2025-12-17_MLB_Kalwall_Replacement_-_IFP_-_Structural_-_Unsigned.pdf
PDF 821 KB Posted
- Attached to
- Skylight Replacement
- Solicitation number
- ITB-2026-0130-0202
- Issued by
- Brevard County, Miramar Beach CDP, Florida
About this file
This is a structural design document prepared by BRPH (Architects Engineers, Inc.) for the Melbourne Airport Authority's Kalwall Replacement project in Melbourne, Florida. The document serves as the unsigned permit-issue structural drawings for the atrium skylight replacement in the main terminal building. The project involves replacing a damaged translucent skylight system with new structural steel framing and Kalwall translucent panels. The structural scope includes installation of HSS (Hollow Structural Section) tubes measuring 8x4x5/16 inches, various angles and plates, field welding to existing structural elements, and coordination with the existing precast concrete walls and truss systems. The design accommodates an ultimate wind speed of 160 mph and nominal wind speed of 124 mph per ASCE 7-22, with occupancy risk category III and exposure category C classifications. The drawings establish design standards referenced from RCSC-20, AISC 360-16, FBC 2023, AWS D1.1-D1.1M-2020, and other applicable codes. All construction must comply with structural steel specifications including ASTM A992 Grade 50 for W and WT shapes, ASTM A500 Grade B for HSS, and ASTM A36 for angles and plates.
The contractor bears responsibility for temporary supports, bracing, and erection procedures during construction to ensure structural stability. All structural steel bolted connections must be snug tight with standard holes made in the shop; field burning of holes and cuts is prohibited except by written engineer approval. Shop drawings require submission to BRPH for review before fabrication commences. The contractor must verify all existing dimensions and conditions prior to ordering materials and fabrication, and notify the structural engineer if conditions differ from the drawings. Adhesive anchors for post-installed applications into cracked concrete must comply with ACI355.4 and ICC-ES AC308, with pre-approved products including Simpson Strong-Tie SET-3G, Hilti HIT-RE 500 V3, Hilti HIT-HY 200 A/R V3, DeWalt PURE110+, and DeWalt AC200+. All welding work requires AWS certification and conformance to structural welding code standards. The finished ground floor elevation is established at 0'-0", with all finished ground floor references to be verified against civil drawings for project-specific datum and elevation information.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Addendum_1_-_RFB20260130-01_Skylight.pdf | ||
| vfile | — | |
| 2025-12-17_MLB_Kalwall_Replacement_-_IFP_-_Architectural_-_Unsigned.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
AFF ABOVE FINISHED FLOOR
AB ANCHOR BOLT
L ANGLE
APPROX APPROXIMATE
ARCH ARCHITECT; ARCHITECTURAL
@ AT
BM BEAM
BLT BOLT
B/; BOTT BOTTOM
CIP CAST-IN-PLACE
CL; C/L CENTERLINE
CLR CLEARANCE; CLEAR
COL COLUMN
CONC CONCRETE
CONN CONNECTION
CONT CONTINUOUS
COORD COORDINATE
CMU CONCRETE MASONRY UNIT
CJ CONTROL JOINT
CC-(XX) CONCRETE COLUMN
DET DETAIL
DIAG DIAGONAL
DIA DIAMETER
DWG DRAWING
DF DROPPED FOOTING
EA EACH
EL; ELEV ELEVATION
EQUIP; EQMT EQUIPMENT
EW EACH WAY
EXIST EXISTING
EXP EXPANSION
EJ; EXP JT EXPANSION JOINT
EXT EXTERIOR
FBA FLAT BAR ANCHOR
FBC FLORIDA BUILDING CODE
FT FOOT; FEET
FIN FINISH
FLR; FL FLOOR; FLOORING
FLD; FD FLOOR DRAIN
FOB FACE OF BRICK
FOF FACE OF FOOTING
FOW FACE OF WALL
FTG FOOTING
FDN FOUNDATION
F(XX) SPREAD FOOTING (TYPE)
GA GAGE
GALV GALVANIZED
GALV STL GALVANIZED STEEL
GEN GENERAL
HP HIGH POINT
HORIZ HORIZONTAL
INT INTERIOR
INFO INFORMATION
LG LONG
LLH LONG LEG HORIZONTAL
LLV LONG LEG VERTICAL
LP LOW POINT
LT GA LIGHT GAGE
MATL MATERIAL
MAX MAXIMUM
MECH MECHANICAL
MFR MANUFACTURER
MID MIDDLE
MTL METAL
MIN MINIMUM
MISC MISCELLANEOUS
MCJ MASONRY CONTROL JOINT
MW(XX) MASONRY WALL REINFORCING (TYPE)
MP(XX) MASONRY PIER (TYPE)
MC(XX) MASONRY COLUMN (TYPE)
NA; N/A NOT APPLICABLE
NTS; N.T.S. NOT TO SCALE
OC; O.C. ON CENTER
OPNG OPENING
OPP OPPOSITE
OPP HND OPPOSITE HAND
QTY QUANTITY
PROJ PROJECTION
LB; # POUND
PLF POUNDS PER LINEAR FOOT
PSF POUNDS PER SQUARE FOOT
PSI POUNDS PER SQUARE INCH
RAD RADIUS
REF REFERENCE
REINF REINFORCED; REINFORCING
REQD REQUIRED
SCHED SCHEDULE
SHT SHEET
SIM SIMILAR
SPEC SPECIFICATION
SQ SQUARE
SF SQUARE FEET
SQ IN SQUARE INCHES
SST; SS STAINLESS STEEL
STD STANDARD
STL STEEL
SC(XX) STEEL COLUMN (TYPE)
T&B TOP AND BOTTOM
THK THICK
THRU THROUGH
T/ CONC TOP OF CONCRETE
T/ FTG TOP OF FOOTING
T/ STL TOP OF STEEL
T&G TONGUE AND GROOVE
TS THICKENED SLAB
TYP TYPICAL
TSE; TE THICKENED SLAB EDGE
UNO; U.N.O. UNLESS NOTED OTHERWISE
VERT VERTICAL
W/ WITH
W/O WITHOUT
WWF WELDED WIRE FABRIC
WF(XX) WALL FOOTING (TYPE)
K KIPS
KSI KIPS PER SQUARE INCH
ABBREVIATIONS
AISC AMERICAN INSTITUTE OF STEEL CONSTRUCTION
AISI AMERICAN IRON AND STEEL INSTITUTE
ASCE AMERICAN SOCIETY OF CIVIL ENGINEERS
AWS AMERICAN WELDING SOCIETY
ASTM AMERICAN SOCIETY FOR TESTING AND MATERIALS
ANSI AMERICAN NATIONAL STANDARDS INSTITUTE
ACI AMERICAN CONCRETE INSTITUTE
NGVD NATIONAL GEODETIC VERTICAL
DATUM
POINT OF REFERENCE
BENCHMARK / WORK POINT
EARTH
CONCRETE
CRUSHED STONE
SECTION LETTER
WHERE DRAWN
DETAIL NUMBER
WHERE DRAWN
ELEVATION
DESCRIPTIONSYMBOLDESCRIPTIONSYMBOL
SYMBOLS AND LEGEND
NORTH
KEY NOTENORTH ARROW
X
S-XXX
GIRDER BEAM
INFILL BEAM
JOIST
CMU WALL
CONCRETE WALL
WALL BELOW
S-XXX
X
GENERAL NOTES:
ALL DETAILS AND SECTIONS SHOWN ON THE DRAWINGS ARE INTENDED TO BE TYPICAL AND SHALL BE CONSTRUED TO APPLY TO ANY SIMILAR SITUATION ELSEWHERE ON THE PROJECT, EXCEPT WHERE A DIFFERENT DETAIL IS SHOWN.
THE CONTRACTOR SHALL WORK STRUCTURAL DRAWINGS TOGETHER WITH ARCHITECTURAL, MECHANICAL, PLUMBING, ELECTRICAL AND CIVIL DRAWINGS AS APPLICABLE TO LOCATE DEPRESSED SLABS, SLOPES, DRAINS, REGLETS, BOLT SETTINGS, GRADES, ETC. ANY DISCREPANCIES SHALL BE CALLED TO THE ATTENTION OF THE ARCHITECT/ENGINEER BEFORE PROCEEDING WITH THE WORK. DO NOT PENETRATE STRUCTURAL ELEMENTS (BEAMS, COLUMNS, WALLS, SLABS, STEEL DECKS, ETC.)
WITHOUT PRIOR WRITTEN APPROVAL OF THE STRUCTURAL ENGINEER.
