUE STI OR CIS. REFER
TO APPENDIX D OF NFPA 72 FOR INTELLIGIBILITY
GUIDANCE. ACCEPTANCE TESTING SHALL INCLUDE
VOICE INTELLIGIBILITY TESTING TO CONFIRM
INTELLIGIBLE SYSTEM DESIGN..
13. WEATHER PROOF FIRE ALARM DEVICES SHALL BE
PROVIDED AS REQUIRED, BASED UPON
OCCUPANCY, ENVIRONMENTAL CONDITIONS AND AS
NOTED ON DRAWINGS.
14. UNLESS OTHERWISE NOTED, ALL EQUIPMENT SHALL
BE NEW, SHALL BE SUITABLE FOR THE APPLICATION
INTENDED, AND SHALL BEAR LABELS OR MARKINGS
INDICATING THIRD PARTY TESTING LABORATORY
LISTINGS ACCEPTABLE TO THE AUTHORITY HAVING
JURISDICTION.
15. FIELD VERIFY LOCATIONS OF DEVICES IN FINISHED
SPACES, WITH WHITEBOARDS, BULLETIN BOARDS,
ELECTRONIC DISPLAYS, FURNITURE, CABINETS,
MILLWORK, AND CASEWORK PRIOR TO ROUGH-IN.
16. FIRE ALARM AND MASS NOTIFICATION CABLES WILL
BE INSTALLED IN METALLIC RACEWAYS. METALLIC
RACEWAYS, CONDUIT, BACK BOXES, AND JUNCTION
BOXES SHALL BE FACTORY PAINTED RED. RACEWAY
AND WIRING SHALL BE CONCEALED IN FINISHED
SPACES, AND MAY BE INSTALLED EXPOSED IN
UNFINISHED SPACES SUCH AS MECHANICAL AND
ELECTRICAL ROOMS. ALL RACEWAY AND WIRING,
WHETHER CONCEALED OR EXPOSED, SHALL BE
INSTALLED EITHER PERPENDICULAR OR PARALLEL
TO THE BUILDING'S STRUCTURAL COMPONENTS.
PROVIDE PULL AND JUNCTION BOXES AS REQUIRED
TO MEET CODE AND INSTALLATION REQUIREMENTS.
17. CONDUIT, BACKBOXES, AND JUNCTION BOXES
WITHIN FINISHED SPACES SHALL BE PAINTED TO
MATCH ADJACENT CEILING AND WALL SURFACES.
CONDUIT SHALL BE IDENTIFIED BY PAINTING 3/4 IN.
RED BANDS ON 20 FT. INTERVALS AND ON BOTH
SIDES OF WALL, FLOOR AND CEILING
PENETRATIONS. JUNCTION BOX COVERS SHALL BE
IDENTIFIED ON THEIR INTERIOR AS "FIRE ALARM".
18. THE CONTRACTOR MAY EXERCISE THE OPTION TO
RE-USE EXISTING CONDUIT, JUNCTION BOXES AND
BACK BOXES, PROVIDED THAT THE CONDUIT IS
INSTALLED IN ACCORDANCE WITH NATIONAL
ELECTRICAL CODE AND NFPA 72, IS FREE FROM
CORROSION, MECHANICAL DAMAGE AND MEETS THE
FIRE ALARM SYSTEM DESIGN INTENT. CONDUIT
RE-USED SHALL BE PAINTED IN ACCORDANCE WITH
PROJECT REQUIREMENTS. ALL RE-USED CONDUIT,
JUNCTION BOXES AND BACK BOXES SHALL BE
DEEMED PART OF THE SYSTEM INSTALLATION AND
BE WARRANTED IN ACCORDANCE WITH THE
CONTRACTS WARRANTY PROVISIONS (WARRANTED
AS NEW MATERIALS).
19. CONDUCTORS SHALL BE IDENTIFIED AT EACH
JUNCTION BOX, OUTLET BOX, CABINET, PULL BOX,
ETC., INDICATING PANEL AND CIRCUIT NUMBER,
CONTROL WIRE IDENTIFICATION NUMBER, OTHER
APPROPRIATE INFORMATION. ALL PULL AND
JUNCTION BOXES SHALL BE LABELED AS TO
FUNCTION. ALL CONDUCTORS SHALL BE IDENTIFIED
WITH PERMANENT MACHINE-PRINTED, HEAT-SHRINK
IDENTIFICATION LABELS MANUFACTURED FOR THE
PURPOSE OF CABLE IDENTIFICATION.
HAND-WRITTEN, ENGRAVED OR "P-TOUCH STYLE
LABELS ARE NOT ACCEPTABLE. IDENTIFICATION
HANDWRITTEN ON CABLE JACKET IS NOT
ACCEPTABLE.
20. EQUIPMENT SHALL BE SECURELY FASTENED BY
MEANS OF ANCHORS, RODS, HANGERS, SUPPORTS,
GUIDES, SWAY BRACES, ETC., MAINTAIN ALIGNMENT
AND PREVENT EQUIPMENT MOVEMENT.
21. THROUGH-AND MEMBRANE-PENETRATIONS OF FIRE
AND SMOKE RATED CONSTRUCTION SHALL BE
SEALED WITH FIRE STOPPING MATERIALS
APPROVED AND LISTED FOR THE RATING OF THE
CONSTRUCTION TO BE PENETRATED. PROVIDE
DOCUMENTATION ON ALL SUCH PENETRATION
SEALING SYSTEMS FOR VERIFICATION OF PROPER
INSTALLATION. CONTRACTOR SHOP DRAWINGS
SHALL SHOW THE LOCATION OF FIRE AND SMOKE
RATED CONSTRUCTION. SHOP DRAWINGS SHALL
INCLUDE FIRESTOPPING DETAILS FOR EACH TYPE
OF FIRESTOPPING MATERIAL USED IN THE PROJECT.
ONLY QUALIFIED CONTRACTOR AND INSTALLERS
SHALL INSTALL FIRESTOPPING. REFER TO 07 84 00
SPECIFICATIONS.
22. PENETRATIONS OF ROOFS, EXTERIOR WALLS,
FOUNDATIONS, OR OTHER WATER OR MOISTURE
PROOF CONSTRUCTION SHALL BE SEALED WITH
APPROPRIATE SEALING FITTINGS OR SEALED
CONSTRUCTION TO PREVENT THE INTRODUCTION
OF MOISTURE INTO THE BUILDING.
23. WHERE EMPTY RACEWAYS ARE INSTALLED FOR
FUTURE USE, THEY SHALL BE LABELED AT BOTH
ENDS AND FITTED WITH NYLON PULL STRINGS FOR
FUTURE USE.
24. WORK SHALL BE PERFORMED ON DE-ENERGIZED
SYSTEMS ONLY TO PREVENT PERSONNEL INJURY
AND POTENTIAL SYSTEM FAILURE. WHERE WORK ON
SYSTEMS WILL REQUIRE INTERRUPTION OF
ELECTRICAL SERVICE, TEMPORARY PROVISIONS
FOR TEMPORARY POWER SHALL BE PROVIDED
UNTIL THE WORK IS COMPLETE. ALL INTERRUPTIONS
TO BUILDING UTILITIES SHALL BE APPROVED IN
WRITING BY THE CONTRACTING OFFICERS
REPRESENTATIVE.
25. SHOP DRAWINGS AND CALCULATIONS MUST BE
PREPARED BY AN INDIVIDUAL WHO HAS OBTAINED
NATIONAL INSTITUTE FOR CERTIFICATION IN
ENGINEERING TECHNOLOGIES, FIRE ALARM
SYSTEMS, LEVEL III CERTIFICATION, AT A MINIMUM.
THE CONTRACTOR SHALL SECURE THE SERVICES
OF A QFPE AND THE QFPE MUST REVIEW THE SHOP
DRAWINGS, CALCULATIONS (INCLUDING, BATTERY
CALCULATIONS AND VOLTAGE DROP
CALCULATIONS), AUDIBILITY AND INTELLIGIBILITY
MODELING, AND MATERIAL SUBMITTALS. THE SHOP
DRAWINGS SHALL BEAR THE REVIEW STAMP OF THE
QFPE PRIOR TO SUBMITTING THE FIRE ALARM
SYSTEM SHOP DRAWINGS TO THE GOVERNMENT
(UFC 3-600-01 SECTION 9-18.2). SUBMIT SHOP
DRAWINGS AND CALCULATIONS TO THE
GOVERNMENT FOR REVIEW IN A MANNER AS
REQUIRED PER NFPA 72 AND UFC 3-600-01.
APPROVED SHOP DRAWINGS, DATA SHEETS, AND
CALCULATIONS SHALL BE REQUIRED PRIOR TO
COMMENCEMENT OF WORK.
