This document is a Request for Quotation (RFQ) issued by UChicago Argonne, LLC for the procurement of electrical equipment, including a transformer, switchboards, and panelboards, as part of the proposed Building 420 Sector 36 Solid State Amplifiers project. The equipment will be ordered under this RFQ but installed and commissioned by an electrical contractor under a future construction contract. The RFQ is based on the lowest price technically acceptable criteria, and responses are due by September 18th. The key equipment required includes a 2000/2666 kVA dry type medium voltage transformer, a 3000A 480Y/277V 3-phase 4-wire switchboard, and four 600A 480V 3-phase 4-wire power distribution panelboards. The Department of Energy Office of Science is the federal agency involved in this procurement.

View the file

Other files

Show all 13

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

COOLING TOWERS

RESERVED

PARKING

ELECTRIC

VEHICLE

CHARGING

ONLY

RESERVED

PARKING

ELECTRIC

VEHICLE

CHARGING

ONLY

RESERVED

PARKING

ELECTRIC

VEHICLE

CHARGING

ONLY

RESERVED

PARKING

ELECTRIC

VEHICLE

CHARGING

ONLY

VISITOR

VISITOR

VISITOR

RESERVED

RESERVED

RESERVED

WARNING

IF PLAN IS ENLARGED OR REDUCED,

GRAPHIC SCALE SHALL BE USED.

J420-104-W- G001 0

BUILDING 420

SOLID STATE AMPLIFIER

TITLE SHEET

AND DRAWING INDEX

Grumman/Butkus Associates Energy Efficiency Consultants and Sustainable Design Engineers

820 Davis St, Ste 300 Evanston, Illinois 60201 4446 847 328.3555 www.grummanbutkus.com Copyright © 2023 Grumman/Butkus Associates Illinois Registration #184-000926 GBA Project: P23-0858-00

1" = 750FT1 SITE PLAN

SEE ENLARGED

LOCATION MAP

1"= 200FT2 ENLARGED VIEW

ARGONNE NATIONAL LABORATORY

BUILDING 420 SOLID STATE AMPLIFIER

PHASE 1 - OWNER EQUIPMENT PRE-PURCHASE

ARGONNE NATIONAL LABORATORY

9700 SOUTH CASS AVENUE

ARGONNE, ILLINOIS 60439

PROJECT MANAGER: LIZ OTT

GENERAL NOTES:

1. ALL WORK DONE BY CONTRACTOR/INSTALLER PURSUANT TO THIS DRAWING

SHALL:

(A) CONFORM TO THE GOVERNING CONTRACT DOCUMENTS.

(B) BE PERFORMED EXCLUSIVELY BY ITS TRAINED, COMPETENT PERSONNEL

OR, WHERE PERMITTED, THAT OF ITS SUBCONTRACTOR(S).

(C) COMPLY WITH ALL APPLICABLE SAFETY LAWS, REGULATIONS, PROGRAMS

AND PRACTICES TO ENSURE THE SAFETY OF ALL PEOPLE LOCATED ON

THE WORK SITE, INCLUDING THE CONTRACTOR'S / INSTALLER'S

PERSONNEL ( OR THAT OF ITS SUBCONTRACTOR(S) ) PERFORMING THE

WORK.

2. UNDERGROUND OR EMBEDDED UTILITIES [MAY] EXIST WITHIN THE AREA OF

AND ADJACENT TO THE LIMITS OF THE WORK. THE LOCATION OR

IDENTIFICATION OF SUCH UTILITIES HAS NOT BEEN VERIFIED BY OWNER.

CONTRACTOR/INSTALLER IS RESPONSIBLE FOR FIELD LOCATING AND

IDENTIFYING UNDERGROUND AND EMBEDDED UTILITIES AND ANY OTHER

UNDERGROUND AND EMBEDDED UTILITY DIMENSIONS.

3. REFERENCES USED HAVE BEEN IDENTIFIED ON EXCAVATION / FOUNDATION /

DEMOLITION DRAWINGS AND HAVE BEEN PROVIDED TO ASSIST THE

CONTRACTOR / INSTALLER IN THE FIELD LOCATING EXISTING UTILITIES AND

OTHER POTENTIAL UNDERGROUND OR EMBEDDED INTERFERENCES. THESE

REFERENCES ONLY SHOW THE APPROXIMATE LOCATION OF POTENTIAL

UNDERGROUND OR EMBEDDED UTILITIES AND MAY NOT INDICATE OR REFLECT

ALL EXISTING UNDERGROUND OR EMBEDDED UTILITIES OR THEIR ACTUAL

LOCATIONS.

4. REFERENCES IDENTIFIED SHALL NOT SUBSTITUTE FOR THE CONTRACTOR'S /

INSTALLER'S OBLIGATION TO FIELD LOCATE ANY UNDERGROUND OR EMBEDDED

UTILITIES OR INTERFERENCES THAT MAY AFFECT THE WORK.

5. DUE CAUTION SHALL BE TAKEN DURING ANY EXCAVATION / FOUNDATION /

DEMOLITION WORK WITHIN THE AREA OF AND ADJACENT TO THE LIMITS OF

THE WORK DUE TO POSSIBLE INTERFERENCES THAT MAY NOT BE REFLECTED

ON THE REFERENCES IDENTIFIED.

6. HORIZONTAL DATUM: NAD83 STATE PLANE ILLINOIS EAST. VERTICAL DATUM:

NAVD88 VERTICAL. UNITS: US SURVEY FOOT.

DRAWING INDEX

GENERAL DRAWING TITLE

J420-G-W-G001 TITLE SHEET & DRAWING INDEX

ELECTRICAL

J420-104-W-E001 ELECTRICAL SYMBOLS, ABBREVIATIONS, AND GENERAL NOTES

J420-104-W-E100 ELECTRICAL BUILDING EXTERIOR NEW WORK

J420-104-W-E101N ELECTRICAL FIRST FLOOR S36 NORTH NEW WORK

J420-104-W-E101S ELECTRICAL FIRST FLOOR S36 SOUTH NEW WORK

J420-104-W-E401 ELECTRICAL SINGLE LINE DIAGRAMS

J420-104-W-E500 ELECTRICAL PANEL SCHEDULES

J420-104-W-E601 ELECTRICAL DETAILS

1. IN THIS PHASE OF WORK, THE MATERIAL VENDORS SHALL PROVIDE THE FOLLOWING MATERIALS ONLY AS PRESCRIBED BY THE ARGONNE NATIONAL LAB SCOPE OF WORK DOCUMENT FOR THIS PREPURCHASE.

GENERAL SCOPE OF WORK IN THIS CONTRACT (PREPURCHASE)

G001.1

FO

R

PR

EP

UR

CH

AS

E

ON

LY

NO

T

FO

R

CO

NS

TR

UC

TI

ON

AutoCAD SHX Text

EXTENSION

AutoCAD SHX Text

LANDFILL

AutoCAD SHX Text

ENE

AutoCAD SHX Text

AREA

AutoCAD SHX Text

AutoCAD SHX Text 330J

AutoCAD SHX Text

AutoCAD SHX Text X

AutoCAD SHX Text 046A

AutoCAD SHX Text

MONUMENT MISSING

AutoCAD SHX Text

ANL GRID BASE

AutoCAD SHX Text

AutoCAD SHX Text

TRAILERS

AutoCAD SHX Text

CONTRACTOR

AutoCAD SHX Text

AutoCAD SHX Text 391A

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

CENTRAL DRIVE

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 597A

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

NORTHGATE ROAD

AutoCAD SHX Text

WESTGATE ROAD

AutoCAD SHX Text

FRONT STREET

AutoCAD SHX Text

FRONT STREET

AutoCAD SHX Text

NORTHGATE ROAD

AutoCAD SHX Text 94th STREET

AutoCAD SHX Text

AutoCAD SHX Text

PONDS

AutoCAD SHX Text

FREUND

AutoCAD SHX Text

SAINT

AutoCAD SHX Text

A.T. & S.F. R.R. SPUR R. O. W.

AutoCAD SHX Text

A N L BOUNDARY LINE

AutoCAD SHX Text

A N L BOUNDARY LINE

AutoCAD SHX Text

A N L BOUNDARY LINE

AutoCAD SHX Text

A N L BOUNDARY LINE

AutoCAD SHX Text

A N L BOUNDARY LINE

AutoCAD SHX Text

A N L BOUNDARY LINE

AutoCAD SHX Text

A N L BOUNDARY LINE

AutoCAD SHX Text

ARGONNE

AutoCAD SHX Text 035B

AutoCAD SHX Text

AREA

AutoCAD SHX Text

LAND FILL

AutoCAD SHX Text

LEMONT ROAD

AutoCAD SHX Text

YARD

AutoCAD SHX Text

COAL

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 108A

AutoCAD SHX Text 108B

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 94th STREET

AutoCAD SHX Text

AutoCAD SHX Text 891A

AutoCAD SHX Text

MADDEN ROAD

AutoCAD SHX Text

NATURE PRESERVE

AutoCAD SHX Text

WATERFALL GLEN

AutoCAD SHX Text

NATURE PRESERVE

AutoCAD SHX Text

WATERFALL GLEN

AutoCAD SHX Text

NORTHERN ILLINOIS GAS CO. EASEMENT (36" PIPE IN 42" CASING)

AutoCAD SHX Text

RAILROAD DRIVE

AutoCAD SHX Text

AutoCAD SHX Text 484A

AutoCAD SHX Text

AutoCAD SHX Text

CEMETERY

AutoCAD SHX Text

PATRICK'S

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

NATURE PRESERVE

AutoCAD SHX Text

WATERFALL GLEN

AutoCAD SHX Text

NORTHERN ILLINOIS GAS CO. EASEMENT (36" PIPE IN 42" CASING)

AutoCAD SHX Text

CASS AVENUE

AutoCAD SHX Text

OLD BLUFF ROAD

AutoCAD SHX Text

AutoCAD SHX Text

NATURE PRESERVE

AutoCAD SHX Text

WATERFALL GLEN

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 389B

AutoCAD SHX Text

BLUFF ROAD

AutoCAD SHX Text

NORTHERN ILLINOIS GAS CO. EASEMENT (36" PIPE IN 42" CASING)