THE CONTRACTOR SHALL VERIFY ALL DIMENSIONS, CONNECTIONS, EMBED PLATE AND ANCHOR BOLT LOCATIONS FROM EQUIPMENT MANUFACTURER'S APPROVED DRAWINGS AND STEEL FABRICATOR'S ANCHOR BOLT AND EMBED PLATE SETTING
PLANS, WHICH HAVE BEEN APPROVED BY THE ARCHITECT/ENGINEER.
ALL MATERIALS AND WORKMANSHIP SHALL COMPLY WITH PROJECT DRAWINGS AND SPECIFICATIONS2.
3.
6.
9.
1. DESIGN IS BASED ON THE APPLICABLE CODES AND STANDARDS REFERENCED IN THE DESIGN STANDARDS.
THE CONTRACTOR SHALL VERIFY ALL EXISTING DIMENSIONS, ELEVATIONS AND CONDITIONS PRIOR TO ORDERING ANY MATERIALS AND SHALL NOTIFY THE ARCHITECT/ENGINEER IF DIFFERENT FROM WHAT IS SHOWN ON THE DRAWINGS.
4.
THE CONTRACTOR SHALL REVIEW THESE DRAWINGS AND VISIT THE PROJECT SITE BEFORE CONSTRUCTION BEGINS TO COMPARE ALL EXISTING CONDITIONS WITH WHAT IS SHOWN ON THESE DRAWINGS. IF THERE ARE CONDITIONS WHICH ARE DIFFERENT FROM WHAT IS SHOWN, THE STRUCTURAL ENGINEER OF RECORD SHALL BE NOTIFIED.
THE CONTRACTOR SHALL ARRANGE A PRE-CONSTRUCTION MEETING WITH THE ARCHITECT/ENGINEER TO ENSURE THAT THE CONTRACTOR'S UNDERSTANDING OF THESE DRAWINGS AND PLAN FOR THE WORK IS IN ACCORDANCE WITH THE DESIGN INTENT
AND TO CLARIFY ANY QUESTIONS THAT THE CONTRACTOR MAY HAVE.
7.
8.
ALL STRUCTURES ARE DESIGNED TO BE STABLE AND SELF-SUPPORTING IN THEIR COMPLETED CONSTRUCTED STATE AT THE END OF CONSTRUCTION. IT IS THE CONTRACTOR'S SOLE RESPONSIBILITY TO DETERMINE ERECTION PROCEDURES AND SEQUENCES THAT ENSURE THE STABILITY OF STRUCTURES AND ITS COMPONENTS DURING CONSTRUCTION. THIS INCLUDES BUT IS NOT LIMITED TO THE ADDITION OF SUPPORTS, BRACING, GUYS WIRES, TIE DOWNS, SHORING AND RE-SHORING. SUCH TEMPORARY SUPPORTS SHALL BE DESIGNED BY QUALIFIED REGISTERED PROFESSIONAL ENGINEERS RETAINED BY THE CONTRACTOR, IN ACCORDANCE WITH LOCAL STATUTES AND REGULATIONS. TEMPORARY SUPPORTS SHALL REMAIN THE PROPERTY OF THE CONTRACTOR AND INFORMATION RELATED TO THEM IS NOT INCLUDED IN THE CONTRACT DOCUMENTS.
5.
12. ELEVATIONS:
FINISHED GROUND FLOOR EL = 0'-0" (TYP. U.N.O.)
FINISHED GROUND FLOOR REF EL = SEE CIVIL DWGS FOR PROJECT SPECIFIC DATUM & ELEVATION
13. SHOP DRAWING SUBMITTALS:
A. CONTRACTOR SHALL SUBMIT TO BRPH FOR REVIEW SHOP DRAWINGS FOR ALL APPLICABLE TRADES IN ACCORDANCE WITH
THE REQUIREMENTS OF THE CONTRACT DOCUMENTS.
B. IN ORDER TO EXPEDITE REVIEW OF SHOP DRAWINGS BY BRPH AND AVOID ANY NEED FOR RE-SUBMITTAL BY THE CONTRACTOR, SUBMITTED SHOP DRAWINGS SHALL BE COMPLETE WITH ADEQUATE AND NECESSARY INFORMATION SHOWN
TO FACILITATE THEIR REVIEW.
C. CONTRACTOR SHALL REVIEW THE SHOP DRAWINGS THOROUGHLY AND VERIFY DIMENSIONS, ELEVATIONS, QUANTITIES, ETC. BEFORE SUBMITTING TO BRPH FOR REVIEW. SHOP DRAWINGS NOT REVIEWED AND MARKED APPROVED BY THE
CONTRACTOR WILL BE REJECTED AND RETURNED.
D. CONTRACTOR SHALL BE RESPONSIBLE FOR THE COORDINATION BETWEEN SHOP DRAWINGS AND DRAWINGS OF DIFFERENT TRADES. ANY FIELD ISSUES AS A RESULT OF THE LACK OF SUCH COORDINATION SHALL BE THE
RESPONSIBILITY OF THE CONTRACTOR.
THAT WHICH IS REFERENCED AS BEING ON "HOLD" SHALL BE INCLUDED IN THE BID AND WORK, HOWEVER FABRICATION AND/OR
CONSTRUCTION SHALL NOT PROCEED UNTIL THE "HOLD" REFERENCE IS REMOVED.
10.
DO NOT SCALE THE STRUCTURAL DRAWINGS TO DETERMINE DIMENSIONS OR MATERIAL QUANTITIES.11.
DESIGN STANDARDS:
1. ALL CONSTRUCTION SHALL BE IN ACCORDANCE WITH THE BUILDING CODE AND PUBLICATIONS LISTED BELOW. IN THE CASE OF
CONFLICTING REQUIREMENTS, THE BUILDING CODE SHALL GOVERN.
2. APPLICABLE CODES AND STANDARDS:
BUILDING CODE
RCSC-20
AISC 360-16
AISI S100-16(2020) WITH SUPPLEMENT 2
ASCE 7-22
ASTM
ICC
AWS D1.1-D1.1M-2020
AISI S240-20
FLORIDA BUILDING CODE 2023 (FBC), 8TH EDITION
RESEARCH COUNCIL ON STRUCTURAL CONNECTIONS,
"SPECIFICATION FOR STRUCTURAL JOINTS USING HIGH-STRENGTH
BOLTS"
AMERICAN INSTITUTE OF STEEL CONSTRUCTION, "SPECIFICATION
FOR STRUCTURAL STEEL BUILDINGS"
AMERICAN IRON AND STEEL INSTITUTE, "NORTH AMERICAN
SPECIFICATION FOR THE DESIGN OF COLD-FOMRED STEEL
STRUCTURAL MEMBERS"
AMERICAN SOCIETY OF CIVIL ENGINEERS, "MINIMUM DESIGN LOADS
AND ASSOCIATED CRITERIA FOR BUILDINGS AND OTHER
STRUCTURES"
AMERICAN SOCIETY FOR TESTING AND MATERIALS (ASTM
INTERNATIONAL)
INTERNATIONAL CODE COUNCIL, INTERNATIONAL CODE COUNCIL -
EVALUATION SERVICES (ICC-ES)
AMERICAN WELDING SOCIETY, "STRUCTURAL WELDING
CODE - STEEL"
AMERICAN IRON AND STEEL INSTITUTE, "NORTH AMERICAN
STANDARD FOR COLD-FORMED STEEL STRUCTURAL FRAMING"
DESIGN CRITERIA:
DESIGN WIND LOAD: (PER ASCE 7)2.
OCCUPANCY RISK CATEGORY III
EXPOSURE CATEGORY C
ULTIMATE WIND SPEED, Vult 160 MPH
NOMINAL WIND SPEED, Vasd 124 MPH
ENCLOSURE CLASSIFICATION ENCLOSED
INTERNAL PRESSURE COEFFICIENT ±0.18
1. DESIGN DEAD LOADS:
ROOFS SELF WEIGHT
WALLS SELF WEIGHT
COMPONENTS & CLADDING SEE DIAGRAMS BELOW
1. THE CONTRACTOR IS REQUIRED TO PROVIDE ALL TEMPORARY SCAFFOLDING, PLATFORMS, BARRICADES, RAILINGS, SCREENING, ETC. NECESSARY TO PROTECT EXISTING FACILITIES, STRUCTURES AND THE PUBLIC DURING DEMOLITION AND ERECTION OF THE CONSTRUCTION, AS WELL AS FOR JOB SAFETY. JOB SAFETY, CONSTRUCTION AND DEMOLITION PROCEDURES ARE THE SOLE RESPONSIBILITY OF THE CONTRACTOR. THE CONTRACTOR IS REQUIRED TO TAKE ALL PRECAUTIONS TO MINIMIZE VIBRATION, NOISE, DUST AND DEBRIS IN ALL AREAS ADJACENT TO AREAS OF DEMOLITION.
