20231010 CSU Pueblo_Roof Dwgs_BID SET.pdf
PDF 7 MB Posted
- Solicitation number
- 2023-090M22
- Issued by
- Pitkin County, Colorado
About this file
These architectural drawings detail a roof replacement project for Colorado State University Pueblo, specifically targeting three campus buildings: the Physical Plant, Heat Plant, and Music Building. The project involves a complete roof tear-off and replacement, with new roofing assemblies designed for concrete and metal roof decks. The scope includes installing new 80-mil thermoplastic membrane, gypsum cover boards, polyisocyanurate insulation layers, vapor retarders, and associated flashing and penetration details. The roof replacement will address multiple roof areas across the three buildings, with careful attention to wind design considerations, drainage requirements, and specific installation techniques for different roof deck substrates.
The project documents indicate a comprehensive approach to roof replacement, with total thermal resistance values ranging from R-30.56 to R-31.27 depending on the specific building and deck substrate. The design includes options for both TPO and PVC membrane materials, with detailed specifications for attachment methods, insulation layers, and flashing techniques. Wind design calculations are provided for different roof zones, with specific attachment requirements for various roof areas. The project appears to be funded through the university's capital improvement budget, with a focus on enhancing building envelope performance and extending the service life of critical campus infrastructure.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
VICINITY MAP:REGION MAP:
· R-100 COVER SHEET
· R-101 DESIGN NOTES
· R-102 ROOF ASSEMBLIES
· R-200 WIND DESIGN
· R-201 WIND DESIGN
· R-202 WIND DESIGN
· R-300 ROOF PLAN
· R-301 ROOF PLAN
· R-302 ROOF PLAN
· R-400 VAPOR RETARDER DETAILS
· R-500 ROOFING DETAILS
· R-501 ROOFING DETAILS
· R-502 ROOFING DETAILS
· R-503 ROOFING DETAILS
· R-600 EXPANSION WALL DETAILS
SHEET INDEX:
AERIAL MAP - MUSIC BUILDING:
ABBREVIATIONS:
APVD. APPROVED
CONT. CONTINUOUS
(E) EXISTING
(ETR) EXISTING TO REMAIN
(FA) FULLY ADHERED
GA. GAUGE
GALV. GALVANIZED
GYP. GYPSUM
MANU. MANUFACTURER
MAX. MAXIMUM
(MA) MECHANICALLY ATTACHED
MTL METAL
MIN. MINIMUM
(N) NEW
O.C. ON CENTER
PENE. PENETRATION
REQ. REQUIREMENT
R.T.S. REINFORCED TERMINATION STRIP
SIM. SIMILAR
TYP. TYPICAL
V.I.F. VERIFY IN FIELD
PLOT SCALE IS 30x42
ISSUED FOR
SHEET NO.
SHEET TITLE
PROJECT
CLIENT
DATE REVISION
DRAWN BY
CHECKED BY
PROJECT NO.
DATE
LEGEND
OF
1720 South Bellaire Street, Suite 1200 Denver, Colorado 80222
(303) 738-0823 | www.amtechsls.com
AMTECH
SOLUTIONS
KEYPLAN LEGEND
DRAFT
THIS DOCUMENT
MAY NOT
BE USED FOR
CONSTRUCTION
COLORADO STATE
UNIVERSITY PUEBLO
2200 BONFORTE BOULEVARD
PUEBLO, COLORADO 81001
2023-020M22
CSU PUEBLO ROOFING PROJECT
2200 BONFORTE BOULEVARD
PUEBLO, COLORADO 81001
DEN.2023.001022
10/2023
BID RELEASE
RKP & SAP
DD
COVER SHEET
R-100 01 14
AMTECH SOLUTIONS, INC.
1720 SOUTH BELLAIRE STREET, SUITE 1200
DENVER, COLORADO 80222
TEL: (303) 738-0823
WEBSITE: WWW.AMTECHSLS.COM
OWNER:PROJECT: CONSULTANT:
AMTECH
SOLUTIONS
2023-020M22 - REPLACE ROOFS - PHYSICAL PLANT, HEAT PLANT, AND MUSIC BUILDING - AMTECH PROJECT NO.: DEN.2023.001022
2200 BONFORTE BOULEVARD
PUEBLO, COLORADO 81001
2200 BONFORTE BOULEVARD
PUEBLO, COLORADO 81001
CSU PUEBLO ROOFING PROJECT - 2023-020M22 COLORADO STATE UNIVERSITY PUEBLO
COLORADO STATE UNIVERSITY PUEBLO ROOFING PROJECT
APPLICABLE DESIGN CODES:
1. 2021 INTERNATIONAL EXISTING BUILDING CODE (IEBC).
2. 2021 INTERNATIONAL BUILDING CODE (IBC).
3. 2021 INTERNATIONAL ENERGY CONSERVATION CODE (IECC).
4. AMERICAN NATIONAL STANDARDS INSTITUTE AND SINGLE-PLY
ROOFING INDUSTRY (ANSI/SPRI):
4.1. ES-1 AND GT-1.
5. BUILDING DATA:
5.1. MONITORED ALARM.
5.2. CONSTRUCTION TYPE III-B - NON-COMBUSTIBLE:
5.2.1. MASONRY, STEEL, AND/OR CONCRETE FRAMING
WITH CONCRETE AND/OR METAL DECKING.
5.3. OCCUPANCY CLASSIFICATION:
5.3.1. GROUP B - BUSINESS - EDUCATIONAL OCCUPANCY
FOR STUDENTS ABOVE GRADE TWELVE (12).
CODE EXCEPTIONS:
1. 2021 IEBC - SECTION 705 REROOFING - 705.1 GENERAL:
1.1. ROOF REPLACEMENT OR ROOF RECOVER OF EXISTING LOW-SLOPE ROOF COVERINGS SHALL NOT BE REQUIRED TO
MEET THE MINIMUM DESIGN SLOPE REQUIREMENTS OF 1
4 UNIT VERTICAL IN 12 UNITS HORIZONTAL (2-PERCENT
SLOPE) IN SECTION 1507 OF THE INTERNATIONAL BUILDING CODE FOR ROOFS THAT PROVIDE POSITIVE ROOF
DRAINAGE.
1.2. RECOVERING OR REPLACING AN EXISTING ROOF COVERING SHALL NOT BE REQUIRED TO MEET THE REQUIREMENTS FOR SECONDARY (EMERGENCY OVERFLOW) DRAINS OR SCUPPERS IN SECTION 1502 OF THE INTERNATIONAL BUILDING CODE FOR ROOFS THAT PROVIDE FOR POSITIVE ROOF DRAINAGE. FOR THE PURPOSES OF THIS EXCEPTION, EXISTING SECONDARY DRAINAGE OR SCUPPER SYSTEM REQUIRED IN ACCORDANCE WITH THIS CODE SHALL NOT BE REMOVED UNLESS THEY ARE REPLACED BY SECONDARY DRAINS OR SUPPERS DESIGNED AND
INSTALLED IN ACCORDANCE WITH SECTION 1502 OF THE INTERNATIONAL BUILDING CODE.
2200 BONFORTE BOULEVARD
PUEBLO, COLORADO 81001
ROOF REPLACEMENT WORK
AREAS @ MUSIC BUILDING
TRUE
NORTH
AERIAL MAP - HEAT BUILDING AND PLANT BUILDING :
TRUE
NORTH
ROOF REPLACEMENT WORK
AREAS @ HEAT BUILDING
ROOF REPLACEMENT WORK
AREAS @ PLANT BUILDING
PLOT SCALE IS 30x42
ISSUED FOR
SHEET NO.
SHEET TITLE
PROJECT
CLIENT
DATE REVISION
DRAWN BY
CHECKED BY
PROJECT NO.
DATE
LEGEND
OF
1720 South Bellaire Street, Suite 1200 Denver, Colorado 80222
(303) 738-0823 | www.amtechsls.com
AMTECH
SOLUTIONS
KEYPLAN LEGEND
DRAFT
THIS DOCUMENT
MAY NOT
BE USED FOR
CONSTRUCTION
COLORADO STATE
UNIVERSITY PUEBLO
2200 BONFORTE BOULEVARD
PUEBLO, COLORADO 81001
2023-020M22
CSU PUEBLO ROOFING PROJECT
2200 BONFORTE BOULEVARD
PUEBLO, COLORADO 81001
DEN.2023.001022
10/2023
BID RELEASE
RKP & SAP
DD
DESIGN NOTES
R-101 02 14
GENERAL NOTES:
1. ALL CONDITIONS OR PENETRATIONS MAY NOT BE SHOWN. THE CONTRACTOR IS
RESPONSIBLE FOR FIELD VERIFYING ALL EXISTING CONDITIONS,
MEASUREMENTS/DIMENSIONS, QUANTITIES, LOCATIONS, ETC. AND NOTIFYING AMTECH
SOLUTIONS OF ANY DISCREPANCIES PRIOR TO BIDDING.
2. ALL SHEET METAL WORK MUST COMPLY WITH SMACNA AND ANSI/SPRI ES-1 AND GT-1 AS
REFERENCED IN THE APPLICABLE VERSION OF THE IBC AND IEBC.
3. THE WORK OF THIS CONTRACT SHALL BE COMPLETED IN ACCORDANCE WITH THE ATTACHED
DRAWINGS, DOCUMENTS AND SPECIFICATIONS.
4. ALL MATERIALS TO BE USED ON THIS PROJECT SHALL BE INSTALLED IN STRICT
ACCORDANCE WITH MANUFACTURER'S RECOMMENDED SPECIFICATIONS FOR INSTALLATION.
5. CONTRACTOR(S) SHALL COORDINATE THE WORK OF THIS CONTRACT TO AVOID ANY
INTERFERENCE WITH ADJOINING AREAS.
6. ANY DEVIATIONS FROM THE CONSTRUCTION DOCUMENTS MUST BE SUBMITTED TO AMTECH
SOLUTIONS IN WRITING FOR APPROVAL.
7. CONTRACTOR SHALL EXERCISE EXTREME CARE NOT TO DAMAGE THE ADJACENT
CONSTRUCTION OF THE BUILDING. ANY DAMAGE SHALL BE CORRECTED BY THE
CONTRACTOR AT THEIR OWN EXPENSE.
8. CONTRACTOR SHALL PROVIDE ALL SAFE GUARDS, AS REQUIRED, TO PRECLUDE INJURY TO
AMTECH SOLUTIONS, THE OWNER'S AND CONTRACTOR'S PERSONNEL, AND TO ALL OTHER
PERSONS AT THE CONSTRUCTION SITE.
9. CONTRACTOR SHALL PERFORM ALL WORK AS INDICATED ON CONTRACT DOCUMENTS
INCLUDING BUT NOT LIMITED TO: ROOFING AND ASSOCIATED CURB AND PARAPET WALL
FLASHINGS AND MODIFICATIONS.
10. ALL SATELLITE RECEIVERS, ANTENNAS, EQUIPMENT SUPPORTS AND PENETRATIONS NOT
UTILIZED ARE TO BE REMOVED AND DISCARDED AS DIRECTED BY THE OWNER AND AMTECH
SOLUTIONS. ALL OPERATIONAL SATELLITE RECEIVERS, ANTENNAS, ETC. ARE TO BE
REMOVED AND RE-INSTALLED USING MANUFACTURER APPROVED DETAILS AS DIRECTED BY
AMTECH SOLUTIONS.
11. ANY EXISTING CABLES/CONDUITS LYING ON THE ROOF SHALL BE REMOVED AND/OR
RE-INSTALLED AS DIRECTED BY THE OWNER AND AMTECH SOLUTIONS.