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

PARK

AutoCAD SHX Text

AVENUE

AutoCAD SHX Text

MERIDIAN ROAD

AutoCAD SHX Text

BLUFF ROAD

AutoCAD SHX Text

SOUTHWOOD DRIVE

AutoCAD SHX Text

MERIDIAN ROAD

AutoCAD SHX Text

KEARNEY ROAD

AutoCAD SHX Text

WATERTOWER ROAD

AutoCAD SHX Text

INNER CIRCLE

AutoCAD SHX Text

OUTER CIRCLE ROAD

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

COMPLEX

AutoCAD SHX Text 401,402

AutoCAD SHX Text

COMPLEX

AutoCAD SHX Text 314,315&316

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 544B

AutoCAD SHX Text 544A

AutoCAD SHX Text

EASTWOOD

AutoCAD SHX Text

AutoCAD SHX Text 531A

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

BLUFF ROAD

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

TECH ROAD

AutoCAD SHX Text

AutoCAD SHX Text

EASTWOOD DRIVE

AutoCAD SHX Text

RAILROAD DRIVE

AutoCAD SHX Text

EASTWOOD EXTENSION

AutoCAD SHX Text

ROAD

AutoCAD SHX Text

FREUND

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

ROCK ROAD

AutoCAD SHX Text 549A

AutoCAD SHX Text

AREA

AutoCAD SHX Text

STAGING

AutoCAD SHX Text C

AutoCAD SHX Text

OLD BLUFF ROAD

AutoCAD SHX Text

AutoCAD SHX Text 366A

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 363A

AutoCAD SHX Text 363B

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 375D

AutoCAD SHX Text

AutoCAD SHX Text 375A

AutoCAD SHX Text

AutoCAD SHX Text 391B

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 331A

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 206A

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

RAMP

AutoCAD SHX Text

GRASS

AutoCAD SHX Text

GRASS

AutoCAD SHX Text

5' WALK

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AREA

AutoCAD SHX Text

TRANSFORMER

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

TX-1

AutoCAD SHX Text

TX-2

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AREA

AutoCAD SHX Text

CLAY STORAGE

AutoCAD SHX Text

TOP SOIL STORAGE

AutoCAD SHX Text

AREA

AutoCAD SHX Text

CONCRETE ASPHALT RECYCLING

AutoCAD SHX Text

AREA

AutoCAD SHX Text

ELECTRICAL STORAGE

AutoCAD SHX Text

AREA

AutoCAD SHX Text

T130-TR1

AutoCAD SHX Text

AutoCAD SHX Text 400A

AutoCAD SHX Text

TRAILER

AutoCAD SHX Text

STORAGE

AutoCAD SHX Text

EQUIPMENT

AutoCAD SHX Text

RIGGERS

AutoCAD SHX Text

PAD

AutoCAD SHX Text

WETLAND

AutoCAD SHX Text

TOP SOIL STORAGE

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text

STORAGE

AutoCAD SHX Text

LOCKED

AutoCAD SHX Text x

AutoCAD SHX Text

DUMPSTER

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text

US EPA & DOE

AutoCAD SHX Text

TRAILERS

AutoCAD SHX Text

WETLAND

AutoCAD SHX Text

BERM AREA

AutoCAD SHX Text

BERM AREA

AutoCAD SHX Text

T-800-TR10

AutoCAD SHX Text

AutoCAD SHX Text

TR 8

AutoCAD SHX Text

TR 9

AutoCAD SHX Text T-800

AutoCAD SHX Text

TR10

AutoCAD SHX Text

TR11

AutoCAD SHX Text

AutoCAD SHX Text

SHED

AutoCAD SHX Text

WEIGH STATION

AutoCAD SHX Text 541A

AutoCAD SHX Text

T333-TR1

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

WETLAND

AutoCAD SHX Text

ROCK ROAD

AutoCAD SHX Text

NORTHERN ILLINOIS GAS CO. EASEMENT

AutoCAD SHX Text

NORTHERN ILLINOIS GAS CO. EASEMENT

AutoCAD SHX Text

NORTHERN ILLINOIS GAS CO. EASEMENT

AutoCAD SHX Text

NORTHERN ILLINOIS GAS CO. EASEMENT

AutoCAD SHX Text

NORTHERN ILLINOIS GAS CO. EASEMENT

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text A/B

AutoCAD SHX Text G

AutoCAD SHX Text

AutoCAD SHX Text

TRAILER

AutoCAD SHX Text

COOLING

AutoCAD SHX Text

TOWER

AutoCAD SHX Text 318B

AutoCAD SHX Text

BLUFF ROAD

AutoCAD SHX Text

AutoCAD SHX Text

ANTENNAE

AutoCAD SHX Text

TOWER

AutoCAD SHX Text

ANTENNAE

AutoCAD SHX Text

TOWER

AutoCAD SHX Text

ANTENNAE

AutoCAD SHX Text

TOWER

AutoCAD SHX Text 042B

AutoCAD SHX Text 042A

AutoCAD SHX Text 541B

AutoCAD SHX Text

DIESEL GENERATOR

AutoCAD SHX Text

500KW

AutoCAD SHX Text 541C

AutoCAD SHX Text

T390 TR1

AutoCAD SHX Text

T390 TR2

AutoCAD SHX Text

WIND TURBINE

AutoCAD SHX Text

SOLAR ARRAY

AutoCAD SHX Text

H2 TRAILER T-205-TR1

AutoCAD SHX Text

COOLING TOWER

AutoCAD SHX Text

CO STORAGE

AutoCAD SHX Text

H2 STORAGE

AutoCAD SHX Text

CO2 STORAGE

AutoCAD SHX Text

N2 STORAGE

AutoCAD SHX Text

C3H8 STORAGE

AutoCAD SHX Text E

AutoCAD SHX Text E

AutoCAD SHX Text E

AutoCAD SHX Text E

AutoCAD SHX Text E

AutoCAD SHX Text T

AutoCAD SHX Text T

AutoCAD SHX Text

T378-TR

AutoCAD SHX Text

T378-TR

AutoCAD SHX Text

T378-TR

AutoCAD SHX Text

TRAILER

AutoCAD SHX Text

TRAILER

AutoCAD SHX Text

TRAILER

AutoCAD SHX Text

TRAILER

AutoCAD SHX Text

TRAILER

AutoCAD SHX Text

TRAILER

AutoCAD SHX Text

TRAILER

AutoCAD SHX Text

TRAILER

AutoCAD SHX Text 13.2kv

AutoCAD SHX Text

ATS

AutoCAD SHX Text

TR-2

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

T-800-TR17

AutoCAD SHX Text

T-800-TR18

AutoCAD SHX Text T12

AutoCAD SHX Text H3

AutoCAD SHX Text H2

AutoCAD SHX Text H1

AutoCAD SHX Text X0

AutoCAD SHX Text T-1

AutoCAD SHX Text T12

AutoCAD SHX Text H3

AutoCAD SHX Text H2

AutoCAD SHX Text H1

AutoCAD SHX Text X0

AutoCAD SHX Text T-2

AutoCAD SHX Text

GCB 152

AutoCAD SHX Text

LINE A3

AutoCAD SHX Text

LINE A4

AutoCAD SHX Text

GCB 252

AutoCAD SHX Text

SWGR. BLDG.

AutoCAD SHX Text H3

AutoCAD SHX Text H2

AutoCAD SHX Text H1

AutoCAD SHX Text X0

AutoCAD SHX Text T12

AutoCAD SHX Text Y9

AutoCAD SHX Text Y8

AutoCAD SHX Text Z9

AutoCAD SHX Text Z8

AutoCAD SHX Text

20'-0" DRIVE GATE (TYP.)

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

TX-1

AutoCAD SHX Text

TX-2

AutoCAD SHX Text 400A

AutoCAD SHX Text

AutoCAD SHX Text

BLUFF ROAD

AutoCAD SHX Text

AutoCAD SHX Text

DRAWING TITLE

AutoCAD SHX Text

CHECKED

AutoCAD SHX Text

DESIGNED

AutoCAD SHX Text

DRAWN

AutoCAD SHX Text

APPROVED

AutoCAD SHX Text

FACILITY DOCUMENT NO.

AutoCAD SHX Text

CADD NUMBER

AutoCAD SHX Text

FACILITY NUMBER

AutoCAD SHX Text

PROJECT TITLE

AutoCAD SHX Text

REV. NO.

AutoCAD SHX Text

DESCRIPTION

AutoCAD SHX Text

BY

AutoCAD SHX Text

APVD

AutoCAD SHX Text

DATE

AutoCAD SHX Text

REV. NO.

AutoCAD SHX Text

DRAWING NO.

AutoCAD SHX Text

J420-104-W-G001.DWG

AutoCAD SHX Text B420

AutoCAD SHX Text

SJD

AutoCAD SHX Text

SJD

AutoCAD SHX Text

SSC

AutoCAD SHX Text

JET

AutoCAD SHX Text A

AutoCAD SHX Text

PRE-PURCHASE REVIEW

AutoCAD SHX Text

SJD

AutoCAD SHX Text

SSC

AutoCAD SHX Text 06-10-24

AutoCAD SHX Text B

AutoCAD SHX Text

ISSUED FOR PREPURCHASE

AutoCAD SHX Text

SJD

AutoCAD SHX Text

SSC

AutoCAD SHX Text 09-03-24

AutoCAD SHX Text N

AutoCAD SHX Text N

WARNING

IF PLAN IS ENLARGED OR REDUCED,

GRAPHIC SCALE SHALL BE USED.

J420-104-W- E001 0

BUILDING 420

SOLID STATE AMPLIFIER

ELECTRICAL SYMBOLS,

ABBREVIATIONS,

AND GENERAL NOTES

Grumman/Butkus Associates Energy Efficiency Consultants and Sustainable Design Engineers

820 Davis St, Ste 300 Evanston, Illinois 60201 4446 847 328.3555 www.grummanbutkus.com Copyright © 2023 Grumman/Butkus Associates Illinois Registration #184-000926 GBA Project: P23-0858-00

DESCRIPTIONDESIGNATION

EXISTING

NEW WORK

DESCRIPTIONSYMBOL

ER EXISTING ELECTRICAL EQUIPMENT OR OUTLET TO REMAIN

EXISTING ELECTRICAL EQUIPMENT OR OUTLET TO BE REMOVED

RELOCATED AND JUNCTION BOX REMOVED OR CAPPED AS REQUIRED.RL

NL EXISTING ELECTRICAL EQUIPMENT OR OUTLET RELOCATED (NEW

LOCATION)

