20230825 Owen Summers_Drawings.pdf_safe.pdf
PDF 3 MB Posted
- Attached to
- OWEN SUMMERS READINESS CENTER SESMIC UPGRADE
- Solicitation number
- S-24800-00009058
- Issued by
- Marion County, Oregon
About this file
The provided document is a set of structural engineering drawings and specifications for a voluntary seismic upgrade to the Owen Summers Building in Salem, Oregon. The project includes a new lateral force resisting system to address seismic loads, as well as diaphragm strengthening, collector and drag strut installation, and strengthening of existing footings. The work is for the Military Department (OMD) and will be located at 1776 Military Way SE, Salem, Oregon. The drawings include detailed plans, elevations, sections, and construction details for the seismic upgrade.
The key information provided includes a scope of work, code summary, foundation design criteria, structural design criteria, special inspection requirements, and construction notes. The drawings indicate the structural upgrades required, including new concrete shear walls, steel braced frames, and foundation modifications. The project is part of a state and local contract opportunity issued by the Oregon Military Department and applicable to Marion County and the City of Salem.
View the file
Other files
Show 40 more
Latest 50 of 85 listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
# NUMBER OR POUNDS
AB ANCHOR BOLT
ACI AMERICAN CONCRETE INSTITUTE
ADDL ADDITIONAL
ADJ ADJACENT
AESS ARCHITECTURALLY EXPOSED STRUCTURAL
STEEL
AFF ABOVE FINISH FLOOR
AISC AMERICAN INSTITUTE OF STEEL CONSTRUCTION
ALT ALTERNATE
ALUM ALUMINUM
APA AMERICAN PLYWOOD ASSOCIATION
ARCH ARCHITECTURAL
ASTM AMERICAN SOCIETY FOR TESTING AND
MATERIALS
ASSY ASSEMBLY
ATR ALL THREAD ROD
ATR/A ALL THREAD ROD WITH ADHESIVE
AWS AMERICAN WELDING SOCIETY
B/ BOTTOM OF
BF BRACED FRAME
BLDG BUILDING
BLKG BLOCKING
BM BEAM
BN BOUNDARY NAIL
BOT BOTTOM
BRBF BUCKLING RESTRAINED BRACED FRAME
BRNG BEARING
BSMT BASEMENT
BTWN BETWEEN
BU BUILT-UP
C CAMBER OR CHANNEL (AMERICAN STANDARD)
CANT CANTILEVER
CIP CAST IN PLACE
CG CENTER OF GRAVITY
CGS CENTER OF GRAVITY OF (PRESTRESSING) STEEL
CJ CONTROL OR CONSTRUCTION JOINT
CJP COMPLETE JOINT PENETRATION
CL CENTERLINE
CLG CEILING
CLR CLEARANCE; CLEAR
CLSM CONTROLLED LOW STRENGTH MATERIAL
CMU CONCRETE MASONRY UNIT
COL COLUMN
CONC CONCRETE
CONN CONNECTION
CONST CONSTRUCTION
CONT CONTINUOUS
COORD COORDINATE
CSA CONCRETE SCREW ANCHOR
d PENNY (NAIL) db NOMINAL BAR DIAMETER
DBA DEFORMED BAR ANCHOR
DBL DOUBLE
DBO DESIGNED BY OTHERS
DEG DEGREE
DEMO DEMOLISH; DEMOLITION
DF/L DOUGLAS FIR-LARCH
DIA DIAMETER
DIAG DIAGONAL
DIM DIMENSION
DIST DISTANCE
DL DEAD LOAD
DN DOWN
DP DEPTH OR DEEP
DTL DETAIL
DWG DRAWING
(E) EXISTING
EA EACH
EB EXPANSION BOLT
EF EACH FACE
EJ EXPANSION JOINT
EL ELEVATION
ELEC ELECTRICAL
EN EDGE NAIL
EQ EQUAL; EARTHQUAKE
EW EACH WAY
EXT EXTERIOR
EXTD EXTEND; EXTENDED
f'c 28 DAY CONC COMPRESSIVE STRENGTH
F/ FACE OF
FF FINISH FLOOR
FN FIELD NAIL
FLR FLOOR
FDN FOUNDATION
FRT FIRE RETARDANT TREATED
FS FAR SIDE
FT FEET
FTG FOOTING
GA GAUGE
GALV GALVANIZED
GLB GLUE LAMINATED BEAM
GWB GYPSUM WALL BOARD
HD HOLDOWN
HDG HOT-DIP GALVANIZED
HDR HEADER
HF HEM-FIR
HGR HANGER
HORIZ HORIZONTAL
HSA HEADED STUD ANCHOR
HSS HOLLOW STRUCTURAL SECTION
HT HEIGHT
IBC INTERNATIONAL BUILDING CODE
ID INSIDE DIAMETER
IN INCH
INT INTERIOR
JST JOIST
JT JOINT
K KIP(S) (1,000 POUNDS)
KSF KIPS PER SQUARE FOOT
KSI KIPS PER SQUARE INCH
L, 2L ANGLE OR DOUBLE ANGLE
LF LINEAR FOOT
LG LIGHT GAUGE
LL LIVE LOAD
LLBB LONG LEGS BACK TO BACK
LLH LONG LEG HORIZONTAL
LLV LONG LEG VERTICAL
LONG LONGITUDINAL
LSL LAMINATED STRAND LUMBER
LSH LONG SLOTTED HOLE
LVL LAMINATED VENEER LUMBER
LWC LIGHT WEIGHT CONCRETE
MAX MAXIMUM
MC MISCELLANEOUS CHANNEL
MECH MECHANICAL
MF MOMENT FRAME
MFR MANUFACTURER
MEP MECHANICAL, ELECTRICAL, PLUMBING
MIN MINIMUM
MIR MIRROR
MISC MISCELLANEOUS
MSA MASONRY SCREW ANCHOR
MT MAGNETIC PARTICLE TESTING
(N) NEW
NDT NON-DESTRUCTIVE TESTING
NIC NOT IN CONTRACT
NOM NOMINAL
NS NEAR SIDE
NTE NOT TO EXCEED
NTS NOT TO SCALE
OC ON CENTER
OCBF ORDINARY CONCENTRIC BRACED FRAME
OD OUTSIDE DIAMETER
OMF ORDINARY MOMENT FRAME
OPP OPPOSITE
OWJ OPEN WEB JOIST
PAF POWDER ACTUATED FASTENER
PC PRECAST
PCF POUNDS PER CUBIC FOOT
PERP PERPENDICULAR
PJP PARTIAL JOINT PENETRATION
PL PLATE
PLF POUNDS PER LINEAL FOOT
PLWD PLYWOOD
PSI POUNDS PER SQUARE INCH
PSF POUNDS PER SQUARE FOOT
PT PRESSURE TREATED
P/T POST TENSIONED
PVC POLYVINYL CHLORIDE
QTY QUANTITY
RAD RADIUS
RBS REDUCED BEAM SECTION
REF REFERENCE
REINF REINFORCING
REQD REQUIRED
RET RETAINING
REV REVISED, REVISION
RO ROUGH OPENING
SC SLIP CRITICAL
SCBF SPECIAL CONCENTRIC BRACE FRAME
SER STRUCTURAL ENGINEER OF RECORD
SFRS SEISMIC FORCE RESISTING SYSTEM
SHT SHEET
SHTG SHEATHING
SIM SIMILAR
SLBB SHORT LEGS BACK TO BACK
SMF SPECIAL MOMENT FRAME
SMS SHEET METAL SCREW
SOG SLAB ON GRADE
SQ SQUARE
SS STAINLESS STEEL
SSH SHORT SLOTTED HOLE
STD STANDARD
STL STEEL
SQ SQUARE
SYM SYMMETRICAL
T/ TOP OF
T&B TOP AND BOTTOM
T&G TONGUE AND GROVE
THRD THREADED
TRANS TRANSVERSE
TYP TYPICAL
UNO UNLESS NOTED OTHERWISE
URM UNREINFORCED MASONRY
UT ULTRASONIC TEST
VERT VERTICAL
VIF VERIFY IN FIELD
W/ WITH
W/O WITHOUT
WD WOOD
WF WIDE FLANGE
WP WORK POINT
WWR WELDED WIRE REINFORCING
STRUCTURAL
DRAWING SYMBOLS
DETAIL REFERENCE
DETAIL SECTION CUT
BUILDING OR
WALL SECTION
CUT
ELEVATION OF
WALL OR FRAME
REVISION SYMBOL
GRID LINES
ROTATE VIEW SYMBOL
NORTH ARROW
SURFACE - STEPPED
SURFACE - SLOPE UP
SURFACE - SLOPE DOWN
SURFACE - SLOPE
TWO DIRECTIONS
DECKING SPAN
DIRECTION
OPENING IN FLOOR / WALL
EXTENT OF
ELEMENT
INDICATES
ELEMENT
CONTINUES
N
S4.1
S3.1
S8.1
S8.1
STRUCTURAL ABBREVIATIONS
A
CONCRETE
EARTH
COMPACTED
STRUCTURAL FILL
MASONRY
SAND OR GROUT
PLYWOOD - SECTION
WOOD - PLAN
STRUCTURAL
MATERIAL PATTERNS
REPEATING
ELEMENT
SUPPORTING
ELEMENT
BEARING
ELEMENT
STEEL
STRUCTURAL
ELEMENT
END OF
REPEATING
ELEMENT
REPEATING
ELEMENT
CONTINUES
PROJECT LOCATION
SCOPE OF WORK:
THESE DRAWINGS ARE FOR A VOLUNTARY SEISMIC UPGRADE TO THE
OWEN SUMMERS BUILDING INCLUDING THE ORIGINAL USP&FO BUILDING
AND THE OWEN SUMMERS BUILDING ADDITION. THE WORK INCLUDES
NEW LATERAL FORCE RESISTING SYSTEM TO RESIST THE CODE
PRESCRIBED LOADS, AS WELL AS DIAPHRAGM STRENGTHENING WITH
COLLECTORS AND DRAG STRUTS AS REQUIRED. THE WORK ALSO
INCLUDES STRENGTHENING THE EXISTING USPFO FOOTINGS TO RESIST
OVERTURNING DUE TO SEISMIC LOADING AND TYING THE USPFO
BUILDING TO THE OWEN SUMMERS ADDITION FOR SEISMIC CONTINUITY.
ADDITIONALLY, THE SWITCHGEAR BUILDING HAS BEEN TIED FOR
SEISMIC CONTINUITY.
THESE DRAWINGS DO NOT ADDRESS NON-STRUCTURAL COMPONENTS
SUCH AS THE ANCHORAGE OF STORAGE RACKS, EQUIPMENT OR
ARCHITECTURAL FINISHES. THERE IS NO CHANGE TO THE FOOTPRINT
OR PROFILE OF THE EXISTING BUILDING.
CODE SUMMARY:
BUILDING CODE: 2022 OSSC
YEAR BUILT: 1985 / 1988
OCCUPANCY: B - BUSINESS (OFFICE), A - ASSEMBLY, S - STORAGE
THERE ARE NO CHANGES TO THE BUILDING OCCUPANCY
NUMBER OF STORIES: 2
BUILDING AREA: 85,000 SQ FT (NO CHANGE)
CONSTRUCTION TYPE: EXISTING TYPE II - B
SHEET
9600 SW Oak St | Suite 400 Portland, OR | 97224
503.246.1250 | miller-se.com
MCE PROJECT NO:
SHEET SCALE:
DRAWN BY:
SHEET CONTENT
ISSUE DATE:
CHECKED BY:
COPYRIGHT 2023
Miller Consulting Engineers, Inc.