12. AVOID PENETRATION SEALER POCKETS AT ROOF PENETRATIONS (INSTALL ONLY WHERE
REQUIRED AND APPROVED BY AMTECH SOLUTIONS).
13. WHERE EXISTING EXTERIOR LIGHTING AND ELECTRICAL EQUIPMENT INTERFERES WITH THE
CONSTRUCTION OF THE NEW ROOF, FASCIAS, OR SOFFITS, SUCH FIXTURES SHALL BE
REMOVED AND RE-INSTALLED TO THE SATISFACTION OF THE OWNER AND AMTECH
SOLUTIONS.
14. CONTRACTOR SHALL EXTEND EXISTING HVAC ROOF TOP UNITS AND INTERIOR DUCTWORK
THAT WILL BE DISTURBED DUE TO NEW WORK, INCLUDING BUT NOT LIMITED TO: CURBS,
DUCTWORK, PIPING, ELECTRICAL, ETC. IN ORDER TO MAINTAIN AN 8-INCH MINIMUM
FLASHING HEIGHT AS REQUIRED BY CODE, DUE TO INSTALLATION OF NEW ROOF SYSTEM.
15. ALL ROOF PIPE VENTS AND OTHER ROOF PENETRATION(S) SHALL BE EXTENDED UP TO
MAINTAIN AN 8-INCH MINIMUM FLASHING HEIGHT ABOVE NEW ROOF, AS REQUIRED BY CODE.
EXTENSIONS SHALL BE OF LIKE MATERIALS AND WELDED IF METAL.
16. ALL METAL FASCIA, COPINGS, LEADERS, SCUPPERS, GUTTERS, DOWNSPOUTS, ETC. ARE TO
BE FACTORY PRE-FINISHED (COLOR TO BE SELECTED AND APPROVED BY OWNER).
17. ALL DIMENSIONS FOR ALL EXISTING CONSTRUCTION CONDITIONS ARE APPROXIMATE AND
ARE TO BE FIELD VERIFIED BY THE CONTRACTOR(S).
18. CONTRACTOR IS TO VERIFY LOCATION, COUNT AND SIZES OF ROOF PENETRATIONS AND
DRAINS PRIOR TO THE COMMENCEMENT OF WORK.
19. ALL NEW CONTINUOUS FLASHINGS ARE TO BE INSTALLED AT A CONSISTENT HEIGHT.
MINIMUM FLASHING HEIGHTS ARE TO BE CALCULATED AT INSULATION HIGH POINTS.
20. THE NEW ROOF SYSTEM AND PERFORMANCE IS TO ADHERE TO LOCAL BUILDING CODE AND
DESIGN WIND SPEED REQUIREMENTS AS SPECIFIED.
21. REFER TO ACCOMPANYING SPECIFICATIONS FOR ADDITIONAL INFORMATION.
22. SPECIFICATIONS ARE TO TAKE PRECEDENCE OVER CONFLICTING INFORMATION ON
DRAWINGS.
23. CONTRACTOR IS TO MAINTAIN PROPER DRAINAGE OF THE ROOF(S) THROUGH ALL PHASES
OF ROOF CONSTRUCTION.
24. ALL NAILERS ARE TO BE FLUSH WITH THE TOP OF ADJACENT SUBSTRATES.
ROOFING NOTES:
1. UP TO ONE WEEKS WORTH OF MATERIALS CAN BE STORED ON THE ROOF, AS LONG AS THEY
ARE ON PALLETS/CRIBBING, COVERED WITH TARPS (NO PLASTIC) AND THE ROOF
STRUCTURE IS NOT OVERLOADED.
2. MATERIALS STORED ON THE GROUND SHOULD BE SECURED IN A FENCED IN AREA OR IN A
COVERED TRAILER TO ENSURE THEY ARE SECURE. ALL ONSITE STORAGE MUST FIRST BE
REVIEWED AND APPROVED BY BOTH THE OWNER AND CONSULTANT.
3. ALL MATERIALS SHALL BE KEPT DRY FROM STANDING WATER, FALLING WATER, AND
CONDENSATION WHEN ON THE GROUND AND ROOF.
4. BONDING ADHESIVES, MASTICS, CAULKING, ETC. ARE TO BE STORED BETWEEN 60 TO 80
DEGREES, AND NOT ALLOWED TO FREEZE.
5. THE CONTRACTOR IS TO TEAR-OFF, LAY-UP, AND COMPLETE DETAILS ON ROOF AREAS BY
THE END OF EACH WORKDAY.
6. ROOF DETAILING AND SHEET METAL INSTALLATION NEED TO FOLLOW CLOSELY BEHIND THE
ROOF MEMBRANE INSTALLATION.
7. NIGHT-SEALS ARE PARAMOUNT! CONTRACTOR IS REQUIRED TO TIE-IN THE NEW ROOF
SYSTEM TO THE EXISTING ROOF, SUCH THAT NO WATER CAN MIGRATE INTO THE NEW ROOF
ASSEMBLY AND/OR THE BUILDING.
8. THE AMBIENT TEMPERATURE REQUIREMENT FOR INSTALLATION IS 40 DEGREES AND RISING.
9. CONTRACTOR IS REQUIRED TO PROTECT ALL NEWLY INSTALLED ROOF MEMBRANES THAT
THEY WILL WORK OVER WITH CLEAN TARPS AND PLYWOOD.
10. ALL TRASH AND DEBRIS MUST BE REMOVED FROM THE ROOF SURFACE/LEVEL AS WELL AS
THE GROUNDS DAILY.
11. CONTRACTOR TO REPLACE ANY MISSING/ BROKEN DRAIN STRAINERS AND PARTS WITH NEW
TO MATCH EXISTING. ALL DRAINS STRAINERS AND CLAMPING RINGS ARE TO BE CLEANED,
PRIMED, AND PAINTED.
12. NEW 1
2-INCH (OR ONE SLOPE GREATER THAN EXISTING ROOF SLOPE) CRICKETS MUST BE
INSTALLED ON THE HIGH SIDE OF ALL CURBS AND PENETRATIONS WIDER THAN 24-INCHES.
13. NEW WALKWAY PADS ARE TO BE INSTALLED AS INDICATED ON THE ROOF PLANS AND AT ALL
LADDERS, ROOF HATCHES, RTU ACCESS PANELS, UNDER ALL SATELLITE SUPPORT SLEDS,
AND AROUND ALL SIDES OF SERVICEABLE MECHANICAL EQUIPMENT. NOT ALL WALK PADS
ARE SHOWN.
13.1. DO NOT INSTALL WALK PADS IN A MANNER THAT WILL CREATE WATER PONDING
CONDITIONS.
13.2. WALK PADS SHALL NOT BE INSTALLED OVER MEMBRANE SEAMS OR VALLEYS.
14. ALL INSULATION BOARD JOINTS SHALL BE 1
8" OR LESS IN WIDTH. FILL ALL UNEVEN OR
OVERSIZED JOINTS.
15. MEMBRANE ADHESIVE APPLICATION MUST BE ALLOWED TO PROPERLY FLASH OFF BEFORE
MATING. ENSURE ADHESIVE IS DRY TO THE POINT OF BEING TACKY, BUT NOT STRINGY TO
THE TOUCH. DO NOT ALLOW ADHESIVE TO "DRY-OUT" COMPLETELY.
16. PROVIDE 4" LAP JOINTS FOR ALL SHEET METAL FLASHING RECEIVERS.
17. PROVIDE CURBS FOR ALL ROOF MOUNTED EQUIPMENT WITH A DECK OPENING OF 12-INCHES
OR GREATER.
18. ALL MEMBRANE SEAMS MUST BE STRIPPED-IN WITH A MINIMUM 6" WIDE SEMI-CURED COVER
TAPE.
19. ALL INSIDE AND OUTSIDE CORNER DETAILING TO BE INSTALLED PER MANUFACTURER
REQUIREMENTS.
20. ELECTRIC METALLIC TUBE (EMT) CONDUITS MAY EXIST WITHIN THE HIGH FLUTES OF THE
METAL ROOF DECK AREAS. CONTRACTOR TO COORDINATE ACCESS TO INTERIOR ROOF
AREAS WITH OWNER AND IDENTIFY LOCATIONS WHERE EMT HAS BEEN INSTALLED WITHIN
THE HIGH FLUTES OF THE METAL DECK PRIOR TO TEAR OFF AND NEW ROOF INSTALLATION.
CONTRACTOR TO TAKE CARE NOT TO PENETRATE OR DAMAGE THE EXISTING EMT AND
ELECTRICAL WIRING COMPONENTS AS PART OF NEW ROOF INSTALLATION. ANY DAMAGE
THAT OCCURS AS A RESULT OF THE ROOF WORK WILL BE REPAIRED AND RETURNED TO
PRE-CONSTRUCTION CONDITION AT NO EXPENSE TO THE OWNER.
PLYWOOD SHEATHING FASTENING ILLUSTRATION:
PROVIDE A 45° CHAMFER ALONG THE
TOP EDGE OF THE (N) PLYWOOD. TYP.
(N) PLYWOOD MUST EXTEND
TO THE DECK SURFACE. TYP.
V.I.F.
BUTT PLYWOOD TIGHT TO BOTTOM
SIDE OF (N) PLYWOOD WOOD NAILER.
(N) NAILER FLUSH WITH PLYWOOD FACE.
(E) SUBSTRATE.
(E) ROOF DECK.
PLYWOOD SHEATHING FASTENING SECTION @ VERTICAL SUBSTRATES:
A-A
(A-A) PLYWOOD SHEATHING SECTION @ TOP OF PARAPET WALLS:
ROOF ASSEMBLY ATTACHMENT SCHEDULE:
ROOF MATERIAL
ATTACHMENT
TYPE
ATTACHMENT MATERIAL
ZONE 1'
ATTACHMENT RATE
ZONE 1
ATTACHMENT RATE
ZONE 2
ATTACHMENT RATE
ZONE 3
ATTACHMENT RATE
MEMBRANE ADHESIVE BONDING ADHESIVE FULL COVERAGE FULL COVERAGE FULL COVERAGE FULL COVERAGE
COVER BOARD
(48"x48" BOARD)
- NOTE 3 -
ADHESIVE LOW RISE FOAM - CONTINUOUS RIBBONS (NOTE 1) 6" O.C. 6" O.C. 4" O.C. 4" O.C.
INSULATION
(48"x48" BOARD)
- NOTE 3 -
ADHESIVE LOW RISE FOAM - CONTINUOUS RIBBONS (NOTE 1) 6" O.C. 6" O.C. 4" O.C. 4" O.C.
VAPOR RETARDER ADHESIVE ADHESIVE/PRIMER FULL COVERAGE FULL COVERAGE FULL COVERAGE FULL COVERAGE
SUBSTRATE BOARD
(48"x48" BOARD)
- NOTE 3 -
MECHANICAL COATED SCREWS AND INSULATION PLATES (NOTE 2) 8 10 12 16
NOTES:
1. LOW-RISE FOAM BEADS ARE TO BE APPLIED WET WITH A MINIMUM THICKNESS OF 3 4-INCH. LOW-RISE FOAM MUST BE ALLOWED TO RISE AND DEVELOP STRING/BODY (APPROXIMATELY 11
2 - 2 MIN.).
STRING TIME WILL VARY BASED ON ENVIRONMENTAL CONDITIONS LIKE TEMPERATURE AND HUMIDITY. DO NOT ALLOW THE ADHESIVE TO OVER-CURE PRIOR TO SETTING MATERIALS. DO NOT INSTALL
MATERIALS IN WET BEADS.