DEMOLITION:
2. THE CONTRACTOR IS REQUIRED TO COORDINATE WITH THE OWNER FOR THE TEMPORARY SUSPENSION OF USE OF ANY FACILITY OR PORTION THEREOF, AND THE ASSOCIATED BARRICADING REQUIREMENTS WITHIN A MINIMUM OF 7 DAYS PRIOR TO
COMMENCING WORK.
3. THE CONTRACTOR IS REQUIRED TO PERFORM HIS WORK IN A MANNER, WHICH WILL NOT CONFLICT WITH ANY OPERATION, WHICH IS TO REMAIN FUNCTIONAL DURING THE COURSE OF THE PROJECT, UNTIL SUCH OPERATION IS SCHEDULED TO BE SHUT
DOWN.
4. THE CONTRACTOR IS REQUIRED TO COORDINATE WITH OWNER FOR THE TEMPORARY SUSPENSION OF USE OF ANY UTILITY
SYSTEM, A MINIMUM OF 3 DAYS PRIOR TO COMMENCING WORK.
5. AT ALL LOCATIONS WHERE CONSTRUCTION WILL INTERFACE WITH EXISTING ELEMENTS, CUT THROUGH EXISTING STRUCTURE
IN STRAIGHT AND TRUE LINES TO ENSURE A NEAT INTERFACE.
6. BEFORE DEMOLISHING ANY STRUCTURAL ELEMENT, INSTALL ALL REQUIRED TEMPORARY AND/OR PERMANENT BRACING AND
SUPPORTS.
7. PROVIDE TEMPORARY CLOSURE OF ALL ROOF FASCIA, WALL AND OTHER OPENINGS TO PROTECT BUILDING FROM EXPOSURE TO UNDESIRABLE ELEMENTS UNTIL CONSTRUCTION IS WEATHERPROOFED, AT WHICH TIME SUCH TEMPORARY CONSTRUCTION SHALL BE REMOVED. ALL TEMPORARY EXTERIOR WALLS THAT ARE SUBJECT TO WIND LOADS ARE TO BE DESIGNED BY A
DELEGATED ENGINEER.
8. UPON COMPLETION OF CONSTRUCTION UNDER EACH PHASE, ALL DEMOLISHED AREAS SHALL BE RESTORED TO ACCEPTABLE USAGE ACCORDING TO THE CONTRACT DOCUMENTS AS DETERMINED BY THE ARCHITECT/ENGINEER.
9. REMOVE COMPLETELY FROM THE SITE AND LEGALLY DISPOSE ALL DEBRIS GENERATED BY THE DEMOLITION WORK AS THE WORK PROGRESSES. STOCKPILING OF DEBRIS AND BURNING OF DEBRIS ON THE PREMISES IS STRICTLY PROHIBITED.
STRUCTURAL STEEL:
CUTS, HOLES AND THEIR REINFORCEMENT (REQUIRED BY OTHER TRADES) SHALL BE SHOWN ON THE STRUCTURAL STEEL SHOP DRAWINGS AND SHALL BE MADE IN THE SHOP. FIELD BURNING OF HOLES & CUTS IN STRUCTURAL STEEL SHALL NOT BE PERMITTED EXCEPT BY WRITTEN PERMISSION FROM THE STRUCTURAL ENGINEER OF RECORD, UNLESS NOTED
OTHERWISE ON THE DRAWINGS.
9.
8.
7.
6.
5.
4.
3.
UNO ALL BEAM CONNECTIONS SHALL BE BOLTED/WELDED CONNECTIONS SNUG TIGHT AND INSTALLED IN STANDARD HOLES.
ALL HOLES SHALL BE MADE IN THE SHOP. FIELD BURNING OF HOLES AND CUTS IN STRUCTURAL STEEL SHALL NOT BE
PERMITTED.
ALL STRUCTURAL STEEL SHALL HAVE THE FOLLOWING ASTM SPECIFICATION AND YIELD STRENGTHS UNO:
W & WT SHAPES FY = 50 KSI (A992, GRADE 50)
RECTANGULAR & SQUARE HSS FY = 46 KSI (A500, GRADE B)
ANGLES FY = 36 KSI (A36)
ALL OTHER SHAPES (U.N.O.) FY = 36 KSI (A36)
PLATES (U.N.O) FY = 36 KSI (A36)
ALL DETAILING, FABRICATION AND ERECTION SHALL CONFORM TO THE LATEST EDITION OF THE AISC STEEL CONSTRUCTION MANUAL AND THE APPLICABLE CODES AND STANDARDS REFERENCED IN THE DESIGN STANDARDS.
ALL BOLTS SHALL BE GROUP A HIGH STRENGTH, UNO. ALL NUTS SHALL BE A563, UNO. ALL WASHERS SHALL BE F436, UNO.
ALL FILLET WELDS SHALL BE AS INDICATED, BUT NOT LESS THAN AISC MINIMUM. SEE CHART BELOW:
ALL WELDING ELECTRODES SHALL BE E70XX, UNO. ALL WELDING SHALL BE PERFORMED BY AWS CERTIFIED WELDERS AND
SHALL CONFORM TO AWS D1.1/D1.1M STRUCTURAL WELDING CODE - STEEL, LATEST EDITION.
THE FABRICATOR SHALL FURNISH A STRUCTURAL SUBMITTAL WHICH SHALL BE CHECKED BY THE CONTRACTOR FOR COMPLETENESS AND CONTENT PRIOR TO SUBMITTAL TO THE STRUCTURAL ENGINEER OF RECORD FOR REVIEW. THE SUBMITTAL SHOULD INCLUDE FABRICATION AND ERECTION DRAWINGS. FABRICATION SHALL NOT COMMENCE UNTIL THIS
REVIEW IS COMPLETED.
MINIMUM SIZE FOR FILLET WELDS
MATERIAL THICKNESS OF THINNER
PART JOINED (INCHES)
TO 1/4" INCLUSIVE
MINIMUM SIZE OF
FILLET WELD (INCHES)
1/8"
OVER 1/4" TO 1/2" 3/16"
OVER 1/2" TO 3/4" 1/4"
OVER 3/4" 5/16"
NOMINAL BOLT HOLE DIMENSIONS (INCHES)
1/2 9/16 5/8 9/16 x 11/16 9/16 x 1 1/4
5/8 11/16 13/16 11/16 x 7/8 11/16 x 1 9/16
3/4 13/16 15/16 13/16 x 1 13/16 x 1 7/8
7/8 15/16 1 1/16 15/16 x 1 1/8 15/16 x 2 3/16
1 1 1/8 1 1/4 1 1/8 x 1 5/16 1 1/8 x 2 1/2
> 1 1/8 d + 1/8 d + 5/16 (d + 1/8)x(d + 3/8) (d + 1/8)x(2.5 * d)
12. AFTER ERECTION, ALL STEEL SHALL BE CLEANED OF ALL RUST, LOOSE MILL, SCALE, AND OTHER FOREIGN MATERIAL.
SCUFFS AND ABRASIONS SHALL BE FIELD TOUCHED-UP.
11. SIZE AND SHAPE OF STRUCTURAL STEEL SHALL BE AS SHOWN ON DRAWINGS. SUBSTITUTES MAY BE USED IF PRE-
APPROVED IN WRITING BY THE STRUCTURAL ENGINEER OF RECORD.
10.
ALL STRUCTURAL STEEL TO BE PRIMED AND PAINTED. ALL FIELD CONNECTIONS ARE TO BE PAINTED TO MATCH
ATTACHED COMPONENTS.
13.
BOLT
DIAMETER
STANDARD
(DIA)
OVERSIZE
(DIA)
SHORT-SLOT
(WIDTHxLENGTH)
LONG-SLOT
(WIDTHxLENGTH)
1. DESIGN, FABRICATION AND ERECTION OF ALL STRUCTURAL STEEL SHALL BE IN ACCORDANCE WITH THE LATEST ADOPTED
EDITION OF THE AISC STEEL CONSTRUCTION MANUAL.
14. ALL WELDING WORK SHALL FOLLOW INFORMATION IN AN APPROVED WELDING PROCEDURE SPECIFICATION SUPPORTED BY A PRE-QUALIFICATION RECORD, FOLLOWING REQUIREMENTS IN THE CURRENT BUILDING CODE ADOPTED VERSION OF THE AMERICAN WELDING SOCIETY (AWS) D1.1 - STRUCTURAL WELDING CODE STEEL. ALL WELDING WORK SHALL BE PERFORMED BY WELDERS CERTIFIED TO PERFORM WELDING WORK IN ACCORDANCE WITH THE GOVERNING WPS.