26. PROVIDE SURGE PROTECTIVE DEVICES (SPDS) TO
PROTECT ALL POWER SUPPLY CIRCUITS TO THE
FA/MNS CONTROL UNIT, RADIO TRANSMITTER,
INCLUDING SUBPANELS (E.G. NOTIFICATION
APPLIANCE CIRCUIT (NAC) BOOSTER PANELS). SPDS
SHALL BE INSTALLED IN ACCORDANCE WITH UFC
3-520-01. ALL SPDS SHALL BE UL 1283 AND UL 1449
LISTED IN ACCORDANCE WITH UFC 3-600-01.
27. PROVIDE SURGE PROTECTIVE DEVICES (SPDS) FOR
ALL FIRE ALARM DATA, SLC AND NOTIFICATION
CIRCUITS THAT LEAVE THE BUILDING'S PROTECTIVE
ENVELOPE. PROVIDE SURGE PROTECTIVE DEVICES
FOR ALL FIRE ALARM NOTIFICATION DEVICES
INSTALLED ON THE BUILDING'S EXTERIOR WALL,
UNLESS THE BUILDING IS PROTECTED WITH AN
APPROVED LIGHTNING PROTECTION SYSTEM. ALL
SPDS SHALL BE UL 1283 AND UL 1449 LISTED IN
ACCORDANCE WITH UFC 3-600-01.
28. PROVIDE A LOCK-ON BREAKER IN THE BRANCH
PANELBOARD THAT SERVES AS PRIMARY POWER
FOR THE FIRE PROTECTION SYSTEMS. WHERE MORE
THAN ONE DEDICATED 120 VAC POWER CIRCUIT IS
REQUIRED FOR FIRE PROTECTION SYSTEMS, A
DEDICATED PANEL BOARD SIZED FOR A MINIMUM OF
SIX (6) CIRCUITS DEDICATED TO FIRE PROTECTION
AND LIFE SAFETY SYSTEMS POWERED FROM A
LOCK-ON BREAKER IN THE UPSTREAM DISTRIBUTION
EQUIPMENT SHALL BE PROVIDED.
29. LOCK-ON BREAKERS SHALL BE FACTORY OR FIELD
PAINTED RED. ADDITIONALLY, PROVIDE A
MECHANICALLY FASTENED RED LAMINATED PLASTIC
LABEL WITH WHITE CENTER CORE WITH THE
FOLLOWING INSCRIPTION: "FIRE PROTECTION/LIFE
SAFETY EQUIPMENT" FOR EACH LOCK-ON BREAKER.
30. FOR FACILITIES THAT ARE PROVIDED WITH STANDBY
EMERGENCY POWER SYSTEMS, FIRE PROTECTION
SYSTEMS SHALL BE POWERED BY THE EMERGENCY
POWER SYSTEM.
31. MULTIPLE PIECES OF FIRE ALARM AND MASS
NOTIFICATION CONTROL EQUIPMENT, POWER
SUPPLIES, ETC. MAY SHARE A DEDICATED POWER
CIRCUIT, PROVIDED THAT THE COMBINED CURRENT
LOAD DOES NOT EXCEED 80% OF THE CIRCUITS
RATING. CONTRACTOR SHALL PROVIDE
CALCULATIONS DEMONSTRATING THE CIRCUIT
LOADING DOES NOT EXCEED 80%.
32. ORIGINAL FIRE ALARM CONTROL UNIT ENCLOSURES
SHALL BE REMOVED AND SHALL NOT SERVE AS FIRE
ALARM TERMINAL CABINETS OR JUNCTION BOXES
FOR THE NEW WORK UNDER ANY CIRCUMSTANCES.
WHERE THE RE-USE OF EXISTING CONDUIT
PREVIOUSLY ENTERING THE ORIGINAL FIRE ALARM
CONTROL UNIT OR FIRE ALARM ENCLOSURE IS
REQUIRED, SUCH AS WHERE CONDUIT ENTERS
FROM BELOW GRADE, CONCEALED SPACE, ETC.
NEW TERMINAL CABINETS, CABLE TROUGHS, OR
NEMA ENCLOSURES RATED FOR THE ENVIRONMENT
PRESENT SHALL BE PROVIDED.
33. ALL CABLES TERMINATED WITHIN CONTROL
EQUIPMENT, REMOTE PANELS, POWER SUPPLIES,
TERMINAL CABINETS, ADDRESSABLE INTERFACE
MODULE ENCLOSURES, ETC. SHALL BE NEATLY
TERMINATED USING SCREWED TERMINALS STRIPS
OR SCREWED JUNCTION BLOCKS. NO WIRE NUTS,
CRIMP-ON, LATCHING, PUSH-ON OR SOLDERED
CONNECTORS SHALL BE ALLOWED.
34. HIGH VOLTAGE (120VAC), NON-POWER LIMITED AND
POWER LIMITED CABLE INSTALLED WITHIN
EQUIPMENT ENCLOSURES SHALL BE SEPARATED IN
ACCORDANCE WITHNATIONAL ELECTRICAL CODE
AND MANUFACTURER'S INSTALLATION
INSTRUCTIONS.
35. INDIVIDUAL EXISTING SUSPENDED ACOUSTICAL
CEILING TILES WILL BE REMOVED AS REQUIRED TO
COMPLETE THE DEMOLITION AND INSTALLATION OF
THE FIRE ALARM / MASS NOTIFICATION SYSTEM.
NEW REPLACEMENT TILES WILL MATCH EXISTING
TILES. WHERE THE EXISTING CEILING TILES HAVE
BEEN DISCONTINUED, THE CONTRACTOR WILL
IDENTIFY A DONOR ROOM FROM WHICH TILES WILL
BE REMOVED AND USED IN OTHER BUILDING AREAS
TO MATCH EXISTING TILES. ALL TILES WITHIN THE
DONOR ROOM WILL BE REPLACED WITH NEW TILES,
CURRENTLY IN PRODUCTION HAVING SIMILAR
SALIENT FEATURES AND CLOSELY MATCHING THE
ORIGINAL TILES. CARE SHOULD BE TAKEN NOT TO
ADVERSELY DISTURB THERMAL OR ACOUSTIC
INSULATION SUPPORTED BY CEILING TILES.
36. ANY ACCESS OPENINGS CUT INTO CEILINGS AND
WALLS TO ACCOMMODATE THE FA/MNS
INSTALLATION WILL BE REPAIRED IN A MANNER
THAT MAINTAINS THE FIRE-RESISTANCE AND SMOKE
RATINGS.
IV
ER
Y O
R D
ER
N
O
D
ES
IG
N
ED
B
Y:
D
ES
C R
IP
TI
O N
M
AR
K
SI
ZE
SU
BM
IT
TE
D B
Y:
D
AT
E
C O
N
TR
AC
T
N U
M
BE
R
C H
EC
KE
D B
Y:
D R
AW
N
B Y:
IS
SU
E D
AT
E:
G
2 3 4 5 6 7 8 9 10
F
E
D
C
B
A SHEET ID
H D
R E ng in ee rin g, In c.
E.
P
AR
KC
EN
TE
R B
LV
D
BO
IS
E, ID
(2
) 3
-7
U .S
. A
IR
F O
R C
E
C
ES
/C
EN
M O
U N
TA
IN
H O
M E
AI
R
F O
R C
E
BA
SE
M
O U
N
TA
IN
H
O M
E, ID
AH
O
FA
-2
0- D
-0
D
EC
EM
BE
R
PR
O
JE
C
T N
U M
BE
R
SH
EE
T N
U M
BE
R
AN
SI
D
FA
-2
5- F-
M O
U N
TA
IN
H O
M E
AI
R
F O
R C
E
BA
SE
B2
FI
R
E
AL
AR
M
R
EP
AI
R
100% DESIGN SUBMITTAL
O
F
Z.
S
AC
H
SE
N
M
AI
ER
W . C
U N
AR
D
R . R
IC
H
TE
R
P.