RE EXISTING ELECTRICAL EQUIPMENT OR OUTLET TO BE REMOVED

EC EXISTING ELECTRICAL EQUIPMENT OR OUTLET TO BE REMOVED AND

JUNCTION BOX CAPPED AS REQUIRED

NR NEW ELECTRICAL EQUIPMENT INSTALLED OVER EXISTING OUTLET

EA EXISTING ELECTRICAL EQUIPMENT OR OUTLET TO BE ABANDONED

EM EXISTING ELECTRICAL EQUIPMENT OR OUTLET TO BE MODIFIED

AC ALTERNATING CURRENT

AF AMPERE FRAME, AMPERE FUSE

AFF ABOVE FINISHED FLOOR

AM AMP METER

AMP AMPERE

AT AMPERE TRIP

ATS AUTOMATIC TRANSFER SWITCH

AWG AMERICAN WIRING GUAGE

BP BRANCH CIRCUIT PANEL

BKR BREAKER

C CONDUIT

CATV CABLE ACCESSED TELEVISION

C/B CIRCUIT BREAKER

CKT CIRCUIT

CT CURRENT TRANSFORMER

CU COPPER

DC DIRECT CURRENT

DISC DISCONNECT

DN DOWN

DWG DRAWING

EM EMERGENCY

EMI ELECTROMAGNETIC INTERFERENCE

EMT ELECTRIC METALLIC TUBING

EPO EMERGENCY POWER OFF

E EXISTING

F FUSE

FA FIRE ALARM

FAAP FIRE ALARM ANNUNCIATOR PANEL

FACP FIRE ALARM CONTROL PANEL

FLA FULL LOAD AMPERES

FLR FLOOR

FMC FLEXIBLE METAL CONDUIT

GEN GENERATOR

GF GROUND FAULT

GFCI GROUND FAULT CIRCUIT INTERRUPTER

G GROUND

HID HIGH INTENSITY DISCHARGE

HOA HAND OFF AUTO

HP HORSEPOWER

HPS HIGH PRESSURE SODIUM

HZ HERTZ (CYCLE)

IC INTERRUPTING CAPACITY

IEEE INSTITUTE OF ELECTRICAL AND

ELECTRONICS ENGINEERS

IG ISOLATED GROUND

IMC INTERMEDIATE METAL CONDUIT

JB JUNCTION BOX

KV KILOVOLT

KVA KILOVOLT-AMPERE

KW KILOWATT

LFMC LIQUIDTIGHT FLEXIBLE METAL CONDUIT

LPS LOW PRESSURE SODIUM

LP LIGHTING PANEL

LRA LOCKED ROTOR AMPERES

LRP LIGHTING RELAY PANEL

LTG LIGHTING

MCB MAIN CIRCUIT BREAKER

MCC MOTOR CONTROL CENTER

MLO MAIN LUGS ONLY

MIN MINIMUM

N/A NOT APPLICABLE

NATS NON-AUTOMATIC TRANSFER SWITCH

NC NORMALLY CLOSED

NEC NATIONAL ELECTRIC CODE

NEMA NATIONAL ELECTRICAL

MANUFACTURERS ASSOCIATION

NETA NATIONAL ELECTRICAL TESTING

ASSOCIATION

NF NON-FUSED

NO NORMALLY OPEN

OC OVER CURRENT

OSHA OCCUPATIONAL SAFETY AND HEALTH

ADMINISTRATION

P POLE

PB PULL BOX

PDU POWER DISTRIBUTION UNIT

PE PROFESSIONAL ENGINEER

PF POWER FACTOR

PH PHASE

PM POWER MONITORING DEVICE

PNL PANELBOARD

PP POWER PANEL

PT POTENTIAL TRANSFORMER

PVC POLYVINYL CHLORIDE

RFI RADIO FREQUENCY INTERFERENCE

RGS RIGID GALVANIZED STEEL CONDUIT

RMC RIGID METAL CONDUIT

RMS ROOT MEAN SQUARE

RP RECEPTACLE PANEL

SCA SHORT CIRCUIT AMPERES

SW SWITCH

SWBD SWITCHBOARD

T TELEPHONE

THD TOTAL HARMONIC DISTORTION

TIA TELECOMMUNICATIONS INDUSTRY

ASSOCIATION

TV TELEVISION

TVSS TRANSIENT VOLTAGE SURGE

SUPPRESSION

UH UNIT HEATER

UL UNDERWRITERS LABORATORIES

UNO UNLESS NOTED OTHERWISE

UPS UNINTERRUPTIBLE POWER SUPPLY

V VOLTAGE

VA VOLT-AMPERE

VFD VARIABLE FREQUENCY DRIVE

VM VOLT METER

W WATT

WP WEATHERPROOF

WM WATT METER

XFMR TRANSFORMER

DESCRIPTIONDESIGNATION

AMMETERA

AUTOMATIC TRANSFER SWITCHN

L

E

BATTERY

BRANCH CIRCUIT PANELBOARD

XX

XX

CONTACT - NORMALLY CLOSEDNC

NORMALLY OPENED CONTACTNO

GROUND FAULT PROTECTIVE DEVICEGF

GROUND

POWER METERPM

SURGE PROTECTION DEVICE (TVSS)

X=A,B,C

SPD

X

THERMAL OVERLOAD

CURRENT TRANSFORMER

CT

POTENTIAL TRANSFORMER

PT

VOLTMETERV

PROTECTIVE RELAY

X=PROTECTIVE DEVICE NUMBER

EX. 59=OVERVOLTAGE

X

SWITCH

X=SWITCH AMPEREX

FUSED SWITCH

X=SWITCH AMPERE

Y=FUSE AMPERE OR TYPEY

X

FUSE

Y=FUSE AMPERE OR TYPEY

CIRCUIT BREAKER - MOLDED CASE

X=AMPERE FRAME (AF)

Y=AMPERE TRIP (AT)Y

X

CIRCUIT BREAKER - DRAWOUT

X=AMPERE FRAME (AF)

Y=AMPERE TRIP (AT)

X Y

GENERATORG

TRANSFORMER

X=KVA RATING

Y=PRIMARY VOLTAGE

Z=SECONDARY VOLTAGE (E.G. 208Y/120V)

Z

X Y T

DESCRIPTIONDESIGNATION

DUPLEX RECEPTACLE (WALL MOUNTED)

+18" AFF UNO

DUPLEX RECEPTACLE (WALL MOUNTED)

ABOVE COUNTER HEIGHT

DOUBLE DUPLEX (WALL MOUNTED)

+18" AFF UNO

GROUND FAULT INTERRUPTER DUPLEX RECEPTACLE (WALL

MOUNTED)

+18" AFF UNO

GFI

SINGLE SPECIAL OUTLET - SEE PLANS FOR NEMA

CONFIGURATION

DISCONNECT SWITCH (NON-FUSED)

FUSED DISCONNECT SWITCHF

BREAKER DISCONNECTB

EQUIPMENT TAG

SEE EQUIPMENT SCHEDULEY

X

HANDHOLEHH

TRANSFORMER

T=KVAT

VARIABLE FREQUENCY DRIVEVFD

EMERGENCY POWER OFF STATION.

"K" INDICATES KEYED OPERATIONK

EPO

BRANCH CIRCUIT PANELBOARDLP-X

POWER DISTRIBUTION PANELBOARDDP-X

CEILING MOUNTED JUNCTION BOXJ

WALL MOUNTED JUNCTION BOXJ

COMBINATION MOTOR STARTER AND DISCONNECT SWITCH

1. CODES

THE WORK SHALL COMPLY WITH ALL APPLICABLE LOCAL, MUNICIPAL, AND NATIONAL

CODES. WHERE THE CONSTRUCTION DOCUMENTS INDICATE MORE RESTRICTIVE

REQUIREMENTS THE CONSTRUCTION DOCUMENTS SHALL GOVERN. HOWEVER, THE

CONSTRUCTION DOCUMENTS SHALL NOT BE INTERPRETED AS AUTHORITY TO VIOLATE

ANY CODE OR REGULATION.

2. DRAWINGS AND SPECIFICATIONS

THE CONTRACTOR SHALL BE RESPONSIBLE FOR READING AND COMPLYING WITH BOTH

THE DRAWINGS AND SPECIFICATIONS. IN THE EVENT OF A CONFLICT OR

INCONSISTENCY BETWEEN THE DRAWINGS, NOTES, SPECIFICATIONS, OR CODES, THE

REFERENCE WHICH PROVIDES THE MORE COMPLETE OR HIGHER STANDARD SHALL

PREVAIL.

3. INTERPRETATION OF THE DOCUMENTS

CAREFULLY COMPARE THE DRAWINGS AND SPECIFICATIONS, CHECKING

MEASUREMENTS AND CONDITIONS UNDER WHICH THIS INSTALLATION IS TO BE MADE.

FOR CLARIFICATION BETWEEN VARIOUS DRAWINGS, BETWEEN DRAWINGS OR

SPECIFICATION, OR BETWEEN SECTIONS OF THE SPECIFICATION, THE MATTER SHALL BE

REFERRED TO THE ENGINEER BEFORE ANY WORK IS EXECUTED. THE CONTRACTOR

SHALL STATE IN THEIR PROPOSAL ANY EXCEPTIONS NECESSARY TO MAKE THIS A

COMPLETE, READY TO USE INSTALLATION. IF NOT STATED IN THE PROPOSAL, IT WILL

NOT BE CONSIDERED EXTRA.

4. ELECTRICAL DRAWINGS

THE ELECTRICAL DRAWINGS ARE DIAGRAMMATIC AND SHALL NOT BE SCALED. THE

CONTRACTOR SHALL DETERMINE THE EXACT LOCATION OF ALL DOORS, WALLS,

FURNITURE, EQUIPMENT, ETC. THE LOCATION OF RACEWAY SYSTEM COMPONENTS IS

SCHEMATIC. THE EXACT LOCATION OF RACEWAY SYSTEM COMPONENTS SHALL BE

DETERMINED BY THE CONTRACTOR IN THE FIELD. THE CONTRACTOR SHALL CONFIRM

THE DIMENSIONS OF THE ACTUAL EQUIPMENT TO BE SUPPLIED FOR THIS PROJECT, AND

VERIFY CLEARANCES AND ROUGH-INS PRIOR TO STARTING WORK.

5. SITE EXAMINATION

BEFORE SUBMITTING A BID, THE CONTRACTOR SHALL VISIT THE SITE, EXAMINE THE

PREMISES, AND MAKE A THOROUGH SURVEY OF THE EXISTING CONDITIONS. THE

SUBMISSION OF A PROPOSAL WILL BE CONSTRUED AS EVIDENCE THAT SUCH AN

EXAMINATION HAS BEEN MADE. NO CONSIDERATION OR ALLOWANCE WILL BE GRANTED

FOR FAILURE TO VISIT THE SITE OR FOR LATER CLAIMS FOR LABOR, EQUIPMENT,

MATERIALS REQUIRED, OR FOR DIFFICULTIES ENCOUNTERED WHICH COULD HAVE BEEN

FORESEEN HAD SUCH AN SITE EXAMINATION BEEN MADE.