THE STRUCTURAL FRAME FABRICATOR SHALL BE AISC CERTIFIED FOR STEEL BUILDING STRUCTURES (STD) OR INCLUDE, AT THE FABRICATORS EXPENSE, INSPECTION SERVICES NECESSARY TO INSURE THAT THE SHOP PROCEDURES AND FABRICATION COMPLIES WITH DRAWINGS AND SPECIFICATIONS. SPECIFICALLY, ALL BOLTED AND WELDED CONNECTIONS FOR TRUSSES, MOMENT CONNECTIONS AND VERTICAL BRACED FRAME COMPONENTS SHALL BE INSPECTED AND TESTED BY A CERTIFIED TESTING AGENCY RETAINED BY THE FABRICATOR. COMPLIANCE REPORTS SHALL BE SENT TO THE STRUCTURAL
ENGINEER OF RECORD.
2.
ADHESIVE ANCHORS:
FOR POST-INSTALLED ADHESIVE ANCHORS INTO CRACKED CONCRETE, PRODUCTS SHALL HAVE BEEN TESTED AND QUALIFIED FOR USE IN ACCORDANCE WITH ACI355.4 AND ICC-ES AC308. INSTALLATION SHALL COMPLY WITH MANUFACTURE'S LATEST
ICCC-ES APPROVAL. PRE-APPROVED ADHESIVES INCLUDE:
1.
SUBSTITUTION REQUESTS FOR PRODUCTS OTHER THAN THOSE LISTED ABOVE MAY BE SUBMITTED BY THE CONTRACTOR TO THE ENGINEER-OF-RECORD (EOR) FOR REVIEW. SUBSTITUTIONS WILL ONLY BE CONSIDERED FOR PRODUCTS HAVING A CODE REPORT RECOGNIZING THE PRODUCT FOR THE APPROPRIATE APPLICATION. SUBSTITUTION REQUESTS SHALL INCLUDE CALCULATIONS DEMONSTRATING THE SUBSTITUTION IS THE EQUIVALENT CAPABLE OF ACHIEVING PERFORMANCE
VALUES OF THE PRE-APPROVED PRODUCTS.
2.
ADHESIVE ANCHORS SHALL BE INSTALLED PER THE MANUFACTURER'S INSTRUCTIONS. THE CONTRACTOR SHALL CONTACT THE MANUFACTURER FOR PRODUCT INSTALLATION TRAINING. MANUFACTURER'S FIELD REPRESENTATIVE SHALL PROVIDE INSTALLATION TRAINING FOR ALL PRODUCTS TO BE USED, PRIOR TO COMMENCEMENT OF WORK. ONLY TRAINED INSTALLERS SHALL PERFORM POST INSTALLED ANCHOR INSTALLATION. A RECORD OF TRAINING SHALL BE KEPT ON SITE
AND BE MADE AVAILABLE TO THE EOR AS REQUESTED.
3.
INSTALLATION OF ADHESIVE ANCHORS IN HORIZONTAL TO VERTICALLY OVERHEAD ORIENTATION, OR OTHER CONFIGURATION THAT RESULTS IN SUSTAINED TENSION, SHALL BE DONE BY A CERTIFIED ADHESIVE ANCHOR INSTALLER (AAI), AS CERTIFIED THROUGH ACI AND IN ACCORDANCE WITH ACI 318. PROOF OF CURRENT CERTIFICATION SHALL BE
SUBMITTED TO THE ENGINEER FOR APPROVAL PRIOR TO COMMENCEMENT OF INSTALLATION.
4.
ADHESIVE ANCHORS SHALL BE INSTALLED IN CONCRETE HAVING A MINIMUM AGE OF 21 DAYS AT THE TIME OF ANCHOR
INSTALLATION, IN ACCORDANCE WITH ACI 318.
5.
A. SIMPSON STRONG-TIE SET-3G
B. HILTI HIT-RE 500 V3 SLOW CURE A (APPROVED FOR DYNAMIC LOADING)
C. HILTI HIT-HY 200 A/R V3 FAST CURE.
D. DEWALT PURE110+
E. DEWALT AC200+ FAST CURE.
THE CONTRACTOR SHALL ARRANGE AN ANCHOR MANUFACTURER’S REPRESENTATIVE TO PROVIDE ONSITE INSTALLATION TRAINING FOR ALL ANCHOR PRODUCTS SPECIFIED. THE STRUCTURAL ENGINEER OF RECORD MUST RECEIVE DOCUMENTED CONFIRMATION THAT ALL PERSONNEL WHO INSTALL ANCHORS ARE TRAINED PRIOR TO THE COMMENCEMENT OF ANCHOR
INSTALLATION.
6.
THE CONTRACTOR SHALL ARRANGE AN ANCHOR MANUFACTURER’S REPRESENTATIVE TO PROVIDE ONSITE INSTALLATION TRAINING FOR ALL ANCHOR PRODUCTS SPECIFIED. THE STRUCTURAL ENGINEER OF RECORD MUST RECEIVE DOCUMENTED CONFIRMATION THAT ALL PERSONNEL WHO INSTALL ANCHORS ARE TRAINED PRIOR TO THE COMMENCEMENT OF ANCHOR
INSTALLATION.
7.
ADHESIVE ANCHOR RODS SHALL BE PRECUT THREADED ROD SUPPLIED WITH NUT AND WASHER MEETING AISI 304
STAINLESS STEEL.
9.
SECTION AT ALCOVE SECTION AT ROOF OVERHANG
ROOF
OVERHANG
ZONE 4/5 WALL
PRESSURE
ZONE 4/5 WALL
PRESSURE
ZONE 4 WALL
PRESSURE OR
1.15 x ZONE 5
WALL PRESSURE
ZONE 4 OR ZONE 5
WALL PRESSURE
ALCOVE WIND PRESSURE DIAGRAM
SCALE: NTS
ZONE 2 ROOF PRESSURE
OR 1.15x ZONE 3 ROOF
PRESSURE
NOTE: PARAPETS SHALL BE DESIGNED FOR THE WIND PRESSURE LOAD CASES SHOWN ABOVE:
CASE 1 & CASE 2 WIND PRESSURES ARE APPLIED INDEPENDENTLY.
PARAPET LOAD CASE 1 PARAPET LOAD CASE 2
O U
T S
ID
E
IN
S
ID
E
O U
T S
ID
E
IN
S
ID
E
WALL ZONE
4/5
WALL ZONE
4/5
ROOF ZONE
2/3
WALL ZONE
4/5
PARAPET WIND PRESSURE DIAGRAM
SCALE: NTS
FOR NET ROOF UPLIFT, 5 PSF DEAD LOAD SHALL BE PERMISSIBLE.
PLUS & MINUS SIGNS SIGNIFY PRESSURE ACTING TOWARD AND AWAY FROM THE SURFACE.
ZONE 4 = WALL AREAS OTHER THAN ZONE 5 & ZONE 5 = WALL AREAS WITHIN "a" = 6'-0" OF EACH CORNER.
PRESSURES SHOWN ARE BASED ON ASCE 7-22 ULTIMATE WIND SPEED. FOR SERVICE LEVEL PRESSURES, MULTIPLY VALUES IN TABLE BY 0.6.
GROSS PRESSURES ARE FOR JOINTS, WINDOWS, DOORS, VENEER, LIGHT GAGE METAL FRAMING, METAL
DECK ATTACHMENTS, ROOFING, ROOFING ACCESSORIES AND OTHER BUILDING COMPONENTS AND
CLADDING.
AT ALCOVES AND CANOPIES, THE TOTAL PRESSURE ON THE ALCOVE SOFFIT OR CANOPY SHALL EQUAL
THE WALL PRESSURE IN THAT AREA.
1.
2.
3.
4.
5.
6.
COMPONENT & CLADDING ROOF WIND PRESSURES (PSF)
ZONE
EFFECTIVE WIND AREA (SF)
20 50 100 200+
+34.7/-88.61
+34.7/-106.6
+34.7/184.4
+33.5/-87.4
+33.5/-100.6
+33.5/-166.5
+30.5/-79.6
+30.5/-88.6
+30.5/-148.5
+28.7/-76.7
+28.7/-82.6
+28.7/-130.5
COMPONENT & CLADDING WALL WIND PRESSURES (PSF)
ZONE
EFFECTIVE WIND AREA (SF)
20 50 100 200+
+70.7/-76.74
+62.3/-69.5 +59.9/-65.9 +57.5/-63.5
+70.7/-94.6 +80.8/-62.3 +59.9/-73.7 +57.5/-67.1
+28.7/-76.7
+28.7/-82.6
+28.7/-130.5
+67.7/-73.7
+67.7/-88.5
* = SEE PARAPET WIND PRESSURE
DIAGRAM FOR DESIGN WIND
PRESSURE.