CONSULTING
MILLER
ENGINEERS
AS INDICATED
BCH
S0.01
V O
LU
N
T A
R Y
S E
IS
M
IC
U
P G
R A
D E
JF
H
Q
O W
E N
S U
M M
E R
S B
U
IL
D
IN
G
M
IL
IT
A R
Y W
A Y
S E
S A
L E
M , O
R E
G O
N
COVER SHEET
230072
08.25.23
STRUCTURAL DRAWING INDEX
SHEET # SHEET NAME 60
D D
S E
T
C D
P E
R M
IT
S
E T
S0.01 COVER SHEET ● ● ●
S0.02 STRUCTURAL NOTES ● ● ●
S0.03 SPECIAL INSPECTIONS ● ● ●
S0.04 SPECIAL INSPECTION ● ●
S1.01 PARTIAL CONCRETE FOUNDATION PLAN - SOUTH ● ● ●
S1.02 PARTIAL CONCRETE FOUNDATION - NORTH ● ● ●
S1.03 LOW ROOF FRAMING PLAN ● ● ●
S1.04 2ND FLOOR FRAMING PLAN ● ● ●
S1.05 UPPER ROOF FRAMING PLAN ● ● ●
S3.01 FRAMING ELEVATIONS ● ●
S3.02 FRAMING ELEVATIONS ● ●
S3.03 FRAMING ELEVATIONS ● ●
S3.04 FRAMING ELEVATION ● ●
S3.05 FRAMING ELEVATIONS ● ●
S5.00 CONCRETE DETAILS ● ● ●
S5.01 CONCRETE DETAILS ● ●
S6.01 BRACE FRAME DETAILS ● ●
S6.02 STEEL FRAMING DETAILS ● ●
S6.03 FRAMING DETAILS ● ●
S6.04 STEEL DETAILS ● ●
S6.05 FRAMING DETAILS ● ●
S7.01 SURE BOARD SHEAR WALL DETAILS ● ●
S8.01 USPFO DETAILS ● ●
S0.01 | 3/32" = 1'-0"1 VICINITY MAP
R E
V
D A
T E
D E
S C
R
IP
T
IO
N
OREGON
J A
N
U A R Y 2 3 , 2
E
N G I N E E
R
51043RE
G ISTERED PROFESS IONAL
ER
I C R . WA T SON
STRUCTURA L
EXPIRES: 06 - 30 - 2024
DIGITALLY SIGNEDEric Watson
Digitally signed by Eric Watson
DN:
E=eric@miller-se.com, CN=Eric Watson, OU=Engineering, O="Miller Consulting Engineers, Inc.", L=Portland, S=Oregon, C=US Date: 2023.08.26 11:44:23-07'00'
GENERAL NOTES
THE CONTRACTOR IS RESPONSIBLE FOR VERIFICATION AND CORRELATION OF ALL ITEMS AND
WORK NECESSARY FOR COMPLETION OF THE PROJECT AS INDICATED BY THE CONTRACT
DOCUMENTS. SHOULD ANY QUESTION ARISE REGARDING THE CONTRACT DOCUMENTS OR SITE
CONDITIONS, THE CONTRACTOR SHALL REQUEST INTERPRETATION AND CLARIFICATION FROM THE
ENGINEER BEFORE BEGINNING THE PROJECT. THE ABSENCE OF SUCH REQUEST SHALL SIGNIFY
THAT THE CONTRACTOR HAS REVIEWED AND FAMILIARIZED HIMSELF WITH ALL ASPECTS OF THE
PROJECT AND HAS COMPLETE COMPREHENSION THEREOF. THE CONTRACTOR SHALL BE
RESPONSIBLE FOR CONFORMANCE TO ALL SAFETY REGULATIONS DURING CONSTRUCTION.
THE CONTRACT DRAWINGS AND SPECIFICATIONS REPRESENT THE FINISHED STRUCTURE. UNLESS
OTHERWISE SPECIFICALLY NOTED, THEY DO NOT INDICATE THE METHOD OF CONSTRUCTION OR
CONSTRUCTION LOADS. ONLY THE CONTRACTOR SHALL PROVIDE ALL METHODS, DIRECTION AND
RELATED EQUIPMENT NECESSARY TO PROTECT THE STRUCTURE, WORKMEN AND OTHER
PERSONS AND PROPERTY DURING CONSTRUCTION. THE CONTRACTOR SHALL, AT THEIR OWN
EXPENSE, ENGAGE PROPERLY QUALIFIED PERSONS TO DETERMINE WHERE AND HOW TEMPORARY
PRECAUTIONARY MEASURES SHALL BE USED AND INSPECT SAME IN THE FIELD. ANY MATERIAL NOT AS SPECIFIED OR IMPROPER MATERIAL INSTALLATION OR WORKMANSHIP SHALL BE REMOVED AND
REPLACED WITH SPECIFIED MATERIAL IN A WORKMANLIKE MANNER AT THE CONTRACTOR'S
EXPENSE.
THESE PLANS, SPECIFICATIONS, ENGINEERING AND DESIGN WORK ARE INTENDED SOLELY FOR THE PROJECT SPECIFIED HEREIN. MILLER CONSULTING ENGINEERS DISCLAIMS ALL LIABILITY IF THESE PLANS AND SPECIFICATIONS OR THE DESIGN, ADVICE AND INSTRUCTIONS ATTENDANT THERETO
ARE USED ON ANY PROJECT OR AT ANY LOCATION OTHER THAN THE PROJECT AND LOCATION
SPECIFIED HEREIN. OBSERVATION VISITS TO THE JOB SITE AND SPECIAL INSPECTIONS ARE NOT
PART OF THE STRUCTURAL ENGINEER'S RESPONSIBILITY UNLESS THE CONTRACT DOCUMENTS
SPECIFY OTHERWISE.
NON-STRUCTURAL PORTIONS OF PROJECT INCLUDING, BUT NOT LIMITED TO, PLUMBING, FIRE
SUPPRESSION, ELECTRICAL, MECHANICAL, LAND USE, SITE PLANNING, EROSION CONTROL
FLASHING AND WATER-PROOFING ARE BEYOND THE SCOPE OF THESE DRAWINGS AND ARE
PROVIDED BY OTHERS.
TEMPORARY SHORING
WHEREVER SHORING IS REQUIRED, THE CONTRACTOR SHALL BE RESPONSIBLE FOR PROVIDING A
SHORING SYSTEM THAT PREVENTS SETTLEMENT AND/OR DAMAGE TO EXISTING FACILITIES AND
PROTECTS PERSONNEL, THE PUBLIC AND THE BUILDING AS REQUIRED. THE CONTRACTOR SHALL ALSO BE RESPONSIBLE FOR PROTECTING STREETS, WALKWAYS, UTILITIES, IMPROVEMENTS AND
EXCAVATION AGAINST LOSS OF GROUND OR CAVING OF EMBANKMENTS DURING CONSTRUCTION,
AS REQUIRED. THE CONTRACTOR SHALL LOCATE THE SHORING SYSTEM CLEAR WITHOUT
OBSTRUCTION OF THE PERMANENT STRUCTURE AND TO PERMIT CONSTRUCTION TO PROCEED.
BUILDING CODE
ALL PHASES OF THE WORK SHALL CONFORM TO THE 2022 OREGON STRUCTURAL SPECIALTY CODE (OSSC), BASED ON THE 2021 INTERNATIONAL BUILDING CODE (IBC), INCLUDING ALL REFERENCE
STANDARDS, UNLESS NOTED OTHERWISE.
SPECIAL INSPECTION / STRUCTURAL OBSERVATION
CONTRACTOR RESPONSIBILITIES
SPECIAL INSPECTION AND/OR TESTING IS REQUIRED IN ACCORDANCE WITH IBC SECTION 1704. THE
CONTRACTOR SHALL PROVIDE SUFFICIENT NOTICE TO ALLOW SCHEDULING OF SPECIAL
INSPECTION. IT IS THE OWNER'S RESPONSIBILITY TO PROVIDE SPECIAL INSPECTION AND TESTING
BY A QUALIFIED THIRD PARTY, SUCH AS A TESTING AGENCY REVIEWED BY THE ENGINEER.
STRUCTURAL OBSERVATION SHALL VERIFY BY PERIODIC VISUAL OBSERVATION THAT THE
STRUCTURAL SYSTEM HAS GENERAL CONFORMANCE WITH THE APPROVED PLANS AND
SPECIFICATIONS AT SIGNIFICANT STAGES OF CONSTRUCTION AND AT COMPLETION AS REQUIRED IN ACCORDANCE WITH IBC SECTION 1704.6. THE CONTRACTOR SHALL PROVIDE SUFFICIENT NOTICE TO ALLOW SCHEDULING FOR A STRUCTURAL OBSERVATION. STRUCTURAL OBSERVATION SHALL BE BY
THE ENGINEER OF RECORD.
REQUIRED SPECIAL INSPECTIONS AND TESTS
SPECIAL INSPECTIONS SHALL CONFORM TO SECTION 1705 OF THE 2021 IBC, CONTRACT
DOCUMENTS AND APPROVED SUBMITTALS. REFER TO THE SPECIAL INSPECTION TABLE ON SHEET
S0.03 FOR PROJECT REQUIREMENTS. SPECIAL INSPECTORS SHALL BE APPROVED BY THE
BUILDING OFFICIAL. THE SPECIAL INSPECTOR SHALL OBSERVE THE INDICATED WORK FOR
COMPLIANCE WITH THE APPROVED CONSTRUCTION DOCUMENTS. ALL DISCREPANCIES SHALL BE
BROUGHT TO THE ATTENTION OF THE CONTRACTOR FOR CORRECTION AND NOTED IN THE
INSPECTION REPORTS.
SHOP DRAWINGS/SUBMITTALS
SHOP DRAWINGS FOR SPECIFIC PRODUCTS GENERATED BY SUPPLIER SHALL BE SUBMITTED FOR
THE ITEMS NOTED IN THE SUBMITTAL SCHEDULE. DRAWINGS SHALL BE TO SCALE AND SHOW
COMPLETE DETAILS AND INSTRUCTIONS FOR FABRICATION AND ASSEMBLY. SHOP DRAWINGS
SHALL INDICATE ERECTION AND TEMPORARY BRACING INFORMATION FOR CONTRACTOR’S USE.
THE DESIGN OF DELEGATED DESIGN ITEMS NOTED IN THE SUBMITTAL SCHEDULE SHALL BE THE
RESPONSIBILITY OF THE CONTRACTOR. DOCUMENTS FOR THE DESIGN AND FABRICATION OF
DELEGATED DESIGN ITEMS (INCLUDING STRUCTURAL CALCULATIONS AND DRAWINGS) SHALL BEAR
THE SEAL AND SIGNATURE OF A LICENSED ENGINEER REGISTERED IN THE STATE THAT THE
PROJECT IS BEING CONSTRUCTED.