D
ER
R
SY
M
BO
LS
L
EG
EN
D
A N
D C
O D
E
AN
AL
YS
IS
FA002
B2318
FIRE ALARM AND MASS NOTIFICATION SYMBOLS LEGEND
FIRE ALARM AND MASS NOTIFICATION CONTROL UNIT
FIRE ALARM ANNUNCIATOR AND LOCAL OPERATORS CONSOLEFAA/LOC
ADDRESSABLE INPUT MODULE
ADDRESSABLE OUTPUT MODULE
AIM
AOM
GAS DETECTOR, SUBSCRIPT DEFINES TYPE
END OF LINE SUPERVISION DEVICE
WF FLOW SWITCH
RL NON-ADDRESSABLE OUTPUT RELAY
PS PRESSURE SWITCH
SS SURGE SUPPRESSOR
VS VALVE SUPERVISORY SWITCH
MANUAL STATION, FIRE ALARM
HEAT DETECTOR, SPECIFY TYPE
DUCT MOUNTED SMOKE DETECTOR
NAC EXTENDER BOOSTER POWER SUPPLYNAC
DH DOOR HOLDER
FIRE ALARM BELL, VIBRATING TYPE
REMOTE ALARM INDICATING AND TEST SWITCH
STROBE ONLY, WALL MOUNT
FMCU
- CONTROL EQUIPMENT -
- MANUAL STATIONS -
- DETECTION -
- ADDRESSABLE MODULES -
- NOTIFICATION APPLIANCES -
ADDRESSABLE DUAL INPUT MODULE
SPEAKER/STROBE COMBO, WALL MOUNT, CLEAR LENS
STROBE ONLY, CEILING MOUNT
SPEAKER ONLY, CEILING MOUNT
AHU AIR HANDLING UNIT
AUX AUXILIARY POWER
C CEILING MOUNT
CO CARBON MONOXIDE
DOD DEPARTMENT OF DEFENSE
FA FIRE ALARM
FA/MNS FIRE ALARM AND MASS NOTIFICATION SYSTEM
HPS HIGH POWER SPEAKER
MNS MASS NOTIFICATION SYSTEM
R RETURN AIR DUCT
RTS REMOTE TEST STATION
RTU ROOF TOP UNIT
S SUPPLY AIR DUCT
SB DORM ROOM SMOKE DETECTOR WITH SOUNDER BASE
SLA SEALED LINE CIRCUIT (BATTERY)
SLC SIGNALING LINE CIRCUIT
SF SUBFLOOR
TYP TYPICAL
VFD VARIABLE FREQUENCY DRIVE
nW WATTAGE SETTING (n=SPEAKER TAP)
WP WEATHERPROOF
XP EXPLOSION PROOF
NOTE: NOT ALL SUBSCRIPTS AND ABBREVIATIONS MAY BE USED.
F
SPEAKER ONLY, WALL MOUNT
SPEAKER/STROBE COMBO, CEILING MOUNT, CLEAR LENS
- PERIPHERAL DEVICES -
SPEAKER ONLY, EXTERIOR WEATHERPROOF, TAPPED AT 2 WATTS
K KNOX BOX
EXTERIOR MOUNTED ANTENNA FOR RF TRANSMISSION
-MANUAL STATIONS-
-DETECTION-
-FIRE ALARM NOTIFICATION APPLIANCES-
DETECTOR TO BE REMOVED
NOTIFICATION APPLIANCE TO BE REMOVED
FIRE ALARM CONTROL UNIT
FIRE ALARM ANNUNCIATOR PANEL
MANUAL STATION, FIRE ALARM
DUCT MOUNTED SMOKE DETECTOR, SPECIFY TYPE
REMOTE ALARM INDICATING AND TEST SWITCH
FLOW SWITCH
VALVE SUPERVISORY SWITCH
PRESSURE SWITCH
ADDRESSABLE INPUT MODULE
-FIRE ALARM DEMOLITION SYMBOLS LEGEND-
DOOR HOLDER
120/208 VAC ELECTRICAL DISTRIBUTION PANEL-
SOURCE OF DEDICATED 120 VAC
120/280 VAC ELECTRICAL DISTRIBUTION PANEL-
SOURCE OF DEDICATED 120 VAC
EOL
2AIM
DHWP
S
V F
CS
WS
C
ADDRESSABLE OUTPUT MODULE
- DEVICE SUBSCRIPTS & ABBREVIATIONS -
RF ALARM TRANSCEIVER
- ADDRESSABLE MODULES -
- CONTROL EQUIPMENT -
- PERIPHERAL DEVICES -
RF TRANSCEIVER ANTENNA, MOUNTING HARDWARE
AND ASSOCIATED CONDUIT
uu uu u u u
S S S SMOKE-RATED PARTITION
1-HOUR FIRE-RATED BARRIER
2-HOUR FIRE-RATED BARRIER
- WALL RATINGS -
SMOKE DETECTOR, SPECIFY TYPE
SMOKE DETECTOR, BEAM TYPE - RECEIVER
SMOKE DETECTOR, BEAM TYPE - TRANSMITTER
AOM
PS
VS
WF
RTS
AIM
F
DET
AES AES INTELLINET 2.0 MESH NETWORK ALARM TRANSMITTER
ROOM
ROOM
MAINT
OFFICE
ROOM
STORAGE
MECH
LAUNDRY
ROOM
ROOM
ROOM
ROOM
STAIRS
STAIRS
ROOM
ROOM
ROOM
ROOM
COMM
136 VESTIBULE
CENTER
LOBBY
VESTIBULE
BREAK
ROOM
1XX
JC
LINEN
CORRIDOR
CORRIDOR
u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u
AIR COOLED
CONDENSOR
MECH. YARD
DET
DET
DET
DET
DET
DET
DET
DET DET
DET DET
DET
F
F
F
F
DET DET DET DET
DET DET DET DET
DET DET DET DET DET DET
FD
1A M
AT
C
H
LI
N E
FD
1B
FD
1A
M
AT
C H
LI
N
E
FD
1B
ELECTRICAL PANELS
1C AND 1D
AC B
B B B B
A
B
B BA A
B B B B
A
B
B A A
B
B A
C C
B A B
B
A
B
B
B
A B
B
B B
A A AB
B
(NON-ENVIRONMENTALLY
CONTROLLED SPACE)
A B
0 8'4' 16'SCALE: 1/8" = 1'-0"
LEVEL ONE DEMOLITION PLAN - AREA A - FIRE ALARMA1
PLAN
NORTH
D
EL
IV
ER
Y O
R D
ER
N
O
D
ES
IG
N
ED
B
Y:
D
ES
C R
IP
TI
O N
M
AR
K
SI
ZE
SU
BM
IT
TE
D B
Y:
D
AT
E
C O
N
TR
AC
T
N U
M
BE
R
C H
EC
KE
D B
Y:
D R
AW
N
B Y:
IS
SU
E D
AT
E:
G
2 3 4 5 6 7 8 9 10
F
E
D
C
B
A SHEET ID
H D
R E ng in ee rin g, In c.
E.
P
AR
KC
EN
TE
R B
LV
D
BO
IS
E, ID
(2
) 3
-7
U .S
. A
IR
F O
R C
E
C
ES
/C
EN
M O
U N
TA
IN
H O
M E
AI
R
F O
R C
E
BA
SE
M
O U
N
TA
IN
H
O M
E, ID
AH
O
FA
-2
0- D
-0
D
EC
EM
BE
R
PR
O
JE
C
T N
U M
BE
R
SH
EE
T N
U M
BE
R
AN
SI
D
FA
-2
5- F-
M O
U N
TA
IN
H O
M E
AI
R
F O
R C
E
BA
SE
B2
FI
R
E
AL
AR
M
R
EP
AI
R
100% DESIGN SUBMITTAL
O
F
Z.
S
AC
H
SE
N
M
AI
ER
W . C
U N
AR
D
R . R
IC
H
TE
R
P.
D
ER
R
LE
VE
L O
N E
D
EM
O
LI
TI
O
N P
LA
N
AR
EA
A
FI
R E
AL
AR
M
FD101A
B2318
SHEET NOTES
1. REMOVE EXISTING FIRE ALARM SYSTEM IN ITS
ENTIRETY. PATCH AND PAINT WALL AND CEILING
OPENINGS NOT SLATED FOR RE-USE TO MATCH
SURROUNDING SURFACES.
2. DEMO EXISTING CEILING AND WALL MOUNTED
DEVICES, BACK BOXES, CONDUIT AND WIRE IN THEIR
ENTIRETY. ALTERNATELY, THE EXISTING BACK
BOXES MAY BE RE-USED FOR NEW DEVICES,
PROVIDED THAT THE BACK BOX DIMENSIONS ARE
COMPATIBLE WITH NEW DEVICES AND THE BACK BOX
IS IN THE CORRECT LOCATION. EXISTING CONDUIT
SERVING THE EXISTING BACK BOX MAY BE RE-USED
IF THE CONDUIT IS NO LESS THAN 3/4 IN., INSTALLED
IN ACCORDANCE WITH NEC AND IS WARRANTED AS
NEW.
3. THIS BUILDING WILL BE VACATED DURING
CONSTRUCTION.
4. UNLESS OTHERWISE NOTED, CEILING HEIGHTS ARE
LESS THAN 10FT.
5. UNLESS OTHERWISE NOTED, CEILINGS FEATURE
ACOUSTICAL CEILING TILES SUPPORTED BY METAL
GRIDDED FRAMES. REFER ALSO TO CEILING LEGEND.
6. THROUGH AND MEMBRANE PENETRATIONS OF FIRE
AND SMOKE RATED CONSTRUCTION SHALL BE
PERFORMED IN A MANNER THAT MAINTAINS THE
EXISTING RATINGS. LISTED FIRESTOPPING SYSTEMS
AND MATERIALS SHALL BE PROVIDED AS REQUIRED.
REFERENCE DIVISION 07 84 00.
SHEET KEY NOTES
1. DEMO EXISTING SILENT KNIGHT 5820XL FACU, NAC POWER
SUPPLY, MONACO ENTERPRISES TRANSCEIVER, CONDUIT
AND WIRE IN ITS ENTIRETY. THE NEW FMCU WILL NOT BE
REINSTALLED AT THIS LOCATION.