6. COORDINATION WITH OTHER TRADES

THE ELECTRICAL CONTRACTOR SHALL OBTAIN A COMPLETE SET OF ARCHITECTURAL

AND ENGINEERING DOCUMENTS AND COORDINATE WITH MECHANICAL, PLUMBING,

ARCHITECTURAL, AND OTHER TRADES FOR EXACT DIMENSIONS, CLEARANCES,

ROUGH-IN LOCATIONS, AND OTHER ADDITIONAL SCOPES OF WORK THAT MAY NOT BE

SHOWN ON THE ELECTRICAL PLANS. THE ELECTRICAL CONTRACTOR SHALL BE

RESPONSIBLE FOR ALL 120 VOLT (AND HIGHER) AC POWER TO OTHER TRADES

EQUIPMENT AND HARDWARE. THIS SHALL INCLUDE, BUT NOT BE LIMITED TO, CONTROLS,

FIRE AND SECURITY SYSTEMS, MOTORIZED DOORS, DAMPERS, LIFTS, AND OTHER

SYSTEMS. UNLESS SPECIFICALLY NOTED OTHERWISE ON THE ELECTRICAL PLANS, THE

ELECTRICAL CONTRACTOR SHALL FURNISH ALL SAFETY DISCONNECT SWITCHES TO

MECHANICAL EQUIPMENT.

7. PERMITS, APPLICATIONS AND RELEASES

THE CONTRACTOR SHALL OBTAIN AND PAY FOR ALL PERMITS INSPECTIONS,

APPLICATIONS, RELEASES AND FEES REQUIRED BY LOCAL, STATE AND FEDERAL

AGENCIES FOR THE EXECUTION OF THIS WORK. SCHEDULING OF ALL REQUIRED

INSPECTIONS SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR.

8. FIRE STOPPING

ALL PENETRATIONS IN WALL, FLOOR OR CEILINGS SHALL BE SUITABLY CLOSED UP AND

SEALED WITH AN INTUMESCENT FIRE STOPPING COMPOUND LISTED IN THE MOST

RECENT FACTORY MUTUAL RESEARCH CORPORATION (FMRC) APPROVAL GUIDE. FIRE

STOPPING PRODUCTS SHALL BE MANUFACTURED BY 3M COMPANY OR APPROVED

EQUAL.

9. PAINTING

ALL NEWLY INSTALLED EXPOSED PIPING SHALL BE PAINTED TO MATCH THE EXISTING

ADJACENT WALL OR CEILING SURFACE.

10. OWNER FURNISHED EQUIPMENT

EQUIPMENT THAT WILL BE FURNISHED BY THE OWNER WILL BE INDICATED ON A

SEPARATE SPECIFIED SCHEDULE. THE CONTRACTOR SHALL COORDINATE WITH THE

OWNER FOR DELIVERY SCHEDULES. THE CONTRACTOR IS TO ASSUME THAT ON SITE

STORAGE MAY NOT BE AVAILABLE WHEN COORDINATING DELIVERY OF EQUIPMENT. THE

CONTRACTOR, IN COORDINATION WITH THE OWNER'S REPRESENTATIVE, WILL INSPECT

THE DELIVERY FOR ACCURACY AND SHIPMENT DAMAGE AND ACCEPTING THE

EQUIPMENT. THE CONTRACTOR SHALL BE RESPONSIBLE TO STORE, PROTECT AND

ULTIMATELY INSTALL THE EQUIPMENT.

11. ELECTRICAL SERVICE DISRUPTIONS

ALL WORK WHICH EXPOSES ACTIVE BUS REQUIRES A WRITTEN NOTIFICATION TO THE

OWNER WHICH WILL OUTLINE THE METHOD OF PROCEDURE FOR THE WORK. THE

CONTRACTOR SHALL PROVIDE A MINIMUM OF 5 DAYS NOTICE TO THE OWNER BEFORE

WORKING ON ANY ENERGIZED ELECTRICAL SYSTEM. ALL POWER DISRUPTION SHALL

OCCUR AT TIMES AND OF DURATIONS ACCEPTABLE TO THE OWNER.

12. EQUIPMENT

ALL MATERIALS AND EQUIPMENT USED IN THIS INSTALLATION SHALL BE NEW, AND HAVE

THE APPROPRIATE UL LISTING AND LABEL.

13. MISCELLANEOUS SUPPORTING MEMBERS

ALL ANGLES CHANNELS, AND OTHER MISCELLANEOUS STEEL, BOLTS, RODS, ETC.

REQUIRED TO SUPPORT LIGHT FIXTURE, CONDUIT, RACEWAY, LADDER TRAY, OR OTHER

ELECTRICAL EQUIPMENT OR DEVICES SHALL BE FURNISHED AND INSTALLED BY THE

CONTRACTOR.

14. PANELBOARDS

ALL PANELBOARDS SHALL BE PROVIDED WITH TYPEWRITTEN DIRECTORIES. SEE PANEL

SCHEDULES ON THE DRAWINGS AND SPECIFICATIONS FOR COMPLETE IDENTIFICATION

AND LABELING REQUIREMENTS.

15. SAFETY

THE CONTRACTOR SHALL TAKE ALL STEPS NECESSARY TO ENSURE THE SAFETY OF

THE OWNERS EMPLOYEES, BUILDING EMPLOYEES AND GUESTS, AS WELL AS THEIR OWN

FORCES, BY ADEQUATELY PROTECTING ANY EXPOSED LIVE CONDUCTORS, OR DEVICES

THROUGHOUT THE COURSE OF THIS WORK.

COMPLY WITH NFPA 241 FOR SAFEGUARDING DURING CONSTRUCTION AND ALTERATION

OPERATIONS. IN ADDITION, ANY OPENINGS IN FIRE RATED SEPARATIONS BETWEEN

OCCUPIED AND UNOCCUPIED (OR OPERATIONAL AND NON-OPERATIONAL) AREAS SHALL

BE SEALED AT THE END OF EACH WORK DAY WITH AN APPROPRIATE FIRE RATED

ENCLOSURE OR SEALANT. DO NOT COMPROMISE EXISTING SECURITY OR FIRE ALARM

SYSTEMS SERVING THE OCCUPIED OR OPERATIONAL AREAS.

16. EQUIPMENT CONNECTIONS

PROVIDE FINAL ELECTRICAL CONNECTIONS TO ALL EQUIPMENT FURNISHED UNDER

OTHER TRADES AND FOR ALL OWNER FURNISHED EQUIPMENT. PROVIDE A FLEXIBLE

LIQUID TIGHT CONNECTION TO ALL VIBRATION PRODUCING EQUIPMENT.

17. INTERFERENCE WITH OCCUPANCY

THE PRESENT BUILDING IS OCCUPIED AND WILL CONTINUE TO BE DURING THE

PROGRESS OF THIS WORK. IT IS IMPERATIVE, THEREFORE, THAT THE WORK COVERED

BY THESE DOCUMENTS BE EXECUTED WITH A MINIMUM OF INCONVENIENCE TO THE

BUILDING PERSONNEL, AND OTHER TENANTS.

18. TEMPORARY REQUIREMENTS

PROVIDE TEMPORARY LIGHTING, POWER, AND FIRE ALARM COMPONENTS AS REQUIRED

IN AREAS UNDERGOING WORK DURING CONSTRUCTION.

FURNISH AND INSTALL ONE OSHA APPROVED PIGTAIL SOCKET WITH 150-WATT LAMP

FOR EVERY 500 SQUARE FEET OF FLOOR SPACE AND A MINIMUM 1 PER ROOM. THE

TEMPORARY LIGHTING SHALL BE LEFT IN PLACE UNTIL PERMANENT LIGHTING IS

COMPLETELY OPERATIONAL.

FURNISH AND INSTALL POWER OUTLETS TO A TOTAL ONE FOR EVERY 2000 SQUARE

FEET OR PART THEREOF OF FLOOR AREA AND THESE SHALL BE 15 AMP, SINGLE PHASE

RECEPTACLES FOR EITHER 110 OR 220 VOLTS AS DIRECTED BY THE GENERAL

CONTRACTOR. COORDINATE FOR ADDITIONAL TEMPORARY POWER REQUIREMENTS

WITH OTHER TRADES AND PROVIDE AN ADEQUATE INSTALLATION.

FURNISH AND INSTALL AN APPROVED TEMPORARY FIRE ALARM SYSTEM AS REQUIRED

BY LOCAL CODES AND AUTHORITY HAVING JURISDICTION.

ALL TEMPORARY ELECTRICAL EQUIPMENT SHALL BE REMOVED BEFORE THE AREA

CEILINGS ARE INSTALLED.

19. CABLING

BRANCH CIRCUITS TO RECEPTACLES, LIGHTING AND MISC. SMALL LOADS (15 OR 20 AMP

CIRCUITS), UNLESS SPECIFICALLY NOTED OTHERWISE, SHALL BE 2#12, 1#12G. - 3/4" C.

SEE NOTE BELOW FOR ADDITIONAL REQUIREMENTS. MINIMUM SIZE WIRE SHALL BE #12

AWG AND MINIMUM SIZE CONDUIT SHALL BE 3/4" TRADE SIZE.

20. CABLING SIZES

BRANCH CIRCUIT CABLE SIZING SHALL BE BASED ON THE VALUES INDICATED BELOW:

A. 120/208V CABLING FROM PANEL TO THE ELECTRICAL LOAD SHALL BE ADJUSTED

AS FOLLOWS UNLESS SPECIFICALLY NOTED OTHERWISE:

0' - 65' #12 AWG MINIMUM COPPER

66 - 100' #10 AWG MINIMUM COPPER

101' - 160' #8 AWG MINIMUM COPPER

161' - 250' #6 AWG MINIMUM COPPER

B. 277/480V CABLING FROM PANEL TO THE ELECTRICAL LOAD SHALL BE ADJUSTED

AS FOLLOWS UNLESS SPECIFICALLY NOTED OTHERWISE:

0' - 150' #12 AWG MINIMUM

150' - 250' #10 AWG MINIMUM

250' - 300' #8 AWG MINIMUM

22. SPECIAL LUG REQUIREMENTS

ANY CABLE WHICH TERMINATES DIRECTLY ON TO A BUS BAR SHALL BE 2 BOLT LONG

BARREL TYPE WITH INSPECTION HOLES PRODUCED WITH NON FLASHING TYPE DYES AS

MANUFACTURED BY THOMAS AND BETTS OR APPROVED EQUAL, MINIMUM 10 TONS OF

COMPRESSION, HEX CRIMP. THE USE OF HEAT SHRINK TUBING IS EXPLICITLY

FORBIDDEN. THERE SHALL BE NO "SHINERS" AT THE LUGS.