THE CONTRACTOR SHALL REVIEW AND MODIFY ALL SUBMITTALS AS REQUIRED FOR CONFORMANCE WITH DATE AND SIGNATURE ON ALL SETS OF DOCUMENTS PRIOR TO SUBMITTAL TO THE ENGINEER.
THE CONTRACTOR SHALL SCHEDULE SUBMITTALS TO ALLOW SUFFICIENT TIME FOR REVIEW AND
POSSIBLE RE-SUBMITTAL.
SUBMITTAL SCHEDULE
ITEM SUBMITTAL
SHOP
DRAWINGS
DELEGATED
DESIGN
CONCRETE MIX DESIGNS X
CONCRETE REINFORCING STEEL X X
CONCRETE ANCHORAGE X
EMBEDDED STEEL ITEMS X X
STRUCTURAL STEEL X X
STEEL WELDING PROCEDURES X
GEOTECHNICAL REPORT X X X
HELICAL ANCHORS X X X
STRUCTURAL DESIGN CRITERIA
LIVE LOAD REDUCTION FOR BEAMS AND COLUMNS WAS USED. DESIGN FOR MECHANICAL LOADS
INCLUDES ONLY THOSE INDICATED ON STRUCTURAL DRAWINGS. THE FOLLOWING ARE THE DESIGN
REQUIREMENTS:
STRUCTURAL DESIGN CRITERIA
RISK CATEGORY II
DEAD LOAD
ROOF 20 PSF
FLOOR 57 PSF
PARTITION WALLS 15 PSF
HEAVY PARTITIONS 83 PSF
FLOOR LIVE LOAD (COMMERCIAL)
OFFICE FLOORS 50 PSF + 15 PSF PARTITIONS OR 2,000 LB
CORRIDORS/EXIT WAYS 100 PSF OR 2,000 LB
ASSEMBLY AREAS (MOVABLE SEATS) 100 PSF
LOBBIES 100 PSF
ROOF LIVE LOAD
ROOF LIVE LOAD 20 PSF
ROOF SNOW LOAD
DESIGN ROOF SNOW LOAD 25 PSF
SNOW DRIFTING
NOT CONSIDERED FOR VOLUNTARY
SEISMIC UPGRADES
IMPORTANCE FACTOR Is = 1.0
GROUND SNOW LOAD Pg = 9 PSF
EXPOSURE FACTOR Ce = 1.0
THERMAL FACTOR Ct = 1.0
SLOPE FACTOR Cs = 1.0
FLAT ROOF SNOW LOAD Pf = 7 PSF
WIND DESIGN DATA
BASIC DESIGN WIND SPEED (3 SEC GUST) V = 98 MPH
ALLOWABLE STRESS DESIGN WIND SPEED Vasd = 76 MPH
EXPOSURE B
INTERNAL PRESSURE COEFFICIENT GCpi = +/- 0.18
WALL COMPONENTS/CLADDING (ULTIMATE PRESSURE BASED ON 10 SF EFFECTIVE AREA)
INTERIOR ZONES (ZONE 4) 25 PSF
END ZONES (ZONE 5) 34 PSF
SEISMIC DESIGN DATA
IMPORTANCE FACTOR Ie = 1.0
SPECTRAL RESPONSE ACCELERATIONS SS = 0.812, S1 = 0.408
SITE CLASS D — DEFAULT
SPECTRAL RESPONSE COEFFICIENTS SDS = 0.65, SD1 = NA
SEISMIC DESIGN CATEGORY D
SEISMIC FORCE RESISTING SYSTEM — 2-
STORY
ORDINARY CONCENTRICALLY BRACED
FRAMES
DESIGN BASE SHEAR V = 500 KIPS
SEISMIC RESPONSE COEFFICIENT Cs = 0.200
RESPONSE MODIFICATION FACTOR R = 3.25
DEFLECTION AMPLIFICATION FACTOR Cd = 3.25
REDUNDANCY FACTOR p = 1.0
OVERSTRENGTH FACTOR OMEGA = 2.0
SEISMIC FORCE RESISTING SYSTEM — 1-
STORY
SPECIAL REINFORCED CONCRETE SHEAR
WALLS
DESIGN BASE SHEAR V = 125 KIPS
SEISMIC RESPONSE COEFFICIENT Cs = 0.108
RESPONSE MODIFICATION FACTOR R = 6.0
DEFLECTION AMPLIFICATION FACTOR Cd = 5 REDUNDANCY FACTOR r = 1.0
OVERSTRENGTH FACTOR OMEGA = 2.5
ANALYSIS PROCEDURE USED ASCE 7-16 EQUIVALENT LATERAL FORCE
INELASTIC STORY DRIFT - NORTH-SOUTH DIRECTION
ROOF LEVEL D = 0.36 INCHES
LEVEL 2 D = 0.17 INCHES
INELASTIC STORY DRIFT - EAST-WEST DIRECTION
ROOF LEVEL D = 0.36 INCHES
LEVEL 2 D = 0.17 INCHES
SOIL DESIGN DATA
ALLOWABLE BEARING PRESSURE
4000 PSF — TO BE CONFIRMED SEE
FOUNDATION CRITERIA
FOUNDATION CRITERIA
ALL FOUNDATION CRITERIA SHALL BE CONFIRMED BY A GEOTECHNICAL ENGINEER. GEOTECHNICAL
REPORT SHALL BE PROVIDED AS A DEFERRED SUBMITTAL. THE FOLLOWING PARAMETERS HAVE
BEEN USED FOR DESIGN BASED ON THE ORIGINAL CONSTRUCTION DRAWINGS THAT REFERENCE
THE GEOTECHNICAL REPORT PREPARED BY NORTHWEST TESTING LABORATORIES DATED
SEPTEMBER 11, 1984:
· DESIGN SOIL PRESSURE = 4000 PSF DL + LL
· ALL FOOTINGS TO BEAR ON FIRM, UNDISTURBED SOIL OR APPROVED COMPACTED FILL
MINIMUM 18” BELOW FINAL GRADE.
ALL FOUNDATION ELEMENTS SHALL BE SUPPORTED ON SUBGRADE PER THE GEOTECHNICAL
REPORT STRUCTURAL FILL MATERIAL AND PLACEMENT SHALL COMPLY WITH THE PROVISIONS
SPECIFIED IN THE GEOTECHNICAL REPORT. GEOTECHNICAL REPORT SHALL INCLUDE DESIGN
CRITERIA FOR HELICAL ANCHORS.
CONCRETE
MIXING, BATCHING, TRANSPORTING, PLACING AND CURING OF CONCRETE SHALL BE IN
ACCORDANCE WITH THE AMERICAN CONCRETE INSTITUTE, ACI 318, ACI 301 AND IBC CHAPTER 19.
CONCRETE MIX DESIGNS SHALL MEET THE FOLLOWING REQUIREMENTS:
CONCRETE MIX DESIGN REQUIREMENTS
MEMBER TYPE/LOCATION
COMPRESSIVE
STRENGTH AT 28
DAYS, F'C (PSI)
MAXIMUM
AGGREGATE
SIZE
MAXIMUM
W/CM RATIO
FOOTINGS 5000 1" 0.50
SHEAR WALLS 5000 3/4" 0.50
INTERIOR SLAB ON GRADE 3000 1" 0.45
CONCRETE MIX AIR CONTENT REQUIREMENTS:
AIR ENTRAINMENT SHALL BE CONTROLLED BY THE CONDITIONS THE CONCRETE IS SUBJECTED TO, AND THE AGGREGATE SIZE.
CONCRETE MIX AIR CONTENT REQUIREMENTS
MAXIMUM AGGREGATE SIZE
CONCRETE SUBJECT TO
FREEZE/THAW CYCLES
CONCRETE SUBJECT TO
CONTINUOUS MOISTURE
AND/OR DEICING
CHEMICALS
3/8” 6% 7.5% 1/2” 5.5% 7% 3/4” 5% 6% 1” 4.5% 6%
1-1/2” 4.5% 5.5%
THE AIR-ENTRAINING ADMIXTURE SHALL CONFORM TO ASTM C260. ALL CONCRETE WITH
REINFORCEMENT SHALL HAVE NO CHLORINE OR CHLORIDES. NO WATER MAY BE ADDED TO THE
CONCRETE IN THE FIELD UNLESS SPECIFICALLY APPROVED IN WRITING BY THE CONCRETE
SUPPLIER IN CONJUNCTION WITH THE APPROVED CONCRETE MIX DESIGN.
SLEEVES, OPENINGS, CONDUIT AND OTHER EMBEDDED ITEMS NOT SHOWN ON THE STRUCTURAL
DRAWINGS SHALL BE REVIEWED BY THE STRUCTURAL ENGINEER BEFORE PLACING CONCRETE.
WHERE NEW CONCRETE IS PLACED AGAINST EXISTING CONCRETE, THE EXISTING CONCRETE
SURFACE SHALL BE CLEANED AND ROUGHENED TO A MINIMUM 1/4” AMPLITUDE.
DESIGN OF FORMWORK, SHORING AND RE-SHORING DESIGN IS THE RESPONSIBILITY OF THE
CONTRACTOR AND SHALL CONFORM TO THE MOST RECENT EDITION OF ACI 347R.
CONCRETE REINFORCING STEEL
ALL REINFORCING STEEL SHALL BE DEFORMED BARS PER ASTM A615 OR A706, GRADE 60 UNLESS NOTED OTHERWISE. SEE 1/S5.00 FOR STANDARD REBAR DIMENSIONS, AND 2/S5.00 AND 3/S5.00 FOR
STANDARD DETAILING DIMENSIONS.
VERTICAL REINFORCING IN SHEAR WALLS SHALL BE DEFORMED BARS CONFORMING TO ASTM A706
GRADE 60. ASTM A615, GRADE 60 REINFORCEMENT MAY BE USED IN THESE MEMBERS IF THE
ACTUAL YIELD STRENGTH BASED ON MILL TESTS DOES NOT EXCEED THE SPECIFIED YIELD
STRENGTH BY MORE THAN 18,000 PSI AND THE RATIO OF THE ACTUAL ULTIMATE TENSILE
STRENGTH TO THE ACTUAL TENSILE YIELD STRENGTH IS NOT LESS THAN 1.25. IF MILL REPORTS ARE
NOT AVAILABLE, THE REINFORCING SHALL BE TESTED AT THE CONTRACTOR’S EXPENSE.
ALL REINFORCING STEEL SHALL BE SUPPORTED ON WELL-CURED CONCRETE BLOCKS, PLASTIC
CHAIRS OR APPROVED METAL CHAIRS, AS SPECIFIED BY THE CRSI MANUAL OF STANDARD
PRACTICE, MSP-1 AND SECURELY TIED IN PLACE WITH #16 ANNEALED IRON WIRE PRIOR TO PLACING
CONCRETE. REINFORCING STEEL SHALL BE DETAILED IN ACCORDANCE WITH THE GUIDE TO
PRESENTING REINFORCING STEEL DESIGN DETAILS, ACI 315R-18. BAR LENGTHS DETAILED ARE OUT
TO OUT AND DO NOT INCLUDE ALLOWANCE FOR HOOKS OR BENDS.