4 55
"a" "a"
GROUND LEVEL
ROOF LEVEL
T.O. PARAPET
LEVEL
CORNER CORNER
SCALE: NTS
WIND LOAD WALL ZONE DIAGRAM
3 3
6' - 0"
6'
6'
6' - 0"
6' - 0"
6'
6' - 0"
6' - 0"
6' - 0"
24' - 0" 24' - 0"
ROOF WINDZONES DIAGRAM
SCALE: NTS
F L O R I D
A
P R
O F
E
S S
I O N A L E N G
I N
E E
R
A
NDREW H . M I L L ERL
I C E N S E
No. 38161
STATE OF
Architects Engineers, Inc.
www.brph.com Copyright © 2025
5700 North Harbor City Blvd, Suite 400 Melbourne, Florida 32940 T 321-254-7666
Florida Architectural Business Qualifier #AR95381 Board of Professional Engineers License #1439
These plans are protected by Federal Copyright protection. Unauthorized use may result in an infringement action.
Offices in Melbourne, Orlando, Atlanta, Lynnwood, Charleston and Huntsville
DOCUMENT HISTORY
DRAWING NO.
TITLE
PROJECT NUMBER
DRAWN BY
DESIGNED BY
ARCH/ENGR OF RECORD
DATE
ISSUE FOR PERMIT
54321 6
A
B
C
D
E
If this item has been electronically signed and sealed by the licensed professional named above using a digital signature and date. Printed copies of this document are not considered signed and sealed, and the signature must be verified on electronic copies.
01/16/2025
U :\R ev it
P ro je ct
F ile s\
\C
_S _2
3_
C en tra l_ kp at te rs on A
A U
N K
.rv t
/1
7/
:4 5:
P
M
M E
L B
O U
R N
E A
IR
P
O R
T K
A L
W A
L L
R E
P L A
C E
M E
N T
PATTERSON
NORDIN
M E
L B
O U
R N
E F
L O
R
ID
A
M E
L B
O U
R N
E A
IR
P
O R
T A
U T
H O
R
IT
Y
C09525.002
S-001
12/17/2025
GENERAL NOTES
& WINDZONES
DIAGRAMS
ANDREW H. MILLER
FL PE 38161
53.5 4 4.5 5.5 6 6.5 7 7.5
U.5
U
T.5
T
S.5
S-201
H S
S 8X
4X 5/
H
S S
8X 4X
5/
H S
S 8X
4X 5/
H S
S 8X
4X 5/
H S
S 8X
4X 5/
H S
S 8X
4X 5/
H S
S 8X
4X 5/
H S
S 8X
4X 5/
H S
S 8X
4X 5/
H S
S 8X
4X 5/
H S
S 8X
4X 5/
H S
S 8X
4X 5/
H S
S 8X
4X 5/
H S
S 8X
4X 5/
H S
S 8X
4X 5/
H S
S 8X
4X 5/
H S
S 8X
4X 5/
H S
S 8X
4X 5/
H S
S 8X
4X 5/
H S
S 8X
4X 5/
H S
S 8X
4X 5/
H S
S 8X
4X 5/
H S
S 8X
4X 5/
H S
S 8X
4X 5/
H S
S 8X
4X 5/
H S
S 8X
4X 5/
H S
S 8X
4X 5/
H S
S 8X
4X 5/
H S
S 8X
4X 5/
H S
S 8X
4X 5/
H S
S 8X
4X 5/
H S
S 8X
4X 5/
H S
S 8X
4X 5/
H S
S 8X
4X 5/
H S
S 8X
4X 5/
H S
S 8X
4X 5/
H S
S 8X
4X 5/
H S
S 8X
4X 5/
H S
S 8X
4X 5/
H S
S 8X
4X 5/
H S
S 8X
4X 5/
H S
S 8X
4X 5/
H S
S 8X
4X 5/
H S
S 8X
4X 5/
H S
S 8X
4X 5/
H S
S 8X
4X 5/
H S
S 8X
4X 5/
H S
S 8X
4X 5/
H S
S 8X
4X 5/
H S
S 8X
4X 5/
H S
S 8X
4X 5/
H S
S 8X
4X 5/
H S
S 8X
4X 5/
H S
S 8X
4X 5/
H S
S 8X
4X 5/
H S
S 8X
4X 5/
H S
S 8X
4X 5/
H S
S 8X
4X 5/
H S
S 8X
4X 5/
H S
S 8X
4X 5/
H S
S 8X
4X 5/
H S
S 8X
4X 5/
H S
S 8X
4X 5/
H S
S 8X
4X 5/
H S
S 8X
4X 5/
H S
S 8X
4X 5/
H S
S 8X
4X 5/
H S
S 8X
4X 5/
H S
S 8X
4X 5/
H S
S 8X
4X 5/
H S
S 8X
4X 5/
H S
S 8X
4X 5/
H S
S 8X
4X 5/
H S
S 8X
4X 5/
H S
S 8X
4X 5/
H S
S 8X
4X 5/
S-501
D
S-501
G
S-501
K
S-501
K
S-501
B
S-501
C
S-501
A
S-501
H
S-501
D
S-501
D
S-501
D
S-501
D
S-501
H
S-501
G
S-501
G
S-501
G
S-501
A
S-501
A
S-501
C
S-501
C
S-501
B
S-501
B
SIM
S-501
G
SIM
OPP
HND
S-501
G
OPP
HND
S-501
G
OPP
HND
S-501
G
OPP
HND
S-501
C
OPP
HND
S-501
C
S-501
C
OPP
HND
OPP
HND
S-501
A
SIM
S-201
A
14.14'(REF)
14' - 1 11/16" (REF)
14.14'(REF)
14' - 1 11/16" (REF)
14.14'(REF)
14' - 1 11/16" (REF)
14.14'(REF)
14' - 1 11/16" (REF)
14.14'(REF)
14' - 1 11/16" (REF)
14.14'(REF)
14' - 1 11/16" (REF)
14.14'(REF)
14' - 1 11/16" (REF)
14.14'(REF)
14' - 1 11/16" (REF)
.1
4' (R
E F
1/
(R
E F
.1
4' (R
E F
1/
(R
E F
.1
4' (R
E F
1/
(R
E F
.1
4' (R
E F
1/
(R
E F
[W8x35] [W8X48] [W8x35]
EXIST TRUSS
SPLICE
EXIST TRUSS
SPLICE
[W8X31]
[W8X18]
EXIST TRUSS
SPLICE
EXIST TRUSS
SPLICE
[W10x49] [W10X60] [W10x49]
S-501
F
S-501
E
S-501
E
S-501
E
S-501
E
S-501
E
S-501
E
(4) EQ SPACES
1 TYP
[W8X24]
[W8X18] [W8X18]
[W8X18] [W8X18]
[W 8X
[W 8X
[W 8X
[W 8X
[W8X18] [W8X18]
[W 8X
[W 8X
(4) EQ SPACES (4) EQ SPACES (4) EQ SPACES (4) EQ SPACES (4) EQ SPACES (4) EQ SPACES(4) EQ SPACES
0.
'(R E
F
1/
(R E
F
0.
'(R E
F
1/
(R E
F
0.
'(R E
F
1/
(R E
F
0.
'(R E
F
1/
(R E
F
0.
'(R E
F
1/
(R E
F
0.
'(R E
F
1/
(R E
F
0.
'(R E
F
1/
(R E
F
0.
'(R E
F
1/
(R E
F
0.42'(REF)
5 1/16" (REF)
0.42'(REF)
5 1/16" (REF)
0.42'(REF)
5 1/16" (REF)
0.42'(REF)
5 1/16" (REF)
0.42'(REF)
5 1/16" (REF)
0.42'(REF)
5 1/16" (REF)
0.42'(REF)
5 1/16" (REF)
0.42'(REF)
5 1/16" (REF)
0.
'(R E
F
1/
(R E
F
0.