ELECTRICAL GENERAL NOTES

1. EXAMINATION

A. THE CONTRACTOR SHALL VISIT THE SITE AND EXAMINE AREAS UNDER WHICH

THE WORK IS TO BE PERFORMED AND NOTIFY THE OWNER IN WRITING OF ANY

CONDITIONS DETRIMENTAL TO THE PROPER AND TIMELY COMPLETION OF THE

WORK. CONTRACTOR SHALL NOT PROCEED WITH WORK UNTIL SATISFACTORY

CONDITIONS HAVE BEEN CORRECTED.

B. VERIFY FIELD MEASUREMENTS AND CIRCUITING ARRANGEMENTS FOR DEVICES

SHOWN ON DRAWINGS.

C. DEMOLITION DRAWINGS ARE BASED ON CASUAL FIELD OBSERVATION AND

EXISTING RECORD DRAWINGS. REPORT DISCREPANCIES TO OWNER BEFORE

DISTURBING EXISTING INSTALLATION.

D. COMMENCEMENT OF DEMOLITION MEANS ACCEPTANCE OF EXISTING

CONDITIONS.

2. PREPARATION

A. DISCONNECT ELECTRICAL SYSTEMS IN WALLS, FLOORS, AND CEILINGS

SCHEDULED FOR REMOVAL.

B. COORDINATE ELECTRICAL SHUTDOWNS ONE WEEK IN ADVANCE WITH ARGONNE

NATIONAL LABORATORY PERSONNEL.

C. PROVIDE TEMPORARY WIRING AND CONNECTIONS TO MAINTAIN EXISTING

SYSTEMS IN SERVICE DURING CONSTRUCTION. EXPERIENCED PERSONNEL

SHALL BE USED WHEN WORKING ON ENERGIZED EQUIPMENT OR CIRCUITS.

D. EXISTING ELECTRICAL SERVICE: MAINTAIN EXISTING ELECTRICAL SYSTEM IN

SERVICE UNTIL NEW SERVICE IS COMPLETE AND READY FOR SERVICE. DISABLE

ELECTRICAL SYSTEM ONLY TO MAKE SWITCHOVERS AND CONNECTIONS.

MINIMIZE OUTAGE DURATION. MAKE TEMPORARY CONNECTIONS TO MAINTAIN

ELECTRICAL SERVICE IN AREAS ADJACENT TO WORK AREA.

E. MAINTAIN EXISTING FIRE ALARM SYSTEM IN SERVICE UNTIL NEW SYSTEM IS

ACCEPTED. DISABLE SYSTEM ONLY TO MAKE SWITCHOVERS AND CONNECTIONS.

WHERE FIRE ALARM DEVICES MUST BE REMOVED TO ACCOMMODATE THE

REMOVAL OF WALLS, NOTIFY THE OWNER AND ENGINEER IN WRITING WITH

LOCATIONS OF DEVICES.

3. DEMOLITION AND EXTENSION OF EXISTING ELECTRICAL WORK.

A. REMOVE, RELOCATE, AND EXTEND EXISTING ELECTRICAL WORK AS INDICATED

ON THE DRAWINGS AND AS NOTED HEREIN.

B. REMOVE ABANDONED WIRING BACK TO SOURCE OF SUPPLY.

C. WHERE SOURCE OF SUPPLY IS A PANELBOARD, RE-LABEL PROTECTIVE DEVICE

AS "SPARE". AFTER DEMOLITION IS COMPLETE, SUBMIT REVISED PANELBOARD

SCHEDULES INDICATING "SPARES" TO OWNER AND ENGINEER.

D. REMOVE EXPOSED ABANDONED CONDUIT ABOVE ACCESSIBLE CEILING FINISHES.

CUT CONDUIT FLUSH WITH WALLS AND FLOORS, AND PATCH SURFACES.

E. DISCONNECT AND REMOVE ABANDONED OUTLETS AND ASSOCIATED DEVICES.

F. DISCONNECT AND REMOVE ABANDONED PANELBOARDS AND DISTRIBUTION

EQUIPMENT.

G. DISCONNECT AND REMOVE ELECTRICAL DEVICES AND EQUIPMENT THAT IS NO

LONGER IN USE.

H. DISCONNECT AND REMOVE ABANDONED LUMINARIES. REMOVE BRACKETS,

STEMS, HANGERS, AND ALL OTHER ACCESSORIES.

I. REPAIR ADJACENT CONSTRUCTION AND FINISHES DAMAGED DURING

DEMOLITION AND EXTENSION OF WORK.

4. CLEANING, REPAIR, AND REPLACEMENT

A. GENERAL: CLEAN AND REPAIR EXISTING MATERIALS AND EQUIPMENT THAT WILL

REMAIN OR ARE TO BE REUSED.

B. PANELBOARDS: CLEAN EXPOSED SURFACES AND TIGHTEN ALL ELECTRICAL

CONNECTIONS. REPLACE DAMAGED CIRCUIT BREAKERS AND PROVIDE CLOSURE

PLATES FOR VACANT POSITIONS. PROVIDE TYPED SCHEDULES SHOWING

REVISED CIRCUITING INFORMATION.

C. LUMINAIRES: REMOVE EXISTING LUMINAIRES FOR CLEANING. USE MILD

DETERGENT TO CLEAN EXTERIOR AND INTERIOR SURFACES, RINSE CLEAN WITH

CLEAN WATER AND WIPE DRY. REPLACE EXISTING LAMPS AND BALLASTS WITH

NEW.

5. DISPOSAL

A. OWNER SHALL HAVE RIGHT TO RETAIN ANY EQUIPMENT OR MATERIALS THAT

HAVE BEEN DEMOLISHED PRIOR TO DISPOSAL OR REMOVAL FROM SITE.

B. ANY EQUIPMENT OR MATERIALS NOT WANTED BY THE OWNER SHALL BECOME

THE PROPERTY OF THE CONTRACTOR AND REMOVED FROM SITE.

C. CONTRACTOR SHALL COMPLY WITH ENVIRONMENTAL LAWS AND REGULATIONS

FOR DISPOSAL OF DEMOLISHED MATERIALS AND EQUIPMENT.

GENERAL NOTES FOR DEMOLITION

FO

R

PR

EP

UR

CH

AS

E

ON

LY

NO

T

FO

R

CO

NS

TR

UC

TI

ON

SHUNT TRIPST

BLOWN FUSE DETECTOR AND RELAYBFD

AutoCAD SHX Text

DRAWING TITLE

AutoCAD SHX Text

CHECKED

AutoCAD SHX Text

DESIGNED

AutoCAD SHX Text

DRAWN

AutoCAD SHX Text

APPROVED

AutoCAD SHX Text

FACILITY DOCUMENT NO.

AutoCAD SHX Text

CADD NUMBER

AutoCAD SHX Text

FACILITY NUMBER

AutoCAD SHX Text

PROJECT TITLE

AutoCAD SHX Text

REV. NO.

AutoCAD SHX Text

DESCRIPTION

AutoCAD SHX Text

BY

AutoCAD SHX Text

APVD

AutoCAD SHX Text

DATE

AutoCAD SHX Text

REV. NO.

AutoCAD SHX Text

DRAWING NO.

AutoCAD SHX Text

J420-104-W-E001.DWG

AutoCAD SHX Text B420

AutoCAD SHX Text

SJD

AutoCAD SHX Text

SJD

AutoCAD SHX Text

SSC

AutoCAD SHX Text

JET

AutoCAD SHX Text A

AutoCAD SHX Text

PRE-PURCHASE REVIEW

AutoCAD SHX Text

SJD

AutoCAD SHX Text

SSC

AutoCAD SHX Text 06-10-24

AutoCAD SHX Text B

AutoCAD SHX Text

ISSUED FOR PREPURCHASE

AutoCAD SHX Text

SJD

AutoCAD SHX Text

SSC

AutoCAD SHX Text 09-03-24

AutoCAD SHX Text

LINETYPE LEGEND

AutoCAD SHX Text

DEMOLITION SYMBOLS

AutoCAD SHX Text

ELECTRICAL ABBREVIATIONS

AutoCAD SHX Text

ELECTRICAL RISER DIAGRAM SYMBOLS

POWER SYMBOLS

X X X X X X X

X X

X X

X X

X X

X X

XXXXXXX

X X

X X

X X

X X

X X

X X

X X

X X

X

X X

X X

X X

X

X X

X X

X X

X X

X X

X X

X X

X X

X X

X X

XXXXXXX

X X

X X

X X

X X

X X

X X

X X

X X

X

X X

X X

X X

X X

X X

X X

X X

X X

X

X X

X X

X X

X X

X X

X X

X X

X X

X X

X X

XXXXXXX

(ER)

(ER)

(ER)

(ER)

(ER)

(ER)

(ER)

(ER)

(ER)

(ER) (ER) (ER)

(ER)

(ER) (ER)

(ER)

(ER)

RF/EXTRACTION BUILDING MAIN

13.2kV LOAD INTERRUPTER SWITCHGEAR

J

(ER)

J TRPC-12: #2,4

TRPC-12: #2,4

EXISTING 15kV LOAD INTERRUPTER SWITCH

EXISTING THROAT CONNECTION

(CABLE DUCT SHALL REMAIN FOR

USE WITH NEW TRANSFORMER)

NEW NEMA-3R SWITCHBOARD MSB-SSA-1

TO BE INCLUDED IN THIS PREPURCHASE

EXISTING UNDERGROUND CABLE

AND CONDUIT SHALL REMAIN

GRC CONDUIT ABOVE GRADE

TO TRANSFORMER PER SINGLE

LINE DIAGRAM E401

NEW MEDIUM VOLTAGE TRANSFORMER TO

BE INCLUDED IN THIS PREPURCHASE

WARNING

IF PLAN IS ENLARGED OR REDUCED,

GRAPHIC SCALE SHALL BE USED.

J420-104-W- E100 0

BUILDING 420

S36 POWER & COOLING FOR SSA

ELECTRICAL

BUILDING EXTERIOR

NEW WORK

Grumman/Butkus Associates Energy Efficiency Consultants and Sustainable Design Engineers

820 Davis St, Ste 300 Evanston, Illinois 60201 4446 847 328.3555 www.grummanbutkus.com Copyright © 2023 Grumman/Butkus Associates Illinois Registration #184-000926 GBA Project: P23-0858-00

1 ELECTRICAL BUILDING EXTERIOR - NEW WORK

1/8"=1'-0"

20 4 8 16

1. CONTRACTOR TO PROVIDE AND INSTALL NEW FUSES IN EXISTING DISCONNECT SWITCH

TO FEED NEW TRANSFORMER. SEE SINGLE LINE DIAGRAM FOR FUSE REQUIREMENTS.

2. CONTRACTOR SHALL CONNECT EXISTING 208V CIRCUITS RETAINED FROM DEMOLITION

FOR QUALITROL FAN CONTROLLER AND FOR TRANSFORMER SPACE HEATERS.