2. FASTENER AND PLATE PATTERNS ARE TO BE INSTALLED PER MANUFACTURER MINIMUM REQUIREMENTS. CONTRACTOR TO FOLLOW FASTENING AND BEAD SPACING RATES AS DEFINED WITHIN THE DESIGN DOCUMENTS WHERE FASTENING AND BEAD SPACING RATES ARE MORE STRINGENT THAN MANUFACTURER REQUIREMENTS. DO NOT INSTALL FASTENERS AND PLATES WITHIN 6-INCHES OF THE MATERIAL EDGE. FASTENERS ARE NOT TO PENETRATE THE BOTTOM FLUTES. CONTRACTOR TO VERIFY FASTENERS LENGTHS AND ENSURE FASTENERS PENETRATE THE TOP OF THE DECK FLUTES A
MINIMUM OF 3 4-INCH.
3. ATTACHMENT RATES SHOWN FOR ZONES 1', 1, 2, AND 3 ARE FOR 48"x48" (4'x4') BOARDS. FASTENING PATTERNS MUST BE DOUBLED FOR 48"x96" (4'x8') BOARDS. TYPICAL.
4. BASE SHEETS AND ASSOCIATED BASE SHEET FASTENERS TO BE USED ON LIGHTWEIGHT INSULATING CONCRETE AND GYPSUM ROOF DECKS AND ONLY WHERE APPROVED BY AMTECH SOLUTIONS.
(N) MIN. 12" FIRE TREATED CDX PLYWOOD
@ ALL VERTICAL SUBSTRATES. TYP.
4"
8"
6"
12"
12"
6"
6"
6"
6"
6"
6"
12"12"12"12" 12" 12"
12"
12"
FASTENER SCHEDULE:
ELEMENT SUBSTRATE FASTENER NUMBER AND SPACING
WOOD NAILER/BLOCKING
CONCRETE BLOCK OR MASONRY WALL 1
4" STAINLESS STEEL CONCRETE SCREWS
12'' O.C. MAX. STAGGERED (NOTE 1)
1.0" PENET., MIN. PULL-OUT RESISTANCE OF 1,000 POUNDS
HORIZONTAL WOOD NAILER #12 MIN. WOOD/STEEL SELF-DRILLING SCREWS
2 ROWS/9'' O.C. EACH ROW, MIN. (NOTE 1)
3/4'' PENET., MIN. PULLOUT RESISTANCE OF 100 POUNDS
VERTICAL WOOD NAILER #12 MIN. WOOD/STEEL SELF-DRILLING SCREWS
2 ROWS/9'' O.C. EACH ROW, MIN. (NOTE 1)
3/4'' PENET., MIN. PULLOUT RESISTANCE OF 100 POUNDS
WOOD DECK WOOD DECKING #15 CORROSION RESISTANT STEEL SCREWS PER SPECIFICATIONS
HOOK STRIP
(CLEAT METAL)
WOOD #8 WOOD SCREWS 8'' O.C. MAX. (NOTE 1)
CONCRETE 3
16" STAINLESS STEEL NAIL-IN EXPANSION FASTENER 6'' O.C. MAX. (NOTE 1)
METAL-ERA ANCHOR-TITE
RETAINER BAR
WOOD
#10 x 2" STAINLESS STEEL FASTENER PROVIDED BY
METAL-ERA
12" O.C. MAX. THROUGH SLOTTED HOLES.
METAL-ERA ANCHOR-TITE
CONTINUOUS CLEAT
MASONRY OR WOOD
4" x 1 14" MASONRY/WOOD FASTENER PROVIDED BY
METAL-ERA
24" O.C. MAX. THROUGH SLOTTED HOLES.
DRIP EDGE WOOD 4D RING SHANK NAILS.
SEE HOOK STRIP
2 ROWS/3"-4" O.C. MAX. STAGGERED (NOTE 1)
GRAVEL STOP
WOOD 4D RING SHANK NAILS.
SEE HOOK STRIP
2 ROWS/3"-4" O.C. MAX. STAGGERED (NOTE 1)
CONCRETE BLOCK OR MASONRY WALL
OUTSIDE-CONTINUOUS HOOK STRIP
INSIDE EDGE GALVANIZED ROOFING NAILS
SEE HOOK STRIP
12'' O.C. MAX. STAGGERED (NOTE 1)
TERMINATION BAR CONCRETE BLOCK OR MASONRY WALL 3
16" STAINLESS STEEL NAIL-IN EXPANSION FASTENERS 12'' O.C. MAX. (NOTE 1)
RTS/SEAM FASTENING PLATES
CONCRETE BLOCK OR MASONRY WALL 3
16" STAINLESS STEEL NAIL-IN EXPANSION FASTENERS
12'' O.C. MAX. (NOTE 1)
PLYWOOD/STEEL STUDS #15 CORROSION RESISTANT STEEL SCREWS
METAL FLASHING RECEIVER CONCRETE BLOCK OR MASONRY WALL 3
16" STAINLESS STEEL NAIL-IN EXPANSION FASTENERS 12'' O.C. MAX. (NOTE 1)
METAL COUNTER FLASHING METAL FLASHING RECEIVER #15 NEOPRENE WASHERED SELF-DRILLING SCREWS 8'' O.C. MAX. (NOTE 1)
PLYWOOD SHEATHING
(ILLUSTRATION BELOW)
METAL STUD FRAMING #15 CORROSION RESISTANT STEEL SCREWS
6" O.C. MAX. @ EDGES AND
12" O.C. MAX. IN THE FIELD @ EACH STUD LOCATION (NOTE 1)
CONCRETE BLOCK OR MASONRY WALL 3
16" STAINLESS STEEL NAIL-IN EXPANSION FASTENERS
METAL WALL PANELS
CONCRETE BLOCK OR MASONRY WALL CLAD WALL WITH PLYWOOD PRIOR TO PANEL INSTALL SEE PLYWOOD SHEATHING
PLYWOOD/STEEL STUDS
#10 CORROSION RESISTANT SELF-TAPPING
TEK SCREWS
12'' O.C. MAX. ALONG PANEL LEG (NOTE 1)
WALL PANEL
CLOSURE METALS
CONCRETE BLOCK OR MASONRY WALL CLAD WALL WITH PLYWOOD PRIOR TO PANEL INSTALL SEE PLYWOOD SHEATHING
PLYWOOD/STEEL STUDS
#10 CORROSION RESISTANT SELF-TAPPING
TEK SCREWS
8'' O.C. MAX. (NOTE 1)
STEEL MECHANICAL CURB WOOD #12 METAL TO WOOD FASTENER 6'' O.C. MAX. AROUND FULL CURB PERIMETER
NOTES:
1. FASTENER FREQUENCY SHALL BE DOUBLED WITHIN 10 FEET OF CORNERS.
ROOF REPLACEMENT SCOPE OF WORK:
1. THIS PROJECT IS FOR A COMPLETE ROOF TEAR OFF OF ALL EXISTING IN SCOPE ROOF
ASSEMBLIES DOWN TO THEIR CORRESPONDING ROOF DECKS. ROOF DECKS CONSIST OF:
1.1. METAL AND CONCRETE.
1.2. REFER TO TABLES 1.0, 1.1, AND 1.2 BELOW FOR EXISTING ASSEMBLY INFORMATION.
2. ALL EXISTING ROOF DECK SUBSTRATES WILL BE CLEANED AND PREPARED FOR THE
INSTALLATION OF THE FOLLOWING NEW ROOF ASSEMBLIES:
2.1. FULL STRENGTH CONCRETE DECK SUBSTRATE (STRUCTURAL SLOPE):
2.1.1. NEW 80-MIL (0.080-INCH) THERMOPLASTIC MEMBRANE - (FULLY ADHERED OVER)
2.1.2. NEW 1
2-INCH FIRE-TREATED, GYPSUM COVER BOARD WITH GLASS MAT FACERS
(48" X 48" BOARDS) - R-0.56 - (SET IN NEW LOW RISE FOAM ADHESIVE OVER)
2.1.3. TWO (2) NEW LAYERS OF 2.6-INCH POLYISOCYANURATE INSULATION (48" X 48"
BOARDS) - R-15.00 PER BOARD - (SET IN NEW LOW RISE FOAM ADHESIVE OVER)
2.1.4. NEW SELF ADHERED VAPOR RETARDER - (FULLY ADHERED OVER PRIMED
SUBSTRATE)
2.1.5. EXISTING CONCRETE ROOF DECK.
2.1.5.1. PREPARATION OF THE EXISTING ROOF DECK SUBSTRATES TO ENSURE
THEY ARE CLEANED AND PREPARED TO RECEIVE THE NEW ASSEMBLY.
2.1.6. TOTAL THERMAL RESISTANCE VALUE: R-30.56.
2.2. METAL DECK SUBSTRATE (STRUCTURAL SLOPE):
2.2.1. NEW 80-MIL (0.080-INCH) THERMOPLASTIC MEMBRANE - (FULLY ADHERED OVER)
2.2.2. NEW 1
2-INCH FIRE-TREATED, GYPSUM COVER BOARD WITH GLASS MAT FACERS
(48" x 48" BOARDS) - R-0.56 - (SET IN NEW LOW RISE FOAM ADHESIVE OVER)
2.2.3. TWO (2) NEW LAYERS OF 2.6-INCH POLYISOCYANURATE INSULATION (48" x 48"
BOARDS) - R-15.00 PER BOARD - (SET IN NEW LOW RISE FOAM ADHESIVE OVER)
2.2.4. NEW SELF ADHERED VAPOR RETARDER - (FULLY ADHERED OVER PRIMED
SUBSTRATE)
2.2.5. NEW 5
8-INCH FIRE-TREATED, GYPSUM SUBSTRATE BOARD WITH GLASS MAT
FACERS (48" x 48" BOARDS) - R-0.67 - (MECHANICALLY FASTENED WITH SCREWS
AND PLATES OVER)
2.2.6. EXISTING METAL ROOF DECK.
2.2.6.1. PREPARATION OF THE EXISTING ROOF DECK SUBSTRATES TO ENSURE
THEY ARE CLEANED AND PREPARED TO RECEIVE THE NEW ASSEMBLY.
2.2.7. TOTAL THERMAL RESISTANCE VALUE: R-31.23.
2.3. LIGHTWEIGHT CONCRETE DECK SUBSTRATE (ROOF ASSEMBLY SLOPE):
2.3.1. NEW 80-MIL (0.080-INCH) THERMOPLASTIC MEMBRANE - (FULLY ADHERED OVER)
2.3.2. NEW 1
2-INCH FIRE-TREATED, GYPSUM COVER BOARD WITH GLASS MAT FACERS
(48" X 48" BOARDS) - R-0.56 - (SET IN NEW LOW RISE FOAM ADHESIVE OVER)
2.3.3. NEW 1/4-INCH PER FOOT SLOPED POLYISOCYANURATE INSULATION - (SET IN
NEW LOW RISE FOAM ADHESIVE OVER)
2.3.3.1. ESTIMATED AVERAGE THICKNESS OF 2.50-INCHES AND A THERMAL
RESISTANCE VALUE OF R-14.17.
2.3.4. ONE (1) NEW BASE LAYERS OF 3.0-INCH POLYISOCYANURATE INSULATION (48" X
48" BOARDS) - R-17.40 PER BOARD - (SET IN NEW LOW RISE FOAM ADHESIVE
OVER)
2.3.5. ONE (1) LAYER OF NEW BASE SHEET OVER THE EXISTING DECK SUBSTRATE WITH
MANUFACTURER REQUIRED SIDE LAPS AND END LAPS - (MECHANICAL FASTENED
WITH NEW BASE SHEET FASTENERS OVER)
2.3.6. EXISTING LIGHTWEIGHT CONCRETE ROOF DECK.
2.3.6.1. PREPARATION OF THE EXISTING ROOF DECK SUBSTRATES TO ENSURE
THEY ARE CLEANED AND PREPARED TO RECEIVE THE NEW ASSEMBLY.