'(R E
F
1/
(R E
F
S-501
M
S-501
M
S-501
M
S-501
M
S-501
K
S-501
J
S-501
J
S-501
J
S-501
J
OPP
HND
S-501
J
OPP
HND
S-501
J
OPP
HND
WT4X12
L4 X
4X 5/
L4 X
4X 5/
S-501
L
S-501
L
OPP
HND
L3-1/2X2-1/2X5/16
SIM
SIM
S-501
D
S-501
D
S-501
D
SIM
S-501
D
SIM
[W 8X
[W 8X
SIM
S-501
D
S-501
D
SIM
S-501
D
SIM
S-501
D
SIM
S-501
D
SIM
TYP
UNO
TYP
UNO
TYP
UNO
0.36'(REF)
4 5/16" (REF)
0.
'(R E
F
9/
(R E
F
LEGEND:
NOTES:
1. SEE SHEET S-001 FOR GENERAL NOTES AND ABBREVIATIONS.
2. COORDINATE ALL WALL DIMENSIONS AND OPENING LOCATIONS WITH
ARCHITECTURAL DRAWINGS.
3. T/ STEEL ELEV = AS INDICATED ON PLAN
4. CONTRACTOR SHALL VERIFY ALL EXISTING DIMENSIONS AND CONDITIONS
PRIOR TO FABRICATION AND SHALL NOTIFY THE EOR IF ANY DIFFER THAN
WHAT IS SHOWN ON THESE DRAWINGS.
1. EXISTING PRECAST CONCRETE WALL.
2. EXISTING TRUSS TOP CHORD. CUT AND REMOVE ALL EXISTING VERTICAL
ANGLES AND EXISTING BLOCKING ATTACHED TO TOP CHORD THAT
INTERFERE WITH NEW CONSTRUCTION.
3. FIELD WELD WT TO UNDERSIDE OF EXISTING BEAM. SEE SECTION F/S-501.
KEY NOTES:
HSS(X)x(X)x(X/XX)
BEAM SIZE
[W(XX)x(XX)]
EXISTING BEAM SIZE
F L O R I D
A
P R
O F
E
S S
I O N A L E N G
I N
E E
R
A
NDREW H . M I L L ERL
I C E N S E
No. 38161
STATE OF
Architects Engineers, Inc.
www.brph.com Copyright © 2025
5700 North Harbor City Blvd, Suite 400 Melbourne, Florida 32940 T 321-254-7666
Florida Architectural Business Qualifier #AR95381 Board of Professional Engineers License #1439
These plans are protected by Federal Copyright protection. Unauthorized use may result in an infringement action.
Offices in Melbourne, Orlando, Atlanta, Lynnwood, Charleston and Huntsville
DOCUMENT HISTORY
DRAWING NO.
TITLE
PROJECT NUMBER
DRAWN BY
DESIGNED BY
ARCH/ENGR OF RECORD
DATE
ISSUE FOR PERMIT
54321 6
A
B
C
D
E
If this item has been electronically signed and sealed by the licensed professional named above using a digital signature and date. Printed copies of this document are not considered signed and sealed, and the signature must be verified on electronic copies.
01/16/2025
U :\R ev it
P ro je ct
F ile s\
\C
_S _2
3_
C en tra l_ kp at te rs on A
A U
N K
.rv t
/1
7/
:4 5:
P
M
M E
L B
O U
R N
E A
IR
P
O R
T K
A L
W A
L L
R E
P L A
C E
M E
N T
PATTERSON
NORDIN
M E
L B
O U
R N
E F
L O
R
ID
A
M E
L B
O U
R N
E A
IR
P
O R
T A
U T
H O
R
IT
Y
C09525.002
S-101
12/17/2025
ATRIUM ROOF
FRAMING PLAN
ANDREW H. MILLER
FL PE 38161
SCALE: 1/4" = 1'-0"1
ATRIUM ROOF FRAMING PLAN
0 2' 4' 8' 12'
SCALE: 1/4" = 1'-0"
NORTH
T/ EXIST CONC CURB
25' - 6 13/16"(REF)
25.57'(REF)
53.5 4 4.5 5.5 6 6.5 7 7.5
T/ EXIST PRECAST PARAPET
62' - 6 13/16"(REF)
62.57'(REF)
3' - 6 9/16"
EQEQ
(14) SPCS @ 3'-6 9/16" = 49' - 7 7/8"(14) SPCS @ 3'-6 9/16" = 49' - 7 7/8"
H S
S 8X
4X 5/
H S
S 8X
4X 5/
H S
S 8X
4X 5/
H S
S 8X
4X 5/
H S
S 8X
4X 5/
H S
S 8X
4X 5/
H S
S 8X
4X 5/
H S
S 8X
4X 5/
H S
S 8X
4X 5/
H S
S 8X
4X 5/
H S
S 8X
4X 5/
H S
S 8X
4X 5/
H S
S 8X
4X 5/
H S
S 8X
4X 5/
H S
S 8X
4X 5/
H S
S 8X
4X 5/
H S
S 8X
4X 5/
H S
S 8X
4X 5/
H S
S 8X
4X 5/
H S
S 8X
4X 5/
H S
S 8X
4X 5/
H S
S 8X
4X 5/
H S
S 8X
4X 5/
H S
S 8X
4X 5/
H S
S 8X
4X 5/
H S
S 8X
4X 5/
H S
S 8X
4X 5/
H S
S 8X
4X 5/
H S
S 8X
4X 5/
H S
S 8X
4X 5/
S-501
P
S-501
N
S-201
A
EXISTING TRUSS
BEYOND
14.14'(REF)
14' - 1 11/16" (REF)
14.14'(REF)
14' - 1 11/16" (REF)
14.14'(REF)
14' - 1 11/16" (REF)
14.14'(REF)
14' - 1 11/16" (REF)
14.14'(REF)
14' - 1 11/16" (REF)
14.14'(REF)
14' - 1 11/16" (REF)
14.14'(REF)
14' - 1 11/16" (REF)
14.14'(REF)
14' - 1 11/16" (REF)
S-501
M
S-501
M
S-501
M
S-501
M
S-501
L
S-501
L
S-501
K
S-501
K
TYP
UNO
TYP
UNO
OPP
HND
T/ EXIST CONC CURB
25' - 6 13/16"(REF)
25.57'(REF)
U.5 U T.5 T S.5
CL EXIST TRUSS 4 CHORD
59' - 5 5/8"(REF)
59.47'(REF)
CL EXIST TRUSS 3 CHORD
52' - 5 5/8"(REF)
52.47'(REF)
CL EXIST TRUSS 2 CHORD
45' - 5 5/8"(REF)
45.47'(REF)
CL EXIST TRUSS 1 CHORD
38' - 5 5/8"(REF)
38.47'(REF)
CL EXIST BEAM AT GRID S.5
31' - 5 5/8"(REF)
31.47'(REF)
T/ EXIST PRECAST PARAPET
62' - 6 13/16"(REF)
62.57'(REF)
BOT/ OF EXIST PRECAST AT TRUSS 4
44' - 5 3/16"(REF)
44.43'(REF)
T/ EXIST PRECAST AT GRID S.5
32' - 6 13/16"(REF)
32.57'(REF)
1' - 3 1/8"
15' - 9 5/16"
15' - 9 5/16"
15' - 9 5/16"
16' - 2 7/16"
KALWALL WP
KALWALL WP
KALWALL WP
KALWALL WP
S-501
K
S-501
N
S-501
P S-501
F
14.14'(REF)
14' - 1 11/16" (REF)
14.14'(REF)
14' - 1 11/16" (REF)
14.14'(REF)
14' - 1 11/16" (REF)
14.14'(REF)
14' - 1 11/16" (REF)
S-501
A
S-501
A
S-501
A
KALWALL WP
HSS8X4X5/16
HSS8X4X5/16
HSS8X4X5/16
HSS8X4X5/16
NOTES:
1. SEE SHEET S-001 FOR GENERAL NOTES AND ABBREVIATIONS.
2. COORDINATE ALL WALL DIMENSIONS AND OPENING LOCATIONS WITH
ARCHITECTURAL DRAWINGS.
3. T/ STEEL ELEV = AS INDICATED ON ELEVATION
4. CONTRACTOR SHALL VERIFTY ALL EXISTING DIMENSIONS AND
CONDITIONS PRIOR TO FABRICATION AND SHALL NOTIFY THE EOR IF ANY
DIFFER THAN WHAT IS SHOWN ON THESE DRAWINGS.
1. EXISTING PRECAST CONCRETE WALL.
2. TRANSLUCENT PANEL BY KALWALL.
KEY NOTES:
F L O R I D
A
P R
O F
E
S S
I O N A L E N G
I N
E E
R
A
NDREW H . M I L L ERL
I C E N S E
No. 38161
STATE OF
Architects Engineers, Inc.
www.brph.com Copyright © 2025
5700 North Harbor City Blvd, Suite 400 Melbourne, Florida 32940 T 321-254-7666
Florida Architectural Business Qualifier #AR95381 Board of Professional Engineers License #1439
These plans are protected by Federal Copyright protection. Unauthorized use may result in an infringement action.