WELDING OR TACK WELDING OF REINFORCING BARS TO OTHER BARS OR EMBEDDED STEEL ITEMS IS PROHIBITED EXCEPT WHERE SPECIFICALLY APPROVED BY THE ENGINEER. WHERE WELDING IS
APPROVED, REINFORCING STEEL SHALL CONFORM TO ASTM A706 AND WELDING SHALL BE
PERFORMED BY AWS CERTIFIED WELDERS USING E9018 OR APPROVED ELECTRODES. WELDING
PROCEDURES SHALL CONFORM TO THE REQUIREMENTS OF AWS D1.4.
CAST-IN-PLACE CONCRETE COVER OVER REINFORCING STEEL SHALL BE AS SHOWN ON 4/S5.00.
SPECIFIED CONCRETE COVER SHALL BE MAINTAINED TO ALL REINFORCEMENT AT CONCRETE
REVEALS AND INSETS. SHOP DRAWINGS SHOWING CONCRETE REVEALS AND OTHER INSETS SHALL
BE SUBMITTED FOR REVIEW.
REINFORCING BARS SHALL BE LAP SPLICED PER 5/S5.00. AT THE CONTRACTOR’S OPTION,
MECHANICAL COUPLINGS MAY BE USED FOR ANY BAR SIZE AND AT ANY LOCATION, PROVIDED A
CURRENT ICC-ES REPORT DEMONSTRATES THE COUPLING CAN ACHIEVE A MINIMUM TENSILE
STRENGTH OF 125% OF THE SPECIFIED YIELD STRENGTH OF THE BAR AND 100% OF THE SPECIFIED
TENSILE STRENGTH OF THE SPLICED BAR.
HEADED BARS OR TERMINATORS SHALL BE PROVIDED WHERE INDICATED ON THE DRAWINGS OR AT
THE CONTRACTOR’S OPTION FOR CONGESTED AREAS OF REINFORCEMENT, SUBJECT TO THE
ENGINEER’S APPROVAL. HEADED BARS OR TERMINATORS SHALL MEET THE REQUIREMENTS OF ACI
318 AND ASTM A970 AND HAVE A CURRENT ICC-ES REPORT.
AT EACH RE-ENTRANT CORNER IN SLABS, PROVIDE ONE #4 X 4’-0” DIAGONALLY CENTERED ON THE
CORNER AT EACH LAYER OF REINFORCING STEEL.
FOR WALLS WITH #5 REINFORCING STEEL AND SMALLER, PROVIDE 2'-6" X 2'-6" REINFORCING STEEL CORNER BARS OF SAME SIZE AND SPACING AS HORIZONTAL BARS. CONTINUE HORIZONTAL WALL REINFORCING THROUGH PILASTERS, COLUMNS AND INTERSECTING WALLS. PROVIDE A MINIMUM OF
ONE #5 X 5’-0” FOR SINGLE LAYER REINFORCING AND TWO #5 X 5’-0” FOR DOUBLE LAYER
REINFORCING DIAGONALLY CENTERED AT EACH CORNER OF ALL WALL OPENINGS. ADDITIONALLY, PROVIDE A MINIMUM OF ONE #5 FOR SINGLE LAYER REINFORCING AND TWO #5 FOR DOUBLE LAYER REINFORCING ON ALL SIDES OF OPENING EXTENDING A MINIMUM OF 2’-6” BEYOND THE OPENING.
WELDED WIRE REINFORCEMENT
WELDED WIRE REINFORCEMENT SHALL BE ELECTRICALLY WELDED AND CONFORM TO ASTM A185.
LAP EDGES AND ENDS OF FABRIC A MINIMUM OF ONE MESH SPACING PLUS 2 INCHES, BUT NOT
LESS THAN 6 INCHES. WELDED WIRE REINFORCEMENT SHALL BE SUPPORTED ON CHAIRS IN
ACCORDANCE WITH THE CRSI MANUAL OF STANDARD PRACTICE.
CONCRETE ANCHORS
ALL CAST IN PLACE ANCHOR BOLTS SHALL BE SECURELY TIED IN THEIR FINAL POSITION PRIOR TO PLACING CONCRETE (WET-SETTING OF ANCHOR BOLTS IS NOT PERMITTED). ANCHOR RODS SHALL CONFORM TO ASTM F1554 GRADE 36. FURNISH ANCHOR RODS WITH MATCHING DOUBLE HEAVY HEX NUTS JAMMED AT THE END EMBEDDED IN CONCRETE. HOOKED ANCHOR RODS SHALL NOT BE USED
EXCEPT WHERE NOTED.
ALL HEADED STUD ANCHORS (HSA) SHALL CONFORM TO THE REQUIREMENTS OF AWS D1.1, TYPE B, AND ASTM A108. DEFORMED BAR ANCHORS (DBA) SHALL CONFORM TO ASTM A1064. ALL HSA AND
DBA SHALL BE WELDED WITH AUTOMATIC STUD WELDING EQUIPMENT PER THE
RECOMMENDATIONS OF THE STUD AND EQUIPMENT MANUFACTURER, UNLESS OTHERWISE
SPECIFIED.
POST INSTALLED CONCRETE ANCHORS SHALL CONSIST OF THE FOLLOWING UNLESS NOTED
OTHERWISE:
POST INSTALLED CONCRETE ANCHOR SCHEDULE:
· ANCHOR TYPE - SPECIFIED ANCHOR
· EXPANSION BOLTS - HILTI KWIK BOLT TZ2
· SCREW ANCHORS - HILTI KWIK HUS-EZ
· ADHESIVE ANCHORS - HILTI HIT-RE 500 V3
· POWER-ACTUATED FASTENERS - HILTI X-U P8 (1” EMBEDMENT)
ALL POST INSTALLED CONCRETE ANCHORS SHALL BE INSTALLED IN CONFORMANCE WITH THE
MANUFACTURER'S INSTALLATION CRITERIA AND PER THE CURRENT ICC EVALUATION REPORT.
ANCHOR INSTALLERS SHALL BE QUALIFIED AS REQUIRED BY JURISDICTION REQUIREMENTS.
ADHESIVE ANCHORS SHALL BE INSTALLED IN CONCRETE HAVING A MINIMUM AGE OF 21 DAYS.
NON-SHRINK GROUT
ALL NON-SHRINK GROUT SHALL BE NON-METALLIC GROUT CONFORMING TO ASTM C1107 AND SHALL HAVE A SPECIFIED MINIMUM COMPRESSIVE STRENGTH AT 28 DAYS OF AT LEAST 1000 PSI HIGHER THAN THE SUPPORTING CONCRETE STRENGTH. GROUT SHALL BE MIXED, APPLIED AND CURED IN
ACCORDANCE WITH THE MANUFACTURER’S INSTRUCTIONS. PRE-GROUTING OF BASE PLATES IS
NOT PERMITTED.
STRUCTURAL STEEL
DESIGN, FABRICATION AND ERECTION OF STRUCTURAL STEEL SHALL CONFORM TO THE
SPECIFICATION FOR STRUCTURAL STEEL BUILDINGS (AISC 360). QUALITY ASSURANCE (QA) IS REQUIRED FOR STRUCTURAL STEEL ITEMS PER AISC 360 AND 341 UNLESS SPECIFICALLY NOTED OTHERWISE. QUALITY CONTROL (QC) TO BE PROVIDED BY THE FABRICATOR, ERECTOR OR OTHER
RESPONSIBLE CONTRACTOR AS APPLICABLE. CONTRACTOR AND SPECIAL INSPECTOR TO
DOCUMENT QUALITY CONTROL AS REQUIRED IN AISC 360 SECTION N3 AND AISC 341 SECTION J2.
ALL STRUCTURAL AND MISCELLANEOUS STEEL SHALL CONFORM TO THE FOLLOWING MATERIAL
STANDARDS:
STRUCTURAL STEEL MATERIAL STANDARDS
SHAPE ASTM SPECIFICATION YIELD STRESS
W-SECTIONS A992 50 KSI
RECTANGULAR HSS A500, GRADE C 50 KSI
ROUND HSS A500, GRADE C 46 KSI
PIPE A53, GRADE B, TYPE E OR S 35 KSI
ALL OTHER SECTIONS AND PL A36 UNO 36 KSI
UNLESS NOTED OTHERWISE, ALL BOLTS TO BE ASTM F3125 GRADE A325 WITH MATCHING NUTS.
UNLESS CONNECTION IS NOTED AS SLIP-CRITICAL OR PRETENSIONED, NUTS SHALL BE TIGHTENED
TO A SNUG TIGHT CONDITION PER RESEARCH COUNCIL ON STRUCTURAL CONNECTIONS (RCSC)
SPECIFICATION FOR STRUCTURAL JOINTS, SECTION 8.1. FOR SLIP-CRITICAL AND PRETENSIONED
CONNECTIONS, INSTALLATION OF FASTENERS SHALL BE PER RCSC SECTION 8.2.
ALL STRUCTURAL STEEL SHALL HAVE ONE SHOP COAT OF PRIMER, EXCEPT SURFACES TO BE
EMBEDDED IN CONCRETE OR MASONRY OR STEEL TO BE GALVANIZED. EMBEDDED SURFACES
SHALL BE FREE OF CONTAMINANTS. ALL EXPOSED STRUCTURAL STEEL TO HAVE ONE FINISH COAT
OF RUST INHIBITING PAINT, COLOR BY OWNER.
ALL ZINC (GALV.) COATINGS ON IRON AND STEEL PRODUCTS SHALL CONFORM TO ASTM A123.
REPAIRS OF GALVANIZED COATINGS ARE TO CONFORM TO ASTM A780. HOT DIP GALVANIZED
COATINGS ON ASTM F3125 GRADE A325 FASTENER ASSEMBLIES SHALL CONFORM TO ASTM A153.
SURFACE PREPARATION OF GALVANIZED STEEL TO RECEIVE A FINISH COAT OF PAINT SHALL
CONFORM TO ASTM D6386.
REFER TO THE ARCHITECTURAL DRAWINGS FOR STEEL ELEMENTS THAT REQUIRE INTUMESCENT
FIRE PROOFING. INTUMESCENT COATINGS SHALL BEAR THE UNDERWRITERS LABORATORIES (UL) LABEL. STEEL MEMBERS SHALL BE PROPERLY PREPARED, INCLUDING THE USE OF A COMPATIBLE
PRIMER, AS SPECIFIED BY THE MANUFACTURER. INSTALL INTUMESCENT COATINGS IN
ACCORDANCE WITH THE MANUFACTURER'S INSTRUCTIONS.
STRUCTURAL STEEL WELDING
ALL WELDING SHALL CONFORM TO AMERICAN WELDING SOCIETY (AWS) D1.1 USING E70XX
ELECTRODES. WELDING SHALL BE PERFORMED BY WELDERS CERTIFIED BY AWS FOR THE WELD
TYPES SPECIFIED. WELD LENGTHS SHOWN ARE EFFECTIVE AS SPECIFIED PER THE SPECIFICATIONS OF THE AMERICAN INSTITUTE OF STEEL CONSTRUCTION (AISC). WHERE WELD LENGTHS ARE NOT SHOWN, THE WELD SHALL BE FULL LENGTH OF MEMBERS BEING JOINED. FIELD WELDING SYMBOLS
HAVE NOT NECESSARILY BEEN INDICATED ON THE DRAWINGS. WHERE SHOWN, PROPER FIELD
WELDING PER AWS D1.1 SHALL BE USED. WHERE NO FIELD WELDING SYMBOLS ARE SHOWN, IT IS
THE CONTRACTOR’S RESPONSIBILITY TO COORDINATE THE USE OF SHOP AND FIELD WELDS.