2. DEMO EXISTING REMOTE ANNUNCIATOR. PATCH AND PAINT
CMU WALL AS REQUIRED TO ACCOMODATE NEW COMBINED
REMOTE ANNUNCIATOR AND LOCAL OPERATORS CONSOLE.
3. DEMO EXISTING DEDICATED 120 VAC TO THE FACU. THE
NEW FMCU WILL NOT BE REINSTALLED AT THIS LOCATION.
4. DEMO EXISTING MONACO TRANSCEIVER ANTENNA,
CONDUIT, SURGE SUPPRESSOR, COAXIAL CABLE AND
MOUNTING HARDWARE.
5. DEMO EXISTING WINDOW AND FRAME COMPLETE,
MEASURING APPROXIMATLEY 48 IN, X 60IN. REMOVE
EXISTING DRYWALL TO NEAREST VERTICAL STUD AND INFILL
OPENING WITH NEW METAL FRAMING AT PERIMETER AND
CENTER OF OPENING MATCHING EXISTING DEPTH. FINISH
OPENING WITH GYPSUM WALL BOARD TO MATCH EXISTING
THICKNESS, TAPE, TEXTURE AND PAINT ENTIRE WALL FROM
CORNER TO CORNER AND FLOOR TO CEILING. INSTALL
METAL BLOCKING AS REQUIRED TO SUPPORT NEW FMCU
AND ASSOCIATED EQUIPMENT ENCLOSURES.
6. DEMO ABANDONED MATV RACK MOUNTED EQUIPMENT (PICO
MACOM MODULATORS, DIRECT TV RECEIVERS AND ABP
DIGITAL AMPLIERS), AND FLOOR RACK. DEMO WALL
MOUNTED SPLITTERS AND DIRECTIONAL COUPLERS.
COORDINATE DEMOLITION WITH COMMS SQUADRON.
7. DOORS SEPARATING CORRIDORS AND DAY ROOMS FROM
CENTER LOBBY WERE ONCE EQUIPPED WITH DOOR
HOLDERS. THE DOOR HOLDERS HAVE BEEN REMOVED AND
DOORS ARE CURRENTLY EQUIPPED WITH DOOR CLOSERS
TO KEEP DOORS CLOSED. SINGLE GANG BACK BOXES WITH
BLANK COVERS REMAIN. CONTRACTOR SHALL DEMO WIRE
AND BACK BOXES ASSOCIATED WITH THE ONCE INSTALLED
DOOR HOLDERS. CONTRACTOR SHALL PATCH AND PAINT
WALL OPENINGS TO MATCH SURROUNDING SURFACES.
CORRIDORS HAVE 1/2-HOUR RATED FIRE-WALLS
uu uu u u u
S S S SMOKE-RATED PARTITION
1-HOUR FIRE-RATED BARRIER
2-HOUR FIRE-RATED BARRIER
WALL RATINGS
SCALE: NTS
KEYPLANA9
PLAN
NORTH
ACT LIFT-OUT CEILING TILES
GYPSUM BOARD
OPEN TO DECK ABOVE
CEILING LEGEND
A
B
C
VESTIBULE
CORRIDOR
DAYROOM
ROOM
ROOM
ROOM
ROOM
ROOM
ROOM
ROOM
ROOM
ROOM
STORAGE
B
ROOM
ROOM
CORRIDOR
STAIRS
u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u
DET DET
DET
DET DET
DET DET
DETDETDETDET
DETDETDETDET
DET DET
DET DET
DET
F
FD
1A M
AT
C
H
LI
N E
FD
1B
FD
1A
M
AT
C H
LI
N
E
FD
1B
ELECTRICAL PANELS
1A AND 1B
DET
A
B
B
B
A
B
B
B
A
B
B
B
A A A
B
B
B
AAAA
AAA
A
A B B B
B B B B
B
B
B
BBB
BB
BB
A B
0 8'4' 16'SCALE: 1/8" = 1'-0"
LEVEL ONE DEMOLITION PLAN - AREA B - FIRE ALARMA1
PLAN
NORTH
D
EL
IV
ER
Y O
R D
ER
N
O
D
ES
IG
N
ED
B
Y:
D
ES
C R
IP
TI
O N
M
AR
K
SI
ZE
SU
BM
IT
TE
D B
Y:
D
AT
E
C O
N
TR
AC
T
N U
M
BE
R
C H
EC
KE
D B
Y:
D R
AW
N
B Y:
IS
SU
E D
AT
E:
G
2 3 4 5 6 7 8 9 10
F
E
D
C
B
A SHEET ID
H D
R E ng in ee rin g, In c.
E.
P
AR
KC
EN
TE
R B
LV
D
BO
IS
E, ID
(2
) 3
-7
U .S
. A
IR
F O
R C
E
C
ES
/C
EN
M O
U N
TA
IN
H O
M E
AI
R
F O
R C
E
BA
SE
M
O U
N
TA
IN
H
O M
E, ID
AH
O
FA
-2
0- D
-0
D
EC
EM
BE
R
PR
O
JE
C
T N
U M
BE
R
SH
EE
T N
U M
BE
R
AN
SI
D
FA
-2
5- F-
M O
U N
TA
IN
H O
M E
AI
R
F O
R C
E
BA
SE
B2
FI
R
E
AL
AR
M
R
EP
AI
R
100% DESIGN SUBMITTAL
O
F
Z.
S
AC
H
SE
N
M
AI
ER
W . C
U N
AR
D
R . R
IC
H
TE
R
P.
D
ER
R
LE
VE
L O
N E
D
EM
O
LI
TI
O
N P
LA
N
AR
EA
B
FI
R E
AL
AR
M
FD101B
B2318
SHEET NOTES
1. REMOVE EXISTING FIRE ALARM SYSTEM IN ITS
ENTIRETY. PATCH AND PAINT WALL AND CEILING
OPENINGS NOT SLATED FOR RE-USE TO MATCH
SURROUNDING SURFACES.
2. DEMO EXISTING CEILING AND WALL MOUNTED
DEVICES, BACK BOXES, CONDUIT AND WIRE IN THEIR
ENTIRETY. ALTERNATELY, THE EXISTING BACK
BOXES MAY BE RE-USED FOR NEW DEVICES,
PROVIDED THAT THE BACK BOX DIMENSIONS ARE
COMPATIBLE WITH NEW DEVICES AND THE BACK BOX
IS IN THE CORRECT LOCATION. EXISTING CONDUIT
SERVING THE EXISTING BACK BOX MAY BE RE-USED
IF THE CONDUIT IS NO LESS THAN 3/4 IN., INSTALLED
IN ACCORDANCE WITH NEC AND IS WARRANTED AS
NEW.
3. THIS BUILDING WILL BE VACATED DURING
CONSTRUCTION.
4. UNLESS OTHERWISE NOTED, CEILINGS HEIGHTS ARE
LESS THAN 10FT.
5. UNLESS OTHERWISE NOTED, CEILINGS FEATURE
ACOUSTICAL CEILING TILES SUPPORTED BY METAL
GRIDDED FRAMES. REFER ALSO TO CEILING LEGEND.
6. THROUGH AND MEMBRANE PENETRATIONS OF FIRE
AND SMOKE RATED CONSTRUCTION SHALL BE
PERFORMED IN A MANNER THAT MAINTAINS THE
EXISTING RATINGS. LISTED FIRESTOPPING SYSTEMS
AND MATERIALS SHALL BE PROVIDED AS REQUIRED.
REFERENCE DIVISION 07 84 00.
CORRIDORS HAVE 1/2-HOUR RATED FIRE-WALLS
uu uu u u u
S S S SMOKE-RATED PARTITION
1-HOUR FIRE-RATED BARRIER
2-HOUR FIRE-RATED BARRIER
WALL RATINGS
SCALE: NTS
KEYPLANA9
PLAN
NORTH
ACT LIFT-OUT CEILING TILES
GYPSUM BOARD
OPEN TO DECK ABOVE
CEILING LEGEND
A
B
C
ROOM
HOSPITALITY
ROOM
ROOM
ROOM
ROOM
ROOM
ROOM
ROOM
ROOM
STAIRS
STAIRS
ROOM
ROOM
ROOM
ROOM
STORAGE
CENTER
LOBBY
CORRIDOR
CORRIDOR
u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u uuu u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u
LODGING
COMM.
EQUIP.
DET DET
DET DET DET
DET
DET
DET DET DET DET DET
DET DET DET DET
DET DET DET DET
DET DET DET DET
F
F
FD
2A M
AT
C
H
LI
N E
FD
2B
FD
2A
M
AT
C H
LI
N
E
FD
2B
ELECTRICAL PANELS
2C AND 2D
AB
B B B
A
B
B BA A
B B B B
A
B
B A A
B
B A
A B
B
A
B
B
B
A B
B
B B
A A AB
B
B
B
A
BB
A
DET
A B
B
A
A B
0 8'4' 16'SCALE: 1/8" = 1'-0"
LEVEL TWO DEMOLITION PLAN - AREA A - FIRE ALARMA1
PLAN
NORTH
D
EL
IV
ER
Y O
R D
ER
N
O
D
ES
IG
N
ED
B
Y:
D
ES
C R
IP
TI
O N
M
AR
K
SI
ZE
SU
BM
IT
TE
D B
Y:
D
AT
E
C O
N
TR
AC
T
N U
M
BE
R
C H
EC
KE
D B
Y:
D R
AW
N
B Y:
IS
SU
E D
AT
E:
G
2 3 4 5 6 7 8 9 10
F
E
D
C
B
A SHEET ID
H D
R E ng in ee rin g, In c.