2.3.6.2. EXISTING CONCRETE TO HAVE ALL SURFACE VOIDS AND DAMAGES
REPAIRED WHERE CREATED FROM REMOVAL OF THE EXISTING ROOF
ASSEMBLY.
2.3.7. TOTAL AREA WEIGHTED THERMAL RESISTANCE VALUE: R-31.27.
ROOF ACCESSORY OPTIONS
1. ROOF ACCESSORY OPTIONS #1:
1.1. IN LIEU OF THE 80-MIL TPO MEMBRANE, FURNISH AND INSTALL A NEW 80-MIL PVC
MEMBRANE IN ACCORDANCE WITH THE PROJECT DOCUMENT REQUIREMENTS.
(ETR) CONCRETE DECK.
(N) FOAM ADHESIVE.
(N) RIGID INSULATION.
(N) RIGID INSULATION.
(N) SELF-ADHERED VAPOR
RETARDER OVER PRIMED
CONCRETE DECK.
(N) ASPHALTIC DECK PRIMER.
(N) PRE-PRIMED COVER BOARD.
(N) THERMOPLASTIC MEMBRANE (FA).
(ETR) METAL DECK.
(N) POLYISO. INSULATION.
(N) GYPSUM COVER BOARD.
(N) SELF-ADHERED VAPOR
RETARDER OVER PRIMED
SUBSTRATE BOARD.
(N) FOAM ADHESIVE.
(N) SUBSTRATE BOARD.
(N) ADHESIVE/PRIMER.
(N) POLYISO. INSULATION.
(N) FASTENERS AND
INSULATION PLATES.
(N) THERMOPLASTIC MEMBRANE (FA).
ROOF
AREA A
ROOF
AREA B
ROOF
AREA A
ROOF
AREA B
ROOF
AREA C
ROOF
AREA D
NOT IN
CONTRACT
ROOF
AREA A
(ETR) LIGHTWEIGHT OVER METAL DECK.
(N) RIGID INSULATION (FA).(N) FOAM ADHESIVE.
(N) TAPERED INSULATION (FA).
(N) COVER BOARD (FA).
(N) BASE SHEET (MA).
(N) BASE SHEET FASTENERS.
(N) THERMOPLASTIC MEMBRANE (FA).
PLOT SCALE IS 30x42
ISSUED FOR
SHEET NO.
SHEET TITLE
PROJECT
CLIENT
DATE REVISION
DRAWN BY
CHECKED BY
PROJECT NO.
DATE
LEGEND
OF
1720 South Bellaire Street, Suite 1200 Denver, Colorado 80222
(303) 738-0823 | www.amtechsls.com
AMTECH
SOLUTIONS
KEYPLAN LEGEND
DRAFT
THIS DOCUMENT
MAY NOT
BE USED FOR
CONSTRUCTION
COLORADO STATE
UNIVERSITY PUEBLO
2200 BONFORTE BOULEVARD
PUEBLO, COLORADO 81001
2023-020M22
CSU PUEBLO ROOFING PROJECT
2200 BONFORTE BOULEVARD
PUEBLO, COLORADO 81001
DEN.2023.001022
10/2023
BID RELEASE
RKP & SAP
DD
ROOF ASSEMBLIES
R-102 03 14
ROOF ASSEMBLY NOTES:
1. GENERAL:
1.1. VERIFY THAT SUBSTRATES ARE DRY, CLEAN, SMOOTH AND FREE OF SHARP EDGES, BURRS, DEEP DEPRESSIONS, LOOSE
MATERIAL, OIL, GREASE OR OTHER FOREIGN MATERIAL PRIOR TO INSTALLATION.
1.2. BEGINNING INSTALLATION MEANS ACCEPTANCE OF ALL EXISTING SURFACE CONDITIONS.
1.3. NEATLY CUT AND FIT MATERIALS AROUND PENETRATIONS AND PROJECTIONS.
1.4. ONLY DRY MATERIALS ARE TO BE INSTALLED AND ONLY AS MUCH AS CAN BE COMPLETED AND DETAILED THE SAME DAY.
1.5. ALL MATERIAL THAT HAS BECOME WET DURING STORAGE WILL BE MARKED AND REMOVED FROM THE JOBSITE BY THE
CONTRACTOR.
1.6. COORDINATE AND CONFIRM THAT MANUFACTURER'S ASSEMBLY MEETS OR EXCEEDS THE MINIMUM SPECIFIED ROOF
ASSEMBLY RATING.
1.7. LISTED ATTACHMENT CRITERIA ARE MINIMUMS; ADDITIONAL OR ENHANCED ATTACHMENT REQUIRED BY
MANUFACTURER'S IS TO BE PROVIDED AT NO ADDITIONAL COST.
2. BARE BACK THERMOPLASTIC MEMBRANES:
2.1. MEMBRANE SHEET MUST BE LOOSELY LAID OUT AND ALLOWED TO RELAX FOR A MINIMUM OF 30-MINUTES PRIOR TO
INSTALLATION.
2.2. BONDING ADHESIVES ARE TO BE APPLIED IN FULL COVERAGE, EVENLY, TO BOTH THE SUBSTRATE AND THE BACK OF THE
MEMBRANE SHEET.
2.3. ALLOW THE ADHESIVE TO DRY TO A POINT OF BEING TACKY, BUT NOT STRINGY TO THE TOUCH. DO NOT ALLOW
ADHESIVE TO “DRY OUT” COMPLETELY. THE MEMBRANE AND SUBSTRATE WILL BE DRY (NON-TACKY) TO THE FINGER
TOUCH.
2.4. NO ADHESIVE SHALL BE APPLIED TO THE LAP “SEAM” AREAS OF THE MEMBRANE WHERE HEAT WELDING WILL OCCUR.
2.5. ENSURE SHEETS ARE INSTALLED WITH LAPS SHINGLED IN THE DIRECTION OF THE ROOF SLOPE DRAINAGE, TO PREVENT
BACKWATER LAPS.
2.6. ALL SEAMS SHALL BE HOT-AIR WELDED.
2.7. ALL FIELD SEAMS EXCEEDING 10 FEET IN LENGTH SHALL BE WELDED WITH AN APPROVED AUTOMATIC TEMPERATURE
COMPENSATING WELDER.
2.8. SEAM OVERLAPS SHOULD BE 3-INCHES WIDE WHEN AUTOMATIC MACHINE-WELDING AND 4-INCHES WIDE WHEN
HAND-WELDING, EXCEPT FOR CERTAIN DETAILS.
3. COVER BOARD:
3.1. BOARDS ARE TO BE INSTALLED WITH A MINIMUM 12-INCH MATERIAL STAGGER IN ALL DIRECTIONS.
3.2. GAPS BETWEEN BOARDS GREATER THAN 1
8-INCH ARE NOT ALLOWED. FILL GAPS WITH ADDITIONAL MATERIAL OR
LOW-RISE FOAM ADHESIVE.
3.3. ALL COVER BOARDS INSTALLED IN FOAM ADHESIVE SHALL BE STEPPED INTO PLACE AND POSITIONED; WEIGHTED DOWN WITH FULL 5-GAL ADHESIVE PAILS (35# WEIGHT MINIMUM) UNTIL THE BEAD FOAM ADHESIVE HAS SET.
3.3.1. WEIGHTS ARE TO BE POSITIONED WITH ONE IN THE CENTER AND ONE ON EACH CORNER, SO THAT NO CUPPING OR
LACK OF ADHESION OCCURS. INSULATION THAT 'BOUNCES' OR DEPRESSES UNDER FOOT PRESSURE IS
UNACCEPTABLE.
3.4. WEIGHTS ARE TO REMAIN IN PLACE ON THE COVER BOARDS FOR A MINIMUM OF 10 MINUTES.
4. INSULATION:
4.1. BOARDS ARE TO BE INSTALLED WITH A MINIMUM 12-INCH MATERIAL STAGGER IN ALL DIRECTIONS. STAGGER ADDITIONAL
LAYERS OF INSULATION A MINIMUM OF 18-INCHES FROM THE PREVIOUS LAYER.
4.2. GAPS BETWEEN BOARDS GREATER THAN 1
8-INCH ARE NOT ALLOWED. FILL GAPS WITH ADDITIONAL MATERIAL OR
LOW-RISE FOAM ADHESIVE.
4.3. ALL INSULATION INSTALLED IN FOAM ADHESIVE SHALL BE STEPPED INTO PLACE AND POSITIONED; WEIGHTED DOWN WITH FULL 5-GAL ADHESIVE PAILS (35# WEIGHT MINIMUM) UNTIL THE BEAD FOAM ADHESIVE HAS SET.
4.3.1. WEIGHTS ARE TO BE POSITIONED WITH ONE IN THE CENTER AND ONE ON EACH CORNER, SO THAT NO CUPPING OR
LACK OF ADHESION OCCURS. INSULATION THAT 'BOUNCES' OR DEPRESSES UNDER FOOT PRESSURE IS
UNACCEPTABLE.
4.4. WEIGHTS ARE TO REMAIN IN PLACE ON THE INSULATION FOR A MINIMUM OF 10 MINUTES.
5. SUBSTRATE BOARD:
5.1. BOARDS ARE TO BE INSTALLED WITH A MINIMUM 12-INCH MATERIAL STAGGER IN ALL DIRECTIONS.
5.2. GAPS BETWEEN BOARDS GREATER THAN 1
8-INCH ARE NOT ALLOWED. FILL GAPS WITH ADDITIONAL MATERIAL OR
LOW-RISE FOAM ADHESIVE.
ROOF ASSEMBLY @ CONCRETE ROOF DECKS
NOTE: SIMILAR - ACTUAL CONDITIONS MAY VARY (N.T.S.)
ROOF ASSEMBLY @ METAL ROOF DECKS
NOTE: SIMILAR - ACTUAL CONDITIONS MAY VARY (N.T.S.)
ROOF ASSEMBLY @ LIGHTWEIGHT CONCRETE ROOF DECKS
NOTE: SIMILAR - ACTUAL CONDITIONS MAY VARY (N.T.S.)
B
ROOF ASSEMBLY KEY PLAN @ THE MUSIC BUILDING
NOTE: SIMILAR - ACTUAL CONDITIONS MAY VARY (N.T.S.)
C
ROOF ASSEMBLY KEY PLAN @ THE PLANT BUILDING
NOTE: SIMILAR - ACTUAL CONDITIONS MAY VARY (N.T.S.)
A
ROOF ASSEMBLY KEY PLAN @ THE HEAT BUILDING
NOTE: SIMILAR - ACTUAL CONDITIONS MAY VARY (N.T.S.)
ROOF REPLACEMENT @ CONCRETE ROOF DECKS.
RE: 1/R-102 & S.O.W. NOTE 2.1.
ROOF ASSEMBLY LEGEND:
ROOF REPLACEMENT @ METAL ROOF DECKS.
RE: 2/R-102 & S.O.W. NOTE 2.2.
ROOF REPLACEMENT @ LIGHTWEIGHT CONCRETE OVER METAL ROOF DECKS.
RE: 3/R-102 - S.O.W. NOTE 2.3.
25'-0" MIN.
TYP.
8-0" MIN.
TYP.
25'-0" MIN.
TYP.
25'-0" MIN.
TYP.
25'-0" MIN.
TYP.
25'-0" MIN.
TYP.
25'-0" MIN.
TYP.
25'-0" MIN.
TYP.
25'-0" MIN.
TYP.
8-0" MIN.
TYP.
25'-0" MIN.
TYP.
25'-0" MIN.
TYP.
8-0" MIN.
TYP.
25'-0" MIN.
TYP.
25'-0" MIN.
TYP.