CONTRACTOR SHALL CONNECT EXISTING RS-485 COMMUNICATION CIRCUIT FOR

QUALITROL TEMPERATURE MONITORING TO NEW TRANSFORMER TEMPERATURE

MONITORING DEVICE. ANL WILL CONNECT EXISTING CABLE INSIDE LABORATORY SPACE

TO NEW EXPERIMENT PLC/HMI FOR REMOTE MONITORING AND DATA DISPLAY.

3. CONTRACTOR SHALL SET, INSTALL, AND WIRE OWNER'S PREPURCHASED 2000kVA DRY

TYPE MEDIUM VOLTAGE TRANSFORMER. PROVIDE ALL CABLE TERMINATIONS AND

GROUNDING. HIGH VOLTAGE ENTRY LOCATION ON NEW TRANSFORMER TO MATCH

LOCATION FROM EXISTING TRANSFORMER. SEE DETAIL #1 ON SHEET E601 FOR EXISTING

TRANSFORMER DETAIL

4. CONTRACTOR SHALL SET AND WIRE OWNER'S PREPURCHASED MSB-SSA-1

SWITCHBOARD AS SHOWN AND INDICATED ON DRAWINGS E401. CONNECT TO

TRANSFORMER WITH NEW CABLE AND CONDUIT AS INDICATED. PROVIDE NEMA-3R

BUSDUCT CONNECTION TO SWITCHBOARD TO MATCH THE SAME MANUFACTURER AS THE

OWNER'S PREPURCHASED SWITCHBOARDS MSB-SSA-1 AND MSB-SSA-2.

5. USE SAME 208V, 20A CIRCUIT (TRPC-12: #2,4) USED FOR TRANSFORMER

FANS/TEMPERATURE CONTROL AND MEDIUM VOLTAGE LOAD INTERRUPTER SWITCH

SHUNT TRIP CIRCUIT TO SERVE THE NEW ANTI-CONDENSATION STRIP HEATERS INSIDE

NEW MSB-SSA-1.

CONSTRUCTION PLAN NOTES#

GENERAL NOTES

A. REFER TO DRAWING E001 FOR SYMBOLS AND ABBREVIATIONS.

B. THE CONTRACTOR SHALL PERFORM COMPLETE ARC FLASH, COORDINATION, AND SHORT

CIRCUIT STUDY AS SPECIFIED IN SPECIFICATION SECTION 26 05 73.

C. THE CONTRACTOR MUST FOLLOW ALL ARGONNE LOCK OUT TAG OUT PROCEDURES IN

ADDITION TO THE REQUIREMENTS OUTLINED BY OSHA.

D. THE OWNER RESERVES THE RIGHT TO RETAIN ANY MATERIALS REMOVED FROM DEMOLITION

ACTIVITIES. THE CONTRACTOR SHALL COORDINATE WITH THE OWNER ALL MATERIALS AND

APPARATUS SCHEDULED TO BE REMOVED AND SHALL TURN OVER ALL ITEMS INDICATED BY

THE OWNER TO BE SALVAGED.

E. EACH AND EVERY POWER CONNECTION MUST HAVE A PRINTED LABEL INDICATING THE

SOURCE PANELBOARD AND CIRCUIT NUMBER.

F. ANL TO PROVIDE THE NATIVE ETAP MODEL FOR THE BUILDING TO THE CONTRACTOR. THE

CONTRACTOR SHALL UPDATE THE MODEL AND SEND THE NATIVE FILE BACK WITH ANY AND

ALL CHANGES. THE CONTRACTOR SHALL PROVIDE AND INSTALL NEW ARC-FLASH LABELS ON

THE EQUIPMENT INVOLVED IN THE STUDY AS PRODUCED BY THE UPDATED MODEL.

G. THE CONTRACTOR SHALL COORDINATE ALL BUSWAY ROUTING WITH EXISTING AND NEW

CONDITIONS INCLUDING FEATURES SUCH AS PIPING, DUCTWORK, SCAFFOLDING,

CABLE-TRAYS, WAVEGUIDES, STRUCTURE, AND ALL OTHERS. THESE DRAWINGS ARE

PROVIDED FOR THE PURPOSE OF ESTABLISHING A BASIS OF DESIGN ROUTING, BUT MAY NOT

DEPICT ALL FEATURES AND OBSTACLES WITHIN THE ROUTE. THE CONTRACTOR SHALL

SUBMIT SHOP DRAWINGS TO THE ENGINEER OF RECORD AND ARGONNE NATIONAL

LABORATORY PRIOR TO RELEASING FOR FABRICATION.

E601

FO

R

PR

EP

UR

CH

AS

E

ON

LY

NO

T

FO

R

CO

NS

TR

UC

TI

ON

1. THIS DRAWING IS PROVIDED FOR REFERENCE ONLY

SPECIAL NOTE FOR PREPURCHASE

AutoCAD SHX Text

RF-1 STAGING

AutoCAD SHX Text A001

AutoCAD SHX Text

RF-2

AutoCAD SHX Text A009

AutoCAD SHX Text

RF-2 STAGING

AutoCAD SHX Text A008

AutoCAD SHX Text

TRUCK AIR LOCK

AutoCAD SHX Text A010

AutoCAD SHX Text

DRAWING TITLE

AutoCAD SHX Text

CHECKED

AutoCAD SHX Text

DESIGNED

AutoCAD SHX Text

DRAWN

AutoCAD SHX Text

APPROVED

AutoCAD SHX Text

FACILITY DOCUMENT NO.

AutoCAD SHX Text

CADD NUMBER

AutoCAD SHX Text

FACILITY NUMBER

AutoCAD SHX Text

PROJECT TITLE

AutoCAD SHX Text

REV. NO.

AutoCAD SHX Text

DESCRIPTION

AutoCAD SHX Text

BY

AutoCAD SHX Text

APVD

AutoCAD SHX Text

DATE

AutoCAD SHX Text

REV. NO.

AutoCAD SHX Text

DRAWING NO.

AutoCAD SHX Text

J420-104-W-E100.DWG

AutoCAD SHX Text B420

AutoCAD SHX Text

SJD

AutoCAD SHX Text

SJD

AutoCAD SHX Text

SSC

AutoCAD SHX Text

JET

AutoCAD SHX Text A

AutoCAD SHX Text

PRE-PURCHASE REVIEW

AutoCAD SHX Text

SJD

AutoCAD SHX Text

SSC

AutoCAD SHX Text 06-10-24

AutoCAD SHX Text B

AutoCAD SHX Text

ISSUED FOR PREPURCHASE

AutoCAD SHX Text

SJD

AutoCAD SHX Text

SSC

AutoCAD SHX Text 09-03-24

36.00"

36.00" MAX

36.00"

48" MIN

(TYP.) WAVEGUIDES ARE AT

9'-6" FROM FINISHED FLOOR

TO BOTTOM OF WAVEGUIDE.

NOTE - DIMENSIONS INDICATED ARE

BASED ON SQUARE-D SWITCHBOARD

EQUIPMENT AND MAY VARY.

47.19"

MSB-SSA-2

TO BE INCLUDED IN THIS

EQUPIMENT PREPURCHASE

PDP-SSA-36-C4

TO BE INCLUDED IN THIS

EQUPIMENT PREPURCHASE

PDP-SSA-36-C3

TO BE INCLUDED IN THIS

EQUPIMENT PREPURCHASE

PDP-SSA-36-C2

TO BE INCLUDED IN THIS

EQUPIMENT PREPURCHASE

PDP-SSA-36-C1

TO BE INCLUDED IN THIS

EQUPIMENT PREPURCHASE

WARNING

IF PLAN IS ENLARGED OR REDUCED,

GRAPHIC SCALE SHALL BE USED.

J420-104-W- E101N 0

BUILDING 420

SOLID STATE AMPLIFIER

ELECTRICAL

FIRST FLOOR S36 NORTH

NEW WORK

Grumman/Butkus Associates Energy Efficiency Consultants and Sustainable Design Engineers

820 Davis St, Ste 300 Evanston, Illinois 60201 4446 847 328.3555 www.grummanbutkus.com Copyright © 2023 Grumman/Butkus Associates Illinois Registration #184-000926 GBA Project: P23-0858-00

1 ELECTRICAL FIRST FLOOR POWER PLAN - MODULE S36 NORTH

1/4"=1'-0"

0 41 2 8

CONSTRUCTION PLAN NOTES#

GENERAL NOTES

A. REFER TO DRAWING E001 FOR SYMBOLS AND ABBREVIATIONS.

B. THE CONTRACTOR SHALL PERFORM COMPLETE ARC FLASH, COORDINATION, AND SHORT

CIRCUIT STUDY AS SPECIFIED IN SPECIFICATION SECTION 26 05 73.

C. THE CONTRACTOR MUST FOLLOW ALL ARGONNE LOCK OUT TAG OUT PROCEDURES IN

ADDITION TO THE REQUIREMENTS OUTLINED BY OSHA.

D. THE OWNER RESERVES THE RIGHT TO RETAIN ANY MATERIALS REMOVED FROM DEMOLITION

ACTIVITIES. THE CONTRACTOR SHALL COORDINATE WITH THE OWNER ALL MATERIALS AND

APPARATUS SCHEDULED TO BE REMOVED AND SHALL TURN OVER ALL ITEMS INDICATED BY

THE OWNER TO BE SALVAGED.

E. EACH AND EVERY POWER CONNECTION MUST HAVE A PRINTED LABEL INDICATING THE

SOURCE PANELBOARD AND CIRCUIT NUMBER.

F. ANL TO PROVIDE THE NATIVE ETAP MODEL FOR THE BUILDING TO THE CONTRACTOR. THE

CONTRACTOR SHALL UPDATE THE MODEL AND SEND THE NATIVE FILE BACK WITH ANY AND

ALL CHANGES. THE CONTRACTOR SHALL PROVIDE AND INSTALL NEW ARC-FLASH LABELS ON

THE EQUIPMENT INVOLVED IN THE STUDY AS PRODUCED BY THE UPDATED MODEL.

G. THE CONTRACTOR SHALL COORDINATE ALL BUSWAY ROUTING WITH EXISTING AND NEW

CONDITIONS INCLUDING FEATURES SUCH AS PIPING, DUCTWORK, SCAFFOLDING,

CABLE-TRAYS, WAVEGUIDES, STRUCTURE, AND ALL OTHERS. THESE DRAWINGS ARE

PROVIDED FOR THE PURPOSE OF ESTABLISHING A BASIS OF DESIGN ROUTING, BUT MAY NOT

DEPICT ALL FEATURES AND OBSTACLES WITHIN THE ROUTE. THE CONTRACTOR SHALL

SUBMIT SHOP DRAWINGS TO THE ENGINEER OF RECORD AND ARGONNE NATIONAL

LABORATORY PRIOR TO RELEASING FOR FABRICATION.