E.
P
AR
KC
EN
TE
R B
LV
D
BO
IS
E, ID
(2
) 3
-7
U .S
. A
IR
F O
R C
E
C
ES
/C
EN
M O
U N
TA
IN
H O
M E
AI
R
F O
R C
E
BA
SE
M
O U
N
TA
IN
H
O M
E, ID
AH
O
FA
-2
0- D
-0
D
EC
EM
BE
R
PR
O
JE
C
T N
U M
BE
R
SH
EE
T N
U M
BE
R
AN
SI
D
FA
-2
5- F-
M O
U N
TA
IN
H O
M E
AI
R
F O
R C
E
BA
SE
B2
FI
R
E
AL
AR
M
R
EP
AI
R
100% DESIGN SUBMITTAL
O
F
Z.
S
AC
H
SE
N
M
AI
ER
W . C
U N
AR
D
R . R
IC
H
TE
R
P.
D
ER
R
LE
VE
L
TW
O D
EM
O
LI
TI
O N
P
LA
N
AR
EA
A
FI
R
E
AL
AR
M
FD102A
B2318
SHEET NOTES
1. REMOVE EXISTING FIRE ALARM SYSTEM IN ITS
ENTIRETY. PATCH AND PAINT WALL AND CEILING
OPENINGS NOT SLATED FOR RE-USE TO MATCH
SURROUNDING SURFACES.
2. DEMO EXISTING CEILING AND WALL MOUNTED
DEVICES, BACK BOXES, CONDUIT AND WIRE IN THEIR
ENTIRETY. ALTERNATELY, THE EXISTING BACK
BOXES MAY BE RE-USED FOR NEW DEVICES,
PROVIDED THAT THE BACK BOX DIMENSIONS ARE
COMPATIBLE WITH NEW DEVICES AND THE BACK BOX
IS IN THE CORRECT LOCATION. EXISTING CONDUIT
SERVING THE EXISTING BACK BOX MAY BE RE-USED
IF THE CONDUIT IS NO LESS THAN 3/4 IN., INSTALLED
IN ACCORDANCE WITH NEC AND IS WARRANTED AS
NEW.
3. THIS BUILDING WILL BE VACATED DURING
CONSTRUCTION.
4. UNLESS OTHERWISE NOTED, CEILINGS HEIGHTS ARE
LESS THAN 10FT.
5. UNLESS OTHERWISE NOTED, CEILINGS FEATURE
ACOUSTICAL CEILING TILES SUPPORTED BY METAL
GRIDDED FRAMES. REFER ALSO TO CEILING LEGEND.
6. THROUGH AND MEMBRANE PENETRATIONS OF FIRE
AND SMOKE RATED CONSTRUCTION SHALL BE
PERFORMED IN A MANNER THAT MAINTAINS THE
EXISTING RATINGS. LISTED FIRESTOPPING SYSTEMS
AND MATERIALS SHALL BE PROVIDED AS REQUIRED.
REFERENCE DIVISION 07 84 00.
SHEET KEY NOTES
1. DEMO EXISTING NAC POWER SUPPLY CONDUIT AND WIRE IN
ITS ENTIRETY.
2. DOORS SEPARATING CORRIDORS AND DAY ROOMS FROM
CENTER LOBBY WERE ONCE EQUIPPED WITH DOOR
HOLDERS. THE DOOR HOLDERS HAVE BEEN REMOVED AND
DOORS ARE CURRENTLY EQUIPPED WITH DOOR CLOSERS
TO KEEP DOORS CLOSED. SINGLE GANG BACK BOXES WITH
BLANK COVERS REMAIN. CONTRACTOR SHALL DEMO WIRE
AND BACK BOXES ASSOCIATED WITH THE ONCE INSTALLED
DOOR HOLDERS. CONTRACTOR SHALL PATCH AND PAINT
WALL OPENINGS TO MATCH SURROUNDING SURFACES.
CORRIDORS HAVE 1/2-HOUR RATED FIRE-WALLS
uu uu u u u
S S S SMOKE-RATED PARTITION
1-HOUR FIRE-RATED BARRIER
2-HOUR FIRE-RATED BARRIER
WALL RATINGS
SCALE: NTS
KEYPLANA9
PLAN
NORTH
ACT LIFT-OUT CEILING TILES
GYPSUM BOARD
OPEN TO DECK ABOVE
CEILING LEGEND
A
B
C
STAIRS
STORAGE
CORRIDOR
STORAGE
236 ROOM
ROOM
ROOM
ROOM
ROOM
ROOM
ROOM
ROOM
ROOM
DAYROOM
ROOM
ROOM
CORRIDOR
u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u uuuu u u
LODGING
COMM.
EQUIP.
2XX
DET
DET
DET DET
DET DET
DETDETDETDET
DETDETDETDET
DET DET
DET DET
DET
F
DETDET
DET
FD
2A M
AT
C
H
LI
N E
FD
2B
FD
2A
M
AT
C H
LI
N
E
FD
2B
ELECTRICAL PANELS
2A AND 2B
DET
A
B
B
B
A
B
B
B
A
B
B
B
A A A
B
B
B
AAAA
AAA
A B B B
B B B B
B
B
B
BBB
B C
A
A
A
A B
0 8'4' 16'SCALE: 1/8" = 1'-0"
LEVEL TWO DEMOLITION PLAN - AREA B - FIRE ALARMA1
PLAN
NORTH
D
EL
IV
ER
Y O
R D
ER
N
O
D
ES
IG
N
ED
B
Y:
D
ES
C R
IP
TI
O N
M
AR
K
SI
ZE
SU
BM
IT
TE
D B
Y:
D
AT
E
C O
N
TR
AC
T
N U
M
BE
R
C H
EC
KE
D B
Y:
D R
AW
N
B Y:
IS
SU
E D
AT
E:
G
2 3 4 5 6 7 8 9 10
F
E
D
C
B
A SHEET ID
H D
R E ng in ee rin g, In c.
E.
P
AR
KC
EN
TE
R B
LV
D
BO
IS
E, ID
(2
) 3
-7
U .S
. A
IR
F O
R C
E
C
ES
/C
EN
M O
U N
TA
IN
H O
M E
AI
R
F O
R C
E
BA
SE
M
O U
N
TA
IN
H
O M
E, ID
AH
O
FA
-2
0- D
-0
D
EC
EM
BE
R
PR
O
JE
C
T N
U M
BE
R
SH
EE
T N
U M
BE
R
AN
SI
D
FA
-2
5- F-
M O
U N
TA
IN
H O
M E
AI
R
F O
R C
E
BA
SE
B2
FI
R
E
AL
AR
M
R
EP
AI
R
100% DESIGN SUBMITTAL
O
F
Z.
S
AC
H
SE
N
M
AI
ER
W . C
U N
AR
D
R . R
IC
H
TE
R
P.
D
ER
R
LE
VE
L
TW
O D
EM
O
LI
TI
O N
P
LA
N
AR
EA
B
FI
R
E
AL
AR
M
FD102B
B2318
CORRIDORS HAVE 1/2-HOUR RATED FIRE-WALLS
SCALE: NTS
KEYPLANA9
PLAN
NORTH
SHEET NOTES
1. REMOVE EXISTING FIRE ALARM SYSTEM IN ITS
ENTIRETY. PATCH AND PAINT WALL AND CEILING
OPENINGS NOT SLATED FOR RE-USE TO MATCH
SURROUNDING SURFACES.
2. DEMO EXISTING CEILING AND WALL MOUNTED
DEVICES, BACK BOXES, CONDUIT AND WIRE IN THEIR
ENTIRETY. ALTERNATELY, THE EXISTING BACK
BOXES MAY BE RE-USED FOR NEW DEVICES,
PROVIDED THAT THE BACK BOX DIMENSIONS ARE
COMPATIBLE WITH NEW DEVICES AND THE BACK BOX
IS IN THE CORRECT LOCATION. EXISTING CONDUIT
SERVING THE EXISTING BACK BOX MAY BE RE-USED
IF THE CONDUIT IS NO LESS THAN 3/4 IN., INSTALLED
IN ACCORDANCE WITH NEC AND IS WARRANTED AS
NEW.
3. THIS BUILDING WILL BE VACATED DURING
CONSTRUCTION.
4. UNLESS OTHERWISE NOTED, CEILINGS HEIGHTS ARE
LESS THAN 10FT.