ALL PARTIAL JOINT PENETRATION GROOVE WELD SIZES SHOWN ON THE DRAWINGS REFER TO THE EFFECTIVE THROAT THICKNESS. ALL BUTT WELDS SHALL BE FULL PENETRATION WELDS UNLESS
NOTED OTHERWISE ON STRUCTURAL DRAWINGS. THE CONTRACTOR SHALL BE RESPONSIBLE FOR
THE JOINT PREPARATION AND WELDING PROCEDURES THAT INCLUDE, BUT ARE NOT LIMITED TO:
REQUIRED ROOT OPENINGS, ROOT FACE DIMENSIONS, GROOVE ANGLES, BACKING BARS, COPES, SURFACE ROUGHNESS VALUES AND TAPERS AND TRANSITIONS OF UNEQUAL PARTS.
SEISMIC FORCE RESISTING SYSTEM WELDS
ALL WELDS USED IN MEMBERS AND CONNECTIONS IN THE SEISMIC FORCE RESISTING SYSTEM
(SFRS) SHALL BE MADE WITH FILLER METALS MEETING THE REQUIREMENTS SPECIFIED IN AWS D1.8/S1.8M CLAUSES 6.1, 6.2 AND 6.3 IN ACCORDANCE WITH AISC 341-16 SECTION A3.4A. ALL WELDS
DENOTED AS 'DEMAND CRITICAL' SHALL CONFORM TO AISC 341-16 SECTION A3.4B.
ALL WELDS SHALL RECEIVE THE SAME FINISH COATING AS THE MEMBER BEING WELDED.
POWER ACTUATED FASTENERS
POWER ACTUATED FASTENERS SHALL CONSIST OF THE FOLLOWING AND MUST BE DRIVEN TO
WHERE THE POINT THE FASTENER PENETRATES THROUGH THE STEEL BASE MATERIAL, UNLESS
NOTED OTHERWISE:
· POWER-ACTUATED FASTENERS: 0.157” DIAMETER SIMPSON PDPA
ALL POWER ACTUATED FASTENERS SHALL BE INSTALLED IN CONFORMANCE WITH THE
MANUFACTURER'S INSTALLATION CRITERIA AND PER THE CURRENT ICC EVALUATION REPORT.
POWER ACTUATED FASTENER INSTALLERS SHALL BE QUALIFIED AS REQUIRED BY JURISDICTION
REQUIREMENTS.
COLD-FORMED STEEL
ALL COLD-FORMED STEEL FRAMING SHALL CONFORM TO THE AISI NORTH AMERICAN
SPECIFICATION FOR THE DESIGN OF COLD-FORMED STEEL STRUCTURAL MEMBERS WITH
SUPPLEMENTS. MEMBER TYPES AND SIZES SHOWN ON THE DRAWINGS REFER TO MEMBERS AS
DEFINED BY THE STEEL STUD MANUFACTURERS ASSOCIATION (SSMA). SEE THE CONTRACT
DRAWINGS AS SPECIFIED ON DETAIL 4/S7.01 FOR REQUIRED THICKNESSES AND JOIST/BEAM
DESIGNATIONS.
ALL STRUCTURAL COLD-FORMED STEEL MEMBERS SHALL BE MILL CERTIFIED PRIME STEEL
MEETING ASTM A653 STRUCTURAL QUALITY. ALL COLD-FORMED STEEL SHALL BE GALVANIZED PER ASTM A653 WITH MINIMUM COATING OF G60 FOR EXTERIOR AND/OR LOAD BEARING MEMBERS AND
G40 FOR INTERIOR NON-LOAD BEARING MEMBERS.
COLD FORMED STEEL MATERIAL STANDARDS
THICKNESS GRADE
ASTM
SPECIFICATION
YIELD
STRESS
(Fy)
TENSILE
STRESS
(Fu)
THINNER THAN 16 GAGE (54 MILS) 33 ASTM A653 33 KSI 45 KSI
16 GAGE (54 MILS) AND THICKER 50 ASTM A653 50 KSI 60 KSI
TRACK SHALL BE THE SAME GAUGE AS STUDS SPECIFIED UNLESS NOTED OTHERWISE AND SHALL
BE UNPUNCHED AT THE TOP AND BOTTOM OF WALL. TRACK SHALL BE OF ADEQUATE SIZE TO
DEVELOP FULL STUD BEARING AT WALLS AND SHALL BE SIZED TO FIT STUDS. PROVIDE COMPLETE, UNIFORM AND LEVEL SUPPORT FOR THE BOTTOM TRACK AT EACH STUD. VERIFY THAT STUDS ARE
PROPERLY SEATED IN TRACKS PRIOR TO FASTENING.
COLD-FORMED STEEL CONNECTORS
BOLTED CONNECTIONS ARE TO USE AS A MINIMUM ASTM A307 (TYPE A) STRUCTURAL BOLTS.
ALL SCREWS SHALL BE A #10 MINIMUM SIZE AND CONFORM TO ASTM C1513 STEEL TAPPING
SCREWS, ASTM C-1002 AND ASTM C-954 TYPE S AND/OR TYPE S-12. SCREWS TO BE TESTED IN ACCORDANCE WITH SAE J78 STANDARDS. LENGTH OF SCREWS SHOULD BE APPROXIMATELY 3/8” TO
1/2” LONGER THAN THE TOTAL MATERIAL THICKNESS AND A MINIMUM OF 3 EXPOSED THREADS
SHOULD EXTEND THROUGH THE STEEL. ALL SCREWS SHALL BE THREAD-FORMING OR THREAD-
CUTTING, WITH OR WITHOUT A SELF-DRILLING POINT. SCREWS SHALL BE INSTALLED AND
TIGHTENED IN ACCORDANCE WITH THE MANUFACTURER'S RECOMMENDATIONS. ALL FASTENERS
THAT FASTEN DISSIMILAR METALS (SUCH AS ALUMINUM AND STEEL) ARE TO BE HOT DIPPED
GALVANIZED OR OTHERWISE ADEQUATELY PROTECTED TO PREVENT CORROSION.
PREFABRICATED METAL CONNECTORS ARE TO BE MANUFACTURED BY THE STEEL NETWORK OR
SIMPSON STRONG-TIE AND SHALL BE INSTALLED IN ACCORDANCE WITH THE MANUFACTURER’S
SPECIFICATIONS USING RECOMMENDED FASTENERS. OTHER SUBSTITUTIONS OF METAL
CONNECTORS REQUIRE REVIEW AND APPROVAL BY THE STRUCTURAL ENGINEER OF RECORD
PRIOR TO INSTALLATION.
COLD-FORMED STEEL FASTENING SCHEDULE
SCREWS SHALL BE INSTALLED PER THE FASTENER SCHEDULE SHOWN UNLESS OTHERWISE NOTED
ON THE DRAWINGS. SCREWS SHALL NOT BE OVERDRIVEN.
COLD-FORMED STEEL FASTENING SCHEDULE
ITEM FASTENERS
TRACK TO STUDS (1) #10 EACH FACE
SHEATHING
GYPSUM WALL BOARD
#6 DRYWALL SCREWS AT 7" OC AT ALL
FRAMING MEMBERS
ALTERNATE FASTENING OF PINS MUST BE REVIEWED AND ACCEPTED BY THE REGISTERED DESIGN
PROFESSIONAL.
TYPICAL SCREW DESIGNATION: #10 SIZE, 0.190” NOMINAL DIAMETER WITH 3/8” WASHER DIAMETER.
COLD-FORMED STEEL ANCHORAGE TO CONCRETE AND STEEL
WHERE INDICATED ON THE DRAWINGS, POWER-ACTUATED FASTENERS TO SUPPORTING FRAMING
SHALL CONSIST OF THE FOLLOWING:
PAF TO CONCRETE: 0.157” DIAMETER SIMPSON PDPA (1” EMBEDMENT)
PAF TO STEEL: 0.157M DIAMETER SIMPSON PDPA (FULL STEEL PENETRATION)
PAF SHALL BE INSTALLED IN CONFORMANCE WITH THE MANUFACTURER'S INSTALLATION CRITERIA
AND PER THE CURRENT ICC EVALUATION REPORT.
HELICAL ANCHORS
BASIS OF DESIGN FOR ALL HELICAL ANCHORS IS THE RAMJACK 4021.SD BRACKET W/ 2 7/8M DIA
HELICAL PILE. HELICAL ANCHOR CAPACITIES SHALL BE PER THE GEOTECHNICAL REPORT.
CONTRACTOR SHALL PROVIDE COMPLETE SUBMITTAL FOR HELICAL ANCHORS.
STATEMENT OF SPECIAL INSPECTION NOTES:
1. SPECIAL INSPECTIONS SHALL CONFORM TO SECTION 1705 OF THE 2019 OSSC,
CONTRACT DOCUMENTS AND APPROVED SUBMITTALS. REFER TO SPECIAL
INSPECTION AND TESTING TABLES FOR PROJECT REQUIREMENTS.
2. SPECIAL INSPECTIONS AND ASSOCIATED TESTING SHALL BE PERFORMED BY
AN APPROVED ACCREDITED INDEPENDENT AGENCY MEETING THE
REQUIREMENTS OF ASTM E329 (MATERIALS). THE INSPECTION AND TESTING
AGENCY SHALL FURNISH TO THE STRUCTURAL ENGINEER A COPY OF THEIR
SCOPE OF ACCREDITATION. SPECIAL INSPECTORS SHALL BE APPROVED BY
THE BUILDING OFFICIAL. WELDING INSPECTORS SHALL BE QUALIFIED PER
SECTION 6.1.4.1(1) OF AWS D1.1.
3. THE SPECIAL INSPECTOR SHALL OBSERVE THE INDICATED WORK FOR
COMPLIANCE WITH THE APPROVED CONSTRUCTION DOCUMENTS. ALL
DISCREPANCIES SHALL BE BROUGHT TO THE ATTENTION OF THE
CONTRACTOR FOR CORRECTION AND NOTED IN THE INSPECTION REPORTS.
4. THE SPECIAL INSPECTOR AND GEOTECHNICAL ENGINEER SHALL FURNISH
INSPECTION REPORTS FOR EACH INSPECTION TO THE BUILDING OFFICIAL,
STRUCTURAL ENGINEER, ARCHITECT, CONTRACTOR AND OWNER. THE
SPECIAL INSPECTION AGENCY SHALL SUBMIT A FINAL REPORT STATING THAT
THE WORK REQUIRING SPECIAL INSPECTION WAS INSPECTED AND IS IN
CONFORMANCE WITH THE APPROVED CONSTRUCTION DOCUMENTS AND THAT
ALL DISCREPANCIES NOTED IN THE INSPECTION REPORTS HAVE BEEN
CORRECTED.
5. QUALITY ASSURANCE (QA) IS REQUIRED FOR STRUCTURAL STEEL ITEMS PER
AISC 360 AND 341, UNLESS SPECIFICALLY NOTED OTHERWISE. QUALITY
CONTROL (QC) TO BE PROVIDED BY THE FABRICATOR, ERECTOR OR OTHER
RESPONSIBLE CONTRACTOR AS APPLICABLE. CONTRACTOR AND SPECIAL
INSPECTOR TO DOCUMENT QUALITY CONTROL AS REQUIRED IN AISC 360
SECTION N3 AND AISC 341 SECTION J2.