25'-0" MIN.
TYP.
8-0" MIN.
TYP.
ROOF
AREA A
ROOF
AREA B
ROOF
AREA C
ROOF
AREA D
NOT IN
CONTRACT
PLAN
NORTH
TRUE
NORTH
PLOT SCALE IS 30x42
ISSUED FOR
SHEET NO.
SHEET TITLE
PROJECT
CLIENT
DATE REVISION
DRAWN BY
CHECKED BY
PROJECT NO.
DATE
LEGEND
OF
1720 South Bellaire Street, Suite 1200 Denver, Colorado 80222
(303) 738-0823 | www.amtechsls.com
AMTECH
SOLUTIONS
KEYPLAN LEGEND
DRAFT
THIS DOCUMENT
MAY NOT
BE USED FOR
CONSTRUCTION
COLORADO STATE
UNIVERSITY PUEBLO
2200 BONFORTE BOULEVARD
PUEBLO, COLORADO 81001
2023-020M22
CSU PUEBLO ROOFING PROJECT
2200 BONFORTE BOULEVARD
PUEBLO, COLORADO 81001
DEN.2023.001022
10/2023
BID RELEASE
RKP & SAP
DD
WIND DESIGN
R-200 04 14
D
WIND ZONE KEY PLAN @ THE MUSIC BUILDING
NOTE: SIMILAR - ACTUAL CONDITIONS MAY VARY (N.T.S.)
ZONE 1 =
ZONE 2 =
ZONE 3 =
ZONE 1' =
WIND DESIGN NOTES:
1. DESIGN ASSUMPTIONS:
1.1. 2021 INTERNATIONAL EXISTING BUILDING CODE
1.1.1. ALTERATION LEVEL 1 - REMOVE AND REPLACE WITH LIKE.
1.2. 2021 INTERNATIONAL BUILDING CODE.
1.3. WIND DESIGN: ASCE 7-16
1.3.1. 3-SECOND PEAK GUST: 113 MPH
1.3.2. EXPOSURE: C
1.3.3. CLIMATE ZONES: 5B
1.3.4. CONFIGURATION: ENCLOSED
1.3.5. RISK CATEGORY: III
ASCE 7 - STRENGTH DESIGN VALUES:
1. ROOF AREAS A, B, C, AND D:
1.1. DESIGN HEIGHT (H): 40-FEET
1.1.1. 0.6h: 25.0-FEET
1.1.2. 0.2h: 8.0-FEET
1.2. ZONE 1' FIELD: -31.3 PSF
1.3. ZONE 1 FIELD: -54.4 PSF
1.4. ZONE 2 EDGE: -71.8 PSF
1.5. ZONE 3 CORNER: -97.9 PSF
1.6. ZONE 4 WALL FIELD: -37.1 PSF
1.7. ZONE 5 WALL CORNER: -45.8 PSF
0.6h 0.6h
0.6h
0.6h
0.6h
0.6h
0.2h
0.2h
ZONE 3
ZONE
1'
ZONE
ZONE
ZONE
ZONE 4 =
ZONE 5 =
ZONE 4
ZONE 5
a a h
6'-0" MIN.
TYP.
18'-0" MIN.
TYP.
6'-0" MIN.
TYP.
18'-0" MIN.
TYP.
PLAN
NORTH
TRUE
NORTH
PLOT SCALE IS 30x42
ISSUED FOR
SHEET NO.
SHEET TITLE
PROJECT
CLIENT
DATE REVISION
DRAWN BY
CHECKED BY
PROJECT NO.
DATE
LEGEND
OF
1720 South Bellaire Street, Suite 1200 Denver, Colorado 80222
(303) 738-0823 | www.amtechsls.com
AMTECH
SOLUTIONS
KEYPLAN LEGEND
DRAFT
THIS DOCUMENT
MAY NOT
BE USED FOR
CONSTRUCTION
COLORADO STATE
UNIVERSITY PUEBLO
2200 BONFORTE BOULEVARD
PUEBLO, COLORADO 81001
2023-020M22
CSU PUEBLO ROOFING PROJECT
2200 BONFORTE BOULEVARD
PUEBLO, COLORADO 81001
DEN.2023.001022
10/2023
BID RELEASE
RKP & SAP
DD
WIND DESIGN
R-201 05 14
E
WIND ZONE KEY PLAN @ THE HEAT BUILDING
NOTE: SIMILAR - ACTUAL CONDITIONS MAY VARY (N.T.S.)
ZONE 1 =
ZONE 2 =
ZONE 3 =
ZONE 1' =
WIND DESIGN NOTES:
1. DESIGN ASSUMPTIONS:
1.1. 2021 INTERNATIONAL EXISTING BUILDING CODE
1.1.1. ALTERATION LEVEL 1 - REMOVE AND REPLACE WITH LIKE.
1.2. 2021 INTERNATIONAL BUILDING CODE.
1.3. WIND DESIGN: ASCE 7-16
1.3.1. 3-SECOND PEAK GUST: 113 MPH
1.3.2. EXPOSURE: C
1.3.3. CLIMATE ZONES: 5B
1.3.4. CONFIGURATION: ENCLOSED
1.3.5. RISK CATEGORY: III
ASCE 7 - STRENGTH DESIGN VALUES:
1. MAIN ROOF AREA:
1.1. DESIGN HEIGHT (H): 30-FEET
1.1.1. 0.6h: 18.0-FEET
1.1.2. 0.2h: 6.0-FEET
1.2. ZONE 1' FIELD: 29.4 PSF
1.3. ZONE 1 FIELD: 51.2 PSF
1.4. ZONE 2 EDGE: 67.5 PSF
1.5. ZONE 3 CORNER: 92.0 PSF
1.6. ZONE 4 WALL FIELD: 34.9 PSF
1.7. ZONE 5 WALL CORNER: 43.0 PSF
0.6h 0.6h
0.6h
0.6h
0.6h
0.6h
0.2h
0.2h
ZONE 3
ZONE
1'
ZONE
ZONE
ZONE
ZONE 4 =
ZONE 5 =
ZONE 4
ZONE 5
ROOF
AREA B
ROOF
AREA A
12'-0" MIN.
TYP.4'-0" MIN.
TYP.
12'-0" MIN.
TYP.
4'-0" MIN.
TYP.
12'-0" MIN.
TYP.
12'-0" MIN.
TYP.
12'-0" MIN.
TYP.
12'-0" MIN.
TYP.
12'-0" MIN.
TYP.
12'-0" MIN.
TYP.
12'-0" MIN.
TYP.
12'-0" MIN.
TYP.
12'-0" MIN.
TYP.
12'-0" MIN.
TYP.
12'-0" MIN.
TYP.
12'-0" MIN.
TYP.
4'-0" MIN.
TYP.
4'-0" MIN.
TYP.
4'-0" MIN.
TYP.
4'-0" MIN.
TYP.
PLAN
NORTH
TRUE
NORTH
PLOT SCALE IS 30x42
ISSUED FOR
SHEET NO.
SHEET TITLE
PROJECT
CLIENT
DATE REVISION
DRAWN BY
CHECKED BY
PROJECT NO.
DATE
LEGEND
OF
1720 South Bellaire Street, Suite 1200 Denver, Colorado 80222
(303) 738-0823 | www.amtechsls.com
AMTECH
SOLUTIONS
KEYPLAN LEGEND
DRAFT
THIS DOCUMENT
MAY NOT
BE USED FOR
CONSTRUCTION
COLORADO STATE
UNIVERSITY PUEBLO
2200 BONFORTE BOULEVARD
PUEBLO, COLORADO 81001
2023-020M22
CSU PUEBLO ROOFING PROJECT
2200 BONFORTE BOULEVARD
PUEBLO, COLORADO 81001
DEN.2023.001022
10/2023
BID RELEASE
RKP & SAP
DD
WIND DESIGN
R-202 06 14
F
WIND ZONE KEY PLAN @ THE PLANT BUILDING
NOTE: SIMILAR - ACTUAL CONDITIONS MAY VARY (N.T.S.)
ZONE 1 =
ZONE 2 =
ZONE 3 =
ZONE 1' =
WIND DESIGN NOTES:
1. DESIGN ASSUMPTIONS:
1.1. 2021 INTERNATIONAL EXISTING BUILDING CODE
1.1.1. ALTERATION LEVEL 1 - REMOVE AND REPLACE WITH LIKE.
1.2. 2021 INTERNATIONAL BUILDING CODE.
1.3. WIND DESIGN: ASCE 7-16
1.3.1. 3-SECOND PEAK GUST: 113 MPH
1.3.2. EXPOSURE: C
1.3.3. CLIMATE ZONES: 5B
1.3.4. CONFIGURATION: ENCLOSED
1.3.5. RISK CATEGORY: III
ASCE 7 - STRENGTH DESIGN VALUES:
1. ROOF AREAS A AND B:
1.1. DESIGN HEIGHT (H): 20-FEET
1.1.1. 0.6h: 12.0-FEET
1.1.2. 0.2h: 4.0-FEET
1.2. ZONE 1' FIELD: -27.0 PSF
1.3. ZONE 1 FIELD: -47.0 PSF
1.4. ZONE 2 EDGE: -62.0 PSF
1.5. ZONE 3 CORNER: -84.5 PSF
1.6. ZONE 4 WALL FIELD: -32.0 PSF
1.7. ZONE 5 WALL CORNER: -39.5 PSF
0.6h 0.6h
0.6h
0.6h
0.6h
0.6h
0.2h
0.2h
ZONE 3
ZONE
1'
ZONE
ZONE
ZONE
ZONE 4 =
ZONE 5 =
ZONE 4
ZONE 5
1. CONTRACTOR TO REMOVE ONLY AS MUCH ROOFING PER DAY AS THEY ARE ABLE TO MAKE WATERTIGHT AND SECURE AT THE END OF THEIR WORK DAY. ANY DAMAGE CAUSED BY WEATHER OR OTHER ELEMENTS AS A RESULT OF UNFINISHED ROOFING WILL BE THE FULL RESPONSIBILITY OF THE CONTRACTOR. THE CONTRACTOR WILL REPLACE/REPAIR ALL INTERIOR AND EXTERIOR DAMAGE, RESULTING FROM
UNFINISHED/UNPROTECTED ROOF CONSTRUCTION AT THEIR OWN EXPENSE.
2. ALL CONDITIONS OR PENETRATIONS MAY NOT BE SHOWN. THE CONTRACTOR IS RESPONSIBLE FOR FIELD VERIFYING ALL EXISTING
CONDITIONS AND MEASUREMENTS.
3. DETAIL CALL OUTS AND KEY NOTES MAY ONLY BE REFERENCED ONCE ON THE DRAWINGS. ONCE A PARTICULAR CALL OUT OR KEY NOTE HAS BEEN REFERENCED OR INDICATED BY LEGEND, IT MAY NOT BE REFERENCED AGAIN ON THE DRAWINGS, BUT ITS USE SHALL BE TYPICAL.
4. ROOF TAPER PLANS ARE PRELIMINARY. ROOFING CONTRACTOR TO FIELD VERIFY ALL DIMENSIONS AND COORDINATE WITH ROOF MEMBRANE MANUFACTURER AND/ OR SUPPLIER FOR FINAL DRAINAGE TAPER PLANS TO BE REVIEWED AND APPROVED BY AMTECH PRIOR TO
CONSTRUCTION.
5. GRID LINES ARE FOR REFERNCE ONLY.
RD RD
RD
RD RDOF
OF OF
OF
OF
RD
TWS TWS
TWS
RIDGE RIDGE
VP
VP
VP
E E
E
EEEEEEEEEEEEEEEEE
VP
VP
VP
ROOF
AREA A
ROOF
AREA B
ROOF
AREA C
ROOF
AREA D
A B C E F GD
W R
-E X
. JT
W R
-E X
. JT
W R
-E X
. JT
W R
-E X
. JT
W R
-E X
. JT
WR-EX. JT.