5. UNLESS OTHERWISE NOTED, CEILINGS FEATURE
ACOUSTICAL CEILING TILES SUPPORTED BY METAL
GRIDDED FRAMES. REFER ALSO TO CEILING LEGEND.
6. THROUGH AND MEMBRANE PENETRATIONS OF FIRE
AND SMOKE RATED CONSTRUCTION SHALL BE
PERFORMED IN A MANNER THAT MAINTAINS THE
EXISTING RATINGS. LISTED FIRESTOPPING SYSTEMS
AND MATERIALS SHALL BE PROVIDED AS REQUIRED.
REFERENCE DIVISION 07 84 00.
uu uu u u u
S S S SMOKE-RATED PARTITION
1-HOUR FIRE-RATED BARRIER
2-HOUR FIRE-RATED BARRIER
WALL RATINGS
ACT LIFT-OUT CEILING TILES
GYPSUM BOARD
OPEN TO DECK ABOVE
CEILING LEGEND
A
B
C
CHAIN LINK
FENCE
ROOM
STORAGE
ROOM
ROOM
ROOM
ROOM
ROOM
ROOM
ROOM
STAIRS
STAIRS
ROOM
ROOM
ROOM
ROOM
STORAGE
CENTER
LOBBY
DAYROOM
CORRIDOR
CORRIDOR
u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u uuu u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u
DET DET
DET DET DET
DET
DET
DET DET DET DET DET
DET DET DET DET
DET DET DET DET
DET DET DET DET
F
F
DET
FD
3A M
AT
C
H
LI
N E
FD
3B
FD
3A
M
AT
C H
LI
N
E
FD
3B
ELECTRICAL PANELS
3C AND 3D
AB
B B B
A
B
B BA A
B B B B
A
B
B A A
B
B A
A B
B
A
B
B
B
A B
B
B B
A A AB
B
B
B
A
BB
A
A B
B
A
C
A A
DET
DET
A B
0 8'4' 16'SCALE: 1/8" = 1'-0"
LEVEL THREE DEMOLITION PLAN - AREA A - FIRE ALARMA1
PLAN
NORTH
D
EL
IV
ER
Y O
R D
ER
N
O
D
ES
IG
N
ED
B
Y:
D
ES
C R
IP
TI
O N
M
AR
K
SI
ZE
SU
BM
IT
TE
D B
Y:
D
AT
E
C O
N
TR
AC
T
N U
M
BE
R
C H
EC
KE
D B
Y:
D R
AW
N
B Y:
IS
SU
E D
AT
E:
G
2 3 4 5 6 7 8 9 10
F
E
D
C
B
A SHEET ID
H D
R E ng in ee rin g, In c.
E.
P
AR
KC
EN
TE
R B
LV
D
BO
IS
E, ID
(2
) 3
-7
U .S
. A
IR
F O
R C
E
C
ES
/C
EN
M O
U N
TA
IN
H O
M E
AI
R
F O
R C
E
BA
SE
M
O U
N
TA
IN
H
O M
E, ID
AH
O
FA
-2
0- D
-0
D
EC
EM
BE
R
PR
O
JE
C
T N
U M
BE
R
SH
EE
T N
U M
BE
R
AN
SI
D
FA
-2
5- F-
M O
U N
TA
IN
H O
M E
AI
R
F O
R C
E
BA
SE
B2
FI
R
E
AL
AR
M
R
EP
AI
R
100% DESIGN SUBMITTAL
O
F
Z.
S
AC
H
SE
N
M
AI
ER
W . C
U N
AR
D
R . R
IC
H
TE
R
P.
D
ER
R
AR
EA
A
FI
R
E
AL
AR
M
LE
VE
L
TH
R
EE
D
EM
O
LI
TI
O
N P
LA
N
FD103A
CORRIDORS HAVE 1/2-HOUR RATED FIRE-WALLS
SCALE: NTS
KEYPLANA9
PLAN
NORTH
SHEET NOTES
1. REMOVE EXISTING FIRE ALARM SYSTEM IN ITS
ENTIRETY. PATCH AND PAINT WALL AND CEILING
OPENINGS NOT SLATED FOR RE-USE TO MATCH
SURROUNDING SURFACES.
2. DEMO EXISTING CEILING AND WALL MOUNTED
DEVICES, BACK BOXES, CONDUIT AND WIRE IN THEIR
ENTIRETY. ALTERNATELY, THE EXISTING BACK
BOXES MAY BE RE-USED FOR NEW DEVICES,
PROVIDED THAT THE BACK BOX DIMENSIONS ARE
COMPATIBLE WITH NEW DEVICES AND THE BACK BOX
IS IN THE CORRECT LOCATION. EXISTING CONDUIT
SERVING THE EXISTING BACK BOX MAY BE RE-USED
IF THE CONDUIT IS NO LESS THAN 3/4 IN., INSTALLED
IN ACCORDANCE WITH NEC AND IS WARRANTED AS
NEW.
3. THIS BUILDING WILL BE VACATED DURING
CONSTRUCTION.
4. UNLESS OTHERWISE NOTED, CEILINGS HEIGHTS ARE
LESS THAN 10FT.
5. UNLESS OTHERWISE NOTED, CEILINGS FEATURE
ACOUSTICAL CEILING TILES SUPPORTED BY METAL
GRIDDED FRAMES. REFER ALSO TO CEILING LEGEND.
6. THROUGH AND MEMBRANE PENETRATIONS OF FIRE
AND SMOKE RATED CONSTRUCTION SHALL BE
PERFORMED IN A MANNER THAT MAINTAINS THE
EXISTING RATINGS. LISTED FIRESTOPPING SYSTEMS
AND MATERIALS SHALL BE PROVIDED AS REQUIRED.
REFERENCE DIVISION 07 84 00.
SHEET KEY NOTES
1. DEMO EXISTING NAC POWER SUPPLY CONDUIT AND WIRE IN
ITS ENTIRETY.
2. DOORS SEPARATING CORRIDORS AND DAY ROOMS FROM
CENTER LOBBY WERE ONCE EQUIPPED WITH DOOR
HOLDERS. THE DOOR HOLDERS HAVE BEEN REMOVED AND
DOORS ARE CURRENTLY EQUIPPED WITH DOOR CLOSERS
TO KEEP DOORS CLOSED. SINGLE GANG BACK BOXES WITH
BLANK COVERS REMAIN. CONTRACTOR SHALL DEMO WIRE
AND BACK BOXES ASSOCIATED WITH THE ONCE INSTALLED
DOOR HOLDERS. CONTRACTOR SHALL PATCH AND PAINT
WALL OPENINGS TO MATCH SURROUNDING SURFACES.
uu uu u u u
S S S SMOKE-RATED PARTITION
1-HOUR FIRE-RATED BARRIER
2-HOUR FIRE-RATED BARRIER
WALL RATINGS
ACT LIFT-OUT CEILING TILES
GYPSUM BOARD
OPEN TO DECK ABOVE
CEILING LEGEND
A
B
C
370CORRIDOR
DAYROOM
336 ROOM
ROOM
ROOM
ROOM
ROOM
ROOM
ROOM
ROOM
ROOM
MECHANICAL
ROOM
ROOM
CORRIDOR
LAUNDRY
u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u uuuu u u
UTILITY
AHU-1
DET
DET
DET DET
DET DET
DETDETDETDET
DETDETDETDET
DET DET
DET DET
DET
F
DETDET
DET
DET
FD
3A M
AT
C
H
LI
N E
FD
3B
FD
3A
M
AT
C H
LI
N
E
FD
3B
ELECTRICAL PANELS
3A AND 3B
DET
AOM
A
B
B
B
A
B
B
B
A
B
B
B
A A A
B
B
B
AAAA
AAA
A B B B
B B B B
B
B
B
BBB
B C
B
A A
DET
A
DET
A B
0 8'4' 16'SCALE: 1/8" = 1'-0"
LEVEL THREE DEMOLITION PLAN - AREA B - FIRE ALARMA1
PLAN
NORTH
D
EL
IV
ER
Y O
R D
ER
N
O
D
ES
IG
N
ED
B
Y:
D
ES
C R
IP
TI
O N
M
AR
K
SI
ZE
SU
BM
IT
TE
D B
Y:
D
AT
E
C O
N
TR
AC
T
N U
M
BE
R
C H
EC
KE
D B
Y:
D R
AW
N
B Y:
IS
SU
E D
AT
E:
G
2 3 4 5 6 7 8 9 10
F
E
D
C
B
A SHEET ID
H D
R E ng in ee rin g, In c.
E.
P
AR
KC
EN
TE
R B
LV
D
BO
IS
E, ID
(2
) 3
-7
U .S
. A
IR
F O
R C
E
C
ES
/C
EN
M O
U N
TA
IN
H O
M E
AI
R
F O
R C
E
BA
SE
M
O U
N
TA
IN
H
O M
E, ID
AH
O
FA
-2
0- D
-0
D
EC
EM
BE
R
PR
O
JE
C
T N
U M
BE
R
SH
EE
T N
U M
BE
R
AN
SI
D
FA
-2
5- F-
M O
U N
TA
IN
H O
M E
AI
R
F O
R C
E
BA
SE
B2
FI
R
E
AL
AR
M
R
EP
AI
R
100% DESIGN SUBMITTAL
O
F
Z.