Offices in Melbourne, Orlando, Atlanta, Lynnwood, Charleston and Huntsville
DOCUMENT HISTORY
DRAWING NO.
TITLE
PROJECT NUMBER
DRAWN BY
DESIGNED BY
ARCH/ENGR OF RECORD
DATE
ISSUE FOR PERMIT
54321 6
A
B
C
D
E
If this item has been electronically signed and sealed by the licensed professional named above using a digital signature and date. Printed copies of this document are not considered signed and sealed, and the signature must be verified on electronic copies.
01/16/2025
U :\R ev it
P ro je ct
F ile s\
\C
_S _2
3_
C en tra l_ kp at te rs on A
A U
N K
.rv t
/1
7/
:4 5:
P
M
M E
L B
O U
R N
E A
IR
P
O R
T K
A L
W A
L L
R E
P L A
C E
M E
N T
PATTERSON
NORDIN
M E
L B
O U
R N
E F
L O
R
ID
A
M E
L B
O U
R N
E A
IR
P
O R
T A
U T
H O
R
IT
Y
C09525.002
S-201
12/17/2025
STRUCTURAL
FRAMING
ELEVATIONS
ANDREW H. MILLER
FL PE 38161
SCALE: 1/4" = 1'-0"1
ATRIUM ELEVATION
0 2' 4' 8' 12'
SCALE: 1/4" = 1'-0"
SCALE: 1/4" = 1'-0"A
SECTION AT GIRD 5.5
SPLICE LOCATION
1' - 0"
L3x3x5/16 x 1'-5"
LONG ANGLE
L3x3x5/16 x 1'-3"
LONG ANGLE
(2)8" x 11" x 1/2"
THICK SPLICE PL
1/4
1/4
TYPTRANSLUCENT
PANEL BY
KALWALL
FASTENERS AND
HARDWARE BY
KALWALL
EXIST W8 TRUSS
TOP CHORD,
SEE PLAN
3/16
3/16
TYP
3/16
TYP
L4x4x5/16
HSS8x4 TUBE, SEE PLAN
CL
COL
FASTENING OF
BATTON TO ANGLE
BY KALWALL
5 7/8"
CL EXIST TRUSS CHORD
SEE ELEV
(6) 3/4"Ø BOLTS
1/
2"
1/ 2"
1/
2"
1/ 2"
1 1/2" TYP
KALWALL WP
3 7/8"
FASTENERS
AND HARDWARE
BY KALWALL
HSS8x4 TUBE, SEE PLAN
EXIST W8 TRUSS
TOP CHORD,
SEE PLAN
L4x4x5/16, TYP
1/2" 1 1/2" 2 1/2" 1 1/2"
1/
4"
1/ 4"
1/4" THICK PL W/ (2)
3/4"Ø BOLTS, TYP
TRANSLUCENT
PANEL BY KALWALL
3/16
3/16
TYP
L3x3x5/16 x 1'-5"
LONG ANGLE
L3x3x5/16 x 1'-3"
LONG ANGLE
FASTENING OF
BATTON TO HSS
BY KALWALL
CL EXIST TRUSS CHORD
SEE ELEV
TRANSLUCENT
PANEL BY
KALWALL
FASTENERS
AND HARDWARE
BY KALWALL
EXIST W8 TRUSS
TOP CHORD,
SEE PLAN
3/16
3/16
3/16
TYP
L4x4x5/16
HSS8x4 TUBE, SEE PLAN
EXIST W8 COL
EXIST
W6x20 BEAM
EXIST W8,
SEE PLAN
BEAM
EXIST W8 COL
STUB
L3x3x5/16 x 1'-5"
LONG ANGLE
L3x3x5/16 x 1'-3"
LONG ANGLE
CL
COL
1/4" WELDED
END PL
4 1/2"
EXIST CONC
WALL BEYOND
FASTENING OF
BATTON TO ANGLE
BY KALWALL
5 7/8"
CL EXIST TRUSS CHORD
SEE ELEV
SEE PLAN SEE PLAN
KALWALL WP
3 7/8"
3/16
TYP
U5
EXIST W10 TRUSS TOP
CHORD, SEE PLAN
HSS8x4x5/16 x 14"
LONG TUBE WITH 1/4"
WELDED END PL'S
3/16
3/16
TYP2"
3/16
TYP
L3x3x5/16 x 1'-0"
LONG ANGLE
NS & FS1/4
1/4
ALUM
FLASHING
BY KALWALLEXIST CONC
WALL
1/4" WELDED
END PL
1/2"
FASTENERS AND
HARDWARE BY
KALWALL
TRANSLUCENT
PANEL BY
KALWALL
L3-1/2x2-1/2x
5/16 LLH
3/16
1/2"
FASTENING OF
BATTON TO ANGLE
BY KALWALL
9"KALWALL WP
1/4" WELDED
END PL
HSS8x4 TUBE, SEE PLAN. COPE
AROUND CONC
EYEBROW.
T/ EXIST PRECAST PARAPET
SEE ELEV
CL EXIST TRUSS CHORD
SEE ELEV
GRIND FLUSH
SEE PLAN SEE PLAN
TRUSS
CHORD
0.13'(REF)
1 9/16" (REF)
0.50'(REF)
6" (REF)
1/2" THICK EXP
JOINT MATL
BETWEEN HSS8x4
AND CONC
TRANSLUCENT
PANEL BY
KALWALL
FASTENERS AND
HARDWARE BY
KALWALL
EXIST W8 BEAM,
SEE PLAN
BEAM
EXIST CONC WALL
CL
COL
FASTENING OF
BATTON TO WALL
BY KALWALL
2 1/2"
SEE PLAN SEE PLAN
4 1/2"
L4x4x5/16
L3x3x5/16 x 1'-0"
LONG ANGLE (FIELD
VERIFY LENGTH)3/16
3/16
FS
ALUM
FLASHING
BY KALWALL
FASTENERS AND
HARDWARE BY
KALWALL
EXIST W8 BEAM,
SEE PLAN
BEAM
EXIST CONC WALL
BLOCKING,
SEE ARCH
DWGS
TRANSLUCENT
PANEL BY
KALWALL
L4x4x5/16
EXIST ANGLE BRACE
EXIST W8 COL
EXIST W8 BEAM,
SEE PLAN
CL
COL
FASTENING OF
BATTON TO ANGLE
BY KALWALL
L3x3x5/16 x 1'-0"
LONG ANGLE (FIELD
VERIFY LENGTH) 5 7/8"
3 7/8"
KALWALL WP
SEE PLAN SEE PLAN
3/16
3/16
EXIST W10
TRUSS TOP
CHORD, SEE
PLAN
L3x3x5/16 x 1'-0"
LONG ANGLE
NS & FS
EXIST CONC
WALL
L3-1/2x2-1/2x
5/16 LLH
1/4" WELDED
END PL
1/2"
3/16
BOTH LEGS, ONE
SIDE EA, TYP
EXIST W6x20 BEAM
TRUSS
CHORD
T/ EXIST PRECAST PARAPET
SEE ELEV
1/2"
ALUM
FLASHING
BY KALWALL
FASTENERS AND
HARDWARE BY
KALWALL
FASTENING OF
BATTON TO ANGLE
BY KALWALL
CL EXIST TRUSS CHORD
SEE ELEV
3/16
TYP
TRANSLUCENT
PANEL BY
KALWALL
3/16
GRIND FLUSH
U5
SEE PLAN SEE PLAN
0.13'(REF)
1 9/16" (REF)
0.50'(REF)
6" (REF)
EXIST ANGLE BRACE
TRIM EXIST PL
TO MISS NEW
HSS8x4 IF REQD
9"KALWALL WP
1/4" WELDED
END PL
HSS8x4 TUBE, SEE PLAN. COPE
AROUND CONC
EYEBROW.
1/2" THICK EXP
JOINT MATL
BETWEEN HSS8x4
AND CONC
U5
EXIST CONC
ROOF
HSS8x4 TUBE W/ 1/4"
WELDED END AND
CLOSURE PL'S, SEE
ELEV. COPE AT CONC
PARAPET.