6. INSPECTION TYPES:
a. CONTINUOUS: THE FULL-TIME OBSERVATION OF WORK REQUIRING
SPECIAL INSPECTION BY AN APPROVED SPECIAL INSPECTOR WHO IS
PRESENT IN THE AREA WHERE THE WORK IS BEING PERFORMED.
b. PERIODIC: THE PART-TIME OR INTERMITTENT OBSERVATION OF WORK
REQUIRING SPECIAL INSPECTION BY AN APPROVED SPECIAL INSPECTOR
WHO IS PRESENT IN THE AREA WHERE THE WORK HAS BEEN OR IS
BEING PERFORMED AND AT THE COMPLETION OF THE WORK.
c. OBSERVE: OBSERVE THESE FUNCTIONS ON A RANDOM, DAILY BASIS.
OPERATIONS NEED NOT BE DELAYED PENDING OBSERVATIONS.
d. PERFORM: INSPECTIONS SHALL BE PERFORMED PRIOR TO THE FINAL
ACCEPTANCE OF THE ITEM.
7. PERFORM INSPECTION PRIOR TO FINAL ACCEPTANCE OF THE ITEM FOR TEN
WELDS TO BE MADE BY A GIVEN WELDER. THE WELDER IS REQUIRED TO
DEMONSTRATE THE UNDERSTANDING OF REQUIREMENTS AND POSSESSION
OF SKILLS AND TOOLS TO VERIFY THESE ITEMS. ONCE THE INITIAL TEN WELDS
HAVE BEEN ACCEPTED, THE WELDER SHALL REDUCE THE PERFORM
DESIGNATION OF THIS TASK TO OBSERVE. SHOULD THE INSPECTOR
DETERMINE THAT THE WELDER HAS STOPPED CONDUCTING THIS TASK, THE
TASK SHALL BE RETURNED TO PERFORM UNTIL SUCH TIME AS THE INSPECTOR
HAS RE-ESTABLISHED ADEQUATE ASSURANCE THAT THE WELDER WILL
CONDUCT THE INSPECTION TASKS LISTED.
8. SPECIAL INSPECTION OF MECHANICAL POST INSTALLED ANCHORS SHALL BE IN
STRICT CONFORMANCE WITH THE ICC REPORT AND MANUFACTURER'S
INSTALLATION REQUIREMENTS. ANCHOR INSTALLERS SHALL BE QUALIFIED AS
REQUIRED BY JURISDICTION REQUIREMENTS. INSPECTION REPORTS SHALL
IDENTIFY NAMES OF INSTALLERS. SPECIAL INSPECTOR SHALL PROVIDE
DOCUMENTATION AT THE END OF ANCHOR INSTALLATIONS STATING THAT THE
ANCHORS WERE INSPECTED PER APPROVED ANCHOR EVALUATION REPORT.
9. TESTING ABBREVIATIONS:
a. NDT - NON-DESTRUCTIVE TESTING
b. C.J.P. - COMPLETE JOINT PENETRATION
c. MT - MAGNETIC PARTICLE TESTING
d. RBS - REDUCED BEAM SECTION
10. DOCUMENT (D): INDICATES CONTRACTOR AND SPECIAL INSPECTOR TO
PROVIDE DOCUMENTATION IN ACCORDANCE WITH AISC 341.
CONTRACTOR RESPONSIBILITY:
EACH CONTRACTOR RESPONSIBLE FOR THE CONSTRUCTION OF THE MAIN WIND OR
SEISMIC FORCE-RESISTING SYSTEM, DESIGNATED SEISMIC SYSTEM OR A WIND OR
SEISMIC RESISTING COMPONENT LISTED THE TABLES SHALL SUBMIT A WRITTEN
STATEMENT OF RESPONSIBILITY TO THE BUILDING OFFICIAL AND THE OWNER PRIOR
TO THE COMMENCEMENT OF WORK ON THE SYSTEM OR COMPONENT. THE
CONTRACTOR'S STATEMENT OF RESPONSIBILITY SHALL CONTAIN THE FOLLOWING:
ACKNOWLEDGEMENT OF AWARENESS OF THE SPECIAL REQUIREMENTS CONTAINED
IN THE STATEMENT OF SPECIAL INSPECTIONS.
1. ACKNOWLEDGEMENT THAT CONTROL WILL BE EXERCISED TO OBTAIN
CONFORMANCE WITH THE CONSTRUCTION DOCUMENTS APPROVED BY THE
BUILDING OFFICIAL.
2. PROCEDURES FOR EXERCISING CONTROL WITHIN THE CONTRACTOR'S
ORGANIZATION, THE METHOD AND FREQUENCY OF REPORTING AND
DISTRIBUTION OF THE REPORTS.
IDENTIFICATION AND QUALIFICATIONS OF THE PERSON(S) EXERCISING SUCH
CONTROL AND THEIR POSITION(S) IN THE ORGANIZATION.
SHEET
9600 SW Oak St | Suite 400 Portland, OR | 97224
503.246.1250 | miller-se.com
MCE PROJECT NO:
SHEET SCALE:
DRAWN BY:
SHEET CONTENT
ISSUE DATE:
CHECKED BY:
COPYRIGHT 2023
Miller Consulting Engineers, Inc.
CONSULTING
MILLER
ENGINEERS
AS INDICATED
BCH
S0.02
V O
LU
N
T A
R Y
S E
IS
M
IC
U
P G
R A
D E
JF
H
Q
O W
E N
S U
M M
E R
S B
U
IL
D
IN
G
M
IL
IT
A R
Y W
A Y
S E
S A
L E
M , O
R E
G O
N
STRUCTURAL NOTES
230072
08.25.23
R E
V
D A
T E
D E
S C
R
IP
T
IO
N
OREGON
J A
N
U A R Y 2 3 , 2
E
N G I N E E
R
51043RE
G ISTERED PROFESS IONAL
ER
I C R . WA T SON
STRUCTURA L
EXPIRES: 06 - 30 - 2024
A DIGITAL SIGNATURE WATERMARK ON
SHEET S0.01 INDICATES THIS SHEET IS PART
OF AN ELECTRONICALLY SIGNED DOCUMENT
GENERAL - SPECIAL INSPECTIONS
SYSTEM OR MATERIAL
OSSC CODE
REFERENCE
CODE OR
STANDARD
REFERENCE
FREQUENCY
REMARKS
CONTINUOUS PERIODIC
FABRICATORS 1705.10 1704.2.5
SPECIAL INSPECTION IS REQUIRED FOR STRUCTURAL LOAD-BEARING
MEMBERS AND ASSEMBLIES FABRICATED ON THE PREMISES OF A
FABRICATOR'S SHOP. SPECIAL INSPECTIONS SHALL BE PERFORMED
DURING FABRICATION. PERFORMING SPECIAL INSPECTIONS IS NOT
REQUIRED WHERE FABRICATOR HAS BEEN APPROVED AS AN
APPROVED FABRICATOR, PER SECTION 1704.2.5.1.
DEFERRED SUBMITTALS X
SPECIAL INSPECTION REQUIREMENTS FOR DEFERRED SUBMITTAL
ITEMS, INCLUDING REQUIREMENTS FOR DESIGNATED SEISMIC
SYSTEMS IN ACCORDANCE WITH OSSC SECTION 1705.12.4 IF
APPLICABLE, TO BE SPECIFIED BY THE SYSTEM ENGINEER AND
INCLUDED WITH DEFERRED SUBMITAL DOCUMENTS.
SUBMITTALS TO THE BUILDING OFFICIAL 1704.5 X
CERTIFICATES OF COMPLIANCE, REPORTS OF PRE-CONSTRUCTION
TESTS, OR REPORTS OF MATERIAL PROPERTIES SHALL BE
SUBMITTED TO THE BUILDING OFFICIAL.
POST INSTALLED MECHANICAL ANCHORS AND ADHESIVE ANCHORS
(EXCLUDING CONDITIONS NOTED ABOVE) IN HARDENED CONCRETE AND
COMPLETED MASONRY
X
SHEET
9600 SW Oak St | Suite 400 Portland, OR | 97224
503.246.1250 | miller-se.com
MCE PROJECT NO:
SHEET SCALE:
DRAWN BY:
SHEET CONTENT
ISSUE DATE:
CHECKED BY:
COPYRIGHT 2023
Miller Consulting Engineers, Inc.
CONSULTING
MILLER
ENGINEERS
AS INDICATED
BCH
S0.03
V O
LU
N
T A
R Y
S E
IS
M
IC
U
P G
R A
D E
JF
H
Q
O W
E N
S U
M M
E R
S B
U
IL
D
IN
G
M
IL
IT
A R
Y W
A Y
S E
S A
L E
M , O
R E
G O
N
SPECIAL
INSPECTIONS
230072
08.25.23
R E
V
D A
T E
D E
S C
R
IP
T
IO
N
INSTALLATION 1705.9
GEOTECHNICAL AND
ICC EVALUATION
REPORTS
X
BY THE GEOTECHNICAL ENGINEER. SPECIAL INSPECTIONS APPLY
TO VERIFYING INSTALLATION EQUIPMENT USED, PILE
DIMENSIONS, TIP ELEVATIONS, FINAL DEPTH, FINAL INSTALLATION
TORQUE AND OTHER PERTINENT INSTALLATION DATA AS
REQUIRED.
HELICAL PILE (SOIL SCREW) ANCHORS
PRIOR TO PLACEMENT OF COMPACTED FILL, INSPECT SUBGRADE AND VERIFY
THAT SITE HAS BEEN PREPARED PROPERLY X
VERIFY USE OF PROPER MATERIALS, DENSITIES AND LIFT THICKNESSES
DURING PLACEMENT AND COMPACTION OF COMPACTED FILL X
PERFORM CLASSIFICATION AND TESTING OF COMPACTED FILL MATERIALS X
VERIFY EXCAVATIONS ARE EXTENDED TO PROPER DEPTH AND HAVE REACHED
PROPER MATERIAL X
VERIFY MATERIALS BELOW SHALLOW FOUNDATIONS ARE ADEQUATE TO
ACHIEVE THE DESIGN BEARING CAPACITY
1705.6
GEOTECHNICAL
REPORT
X
BY THE GEOTECHNICAL ENGINEER - TO BE SPECIFIED IN
GEOTECHNICAL REPORT
SOILS
CONTINUOUS PERIODIC
SYSTEM OR MATERIAL
OSSC CODE
REFERENCE
CODE OR STANDARDS
REFERENCE
FREQUENCY
REMARKS
SOILS/GEOTECHNICAL - SPECIAL INSPECTIONS
TEST ELEMENTS
1705.6 1705.7
REFERENCE SPECIFICATIONS
FOR PERFORMANCE
VARIFICATION AND PROOF LOAD
TESTING REQUIREMENTS
BY THE GEOTECHNICAL ENGINEER - TO BE SPECIFIED IN
GEOTECHNICAL REPORT
MATERIAL VERIFICATION
VARIES; CLASSIFICATION AND
TESTING OF CONTROLLED FILL
MATERIALS
X
BY THE GEOTECHNICAL ENGINEER - TO BE SPECIFIED IN
GEOTECHNICAL REPORT
FILL IN-PLACE DENSITY OR PREPARED SUBGRADE DENSITY
1705.6
VARIES; GEOTECHNICAL
REPORT OR MINIMUM PER
OSSC APPENDIX J107.5,
WHICHEVER IS GREATER
X
BY THE GEOTECHNICAL ENGINEER - TO BE SPECIFIED IN
GEOTECHNICAL REPORT
CONTINUOUS PERIODIC
SYSTEM OR MATERIAL
OSSC CODE
REFERENCE
CODE OR STANDARD
REFERENCE
FREQUENCY
REMARKS
SOILS/GEOTECHNICAL - TESTING
REINFORCING STEEL MECHANICAL COUPLERS, TERMINATORS AND
FORMSAVERS
ICC EVALUATION
REPORTS X
EMBEDDED ITEMS IN CONCRETE X
ALL NON-STRUCTURAL EMBEDDED ITEMS, SUCH AS CONDUITS, PIPES
AND SLEEVES, SHALL BE REVIEWED FOR CONFORMANCE WITH
STRUCTURAL DOCUMENTS FOR SIZE, SPACING, LOCATION, EDGE
DISTANCE AND TRIM REINFORCING.