S
AC
H
SE
N
M
AI
ER
W . C
U N
AR
D
R . R
IC
H
TE
R
P.
D
ER
R
AR
EA
B
FI
R
E
AL
AR
M
LE
VE
L
TH
R
EE
D
EM
O
LI
TI
O
N P
LA
N
FD103B
CORRIDORS HAVE 1/2-HOUR RATED FIRE-WALLS
SCALE: NTS
KEYPLANA9
PLAN
NORTH
SHEET NOTES
1. REMOVE EXISTING FIRE ALARM SYSTEM IN ITS
ENTIRETY. PATCH AND PAINT WALL AND CEILING
OPENINGS NOT SLATED FOR RE-USE TO MATCH
SURROUNDING SURFACES.
2. DEMO EXISTING CEILING AND WALL MOUNTED
DEVICES, BACK BOXES, CONDUIT AND WIRE IN THEIR
ENTIRETY. ALTERNATELY, THE EXISTING BACK
BOXES MAY BE RE-USED FOR NEW DEVICES,
PROVIDED THAT THE BACK BOX DIMENSIONS ARE
COMPATIBLE WITH NEW DEVICES AND THE BACK BOX
IS IN THE CORRECT LOCATION. EXISTING CONDUIT
SERVING THE EXISTING BACK BOX MAY BE RE-USED
IF THE CONDUIT IS NO LESS THAN 3/4 IN., INSTALLED
IN ACCORDANCE WITH NEC AND IS WARRANTED AS
NEW.
3. THIS BUILDING WILL BE VACATED DURING
CONSTRUCTION.
4. UNLESS OTHERWISE NOTED, CEILINGS HEIGHTS ARE
LESS THAN 10FT.
5. UNLESS OTHERWISE NOTED, CEILINGS FEATURE
ACOUSTICAL CEILING TILES SUPPORTED BY METAL
GRIDDED FRAMES. REFER ALSO TO CEILING LEGEND.
6. THROUGH AND MEMBRANE PENETRATIONS OF FIRE
AND SMOKE RATED CONSTRUCTION SHALL BE
PERFORMED IN A MANNER THAT MAINTAINS THE
EXISTING RATINGS. LISTED FIRESTOPPING SYSTEMS
AND MATERIALS SHALL BE PROVIDED AS REQUIRED.
REFERENCE DIVISION 07 84 00.
uu uu u u u
S S S SMOKE-RATED PARTITION
1-HOUR FIRE-RATED BARRIER
2-HOUR FIRE-RATED BARRIER
WALL RATINGS
ACT LIFT-OUT CEILING TILES
GYPSUM BOARD
OPEN TO DECK ABOVE
CEILING LEGEND
A
B
ROOM
MAINT
OFFICE
ROOM
STORAGE
MECH
LAUNDRY
ROOM
ROOM
ROOM
ROOM
STAIRS
STAIRS
ROOM
ROOM
ROOM
ROOM
COMM
136 VESTIBULE
CENTER
LOBBY
VESTIBULE
BREAK
ROOM
1XX
JC
LINEN
CORRIDOR
CORRIDOR
u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u
AIR COOLED
CONDENSOR
N
AC
FM
CU
N
AC
FAA
/LO
C
CS CS CS CS
CS CS CS CS
CSCS
CS
C
C C
F C C
C C
C
C
WP
WP
F
F
FC
FA
1A M
AT
C
H
LI
N E
FA
1B
FA
1A
M
AT
C H
LI
N
E
FA
1B
ELECTRICAL PANELS
1C AND 1D
WP
A E S
SBSBSBSB
SBSBSBSB
SB
SB SB
AC B
B B B B
A
B
B BA A
B B B B
A
B
B A A
B
B A
C C
B A B
B
A
B
B
B
A B
B
B B
A A AB
B
MECH. YARD
WP
WP
WP
COF WP
(NON-ENVIRONMENTALLY
CONTROLLED SPACE)
A B
0 8'4' 16'SCALE: 1/8" = 1'-0"
LEVEL ONE FLOOR PLAN - AREA A - FIRE ALARM AND MASS NOTIFICATION SYSTEMA1
PLAN
NORTH
D
EL
IV
ER
Y O
R D
ER
N
O
D
ES
IG
N
ED
B
Y:
D
ES
C R
IP
TI
O N
M
AR
K
SI
ZE
SU
BM
IT
TE
D B
Y:
D
AT
E
C O
N
TR
AC
T
N U
M
BE
R
C H
EC
KE
D B
Y:
D R
AW
N
B Y:
IS
SU
E D
AT
E:
G
2 3 4 5 6 7 8 9 10
F
E
D
C
B
A SHEET ID
H D
R E ng in ee rin g, In c.
E.
P
AR
KC
EN
TE
R B
LV
D
BO
IS
E, ID
(2
) 3
-7
U .S
. A
IR
F O
R C
E
C
ES
/C
EN
M O
U N
TA
IN
H O
M E
AI
R
F O
R C
E
BA
SE
M
O U
N
TA
IN
H
O M
E, ID
AH
O
FA
-2
0- D
-0
D
EC
EM
BE
R
PR
O
JE
C
T N
U M
BE
R
SH
EE
T N
U M
BE
R
AN
SI
D
FA
-2
5- F-
M O
U N
TA
IN
H O
M E
AI
R
F O
R C
E
BA
SE
B2
FI
R
E
AL
AR
M
R
EP
AI
R
100% DESIGN SUBMITTAL
O
F
Z.
S
AC
H
SE
N
M
AI
ER
W . C
U N
AR
D
R . R
IC
H
TE
R
P.
D
ER
R
AN
D
M
AS
S N
O
TI
FI
C
AT
IO
N S
YS
TE
M
LE
VE
L
O N
E
FL
O O
R P
LA
N
AR
EA
A
FI
R E
AL
AR
M
FA101A
B2318
CORRIDORS HAVE 1/2-HOUR RATED FIRE-WALLS
SHEET NOTES
1. THIS BUILDING WILL BE VACATED DURING
CONSTRUCTION.
2. UNLESS OTHERWISE NOTED, CEILINGS HEIGHTS ARE
LESS THAN 10FT.
3. UNLESS OTHERWISE NOTED, CEILINGS FEATURE
ACOUSTICAL CEILING TILES SUPPORTED BY METAL
GRIDDED FRAMES. REFER ALSO TO CEILING LEGEND.
4. AUDIBLE APPLIANCES INSTALLED WITHIN SLEEPING
ROOMS SHALL HAVE A SOUND LEVEL OF AT LEAST 15
DB ABOVE THE AVERAGE AMBIENT SOUND LEVEL OR
5 DB ABOVE THE MAXIMUM SOUND LEVEL HAVING A
DURATION OF AT LEAST 60 SECONDS OR A SOUND
LEVEL OF AT LEAST 75 DBA, WHICHEVER IS GREATER,
MEASURED AT THE PILLOW LEVEL USING THE
A-WEIGHTED SCALE (DBA) (REFERENCE NFPA 72
§18.4.6).
5. AUDIBLE APPLIANCES INSTALLED WITHIN SLEEPING
ROOMS SHALL BE LOW FREQUENCY (520HZ) DEVICES.
6. UPON DETECTION OF SMOKE WITHIN A SINGLE DORM
ROOM, THE SOUNDER BASE SHALL INITIATE 520 HZ
TEMPORAL 3 ALARM TONE. UPON ACTIVATION OF
TWO OR MORE ROOM SMOKE DETECTORS,
ACTIVATION OF COMMON AREA SMOKE OR HEAT
DETECTOR OR ACTIVATION OF MANUAL PULL
STATION, DORM ROOM SOUNDER BASE SHALL
SILENCE, ALLOWING SPEAKERS TO INITIATE GENERAL
AUDIO EVACUATION MESSAGES.
7. SPEAKERS WITHIN THE DORM ROOM SHALL SOUND
UPON ACTIVATION OF SECOND DORM ROOM SMOKE
DETECTOR, ACTIVATION OF COMMON AREA HEAT OR
SMOKE DETECTION, SPRINKLER SYSTEM WATER
FLOW, ACTIVATION OF MANUAL PULL STATION OR
ACTIVATION OF CARBON MONOXIDE DETECTION.
8. CENTER SPEAKERS WITHIN DORM ROOMS TO ALLOW
FOR THE GREATEST FLEXIBILITY WITH RESPECT TO
FURNITURE PLACEMENT.
9. THROUGH AND MEMBRANE PENETRATIONS OF FIRE
AND SMOKE RATED CONSTRUCTION SHALL BE
PERFORMED IN A MANNER THAT MAINTAINS THE
EXISTING RATINGS. LISTED FIRESTOPPING SYSTEMS
AND MATERIALS SHALL BE PROVIDED AS REQUIRED.