1. PROVIDE NEW 3000A, 480Y/277V 3P, 4W + GND. SWITCHBOARD. SWITCHBOARD TO

INCLUDE 65kAIC INSULATED CASE MAIN BREAKER WITH LSIG TRIP UNIT AND POWER

METER PER SPECIFICATION SECTION 26 2413 . SEE DETAIL #3 ON SHEET E601 FOR

ADDITIONAL INFORMATION.

2. PROVIDE NEW 600A, 480V 3P, 4W + GND. WALL MOUNTED DISTRIBUTION

PANELBOARD EQUIPPED WITH A 600A MAIN BREAKER WITH 120V SHUNT TRIP AND (2)

250A 3P BRANCH BREAKERS, HINGED FRONT COVERS, AND NEW POWER METER

AHEAD OF THE MAIN CIRCUIT BREAKER PER SPECIFICATION SECTION 26 2416.

3. THIS DISTRIBUTION SECTION (SECTION #3) SHALL BE SHIPPED AS ITS OWN SPLIT PER

THE SINGLE LINE DRAWING J420-104-W-E401 AND WILL BE INSTALLED IN FUTURE

PHASE IN FUTURE LOCATION TO BE DETERMINED.

FO

R

PR

EP

UR

CH

AS

E

ON

LY

NO

T

FO

R

CO

NS

TR

UC

TI

ON

1. THIS DRAWING IS PROVIDED FOR REFERENCE ONLY

SPECIAL NOTE FOR PREPURCHASE

AutoCAD SHX Text

ELECTRONICS

AutoCAD SHX Text

RF-2 STAGING

AutoCAD SHX Text A008

AutoCAD SHX Text

EXPERIMENT HALL

AutoCAD SHX Text D

AutoCAD SHX Text 05-A

AutoCAD SHX Text 6'-0"

AutoCAD SHX Text 7'-2"

AutoCAD SHX Text D

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text M

AutoCAD SHX Text

AutoCAD SHX Text

PT

AutoCAD SHX Text 1 3/4"

AutoCAD SHX Text C

AutoCAD SHX Text

PT

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

EXPERIMENT HALL

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text L

AutoCAD SHX Text A

AutoCAD SHX Text

DRAWING TITLE

AutoCAD SHX Text

CHECKED

AutoCAD SHX Text

DESIGNED

AutoCAD SHX Text

DRAWN

AutoCAD SHX Text

APPROVED

AutoCAD SHX Text

FACILITY DOCUMENT NO.

AutoCAD SHX Text

CADD NUMBER

AutoCAD SHX Text

FACILITY NUMBER

AutoCAD SHX Text

PROJECT TITLE

AutoCAD SHX Text

REV. NO.

AutoCAD SHX Text

DESCRIPTION

AutoCAD SHX Text

BY

AutoCAD SHX Text

APVD

AutoCAD SHX Text

DATE

AutoCAD SHX Text

REV. NO.

AutoCAD SHX Text

DRAWING NO.

AutoCAD SHX Text

J420-104-W-E101N.DWG

AutoCAD SHX Text B420

AutoCAD SHX Text

SJD

AutoCAD SHX Text

SJD

AutoCAD SHX Text

SSC

AutoCAD SHX Text

JET

AutoCAD SHX Text A

AutoCAD SHX Text

PRE-PURCHASE REVIEW

AutoCAD SHX Text

SJD

AutoCAD SHX Text

SSC

AutoCAD SHX Text 06-10-24

AutoCAD SHX Text B

AutoCAD SHX Text

ISSUED FOR PREPURCHASE

AutoCAD SHX Text

SJD

AutoCAD SHX Text

SSC

AutoCAD SHX Text 09-03-24

TRPC-R18

TRPC-12

RF-C

TRPC-12

TRPC-R18

TRANSFORMER

(ON MEZZANINE ABOVE)

LADDER UP TO

MEZZANINE

J

MSB-SSA-1

TO BE INCLUDED IN THIS

EQUPIMENT PREPURCHASE

NEW MEDIUM VOLTAGE

TRANSFORMER TO BE INCLUDED

IN THIS PREPURCHASE

36.00"

8.75"

51.00"

GRC CONDUIT ABOVE GRADE

TO TRANSFORMER PER

SINGLE LINE DIAGRAM E401

AND PER DRAWING

E601 DETAIL #2

EXISTING CABLE

TRAY ~15'-0" AFF TO

BOTTOM OF TRAY.

108.00"

66.00"

WARNING

IF PLAN IS ENLARGED OR REDUCED,

GRAPHIC SCALE SHALL BE USED.

J420-104-W E101S 0

BUILDING 420

SOLID STATE AMPLIFIER

ELECTRICAL

FIRST FLOOR S36 SOUTH

NEW WORK

Grumman/Butkus Associates Energy Efficiency Consultants and Sustainable Design Engineers

820 Davis St, Ste 300 Evanston, Illinois 60201 4446 847 328.3555 www.grummanbutkus.com Copyright © 2023 Grumman/Butkus Associates Illinois Registration #184-000926 GBA Project: P23-0858-00

1 ELECTRICAL FIRST FLOOR POWER PLAN - MODULE S36 SOUTH

1/4"=1'-0"

0 41 2 8

1. EXISTING CONDUIT CONTAINING EXISTING TRANSFORMER HEATER CIRCUIT AND

RS-485 TEMPERATURE MONITORING CIRCUIT. CONTRACTOR TO EXTEND TO NEW

TRANSFORMER.

2. EXISTING CONDUIT CONTAINING EXISTING RS-485 TEMPERATURE MONITORING

CIRCUIT WHICH SHALL BE EXTENDED TO NEW LABORATORY SSA PLC CONTROLLER.

3. NEW JUNCTION BOX WITH TERMINAL STRIP PROVIDED TO INTERCEPT AND EXTEND

EXISTING RS-485 TEMPERATURE MONITORING CIRCUIT TO NEW LABORATORY SSA

PLC CONTROLLER.

4. INTERCEPT EXISTING GROUND RING USED FOR EXISTING TRANSFORMER AND

ROUTE INTO NEW TRANFORMER. CONNECT TO GROUND BUS IN TRANSFORMER

ENCLOSURE. REFER TO DRAWING E401 FOR CONNECTION DETAIL.

CONSTRUCTION PLAN NOTES#

GENERAL NOTES

A. REFER TO DRAWING E001 FOR SYMBOLS AND ABBREVIATIONS.

B. THE CONTRACTOR SHALL PERFORM COMPLETE ARC FLASH, COORDINATION, AND SHORT

CIRCUIT STUDY AS SPECIFIED IN SPECIFICATION SECTION 26 05 73.

C. THE CONTRACTOR MUST FOLLOW ALL ARGONNE LOCK OUT TAG OUT PROCEDURES IN

ADDITION TO THE REQUIREMENTS OUTLINED BY OSHA.

D. THE OWNER RESERVES THE RIGHT TO RETAIN ANY MATERIALS REMOVED FROM DEMOLITION

ACTIVITIES. THE CONTRACTOR SHALL COORDINATE WITH THE OWNER ALL MATERIALS AND

APPARATUS SCHEDULED TO BE REMOVED AND SHALL TURN OVER ALL ITEMS INDICATED BY

THE OWNER TO BE SALVAGED.

E. EACH AND EVERY POWER CONNECTION MUST HAVE A PRINTED LABEL INDICATING THE

SOURCE PANELBOARD AND CIRCUIT NUMBER.

F. ANL TO PROVIDE THE NATIVE ETAP MODEL FOR THE BUILDING TO THE CONTRACTOR. THE

CONTRACTOR SHALL UPDATE THE MODEL AND SEND THE NATIVE FILE BACK WITH ANY AND

ALL CHANGES. THE CONTRACTOR SHALL PROVIDE AND INSTALL NEW ARC-FLASH LABELS ON

THE EQUIPMENT INVOLVED IN THE STUDY AS PRODUCED BY THE UPDATED MODEL.

G. THE CONTRACTOR SHALL COORDINATE ALL BUSWAY ROUTING WITH EXISTING AND NEW

CONDITIONS INCLUDING FEATURES SUCH AS PIPING, DUCTWORK, SCAFFOLDING,

CABLE-TRAYS, WAVEGUIDES, STRUCTURE, AND ALL OTHERS. THESE DRAWINGS ARE

PROVIDED FOR THE PURPOSE OF ESTABLISHING A BASIS OF DESIGN ROUTING, BUT MAY NOT

DEPICT ALL FEATURES AND OBSTACLES WITHIN THE ROUTE. THE CONTRACTOR SHALL

SUBMIT SHOP DRAWINGS TO THE ENGINEER OF RECORD AND ARGONNE NATIONAL

LABORATORY PRIOR TO RELEASING FOR FABRICATION.

FO

R

PR

EP

UR

CH

AS

E

ON

LY

NO

T

FO

R

CO

NS

TR

UC

TI

ON

1. THIS DRAWING IS PROVIDED FOR REFERENCE ONLY

SPECIAL NOTE FOR PREPURCHASE

AutoCAD SHX Text

MAGNET

AutoCAD SHX Text

ELECTRONICS

AutoCAD SHX Text A005

AutoCAD SHX Text

RF-1 STAGING

AutoCAD SHX Text A001

AutoCAD SHX Text

RF-2

AutoCAD SHX Text A009

AutoCAD SHX Text

RF-2 STAGING

AutoCAD SHX Text A008

AutoCAD SHX Text J.C.

AutoCAD SHX Text A006

AutoCAD SHX Text

TOILET

AutoCAD SHX Text A007

AutoCAD SHX Text

FE-1

AutoCAD SHX Text

FE-1

AutoCAD SHX Text

OPP. HAND

AutoCAD SHX Text 755.70

AutoCAD SHX Text

ELEV.

AutoCAD SHX Text 755.70

AutoCAD SHX Text

ELEV.

AutoCAD SHX Text

TRUCK AIR LOCK

AutoCAD SHX Text A010

AutoCAD SHX Text

UP

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text A

AutoCAD SHX Text A.6

AutoCAD SHX Text B

AutoCAD SHX Text C

AutoCAD SHX Text

DRAWING TITLE

AutoCAD SHX Text

CHECKED

AutoCAD SHX Text

DESIGNED

AutoCAD SHX Text

DRAWN

AutoCAD SHX Text

APPROVED

AutoCAD SHX Text

FACILITY DOCUMENT NO.