WR-EX. JT.
WR-EX. JT.
WR-EX. JT.
WR-EX. JT.
NOT IN
CONTRACT
R-500
R-400
R-500
R-400
R-500
R-400 SIM
R-500
R-400
R-500
R-400
R-500
R-400
R-500
R-400
R-600LOW
R-600
LO
W
R-500
R-400
HIG
H
HIG
H
R-500
R-400
HIGH
R-500
R-400
HIG
H
HIG
H
R-500
R-500
HIG
H
HIGH
HIGH
1A R-501
1A R-501
R-502
R-400
R-503
LO
W
R-600
R-502
7B R-502
7B R-502
7B R-502
7B R-502
7B R-502
7A R-502
7A R-502
7A R-502
R-503
R-503
R-503
R-503
R-503
LO
W
R-503
LOW
HIG
H
LO
W
R-600
LO
W
1A&2A R-600
1A&2A R-600
SIM
. LOW
LOW
ACCU
R-503
R-503
R-503
SIM
OF
AB
GAS
E
R-###
SECTION AND DETAIL REFERENCE
NOT IN CONTRACT
ROOFING KEY NOTE
STRUCTURAL ROOF SLOPE
8" TAPERED ROOF SLOPE
RIDGE LINE
VALLEY LINE
PRIMARY ROOF DRAIN
OVERFLOW ROOF DRAIN
THRU-WALL ROOF DRAIN
THRU-WALL SCUPPER
OVERFLOW SCUPPER
ROOF HATCH
WALL-TO-ROOF EXPANSION JOINT
ROOF-TO-ROOF EXPANSION JOINT
CONTROL JOINT
EXISTING GAS LINE
EXISTING CONDUIT LINE
EXISTING LIGHTNING PROTECTION
HOT STACK PENETRATION
VENT PIPE PENETRATION
SOIL PIPE PENETRATION
DAVIT ARM PENETRATION
TIE-BACK ANCHOR PENETRATION
ELECTRICAL LINE PENETRATION
GAS LINE PENETRATION
PIPE PENETRATION
ROOF TOP UNIT
EXHAUST HOOD
EXHAUST FAN
MECHANICAL EQUIPMENT CURB
FREE STANDING MECHANICAL EQUIPMENT.
ABANDONED EQUIPMENT/CURB TO BE
REMOVED AT OWNERS DIRECTION
NEW 12" TAPERED CRICKETS WITH 6"
TAPERED EDGE STRIP
NEW 14" TAPERED CRICKETS WITH 6"
TAPERED EDGE STRIP
NEW WALKWAY PAD
SKYLIGHT
SPLASH BLOCK
ROOF AREA ELEVATION OFFSET
ROOFING DETAIL NUMBER
ROOFING PAGE NUMBER
RD
OF
WD
TWS
RH
EH
EF
RR-EX. JT.
RTU
SL
OFS
SP
VP
HS
TA
EP
WR-EX. JT.
MC
SB
DA
GP
PP
ACCU
CTRL. JT.
KEYNOTES:
1. APPROXIMATE DOWNSPOUT(S) LOCATION - CONTRACTOR
TO FIELD VERIFY.
1.1. REMOVE AND DISPOSE OF EXISTING DOWNSPOUT
AND INSTALL NEW OPEN FACE DOWNSPOUTS
INSTALLED PER SPECIFICATION REQUIREMENTS.
1.2. CONTRACTOR TO ENSURE NEW DOWNSPOUTS AND
DOWNSPOUT OUTLETS MEET SIZING
REQUIREMENTS AS DEFINED BY CODE.
2. EXISTING ROOF TOP UNIT TO BE RAISED TO MEET THE
MINIMUM 8-INCH FLASHING REQUIREMENTS. EXTEND ALL
DUCT WORK AND ELECTRICAL AS REQUIRED.
3. CONTRACTOR TO COORDINATE WITH OWNER PRIOR TO
ABANDONED CURB/PENETRATION REMOVAL. ALL
ABANDONED CURBS MARKED FOR REMOVAL WILL NEED
TO HAVE THE ROOF DECK OPENINGS PATCHED AND
REPAIRED WITH NEW ROOFING INSTALLED OVER THESE
LOCATIONS. OVERLAY DECK WITH NEW MINIMUM 3'x3'
16-GA. SHEET METAL FLAT STOCK FOR OPENINGS THAT
ARE 2'x2' OR LESS. FASTEN NEW FLAT STOCK SHEET
METAL AT 6-INCHES ON CENTER AT 3-INCHES FROM THE
EDGE OF THE DECK OPENING. TYPICAL.
4. CONTRACTOR TO COORDINATE WITH OWNER REGARDING
ALL WALL MOUNTED ELECTRICAL UNITS, CAMERAS, AND
UNISTRUT SUPPORTS WHERE INTERFERENCE WITH
ROOFING WORK MAY OCCUR. ELECTRICAL TO ONLY BE
REMOVED AND REINSTALLED PER THE OWNER'S
DIRECTION.
5. EXISTING THROUGH DECK PIPE PENETRATION TO BE
RELOCATED A MINIMUM OF 24-INCHES AWAY FROM THE
NEW CONTROL JOINT WALL FLASHING.
6. NEW ROOF MEMBRANE WALL FLASHING AND PLYWOOD TO
BE EXTENDED UP FULL FACE OF INTERIOR SUBSTRATE
ALONG THE EAST AND SOUTH AREA D WALLS.
7. EXISTING HOOD VENT HATCH TO BE REMOVED, DISPOSED,
AND REPLACED WITH A NEW PREFABRICATED CODE
COMPLIANT ROOF HATCH WITH SAFETY RAIL. REFER TO
SPECIFICATION SECTION 07 7200 FOR ADDITIONAL
INFORMATION.
A
ROOF PLAN - THE MUSIC BUILDING
NOTE: SIMILAR - ACTUAL CONDITIONS MAY VARY (N.T.S.)
PLAN
NORTH
TRUE
NORTH
PLOT SCALE IS 30x42
ISSUED FOR
SHEET NO.
SHEET TITLE
PROJECT
CLIENT
DATE REVISION
DRAWN BY
CHECKED BY
PROJECT NO.
DATE
LEGEND
OF
1720 South Bellaire Street, Suite 1200 Denver, Colorado 80222
(303) 738-0823 | www.amtechsls.com
AMTECH
SOLUTIONS
KEYPLAN LEGEND
DRAFT
THIS DOCUMENT
MAY NOT
BE USED FOR
CONSTRUCTION
COLORADO STATE
UNIVERSITY PUEBLO
2200 BONFORTE BOULEVARD
PUEBLO, COLORADO 81001
2023-020M22
CSU PUEBLO ROOFING PROJECT
2200 BONFORTE BOULEVARD
PUEBLO, COLORADO 81001
DEN.2023.001022
10/2023
BID RELEASE
RKP & SAP
DD
ROOF PLAN
R-300 07 14
1. CONTRACTOR TO REMOVE ONLY AS MUCH ROOFING PER DAY AS THEY ARE ABLE TO MAKE WATERTIGHT AND SECURE AT THE END OF THEIR WORK DAY. ANY DAMAGE CAUSED BY WEATHER OR OTHER ELEMENTS AS A RESULT OF UNFINISHED ROOFING WILL BE THE FULL RESPONSIBILITY OF THE CONTRACTOR. THE CONTRACTOR WILL REPLACE/REPAIR ALL INTERIOR AND EXTERIOR DAMAGE, RESULTING FROM
UNFINISHED/UNPROTECTED ROOF CONSTRUCTION AT THEIR OWN EXPENSE.
2. ALL CONDITIONS OR PENETRATIONS MAY NOT BE SHOWN. THE CONTRACTOR IS RESPONSIBLE FOR FIELD VERIFYING ALL EXISTING
CONDITIONS AND MEASUREMENTS.
3. DETAIL CALL OUTS AND KEY NOTES MAY ONLY BE REFERENCED ONCE ON THE DRAWINGS. ONCE A PARTICULAR CALL OUT OR KEY NOTE HAS BEEN REFERENCED OR INDICATED BY LEGEND, IT MAY NOT BE REFERENCED AGAIN ON THE DRAWINGS, BUT ITS USE SHALL BE TYPICAL.
4. ROOF TAPER PLANS ARE PRELIMINARY. ROOFING CONTRACTOR TO FIELD VERIFY ALL DIMENSIONS AND COORDINATE WITH ROOF MEMBRANE MANUFACTURER AND/ OR SUPPLIER FOR FINAL DRAINAGE TAPER PLANS TO BE REVIEWED AND APPROVED BY AMTECH PRIOR TO
CONSTRUCTION.
5. GRID LINES ARE FOR REFERNCE ONLY.
RD
RD
RD
RDRD RD
RH MC MC MC MC
MCMCMCMCMC
HS
VP
VP
VP
VP
VP
VP
VP
VP
AB
AB
AB
AB
AB
AB
AB
AB
AB
AB
AB
AB
ABAB
MC
MC
MC
A B
R-500
R-500
R-500
R-500
R-501
R-501
4A R-501
4A R-501
4A R-501
R-502
7A R-502
7A R-502
7A R-502
7A R-502
7B R-502
7B R-502
7B R-502
7B R-502
R-502
R-502
22222
AB
GAS
E
R-###
SECTION AND DETAIL REFERENCE
NOT IN CONTRACT
ROOFING KEY NOTE
STRUCTURAL ROOF SLOPE
8" TAPERED ROOF SLOPE
RIDGE LINE
VALLEY LINE
PRIMARY ROOF DRAIN
OVERFLOW ROOF DRAIN
THRU-WALL ROOF DRAIN
THRU-WALL SCUPPER
OVERFLOW SCUPPER
ROOF HATCH
WALL-TO-ROOF EXPANSION JOINT
ROOF-TO-ROOF EXPANSION JOINT
CONTROL JOINT
EXISTING GAS LINE
EXISTING CONDUIT LINE
EXISTING LIGHTNING PROTECTION
HOT STACK PENETRATION
VENT PIPE PENETRATION
SOIL PIPE PENETRATION
DAVIT ARM PENETRATION
TIE-BACK ANCHOR PENETRATION
ELECTRICAL LINE PENETRATION
GAS LINE PENETRATION
PIPE PENETRATION
ROOF TOP UNIT
EXHAUST HOOD
EXHAUST FAN
MECHANICAL EQUIPMENT CURB
FREE STANDING MECHANICAL EQUIPMENT.
ABANDONED EQUIPMENT/CURB TO BE
REMOVED AT OWNERS DIRECTION
NEW 12" TAPERED CRICKETS WITH 6"
TAPERED EDGE STRIP
NEW 14" TAPERED CRICKETS WITH 6"
TAPERED EDGE STRIP
NEW WALKWAY PAD
SKYLIGHT
SPLASH BLOCK
ROOF AREA ELEVATION OFFSET
ROOFING DETAIL NUMBER
ROOFING PAGE NUMBER
RD
OF
WD
TWS
RH
EH
EF
RR-EX. JT.
RTU
SL
OFS
SP
VP
HS
TA
EP
WR-EX. JT.
MC
SB
DA
GP
PP
ACCU
CTRL. JT.
KEYNOTES:
1. APPROXIMATE DOWNSPOUT(S) LOCATION - CONTRACTOR
TO FIELD VERIFY.
1.1. REMOVE AND DISPOSE OF EXISTING DOWNSPOUT
AND INSTALL NEW OPEN FACE DOWNSPOUTS
INSTALLED PER SPECIFICATION REQUIREMENTS.