VERIFICATION OF FORMWORK
ACI 318: 26.11.1.2(b),
26.13.3.3 X
SPECIAL INSPECTIONS APPLY TO SHAPE, LOCATION AND DIMENSIONS
OF THE CONCRETE MEMBER BEING FORMED
CONCRETE CURING 1908.9
ACI 318: 26.5.3 -
26.5.5, 26.13.3.3 X
VERIFY MAINTENANCE OF SPECIFIED CURING TEMPERATURES AND
TECHNIQUES
CONCRETE PLACEMENT, NON-SHRINK GROUT
1908.6, 1908.7, 1908.8
ACI 318: 26.5,
26.13.3.2(a) X
CONCRETE SPECIMENS FOR TESTING 1908.10
ASTM C172
ASTM C31
ACI 318: 26.5, 26.12
X
PRIOR TO CONCRETE PLACEMENT, FABRICATE CONCRETE SPECIMENS
FOR TESTING. SEE THE CONCRETE TESTING TABLE FOR ADDITIONAL
INFORMATION.
VERIFYING USE OF REQUIRED MIX DESIGN(S)
1904.1 1904.2 1908.2 1908.3
ACI 318: CH. 19,
26.4.3, 26.4.4 X
INSPECT ANCHORS/BOLTS CAST IN CONCRETE - ACI 318: 17.8.2 X
ALL CAST-IN-PLACE ANCHORS/BOLTS SHALL BE VISUALLY INSPECTED.
REFERENCE STEEL INSPECTIONS FOR ADDITIONAL INSTALLATION,
MATERIAL AND WELDING INSPECTIONS OF STEEL ITEMS EMBEDDED IN
CONCRETE (HEADED STUDS, DBA's, ETC.)
3. ALL OTHER REINFORCING STEEL WELDING, X
2. INSPECT SINGLE-PASS FILLET WELDS, MAXIMUM 5/16" FILLET X
1. VERIFICATION OF WELDABILITY OF REINFORCING STEEL OTHER
THAN ASTM A706 X
WELDING REINFORCING STEEL
1705.3.1 1705.3.2 1903.1 1903.2
AWS D1.4
ACI 318: 26.6.4
REINFORCING STEEL
1901.5.2 1908.4
ACI 318: CH. 20,
25.2, 25.3, 26.6.1-26.6.3, 26.13.3.3
X
REINFORCING TO COMPLY WITH ALL CODE PROTECTION, SPACING AND
TOLERANCE LIMITS.
GENERAL
1705.3
1901.6 ACI 318: 26.13
SPECIAL INSPECTIONS OF CONCRETE SHALL CONFORM TO THE
REQUIREMENTS OF SECTION 1705.3 OF THE IBC AND SECTION 26.13 OF
ACI 318.
CONTINUOUS PERIODIC
SYSTEM OR MATERIAL
OSSC CODE
REFERENCE
CODE OR
STANDARD
REFERENCE
FREQUENCY
REMARKS
CONCRETE - SPECIAL INSPECTIONS
CONCRETE TEMPERATURE ASTM C1064
CONCRETE AIR CONTENT ASTM C231
CONCRETE SLUMP ASTM C143
CONCRETE STRENGTH
1705.3, ASTM
C172, ASTM C
31, ACI 318
26.12, ACI 318
26.5
ASTM C39
EACH 150 CY NOR LESS THAN
EACH 5000 SF OF SLAB OR
WALL PLACED EACH SHIFT
FABRICATE SPECIMENS AT TIME FRESH CONCRETE IS PLACED
SYSTEM OR MATERIAL
OSSC CODE
REFERENCE
CODE OR
STANDARD
REFERENCE
FREQUENCY REMARKS
CONCRETE - TESTING
2c) BASE METAL NDT FOR LAMELLAR TEARING AND LAMINATIONS
FOR BASE METAL THICKNESS (t) OF 1 1/2"
AND GREATER AND CONNECTED
MATERIAL THICKNESS OF 3/4" AND
GREATER, UT FOR DISCONTINUITIES
BEHIND AND ADJACENT TO THE FUSION
LINE.
ANY BASE METAL DISCONTINUITIES FOUND WITHIN t/4 OF THE STEEL
SURFACE SHALL BE ACCEPTED OR REJECTED ON THE BASIS OF THE
CRITERIA OF AWS D1.1/D1.1M TABLE 6.2. t IS THE THICKNESS OF THE
PART SUBJECTED TO THE THROUGH-THICKNESS STRAIN
2b) COLUMN SPLICE AND COLUMN TO BASE PL PJP GROOVE WELD NDT
UT SHALL BE PERFORMED ON PJP
GROOVE WELDS IN COLUMN SPLICES AND
COLUMN TO BASE PL WELDS
2a) CJP GROOVE WELD NDT
1705.13.1 AISC 341 SECTION J6
UT SHALL BE PERFORMED ON 5/16"
THICKNESS AND GREATER. MT SHALL BE
PERFORMED ON 25% OF ALL
BEAM-TO-COLUMN CJP GROOVE WELDS.
WELD DISCONTINUITIES SHALL BE ACCEPTED OR REJECTED ON THE
BASIS OF CRITERIA OF AWS D1.1/D1.1M TABLE 6.2. UT TESTING NOT
REQUIRED ON THICKNESS LESS THAN 5/16"
SYSTEM OR MATERIAL
OSSC CODE
REFERENCE
CODE OR STANDARD
REFERENCE DESCRIPTION/FREQUENCY REMARKS
STEEL LATERAL SYSTEM - TESTING
STUD/DBA APPLICATION QUALIFICATION 1705.2.1 AWS D1.1 7.6 NON-PREQUALIFIED APPLICATIONS
THIS TESTING PERFORMED BY CONTRACTOR AND CONFIRMED BY
SPECIAL INSPECTOR
PRE-CONSTRUCTION TESTING OF WELDING STUDS, WELDED REINFORCING
BARS AND DBA'S 1705.2.1 AWS D1.1 7.7.1
EACH SIZE AND TYPE OF STUD/BAR EACH
SHIFT
THIS TESTING PERFORMED BY CONTRACTOR AND CONFIRMED BY
SPECIAL INSPECTOR
MAGNETIC PARTICLE (MT) TESTING OF WELDS 1705.2.1
AWS D1.1 6.14.4
AISC360 N5.5c
REQUIRED AT THERMALLY CUT ACCESS HOLES WHERE FLANGE
THICKNESS EXCEEDS 2" FOR ROLLED SHAPES OR WHEN THE WEB
THICKNESS EXCEEDS 2" FOR BUILT-UP SHAPES. REQUIRED WHERE
SPECIFICALLY NOTED ON DRAWINGS
ULTRASONIC (UT) TESTING OF WELDS 1705.2.1 AWS D1.1 6.13 & 6.14.3 ALL C.J.P. WELDS 5/16" AND THICKER REQUIRE UT TESTING.
STEEL
SYSTEM OR MATERIAL
OSSC CODE
REFERENCE
CODE OR STANDARD
REFERENCE DESCRIPTION/FREQUENCY REMARKS
STEEL - TESTING
PRIOR TO APPLICATION OF FINISHES
PRIOR TO INSTALLATION OF FIRST BRACE FRAMEAS REQUIRED BY THE DESIGN PROFESSIONAL 1704.6.1 X
PRIOR TO FIRST FOUNDATION POUR
CONTINUOUS PERIODIC
IBC CODE
REFERENCE
CODE OR
STANDARD
REFERENCE
FREQUENCY
SYSTEM OR MATERIAL
INSPECTION
REMARKS
STRUCTURAL OBSERVATION
OREGON
J A
N
U A R Y 2 3 , 2
E
N G I N E E
R
51043RE
G ISTERED PROFESS IONAL
ER
I C R . WA T SON
STRUCTURA L
EXPIRES: 06 - 30 - 2024
A DIGITAL SIGNATURE WATERMARK ON
SHEET
9600 SW Oak St | Suite 400 Portland, OR | 97224
503.246.1250 | miller-se.com
MCE PROJECT NO:
SHEET SCALE:
DRAWN BY:
SHEET CONTENT
ISSUE DATE:
CHECKED BY:
COPYRIGHT 2023
Miller Consulting Engineers, Inc.
CONSULTING
MILLER
ENGINEERS
AS INDICATED
BCH
S0.04
V O
LU
N
T A
R Y
S E
IS
M
IC
U
P G
R A
D E
JF
H
Q
O W
E N
S U
M M
E R
S B
U
IL
D
IN
G
M
IL
IT
A R
Y W
A Y
S E
S A
L E
M , O
R E
G O
N
SPECIAL
INSPECTION
230072
08.25.23
R E
V
D A
T E
D E
S C
R
IP
T
IO
N
PROTECTED ZONE - NO HOLES AND UNAPPROVED ATTACHMENTS MADE BY
FABRICATOR OR ERECTOR, AS APPLICABLE
AISC 341 TABLE J8.1
AISC 341 D1.3
AISC 341 I2.1
X(D)
(D)DOCUMENT - THE INSPECTOR SHALL PREPARE REPORTS
INDICATING THAT THE WORK HAS BEEN PERFORMED IN
ACCORDANCE WITH THE CONTRACT DOCUMENTS.
OTHER INSPECTION TASKS
DOCUMENT ACCEPTED AND REJECTED CONNECTION 1705.12.1 AISC 341 TABLE J7.3 X(D)
(D)DOCUMENT - THE INSPECTOR SHALL PREPARE REPORTS
INDICATING THAT THE WORK HAS BEEN PERFORMED IN
ACCORDANCE WITH THE CONTRACT DOCUMENTS.