AutoCAD SHX Text

CADD NUMBER

AutoCAD SHX Text

FACILITY NUMBER

AutoCAD SHX Text

PROJECT TITLE

AutoCAD SHX Text

REV. NO.

AutoCAD SHX Text

DESCRIPTION

AutoCAD SHX Text

BY

AutoCAD SHX Text

APVD

AutoCAD SHX Text

DATE

AutoCAD SHX Text

REV. NO.

AutoCAD SHX Text

DRAWING NO.

AutoCAD SHX Text

J420-104-W-E101S.DWG

AutoCAD SHX Text B420

AutoCAD SHX Text

SJD

AutoCAD SHX Text

SJD

AutoCAD SHX Text

SSC

AutoCAD SHX Text

JET

AutoCAD SHX Text A

AutoCAD SHX Text

PRE-PURCHASE REVIEW

AutoCAD SHX Text

SJD

AutoCAD SHX Text

SSC

AutoCAD SHX Text 06-10-24

AutoCAD SHX Text B

AutoCAD SHX Text

ISSUED FOR PREPURCHASE

AutoCAD SHX Text

SJD

AutoCAD SHX Text

SSC

AutoCAD SHX Text 09-03-24

S-R11 N.C.

S-R12 N.O.

200E

S-R13 N.C.

S-R14 N.O.

200E

S-R9 N.C.

S-R10 N.O.

200E

S-R7 N.C.

S-R8 N.O.

200E

S-R5 N.C.

S-R6 N.O.

200E

TO SWITCHGEAR S2 BUS 2

TO SWITCHGEAR S1 BUS 1

EXISTING RF/EXTRACTION BUILDING OUTDOOR 13.2kV LOAD

INTERRUPTER SWITCHGEAR

NEW PREPURCHASED DRY TYPE MV NEMA-3R TRANSFORMER

2000/2666kVA AA/FA @ 80°C RISE

2700/3600kVA AA/FA @ 150°C RISE

13.2KV PRIMARY

480Y/277V SECONDARY

Z% = 5.75%

150E

MSB-SSA-2

3000A 480Y/277V

3-PHASE, 4-WIRE,

65kA RATED BUSSING AND BRANCH BREAKERS

SECT. 1SECT. 2

PM 3000:5A

4CT

K1 K1

LO LO

K1

EXISTING 15kV LOAD

INTERRUPTER SWITCH AT

TRANSFORMER

VTS

GRACE VOLTAGE

TEST STATION PER

SPECIFICATIONS

3000A COPPER BUS

ST

MAIN CIRCUIT

BREAKER W/120V

SHUNT TRIP

TYPICAL NEW SSA PANELBOARD

EPO

EMERGENCY POWER

OFF (EPO) BUTTON

TURN TO RESET TYPE

H

N

TO TECHNICAL

POWER PANEL -

SEE PLANS FOR

CIRCUIT NUMBERS

SPD

SURGE PROTECTIVE

DEVICE PER

SPECIFICATIONS

600A/3P

3000A COPPER BUS

SECT. 3

SHOWN FOR REFERENCE, NOT IN CONTRACT:

3000A CU 3P, 4W, WITH 50% GROUND BAR

CONTRACTOR'S FEEDER BUSDUCT BUSDUCT SHALL

MATCH MANUFACTURER (OR INTERIOR BUS DETAILS)

OF SWITCHBOARD. BUSDUCT IS NOT IN THIS

CONTRACT.

N

G

G N

NEUTRAL SHALL

BE UNBONDED AT

TRANSFORMER

CONNECT TO EXISTING

GROUNDING RING AT TRANSFORMER

FOUNDATION WITH #4/0 CU

EXOTHERMIC WELDED

GROUNDING SPLICE PER UL

BUSWAY FLANGE TO JOIN BUSDUCT TO

SWITCHBOARD. BUSWAY FLANGE TO MATCH

SWITCHBOARD MANUFACTURER

LC

K1 K1

LO LO

LC

K1

K1 K1

LO LO

LC

K1

K1 K1

LO LO

LC

K1

K1 K1

LO LO

LC

K1

NEW 3-1/C #1/0 COPPER NON-SHIELDED 15kV CABLE BY TRANSFORMER

MANUFACTURER SHIPPED IN 150 FOOT LENGTH (50 FEET PER PHASE) AND TO

BE INSTALLED AND TERMINATED BY ELECTRICAL CONTRACTOR. ELECTRICAL

CONTRACTOR SHALL INSTALL CABLING IN EXISTING THROAT CONNECTION

BETWEEN EXISTING LOAD INTERRUPTER SWITCH AND NEW TRANSFORMER

USING EXISTING SUPPORT INSULATORS/GLASTIC PANELS.

NEW 150E FUSES TO MATCH

EXISTING TYPES IN LOAD

INTERRUPTER SWITCH

EXISTING UNDERGROUND

CABLE AND CONDUIT

EXISTING 208V SHUNT TRIP:

TRPC-12: #2,4

3LA

15kV

12.7MCOV

ST

G

#12 AWG, 3/4"C

MSB-SSA-1

NEW 3000A 480Y-277V NEMA-3R UL

SERVICE ENTRANCE RATED

SWITCHBOARD. PROVIDED AS

PREPURCHASED EQUIPMENT.G N

ST

8 SETS OF

4-500KCMIL, 1#3/0G,

3 1/2" GRC

TO MSB-SSA-2

2#12, 1#12G, 3/4" C

SEE PLANS FOR CIRCUIT

2#12, 1#12G, 3/4" C

TO MSB-SSA-1

SEE PLANS FOR PANEL

AND CIRCUIT NUMBER

3000A

LSIG

ARMS

100%

RATED

208V - 1Ø TO

TRPC-12

ANTI-COND.

HEATER

600A

LSI

600A

LSI

600AF

600AT

PM 600:5A

4CT

ST

250AF

250AT

250AF

250AT

PM 600:5A

4CT

250AF

250AT

250AF

250AT

PM 600:5A

4CT

250AF

250AT

250AF

250AT

PM 600:5A

4CT

250AF

250AT

250AF

250AT

PDP-SSA-36-C1

480V 3Ø-4W 35kA RATED

PDP-SSA-36-C3

480V 3Ø-4W 35kA RATED

PDP-SSA-36-C4

480V 3Ø-4W 35kA RATED

PDP-SSA-36-C2

480V 3Ø-4W 35kA RATED

600A

LSI

600A

LSI

600A

LSI

600A

LSI

600A

LSI

600A

LSI

600A

LSI

600A

LSI

600A

LSI

EPO

120V POWER BY E.C.

SHALL BE PROVIDED TO

SHUNT TRIP OPERATOR.

SEE DETAIL #2 ON THIS

DRAWING

600AF

600AT

600AF

600AT

600AF

600ATST

EPO

ST

EPO

ST

EPO

TYPICAL: 120VAC SHUNT TRIP

ON MAIN

POWER

DISTRIBUTION

STYLE PANEL

POWER

DISTRIBUTION

STYLE PANEL

POWER

DISTRIBUTION

STYLE PANEL

POWER

DISTRIBUTION

STYLE PANEL

(2) SETS OF 4#350kCMIL, 1#1G, 3"C

2#12, 1#12G, 3/4"C

TO EACH EPO

SEE PLANS FOR CIRCUIT #

SPARESPARE SPARESPARESPARESPARESPARESPARE

600A

LSI

PDP-SSA-36-C1

480V 3Ø-4W 35kA RATED

WIRING BY OTHERS

TYPICAL - EPO BUTTONS

PROVIDED BY OTHERS;

NOT IN THIS CONTRACT

BUSWAY FLANGE TO JOIN BUSDUCT

TO SWITCHBOARD. BUSWAY FLANGE

TO MATCH SWITCHBOARD

MANUFACTURER

WARNING

IF PLAN IS ENLARGED OR REDUCED,

GRAPHIC SCALE SHALL BE USED.

J420-104-W- E401 0

BUILDING 420

SOLID STATE AMPLIFIER

ELECTRICAL

SINGLE LINE

DIAGRAM

Grumman/Butkus Associates Energy Efficiency Consultants and Sustainable Design Engineers

820 Davis St, Ste 300 Evanston, Illinois 60201 4446 847 328.3555 www.grummanbutkus.com Copyright © 2023 Grumman/Butkus Associates Illinois Registration #184-000926 GBA Project: P23-0858-00

GENERAL NOTES

A. REFER TO DRAWING E001 FOR SYMBOLS AND ABBREVIATIONS.

B. THE CONTRACTOR SHALL PERFORM COMPLETE ARC FLASH, COORDINATION, AND SHORT

CIRCUIT STUDY AS SPECIFIED IN SPECIFICATION SECTION 26 05 73.

C. THE CONTRACTOR MUST FOLLOW ALL ARGONNE LOCK OUT TAG OUT PROCEDURES IN

ADDITION TO THE REQUIREMENTS OUTLINED BY OSHA.

D. THE OWNER RESERVES THE RIGHT TO RETAIN ANY MATERIALS REMOVED FROM DEMOLITION

ACTIVITIES. THE CONTRACTOR SHALL COORDINATE WITH THE OWNER ALL MATERIALS AND

APPARATUS SCHEDULED TO BE REMOVED AND SHALL TURN OVER ALL ITEMS INDICATED BY

THE OWNER TO BE SALVAGED.

E. EACH AND EVERY POWER CONNECTION MUST HAVE A PRINTED LABEL INDICATING THE

SOURCE PANELBOARD AND CIRCUIT NUMBER.

F. ANL TO PROVIDE THE NATIVE ETAP MODEL FOR THE BUILDING TO THE CONTRACTOR. THE

CONTRACTOR SHALL UPDATE THE MODEL AND SEND THE NATIVE FILE BACK WITH ANY AND

ALL CHANGES. THE CONTRACTOR SHALL PROVIDE AND INSTALL NEW ARC-FLASH LABELS ON

THE EQUIPMENT INVOLVED IN THE STUDY AS PRODUCED BY THE UPDATED MODEL.

G. THE CONTRACTOR SHALL COORDINATE ALL BUSWAY ROUTING WITH EXISTING AND NEW

CONDITIONS INCLUDING FEATURES SUCH AS PIPING, DUCTWORK, SCAFFOLDING,

CABLE-TRAYS, WAVEGUIDES, STRUCTURE, AND ALL OTHERS. THESE DRAWINGS ARE

PROVIDED FOR THE PURPOSE OF ESTABLISHING A BASIS OF DESIGN ROUTING, BUT MAY NOT

DEPICT ALL FEATURES AND OBSTACLES WITHIN THE ROUTE. THE CONTRACTOR SHALL

SUBMIT SHOP DRAWINGS TO THE ENGINEER OF RECORD AND ARGONNE NATIONAL

LABO…