1.2. CONTRACTOR TO ENSURE NEW DOWNSPOUTS AND
DOWNSPOUT OUTLETS MEET SIZING
REQUIREMENTS AS DEFINED BY CODE.
2. EXISTING ROOF TOP UNIT TO BE RAISED TO MEET THE
MINIMUM 8-INCH FLASHING REQUIREMENTS. EXTEND ALL
DUCT WORK AND ELECTRICAL AS REQUIRED.
3. CONTRACTOR TO COORDINATE WITH OWNER PRIOR TO
ABANDONED CURB/PENETRATION REMOVAL. ALL
ABANDONED CURBS MARKED FOR REMOVAL WILL NEED
TO HAVE THE ROOF DECK OPENINGS PATCHED AND
REPAIRED WITH NEW ROOFING INSTALLED OVER THESE
LOCATIONS. OVERLAY DECK WITH NEW MINIMUM 3'x3'
16-GA. SHEET METAL FLAT STOCK FOR OPENINGS THAT
ARE 2'x2' OR LESS. FASTEN NEW FLAT STOCK SHEET
METAL AT 6-INCHES ON CENTER AT 3-INCHES FROM THE
EDGE OF THE DECK OPENING. TYPICAL.
4. CONTRACTOR TO COORDINATE WITH OWNER REGARDING
ALL WALL MOUNTED ELECTRICAL UNITS, CAMERAS, AND
UNISTRUT SUPPORTS WHERE INTERFERENCE WITH
ROOFING WORK MAY OCCUR. ELECTRICAL TO ONLY BE
REMOVED AND REINSTALLED PER THE OWNER'S
DIRECTION.
5. EXISTING THROUGH DECK PIPE PENETRATION TO BE
RELOCATED A MINIMUM OF 24-INCHES AWAY FROM THE
NEW CONTROL JOINT WALL FLASHING.
6. NEW ROOF MEMBRANE WALL FLASHING AND PLYWOOD TO
BE EXTENDED UP FULL FACE OF INTERIOR SUBSTRATE
ALONG THE EAST AND SOUTH AREA D WALLS.
7. EXISTING HOOD VENT HATCH TO BE REMOVED, DISPOSED,
AND REPLACED WITH A NEW PREFABRICATED CODE
COMPLIANT ROOF HATCH WITH SAFETY RAIL. REFER TO
SPECIFICATION SECTION 07 7200 FOR ADDITIONAL
INFORMATION.
B
ROOF PLAN - THE HEAT BUILDING
NOTE: SIMILAR - ACTUAL CONDITIONS MAY VARY (N.T.S.)
PLAN
NORTH
TRUE
NORTH
PLOT SCALE IS 30x42
ISSUED FOR
SHEET NO.
SHEET TITLE
PROJECT
CLIENT
DATE REVISION
DRAWN BY
CHECKED BY
PROJECT NO.
DATE
LEGEND
OF
1720 South Bellaire Street, Suite 1200 Denver, Colorado 80222
(303) 738-0823 | www.amtechsls.com
AMTECH
SOLUTIONS
KEYPLAN LEGEND
DRAFT
THIS DOCUMENT
MAY NOT
BE USED FOR
CONSTRUCTION
COLORADO STATE
UNIVERSITY PUEBLO
2200 BONFORTE BOULEVARD
PUEBLO, COLORADO 81001
2023-020M22
CSU PUEBLO ROOFING PROJECT
2200 BONFORTE BOULEVARD
PUEBLO, COLORADO 81001
DEN.2023.001022
10/2023
BID RELEASE
RKP & SAP
DD
R-301 08 14
1. CONTRACTOR TO REMOVE ONLY AS MUCH ROOFING PER DAY AS THEY ARE ABLE TO MAKE WATERTIGHT AND SECURE AT THE END OF THEIR WORK DAY. ANY DAMAGE CAUSED BY WEATHER OR OTHER ELEMENTS AS A RESULT OF UNFINISHED ROOFING WILL BE THE FULL RESPONSIBILITY OF THE CONTRACTOR. THE CONTRACTOR WILL REPLACE/REPAIR ALL INTERIOR AND EXTERIOR DAMAGE, RESULTING FROM
UNFINISHED/UNPROTECTED ROOF CONSTRUCTION AT THEIR OWN EXPENSE.
2. ALL CONDITIONS OR PENETRATIONS MAY NOT BE SHOWN. THE CONTRACTOR IS RESPONSIBLE FOR FIELD VERIFYING ALL EXISTING
CONDITIONS AND MEASUREMENTS.
3. DETAIL CALL OUTS AND KEY NOTES MAY ONLY BE REFERENCED ONCE ON THE DRAWINGS. ONCE A PARTICULAR CALL OUT OR KEY NOTE HAS BEEN REFERENCED OR INDICATED BY LEGEND, IT MAY NOT BE REFERENCED AGAIN ON THE DRAWINGS, BUT ITS USE SHALL BE TYPICAL.
4. ROOF TAPER PLANS ARE PRELIMINARY. ROOFING CONTRACTOR TO FIELD VERIFY ALL DIMENSIONS AND COORDINATE WITH ROOF MEMBRANE MANUFACTURER AND/ OR SUPPLIER FOR FINAL DRAINAGE TAPER PLANS TO BE REVIEWED AND APPROVED BY AMTECH PRIOR TO
CONSTRUCTION.
5. GRID LINES ARE FOR REFERNCE ONLY.
SL
SL SL SL SL
SL
SL SL SL SL
SL
SL SL SL SLSL
SL SL SL
VP
VP
VP
VP
VP
VP
VP
EF
EF
EF
EF
EF
EF
EF
EF
EH
EF
VP
VP
GAS GAS GAS GAS
G A
S
GAS
VP
HS
HS
PP
PP
PP
ACCU
ACCU
VP
E PSP
VP
EH
EF
ROOF
AREA A
ROOF
AREA B
D E F G H
A B C
RIDGE
R-500
R-500
R-500
R-500
R-500
R-500
R-400
R-500
R-400
R-500
R-400
R-500
R-4004
R-500
LO
W
4A R-501
4A R-501
4A R-501
R-502
R-400
R-502
R-400
R-502
R-502
R-400
R-502
R-502
R-502
7A R-502
7A R-502
7A R-502
7A R-502
7A R-502
7A R-502
7B R-502
7B R-502
7B R-502
7A R-502
7B R-502
7A R-502
7A R-502
R-503
1 1
AB
GAS
E
R-###
SECTION AND DETAIL REFERENCE
NOT IN CONTRACT
ROOFING KEY NOTE
STRUCTURAL ROOF SLOPE
8" TAPERED ROOF SLOPE
RIDGE LINE
VALLEY LINE
PRIMARY ROOF DRAIN
OVERFLOW ROOF DRAIN
THRU-WALL ROOF DRAIN
THRU-WALL SCUPPER
OVERFLOW SCUPPER
ROOF HATCH
WALL-TO-ROOF EXPANSION JOINT
ROOF-TO-ROOF EXPANSION JOINT
CONTROL JOINT
EXISTING GAS LINE
EXISTING CONDUIT LINE
EXISTING LIGHTNING PROTECTION
HOT STACK PENETRATION
VENT PIPE PENETRATION
SOIL PIPE PENETRATION
DAVIT ARM PENETRATION
TIE-BACK ANCHOR PENETRATION
ELECTRICAL LINE PENETRATION
GAS LINE PENETRATION
PIPE PENETRATION
ROOF TOP UNIT
EXHAUST HOOD
EXHAUST FAN
MECHANICAL EQUIPMENT CURB
FREE STANDING MECHANICAL EQUIPMENT.
ABANDONED EQUIPMENT/CURB TO BE
REMOVED AT OWNERS DIRECTION
NEW 12" TAPERED CRICKETS WITH 6"
TAPERED EDGE STRIP
NEW 14" TAPERED CRICKETS WITH 6"
TAPERED EDGE STRIP
NEW WALKWAY PAD
SKYLIGHT
SPLASH BLOCK
ROOF AREA ELEVATION OFFSET
ROOFING DETAIL NUMBER
ROOFING PAGE NUMBER
RD
OF
WD
TWS
RH
EH
EF
RR-EX. JT.
RTU
SL
OFS
SP
VP
HS
TA
EP
WR-EX. JT.
MC
SB
DA
GP
PP
ACCU
CTRL. JT.
KEYNOTES:
1. APPROXIMATE DOWNSPOUT(S) LOCATION - CONTRACTOR
TO FIELD VERIFY.
1.1. REMOVE AND DISPOSE OF EXISTING DOWNSPOUT
AND INSTALL NEW OPEN FACE DOWNSPOUTS
INSTALLED PER SPECIFICATION REQUIREMENTS.
1.2. CONTRACTOR TO ENSURE NEW DOWNSPOUTS AND
DOWNSPOUT OUTLETS MEET SIZING
REQUIREMENTS AS DEFINED BY CODE.
2. EXISTING ROOF TOP UNIT TO BE RAISED TO MEET THE
MINIMUM 8-INCH FLASHING REQUIREMENTS. EXTEND ALL
DUCT WORK AND ELECTRICAL AS REQUIRED.
3. CONTRACTOR TO COORDINATE WITH OWNER PRIOR TO
ABANDONED CURB/PENETRATION REMOVAL. ALL
ABANDONED CURBS MARKED FOR REMOVAL WILL NEED
TO HAVE THE ROOF DECK OPENINGS PATCHED AND
REPAIRED WITH NEW ROOFING INSTALLED OVER THESE
LOCATIONS. OVERLAY DECK WITH NEW MINIMUM 3'x3'
16-GA. SHEET METAL FLAT STOCK FOR OPENINGS THAT
ARE 2'x2' OR LESS. FASTEN NEW FLAT STOCK SHEET
METAL AT 6-INCHES ON CENTER AT 3-INCHES FROM THE
EDGE OF THE DECK OPENING. TYPICAL.
4. CONTRACTOR TO COORDINATE WITH OWNER REGARDING
ALL WALL MOUNTED ELECTRICAL UNITS, CAMERAS, AND
UNISTRUT SUPPORTS WHERE INTERFERENCE WITH
ROOFING WORK MAY OCCUR. ELECTRICAL TO ONLY BE
REMOVED AND REINSTALLED PER THE OWNER'S
DIRECTION.
5. EXISTING THROUGH DECK PIPE PENETRATION TO BE
RELOCATED A MINIMUM OF 24-INCHES AWAY FROM THE
NEW CONTROL JOINT WALL FLASHING.
6. NEW ROOF MEMBRANE WALL FLASHING AND PLYWOOD TO
BE EXTENDED UP FULL FACE OF INTERIOR SUBSTRATE
ALONG THE EAST AND SOUTH AREA D WALLS.
7. EXISTING HOOD VENT HATCH TO BE REMOVED, DISPOSED,
AND REPLACED WITH A NEW PREFABRICATED CODE
COMPLIANT ROOF HATCH WITH SAFETY RAIL. REFER TO
SPECIFICATION SECTION 07 7200 FOR ADDITIONAL
INFORMATION.
C
ROOF PLAN - THE PLANT BUILDING
NOTE: SIMILAR - ACTUAL CONDITIONS MAY VARY (N.T.S.)
PLAN
NORTH
TRUE
NORTH
PLOT SCALE IS 30x42
ISSUED FOR
SHEET NO.
SHEET TITLE
PROJECT
CLIENT
DATE REVISION
DRAWN BY
CHECKED BY
PROJECT NO.