INSPECTION TASKS AFTER BOLTING
FASTENER COMPONENT NOT TURNED BY THE WRENCH PREVENTED FROM
ROTATING X
JOINT BROUGHT TO THE SNUG TIGHT CONDITION PRIOR TO THE
PRETENSIONING OPERATION X
FASTENER ASSEMBLIES PLACED IN ALL HOLES AND WASHERS (IF REQUIRED)
ARE POSITIONED AS REQUIRED
1705.12.1
AISC 341 TABLE J7.2
RCSC
SPECIFICATION FOR
STRUCTURAL
JOINTS USING
HIGH-STRENGTH
BOLTS
X
INSPECTION TASKS DURING BOLTING
PROPER STORAGE PROVIDED FOR BOLTS, NUTS, WASHERS AND OTHER
FASTENER COMPONENTS X
PRE-INSTALLATION VERIFICATION TESTING BY INSTALLATION PERSONNEL
OBSERVED FOR FASTENER ASSEMBLIES AND METHODS USED X (D)
(D)DOCUMENT - THE INSPECTOR SHALL PREPARE REPORTS
INDICATING THAT THE WORK HAS BEEN PERFORMED IN
ACCORDANCE WITH THE CONTRACT DOCUMENTS.
CONNECTING ELEMENTS, INCLUDING THE APPROPRIATE FAYING SURFACE
CONDITION AND HOLE PREPARATION, IF SPECIFIED, MEET APPLICABLE
REQUIREMENTS
X
PROPER BOLTING PROCEDURE SELECTED FOR JOINT DETAIL X
PROPER FASTENERS SELECTED FOR THE JOINT DETAIL
1705.12.1
AISC 341 TABLE J7.1
RCSC
SPECIFICATION FOR
STRUCTURAL
JOINTS USING
HIGH-STRENGTH
BOLTS
X
INSPECTION TASKS PRIOR TO BOLTING
REPAIR ACTIVITIES X(D)
BACKING REMOVED, WELD TABS REMOVED AND FINISHED, AND FILLET WELDS
ADDED (IF REQUIRED) X(D)
PLACEMENT OF REINFORCING OR CONTOURING FILLET WELDS (IF REQUIRED)
K-AREA * X(D)
POROSITY X(D)
UNDERCUT X(D)
WELD PROFILE AND SIZE X(D)
CRATER CROSS SECTION X(D)
WELD/BASE-METAL FUSION X(D)
CRACK PROHIBITION X(D)
WELDS MEET VISUAL ACCEPTANCE CRITERIA
(D)DOCUMENT - THE INSPECTOR SHALL PREPARE REPORTS
INDICATING THAT THE WORK HAS BEEN PERFORMED IN
ACCORDANCE WITH THE CONTRACT DOCUMENTS.
* WHEN WELDING OF DOUBLER PLATES, CONTINUITY PLATES, OR
STIFFENERS HAS BEEN PERFORMED IN THE K-AREA, VISUALLY
INSPECT THE WEB K-AREA FOR CRACKS WITHIN 3 INCHES OF THE
WELD. THE VISUAL INSPECTION SHALL BE PERFORMED NO
SOONER THAN 48 HOURS FOLLOWING COMPLETION OF THE
WELDING
SIZE, LENGTH, AND LOCATION OF WELDS
1705.12.1
AISC 341 TABLE J6.3
AWS D1.8/D1.8M
X
WELDS CLEANED X
VISUAL INSPECTION TASKS AFTER WELDING
NO WELDING OVER CRACKED TACKS X
EACH PASS MEETS QUALITY REQUIREMENTS X
EACH PASS WITHIN PROFILE LIMITATIONS X
INTERPASS AND FINAL CLEANING X
WELDING TECHNIQUES
PRECIPITATION AND TEMPERATURE X
WIND SPEED WITHIN LIMITS X
ENVIRONMENTAL CONDITIONS
EXPOSURE CONTROL X
PACKAGING X
CONTROL AND HANDLING OF WELDING CONSUMABLES
USE OF QUALIFIED WELDERS X
INTERMIX OF FILLER METALS AVOIDED UNLESS
APPROVED X
PROPER POSITION (F, V, H, OH) X
INTERPASS TEMPERATURE MAINTAINED (MIN/MAX.) X
PREHEAT APPLIED X
SHIELDING GAS TYPE/FLOW RATE X
SELECTED WELDING MATERIALS X
TRAVEL SPEED X
SETTINGS ON WELDING EQUIPMENT X
WPS FOLLOWED
1705.12.1
AISC 341 TABLE J6.2
AWS D1.8/D1.8M
VISUAL INSPECTION TASKS DURING WELDING
TACKING (TACK WELD QUALITY AND LOCATION) X
CLEANLINESS(CONDITION OF STEEL SURFACES) X
DIMENSIONS (ALIGNMENT, GAPS AT ROOT) X
NOTE 7
FIT-UP OF FILLET WELDS
BACKING TYPE AND FIT (IF APPLICABLE) X
TACKING (TACK WELD QUALITY AND LOCATION) X
CLEANLINESS (CONDITION OF STEEL SURFACES) X
DIMENSIONS (ALIGNMENT, ROOT OPENING, ROOT FACE, BEVEL) X
JOINT PREPARATION X
NOTE 7
FIT-UP OF GROOVE WELDS (INCLUDING JOINT GEOMETRY)
WELDER IDENTIFICATION SYSTEM X
MATERIAL IDENTIFICATION (TYPE/GRADE)
1705.12.1
AISC 341 TABLE J6.1
AWS D1.8/D1.8M
X
VISUAL INSPECTION TASKS PRIOR TO WELDING
OBSERVE PERFORM
SYSTEM OR MATERIAL
OSSC CODE
REFERENCE
CODE OR
STANDARD
REFERENCE
STATEMENT OF SPECIAL
INSPECTIONS (NOTES 5,6,10) REMARKS
STEEL LATERAL SYSTEM - SPECIAL INSPECTIONS
DOCUMENT ACCEPTANCE OR REJECTION OF BOLTED CONNECTIONS
1705.2.1.2
TABLE 1705.2-2
AISC 360
TABLE N5.6-3 X
INSPECTION TASKS AFTER BOLTING
FASTENER COMPONENT NOT TURNED BY THE WRENCH PREVENTED FROM
ROTATING X
JOINT BROUGHT TO THE SNUG-TIGHT CONDITION PRIOR TO THE
PRETENSIONING OPERATION X
FASTENER ASSEMBLIES, OF SUITABLE CONDITION, PLACED IN ALL HOLES AND
WASHERS (IF REQUIRED) ARE POSITIONED AS REQUIRED
1705.2.1.2
TABLE 1705.2-2
AISC 360
TABLE N5.6-2
AISC M2.5
RCSC SPECIFICATION
FOR STRUCTURAL
JOINTS USING ASTM
A325 OR A490 BOLTS
SECTION 9
X
INSPECTION TASKS DURING BOLTING
PROPER STORAGE PROVIDED FOR BOLTS, NUTS, WASHERS AND OTHER
FASTENER COMPONENTS X
CONNECTING ELEMENTS< INCLUDING THE APPROPRIATE FAYING SURFACE
CONDITION AND HOLE PREPARATION, IF SPECIFIED, MEET APPLICABLE
REQUIREMENTS
X
PROPER BOLTING PROCEDURE SELECTED FOR JOINT DETAIL X
PROPER FASTENERS SELECTED FOR THE JOINT DETAIL (GRADE, TYPE, BOLT
LENGTH, IF THREADS ARE TO BE EXCLUDED FROM THE SHEAR PLANE) X
FASTENERS MARKED IN ACCORDANCE WITH ASTM REQUIREMENTS X
MANUFACTURER'S CERTIFICATIONS AVAILABLE FOR FASTENER MATERIALS
1705.2.1.2
TABLE 1705.2-2
AISC 360
TABLE N5.6-1
AISC 360 M2.5
X
INSPECTION TASKS PRIOR TO BOLTING
VERIFICATION OF JOINT & CONNECTION DETAILS INCLUDING MEMBER AND
COMPONENT LOCATIONS, BRACING, AND STIFFENERS TABLE 1705.2-7 AWS D1.1 X
SINGLE PASS FILLET WELDS LESS THAN OR EQUAL TO 5/16" X
SINGLE PASS FILLET WELDS GREATER THAN 5/16" X ALL WELDS VISUALLY INSPECTED PER AWS D1.16.9
MULTIPASS FILLET WELDS X
COMPLETE AND PARTIAL JOINT PENETRATION GROOVE WELDS
TABLE 1705.2-6 AWS D1.1 CLAUSE 6
X
VERIFYING WELDER QUALIFICATIONS AWS D1.1 X RETAIN A RECORD OF QUALIFICATION CARDS
VERIFYING USE OF PROPER WPS'S
1705.2.1
AWS D1.1 AISC 360 N3.2 RETAIN A RECORD OF WELDING PROCEDURE SPECIFICATIONS
STRUCTURAL STEEL WELDING
MATERIAL VERIFICATION OF WELD FILLER METALS
1705.2.1.1
TABLE 1705.2-5
AISC 360 A3.5
AISC 360 N3.2
APPLICABLE AWS A5
DOCUMENTS
X MANUFACTURER'S CERTIFIED TEST REPORTS
MATERIAL VERIFICATION OF HIGH STRENGTH BOLTS, NUTS, AND WASHERS
1705.2.1.2
AISC 360 N5
TABLE 1705.2-2
AISC 360 A3.3
AISC 360 N3.2
ASTM STANDARDS
SPECIFIED IN
CONSTRUCTION
DOCUMENTS
RCSC 2.1
X MANUFACTURER'S CERTIFIED TEST REPORTS
MATERIAL VERIFICATION OF STRUCTURAL STEEL COMPONENTS
1507.4 2205.1
TABLE 1705.2
ASTM A6
ASTM STANDARDS
SPECIFIED IN
CONSTRUCTION
DOCUMENTS
AISC 360 A3.1
AISC 360 N3.2
X CERTIFIED MILL TEST REPORTS
FABRICATION OF STRUCTURAL ELEMENTS 1704.2.5.1 AISC 360 X REFER TO INSPECTION OF FABRICATOR REQUIREMENTS
STEEL FABRICATION
CONTRACTOR QUALITY CONTROL REQUIREMENTS AISC 360 CHAPTER N X X
CONTRACTOR TO PROVIDE QUALITY CONTROL FOR ALL ITEMS
INDICATED TO BE OBSERVED AND/OR PERFORMED IN TABLE BELOW
CONTINUOUS/
PERFORM
PERIODIC/
OBSERVE
SYSTEM OR MATERIAL
OSSC CODE
REFERENCE
CODE OR STANDARD
REFERENCE
FREQUENCY / INSPECTION
REMARKS
STEEL - SPECIAL INSPECTIONS
OREGON
J A
N
U A R Y 2 3 , 2
E
N G I N E E
R
51043RE
G ISTERED PROFESS IONAL
ER
I C R . WA T SON
STRUCTURA L
EXPIRES: 06 - 30 - 2024
A DIGITAL SIGNATURE WATERMARK ON
FOUNDATION SHEET NOTES:
F1. SEE AND FOR TYP CONCRETE DETAILS
F2. T/FTG OR PILE CAP ELEVATION (MEASURED FROM
T/SOG UNO)
F3. SPREAD FOOTING PER SCHEDULE
F4. CONTINUOUS FOOTING PER SCHEDULE
F5. CONCRETE WALL TYPE PER SCHEDULE
MARK PLAN
SIZE
THICK…
This is the start of the file's text. The full file is on GovTribe.
File details come from the government source that posted it. Updated .