REFERENCE DIVISION 07 84 00.
SHEET KEY NOTES
1. INSTALL NEW FMCU, NAC POWER SUPPLIES, AES
TRANSMITTERS AND SURGE SUPPRESSORS. INSTALL
ENGRAVED PLASTIC SIGN IDENTIFYING FIRE ALARM/MASS
NOTIFICATION CONTROL UNIT, NOTIFICATION APPLIANCE
POWER SUPPLIES, AND SURGE SUPPRESSOR ENCLOSURE.
INSTALL ENGRAVED SIGNAGE INDICATING DEDICATED
120VAC SOURCE, TO INCLUDE PANEL NUMBER/NAME AND
CIRCUIT NUMBER(S).
2. DEDICATED 120 VAC POWER SHALL BE INSTALLED IN
ACCORDANCE WITH THE NATIONAL ELECTRICAL CODE,
NFPA 72, AND UFC 3-520-01 §3-2.7 - INTERIOR ELECTRICAL
SYSTEMS. WHERE MORE THAN ONE DEDICATED CIRCUIT IS
REQUIRED, INSTALL DEDICATED FIRE PROTECTION
SUB-PANEL HAVING NO FEWER THAN 6 CIRCUITS.
3. INSTALL EXTERIOR OMNIDIRECTIONAL VHF ANTENNA FOR
AES RADIO TRANSMITTER. COORDIANTE LOCATION WITH
GOVERNMENT. ANTENNA MOUNTING LOCATION SHALL BE
BASED UPON SIGNAL STRENGTH.
uu uu u u u
S S S SMOKE-RATED PARTITION
1-HOUR FIRE-RATED BARRIER
2-HOUR FIRE-RATED BARRIER
WALL RATINGS
SCALE: NTS
KEYPLANA9
PLAN
NORTH
ACT LIFT-OUT CEILING TILES
GYPSUM BOARD
OPEN TO DECK ABOVE
CEILING LEGEND
A
B
C
VESTIBULE
CORRIDOR
DAYROOM
ROOM
ROOM
ROOM
ROOM
ROOM
ROOM
ROOM
ROOM
ROOM
STORAGE
B
ROOM
ROOM
CORRIDOR
STAIRS
u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u
CS CS
CS CS
CSCSCSCS
CSCSCS
C CC
CC
C
C
WP
F
FA
1A M
AT
C
H
LI
N E
FA
1B
FA
1A
M
AT
C H
LI
N
E
FA
1B
ELECTRICAL
PANELS
1A AND 1B
C
SB SB
SB SB
SBSBSBSB
SBSBSB
A
B
B
B
A
B
B
B
A
B
B
B
A A A
B
B
B
AAAA
AAA
A
A B B B
B B B B
B
B
B
BBB
BB
BB
A B
0 8'4' 16'SCALE: 1/8" = 1'-0"
LEVEL ONE FLOOR PLAN - AREA B - FIRE ALARM AND MASS NOTIFICATION SYSTEMA1
PLAN
NORTH
D
EL
IV
ER
Y O
R D
ER
N
O
D
ES
IG
N
ED
B
Y:
D
ES
C R
IP
TI
O N
M
AR
K
SI
ZE
SU
BM
IT
TE
D B
Y:
D
AT
E
C O
N
TR
AC
T
N U
M
BE
R
C H
EC
KE
D B
Y:
D R
AW
N
B Y:
IS
SU
E D
AT
E:
G
2 3 4 5 6 7 8 9 10
F
E
D
C
B
A SHEET ID
H D
R E ng in ee rin g, In c.
E.
P
AR
KC
EN
TE
R B
LV
D
BO
IS
E, ID
(2
) 3
-7
U .S
. A
IR
F O
R C
E
C
ES
/C
EN
M O
U N
TA
IN
H O
M E
AI
R
F O
R C
E
BA
SE
M
O U
N
TA
IN
H
O M
E, ID
AH
O
FA
-2
0- D
-0
D
EC
EM
BE
R
PR
O
JE
C
T N
U M
BE
R
SH
EE
T N
U M
BE
R
AN
SI
D
FA
-2
5- F-
M O
U N
TA
IN
H O
M E
AI
R
F O
R C
E
BA
SE
B2
FI
R
E
AL
AR
M
R
EP
AI
R
100% DESIGN SUBMITTAL
O
F
Z.
S
AC
H
SE
N
M
AI
ER
W . C
U N
AR
D
R . R
IC
H
TE
R
P.
D
ER
R
AN
D
M
AS
S N
O
TI
FI
C
AT
IO
N S
YS
TE
M
LE
VE
L
O N
E
FL
O O
R P
LA
N
AR
EA
B
FI
R E
AL
AR
M
FA101B
B2318
CORRIDORS HAVE 1/2-HOUR RATED FIRE-WALLS
SHEET NOTES
1. THIS BUILDING WILL BE VACATED DURING
CONSTRUCTION.
2. UNLESS OTHERWISE NOTED, CEILINGS HEIGHTS ARE
LESS THAN 10FT.
3. UNLESS OTHERWISE NOTED, CEILINGS FEATURE
ACOUSTICAL CEILING TILES SUPPORTED BY METAL
GRIDDED FRAMES. REFER ALSO TO CEILING LEGEND.
4. AUDIBLE APPLIANCES INSTALLED WITHIN SLEEPING
ROOMS SHALL HAVE A SOUND LEVEL OF AT LEAST 15
DB ABOVE THE AVERAGE AMBIENT SOUND LEVEL OR
5 DB ABOVE THE MAXIMUM SOUND LEVEL HAVING A
DURATION OF AT LEAST 60 SECONDS OR A SOUND
LEVEL OF AT LEAST 75 DBA, WHICHEVER IS GREATER,
MEASURED AT THE PILLOW LEVEL USING THE
A-WEIGHTED SCALE (DBA) (REFERENCE NFPA 72
§18.4.6).
5. AUDIBLE APPLIANCES INSTALLED WITHIN SLEEPING
ROOMS SHALL BE LOW FREQUENCY (520HZ) DEVICES.
6. UPON DETECTION OF SMOKE WITHIN A SINGLE DORM
ROOM, THE SOUNDER BASE SHALL INITIATE 520 HZ
TEMPORAL 3 ALARM TONE. UPON ACTIVATION OF
TWO OR MORE ROOM SMOKE DETECTORS,
ACTIVATION OF COMMON AREA SMOKE OR HEAT
DETECTOR OR ACTIVATION OF MANUAL PULL
STATION, DORM ROOM SOUNDER BASE SHALL
SILENCE, ALLOWING SPEAKERS TO INITIATE GENERAL
AUDIO EVACUATION MESSAGES.
7. SPEAKERS WITHIN THE DORM ROOM SHALL SOUND
UPON ACTIVATION OF SECOND DORM ROOM SMOKE
DETECTOR, ACTIVATION OF COMMON AREA HEAT OR
SMOKE DETECTION, SPRINKLER SYSTEM WATER
FLOW, ACTIVATION OF MANUAL PULL STATION OR
ACTIVATION OF CARBON MONOXIDE DETECTION.
8. CENTER SPEAKERS AND SMOKE DETECTORS WITHIN
DORM ROOMS TO ALLOW FOR THE GREATEST
FLEXIBILITY WITH RESPECT TO FURNITURE
PLACEMENT.
9. THROUGH AND MEMBRANE PENETRATIONS OF FIRE
AND SMOKE RATED CONSTRUCTION SHALL BE
PERFORMED IN A MANNER THAT MAINTAINS THE
EXISTING RATINGS. LISTED FIRESTOPPING SYSTEMS
AND MATERIALS SHALL BE PROVIDED AS REQUIRED.
REFERENCE DIVISION 07 84 00.
(TYPICAL)
uu uu u u u
S S S SMOKE-RATED PARTITION
1-HOUR FIRE-RATED BARRIER
2-HOUR FIRE-RATED BARRIER
WALL RATINGS
SCALE: NTS
KEYPLANA9
PLAN
NORTH
ACT LIFT-OUT CEILING TILES
GYPSUM BOARD
OPEN TO DECK ABOVE
CEILING LEGEND
A
B
C
SHEET KEY NOTES
1. INSTALL EXTERIOR OMNIDIRECTIONAL VHF ANTENNA FOR
AES RADIO TRANSMITTER. COORDIANTE LOCATION WITH
GOVERNMENT. ANTENNA MOUNTING LOCATION SHALL BE
BASED UPON SIGNAL STRENGTH.
ROOM
HOSPITALITY
ROOM
ROOM
ROOM
ROOM
ROOM
ROOM
ROOM
ROOM
STAIRS
STAIRS
ROOM
ROOM
ROOM
ROOM
STORAGE
CENTER
LOBBY
CORRIDOR
CORRIDOR
u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u uuu u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u u
LODGING
FAA
/LO
C
CS CS CS CS
CS…
This is the start of the file's text. The full file is on GovTribe.
File details come from the government source that posted it. Updated .