1/2"
TRANSLUCENT
PANEL BY
KALWALL
L3x3x5/16 x 3"
LONG ANGLE
W/ 3/4"Ø EPOXY
ANCHOR (4 1/2"
MIN EMBED)
BOTH SIDES
3/16
3 SIDES TYP
T/ EXIST CONC CURB
SEE ELEV
3/
4"
0.67'(REF)
8" (REF)
0.17'(REF)
2" (REF)
6"
U5
EXIST W10 TRUSS
BOTTOM CHORD
HSS8x4x5/16 x 7" LONG
TUBE WITH 1/4"
WELDED END PL'S
1/4
1/4
1/4
1/4
HSS8x4 TUBE W/ 1/4"
WELDED END AND
CLOSURE PL'S, SEE
ELEV. COPE AT CONC
OVERHANG.
EXIST CONC
WALL
TRANSLUCENT
PANEL BY
KALWALL
2"
BOT/ OF EXIST
PRECAST AT TRUSS 4
SEE ELEV
CL EXIST TRUSS CHORD
SEE ELEV
SEE PLAN SEE PLAN
TRUSS
CHORD
0.75'(REF)
9" (REF)
0.13'(REF)
1 9/16" (REF)
ALUM
FLASHING
BY KALWALL
FASTENERS AND
HARDWARE BY
KALWALL
EXIST W8 BEAM,
SEE PLAN
BEAM
3/16
BOTH LEGS,
ONE SIDE EA,
TYP
EXIST CONC WALL
BLOCKING,
SEE ARCH
DWGS
TRANSLUCENT
PANEL BY
KALWALL
L4x4x5/16
3/16
TYP
L3x3x5/16 x 1'-0"
LONG ANGLE
NS & FS
CL
COL
1/4" WELDED
END PL
5 7/8"
FASTENING OF
BATTON TO ANGLE
BY KALWALL
1/2"
3 7/8"
KALWALL WP
SEE PLAN SEE PLAN
1 1/2"
ALUM
FLASHING
BY KALWALL
FASTENERS AND
HARDWARE BY
KALWALL
EXIST W8 BEAM,
SEE PLAN
BEAM
3/16
BOTH LEGS,
ONE SIDE EA,
TYP
EXIST CONC WALL
BLOCKING,
SEE ARCH
DWGS
TRANSLUCENT
PANEL BY
KALWALL
L4x4x5/16
3/16
TYP
L3x3x5/16 x 1'-0"
LONG ANGLE
NS & FS
CL
COL
1/4" WELDED
END PL
L6x4x5/16 x 3" LONG ANGLE
BETWEEN L3X3 VERT
ANGLES W/ 3/4"Ø EPOXY
ANCHOR (2 1/2" MIN
EMBED). FIRST NUT ON
ANCHOR SHALL BE FINGER
TIGHT AND SECURED W/ A
SECOND NUT. ANGLE
SHALL HAVE LONG-
SLOTTED HOLE ORIENTED
VERTICALLY, TYP
3/16
5 7/8"
FASTENING OF
BATTON TO ANGLE
BY KALWALL
1/2"
3 7/8"
KALWALL WP
3/16
3 SIDES, TYP
O F
H O
LE
, T
Y P
3/
4" T
O C
E T
N E
R
WT4x12
SPANNING FROM
COL LINE 5 TO 6,
SEE PLAN
SEE PLAN SEE PLAN
1 1/2"
NOTES:
1. SEE SHEET S-001 FOR GENERAL NOTES AND ABBREVIATIONS.
2. CONTRACTOR SHALL VERIFY ALL EXISTING DIMENSIONS AND CONDITIONS
PRIOR TO FABRICATION AND SHALL NOTIFY THE EOR IF ANY DIFFER THAN
WHAT IS SHOWN ON THESE DRAWINGS.
TRANSLUCENT
PANEL BY
KALWALL
FASTENERS AND
HARDWARE BY
KALWALL
EXIST W8 BEAM,
SEE PLAN
BEAM
L4x4x5/16 x
CONT ANGLE
3/4"Ø EPOXY
ANCHOR (2 1/2"
MIN EMBED) @
18" OC MAX
EXIST CONC WALL
CL
COL
T/ EXIST PRECAST PARAPET
SEE ELEV
SEE PLAN SEE PLAN
FASTENING OF
BATTON TO ANGLE
BY KALWALL
3/
4"
EXIST ANGLE BRACE
CL EXIST TRUSS CHORD
SEE ELEV
1.20'(REF)
1' - 2 3/8" (REF)
CL
COL
0.47'(REF)
5 5/8" (REF)
S-501
B
EXIST W8 BEAM,
SEE PLAN
EXIST W8 COL
EXIST W8 TRUSS
TOP CHORD,
SEE PLAN
3/16
3/16
PL
3/16
COPE ANGLE
L3x3 ANGLE, SEE
SECTION C/S-501
U5
ALUM
FLASHING
BY KALWALLEXIST CONC
WALL
FASTENERS AND
HARDWARE BY
KALWALL
TRANSLUCENT
PANEL BY
KALWALL
L3-1/2x2-1/2x
5/16 LLH
3/16
1/2"
FASTENING OF
BATTON TO ANGLE
BY KALWALL
9"
KALWALL WP
L4x4x5/16 ANGLE.
COPE AROUND
CONC EYEBROW.
T/ EXIST PRECAST PARAPET
SEE ELEV
CL EXIST TRUSS CHORD
SEE ELEV
3/16
GRIND FLUSH
SEE PLAN SEE PLAN
COL
0.13'(REF)
1 9/16" (REF)
0.50'(REF)
6" (REF)
1 1/2"
3/4"Ø EPOXY
ANCHOR (2 1/2"
MIN EMBED) @
18" OC MAX
EXIST W10
TRUSS TOP
CHORD, SEE
PLAN
EXIST W8 COL
EXIST W6x20 BEAM
EXIST CONC WALL
BEYOND
1/2"
1/ 2" F
L O R I D A
P R
O F
E
S S
I O N A L E N G
I N
E E
R
A
NDREW H . M I L L ERL
I C E N S E
No. 38161
STATE OF
Architects Engineers, Inc.
www.brph.com Copyright © 2025
5700 North Harbor City Blvd, Suite 400 Melbourne, Florida 32940 T 321-254-7666
Florida Architectural Business Qualifier #AR95381 Board of Professional Engineers License #1439
These plans are protected by Federal Copyright protection. Unauthorized use may result in an infringement action.
Offices in Melbourne, Orlando, Atlanta, Lynnwood, Charleston and Huntsville
DOCUMENT HISTORY
DRAWING NO.
TITLE
PROJECT NUMBER
DRAWN BY
DESIGNED BY
ARCH/ENGR OF RECORD
DATE
ISSUE FOR PERMIT
54321 6
A
B
C
D
E
If this item has been electronically signed and sealed by the licensed professional named above using a digital signature and date. Printed copies of this document are not considered signed and sealed, and the signature must be verified on electronic copies.
01/16/2025
U :\R ev it
P ro je ct
F ile s\
\C
_S _2
3_
C en tra l_ kp at te rs on A
A U
N K
.rv t
/1
7/
:4 5:
P
M
M E
L B
O U
R N
E A
IR
P
O R
T K
A L
W A
L L
R E
P L A
C E
M E
N T
PATTERSON
PATTERSON
M E
L B
O U
R N
E F
L O
R
ID
A
M E
L B
O U
R N
E A
IR
P
O R
T A
U T
H O
R
IT
Y
C09525.002
S-501
12/17/2025
SECTIONS &
DETAILS
ANDREW H. MILLER
FL PE 38161
SCALE: 1 1/2" = 1'-0"A
SECTION
SCALE: 1 1/2" = 1'-0"B
SECTION
SCALE: 1 1/2" = 1'-0"C
SECTION
SCALE: 1 1/2" = 1'-0"K
SECTION
SCALE: 1 1/2" = 1'-0"D
SECTION
SCALE: 1 1/2" = 1'-0"G
SECTION
SCALE: 1 1/2" = 1'-0"M
SECTION
SCALE: 1 1/2" = 1'-0"P
SECTION
SCALE: 1 1/2" = 1'-0"N
SECTION
0 1/2' 1' 1 1/2' 2'
SCALE: 1 1/2" = 1'-0"
SCALE: 1 1/2" = 1'-0"E
SECTION
SCALE: 1 1/2" = 1'-0"F
SECTION
SCALE: 1 1/2" = 1'-0"H
SECTION
SCALE: 1 1/2" = 1'-0"J
SECTION
SCALE: 1 1/2" = 1'-0"L
SECTION
| Sheets |
| S-001 - GENERAL NOTES & WINDZONES DIAGRAMS |
| S-101 - ATRIUM ROOF FRAMING PLAN |
| S-201 - STRUCTURAL FRAMING ELEVATIONS |
| S-501 - SECTIONS & DETAILS |
File details come from the government source that posted it. Updated .