DATE
LEGEND
OF
1720 South Bellaire Street, Suite 1200 Denver, Colorado 80222
(303) 738-0823 | www.amtechsls.com
AMTECH
SOLUTIONS
KEYPLAN LEGEND
DRAFT
THIS DOCUMENT
MAY NOT
BE USED FOR
CONSTRUCTION
COLORADO STATE
UNIVERSITY PUEBLO
2200 BONFORTE BOULEVARD
PUEBLO, COLORADO 81001
2023-020M22
CSU PUEBLO ROOFING PROJECT
2200 BONFORTE BOULEVARD
PUEBLO, COLORADO 81001
DEN.2023.001022
10/2023
BID RELEASE
RKP & SAP
DD
R-301 09 14
ROOF SYSTEM
INSULATION
(N) VAPOR RETARDER
PRIMER AS REQ.. TYP.
(N) VAPOR RETARDER. TYP.
4" MIN.
DO NOT EXTEND
PAST TOP OF
INSULATION. TYP.
VERTICAL SUBSTRATE. TYP.
ROOF MEMBRANE AND ASSOCIATED
FLASHINGS NOT SHOWN FOR CLARITY.
(E) CONCRETE DECK OR
(N) GYP. SUBSTRATE BOARD
(N) MIN. 4"x4" VAPOR RETARDER PATCH @
ALL 90-DEGREE SEAM TRANSITIONS. TYP.
2"
MIN.
2"
MIN.
ROOF SYSTEM
INSULATION
3" MIN.
2"
MIN.
PENETRATION. TYP.
(E) MTL DECK. TYP.
(N) VAPOR RETARDER
PRIMER AS REQ. TYP.
(N) VAPOR
RETARDER. TYP.
(N) PRESSURE SENSITIVE ELASTOFORM
FLASHING WITH EPDM PRIMER. TYP.
ROOF MEMBRANE AND ASSOCIATED
FLASHINGS NOT SHOWN FOR CLARITY.
(E) CONCRETE DECK OR
(N) GYP. SUBSTRATE BOARD
4" MIN.
DO NOT EXTEND
PAST TOP OF
INSULATION. TYP.
PLOT SCALE IS 30x42
ISSUED FOR
SHEET NO.
SHEET TITLE
PROJECT
CLIENT
DATE REVISION
DRAWN BY
CHECKED BY
PROJECT NO.
DATE
LEGEND
OF
1720 South Bellaire Street, Suite 1200 Denver, Colorado 80222
(303) 738-0823 | www.amtechsls.com
AMTECH
SOLUTIONS
KEYPLAN LEGEND
DRAFT
THIS DOCUMENT
MAY NOT
BE USED FOR
CONSTRUCTION
COLORADO STATE
UNIVERSITY PUEBLO
2200 BONFORTE BOULEVARD
PUEBLO, COLORADO 81001
2023-020M22
CSU PUEBLO ROOFING PROJECT
2200 BONFORTE BOULEVARD
PUEBLO, COLORADO 81001
DEN.2023.001022
10/2023
BID RELEASE
RKP & SAP
DD
VAPOR RETARDER DETAILS
R-400 10 14
SELF-ADHERED VAPOR RETARDER FLASHING
@ ROOF PENETRATIONS (TYPICAL)
NOTE: SIMILAR - ACTUAL CONDITIONS MAY VARY (N.T.S.)
SELF-ADHERED VAPOR RETARDER FLASHINGS
@ DECK ANGLE CHANGE (TYPICAL)
NOTE: SIMILAR - ACTUAL CONDITIONS MAY VARY (N.T.S.)
VAPOR RETARDER NOTES:
1. GENERAL:
1.1. SELF-ADHERED VAPOR RETARDER AND BASE SHEETS TO BE INSTALLED AT ALL IN SCOPE ROOF AREAS WHERE THE EXISTING
ROOF SYSTEM IS BEING REMOVED DOWN TO THE CORRESPONDING EXISTING ROOF DECK.
1.2. REFER TO ASSOCIATED DETAILS ON R-400 FOR APPLICATION OVER SUBSTRATE BOARDS, CONCRETE, AND METAL DECKS.
2. EXAMINATION AND PREPARATION:
2.1. THE CONTRACTOR SHALL EXAMINE ALL ROOFING SUBSTRATES INCLUDING, BUT NOT LIMITED TO: INSULATION MATERIALS, ROOF
DECKS, WALLS, CURBS, ROOFTOP EQUIPMENT, FIXTURES, AND WOOD BLOCKING.
2.2. THE APPLICATOR SHALL NOT BEGIN INSTALLATION UNTIL CONDITIONS HAVE BEEN PROPERLY EXAMINED AND DETERMINED TO BE
CLEAN, DRY, AND OTHERWISE SATISFACTORY TO RECEIVE SPECIFIED ROOFING MATERIALS.
2.3. DURING THE APPLICATION OF SPECIFIED MATERIALS, THE APPLICATOR SHALL CONTINUE TO EXAMINE ALL PROJECT CONDITIONS
TO ENSURE CONDITIONS REMAIN SATISFACTORY TO COMPLETE THE SPECIFIED ROOFING SYSTEM.
2.4. BEFORE COMMENCING WORK EACH DAY, THE CONTRACTOR SHALL PREPARE ALL ROOFING SUBSTRATES TO ENSURE
CONDITIONS ARE SATISFACTORY TO PROCEED WITH THE INSTALLATION OF SPECIFIED ROOFING MATERIALS. PREPARATION OF SUBSTRATES INCLUDES, BUT IS NOT LIMITED TO, SUBSTRATE REPAIRS, SECUREMENT OF SUBSTRATES, ELIMINATING ALL
INCOMPATIBLE MATERIALS, AND CLEANING.
2.5. WHERE CONDITIONS ARE FOUND TO BE UNSATISFACTORY, WORK SHALL NOT BEGIN UNTIL CONDITIONS ARE MADE SATISFACTORY TO BEGIN WORK. COMMENCING OF WORK SHALL INDICATE CONTRACTOR'S ACCEPTANCE OF CONDITIONS.
3. PRIMER APPLICATION:
3.1. EXAMINE ALL SUBSTRATES, AND CONDUCT ADHESION PEEL TESTS AS NECESSARY, TO ENSURE SATISFACTORY ADHESION IS
ACHIEVED.
3.2. APPLY THE APPROPRIATE SPECIFIED PRIMER TO DRY, COMPATIBLE SUBSTRATES AS REQUIRED TO ENHANCE ADHESION OF NEW
SPECIFIED MATERIALS.
3.3. APPLY PRIMER USING BRUSH, ROLLER, OR SPRAYER AT THE RATE PUBLISHED ON THE PRODUCT DATA SHEET PER
MANUFACTURER REQUIREMENTS.
3.4. PRIMER IS SATISFACTORYILY CURED WHEN IT WILL NOT TRANSFER WHEN TOUCHED.
3.5. ONLY PRIME AREAS WHERE THE MEMBRANE AND ROOF SYSTEM WILL BE INSTALLED ON THE SAME DAY.
3.6. RE-PRIME AREAS THAT HAVE BECOME DRY.
3.7. PROJECT CONDITIONS VARY THROUGHOUT THE DAY. MONITOR CHANGING CONDITIONS, MONITOR THE DRYING TIME OF
PRIMERS, AND MONITOR THE ADHESION OF THE MEMBRANE PLIES. ADJUST PRIMER AND MEMBRANE APPLICATION METHODS AS
NECESSARY TO ACHIEVE THE DESIRED RESULTS.
4. VAPOR RETARDER APPLICATION:
4.1. APPLY VAPOR RETARDER FROM LOW TO HIGH POINT IN A SHINGLE FASHION SO THAT LAPS WILL SHED WATER.
4.2. INSTALL NEW VAPOR RETARDER WITH SIDE LAPS AND END LAPS IN ACCORDANCE WITH MANUFACTURER MINIMUM OVERLAP
REQUIREMENTS.
4.3. END LAPS SHALL BE STAGGERED.
4.4. SEAMS AND END LAPS MUST BE ROLLED WITH A 2-INCH SEAM ROLLER.
4.5. PLACE MEMBRANE CAREFULLY TO AVOID WRINKLES AND FISHMOUTHS.
4.6. VAPOR RETARDER IS TO BE INSTALLED PARALLEL TO THE DECK FLUTES AT METAL ROOF DECKS.
4.7. VAPOR RETARDER MUST EXTEND A MINIMUM OF 4-INCHES UP ALL VERTICAL SURFACES.
4.8. VAPOR RETARDER MUST BE ROLLED INTO PLACE WITH A MIN. 100LB WEIGHTED ROLLER IMMEDIATELY AFTER BEING SET.
5. VAPOR RETARDER REPAIRS:
5.7. AFTER INSTALLATION, INSPECT VAPOR RETARDER MEMBRANE FOR TEARS, PUNCTURES, FISHMOUTHS, AIR BUBBLES, AND VOIDS
DUE TO MISALIGNMENT AT SEAMS.
5.8. REMOVE DAMAGED MEMBRANE.
5.9. PRIME EXPOSED SUBSTRATE AND ALLOW PRIMER TO DRY. APPLY A NEW SECTION OF THE VAPOR RETARDER TO PRIMED
SUBSTRATE, EXTENDING ONTO ADHERED MEMBRANE 6-INCHES ON ALL SIDES. FIRMLY PRESS MEMBRANE REPAIR SECTION TO
ENSURE A GOOD SEAL.
5.10. SLIT FISHMOUTHS AND OVERLAP THE EDGES. PLACE A SECTION OF MEMBRANE OVER THE REPAIR AND EXTEND 6-INCHES IN ALL
DIRECTIONS. FIRMLY PRESS REPAIR SECTION TO ENSURE A GOOD SEAL
(N) THERMOPLASTIC FIELD MEMBRANE (FA).
2" MIN.
HEAT WELD. TYP.
(N) SEAM FASTENING PLATES. TYP.
3"
MIN.
(E & N) WALL SUBSTRATE. TYP. - V.I.F.
(N) THERMOPLASTIC WALL
MEMBRANE FLASHING (FA). TYP.
ROOF SLOPE.
SET FLANGE IN (N)
CONT. MASTIC. TYP.
EXTEND (N) FASCIA METAL
TO CONCEAL ALL MEMBRANE
AND SUN/PAINT LINES. TYP.
(N) MANU. APPROVED. #10 x 2"
STAINLESS STEEL FASTENERS
@ 12" O.C. TYP.
(N) MANU. APPROVED FASTENERS
@ 24" O.C. TYP.
4"
V.I.F.
(N) EXTRUDED ANCHOR-BAR. TYP.
(N) 20-GA. GALV. CONT. CLEAT. TYP.
(N) FASCIA COVER IN
12'-0" LENGTHS. TYP.
(E) WALL SUBSTRATE. TYP.
(N) 6" WIDE UNCURED
EPDM STRIPPING-PLY @
ALL GUTTER SEAMS. TYP.
(N) EXTRUDED ALUMINUM
TERMINATION BAR FASTENED
@ 6" O.C. MAX. TYP.
(N) MANU. PROVIDED HANGERS
FASTENED @ 30" O.C. MAX. WITH
NEOPRENE GASKETED FASTENERS
THRU TERMINATION BAR. TYP.
(N) 24-GA. PRE-FABRICATED
PRE-FINISHED GUTTER
SECURED TO PROVIDE
POSITIVE SLOPE TO
DOWNSPOUTS.
(N) CONT. BED OF WATER CUT-OFF
SEALANT BEHIND MEMBRANE. TYP.
(N) CONT. URETHANE SEALANT
TOOLED IN TO CREATE A WATER
SHEDDING SURFACE. TYP.
7"
MIN.
1" MIN.
7" MIN.
(N) ROOF MEMBRANE EXTENDED
INTO GUTTER. TYP.
(E) ROOF SLOPE.
REFER TO
R-102 FOR
FULL ROOF
ASSEMB…